RC006 RC045 G03 820 0109

User Manual: RC006-RC045-G03-820-0109

Open the PDF directly: View PDF PDF.
Page Count: 53

DownloadRC006-RC045-G03-820-0109
Open PDF In BrowserView PDF
KODIAK£ RECIRCULATING CHILLERS
TECHNICAL MANUAL

RC006, RC009, RC011, RC022, RC030 and RC045
G03, H03 and J03 Series

Lytron Inc., 55 Dragon Court, Woburn, MA 01801, USA
Tel: +1-781-933-7305 Fax: +1-781-935-4529
www.Lytron.com
© Lytron Inc., 2010
Manual # 820-0109, Rev. Y, 07/23/10

Kodiak Recirculating Chiller Technical Manual

{THIS PAGE IS LEFT BLANK INTENTIONALLY}

Kodiak Recirculating Chiller Technical Manual

TABLE OF CONTENTS
TABLE OF CONTENTS....................................................................................................................................................... 1
REVISION HISTORY........................................................................................................................................................... 3
INTRODUCTION.................................................................................................................................................................. 4
SAFETY PRECAUTIONS .................................................................................................................................................... 5
LABELS AND SILKSCREEN MARKING......................................................................................................................... 6
PART NUMBER DESCRIPTION ....................................................................................................................................... 8
SPECIFICATIONS................................................................................................................................................................ 9
PERFORMANCE GRAPHS............................................................................................................................................... 10
GENERAL INFORMATION ............................................................................................................................................. 11
CONTROLLER DISPLAY PANEL FUNCTIONS .......................................................................................................... 12
REAR PANEL COMPONENTS ........................................................................................................................................ 13
OPTIONAL SYSTEM FEATURES................................................................................................................................... 14
CONTROLLER OPTIONS ................................................................................................................................................ 16
INSTALLATION REQUIREMENTS ............................................................................................................................... 17
INSTALLATION PROCEDURE ....................................................................................................................................... 18
PRIMING TURBINE AND CENTRIFUGAL PUMPS.................................................................................................... 19
CONNECTING POWER (FOR UNITS WITHOUT HEATER OPTION).................................................................... 20
CHILLER OPERATION .................................................................................................................................................... 21
SYSTEM MAINTENANCE AND SERVICE ................................................................................................................... 24
DRAINING PROCEDURE FOR KODIAK CHILLERS ................................................................................................ 26
COOLANT MAINTENANCE ............................................................................................................................................ 27
ERROR CODES................................................................................................................................................................... 28
TROUBLE SHOOTING GUIDE........................................................................................................................................ 29
KODIAK SPARE PARTS ................................................................................................................................................... 31
ACCESSORIES FOR THE KODIAK RECIRCULATING CHILLER......................................................................... 32
FRONT VIEW...................................................................................................................................................................... 33

Manual # 820-0109, Rev. Y, 07/08/10

-1-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual
REAR VIEW (WITH PANEL)........................................................................................................................................... 34
TOP VIEW ........................................................................................................................................................................... 35
REAR VIEW (OPENED).................................................................................................................................................... 36
SIDE VIEW .......................................................................................................................................................................... 37
SIDE VIEW (WITH HIGH PRESSURE CUTOUT) ....................................................................................................... 38
CHILLER DIMENSIONS FOR RC011 AND RC022...................................................................................................... 40
CHILLER DIMENSIONS FOR RC030 AND RC045..................................................................................................... 41
WIRING DIAGRAM........................................................................................................................................................... 42
PLUMBING DIAGRAM..................................................................................................................................................... 42
PLUMBING DIAGRAM..................................................................................................................................................... 43
REFRIGERATION DIAGRAM ........................................................................................................................................ 44
HOST INTERFACE DATA LINK .................................................................................................................................... 44
HOST INTERFACE DATA LINK .................................................................................................................................... 45
LYTRON COOLING SYSTEMS SERVICE POLICY ................................................................................................... 48
LYTRON KODIAK RECIRCULATING CHILLER STANDARD WARRANTY ...................................................... 50
DECLARATION OF CONFORMITY.............................................................................................................................. 51

Manual # 820-0109, Rev. Y, 07/08/10

-2-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REVISION HISTORY
REV
Y

ECN / DATE
17284 / 07/08/2010

Manual # 820-0109, Rev. Y, 07/08/10

REASON FOR CHANGE
Updated Declaration of Conformity and safety symbols.

-3-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

INTRODUCTION
Receiving the New Kodiak£ Chiller
Inspect the new chiller immediately upon receiving it. If the unit shows shipping damage, contact the
transportation company and file a freight damage claim. Retain all cartons and packing material until the unit is
operated and found to be in good condition. The chiller has been fully tested at the Lytron factory with clean
water. Although the system has been drained, some residual fluid may remain. This will not hinder the
performance of the chiller.

About the Warranty
All units returned for warranty claims must have an RMA (Return Material Authorization) number on the outside
of the container. Call Lytron Customer Service at +1-781- 933-7300 for an RMA number. Refer to the end of
manual for the chiller warranty. Units should be drained of all fluids and packaged in its original packaging.

Customer Service Support
Lytron is committed to servicing the customer, both during and after the sale. If you have any questions
concerning the operation of your unit, contact our Application Engineering Department at +1-781- 933-7300.
To facilitate your call, please have the model number and serial number of the unit (located on the rear of the
chiller) for the Lytron Applications Engineer.

Service Hotline
Lytron has a 24-hour per day, 7 day per week service hotline to help you with questions on the startup and
operation of your Kodiak recirculating chiller. (Lytron recommends consulting the troubleshooting guide
on page 29 before calling the service hotline.) Lytron service can be reached by dialing +1-781- 933-7300.
To facilitate your call please have the model number and serial number (located on rear of the chiller) of the
unit for the Lytron Service Technician.

£

Kodiak is a registered trademark of Lytron, Inc.
Manual # 820-0109, Rev. Y, 07/08/10

-4-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SAFETY PRECAUTIONS
This system is designed to provide fluid cooling only as specified in this manual. If this system is used in a
manner other than as specified, the safety protection of the system may be impaired.
Warnings are posted throughout the manual. Read and follow these important instructions. Failure to observe
these instructions or use the chiller other than as specified may impair safety protection, void the warranty, and
can result in permanent damage to the unit, significant property damage, personal injury, and/or death.
Make sure you read, understand, and follow all instructions and safety precautions listed in this manual before
operating your unit. If you have any questions concerning the operation of your unit or the information in this
manual, please contact our Applications Engineering Department at +1-781- 933-7300.
¾

Always turn the unit "OFF" and disconnect the power cord from the power source before
performing any service, maintenance procedures or before moving the unit.

¾

Do not operate equipment with damaged power cords.

¾

A qualified technician should perform Service and repairs.

¾

If the set point is 10° C (50° F) or below, a freezing point depressant, such as ethylene glycol, is
required. This unit is equipped with a low flow switch. This feature will shut the chiller down
during a low flow situation to prevent freezing.

¾

DO NOT USE AUTOMOTIVE ANTI-FREEZE IN THE CHILLER. The rust inhibitors in the
automotive type may cause premature failure of the pump seals. Use of automotive anti-freeze
in a Lytron chiller will void the warranty.

¾

Never place the unit in a location where excessive heat, moisture, or corrosive materials are
present.

¾

The unit must be plugged into a properly grounded power source.

¾

Do not connect the SUPPLY or RETURN fitting to your building water supply or any pressurized
source.

¾

DO NOT USE OR MAINTAIN THE CHILLER OUTDOORS. These units were not designed to
withstand outdoor weather conditions.

¾

Performance of installation, operation, or maintenance procedures other than those described
in this manual may result in a hazardous situation and may void the Lytron warranty.

¾

Transport the unit with care. Sudden jolts or drops can damage the unit.

¾

Drain the chiller of all water when transporting, shipping or leaving unused for long periods of
time. This will prevent freezing and algae build up while idle.

¾

Observe all warning labels. Never remove warning labels.

¾

Do not operate damaged or leaking equipment.

¾

Do not operate the unit without fluid in the reservoir.

Manual # 820-0109, Rev. Y, 07/08/10

-5-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

LABELS AND SILKSCREEN MARKING
¾ The symbol on this label is intended to alert the user to
the presence of important operating and maintenance
(servicing) instructions in the literature accompanying the
equipment.
¾ This symbol on this label cautions the user against the risk
of electrical shock. This label is mounted near of main
voltages of the system.
EXTERNAL CONTACTS
.5 AMPS MAX

FILTER CARTRIDGE HAS
BEEN INSTALLED

RS-232

PUMP PRIMING VALVE

¾ External contacts have been installed.

¾ Lets customer know element has been installed.

¾ RS232 has been installed.

¾ Identifies the location of the pump priming valve.

OPEN TO PRIME - CLOSE TO RUN

RETURN
SUPPLY

¾ This silk-screen marking identifies the connection where
heated fluid is returned from the user’s machine.
¾ This silk-screen marking identifies the connection where
chilled fluid is supplied to the user’s machine.

¾ Positive earth (ground) terminal.

¾ The markings on this label certifies that the equipment has
been certified to the UL standard 61010A-1 and
CAN/CSA STD C22.2 No. 1010.1 standards.

¾ The symbol on this label identifies that the equipment has
been certified to regulations of the European Community.

Manual # 820-0109, Rev. Y, 07/08/10

-6-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

¾ The product ID label identifies the model number,
serial number, electrical information, pump type,
refrigerant type, charge, and date of manufacture of
the product.

¾ The crossed out wheeled bin label requires that the
product be disposed of or recycled with the
requirements of local law.

¾ The RoHS compliant label indicates that the product
complies with the European union restriction of
hazardous substances (RoHS) directive.

¾ This label indicates that none of the six hazardous
substances are present in the product above the
maximum concentration values in its homogeneous
form per China RoHS.

¾ This label indicates which of the six hazardous
substances are present in the product above the
maximum concentration values in its homogeneous
form and the environmental protection use period of
the product per China RoHS.

Manual # 820-0109, Rev. Y, 07/08/10

-7-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

PART NUMBER DESCRIPTION
RC006 G03 BB 1 MXXX

Basic
Model No.

Electrical
Configurations

Pump
Options

RC006 - 825 Watts

G03 = 115V~/1ph/60Hz AA* †= CP-15
Centrifugal Pump
RC009 – 1,050 Watts H03 = 230V~/1ph/50Hz
BB (CB†) = 1.3 gpm
RC011 – 1,650 Watts J03 = 230V~/1ph/60Hz Positive Displacement
Pump
RC022 – 2,400 Watts
BC (CC†) = 1.8 gpm
Positive Displacement
RC030 – 3,450 Watts
Pump
RC045 – 5,900 Watts
BE (CE†) = 2.3 gpm
Positive Displacement
Pump
BG (CG†) = 4.3 gpm
Positive Displacement
Pump
DA* † = CP-25
Centrifugal Pump
EB* (FB†) = 1/4 Hp
Turbine Pump
EC* (FB†) = 1/6 Hp
Turbine Pump
Note:
Cooling capacity and
pump flows are rated
at 60Hz. For 50Hz
power capacity is
reduced by 17%.

Notes:

* Water filter and DI
cartridge not
recommended with
Centrifugal & Turbine
pumps.

Controller
Configuration

Std.
Modification

CONTROLLER PACKAGE #1
1.
2.
3.
4.
5.
6.

Alarm Mute
Audible Alarm
Auto-Restart
Calibration Offset
Deg °C / Deg °F Toggle
Digital Temperature
Display
7. Low Flow Shut-Off Fault
CONTROLLER PACKAGE #2:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

Alarm Mute
Audible Alarm
Auto-Restart
Calibration Offset
Deg °C / Deg °F Toggle
Digital Pressure Sensing &
Display
Digital Temperature
Display
Fault Shut-Off (toggle
on/off)
Low Flow Shut-Off Fault
Low Level Fault
Low Temp / High Temp
Fault
Relay Contacts

CONTROLLER PACKAGE #3:
Same as "PKG 2" above
with the addition of RS-232
communications.

† Indicates high
purity compatible
pump.
NOTE:
Refer to the product ID label on the on the rear of your chiller for the configuration you have purchased.
The table above refers to Lytron’s standard product offering for the Kodiak product line.

Manual # 820-0109, Rev. Y, 07/08/10

-8-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SPECIFICATIONS1
RC006

RC009

RC011

RC022

RC030

RC045

60Hz
50Hz
825
685
2,800
2,330

60Hz
50Hz
1,050
875
3,585
2,988

60Hz
50Hz
1,650
1,400
5,780
4,760

60Hz
50Hz
2,400
2,150
8,755
7,310

60Hz
50Hz
3,450
2,950
12,070
10,030

60Hz
50Hz
5,900
4,950
20,230
16,830

115V~ 60Hz 1ph

G03

G03

G03

N/A

N/A

N/A

230V~ 50Hz 1ph

H03

H03

H03

H03

H03

H03

230V~ 60Hz 1ph

NA

J03

J03

J03

J03

J03

G03

9.9 A

12.2 A

14.3 A

---

---

---

J03

---

5.8 A

7.4 A

10.0 A

14.5 A

19.6 A

H03

4.5 A

5.3 A

6.3 A

9.5 A

13.7 A

17.2 A

Compressor Size

¼ Hp

1/3 Hp

½ Hp

¾ Hp

1 Hp

1 ½ Hp

Refrigerant Type

R134A

R134A

R134A

R134A

R134A

R134A

± 0.2°F
(0.1°C)
50°F to 95°F
(10°C to 35°C)

± 0.2°F
(0.1°C)
50° F to 95°F
(10°C to 35°C)

± 0.2°F
(0.1°C)
50°F to 95°F
(10°C to 35°C)

± 0.2°F
(0.1°C)
50°F to 95°F
(10°C to 35°C)

± 0.2°F
(0.1°C)
50°F to 95°F
(10°C to 35°C)

± 0.2°F
(0.1°C)
50°F to 95°F
(10°C to 35°C)

41°F to 95°F
(5°C to 35°C)

41°F to 95°F
(5°C to 35°C)

41°F to 95°F
(5°C to 35°C)

41°F to 95°F
(5°C to 35°C)

41°F to 95°F
(5°C to 35°C)

41°F to 95°F
(5°C to 35°C)

1 gal (3.8 l)

1 gal (3.8 l)

2 gal (7.6 l)

2 gal (7.6 l)

6 gal (22.6 l)

6 gal (22.6 l)

Width

12.5" (318)

12.5" (318)

14.8" (376)

14.8" (376)

21.4" (543)

21.4" (543)

Depth

19.0" (483)

19.0" (483)

24.5" (622)

24.5" (622)

27.8" (705)

27.8" (705)

Height

22.0" (559)

22.0" (559)

26.5" (673)

26.5" (673)

31.0" (787)

31.0" (787)

½” FNPT

½” FNPT

½” FNPT

½” FNPT

½” FNPT

½” FNPT

97 lbs (44 kg)

100 lbs (45 kg)

122 lbs (55 kg)

166 lbs (75 kg)

260 lbs (118 kg)

270 lbs (123 kg)

Thermal Capacity2
Watts
BTU/hr

Full Load Amps3

Temperature
Stability
Operating
Environment
Coolant
Temperature
Range4
Reservoir Capacity
Dimensions5

Connection
Weight
Process Coolant
Delivery Pressure

Factory preset to 90 psig max (for PD and turbine pumps only)

1

Specifications are subject to change.
Capacity is for 20°C delivery water at a 20°C ambient.
3
Full load amperage for air -cooled models with standard pumps without the optional heater. Standard pumps are the BB
for the RC006, RC009, RC011, RC022 and BG for the RC030 and RC045. Contact Lytron for current draw of other models.
4
Chiller will shut down when coolant temperature reaches 10°C above the coolant temperature range.
5
Dimensions do not include filters or external valves.
2

Manual # 820-0109, Rev. Y, 07/08/10

-9-

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

PERFORMANCE GRAPHS

1

1

Temperature represents output temperature of water assuming 20°C ambient air conditions. Performance
subject to change due to variations such as: fluid type or operating conditions.
Manual # 820-0109, Rev. Y, 07/08/10

- 10 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

GENERAL INFORMATION
Chiller System Description
Your chiller consists of a refrigeration system, a coolant loop, associated controls and plumbing. The
pump draws coolant from the internal reservoir and pumps it out to cool the process equipment, and
then the coolant flows back to the chiller. The fluid then flows through the evaporator, where the heat is
removed, and then back to the reservoir.

Coolant Loop
Kodiak chillers are designed to operate with continuous coolant flow through a closed loop. This loop
contains the system pump, temperature sensor, reservoir, internal and external plumbing lines and
fittings, and the external heat load. The external plumbing and the heat loads are provided by the end
user and are generally unique to the user’s process or location.

Refrigeration System and Hot Gas Bypass
The chiller uses a standard refrigeration system to keep the coolant at the process temperature set
point. The compressor compresses the refrigerant vapor. The vapor then passes through the
condenser where it is cooled and turns to a liquid. The refrigerant then passes through the evaporator.
The coolant also flows into the evaporator, through passages separated by thin layers of metal from the
refrigerant. The refrigerant evaporates, drawing heat from the coolant. The refrigerant vapor returns to
the compressor and continues the cycle.
Many refrigeration systems, such as those used in household refrigerators, control the temperature by
turning the compressor on and off. This is a simple, inexpensive method of controlling the cooling, but
its temperature control is not precise and the frequent on-off cycles causes wear on the compressor
motor.
Lytron’s recirculating chillers use a better method for controlling the cooling rate: a hot-gas bypass
system. This employs a liquid line solenoid valve and a hot-gas bypass valve to meter the refrigerant
flow through the evaporator when cooling is needed. When the coolant reaches its set point
temperature, the liquid line solenoid valve closes, causing the hot-gas bypass valve to open. The hotgas valve lets hot gas from the compressor discharge into the evaporator, adjusting the temperature in
the evaporator to maintain the correct coolant temperature. When refrigeration is needed the liquid line
solenoid valve opens, the hot-gas valve closes and the cycle starts again.
This hot gas bypass control method provides precise temperature control. It also minimizes wear on
the compressor motor, since the compressor runs continuously and does not experience the stress of
repeated cycling.

Manual # 820-0109, Rev. Y, 07/08/10

- 11 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CONTROLLER DISPLAY PANEL FUNCTIONS

Controller Display

Key

Operation
Turn on/off chiller
Displays Pressure briefly

“UP” + “DOWN” +

Enter menu (press simultaneously and hold for 3 seconds and
release)
Push to display or change set point

“UP” arrow
“DOWN” arrow

Increase set point temperature
Decrease set point temperature
Alarm Sound disabled or Muted (alarm will stay muted until error
is corrected, then resets)

DESCRIPTION OF INDICATORS
Temperature Set Point

Displays coolant temperature or set point in °C or °F.

Pressure Display

Displays outputs pump pressure in PSI/bar digitally for a few seconds.

Cooling Indicator

Solenoid valve is open and chiller is cooling the process fluid when this light is
illuminated.

Low Flow Indicator

Indicates that the minimum flow requirement of the chiller is not being satisfied.

Alarm Indicator

Illuminates to indicate an alarm fault condition.

Low-Level Indicator

Illuminates to indicate a low fluid level in the tank.

Over Temperature
Indicator
Low Temperature
Indicator

Illuminates to indicate water temperature is above high temperature alarm set
point.
Illuminates to indicate water temperature is below low temperature alarm set
point.

Manual # 820-0109, Rev. Y, 07/08/10

- 12 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REAR PANEL COMPONENTS
(Reference Spare Parts List in this manual)

FLUID OUT
OF CHILLER

CIRCUIT
BREAKER

POWER
ENTRY

NOTCH
INDICATES
PIN 1

14
25

RS232

REMOTE START &
CUSTOMER CONTACTS

FLUID IN
TO CHILLER

-

Manual # 820-0109, Rev. Y, 07/08/10

- 13 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

OPTIONAL SYSTEM FEATURES
Coolant Water Filter
The factory installed water filter removes particulate from the coolant water. The water filter is not recommended
with centrifugal pumps or turbine pumps. For replacement filters, call Lytron’s Customer Service at 781-9337300.

Deionization Package
The Deionization Package consists of a factory-installed deionization cartridge. The deionization cartridge
requires replacement only when the mixed bed is depleted. For replacement cartridges, Call Lytron’s Customer
Service at 781-933-7300. This package is offered for deionized water applications where the resistance of the
water does not exceed 1 Mega-ohm-cm. The deionization package is not recommended with centrifugal pumps.

External Customer Contacts
This option will send a signal indicating there is a problem with the chiller. It can be wired to open on fault or
close on fault. This connector is located on the rear left of the system. Pin 5 is the common, Pin 6 closes on
fault, and pin 4 opens on fault. The mating connector is Amp part number 350715-1, and the pins for the
connector are Amp part number 350547-1. These contacts are rated for 250 V, ½ amp maximum.

External Manually Adjustable Flow Valve
This option allows the flow rate to the equipment to be controlled with a globe valve. Opening the valve allows
the flow to bypass from the supply to the return. By adjusting the valve a precise flow rate can be set. To be
sure the process equipment is receiving the appropriate flow install a flow meter at the outlet from the process
equipment.

External Pressure Relief Valve
This option is for applications with a maximum allowable pressure. It can also be used where flow to the
equipment being cooled needs to be shut off without stopping the chiller. In this case the pressure relief valve
will open and allow the flow to bypass from the supply to the return. The standard valve has an adjustment
range from 50 psi to 100 psi.

Fault Chiller Shut-off
This option will shut the chiller off in the event that there is an alarm condition. It will turn off the power to the
pump and compressor and give an error signal on the front panel of the chiller. To reset the system after a fault
the main power must be turned off at the circuit breaker.

Heater Package RC011, RC022, RC030 and RC045
The heater package is for applications requiring coolant temperature well above ambient temperature. This
package is a single set point type. The heater is activated when the water temperature is 3qF below set point.
The heater option is not intended to provide tight temperature control, but to bring coolant temperature up to an
application's requirement faster than the refrigeration cycle (hot gas bypass).

High Purity Plumbing
This option is intended for use with deionized water. Only stainless steel and/or plastic components and a
nickel-brazed heat exchanger come in contact with the coolant. This option must be specified before the chiller
is purchased. It cannot be upgraded in the field.

Remote Start
This option allows the Kodiak chiller to be started or stopped through a computer or a relay. The chiller can e
run using a normally open circuit or normally closed. (Look under the section labeled Chiller Operation for more
details) R.S. contacts are located on the rear left of the chiller shown previously. It is a six-pin connector with
pins 1 and 2 controlling R.S. The mating connector is an Amp 350715-1 plastic housing. The pins are Amp
350547-1. The controlling relay should have SPDT type contacts rated for low current less than or equal to
5VDC at 0.1 milliamp.

Manual # 820-0109, Rev. Y, 07/08/10

- 14 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

RS-232 Serial Port Communication
This option allows control of the chiller via a standard 9 pin serial port connected to a computer. Lytron
software is available that simulates the front control panel and all its functions. Alternatively, software can be
created to interface with the system described in the section labeled Host Interface Data Link.

Water Cooled Condenser RC011, RC022, RC030 and RC045
This feature replaces the standard condenser and fan with a water-cooled condenser. This requires cooling
water to be supplied to the chiller at 75qF (25qC). The facility water pressure must be less than 100 psi.
Minimum flow rates are as follows:
Model
RC011
RC022
RC030
RC045

Manual # 820-0109, Rev. Y, 07/08/10

Flow Rate (min)
1.4 gpm
1.4 gpm
1.9 gpm
3.4 gpm

- 15 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CONTROLLER OPTIONS
“
CONTROLLER PACKAGES (1, 2, 3) FOR KODIAK CHILLERS
CONTROL PACKAGE #1:
1.
2.
3.
4.
5.

Auto-Restart
Calibration Offset
Deg °C / Deg °F Toggle
Digital Temperature Display
Low Flow Fault Chiller Shut-Off

STANDARD OPTIONS FOR CONTROLLER PACKAGE #2:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

Alarm Mute
Audible Alarm
Auto-Restart
Calibration Offset
Deg °C / Deg °F Toggle
Digital Pressure Sensing & Display
Digital Temperature Display
Fault Shut-Off (toggle on/off)
Low Flow Fault Chiller Shut-Off
Low Level Fault
Low Temp / High Temp Fault
Relay Contacts

STANDARD OPTIONS FOR CONTROLLER PACKAGE #3:
This option has the same features as Package 2 with the addition of:
x

RS-232 Serial Port Communications

Manual # 820-0109, Rev. Y, 07/08/10

- 16 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

INSTALLATION REQUIREMENTS
Coolant Requirements
x

Lytron recommends using filtered clean water above 10°C/50°F as coolant.

x

If the set point is 10°C/50°F or below, a freezing point depressant, such as ethylene glycol,
is required. This unit is equipped with a low flow switch. This feature will shut the chiller down during a low
flow situation to prevent freezing.

x

Do not use automotive anti-freeze in the chiller. The rust inhibitors in the automotive type
may cause premature failure of the pump seals. Use of automotive anti-freeze in a Lytron chiller will void
the warranty.

x

Avoid using water with a high mineral content.

x

If the coolant is exposed to sunlight add an algaecide to control organic growth in lines.

Electrical Requirements (for units without heater option)
Refer to the Specification section and to the product ID label on the rear of the chiller for the specific electrical
requirements of your unit. The chiller power module is configured with a standard international IEC320/C20
inlet. To safely operate the chiller, use an SJT cord set with an IEC 320/C19 receptacle and an inlet plug that is
compatible to the local power grid and the power requirements of the chiller. All Kodiak chillers should use SJT
3 conductor 12 AWG minimum power cord.

Selecting Chiller Location
Do not operate or store Kodiak chillers outside. These systems are not intended for outdoor
use.
To minimize the heat gain and pressure drop through the connecting hoses, the chiller unit should be located as
close as possible to the heat load (user equipment). This is more important for units with centrifugal pumps as
they are not capable of high head pressures. Coolant lines are best run at or near the same level as the cooling
system. Once the chiller is in position lock the casters.
Airflow is critical to optimize performance of the chiller. The front and one side or the back of the unit MUST be
kept clear and unobstructed. The remaining two sides or back must have minimum clearance of 18" (456 mm).
The top clearance must be at least 6" (152 mm). Ensure that the hot air exiting the chiller does not recirculate
into the inlet openings. The front of the unit must have a free supply of ambient-temperature air.
Before moving the chiller cap all ports to prevent any coolant leakage. Unlock the casters and move to new
location. Once in the new location lock the casters. To prevent freezing during storage drain water if the chiller
is located in an area below 10qC (50qF).

Manual # 820-0109, Rev. Y, 07/08/10

- 17 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

INSTALLATION PROCEDURE
Selecting and Locating Hoses
x

The coolant ports are located on the rear of the system and are labeled as previously shown on page 13.

x

To minimize the pressure loss in the coolant lines, use the largest practical diameter tubing. If substantial
lengths of cooling lines are required, they should be pre-filled with coolant before connecting them to the
chiller.

x

To minimize heat gain, all lines should be as short as possible. Keep them away from heat sources such as
radiators and hot water pipes. Lines that cannot be routed away from heat sources should be protected
with thermal insulation, preferably at least 1/2" (12.7mm) thick.

x

Flexible tubing should be of heavy wall or reinforced construction. All tubing should be rated to withstand
125 psig (9 bar) at 86°F (30°C). Make sure all tubing connections are secured and leak-tight. Also,
whenever possible use opaque lines to prevent algae growth during prolonged non-operating periods.

Connecting Plumbing
To connect the fluid lines to the chiller and user equipment follow these steps:
1. Remove the plastic caps covering the supply and return ports on the rear panel of the unit.
2. Attach coolant lines to the supply and return ports on the rear panel. Fittings should either be brass,
Never use steel or cast iron fittings, as the corrosion will damage
stainless steel or nylon.
the chiller. For chillers with de-ionization cartridges or high purity plumbing Lytron recommends the use of
either stainless steel or nylon fittings. The supply port provides chilled coolant to the user’s equipment. The
return port connects to the outlet of the user’s equipment.
3. Check that fittings are tight to prevent leaks.
4. Remove water filler cover on top of the unit to access the reservoir.
5. Fill the reservoir. Use the reservoir sight tube on the front of the unit to see the coolant level in the tank
during filling. Be sure to allow for the volume of coolant needed to fill the cooling lines between the chiller
and the equipment, if they were not filled with coolant before installation.
6. If the system is a water-cooled chiller, connect facility water to connections labeled "City Water In" and "City
Water Out". Minimum flow rate of facility water is shown on page 15. Facility water flow must be started
before chiller is turned on.

Manual # 820-0109, Rev. Y, 07/08/10

- 18 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

PRIMING TURBINE AND CENTRIFUGAL PUMPS
Running centrifugal and turbine pumps dry for even a few seconds can permanently damage
the pump. This style of pump must be “primed” prior to operation.
Pump priming must be performed under the following conditions:
a. At initial start-up.
b. The system is drained of its fluid.
c. A new pump is installed.
x

Centrifugal and turbine pumps are classified as non-self priming pumps. This means that the pump will not
displace the air inside the pump housing, which prevents fluid from being drawn in. Each must be “primed”
prior to operation. “Priming” simply means to manually introduce fluid into the pump housing prior to
operation.

x

In a typical chiller installation, the flow of fluid through the pump suction hose into the pump is prevented by
the presence of trapped air. Without a way for the air to escape, the fluid has no way of entering the pump
housing. The following are recommended procedures to prime a turbine or centrifugal pump.

a. Valve in open position

b. Valve in closed position

1.

Units equipped with priming valve. – The priming valve circuit is located between the pump
discharge plumbing line and the top of the tank. There is a valve labeled “pump priming valve” located
in this line. To prime the pump simply open this valve prior to starting the chiller (photo a). Start the
chiller. After flow is observed returning to the tank, close the priming valve (photo b).

2.

Units that do not have a priming valve. – To prime pumps that do not have a priming valve,
disconnect the supply line from the rear of the chiller. Allow time for the fluid to gravity feed into the
pump housing. If there is difficulty priming the pump using this method, use a wet vac to assist in
drawing the fluid from the tank into the pump housing.

Note: If the pump has failed to prime turn the chiller off and contact Lytron’s Service
Department - 781-933-7300.

Manual # 820-0109, Rev. Y, 07/08/10

- 19 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CONNECTING POWER (FOR UNITS WITHOUT HEATER OPTION)
In order to avoid an electrical potential at the chiller frame due to insulation failure, a proper
ground connection to the system must be provided. Failure to do so could result in damage to
the equipment, personal injury, and/or death.
Connect a 3-conductor SJT type power cord with an IEC 320/C19 receptacle to the inlet power to the module
on the rear of the unit and to an appropriate AC power source. All chillers should use a 12-gauge power cord.

Startup Procedure
1. Turn "ON" the circuit breaker on the rear of the unit. The controller will go through a diagnostic test. Turn
on the chiller unit using the top left key located on the Keypad Display panel. The controller displays "OFF"
for 8 seconds. The delay prevents rapid cycling of the compressor using the "ON" and "OFF" switch. If
your chiller is equipped with control package 2 or 3 the fault shut off may prevent the chiller from starting up.
If the chiller displays an alarm after pushing the “ON” button disable the fault shutoff on the customer menu
and restart the chiller.
2. Adjust the temperature set point using the controls on the keypad display as follows:
x Press the “SET” key once to display the current coolant temperature set point.
x Press the “UP” or “DOWN” arrow key until the desired coolant temperature set point appears on the
LED display.
x Press the “SET” key again to accept the set point and return to normal operation.
3. Operate the chiller for a short time and then check the coolant level in the reservoir. If the level drops, add
more coolant.
4. Check all fittings and hoses for fluid leaks. If a leak exists turn chiller off, disconnect power and take
necessary action to repair the leak.

Please Note:
During initial start up the temperature display may occasionally appear to be dim. This is a normal occurrence
and does not indicate that there is problem with the chiller. After 10 seconds the display will brighten to its
normal level.

Manual # 820-0109, Rev. Y, 07/08/10

- 20 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CHILLER OPERATION
The following sections explain how to perform other operations with the chiller’s controller, using the keys and
display on the front of the unit. Refer to the Controller Display Panel Functions section in this manual.
In normal operation the display shows the current temperature of the coolant (or the current temperature with an
offset applied).

Customer Menu Options
Display
Abbreviation
DEGC

Function
English or Metric Units
Changes the temperature readings on the display from °C to °F and
pressure from Bar to PSI.

CAL

Calibration Offset
Adjusts the reading on the display by the offset that you enter, from -4°C
to 4°C (-7°F to 7°F).

Ar

Auto Restart
When enabled this allows the chiller to start automatically in the event of
a power failure.

Ot

Over temperature Fault Indication (option)
Indicator illuminates when the coolant temperature exceeds the overtemperature set point. The over-temperature set point should be at least
3°C (6°F) above the coolant set point to prevent nuisance alarms.

Lt

Low-temperature Fault Indication (option)
Indicator illuminates when the coolant temperature falls below the lowtemperature set point. The low-temperature set point should be at least
3°C (6°F) below the coolant set point to prevent nuisance alarms.

AL

Audible alarm (option)
When this is enabled, an audible alarm sounds when any fault occurs.

FS

*Fault chiller shutoff (option)
When enabled, this turns off the chiller when any fault occurs.

rS

Remote Start (option)
Allows the chiller to be started and stopped with a dry contact.

bAr

Pressure Units (option)
Allows the chiller to display the pressure in units of bar or psi. When bar
is “ON” pressure is displayed in units of bar, in the format X.XX b. When
bar is off, the pressure will be shown in psi, in the format XX p.

*Low flow shutoff cannot be disabled.

Manual # 820-0109, Rev. Y, 07/08/10

- 21 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

AL—Audible Alarm (option)
1.
2.
3.
4.
5.

To enter the menu, press and hold both the “UP” and “DOWN” arrow keys for 3 seconds.
Use the “SET” key to scroll to “AL.”
The display toggles between “AL” and its current setting.
Use “UP” or "DOWN" arrow key to toggle between “ON” and “OFF.”
Press, “SET” to accept the setting on the display and continue to the next feature.

Ar - Auto Restart Feature (standard)
If auto restart is enabled (ON):
If the chiller is running and the power is interrupted due to power outage, tripped circuit breaker, etc.,
the chiller will automatically start when the power is restored.
If auto restart is enabled (OFF):
If the chiller is running and the power is interrupted due to power outage, tripped circuit breaker, etc.,
the chiller will stay off when the power is restored. Push “ON” to restart the chiller.

To activate the auto restart feature:
1.
2.
3.
4.
5.

Enter the customer menu by holding both the “UP” and “DOWN” arrow keys for 3 seconds.
Use the “SET” key to scroll to “Ar.”
The display toggles between “Ar” and its current setting.
Use “UP” or “DOWN” arrow key to toggle between “ON” and “OFF.”.
Press, “SET” to accept the setting on the display and continue to the next feature.

CAL - Calibration offset (standard)
1.
2.
3.
4.
5.

To enter the menu, press and hold both the “UP” and “DOWN” arrow keys for 3 seconds and release.
Use the SET key to scroll to “CAL.”
The display toggles between “CAL” and current offset setting.
Use “UP” or “DOWN” arrows to change the calibration offset, which must be between -4°C and +4°C. If
you do not want to use an offset set it to zero (0).
Press, “SET” to accept the setting on the display and exit the menu.

DEGC - Temperature scale (standard)
1. To enter the menu, press and hold both the “UP” and “DOWN” arrow keys for 3 seconds and release.
2. The first option to change will be “DEGC.”
3. The display toggles between “DEGC” and current setting. Use “UP” or “DOWN” arrows to turn the
degree Celsius display on and off. This will automatically change the pressure scale to psi or to bar.
4. Press, “SET” to accept the setting on the display and exit the menu.

FS—Fault Chiller Shutoff (option)
1.
2.
3.
4.
5.

To enter the menu, press and hold both the “UP” and “DOWN” arrow keys for 3 seconds.
Use the “SET” key to scroll to “FS.”
The display toggles between “FS” and its current setting.
Use “UP” or "DOWN" arrow key to toggle between “ON” and “OFF.”
Press, “SET” to accept the setting on the display and continue to the next feature.

Lt— Low temperature indication (option)
1.
2.
3.
4.

To enter the menu, press and hold both the “UP” and “DOWN” arrow keys for 3 seconds.
Use the “SET” key to scroll to “Lt.”
The display toggles between “Lt” and current over-temperature set point
Use “UP” or “DOWN” arrows to change the low temperature set point, which should be at least 3°C
(6°F) below the coolant set point temperature.
5. Press, “SET” to accept the setting on the display and continue to the next feature.

Manual # 820-0109, Rev. Y, 07/08/10

- 22 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Ot— Over temperature indication (option)
1.
2.
3.
4.

To enter the menu, press and hold both the “UP” and “DOWN” arrow keys for 3 seconds and release.
Use the “SET” key to scroll to “Ot.”
The display toggles between “Ot” and current over temperature set point.
Use “UP” or “DOWN” arrows to change the over temperature set point, which should be at least 3°C
(6°F) above the coolant set point temperature.
5. Press, “SET” to accept the setting on the display and continue to the next feature.

bAr—Pressure Units
1.
2.
3.
4.

To enter the menu, press and hold both the “UP” and “DOWN” arrow keys for 3 seconds.
Use the “SET” key to scroll to “bAr.”
The display toggles between “bAr” and its current setting.
Use “UP” or "DOWN" arrow key to toggle between “ON” and “OFF.” “ON” will display the units in bar
and “OFF” will display the units in psi.
5. Press, “SET” to accept the setting on the display and continue to the next feature.

rS—Remote Start Feature (option)

When it is set to off the chiller acts as if it does not have the remote start feature. By setting this feature to”NC”
(normally closed or run on closed) the chiller will start when pins 1 and 2 on the six-pin connector on the rear of
the chiller are closed. The chiller will shut off when pins 1 and 2 are open. By setting this feature to “NO”
(normally open or run on open) the chiller will start when pins 1 and 2 are open. The chiller will shut off when
pins 1 and 2 are closed. When the remote start feature is enabled within the user menu and the chiller is in the
off state, the chiller cannot be turned on from the front control panel and “rS” will appear on the display. When
the remote start feature is enabled within the user menu and the chiller is operating, turning the chiller off from
the front panel will result in an “Err 05” on the front display. This can be cleared by pressing the On/Off button
again or cycling the remote contact.
1.
2.
3.
4.
5.

To enter the menu, press and hold both the “UP” and “DOWN” arrow keys for 3 seconds.
Use the “SET” key to scroll to “rS.”
The display toggles between “rS” and its current setting.
Use “UP” or "DOWN" arrow key to toggle between “OFF”, “nO”, and “nC.”
Press, “SET” to accept the setting on the display and continue to the next feature.

Manual # 820-0109, Rev. Y, 07/08/10

- 23 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SYSTEM MAINTENANCE AND SERVICE
A qualified service technician must perform all service and maintenance internal to the chiller.
Unqualified individuals conducting service on the chiller could result in damage to the
equipment, personal injury and/or death.
After your Kodiak Recirculating Chiller is up and running, it takes only a small amount of care and maintenance
to keep it running well.
Every installation is unique, and the operating conditions determine how often the equipment should be
inspected and maintenance be performed. The following are some guidelines.

Periodic Inspections
Noise Level
Any abnormal sounds or a substantial increase in noise level since the last weekly inspection may indicate the
following: impending pump, fan or coolant blockage problem. Investigate the cause and perform the necessary
service. Refer to the troubleshooting guide in this manual.

Leakage
If you notice coolant on the floor near the chiller or dripping from the chiller enclosure turn off the chiller.
Disconnect the power cord. Find and repair any leaks immediately.

Coolant Level
Any significant drop in the coolant level should be investigated further. If there is no visible system leak, then
the loss may be due to equipment leakage elsewhere.

Pump / Motor
Some pumps may require lubrication. If the pump needs lubrication, lubricate annually with 20-30 drops of SAE
Oil.

Fan Assembly
No maintenance is required on the fan. Listen for any abnormal sounds.

Condenser Fin
Remove the front grill by sliding it upward, pulling the bottom out and pulling it straight down. For maximum
performance the condenser fin should be free of dust and debris. Use a vacuum cleaner or compressed air to
remove any debris and keep the fin clean.

Water Filter
With a new system the filter quickly accumulates foreign matter introduced during system setup. This can lead
to a decrease in system performance in a short period of time. Inspect the filter cartridge one day after you set
up a new system to ensure the filter is clean and the system runs at maximum capacity. After this initial filter
inspection, check the filter weekly. For replacement filters contact Lytron’s Customer Service at 781-933-7300.

Deionization Package
The cartridge life is a function of the user’s application. Check the water resistively weekly and change the
cartridge as required. For replacement filters contact Lytron’s Customer Service at 781-933-7300.

Low Level Switch
The level switch protects the pump in the event of accidental fluid loss. Since this switch is "passive" during
normal operation, it is advisable to check it every 6 months. Open the tank cover and push down on the switch
to see if the low level alarm is activated.

Manual # 820-0109, Rev. Y, 07/08/10

- 24 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Algae
Lytron recommends the use of an algae inhibitor to prevent growth in the reservoir.

Cleaning the System and Reservoir
To clean the unit follow these steps:
1.
2.
3.
4.
5.
6.

Drain the entire unit including the hoses and equipment being cooled.
Replace the coolant with clean water.
Run the unit with the clean water for 10 minutes.
Drain the unit again.
Replace all filters.
Refill unit with either water or a water and freezing point depressant.

Pump Strainer
All positive displacement pumps have a strainer to protect the vanes inside the pump. For pumps less than 2.5
gpm it is located in the pump housing. For larger PD pumps it is installed in the hose between the pump and
the tank. Periodically inspect and clean the pump strainer. If it becomes fouled the flow rate will decrease and
the pump may wear prematurely.
The strainer can be cleaned by rinsing it in warm water and brushing it gently. For a detailed procedure in
cleaning the pump strainer visit the Maintenance and Troubleshooting section of Lytron’s website at
www.Lytron.com.

Pumps
As a precaution, the pump must be periodically replaced. This will avoid damaging the unit and the cost
associated with excessive downtime. Typical operating life of the pump depends on pump type.

Pump Model
Positive Displacement
Centrifugal
Turbine

Typical
Operating Life
7,000 Hours
28,000 Hours
28,000 Hours

Note: Please contact Lytron for pump pricing and delivery.

Manual # 820-0109, Rev. Y, 07/08/10

- 25 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

DRAINING PROCEDURE FOR KODIAK CHILLERS
Always disconnect power to chiller when performing service. Failure to do so could result in
damage to the equipment, personal injury and/or death.
A container should be available to hold the fluid removed from the chiller. This container
should be labeled in accordance with OSHA rules and regulations concerning handling of the
fluid being removed from the chiller. Failure to do so could result in personal injury.
Reference the MSDS sheet for the fluid being removed from the chiller for further handling,
storage, and disposal instructions. Disposal of fluid removed from the Lytron chiller should be
in accordance with all Local and Federal disposal laws. Failure to do so could result in personal injury.
Not following this procedure may result in extensive damage to the chiller. It is extremely
important to completely drain the chiller when not in use for extended period of time, shipping
outside of its current location, during certain repairs, and for scheduled fluid maintenance. Failure to fully drain
the system could result in damage of the equipment. Lytron recommends method #1 as the most efficient way
to remove fluid from the chiller.
Method #1- Recommended
1. Lytron recommends using a wet/vac to thoroughly remove fluid from the chiller. Remove plastic cap
from top of the clean fluid reservoir. Vacuum this tank until it is completely free of any fluid. Keep
reservoir cap removed from reservoir until step #5.
2. Using wet/vac, first vacuum the “supply” connection located at the rear of the chiller. After all the fluid
has been removed from the supply side, move vacuum to the “return” connection. Vacuum this
connection until all fluid has been removed.
3. Remove side panel of chiller to expose the tank drain hose. The drain line is a ½” braided hose
terminated with a white PVC cap. The drain line branches off from a tee on the chiller return line.
4. Remove plastic cap plug and place vacuum at the end of the hose. Vacuum any remaining fluid from
the system. (Note: make sure reservoir cap is removed, allowing air to enter system).
5. Install plastic cap plug to the end of the drain hose. Install side panel. Attach plastic cap to the clean
fluid reservoir. Install chiller cover.
Method #2- without access to wet/vac
1. Remove chiller cover. Remove reservoir plastic cap. Keep reservoir cap removed from reservoir until
step #4. Remove side panel of chiller to expose the tank drain hose. The drain line is a ½” braided hose
terminated with a white PVC cap. The drain line branches off from a tee on the chiller return line.
2. If possible, elevate the chiller approximately 3’ off the ground. This will allow you to drain the system
into a 5-gallon bucket.
3. Remove the plastic cap plug from the end of the hose. (Note: make sure reservoir cap is removed,
allowing air to enter system). Drain the system into a 5-gallon bucket. Because this process is relying
on gravity, it may take a few minutes to completely drain the system. If the volume of your system
exceeds 5 gallons, have a second bucket nearby.
4. Install plastic cap plug to the end of the drain hose. Install side panel. Attach plastic cap to the clean
fluid reservoir. Install chiller cover.

Manual # 820-0109, Rev. Y, 07/08/10

- 26 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

COOLANT MAINTENANCE
Recommended coolant for use in Lytron systems
x Clean water is recommended for most systems. Systems ordered with the deoinized plumbing package
require that deoinized water be used. Use of deoinized water in systems with brass components may cause
premature failure of the system.
x If the set point temperature is below 50°F/10°C, Ethylene or Propylene Glycol should be added to the water
with a mix ratio of 30% Ethylene or Propylene Glycol to 70% water.
x Do not use automotive antifreeze as the rust inhibitors may cause premature failure of the pump seals.
x Avoid using water with a high mineral content.
x If the chiller is exposed to sunlight, add an algaecide to control organic growth in the coolant. A mixture of
30% Ethylene or Propylene Glycol can also be used to control algae growth.

Checking coolant level
x There is a coolant level site tube on the front of the unit. Coolant should be added as soon as this indicator
approaches the half-full mark.
x Reducing the coolant volume may reduce the chillers cooling capacity.
x Inspect coolant level weekly or whenever the chiller is powered on.

Flush & replace coolant periodically
In order to avoid electric shock, be sure to wipe up all fluid spills in the unit before applying
electrical power. Failure to do so could result in damage to the equipment, personal injury
and/or death.
x Depending on the environmental conditions, the coolant should be flushed and replaced as necessary,
depending on the amount of particulate matter that has been found in the system during planned
maintenance inspections.
x If the pump strainer and coolant is found to have little or no contamination after the first inspection, replacing
the coolant and cleaning the strainer can be done less frequently.
x The pump strainer may be located in one of two places. Refer to the strainer cleaning procedures under
System Maintenance and Service.
x When the strainer is cleaned or replaced, the electrical power must be disconnected and the system drained
of all coolant.

Manual # 820-0109, Rev. Y, 07/08/10

- 27 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

ERROR CODES
There are a few different error codes that can occur during the operation of the chiller. These error codes are
displayed on the front keypad of the system. See below for an explanation of each error code.

Err 01 – Controller Initialization Error
This error code signifies an error in the controller software initialization during power up. Contact the Lytron
Service Department to resolve this type of error.

Err 02 – RTD Error
This error codes means that the resistance temperature device (RTD) is disconnected or damaged. The
controller will display error 02 when the resistance of the RTD is outside of the expected range. A cut wire, a
short to the RTD, and an internal malfunction in the RTD, can cause this or if the wires are disconnected.
Contact the Lytron Service Department for a replacement part number.

Err 03 – Controller Operational Error
This error code signifies an error in the controller software while the chiller is running. Contact the Lytron
Service Department to resolve this type of error.

Err 04 – Low Flow Error
This error code signifies a low flow condition exists. The low flow light, the alarm light and the audible alarm will
all sound when an error 04 occurs. The controller will also shutdown the pump, compressor, and fan. See the
trouble shooting section for suggestions on how to clear this alarm code.

Err 05 – Remote Start
This error code signifies that chiller has been turned off from the front panel while the remote start feature is
enabled within the user menu. This can be cleared by pressing the On/Off button again or cycling the remote
contact.

Err 07 – Auto Temperature Shut Down
This error code signifies that the process fluid temperature is above the highest allowable temperature for this
chiller. This feature is design to shut the chiller down when the process fluid temperature reaches 10°C above
the highest allowable chiller set point. All standard chillers (including part numbers ending in Mxxx) built after
09/24/07 have this feature enabled. Part numbers ending in Cxxx chillers will have this feature enabled upon
request of the customer.

Manual # 820-0109, Rev. Y, 07/08/10

- 28 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

TROUBLE SHOOTING GUIDE
Possible Cause

Problem

No power to the unit, circuit breaker "off"
or tripped.

Fault shutoff enabled.
Low flow shut off will cause the chiller to
stop after 10 seconds.
Unit does not start
or shuts off shortly
after starting.

Low Voltage.
Cooling load exceeds cooling capacity.

Reduce the cooling load on the unit.

Controller set point temperature is too
high.

Reset the set point to the proper
temperature.
Remove the lower grill and vacuum the
coil face clean.

Condenser coil fouled with dust or debris.

Compressor has tripped its internal
overload.
Liquid refrigerant in the suction line to the
compressor.

Remove air obstructions from around the
unit; manually reset the high-pressure
control (Inside rear of unit, this is a blue
button on a white box. Press to reset.)
Let the unit cool. The overload will reset
itself, normally in 30 minutes or less.
This should go away after the system
runs for a few minutes.

Unit has tripped the high-pressure cutout
(RC030, RC045 and water cooled units
only.) (See Pg. 38)

Manually reset the high-pressure control
inside rear of unit, this is a white plastic
button on the box. Press to reset.

Low voltage or wrong voltage to unit.

Verify power source; check electrical
service.

Unit stored in cool environment for a long
period may have collected liquid
refrigerant in the compressor.

This should go away after the system
runs for a few minutes.

Pump shaft seal damage

Replace pump.

Unit has tripped the high-pressure cutout
(RC030, RC045 and water cooled units
only.) (See Pg. 38)

Excessive noise on
startup
Excessive Pressure
in facility water
(water-cooled unit
only)
Noisy compressor

Noisy pump motor

Excessive pressure drop.
Positive displacement pump is worn out.

Pump motor
overheats
Audible alarm stays
on (Control Package II
and III only)

Recommended Remedy
Make sure the unit is plugged in. Verify
power to the unit.
Turn circuit breaker to the "ON" ( I )
position.
Turn on the unit with the ON ( I ) key on
the keypad.
Disable fault shutoff. Start unit. Enable
shutoff after it is running, if desired.
Fill external line prior to start up.
Pump is not Primed – See Pg. 19.
Have a qualified electrician check the
electrical service to the unit.

Improper voltage to the system.
Obstruction in pump head.

Use either larger hoses or a shorter line
length to reduce the pressure drop to
equipment to be cooled.
Replace pump with new one. Contact
Lytron Service Department for part
number and pricing.
Verify and correct the voltage to the
chiller.
Shut down unit, clear obstructions and
restart unit.

Low level in reservoir

Add more fluid to reservoir to full mark.

Level switch is stuck.

Clean the reservoir and level switch.

Level switch is damaged.

Replace level switch.

Manual # 820-0109, Rev. Y, 07/08/10

- 29 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Possible Cause

Problem

Low coolant flow

Low coolant flow

Low temperature alarm is set too close to
cooling set point temperature.
High temperature alarm is set too close to
cooling temperature set point.
Pump suction strainer is clogged.
(Positive displacement pumps only.)
Low coolant level or no coolant in the
reservoir.

Recirculating
pressure is too high
Temperature display
dim at start up.

Adjust high temperate alarm set point.
Remove strainer, clean and reassemble.
Check for leaks. Repair any leaks and fill
reservoir.
Change filter cartridge.

Pressure relief on the pump is set too low.
(Positive displacement and turbine pumps
only.)
Restriction in coolant lines external to the
chiller.

Adjust the pressure relief to 90 psig. For
a high-pressure application (over 90 psig)
contact Lytron Applications Engineering.
Eliminate restrictions in the lines. Open
any valves.
Turn unit off. Wait for overload to cool. It
will reset on its own in 30 minutes or less.

Leaks in external piping.

Repair leaks.

Pump motor shaft is bound.

Replace pump motor.

Damaged pump.

Replace pump.

Shutoff feature is enabled in the controller
set up menu. (Controllers with options II
and III)

Find out and correct the fault that is
causing the shutoff. Disable shutoff
feature (see controller set up).

Low flow switch tripped.

See Low Coolant Flow

Auto Temperature alarm has tripped.
Temperature display
reads incorrectly

Adjust low temperature alarm set point.

Water filter dirty or clogged.

Pump overload has tripped.

Chiller shuts down
during operation

Recommended Remedy

Temperature set point is not set properly.

Process fluid temperature has reach a
temperature higher than the system’s
design temperature.
Verify values in the controller, including
offset. Reset as necessary.

Offset incorrectly set.

Reset temperature offset.

Pressure drop through system is too
large.
Pump internal pressure relief is set too
high.
This is a normal part of the start up
process. It does not indicate that there is
a problem.

Reduce line length or increase line
diameter.

Manual # 820-0109, Rev. Y, 07/08/10

- 30 -

Reset pressure relief to 90 psig.
Wait 5 to 10 seconds and the display will
brighten to its normal level.

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

KODIAK SPARE PARTS
Item #

Description

RC006/RC009

Model# Series
RC011/RC022

RC030/RC045

Lytron Part Number
1
3
4
5
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26

Controller PCB
Circuit Breaker 115V
Circuit Breaker 230V2
Pump and Compressor Relay
Pressure Transducer, Brass
Pressure Transducer, Stainless Steel
Pressure Transducer, Plastic
Temperature Sensor (RTD)
Tank
Low Level Switch
Upper Front Panel
Keypad
Cover
Access Panel
Side Panel
Front Grille
Casters with lock
Casters without lock
Rear Panel
Hot Gas Bypass Valve
Solenoid Valve
Heat Exchanger
Capillary Tube
Liquid Line Filter Dryer
Condenser
Compressor
Condenser Fan
Flow Switch

230-0874-P1
230-0593
230-0588
230-0592
101903-03
230-1006
230-1007
230-0603
250-0072
340-0020
340-0018
230-0892
340-0012
340-0014
230-0947
330-1139-06
330-1165-06
330-0880-06
330-1138-06
330-1166-06
340-0013
340-0015
531-0026
531-0027
330-1141
330-1167

N/A
230-0591

340-0019
340-0016
330-1172-06
330-1173-06
340-0017
531-0016
531-0017
330-1174

All of these parts require service by a qualified refrigeration
technician. Please contact Lytron if you have any problems
with one of these parts.

Contact Lytron for replacement fan part number.
250-0136
230-0912

1

Please include model and serial number when ordering the controller PCB so they may be correctly programmed.
Chillers with a heater require a different circuit breaker. Contact Lytron’s Customer Service at +1-781-933-7300 for
additional information.
2

Manual # 820-0109, Rev. Y, 07/08/10

- 31 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Item #

6

2

* 6A1

(All Models)
Part Number

Pumps and Motors
1.3 gpm Brass Pump Kit
1.8 gpm Brass Pump Kit
2.3 gpm Brass Pump Kit
4.3 gpm Brass Pump Kit
1.3 gpm Stainless Steel Pump Kit
1.8 gpm Stainless Steel Pump Kit
2.3 gpm Stainless Steel Pump Kit
4.3 gpm Stainless Steel Pump Kit
1/4 Hp 115 V Motor
1/4 Hp 230 V Motor
1/3 Hp 115/230 V Motor
1/2 Hp 115/230 V Motor
1/20 Hp Centrifugal Pump 115 V
1/20 Hp Centrifugal Pump 230 V
1/4 Hp Centrifugal Pump 115 V
1/4 Hp Centrifugal Pump 230 V
1/2 Hp Turbine Pump 115/230 V
1/6 Hp Turbine Pump 115V “EC”
1/6 Hp Pump 230V “EC”

205-0004
205-0005
205-0006
205-0007
205-0009
205-0010
205-0105
205-0011
230-0202
230-0214
230-0215
230-0203
410-0196
410-0197
101773-06
101773-05
410-0229
410-0336
410-0337

ACCESSORIES FOR THE KODIAK RECIRCULATING CHILLER
Description

Lytron Part Number

5” Water Filters (min order 10)
Air Filter RC006/RC009
Air Filter RC011/RC022
Air Filter RC030/RC045
Water Filter Kit
External Pressure Relief Kit (0-50 psig)
External Pressure Relief Kit (50-100 psig)

1

330-0022
330-0053
330-0692
330-0683
200-0441
200-0196
200-0080

Item 6A refers to Pump & Motor combination.
Manual # 820-0109, Rev. Y, 07/08/10

- 32 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

FRONT VIEW
(Reference Spare Parts List in this manual)

ACCESS PANEL

COVER

13

12

KEYPAD
11
UPPER
FRONT
10

SIDE
14

FRONT
GRILLE
15
CASTERS
16

Manual # 820-0109, Rev. Y, 07/08/10

- 33 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REAR VIEW (WITH PANEL)
(Reference Spare Parts List in this manual)
CIRCUIT
BREAKER
3

REAR
PANEL
17

Manual # 820-0109, Rev. Y, 07/08/10

- 34 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

TOP VIEW
(Reference Spare Parts List in this manual)
PUMP AND
COMPRESSOR RELAY
4

PUMP
6

PRESSURE
TRANSDUCE

6A

5
TEMP
SENSOR
7

TANK
8

MOTOR
2

FLOW
SWITCH
9

Manual # 820-0109, Rev. Y, 07/08/10

- 35 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REAR VIEW (OPENED)
(Reference Spare Parts List in this manual)
HOT GAS
BYPASS VALVE

FLOW
SWITCH

18

26

20

21

HEAT EXCHANGER

Manual # 820-0109, Rev. Y, 07/08/10

CAPILLARY TUBE

- 36 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SIDE VIEW
(Reference Spare Parts List in this manual)

FLOW SWITCH

COMPRESSOR

26

24

Manual # 820-0109, Rev. Y, 07/08/10

25

19

22

23

SOLENOID VALVE

LIQUID LINE
FILTER DRYER

CONDENSER

- 37 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SIDE VIEW (WITH HIGH PRESSURE CUTOUT)

RESET BUTTON

HIGH PRESSURE CUTOUT

Manual # 820-0109, Rev. Y, 07/08/10

- 38 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CHILLER DIMENSIONS FOR RC006 AND RC009

½”

Manual # 820-0109, Rev. Y, 07/08/10

- 39 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CHILLER DIMENSIONS FOR RC011 AND RC022

½”

Manual # 820-0109, Rev. Y, 07/08/10

- 40 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CHILLER DIMENSIONS FOR RC030 AND RC045

Manual # 820-0109, Rev. Y, 07/08/10

- 41 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

WIRING DIAGRAM

Manual # 820-0109, Rev. Y, 07/08/10

- 42 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

PLUMBING DIAGRAM

Manual # 820-0109, Rev. Y, 07/08/10

- 43 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REFRIGERATION DIAGRAM

Manual # 820-0109, Rev. Y, 07/08/10

- 44 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

HOST INTERFACE DATA LINK
Control Package 3 only
1.0 Host Interface Data Link
The chiller supports basic host control capability through the Chiller RS-232 port.

1.1 Port Settings
The host port runs at 9600 baud, 8 data bits, 1 stop bit, and no parity.

1.2 Flow Control
The chiller negates the Chiller RTS (output from Chiller) line whenever the Chiller is busy in a non-interruptible
process. The Chiller ignores the Host CTS line. No software (Xon/Xoff) flow control is provided. It is the
responsibility of the host to issue only a single command for which a response from the Chiller Control is
required until the response is received from the Chiller Control. Inter and intra message timeout is defined as 1
second. (Typical response times and character pacing will be baud rate limited.)

1.3 Encoding
All characters are to be ASCII characters. All messages from the host to the control and from the control to the
host will have 0x10 (ASCII Line Feed) as a start-of-message delimiter, and 0x0D (ASCII Carriage return) as an
end-of-message delimiter. Permitted message characters are in the range of 0x20 through 0x7F
(hexadecimal).

1.4 Numeric Representation
Hexadecimal numbers, using ASCII characters ‘0’ – ‘9’ & ‘A’ – ‘F’, will represent all numeric values. When the
Chiller Control returns multiple variables or parameters they will be white space separated (using ASCII 0x20).
The host should recognize and use comma, tab and space as white space characters.

1.5 Units
All temperature values will be communicated in two byte hex values of qCx100 (.01 Cq). Resolution of
temperature values is .1 degree. All pressure values will be communicated in integer psi with no offset.

1.6 Commands
1.6.1

The following host Control messages are defined:

1.6.2

Read Chiller Status
This command (‘R’) will cause the Chiller Control to return a complete status string with the
following form:
^JR ControlFlags AlarmFlags PlantTemp SetTemp Pressure ^M
Where: ControlFlags Status in Bit encoded Byte (2 chars). Assignments are:
Bit 7:
Bit 6:
Bit 5:
Bit 4:
Bit 3:
Bit 2:
Bit 1:
Bit 0:

(MSB); Machine on:
Expansion Relay2 on:
Expansion Relay1 on:
Heater on:
Autopilot:
Condenser Relay on:
Cool Valve On:
(LSB); Celsius Display on:

Manual # 820-0109, Rev. Y, 07/08/10

Lights the temperature display and pressure indicator bar
Not used by host program
Not used by host program
Not used by host program
Not used by host program
Not used by host program
Light the Cool Status
Determines the display in Low resolution

- 45 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual
Where:
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit0

Alarm Flags Status in Bit encoded Byte (2 chars). Assignments are:
(MSB) Over Temp:
Over Temperature Alarm is lit
Lo Temp:
Low Temperature Alarm is lit
Low Flow:
Low Flow Alarm is lit
Low Level:
Low Level Alarm is lit
Not used:
Not used
Not used:
Not used
Audible Alarm on:
Alarm transistor (Al toggle)
(LSB); Summary Alarm on: Beeps computer

PlantTemp and SetTemp encoded (2-byte hex (qCx100)
Pressure encoded is integer value (hex 1-byte)

1.6.3

Read Plant Temperature
This command (‘T’) will cause the Chiller Control to return the plant temperature in a status
string with the following form:
^JT PlantTemp^M
Where: PlantTemp Plant Temperature Value (2-byte hex (qCx100)
^J ^M Ascii Linefeed and Carriage Return

1.6.4

Read Set Point Temperature
This command (‘S’) will cause the Chiller Control to return the current setpoint temperature in
a status string with the following form:
^JS SetTemp^M
Where: SetTemp Setpoint Temperature Value (2-byte hex (qCx100)
^J ^M Ascii Linefeed and Carriage Return

1.6.5

Read User Menu Configuration
This command (‘U’) will cause the Chiller Control to return the current User Menu configuration
information in a status string with the following form:
^JU UserControlFlags OverTempAlmLmt LowTempAlmLmt OffsetCal^M
Where: UserControlFlags Status in Bit encoded Byte (2 chars). Audible Alarm Enable & Fault
Chiller Shutoff are encoded in this byte as follows:
Bit 7:
Bit 6:
Bit 5:
Bit 4:
Bit 3:
Bit 2:
Bit 1:
Bit 0:

(MSB): Chiller PowerOn : Host signal to turn on
Chiller PowerOff:
Host signal to turn off
Chiller F/C:
Host Signal to toggle F/C
Fault Chiller Shut Off : Fault chiller shutoff is enabled, lights host window
Audible Alarm Enable: Audible Alarm is enabled
Not used
Remote Start NC:
Remote start contact closure to run, else Off
(LSB); Remote Start NO:Remote start contact open to run, else Off

OverTempAlmLmt: High Temp Limit Setpoint (2-byte hex (qCx100)
LowTempAlmLmt: Low Temp Limit Setpoint (2-byte hex (qCx100)
OffsetCal Plant Temp Offset (2-byte hex (qCx100)
^J ^M Ascii Linefeed and Carriage Return

Manual # 820-0109, Rev. Y, 07/08/10

- 46 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

1.6.6

Set Chiller Control Plant Setpoint Temperature
This command (‘P’) from the host will set the Chiller Control Temperature Setpoint.
The Host command is of the form:
^JP SetTemp^M
Where: SetTemp Setpoint Temperature Value (2-byte hex (qCx100)
^J ^M ASCII Linefeed and Carriage Return

1.6.7

Set Optional Over-temperature Limit
This command (‘X’) from the host will set the Chiller Optional Over-temperature Limit. Note
that it is the host’s responsibility to determine if this option is active. The Host command is of
the form:
^JX OverTempAlmLmt ^M
Where: OverTempAlmLmtHigh Temp Limit Setpoint (2-byte hex (qCx100)
^J ^M ASCII Linefeed and Carriage Return

1.6.8

Set Low Temperature Alarm Limit
This command (‘Y’) from the host will set the Chiller Optional Low-temperature Limit. Note
that it is the host’s responsibility to determine if this option is active. The Host command is of
the form:
^JY LowTempAlmLmt ^M
Where: LowTempAlmLmt Low Temp Limit Setpoint (2-byte hex (qCx100)
^J ^M ASCII Linefeed and Carriage Return

1.6.9

Set Offset Calibration
This command (‘Z’) from the host will set the Chiller Plant Temperature Offset Calibration. The
Host command is of the form:
^JZ OffsetCal ^M
Where: OffsetCal Offset Calibration (2-byte hex (qCx100)
^J ^M ASCII Linefeed and Carriage Return

1.6.10 Set User Control Flags
This command (‘W’) from the host will set the Chiller User Control Flags. As noted in the bit
descriptions above, the host may use the Power-On and Power-off bits to force the Chiller
On/Off. The Host command is of the form:
^JW UserControlFlags ^M
Where: UserControlFlags in Bit encoded Byte (2 chars)
Bit 7:
(MSB); Chiller On
Bit 6:
Chiller Off
Bit 5:
F/C degree display toggle (not active in .1 display mode)
Bit 4:
Fault Chiller shutoff enable
Bit 3:
Audible alarm enable
Bit 2:
Not used
Bit 1:
Auto Start with NC
Bit 0:
(LSB); Auto Start with NO
^J ^MASCII Linefeed and Carriage Return

Manual # 820-0109, Rev. Y, 07/08/10

- 47 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

LYTRON COOLING SYSTEMS SERVICE POLICY
Lytron’s cooling systems are the product of over 40 years of thermal engineering and
manufacturing experience. We designed them to provide superior reliability, easy
maintenance, and worry-free operation. However, occasionally a system may need repair. To
ensure your process is back up and running quickly, Lytron has implemented the following
cooling system service policy.
Lytron's Standard Warranty
Lytron's warranty is set forth at the end of the cooling system manual sent with each product.
Diagnostic Consultation:
At no cost, Lytron will attempt to diagnose the problem over the phone. Our service department can
be reached by calling +1-781-933-7305 and following the menu. Service technicians are available 24
hours/7 days for consultation. Lytron strongly encourages customers to take advantage of this service
before returning a cooling system to Lytron for evaluation. Often a problem with a system can be fixed
quickly in-house or is an application problem. By working with Lytron’s service department to
troubleshoot a cooling system, you do not have the downtime and expense associated with returning
the system to our factory.
Phone diagnosis can be difficult and may actually be a trial and error process. Lytron will not assume
any liability for misdiagnosis when diagnosing over the phone.
Warranty and Non-warranty Returns:
To return a cooling system, a Lytron Return Material Authorization (RMA) number must be obtained
from Lytron’s service department, which can be reached by calling +1-781-933-7305 and following the
menu. Prior to calling, the system part number, serial number, and a detailed description of the
problem must be recorded, as this information is required to assign an RMA number. A Purchase
Order, (PO), is also required for the evaluation and repair charges if Lytron determines the system is
not defective as defined by the warranty (see below for more details). The RMA number should be
indicated on the outside packaging of the returned unit. Systems must be returned clean, dry, and
free from chemicals to Lytron’s factory, shipping costs prepaid. Lytron is not responsible for any
damage incurred in the return shipment.
Lytron ordinarily will evaluate the unit within 2 or 3 business days of receipt. Lytron will use
reasonable effort to repair the unit promptly, in most cases within one week of receiving all the
required parts.
If upon examination Lytron determines the system is not defective as defined by the warranty, an
evaluation fee of $375 to $595, depending upon the system type will be charged. The evaluation fee
will be charged regardless of disposition (i.e.: scrap).
In order to expedite the repair process for both warranty and non-warranty repair returns, a PO is
required with recommended limits that will be determined when calling for the RMA. The amount
suggested will cover the evaluation fee and most repair charges for non-warranty repairs. Lytron will
proceed with the repair unless the total charges (evaluation and repair) exceed the amount of the PO.
If this is the case, Lytron will provide a quote before proceeding with the repair. Repairs determined to
be covered under warranty will not have any charges posted against the PO.

Manual # 820-0109, Rev. Y, 07/08/10

- 48 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Debit memos should not be issued for warranty and non-warranty repairs unless the unit is returned
as a result of an out-of-box (new) failure.
Lytron will warranty the repair for one year from the repair date under the terms of our standard
warranty or for the balance of the original warranty, whichever is longer.
Return Shipments:
Lytron’s warranty covers payment for standard, ground return shipment of warranted repairs. The
incremental difference for expedited return shipments, if requested, are the responsibility of the
customer. After non-warranty repair, Lytron will ship the system back using the customer’s preferred
shipping method.
Field Service/Installation Charges
Where available, Lytron can arrange field service for cooling system installation or repair. Under no
circumstances does Lytron’s warranty cover on-site service. All on-site service must be arranged
through Lytron’s service department. The charges for this service are as follows:
$250 administrative fee
x
x
x

Plus the following:
$100/hr for on-site services provided*
Any related travel charges
Parts not covered under warranty.
*

The hourly labor rate may vary depending upon city. Contact Lytron’s service
department for current rates in effect at the time.

All requests for On-Site Services require a PO or credit card in the amount of $800 before services
will be scheduled.
When using Lytron-arranged, on-site service, Lytron warranties the replacement parts and repair
labor for 90 days from the repair date under the terms of our standard warranty or for the balance of
the original warranty, whichever is longer. If non-authorized labor repairs the system or installs
replacement parts, Lytron does not warranty the parts or work and this action potentially voids any
remaining warranty.
Lytron is expanding its worldwide service presence. Please contact the Service Department for the
latest areas where on site service is available.
Replacement Parts:
Replacement parts can be ordered using a credit card or purchase order. Parts being returned from
systems under warranty should be returned using a Lytron issued RMA number. If the parts are found
to be defective and the claim is within the warranty period, credit will be issued for the price of the
parts and one-way ground shipping charges. If the parts are not defective or indicate end user
damage, no credit will be issued. Lytron will not cover the incremental cost of air shipment of
replacement parts, regardless of warranty status.
In-stock parts normally will be shipped the next business day; non-stocked parts will be shipped as
quickly as reasonably possible.
This policy is subject to change. Please check with Lytron’s service department for the current policy.
Form F4.3.25 Rev D, 7/21/04

Manual # 820-0109, Rev. Y, 07/08/10

- 49 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

LYTRON KODIAK RECIRCULATING CHILLER STANDARD WARRANTY
Lytron agrees that the apparatus manufactured by it will be free from defects in materials and workmanship for
the warranty period under normal use and service and when properly installed. The warranty period for
recirculating chillers is two years from date of shipment of such apparatus to the original purchaser,
maintenance items excluded, and one year from date of shipment of such apparatus to the original purchaser
for all other products Lytron sells. Lytron’s obligation under this agreement is limited solely to repair or
replacement, at its option, at its factories, of any part or parts thereof, returned to Lytron with transportation
charges prepaid, which examination shall disclose to Lytron’s satisfaction to have been defective.
THE
FOREGOING EXPRESS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED,
INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE.
LYTRON'S OBLIGATION UNDER THIS WARRANTY IS STRICTLY AND
EXCLUSIVELY LIMITED TO THE REPAIR OR REPLACEMENT OF DEFECTIVE COMPONENT PARTS AND
LYTRON DOES NOT ASSUME OR AUTHORIZE ANYONE TO ASSUME FOR IT ANY OTHER OBLIGATION.
LYTRON ASSUMES NO RESPONSIBILITY FOR INCIDENTAL, CONSEQUENTIAL, OR OTHER DAMAGES
INCLUDING, BUT NOT LIMITED TO LOSS OR DAMAGE TO PROPERTY, LOSS OF PROFITS OR
REVENUE, LOSS OF THE UNIT, LOSS OF TIME, OR INCONVENIENCE. Lytron’s liability does not include
any labor charges for replacement of parts, adjustments, repairs, or any other work done outside its factories
and its liability does not include any resulting damage to persons, property, equipment, goods or merchandise
arising out of any defect in or failure of its apparatus. Lytron’s obligation to repair or replace shall not apply to
any apparatus which shall have been repaired or altered outside of its factory in any way, or which has been
subject to negligence, to misuse, or to pressures in excess of stated limits. On parts not of Lytron’s
manufacture, such as motors, controls, etc., Lytron extends only those warranties given to Lytron, Inc. to the
extent Lytron can do so. Lytron’s agreement hereunder runs only to the immediate purchaser from Lytron, Inc.
and does not extend, expressly or by implication, to any other person.
Form F4.3.18 Rev E June 6, 2003

Manual # 820-0109, Rev. Y, 07/08/10

- 50 -

Check Lytron’s website www.Lytron.com
for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

DECLARATION OF CONFORMITY

Manual # 820-0109, Rev. Y, 07/08/10

- 51 -

Check Lytron’s website www.Lytron.com
for the most current technical information.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
Linearized                      : No
Page Count                      : 53
PDF Version                     : 1.4
Producer                        : Mac OS X 10.6.8 Quartz PDFContext
Create Date                     : 2011:12:02 16:45:38Z
Modify Date                     : 2011:12:02 16:45:38Z
EXIF Metadata provided by EXIF.tools

Navigation menu