Landis Gyr Technologies HUNTSU825 3G S4e Gridstream User Manual 98 9103

Landis+Gyr Technologies, LLC 3G S4e Gridstream 98 9103

Contents

Exhibit D - Product Ship Sheet

Download: Landis Gyr Technologies HUNTSU825 3G S4e Gridstream User Manual 98 9103
Mirror Download [FCC.gov]Landis Gyr Technologies HUNTSU825 3G S4e Gridstream User Manual 98 9103
Document ID1223348
Application IDG6x/1IrXTGrt9U28BEpeLA==
Document DescriptionExhibit D - Product Ship Sheet
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize9.47kB (118333 bits)
Date Submitted2010-01-06 00:00:00
Date Available2010-03-08 00:00:00
Creation Date2001-06-20 16:18:34
Producing SoftwareAcrobat Distiller 9.0.0 (Windows)
Document Lastmod2009-10-16 13:58:31
Document Title98-9103.fm
Document CreatorFrameMaker 9.0

3G S4e Gridstream
Endpoint with
ZigBee Data Sheet
General
The 3G S4e Gridstream endpoint is designed to accommodate Landis+Gyr S4e poly-phase meters
for use in commercial and light industrial services. The S4e Advanced Function meter is an Active
Energy kWh/kW/TOU Meter. The meter features Digital Multiplication Measurement Technique,
meets ANSI standards for performance and utilizes ANSI C12.19 protocol (between meter and
AMR device). Can be deployed with or without ZigBee.
Display Options
•
Energy Metrics: +kWh, -kWh, Net kWh, and added kWh (Security).
Figure 1. The 3G S4e Gridstream Endpoint Module and the Landis+Gyr S4e Meter
FCC Compliance Information
Model: FASY-0825
FCCID: TEB-HUNTSU825
IC: 5931A-HUNTSU825
Landis+Gyr Confidential Information
98-9103 Rev AA
3G S4e Gridstream Endpoint with ZigBee Data Sheet
Landis+Gyr
Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause
undesired operation.
Changes or modifications not expressly approved by Landis+Gyr could void the
user’s authority to operate the equipment.
Endpoint Location
To comply with FCC’s RF exposure limits for general population/uncontrolled exposure, the
antenna(e) used for this transmitter must be installed to provide a separation distance of at
least 20 cm from all persons and must not be collocated or operating in conjunction with any
other antenna or transmitter.
Endpoint Usage
The 3G S4e Gridstream endpoint will be used:
•
for commercial and light industrial metering applications.
•
at homes and businesses.
The 3G S4e Gridstream endpoint requires professional installation by qualified personnel.
RF Interference
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the meter off, the user is encouraged to try to correct the interference by one
or more of the following measures:
•
Re-orient or relocate the receiving antenna.
•
Increase the separation between the equipment and receiver.
•
Consult Landis+Gyr or an experienced radio/TC technician for help.
98-9103 Rev AA
Landis+Gyr Confidential Information
Landis+Gyr
3G S4e Gridstream Endpoint with ZigBee Data Sheet
Required Software
To work with the endpoint, you need one of the following software tools:
•
Command Center ver. 4.1 or greater
•
RadioShop.
•
Network Configuration Manager.
•
Landis+Gyr 1132Prog application.
•
Endpoint Testing Manager.
•
Endpoint Implementation Manager.
Specifications
Table 1. 3G S4e Gridstream Endpoint Specifications
Category
Specification
Value or Range
Form
Compatible
Meters
Electrical
RF 900 MHz
RF ZigBee
Landis+Gyr Confidential Information
Landis+Gyr S4e Supported
Meter Forms
Class
Form
Class
3S
20
16SE
320
5S/45S
20
16/15K
480
6S/36S
20
9S/8S
20
2S
200
12S
200
16S/15S
200
25S
200
12SE
320
Voltage
10.5-13.5V (from the meter’s power supply)
Power
Max: 2.5W
Typical: 0.5W
Output Power
+26 dBm +/-1 dBm
Adjacent Channel Power
39 dBc Nominal
Transmit Frequency
902 to 928 MHz ISM unlicensed (FCC Part 15)
Communication Protocol
Gridstream Protocol for Command Center
Receive Sensitivity
-108 dBm minimum
Output Power
+20 dBm +/-1
Adjacent Channel Power
40 dBc Minimum
Transmit Frequency
2405-2480 MHz
Communication Protocol
ZigBee Protocol
Receive Sensitivity
-104 dBm minimum
98-9103 Rev AA
3G S4e Gridstream Endpoint with ZigBee Data Sheet
Landis+Gyr
Table 1. 3G S4e Gridstream Endpoint Specifications
Category
Standards
Compliance
Environmental
Mechanical
Specification
Value or Range
FCC Title 47 CFR Part 15
Radiated and Conducted Emissions (incl.
intentional radiators)
IEC 61000 4-2,3,4,5,11,12
Electromagnetic Compatibility
ANSI C12.19
Compatible with Utility Industry End Device
Tables
ANSI C12.20
National Standard for Electricity Meters - 0.2
and 0.5 Accuracy Classes
ANSI C12.21
Code for Electricity Metering
ANSI C37.90.1 (1989)
Standard Surge Withstand Capability (SWC)
Tests
ANSI C12.22
Transport of ANSI C12.19 Over Network
Transmissions
General Environmental
Outdoor, rain-protected, sunlight-exposed
Operating Temperature Range
-40 to +70 C (under meter glass)
Humidity
0 to 95% relative humidity, non-condensing
Size
Weight
Contact Information
Technical Support:
Internet:
Fax
E-mail:
1-888-390-5733
www.landisgyr.com
1-218-562-5530
solutionsupport.na@landisgyr.com
98-9103 Rev AA
Landis+Gyr Confidential Information

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Page Mode                       : UseNone
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Create Date                     : 2001:06:20 16:18:34Z
Creator Tool                    : FrameMaker 9.0
Modify Date                     : 2009:10:16 13:58:31-05:00
Metadata Date                   : 2009:10:16 13:58:31-05:00
Producer                        : Acrobat Distiller 9.0.0 (Windows)
Format                          : application/pdf
Title                           : 98-9103.fm
Document ID                     : uuid:e19affc6-00be-4088-ae0d-35efdc21e250
Instance ID                     : uuid:c6bd5ff5-b78d-4f10-bcfc-45281d8c8d80
Page Count                      : 4
Creator                         : FrameMaker 9.0
EXIF Metadata provided by EXIF.tools
FCC ID Filing: TEB-HUNTSU825

Navigation menu