LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0806497
User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 24
Download | |
Open PDF In Browser | View PDF |
INSTALLATION INSTRUCTIONS '1_2006 Lennox Industries Jnc, Dallas, Texas, USA HPXA16 Series Units HEAT PUMP 504,954M _Technical UNITS LLJJ 08/06 Publications Litho U.S.A. Supersedes 03/06 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE _, WARNING CAUTION A IMPORTANT _, IMPORTANT HPXA16 Outdoor Unit .......................... Shipping & Packing List ........................ General Information ........................... Unit Dimensions ............................... Parts Arrangement ............................ Setting the Unit ............................... Electrical ..................................... Refrigerant Piping ............................. Refrigerant Metering Device .................... Flushing Existing Line Set & Indoor Coil .......... Manifold Gauge Set ........................... Service Valves ................................ Leak Testing .................................. Evacuation ................................... Start-Up ...................................... Refrigerant Charging .......................... System Operation ............................. Defrost System ............................... Maintenance .................................. Optional Accessories .......................... Check Points ................................. 1 2 2 2 3 3 4 6 8 8 10 10 11 12 12 12 15 16 21 21 22 Homeowner Information: Maintenance .................................. Thermostat Operation .......................... 23 24 Lennox HPXA16 outdoor units use HFC-410A refrigerant. This unit must be installed with a matching indoor coil and line set as outlined in the Lennox Engineering Handbook. Elite ® Series HPXA16 outdoor units are designed for use in check expansion valve (CTXV) systems only and must not be used with other refrigerant flow control devices, See Lennox Engineering Handbook list of indoor expansion valve kits (ordered separately). 08/06 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII Page 1 504,954M IIIIIIIIIIIIIIIIIIIIIIIIIIIIII Check unit for shipping damage, Consult last carrier immediately if damage is found, 1 -Assembled HPXA16 outdoor unit These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation, WARNING 2 - Grommets (for liquid and vapor lines) When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened, Table 1 shows torque values for fasteners. Table 1 Torque Requirements Part Recommended Torque Service valve cap 8 ft.- lb. 11 NM Sheet metal screws 16 in.- lb. 2 NM Machine screws #10 28 in.- lb. 3 NM Compressor bolts 90 in.- lb. 10 NM Gauge port seal cap 8 ft.- lb. 11 NM INLET AIR Model A B C HPXA16-024,-036 30-7/8 (784) 12-3/4 (324) 17-1/4 (438) HPXA16-048, 44-7/8 (1140) 14-1/4 (362 18-3/4 (476) -060 O COMPRESSOR j INLET AIR z_ Top View ELECTRICAL 32-1/8 (816) i_ i _i VAPOR LINE INLET'-_ (114) 4-1/2 A C J_ 2-_/16 B 2 (51) LIQUID LINE INLET Page 2 504954M 08/06 1-3/6 (35) INLET AIR Coil drain outlets (around perimeter of base) RUN CAPACITOR START CAPACITOR (-024 UNIT ONLY) CHARGE COMPENSATOR (-048 UNITS) TXV/CHECK VALVE DISCHARGE LINE CONTACTOR COMPRESSOR TERMINAL PLUG VAPOR VALVE AND GAUGE PORT VAPOR LINE LOW PRESSURE TWO-STAGE SWITCH DRIER DISCHARGE TEMPERATURE SENSOR HIGH PRESSURE COMPRESSOR SWITCH Figure 1 Installation CAUTION Clearances as noted These units operate under a wide range of weather conditions; therefore, several factors must be considered when positioning the outdoor unit. The unit must be positioned to give adequate clearances for sufficient airflow and servicing. Refer to figure 2 for installation clearances. 1. Place a sound-absorbing material, such as Isomode, under the unit if it will be installed in a location or position that will transmit sound or vibration to the living area or adjacent buildings. 2. Mount unit high enough above ground or roof to allow adequate drainage of defrost water and prevent ice build-up. (762 mm) ,,11- 30" _ _} not_ l as noted J NOTE - A service access clearance of 30" (762 mm) must be maintained in front of the service access panel. Clearance to one side must be 36" (914 mm), Clearance to one of the remaining two sides may be 12" (305 mm) and the final side may be 6" (152 ram). NOTE -A clearance of 24" (610 mm) must be maintained between two units. 3. In heavy snow areas, do not locate unit where drifting will occur. The unit base should be elevated above the depth of average snows. NOTE -Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a support frame is constructed, it must not block drain holes in unit base. NOTE -48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm). Figure 2 4. When installed in areas where low ambient temperatures exist, locate unit so winter prevailing winds do not blow directly into outdoor coil. 5. Locate unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil or into unit. Page 3 HPXA16 SERIES Slab Mounting When installing unit at grade level, top of slab should be high enough above the grade so that water from higher ground will not collect around unit, See figure 3. Slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1,5 m), This will prevent ice build-up under unit during a defrost cycle. Refer to roof mounting section for barrier construction if unit must face prevailing winter winds. Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. _WARNING Slab Mounting discharge structure building air 2 DEGREES OR 2 IN. PER 5 FOOT (51 MM PER 1.5 M) SLOPE TOLERANCE AWAY FROM BUILDING STRUCTURE ground / / mounting slab level Figure Install line voltage power supply to unit from a properly sized disconnect switch, 2, Ground unit at unit disconnect switch or to an earth ground, NOTE - Connect conduit to the unit using a proper conduit fitting. Units are approved for use only with copper conductors, Refer to figure 5 for high voltage field wiring diagram, A complete unit wiring diagram is located on the back side of the unit's access panel. . 3 Roof Mounting Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications. If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. See figure 4. Size barrier at least the same height and width as outdoor unit, Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds. Typical START Field Wiring CAPACITOR C7 POTENTIAL Diagram AI08 RELAY T4 KSI OUTDOOR FAN GROUND DEFROST r_ CONTROL 6[_ LUG K195 SOLENOID TRANSFORMER GND RELA_ ORANGE-COMMON BLACK-RUN PURPLE-CAPACITOR _2 C_8 ILl DUAL CAPACITOR Rooftop Wind Barrier Construction prevailing winter winds wind barrier I inlet air I T © _Lmm/ 3rotection size Figure 5 NOTE - For proper voltages, select thermostat wire gauge per the following chart: O I I inlet air Wire run length AWG # Insulation type less than 100' (30m) 18 color-coded, temperature more than 100' (30m) 16 rating 35°C minimum ,J . O Figure inlet air 4 . In the U,S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Page 4 08/06 60/1 NOTE - For use with copper conductors only. Refer to unit rating alate for minimum circuit ampacity and maximum over-current (21'0 I 504954M 230/ CONTACTOR WARNING! - ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with national and local codes. O I 208KI COMPRESSOR Install room thermostat (ordered separately) on an inside wall approximately in the center d the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations, Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit, See figures 6 through 8. NOTE - 24V, Class II circuit connections are made in the low voltage junction box. HPXA16 Outdoor Thermostat Unit and Blower Designations HPXA16 Unit ] Thermostat A2 Thermostat Indoor Unit TB1 I I ® I I Unit and CB31MV/CB32MV Designations (Some connections may not apply. Refer to specific thermostat and indoor unit.) r i CB31MV/ I Signature_at q Outdoor Unit // CBX32MV TB1 A2 Thermostat (Some connections may not apply. Refer to specific thermostat and indoor unit Outdoor Unit Outdoor I _--- _ L_I_ i I I i _.. ® ®--i @ ® (_) [ 1R4 T" I I I I ©1 ®1 q--I-',Board , Defrost Y2 © _ LI__® __ I 'Board -iJ--i--_li-I i - J I: i I, :out L ..... --t Y2 OUT _ _ ® - +---®- @ I _ ) 6 --,_,--_DENOTES -- SW[TCH_ Wiring Diagram $87 LDW PRESSURE SWITCH -- -- OPTIONAL LI REVERSING VALVE RTE3 AMBIENT SENSOR A NOTEFOR USE WITH COPPER CONDUCTORS ONLY.REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE A REFER TO COMPRESSOR IN UNIT FOR ACTUAL TERMINAL ARRANGEMENT, A WARNINGELECTRIC SHOCK HAZARD,CAN CAUSE INJURY OR DEATH,UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES• A A A A A REMOVE COMPONENTS LINE VOLTAGE FIELD INSTALLED CLASS II VOLTAGE FIELD INSTALLED _L_ RT21 DEFROST CDIL SENSOR I Figure 7 HPXA16 BI COMPRESSOR @f @ I k $4 Z_ @.L -i ' L HIGH PRESSURE i i I, i_ Figure I I [Defrost, _ i i - v- -• If RT28 OISCHARGE SENSOR RTi4 _ COIL FAN @ FOR TWO K31 AND C7 SII AND KSB ARE ARE STAGE TEMP USED ON COOL IOPTIONAL) 024 OPTIONAL UNITS LOW L3¢,SECOND STAGE, SOLENOID COMPRESSOR, COIL IS 24VOC, 24VAC T_OY_IU TER_[N_. z_K5B-I z_Y2 BLAC_I JUMPER SENSOR,OUTDOOR OUT NOTUSEDIN ONLY AMBIENT HARMONYIIIZONE CON_ OL APPLICATIONS SIGNATURE 81MBB CB31MV CBX32MV TBI AIO8 CONTROLS IS LOCATED IN DO NOT CONNECT A2 THERMOSTAT KI 49 _MB @ -(z)OIS -- I ®® rl K2 r I I II FT II II II II II II P2 s© 24v HI-PS '© © BLUE Z_ { _ Figure J __ A rl rl LO-PS __YI OUT 9 IRT,A I I wF -_):>-IQ-I--4_-I- F" , _ Y2 OUT _-_ DEFROST BOARD DETAIL 1 -- 0 /I °_ - c_ BLUE WIRE WITH m _1 o CRIMPED TERM,NAL I 111 _'/'_lil _ _'_-_-_ Shipped as shown wire; cut off terminal and above splice with blue terminal wire withcrimped Y2 wire totoblue indoor unit.use terminal or 8 Page 5 HPXA16 SERIES 1, Placement--Be aware some localities are adopting sound ordinances based on how noisy the unit is at the neighbors' home, not at the original installation. Install the unit as far as possible from the property line, When possible, do not install the unit directly outside a bedroom window, Glass has a very high level of sound transmission, Figure 9 shows how to place the outdoor unit and line set, If the HPXA16 unit is being installed with a new indoor coil and line set, the refrigerant connections should be made as outlined in this section. If an existing line set and/or indoor coil is going to be used to complete the HPXA16 system, refer to the following section which includes flushing procedures. Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, nonflare) series line sets as shown in table 2 or use field-fabricated refrigerant lines. Valve sizes are also listed in table 2. Refrigerant Connections - HPXA16 with New Indoor Coil and Line Set Outside Unit Placement and Installation Matched If an existing indoor coil which was equipped with an RFCl metering device is being replaced, the liquid line must also be replaced prior to the installation of the HPXA16 unit. Table 2 Refrigerant Line Sets Field Connections Recommended Model -024 -036 -048 -060 Liquid Line 3/8in. Vapor Line 7/8 in (10 mm) 3/8 in, (10 mm) Line Set Liquid Line Vapor Line L15 Line Sets (22 mm) 3/8 in, (10ram) 7/8 in (22ram) L15-65 15ft,-50ft, (4.6 m - 15 m) 1-1/8 in. (29 mm) 3/8 in, (10 ram) 1-1/8 in, (29 ram) Field Fabricated Two 90 ° elbows installed in line set will reduce line set vibration, NOTE - Units are designed for fine sets of up to fifty feet (15m), Figure 9 Installing Refrigerant Line Pay close attention to line set isolation during installation of any heat pump or a/c system. When properly isolated from building structures (walls, ceilings, floors), the refrigerant lines will not create unnecessary vibration and subsequent noises. Also, consider the following when placing and installing a high-efficiency outdoor unit: Refrigerant Line Sets: 2. Line Set Isolation--The following illustrations demonstrate procedures which ensure proper refrigerant line set isolation, Figure 10 shows how to make a transition from horizontal to vertical. Figure 11 shows how to install line sets on vertical runs. Figure 12 shows how to install line sets on horizontal runs, Transition From ANCHORED HEAVY NYLON WIRE TIE Vertical To Horizontal AUTOMOTIVE MUFFLER-_PE HANGER WALL STUD WALL STUD Strap Liquid Line To Vapor Line Strap Liquid Line To Vapor Line UID LINE METAL SLEEVE LIQUID LINE VAPOR LINE - WRAPPED IN ARMAFLEX METAL SLEEVE Figure 10 Page 6 504954M 08/06 VAPOR LINE - WRAPPED IN ARMAFLEX Refrigerant Line Sets: Installing Vertical Runs (new construction shown) NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside wall. OUTSIDE WALL IMPORTANT - Refrigerant lines must not contact wall. VAPOR LINE LI -_. UID LINE WIRE TIE INSIDE WALL - STRAP SLEEVE VAPOR LINE WRAPPED "_- WIRE TIE "_ ----------WOOD IMPORTANT! Refrigerant lines must not contact structure. _. _ BLOCK WIRE TIE STRAP 1_ PVC PIPE CAULK FIBERGLASS INSULATION SLEEVE Figure 11 Refrigerant Line Sets: Installing To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties. Runs WIRE TIE 8 feet STRAPPING Horizontal (Around vapor line only) MATERIAL (Around vapor line only) FLOOR JOIST OR ROOF RAFTER r\ TAPE OR WIRE TIE 8 feet METAL SLEEVE FLOOR JOIST OR ROOF RAFTER TAPE OR WIRE TIE Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line. . _rl Figure 12 Page 7 HPXA16 SERIES Isolation Grommets II Locate the provided isolation grommets. Use a knife to slit the webbing on each grommet. Slide larger grommet onto vapor line and smaller grommet onto liquid line. Insert grommets into mullion to isolate refrigerant lines from sheet metal edges, Device Installation O-RING _-_% @/ EXPANSION /O-RING / ° I WARNING Metering _ o DISTRIBUTOR __ 13 A, IMPORTANT NOTE -If the indoor unit line and set are new, skip this section and go on to the Manifold Gauge Set section. _WARNING 4, Quench the joint with water or a wet cloth to prevent heat damage to the valve core and opening port, NOTE - The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing and rigidity. HPXA16 units may be used in check expansion valve (CTXV) systems only, See indoor coil installation instructions and the Lennox engineering handbook for approved HFC-410A TXV match-ups and application information, NOTE - HFC-410A systems will not operate properly with an HCFC-22 valve. Check Expansion Valve Systems Check expansion valves equipped with either Chatleff or flare-type fittings are available from Lennox. Refer to the Engineering Handbook forapplicable expansion valves for use with specific match-ups. If you install a check expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before the check expansion valve is installed. See figure 13 for installation of the check expansion valve. Page 8 504954M 0_06 LITQuU;D LINE NOTE - Ifnecessary,remove HCFC-22 flowcontrol device (fixed orifice/check expansionvalve)from existing linesetbeforeinstalling HFC-410A approved expansionvalveand o-ring. Brazing Connection Procedure 1, The end of the refrigerant line must be cut square and its internal shape must remain round. The line must be free of nicks or dents and must be deburred (I,D, and O.D,) 3, Use silver alloy brazing rods (5 or 6 percent minimum silver alloy for copper4o-copper brazing or 45 percent silver alloy for copper-to-brass or coppeFto-steel brazing). Wrap a wet cloth around the valve body and the copper tube stub. Remove light maroon washers from service valves and shield light maroon stickers in order to protect them during brazing, Braze the line set to the service valve, (See NOTE) STRA, NER Figure 2, Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the system. VALVE & A IMPORTANT If the existing outdoor unit is equipped with manual shut-off valves AND you plan to use NEW HCFC-22 refrigerant to flush the system • Start the existing HCFC-22 system in the cooling mode and close the liquid line valve. • Pump all of the existing HCFC-22 refrigerant back into the outdoor unit. (It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.) • When the low side system pressures reach 0 psig, close the vapor line valve. • Disconnect all power to the existing outdoor unit. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. • Disconnect the liquid and vapor lines from the existing outdoor unit. 2. Remove the existing outdoor unit. Set the new HFC-410A unit and follow the brazing connection procedure (see page 8) to make line set connections. DO NOT install metering device at this time. IMPORTANT CAUTION Required Equipment You will need the following equipment in order to flush the existing line set and indoor coil: two clean HCFC-22 recovery bottles, an oilless recovery machine with a pump down feature, and two sets of gauges (one for use with HCFC-22 and one for use with the HFC-410A). 3. Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit or open the outdoor unit service valves at this time. Flushing Procedure 1. Remove existing HCFC-22 refrigerant using the appropriate procedure below. If the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational AND you plan to use the existing HCFC-22 refrigerant to flush the system • Disconnect all power to the existing outdoor unit. • Connect to the existing unit, a clean recovery cylinder and the recovery machine according to the instructions provided with the recovery machine. • Remove all HCFC-22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant. • Disconnect the liquid and vapor lines from the existing outdoor unit. IMPORTANT 4. Remove the existing refrigerant flow control orifice or thermal expansion/check valve before continuing with flushing procedures. The existing devices are not approved for use with HFC-410A refrigerant and may prevent proper flushing, Use a field-provided fitting to reconnect the lines. Flushing Connections Inverted HCFC-22 Cylinder (Contains clean HCFC-22 to be used for flushing) Low Pressure EXISTING VAPOR LINE EXISTING LIQUID LINE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE NOTE - The inverted HCFC-22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system. Tank Inlet Return Discharge RECOVERY CYLINDER High Pressure RECOVERY MACHINE Figure 14 Page 9 HPXA16 SERIES 5, Remove the pressure tap valve cores from the HPXA16 unit's service valves. Connect an HCFC-22 cylinder with clean refrigerant to the vapor service valve, Connect the HCFC-22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set. Front-Seated (Valve Shown Closed) Line Service Valve SERVICE Insert hex wrench here 6, Set the recovery machine for liquid recovery and start the recovery machine, Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor coil. 7, Invert the cylinder of clean HCFC-22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine, 8, After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered, Liquid STEM CAP To indoor coil To outdoor coil (Valve Shown Open) insert hex wrench here NOTE - A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush, Each time the system is flushed, you must allow the recovery machine to pull a vacuum on the system at the end of the procedure. 9, Close the valve on the inverted HCFC-22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off. 10, Use dry nitrogen to break the vacuum on the refrigerant lines and indoor coil before removing the recovery machine, gauges and HCFC-22 refrigerant drum. Reinstall pressure tap valve cores into HPXA16 service valves. SERVICE PORT STEM CAP To indoor coil Service port Is open to line set when valve is To outdoor coil closed (front seated) Figure Bali-Type 15 Vapor Valve (Valve Closed) STEM CAP 11. Install the provided check expansion valve (approved for use with HFC-410A refrigerant) in the liquid line at the indoor coil, OUTDOOR USE ADJUSTABLE TO OPEN: TO CLOSE: WRENCH ROTATE STEM _.. STEM (STEM ._L_I:,_ \ ROTATE STEM CLOCKWIS_ COUNTER-CLOCKWISE 90 °. BALL (SHOWN __ TO _; ,NDOOR COIL SCHRADER VALVE SERVICE PORT CAP 16 Each valve is equipped with a service port which has a factory-installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal. Page 10 08/06 COIL _._---,_ Figure 504954M _ CLOSEO Manifold gauge sets used with systems charged with HFC-410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 - 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating, The liquid line and vapor line service valves (figures 15 and 16) and gauge ports are used for leak testing, evacuating, charging, and checking charge. See table for torque requirements. TO , WARNING IMPORTANT To Access Schrader Port: 1. Remove service port cap with an adjustable wrench, 2. Connect gauge to the service port. 3, When testing is completed, replace service port cap. Replace the stem cap. Tighten finger tight; then torque per table 1 (Page 2), To Open Front-Seated Service ,&WARNING Valves: 1. Remove stem cap with an adjustable wrench, 2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go, 3. Replace the stem cap, Tighten finger tight; then torque per table 1 (Page 2), To Close Front-Seated Service Valves: 1. Remove the stem cap with an adjustable wrench, 2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly, 3, Replace the stem cap, Tighten finger tight; then torque per table 1 (Page 2), Bali-Type Service Valve (Vapor Line) Ball-type service valves function the same way as the other valves; the difference is in the construction, These valves are not rebuildable, If a valve has failed, you must replace it. A ball valve is illustrated in figure 16, The ball valve is equipped with a service port with a factoryinstalled Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leakfree seal, After the line set has been connected to the indoor and outdoor units, the line set connections and indoor unit must be checked for leaks, Xk WARNING Using an Electronic Leak Detector 1. Connect a cylinder of HFC-410A to the center port of the manifold gauge set. 2, With both manifold valves closed, open the valve on the HFC-410A cylinder (vapor only), 3, Open the high pressure side of the manifold to allow the HFC-410A into the line set and indoor unit, Weigh in a trace amount of HFC-410A, [A trace amount is a maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure,] Close the valve on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set, Disconnect the HFC-410A cylinder. 4, Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set. 5, Connect the manifold gauge set high pressure hose to the vapor valve service port. (Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.) 6, Adjust the dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit. 7, After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge dry nitrogen and HFC-410A mixture. Correct any leaks and recheck, ,& IMPORTANT Page 11 HPXA16 SERIES gauge valves to release the dry nitrogen from the line set and indoor unit. Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts, , g, A, IMPORTANT Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC-410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit, Close manifold gauge valves and shut off the HFC-410A cylinder and remove the manifold gauge set, 1, Connect manifold gauge set to the service valve ports as follows: • low pressure gauge to vapor line service valve • high pressure gauge to liquid line service valve 2. Connect micron gauge. A, IMPORTANT 3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set, 4, Open both manifold valves; start the vacuum pump. 5, Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29,01 inches of mercury). During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure, A rapid rise in pressure indicates a relatively large leak, If this occurs, repeat the leak testing procedure, 1, Rotate fan to check for frozen bearings or binding, 2, Inspect all factory- and field-installed wiring for loose connections. 3, After evacuation is complete, open the liquid line and vapor line service valves (counterclockwise) to release refrigerant charge (contained in outdoor unit) into the system, 4, Replace stem caps and secure finger tight, then tighten an additional (1/6) one-sixth of a turn, 5, Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit nameplate. If not, do not start the equipment until the power company has been consulted and the voltage condition has been corrected. NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure, Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure, 6, When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit, Close the manifold gauge valves, 6, Set the thermostat for a cooling demand. Turn on power to indoor blower unit and close the outdoor unit disconnect to start the unit, 7, Recheck voltage while the unit is running. Power must be within range shown on the nameplate. I WARNING 7, Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder, Open the manifold This system is charged with HFC-410A refrigerant which operates at much higher pressures than HCFC-22. The field-provided check expansion valve for the indoor unit must be approved for use with HFC-410A. This unit is NOT approved for use with coils which include metering orifices or capillary tubes. Factory Charge The unit is factory-charged with the amount of HFC-410A refrigerant indicated on the unit rating plate, This charge is based on a matching indoor coil and outdoor coil with a 15 foot (4,6 m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment, Page 12 504954M 0_06 HPXA16 Cooling Cycle (Showing Gauge DISTRIBUTOR Manifold OUTDOOR Connections) UNIT NOTE _ARROWS INDICATE DIRECTION OF REFRIGERANT REVERSING FLOW VALVE CHECK VALVE BIFLOW FILTER / DRIER LOW OUTDOOR COIL HUGH PRESSURE EXPANSION/PRESSURE INDOOR I INI ..---1 I A I X N S VAPOR VA R VAPOR PORT SERVICE svc POR COMPRESSOR VALVE EXPANSION/CHECK Vl i VALVE -- -4_111 NOTE- Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging. Figure Table Refrigerant Charge (20_C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature. per Line Set Lengths Ounces per 5 feet (grams per 1.52 meter) adjust from 15 ft. (4.57m) line set* 3/8 in. (9.5ram) 3 ounces per 5 feet (85 grams per 1.52 meter) INDOOR COIL 17 3 Liquid Line Set Diameter , 5. The outdoor temperature will determine which charging method to use. Proceed with whichever of the following charging procedure deemed appropriate for the situation. *Add the amount shown if line length is greater than 15' (4.57m), subtract the amount shown if less than 15'. Charge Using the Weigh-in Method Outdoor Temperature < 65°F (18°C) If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. 1. Recover the refrigerant from the unit. IMPORTANT 2. Conduct leak check; evacuate as previously outlined. 3. Weigh in the unit nameplate charge. If weighing facilities are not available or if charging the unit during warm weather, use one of the following procedures. Checking Charge The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is determined by the outdoor ambient temperature. Measure the liquid line temperature and the outdoor ambient temperature as outlined below: 1. Connect the manifold gauge set to the service valves: • low pressure gauge to vapor valve service port • high pressure gauge to liquid valve service port Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC-410A. See figure 17. Charge Using the Subcooling Method Outdoor Temperature < 65°F (18°C) When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. It may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 325-375 psig (2240-2585 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liquid pressure is in the 325-375 psig (2240-2585 kPa) range. See figure 18. locking 2. Set the room thermostat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle. 3. Record outdoor ambient temperature thermometer. Coil side at a time with cardboard or plastic sheet untilcoil proper testing pressures *Outdoor should be blocked one are reached. using a digital cardboard *FouFsided 4. When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68 '_F Outdoor Figure or plastic sheet unit shown. 18 Page 13 HPXA16 SERIES 1. With the manifold gauge hose still on the liquid service port and the unit operating stably, use a digital thermometer to record the liquid line temperature. 2. At the same time, record the liquid line pressure reading, 3. Use a temperature/pressure chart for HFC-410A to determine the saturation temperature for the liquid line pressure reading, See table 4. Table 4 HFC-410A Temperature (°F) - Pressure (Psig) °F Psig °F Psig °F Psig °F Psig 32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8 34 105.0 65 184.3 96 299.4 127 457.6 35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5 37 111.4 68 194.1 99 312.7 130 475.6 38 113.6 69 197.3 100 317.2 131 39 115.8 70 200.6 101 321.8 40 118.0 71 203.9 102 326.4 41 120.3 72 207.2 103 42 122.6 73 210.6 43 125.0 74 214.0 44 127.3 75 45 129.7 76 46 132.2 47 frigerant. Be aware of the HFC-410A refrigerant cylindec It will be light maroon-colored. Refrigerant should be added through the vapor line valve in the liquid state. NOTE - Some HFC-410A cylinders are equipped with a dip tube that allows you to draw liquid refrigerant from the bottom of the cylinder without turning the cylinder upsidedown. The cylinder will be marked if it is equipped with a dip tube. Table Subcooling 5 Values for Charging Model Number Second Stage (High Capacity) Subcooling Values Conversion Temp. Liquid Line Temp. °F (°C) HPXA16-024 11.0+ 1 (6 + .5) 481.6 HPXA16-036 8.5 + 1 (4.7 + .5) 132 487.8 HPXA16-048 7.5 + 1 (4.1 + .5) 133 494.0 HPXA16-060 7.0 + 1 (3.9 + .5) 331.0 134 500.2 104 335.7 135 506.5 105 340.5 136 512.9 217.4 106 345.3 137 519.3 220.9 107 350.1 138 525.8 77 224.4 108 355.0 139 532.4 134.6 78 228.0 109 360.0 140 539.0 48 137.1 79 231.6 110 365.0 141 545.6 49 139.6 80 235.3 111 370.0 142 552.3 50 142.2 81 239.0 112 375.1 143 559.1 51 144.8 82 242.7 113 380.2 144 565.9 52 147.4 83 246.5 114 385.4 145 572.8 53 150.1 84 250.3 115 390.7 146 579.8 54 152.8 85 254.1 116 396.0 147 586.8 55 155.5 86 258.0 117 401.3 148 593.8 56 158.2 87 262.0 118 406.7 149 601.0 57 161.0 88 266.0 119 412.2 150 608.1 58 163.9 89 270.0 120 417.7 151 615.4 59 166.7 90 274.1 121 423.2 152 622.7 60 169.6 91 278.2 122 428.8 153 630.1 61 172.6 92 282.3 123 434.5 154 637.5 62 175.4 93 286.5 124 440.2 155 645.0 Charge Using the Approach Method Outdoor Temperature _>65°F (18°C) The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging. 1. Record outdoor ambient temperature thermometer, 2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize. 3. Compare stabilized pressures with those provided in tables 6 and 7, "Normal Operating Pressures." Xk IMPORTANT 4. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine subcooling. (Saturation temperature - Liquid line temperature = Subcooling) 5. Compare the subcooling value with those in table 5, If subcooling is greater than shown, recover some refrigerant, If subcooling is less than shown, add some re- Page 14 504954M 08/06 using a digital Table 6 HPXA16 COOLING Normal (Liquid Operating Pressures +10 & Vapor +5 psig)* -024 °F (°C)** 5. The difference between the ambient and liquid temperatures should match values given in table 8. If the values don't agree with the those in table 8, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature. -036 -048 -060 uqlvopuqlvapu lvo u lvo Table 8 First Stage (Low Capacity) 65 (18.3) 217 143 227 142 222 140 225 140 75 (23.9) 250 145 262 145 258 143 259 142 85 (29.4) 291 147 305 146 298 145 293 146 95 (35.0) 336 149 352 148 343 147 356 147 105 (40.6) 386 151 403 152 402 147 408 147 115 (49.0) 440 153 458 155 452 152 455 151 Approach Second Stage (High Capacity) ApModel Number proach Temperature Liquid Line Temp. Outdoor Ambient °F (°C) Second Stage (High Capacity) 65 (18.3) 222 143 244 136 232 134 249 126 75 (23.9) 256 145 282 139 266 136 289 134 85 (29.4) 302 145 325 142 309 139 330 140 95 (35.0) 349 147 377 144 359 142 378 143 105 (40.6) 403 149 428 146 410 144 433 146 115 (49.0) 464 152 488 148 468 147 492 149 *These are most-popular-match-up up, indoor air quality, and indoor **Temperature pressures. Indoor load cause pressures of the air entering the outside to vary coil. -048 -060 °F (°C)** First Stage (Low Capacity) 40 (4.4) 321 99 296 95 315 97 319 93 50 (10) 340 120 310 112 330 114 335 111 Second Stage (High Capacity) 20 (-7.0) 273 68 277 60 294 60 300 57 30 (-1.0) 296 80 296 74 303 75 312 70 40 (4.4) 321 95 321 88 314 90 323 83 50 (10) 341 115 341 104 325 106 339 97 *These are most-popular-match-up up, indoor air quality, **Temperature and indoor of the air entering pressures. Indoor load cause pressures the outside 4.0 + 1 (2.2 + .5) HPXA16-036 7.0 + 1 (3.9 + .5) HPXA16-048 8.0 + 1 (4.4 + .5) HPXA16-060 10.0 + 1 (5.6 + .5) Thermostat Operation Some indoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber indicating light). The thermostat is not included with the unit and must be purchased separately. match HPXA16 Normal Operating Pressures HEATING (Liquid +10 & Vapor +5 psig) -036 HPXA16-024 The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously. Table 7 -024 Values for Charging Emergency Heat (Amber Light) An emergency heat function is designed into some room thermostats. This feature is applicable when isolation d the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode. Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging. match to vary Filter Drier coil. 4. Use the same digital thermometer used to check outdoor ambient temperature to check liquid line temperature. Verify the unit charge using the approach method. The unit is equipped with which keeps the system necessary, order another replacement filter drier HFC-410A refrigerant. a large-capacity biflow filter drier clean and dry. If replacement is of like design and capacity. The must be suitable for use with Page 15 HPXA16 SERIES Defrost Defrost System Description The demand defrost controller measures differential temperatures to detect when the system is performing poorly because of ice build-up on the outdoor coil. The controller "self-calibrates" when the defrost system starts and after each system defrost cycle. The defrost control board components are shown in figure 19. Defrost Note - Component Control Locations Board Vary by Board TERMINATION PIN SETTINGS DEFROST _ AMBIENT THERMOSTAT PINS t_i _ DELAY -PINS Low Pressure Switch (LO-PS)--When the low pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is ignored under the following conditions: • during the defrost cycle and 90 seconds after the termination of defrost • when the average ambient sensor temperature is below 15° F (-9°C) • for 90 seconds following the start up of the compressor • during "test" mode Low Pressure psig. 24V TERMINAL STRIP CONNECTIONS Pressure TIONS 19 The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation. NOTE - The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles. Defrost Board Diagnostic LEDs The state (Off, On, Flashing) of two LEDs on the defrost board (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 10 (on page 20). 08/06 Switch 5-Strike Lockout The 5-strike pressure switch lockout condition can be reset by cycling OFF the 24-volt power to the control board or by shorting the TEST pins between 1 to 2 seconds. All timer functions (run times) will also be reset. If a pressure switch opens while the Y1 Out line is engaged, a 5-minute short cycle will occur after the switch closes. Defrost System Sensors Sensors connect to the defrost board through a field-replaceable harness assembly that plugs into the board (see figure 21 ). Through the sensors, the board detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. Figure 20 shows how the resistance varies as the temperature changes for both type of sensors. Sensor resistance values can be checked by ohming across pins shown shown in table 9. Page 16 504954M (auto reset) - trip at 25 psig; reset at 55 The internal control logic of the board counts the pressure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition. PRESSURE / SWITCH CIRCUIT CONNEC- _, Figure Connections Defrost Board Pressure Switch Settings High Pressure (auto reset) - trip at 590 psig; reset at 418 psig. LEDS REVERSING VALVE Switch High Pressure Switch (HI-PS)--When the high pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. PLUG IN (COIL & AM_ BENT -SENSOR SENSORS) Pressure The unit's automatic reset pressure switches (LO PS - $87 and HI PS - $4) are factory-wired into the defrost board on the LO-PS and HI-PS terminals, respectively. Manufacturer. TEST PINS Board Table NOTE - When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 9, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced. NOTE - Under certain ambient conditions, the internal cabinet temperature of the HPXA16-036 cabinet will affect the temperature that is sensed by the coil sensor. This can set up a condition where the defrost board may not initiate a defrost cycle. To overcome this issue, the coil sensor should be moved to the alternate location on the other side of the cabinet to the coil hairpin shown in figure 21. Ambient Sensor Temperature 9 / Resistance Range Pins/VV ire Color Sensor Temperature Range °F (°C) Resistance values range (ohms) Outdoor -35 (-37) to 120 (48) 280,000 to 3750 3&4 (Black) Coil -35 (-37) to 120 (48) 280,000 to 3750 5& 6 (Brown) Discharge (if applicable) 24 (-4) to 350 (176) 41,000 to 103 1& 2 (Yellow) Note: Sensor resistance decreases as sensed temperature (see figure 20). and Coil Sensor increases e Sensor 3OO _7450 11775 _m 15425 240 _425 _ 220 mmllmlml!19975 26200 m34375 _ 200 _ 180 _ 160 _ 140 H m46275 I 62700 I 85300 30000 50000 RESISTANCE 825 B1175 WOO ,025 2500 3000 3750 m ¢650 70000 90000 lOOO (OHMS) 2000 3000 RESISTANCE Sensor DISCHARGE LINE SENSOR 5825 lOO Figure ALTERNATE COIL SENSOR LOCATION. _600 120 I 10000 260 m m250 m mm325 280 4000 5000 6000 (OHMS) 20 Locations AMBIENT SENSOR (inside PVC tube) Extend tip of plastic sensor just outside of plastic sleeve. COIL SENSOR DETAIL - Sensor clips on the return bend as shown, located on bends as follows: HPXA16-024: 6th bend from top on outside column. HPXA16-036*, -048, -060: 5th bend from bottom on outside column. NOTE - DIAGRAMS ARE TYPICAL OF @24 AND @36 COIL; -048 & @60 COILS HAVE MORE COIL SURFACE AREA AND GREATER NUMBER OF BENDS. * - @36 MODEL HAS ALTERNATE LOCATION ON OPPOSITE SIDE AS SHOWN TO THE LEFT HPXA16-036 ALTERNATE COIL SENSOR LOCATION Figure 21 Page 17 HPXA16 SERIES Defrost System Sensors Ambient Sensor--The ambient sensor considers outdoor temperatures below -35°F (-37°C) or above 120°F (48°C) as a fault. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand defrost operation. The board will revert to time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition. Coil Sensor--The coil temperature sensor considers outdoor temperatures below -35°F (-37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition. Discharge Line Sensor--If the discharge line temperature exceeds a temperature of 300°F (148°C) during compressor operation, the board will de-energize the compressor contactor output (and the defrost output, if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C) and the 5-minute antishort cycle delay has been satisfied. This sensor has two fault and lockout codes: 1. If the board recognizes five high discharge line temperature faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. This code detects shorted sensor or high discharge temperatures. (Code on board is "Discharge Line Temperature Fault and Lockout"). 2. If the board recognizes five temperature sensor range faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. The board detects open sensor or out-of-temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout. (Code on board is "Discharge Sensor Fault and Lockout"). If first-stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock-in temperature, the second-stage compressor solenoid output will be energized without the "Y2" input. If the jumper is not connected to one of the temperature selection pins on P3 (40, 45, 50, 55°F), the default lock-in temperature of 40°F (4.5°C) will be used. The board de-energizes the second-stage compressor solenoid output immediately when the "Y2" signal is removed or the outdoor ambient temperature is 5°F above the selected compressor lock-in temperature, or the first-stage compressor output is de-energized for any reason. Defrost Temperature Termination Shunt (Jumper) Pins--The defrost board selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C). Delay Mode The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins. NOTE - The 30 second off cycle is NOT functional when jumpering the TEST pins. Operational Description The defrost control board has three basic operational modes: normal, defrost, and calibration. • • The discharge line sensor, which covers a range of 150°F (65°C) to 350°F (176°C), is designed to mount on a V:" refrigerant discharge line. • NOTE - Within a single room thermostat demand, if 5-strikes occur, the board will lockout the unit. Defrost board 24 volt power "R" must be cycled "OFF" or the "TEST" pins on board must be shorted between 1 to 2 seconds to reset the board. Second-Stage Operation--If the board receives a call for second-stage compressor operation "Y2" in heating or cooling mode and the first-stage compressor output is active, the second-stage compressor solenoid output will be energized. NOTE - Figure 8 on page 5 shows the correct Y2 field wiring. 0_06 Defrost Mode--The following paragraphs provide a detailed description of the defrost system operation. Detailed Defrost System Operation The demand defrost control board initiates a defrost cycle based on either frost detection or time. Frost Detection--If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control, a defrost cycle will be initiated. IMPQR TANT - The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature defrost system. Page 18 504954M Normal Mode--The demand defrost board monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required. Calibration Mode--The board is considered uncalibrated when power is applied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode. Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle. Time--If 6 hoursof heatingmodecompressor runtime haselapsedsincethelastdefrostcyclewhilethecoiltemperatureremainsbelow35°F(2°C),thedemanddefrost controlwillinitiatea defrostcycle. Actuation--Whenthe reversingvalveis de-energized, theY1circuitis energized, andthecoiltemperature is below35°F(2°C),theboardlogsthecompressor runtime,If theboardis notcalibrated, a defrostcyclewillbeinitiated after34minutesof heatingmodecompressor runtime. Thecontrolwillattempttoself-calibrate afterthis(andall other)defrostcycle(s), Calibration successdependsonstablesystemtemperaturesduringthe20-minute calibration period,Iftheboard failstocalibrate, anotherdefrostcyclewillbeinitiatedafter 90minutesof heatingmodecompressor runtime,Once thedefrostboardis calibrated, itinitiatesademanddefrost cyclewhen the differencebetweenthe clearcoil and frostedcoiltemperatures exceedsthe maximumdifferenceallowedby thecontrolORafter6 hoursof heating modecompressor runtimehasbeenloggedsincethelast defrostcycle. Termination--Thedefrostcycleendswhenthecoiltemperatureexceedsthetermination temperature or after14 minutesofdefrostoperation. Ifthedefrostisterminated by the14-minute timer,anotherdefrostcyclewillbeinitiated after34minutesofruntime. Test Mode--[NOTE - Coil sensor temperature must be below 35°F before the defrost board will initiate a "test" defrost.] When Y1 is energized and 24V power is being applied to the board, a test cycle can be initiated by placing the termination temperature jumper across the "Test" pins for 2 to 5 seconds. If the jumper remains across the "Test" pins longer than 5 seconds, the control will ignore the test pins and revert to normal operation, The jumper will initiate one cycle per test, Enter the "TEST" mode by placing a shunt (jumper) across the "TEST" pins on the board after power-up. (The "TEST" pins are ignored and the test function is locked out if the shunt is applied on the "TEST" pins before power-up), Board timings are reduced, the low-pressure switch is ignored and the board will clear any active lockout condition, Each test pin shorting will result in one test event. For each "TEST" the shunt (jumper) must be removed for at least 1 second and reapplied, Refer to flow chart (figure 22) for "TEST" operation, Note: The Y1 input must be active (ON) and the "0" room thermostat terminal into board must be inactive. Defrost Board Diagnostics See table 10 to determine defrost board operational conditions and to diagnose cause and solution to problems. Test Mode I Y1 Active ("0" line inactive) I ] Short test pins for more than 2.0 seconds Short test pins for longer than I second but less than 2,0 seconds Clear any short cycle lockout or 5-strike fault lockout function, if applicable. If in HEATING Mode I [ Clear any short cycle lockout I If in COOLING Mode I I and/or 5-strike fault lockout function, if applicable. No No further test mode The controller will check for other functions will be operation will be ambient and coil faults (open or executed and unit will executed until the test shorted). If a fault exists the unit continue in the mode it was short is removed and will remain in Heat Mode and no operating. reapplied. further test mode operation will be executed until the test short is removed and re applied. If no fault exists and ambient temperature is below 35°F, the unit will go into Defrost mode. F Test pin short REMAINS in place for more than 5 seconds The unit will return to Heat mode uncalibrated with defrost timer set for 34 minutes. No further test mode operation will be executed until the test short is removed and re applied. Figure If in DEFROST Mode The unit will terminate defrost and enter Heat Mode uncalibrated with defrost timer set for 34 minute test. No further test mode operation will be executed until the test short is removed and reapplied. Test pins short REMOVED before a maximum of 5 seconds The unit will remain in Defrost mode until termination on time or temperature 22 Page 19 HPXA16 SERIES Table 10 Defrost Control Board Diagnostic LEDs DS2 Green DS1 Red Condition/Code Possible OFF OFF Power problem No power (24V) to board terminals R & C or board failure. 1 Check control transformer power (24V). 2 If power is available to board and LED(s) do not light, replace board. Simultaneous SLOW Flash Normal operation Unit operating normally or in standby mode. None required. Alternating SLOW Flash 5-minute anti-short cycle delay Initial power up, safety trip, end of room thermostat demand. None required (Jumper TEST pins to override) Simultaneous FAST Flash Ambient Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will revert to time/temperature defrost operation. (System will still heat or cool). Alternating FAST Flash Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will not perform demand or time/temperature defrost operation. (System will still heat or cool). ON ON Circuit Board Failure code Indicates doesthat notboard clear, has replace internal board, component failure. Cycle 24 volt power to board. If FAULT & LOCKOUT OFF SLOW Flash Low Pressure Fault OFF ON Low Pressure SLOW Flash OFF High Pressure ON OFF High Pressure LOCKOUT SLOW Flash ON Discharge Line Temperature Fault FAST Flash ON Discharge Line Temperature LOCKOUT OFF Fast Flash Discharge Sensor Fault Fast Flash OFF Discharge LOCKOUT CODES (Each fault adds 1 strike to that code's LOCKOUT Fault Sensor Cause(s) 0_06 counter; 5 strikes per code = LOCKOUT) 1 Restricted air flow over indoor or 1 Remove any blockages or restrictions from outdoor coil. coils and/or fans. Check indoor and outdoor 2 Improper refrigerant charge in fan motor for proper current draws. 2 Check system charge using approach & subsystem. 3 Improper metering device cooling temperatures. installed or incorrect operation 3 Check system operating pressures and of metering device. compare to unit charging charts. 4 Incorrect or improper sensor 4 Make sure all pressure switches and sensors location or connection to syshave secure connections to system to prevent tem. refrigerant leaks or errors in pressure and temperature measurements. This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 300°F (148°C) during compressor operation, the board will de-energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C). The board detects open sensor or out of temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout. Page 20 504954M Solution ,WARNING Before the start of each heating and cooling season, the following service checks should be performed by a qualified service technician. First, turn off electrical power to the unit prior to performing unit maintenance, • Inspect and clean the outdoor and indoor coils, The outdoor coil may be flushed with a water hose, NOTE - It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, etc.) • Visually inspect the refrigerant lines and coils for leaks, • Check the condensate drain line for free and unobstructed flow; clean, if necessary. • Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure. • Check drive belt for wear and proper tension. NOTE - If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction. Refer to the Engineering Handbook for optional accessories that may apply to this unit. The following may or may not apply: • Loss of charge kit • High pressure switch kit • Compressor monitor • Compressor crankcase heater Hail guards • Check wiring for loose connections, • • Check voltage at the indoor and outdoor units (with units operating), • Mounting bases • Timed-off control Check the amperage draw at the outdoor fan motor, compressor, and indoor blower motor. Values should be compared with those given on unit nameplate, • Stand-off Kit • Sound cover • Low ambient kit • Monitor kit • Dave Lennox SignatureStat • • Check, clean (or replace) indoor unit filters, • Check the refrigerant charge and gauge the system pressures, T_ Room Thermostat Page 21 HPXA16 SERIES Job Name Job no. Date Job Location City State Installer City State Unit Model No, Serial No. Service Technician Nameplate Voltage Rated Load Ampacity Compressor Amperage: 1st Stage 2nd Stage: Maximum Fuse or Circuit Breaker Electrical Connections Tight? Indoor Blower RPM Indoor Filter clean? S.P. Drop Over Indoor (Dry) Supply Voltage (Unit Off) Outdoor Coil Entering Air Temp. COOLING (2ND STAGE) Liquid Line Pressure: Vapor Pressure: Refrigerant Charge Checked? Liquid Line Pressure: Vapor Pressure: Refrigerant Charge Checked? Vapor Pressure; 1st Stage: 2nd Stage: HEATING (2ND STAGE) Refrigerant Lines: - Leak Checked? Service Valves: --- Fully Opened? SEQUENCE Heating Correct? _ _ Properly Insulated? Outdoor Fan Checked? _ Caps Tight? Voltage With Compressor Operating THERMOSTAT OF OPERATION Cooling Correct? Calibrated? Page 22 504954M 08/06 Properly Set? _ Level? :c'2006 Lennox industries Inc, Dallas, Texas, USA HPXA16 In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level. A IMPORTANT 1. Ask your Lennox dealer to show you where your indoor unit's filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed. 2. Disposable filters should be replaced with a filter of the same type and size. NOTE - If you are unsure about the filter you need for your system, call your Lennox dealer for assistance. Heat Pump Operation Your new Lennox heat pump has several characteristics that you should be aware of: • A IMPORTANT • 3. Many indoor units are equipped with reusable foam filters. These filters can be cleaned with a mild soap and water solution. Rinse the filter thoroughly and let it dry completely before it is returned to the unit or grille. NOTE - The filter and all access panels must be M place any time the unit is in operation. 4. Some systems are equipped with an electronic air cleaner, designed to remove the majority of airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions. 5. Inspect and clean indoor coil. The indoor evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.) • Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space. This is quite different from gas- or oil4ired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space. Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost. During the defrost cycle, you may notice steam rising from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle. In case of extended power outage... The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant "slugging" during cold weather operation. If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the "Emergency Heat" setting to obtain temporary heat without the risk of serious damage to the heat pump. In Emergency Heat mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase "warm-up" period, the thermostat can be switched to the "Heat" setting and normal heat pump operation may resume. Page 23 HPXA16 SERIES Though your thermostat may vary somewhat from the description below, its operation will be similar, dicates when the heat pump is operating in the emergency heat mode, Temperature Setting Levers Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling, Set the levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor, Temperature Indicator The temperature indicator displays the actual room temperature, Fan Switch In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired, Programmable Thermostats Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user's information manual provided with your particular thermostat for operation details, Preservice Check If your system fails to operate, check the following before calling for service: • Check to see that all electrical disconnect switches are ON. System Switch Set the system switch for heating, cooling or auto operation, The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings. Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat, • Make sure the room thermostat temperature selector is properly set. • Make sure the room thermostat system switch is properly set. • Replace any blown fuses, or reset circuit breakers, • • Make sure unit access panels are in place, Make sure air filter is clean, Indicating Light Most heat pump thermostats have an amber light which in- • Locate unit model number and have it handy before calling, Page 24 504954M 0_06
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 24 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 05:00:25 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools