Energy Tech Laboratories Edp70 Users Manual REV1
EDP70 to the manual b51f7367-dfbe-424c-a46b-eb4984959c7a
2015-02-06
: Energy-Tech-Laboratories Energy-Tech-Laboratories-Edp70-Users-Manual-540520 energy-tech-laboratories-edp70-users-manual-540520 energy-tech-laboratories pdf
Open the PDF directly: View PDF .
Page Count: 65
Download | |
Open PDF In Browser | View PDF |
EDP70 PLUS UNINTERRUPTIBLE POWER SYSTEM 24/36/50/80kVA – 3 phase input / 3 phase output USER HANDBOOK PART NUMBER 10H52152PU9C rev.1 IMPORTANT SAFETY INSTRUCTIONS READ BEFORE INSTALLING 1) SAVE THESE INSTRUCTIONS 2) 3) This manual contains important instructions for the EDP70 PLUS which should be followed during installation and maintenance of the UPS and associated batteries. The installation must be inspected by trained technicians. The instructions must be followed. When external batteries are provided by the Customer and not Chloride, reference must be made to the installation instructions provided by the battery supplier. WARNINGS 1) The AC and DC supplies to the EDP70 PLUS UPS and the AC output from the UPS MUST be fed through suitably rated circuit breakers or fuses and isolating switches suitable for branch circuit operation. 2) Any external battery cabinet connected to the UPS MUST be provided with an over-current protection device per UL1778 Par. No. 10.4 3) To reduce the risk of fire or electric shock, the equipment must be installed indoors, in a humidity and temperature controlled environment which is free from conductive contaminants. SAFETY 1) DO NOT REMOVE COVERS DURING NORMAL OPERATION. The panels will be removed during installation, however this should only be undertaken by qualified technicians. It should be ensured that the UPS is switched off and that all power sources are disconnected (A.C. mains and Battery) before either the rear or side panels are removed. 2) FOREIGN OBJECTS MUST NOT BE INTRODUCED INTO THE VENTILLATION GRILLES. HAZARDOUS VOLTAGES are present within the EDP70 PLUS even when it is switched off. 3) Fuses must ONLY be replaced with the same type and rating. 4) The EDP70 PLUS contains a battery which can be DANGEROUS if interfered with. Contact the supplier for replacement. 5) The UPS and/or its components must be disposed of as notifiable waste in accordance with local pollution control (special waste) regulations. page 2 -- MI00/10056 rev.1--05/2001 WARNING The UPS contains hazardous voltages, even when all switches are open. In case of fire in the installation area, do not use water to extinguish fire. ELECTRICAL PRECAUTIONS: If the UPS is in By-pass mode and the Output switch is closed, no indications will be displayed; fans will however function, and hazardous voltages are present downline from the static switches. EMERGENCY PROCEDURE In the case of an emergency, the load supply can be interrupted by switching off all the switches fitted in the UPS. ELECTRIC SHOCK Switch off power; use dry insulating material for protection when pulling the injured person clear of conductors. NEVER TOUCH THE INJURED PERSON WITH BARE HANDS UNTIL CLEAR OF CONDUCTORS. SEEK QUALIFIED ASSISTANCE IMMEDIATELY. INJURIES CAUSED BY CONTACT WITH CORROSIVE LIQUIDS In normal conditions, installed batteries are sealed. A damaged battery container may however leak electrolyte, or cause the latter to come into contact with battery parts. In the event of electrolyte contact with the eyes, rinse eyes thoroughly with a saline solution or fresh water for at least 10 minutes. In the event of electrolyte contact with skin, rinse the affected area with abundant water. Remove contaminated clothing. Cover affected area with dry gauze. If electrolyte is swallowed, do not induce vomiting. Administer large quantities of milk or water. IN ALL CASES, SEEK MEDICAL ATTENTION IMMEDIATELY MI00/10056 rev.1--05/2001-- page 3 Contents 1.0 INTRODUCTION................................................................................................................6 1.1 Summary of the manual ................................................................................................6 1.2 Summary of the equipment ..........................................................................................6 1.3 Block diagram................................................................................................................6 1.4 Functions .......................................................................................................................8 1.5 Operational modes ........................................................................................................9 2.0 SAFETY ...........................................................................................................................11 2.1 General safety..............................................................................................................11 2.2 Symbols .......................................................................................................................11 2.3 Electrical precautions .................................................................................................12 2.4 Battery precautions.....................................................................................................12 2.5 Battery safety equipment............................................................................................12 3.0 STORAGE .......................................................................................................................13 4.0 INSTALLATION ...............................................................................................................13 4.1 Mechanical characteristics .........................................................................................13 4.2 Installation ...................................................................................................................21 Recommended wire sizes....................................................................................................22 4.4 Ventilation ....................................................................................................................24 5.0 CONNECTION .................................................................................................................25 5.1 Electrical connections.................................................................................................28 5.2 24 – 12/18/24kVA..........................................................................................................29 5.3 36 – 24/30/36kVA..........................................................................................................32 5.3 EDP70 PLUS 50/80kVA................................................................................................35 5.4 Signal connections......................................................................................................38 6.0 CONTROLS .....................................................................................................................39 6.1 User Controls...............................................................................................................39 6.2 Control Panel ...............................................................................................................40 7.0 START UP .......................................................................................................................41 page 4 -- MI00/10056 rev.1--05/2001 Figures Figure 1 – Block diagrams – 24/36kVA ....................................................................................7 Figure 2 – Block diagram – 50/80kVA ......................................................................................8 Figure 3 – Normal operation.....................................................................................................9 Figure 4 – Utility Supply failure ................................................................................................9 Figure 5 – Re-establishing the Utility Supply ........................................................................10 Figure 6 – Transferring the Load onto the Reserve Supply .................................................10 Figure 7 – 24 Footprint and cabinet dimensions ..................................................................14 Figure 8 – 36 Footprint and cabinet dimensions ..................................................................15 Figure 9 – 50/80 Footprint and cabinet dimensions .............................................................16 Figure 10 – “A” Battery Cabinet Drawing for 24/36kVA Ratings..........................................17 Figure 11 – “B” Battery Cabinet Drawing for 24/36kVA Ratings..........................................18 Figure 12 – “E” Battery Cabinet Drawing for 50/80kVA Ratings..........................................19 Figure 13 – “F” Battery Cabinet Drawing for 50/80kVA Ratings ..........................................20 Figure 14 – UPS Ratings .........................................................................................................21 Figure 15 – Connection diagrams ..........................................................................................25 Figure 16 - 24 – 12/18/24kVA: Switches and Breakers .........................................................29 Figure 17 - 24 – 12/18/24kVA: Switches .................................................................................30 Figure 18 - 24 – 12/18/24kVA: Cable Connections ................................................................31 Figure 19 - 36 – 24/30/36kVA: Switches and Breakers .........................................................32 Figure 20 - 36 – 24/30/36kVA: Connections...........................................................................33 Figure 21 - 36 – 24/30/36kVA: Cable Connections ................................................................34 Figure 22 – 50/80kVA: Switches and Breakers .....................................................................35 Figure 23 – 50/80kVA: Connections.......................................................................................36 Figure 24 – 50/80kVA: Cable Connections ............................................................................37 Figure 25 – Control panel .......................................................................................................39 MI00/10056 rev.1--05/2001-- page 5 1.0 INTRODUCTION 1.1 Summary of the manual This handbook provides for the safe installation, startup and use of the EDP70 PLUS Uninterruptible Power System (UPS). The Company recommends that the equipment be installed and regularly maintained by a Chloride Authorized personnel. DO: - DO NOT: 1.2 read the User Handbook before operating the EDP70 PLUS UPS. keep a log of all incidents. protect the batteries from damage. Batteries leak acid; avoid contact with skin, clothes or eyes. - operate the control switches. - operate the EDP70 PLUS UPS with any covers removed. - obstruct the ventilation grilles. Summary of the equipment The EDP70 PLUS Uninterruptible Power System (UPS) totally isolates the load from voltage drops, spikes, transients frequency variations in the utility supply. In the event of failure or brownout of the AC utility supply, an internal audible alarm sounds and an LED on the control panel illuminates, the EDP70 PLUS UPS will continue to provide safe, clean continuous power, without interruption, from the battery, for a duration dependent on battery capacity and output load. The audible alarm alerts the user to start a safe orderly shutdown of the load. When the AC utility supply returns to normal, the EDP70 PLUS UPS automatically recharges the battery ready for any future power failure. The microprocessor display panel provides access to very detailed information regarding the status of the supplies and EDP70 PLUS UPS. Refer to current publication for detailed specification. The block diagram, shows the main functional sub-assemblies of the EDP70 PLUS UPS. The AC three phase utility supply is rectified to provide direct current, which maintains the battery in a fully charged state and also supplies the inverter, which provides the three phase output via an electronic static switch. Normally the supply of the reserve line is taken from the AC utility input, but special units, with a separate reserve input supply, are available. This allows the inputs to be supplied from independent three phase sources. Provided the reserve supply is within limits, the inverter will match the output frequency with the reserve supply frequency. The inverter has its own internal crystal control to stabilize the output frequency if the reserve supply frequency is out of limits. The electronic static switch switches the output from the inverter to the reserve supply, without interruption, to meet any load current surges, or to supply the load if the battery is discharged during an AC utility supply failure. Maintenance and testing can be carried out on the EDP70 PLUS UPS without interrupting the output, by switching the load from the reserve supply to the maintenance bypass circuit. This work should only be carried out by Chloride-trained personnel. 1.3 Block diagram page 6 -- MI00/10056 rev.1--05/2001 24kVA - STANDARD CONFIGURATION S3 S2 Reserve Supply 208Y/120V Maintenance By-pass 3 S1 5 290 150 AC Supply S4 208 4 1 Battery Contactor IN THE ABSENCE OF A SEPARATE RESERVE SUPPLY THE RESRVE IS DERIVED FROM THE AC UTILITY INPUT WITH THE JUMPER CONNECTED AS INDICATED 2 144 Cells (Internal) 36kVA - STANDARD CONFIGURATION S3 Maintenance By-pass S2 Reserve Supply 208Y 208Y 250 480 AC Supply 5 3 S1 S4 208Y 4 1 Battery Contactor IN THE ABSENCE OF A SEPARATE RESERVE SUPPLY THE RESRVE IS DERIVED FROM THE AC UTILITY INPUT WITH THE JUMPER CONNECTED AS INDICATED 240 Cells (External) 2 36kVA - 480V/208V CONFIGURATION S3 Maintenance By-pass S2 Reserve Supply 208Y 480V AC Supply 5 3 S1 250 480 4 1 IN THE ABSENCE OF A SEPARATE RESERVE SUPPLY THE RESRVE IS DERIVED FROM THE AC UTILITY INPUT WITH THE JUMPER CONNECTED AS INDICATED S4 208Y Battery Contactor 240 Cells (External) 2 Figure 1 – Block diagrams – 24/36kVA MI00/10056 rev.1--05/2001-- page 7 S3 Reserve Supply Maintenance Bypass S5 S2 480V 480Y/277V 5 3 S4 S1 208Y/120V AC Supply 1 4 Battery Contactor IN THE ABSENCE OF A SEPARATE RESERVE SUPPLY THE RESERVE IS DERIVED FROM THE AC UTILITY INPUT WITH THE JUMPER CONNECTED AS INDICATED 240 Cells (External) 2 Figure 2 – Block diagram – 50/80kVA The uninterruptible power system consists of the following: 1 2 3 4 5 1.4 - RECTIFIER/INVERTER BATTERY BACKFEED PROTECTION INVERTER STATIC SWITCH RESERVE STATIC SWITCH S1 = Equipment ON/OFF switch S2 = Equipment Reserve switch S3 = Equipment By-pass switch S4 = Equipment OUTPUT switch (INVERTER OUTPUT switch for 50/80kVA only) S5 = RESERVE OUTPUT switch for 50/80kVA only Functions RECTIFIER / BATTERY CHARGER The rectifier/battery charger transforms the alternating current of the mains supply to direct voltage to maintain the battery in a fully charged state and also supply the inverter. BATTERY The battery is an energy reserve that is used by the inverter and the load whenever the mains supply fails. INVERTER The inverter changes the direct voltage from the rectifier or from the battery into a three phase sinusoidal alternating voltage for the external supply. ELECTRONIC STATIC SWITCH The function of the electronic static switch is to select one of the two sources of alternating voltage and to supply it to the external load. The two sources of voltage supplied to the static switch are the output of the inverter and the reserve supply. In normal working conditions, the static switch supplies the load from the inverter. SWITCHES The switches permits maintenance and repair of the UPS, without interrupting the supply to the load. page 8 -- MI00/10056 rev.1--05/2001 1.5 Operational modes S3 Maintenance By-pass S2 S1 LOAD AC Supply S4 Battery Contactor 24/36kVA Ratings S3 Maintenance By-pass S2 S5 480Y/277V LOAD S4 S1 208Y/120V AC Supply Battery Contactor 50/80kVA Ratings Figure 3 – Normal operation During normal operation the load is supplied by the mains through the rectifier and inverter. The rectifier also supplies the current for recharging and maintaining the battery in a fully charged state. S3 Maintenance By-pass Reserve Supply S2 S4 S1 LOAD AC Supply Battery Contactor S3 Reserve Supply 24/36kVA Ratings Maintenance By-pass S2 S5 480Y/277V LOAD S4 S1 208Y/120V AC Supply Battery Contactor 50/80kVA Ratings Figure 4 – Utility Supply failure When the utility supply voltage is absent or outside the allowed tolerances, the battery supplies the inverter. This will be indicated on the UPS front panel display and the Remote Alarm Unit (if fitted). The standby time available depends both on the capacity of the battery and on the size of load. It is possible to extend autonomy by reducing the output power by disconnecting non-important loads. In all cases, the alphanumerical display shows the residual autonomy. MI00/10056 rev.1--05/2001-- page 9 S3 Reserve Supply Maintenance By-pass S2 S4 S1 AC Supply Battery Contactor S3 Reserve Supply 24/36kVA Ratings Maintenance By-pass S2 S5 480Y/277V S4 S1 208Y/120V AC Supply Battery Contactor 50/80kVA Ratings Figure 5 – Re-establishing the Utility Supply When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will result in reduced standby times. S3 Reserve Supply Maintenance By-pass S2 S4 S1 AC Supply Battery Contactor S3 Reserve Supply 24/36kVA Ratings Maintenance By-pass S2 S5 S4 S1 480Y/277V 208Y/120V AC Supply Battery Contactor 50/80kVA Ratings Figure 6 – Transferring the Load onto the Reserve Supply Transfer onto the reserve line is caused by two conditions: a) inverter stop b) overload In both instances the load is transferred onto the reserve without interruption. If the overload is temporary, the system will re-transfer from reserve to inverter as soon as the it ceases. This allows for the initial start-up of loads with high or excessive switch-on currents. page 10 -- MI00/10056 rev.1--05/2001 2.0 SAFETY Read all instructions carefully before installing or operating the equipment. 2.1 General safety The procedure described in these instructions is intended for use by persons experienced in the operation of Uninterruptible Power Systems and ancillary equipment. Persons unfamiliar with this type of equipment should seek guidance from experienced personnel. The EDP70 PLUS UPS is designed to be operated in accordance with existing safe operating procedures. These instructions are not intended to replace existing safety practices. If there are any questions regarding the safe operation of the system, contact a Chloride service representative. This equipment is designed and built for safe operation when used to supply its rated load, providing it is installed as specified by qualified, licensed and competent electricians. Electrical energy can be supplied by the equipment and the battery. 2.2 Symbols The following symbols appear in this book and in the unit: Warning - Hazardous voltages are present. If the instructions are not heeded, there is a risk of electrical shock and danger to personal safety. DIRECT CURRENT SUPPLY ALTERNATING CURRENT SUPPLY ON position of the switches OFF position of the switches Inverter Start Up For explanation see Para. 6.2. of this manual Inverter Shutdown For explanation see Para. 6.2. of this manual Audible Alarm Cancel Switch For explanation see Para. 6.2. of this manual MI00/10056 rev.1--05/2001-- page 11 2.3 Page Right Control For explanation see Para. 6.2. of this manual Record Up For explanation see Para. 6.2. of this manual Record Down For explanation see Para. 6.2. of this manual Electrical precautions Never handle a component or assembly without first confirming that no voltage is applied or present. Remove only those protective covers that are essential to perform the repairs or adjustment currently required, and replace them as soon as possible. . . . 2.4 Use only insulated tools. Place a rubber insulating mat in front of all equipment doors. Keep all door closed and locked at all times during normal operation. Battery precautions Always isolate the load before connecting or disconnecting the batteries or battery cells. Ensure that batteries are fully isolated by disconnecting the battery connectors, opening circuit breakers, or both. Remove all jewellery from hands, wrists and neck before working on batteries or battery cells. Before leaning over batteries, remove any metal object that could fall out of pockets. Do not place tools or other conductive objects on the batteries. 2.5 Battery safety equipment When working on or handling batteries, ensure that the following items are worn: . . . . Eye goggles Rubber gloves Rubber apron Rubber boots When batteries are being moved or worked on, ensure the following items are available in the immediate vicinity: . . . . An eye bath, eyewash station or equivalent A clean water source to wash spilled acids Absorbent materials to soak up spilled acids Disposal for contaminated materials. page 12 -- MI00/10056 rev.1--05/2001 3.0 STORAGE If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life. The date the battery was last recharged and the date the battery is due for its next recharge are both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge date. When the EDP70 PLUS is due to be recharged, refer to the Installation instructions and connect the EDP70 PLUS UPS to a temporary AC supply. The battery MUST be recharged for at least 24 hours every 3 months. 4.0 INSTALLATION 4.1 Mechanical characteristics - Ambient temperature 18°F[-10°C] to 104°F [+40°C ] Relative Humidity (w/out condensing @ 68°F[20°C]) < 90% Max altitude (w/out derating) 3300 feet [1000 m] above sea-level Protection degree (panel fitted) Input cables bottom Air inlet bottom Air outlet rear UPS model Description 50 80 Size width depth height In [mm] 27.5 [700] 28.7 [730] 56 [1420] 27.5 [700] 28.7 [730] 56 [1420] 35.4 [900] 28.7 [730] 63 [1600] 35.4 [900] 28.7 [730] 63 [1600] Total Weight (UPS + Battery) w/out cells 25 Ah cells 30 Ah cells 35 Ah cells Lbs [kg] 880 [400] 1342 [610] 1456 [662] 1526 [694] 1300 [590] n.a. n.a. n.a. 1342 [610] 1800 [818] n.a. n.a. n.a. n.a. n.a. n.a. In2[m2] 789 [0.511] 789 [0.511] 1019 [0.657] 1019 [0.657] 2 Lbs/in [kg/m2] 1.12 [782] 1.70 [1194] 1.85 [1296] 1.93 [1358] 1.65 [1155] n.a. n.a. n.a. 1.32 [930] 1.77 [1245] n.a. n.a. n.a. n.a. n.a. n.a. Air-Flow cfm [mc/h] 235 [400] 647 [1100] Acoustic Noise 100% Linear Load dBA 52 55 Floor Area w/out cells 25 Ah cells 30 Ah cells 35 Ah cells Floor Loading (UPS + Battery) Notes: 1) 2) u.m. 24 36 n.a. = not applicable Longer autonomies, and battery for EDP above 20 kVA are available with external battery cubicles. MI00/10056 rev.1--05/2001-- page 13 ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES) 680,0 700,0 (27.56) (26.77) 1417,0 (55.79) 726,0 (28.58) 728,0 (28.66) 58,0 (2.28) 67,0 (2.64) CABLE ENTRY 260 (10.24) X 66 (2.6) NR 4 X ø8 (ø0,31) 30,0(1.18) 645,0 (25.39) 600,0 (23.62) 63,0 (2.48) Figure 7 – 24 Footprint and cabinet dimensions page 14 -- MI00/10056 rev.1--05/2001 ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES) 680,0 (26.77) 700,0 (27.56) 1417,0 (55.79) 88,0 (3.46) NR 4 X ø8 (ø0,31) 125,0 (4.92) 728,0 (28.66) CABLE ENTRY 500 (19.68) X 110 (4.33) 30,0 (1.18) 645,0 (25.39) 600,0 (23.62) 50,0 (1.97) Figure 8 – 36 Footprint and cabinet dimensions MI00/10056 rev.1--05/2001-- page 15 ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES) 900,0 (35.43) 1600 (63.0) 68,0 (2.68) NR 4 X ø8 (ø0,31) 100,0 (3.94) 740,0 (29.13) CABLE ENTRY 700 (27.56) X 110 (4.33) 30,0 (1.18) 645,0 (25.39) 800,0 (31.5) 50,0 (1.97) Figure 9 – 50/80 Footprint and cabinet dimensions page 16 -- MI00/10056 rev.1--05/2001 Figure 10 – “A” Battery Cabinet Drawing for 24/36kVA Ratings MI00/10056 rev.1--05/2001-- page 17 Figure 11 – “B” Battery Cabinet Drawing for 24/36kVA Ratings page 18 -- MI00/10056 rev.1--05/2001 Figure 12 – “E” Battery Cabinet Drawing for 50/80kVA Ratings MI00/10056 rev.1--05/2001-- page 19 Figure 13 – “F” Battery Cabinet Drawing for 50/80kVA Ratings page 20 -- MI00/10056 rev.1--05/2001 4.2 Installation Check the rating label on the rear of the front panel of the EDP70 PLUS UPS to ensure the input/output voltages, frequency and load are all within the rating of the UPS. EDP70 PLUS is designed to operate in an office environment with an optimum temperature of 68°F [20 C]. A gap of at least 4In [ 10cm. ] must be maintained at rear of the UPS to ensure adequate ventilation. Nothing should be placed around the equipment which might restrict the airflow. Ensure the interconnecting cables do not cause a hazard to the user. A gap of at least 32 In [ 800 mm] must be maintained above the UPS to ensure adequate space for maintenance. The appropriate lifting equipment must be used to move the EDP70 PLUS UPS. Figure 14 – UPS Ratings UPS ratings Description U.M. Output power kVA Nominal Load Maximum input power (with unit @ nominal Load & battery recharge) Maximum dissipation (with inverter @ nominal Load) Number of battery cells 24 24 24 36 36 36 12kVA 18kVA 24kVA 24kVA 30kVA 36kVA 12 18 24 24 30 36 kW 8 12 16 16 20 24 kVA 15 21 28 28 35 42 BTU/H 3750 5460 6800 7700 9500 11300 n 144 240 Battery voltage range V Battery end-discharge current A 37 55 74 Description U.M. 50 50 50 30kVA 40kVA Output power kVA 30 40 Nominal Load kW 24 kVA 43 238-327 396-545 53 67 80 80 80 80 50kVA 50kVA 65kVA 80kVA 50 50 65 80 32 40 40 52 64 57 71 71 91 112 14300 14300 18600 22100 140 173 UPS ratings Maximum input power (with unit @ nominal Load & battery recharge) Maximum dissipation (with inverter @ nominal Load) Number of battery cells BTU/H n Battery voltage range V Battery end-discharge current A 240 396-545 67 88 110 105 MI00/10056 rev.1--05/2001-- page 21 Recommended wire sizes 1) It is recommended that the external cables and protection be selected for the highest rated unit of the model in use. 2) Reserve (or primary) input and output Neutral cable size should be greater than that of the line cables in order to be able to supply non-linear loads having a Crest Factor of up to 3:1 (i.e. where neutral current = 1.7 x line current). If non-linear loads are not to be supplied from the Installation, the Neutral can be of the same size as the load cable. 3) Recommended AC input overcurrent protection represents 125% of nominal full load current (continuous) plus the short duration input current (non-continuous) for battery recharging per NEC 220-10 b. 4) UPS output cables should be run in separate conduits from input cables. 5) Grounding conductors are sized per NEC 250-95. 6) Cable sizes are based upon NEC. Recommended sizes only. Be sure to follow the codes which apply to your installation. Refer to UPS connection data table on following page. page 22 -- MI00/10056 rev.1--05/2001 A.C. Supply UPS Type Vin/Vout Rated current (A) Protection device (A) Output Nominal current (A) Reserve Supply Nominal current (A) Protection device (A) 42 50 33 33 50 60 80 50 50 75 24/24kVA 78 100 67 67 100 36/24kVA 78 100 67 67 100 97 100 83 83 125 36/36kVA 118 125 100 100 150 36/24kVA 34 45 67 30 45 42 50 83 36 55 36/36kVA 51 70 100 43 65 50/30kVA 50 70 36 36 50 66 90 48 48 80 50/50kVA 83 110 60 60 80 50/30kVA 50 70 83 36 50 66 90 111 48 80 50/50kVA 83 110 139 60 80 80/50kVA 83 110 60 60 80 110 125 78 78 100 80/80kVA 135 150 96 96 125 80/50kVA 83 110 139 60 80 110 125 180 78 100 135 150 222 96 125 24/12kVA 24/18kVA 36/30kVA 36/30kVA 50/40kVA 50/40kVA 80/65kVA 80/65kVA 80/80kVA 208/208 208/208 480/208 480/480 480/208 480/480 480/208 MI00/10056 rev.1--05/2001-- page 23 4.4 Ventilation UPS can work in a continuous environment within 18°F[-10°C] to 104°F [+40°C ] temperature range, although, ideally the ambient temperature should be below 78°F [25°C]. The heat, dissipated by the UPS (indicated on figure 7), is extracted by internal fans and then dissipated into the air. The heat can be removed from the UPS room by a forced cooling ventilation system or, alternatively, an air conditioning system. The required air changes per hour will depend on the UPS rating and this heat loss and on the cooling air temperature. To calculate the required air flow for the dissipated power, the altitude and the cooling air temperature, the following equation can be used: • Pd V = 2770 - - - - - - • e (0.125 h Tk / T0 ) Tr - Tk with: V = Pd Tr air flow [mc/h] = total dissipated power [kW] = max. temperature allowed into the room [104°F = 40°C = 313°K] Tk T0 = Temperature of input cooling air = 273 °K h = altitude above the sea level [km] page 24 -- MI00/10056 rev.1--05/2001 5.0 CONNECTION Protection devices to be installed by the customer according to the information shown on page 23 L1 UTILITY L2 INPUT L3 N A B C N A B C N Neutral not present on 50 and 80kVA ratings L1 L2 OUTPUT L3 N (Neutral separately derived on 50 and 80kVA ratings) EXTERNAL BATTERIES 1 2 3 4 5 6 G Remove link to connect remote E.P.O. Battery Charge Inhibit Thermostick contacts GROUND Protection devices to be installed by the customer according to the information shown on page 23 L1 RESERVE L2 INPUT L3 N UTILITY L1 L2 INPUT L3 A B C N Neutral not A B C present on 50 and 80kVA ratings G L1 L2 OUTPUT L3 N (Neutral separately derived on 50 and 80kVA ratings) A B C N EXTERNAL BATTERIES 1 2 3 4 5 6 Remove link to connect remote E.P.O. Battery Charge Inhibit Thermostick contacts GROUND Figure 15 – Connection diagrams THE AC AND DC SUPPLIES TO THE EDP70 PLUS UPS, AND THE AC OUTPUT FROM THE UPS, SHOULD BE FED THROUGH SUITABLY RATED CIRCUIT BREAKER OR FUSE(S) AND ISOLATING SWITCH SUITABLE FOR BRANCH CIRCUIT PROTECTION. NOTE: INTERRUPTING THE NEUTRAL FEED MAY CAUSE THE CHANGE IN GROUND-NEUTRAL VOLTAGE TO AFFECT THE LOAD. NOTE: ALL CIRCUIT BREAKERS OR FUSES AND ISOLATING SWITCHES SHOULD BE FITTED AS CLOSE TO THE EDP70 PLUS UPS AS POSSIBLE AND MARKED WITH THE LABELS PROVIDED WITH THE UNIT. IT IS ALSO RECOMMENDED A LABEL AS FOLLOWS MI00/10056 rev.1--05/2001-- page 25 UNINTERRUPTIBLE POWER SYSTEM NO UNAUTHORIZED OPERATION page 26 -- MI00/10056 rev.1--05/2001 CAUTION! All power connection must carried out by qualified licensed personnel experienced in wiring this type of equipment The safety ground wire must be connected before the power input cables The correct phase rotation (phase A leads B leads C) must be observed on the UPS terminals. An input grounded neutral conductor is required (24/36kVA only) WARNING! In maintenance by-pass operation, the UPS components are de-energized, with the exception of input/output terminals, battery cabinet, input matching voltage transformer (for 480/208 configuration) and isolating transformer (for 50 and 80kVA). All input power (AC and DC) must be disconnected to ensure complete isolation MI00/10056 rev.1--05/2001-- page 27 5.1 Electrical connections WARNING! All electrical connections must be made by a qualified electrician and meet local electrical code standards Before attempting to connect the mains supply, the reserve/bypass supply or the load, ensure that all supplies, including the battery, are isolated and that all the equipment switches are in their »OFF» position. Open UPS front access panel and remove internal panel over main switches and terminal blocks. NOTES: 1) In accordance with para. 12.7 of UL 1778, the installation must be performed by a qualified electrician. The terminals require the use of the proper crimp tools and terminals in order to perform an installation in accordance with the National Electrical Code (NEC). The recommended crimp tools, terminals and torque are shown in the followings tables: 2)Use Copper Conductors Only Table of T& B’s cat.no.s for terminals and crimp tools page 28 -- MI00/10056 rev.1--05/2001 5.2 24 – 12/18/24kVA Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see Figure 16 . The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the EDP70 PLUS UPS terminals is within +/- 10% of nominal. The EDP70 PLUS UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box. Installation and connection should only be carried out by qualified electrical personnel. S2 = Equipment Reserve Switch S1 = Equipment ON/OFF Breaker S3 = Equipment By-pass Switch S4 = Equipment OUTPUT Breaker Battery Compartment Figure 16 - 24 – 12/18/24kVA: Switches and Breakers MI00/10056 rev.1--05/2001-- page 29 Output, Reserve, Input and External Battery Terminals Hinged panel security screws Cable support Cable channel Figure 17 - 24 – 12/18/24kVA: Switches Access to the terminals for electrical connections is as follows: a) Remove front panel see Figure 16. b) Remove the two securing screws for the hinged front panel. c) This exposes the electrical terminal rail, see Figure 18 d) Remove the screws securing the access plate. e) Push the interconnection cables up through the cable channel and the access plate. f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked. g) Install or start-up batteries see section 13.1 h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate. i) Replace the terminal board compartment panel and the front cover. OBSERVE POLARITIES AND ORIENTATIONS. See Remote Alarms and Computer Interface for connections to these facilities. For optional battery cubicles, refer to section 13.2. page 30 -- MI00/10056 rev.1--05/2001 Computer relay interface - FEMALE RAU - FEMALE RS232 - MALE Modem and Multicom power supplies FRONT REAR Label sec. max 14 AWG EXTERNAL BATTERIES E.P.O. Battery Charger Inhibited OUTPUT PRIMARY INPUT GROUND M6 RESERVE INPUT U1 V1 W1N PE U V W N U2 V2 W2 N Figure 18 - 24 – 12/18/24kVA: Cable Connections MI00/10056 rev.1--05/2001-- page 31 5.3 36 – 24/30/36kVA Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see figure 13. The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the EDP70 PLUS UPS terminals is within +/- 10% of nominal. The EDP70 PLUS UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box. Installation and connection should only be carried out by qualified S3 = Equipment By-pass switch S4 = Equipment OUTPUT Breaker S1 = Equipment ON/OFF Breaker S2 = Equipment Reserve switch Terminal board compartment Figure 19 - 36 – 24/30/36kVA: Switches and Breakers page 32 -- MI00/10056 rev.1--05/2001 electrical personnel. S3 = Equipment By-pass switch S4 = Equipment OUTPUT Breaker S1 = Equipment ON/OFF Breaker S2 = Equipment Reserve switch Output, Input, Reserve and External Battery Terminals Access plate Figure 20 - 36 – 24/30/36kVA: Connections Access to the terminals for electrical connections is as follows: a) Remove front panel see Figure 20. b) Remove the terminal board compartment panel by unscrewing the fixing screws at the front. c) This exposes the electrical terminal rail, see Figure 21 d) Remove the screws securing the access plate. e) Push the interconnection cables up through the access plate. f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked. g) Install or start-up batteries see section 13.3 and 13.4. h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate. i) Replace the terminal board compartment panel and the front cover. OBSERVE POLARITIES AND ORIENTATIONS. See Remote Alarms and Computer Interface for connections to these facilities. MI00/10056 rev.1--05/2001-- page 33 Computer relay interface - FEMALE RAU - FEMALE RS232 - FEMALE FRONT REAR Modem and Multicom power supplies QS1 QS4 QS3 QS2 EXTERNAL BATTERIES OUTPUT NEUTRAL (RES/OUT) RESERVE INPUT PRIMARY INPUT GROUND E.P.O. Battery charge inhibited PE U V W U1 V1W1 N U2 V2W2 Figure 21 - 36 – 24/30/36kVA: Cable Connections page 34 -- MI00/10056 rev.1--05/2001 5.3 EDP70 PLUS 50/80kVA Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see figure 16. The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the EDP70 PLUS UPS terminals is within +/- 10% of nominal. The EDP70 PLUS UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box. Installation and connection should only be carried out by qualified electrical personnel. S5 = RESERVE OUTPUT switch S4 = INVERTER OUTPUT Breaker S3 = BY-PASS switch S2 = Equipment RESERVE switch S1 = Equipment ON/OFF Breaker Terminal board compartment Figure 22 – 50/80kVA: Switches and Breakers MI00/10056 rev.1--05/2001-- page 35 S5 = RESERVE OUTPUT switch S4 = INVERTER OUTPUT Breaker S3 = BY PASS switch S2 = Equipment RESERVE switch S1 = Equipment ON/OFF Breaker Output, Input, Reserve and External Battery Terminals Access plate Figure 23 – 50/80kVA: Connections Access to the terminals for electrical connections is as follows: a) Remove front panel see Figure 20. b) Remove the terminal board compartment panel by unscrewing the fixing screws at the front. e) This exposes the electrical terminal rail, see Figure 21 f) Remove the screws securing the access plate. e) Push the interconnection cables up through the access plate. f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked. g) Install or start-up batteries see section 13.3 and 13.4. h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate. i) Replace the terminal board compartment panel and the front cover. OBSERVE POLARITIES AND ORIENTATIONS. See Remote Alarms and Computer Interface for connections to these facilities. page 36 -- MI00/10056 rev.1--05/2001 Computer relay interface - FEMALE RAU - FEMALE RS232 - MALE FRONT REAR Modem and Multicom power supplies QS1 QS2 QS4 QS5 U2 V2 W2 N N PE 1 2 3 4 5 6 OUTPUT EXTERNAL BATTERIES RESERVE INPUT PRIMARY INPUT E.P.O. Battery charge inhibited Thermostick contacts U V W U1 V1 W1 QS3 Figure 24 – 50/80kVA: Cable Connections MI00/10056 rev.1--05/2001-- page 37 5.4 Signal connections a) Emergency Power Off When the connection between terminals 1 and 2 is opened, the UPS will stop, and it will automatically restart when the switch is closed. This allows a remote E.P.O. to be installed, in series with the standard one installed inside the UPS. (See Para. 9.1) Warning: To avoid unauthorized stopping, it is strongly recommended that some form of security switch be used.. b) Battery charge inhibited By removing the link between terminals 3 and 4, the battery charge will be inhibited, and a warning message will be displayed. Possible uses of this could be one, or more, of the following: • connect the above terminals to a contact which will be opened if there is Hydrogen within the battery compartment(s). In this way the cause of hydrogen generation will be stopped, and a warning about the operating status of the system will be displayed. • connect the above terminals to a contact which will be opened when the UPS is supplied by a Generator (it should be an auxiliary contact of the Line <-> Generator changeover). In this way it will be possible to limit the power supplied by the Generator to the only value required to supply the critical loads, and not to charge the battery until the mains supply returns. In this way it is possible to use a Generator having a power rating less than the maximum input power of the UPS. Also in this case a warning about the operating status of the system will be displayed. c) Thermostick connector (50/80kVA only) This connection provides the customer with remote control over the output transformer Overtemperature Alarm (TCORE = 180°C). NOTE: If more than one of the above applications (or similar) are installed, the contacts MUST be connected in series. page 38 -- MI00/10056 rev.1--05/2001 6.0 CONTROLS 6.1 User Controls The user controls are situated on the front panel, see Figure 25. Access to the Equipment Power Switches can be obtained by removing the front cover. Figure 25 – Control panel 1 2 3 4 5 Illuminated Liquid Crystal Display R ~ I ~ S~ ~ ~ B User Switches 6 Audible Alarm Cancel Switch Inverter Start Inverter Stop Display indicators 1) Utility Supply Indicator (Green) 2) Battery Indicator (Green) 3) Inverter Indicator 4) Static Switch indicator (Green) (Green) 5) Reserve Supply Indicator (Green) 6) Warning Indicator (Red) MI00/10056 rev.1--05/2001-- page 39 6.2 Control Panel Inverter Start Up This allows the user to turn on and reset the inverter. This is normally only used when starting the UPS. Inverter Shutdown The switch incorporates a safety feature to prevent inadvertent operation yet still allow rapid shutdown in the event of an emergency. This is achieved by the requirement that the switch be depressed for 2 seconds before the inverter stops during which time the audible alarm will be heard. Audible Alarm Cancel Switch This switch cancels the audible alarm. When pressed the red warning light goes from continuous illumination to flashing on and off. Page Right Control This switch changes the page headings displayed on the LCD. It also allows the alarm and measurement statuses to be stepped through when examining the power history (refer to section 10.6) Record Up This switch changes the record displayed on the LCD to the previous message displayed. When the top of the page has been reached the display will no longer scroll. Record Down This switch changes the record displayed on the LCD to the next record on the page. When the bottom of the page has been reached the display will no longer scroll. page 40 -- MI00/10056 rev.1--05/2001 7.0 START UP 1. Switch on the AC reserve and the main AC Utility supply to the UPS. 2. Turn on the Utility supply Input, Reserve Input (if fitted) and UPS Output switches located behind the front panel, see figure 14 for 24kVA, figure 17 for 36kVA or figure 20 for 50/80kVA. 3. Replace the front panel. 4. Press the CANCEL AUDIBLE ALARM switch (see section 6.2) 5. Initially, all the green indicators will flash on the display mimic. After about 30 seconds the supply and battery indicators should stop flashing. 6. Press the Inverter On push button (I). 7. The inverter should now start and after a delay of approximately 30 seconds the message ‘SYSTEM NORMAL’, in English, will appear on the liquid crystal display. 8. Select the required language by pressing page right control until the ‘SELECT LANGUAGE’ message appears on the liquid crystal display. Press the page down control until the required language is selected. Press the page right control once more confirm the language selection. Thereafter, all messages will appear in the selected language. MI00/10056 rev.1--05/2001-- page 41 8.0 MAINTENANCE BYPASS The EDP70 PLUS UPS is equipped with Manual Maintenance Bypass systems. If a unit requires servicing, the Manual Maintenance Bypass allows the load to be connected directly to the AC supply so that the unit may be serviced in safety. The following instructions must be followed: 1. Ensure that ‘SYSTEM NORMAL’ is displayed on the LCD. (Note: If ‘SYSTEM NORMAL’ is not displayed check that the inverter is not ‘OUT OF SYNC’, see section 10.7. Turning the inverter off under this fault condition will interrupt the load supply.) 2. Turn off the inverter by pressing the inverter shutdown button for more than 2 seconds 3. Turn the Maintenance Bypass Switch (located behind front panel, see figure 14, 17 or 20) to ON. 4. Turn off the Primary Input, Reserve Input and UPS Output Switches, see figure 14, 17 or 20. THE LOAD IS NOW SUPPLIED DIRECTLY FROM THE AC UTILITY SUPPLY AND IS NO LONGER PROTECTED BY THE UPS CAUTION: Some components in the UPS will retain a static voltage even after the switches have been opened. Also, on the 50/80kVA ratings, the isolating transformer and the relative cooling fans are still supplied from the Bypass. To return to the normal operating mode, follow the above procedure in reverse. Note: 9.0 The EDP70 PLUS UPS must not be left operating with the Maintenance Bypass Switch in the ON position. SHUT-DOWN 1. Close down the load in an orderly manner. 2. Push the (inverter shutdown) button for more than 2 seconds. 3. Turn the main switch to OFF. Note: If the electricity supply to the site is switched off outside normal working hours, the EDP70 PLUS should be shut down each evening, by either using the shutdown procedure or wiring in the Emergency Power Off (EPO) function, see figures 14, 17, 19 or 22 (depending on the UPS size). This will prevent the battery from discharging. If, on the other hand, the supply to the site is continuous, the EDP70 PLUS should be operated 24 hours a day. 9.1 Installing the EPO To wire the EPO, open the link between terminal boards 1 and 2 and connect a signal switch: when the switch is enabled, the inverter and rectifier will stop, the battery relay will be opened and the load will be de-energized page 42 -- MI00/10056 rev.1--05/2001 To ensure that the EPO functions correctly, the signal should remain active for a period > 400 msec. MI00/10056 rev.1--05/2001-- page 43 10.0 VISUAL AND AUDIBLE ALARMS The EDP70 PLUS UPS is equipped with visual and audible alarms which indicate the status of the UPS to the operator. The visual alarms are displayed on the LCD and the mimic panel. 10.1 Silencing Audible Alarm The audible alarm sounds when the UPS is in an alarm condition. The sound is silenced by pressing the button marked . When pressed, the red warning light which is illuminated continuously starts to flash, providing an even clearer indication of the alarm condition, even though the audible alarm has been silenced. 10.2 Mimic The display mimic consists of a pictorial representation of the functional blocks in the EDP70 PLUS UPS. When the system is in NORMAL OPERATING CONDITION the green indicators are illuminated continuously. In the event of an ALARM condition the indicators start to flash identifying the part (or parts) of the system in alarm (see figure 19). Further information on the alarms can be obtained from the LCD by scrolling through the page headings using the button (page right control) until the message on the display describes the functional block in the UPS identified by the flashing LED(s). The alarms can then be accessed using the procedure is described in detail in section 10.4. 10.3 (scrolling up) and (scrolling down) record buttons. This Liquid Crystal Display The display is a 40-character (2 line x 20 character) module which is back lit. The messages describing the functioning of the system are accessed via the user switches (see figure 18). page 44 -- MI00/10056 rev.1--05/2001 10.4 Display Page Headings After initial power up, under normal operating conditions, the main page heading will be displayed: UPS xx KVA SYSTEM NORMAL The first line displays the power rating of the EDP70 PLUS UPS, the second line is the system status. During normal operating conditions, the display reading always returns to this page heading whenever the user switches are not operated for at least 5 minutes. By pressing the button marked once, the battery rectifier heading is displayed: RECT/BATT ALARMS NO ALARMS ACTIVE The second line of the display confirms that the rectifier and battery are functioning correctly. By pressing the button marked again, the inverter heading is shown on the display: INVERTER ALARMS NO ALARMS ACTIVE The second line of the display confirms that the inverter is functioning correctly. By pressing the button marked again, the load output and reserve supply heading is displayed: LOAD/RES ALARMS NO ALARMS ACTIVE The second line of the display indicates that the UPS load output and reserve supply input are correct. MI00/10056 rev.1--05/2001-- page 45 By pressing the button marked again, the selected battery test period appears on the display: BATTERY TEST WEEKLY The button marked is pressed to scroll through the 4 battery test period available (WEEKLY, FORTNIGHTLY, MONTHLY and NONE). The button marked is pressed to scroll through the list in reverse order. When the required battery test period appears, press the button marked the selected language heading appears on the display. to select the battery test period and SELECTED LANGUAGE ENGLISH The button marked and Spanish). is pressed to scroll through the languages available (English, French, German, Italian The button marked is pressed to scroll through the list in reverse order. When the required language appears, press the button marked display to the main UPS status message. page 46 -- MI00/10056 rev.1--05/2001 to select the language and to return the If at any time the inverter is blocked then the power history heading appears: POWER HISTORY DOWN TO ACCESS The power history page is described in detail in section 10.6. The machine measurement signals are accessed from the main page heading as follows: UPS xx kVA SYSTEM NORMAL press once RECTIFIER Vdc xxx V Idc xxx A Displays the output voltage and current supplied by the rectifier. press once BATTERY Vb xxx V Ib xxx A Displays the battery voltage and the charge or discharge current of the battery (ve = charge, - ve = discharge) press once INVERTER F xx.x Hz A xxx V B xxx V C xxx V Displays the frequency and phase-neutral voltage at which the inverter is running. press once INVERTER F xx.x Hz AB xxx V BC xxx V CA xxx V Displays the frequency and phase-phase voltage at which the inverter is running. press once RESERVE F xx.x Hz A xxx V B xxx V C xxx V Displays the frequency and the phase-neutral voltage of the reserve supply. press once MI00/10056 rev.1--05/2001-- page 47 RESERVE F xx.x Hz AB xxx V BC xxx V CA xxx V Displays the frequency and the phase-phase voltage of the reserve supply. press once LOAD F xx.x Hz A xxx V B xxx V C xxxV Displays the frequency and phase-neutral voltage supplied to the load. press once LOAD F xx.x Hz AB xxx V BC xxx V CA xxxV Displays the frequency and phase-phase voltage supplied to the load. press once LOAD A xxx A B xxx A C xxx A Displays the current supplied to the load. press once LOAD A x% B x% C x% Displays the load capacity percentage of the UPS rated value. press once LOAD P.F. 0.99 P = 80kW Displays the Peak Factor of the load current. s = 80kVA press once TIME ON INVERTER xxg: xxh: xxm: xxs press once page 48 -- MI00/10056 rev.1--05/2001 Displays the total time the load has been supplied by the inverter since the machine was last switched off. TIME ON RESERVE xxg: xxh: xxm: xxs Displays the total time the load has been supplied by the reserve since the machine was last switched off. press once LAST MAINS FAILURE xxd: xxh: xxm: xxs Displays the duration time of the most recent Mains Failure press once MAINS FAILURE yy xxgg: xxh: xxm: xxs Displays the number of mains failures and the total duration of these failures since the machine was last switched off. press once TOTAL MAINS FAILURE yy xxg: xxh: xxm: xxs Displays the total number of mains failures and their total duration since the machine was installed. press once REV A. XX xx-xx-xx 10h00yyy Displays the code for the version of software resident (and relevant data) within the EDP70 PLUS UPS system MI00/10056 rev.1--05/2001-- page 49 The measurement signals are accessed from the battery rectifier page as follows: RECT/BATT ALARMS NO ALARMS ACTIVE Normal operating mode press once RECTIFIER Vdc xxx V Idc xxx A Displays the output voltage and current supplied by the rectifier. press once BATTERY Vdc xxx V Ib xxxx A Displays the battery voltage and the charge or discharge current of the battery (ve = charge, - ve = discharge) The measurement signals are accessed from the inverter page as follows: INVERTER ALARMS NO ALARMS ACTIVE Normal operating mode press once INVERTER F xx.x Hz A xxx V B xxx V C xxx V Displays the frequency and phase-neutral voltage at which the inverter is running. press once INVERTER F xx.x Hz AB xxx V BC xxx V CA xxx V Displays the frequency and phase-phase voltage at which the inverter is running. press once INVERTER A xxx A B xxx A C xxx A page 50 -- MI00/10056 rev.1--05/2001 Displays the current at which the inverter is running. The measurement signals are accessed from the load output - reserve supply page as follows: LOAD/RES ALARMS NO ALARMS ACTIVE Normal operating mode press once LOAD f xx.x Hz A xxx V B xxx V C xxx V Displays the frequency and phase-neutral voltage supplied to the load. press once LOAD f xx.x Hz AB xxx V BC xxx V CA xxx V Displays the frequency and phase-phase voltage supplied to the load. press once LOAD A xxx A B xxx A C xxx A Displays the current supplied to the load. press once LOAD A x% B x% C x% Displays the load capacity percentage of the UPS rated value. press once LOAD P.F. 0.99 P = 80kW Displays the Peak Factor of the load current. s = 80kVA press once RESERVE F xx.xHz A xxx V B xxx V Cxxx V Displays the frequency and phase-neutral voltage supplied to the reserve line. press once RESERVE F xx.xHz AB xxx V BC xxx V CA xxx V Displays the frequency and phase-phase voltage supplied to the reserve line. MI00/10056 rev.1--05/2001-- page 51 10.5 Abnormal operating mode messages Under abnormal operating conditions, the normal functioning heading on the main page UPS xx KVA SYSTEM NORMAL is replaced with the alarm page: UPS xx KVA SYSTEM ALARM If at least 1 alarm is activated for each block; the »NO ALARMS ACTIVE» message in the second line on the display is replaced with the first active alarm. Whenever there is more than one active alarm, they can be scrolled through using the and keys. Each message is associated with one of the following conditions: NORMAL Conditions which do not adversely affect the normal functioning of the machine are identified under this heading. No action is required on the part of the operator. WARNING Transitory conditions which can either return to normal condition or result in a permanent fault are identified under this heading. No action is required on the part of the operator. FAULT Faults are identified under this heading. The intervention of a qualified technician is required. Alarms which do not come under any of these headings do not require any action if arising separately. MAIN PAGE HEADING ALARMS MESSAGE CONDITION TESTING BATTERY NORMAL EPO ACTIVE WARNING NOT CALIBRATED FAULT TESTING AUTONOMY WARNING SYSTEM TEST MODE FAULT page 52 -- MI00/10056 rev.1--05/2001 a) When the battery is discharging, the machine displays the residual autonomy and the discharging time information. 1. If no information on autonomy is available, then the following message is displayed: BATTERY DISCHARGING AUT calc DIS xx min where xx represents the discharging time 2. Where AUTONOMY information is available, the following message will appear: BATTERY DISCHARGING AUT yy min DIS xx min where yy represents the residual autonomy of the batteries. b) In overload condition, the machine calculates the time remaining before the inverter is switched off. Under this condition, the following message is displayed: OVERLOAD INV STOP xx min: yy:s If the inverter is inhibited due to overloading, the time at which the inverter will be reactivated is displayed, with the following message: STOP DUE TO OVERLOAD RESTART IN xx min: yy: s MI00/10056 rev.1--05/2001-- page 53 RECTIFIER/BATTERY ALARMS MESSAGE CONDITION NOT CALIBRATED FAULT DC FEEDBACK FAULT FAULT VERIFY DC FEEDBACK NORMAL PRIMARY SUPPLY FAULT WARNING PHASE SEQUENCE ERROR FAULT BATTERY FAULT FAULT PCB SUPPLY FAULT FAULT BATT CONTACTOR OPEN - BATTERY DISCHARGING WARNING SHUTDOWN IMMINENT WARNING DC VOLTAGE HIGH FAULT DC VOLTAGE LOW WARNING INPUT SWITCH OPEN FAULT HARMONIC FILTER OPEN FAULT RECTIFIER ALARM FAULT RECTIFIER INHIBITED RECTIFIER BLOCKED BATT. CHARGE INHIBIT page 54 -- MI00/10056 rev.1--05/2001 WARNING FAULT WARNING INVERTER ALARMS MESSAGE NOT CALIBRATED PCB SUPPLY FAULT OUT OF SYNC DESATURATION OVER TEMPERATURE BYPASS SWITCH CLOSED SHUTDOWN IMMINENT DC VOLTAGE HIGH DC VOLTAGE LOW INVERTER NOT RUNNING INVERTER INHIBITED INVERTER BLOCKED INVERTER VOLTS HIGH INVERTER VOLTS LOW OVERLOAD STOP DUE TO OVERLOAD CURRENT LIMIT INV.ST. SWITCH FAULT INV.FREQ.OUT RANG. 8% INV. FEEDBACK FAULT VERIFYING INV. FREQ. VERIFYING BATT. CONT. INV.FREQ.OUT 1% CONDITION FAULT FAULT WARNING FAULT FAULT FAULT WARNING FAULT WARNING FAULT FAULT FAULT FAULT FAULT WARNING FAULT WARNING FAULT FAULT FAULT FAULT MI00/10056 rev.1--05/2001-- page 55 LOAD/RESERVE ALARMS MESSAGE NOT CALIBRATED LOAD ON RESERVE LOAD NOT SUPPLIED BYPASS SWITCH CLOSED RESERVE SUPPLY FAULT RESERVE FREQ FAULT RESERVE VOLTS HIGH RESERVE VOLTS LOW ST. SW. BLOCKED ON INV ST. SW. BLOCKED ON RES INV.ST. SWITCH FAULT OVERLOAD OUTPUT SWITCH OPEN RESERVE SWITCH OPEN PHASE SEQUENCE ERROR RESERVE INHIBITED BACKFEED PROT ACTIVE page 56 -- MI00/10056 rev.1--05/2001 CONDITION FAULT WARNING FAULT FAULT WARNING WARNING WARNING WARNING FAULT FAULT FAULT WARNING FAULT FAULT FAULT WARNING FAULT 10.6 Power History The power history is only available when the inverter is blocked; it provides a visual display of the status of the alarms and measurements over a period of 10 seconds before and 1 second after the inverter stops in steps of 0.1 s. The power history is lost when the inverter is restarted. Figure 20 provides a graphic representation of how to access the Power History. Fig.20: Power History Structure LOAD ALARMS BATTERY TEST SELECT POWER HISTORY DOWN TO ACCESS POWER HISTORY MATRIX Time (seconds) -10 Measurements Alarms POWER HISTORY UP TO EXIT Initial position Inverter Shutdown 0 +1 Typical Power History Display Measurement Alarm RECTIFIER +0.3 SEC VDC = 327V IB = 5A -5.3 SEC ON OVER TEMPERATURE MI00/10056 rev.1--05/2001-- page 57 10.7 Battery Test The EDP70 PLUS has an automatic battery control function which checks the condition of the battery periodically without affecting the output in any way. While this test is being carried out, the message »TESTING BATTERY» will appear. This test can also be activated manually. Return to the main title page so that ‘SYSTEM NORMAL’ is displayed. UPS xx KVA SYSTEM NORMAL system normal message PRESS SIMULTANEOUSLY (The test is disabled if the BATTERY TEST selected is NONE) UPS xx KVA TESTING BATTERY 10.8 The battery test is underway and takes approx. 1 minute. If the test is completed without giving off any alarm, then the system returns to normal operating mode; otherwise, the alarm message »BATTERY FAULT» is displayed. Battery Autonomy Test The EDP70 PLUS has a battery autonomy test which disables the rectifier manually. To carry out this test, return to the main title page so that ‘SYSTEM NORMAL’ is displayed. UPS xx KVA SYSTEM NORMAL system normal message PRESS SIMULTANEOUSLY and keep pressed for 2 seconds (The test is diabled if the BATTERY TEST selected is NONE) UPS xx KVA TESTING AUTONOMY The battery starts to discharge completely thereby allowing the autonomy to be checked. Once the battery has been discharged, the test comes to an end automatically and the rectifier restarts. To interrupt BATTERY autonomy Test, at any time: PRESS SIMULTANEOUSLY pressed for 2 seconds 10.9 and keep Resetting data loss manually If the message »NOT CALIBRATED» appears on the main title page, this means that data (language and total number of mains failures) which do not directly affect the functioning of the machine have been lost. Despite this, page 58 -- MI00/10056 rev.1--05/2001 data has still been lost and the intervention of a qualified technician is required.It is, nevertheless, possible to reset the normal operating mode by selecting the language desired as described under sect. 7.0. MI00/10056 rev.1--05/2001-- page 59 11.0 COMPUTER INTERFACE 11.1 AS400 The EDP70 PLUS UPS is fitted with a 9 pin female ‘D’ type socket for direct connection to a IBM AS/400 computer or equivalent, see figure 21. This facility can also be used with operating system software of other manufacturers. The function of the pins on the socket are shown below: Pin Number DESCRIPTION FUNCTION NUMBER 8 EDP70 PLUS UPS ON The UPS is supplying the load. 6 RESERVE TO LOAD The reserve AC supply is supplying the load. 9 UTILITY SUPPLY FAIL The AC utility supply to the UPS has failed. 7 BATTERY LOW The battery capacity is at a minimum and the inverter will shortly shut down and the load will be automatically transferred to the reserve AC supply. 5 COMMON All the above are connected to common when the function is true. Fig.21: EDP 70 Plus Computer Interface Pin Layout page 60 -- MI00/10056 rev.1--05/2001 11.2 RS232 The EDP70 PLUS UPS is fitted with a 9 pin male ‘D’ type plug which enables a communication link to be established between a computer and the microprocessor controller in the EDP70 PLUS UPS. The link allows the Chloride ‘EASY PLUS’ and ‘LIFE 2000’ software to be run on an IBM compatible PC. The link also allows the communications with a Master JBUS and Multicom/LIFE 2000 adapter. The function of the pins on the socket are shown below: The function of each pin is the following : Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 DCD RXD TXD DTR GND DSR RTS CTS (Data Carrier Detect) (Received data) (Transmitted data) (Data terminal ready) (Ground) (Data Set Ready) (Request To Send) (Clear To Send) The signals applied on each pin follows the standard EIA RS232. 12.0 REMOTE ALARMS Remote indication of the state of the EDP70 PLUS UPS is provided by a 15 pin female ‘D’ type socket and is designed to be used in conjunction with the Chloride EDP Remote Alarm Unit. The function of the pins on the socket are shown below: Fig.22: EDP70 PLUS Remote Alarms Pin Layout Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 Pin 10 System normal signal System normal and system summary alarm ground Inverter fail signal Inverter fail ground Reserve to load signal Reserve to load ground Primary supply failure signal Primary supply failure ground Shutdown imminent signal Shutdown imminent ground Pin11, 12 supply: 18V/200mA nominal AC output Pin 15 Summary alarm signal Pins 1,2 and15 are available for use as a remote summary alarm indicator in alternative to the Chloride Remote Alarm Unit. All pins are volt free contacts which are capable of carrying a current of 0.5 A and switching 30 V. MI00/10056 rev.1--05/2001-- page 61 13.0 BATTERIES 13.1 EDP70 PLUS/24/18/12 : Battery Installation/Start-up SAFETY - Ensure all the Switches are turned to OFF before starting to install the batteries. If any Switches are not turned to OFF the equipment and battery may be damaged. It is also essential for safety reasons that the battery connectors be disconnected before removing the fuse F2 (located behind the hinged panel, see figure 23) to interrupt the battery circuit. - Stand on a rubber mat and use insulated tools. - Remove all personal effects, rings, watches, pens, which might cause a short circuit when working on the battery. Batteries are live at all times and short circuits can melt metals and cause injury, damage or fire. - DO NOT smoke or use naked flames, and avoid creating arcs or sparks when working on the equipment; do not wear clothes which may generate static electricity. - The sealed lead-acid batteries contain sulphuric acid. If a battery container is broken any acid leaking will cause burns on contact with skin and attack metal, paint and fabrics. Any area contaminated with acid should be thoroughly washed with large volumes of clean water. Rubber gloves should be worn when handling damaged batteries. i) Remove front panel see figure 10 ii) Remove the battery compartment panel by unscrewing the fixing screws at the front. DO NOT remove the safety ground connection. Battery connections are provided with the UPS. Each battery is provided with fastenings. Internal batteries are housed on three shelves at the bottom of the equipment as shown on figure 23. If the batteries are fitted, starting with the lower shelf first, remove the packaging. Connect the batteries to the UPS using the plug/socket connectors provided. If batteries are not already assembled on the shelves arrange then as figures 24 (depending on the battery size), strapping the batteries to the tray as shown. Starting with the lower shelf, fit and connect the batteries. Ensure that the polarities are correct in accordance with the relevant battery layout diagram. For each shelf make sure that the polarities are correct and the overall battery shelf voltage is at least 108v for the bottom two shelves and 72v for the top shelf. Replace the fuse F2, then connect the intershelves connectors and all panels in reverse order of removal before operating the equipment. page 62 -- MI00/10056 rev.1--05/2001 13.2 EDP70 PLUS/24/18/12 : Optional Battery Cubicle The battery autonomy can be increased by employing either one or two optional battery cubicles. Both the UPS and battery cubicles are similar in appearance, however, there is no display panel in the battery cubicle. The battery cubicle has independent fuse located internally. To connect the battery cubicle to the EDP70 PLUS UPS follow the following procedure: 1. Shutdown the UPS using the procedure set out in section 9. Access the terminal rail. 2. Disconnect the battery connectors of the internal battery, then remove the fuse F2 located behind the hinged panel, see figure 23. 3. Be sure that the battery on the cubicle are disconnected. Remove the fuse of the battery cubicle. 4. Wire the cubicle according to the extension battery cubicle wiring instructions and the relevant battery layout diagram. 5. Replace the fuses F2 both on the cubicle and the UPS, then connect all the intershelves connectors, and all the panels and restart UPS using the procedure set out in section 7. Fig. 23 = EDP70 PLUS/24/18/12: Internal Battery Shelves FUSE F2 SHELF RETAINING SCREW SHELF GUIDE MI00/10056 rev.1--05/2001-- page 63 13.3 EDP70 PLUS above 20kVA: Battery Installation/Start-up SAFETY - Ensure the Equipment ON/OFF Switch is turned to OFF before starting to install the batteries. If the Equipment ON/OFF Switch is not turned to OFF the equipment and battery may be damaged. It is also essential for safety reasons that the battery connectors are disconnected before to remove the fuse of the battery cubicle. - Stand on a rubber mat and use insulated tools. - Remove all personal effects, rings, watches, pens, which might cause a short circuit when working on the battery. Batteries are live at all times and short circuits can melt metals and cause injury, damage or fire. - DO NOT smoke or use naked flames and avoid creating arcs or sparks when working on the equipment; do not wear clothes which may generate static electricity. - The sealed lead-acid batteries contain sulphuric acid. If a battery container is broken any acid leaking will cause burns on contact with skin and attack metal, paint and fabrics. Any area contaminated with acid should be thoroughly washed with large volumes of clean water. Rubber gloves should be worn when handling damaged batteries. 13.4 EDP70 PLUS above 20kVA: Battery Cubicle For these sizes of EDP70 PLUS, the batteries are housed in battery cubicles. Both the UPS and battery cubicles are similar in appearance, however, the battery cubicle does not have a dusplay. The battery cubicle has a separate fuse, located internally. To connect the battery cubicle to the EDP70 PLUS UPS follow the following procedure: 1. Shutdown the UPS using the procedure set out in section 9. Access the terminal rail. 2. Be sure that all the batteries in the cubicle(s) are disconnected. Remove the fuses from the battery cubicle(s). 4. Wire the cubicle according to the extension battery cubicle wiring instructions and the relevant battery layout diagram. 5. Replace the fuses on all the cubicles then connect all the inter-shelf connectors, and replace all the panels and restart UPS using the procedure described in section 7. 14.0 MAINTENANCE AND SPARE PARTS The EDP70 PLUS UPS is designed to be virtually user maintenance free, requiring with a damp cloth or non-abrasive cleaner. only the occasional wipe Spares kits are available for the EDP70 PLUS series, please contact a Chloride Power Electronics service center for details. page 64 -- MI00/10056 rev.1--05/2001 EDP70 PLUS SYSTEM LOG It is recommended that any maintenance action or failure of the SYSTEM be recorded in this log. Date Time Event Action/Result MI00/10056 rev.1--05/2001-- page 65
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : Yes Creator : Microsoft Word Create Date : Wednesday, August 08, 2001 11:56:10 AM Title : REV1.PDF Author : Unknown Producer : Acrobat PDFWriter 3.02 for Windows Subject : Modify Date : 2002:07:03 12:18:38-05:00 Page Count : 65EXIF Metadata provided by EXIF.tools