Page 1R-3451
INSTALLATION INSTRUCTIONS
AND
OWNER'S MANUAL
CAST IRON
UNVENTED
ROOM HEATER
MODEL
CIVF-25-2
EFFECTIVE DATE
JULY, 2000
This is an unvented gas-fired heater. It
uses air (oxygen) from the room in which
it is installed. Provisions for adequate com-
bustion and ventilation air must be pro-
vided. Refer to page 4.
WARNING: If not installed, operated and
maintained in accordance with the manu-
facturer's instructions, this product could
expose you to substances in fuel or from
fuel combustion which can cause death or
serious illness.
WATER VAPOR: A BY-PRODUCT OF
UNVENTED ROOM HEATERS
Water vapor is a by-product of gas com-
bustion. An unvented room heater pro-
duces approximately one (1) ounce (30ml)
of water for every 1,000 BTU's (.3KW's) of
gas input per hour. Refer to page 4.
FOR YOUR SAFETY: What to do if you
smell gas:
Do not touch any electrical switches
Do not try to light any appliance.
Do not use the phone in your building.
Immediately call your gas supplier
from a neighbor's phone.
Follow the gas supplier's instructions.
If you cannot reach your gas supplier,
call the fire department.
WARNING: If the information in this
manual is not followed exactly, a fire or
explosion may result causing property
damage, personal injury or loss of life.
Installation and service must be per-
formed by a qualified installer, service
agency, or the gas supplier. Do not store
or use gasoline or other flammable va-
pors and liquids in the vicinity of this or
any other appliance.
Page 2 R-3451
Introduction
Always consult your local Building Department regarding regulations,
codes or ordinances which apply to the installation of an unvented room
heater.
This appliance may be installed in an aftermarket* permanently located,
manufactured (mobile) home, where not prohibited by state or local
codes.
*Aftermarket: Completion of sale, not for purpose of resale, from the
manufacturer.
This appliance is only for use with the type of gas indicated on the rating
plate.
Instructions to Installer
1. Installer must leave instruction manual with owner after installa-
tion.
2. Installer must have owner fill out and mail warranty card supplied
with unvented room heater.
3. Installer should show owner how to start and operate unvented
room heater.
WARNING: ANY CHANGE TO THIS HEATER OR ITS CON-
TROLS CAN BE DANGEROUS.
Any safety screen or guard removed for servicing an appliance
must be replaced prior to operating the heater.
WARNING
More frequent cleaning may be required due to excessive lint
from carpeting, bedding materials, etc. It is imperative that
control compartments, burners and circulating air passageways
of the appliance be kept clean.
DO make a periodic visual check of pilot and burners. Clean and
replace damaged parts.
DO NOT use this room heater if any part has been under water.
Immediately call a qualified service technician to inspect the
room heater and to replace any part of the control system and
any gas control which has been under water.
Due to high surface temperatures, keep children, clothing and
furniture away.
Under no circumstances should any solid fuels (wood, coal, paper
or cardboard etc.) be used in this appliance.
The flow of combustion and ventilation air must not be obstructed
in any way.
An unvented room heater having an input rating of more than
10,000 Btu per hour shall not be installed in a bedroom or
bathroom.
Due to high temperatures, the appliance should be located out
of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazard of high
surface temperature and should stay away to avoid burns or
clothing ignition.
Young children should be carefully supervised when they are
in the same room with the appliance.
Do not place clothing or other flammable material on or near
the appliance.
Keep burner and control compartment clean.
Installation and repair should be done by a QUALIFIED
SERVICE PERSON. The appliance should be inspected before
use and at least annually by a professional service person.
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANEL INSTALLED.
When used without adequate combustion and ventilation air,
heater may give off CARBON MONOXIDE, an odorless, poison-
ous gas.
Do not install heater until all necessary provisions are made
for combustion and ventilation air. Consult the written in-
structions provided with the heater for information concern-
ing combustion and ventilation air. In the absence of instruc-
tions, refer to the National Fuel Gas Code, ANSI Z223.1,
Section 5.3 or applicable local codes.
This heater is equipped with a PILOT LIGHT SAFETY SYS-
TEM designed to turn off the heater if not enough fresh air is
available.
DO NOT TAMPER WITH PILOT LIGHT SAFETY
SYSTEM!
If heater shuts off, do not relight until you provide fresh air.
If heater keeps shutting off, have it serviced. Keep burner and
control compartment clean.
CARBON MONOXIDE POISONING MAY LEAD TO
DEATH.
Early signs of carbon monoxide poisoning resemble the flu, with
headache, dizziness and/or nausea. If you have these signs, heater
may not be working properly. Get fresh air at once! Have heater
serviced.
Some people — pregnant women, persons with heart or lung
disease, anemia, those under the influence of alcohol , those at high
altitudes — are more affected by carbon monoxide than others.
The pilot light safety system senses the depletion of oxygen at its
location. If this heater is installed in a structure having a high
vertical dimension, the possibility exists that the oxygen supply at
the higher levels will be less than that at the heater. In this type of
application, a fan to circulate the structure air will minimize this
effect. The use of this fan will also improve the comfort level in the
structure. When a fan is used to circulate air, it should be located
so that the air flow is not directed at the burner.
General Information
This CIVF-25 is design certified in accordance with American National
Standards Institute Z21.11.2b-1998 by the American Gas Associaton as
an Unvented Room Heater and should be installed according to these
instructions.
Attention: During initial use of ceramic log you will detect an odor
as the ceramic log is cured. Also, during the curing process the
ceramic log will burn with a yellow flame.
Any alteration of the original design, installed other than as shown
in these instructions or use with a type of gas not shown on the rating
plate is the responsibility of the person and company making the
change.
Important
All correspondence should refer to complete Model No., Serial No. and
type of gas.
Notice: During initial firing of this unit, its paint will bake out, and
smoke will occur. To prevent triggering of smoke alarms, ventilate the
room in which the unit is installed.
Page 3R-3451
Some people cannot smell well. Some people cannot smell the
odor of the chemical stench put into the gas. You must find
out if you can smell the odorant in propane. Smoking can
decrease your ability to smell. Being around an odor for a time
can affect your sensitivity or ability to detect that odor. Some-
times other odors in the area mask the gas odor. People may not
smell the gas odor or their minds are on something else. Thinking
about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under
some circumstances. For example, if there is an underground
leak, the movement of the gas through soil can filter the odorant.
Odorants in LP-Gas also are subject to oxidation. This fading can
by point with the members of your household. Someday
when there may not be a minute to lose, everyone's safety will
depend on knowing exactly what to do. If, after reading the
following information, you feel you still need more informa-
tion, please contact your gas supplier.
Propane (LP-Gas) is a flammable gas which can cause fires
and explosions. In its natural state, propane is odorless and
colorless. You may not know all the following safety precau-
tions which can protect both you and your family from an
accident. Read them carefully now, then review them point
occur if there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That
will take some of the odorant out of the gas, reducing its odor
intensity.
LP-Gas may stratify in a closed area, and the odor intensity could
vary at different levels. Since it is heavier than air, there may be
more odor at lower levels. Always be sensitive to the slightest
gas odor. If you detect any odor, treat it as a serious leak.
Immediately go into action as instructed earlier.
Learn to recognize the odor of LP-gas. Your local LP-Gas
Dealer can give you a "Scratch and Sniff" pamphlet. Use it to
find out what the propane odor smells like. If you suspect that
your LP-Gas has a weak or abnormal odor, call your LP-Gas
Dealer.
If you are not qualified, do not light pilot lights, perform
service, or make adjustments to appliances on the LP-Gas
system. If you are qualified, consciously think about the odor
of LP-Gas prior to and while lighting pilot lights or perform-
ing service or making adjustments.
Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the
odor if there has been a leak of LP-Gas.
Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people
should be particularly alert and careful when new tanks or
cylinders are placed in service. Odor fade can occur in new
tanks, or reinstalled old tanks, if they are filled and allowed
to set too long before refilling. Cylinders and tanks which
have been out of service for a time may develop internal rust
which will cause odor fade. If such conditions are suspected
to exist, a periodic sniff test of the gas is advisable. If you
have any question about the gas odor, call your LP-gas
dealer. A periodic sniff test of the LP-gas is a good safety
measure under any condition.
If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the same
immediate action recommended above for the occasion when
you do detect the odorized LP-Gas.
If you experience a complete "gas out," (the container is
under no vapor pressure), turn the tank valve off immedi-
ately. If the container valve is left on, the container may draw
in some air through openings such as pilot light orifices. If
this occurs, some new internal rusting could occur. If the
valve is left open, then treat the container as a new tank.
Always be sure your container is under vapor pressure by
turning it off at the container before it goes completely empty
or having it refilled before it is completely empty.
SAFETY INFORMATION FOR USERS OF LP-GAS
Do not operate electric switches, light matches, use your
phone. Do not do anything that could ignite the gas.
Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
Close all gas tank or cylinder supply valves.
LP-Gas is heavier than air and may settle in low areas such
as basements. When you have reason to suspect a gas leak,
keep out of basements and other low areas. Stay out until
firefighters declare them to be safe.
Use your neighbor's phone and call a trained LP-Gas service
person and the fire department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not re-
enter the building, vehicle, trailer, or area.
Finally, let the service man and firefighters check for
escaped gas. Have them air out the area before you return.
Properly trained LP-Gas service people should repair the
leak, then check and relight the gas appliance for you.
SOME POINTS TO REMEMBER
NO ODOR DETECTED - ODOR FADE
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
Page 4 R-3451
Provisions for Adequate Combustion and Ventilation Air
This heater shall not be installed in a confined space or unusually tight
construction unless provisions are provided for adequate combustion and
ventilation air.
The National Fuel Gas Code, ANSI Z223.1 defines a confined space as a
space whose volume is less than 50 cubic feet per 1,000 Btu per hour
(4.8m3 per kw) of the aggregate input rating of all appliances installed in
that space and an unconfined space as a space whose volume is not less
than 50 cubic feet per 1,000 Btu per hour (4.8m3 per kw) of the aggregate
input rating of all appliances installed in that space. Rooms communicat-
ing directly with the space in which the appliances are installed, through
openings not furnished with doors, are considered a part of the unconfined
space.
The following example is for determining the volume of a typical area in
which the CIVF-25 may be located and for determining if this area fits
the definition of an unconfined space.
The maximum input of the CIVF-25 is 25,000 Btu per hour. Based on the
50 cubic feet per 1,000 Btu per hour formula, the minimum area that is
an unconfined space for installation of the CIVF-25 is 1,250 cubic feet,
50 cubic feet x 25 = 1,250 cubic feet. To determine the cubic feet of the
area in which the CIVF-25 is to be installed, measure the length, width
and height of the area. Example: The area measures 16 feet in length, 10
feet in width and 8 feet in height, the area is 1,280 cubic feet. The CIVF-
25 can be installed in this unconfined space with no requirement to
provide additional combustion and ventilation air.
Warning: If the area in which the heater may be operated is smaller than
that defined as an unconfined space or if the building is of unusually tight
construction, provide adequate combustion and ventilation air by one of
the methods described in the National Fuel Gas Code, ANSI Z223.1,
Section 5.3 or applicable local codes.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh
air for combustion and ventilation. However, in buildings of unusually
tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. Walls and ceilings exposed to the outside atmosphere have a
continuous water vapor retarder with a rating of one perm or less
with openings gasketed or sealed, and
b. Weatherstripping has been added on openable windows and
doors, and
c. Caulking or sealants are applied to areas such as joints around
window and door frames, between sole plates and floors, be-
tween wall-ceiling joints, between wall panels, at penetrations
for plumbing, electrical, and gas lines, and at other openings.
If the CIVF-25 heater is installed in a building of unusually tight
construction, adequate air for combustion, ventilation and dilution of
flue gases shall be provided in accordance with ANSI Z223.1/NFPA54.
Clearances (Figures 1, 2 and 3)
When facing the front of the appliance the following minimum clearances
to combustible construction must be maintained.
Top of appliance (ceiling) 24 inches
Rear Wall 2 inches
Side Wall 6 inches
Heater Corners (45° angle) to Wall 4 inches
Floor 0 inches
Provide adequate clearances around air openings.
Adequate accessibility clearances for purposes of servicing and proper
operation must be provided.
Installation on Rugs and Vinyl
If this appliance is installed directly on carpeting, vinyl or other combus-
tible material, other than wood flooring, the appliance shall be installed
on a metal or wood panel extending the full width and depth of the
appliance.
Specifications
Model CIVF-25
Input BTU/HR (KW/H) Max. (LP/NAT) 25,000 ( 7.3)
BTU/HR (KW/H) Min. LP 18,000 (5.3)
BTU/HR (KW/H) Min. Nat. 17,000 (5.0)
Height 27 3/4" (70.5cm)
Width 25 1/2" (64.8cm)
Depth 15 1/2" (39.4cm)
Gas Inlet 3/8" (9.5mm)
Stove Casting (Must be ordered with Firebox.)
CIFB-1 Flat Black
CIPB-1 Porcelain Black
CIPG-1 Porcelain Green
CIPS-1 Porcelain Sand
CIPN-1 Porcelain Navy
CIPR-1 Porcelain Red
Accessories
GWSG-T 750 Millivolt Wall Thermostat
FRBC-1 Battery Operated Remote Control
FRBTC-1 Battery Operated Remote Control
with Thermostat
FREC-1 Electric Remote Control
FWS-1 Wall Switch
CIB-2 Automatic Blower
Stone Inlay Replaces Standard Grille Top
CII-2 Stone Inlay Empress Green
CII-3 Stone Inlay Hunan Jade
CII-4 Stone Inlay Gray Botticino
CII-5 Stone Inlay Azul
CII-6 Stone Inlay Salome
CII-7 Stone Inlay Black Swan
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment or
accessories and repair and servicing of equipment shall be performed only
by a qualified agency. The term "qualified agency" means any individual,
firm, corporation or company which either in person or through a
representative is engaged in and is responsible for (a) the installation or
replacement of gas piping or (b) the connection, installation, repair or
servicing of equipment, who is experienced in such work, familiar with
all precautions required and has complied with all the requirements of the
authority having jurisdiction.
The installation must conform with local codes or, in the absence of local
codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54.*
*Available from the American National Standards Institute, Inc., 11 West 42nd St.,
New York, N.Y. 10036.
Water Vapor: A By-Product of Unvented Room Heaters
Water vapor is a by-product of gas combustion. An unvented room
heater produces approximately one (1) ounce (30ml) of water for every
1,000 BTU's (.3KW's) of gas input per hour.
Unvented room heaters are recommended as supplemental heat (a room)
rather than a primary heat source (an entire house). In most supplemental
heat applications, the water vapor does not create a problem. In most
applications, the water vapor enhances the low humidity atmosphere
experienced during cold weather.
The following steps will help insure that water vapor does not become a
problem.
1. Be sure the heater is sized properly for the application, including
ample combustion air and circulation air.
2. If high humidity is experienced, a dehumidifier may be used to help
lower the water vapor content of the air.
3. Do not use an unvented room heater as the primary heat source.
Page 5R-3451
Figure 1
Figure 2
Figure 3
Page 6 R-3451
Appliance Hardware Package (Figure 4)
Figure 4
Appliance Hardware Package Parts List
Part Part Quantity
Description Number Supplied
1/4-20 x 1" Phillips Head Bolt R-3188 4
1/4-20 x 3/8" Phillips Head Bolt R-3646 16
1/4-20 x 1/2" Leveling Bolt R-3747 4
No. 10 x 1/2" R-2737 6
Hex Washer Head Screw
1/4-20 Washer Head Nut R-3185 4
Leg Pad "A" (see Figure 5) CI-008 2
Leg Pad "B" (see Figure 5) CI-009 2
1-1/4" x 1/2" Retaining Tab CI-007 4
(see Figure 8)
1/4" x 9/32 Washer (Not Shown) R-1150 8
Assembly of Cast Iron (Outer Casing) Stove Casting
(Figures 5, 6, 7, 8, and 9)
Attention: Included in the hardware package are (8) 1/4" inside diam-
eter washers. A 1/4" washer may be used with a 1/4-20 x 3/8" bolt when
assembling the stove casting parts. If a bolt hole is not tapped deep
enough for a tight fit between stove casting parts, the 1/4" washer can
be used as a shim to provide a tight fit.
The 1/4" washers are not required for assembly of the stove casting if all
the bolt holes are tapped to a proper depth.
Additonal 1/4" washers are to be purchased locally.
1. Place porcelain casting pieces on a non-abrasive surface in order
to protect the porcelain finish. The exterior of the porcelain
casting pieces should be facing the non-abrasive surface.
2. The assembly of the casting is accomplished in 6 stages:
A. Attaching legs to the sides (Figure 5).
B. Attaching rear cover to sides (Figure 6).
C. Removing protective packaging from casing front and window
(Figure 7).
D. Assembly of front by attaching retaining tabs and placing front
on unit (Figure 8).
E. Inserting firebox into partially completed assembly (Figure 9).
F. Placing top on unit.
3. Refer to Figure 5, the leg pads will have the letter "A" and "B"
stamped into the metal. Place leg pad "A" and leg pad "B" at the
bottom of each casing side. Leg pad "A" attaches to the front of the
casing side, right and to the rear of the casing side, left. Leg pad "B"
attaches to the rear of the casing side, right and to the front of the
casing side, left. Position the 3/4" flange on the leg pad against the
(2) locator dimples on the casing side. The 3/4" flange must be facing
upward, toward the top louver openings on the casing side. Attach
the two rear leg pads to the casing sides with (2) 3/8" bolts. Attach
but do not completely tighten the two front leg pads to the casing
sides with (2) 3/8" bolts. Attention: The front leg pads can be
adjusted to provide a snug fit between the casing front and the casing
sides.
4. Attach (4) leveling bolts to the bottom of the (4) legs.
5. Align the 3/8" hole at the top of the leg with the 3/8" hole in the leg
pad. Attention: For proper positioning of the leg to the leg pad the
(2) 1-1/2" top edges of the leg must be placed flush and parallel to
the (2) edges on the leg pad. Attach leg to leg pad by inserting (1)
1" bolt through the leg pad and into the leg, secure bolt with 1/4"
nut.
6. Insert (2) 3/8" bolts into the (2) holes on the edges of the casing
sides. The bolts should only be threaded half-way into the holes in
order to allow for clearance when the casing back is attached to the
casing sides.
7. Refer to Figure 6, the rear cover has (4) keyholes for attachment to
the casing sides. Stand the casing sides on the floor with the (2)
bolts attached half-way into the edges of the rear cover positioned
at the rear. The large diameter holes in the keyholes of the rear cover
will be toward the floor. Working with one casing side at a time,
place the large diameter holes in the keyholes over and behind both
of the bolts at the same time. Push downward on the rear cover to
lock the keyholes into position behind the bolts. Finish tightening
both bolts to secure rear cover to casing side. Repeat this procedure
to secure rear cover to the second casing side.
8. Position the completed portion of the casing in the approximate
location for installation as the completed assembly will be heavy.
9. Refer to Figure 7, removing protective packing foam from casing
front and window. Remove the (1) 3/4" bolt and (1) 1/4" washer
from top of window. Remove (1) 3/8" bolt and 1 - 5/8" x 3/4"
retaining tab from bottom of window. Remove the window from
casing front. Remove the protective sheet of foam from the casing
front.
Place the window into the casing front. Attach the top of the
window to the casing front with (1) 1/4" washer and (1) 3/4" bolt.
Place the 1 -5/8" x 3/4" retaining tab into the locator notch on the
bottom of the casing front. Attach the bottom of the window to the
casing front by inserting (1) 3/8" bolt through retaining tab and into
locator notch.
Page 7R-3451
Figure 6
10. Attach the (4) 1-1/4" x 1/2" retaining tabs to the casing front with (4)
3/8" bolts. The retaining tabs should be positioned downward, from
the casing front, top to the casing front, bottom.
11. Refer to Figure 8, attach casing front to outer casing by using the
(4) retaining tabs on the casing front. The (2) top, retaining tabs on
the casing front will be placed behind the (2) top, locator tabs on the
front of the casing sides. The (2) bottom, retaining tabs will be
inserted into the (2) 9/16" slots on the front, leg pads. Place the top,
retaining tabs behind the top, locator tabs as you pivot inward the
bottom of the casing front in order to insert the bottom, retaining
tabs into the slots.
12. The following procedure will provide a snug fit between the casing
front and the casing sides. Grasp the right, front leg, push inward on
the leg in order to provide a snug fit between the casing front and the
casing side. Continue to hold the right, front leg as you completely
tighten the (2) 3/8" bolts that attach the leg pad to the right, casing
side. Repeat procedure for left, front leg to achieve a snug fit between
the casing front and the casing side.
13. Remove the casing front from the outer casing.
14. Refer to Figure 9, the appliance firebox can now be inserted into the
outer casing. Center the firebox in the outer casing. Attention:
Remove (1) Phillips-head screw in the top of the valve cover. The
screw is used to secure the valve cover in place during shipping.
The (1) Phillips-head screw can be discarded.
15. Attach casing front to outer casing as described in Step 11.
16. Place the casing top onto the outer casing. The casing top nests into
the outer casing.
17. Insert center grille, left grille and right grille into casing top.
18. Level appliance by adjusting leveling bolts.
19. Assembly of cast iron (outer casing) stove casting is completed.
Figure 5
Page 8 R-3451
Figure 8 Figure 9
Stone Inlay Replacement of Standard Grille Top
Whenever the standard grille top is replaced with a stone inlay you must
install the top shield and heat shield, which are provided with the stone
inlay.
Installation of Optional Stone Inlay
1. Remove left grille, center grille and right grille from casing top.
2. Remove casing top from outer casing.
Figure 7
Page 9R-3451
3. Place the casing top on a non-abrasive surface in order to protect the
porcelain finish. The exterior of the casing top should be facing the
non-abrasive surface.
4. Attach 11 5/8" x 11 5/8" top shield to the interior of the casing top
with (1) 3/8" bolt provided in hardware package.
5. Locate the (4) screw holes on the heat exchanger top. The screw
holes are 8 3/4" apart. Position the angled front edge on the 12" x 19
3/8" heat shield with the front of the appliance. Align the (4) tabs
with clearance holes on the 12" x 19 3/8" heat shield with the (4)
screw holes on the heat exchanger top. Attach the 12" x 19 3/8" heat
shield to the heat exchanger top with (4) 1/2" hex-head screws
provided in hardware package.
6. Place the casing top onto the outer casing. The casing top nests into
the outer casing.
7. Insert center stone inlay, left stone inlay and right stone inlay into
casing top.
8. Installation of stone inlay is completed.
Parts List
Part Part Quantity
Description Number Supplied
11 5/8" x 11 5/8" Top Shield CI-091 1
12" x 19 3/8" Heat Shield CI-092 1
3/8" Bolt R-3646 1
1/2" Hex-Head Screw R-2737 4
Installation of Wire Channel Assembly (Figure 10)
The ON/OFF/REMOTE switch with harness is factory installed into the
switch box.
After the appliance housing is installed into the cast iron outer casing the
wire channel can be installed.
1. Attach switch box on the left side of casing back with (2) 10 x 1/2"
provided screws.
2. Route wires from ON/OFF/REMOTE switch within wire channel.
3. Attach wire channel on the left side of the casing back with (4) 10
x 1/2" provided screws.
4. Attach the black and green (wires) female push-ons to the TH/TP
and TH (two outside male tabs) terminals on gas valve.
Figure 10
Gas Supply (Figure 11)
Check all local codes for requirements, especially for the size and type
of gas supply line required.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe Tubing, Type L
(Feet) Inside Diameter Outside Diameter
Nat. L.P. Nat. L.P.
0-10 1/2" 3/8" 1/2" 3/8"
1.3 cm 1.0 cm 1.3 cm 1.0 cm
10-40 1/2" 1/2" 5/8" 1/2"
1.3 cm 1.3 cm 1.6 cm 1.3 cm
40-100 1/2" 1/2" 3/4" 1/2"
1.3 cm 1.3 cm 1.9 cm 1.3 cm
100-150 3/4" 1/2" 7/8" 3/4"
1.9 cm 1.3 cm 2.2 cm 1.9 cm
Note: Never use plastic pipe. Check to confirm whether your local codes
allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is always
best to consult your local authority and installation code.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate, contact
your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant to the
action of liquefied petroleum gases. The gas lines must be checked for
leaks by the installer. This should be done with a soap solution watching
for bubbles on all exposed connections, and if unexposed, a pressure test
should be made.
Never use an exposed flame to check for leaks. Appliance must be
disconnected from piping at inlet of control valve and pipe capped or
plugged for pressure test. Never pressure test with appliance con-
nected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas line
upstream of the gas control to aid in servicing. It is required by the
National Fuel Gas Code that a drip line be installed near the gas inlet. This
should consist of a vertical length of pipe tee connected into the gas line
that is capped on the bottom in which condensation and foreign particles
may collect.
Figure 11
Method of Installing a Tee Fitting Sediment Trap
The use of the following gas connectors is recommended:
ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority having
jurisdiction.
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T.
plugged tapping, accessible for test gauge connection, must be
placed immediately upstream of the gas supply connection to the
appliance.
Page 10 R-3451
2. The appliance and its appliance main gas valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
3. The appliance must be isolated from the gas supply piping system by
closing its equipment shutoff valve during any pressure testing of the
gas supply piping system at test pressures equal to or less than 1/2
psig (3.5 kPa).
Attention! If one of the above procedures results in pressures in excess
of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result
in a hazardous condition.
Checking Manifold Pressure
Natural gas will have a manifold pressure of approximately 3.5" w.c.
(.871kPa) for maximum input or 1.7" w.c. (.423kPa) for minimum input
at the pressure regulator outlet with the inlet pressure to the pressure
regulator from a minimum of 5.0" w.c. (1.245kPa) for the purpose of
input adjustment to a maximum of 10.5" w.c. (2.614kPa). Propane gas
will have a manifold pressure approximately 10.0"w.c. (2.49kPa) for
maximum input or 6.3"w.c. (1.568kPa) for minimum input at the
pressure regulator outlet with the inlet pressure to the pressure regulator
from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input
adjustment to a maximum of 13.0"w.c. (3.237kPa).
NOTE: The gas control is equipped with a captured screw type pressure
test point, therefore it is not necessary to provide a 1/8" test point up
stream of the control.
A test gauge connection is located downstream of the gas appliance
pressure regulator for measuring gas pressure. The connection is a 1/8
inch 3mm) N.P.T. plugged tapping.
High Altitudes
For altitudes/elevations above 2,000 feet (610m), ratings should be
reduced at the rate of 4 percent for each 1,000 feet (305m) above sea
level. Contact the manufacturer or your gas company before changing
spud/orifice size.
Keep appliance area clear and free from combustible materials,
gasoline and other flammable vapors and liquids.
Pilot Flame Pattern (Figure 12 and Figure 13)
Figure 12 shows a correct pilot flame pattern. The correct flame will be
blue and will extend beyond the thermocouple and thermopile. The flame
will surround the thermocouple and thermopile just below the tip. A slight
yellow flame may occur where the pilot flame and main burner flame
meet. Figure 13 shows an incorrect pilot flame pattern. The incorrect
pilot flame is not touching the thermocouple or thermopile. This will
cause the thermocouple or thermopile to cool. When the thermocouple
cools, the heater will shut down.
Correct Pilot Flame Pattern
Figure 12
Incorrect Pilot Flame Pattern
Figure 13
If pilot flame pattern is incorrect, as shown in Figure 13
See Troubleshooting, page 15.
Cleaning and Maintenance/Pilot
Oxygen Depletion Sensor Pilot (Figure 14)
When the pilot has a large yellow tip flame, clean the Oxygen Depletion
Sensor as follows:
1. Clean the ODS pilot by loosening nut B from the pilot tubing. When
this procedure is required, grasp nut A with an open wrench.
2. Blow air pressure through the holes indicated by the arrows. This
will blow out foreign materials such as dust, lint and spider webs.
Tighten nut B also by grasping nut A.
Figure 14
Page 11R-3451
Main Burner Flame Pattern (Figure 15 and Figure 16)
Figure 15 shows a correct main burner flame pattern. Figure 16 shows
an incorrect main burner flame pattern.
Correct Main Burner Flame
Figure 15
Incorrect Main Burner Flame
Figure 16
If main burner flame pattern is incorrect, as shown in Figure 16
See Troubleshooting, page 15.
Cleaning and Maintenance / Main Burner
Warning: Turn off heater and let cool before cleaning
After use, cleaning of the main burner may be required for the proper
flame. The main burner may be cleaned by applying air pressure to the
ports on the main burner.
Cleaning the Log Set and Firebox
During the annual inspection and maintenance appointment, the service
person should clean dust, lint, and any light accumulation from the logs
and the firebox area. An extra-soft brush should be used on the logs as
they are extremely fragile; a vacuum cleaner may be used on the firebox.
If at any time the logs cannot be removed or installed without forcing,
the cause must be found. The logs must never be forced.
CAUTION: The ceramic logs are durable when handled and installed
properly. However, they are delicate and may be damaged easily if not
handled with care. Handling damage to the ceramic logs is not covered
by warranty.
DO NOT HANDLE LOGS WHILE THEY ARE HOT. ALLOW
PLENTY OF TIME FOR THE APPLIANCE TO COOL COM-
PLETELY BEFORE HANDLING.
OPERATING INSTRUCTIONS
CIVF-25 ON/OFF/REMOTE Switch
CIVF-25 is equipped with an ON/OFF/REMOTE switch which is
located on the wiring chase. A wire harness is attached to the ON/OFF/
REMOTE switch. The red, black and green (wires) female push-ons
attach to the ON/OFF/REMOTE switch. At the opposite end of the wire
harness, the black and green (wires) female push-ons attach to the gas
valve. An additional green wire and the red wire, which are stripped and
bare, will attach to the 750 millivolt wall thermostat accessory, or, to one
of the other accessories that can be purchased for use with your log set.
Operation of ON/OFF/REMOTE Switch with no Accessories
To ignite main burner, turn the control knob on the gas valve from the
PILOT position to the ON position. Turn the ON/OFF/REMOTE switch
from the OFF position to the ON position. The additional green wire and
red wire, which are stripped and bare are not used.
Operation of ON/OFF/REMOTE Switch with Accessories
750 Millivolt Wall Thermostat, GWSG-T
Connect the green and red, stripped and bare, wires on the ON/OFF/
REMOTE switch wire harness to the wall thermostat. Turn the ON/OFF/
REMOTE switch on the wiring chase to the REMOTE position. Set the
wall thermostat to the desired temperature.
It is important to use wire of a gauge proper for the length of the wire:
RECOMMENDED WIRE GAUGES
Maximum Wire
Length Gauge
1' to 10' 18
10' to 25' 16
25' to 35' 14
Wall Switch, FWS-1
Connect the green and red, stripped and bare, wires on the ON/OFF/
REMOTE switch wire harness to the wall switch. Turn the ON/OFF/
REMOTE switch on the wiring chase to the REMOTE position. Pivot
the rocker switch on the FWS-1 to the ON position.
Battery Operated Remote Control, FRBC-1 and FRBTC-1
Connect the green and red, stripped and bare, wires on the ON/OFF/
REMOTE switch wire harness to the remote receiver that is a component
in the FRBC-1 and FRBTC-1. Turn the ON/OFF/REMOTE switch on
the wiring chase to the REMOTE position. Follow instructions in the
FRBC-1 and FRBTC-1 to complete installation.
Note: If batteries fail in FRBC-1 or FRBTC-1, and immediate heat is
desired, turn the ON/OFF/REMOTE switch on wiring chase from the
REMOTE position to the ON position.
Electric (120 volt) Operated Remote Control, FREC-1
Connect the green and red, stripped and bare, wires on the ON/OFF/
REMOTE switch wire harness to the wires on remote receiver that is a
component in the FREC-1. Turn the ON/OFF/REMOTE switch on the
wiring chase to the REMOTE position. Follow instructions in the
FREC-1 to complete installation.
Note: If electric (120 volt) fails in FREC-1, and immediate heat is
desired, turn the ON/OFF/REMOTE switch on wiring chase from the
REMOTE position to the ON position.
Page 12 R-3451
Wiring of ON/OFF/REMOTE Switch with 750 Millivolt Wall
Thermostat Accessory and Another Accessory
Connect the green and red, stripped and bare, wires on the ON/OFF/
REMOTE switch wire harness to the 750 millivolt wall thermostat AND
to the remote receiver that is a component in the FRBC-1, FREC-1 OR
to the FWS-1, wall switch.
1. Connect (1) wire from the 750 millivolt wall thermostat and (1) wire
from appropriate accessory to the GREEN, stripped and bare wire
from the ON/OFF/REMOTE wire harness.
2. Connect (1) wire from the 750 millivolt wall thermostat and (1) wire
from appropriate accessory to the RED, stripped and bare wire from
the ON/OFF/REMOTE wire harness.
Note: When the appliance is in the MANUAL mode and the batteries
fail in the FRBC-1 or if the electric (120 volt) fails in the FREC-1, and
immediate heat is desired, turn the ON/OFF/REMOTE switch on
wiring chase from the REMOTE position to the ON position.
Manual Operation
1. Turn ON/OFF/REMOTE switch on wiring chase to REMOTE
position.
2. Turn wall thermostat OFF.
3. Turn accessory, FRBC-1, FREC-1 or FWS-1, ON. Appliance is now
in the manual mode. You must turn the appliance ON or OFF with
appropriate accessory.
Wall Thermostat Operation
1. Turn the ON/OFF/REMOTE switch on wiring chase to REMOTE
position.
2. Turn accessory, FRBC-1, FREC-1 or FWS-1, OFF.
3. Turn wall thermostat ON and set appropriate temperature. Wall
thermostat will cycle the appliance ON and OFF.
Installation of Remote Receiver
(Figure 17)
1. Attach, from left to right, the slide-on cover plate onto the remote
receiver. ON will be to the top and OFF will be to the bottom on the
slide-on cover plate.
2. Push the receiver slide button onto the receiver slide switch. Reverse
installation of the slide button if it is off center.
3. Attach velcro loop on the left side of the valve cover support.
4. Attach velcro hook onto remote receiver. The word TOP on the
remote receiver should be to the top when installed onto valve cover
support.
5. Attach velcro hook on remote receiver onto velcro loop on valve
cover support..
Figure 17
Wiring Diagram (Figure 18)
.
Figure 18
PLEASE NOTE
It is normal for appliances fabricated of steel to give off some
expansion and/or contraction noised during the start up or cool
down cycle. Similar noises are found with your furnace heat
exchanger or car engine.
Installation of Logs (Figure 19)
1. Remove screen front from inner body by removing (4) 1/2" hex-head
screws.
2. Remove logs from interior of inner body. Remove all protective
packaging from logs and interior of inner body.
3. Align the two rear pins on the base with the two alignment holes on
the underside of the rear log. Place the rear log onto the two rear pins
on the base.
4. Align the two front pins on the base with the two alignment holes on
the underside of the front log. Place the front log onto the two front
pins on the base.
5. Align the two pins on the front log with the two alignment holes on
the underside of the top log. Place the top log onto the two pins on
the front log.
6. Replace and attach screen front onto inner body with (4) 1/2" hex-
head screws from Step 1.
7. Installation of logs is completed.
Refer to Figure 19 for the following warning.
Warning: Failure to position the parts in accordance with this
diagram or failure to use only parts specifically approved with this
appliance may result in property damage or personal injury.
Page 13R-3451
Figure 19
Operating Guidelines
Before operating this heater, please review the safety warnings pages at
the beginning of this manual and those precautions and warnings listed
below.
1. Know what type of ignition system this model has (standing pilot)
and follow the applicable SAFETY and LIGHTING instructions.
2. Check to ensure there are no gas leaks. If you are unsure, turn gas off
to the heater and call a service person or your gas utility.
CAUTION: Clothing or other flammable material should not be
placed on or near the appliance.
WARNING: Children and adults should be alerted to the hazard
of high surface temperature and should stay away to avoid burns
or clothing ignition. Young children should be carefully
supervised when they are in the same room as the appliance.
3. Tampering is DANGEROUS and voids all warranties. Any
component that is found to be faulty, must be replaced with an
approved component.
Initial Lighting (Figure 20)
Upon completing the gas line or turning the gas valve "ON" after it has
been in the "OFF" position, a small amount of air will be in the lines.
When first lighting the appliance, it will take a few minutes for the lines
to purge themselves of this air. Once the purging is complete, the
appliance will light and operate satisfactorily.
Subsequent lightings of the appliance will not require such purging if the
gas valve is not turned to "OFF."
Standing Pilot Operation
1. Follow the SAFETY and LIGHTING INSTRUCTIONS for standing
pilot controls found in this manual and on labels found attached to
the appliance.
CAUTION: During the initial purging and subsequent lightings,
never allow the gas valve control knob to remain depressed in the
"pilot" position without pushing the piezo ignitor button at least
once every second.
2. During the heating season, leave the control valve knob in the "ON"
position. This will allow the pilot flame to remain lit. Turn the burner
flame on or off with the appliance ON/OFF rocker switch, wall
switch, remote control kits or 750 millivolt wall thermostat.
NOTE: The gas control valve allows you to increase or decrease the
height of the main burner flame. The control valve has a pressure
regulator with a knob as shown in Figure 20. Rotate the knob clockwise
to "HI" to increase the flame height and counterclockwise to "LO" to
decrease the flame height.
3. When the heating season is over, turn the on/off switch to "OFF" and
the control valve to "OFF". The system, including the pilot light, will
be shut down.
Figure 20
Maximum and Minimum Input
The gas valve on the appliance allows the input to adjust between a
maximum input of 25,000 Btuh for Natural gas and Propane gas to a
minimum input of 17,000 Btuh for Natural and 18,000 Btuh for Propane.
Please be advised, the maximum input provides the greatest amount of
yellow flame and ember glow on the log set. The minimum input
substantially decreases the yellow flame and ember glow on the log set.
Maintenance & Service Instructions
IMPORTANT: Turn off gas before servicing appliance. It is
recommended that a competent service technician perform these check-
ups at the beginning of each heating season.
Clean Burner and Control Compartment
Keep the control compartment, logs, and burner areas surrounding the
logs clean by vacuuming or brushing at least twice a year.
Cleaning Procedure (Figure 21)
1. Turn off pilot light at gas valve.
2. Remove screen front. (4 hex-head screws)
3. Vacuum burner compartment especially around orifice/primary
air openings.
4. Replace screen front. (4 hex-head screws)
5. Ignite pilot. (See Lighting/Operating Section of Manual)
6. Operate the main burner and visually check to make sure the flame
pattern appears similar to the pictorial illustration shown for
proper main burner flame pattern, Figure 15. If it appears abnormal
call a service person.
Verify proper operation after servicing.
Figure 21
Page 14 R-3451
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by
hand. When lighting the pilot, follow these instructions
exactly.
B. BEFORE LIGHTING smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a neigh-
bor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it; call a qualified
service technician. Force or attempted repair may
result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service techni-
cian to inspect the appliance and to replace any part
of the control system and any gas control which has
been under water.
1. Set the thermostat to lowest setting.
2. Turn off all electric power to appliance if service is to be
performed (if applicable).
3. Lower valve cover.
4. Push in gas control knob slightly and turn clock-
wise to "OFF". Do not force.
5. Raise valve cover.
TO TURN OFF GAS TO APPLIANCE
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance (if appli-
cable).
4. Lower valve cover.
5. Push in gas control knob slightly and turn clockwise
to "OFF".
6. Wait ten (10) minutes to clear out any gas. Then smell
for gas, including near the floor. If you smell gas, STOP!
Follow "B" in the safety information above. If you don't
smell gas, go to the next step.
7. Find pilot - The pilot is attached to the main burner
behind the front log.
8. Turn knob on gas control counterclockwise
to "PILOT."
9. Push in gas control knob all the way and hold in.
Repeatedly push the piezo ignitor button until
pilot is lit. Continue to hold the control knob in for
about one (1) minute after the pilot is lit. Release
knob and it will pop back up. Pilot should remain
lit. If it goes out, repeat steps 5 through 9.
If knob does not pop up when released, stop and
immediately call your service technician or gas
supplier.
If the pilot will not stay lit after several tries, turn
the gas control knob to "OFF" and call your
service technician or gas supplier.
10. Attention! Gas control has an INTERLOCK latching
device. When the pilot is initially lit and the safety
magnet is energized (pilot stays "ON") the INTER-
LOCK latching device becomes operative. If the gas
control is turned to the "OFF" position or gas flow to
the appliance is shut off, the pilot cannot be relighted
until the safety magnet is de-energized (approxi-
mately 60 seconds). There will be an audible "click"
when the safety magnet in the gas control is de-
energized. Pilot can now be relighted. Repeat steps 5
through 9.
11. Turn gas control knob counterclockwise to
"ON".
12. Raise valve cover.
13. Turn on all electric power to the appliance (if appli-
cable).
14. Set thermostat to desired setting.
Page 15R-3451
TROUBLE-SHOOTING
SYMPTOMS - POSSIBLE CAUSES AND CORRECTIONS
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and
glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors.
1. When ignitor button is pressed, there is no spark at ODS/
pilot.
a. Ignitor electrode positioned wrong - Replace ignitor.
b. Ignitor electrode broken - Replace ignitor.
c. Ignitor electrode not connected to ignitor cable - Reconnect
ignitor cable.
d. Ignitor cable pinched or wet - Free ignitor cable if pinched by
any metal or tubing. Keep ignitor cable dry.
e. Broken ignitor cable - Replace ignitor cable.
f. Bad piezo ignitor - Replace piezo ignitor.
2. When ignitor button is pressed, there is spark at ODS/pilot,
but no ignition.
a. Gas supply turned off or manual shutoff valve closed - Turn
on gas supply or open manual shutoff valve.
b. Control knob not in PILOT position - Turn gas control knob
to PILOT position.
c. Control knob not pressed in while in PILOT position - Press
in control knob while in PILOT position.
d. Air in gas lines when installed - Continue holding down
control knob. Repeat igniting operation until air is removed.
e. Depleted gas supply - Contact local gas company.
f. ODS/pilot is clogged - Clean ODS/pilot or replace ODS/pilot
assembly.
g. Gas regulator setting is not correct - Replace gas regulator.
3. ODS/pilot lights but flame goes out when control knob is
released.
a. Control knob not fully pressed in - Press in control knob
fully.
b. Control knob not pressed in long enough - After ODS/pilot
lights, keep control knob pressed in 30 seconds.
c. Safety interlock system has been triggered (thermostat models
only) - Wait one minute for safety interlock system to reset.
Repeat ignition operation.
d. Manual Shutoff valve not fully open - Fully open manual
shutoff valve.
e. Thermocouple connection loose at control valve - Hand
tighten until snug, then tighten 1/4 turn more.
f. Pilot flame not touching thermocouple, which allows
thermocouple to cool, causing pilot flame to go out. This
problem could be caused by either 1) low gas pressure -
Contact local gas company or 2) dirty or partially clogged
ODS/pilot - Clean ODS/pilot or replace ODS/pilot assembly.
g. Thermocouple damaged - Replace thermocouple.
h. Control valve damaged - Replace control valve.
4. Main burner does not light after ODS/pilot is lit.
a. Main burner orifice clogged - Clean main burner or replace
main burner orifice.
b. Main burner orifice diameter is too small - Replace main
burner orifice.
c. Inlet gas pressure is too low - Contact local gas company.
5. Pilot burning, no gas to burner, valve knob "ON", on/off
switch "ON."
a. "On/Off" switch, wall switch, remote control or wires
defective - Check "on/off" switch and wires for proper
connections. Place jumper wires across terminal at switch -
if burner comes on, replace defective switch. If OK, place
jumper wires across switch wires at gas valve-if burner
comes on, wires are faulty or connections are bad.
b. Thermopile may not be generating sufficient millivolts - If
the pilot flame is not close enough physically to the thermopile,
clean the ODS/pilot.
- Be sure the wire connections from the thermopile at the gas
valve terminals are tight and the thermopile is fully inserted
into the pilot bracket.
- Check the thermopile with a millivolt meter. Take the
reading at TH-TP & TP terminals of the gas valve. The meter
should read 350 millivolts minimum, while holding the valve
knob depressed in the PILOT position, with the pilot lit, and
the ON/OFF switch in the OFF position. Replace the faulty
thermopile if the reading is below the specified minimum.
- With the pilot in the ON position, disconnect the thermopile
leads from the valve. Take a reading at the thermopile leads.
The reading should be 350 millivolts minimum. Replace the
thermopile if the reading is below the minimum.
c. Defective valve - Turn valve knob to "ON." Place ON/OFF
switch to "ON." Check with millivolt meter at thermopile
terminals. Millivolt meter should read greater than 200
millivolts. If the reading is okay and the main burner does not
ignite, replace the gas valve
d. Plugged main burner orifice - Check main burner orifice for
blockage and remove.
6. Delayed ignition of main burner.
a. Manifold pressure is too low - Contact local gas company.
b. Main burner orifice clogged - Clean main burner and main
burner orifice.
7. Main burner backfiring during combustion.
a. Main burner orifice is clogged or damaged - Clean main
burner and main burner orifice or replace main burner orifice.
b. Damaged main burner - Replace damaged main burner.
c. Gas regulator defective - Replace gas regulator.
8. Yellow flame in front section of main burner during main
burner combustion.
a. Not enough air - Check main burner for dirt and debris. If
found, clean main burner.
b. Gas regulator defective - replace gas regulator.
9. Slight smoke or odor during initial operation.
a. Residues from manufacturing processes and logs curing -
Problem will stop after a few hours of operation.
10. Heater produces a whistling noise when main burner is lit.
a. Turning control knob to HI position when main burner is cold
- Turn control knob to LO position and let warm up for a
minute.
b. Air in gas line - Operate main burner until air is removed from
line. Have gas line checked by local gas company.
c. Air passageways on heater blocked - Observe minimum
installation clearances (see page 4).
d. Dirty or partially clogged main burner orifice - Clean main
burner and main burner orifice or replace main burner orifice.
11. Heater produces a clicking/ticking noise just after main
burner is lit or shut off.
a. Metal expanding while heating or contracting while cooling
- This is common with most heaters. If noise is excessive,
contact service person.
12. Heater produces unwanted odor.
a. Heater burning vapors from paint, hair spray, glues, cleaners,
chemicals, new carpet, etc. - Open window to ventilate room.
Stop using odor causing products while heater is operating.
b. Low fuel supply - Refill supply tank.
c. Gas leak - Locate and correct all leaks.
13. Heater shuts off in use (ODS operates).
a. Not enough fresh air is available - Open window and/or door
for ventilation.
b. Low line pressure - Contact local gas company.
c. ODS/pilot is partially clogged - Clean ODS/pilot.
14. Gas odor even when control knob is in OFF position.
a. Gas leak - Locate and correct all leaks.
b. Control valve defective - Replace control valve.
15. Gas odor during combustion.
a. Foreign matter between logs and main burner - remove
foreign matter.
b. Gas leak - Locate and correct all leaks.
Page 16 R-3451
Empire Comfort Systems, Inc. Nine Eighteen Freeburg Ave. Belleville, Illinois 62222-0529
How To Order Repair Parts...
Parts can be ordered only through your service person or dealer. For best results, the service person or dealer should order parts through
the distributor. Parts can be shipped directly to the service person/dealer.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your
equipment. Then determine the Part Number (not the Index Number) and the Description of each part from the following appropriate
illustration and list. Be sure to give all this information . . .
Heater Model Number Part Description
Heater Serial Number Kind of Gas (Propane or Natural)
Part Number
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipments contingent upon strikes, fires and all causes beyond our control.
Page 17R-3451
Index Part
No. Number Description Index Part
No. Number Description
PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.
Parts List for CIVF-25 Firebox
1 *CI-006 WINDOW RETAINING TAB
2 R-3948 WINDOW (BLACK PAINT)
2 R-3688 WINDOW (BLACK ENAMEL)
2 R-3696 WINDOW (SAND ENAMEL)
2 R-3704 WINDOW (GREEN ENAMEL)
2 R-3712 WINDOW (RED ENAMEL)
2 R-3720 WINDOW (NAVY ENAMEL)
3 R-3949 GRILL - LEFT (BLACK PAINT)
3 R-3726 GRILL - LEFT (BLACK ENAMEL)
3 R-3729 GRILL - LEFT (SAND ENAMEL)
3 R-3732 GRILL - LEFT (GREEN ENAMEL)
3 R-3735 GRILL - LEFT (RED ENAMEL)
3 R-3738 GRILL - LEFT (NAVY ENAMEL)
4 R-3950 GRILL - CENTER (BLACK PAINT)
4 R-3727 GRILL - CENTER (BLACK ENAMEL)
4 R-3730 GRILL - CENTER (SAND ENAMEL)
4 R-3733 GRILL - CENTER (GREEN ENAMEL)
4 R-3736 GRILL - CENTER (RED ENAMEL)
4 R-3739 GRILL - CENTER (NAVY ENAMEL)
5 R-3951 GRILL - RIGHT (BLACK PAINT)
5 R-3728 GRILL - RIGHT (BLACK ENAMEL)
5 R-3731 GRILL - RIGHT (SAND ENAMEL)
5 R-3734 GRILL - RIGHT (GREEN ENAMEL)
5 R-3737 GRILL - RIGHT (RED ENAMEL
5 R-3740 GRILL - RIGHT (NAVY ENAMEL)
6 R-3944 TOP (BLACK PAINT)
6 R-3683 TOP (BLACK ENAMEL)
6 R-3691 TOP (SAND ENAMEL)
6 R-3699 TOP (GREEN ENAMEL)
6 R-3707 TOP (RED ENAMEL)
6 R-3715 TOP (NAVY ENAMEL)
7 * CI-007 RETAINING TAB - 4 REQUIRED
8 R-3946 SIDE - RIGHT (BLACK PAINT)
8 R-3685 SIDE - RIGHT (BLACK ENAMEL)
8 R-3693 SIDE - RIGHT (SAND ENAMEL)
8 R-3701 SIDE - RIGHT (GREEN ENAMEL)
8 R-3709 SIDE - RIGHT (RED ENAMEL)
8 R-3717 SIDE - RIGHT (NAVY ENAMEL)
9 R-3947 FRONT (BLACK PAINT)
9 R-3687 FRONT (BLACK ENAMEL)
9 R-3695 FRONT (SAND ENAMEL)
9 R-3703 FRONT (GREEN ENAMEL)
9 R-3711 FRONT (RED ENAMEL)
9 R-3719 FRONT (NAVY ENAMEL)
10 * CI-009 LEG PAD “B” - 2 REQUIRED
11 * CI-008 LEG PAD “A” - 2 REQUIRED
12 * R-3747 LEVELING BOLT - 4 REQUIRED
13 R-3952 LEG - 4 REQUIRED (BLACK PAINT)
13 R-3742 LEG - 4 REQUIRED (BLACK ENAMEL)
13 R-3743 LEG - 4 REQUIRED (SAND ENAMEL)
13 R-3744 LEG - 4 REQUIRED (GREEN ENAMEL)
13 R-3745 LEG - 4 REQUIRED (RED ENAMEL)
13 R-3746 LEG - 4 REQUIRED (NAVY ENAMEL)
14 R-3945 SIDE - LEFT (BLACK PAINT)
14 R-3684 SIDE - LEFT (BLACK ENAMEL)
14 R-3692 SIDE - LEFT (SAND ENAMEL)
14 R-3700 SIDE - LEFT (GREEN ENAMEL)
14 R-3708 SIDE - LEFT (RED ENAMEL)
14 R-3716 SIDE - LEFT (NAVY ENAMEL)
*PART IS NOT SUPPLIED WITH CASTING, IT IS INCLUDED IN THE FIREBOX
HARDWARE PACKAGE
USE ONLY MANUFACTURER'S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
Index Part
No. Number Description
Index Part
No. Number Description
1 R-3436 REMOTE/OFF/ON SWITCH
2 CI-326 SWITCH BOX
3 CI-328 WIRE CHANNEL
4 CI-335 REAR COVER
5 CI-188 OUTLET BAFFLE
6 CI-287 INNER TOP
7 CI-391 REFLECTOR
8 CI-280 INNER BODY
9 CI-380 SCREEN FRAME ASSEMBLY
10 R-2708 PIEZO IGNITOR
11 CI-068 VALVE COVER ASSEMBLY
12 CI-253 MAGNET ASSEMBLY (2 REQUIRED)
13 * CI-008 LEG PAD-A (2 REQ’D)
14 * CI-009 LEG PAD-B (2 REQ’D)
15 CI-288 INNER BOTTOM FACE
16 CI-181 INNER BOTTOM ASSEMBLY
17 R-3625 GAS VALVE - LPG
17 R-3626 GAS VALVE - NAT
18 P-86-54L ORIFICE-LPG
18 P-86-40N ORIFICE-NAT
19 CI-176 MANIFOLD ASSEMBLY
Parts List for Stove Casting
20 CI-023 BURNER BRACKET - RIGHT
21 CI-258 AIR SHUTTER BODY - NAT
21 CI-259 AIR SHUTTER BODY - LPG
22 R-5278 BURNER
23 R-3623 PILOT ASSEMBLY-LPG
23 R-3624 PILOT ASSEMBLY-NAT
24 CI-180 PILOT TUBING
25 CI-166 BURNER BRACKET - LEFT
26 CI-347 LOG SUPPORT ASSEMBLY
27 CI-351 LOG SUPPORT BAFFLE
28 R-3642 FRONT LOG
29 R-3644 TOP LOG
30 R-3643 REAR LOG
NOT SHOWN CI-348 SWITCH BOX INSULATION
NOT SHOWN R-2789 ELECTRODE WIRE
NOT SHOWN * R-3747 LEVELING BOLT (4 REQUIRED)
NOT SHOWN * CI-007 RETAINING TAB (4 REQUIRED)
NOT SHOWN R-3765-A WIRE ASSEMBLY
NOT SHOWN M-166 MANIFOLD ORIFICE GASKET
* PART IS INCLUDED IN THE HARDWARE PACKAGE AND IS USED IN THE
ASSEMBLY OF THE STOVE CASTING
Page 18 R-3451
Page 19R-3451
OPTIONAL BLOWER CIB-2
Unvented Room Heater CIVF-25
Installing Optional CIB-2 Blower
1. Loosen, but do not remove, (4) hex-head screws located on the
exterior, bottom of the appliance.
2. Position the blower assembly at the rear of the appliance. The
blower assembly has (4) keyholes for attachment to the exterior,
bottom of the appliance.
3. Place the large diameter holes in the keyholes over and behind the
(4) hex-head screws that were loosened in Step 1. Push inward on
the blower assembly to lock the keyholes into position behind the
screws. Tighten (4) hex-head screws to secure blower assembly to
exterior, bottom of the appliance.
4. Remove wire channel from rear cover by removing (4) hex-head
screws. Note: If optional blower is being installed during initial
installation of appliance, the wire channel will not be attached to
casing back. (Refer to Installation of Wire Channel Assembly,
Page 9)
5. Remove casing top and casing front from outer casing.
6. If optional stone inlay is installed in casing top, remove the 12" x
19 3/8" heat shield from the heat exchanger top by removing (4)
1/2" hex-head screws.
7. When facing the rear of the appliance, insert fan control shield
between rear cover and inner body of appliance on the left side of
the rear cover.
8. Attach fan control shield to top of inner body with (2) #10 x 1/2"
screw provided in hardware package.
9. If applicable, attach 12" x 19 3/8" heat shield to heat exchanger top
with (4) 1/2" hex-head screws from Step 6.
10. Place the casing top onto the outer casing. The casing top nests
into the outer casing.
11. Attach fan control to FLAT, fan control bracket (Part 9A, Page 20)
with (2) 6 x 1/4" screws provided in hardware package.
12. Attach fan control with bracket onto the wire channel by using (2)
8 x 1/4" screws provided in hardware package.
13. Route wires from fan control and ON/OFF/REMOTE switch
within wire channel.
14. When facing the rear of the appliance, align and insert fan control
with bracket into 1 3/8" x 2" opening on the left side of the rear
cover.
15. Attach wire channel to rear cover by using (4) hex-head screws
removed in Step 4. (Refer to Installation of Wire Channel
Assembly, Page 9)
16. Insert AUTO/OFF/ON switch into rectangular notch on valve
bracket. Be sure to insert AUTO/OFF/ON switch with letters
(words) upright. (See wiring diagram)
17. Attach 1/4" push-on terminal from blue wire on the fan control
to the AUTO (top) tab on the switch.
18. Attach 1/4" push-on terminal from black wire to the OFF
(middle) tab on the switch.
19. Attach 1/4" push-on terminal from white wire on the fan
control to the ON (bottom) tab on the switch.
20. Installation of optional CIB-2 blower is completed.
Fan Control
The fan control is a non-adjustable automatic type. The fan control
will require between 5 and 10 minutes of main burner operation
before the fan control "closes" and activates the blower. The blower
will continue to run between 5 and 10 minutes after the main burner
shuts off, before the fan control "opens" and deactivates the blower.
Wiring
The appliance, when installed, must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the National
Electrical Code ANSI/NFPA No. 70, if an external electrical source is
utilized. This appliance is equipped with a three-prong [grounding]
plug for your protection against shock hazard and should be
plugged directly into a properly grounded three-prong receptacle.
Do not cut or remove the grounding prong from this plug. For an
ungrounded receptacle, an adapter, which has two prongs and a wire
for grounding, can be purchased, plugged into the ungrounded
receptacle and its wire connected to the receptacle mounting screws.
With this wire completing the ground, the appliance cord plug can
be plugged into the adapter and be electrically grounded.
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
WARNING:
Unplugging of blower accessory will not stop the heater from
cycling. To shut heater off: Turn temperature dial or
thermostat to lowest setting. Turn knob on gas control to
"OFF", depressing slightly. Do not force.
Page 20 R-3451
Cleaning
The blower wheel will collect lint and could require cleaning once
a year. If the air output decreases or the noise level increases, it
indicates a dirty wheel.
Blower Motor
The blower motor does not have oiling holes. Do not attempt to oil
blower motor.
PARTS LIST
Index Part
No. No. Description
1 R-1454 Brass Bushing (4 Required)
2 R-1499 Rubber Grommet (4 Required)
3 CI-002 Blower Housing
4 R-1517 Tinnerman Clip (4 Required)
5 R-2804-A Blower Assembly
6 CI-003 Blower Housing Cover
7 R-2099 Cord Set
8 R-3767-A Wire Harness
9A CI-004 Fan Control Bracket
(Use with CIBV-30, CIVF-25,
CIVF-25C Only)
9B CI-325 Fan Control Bracket
(Use with CIDV-30 Only)
10 R-2503 Fan Control
11 R-2805 Auto/Off/On Switch
12 CI-220 Fan Control Shield
(Use with CIVF-25-1 only)
13 R-1410 Bushing 7/8" Dia.