Distribution & Control Transformers and Power Supplies

44-1

Distribution & Control Transformers and Power Supplies

April 2009

CA08102001E

Contents
Description

Page

Distribution Transformers
Single-Phase Encapsulated and Ventilated, 60 Hz. . . . . . . . . . . . . . . . . . .
Electrostatically Shielded Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . .
Open Type Core and Coil Assembly Transformers . . . . . . . . . . . . . . . . . .
Buck-Boost and Low Voltage Lighting Transformers . . . . . . . . . . . . . . . .
Control Transformers
Type MTA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type MTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type MTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type MTK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CE Marked . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type AP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PSG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PSS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sensor Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

44-2
44-8
44-13
44-15
44-32
44-37
44-39
44-48
44-53
44-61
44-63
44-65
44-65
44-71
44-77
44-79
44-81

44

Control Transformers

For more information visit: www.eaton.com

PSG Power Supplies

Distribution & Control Transformers and Power Supplies
General Purpose Transformers

44-2

April 2009

Single-Phase Encapsulated (Type EP), Ventilated (Type DS-3), 60 Hz

Single-Phase Encapsulated
(Type EP), Ventilated (Type
DS-3), 60 Hz

Features, Benefits
and Functions
UL listed.
60 Hz operation.
■ Short-term overload capability
as required by ANSI.
■ Meet NEMA ST-20 sound levels.
■

Continuous overload capacity is not
deliberately designed into a transformer because the design objective is
to be within the allowed winding temperature rise with nameplate loading.

■

Insulation System and Temperature Rise
Industry standards classify insulation
systems and rise as shown below:
Table 44-1. Insulation System Classification

Standards and Certifications

Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

Industry Standards

Type EP 3-25 kVA

Product Description
Type EP
■
■
■

44

■
■
■
■
■

Sand and Resin Encapsulated design.
Suitable for indoor or outdoor
applications.
Totally enclosed, non-ventilated
enclosures.
Enclosures are NEMA 3R rated.
Mountable in any position indoors
and upright only outdoors.
185ºC insulation system.
115ºC rise standard; 80°C optional.
Available in ratings through 37.5 kVA
and 4160 volts primary.

Type DS-3
■
■

■
■
■
■

Ventilated, NEMA 2 enclosure
standard.
Suitable for indoor applications,
outdoors when weathershields are
also installed.
Upright mounting only.
220ºC insulation system.
150ºC rise standard; 115°C or 80°C
optional.
Available in single-phase ratings
15 – 167 kVA and up to 4160 volts
primary.

All Cutler-Hammer dry-type distribution and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI and IEEE Standards. All 600 volt
class transformers are UL listed unless
otherwise noted.

Seismically Qualified
Cutler-Hammer manufactured dry-type
distribution transformers are seismically qualified, and exceed requirements of the Uniform Building Code
(UBC), International Building Code
(IBC), and California Code Title 24.

Product Specifications
Frequency
Cutler-Hammer standard dry-type
distribution transformers are designed
for 60 Hertz operation. Transformers
required for other frequencies are
available and must be specifically
designed.

Overload Capability
Short-term overload is designed into
transformers as required by ANSI.
Dry-type distribution transformers
will deliver 200% nameplate load for
one-half hour; 150% load for one hour;
and 125% load for four hours without
being damaged provided that a constant 50% load precedes and follows
the overload. See ANSI C57.96-01.250
for additional limitations.

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Enclosures
Cutler-Hammer ventilated transformers, Type DS-3, utilize a NEMA 2 rated
(drip-proof) enclosure as standard,
and are rated NEMA 3R with the addition of weathershields. Cutler-Hammer
encapsulated transformers, Type EP,
utilize a NEMA 3R rated enclosure
as standard.

Sound Levels
All Cutler-Hammer 600 volt class
general purpose dry-type distribution
transformers are designed to meet
NEMA ST-20 sound levels listed here.
These are the sound levels measured
in a soundproof environment. Actual
sound levels measured at an installation will likely be higher due to electrical connections and environmental
conditions. Lower sound levels are
available and should be specified
when the transformer is going to
be installed in an area where sound
may be a concern.
Table 44-2. Average Sound Levels 
NEMA ST-20 Average Sound Level in dB
kVA

Up to 1.2 kV

Above 1.2 kV

Ventilated Encap- Ventilated
sulated

Application Description
The basic purpose of a transformer
is voltage transformation as near as
practically possible to the load for
economy and distribution of power.
Typical loads for dry-type distribution
transformers include lighting, heating,
air conditioners, fans and machine
tools. Such loads are found in commercial, institutional, industrial
and residential structures.

0–9
10 – 50
51 – 150
151 – 300

40
45
50
55

45
50
55
57

45
50
55
58

301 – 500
501 – 700
701 – 1000
1001 – 1500

60
62
64
65

59
61
63
64

60
62
64
65



For more information visit: www.eaton.com

Currently being reviewed and revised by
NEMA.

CA08102001E

Distribution & Control Transformers and Power Supplies
General Purpose Transformers

44-3

April 2009

Single-Phase Encapsulated (Type EP), Ventilated (Type DS-3), 60 Hz
Winding Terminations

Series-Multiple Windings

Primary and secondary windings are
terminated in the wiring compartment.
Encapsulated units have copper leads
or stabs brought out for connections.
Ventilated transformers have leads
brought out to aluminum pads that
are pre-drilled to accept Cu/Al lugs.
Lugs are not supplied with these
transformers. Eaton recommends
external cables be rated 90°C (sized
at 75°C ampacity) for encapsulated
designs and 75°C for ventilated
designs.

Series-multiple windings consist of
two similar coils in each winding
which can be connected in series or
parallel (multiple). Transformers with
series-multiple windings are designated with an “X” or “/” between the
voltage ratings, such as voltages of
“120/240” or “240 X 480.” If the seriesmultiple winding is designated by an
“X,” the winding can be connected
only for a series or parallel. With the
“/” designation, a mid-point also
becomes available in addition to the
series or parallel connection. As an
example, a 120 X 240 winding can be
connected for either 120 (parallel) or
240 (series), but a 120/240 winding can
be connected for 120 (parallel), or 240
(series), or 240 with a 120 mid-point.

44

The following pages provide listings for most
standard transformer ratings and styles.
For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
General Purpose Transformers

44-4

April 2009

Single-Phase Encapsulated (Type EP), Ventilated (Type DS-3), 60 Hz

Product Selection
Additional Product Selection information begins on Page 44-63.

Type DS-3 15-167 kVA

Type EP 3-37.5 kVA

Table 44-3. Single-Phase Selection Information — Types EP, DS-3, 60 Hz
kVA Full Cap. Taps
FCAN

FCBN

Type °C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt. Dimensions (mm) Wt. Frame Wiring
Weathershield
Style
Lbs. H
kg
Diagram Catalog Price Number
W
D
Number Number U.S. $

Price
U.S. $

120 x 240 Volts to 120/240 Volts 

44

.5 —
1 —
1.5 —

—
—
—

EP
EP
EP

115
115
115

6-1/2
8-5/8
10-3/4

2
3
5

—
—
—

—
—
—

EP
EP
EP

115
115
115

7.5
10
15
25

—
—
—
—

—
—
—
—

EP
EP
EP
EP

115
115
115
115

37.5
50







4-5/8
4-15/16
5-3/4
5-3/4
6-3/16 6-5/8

16
31
42

165
219
273

117
146
157

125
146
166

7 FR57 3E
14 FR59A 3E
19 FR67 3E

IndoorOutdoor

S10N11S51N
S10N11S01N
S10N11S16N

10-3/4 6-3/16 6-5/8
14-1/8 7-3/4
8
16
10-3/8 9-7/8

42
55
113

273
359
406

157
197
263

166
203
251

19 FR68 3E
25 FR176 3E
51 FR177 3E

IndoorOutdoor

S10N11S02N
S10N11S03N
S10N11S05N

16
19
19
22-3/8

10-3/8 9-7/8
13-3/8 10-1/2
13-3/8 13-3/8
16-3/8 14-1/2

123
193
216
375

406
482
482
568

263
339
339
416

251
266
266
368

56
88
98
170

IndoorOutdoor

S10N11S07N
S10N11S10N
S10N11S15N
S10N11S25N

DS-3 150
DS-3 150

37-5/8 22-5/8 19-1/2
37-5/8 22-5/8 19-1/2

306
340

953
956

574
574

495
495

139 FR817 3XD
154 FR818 3XD

WS11
WS11

T10P11S37
T10P11S50

16
31
42

165
219
273

117
146
157

125
146
166

7 FR57 26A
14 FR59A 26A
19 FR67 26A

IndoorOutdoor

S29N11S51N
S29N11S01N
S29N11S16N

6-5/8
8
9-7/8

42
65
113

273
359
406

157
197
263

166
203
251

19 FR68 26A
30 FR176 26A
51 FR177 26A

IndoorOutdoor

S29N11S02N
S29N11S03N
S29N11S05N

10-3/8
13-3/8
13-3/8
16-3/8

9-7/8
10-1/2
13-3/8
14-1/2

123
193
216
395

406
482
482
568

263
339
339
416

251
266
266
359

56
88
98
179

IndoorOutdoor

S29N11S07N
S29N11S10N
S29N11S15N
S29N11S25N

31-1/4 22-5/8
37-5/8 22-5/8
37-5/8 22-5/8

17-1/2
19-1/2
19-1/2

212
306
340

793
953
956

574
574
574

445
495
495

96 FR816 260A
139 FR817 260A
154 FR818 260A

WS11
WS11
WS11

T29M11S25
T29M11S37
T29M11S50

42-1/8 24
42-1/8 24

23-3/8
23-3/8

510 1070
600 1070

610
610

594
594

232 FR819 260A
272 FR820 551A

WS16
WS16

T29M11S75
T29R11S99

FR178
FR179
FR180
FR182

3E
3E
3E
3E

208 Volts to 120/240 Volts 
.5 —
1 —
1.5 —

—
—
—

EP
EP
EP

115
115
115

6-1/2
8-5/8
10-3/4

2
3
5

—
—
—

—
—
—

EP
EP
EP

115
115
115

10-3/4 6-3/16
14-1/8 7-3/4
16
10-3/8

7.5
10
15
25

—
—
—
—

—
—
—
—

EP
EP
EP
EP

115
115
115
115

16
19
19
22-3/8

25 2@+2.5% 4@-2.5% DS-3 150
37.5 2@+2.5% 4@-2.5% DS-3 150
50 2@+2.5% 4@-2.5% DS-3 150
75
100

2@+2.5% 4@-2.5% DS-3 150
1@+5% 2@-5% DS-3 150

4-5/8
5-3/4
6-3/16

4-15/16
5-3/4
6-5/8

FR178
FR179
FR180
FR182

26A
26A
26A
26A

277 Volts to 120/240 Volts 
5-3/4
5-3/4
6-5/8

26
31
42

165
219
273

146
146
157

146
146
166

12 FR58A 524A
14 FR59A 524A
19 FR67 524A

IndoorOutdoor

S27N11S51A
S27N11S01A
S27N11S16A

8
8
9-7/8

65
55
113

359
359
406

197
197
263

203
203
251

30 FR176 524A
25 FR176 524A
51 FR177 524A

IndoorOutdoor

S27N11S02A
S27N11S03N
S27N11S05N

10-3/8
13-3/8
13-3/8
16-3/8

9-7/8
10-1/2
13-3/8
14-1/2

123
193
180
375

406
482
482
568

263
339
339
416

251
266
266
359

56
88
82
170

IndoorOutdoor

S27N11S07N
S27N11S10N
S27N11S15N
S27N11S25N

31-1/4 22-5/8
37-5/8 22-5/8
37-5/8 22-5/8

17-1/2
19-1/2
19-1/2

212
306
340

793
953
956

574
574
574

445
495
495

96 FR816 262C
139 FR817 262C
154 FR818 262C

WS11
WS11
WS11

T27M11S25
T27M11S37
T27M11S50

42-1/8 24
42-1/8 24

23-3/8
23-3/8

510 1070
600 1070

610
610

594
594

232 FR819 262C
272 FR820 262C

WS16
WS16

T27M11S75
T27M11S99

.5 —
1 —
1.5 —

—
—
—

EP
EP
EP

115
115
115

8-5/8
8-5/8
10-3/4

2
3
5

—
—
—

—
—
—

EP
EP
EP

115
115
115

10-3/4 7-3/4
14-1/8 7-3/4
16
10-3/8

7.5
10
15
25

—
—
—
—

—
—
—
—

EP
EP
EP
EP

115
115
115
115

16
19
19
22-3/8

25 2@+2.5% 4@-2.5% DS-3 150
37.5 2@+2.5% 4@-2.5% DS-3 150
50 2@+2.5% 4@-2.5% DS-3 150
75
100



2@+2.5% 4@-2.5% DS-3 150
2@+2.5% 4@-2.5% DS-3 150

5-3/4
5-3/4
6-3/16

FR178
FR179
FR180
FR182

524A
524A
524A
524A

Contact Eaton for availability of 0.05 – 0.25 kVA designs.
1@+5%, 2@-5% at 240 volts primary; 2@+2.5%, 4@-2.5% at 480 volts primary.

Note: Contact your local Eaton sales office for CE Mark transformer requirements.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies
General Purpose Transformers

44-5

April 2009

Single-Phase Encapsulated (Type EP), Ventilated (Type DS-3), 60 Hz
Table 44-4. Single-Phase Selection Information — Types EP, DS-3, 60 Hz
kVA

Full Cap. Taps
FCAN

FCBN

Type °C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt. Dimensions (mm) Wt. Frame
Lbs. H
kg
W
D

Wiring
Weathershield Style
Diagram Catalog Price Number
Number Number U.S. $

Price
U.S. $

240 x 480 Volts to 120/240 Volts
.050 —
.075 —
.100 —

—
—
—

EP
EP
EP

115
115
115

6-1/2
6-1/2
6-1/2

3-7/8
3-7/8
3-7/8

3-7/8
3-7/8
3-7/8

.150 —
.25 —
.5 —

—
—
—

EP
EP
EP

115
115
115

6-1/2
6-1/2
6-1/2

3-7/8
4-5/8
4-5/8

3-7/8
4-1/8
4-15/16

.75 —
—
1
1.5 —

—
—
—

EP
EP
EP

115
115
115

2
3
3

—
—

—
—

EP
EP
EP

5
5
7.5

—

—

7.5
10
10





—

—

15
15
25

—

25
37.5
15
25
37.5
50
75
100
167














—

—





—

7
7
7

165
165
165

98
98
98

98
98
98

3 FR52
3 FR54
3 FR54

3A
3A
3A

IndoorOutdoor

S20N11S81N
S20N11S85N
S20N11S82N

8
12
16

165
165
165

98
117
117

98
103
125

4 FR55
5 FR56
7 FR57

3A
3A
3A

IndoorOutdoor

S20N11S83N
S20N11S26N
S20N11S51N

8-5/8 5-3/4 5-3/4
8-5/8 5-3/4 5-3/4
10-3/4 6-3/16 6-5/8

26
31
42

219
219
273

146
146
157

146
146
166

12 FR58A 3A
14 FR59A 3A
19 FR67
3A

IndoorOutdoor

S20N11S76N
S20N11S01N
S20N11S16N

115
115
115

10-3/4 6-3/16 6-5/8
14-1/8 7-3/4 8
14-1/8 7-3/4 8

42
65
65

273
359
359

157
197
197

166
203
203

19 FR68
30 FR176
30 FR176

3A
3A
9A

IndoorOutdoor

S20N11S02N
S20N11S03N
S20K11S03N

EP
EP
EP

115
115
115

16
16
16

10-3/8
10-3/8
10-3/8

9-7/8
9-7/8
9-7/8

113
105
105

406
406
406

263
263
263

251
251
251

51 FR177
48 FR177
48 FR178

3A
9A
3A

IndoorOutdoor

S20N11S05N
S20K11S05N
S20N11S07N

EP
EP
EP

115
115
115

16
19
19

10-3/8 9-7/8
13-3/8 10-1/2
13-3/8 10-1/2

123
193
193

406
482
482

263
339
339

251
266
266

56 FR178
88 FR179
88 FR179

9A
3A
9A

IndoorOutdoor

S20K11S07N
S20N11S10N
S20K11S10N

115
115
115

19
13-3/8 13-3/8
19
13-3/8 13-3/8
22-3/8 16-3/8 14-1/2

216
216
385

482
482
568

339
339
416

266
266
368

98 FR180
98 FR180
175 FR182

3A
23A
3A

IndoorOutdoor

S20N11S15N
S20L11S15N
S20N11S25N





—

—

EP
EP
EP







EP
EP

115
115

22-3/8 16-3/8 14-1/2
28-1/4 22-5/8 14-5/8

375
735

568
717

416
570

368
371

170 FR182 23A
334 FR300A 248A

IndoorOutdoor

S20L11S25N
S20L11S37 









DS-3 150
DS-3 150
DS-3 150

30-1/4 16-7/8 15-7/8
31-1/4 22-5/8 17-1/2
37-5/8 22-5/8 19-1/2

147
212
306

768
793
953

428
574
574

402
445
495

67 FR815
96 FR816
139 FR817

3XA
3XA
3XA

WS15
WS11
WS11

T20P11S15
T20P11S25
T20P11S37









150
150
150
150

340
510
600
1200

956
1070
1070
1597

574
610
610
762

495
594
594
863

154
232
272
545

3XA
3XA
3XA
288A

WS11
WS16
WS16
WS13

T20P11S50
T20P11S75
T20P11S99
T48M11S67D 

DS-3
DS-3
DS-3
2@+2.5% 4@-2.5% DS-3

37-5/8
42-1/8
42-1/8
62-7/8

22-5/8
24
24
30

19-1/2
23-3/8
23-3/8
34

FR818
FR819
FR820
FR814

1@+10% FCBN at 240 volts; 2@+5% FCBN at 480 volts.
2@+5% FCBN at 240 volts; 4@+2.5% FCBN at 480 volts.
1@+5%, 2@-5% at 240 volts primary; 2@+2.5%, 4@-2.5% at 480 volts primary.
Floor-mount only.
480 volts primary to 120/240 volts secondary.

Note: Contact your local Eaton sales office for CE Mark transformer requirements.

For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

44

Distribution & Control Transformers and Power Supplies
General Purpose Transformers

44-6

April 2009

Single-Phase Encapsulated (Type EP), Ventilated (Type DS-3), 60 Hz
Table 44-5. Single-Phase Selection Information — Types EP, DS-3, 60 Hz
kVA

Full Cap. Taps
FCAN

FCBN

Type °C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt. Dimensions (mm)
Lbs. H
W
D

Wt. Frame Wiring
Weathershield
Style
kg
Diagram Catalog Price Number
Number Number U.S. $

Price
U.S. $

190/200/208/220 x 380/400/416/440 Volts to 110/220 Volts 50/60 Hz — Export Model IP 22 Rated
.5
1
1.5
2

—
—
—
—

—
—
—
—

EP
EP
EP
EP

115
115
115
115

10-3/4
10-3/4
14-1/8
14-1/8

3
5
7.5

—
—
—

—
—
—

EP
EP
EP

115
115
115

16
16
19

—
—

—
—

EP
EP

115
115

19
22-3/8

10
15

6-3/16
6-3/16
7-3/4
7-3/4

6-5/8
6-5/8
8
8

42
42
65
65

273
273
359
359

157
157
197
197

166
166
203
203

19
19
30
30

FR67
FR67
FR176
FR176

538A
538A
538A
538A

IndoorOutdoor

S40N14S51CE
S40N14S01CE
S40N14S16CE
S40N14S02CE

10-3/8
10-3/8
13-3/8

9-7/8
9-7/8
10-1/2

113
140
193

406
406
482

263
263
339

251
251
266

51
64
88

FR177
FR178
FR179

538A
538A
538A

IndoorOutdoor

S40N14S03CE
S40N14S05CE
S40N14S07CE

13-3/8
16-3/8

13-3/8
14-1/2

216
375

482
433

339
415

266
359

98
170

FR180
FR182

538A
538A

IndoorOutdoor

S40N14S10CE
S40N14S15CE

6-5/8
8
8

42
65
65

273
359
359

157
197
197

166
203
203

19
30
30

FR67
FR176
FR176





IndoorOutdoor

S54N11S01
S54N11S16
S54N11S02

10-3/8
10-3/8
13-3/8
13-3/8

9-7/8
9-7/8
10-1/2
13-3/8

113
140
193
216

406
406
482
482

263
263
339
339

251
251
266
266

51
64
88
98

FR177
FR178
FR179
FR180






IndoorOutdoor

S54N11S03
S54N11S05
S54N11S07
S54N11S10

120/208/240/277 Volts to 120/240 Volts 60 Hz
1
1.5
2

—
—
—

—
—
—

EP
EP
EP

115
115
115

10-3/4
14-1/8
14-1/8

3
5
7.5
10

—
—
—
—

—
—
—
—

EP
EP
EP
EP

115
115
115
115

16
16
19
19

6-3/16
7-3/4
7-3/4

240 x 480 Volts to 120/240 Volts Stainless Steel 
3
5
7.5
10
15
25

—
—
—

—
—
—

EP
EP
EP

115
115
115

14-1/8
16
16

7-3/4
10-3/8
10-3/8

8
9-7/8
9-7/8

65
113
123

359
406
406

197
263
263

203
251
251

30
51
56

FR176
FR177
FR178

3A
3A
3A

IndoorOutdoor

S20N11S03SS
S20N11S05SS
S20N11S07SS

—
—
—

—
—
—

EP
EP
EP

115
115
115

19
19
22-3/8

13-3/8
13-3/8
16-3/8

10-1/2
13-3/8
14-1/2

193
205
375

482
482
566

339
339
416

266
266
359

88
93
170

FR179
FR180
FR182

3A
3A
3A

IndoorOutdoor

S20N11S10SS
S20N11S15SS
S20N11S25SS

5-3/4
6-5/8
6-5/8

31
42
42

219
273
273

146
157
157

146
166
166

14
19
19

FR59A
FR67
FR68

2D
2D
2D

IndoorOutdoor

S48G11S01N
S48G11S16N
S48G11S02N

480 Volts to 120/240 Volts

44

1
1.5
2

—
—
—

EP
EP
EP

115
115
115

8-5/8
10-3/4
10-3/4

3
3
5

—
2@-5%
EP
2@+2.5% 2@+2.5% EP
—
2@-5%
EP

115
115
115

14-1/8
14-1/8
16

7-3/4
7-3/4
10-3/8

8
8
9-7/8

65
65
113

359
359
406

197
197
263

203
203
251

30
30
51

FR176
FR176
FR177

2D
16A
2D

IndoorOutdoor

S48G11S03N
S48D11S03N
S48G11S05N

5
7.5
7.5

2@+2.5% 2@+2.5% EP
—
2@-5%
EP
2@+2.5% 2@+2.5% EP

115
115
115

16
16
16

10-3/8
10-3/8
10-3/8

9-7/8
9-7/8
9-7/8

113
123
123

406
406
406

263
263
263

251
251
251

51
56
56

FR177
FR178
FR178

16A
2D
16A

IndoorOutdoor

S48D11S05N
S48G11S07N
S48D11S07N

10
10
15

—
2@-5%
EP
2@+2.5% 2@+2.5% EP
—
2@-5%
EP

115
115
115

19
19
19

13-3/8
13-3/8
13-3/8

10-1/2
10-1/2
13-3/8

193
193
216

482
482
482

339
339
339

266
266
266

88
88
98

FR179
FR179
FR180

2D
16A
2D

IndoorOutdoor

S48G11S10N
S48D11S10N
S48G11S15N

15
25
25

2@+2.5% 2@+2.5% EP
—
2@-5%
EP
2@+2.5% 4@-2.5% EP

115
115
115

19
22-3/8
20-3/4

13-3/8
16-3/8
19-1/8

13-3/8
14-1/2
13-5/8

216
385
410

482
568
525

339
416
483

266
359
349

98
175
186

FR180
FR182
FR132

16A
2D
83A

IndoorOutdoor

S48D11S15N
S48G11S25N
S48M11S25N

210
235
415

482
482
525

339
339
483

266
266
349

95
107
188

FR179
FR180
FR182

16A
16A
83A

IndoorOutdoor

S48D11S10SSCU
S48D11S15SSCU
S48M11S25SSCU

2@-5%
2@-5%
2@-5%

5-3/4
6-3/16
6-3/16

480 Volts to 120/240 Volts Stainless Steel, Copper Windings 
10
15
25

2@+2.5% 2@+2.5% EP
2@+2.5% 2@+2.5% EP
2@+2.5% 4@-2.5% EP

115
115
115

19
19
22-3/8

13-3/8
13-3/8
16-3/8

10-1/2
13-3/8
14-1/2

600 Volts to 120/240 Volts
1



2@-5%
2@-5%
2@-5%

EP
EP
EP

115
115
115

6-1/2
8-5/8
8-5/8

4-5/8
5-3/4
5-3/4

4-15/16
5-3/4
5-3/4

16
26
31

165
219
219

117
146
146

125
146
146

7
12
14

FR57
FR58A
FR59A

2I
2I
2I

IndoorOutdoor

S60G11S51N
S60G11S76N
S60G11S01N

6-3/16
6-3/16
7-3/4

6-5/8
6-5/8
8

42
42
65

273
273
359

157
157
197

166
166
203

19
19
30

FR67
FR68
FR176

2I
2I
2I

IndoorOutdoor

S60G11S16N
S60G11S02N
S60G11S03N

1.5
2
3

—
—
—

2@-5%
2@-5%
2@-5%

EP
EP
EP

115
115
115

10-3/4
10-3/4
14-1/8

5
7.5
10

—
—
—

2@-5%
2@-5%
2@-5%

EP
EP
EP

115
115
115

16
16
19

10-3/8
10-3/8
13-3/8

9-7/8
9-7/8
10-1/2

105
123
193

406
406
482

263
263
339

251
251
266

48
56
88

FR177
FR178
FR179

2I
2I
2I

IndoorOutdoor

S60G11S05N
S60G11S07N
S60G11S10N

15
25
25

—
—
2 @ 2.5%

4@-2.5%
4@-2.5%
4@-2.5%

EP
EP
EP

115
115
115

19
22-3/8
20-3/4

13-3/8
16-3/8
19-1/8

13-3/8
14-1/2
13-5/8

216
385
395

482
568
525

339
416
483

266
359
349

98
175
180

FR180
FR182
FR132

527A
527A
83B

IndoorOutdoor

S60J11S15N
S60J11S25N
S60M11S25N

25
37.5
50

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DS-3
DS-3
DS-3

150
150
150

31-1/4
37-5/8
37-5/8

22-5/8
22-5/8
22-5/8

17-1/2
19-1/2
19-1/2

212
306
340

793
953
956

574
574
574

445
495
495

96
139
154

FR816
FR817
FR818

276B
262B
262B

WS11
WS11
WS11

T60M11S25
T60M11S37
T60M11S50D

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DS-3
DS-3
DS-3

150
150
150

42-1/8
42-1/8
62-7/8

24
24
30

23-3/8
23-3/8
34

510 1070
600 1070
1200 1597

610
610
762

594
594
863

232
272
545

FR819
FR820
FR814

262B
262B
288B

WS16
WS16
WS13

T60M11S75
T60M11S99
T60M11S67A

75
100
167


.5 —
.75 —
—

NEMA 3R, 316 stainless steel enclosure.
Refer to your local Eaton sales office

Note: Contact your local Eaton sales office
for CE Mark transformer requirements.

For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies
General Purpose Transformers

44-7

April 2009

Single-Phase Encapsulated (Type EP), Ventilated (Type DS-3), 60 Hz
Table 44-6. Single-Phase Selection Information — Types EP, DS-3, 60 Hz
kVA

Full Cap. Taps
FCAN

FCBN

Type °C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt. Dimensions (mm) Wt.
Lbs. H
kg
W
D

Frame Wiring
Weathershield Style
Diagram Catalog Price Number
Number Number U.S. $

Price
U.S. $

2400 Volts to 120/240 Volts
1.5
3
5
10
15
25
37.5
50
75
100

—

—

EP

115

10-3/4

6-5/8

42

273

157

166

19

FR68

18A

—

S42N11S16N 

—
—
—
—
—

4@-2.5%
4@-2.5%
4@-2.5%
4@-2.5%
4@-2.5%

EP
EP
EP
EP
EP

115
115
115
115
115

16
16
19
22-3/8
26-3/8

10-3/8
10-3/8
13-3/8
16-3/8
16-3/8

9-7/8
9-7/8
10-1/2
14-1/2
14-1/8

113
123
216
375
405

406
406
482
566
668

263
263
339
416
416

251
251
266
359
359

51
56
98
170
184

FR177
FR178
FR179
FR182
FR190

12A
12A
12A
12A
12A

—
—
—
—
—

S42J11S03N 
S42J11S05N 
S42J11S10N 
S42J11S15N 
S42J11S25N 

2@+2.5%
2@+2.5%
2@+2.5%
2@+2.5%

2@-2.5%
2@-2.5%
2@-2.5%
2@-2.5%

DS-3
DS-3
DS-3
DS-3

150
150
150
150

28
30
30
36

22
24
24
27

20
26
26
26

300
420
500
570

684
732
732
879

537
586
586
659

488
635
635
635

137
191
228
260











—
—
—
—

T42D11S37 
T42D11S50 
T42D11S75 
T42D11S99 

DS-3
DS-3

150
150

28
30

22
24

20
26

300
420

684
732

537
586

488
635

137
191







—
—

T42D21S37 
T42D21S50 

6-5/8

42

273

157

166

19

FR68

524G

—

S46N11S16N 

6-3/16

2400 Volts to 240/480 Volts
37.5
50

2@+2.5% 2@-2.5%
2@+2.5% 2@-2.5%

4160 Volts to 120/240 Volts
1.5

—

—

EP

115

10-3/4

3
5
10
15

—
—
—
—

4@-2.5%
4@-2.5%
4@-2.5%
4@-2.5%

EP
EP
EP
EP

115
115
115
115

16
16
19
22-3/8

10-3/8
10-3/8
13-3/8
16-3/8

9-7/8
9-7/8
10-1/2
14-1/2

113
123
193
375

406
406
482
566

263
263
339
416

251
251
266
359

51
56
88
170

FR177
FR178
FR179
FR182

12B
12B
12B
12B

—
—
—
—

S46J11S03N 
S46J11S05N 
S46J11S10A 
S46J11S15A 

25
37.5
50

2@+2.5% 2@-2.5%
2@+2.5% 2@-2.5%
2@+2.5% 2@-2.5%

DS-3
DS-3
DS-3

150
150
150

28
28
30

22
22
24

20
20
26

280
300
420

984
684
732

537
537
586

488
488
635

128
137
191









—
—
—

T46D11S25 
T46D11S37 
T46D11S50 

2@+2.5% 2@-2.5%
2@+2.5% 2@-2.5%
2@+2.5% 2@-2.5%

DS-3
DS-3
DS-3

150
150
150

30
36
50

24
27
33

26
26
35

500
570
1000

732
879
1220

586
659
806

635
635
854

228
260
455









—
—
—

T46D11S75 
T46D11S99 
T46D11S67 

DS-3
DS-3
DS-3
DS-3

150
150
150
150

28
30
30
36

22
24
24
27

20
26
26
26

300
420
500
570

684
732
732
879

537
586
586
659

488
635
635
635

137
191
228
260











—
—
—
—

T46D21S37 
T46D21S50 
T46D21S75 
T46D21S99 

75
100
167

6-3/16

4160 Volts to 240/480 Volts
37.5
50
75
100





2@+2.5%
2@+2.5%
2@+2.5%
2@+2.5%

2@-2.5%
2@-2.5%
2@-2.5%
2@-2.5%

No UL label.
Refer to your Eaton sales office.
NEMA 3R enclosure and/or UL label available at additional cost. Specify at time of order entry if required.
Not seismic qualified. Available by special order.

For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

44

Distribution & Control Transformers and Power Supplies
Electrostatically Shielded Transformers

44-8

April 2009

Single- and Three-Phase Types EP, DS-3, EPT, DT-3, 60 Hz

Single- and Three-Phase,
Types EP, DS-3, EPT, DT-3, 60 Hz

Application Description

Product Specifications

Electrostatically shielded transformers
are used to protect sensitive electrical
equipment from undesirable high frequency signals commonly generated
by lighting, switching surges, motors,
and SCRs feeding noise back into the
line. An electrostatic shield, consisting
of a single turn of aluminum foil placed
between the primary and secondary
winding, is used to provide from
30 to 70 dB attenuation of wide band
line-to-ground (common mode) noise.

Frequency

Typical uses of shielded isolation
transformers include:
Type DT-3

Product Description
Types EP, EPT
■
■
■
■

44

■
■
■
■

■

Sand and Resin Encapsulated design.
Suitable for indoor or outdoor
applications.
Totally enclosed, non-ventilated
enclosures.
Enclosures are NEMA 3R rated.
Mountable in any position indoors
and upright only outdoors.
185ºC insulation system.
115ºC rise standard; 80°C rise
optional.
Available in single-phase ratings
through 37.5 kVA and 4160 volts
primary (EP).
Available in three-phase ratings
through 75 kVA and 4160 volts
primary (EPT).

Types DS-3, DT-3
■
■

■
■
■
■

■

Ventilated, NEMA 2 enclosure
standard.
Suitable for indoor applications,
outdoors when weathershields are
also installed.
Upright mounting only.
220ºC insulation system.
150ºC rise standard; 115°C or 80°C
optional.
Available in single-phase ratings
15 – 167 kVA and up to 4160 volts
primary (DS-3).
Available in three-phase ratings
15 – 1500 kVA and up to 4160 volts
primary (DT-3).

Suppression of transients and noise
which travels from its source to the
sensitive load equipment.
■ Suppression of noise and transients
at the point where the noise or
transients are originating, thus
preventing them from backfeeding
from the source to the feeders.
■ Transform one voltage level to
another.
■ Isolate one circuit from another.
■

Features, Benefits
and Functions
UL listed.
■ 60 Hz operation standard,
50/60 Hz operation available.
■ Short-term overload capability
as required by ANSI.
■ Meet NEMA ST-20 sound levels.

Cutler-Hammer standard dry-type distribution transformers are designed
for 60 Hertz operation. Transformers
required for other frequencies are
available and must be specifically
designed.

Overload Capability
Short-term overload is designed into
transformers as required by ANSI.
Dry-type distribution transformers
will deliver 200% nameplate load for
one-half hour; 150% load for one hour;
and 125% load for four hours without
being damaged provided that a constant 50% load precedes and follows
the overload. See ANSI C57.96-01.250
for additional limitations.
Continuous overload capacity is not
deliberately designed into a transformer because the design objective is
to be within the allowed winding temperature rise with nameplate loading.

Insulation System and Temperature Rise
Industry standards classify insulation
systems and rise as shown below:
Table 44-7. Insulation System Classification
Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

■

Standards and Certifications
Industry Standards
All Cutler-Hammer dry-type distribution
and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI and IEEE Standards. All 600 volt
class transformers are UL listed unless
otherwise noted.

Seismically Qualified
Cutler-Hammer manufactured dry-type
distribution transformers are seismically qualified, and exceed requirements of the Uniform Building Code
(UBC), International Building Code (IBC)
and California Code Title 24.

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Enclosures
Cutler-Hammer ventilated
transformers, Types DS-3 and DT-3
utilize a NEMA 2 rated (drip-proof)
enclosure as standard, and are rated
NEMA 3R with the addition of
weathershields. Cutler-Hammer
encapsulated transformers, Types
EP and EPT, utilize a NEMA 3R rated
enclosure as standard.

The following pages provide listings for most
standard transformer ratings and styles.
For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies
Electrostatically Shielded Transformers

44-9

April 2009

Single- and Three-Phase, Types EP, 60 Hz
Table 44-8. Average Sound Levels 

Sound Levels
All Eaton’s Cutler-Hammer 600 volt
class general purpose dry-type distribution transformers are designed to
meet NEMA ST-20 sound levels listed
here. These are the sound levels measured in a soundproof environment.
Actual sound levels measured at an
installation will likely be higher due to
electrical connections and environmental conditions. Lower sound levels
are available and should be specified
when the transformer is going to
be installed in an area where sound
may be a concern.

Series-Multiple Windings

NEMA ST-20 Average Sound Level in dB
kVA
Up to 1.2 kV
Above 1.2 kV
Ventilated Encap- Ventilated
sulated
0–9
10 – 50
51 – 150
151 – 300
301 – 500
501 – 700
701 – 1000
1001 – 1500


40
45
50
55
60
62
64
65

45
50
55
57
59
61
63
64

45
50
55
58
60
62
64
65

Currently being reviewed and revised by
NEMA.

Winding Terminations
Primary and secondary windings are
terminated in the wiring compartment.
Encapsulated units have copper leads or
stabs brought out for connections. Ventilated transformers have leads brought
out to aluminum pads that are pre-drilled
to accept Cu/Al lugs. Lugs are not supplied with these transformers. Eaton recommends external cables be rated 90°C
(sized at 75°C ampacity) for encapsulated
designs and 75°C for ventilated designs.

Series-multiple windings consist of
2 similar coils in each winding which
can be connected in series or parallel
(multiple). Transformers with seriesmultiple windings are designated with
an “X” or “/” between the voltage
ratings, such as voltages of “120/240”
or “240 X 480.” If the series-multiple
winding is designated by an “X,” the
winding can be connected only for a
series or parallel. With the “/” designation, a mid-point also becomes available in addition to the series or parallel
connection. As an example, a 120 X 240
winding can be connected for either
120 (parallel) or 240 (series), but a
120/240 winding can be connected
for 120 (parallel), or 240 (series), or
240 with a 120 mid-point.

Product Selection
Additional Product Selection information begins on Page 44-63.

44

Table 44-9. Single-Phase Selection Information — Types EP, 60 Hz
kVA

Full Cap. Taps
FCAN FCBN

Type °C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt. Dimensions (mm)
Lbs. H
W
D

Wt.
kg

Frame

Wiring
Weathershield Style
Diagram Catalog Price Number
Number Number U.S. $

Price
U.S. $

120 x 240 Volts to 120/240 Volts
3
5
7.5
10
15
25

—
—
—

—
—
—

EP
EP
EP

115
115
115

14-1/8 7-3/4
10-3/8
16
10-3/8
16

50
90
123

359
406
406

197
263
263

203
251
251

23
41
56

FR176
FR177
FR178

90B
90B
90B

IndoorOutdoor

S10N11E03N
S10N11E05N
S10N11E07N

—
—
—

—
—
—

EP
EP
EP

115
115
115

13-3/8 10-1/2 210
19
13-3/8 13-3/8 205
19
22-3/8 16-3/8 14-1/2 375

482
482
568

339
339
416

266
266
359

95
93
170

FR179
FR180
FR182

90B
90B
90B

IndoorOutdoor

S10N11E10N
S10N11E15N
S10N11E25N

8
9-7/8
9-7/8

120 Volts to 120 Volts
3
5
7.5
10
15
25

—
—
—

—
—
—

EP
EP
EP

115
115
115

14-1/8 7-3/4
10-3/8
16
10-3/8
16

60
100
123

359
406
406

197
263
263

203
251
251

27
45
56

FR176
FR177
FR178

77A
77A
77A

IndoorOutdoor

S12N12E03N
S12N12E05N
S12N12E07N

—
—
—

—
—
—

EP
EP
EP

115
115
115

13-3/8 10-1/2 180
19
13-3/8 13-3/8 216
19
22-3/8 16-3/8 14-1/2 375

482
482
568

339
339
416

266
266
359

82
98
170

FR179
FR180
FR182

77A
77A
77A

IndoorOutdoor

S12N12E10N
S12N12E15N
S12N12E25N

8
9-7/8
9-7/8

208 Volts to 120/240 Volts
3
5
7.5
10
15
25

—
—
—

—
—
—

EP
EP
EP

115
115
115

14-1/8 7-3/4
10-3/8
16
10-3/8
16

60
135
95

359
406
406

197
263
263

203
251
251

27
61
43

FR176
FR177
FR178

578A
578A
578A

IndoorOutdoor

S29N11E03N
S29N11E05N
S29N11E07N

—
—
—

—
—
—

EP
EP
EP

115
115
115

13-3/8 10-1/2 165
19
13-3/8 13-3/8 185
19
22-3/8 16-3/8 14-1/2 375

482
482
568

339
339
416

266
266
359

75
94
170

FR179
FR180
FR182

578A
578A
578A

IndoorOutdoor

S29N11E10N
S29N11E15N
S29N11E25N

8
9-7/8
9-7/8

208 Volts to 208 Volts
3
5
7.5
10
15
25

—
—
—

—
—
—

EP
EP
EP

115
115
115

14-1/8 7-3/4
10-3/8
16
10-3/8
16

65
113
123

359
406
406

197
263
263

203
251
251

30
51
56

FR176
FR177
FR178

77B
77B
77B

IndoorOutdoor

S29N29E03N
S29N29E05N
S29N29E07N

—
—
—

—
—
—

EP
EP
EP

115
115
115

13-3/8 10-1/2 195
19
13-3/8 13-3/8 216
19
22-3/8 16-3/8 14-1/2 375

482
482
568

339
339
416

266
266
359

89
98
170

FR179
FR180
FR182

77B
77B
77B

IndoorOutdoor

S29N29E10N
S29N29E15N
S29N29E25N

8
9-7/8
9-7/8

Note: Contact your local Eaton sales office
for CE Mark transformer requirements.
For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

Distribution & Control Transformers and Power Supplies
Electrostatically Shielded Transformers

44-10

April 2009

Single-Phase, Types EP, DS-3, 60 Hz
Table 44-10. Single-Phase Selection Information — Types EP, DS-3, 60 Hz
kVA

Full Cap. Taps
FCAN

FCBN

Type °C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt. Dimensions (mm)
Lbs. H
W
D

Wt.
kg

Frame Wiring
Weathershield
Style
Diagram Catalog Price Number
Number Number U.S. $

Price
U.S. $

240 Volts to 240 Volts
3
5
7.5
10
15
25

—
—
—

—
—
—

EP
EP
EP

115
115
115

14-1/8 7-3/4
16
10-3/8
16
10-3/8

8
9-7/8
9-7/8

65
113
123

359
406
406

197
263
263

203
251
251

30
51
56

FR176 77C
FR177 77C
FR178 77C

IndoorOutdoor

S24N24E03N
S24N24E05N
S24N24E07N

—
—
—

—
—
—

EP
EP
EP

115
115
115

19
13-3/8
19
13-3/8
22-3/8 16-3/8

10-1/2
13-3/8
14-1/2

193
216
375

482
482
568

339
339
416

266
266
359

88
98
170

FR179 77C
FR180 77C
FR182 77C

IndoorOutdoor

S24N24E10N
S24N24E15N
S24N24E25N

277 Volts to 120/240 Volts
3
5
7.5
10
15
25

—
—
—

—
—
—

EP
EP
EP

115
115
115

14-1/8 7-3/4
16
10-3/8
16
10-3/8

8
9-7/8
9-7/8

65
113
75

359
406
406

197
263
263

203
251
251

30
51
34

FR176 513B
FR177 513B
FR178 513B

IndoorOutdoor

S27N11E03N
S27N11E05N
S27N11E07N

—
—
—

—
—
—

EP
EP
EP

115
115
115

19
13-3/8
19
13-3/8
22-3/8 16-3/8

10-1/2
13-3/8
14-1/2

162
216
375

482
482
568

339
339
416

266
266
359

74
98
170

FR179 513B
FR180 513B
FR182 513B

IndoorOutdoor

S27N11E10N
S27N11E15N
S27N11E25N

240 x 480 Volts to 120/240 Volts
.25 —
.50 —
.75 —

44




EP
EP
EP

115
115
115

6-1/2
6-1/2
8-5/8

4-5/8
4-5/8
5-3/4

4-1/8
4-15/16
5-3/4

12
16
26

165
165
219

117
117
146

103
125
146

5
7
12

FR56 90A
FR57 90A
FR58A 90A

IndoorOutdoor

S20N11E26A
S20N11E51A
S20N11E76A

5-3/4
6-3/16
6-3/16

5-3/4
6-5/8
6-5/8

31
42
42

219
273
273

146
157
157

146
166
166

14
19
19

FR59A 90A
FR67 90A
FR68 90A

IndoorOutdoor

S20N11E01A
S20N11E16A
S20N11E02A

8
9-7/8
9-7/8

65
113
123

359
406
406

195
263
263

203
251
251

30
51
56

FR176 90A
FR177 90A
FR178 90A

IndoorOutdoor

S20N11E03A
S20N11E05A
S20N11E07A

1
1.5
2

—
—
—

—
—
—

EP
EP
EP

115
115
115

8-5/8
10-3/4
10-3/4

3
5
7.5

—
—
—

—
—
—

EP
EP
EP

115
115
115

14-1/8 7-11/16
16
10-3/8
16
10-3/8

10
15
25

—
—



—
—


EP
EP
EP

115
115
115

19
13-3/8
19
13-3/8
22-3/8 16-3/8

10-1/2
13-3/8
14-1/2

166
216
375

482
482
568

339
339
416

266
266
359

75
98
170

FR179 90A
FR180 90A
FR182 526A

IndoorOutdoor

S20N11E10A
S20N11E15A
S20L11E25A

15
25
37.5









DS-3 150
DS-3 150
DS-3 150

30-1/4 16-7/8
31-1/4 22-5/8
37-5/8 22-5/8

15-7/8
17-1/2
19-1/2

147
212
306

768
793
953

428
574
574

402
445
495

67
96
139

FR815 261A
FR816 261A
FR817 261A

WS15
WS11
WS11

T20P11E15 
T20P11E25 
T20P11E37 









DS-3 150
DS-3 150
DS-3 150

37-5/8 22-5/8
42-1/8 24
42-1/8 24

19-1/2
23-3/8
23-3/8

340
510
600

953 574
1070 610
1070 610

495
594
594

154
232
272

FR818 261A
FR819 261A
FR820 261A

WS11
WS16
WS16

T20P11E50 
T20P11E75 
T20P11E99 

50
75
100


—
—
—

2@+5% FCBN at 240 volts; 4@-2.5% FCBN at 480 volts.
1@+5%, 2@-5% at 240 volts primary; 2@+2.5%, 4@-2.5% at 480 volts primary.
Do not meet Federal Energy Efficiency standards that are effective January 1, 2007. Cannot be purchased for use in the United States or territories.

Note: Contact your local Eaton sales office for CE Mark transformer requirements.

For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-11
Electrostatically Shielded Transformers
April 2009

Three-Phase, Types EPT, DT-3, 60 Hz
Table 44-11. Three-Phase Selection Information — Types EPT, DT-3, 60 Hz
kVA

Full Cap. Taps
FCAN

FCBN

Type °C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt. Dimensions (mm) Wt. Frame
Lbs. H
kg
W
D

Wiring
Weathershield Style
Diagram Catalog Price Number
Number Number U.S. $

Price
U.S. $

208 ∆ Volts to 208Y/120 Volts
15

2@+2.5% 2@-2.5%

EPT

115

17-3/8

20

10-9/16

275

441

508

267

125 FR95

86A

15
30

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DT-3
DT-3

150
150

25
30

20-1/8
20-1/8

14-1/8
14-1/8

152
230

635
762

511
511

359
359

69 FR909
104 FR910A

45
2@+2.5% 4@-2.5%
75
2@+2.5% 4@-2.5%
112.5 1@+5%
2@-5%

DT-3
DT-3
DT-3

150
150
150

30
39-1/4
39-1/4

20-1/8
26-1/8
26-1/8

14-3/8
19-1/8
19-1/8

310
480
600

762
995
995

511
663
663

364
486
485

150
225
300

DT-3
DT-3
DT-3

150
150
150

46-5/8
62-1/4
62-1/4

28
31-1/4
31-1/4

23
30-1/4
30-1/4

870
1600
1600

1183
1581
1581

710
794
794

584
768
768

1@+5%
1@+5%
1@+5%

2@-5%
2@-5%
2@-5%

Y29D28E15B 

283A
283A

IndoorOutdoor
WS31
WS31

V29M28E15A 
V29M28E30B 

140 FR912A
218 FR914B
272 FR915B

283A
283A
325A

WS31
WS33
WS33

V29M28E45B 
V29M28E75B 
V29R28E12B 

395 FR916A
728 FR918A
728 FR918A

325A
287A
287A

WS19
WS34
WS34

V29R28E49B 
V29R28E22B 
V29R28E33B 

86B
86B
86B
86B

IndoorOutdoor

Y48D28E03A 
Y48D28E06A 
Y48D28E09N 
Y48D28E15B 

480 ∆ Volts to 208Y/120 Volts
3
6
9
15

2@+2.5%
2@+2.5%
2@+2.5%
2@+2.5%

2@-2.5%
2@-2.5%
2@-2.5%
2@-2.5%

EPT
EPT
EPT
EPT

115
115
115
115

13-3/8
15-7/8
15-7/8
17-3/8

15-15/16 8-5/16
16-1/2
9-7/8
16-1/2
9-7/8
20
10-9/16

116
165
190
275

340
403
403
441

405
419
419
508

211
251
251
267

52
75
86
125

15
30
45

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

25
30
30

20-1/8
20-1/8
20-1/8

14-1/8
14-1/8
14-3/8

152
230
325

635
762
762

511
511
511

359
359
364

69 FR909
104 FR910A
148 FR912A

283B
283B
283B

WS31
WS31
WS31

V48M28E15B 
V48M28E30B 
V48M28E45 

75
2@+2.5% 4@-2.5%
112.5 2@+2.5% 4@-2.5%
150
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

39-1/4
46-5/8
46-5/8

26-1/8
28
28

19-1/8
23
23

515
870
870

995
1183
1183

663
710
710

486
584
584

234 FR914B
395 FR916A
395 FR916A

283B
283B
283B

WS33
WS19
WS19

V48M28E75 
V48M28E12 
V48M28E49 

225
300
500

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

56-1/4
57-1/2
75

31-1/4
36-1/4
44-1/2

24-1/4
32-1/4
36

1200
1710
2500

1427
1460
1905

790
921
1130

616
817
914

545 FR917
776 FR923
1135 FR919

292A
292A
292A

WS34
WS37
WS35

V48M28E22 
V48M28E33 
V48M28E55G 

750
1000

2@+2.5% 4@-2.5%
1@+3.5% 1@-3.5%

DT-3
DT-3

150
150



75

44-1/2

36

2900

1905

1130

914

1315 FR920

292A

WS35


V48M28E77B 
V48W28E11A 















FR201
FR200
FR103
FR95





480 ∆ Volts to 208Y/120 Volts — Copper Windings
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

25
30
30

20-1/8
20-1/8
20-1/8

14-1/8
14-1/8
14-3/8

172
300
370

635
762
762

511
511
511

359
359
364

78 FR909
136 FR910A
168 FR912A

283B
283B
283B

WS31
WS31
WS31

V48M28E15CU 
V48M28E30CU 
V48M28E45CU 

75
2@+2.5% 4@-2.5%
112.5 2@+2.5% 4@-2.5%
150
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

39-1/4
39-1/4
46-5/8

26-1/8
26-1/8
28

19-1/8
19-1/8
23

600
675
900

995
995
1183

663
663
710

485
485
584

272 FR915B
306 FR915B
409 FR916A

283B
283B
283B

WS33
WS33
WS19

V48M28E75CU 
V48M28E12CU 
V48M28E49CU 

225
300
500

DT-3
DT-3
DT-3

150
150
150

56-1/4
62-1/4
75

31-1/4
31-1/4
44-1/2

24-1/4
30-1/4
36

1200
2150
3100

1427
1581
1905

790
794
1130

616
768
914

545 FR917
977 FR918A
1407 FR919

283B
283B
292A

WS34
WS34
WS35

V48M28E22CU 
V48M28E33CU 
V48M28E55CU 

15
30
45

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

480 ∆ Volts to 480Y/277 Volts






9
15

2@+2.5% 2@-2.5%
2@+2.5% 2@-2.5%

EPT
EPT

115
115

15-7/8
17-3/8

16-1/2
20

9-7/8
10-9/16

190
275

403
441

419
508

251
267

86 FR103
125 FR95

86C
86C

IndoorOutdoor

Y48D47E09N 
Y48D47E15B 

30
45
75

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

30
30
39-1/4

20-1/8
20-1/8
26-1/8

14-1/8
14-3/8
19-1/8

230
310
480

762
762
995

511
511
663

359
364
486

104 FR910A
140 FR912A
218 FR914B

283B
283B
283B

WS31
WS31
WS33

V48M47E30B 
V48M47E45B 
V48M47E75B 

112.5 2@+2.5% 4@-2.5%
150
2@+2.5% 4@-2.5%
225
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

39-1/4
46-5/8
56-1/4

26-1/8
28
31-1/4

19-1/8
23
24-1/4

600
950
1100

995
1183
1427

663
710
790

485
584
616

272 FR915B
431 FR916A
499 FR917

283B
283B
283B

WS33
WS19
WS34

V48M47E12B 
V48M47E49B 
V48M47E22B 

300
500
750

DT-3
DT-3
DT-3

150
150
150

62-1/4
75
75

31-1/4
44-1/2
44-1/2

30-1/4
36
36

1600
2400
2900

1581
1905
1905

794
1130
1130

768
914
914

728 FR918A
1088 FR919
1315 FR920

283B
292A
292A

WS34
WS35
WS35

V48M47E33B 
V48M47E55G 
V48M47E77A 

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

T-T connected secondary.
Do not meet Federal Energy Efficiency standards that are effective January 1, 2007. Cannot be purchased for use in the United States or territories.
Refer to your Eaton sales office.
Not seismic qualified. Available by special order.

Note: Contact your local Eaton sales office for CE Mark transformer requirements.

For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

44

Distribution & Control Transformers and Power Supplies
Electrostatically Shielded Transformers

44-12

April 2009

Three-Phase, Types EPT, DT-3, 60 Hz
Table 44-12. Three-Phase Selection Information — Types EPT, DT-3, 60 Hz
kVA

Full Cap. Taps
FCAN

FCBN

Type °C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt. Dimensions (mm) Wt.
Lbs. H
kg
W
D

Frame

Wiring
Weathershield Style
Diagram Catalog Price Number
Number Number U.S. $

Price
U.S. $

FR201
FR200
FR103
FR95

88A
88A
505B
505B

IndoorOutdoor

Y48G24E03A 
Y48G24E06A 
Y48J24E09A 
Y48J24E15A 

480 ∆ Volts to 240 ∆ Volts
3
6
9
15

—
—
—
—

2@-5%
2@-5%
4@-2.5%
4@-2.5%

EPT
EPT
EPT
EPT

115
115
115
115

13-3/8
15-7/8
15-7/8
17-3/8

15-15/16 8-5/16
16-1/2
9-7/8
16-1/2
9-7/8
20
10-9/16

116
165
195
275

340
403
403
441

405
419
419
508

211
251
251
267

52
75
89
125

480 ∆ Volts to 240 ∆ Volts With 120 Volt Lighting Tap on B Phase 
15
30
45

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

25
30
30

20-1/8
20-1/8
20-1/8

14-1/8
14-1/8
14-3/8

152
230
310

635
762
762

511
511
511

359
359
364

69 FR909
104 FR910A
140 FR912A

284B
284B
284B

WS31
WS31
WS31

V48M22E15B 
V48M22E30A 
V48M22E45A 

75
112.5
150

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

39-1/4
39-1/4
46-5/8

26-1/8
26-1/8
28

19-1/8
19-1/8
23

480
600
785

995
995
1183

663
663
710

486
485
584

218 FR914B
272 FR915B
356 FR916A

284B
284B
284B

WS33
WS33
WS19

V48M22E75A 
V48M22E12A 
V48M22E49A 

225
300
500

2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%
2@+2.5% 4@-2.5%

DT-3
DT-3
DT-3

150
150
150

56-1/4
62-1/4
75

31-1/4
31-1/4
44-1/2

24-1/4
30-1/4
36

1100
1600
2400

1427
1581
1905

790
794
1130

616
768
914

499 FR917
728 FR918A
1088 FR919

284B
284B
293A

WS34
WS34
WS35

V48M22E22A 
V48M22E33A 
V48M22E55A 





T-T connected secondary.
Center Tap capacity limited to 5% of rated kVA.
Do not meet Federal Energy Efficiency standards that are effective January 1, 2007. Cannot be purchased for use in the United States or territories.

Note: Contact your local Eaton sales office for CE Mark transformer requirements.

44

For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-13
Open Type Core and Coil Assembly Transformers
April 2009

Single- and Three-Phase

Single- and Three-Phase,
Types DS-3C, DT-3C, 60 Hz
Product Description
220°C insulation system, 150°C
rise standard; 115°C or 80°C
optional.
■ Aluminum windings
(copper optional).
■

Application Description
The basic purpose of a transformer
is voltage transformation as near as
practically possible to the load for
economy and distribution of power.
Typical loads for dry-type distribution
transformers include lighting, heating,
air conditioners, fans, and machine
tools. Such loads are found in
commercial, institutional, industrial,
and residential structures.
Open core and coil assemblies are
typically used by panel builders and
equipment OEM customers who
incorporate the entire transformer
into their structures. A versatile option
to purchasing a standard, enclosed
transformer and discarding the
unneeded enclosure parts.

Features, Benefits
and Functions
■

 (UL recognized).

60 Hz operation standard,
50/60 Hz operation available.
■ Short-term overload capability as
required by ANSI.
■ Meet NEMA ST-20 sound levels.
■

Product Specifications

Sound Levels

Frequency
Cutler-Hammer standard dry-type distribution transformers are designed for 60
Hz operation. Transformers required for
other frequencies are available and
must be specifically designed.

Overload Capability
Short-term overload is designed into
transformers as required by ANSI.
Dry-type distribution transformers
will deliver 200% nameplate load for
one-half hour; 150% load for one-hour;
and 125% load for four-hours without
being damaged provided that a constant 50% load precedes and follows
the overload. See ANSI C57.96-01.250
for additional limitations.
Continuous overload capacity is not
deliberately designed into a transformer because the design objective is
to be within the allowed winding temperature rise with nameplate loading.

Insulation System and Temperature Rise
Industry standards classify insulation
systems and rise as shown below:
Table 44-13. Insulation System Classification
Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Standards and Certifications
Industry Standards
All Cutler-Hammer dry-type distribution and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI, and IEEE Standards.

Seismically Qualified
All Cutler-Hammer manufactured
dry-type distribution transformers
are seismically qualified, and exceed
requirements of the Uniform Building
Code (UBC), International Building
Code and California Code Title 24.
The following pages provide listings for most
standard transformer ratings and styles.
For other ratings or styles not shown, refer
to Eaton.

CA08102001E

For more information visit: www.eaton.com

All Cutler-Hammer 600 volt class general
purpose dry-type distribution transformers are designed to meet NEMA ST-20
sound levels listed here. These are the
sound levels measured in a soundproof
environment. Actual sound levels measured at an installation will likely be higher
due to electrical connections and environmental conditions. Lower sound levels are
available and should be specified when
the transformer is going to be installed in
an area where sound may be a concern.
Table 44-14. Average Sound Levels 
NEMA ST-20 Average Sound Level in dB
kVA

Up to 1.2 kV

Above 1.2 kV

Ventilated Encap- Ventilated
sulated
0–9
10 – 50
51 – 150
151 – 300

40
45
50
55

45
50
55
57

45
50
55
58

301 – 500
501 – 700
701 – 1000
1001 – 1500

60
62
64
65

59
61
63
64

60
62
64
65



Currently being reviewed and revised by
NEMA.

Winding Terminations
Lugs are not supplied with these transformers. Eaton recommends external
cables be rated 90°C (sized at 75°C
ampacity) for encapsulated designs
and 75°C for ventilated designs.

Series-Multiple Windings
Series-multiple windings consist of 2
similar coils in each winding which can
be connected in series or parallel (multiple). Transformers with series-multiple
windings are designated with an “X” or
“/” between the voltage ratings, such as
voltages of “120/240” or “240 X 480.” If
the series-multiple winding is designated by an “X,” the winding can be
connected only for a series or parallel.
With the “/” designation, a mid-point
also becomes available in addition to
the series or parallel connection. As an
example, a 120 X 240 winding can be
connected for either 120 (parallel) or 240
(series), but a 120/240 winding can be
connected for 120 (parallel), or 240
(series), or 240 with a 120 mid-point.

44

Distribution & Control Transformers and Power Supplies
Open Type Core and Coil Assembly Transformers

44-14

April 2009

Single- and Three-Phase

Product Selection
Additional Product Selection information begins on Page 44-63.
Table 44-15. Single-Phase Selection Information — Type DS-3C, 60 Hz
kVA

Full Cap. Taps
FCAN

Type

FCBN

°C
Dimensions (Inches)
Temp. H
W
D
Rise

Wt.
Lbs.

150
150
150
150

147
212
306
340

Dimensions (mm)
D

Wt.
kg

Frame

W

Wiring
Style
Diagram Number
Number

428
574
574
574

402
445
495
495

67
96
139
154

FR815C
FR816C
FR817C
FR818C

3XA
3XA
3XA
3XA

Wt. Dimensions (mm)
Lbs. H
W
D

Wt.
kg

Frame

Wiring
Style
Diagram Number
Number

14
14
14

128
195
250

516
605
629

511
511
511

356
356
356

58
89
114

FR909C
FR910C
FR912C

280B
280B
280B

V48M28T15ZZ
V48M28T30ZZ
V48M28T45ZZ

25-5/16 19
25-5/16 19
25-5/16 20

395
530
656

746
797
1052

643
643
643

483
483
508

180
241
298

FR914AC 280B
FR915C
280B
FR916C
280B

V48M28T75ZZ
V48M28T12ZZ
V48M28T49ZZ

H

Price
U.S. $

240 x 480 Volts to 120/240 Volts
15
25
37.5
50












DS-3C
DS-3C
DS-3C
DS-3C

30-1/4
31-1/4
37-5/8
37-5/8

16-7/8
22-5/8
22-5/8
22-5/8

15-7/8
17-1/2
19-1/2
19-1/2

768
793
953
953

T20P11S15ZZ
T20P11S25ZZ
T20P11S37ZZ
T20P11S50ZZ

1@+5%, 2@–5% at 240 volts primary; 2@+2.5%, 4@–2.5% at 480 volts primary.

Table 44-16. Three-Phase Selection Information — Type DT-3C, 60 Hz
kVA

Full Cap. Taps
FCAN

FCBN

Type

°C
Dimensions (Inches)
Temp. H
W
D
Rise

Price
U.S. $

480 ∆ Volts to 208Y/120 Volts
15
30
45

2@+2.5% 4@-2.5% DT-3C 150
2@+2.5% 4@-2.5% DT-3C 150
2@+2.5% 4@-2.5% DT-3C 150

20-5/16 20-1/8
23-13/16 20-1/8
24-3/4
20-1/8

75
112.5
150

2@+2.5% 4@-2.5% DT-3C 150
2@+2.5% 4@-2.5% DT-3C 150
2@+2.5% 4@-2.5% DT-3C 150

29-3/8
31-3/8
41-7/16

Note: Contact your local Eaton sale offices for availability of additional Open Type Core and Coil Assemblies.
Note: Contact your local Eaton sales office for CE Mark transformer requirements.

44

For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-15
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Single- and Three-Phase

Single- and Three-Phase
Applications, 60 Hz

Features, Benefits
and Functions

Insulation System and Temperature Rise

UL listed.
60 Hz operation.
■ 600 volt class insulation.
■ Short-term overload capability
as required by ANSI.
■ Meet NEMA ST-20 sound levels.

Table 44-17. Insulation System Classification

■
■

Standards and Certifications
Industry Standards
Type EP

Product Description
Types EP, EPT
■
■
■
■
■
■
■
■

Sand and Resin Encapsulated design.
Suitable for indoor or outdoor
applications.
Totally enclosed, non-ventilated
enclosures.
Enclosures are NEMA 3R rated.
Mountable in any position indoors
and upright only outdoors.
185ºC insulation system.
115ºC rise standard; 80°C rise
optional.
Available in single-phase ratings
through 7.5 kVA.

All Cutler-Hammer dry-type distribution
and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI and IEEE Standards. All 600 volt
class transformers are UL listed unless
otherwise noted.

Seismically Qualified
Cutler-Hammer manufactured dry-type
distribution transformers are seismically qualified, and exceed requirements of the Uniform Building Code
(UBC), International Building Code (IBC)
and California Code Title 24.

Product Specifications
Frequency
Cutler-Hammer buck-boost transformers are designed for 60 Hz operation.

Overload Capability

Application Description
A buck-boost transformer is used
to provide an economical method of
correcting a lower or higher voltage
rating more suitable for efficient operation of electrical equipment. Type EP
Buck-Boost transformers are small
kVA, single-phase transformers with
dual primary and dual secondary
windings and are usually connected as
autotransformers by utilizing one unit
for single-phase applications and
either two or three units banked for
three-phase operation. They are primarily used for motor operation and
should not be used for motor control
circuits, to correct fluctuating line
voltage or to obtain a neutral on a
delta system. Buck-boost transformers
are ideally suited for use with low
voltage lighting systems, such as
outdoor lighting.

CA08102001E

Short-term overload is designed into
transformers as required by ANSI.
Dry-type distribution transformers
will deliver 200% nameplate load for
one-half hour; 150% load for one-hour;
and 125% load for four-hours without
being damaged provided that a constant 50% load precedes and follows
the overload. See ANSI C57.96-01.250
for additional limitations.
Continuous overload capacity is not
deliberately designed into a transformer because the design objective is
to be within the allowed winding temperature rise with nameplate loading.

Industry standards classify insulation
systems and rise as shown below:
Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Enclosures
Cutler-Hammer encapsulated buckboost transformers utilize a NEMA 3R
rated enclosure.

Sound Levels
All Cutler-Hammer 600 volt class general purpose dry-type distribution
transformers are designed to meet
NEMA ST-20 sound levels listed here.
These are the sound levels measured
in a soundproof environment. Actual
sound levels measured at an installation will likely be higher due to electrical connections and environmental
conditions. Lower sound levels are
available and should be specified
when the transformer is going to be
installed in an area where sound may
be a concern.
Table 44-18. Average Sound Levels 
NEMA ST-20 Average Sound Level in dB
kVA

Up to 1.2 kV
Encapsulated

0–9
10 – 50
51 – 150
151 – 300

45
50
55
57

301 – 500
501 – 700
701 – 1000
1001 – 1500

59
61
63
64



Currently being reviewed and revised by
NEMA.

Winding Terminations
Primary and secondary windings are
terminated in the wiring compartment.
Encapsulated units have copper leads
or stabs brought out for connections.
Lugs are not supplied with these
transformers. Eaton recommends
external cables be rated 90°C (sized
at 75°C ampacity) for encapsulated
designs.

For more information visit: www.eaton.com

44

44-16

Distribution & Control Transformers and Power Supplies
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Single- and Three-Phase
Series-Multiple Windings
Series-multiple windings consist of 2
similar coils in each winding which
can be connected in series or parallel
(multiple). Transformers with seriesmultiple windings are designated with
an “X” or “/” between the voltage
ratings, such as voltages of “120/240”
or “240 X 480.” If the series-multiple
winding is designated by an “X,” the
winding can be connected only for a
series or parallel. With the “/” designation, a mid-point also becomes available in addition to the series or parallel
connection. As an example, a 120 X
240 winding can be connected for
either 120 (parallel) or 240 (series), but
a 120/240 winding can be connected
for 120 (parallel), or 240 (series),
or 240 with a 120 mid-point.
Note: When installation is to be made on a
grounded system, consideration must be
given to the resulting voltage. Thus, on a
208 grounded wye/120 system the voltage
can be boosted to 240 volts but the voltage
to ground will be 139 volts. If 240/120 volts
with a mid-point ground is needed, a standard two-winding transformer must be used.

44

The following formulas can be used to
calculate specific requirements.
For Single-Phase:
Load Voltage x
Full Line Amperes
LOAD kVA = --------------------------------------------1000

For Three-Phase:
Line Load Voltage x 1.73 x
Full Load Amperes
LOAD kVA = -----------------------------------------------------------------1000

Product Selection

5-Step Selector

For quick selection data, refer to the
tables on the following pages.

The tables which follow will simplify
the selection of the buck-boost transformers. There are no calculations
needed; simply follow these 5 steps.

Selection Requirements
You should have the following
information before selecting a
buck-boost transformer.
Line Voltage
The voltage that you want to buck
(decrease) or boost (increase). This
can be found by measuring the supply
line voltage with a voltmeter.
Load Voltage
The voltage at which your equipment
is designed to operate. This is listed on
the nameplate of the load equipment.
Load Amperes or Load kVA
You do not need to know both — one
or the other is sufficient for selection
purposes. This information usually can
be found on the nameplate of the
equipment that you want to operate.
Frequency
The supply line frequency must be the
same as the frequency of the equipment to be operated — Eaton’s CutlerHammer Buck-Boost Transformers
operate at 60 Hz only.
Phase
The supply line should be the same as
the equipment to be operated — either
single or three-phase.

Transformer Interconnection
For three-phase applications, interconnections of transformers should be
made in a junction box. Two or three
transformers may be used depending
on an open delta (2) or wye (3)
connection.

For more information visit: www.eaton.com

1. Refer to the table having the same
output voltage as the equipment
you want to operate. For example,
if you are installing a 240 volt 6 kVA
single-phase load use Selection
Table 44-23.
2. Select the available line voltage
across the top of the chart which
is closest to the actual supply voltage. Therefore, for example, if the
available line voltage is 213 volts,
use the 212 volt column.
3. Read down the column until you
reach an output kVA or amps rating equal to or greater than the
load requirements. Since 6 kVA, in
the example, is not listed, use the
next higher rating or 7.5 kVA.
4. Read across to the far left columns
for the catalog number and quantity of transformers for your application. In this case, you will need
one (1) catalog number
S10N06A01N.
5. Connect the buck-boost transformer(s) you have selected in
accordance with the connection
diagram specified at the bottom of
the available line voltage column.
In this example, Diagram “F”
would be used.
Note: For 1-phase connections and 3-phase
open delta connections, inputs and outputs
may be reversed. kVA capacity remains
constant.

Additional Product Selection
information begins on Page 44-63.

CA08102001E

Distribution & Control Transformers and Power Supplies 44-17
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Single- and Three-Phase

Wiring Diagrams
Diagram A

Diagram B

Diagram C

High Voltage

Low Voltage

High Voltage

X3

X4

X1

X2

H4

H3

H4

H2

H1

H2

X1

X3

X4

X1

X2

H3

H4

H3

H1

H2

X2 X3

Low Voltage

X4

Diagram D

Diagram E

Diagram F

Low Voltage

X1

High Voltage

High Voltage

X2 X3

X4

H4

H3

H2

H1

X3

X4

X1

X2

H4

H3

X1

H2

H1

H4

X2

H4

X4

H2

X3

X4

X1

X2

X3

X4

X4

X3

X1

X2

X2

X1

H4 H3 H2

H1

H2 H3 H4

Low Voltage

High Voltage

Diagram J

H1

High Voltage

H2

H1

H2

Diagram I
High Voltage

X3

H3

H3

X4

Low Voltage

Diagram H
Low Voltage

X1

X2 X3

Low Voltage

High Voltage

Diagram G

H1

High Voltage

Low Voltage

Vo

Diagram K

Diagram L

High Voltage

Low Voltage

High Voltage

44
X3

X4

X4

X3

X1

X2

X2

X1

H1 H1

H2

H2

X1 X2 X3 X4

X4 X3 X2 X1

H4 H3 H2 H1

H1 H2 H3 H4

Diagram M 
X3

X2
H3

H2

H1

X4

X3

X1
H4

X2
H3

X1
H4

H2

H1

H2

Low Voltage

Diagram O 

X3
X2

X2
H3

H4

H1

H2

X1
X4

H3

X3
X2

Neutral

X4

X2
X1

X3

H4

H3

H4

H3

H2

H1

H2

H1

X2
X3

H3

H2

H4

H2

H4

X2
H3

X1
H4

X2
H3

H2

H1

H1

H2

H1

High Voltage

Neutral

High Voltage

X3

X4

X3

X4

X1

X2

X1

X2

X1

X2

H3

H1

H3

H1
H2

X1

H3 H1
H4 H2

H4

X3

X2

H1
H2

Low Voltage

High Voltage

X4
X3

H3
H4

X1

X3

X1

X3

X2

X4

X2

X4

X2

H3

H1

H3

H1

H3 H1

H2

H4

H2

X4

H2

H1

Neutral

X1

Neutral

Diagram R 

Low Voltage

Neutral

Neutral

Diagram U
High Voltage

High Voltage

X2

H3

X1
H4

H2

Diagram T

H1

X4

X2
H3

X4

Low Voltage

X3

X3

X1
H4

X3

H3

Diagram S 

X1

X4

H3

X4

X1

High Voltage

X4

X3

X4

H4

Low Voltage

H4

X3

X4

High Voltage

X4

X3

X3
X3
X2

Diagram Q 

X2

X2

X1
X4

H3

H4

Low Voltage

X1

Low Voltage

X4

Diagram P 

X1

H1 H2 H3 H4

High Voltage
X1

X1
H4

H4 H3 H2 H1

High Voltage

Diagram N 
High Voltage

X4

X4 X3 X2 X1

Low Voltage

Low Voltage

X3

X1 X2 X3 X4

X3

X4

X4

X3

X1

X2

X2

X1

X3

X4

X1

X2

H1
H4

H2

H1

H1

H4

Low Voltage

Neutral

H1

H4

Low Voltage

Figure 44-1. Buck-Boost Transformers Wiring Diagrams


WARNING! If input is 3-wire, “neutral” connection must be isolated and insulated! When used to supply a 3-phase, 4-wire load, the source must be
3-phase, 4-wire wye.

CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Buck-Boost and Low Voltage Lighting Transformers

44-18

April 2009

Single- and Three-Phase
Table 44-19. Selection Information
kVA

°C Temp.
Rise

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Frame

Style
Number

FR52
FR54
FR55

S10N04A81N
S10N04A82N
S10N04A83N

Price
U.S. $

120 x 240 Volts to 12/24 Volts
.05
.10
.15

115
115
115

6-1/2
6-1/2
6-1/2

3-7/8
3-7/8
3-7/8

3-1/2
3-1/2
3-1/2

7
7
8

165
165
165

98
98
98

89
89
89

3
3
4

.25
.50
.75

115
115
115

6-1/2
6-1/2
8-3/8

4-7/8
4-7/8
6

3-7/8
4-5/8
5-3/4

12
13
21

165
165
213

124
124
152

98
117
146

5
5
10

FR56
FR57
FR58A

S10N04A26N
S10N04A51N
S10N04A76N

1
1.5
2

115
115
115

8-3/8
10-3/4
10-3/4

6
6-3/16
6-3/16

5-3/4
6-1/8
6-1/8

31
40
40

213
273
273

152
157
157

146
156
156

14
18
18

FR59A
FR67
FR68

S10N04A01N
S10N04A16N
S10N04A02N

3
5
7.5

115
115
115

14-1/8
16
16

7-11/16
10-3/8
10-3/8

8
9-7/8
9-7/8

65
113
123

359
406
406

195
263
263

203
251
251

29
51
55

FR176
FR177
FR178

S10N04A03N
S10N04A05N
S10N04A07N

FR52
FR54
FR55

S10N06A81N
S10N06A82N
S10N06A83N

120 x 240 Volts to 16/32 Volts
.05
.10
.15

115
115
115

6-1/2
6-1/2
6-1/2

3-7/8
3-7/8
3-7/8

3-1/2
3-1/2
3-1/2

7
7
8

165
165
165

98
98
98

89
89
89

3
3
4

.25
.50
.75

115
115
115

6-1/2
6-1/2
8-3/8

4-7/8
4-7/8
6

3-7/8
4-5/8
5-3/4

12
13
21

165
165
213

124
124
152

98
117
146

5
5
10

FR56
FR57
FR58A

S10N06A26N
S10N06A51N
S10N06A76N

1
1.5
2

115
115
115

8-3/8
10-3/4
10-3/4

6
6-3/16
6-3/16

5-3/4
6-1/8
6-1/8

31
40
40

213
273
273

152
157
157

146
156
156

14
18
18

FR59A
FR67
FR68

S10N06A01N
S10N06A16N
S10N06A02N

3
5
7.5

115
115
115

14-1/8
16
16

7-11/16
10-3/8
10-3/8

8
9-7/8
9-7/8

65
113
123

359
406
406

195
263
263

203
251
251

29
51
55

FR176
FR177
FR178

S10N06A03N
S10N06A05N
S10N06A07N

FR52
FR54
FR55

S20N08A81N
S20N08A82N
S20N08A83N

240 x 480 Volts to 24/48 Volts

44

.05
.10
.15

115
115
115

6-1/2
6-1/2
6-1/2

3-7/8
3-7/8
3-7/8

3-1/2
3-1/2
3-1/2

7
7
8

165
165
165

98
98
98

89
89
89

3
3
4

.25
.50
.75

115
115
115

6-1/2
6-1/2
8-3/8

4-7/8
4-7/8
6

3-7/8
4-5/8
5-3/4

12
13
21

165
165
213

124
124
152

98
117
146

5
5
10

FR56
FR57
FR58A

S20N08A26N
S20N08A51N
S20N08A76N

1
1.5
2

115
115
115

8-3/8
10-3/4
10-3/4

6
6-3/16
6-3/16

5-3/4
6-1/8
6-1/8

31
40
40

213
273
273

152
157
157

146
156
156

14
18
18

FR59A
FR67
FR68

S20N08A01N
S20N08A16N
S20N08A02N

3
5
7.5

115
115
115

14-1/8
16
16

7-11/16
10-3/8
10-3/8

8
9-7/8
9-7/8

65
113
123

359
406
406

195
263
263

203
251
251

29
51
55

FR176
FR177
FR178

S20N08A03N
S20N08A05N
S20N08A07N

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-19
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Single-Phase
Table 44-20. Single-Phase 115 Volt Output Required, 60 Hz
Units
Unit
Required  kVA

Input Available Voltage
84

91

Output

96

Output

100

Output

Style
Number

102

Output

Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

1
1
1

.05
.05
.10

—
.13
—

—
1.14
—

—
.18
—

—
1.56
—

.24
—
.48

2.09
—
4.17

—
.31
—

—
2.70
—

—
.36
—

—
3.13
—

S10N04A81N
S10N06A81N
S10N04A82N

1
1
1

.10
.15
.15

.26
—
.39

2.29
—
3.44

.36
—
.54

3.12
—
4.69

—
.72
—

—
6.25
—

.62
—
.93

5.41
—
8.12

.72
—
1.08

6.25
—
9.37

S10N06A82N
S10N04A83N
S10N06A83N

1
1
1

.25
.25
.50

—
.659
—

—
5.73
—

—
.899
—

—
7.81
—

1.2
—
2.4

10.4
—
20.8

—
1.56
—

—
13.5
—

—
1.8
—

—
15.6
—

S10N04A26N
S10N06A26N
S10N04A51N

1
1
1

.50
.75
.75

1.32
—
1.98

11.5
—
17.2

1.8
—
2.7

15.6
—
23.4

—
3.6
—

—
31.2
—

3.11
—
4.67

27.1
—
40.6

3.59
—
5.39

31.2
—
46.8

S10N06A51N
S10N04A76N
S10N06A76N

1
1
1

1
1
1.5

—
2.64
—

—
22.9
—

—
3.59
—

—
31.2
—

4.79
—
7.2

41.7
—
62.5

—
6.23
—

—
54.1
—

—
7.19
—

—
62.5
—

S10N04A01N
S10N06A01N
S10N04A16N

1
1
1

1.5
2
2

3.95
—
5.27

34.4
—
45.8

5.39
—
7.19

46.9
—
62.5

—
9.58
—

—
83.3
—

9.34
—
12.5

81.2
—
108

10.8
—
14.4

93.7
—
125

S10N06A16N
S10N04A02N
S10N06A02N

1
1
1

3
3
5

—
7.92
—

—
68.7
—

—
10.77
—

—
93.6
—

14.37
—
23.95

125.1
—
208.5

—
18.69
—

—
162.3
—

—
21.57
—

—
187.5
—

S10N04A03N
S10N06A03N
S10N04A05N

1
1
1

5
7.5
7.5

13.2
—
19.8

115
—
172

18
—
27

156
—
234

—
36
—

—
312
—

31.15
—
46.7

270.5
—
406

35.95
—
53.9

312.5
—
468

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 

D

Unit
Units
Required  kVA

Input Available Voltage

B

B

Price
U.S. $

C

A

44
105

127

130

138

Output

Output

Output

Output

Style
Number

146
Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

1
1
1

.05
.05
.10

.48
—
.96

4.17
—
8.33

.54
—
1.1

4.58
—
9.17

—
.41
—

—
3.54
—

.29
—
.58

2.5
—
5.0

—
.23
—

—
1.98
—

S10N04A81N
S10N06A81N
S10N04A82N

1
1
1

.10
.15
.15

—
1.44
—

—
12.5
—

—
1.6
—

—
13.7
—

.82
—
1.3

7.08
—
10.6

—
.87
—

—
7.5
—

.46
—
.69

3.95
—
5.93

S10N06A82N
S10N04A83N
S10N06A83N

1
1
1

.25
.25
.50

2.39
—
4.79

20.8
—
41.6

2.63
—
5.27

22.9
—
45.8

—
2.03
—

—
17.7
—

1.44
—
2.87

12.5
—
25

—
1.14
—

—
9.88
—

S10N04A26N
S10N06A26N
S10N04A51N

1
1
1

.50
.75
.75

—
7.19
—

—
62.4
—

—
7.9
—

—
68.7
—

4.07
—
6.1

35.4
—
53.1

—
4.31
—

—
37.5
—

2.27
—
3.41

19.8
—
29.6

S10N06A51N
S10N04A76N
S10N06A76N

1
1
1

1
1
1.5

9.58
—
14.4

83.3
—
125

10.5
—
15.8

91.7
—
137

—
8.14
—

—
70.8
—

5.75
—
8.62

50
—
75

—
4.55
—

—
39.5
—

S10N04A01N
S10N06A01N
S10N04A16N

1
1
1

1.5
2
2

—
19.2
—

—
16.7
—

—
21.1
—

—
183
—

12.2
—
16.3

106
—
142

—
11.5
—

—
100
—

6.82
—
9.10

59.3
—
79.2

S10N06A16N
S10N04A02N
S10N06A02N

1
1
1

3
3
5

28.7
—
47.9

249.9
—
416.5

31.5
—
52.5

275.1
—
458.5

—
24.4
—

—
212.4
—

17.3
—
28.7

150
—
250

—
13.6
—

—
118.5
—

S10N04A03N
S10N06A03N
S10N04A05N

1
1
1

5
7.5
7.5

—
71.9
—

—
624
—

—
79
—

—
687
—

40.7
—
61

354
—
531

—
43.1
—

—
357
—

22.7
—
34.1

197.5
—
296

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 



A

A

A

Price
U.S. $

B

B

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Buck-Boost and Low Voltage Lighting Transformers

44-20

April 2009

Single-Phase
Table 44-21. Single-Phase 120 Volt Output Required, 60 Hz
Units
Unit
Required  kVA

Input Available Voltage
88

95

Output

100

Output

104

Output

Style
Number

106

Output

Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

1
1
1

.05
.05
.10

—
.14
—

—
1.15
—

—
.19
—

—
1.56
—

.25
—
.50

2.09
—
4.17

—
.33
—

—
2.70
—

—
.38
—

—
3.13
—

S10N04A81N
S10N06A81N
S10N04A82N

1
1
1

.10
.15
.15

.28
—
.41

2.29
—
3.44

.38
—
.56

3.12
—
4.69

—
.75
—

—
6.25
—

.65
—
.98

5.41
—
8.12

.75
—
1.12

6.25
—
9.37

S10N06A82N
S10N04A83N
S10N06A83N

1
1
1

.25
.25
.50

—
.687
—

—
5.73
—

—
.937
—

—
7.81
—

1.25
—
2.5

10.4
—
20.8

—
1.62
—

—
13.5
—

—
1.87
—

—
15.6
—

S10N04A26N
S10N06A26N
S10N04A51N

1
1
1

.50
.75
.75

1.37
—
2.06

11.5
—
17.2

1.87
—
2.82

15.6
—
23.4

—
3.75
—

—
31.2
—

3.25
—
4.87

27.1
—
40.6

3.75
—
5.62

31.2
—
46.8

S10N06A51N
S10N04A76N
S10N06A76N

1
1
1

1
1
1.5

—
2.75
—

—
22.9
—

—
3.75
—

—
31.2
—

5
—
7.5

41.7
—
62.5

—
6.5
—

—
54.1
—

—
7.5
—

—
62.5
—

S10N04A01N
S10N06A01N
S10N04A16N

1
1
1

1.5
2
2

4.12
—
5.5

34.4
—
45.8

5.62
—
7.5

46.9
—
62.5

—
10
—

—
83.3
—

9.75
—
13

81.2
—
108

11.2
—
15

93.7
—
125

S10N06A16N
S10N04A02N
S10N06A02N

1
1
1

3
3
5

—
8.25
—

—
68.7
—

—
11.25
—

—
93.6
—

15
—
25

125.1
—
208.5

—
19.5
—

—
162.3
—

—
22.5
—

—
187.5
—

S10N04A03N
S10N06A03N
S10N04A05N

1
1
1

5
7.5
7.5

13.75
—
20.6

114.5
—
172

18.75
—
28.2

156
—
234

—
37.5
—

—
312
—

32.5
—
48.7

270.5
—
406

37.5
—
56.2

312.5
—
468

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 

D

Unit
Units
Required  kVA

109

B

Price
U.S. $

B

C

A

136

144

152

44
Input Available Voltage
132

Output

Output

Output

Output

Style
Number

Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

1
1
1

.05
.05
.10

.5
—
1.0

4.17
—
8.33

.55
—
1.1

4.58
—
9.17

—
.43
—

—
3.54
—

.3
—
.6

2.5
—
5.0

—
.24
—

—
1.98
—

S10N04A81N
S10N06A81N
S10N04A82N

1
1
1

.10
.15
.15

—
1.5
—

—
12.5
—

—
1.6
—

—
13.7
—

.85
—
1.27

7.08
—
10.6

—
.9
—

—
7.5
—

.48
—
.71

3.95
—
5.93

S10N06A82N
S10N04A83N
S10N06A83N

1
1
1

.25
.25
.50

2.5
—
5

20.8
—
41.6

2.75
—
5.5

22.9
—
45.8

—
2.12
—

—
17.7
—

1.5
—
3

12.5
—
25

—
1.19
—

—
9.88
—

S10N04A26N
S10N06A26N
S10N04A51N

1
1
1

.50
.75
.75

—
7.5
—

—
62.4
—

—
8.25
—

—
68.7
—

4.25
—
6.37

35.4
—
53.1

—
4.5
—

—
37.5
—

2.37
—
3.56

19.8
—
29.6

S10N06A51N
S10N04A76N
S10N06A76N

1
1
1

1
1
1.5

10
—
15

83.3
—
125

11
—
16.5

91.7
—
137

—
8.5
—

—
70.8
—

6
—
9

50
—
75

—
4.75
—

—
39.5
—

S10N04A01N
S10N06A01N
S10N04A16N

1
1
1

1.5
2
2

—
20
—

—
167
—

—
22
—

—
183
—

12.7
—
17

106
—
142

—
12
—

—
100
—

7.12
—
9.5

59.3
—
79.2

S10N06A16N
S10N04A02N
S10N06A02N

1
1
1

3
3
5

30
—
50

249.9
—
416.5

33
—
55

275.1
—
458.5

—
25.5
—

—
212.4
—

18
—
30

150
—
250

—
14.25
—

—
118.5
—

S10N04A03N
S10N06A03N
S10N04A05N

1
1
1

5
7.5
7.5

—
75
—

—
624
—

—
82.5
—

—
687
—

42.5
—
63.7

354
—
531

—
45
—

—
375
—

23.7
—
35.6

197.5
—
296

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 



A

A

A

Price
U.S. $

B

B

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-21
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Single-Phase
Table 44-22. Single-Phase 230 Volt Output Required, 60 Hz
Units
Unit
Required  kVA

Input Available Voltage
199
203
Output
Output
kVA
Amps
kVA

1
.05
1
.05
1
.10
1
.10
1
.15
1
.15
1
.25
1
.25
1
.50
1
.50
1
.75
1
.75
1
1
1
1
1
1.5
1
1.5
1
2
1
2
1
3
1
3
1
5
1
5
1
7.5
1
7.5
Connection Diagram 

—

Unit
Units
Required  kVA

1
.05
1
.05
1
.10
1
.10
1
.15
1
.15
1
.25
1
.25
1
.50
1
.50
1
.75
1
.75
1
1
1
1
1
1.5
1
1.5
1
2
1
2
1
3
1
3
1
5
1
5
1
7.5
1
7.5
Connection Diagram 



.31
—
.62
—
.93
—
1.55
—
3.11
—
4.66
—
6.23
—
9.34
—
12.5
—
18.6
—
31.1
—
46.6
G

—
1.36
—
2.71
—
4.06
—
6.77
—
13.5
—
20.3
—
27.1
—
40.6
—
54.2
—
81.3
—
135.5
—
203

—
.36
—
.72
—
1.08
—
1.8
—
3.6
—
5.4
—
7.2
—
10.8
—
14.4
—
21.6
—
36
—
54
F

Input Available Voltage
219
242
Output
Output
kVA
Amps
kVA
.96
—
1.92
—
2.87
—
4.79
—
9.58
—
14.4
—
19.2
—
28.7
—
38.3
—
57.6
—
96
—
144
—
E

4.16
—
8.33
—
12.5
—
20.8
—
41.6
—
62.4
—
83.3
—
125
—
167
—
249.9
—
416.5
—
624
—

1.0
—
2.01
—
3.02
—
5.03
—
10.1
—
15.1
—
20.1
—
30.2
—
40.2
—
60.3
—
100.5
—
151
—
E

Amps
—
1.56
—
3.12
—
4.69
—
7.81
—
15.6
—
23.4
—
31.2
—
46.9
—
62.5
—
93.6
—
156
—
234

Amps
4.38
—
8.75
—
13.1
—
21.9
—
43.7
—
65.6
—
87.5
—
131
—
175
—
262.5
—
437.5
—
656
—

207
Output
kVA
.43
—
.86
—
1.29
—
2.15
—
4.31
—
6.46
—
8.62
—
12.9
—
17.2
—
25.8
—
43.1
—
64.6
—
G

246
Output
kVA
—
.77
—
1.53
—
2.3
—
3.83
—
7.67
—
11.5
—
15.3
—
23
—
30.7
—
45.9
—
76.5
—
115
E

Amps
1.88
—
3.75
—
5.62
—
9.37
—
18.7
—
28.2
—
37.5
—
56.2
—
75
—
112.5
—
187.5
—
282
—

Amps
—
3.34
—
6.67
—
10.0
—
16.7
—
33.3
—
50
—
66.7
—
100
—
133
—
200.1
—
333.5
—
500

209
Output
kVA
.48
—
.96
—
1.44
—
2.39
—
4.79
—
7.19
—
9.58
—
14.4
—
19.2
—
28.7
—
47.9
—
71.9
—
F

253
Output
kVA
.53
—
1.05
—
1.58
—
2.63
—
5.27
—
7.9
—
10.5
—
15.8
—
21.1
—
31.5
—
52.5
—
79
—
F

Amps
2.08
—
4.17
—
6.25
—
10.4
—
20.8
—
31.2
—
41.7
—
62.5
—
83.3
—
125.1
—
208.5
—
312
—

Amps
2.29
—
4.58
—
6.87
—
11.5
—
22.9
—
34.4
—
45.8
—
68.7
—
91.7
—
137.4
—
229
—
344
—

216
Output
kVA
—
.72
—
1.44
—
2.16
—
3.59
—
7.19
—
10.8
—
14.4
—
21.6
—
28.7
—
43.2
—
72
—
108
E

260
Output
kVA
—
.41
—
.82
—
1.22
—
2.04
—
4.07
—
6.11
—
8.15
—
12.2
—
16.3
—
24.4
—
40.7
—
61.1
F

Style
Number

Price
U.S. $

Amps
—
3.12
—
6.25
—
9.37
—
15.6
—
31.2
—
46.8
—
62.5
—
93.7
—
125
—
187.5
—
312.5
—
468

S10N04A81N
S10N06A81N
S10N04A82N
S10N06A82N
S10N04A83N
S10N06A83N
S10N04A26N
S10N06A26N
S10N04A51N
S10N06A51N
S10N04A76N
S10N06A76N
S10N04A01N
S10N06A01N
S10N04A16N
S10N06A16N
S10N04A02N
S10N06A02N
S10N04A03N
S10N06A03N
S10N04A05N
S10N06A05N
S10N04A07N
S10N06A07N

Style
Number

Price
U.S. $

Amps
—
1.77
—
3.54
—
5.31
—
8.85
—
17.7
—
26.6
—
35.4
—
53.1
—
70.8
—
106.2
—
177
—
266

S10N04A81N
S10N06A81N
S10N04A82N
S10N06A82N
S10N04A83N
S10N06A83N
S10N04A26N
S10N06A26N
S10N04A51N
S10N06A51N
S10N04A76N
S10N06A76N
S10N04A01N
S10N06A01N
S10N04A16N
S10N06A16N
S10N04A02N
S10N06A02N
S10N04A03N
S10N06A03N
S10N04A05N
S10N06A05N
S10N04A07N
S10N06A07N

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

44

Distribution & Control Transformers and Power Supplies
Buck-Boost and Low Voltage Lighting Transformers

44-22

April 2009

Single-Phase
Table 44-23. Single-Phase 240 Volt Output Required, 60 Hz
Units
Unit
Required  kVA

Input Available Voltage
208

212

Output

216

Output

Output

kVA

Amps

kVA

Amps

kVA

—

—
1.35
—

—

—
1.56
—

—

1
1
1

.05
.05
.10

1
1
1

.10
.15
.15

—

1
1
1

.25
.25
.50

1
1
1

.50
.75
.75

.32
—
.65

.38
—
.75

218

Style
Number

225

Output

Output

Amps

kVA

Amps

kVA

Amps

1.88
—
3.75

.5
—
1.0

2.08
—
4.17

—
.75
—

—
3.12
—

S10N04A81N
S10N06A81N
S10N04A82N

—
1.35
—

—
5.62
—

—
1.5
—

—
6.25
—

1.5
—
2.25

6.25
—
9.37

S10N06A82N
S10N04A83N
S10N06A83N

.45
.9

.98

2.71
—
4.06

—
1.12

3.12
—
4.69

—
1.62
—

—
6.77
—

—
1.87
—

—
7.81
—

2.25
—
4.5

9.37
—
18.7

2.5
—
5

10.4
—
20.8

—
3.75
—

—
15.6
—

S10N04A26N
S10N06A26N
S10N04A51N

3.25
—
4.87

13.5
—
20.3

3.75
—
5.62

15.6
—
23.4

—
6.75
—

—
28.2
—

—
7.5
—

—
31.2
—

7.5
—
11.2

31.2
—
46.8

S10N06A51N
S10N04A76N
S10N06A76N

1
1
1

1
1
1.5

—
6.5
—

—
27.1
—

—
7.5
—

—
31.2
—

9
—
13.5

37.5
—
56.2

10
—
15

41.7
—
62.5

—
15
—

—
62.5
—

S10N04A01N
S10N06A01N
S10N04A16N

1
1
1

1.5
2
2

9.75
—
13

40.6
—
54.2

11.2
—
15

46.9
—
62.5

—
18
—

—
75
—

—
20
—

—
83.3
—

22.5
—
30

93.7
—
125

S10N06A16N
S10N04A02N
S10N06A02N

1
1
1

3
3
5

—
19.5
—

—
81.3
—

—
22.5
—

—
93.6
—

27
—
45

112.5
—
187

30
—
50

125.1
—
208

—
45
—

—
187.5
—

S10N04A03N
S10N06A03N
S10N04A05N

1
1
1

5
7.5
7.5

32.5
—
48.7

135
—
203

37.5
—
56.2

156
—
234

—
67.5
—

—
282
—

—
75
—

—
312
—

75
—
112

312
—
468

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 

G

Unit
Units
Required  kVA

Input Available Voltage

F

Price
U.S. $

G

F

E

256

264

272

44
229

252

Output

Output

Output

Output

Style
Number

Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

1
1
1

.05
.05
.10

1.0
—
2.0

4.16
—
8.33

1.05
—
2.1

4.38
—
8.75

—

.55
—
1.1

2.29
—
4.58

.42

—

—
3.33
—

—

.8

—

—
1.77
—

S10N04A81N
S10N06A81N
S10N04A82N

1
1
1

.10
.15
.15

—
3.0
—

—
12.5
—

—
3.15
—

—
13.1
—

1.6
—
2.4

6.67
—
10.0

—
1.65
—

—
6.87
—

.85
—
1.27

3.54
—
5.31

S10N06A82N
S10N04A83N
S10N06A83N

1
1
1

.25
.25
.50

5
—
10

20.8
—
41.6

5.25
—
10.5

21.9
—
43.7

—
4
—

—
16.7
—

2.75
—
5.5

11.5
—
22.9

—
2.12
—

—
8.85
—

S10N04A26N
S10N06A26N
S10N04A51N

1
1
1

.50
.75
.75

—
15
—

—
62.4
—

—
15.7
—

—
65.6
—

8
—
12

33.3
—
50

—
8.25
—

—
34.4
—

4.25
—
6.37

17.7
—
26.6

S10N06A51N
S10N04A76N
S10N06A76N

1
1
1

1
1
1.5

20
—
30

83.3
—
125

21
—
31.5

87.5
—
131

—
16
—

—
66.7
—

11
—
16.5

45.8
—
68.7

—
8.5
—

—
35.4
—

S10N04A01N
S10N06A01N
S10N04A16N

1
1
1

1.5
2
2

—
40
—

—
167
—

—
42
—

—
175
—

24
—
32

100
—
133

—
22
—

—
91.7
—

12.7
—
17

53.1
—
70.8

S10N06A16N
S10N04A02N
S10N06A02N

1
1
1

3
3
5

60
—
100

249.9
—
416.5

63
—
105

262.5
—
437.5

—
48
—

—
200.1
—

33
—
55

137.4
—
229

—
25.5
—

—
106.2
—

S10N04A03N
S10N06A03N
S10N04A05N

1
1
1

5
7.5
7.5

—
150
—

—
624
—

—
157
—

—
656
—

80
—
120

333
—
500

—
82.5
—

—
344
—

42.5
—
63.7

177
—
266

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 



E

E

E

Price
U.S. $

F

F

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-23
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Three-Phase
Table 44-24. Three-Phase Open Delta Connection 230 Volt Output Required, 60 Hz
Units
Unit
Required  kVA

Input Available Voltage
199

203

Output

207

Output

209

Output

Style
Number

216

Output

Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

2
2
2

.05
.05
.10

—

.62

—

—
1.35
—

—

.54

—

—
1.56
—

.75
—
1.49

1.87
—
3.75

.83
—
1.66

2.08
—
4.17

—
1.24
—

—
3.12
—

S10N04A81N
S10N06A81N
S10N04A82N

2
2
2

.10
.15
.15

1.08
—
1.62

2.71
—
4.06

1.24
—
1.87

3.12
—
4.69

—
2.24
—

—
5.62
—

—
2.49
—

—
6.25
—

2.49
—
3.73

6.25
—
9.37

S10N06A82N
S10N04A83N
S10N06A83N

2
2
2

.25
.25
.50

—
2.7
—

—
6.77
—

—
3.11
—

—
7.81
—

3.3
—
7.47

9.37
—
18.7

4.15
—
8.3

10.4
—
20.8

—
6.22
—

—
15.6
—

S10N04A26N
S10N06A26N
S10N04A51N

2
2
2

.50
.75
.75

5.39
—
8.09

13.5
—
20.3

6.22
—
9.33

15.6
—
23.4

—
11.2
—

—
28.2
—

—
12.4
—

—
31.2
—

12.4
—
18.7

31.2
—
46.8

S10N06A51N
S10N04A76N
S10N06A76N

2
2
2

1
1
1.5

—
10.8
—

—
27.1
—

—
12.4
—

—
31.2
—

14.9
—
22.4

37.5
—
56.2

16.6
—
24.9

41.7
—
62.5

—
24.9
—

—
62.5
—

S10N04A01N
S10N06A01N
S10N04A16N

2
2
2

1.5
2
2

16.2
—
21.6

40.6
—
54.2

18.7
—
24.9

46.9
—
62.5

—
29.9
—

—
75
—

—
33.2
—

—
83.3
—

37.3
—
49.8

93.7
—
125

S10N06A16N
S10N04A02N
S10N06A02N

2
2
2

3
3
5

—
32.4
—

—
81.3
—

—
32.7
—

—
93.6
—

44.7
—
74.7

112.5
—
187

49.8
—
83

125.1
—
208

—
74.7
—

—
187.5
—

S10N04A03N
S10N06A03N
S10N04A05N

2
2
2

5
7.5
7.5

53.9
—
80.9

135
—
203

62.2
—
93.3

156
—
234

—
112
—

—
282
—

—
124
—

—
312
—

124
—
187

312.5
—
468

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 

L

Unit
Units
Required  kVA

Input Available Voltage

K

L

Price
U.S. $

K

I

44
219

242

246

253

Output

Output

Output

Output

Style
Number

260
Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

2
2
2

.05
.05
.10

1.66
—
3.32

4.17
—
8.33

1.74
—
3.48

4.37
—
8.75

—
1.33
—

—
3.33
—

.91
—
1.83

2.29
—
4.58

—
.70
—

—
1.77
—

S10N04A81N
S10N06A81N
S10N04A82N

2
2
2

.10
.15
.15

—
4.98
—

—
12.5
—

—
5.23
—

—
13.1
—

2.65
—
3.98

6.67
—
10.0

—
2.74
—

—
6.87
—

1.41
—
2.12

3.54
—
5.13

S10N06A82N
S10N04A83N
S10N06A83N

2
2
2

.25
.25
.50

8.3
—
16.6

20.8
—
41.7

8.71
—
17.4

21.9
—
43.7

—
6.64
—

—
16.7
—

4.56
—
9.73

11.5
—
22.9

—
3.52
—

—
8.85
—

S10N04A26N
S10N06A26N
S10N04A51N

2
2
2

.50
.75
.75

—
24.9
—

—
62.4
—

—
26.1
—

—
65.6
—

13.3
—
19.9

33.3
—
50

—
13.7
—

—
34.4
—

7.05
—
10.6

17.7
—
26.6

S10N06A51N
S10N04A76N
S10N06A76N

2
2
2

1
1
1.5

33.2
—
49.8

83.3
—
125

34.8
—
52.3

87.5
—
131

—
26.5
—

—
66.7
—

18.3
—
27.4

45.8
—
68.7

—
14.1
—

—
35.4
—

S10N04A01N
S10N06A01N
S10N04A16N

2
2
2

1.5
2
2

—
66.4
—

—
167
—

—
69.7
—

—
175
—

39.8
—
53.1

100
—
133

—
36.5
—

—
91.7
—

21.2
—
28.2

53.1
—
70.8

S10N06A16N
S10N04A02N
S10N06A02N

2
2
2

3
3
5

99.6
—
166

249.9
—
417

104.4
—
174

262.5
—
437

—
79.5
—

—
200
—

54.9
—
91.3

137.4
—
229

—
42.3
—

—
106.2
—

S10N04A03N
S10N06A03N
S10N04A05N

2
2
2

5
7.5
7.5

—
249
—

—
624
—

—
261
—

—
656
—

133
—
199

333
—
500

—
137
—

—
344
—

70.5
—
106

177
—
266

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 



I

I

I

Price
U.S. $

K

K

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Buck-Boost and Low Voltage Lighting Transformers

44-24

April 2009

Three-Phase
Table 44-25. Three-Phase Open Delta Connection 240 Volt Output Required, 60 Hz
Units
Unit
Required  kVA

Input Available Voltage
208

212

Output

216

Output

218

Output

Style
Number

225

Output

Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

2
2
2

.05
.05
.10

—

.65

—

—
1.35
—

—

.56

—

—
1.56
—

.73
—
1.56

1.87
—
3.75

.87
—
1.73

2.08
—
4.17

—
1.3
—

—
3.12
—

S10N04A81N
S10N06A81N
S10N04A82N

2
2
2

.10
.15
.15

1.13
—
1.69

2.71
—
4.06

1.3
—
1.95

3.12
—
4.69

—
2.34
—

—
5.62
—

—
2.6
—

—
6.25
—

2.6
—
3.9

6.25
—
9.37

S10N06A82N
S10N04A83N
S10N06A83N

2
2
2

.25
.25
.50

—
2.81
—

—
6.77
—

—
3.25
—

—
7.81
—

3.9
—
7.79

9.37
—
18.7

4.33
—
8.66

10.4
—
20.8

—
6.49
—

—
15.6
—

S10N04A26N
S10N06A26N
S10N04A51N

2
2
2

.50
.75
.75

5.63
—
8.44

13.5
—
20.3

6.5
—
9.75

15.6
—
23.4

—
11.7
—

—
28.2
—

—
13
—

—
31.2
—

13
—
19.5

31.2
—
46.8

S10N06A51N
S10N04A76N
S10N06A76N

2
2
2

1
1
1.5

—
11.3
—

—
27.1
—

—
13
—

—
31.2
—

15.6
—
23.4

37.5
—
56.2

17.3
—
26

41.7
—
62.5

—
26
—

—
62.5
—

S10N04A01N
S10N06A01N
S10N04A16N

2
2
2

1.5
2
2

16.9
—
22.5

40.6
—
54.2

19.5
—
26

46.9
—
62.5

—
31.2
—

—
75
—

—
34.6
—

—
83.3
—

39
—
52

93.7
—
125

S10N06A16N
S10N04A02N
S10N06A02N

2
2
2

3
3
5

—
33.9
—

—
81.3
—

—
39
—

—
93.6
—

46.8
—
77.9

112.5
—
187

51.9
—
86.6

125.1
—
208

—
78
—

—
187.5
—

S10N04A03N
S10N06A03N
S10N04A05N

2
2
2

5
7.5
7.5

56.3
—
84.4

135
—
203

65
—
97.5

156
—
234

—
117
—

—
282
—

—
130
—

—
312
—

130
—
195

312
—
468

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 

L

Units
Unit
Required  kVA

Input Available Voltage

K

Price
U.S. $

L

K

I

256

264

272

44
229

252

Output

Output

Output

Output

Style
Number

Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

2
2
2

.05
.05
.10

1.73
—
3.46

4.16
—
8.33

1.82
—
3.64

4.37
—
8.75

—
1.38
—

—
3.33
—

.95
—
1.91

2.29
—
4.58

—
.74
—

—
1.77
—

S10N04A81N
S10N06A81N
S10N04A82N

2
2
2

.10
.15
.15

—
5.19
—

—
12.5
—

—
5.45
—

—
13.1
—

2.77
—
4.15

6.67
—
10.0

—
2.86
—

—
6.87
—

1.47
—
2.21

3.54
—
5.31

S10N06A82N
S10N04A83N
S10N06A83N

2
2
2

.25
.25
.50

8.66
—
17.3

20.8
—
41.6

9.09
—
18.2

21.9
—
43.7

—
6.92
—

—
16.7
—

4.76
—
9.53

11.5
—
22.9

—
3.68
—

—
8.85
—

S10N04A26N
S10N06A26N
S10N04A51N

2
2
2

.50
.75
.75

—
26
—

—
62.4
—

—
27.3
—

—
65.6
—

13.8
—
20.8

33.3
—
50

—
14.3
—

—
34.4
—

7.36
—
11

17.7
—
26.6

S10N06A51N
S10N04A76N
S10N06A76N

2
2
2

1
1
1.5

34.6
—
51.9

83.3
—
125

36.4
—
54.5

87.5
—
131

—
27.7
—

—
66.7
—

19.1
—
28.6

45.8
—
68.7

—
14.7
—

—
35.4
—

S10N04A01N
S10N06A01N
S10N04A16N

2
2
2

1.5
2
2

—
69.3
—

—
167
—

—
72.7
—

—
175
—

41.5
—
55.4

100
—
133

—
38.1
—

—
91.7
—

22.1
—
29.4

53.1
—
70.8

S10N06A16N
S10N04A02N
S10N06A02N

2
2
2

3
3
5

103.8
—
173

249.9
—
416

109.2
—
182

262.5
—
437

—
83.1
—

—
200
—

57.3
—
95.3

137.4
—
229

—
44.1
—

—
106.2
—

S10N04A03N
S10N06A03N
S10N04A05N

2
2
2

5
7.5
7.5

—
260
—

—
624
—

—
273
—

—
656
—

138
—
208

333
—
500

—
143
—

—
344
—

73.6
—
110

177
—
266

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 



I

I

I

Price
U.S. $

K

K

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-25
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Three-Phase
Table 44-26. Three-Phase Wye Connection 208 Volt Output Required, 60 Hz
Note: WARNING! Three-phase autotransformers should never be used to obtain 4-wire output with 3-wire input. 4-wire output requires
4-wire wye input.
Units
Unit
Required  kVA

Input Available Voltage
152

164

Output

173

Output

180

Output

Style
Number

184

Output

Output

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

kVA

Amps

3
3
3

.05
.05
.10

—

—
1.15
—

—

.75
—
1.50

2.08
—
4.17

.98

—

—
1.56
—

—

—

—

—
2.71
—

—
1.12
—

—
3.12
—

S10N04A81N
S10N06A81N
S10N04A82N

3
3
3

.10
.15
.15

.82
—
1.24

2.29
—
3.44

1.12
—
1.69

3.12
—
4.69

—
2.25
—

—
6.25
—

1.95
—
2.92

5.41
—
8.12

2.25
—
3.73

6.25
—
9.37

S10N06A82N
S10N04A83N
S10N06A83N

3
3
3

.25
.25
.50

—
2.06
—

—
5.73
—

—
2.81
—

—
7.81
—

3.75
—
7.5

10.4
—
20.8

—
4.87
—

—
13.5
—

—
5.62
—

—
15.6
—

S10N04A26N
S10N06A26N
S10N04A51N

3
3
3

.50
.75
.75

4.12
—
6.19

11.5
—
17.2

5.62
—
8.44

15.6
—
23.4

—
11.2
—

—
31.2
—

9.75
—
14.6

27.1
—
40.6

11.2
—
16.8

31.2
—
46.8

S10N06A51N
S10N04A76N
S10N06A76N

.41

.56

3
3
3

1
1
1.5

—
8.25
—

—
22.9
—

—
11.2
—

—
31.2
—

15
—
22.5

41.7
—
62.5

—
19.5
—

—
54.1
—

—
22.5
—

—
62.5
—

S10N04A01N
S10N06A01N
S10N04A16N

3
3
3

1.5
2
2

12.4
—
16.5

34.4
—
45.8

16.9
—
22.5

46.9
—
62.5

—
30
—

—
83.3
—

29.2
—
39

81.2
—
108

33.7
—
45

93.7
—
125

S10N06A16N
S10N04A02N
S10N06A02N

3
3
3

3
3
5

—
24.7
—

—
68.7
—

—
33.6
—

—
93.6
—

45
—
75

125
—
208

—
58.5
—

—
162.3
—

—
67.5
—

—
187.5
—

S10N04A03N
S10N06A03N
S10N04A05N

3
3
3

5
7.5
7.5

41.2
—
61.9

115
—
172

56.2
—
84.4

156
—
234

—
112
—

—
312
—

97.5
—
146

271
—
406

112
—
168

312
—
468

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 

P

Unit
Units
Required  kVA

Input Available Voltage

N

189

229

Output

Output
Amps

kVA

Amps
—

4.58

44

N

O

M

236

250

264

Output

kVA

Output

Style
Number

Amps

kVA

Amps

kVA

Amps

—

—

.9
—
1.8

2.5
—
5.0

—

—

—

—

—
10.6

—
2.7
—

—
7.5
—

1.42
—
2.14

—

4.5
—
9

12.5
—
25

—

—

3.56
—

S10N04A81N
S10N06A81N
S10N04A82N

3
3
3

.05
.05
.10

1.5
—
3.0

4.16
—
8.33

1.65
—
3.3

3
3
3

.10
.15
.15

—
4.5
—

—
12.5
—

—
4.95
—

—
13.7
—

3
3
3

.25
.25
.50

7.5
—
15

20.8
—
41.6

8.25
—
16.5

22.9
—
45.8

—
—

—
17.7
—

—

S10N04A26N
S10N06A26N
S10N04A51N

3
3
3

.50
.75
.75

—
22.5
—

—
62.4
—

—
24.7
—

—
68.7
—

12.7
—
19

35.4
—
53.1

—
13.5
—

—
37.5
—

7.12
—
10.7

19.3
—
29.3

S10N06A51N
S10N04A76N
S10N06A76N

3.54

9.17

—

—
2.55
—
3.82
6.35

7.08

1.98

.71

3.95
5.93
9.88

S10N06A82N
S10N04A83N
S10N06A83N

3
3
3

1
1
1.5

30
—
45

83.3
—
125

33
—
49.5

91.7
—
137

—
25.5
—

—
70.8
—

18
—
27

50
—
75

—
14.2
—

—
39.5
—

S10N04A01N
S10N06A01N
S10N04A16N

3
3
3

1.5
2
2

—
60
—

—
167
—

—
66
—

—
183
—

38.2
—
51

106
—
142

—
361
—

—
100
—

21.4
—
28.5

59.3
—
79.2

S10N06A16N
S10N04A02N
S10N06A02N

3
3
3

3
3
5

90
—
150

249.9
—
416

99
—
165

275.1
—
458

—
76.5
—

—
212.4
—

54
—
90

150
—
250

—
46.2
—

—
118.5
—

S10N04A03N
S10N06A03N
S10N04A05N

3
3
3

5
7.5
7.5

—
225
—

—
624
—

—
274
—

—
687
—

127
—
190

354
—
531

—
135
—

—
375
—

71.2
—
107

198
—
293

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 



M

M

M

Price
U.S. $

Output

kVA
1.27

Price
U.S. $

N

N

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Buck-Boost and Low Voltage Lighting Transformers

44-26

April 2009

Three-Phase
Table 44-27. Three-Phase Wye Connection 230 Volt Output Required, 60 Hz
Note: WARNING! Three-phase autotransformers should never be used to obtain 4-wire output with 3-wire input. 4-wire output requires
4-wire wye input.
Units
Unit
Required  kVA

Input Available Voltage
183

192

Output

44

199

Output

kVA

Amps
—

kVA

Output
Amps
2.08

.83

Output
kVA

Amps

kVA

Amps

—

—

1.65
—
3.3

4.58
—
9.17

1.66
—
3.32

—

—

—
13.7
—

—

4.95
—

4.98
—

—
12.5
—

S10N06A82N
S10N04A83N
S10N06A83N

—

8.2
—
16.5

22.9
—
45.8

8.3
—
16.6

20.9
—
41.7

S10N04A26N
S10N06A26N
S10N04A51N

13.5
—
20.3

—
24.7
—

—
68.8
—

—
24.9
—

—
62.6
—

S10N06A51N
S10N04A76N
S10N06A76N

—

1.56
—

—

—

3
3
3

.10
.15
.15

1.25
—
1.87

3.12
—
4.69

—
2.49
—

—

3
3
3

.25
.25
.50

—

—

3.11
—

7.81
—

4.15
—
8.3

10.4
—
20.8

3
3
3

.50
.75
.75

6.22
—
9.33

15.6
—
23.4

—
12.4
—

—
31.2
—

—

1.35

.54

—
4.17

—

—

2.71

1.08

—
6.25

—

—

4.06

1.62

—

—

6.77

2.70
—
5.39
8.09

4.17
8.35

S10N04A81N
S10N06A81N
S10N04A82N

3
3
3

1
1
1.5

—
12.5
—

—
31.2
—

16.6
—
24.9

41.7
—
62.5

—
10.8
—

—
27.1
—

33
—
49.5

91.7
—
137

33.2
—
49.8

83.5
—
125

S10N04A01N
S10N06A01N
S10N04A16N

3
3
3

1.5
2
2

18.7
—
24.9

46.9
—
62.5

—
33.2
—

—
83.3
—

16.2
—
21.6

40.6
—
54.2

—
66
—

—
183
—

—
66.4
—

—
167
—

S10N06A16N
S10N04A02N
S10N06A02N

3
3
3

3
3
5

—
37.5
—

—
93.6
—

49.8
—
83

125.1
—
208

—
32.4
—

—
81.3
—

99
—
165

275
—
458

99.6
—
166

250.5
—
417

S10N04A03N
S10N06A03N
S10N04A05N

3
3
3

5
7.5
7.5

62.2
—
93.3

156
—
234

—
124
—

—
312
—

53.9
—
80.9

135
—
203

—
247
—

—
688
—

—
249
—

—
626
—

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 

N

Unit
Units
Required  kVA

Input Available Voltage

N

242

245

Output

Output

S

M

Q

253

260

265

Output

kVA

Amps

kVA

Amps
—

kVA

Amps

—

—

—

—

—

S10N04A81N
S10N06A81N
S10N04A82N

1.41
—
2.12

3.54
—
5.31

1.25
—
1.87

3.12
—
4.69

S10N06A82N
S10N04A83N
S10N06A83N

11.5
—
22.9

—

—

—

3.52
—

8.85
—

3.11
—

—
7.81
—

S10N04A26N
S10N06A26N
S10N04A51N

—
13.7
—

—
34.4
—

7.05
—
10.6

17.7
—
26.6

6.22
—
9.33

15.6
—
23.4

S10N06A51N
S10N04A76N
S10N06A76N

—

3
3
3

.10
.15
.15

—
5.23
—

—
13.1
—

2.65
—
3.98

3
3
3

.25
.25
.50

8.71
—
17.4

21.9
—
43.7

—
6.63
—

—
16.7
—

—

3
3
3

.50
.75
.75

—
26.1
—

—
65.6
—

13.3
—
19.9

33.3
—
50

—

—
1.83

—
—
10.0

kVA

—
1.56
—

4.37
—
8.75

6.67

Amps

.62

1.74
—
3.48

4.58
—

—

6.87

2.74
—

—
4.56
9.31

3
3
3

1
1
1.5

34.8
—
52.3

87.5
—
131

—
26.5
—

—
66.7
—

18.3
—
27.4

45.8
—
68.7

—
14.1
—

—
35.4
—

—
12.5
—

—
31.2
—

S10N04A01N
S10N06A01N
S10N04A16N

3
3
3

1.5
2
2

—
69.7
—

—
175
—

39.8
—
53.1

100
—
133

—
36.6
—

—
91.6
—

21.2
—
28.2

53.1
—
70.8

18.7
—
24.9

46.9
—
62.5

S10N06A16N
S10N04A02N
S10N06A02N

3
3
3

3
3
5

104.4
—
174

262.5
—
437

—
79.5
—

—
200
—

54.9
—
91.3

137.4
—
229

—
42.3
—

—
106.2
—

—
37.5
—

—
93.6
—

S10N04A03N
S10N06A03N
S10N04A05N

3
3
3

5
7.5
7.5

—
261
—

—
656
—

133
—
199

333
—
500

—
137
—

—
344
—

70.5
—
106

177
—
266

62.2
—
93.3

156
—
234

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 



Q

Q

R

Price
U.S. $

Output

kVA

1.77
—

.05
.05
.10

3.33

Style
Number

.70

2.29

.91

3
3
3

1.33
—

Output
Amps

Price
U.S. $

Output

Amps

.05
.05
.10

1.66

Style
Number

218

kVA

3
3
3

.62

208

R

S

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-27
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Three-Phase
Table 44-28. Three-Phase Wye Connection 240 Volt Output Required, 60 Hz
Note: WARNING! Three-phase autotransformers should never be used to obtain 4-wire output with 3-wire input. 4-wire output requires
4-wire wye input.
Units
Unit
Required  kVA

Input Available Voltage
190

200

Output

208

Output

kVA

Amps
—

kVA
.86

218

Output

Output

Amps

kVA

Amps

kVA

2.08
—
4.17

—

—

1.27
—

3.05
—

—

6.12
—
9.16

—
2.59
—

Style
Number

228
Output
Amps
2.08

.86

kVA

Amps

1.73
—
3.46

4.17
—
8.34

S10N04A81N
S10N06A81N
S10N04A82N

—

—
12.5
—

S10N06A82N
S10N04A83N
S10N06A83N

3
3
3

.05
.05
.10

—
.65

—

—

1.65
—

3
3
3

.10
.15
.15

1.3
—
1.95

3.12
—
4.69

—

—

2.59
—

6.25
—

2.55
—
3.82

—

5.20
—

3
3
3

.25
.25
.50

—

—

3.25
—

7.81
—

4.32
—
8.65

10.4
—
20.8

—
6.3
—

—
15.1
—

4.32
—
8.65

10.4
—
20.8

8.66
—
17.3

20.9
—
41.7

S10N04A26N
S10N06A26N
S10N04A51N

3
3
3

.50
.75
.75

6.5
—
9.75

15.6
—
23.4

—
13
—

—
31.2
—

12.7
—
19.2

30.4
—
46

—
13
—

—
31.2
—

—
26
—

—
62.6
—

S10N06A51N
S10N04A76N
S10N06A76N

1.73

—
4.17

1.73

—
6.25

3
3
3

1
1
1.5

—
13
—

—
31.2
—

17.3
—
25.9

41.7
—
62.5

—
25.5
—

—
61.2
—

17.3
—
25.9

41.7
—
62.5

34.6
—
52

83.4
—
125

S10N04A01N
S10N06A01N
S10N04A16N

3
3
3

1.5
2
2

19.5
—
26

46.9
—
62.5

—
34.6
—

—
83.3
—

38.2
—
51

91.6
—
122.4

—
34.6
—

—
83.3
—

—
69.3
—

—
167
—

S10N06A16N
S10N04A02N
S10N06A02N

3
3
3

3
3
5

—
39
—

—
93.6
—

51.9
—
86.5

125.1
—
208

—
76.5
—

—
183.6
—

51.9
—
86.5

125.1
—
208

103.8
—
173

250.2
—
417

S10N04A03N
S10N06A03N
S10N04A05N

3
3
3

5
7.5
7.5

65
—
97.5

156
—
234

—
130
—

—
312
—

127.2
—
192

305.2
—
460

—
130
—

—
312
—

—
260
—

—
626
—

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 

N

Unit
Units
Required  kVA

252

N

44

M

R

Q

264

272

277

Input Available Voltage
256

Output

Output

Output

kVA

Amps

kVA

Amps

kVA
.95

Output

Style
Number

kVA

Amps

kVA

Amps

2.29
—
4.58

—

—

—
.65
—

—
1.56
—

S10N04A81N
S10N06A81N
S10N04A82N

1.47
—
2.21

—

1.3
—
1.95

3.12
—
4.69

S10N06A82N
S10N04A83N
S10N06A83N

—

—

—
7.81
—

S10N04A26N
S10N06A26N
S10N04A51N

.05
.05
.10

1.85
—
3.64

4.37
—
8.75

—
1.39
—

—
3.33
—

3
3
3

.10
.15
.15

—

2.77
—
4.16

6.67
—
10.0

—

—

5.46
—

—
13.1
—

2.86
—

6.87
—

3
3
3

.25
.25
.50

9.09
—
18.2

21.9
—
43.7

—

4.76
—
9.53

11.5
—
22.9

—

6.93
—

—
16.7
—

3.68
—

—

3.25
—

3
3
3

.50
.75
.75

—
27.3
—

—
65.6
—

13.9
—
20.8

33.3
—
50

—
14.3
—

—
34.4
—

7.36
—
11

17.7
—
26.6

6.5
—
9.75

15.6
—
23.4

S10N06A51N
S10N04A76N
S10N06A76N

1.91

1.77

.74
—

—
3.54
5.31
8.85

3
3
3

1
1
1.5

36.4
—
54.6

87.5
—
131

—
27.7
—

—
66.7
—

19.1
—
28.6

45.8
—
68.7

—
14.7
—

—
35.4
—

—
13
—

—
31.2
—

S10N04A01N
S10N06A01N
S10N04A16N

3
3
3

1.5
2
2

—
72.8
—

—
175
—

41.6
—
55.4

100
—
133

—
38.1
—

—
91.7
—

22.1
—
29.5

53.1
—
70.8

19.5
—
26

46.9
—
62.5

S10N06A16N
S10N04A02N
S10N06A02N

3
3
3

3
3
5

109.2
—
182

262.5
—
437

—
83.1
—

—
200
—

57.3
—
95.3

137.4
—
229

—
44.1
—

—
106.2
—

—
39
—

—
93.6
—

S10N04A03N
S10N06A03N
S10N04A05N

3
3
3

5
7.5
7.5

—
273
—

—
656
—

139
—
208

333
—
500

—
143
—

—
344
—

73.6
—
110

177
—
266

65
—
97.5

156
—
234

S10N06A05N
S10N04A07N
S10N06A07N

Connection Diagram 



Q

Q

R

Price
U.S. $

Output

Amps

3
3
3

—

Price
U.S. $

R

S

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Buck-Boost and Low Voltage Lighting Transformers

44-28

April 2009

Three-Phase
Table 44-29. Three-Phase Wye Connection 460 Volt Output Required, 60 Hz
Note: WARNING! Three-phase autotransformers should never be used to obtain 4-wire output with 3-wire input. 4-wire output requires
4-wire wye input.
Units
Unit Input Available Voltage
Required  kVA 406
418
Output
kVA

44

Output
Amps kVA

432

438

Output
Amps kVA

424

Output
Amps kVA

436

Output
Amps kVA

Style
Number

450

Output

Output

Amps kVA

Amps kVA

Amps

3
3
3

.05
.05
.10

—
—
1.66
2.08 —
—
3.22
4.04 —
1.25
1.57 —
—
2.49
3.12 —
—
1.3
—
—
3.31
4.15 —
—
6.62
8.31 —

1.7
2.1
1.56 —
—
3.5

—
—
4.2

—
2.6
—

—
S10N04A81N
3.13 S10N06A81N
—
S10N04A82N

3
3
3

.10
.15
.15

2.49
3.12 —
—
4.97
6.24 —
—
2.6
—
—
4.97
6.24 —
—
9.94 12.48 —
3.73
4.68 —
—
7.46
9.36 —
—
3.9

3.12 —
—
5.2
4.68 —

—
5.2
6.25 —
—
7.8

6.25 S10N06A82N
—
S10N04A83N
9.38 S10N06A83N

3
3
3

.25
.25
.50

—
—
8.28 10.39 —
6.22
7.81 —
—
12.4
—
—
16.6
20.84 —

3
3
3

.50
.75
.75

12.5
—
18.7

—
16.6
15.56 —
—
33.2

20.84 —
—
6.5
41.67 —

—
8.7
7.82 —
—
17.4

10.4
—
20.9

—
13
—

—
15.6
—

S10N04A26N
S10N06A26N
S10N04A51N

15.69 —
—
24.8
23.47 —

—
24.69 31.25 —
31.12 —
—
49.6
—
37.3
46.82 —

—
13
62.25 —
—
19.5

15.6
—
23.4

—
26
—

—
31.2
—

26
—
39

31.2
—
46.9

S10N06A51N
S10N04A76N
S10N06A76N

3
3
3

1
1
1.5

—
24.9
—

—
33.1
31.25 —
—
49.7

41.54 —
—
49.7
62.38 —

—
66.2
62.38 —
—
99.4

83.09 —
—
26
124.75 —

—
31.2
—

35
—
52

42
—
62.5

—
52
—

—
62.5
—

S10N04A01N
S10N06A01N
S10N04A16N

3
3
3

1.5
2
2

37.3
—
49.7

46.94 —
—
66.3
62.38 —

—
74.6
83.22 —
—
99.5

93.63 —
—
133
124.88 —

—
39
166.93 —
—
52

46.8
—
62.5

—
69
—

—
82.9
—

78
—
104

93.8
—
125

S10N06A16N
S10N04A02N
S10N06A02N

3
3
3

3
3
5

—
74.6
—

—
99.3
93.63 —
—
166

124.64 —
—
149
208.35 —

—
198.6
187.01 —
—
322

249.27 —
—
78
404.16 —

—
93.8
—

104
—
174

125
—
209.2

—
156
—

—
187.6
—

S10N04A03N
S10N06A03N
S10N04A05N

3
3
3

5
7.5
7.5

125
—
187

156.89 —
—
248
235
—

—
311
—

312.53 —
—
496
468
—

—
622
—

156.3
—
234

—
260
—

—
312
—

260
—
390

312.7
—
469

S10N06A05N
S10N04A07N
S10N06A07N

Connection
Diagram 



R

R

249
—
373
Q

Q

130
—
195
R

R

Price
U.S. $

Q

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-29
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Single-Phase
Table 44-30. Single-Phase Required, 60 Hz
Units
Unit
Required  kVA

Input Available Voltage/Output Voltage
200/240

230/277

Output
kVA
1
1
1

.25
.50
.75

346/380

Output
Amps

kVA

362/380

Output
Amps

kVA

378/416

Output
Amps

kVA

Output
Amps

kVA

Style
Number

416/457
Output
Amps

kVA

Amps

1.25
2.50
3.75

5.2
10.4
15.6

1.44
2.88
4.32

5.2
10.4
15.6

1.98
3.95
5.93

5.2
10.4
15.6

3.95
7.90
11.9

10.4
20.8
31.2

2.16
4.33
6.49

5.2
10.4
15.6

2.38
4.76
7.14

5.2
10.4
15.6

S20N08A26N
S20N08A51N
S20N08A76N

1
1
1

1
1.5
2

5.00
7.50
10.00

20.8
31.2
41.6

5.76
8.64
11.5

20.8
31.2
41.6

7.90
11.9
15.8

20.8
31.2
41.6

15.8
23.8
31.6

41.6
62.5
83.3

8.65
13.0
17.3

20.8
31.2
41.6

9.52
14.3
19.0

20.8
31.2
41.6

S20N08A01N
S20N08A16N
S20N08A02N

1
1
1

3
5
7.5

15.0
25.0
37.5

62.5
104.0
156.0

17.3
28.8
43.2

62.5
104.0
156.0

23.8
39.5
59.3

62.5
104.0
156.0

47.5
79.0
118.6

125.0
208.0
312.0

26.0
43.3
64.9

62.5
104.0
156.0

28.6
47.6
71.4

62.5
104.0
156.0

S20N08A03N
S20N08A05N
S20N08A07N

Connection
Diagram 

B

Unit
Units
Required  kVA

Input Available Voltage/Output Voltage

B

436/480

458/480

Output
kVA
1
1
1

.25
.50
.75

F

277/230

Output
Amps

kVA

Output
Amps

kVA

E

F

F

480/456

504/480

528/480

Output
Amps

kVA

Output
Amps

kVA

Style
Number

2.50
4.99
7.49

5.2
10.4
15.6

4.99
9.98
15.0

10.4
20.8
31.2

1.44
2.88
4.33

6.26
12.5
18.8

5.23
10.4
15.7

11.4
22.8
34.2

5.47
10.9
16.4

11.4
22.8
34.2

kVA
2.75
5.49
8.24

Amps
5.72
11.4
17.2

S20N08A26N
S20N08A51N
S20N08A76N

1
1.5
2

9.98
15.0
20.0

20.8
31.2
41.6

20.0
30.0
40.0

41.6
62.5
83.3

5.76
8.64
11.5

25.0
37.6
50.1

20.9
31.3
41.8

45.6
68.4
91.2

21.8
32.8
43.7

45.6
68.4
91.2

11.0
16.5
22.0

22.9
34.3
45.8

S20N08A01N
S20N08A16N
S20N08A02N

1
1
1

3
5
7.5

30.0
49.9
74.9

62.5
104.0
156.0

60.0
99.8
149.8

125.0
208.0
312.0

17.3
28.8
43.2

75.3
125.3
187.9

62.7
104.5
156.8

136.0
227.0
341.0

65.2
108.0
163.0

136.0
227.0
341.0

33.0
54.9
82.4

68.8
114.4
171.6

S20N08A03N
S20N08A05N
S20N08A07N




F

E

B

E

E

Price
U.S. $

Output
Amps

1
1
1

Connection
Diagram 

Price
U.S. $

F

Additional wiring trough may be required.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

44

Distribution & Control Transformers and Power Supplies
Buck-Boost and Low Voltage Lighting Transformers

44-30

April 2009

Three-Phase
Table 44-31. Three-Phase Required, 60 Hz
Unit
kVA

Input Available Voltage/Output Voltage
362/380

346/416

Output
kVA
.25
.50
.75

Output
Amps

kVA

400/480

Output
Amps

kVA

Output
Amps

kVA

Style
Number

436/480
kVA

Amps

10.4
20.8
31.2

3.75
7.50
11.2

5.2
10.4
15.6

4.26
8.52
12.8

5.2
10.4
15.6

4.33
8.65
13.0

5.2
10.4
15.6

4.33
8.65
13.0

5.2
10.4
15.6

S20N08A26N
S20N08A51N
S20N08A76N

1
1.5
2

26.1
39.1
52.2

41.6
62.4
83.2

15.0
22.5
30.0

20.8
31.2
41.6

17.0
25.5
34.1

20.8
31.2
41.6

17.3
26.0
34.6

20.8
31.2
41.6

17.3
26.0
34.6

20.8
31.2
41.6

S20N08A01N
S20N08A16N
S20N08A02N

3
5
7.5

78.4
130.4
195.6

125.0
208.0
312.0

45.0
75.1
112.6

62.5
104.0
156.0

51.2
85.2
127.8

62.5
104.0
156.0

52.0
86.6
129.9

62.5
104.0
156.0

52.0
86.6
129.9

62.5
104.0
156.0

S20N08A03N
S20N08A05N
S20N08A07N

Connection Diagram 

I

N

K

N

K

Units Required 

2

3

2

3

2

Unit
kVA

460/483

Input Available Voltage/Output Voltage
457/380

kVA
.25
.50
.75

504/480

Output
Amps

kVA

kVA

Style
Number

528/480

Output
Amps

kVA

Amps

10.4
20.8
31.2

4.12
8.23
12.3

6.25
12.5
18.8

9.08
18.2
27.2

10.9
21.8
32.8

4.76
9.51
14.3

5.72
11.4
17.2

S20N08A26N
S20N08A51N
S20N08A76N

1
1.5
2

34.8
52.2
69.6

41.6
62.4
83.2

16.5
24.7
32.9

25.0
37.5
50.0

36.3
54.5
72.6

43.7
65.5
87.4

19.0
28.5
38.0

22.9
34.3
45.8

S20N08A01N
S20N08A16N
S20N08A02N

3
5
7.5

104.6
174.0
261.0

125.0
208.0
312.0

49.5
82.3
123.5

75.2
125.1
187.6

109.7
181.6
272.4

131.3
218.4
327.6

57.2
95.1
142.7

68.8
114.4
171.6

S20N08A03N
S20N08A05N
S20N08A07N

Connection Diagram 

I

N

I

K

Units Required 

2

3

2

2



Price
U.S. $

Output
Amps

8.7
17.4
26.1



Price
U.S. $

Output
Amps

6.52
13.0
19.6

Output

44

430/473

Refer to Page 44-17 for Buck-Boost wiring diagrams.
Additional wiring trough may be required.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-31
Buck-Boost and Low Voltage Lighting Transformers
April 2009

Autotransformer Applications
Table 44-32. Three-Phase Open Delta Connection 480 Volt Output
Required, 60 Hz
Units
Required


Input Available Voltage
600

575

575

Output

Output

Output

kVA
2
2
2

Style
Number 

5.1
7.8

—
—
—

—
—
4.1 4.9
—
—

S20N11S51N
S60G11S51N
S20N11S76N

2
2
2

—

—
8.6 10.3
—
—

—
—
—

—
—
—

6.2 7.4
—
—
8.3 9.9

S60G11S76N
S20N11S01N
S60G11S01N

2
2
2

13.0 15.6
—
—
17.2 20.6

—
—
—

—
—
—

—
—
12.4 14.9
—
—

S20N11S16N
S60G11S16N
S20N11S02N

2
2
2

—
—
25.8 31
—
—

—
—
—

—
—
—

16.5 19.8
—
—
24.8 29.8

S60G11S02N
S20N11S03N
S60G11S03N

2
2
2

43.2 51.9
—
—
65
78.1

—
—
—

—
—
—

—
41
—

—
49.3
—

S20N11S05N
S60G11S05N
S20N11S07N

2
2
2

—
86
—

—
103.4
—

—
—
83

—
—
99.8

62
—
—

74.5
—
—

S60G11S07N
S20N11S10N
S60G11S10N

2
2
2

130
—
216

156.3
—
259.8

—
124
—

—
149.1
—

—
—
—

—
—
—

S20N11S15N
S60N11S15N
T20P11S25

2
2
2

—
324
432

—
389.7
519.6

207
—
—

248.9
—
—

—
—
—

—
—
—

S60J11S25N
T20P11S37
T20P11S50

Connection I
Diagram 




J

Units
Required


Input Available Voltage
600
Output
kVA

—
—
—

—
6.5

Price
U.S.

Amps kVA Amps kVA Amps

4.3
—

Table 44-33. Single-Phase 480 Volt Output Required, 60 Hz

T

1
1
1

575

Output

Output

2.5

7.7

1
1
1

—

—
5.0 10.4
—
—

—
—
—

—
—
—

3.6 7.5
—
—
4.8 10

S60G11S76N
S20N11S01N
S60G11S01N

1
1
1

7.5 15.6
—
—
10
20.8

—
—
—

—
—
—

—
—
7.2 15
—
—

S20N11S16N
S60G11S16N
S20N11S02N

1
1
1

—
15
—

—
31.2
—

—
—
—

—
—
—

9.6 20
—
—
14.3 29.7

S60G11S02N
S20N11S03N
S60G11S03N

1
1
1

25
52
—
—
37.5 78.1

—
—
—

—
—
—

—
24
—

—
50
—

S20N11S05N
S60G11S05N
S20N11S07N

1
1
1

—
50
—

—
104.1
—

—
—
43

—
—
100

36
—
—

75
—
—

S60G11S07N
S20N11S10N
S60G11S10N

1
1
1

75
—
125

156.2
—
260.4

—
72
—

—
150
—

—
—
—

—
—
—

S20N11S15N
S60N11S15N
T20P11S25

1
1
1

—
187
250

—
389.6
520.8

120
—
—

250
—
—

—
—
—

—
—
—

S60J11S25N
T20P11S37
T20P11S50

—

Connection E
Diagram 



5.2
—

3.7

Price
U.S.

Amps kVA Amps kVA Amps
—
—
—



Additional wiring trough may be required.
On transformers supplied with standard taps, taps must be placed at
nominal settings.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Style
Number 

575

H

—
—
—

—
—
2.4 5
—
—

S20N11S51N
S60G11S51N
S20N11S76N

U

Additional wiring trough may be required.
On transformers supplied with standard taps, taps must be placed at
nominal settings.
Refer to Page 44-17 for Buck-Boost wiring diagrams.

Note: Autotransformers can be used only where local electric codes
permit and isolation of the two circuits is not required.

Rated Output Voltage
Note: Output voltage for lower input voltage can be found by: -------------------------------------------------- x Input Actual Voltage = Output New Voltage.
Rated Input Voltage
Actual Input Voltage
Note: Output kVA available at reduced input voltage can be found by: ------------------------------------------------ x Output kVA = New kVA Rating.
Rated Input Voltage

Discount Symbol. . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

44

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-32

April 2009

Type MTA

Type MTA

Features, Benefits
and Functions
■
■
■
■
■
■
■

Type MTA Transformer

■

Product Description
Varnish impregnated core and
coil design.
■ Suitable for indoor applications.
■ Open core and coil design.
■

Application Description

44

Machine Tool and Industrial Control
Transformers provide stepped-down
voltages to machine tool control
devices enabling control circuits to
be isolated from all power and lighting
circuits. This allows the use of grounded or ungrounded circuits that are
independent of the power or lighting
grounds; greater safety is afforded the
operator. The control transformer line
is particularly adaptable on applications where compact construction
is demanded.

■

UL recognized component for units
rated 1000 VA and below.
CSA certified for units rated 1000 VA
and below.
55ºC rise, 105ºC insulation system.
60 Hz operation standard.
100% tested to verify product quality.
Performance equals or exceeds
requirements of ANSI/NEMA ST-1.
Regulation exceeds ANSI/NEMA
requirements for all ratings.
Each unit must pass rigid tests for
turns ratio, insulation, continuity,
and over potential.
50 – 5000 VA ratings.

Standards and Certifications
Industry Standards
All Cutler-Hammer dry-type distribution and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI and IEEE Standards.

Product Specifications
Frequency
Cutler-Hammer Type MTA control
transformers are designed for 60 Hertz
operation. Transformers required for
other frequencies are available and
must be specifically designed.

Insulation System and Temperature Rise
Industry standards classify insulation
systems and rise as shown below:
Table 44-34. Insulation System Classification
Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Series-Multiple Windings
Series-multiple windings consist of
2 similar coils in each winding which
can be connected in series or parallel
(multiple). Transformers with seriesmultiple windings are designated with
an “X” or “/” between the voltage
ratings, such as voltages of “120/240”
or “240 X 480.” If the series-multiple
winding is designated by an “X,” the
winding can be connected only for a
series or parallel. With the “/” designation, a mid-point also becomes available in addition to the series or parallel
connection. As an example, a 120 X
240 winding can be connected for
either 120 (parallel) or 240 (series), but
a 120/240 winding can be connected
for 120 (parallel), or 240 (series), or 240
with a 120 mid-point.

The following pages provide listings for most
standard transformer ratings and styles.
For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-33
Industrial Control Transformers
April 2009

Type MTA

Overcurrent Protection Tables
Overcurrent protection on both the primary and secondary sides of transformers are specified in UL 508 and the National
Electrical Code. The maximum acceptable ratings are shown below. Due to high inrush currents present when a transformer
is initially energized, it is recommended that the primary fuse be time delay to prevent nuisance trips during startup.
Table 44-35. Maximum Acceptable Rating of Primary Overcurrent Protection
Primary VA Rating
Voltage 25
50

75

100

150

200

250

300

350

500

750

1000

1500

2000

3000

5000

7000

115

6/10
(1)

1-1/4
(2)

1-8/10 2-1/2
(3-2/10) (4)

3-1/2
(6-1/4)

5
(8)

4

5

5

8

10

15

20

25

—

—

—

120

6/10
(1)

1-1/4
(2)

1-8/10
(3)

3-1/2
(6-1/4)

5
(8)

4

5

5

8

10

15

15

20

—

—

—

200

3/10
(6/10)

3/4
(1-1/4)

1-1/8
1-1/2
(1-8/10) (2-1/2)

2-1/4
(3-1/2)

3
(5)

3-1/2
(6-1/4)

4-1/2
(7-1/2)

5
(8)

4-1/2

7

9

15

15

20

—

—

208

3/10
(6/10)

6/10
(1-1/8)

1
1-4/10
(1-8/10) (2-1/4)

2
(3-1/2)

2-8/10
(4-1/2)

3-1/2
(6)

4
(7)

5
(8)

4

6

8

12

15

20

30

—

220

3/10
(1/2)

6/10
(1-1/8)

1
1-1/4
(1-6/10) (2-1/4)

2
2-1/2
(3-2/10) (4-1/2)

3-2/10 4
(5-6/10) (6-1/4)

4-1/2
(7-1/2)

4

6

8

12

15

20

30

—

230

3/10
(1/2)

6/10
(1)

8/10
1-1/4
(1-6/10) (2)

1-8/10 2-1/2
(3-2/10) (4)

3-2/10
(5)

3-1/2
(6-1/4)

4-1/2
(7-1/2)

4

6

8

10

15

20

30

—

240

3/10
(1/2)

6/10
(1)

8/10
(1-1/2)

1-1/4
(2)

1-8/10
(3)

2-1/4
(4)

3
(5)

3-1/2
(6-1/4)

4
(7)

3-1/2

5

7

10

15

20

30

—

277

1/4
(4/10)

1/2
(8/10)

8/10
(1-1/4)

1
1-6/10
(1-8/10) (2-1/2)

2
(3-1/2)

2-1/2
(4-1/2)

3-2/10
(5)

3-1/2
(6-1/4)

5
(9)

5

6

9

12

15

25

—

380

3/16
(3/10)

3/10
(6/10)

1/2
(8/10)

3/4
(1-1/4)

1-1/8
1-1/2
(1-8/10) (2-1/2)

1-8/10 2-1/4
(3-2/10) (3-1/2)

2-1/2
(4-1/2)

3-1/2
(6-1/4)

5-6/10
(9)

4-1/2

6-1/4

9

15

20

25

400

3/16
(3/10)

3/10
(6/10)

1/2
(8/10)

3/4
(1-1/4)

1-1/8
1-1/2
(1-8/10) (2-1/2)

1-8/10
(3)

2-1/4
(3-1/2)

2-1/2
(4)

3-1/2
(6-1/4)

5-6/10
(9)

4-1/2

6-1/4

9

12

15

20

416

15/100 3/10
(3/10) (6/10)

1/2
(8/10)

6/10
(1-1/8)

1
1-4/10
(1-8/10) (2-1/4)

1-8/10
(3)

2
(3-1/2)

2-1/2
(4)

3-1/2
(6)

5
(9)

4

6

8

12

15

20

440

15/100 3/10
(1/4)
(1/2)

1/2
(8/10)

6/10
(1-1/8)

1
1-1/4
(1-6/10) (2-1/4)

1-6/10 2
2-1/4
(2-8/10) (3-2/10) (3-1/2)

3-2/10
(5)

5
(8)

4

6

8

12

15

20

460

15/100 3/10
(1/4)
(1/2)

4/10
(8/10)

6/10
(1)

8/10
(1-1/2)

1-1/4
(2)

1-6/10
(2-1/2)

1-8/10 2-1/4
3-2/10
(3-2/10) (3-2/10) (5)

4-1/2
(8)

3-1/2

6

8

12

15

20

480

15/100 3/10
(1/4)
(1/2)

4/10
(3/4)

6/10
(1)

8/10
(1-1/2)

1-1/4
(2)

1-1/2
(2-1/2)

1-8/10
(3)

2
(3-1/2)

3
(5)

4-1/2
(7-1/2)

3-1/2

5

7

10

15

20

550

1/8
(2/10)

1/4
(4/10)

4/10
(6/10)

1/2
(8/10)

8/10
(1-1/4)

1
1-1/4
(1-8/10) (2-1/4)

1-6/10
(2-1/2)

1-8/10
(3)

2-1/2
(4-1/2)

4
(6-1/4)

5

4-1/2

6

9

15

15

575

1/8
(2/10)

1/4
(4/10)

3/10
(6/10)

1/2
(8/10)

3/4
(1-1/4)

1
1-1/4
(1-6/10) (2)

1-1/2
(2-1/2)

1-8/10
(3)

2-1/2
(4)

3
(6-1/4)

5

4-1/2

6

9

15

15

600

1/8
(2/10)

2/10
(4/10)

3/10
(6/10)

1/2
(8/10)

3/4
(1-1/4)

8/10
1-1/4
(1-6/10) (2)

1-1/2
(2-1/2)

1-6/10 2-1/4
(2-8/10) (4)

3-1/2
(6-1/4)

5

4

6

9

15

15

2-1/4
(4)

Note: If the rated primary current is less than 2 amperes, the maximum rating of the overcurrent device is 300% for power circuits, shown
above, or 500% for control circuits, shown above (in brackets). If the rated primary current is 2 amperes or more, the maximum rating of the
overcurrent device is 250%. All figures assume secondary overcurrent protection per NEC/UL.
References: NEC 430-72 (c) exception 2, 450-3 (b) 1 & 2, UL 508 32.7, UL 845 11.16 and 11.17.

Table 44-36. Maximum Acceptable Rating of Secondary Overcurrent Protection
Secondary VA Rating
Voltage
25
50
12
24

75

100

150

200

250

300

350

500

750

1000

1500

2000

3000

5000

3-1/2
1-6/10

7
3-2/10

10
5

15
6-1/4

20
10

30
12

—
15

—
20

—
20

—
30

—
—

—
—

—
—

—
—

—
—

—
—

90
95
100

4/10
4/10
4/10

8/10
8/10
8/10

1-1/4
1-1/4
1-1/4

1-8/10
1-6/10
1-6/10

2-1/2
2-1/2
2-1/2

3-1/2
3-1/2
3-2/10

4-1/2
4
4

5
5
5

6-1/4
6
5-6/10

9
8
8

12
12
12

15
15
15

30
20
20

30
30
30

—
—
—

—
—
—

110
115
120

3/10
3/10
3/10

3/4
6/10
6/10

1-1/8
1
1

1-1/2
1-4/10
1-1/4

2-1/4
2
2

3
2-8/10
2-1/2

3-1/2
3-1/2
3-2/10

4-1/2
4
4

5
5
4-1/2

7-1/2
7
6-1/4

10
10
10

15
15
15

20
20
20

30
30
20

—
—
—

—
—
—

220
230
240

15/100
15/100
15/100

3/10
3/10
3/10

1/2
1/2
1/2

3/4
6/10
6/10

1-1/8
1
1

1-1/2
1-4/10
1-1/4

1-8/10
1-8/10
1-6/10

2-1/4
2
2

2-1/2
2-1/2
2-1/2

3-1/2
3-1/2
3-2/10

5-6/10
5
5

7
7
7

9
8
8

15
15
12

20
20
20

30
30
30

Note: If the rated secondary current is less than 9 amperes, the maximum rating of the overcurrent device is 167%; 9 amperes or more, the maximum
rating of the overcurrent device is 125%. If 125% does not correspond to a standard fuse rating, the next highest standard rating may be used.
References: NEC 430-72 (c) exception 2, 450-3 (b) 1 & 2, UL 508 32.7, UL 845 11.16 and 11.17.

CA08102001E

For more information visit: www.eaton.com

44

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-34

April 2009

Types MTA, MTC and AP

Wiring Diagrams
Type MTA and MTC Control Transformers
Table 44-39. Wiring for Diagram 3

Table 44-37. Wiring for Diagram 1
Volts

Connect

Lines

A

B

460
230

—
—

H2 to H3
H1 to H3 and H2 to H4

115

—

—

H1

H3

H2

H1-H4
H1-H4

460
230

—
—

H2 to H3
H1 to H3 and H2 to H4

X1-X2

230
115

—
—

X2 to X3
X1 to X3 and X2 to X4

Connect

Lines

—
—

H2 to H3
H1 to H3 and H2 to H4

H1-H4
H1-H4

—
—

X2 to X3
X1 to X3 and X2 to X4

X1-X4
X1-X4

A

B

H1-H4
H1-H4

480
240

X1-X4
X1-X4

240
115

H1

H3

H2

H4

H1

H3

H2

H4

X4

X2

X3

X1

X4

X2

X3

X1

Lines

Table 44-40. Wiring for Diagram 4
Volts

575
460
230
—

416
380
—
208

H2 to H3
H2 to H3
H1 to H3 and H2 to H4
H1 to H3 and H2 to H5

H1-H5
H1-H4
H1-H4
H1-H5

115
95

115
95

—
—

X1-X3
X1-X2

H3

H2

X2

Figure 44-6. Diagram 5

Figure 44-4. Diagram 3

B

X3

Volts

X1

Connect

H1

Lines

B

Table 44-38. Wiring for Diagram 2

44

Table 44-41. Wiring for Diagram 5

Connect

A

Figure 44-2. Diagram 1

A

Volts

H4

X2

Volts

Type AP Control Transformers

H4

Connect

Lines

115

—

H1-H2

24

—

X1-X2

A

B

115
12

H1

H2

X2

X1

H5

X1

Figure 44-5. Diagram 4

Figure 44-3. Diagram 2

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-35
Industrial Control Transformers
April 2009

Type MTA

Product Selection
Additional Product Selection information begins on Page 44-63.
Table 44-42. Type MTA
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Frame

Wiring
Style
Diagram  Number

Price
U.S.

230/460 Volts to 115 Volts, 60 Hz
50

(Use Type MTC – C0050C2A)

75
100

3-3/16
3-3/16

3-3/4
3-3/4

3-3/4
4

3
4

80
80

95
95

95
102

1.4
1.8

FR1510
FR1512

1
1

C0075A2F
C0100A2F

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4-3/4
4-1/2
5

6
7
8

80
96
96

95
114
114

95
114
127

2.7
3.2
3.6

FR1520
FR1714
FR1717

1
1
1

C0150A2F
C0200A2F
C0250A2F

300
350
500

3-13/16
3-13/16
4-3/8

4-1/2
4-1/2
5-1/4

6
6
5-5/8

12
12
15

96
96
111

114
114
133

152
152
143

5.4
5.4
6.8

FR1730
FR1727
FR1923

1
1
1

C0300A2F
C0350A2F
C0500A2F

750
1000
1500

4-3/8
5-1/4
6

5-1/4
6-1/8
6-7/8

6-1/8
6-3/4
7-1/2

19
19
27

111
133
152

133
155
174

155
171
190

8.6
8.6
12.3

FR1931
FRC613
FRC614

1
1
1

C0750A2F
C1000A2F
C1500A2F

2000
3000
5000

5-7/8
6-1/2
7-5/8

6-7/8
8-3/16
8-15/16

8-1/2
8-3/4
10-1/4

36
52
79

149
165
193

174
207
227

215
222
260

16.3
23.6
35.8

FRC827
FRC828
FRC829

1
1
1

C2000A2F
C3000A2F
C5000A2F

230/460 Volts to 115/230 Volts, 60 Hz
50
75
100

2-19/32
3-3/16
3-3/16

3
3-3/4
3-3/4

3-1/4
3-3/4
4

2
3
4

65
80
80

76
95
95

82
95
102

.9
1.4
1.8

FR1310
FR1510
FR1512

3
3
3

C0050A2G
C0075A2G
C0100A2G

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4-3/4
4-1/2
5

6
7
8

80
96
96

95
114
114

95
114
127

2.7
3.2
3.6

FR1520
FR1714
FR1717

3
3
3

C0150A2G
C0200A2G
C0250A2G

300
350
500

3-13/16
3-13/16
4-3/8

4-1/2
4-1/2
5-1/4

6
6
6-1/4

10
12
15

96
96
111

114
114
133

152
152
158

4.5
5.4
6.8

FR1727
FR1727
FR1930

3
3
3

C0300A2G
C0350A2G
C0500A2G

750
1000
1500

5-1/4
5-1/4
6

6-1/8
6-1/8
6-7/8

6-3/4
6-3/4
7-1/2

19
19
27

133
133
152

155
155
174

171
171
190

8.6
8.6
12.3

FRC613
FRC613
FRC614

3
3
3

C0750A2G
C1000A2G
C1500A2G

2000
3000
5000

5-7/8
6-1/2
5-5/8

6-7/8
8-3/16
8-15/16

8-1/2
8-3/4
10-1/4

36
52
79

149
165
193

174
207
227

215
222
260

16.3
23.6
35.8

FRC827
FRC828
FRC829

3
3
3

C2000A2G
C3000A2G
C5000A2G



See Page 44-34 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

44

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-36

April 2009

Type MTA
Table 44-43. Type MTA
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Frame

Wiring
Style
Diagram  Number

Price
U.S.

230/460/575 Volts to 115/95 Volts, 50/60 Hz
50
75
100

2-19/32
3-3/16
3-3/16

3
3-3/4
3-3/4

3-3/4
4
4 3/4

2
4
5

98
80
80

76
95
95

95
102
120

1.5
1.8
2.7

FR1314
FR1512
FR1517

2A
2A
2A

C0050A3C
C0075A3C
C0100A3C

150
200
250

3-13/16
3-13/16
3-13/16

4-1/2
4-1/2
4-1/2

4-1/2
5
5-1/2

7
8
10

96
96
96

114
114
114

114
127
139

3.2
3.6
4.5

FR1714
FR1717
FR1723

2A
2A
2A

C0150A3C
C0200A3C
C0250A3C

300
350
500

3-13/16
4-3/8
4-3/8

4-1/2
5-1/4
5-1/4

6
5-5/8
6-1/8

12
14
17

96
111
111

114
133
133

152
143
155

5.4
6.8
8.6

FR1730
FR1923
FR1931

2A
2A
2A

C0300A3C
C0350A3C
C0500A3C

4-3/8
6
5-7/8

5-1/4
6-7/8
6-7/8

7-3/4
7-1/2
8-1/2

27
24
34

111
152
149

133
174
174

196
190
215

12.3
10.9
15.4

FR1943
FRC614
FRC827

2A
2A
2A

C0750A3C
C1000A3C
C1500A3C

3-3/4
4-1/8
4-1/2

2
5
7

65
80
96

76
95
114

82
104
114

.9
2.3
3.2

FR1310
FR1513
FR1714

4B
4B
4B

C0050A3B
C0100A3B
C0200A3B

750
1000
1500

115 Volts to 24 Volts, 50/60 Hz
50
100
200

2-19/32
3-3/16
3-13/16

3
3-3/4
4-1/2

208/380/416 Volts to 115/95 Volts, 50/60 Hz

44

50
100
150
200

2-19/32
3-3/16
3-13/16
3-13/16

3
3-3/4
4-1/2
4-1/2

3-3/4
4-3/4
4-1/2
5

3
5
7
8

98
80
96
96

76
95
114
114

95
120
114
127

1.5
2.3
3.2
3.6

FR1314
FR1516
FR1714
FR1717

2B
2B
2B
2B

C0050A3D
C0100A3D
C0150A3D
C0200A3D

250
300
500

3-13/16
3-13/16
4-3/8

4-1/2
4-1/2
5-1/4

5-1/2
6
6-1/8

10
13
18

96
96
111

114
114
133

139
152
155

4.5
5.4
8.6

FR1723
FR1730
FR1931

2B
2B
2B

C0250A3D
C0300A3D
C0500A3D

4-3/8
6
5-7/8

5-1/4
6-7/8
6-7/8

7-3/4
7-1/2
8-1/2

27
25
33

111
152
149

133
174
174

196
190
215

12.3
10.9
15.4

FR1943
FRC614
FRC827

2B
2B
2B

C0750A3D
C1000A3D
C1500A3D

750
1000
1500


See Page 44-34 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-37
Industrial Control Transformers
April 2009

Type MTC

Type MTC

Features, Benefits
and Functions
■

■
■
■
■

Type MTC Transformers

Product Description
Varnish impregnated core and
coil design.
■ Suitable for indoor applications.
■

Application Description
Transformers provide stepped down
voltages to machine tool control
devices enabling control circuits to be
isolated from all power and lighting
circuits. This allows the use of
grounded or ungrounded circuits that
are independent of the power or lighting grounds; greater safety is afforded
the operator. The control transformer
line is particularly adaptable on applications where compact construction
is demanded. The MTC line is similar
to the MTA line except it provides
increased regulation.

■

■
■
■
■

Designed specifically for loads
requiring extremely good regulation
— 10% – 200% better regulation
than Type MTA.
UL recognized component for units
rated 1000 VA and below.
CSA certified for units rated 1000 VA
and below.
50/60 Hz operation standard.
100% tested to verify product quality.
Each unit must pass rigid tests for
turns ratio, insulation, continuity,
and over potential.
Performance equals or exceeds
requirements of ANSI/NEMA ST-1.
Regulation exceeds ANSI/NEMA
requirements for all ratings.
50 – 5000 VA ratings.
55ºC rise, 105ºC insulation system.

Standards and Certifications
Industry Standards
All Cutler-Hammer dry-type distribution and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI and IEEE Standards.

The following pages provide listings for most
standard transformer ratings and styles.
For other ratings or styles not shown, refer
to Eaton.

CA08102001E

For more information visit: www.eaton.com

Product Specifications
Frequency
Cutler-Hammer standard dry-type distribution transformers are designed
for 60 Hz operation. Transformers
required for other frequencies are
available and must be specifically
designed.

Insulation System and Temperature Rise
Industry standards classify insulation
systems and rise as shown below:
Table 44-44. Insulation System Classification
Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Series-Multiple Windings
Series-multiple windings consist of 2
similar coils in each winding which
can be connected in series or parallel
(multiple). Transformers with seriesmultiple windings are designated with
an “X” or “/” between the voltage
ratings, such as voltages of “120/240”
or “240 X 480.” If the series-multiple
winding is designated by an “X,” the
winding can be connected only for a
series or parallel. With the “/” designation, a mid-point also becomes available in addition to the series or parallel
connection. As an example, a 120 X
240 winding can be connected for
either 120 (parallel) or 240 (series), but
a 120/240 winding can be connected
for 120 (parallel), or 240 (series), or 240
with a 120 mid-point.

44

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-38

April 2009

Type MTC

Product Selection
Additional Product Selection information begins on Page 44-63.
Table 44-45. Type MTC
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Frame

Wiring
Style
Diagram  Number

Price
U.S.

240/480 Volts to 120 Volts, 60 Hz
230/460 Volts to 115 Volts, 50/60 Hz
220/440 Volts to 110 Volts, 50/60 Hz
50
75
100

2-19/32
2-19/32
2-7/8

3
3
3-3/8

3-3/4
3-3/4
4

2
3
3

66
66
73

76
76
86

95
95
102

.9
1.4
1.4

FR1310
FR1314
FR1413

1
1
1

C0050C2A
C0075C2A
C0100C2A

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4-3/4
4-1/2
5

6
7
8

81
97
97

95
114
114

121
114
127

2.7
3.2
3.6

FR1517
FR1714
FR1717

1
1
1

C0150C2A
C0200C2A
C0250C2A

300
350
500

3-13/16
3-13/16
4-3/8

4-1/2
4-1/2
5-1/4

5-3/8
6
6-1/8

10
11
20

97
97
111

114
114
133

137
152
156

4.5
5.0
9.1

FR1722
FR1726
FR1931

1
1
1

C0300C2A
C0350C2A
C0500C2A

750
1000
1500

4-3/8
5-7/16
6-1/8

5-1/4
6-3/8
6-7/8

7-3/4
7-1/2
8-3/8

28
34
35

111
138
156

133
162
175

197
191
213

12.7
15.4
15.9

FR1934
FR2236
FRC822

1
1
1

C0750C2A
C1000C2A
C1500C2A

2000
3000
5000

6
7-3/8
7-7/8

6-3/4
8-7/16
8-11/16

8-1/2
8-3/4
11

38
53
82

152
187
200

171
214
221

216
222
279

17.3
24.1
37.2

FRC823
FRC824
FRC825

1
1
1

C2000C2A
C3000C2A
C5000C2A



See Page 44-34 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

Table 44-46. Type MTC with Integrally Mounted 30 Amperes, 600 volt Class with 2-Pole Primary Fuse Block for Rejection Type Fuses
(Fuses Not Included)

44

VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Frame

Wiring
Style
Diagram  Number

Price
U.S.

240/480 Volts to 120 Volts, 60 Hz
230/460 Volts to 115 Volts, 50/60 Hz
220/440 Volts to 110 Volts, 50/60 Hz
50
75
100
150

3-7/8
3-7/8
4-5/32
4-15/32

3
3
3-3/8
3-3/4

3-3/4
3-3/4
4
4-3/4

2.2
3.2
3.2
6.2

98
98
106
114

76
76
86
95

83
95
102
121

1.0
1.5
1.5
2.8

FR1310
FR1314
FR1413
FR1517

1
1
1
1

C0050C2AFB
C0075C2AFB
C0100C2AFB
C0150C2AFB

200
250
300

5-3/32
5-3/32
5-3/32

4-1/2
4-1/2
4-1/2

4-1/2
5
5-3/8

7.2
8.2
10.2

129
129
129

114
114
114

114
127
137

3.3
3.7
4.7

FR1714
FR1717
FR1722

1
1
1

C0200C2AFB
C0250C2AFB
C0300C2AFB

350
500
750

5-3/32
5-21/32
5-21/32

4-1/2
5-1/4
5-1/4

6
6-1/8
7-3/4

11.2
20.2
28.2

129
144
144

114
133
133

152
156
197

5.1
9.2
12.8

FR1726
FR1931
FR1934

1
1
1

C0350C2AFB
C0500C2AFB
C0750C2AFB

1000
1500
2000

6-23/32
7-13/32
7-9/32

6-3/8
6-7/8
6-3/4

7-1/2
8-3/8
8-1/2

34.2
35.2
38.2

171
188
185

162
175
171

191
213
216

15.5
16.0
17.4

FR2236
FRC822
FRC823

1
1
1

C1000C2AFB
C1500C2AFB
C2000C2AFB



See Page 44-34 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-39
Industrial Control Transformers
April 2009

Type MTE

Type MTE

Features, Benefits
and Functions
■
■
■
■

■
■

Type MTE Transformers

■
■

Product Description

■
■

Epoxy-encapsulated coils.

■

Application Description

■

Transformers provide stepped down
voltages to machine tool control
devices enabling control circuits to be
isolated from all power and lighting
circuits. This allows the use of
grounded or ungrounded circuits that
are independent of the power or lighting grounds; greater safety is afforded
the operator. The control transformer
line is particularly adaptable on applications where compact construction
is demanded.

■

■

Note: The MTG, “open core-coil design”
has been superseded by the epoxyencapsulated core-coil design MTE with
no change to dimensions or functionality.

■

Finger-Safe Terminal Covers (Optional)
■
■

UL listed.
CSA certified.
Epoxy encapsulated.
Laminations of high quality silicon
steel to minimize core losses and
optimize performance.
Copper magnet wire for high
quality, efficient operation.
Secondary fuse clips where
applicable.
Optional primary fusing.
Molded in terminals.
50/60 Hz operation.
55°C rise, 105ºC insulation system.
Performance meets/exceeds
requirements of ANSI/NEMA ST-1.
Regulation exceeds ANSI/NEMA
requirements for all ratings.
25 – 1500 VA ratings.
Molded-in terminals for maximum
durability.

Fits CE marked designs 50 – 750 VA.
Fits MTE designs 25 – 750 VA.

Table 44-48. Finger-Safe Terminal Covers
Description

Catalog Price
Number U.S. $

4 Terminal Transformers
6 Terminal Transformers

FSK4
FSK6

Finger-Safe Terminal Covers — FSK4

Standards and Certifications

44

Industry Standards
All Cutler-Hammer dry-type distribution
and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI, and IEEE Standards. All 600 volt
class transformers are UL listed unless
otherwise noted.

Options and Accessories

Finger-Safe Terminal Covers — FSK6

Finger-Safe Primary Fuse Block Covers
■

Fits 2-pole primary fuse blocks on
MTE designs.

Primary Fuse Kit

Table 44-49. Finger-Safe Primary Fuse

The primary fuse kit includes a 2-pole
class CC fuse block, instructions, and
all associated mounting and wiring
hardware. Fuses are not included.
When installed, the primary fuse kit
will add a maximum of 11/16 inch to
the transformer depth and 1-15/16
inches to the transformer height.

Block Covers
Description

Catalog Price
Number U.S. $

Primary Fuse Block Covers FSKFB

Table 44-47. Primary Fuse Kit
Description

Catalog Price
Number U.S. $

Primary Fuse Kit

PFK1

Note: 1000 VA and larger are Class 130°C
Insulation System.
Finger-Safe Primary Fuse Block Covers

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-40

April 2009

Type MTE

Product Specifications

Wiring Diagrams

Insulation System and Temperature Rise
Industry standards classify insulation
systems and rise as shown below:
Table 44-50. Insulation System Classification
Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Figure 44-7. Diagram 1
Figure 44-10. Diagram 4

Series-Multiple Windings

44

Series-multiple windings consist of
2 similar coils in each winding which
can be connected in series or parallel
(multiple). Transformers with seriesmultiple windings are designated with
an “X” or “/” between the voltage
ratings, such as voltages of “120/240”
or “240 X 480.” If the series-multiple
winding is designated by an “X,” the
winding can be connected only for a
series or parallel. With the “/” designation, a mid-point also becomes available in addition to the series or parallel
connection. As an example, a 120 X
240 winding can be connected for
either 120 (parallel) or 240 (series), but
a 120/240 winding can be connected
for 120 (parallel), or 240 (series),
or 240 with a 120 mid-point.

Figure 44-8. Diagram 2

Figure 44-11. Diagram 5

Figure 44-9. Diagram 3

Figure 44-12. Diagram 6

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-41
Industrial Control Transformers
April 2009

Type MTE

Wiring Diagrams

X3

240 V

575 V

110,115,120 V

0V

220,230,240 V

380,400,416 V

H3

H4

H5

H6

H2

24 V

600 V
575 V
550 V

H2

0V

H1

Figure 44-20. Diagram 14
H1

Figure 44-17. Diagram 11

X1

460 V

120 V

Figure 44-13. Diagram 7

X2

0V

X1

X4 X2 X3 X1

Figure 44-14. Diagram 8

X4

X3

X2

230 V

X3

X4 X2 X3 X1

H5

208 V

X2

H4

230 V

X4

H2

115 V

H3

0V

H1

H4

400 V

H1 H3 H2 H4

H3

440,460,480 V

H1 H3 H2 H4

H2

23/24/25

480 V

550,575,600 V

H1

240 V

44

X1

Figure 44-21. Diagram 15

X4

X3

X2

Figure 44-22. Diagram 16
X2

X1

Figure 44-19. Diagram 13

Figure 44-16. Diagram 10

CA08102001E

H6

For more information visit: www.eaton.com

0V
115 V

115 V

0V

Figure 44-15. Diagram 9

24 V
23 V
22 V

H5
208 V

H4
230 V

H3

H2

0V

420 V
400 V
380 V

H2

400 V

Figure 44-18. Diagram 12
H1

H1

460 V

X1

575 V

X2

24 V
23 V
22 V

X1

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-42

April 2009

Type MTE

Product Selection
Additional Product Selection information begins on Page 44-63.
Table 44-51. Type MTE — Product Selection
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 240 x 480, 230 x 460, 220 x 440 with Jumpers
Secondary: 120/115/110 with Fuse Clips for 13/32 x 1-1/2 Fuses
25
50
75
100

2-9/16
2-9/16
2-9/16
2-7/8

3
3
3
3-3/8

2-1/2
3
3-1/2
3-3/8

1.7
2.6
3.5
4.2

65
65
65
73

76
76
76
86

64
76
89
86

.8
1.2
1.6
1.9

1
1
1
1

C0025E2A
C0050E2A
C0075E2A
C0100E2A

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

6.7
8.5
10.0

81
97
97

95
114
114

102
102
111

3.0
3.9
4.5

1
1
1

C0150E2A
C0200E2A
C0250E2A

300
350
500

3-13/16
3-13/16
4-3/4

4-1/2
4-1/2
5-1/4

4-3/4
5-1/4
5-1/2

11.3
13.6
19.2

97
97
121

114
114
133

121
133
140

5.1
6.2
8.7

1
1
1

C0300E2A
C0350E2A
C0500E2A

750
1000
1500

4-3/4
5-11/16
6-3/8

5-1/4
6-3/4
7-1/2

7
6-7/16
7-3/8

28.1
29.5
40.0

121
144
162

133
171
191

178
164
187

12.8
13.4
18.1

1
1
1

C0750E2A
C1000E2A
C1500E2A

Primary: 240 x 480 with Jumpers
Secondary: 24 with Fuse Clips for 13/32 x 1-1/2 Fuses (through 500 VA)

44

50
75
100
150

2-9/16
2-9/16
2-7/8
3-3/16

3
3
3-3/8
3-3/4

3
3-1/2
3-3/8
4

2.7
3.5
4.2
6.7

65
65
73
81

76
76
86
95

76
89
86
102

1.2
1.6
1.9
3.0

2
2
2
2

C0050E2B
C0075E2B
C0100E2B
C0150E2B

200
250
300

3-13/16
3-13/16
3-13/16

4-1/2
4-1/2
4-1/2

4
4-3/8
4-3/4

8.5
10.1
11.4

97
97
97

114
114
114

102
111
121

3.9
4.6
5.2

2
2
2

C0200E2B
C0250E2B
C0300E2B

350
500
750

3-13/16
4-3/4
4-3/4

4-1/2
5-1/4
5-1/4

5-1/4
5-5/8
7

13.4
17.5
28.1

97
121
121

114
133
133

133
143
178

6.1
7.9
12.8

2
2
2

C0350E2B
C0500E2B
C0750E2B

Primary: 120 x 240 with Jumpers
Secondary: 24 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100

2-9/16
2-9/16
2-7/8

3
3
3-3/8

3
3-1/2
3-3/8

2.6
3.6
4.4

65
65
73

76
76
86

76
89
56

1.2
1.6
2.0

3
3
3

C0050E1B
C0075E1B
C0100E1B

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

6.7
8.3
10.1

81
97
97

95
114
114

102
102
111

3.0
3.8
4.6

3
3
3

C0150E1B
C0200E1B
C0250E1B

300
350
500

3-13/16
3-13/16
4-3/4

4-1/2
4-1/2
5-1/4

4-3/4
5-1/4
5-5/8

11.2
13.2
17.5

97
97
121

114
114
133

121
133
143

5.1
6.0
7.9

3
3
3

C0300E1B
C0350E1B
C0500E1B

Primary: 208/277
Secondary: 120 with Fuse Clips for 13/32 x 1-1/2 Fuses



50
75
100
150

2-9/16
2-9/16
2-7/8
3-3/16

3
3
3-3/8
3-3/4

3
3-1/2
3-3/8
4

2.9
3.8
4.5
6.9

65
65
73
81

76
76
86
95

76
89
86
102

1.3
1.7
2.0
3.1

4
4
4
4

C0050E3A
C0075E3A
C0100E3A
C0150E3A

200
250
300

3-13/16
3-13/16
3-13/16

4-1/2
4-1/2
4-1/2

4
4-3/8
4-3/4

8.7
10.2
11.4

97
97
97

114
114
114

102
111
121

3.9
4.6
5.2

4
4
4

C0200E3A
C0250E3A
C0300E3A

350
500
750

3-13/16
4-3/4
4-3/4

4-1/2
5-1/4
5-1/4

5-1/4
5-3/8
7

13.7
17.2
25.7

97
121
121

114
133
133

133
136
178

6.2
7.8
11.7

4
4
4

C0350E3A
C0500E3A
C0750E3A

See Page 44-40 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-43
Industrial Control Transformers
April 2009

Type MTE
Table 44-52. Type MTE — Product Selection
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 240 x 480 with Jumpers
Secondary: 120 x 240 with Jumpers, Secondary Fuse Clips not Applicable
50
75
100
150

2-9/16
2-9/16
2-7/8
3-3/16

3
3
3-3/8
3-3/4

3
3-1/2
3-3/8
4

2.6
3.5
4.2
6.7

65
65
73
81

76
76
86
95

76
89
86
102

1.2
1.6
1.9
3.1

11
11
11
11

C0050E2CXX
C0075E2CXX
C0100E2CXX
C0150E2CXX

200
250
300

3-13/16
3-13/16
3-13/16

4-1/2
4-1/2
4-1/2

4
4-3/8
4-7/8

8.5
10.0
11.8

97
97
97

114
114
114

102
111
124

3.9
4.6
5.4

11
11
11

C0200E2CXX
C0250E2CXX
C0300E2CXX

350
500
750

3-13/16
4-3/4
4-3/4

4-1/2
5-1/4
5-1/4

5-1/4
5-1/4
7

13.6
17.5
26.4

97
121
121

114
133
133

133
133
178

6.2
8.0
12.0

11
11
11

C0350E2CXX
C0500E2CXX
C0750E2CXX

Primary: 550/575/600
Secondary: 110/115/120 with for 13/32 x 1-1/2 Fuses
50
75
100
150

2-9/16
2-9/16
2-7/8
3-3/16

3
3
3-3/8
3-3/4

3
3-1/2
3-3/8
4

2.7
3.6
4.2
6.8

65
65
73
81

76
76
86
95

76
89
86
102

1.2
1.6
1.9
3.1

10
10
10
10

C0050E4C
C0075E4C
C0100E4C
C0150E4C

200
250
300

3-13/16
3-13/16
3-13/16

4-1/2
4-1/2
4-1/2

4
4-3/8
4-3/4

8.4
10.0
11.3

97
97
97

114
114
114

102
111
121

3.8
4.6
5.1

10
10
10

C0200E4C
C0250E4C
C0300E4C

350
500
750

3-13/16
4-3/4
4-3/4

4-1/2
5-1/4
5-1/4

5-1/4
5-3/8
7

13.6
16.8
25.7

97
121
121

114
133
133

133
137
178

6.2
7.6
11.7

10
10
10

C0350E4C
C0500E4C
C0750E4C

Primary: 380/400/415
Secondary: 22/23/24 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100

2-9/16
2-9/16
2-7/8

3
3
3-3/8

3
3-1/2
3-3/8

2.5
3.5
4.0

65
65
73

76
76
86

76
89
86

1.1
1.6
1.8

13
13
13

C0050E4H
C0075E4H
C0100E4H

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

6.5
8.2
10.0

81
97
97

95
114
114

102
102
111

3.0
3.7
4.5

13
13
13

C0150E4H
C0200E4H
C0250E4H

300
350
500

3-13/16
3-13/16
4-3/4

4-1/2
4-1/2
5-1/4

4-3/4
5-1/4
5-1/2

11.0
13.6
17.7

97
97
121

114
114
133

121
133
140

5.0
6.2
8.0

13
13
13

C0300E4H
C0350E4H
C0500E4H

Primary: 550/575/600
Secondary: 22/23/24 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100
150

2-9/16
2-9/16
2-7/8
3-3/16

3
3
3-3/8
3-3/4

3
3-1/2
3 3/8
4

2.5
3.5
4.0
6.5

65
65
73
81

76
76
86
95

76
89
86
102

1.1
1.6
1.8
3.0

12
12
12
12

C0050E4W
C0075E4W
C0100E4W
C0150E4W

200
250
300

3-13/16
3-13/16
3-13/16

4-1/2
4-1/2
4-1/2

4
4-3/8
4-3/4

8.2
10.0
11.0

97
97
97

114
114
114

102
111
121

3.7
4.5
5.0

12
12
12

C0200E4W
C0250E4W
C0300E4W

350
500
750

3-13/16
4-3/4
4-1/2

4-1/2
5-1/4
5-1/4

5-1/4
5-1/2
7-3//8

13.6
17.7
28.0

97
121
114

114
133
133

133
140
187

6.2
8.0
12.7

12
12
12

C0350E4W
C0500E4W
C0750E4WXX 




See Page 44-41 for Wiring Diagrams.
Secondary fuse clips are not available on this catalog number.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

44

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-44

April 2009

Type MTE
Table 44-53. Types MTE — Product Selection
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 230/460/575
Secondary: 115/95 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100
150

2-9/16
2-7/8
2-7/8
3-3/16

3
3-3/8
3-3/8
3-3/4

3
3-3/8
3-7/8
4-1/4

3.5
4.5
6.0
7.7

65
73
73
81

76
86
86
95

76
86
98
108

1.6
2.0
2.7
3.5

5
5
5
5

C0050E3C
C0075E3C
C0100E3C
C0150E3C

200
250
300

3-13/16
3-13/16
3-13/16

4-1/2
4-1/2
4-1/2

4-1/4
4-3/4
5-1/8

9.0
9.7
11.7

97
97
97

114
114
114

108
121
130

4.1
4.4
5.3

5
5
5

C0200E3C
C0250E3C
C0300E3C

350
500
750

4-3/4
4-3/4
4-3/4

5-1/4
5-1/4
5-1/4

5
5-5/8
7

16.5
21.5
28.0

121
121
121

133
133
133

127
143
178

7.5
9.8
12.7

5
5
5

C0350E3C
C0500E3C
C0750E3C

Primary: 380/400/415
Secondary: 110 x 220 with Jumpers; Fuse Clips not Applicable
50
75
100
150

2-9/16
2-9/16
2-7/8
3-3/16

3
3
3-3/8
3-3/4

3
3-1/2
3-9/16
4

3.0
4.0
5.2
7.0

65
65
73
81

76
76
86
95

76
89
90
102

1.4
1.8
2.4
3.2

6
6
6
6

C0050E4D
C0075E4D
C0100E4D
C0150E4D

200
250
300

3-13/16
3-13/16
3-13/16

4-1/2
4-1/2
4-1/2

4
4-3/8
4-3/4

8.7
10.2
11.0

97
97
97

114
114
114

102
111
121

3.9
4.6
5.0

6
6
6

C0200E4D
C0250E4D
C0300E4D

350
500
750

3-13/16
4-3/4
4-3/4

4-1/2
5-1/4
5-1/4

5-1/4
5-3/8
7

13.0
20.0
28.0

97
121
121

114
133
133

133
136
178

5.9
9.1
12.7

6
6
6

C0350E4D
C0500E4D
C0750E4D

Primary: 200/220/440, 208/230/460, 240/480
Secondary: 23/110, 24/115, 25/120 with Fuse Clips for 13/32 x 1-1/2 Fuses

44

50
75
100

2-9/16
2-7/8
3-3/16

3
3-3/8
3-3/4

3-1/4
3-1/2
5-5/8

3.4
4.8
5.9

65
73
81

76
86
95

83
89
143

1.5
2.2
2.7

7
7
7

C0050E5E
C0075E5E
C0100E5E

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4-3/8
4-1/2
5-1/4

7.9
10.6
13.9

81
97
97

95
114
114

111
114
133

3.6
4.8
6.3

7
7
7

C0150E5E
C0200E5E
C0250E5E

300
350
500

4-3/4
4-3/4
4-3/4

5-1/4
5-1/4
5-1/4

5-1/8
5-3/8
6-7/8

15.5
16.8
23.4

121
121
121

133
133
133

130
136
175

7.0
7.6
10.6

7
7
7

C0300E5E
C0350E5E
C0500E5E

Universal Design (MTE Epoxy Encapsulated)
Primary: 240/416/480/600, 230/400/460/575, 220/380/440/550, 208/500
Secondary: 99/120/130, 95/115/125, 91/110/120, 85/100/110 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
100
150
250

2-7/8
3-3/16
3-13/16
3-13/16

3-3/8
3-3/4
4-1/2
4-1/2

4
4-5/8
4-7/16
5-7/8

4.0
6.6
8.8
14.7

73
81
97
97

86
95
114
114

102
117
113
149

1.8
3.0
4.0
6.7

8
8
8
8

C0050E6U 
C0100E6U 
C0150E6U 
C0250E6U 

350
500
750

4-7/16
4-7/16
5-3/4

5-1/4
5-1/4
6-3/4

5-5/8
7
5-11/16

18.6
25.6
30.5

113
113
146

133
133
171

143
178
144

8.4
11.6
13.8

8
8
8

C0350E6U 
C0500E6U 
C0750E6U 





See Pages 44-40 and 44-41 for Wiring Diagrams.
Type MTG Open Core-Coil Universal Design has been superseded by Type MTE Epoxy Encapsulated Universal Design with no changes to form,
fit or function.
Type MTE Epoxy Encapsulated Universal Design.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-45
Industrial Control Transformers
April 2009

Type MTE
Table 44-54. Transformers with Primary Fuse Blocks — Product Selection
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 240 x 480, 230 x 460, 220 x 440 with Jumpers and Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 120/115/110 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100

3-15/16
3-15/16
4-1/4

3
3
3-3/8

3
3-1/2
3-3/8

2.8
3.7
4.4

100
100
108

76
76
86

76
89
86

1.3
1.7
2.0

1
1
1

C0050E2AFB
C0075E2AFB
C0100E2AFB

150
200
250

4-9/16
5-3/16
5-3/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

6.9
8.7
10.2

116
132
132

95
114
114

102
102
111

3.1
3.9
4.6

1
1
1

C0150E2AFB
C0200E2AFB
C0250E2AFB

300
350
500

5-3/16
5-3/16
6-1/8

4-1/2
4-1/2
5-1/4

4-3/4
5-1/4
5-1/2

11.5
13.8
19.4

132
132
156

114
114
133

121
133
140

5.2
6.3
8.8

1
1
1

C0300E2AFB
C0350E2AFB
C0500E2AFB

750
1000
1500

6-1/8
7-1/16
7-3/4

5-1/4
6-3/4
7-1/2

7
6-7/16
7-3/8

28.3
29.7
40.2

156
179
197

133
171
191

178
164
187

12.8
13.4
18.1

1
1
1

C0750E2AFB
C1000E2AFB
C1500E2AFB

Primary: 240 x 480 with Jumpers and Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 24 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100

3-15/16
3-15/16
4-1/4

3
3
3-3/8

3
3-1/2
3-3/8

2.8
3.8
4.4

100
100
108

76
76
86

76
89
86

1.3
1.7
2.1

2
2
2

C0050E2BFB
C0075E2BFB
C0100E2BFB

150
200
250

4-9/16
5-3/16
5-3/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

6.9
8.7
10.3

116
132
132

95
114
114

102
102
111

3.1
3.9
4.7

2
2
2

C0150E2BFB
C0200E2BFB
C0250E2BFB

300
350
500

5-3/16
5-3/16
6-1/8

4-1/2
4-1/2
5-1/4

4-3/4
5-1/4
5-5/8

11.6
13.6
17.7

132
132
156

114
114
133

121
133
143

5.3
6.2
8.0

2
2
2

C0300E2BFB
C0350E2BFB
C0500E2BFB

Primary: 120 x 240 with Jumpers and Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 24 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100

3-15/16
3-15/16
4-1/4

3
3
3-3/8

3
3 1/2
3 3/8

2.8
3.8
4.6

100
100
108

76
76
86

76
89
86

1.3
1.7
2.1

3
3
3

C0050E1BFB
C0075E1BFB
C0100E1BFB

150
200
250

4-9/16
5-3/16
5-3/16

3-3/4
4-1/2
4-1/2

4
4
4 3/8

6.9
8.5
10.3

116
132
132

95
114
114

102
102
111

3.1
3.9
4.7

3
3
3

C0150E1BFB
C0200E1BFB
C0250E1BFB

300
350
500

5-3/16
5-3/16
6-1/8

4-1/2
4-1/2
5-1/4

4 3/4
5 1/4
5 5/8

11.4
13.4
17.7

132
132
156

114
114
133

121
133
143

5.2
6.1
8.0

3
3
3

C0300E1BFB
C0350E1BFB
C0500E1BFB

Primary: 208/277 with Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 120 with Fuse Clips for 13/32 x 1-1/2 Fuses



50
75
100

3-15/16
3-15/16
4-1/4

3
3
3-3/8

3
3-1/2
3-3/8

3.1
4.0
4.7

100
100
108

76
76
86

76
89
86

1.4
1.8
2.1

4
4
4

C0050E3AFB
C0075E3AFB
C0100E3AFB

150
200
250

4-9/16
5-3/16
5-3/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

7.1
8.9
10.4

116
132
132

95
114
114

102
102
111

3.2
4.0
4.7

4
4
4

C0150E3AFB
C0200E3AFB
C0250E3AFB

300
350
500

5-3/16
5-3/16
6-1/8

4-1/2
4-1/2
5-1/4

4-3/4
5-1/4
5-3/8

11.6
13.9
17.4

132
132
156

114
114
133

121
133
143

5.3
6.3
7.9

4
4
4

C0300E3AFB
C0350E3AFB
C0500E3AFB

See Page 44-40 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

44

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-46

April 2009

Type MTE
Table 44-55. Transformers with Primary Fuse Blocks — Product Selection
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 550/575/600 with Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 110/115/120 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100
150

3-15/16
3-15/16
4-1/4
4-9/16

3
3
3 -3/8
3-3/4

3
3-1/2
3 3/8
4

2.9
3.8
4.4
7.0

100
100
108
116

76
76
86
95

76
89
86
102

1.3
1.7
2.0
3.2

10
10
10
10

C0050E4CFB
C0075E4CFB
C0100E4CFB
C0150E4CFB

200
250
300

5-3/16
5-3/16
5-3/16

4-1/2
4-1/2
4-1/2

4
4 3/8
4 3/4

8.6
10.2
11.5

132
132
132

114
114
114

102
111
121

3.9
4.6
5.2

10
10
10

C0200E4CFB
C0250E4CFB
C0300E4CFB

350
500
750

5-3/16
6-1/8
6-1/8

4-1/2
5-1/4
5-1/4

5 1/4
5 3/8
7

13.8
17.0
25.9

132
156
156

114
133
133

133
137
178

6.3
7.7
11.8

10
10
10

C0350E4CFB
C0500E4CFB
C0750E4CFB

Primary: 380/400/415 with Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 22/23/24 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100

2-9/16
2-9/16
2-7/8

3
3
3-3/8

3
3-1/2
3-3/8

2.6
3.7
4.2

65
65
73

76
76
86

76
89
86

1.2
1.7
1.9

13
13
13

C0050E4HFB
C0075E4HFB
C0100E4HFB

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

6.7
8.4
10.2

81
97
97

95
114
114

102
102
111

3.0
3.8
4.6

13
13
13

C0150E4HFB
C0200E4HFB
C0250E4HFB

Primary: 550/575/600 with Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 22/23/24 with Fuse Clips for 13/32 x 1-1/2 Fuses

44

50
75
100

2-9/16
2-9/16
2-7/8

3
3
3-3/8

3
3-1/2
3-3/8

2.7
3.7
4.2

65
65
73

76
76
86

76
89
86

1.2
1.7
1.9

12
12
12

C0050E4WFB
C0075E4WFB
C0100E4WFB

150
200
250

3-3/16
3-13/16
3-13/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

6.7
8.4
10.2

81
97
97

95
114
114

102
102
111

3.0
3.8
4.6

12
12
12

C0150E4WFB
C0200E4WFB
C0250E4WFB



See Page 44-41 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-47
Industrial Control Transformers
April 2009

Type MTE
Table 44-56. Transformers with Primary Fuse Blocks — Product Selection
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 230/460/575 with Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 115/95 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100

3-13/16
4-1/4
4-1/4

3
3-3/8
3-3/8

3
3-3/8
3-7/8

3.7
4.7
6.2

97
108
108

76
86
86

76
86
98

1.7
2.1
2.8

5
5
5

C0050E3CFB
C0075E3CFB
C0100E3CFB

150
200
250

4-9/16
5-3/16
5-3/16

3-3/4
4-1/2
4-1/2

4-1/4
4-1/4
4-3/4

7.9
9.2
9.9

116
132
132

95
114
114

108
108
121

3.6
4.2
4.5

5
5
5

C0150E3CFB
C0200E3CFB
C0250E3CFB

300
350
500

5-3/16
6-1/8
6-1/8

4-1/2
5-1/4
5-1/4

5-1/8
5
5-7/8

11.9
16.7
21.7

132
156
156

114
133
133

130
127
149

5.4
7.6
9.9

5
5
5

C0300E3CFB
C0350E3CFB
C0500E3CFB

Primary: 380/400/415 with Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 110 x 220 with Jumpers; Fuse Clips Not Available
50
75
100

3-15/16
3-15/16
4-1/4

3
3
3-3/8

3
3-1/2
3-9/16

3.2
4.2
5.4

100
100
108

76
76
86

76
89
90

1.5
1.9
2.5

6
6
6

C0050E4DFB
C0075E4DFB
C0100E4DFB

150
200
250

4-9/16
5-3/16
5-3/16

3-3/4
4-1/2
4-1/2

4
4
4-3/8

7.2
8.9
10.4

116
132
132

95
114
114

102
102
111

3.3
4.0
4.7

6
6
6

C0150E4DFB
C0200E4DFB
C0250E4DFB

300
350
500

5-3/16
5-3/16
6-1/8

4-1/2
4-1/2
5-1/4

4-3/4
5-1/4
5-5/8

11.2
13.2
20.2

132
132
156

114
114
133

121
133
143

5.1
6.0
9.2

6
6
6

C0300E4DFB
C0350E4DFB
C0500E4DFB

Primary: 200/220/440, 208/230/460, 240/480 with Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 23/110, 24/115, 25/120 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
75
100

3-15/16
4-1/4
4-9/16

3
3-3/8
3-3/4

3-1/4
3-1/2
3-5/8

3.6
5.0
6.1

100
108
116

76
86
95

83
89
92

1.6
2.3
2.8

7
7
7

C0050E5EFB
C0075E5EFB
C0100E5EFB

150
200
250

4-9/16
5-3/16
5-3/16

3-3/4
4-1/2
4-1/2

4-3/8
4-1/2
5-1/4

8.1
10.8
14.1

116
132
132

95
114
114

111
114
133

3.7
4.9
6.4

7
7
7

C0150E5EFB
C0200E5EFB
C0250E5EFB

300
350
500

6-1/8
6-1/8
6-1/8

5-1/4
5-1/4
5-1/4

5-1/8
5-3/8
6-7/8

15.7
17.0
23.6

156
156
156

133
133
133

130
136
175

7.1
7.7
10.7

7
7
7

C0300E5EFB
C0350E5EFB
C0500E5EFB

Universal Design (MTE Epoxy Encapsulated)
Primary: 240/416/480/600, 230/400/460/575, 220/380/440/550, 208/500 with Two-Pole Primary Fuse Block for Rejection Type Fuses
Secondary: 99/120/130, 95/115/125, 91/110/120, 85/100/110 with Fuse Clips for 13/32 x 1-1/2 Fuses
50
100
150

4-1/4
4-9/16
5-3/16

3-3/8
3-3/4
4-1/2

4
4-5/8
4-7/16

4.2
6.8
9.0

108
116
132

86
95
114

102
117
113

1.9
3.1
4.1

8
8
8

C0050E6UFB 
C0100E6UFB 
C0150E6UFB 

250
350
500

5-3/16
5-13/16
5-13/16

4-1/2
5-1/4
5-1/4

5-7/8
5-5/8
7

14.9
18.8
25.8

132
148
148

114
133
133

149
143
178

6.8
8.5
11.7

8
8
8

C0250E6UFB 
C0350E6UFB 
C0500E6UFB 





See Pages 44-40 and 44-41 for Wiring Diagrams.
Type MTG Open Core-Coil Universal Design has been superseded by Type MTE Epoxy Encapsulated Universal Design with no changes to form,
fit or function.
Type MTE Epoxy Encapsulated Universal Design.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

44

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-48

April 2009

Type MTK

Type MTK

Features, Benefits
and Functions
■
■
■
■
■
■
■
■

Epoxy resin-impregnated coil.
■ Economical solution for high
inrush applications.

Application Description

44

Transformers provide stepped down
voltages to machine tool control
devices enabling control circuits to be
isolated from all power and lighting
circuits. This allows the use of
grounded or ungrounded circuits that
are independent of the power or lighting grounds; greater safety is afforded
the operator. The control transformer
line is particularly adaptable on applications where compact construction
is demanded.

Industry standards classify insulation
systems and rise as shown below:
Table 44-57. Insulation System Classification
Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

Standards and Certifications
Industry Standards

Series-Multiple Windings

All Cutler-Hammer dry-type distribution
and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI, and IEEE Standards. All 600 volt
class transformers are UL listed unless
otherwise noted.

Series-multiple windings consist of 2
similar coils in each winding which
can be connected in series or parallel
(multiple). Transformers with seriesmultiple windings are designated with
an “X” or “/” between the voltage
ratings, such as voltages of “120/240”
or “240 X 480.” If the series-multiple
winding is designated by an “X,” the
winding can be connected only for a
series or parallel. With the “/” designation, a mid-point also becomes available in addition to the series or parallel
connection. As an example, a 120 X
240 winding can be connected for
either 120 (parallel) or 240 (series), but
a 120/240 winding can be connected
for 120 (parallel), or 240 (series), or 240
with a 120 mid-point.

■

■

Insulation System and Temperature Rise

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Type MTK Transformers

Product Description

UL listed.
CSA certified.
Epoxy resin impregnated coil design.
Copper magnet wire for high
quality, efficient operation.
50/60 Hz operation.
115°C rise, 180ºC insulation system.
Performance meets/exceeds
requirements of ANSI/NEMA ST-1.
Regulation exceeds ANSI/NEMA
requirements for all ratings.
500 – 5000 VA ratings.

Product Specifications

The following pages provide listings for most
standard transformer ratings and styles.
For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-49
Industrial Control Transformers
April 2009

Type MTK

Wiring Diagrams

Figure 44-23. Diagram 1
Figure 44-27. Diagram 5

Figure 44-31. Diagram 9

Figure 44-24. Diagram 2

44
Figure 44-32. Diagram 10
Figure 44-28. Diagram 6

Figure 44-25. Diagram 3

Figure 44-29. Diagram 7

240 V

480 V

H1 H3 H2 H4

H1 H3 H2 H4

H1

H3

X4

X2

Figure 44-30. Diagram 8

CA08102001E

For more information visit: www.eaton.com

H4

X3

X1

X4 X2 X3 X1

X4 X2 X3 X1

120 V

240 V

Figure 44-33. Diagram 11

Figure 44-26. Diagram 4

H2

44-50

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers
April 2009

Type MTK

Wiring Diagrams

X3

X2

Figure 44-35. Diagram 13

X4

0V

208 V
115 V

230 V
115 V

400 V

H6

X2

X1

X2

H6
0V

208 V

H5

230 V

H4

400 V

X3

X3

230 V

X1

H3

460 V

H2

575 V

H1

H5

Figure 44-38. Diagram 16

115 V

X2

24 V
23 V
22 V

H2

24 V

44

420 V
400 V
380 V

Figure 44-36. Diagram 14

0V

H1

H4

X1

X4

Figure 44-34. Diagram 12

H3

0V

575 V

H2
460 V

H1

0V

X1

H4

110,115,120 V

440,460,480 V

H3

220,230,240 V

H2

380,400,416 V

H1

23/24/25

24 V
23 V
22 V

H2

0V

X2

600 V
575 V
550 V

550,575,600 V

H1

X1

Figure 44-37. Diagram 15

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-51
Industrial Control Transformers
April 2009

Type MTK

Product Selection
Additional Product Selection information begins on Page 44-63.
Table 44-58. Type MTK — Product Selection
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 240 x 480, 230 x 460, 220 x 440
Secondary: 120/115/110
500
750
1000
1500

3-13/16
4-7/16
4-7/16
5-11/16

4-1/2
5-1/2
5-1/4
6-3/4

6
6-1/2
7-7/8
6-3/4

13.0
19.5
29.8
30.0

97
113
113
144

114
133
133
171

152
165
200
171

5.9
8.9
13.6
13.6

1
1
1
1

C0500K2A
C0750K2A
C1000K2A
C1500K2A

2000
3000
5000

5-11/16
7-9/16
7-9/16

6-3/4
9
9

7
7-1/2
7-3/4

38.0
53.0
89.0

144
192
192

171
229
229

178
191
197

17.3
24.1
40.5

1
1
1

C2000K2A
C3000K2A
C5000K2A

6-3/8
6-3/4
6-3/4

7-1/8
7-1/2
8-1/4

29.0
33.0
43.0

137
144
144

162
171
171

181
191
210

13.1
15.0
19.5

4
4
4

C1000K3A
C1500K3A
C2000K3A

8-1/4
10-1/2

64.0
102.0

194
259

229
229

210
267

29.0
46.3

4
4

C3000K3A
C5000K3A

29.2
33.5
42.5

137
144
192

162
171
229

184
210
192

13.3
15.2
19.3

5
5
5

C1000K3C
C1500K3C
C2000K3C

63.7
102.0

192
259

229
229

219
343

29.0
46.4

5
5

C3000K3C
C5000K3C

Primary: 208/277
Secondary: 120
1000
1500
2000
3000
5000

5-3/8
5-11/16
5-11/16
7-5/8
10-3/16

9
9

Primary: 230/460/575
Secondary: 115/95
1000
1500
2000

5-3/8
5-11/16
7-9/16

6-3/8
6-3/4
9

3000
5000

7-9/16
7-3/16

9
9

7-1/8
8-1/4
7-9/16
8-5/8
13-1/2

Primary: 208/380/416
Secondary: 115/95
1000
1500
2000
3000
5000

5-3/8
5-11/16
5-11/16
7-5/8
10-3/16

44
6-3/8
6-3/4
6-3/4
9
9

7-1/8
8-1/4
9-1/4

29.0
43.0
55.0

137
144
144

162
171
171

181
210
235

13.1
19.5
25.0

9
9
9

C1000K3D
C1500K3D
C2000K3D

8-5/8
11

74.0
108.0

194
259

229
229

219
279

33.5
49.0

9
9

C3000K3D
C5000K3D

7-1/8
7-1/2
8-1/4

29.0
33.0
43.0

137
144
144

162
171
171

181
191
210

13.1
15.0
19.5

10
10
10

C1000K4C
C1500K4C
C2000K4C

8-1/4
10-1/2

64.0
102.0

194
259

229
229

210
267

29.0
46.3

10
10

C3000K4C
C5000K4C

6-1/2
7-1/2
8-1/4

28.0
33.0
43.0

144
144
144

171
171
171

165
191
210

12.7
15.0
19.5

6
6
6

C1000K4D
C1500K4D
C2000K4D

8-1/4
10-1/2

64.0
102.0

194
259

229
229

210
267

29.0
46.3

6
6

C3000K4D
C5000K4D

Primary: 550/575/600
Secondary: 110/115/120
1000
1500
2000
3000
5000

5-3/8
5-11/16
5-11/16
7-5/8
10-3/16

6-3/8
6-3/4
6-3/4
9
9

Primary: 380/400/415
Secondary: 110 x 220
1000
1500
2000
3000
5000


5-11/16
5-11/16
5-11/16
7-5/8
10-3/16

6-3/4
6-3/4
6-3/4
9
9

See Page 44-49 and for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

For other ratings or styles not shown, refer
to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-52

April 2009

Type MTK
Table 44-59. Type MTK — Product Selection
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 240 x 480 with Jumpers
Secondary: 120 x 240 with Jumpers, Secondary Fuse Clips Not Applicable
1000
1500
2000

4-7/16
5-11/16
5-3/4

5-1/4
6-3/4
6-3/4

7-7/8
7-1/4
8

26.4
31.0
40.0

113
144
146

133
171
171

200
184
203

12.0
14.1
18.2

11
11
11

C1000K2CXX
C1500K2CXX
C2000K2CXX

3000
5000

7-5/8
7-5/8

9
9

7-1/2
9-1/4

56.0
85.5

194
194

229
229

191
235

25.5
28.9

11
11

C3000K2CXX
C5000K2CXX

6-3/4
8-3/4

19.0
26.4

114
114

133
133

171
222

8.6
12.0

3
3

C0750K1B
C1000K1B

26.5
38.5
52.0

146
146
146

171
171
171

165
200
233

12.0
17.5
23.6

8
8
8

C1000K6U
C1500K6U
C2000K6U

68.0
105.0

197
248

229
229

191
267

30.9
47.7

8
8

C3000K6U
C5000K6U

Primary: 120 x 240 with Jumpers
Secondary: 24
750
1000

4-1/2
4-1/2

5-1/4
5-1/4

Primary: 240/416/480/600, 230/400/460/575, 220/380/440/550, 208/500
Secondary: 99/120/130, 95/115/125, 91/110/120, 85/100/110
1000
1500
2000

5-3/4
5-3/4
5-3/4

6-3/4
6-3/4
6-3/4

3000
5000

7-3/4
9-7/8

9
9



6-1/2
7-7/8
9-3/16
7-1/2
10-1/2

See Page 44-49 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

44

For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-53
Industrial Control Transformers
April 2009

CE Marked

CE Marked

Features, Benefits
and Functions
Type MTE
■
■
■
■
■

Terminal Type A

Application Description
Transformers provide stepped down
voltages to machine tool control devices
enabling control circuits to be isolated
from all power and lighting circuits.
This allows the use of grounded or
ungrounded circuits that are independent of the power or lighting grounds;
greater safety is afforded the operator.
The control transformer line is particularly adaptable on applications where
compact construction is demanded.

■

■
■
■
■
■
■

CE marked units comply with IEC
EN-61558-2.
UL listed.
CSA certified.
Epoxy encapsulated coil design.
Copper magnet wire for high
quality, efficient operation.
Laminations of high quality silicon
steel to minimize core losses and
optimize performance.
Molded-in terminals.
50/60 Hz operation.
55°C rise, class 105 insulation.
Performance meets/exceeds
requirements of ANSI/NEMA ST-1.
Regulation exceeds ANSI/NEMA
requirements for all ratings.
Non-short circuit proof transformer,
isolation type.

Finger-Safe Terminal Covers (Optional)
■
■

Fits CE marked designs 50 – 750 VA.
Fits MTE designs 25 – 750 VA.

Table 44-60. Finger-Safe Terminal Covers
Description

Catalog Price
Number U.S. $

4 Terminal Transformers
6 Terminal Transformers

FSK4
FSK6

Finger-Safe Terminal Covers — FSK4

Type MTK
■
■
■
■
■
■
■
■
■
■

CE marked units comply with IEC
EN-61558-2.
UL listed.
CSA certified.
Epoxy resin-impregnated coil design.
Copper magnet wire for high
quality, efficient operation.
50/60 Hz operation.
115°C rise, 180°C insulation system.
Performance meets/exceeds
requirements of ANSI/NEMA ST-1.
Regulation exceeds ANSI/NEMA
requirements for all ratings.
500 – 5000 VA ratings.

Standards and Certifications
Industry Standards

44

Finger-Safe Terminal Covers — FSK6

Finger-Safe Primary Fuse Block Covers
■

Fits 2-pole primary fuse blocks on
MTE designs.

Table 44-61. Finger-Safe Primary Fuse
Block Covers
Description

Catalog
Number

Price
U.S. $

Primary Fuse Block Covers FSKFB

All Cutler-Hammer dry-type distribution
and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI, and IEEE Standards. All 600 volt
class transformers are UL listed unless
otherwise noted.

Options and Accessories
Protection Index IP00
When terminal covers are installed on
primary and secondary, and fuse block
covers are used, the Protection Index
is IP20.

Finger-Safe Primary Fuse Block Covers

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-54

April 2009

CE Marked

Product Specifications

Wiring Diagrams

Overload Capability
Short-term overload is designed into
transformers as required by ANSI.
Basically, dry-type distribution transformers will deliver 200% nameplate
load for one-half hour; 150% load for
one-hour; and 125% load for four-hours
without being damaged provided that
a constant 50% load precedes and
follows the overload. See ANSI
C57.96-01.250 for additional limitations.
Continuous overload capacity is not
deliberately designed into a transformer because the design objective is
to be within the allowed winding temperature rise with nameplate loading.

Figure 44-39. Diagram 1
Figure 44-42. Diagram 4

Insulation System and Temperature Rise
Industry standards classify insulation
systems and rise as shown below:
Table 44-62. Insulation System Classification

44

Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

Figure 44-40. Diagram 2

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

Figure 44-43. Diagram 5

Series-Multiple Windings
Series-multiple windings consist of
2 similar coils in each winding which
can be connected in series or parallel
(multiple). Transformers with seriesmultiple windings are designated with
an “X” or “/” between the voltage
ratings, such as voltages of “120/240”
or “240 X 480.” If the series-multiple
winding is designated by an “X,” the
winding can be connected only for a
series or parallel. With the “/” designation, a mid-point also becomes available in addition to the series or parallel
connection. As an example, a 120 X
240 winding can be connected for
either 120 (parallel) or 240 (series), but
a 120/240 winding can be connected
for 120 (parallel), or 240 (series), or 240
with a 120 mid-point.

Figure 44-41. Diagram 3

Figure 44-44. Diagram 6

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-55
Industrial Control Transformers
April 2009

CE Marked

Wiring Diagrams

H3

X4

X2

H2

H4

X3

X1

X3

X4 X2 X3 X1

H5

0V

380,400,416 V

220,230,240 V

H4

110,115,120 V

H1

440,460,480 V

H1 H3 H2 H4

H3

23/24/25

H1 H3 H2 H4

H2

0V

480 V

550,575,600 V

H1

240 V

X2

X1

X4 X2 X3 X1

Figure 44-45. Diagram 7

Figure 44-52. Diagram 14
120 V

240 V
H6
0V

208 V

H5

230 V

H4

400 V

H3

230 V

115 V

H2

24 V

600 V
575 V
550 V

0V

H1

575 V

Figure 44-49. Diagram 11

H2
460 V

H1

Figure 44-46. Diagram 8
X4

X3

H5

H6
0V

208 V

230 V

X1

Figure 44-48. Diagram 10

For more information visit: www.eaton.com

115 V

115 V
X2

Figure 44-54. Diagram 16

Figure 44-51. Diagram 13

CA08102001E

0V

0V
X4

X2

H4

H2

Figure 44-47. Diagram 9

24 V
23 V
22 V

H3
400 V

H2

575 V

Figure 44-50. Diagram 12
420 V
400 V
380 V

44

X1

X1
H1

H1

X2

Figure 44-53. Diagram 15

460 V

X2

24 V
23 V
22 V

X3

X1

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-56

April 2009

CE Marked

Product Selection
Additional Product Selection information begins on Page 44-63.
Table 44-63. Type MTE CE Marked IP00
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 240 x 480, 230 x 460, 220 x 440 with Jumpers
Secondary: 120/115/110
50
75
100
150

3
3-1/4
3-1/2
4

3
3-3/8
3-3/4
4-1/2

3-3/8
3-3/8
3-3/8
3-3/4

3.5
4.8
5.9
8.5

76
83
89
102

76
86
95
114

86
86
86
95

1.6
2.2
2.7
3.9

1
1
1
1

CE0050E2ACE
CE0075E2ACE
CE0100E2ACE
CE0150E2ACE

200
250
300

4
4
4

4-1/2
4-1/2
4-1/2

3-3/4
4
4-3/8

10.6
11.3
13.2

102
102
102

114
114
114

95
102
111

4.8
5.1
6.0

1
1
1

CE0200E2ACE
CE0250E2ACE
CE0300E2ACE

350
500
750

4-1/2
4-1/2
4-1/2

5-1/4
5-1/4
5-1/4

4-7/8
5-1/8
7

14.9
21.0
29.8

114
114
114

133
133
133

124
130
178

6.8
9.5
13.5

1
1
1

CE0350E2ACE
CE0500E2ACE
CE0750E2ACE

Primary: 240 x 480 with Jumpers
Secondary: 24

44

50
75
100
150

3
3-1/4
3-1/2
4

3
3-3/8
3-3/4
4-1/2

3-3/8
3-3/8
3-3/8
4

3.4
4.2
5.9
8.5

76
83
89
102

76
86
95
114

86
86
86
102

1.5
1.9
2.7
3.9

2
2
2
2

CE0050E2BCE
CE0075E2BCE
CE0100E2BCE
CE0150E2BCE

200
250
300

4
4
4

4-1/2
4-1/2
4-1/2

3-3/4
4
4-3/8

10.6
11.3
13.2

102
102
102

114
114
114

95
102
111

4.5
5.1
6.0

2
2
2

CE0200E2BCE
CE0250E2BCE
CE0300E2BCE

350
500
750

4-1/2
4-1/2
5

5-1/4
5-1/4
5-1/4

4-1/2
5-1/8
7

14.9
19.2
28.1

114
114
127

133
133
133

114
130
178

6.8
8.7
12.8

2
2
2

CE0350E2BCE
CE0500E2BCE
CE0750E2BCE

Primary: 120 x 240 with Jumpers
Secondary: 24
50
75
100
150

3
3-1/4
3-1/2
4

3
3-3/8
3-3/4
4-1/2

3-3/8
3-3/8
3-3/8
3-3/4

3.4
4.2
5.9
8.5

76
83
89
102

76
86
95
114

86
86
86
95

1.5
1.9
2.7
3.9

3
3
3
3

CE0050E1BCE
CE0075E1BCE
CE0100E1BCE
CE0150E1BCE

200
250
300

4
4
4

4-1/2
4-1/2
4-1/2

3-3/4
4
4-3/8

10.6
11.3
13.2

102
102
102

114
114
114

95
102
111

4.5
5.1
6.0

3
3
3

CE0200E1BCE
CE0250E1BCE
CE0300E1BCE

350
500
750

4-1/2
4-1/2
4-1/2

5-1/4
5-1/4
5-1/4

4-1/2
5-1/8
7

14.9
19.2
29.8

114
114
114

133
133
133

114
130
178

6.8
8.7
13.5

3
3
3

CE0350E1BCE
CE0500E1BCE
CE0750E1BCE

Primary: 550/575/600
Secondary: 110/115/120
50
75
100
150

3
3-1/4
3-1/2
4

3
3-3/8
3-3/4
4-1/2

3-3/8
3-3/8
3-3/8
3-3/4

3.5
4.8
5.9
8.5

76
83
89
102

76
86
95
114

86
86
86
95

1.6
2.2
2.7
3.9

10
10
10
10

CE0050E4CCE
CE0075E4CCE
CE0100E4CCE
CE0150E4CCE

200
250
300

4
4
4

4-1/2
4-1/2
4-1/2

3-3/4
4
4-3/8

10.6
11.3
13.2

102
102
102

114
114
114

95
102
111

4.8
5.1
6.0

10
10
10

CE0200E4CCE
CE0250E4CCE
CE0300E4CCE

350
500
750

4-1/2
4-1/2
4-1/2

5-1/4
5-1/4
5-1/4

4-1/2
5-1/8
7

14.9
21.0
29.8

114
114
114

133
133
133

114
130
178

6.8
9.5
13.5

10
10
10

CE0350E4CCE
CE0500E4CCE
CE0750E4CCE



See Pages 44-54 and 44-55 for Wiring Diagrams.

Note: Transformers are designed to operate in a maximum ambient of 40°C.
Note: Contact your local Eaton sales office for availability on additional CE Marked control transformers.

For other ratings or styles not shown, refer
to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-57
Industrial Control Transformers
April 2009

CE Marked
Table 44-64. Type MTE CE Marked IP00
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Wiring
Diagram 

Style
Number

Price
U.S. $

Primary: 380/400/415
Secondary: 110 x 220 with Jumpers
50
75
100
150

3
3-1/2
3-1/2
4

3
3-3/8
3-3/4
4-1/2

3-3/8
3-3/8
3-3/8
3-3/4

3.5
4.8
5.9
8.5

76
89
89
102

76
86
95
114

86
86
86
95

1.6
2.2
2.7
3.9

6
6
6
6

CE0050E4DCE
CE0075E4DCE
CE0100E4DCE
CE0150E4DCE

200
250
300

4
4
4

4-1/2
4-1/2
4-1/2

3-3/4
4
4-3/8

10.6
11.3
13.2

102
102
102

114
114
114

95
102
111

4.8
5.1
6.0

6
6
6

CE0200E4DCE
CE0250E4DCE
CE0300E4DCE

350
500
750

4
4-1/2
4-1/2

4-1/2
5-1/4
5-1/4

4-3/4
5-1/8
7

15.2
21.0
29.8

102
114
114

114
133
133

121
130
178

6.9
9.5
13.5

6
6
6

CE0350E4DCE
CE0500E4DCE
CE0750E4DCE

Primary: 200/220/440, 208/230/460, 240/480
Secondary: 23/110, 24/115, 25/120
50
75
100

3-1/4
3-1/2
3-1/2

3-3/8
3-3/4
3-3/4

3-3/8
3-3/8
3-5/8

4.2
5.9
7.9

83
89
89

86
95
95

86
86
92

1.9
2.7
3.6

7
7
7

CE0050E5ECE
CE0075E5ECE
CE0100E5ECE

150
200
250

4
4
4

4-1/2
4-1/2
4-1/2

3-3/4
4-3/8
4-3/4

10.0
12.8
15.2

102
102
102

114
114
114

95
111
121

4.5
5.8
6.9

7
7
7

CE0150E5ECE
CE0200E5ECE
CE0250E5ECE

300
350
500

4-1/2
4-1/2
4-1/2

5-1/4
5-1/4
5-1/4

4-7/8
4-7/8
5-5/8

16.8
19.2
27.0

114
114
114

133
133
133

124
124
143

7.6
8.7
12.3

7
7
7

CE0300E5ECE
CE0350E5ECE
CE0500E5ECE



See Pages 44-54 and 44-55 for Wiring Diagrams.

Note: Transformers are designed to operate in a maximum ambient of 40°C.
Note: Contact your local Eaton sales office for availability on additional CE Marked control transformers.

44

For other ratings or styles not shown, refer
to Eaton.

CA08102001E

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-58

April 2009

CE Marked

Factory Mounted Finger-Safe Terminal Covers

Terminal Type A

Terminal Type B

Terminal Type C

Table 44-65. Type MTK CE Marked with Factory Mounted Finger-Safe Terminal Covers IP20
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Terminal
Type

Wiring
Style
Diagram  Number

Price
U.S. $

Primary: 240 x 480, 230 x 460, 220 x 440 with Jumpers
Secondary: 120/115/110
250
300
350
500

4
4
4
4

4-1/2
4-1/2
4-1/2
4-1/2

4-5/16
4-7/8
5-3/16
5-5/8

8.8
11.0
11.2
14.8

102
102
102
102

114
114
114
114

110
124
132
143

4.0
5.0
5.1
6.7

A
A
A
A

1
1
1
1

CE0250K2ACEFS
CE0300K2ACEFS
CE0350K2ACEFS
CE0500K2ACEFS

750
1000
1500

4-1/2
5-1/2
6

5-1/4
6-3/8
6-3/4

5-15/16
6-5/8
7-5/16

18.0
26.3
40.0

114
140
152

133
162
172

151
168
186

8.2
11.9
18.1

A
A
C

1
1
1

CE0750K2ACEFS
CE1000K2ACEFS
CE1500K2ACEFS

2000
3000
5000

6
8
8

6-3/4
9
9

8-1/8
8-1/16
10

45.1
65.2
104.8

152
200
200

172
229
229

203
202
250

20.5
29.6
47.5

C
C
C

1
1
1

CE2000K2ACEFS
CE3000K2ACEFS
CE5000K2ACEFS

Primary: 240 x 480 with Jumpers
Secondary: 24

44

250
300
350

5-5/8
5-5/8
5-5/8

4-1/2
4-1/2
4-1/2

3-1/4
3-5/8
4-3/16

8.2
9.5
12.2

143
143
143

114
114
114

83
92
106

3.7
4.3
5.5

C
C
C

2
2
2

CE0250K2BCEFS
CE0300K2BCEFS
CE0350K2BCEFS

500
750
1000

5-5/8
6-1/2
6

4-1/2
5-1/4
6-3/8

4-11/16
5-15/16
7

14.4
19.5
26.2

143
165
152

114
133
162

119
151
178

6.5
8.9
11.9

C
C
C

2
2
2

CE0500K2BCEFS
CE0750K2BCEFS
CE1000K2BCEFS

Primary: 120 x 240 with Jumpers
Secondary: 24
250
300
350

5-5/8
5-5/8
5-5/8

4-1/2
4-1/2
4-1/2

3-1/4
3-5/8
4-3/16

8.3
9.3
12.0

143
143
143

114
114
114

83
92
106

3.8
4.2
5.4

C
C
C

3
3
3

CE0250K1BCEFS
CE0300K1BCEFS
CE0350K1BCEFS

500
750
1000

5-5/8
6-1/2
6

4-1/2
5-1/4
6-3/8

4-13/16
5-15/16
7

14.4
19.5
25.2

143
165
152

114
133
162

122
151
178

6.5
8.9
11.4

C
C
C

3
3
3

CE0500K1BCEFS
CE0750K1BCEFS
CE1000K1BCEFS

Primary: 200/220/440, 208/230/460, 240/480
Secondary: 23/110, 24/115, 25/120
250
300
350

3-7/8
3-7/8
3-7/8

4-1/2
4-1/2
4-1/2

4-7/16
4-3/4
5-3/16

12.5
14.0
15.3

98
98
98

114
114
114

113
121
140

5.7
6.3
6.9

B
B
B

7
7
7

CE0250K5ECEFS
CE0300K5ECEFS
CE0350K5ECEFS

500
750
1000

5-1/16
7-3/16
6

5-1/4
6-3/8
6-3/8

6-1/4
5-13/16
7-1/16

20.8
29.8
30.2

129
183
152

133
162
162

159
148
179

9.4
13.5
13.7

B
C
C

7
7
7

CE0500K5ECEFS
CE0750K5ECEFS
CE1000K5ECEFS

Primary: 220/380/440/550, 230/400/460/575, 240/416/480/600
Secondary: 23/110, 24/115, 25/120
250
300
350

3 7/8
3-7/8
4-7/16

4 1/2
4-1/2
5-1/4

5 3/8
5-11/16
5-1/2

14.3
15.8
16.5

98
98
113

114
114
133

137
144
140

6.5
7.2
7.5

B
B
B

14
14
14

CE0250K2UCEFS
CE0300K2UCEFS
CE0350K2UCEFS

500
750
1000

5-1/16
7-3/16
6

5-1/4
6-3/8
6-3/8

6-3/16
5-11/16
8-1/8

20.5
28.8
39.4

129
183
152

133
162
162

157
144
207

9.3
13.1
17.9

B
C
C

14
14
14

CE0500K2UCEFS
CE0750K2UCEFS
CE1000K2UCEFS



See Pages 44-54 and 44-55 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.
Note: Contact your local Eaton sales office for availability on additional CE Marked control transformers.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-59
Industrial Control Transformers
April 2009

CE Marked
Table 44-66. Type MTK CE Marked with Factory Mounted Finger-Safe Terminal Covers IP20
VA

Dimensions (Inches)
Height

Width

Depth

Weight
Lbs.

Dimensions (mm)
Height

Width

Depth

Weight
kg

Terminal
Type

Wiring
Style
Diagram  Number

Pricing
U.S. $

Primary: 208/230/400/460/575
Secondary: 24 /115/230
250
300
350
500

3-7/8
3-7/8
4-7/16
4-7/16

4-1/2
4-1/2
5-1/4
5-1/4

5-1/2
6-1/16
5-3/4
7-5/16

14.9
17.4
17.8
26.6

98
98
113
113

114
114
133
133

140
154
146
186

6.8
7.9
8.1
12.1

B
B
B
B

15
15
15
15

CE0250K2VCEFS
CE0300K2VCEFS
CE0350K2VCEFS
CE0500K2VCEFS

750
1000
1500

5-15/16
6-1/4
6

6-3/8
6-3/4
6-3/4

6-3/16
7-3/4
7-3/4

32.5
44.0
45.4

151
159
152

162
172
172

157
199
199

14.7
20.0
20.6

B
C
C

15
15
16

CE0750K2VCEFS
CE1000K2VCEFS
CE1500K2WCEFS

2000
3000
5000

7-5/8
7-5/8
7-5/8

9
9
9

7-5/8
8-3/4
10-7/16

58.6
92.9
127.4

194
194
194

229
229
229

194
222
265

26.6
42.1
57.8

C
C
C

16
16
16

CE2000K2WCEFS
CE3000K2WCEFS
CE5000K2WCEFS

Primary: 240/416/480/600, 230/400/460/575, 220/380/440/550, 208/500
Secondary: 99/120/130, 95/115/125, 91/110/120, 85/100/110
250
300
350

4
4
4

4-1/2
4-1/2
4-1/2

5-1/16
5-1/2
5-1/2

11.4
13.6
14.2

102
102
102

114
114
114

135
140
140

5.2
6.2
6.4

A
A
A

8
8
8

CE0250K6UCEFS
CE0300K6UCEFS
CE0350K6UCEFS

500
750
1000

4-1/2
4-1/2
5-1/2

5-1/4
5-1/4
6-3/8

5-5/8
5-5/8
7

17.4
27.5
27.9

114
114
140

133
133
162

143
187
178

7.9
12.5
12.6

A
A
A

8
8
8

CE0500K6UCEFS
CE0750K6UCEFS
CE1000K6UCEFS

1500
2000
3000

6
8
7-5/8

6-3/4
9
9

7-3/4
7-5/8
8-9/16

43.1
56.0
76.2

152
203
194

172
229
229

199
194
217

19.5
25.4
34.6

A
B
B

8
8
8

CE1500K6UCEFS
CE2000K6UCEFS
CE3000K6UCEFS




See Pages 44-54 and 44-55 for Wiring Diagrams.
24 volt secondary only available through 1000 VA.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.
Note: Contact your local Eaton sales office for availability on additional CE Marked control transformers.

44

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-60

April 2009

CE Marked
Table 44-67. Acceptable Rating of Primary Overcurrent Protection for CE Marked Control Transformers
Fuses 10 x 38 mm (13/32” x 1-1/2”) Time-lag (IEC 269)
Sec. Voltage 50

75

100

150

200

250

300

350

500

750

115
120
200

2.0
2.0
1.0

2.0
2.0
2.0

4.0
4.0
2.0

4.0
4.0
4.0

6.0
6.0
4.0

6.0
6.0
4.0

8.0
8.0
4.0

10.0
10.0
6.0

12.0
12.0
8.0

20.0
20.0
12.0

208
220
230

1.0
1.0
1.0

2.0
1.0
1.0

2.0
2.0
2.0

4.0
4.0
4.0

4.0
4.0
4.0

4.0
4.0
4.0

4.0
4.0
4.0

6.0
6.0
6.0

8.0
6.0
6.0

12.0
10.0
10.0

240
277
380

1.0
.5
.5

1.0
1.0
1.0

2.0
1.0
1.0

4.0
2.0
2.0

4.0
4.0
2.0

4.0
4.0
4.0

4.0
4.0
4.0

4.0
4.0
4.0

6.0
6.0
6.0

10.0
8.0
6.0

400
415
440

.5
.5
.5

.5
.5
.5

1.0
1.0
1.0

2.0
1.0
1.0

2.0
2.0
2.0

4.0
4.0
2.0

4.0
4.0
4.0

4.0
4.0
4.0

4.0
4.0
4.0

6.0
6.0
6.0

460
480
550

.5
.5
.5

.5
.5
.5

1.0
.5
.5

1.0
1.0
1.0

2.0
2.0
1.0

2.0
2.0
2.0

4.0
4.0
2.0

4.0
4.0
4.0

4.0
4.0
4.0

6.0
6.0
4.0

575
600

.5
.5

.5
.5

.5
.5

1.0
1.0

1.0
2.0

2.0
2.0

2.0
2.0

4.0
4.0

4.0
4.0

4.0
4.0

Table 44-68. Acceptable Maximum Rating of Secondary Overcurrent Protection
Miniature Fuses 5 x 20 mm Time-lag (IEC 127-2/III)
Sec. Voltage 50

44

75

100

150

200

250

300

350

500

750

23
24
25

2.50
2.50
2.50

4.00
4.00
4.00

5.00
5.00
5.00

8.00
8.00
8.00

10.0
10.0
10.0

12.00
12.00
12.00

16.00
16.00
16.00

16.00
16.00
16.00

25.00
25.00
25.00

—
32.00
32.00

90
95
100

.63
.63
.50

1.00
.80
.80

1.25
1.25
1.00

2.00
1.60
1.60

2.50
2.50
2.00

3.15
3.15
2.50

4.00
4.00
3.15

4.00
4.00
4.00

6.30
6.30
5.00

10.00
8.00
8.00

110
115
120

.50
.50
.50

.80
.80
.63

1.00
1.00
1.00

1.60
1.60
1.25

2.00
2.00
2.00

2.50
2.50
2.50

3.15
3.15
2.50

4.00
3.15
3.15

5.00
5.00
5.00

8.00
8.00
6.30

220
230
240

.25
.25
.25

.40
.40
.315

.50
.50
.50

.80
.80
.63

1.00
1.00
1.00

1.25
1.25
1.25

1.60
1.60
1.25

1.60
1.60
1.60

2.50
2.50
2.50

4.00
4.00
3.15

Note: For values over 6.3A use 10 x 38 mm time-lag (IEC - 269-3-1). Ta = 40°C Control Type.

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-61
Industrial Control Transformers
April 2009

Type AP

Type AP

Standards and Certifications
Industry Standards
All Cutler-Hammer dry-type distribution
and control transformers by Eaton
Corporation are built and tested in
accordance with applicable NEMA,
ANSI and IEEE Standards.

Product Specifications

Product Description
■

Sand and Resin encapsulated
designs.

Application Description
Transformers provide stepped down
voltages to machine tool control
devices enabling control circuits to be
isolated from all power and lighting
circuits. This allows the use of
grounded or ungrounded circuits that
are independent of the power or lighting grounds; greater safety is afforded
the operator. The control transformer
line is particularly adaptable on applications where compact construction
is demanded.

Features, Benefits
and Functions
■
■
■
■
■
■
■
■

UL recognized.
Resin encapsulated.
60 Hz operation.
115°C winding rise.
Convenient screw-type terminal
board.
Bottom or side/wall mounting
designs.
Performance meets/exceeds
requirements of ANSI/NEMA ST-1.
Regulation exceeds ANSI/NEMA
requirements for all ratings.

CA08102001E

All Cutler-Hammer 600 volt class general purpose dry-type distribution
transformers are designed to meet
NEMA ST-20 levels.

Winding Terminations
Eaton recommends external cables be
rated 90ºC (sized at 75°C ampacity) for
encapsulated designs.

Series-Multiple Windings

Overload Capability

Type AP Transformer

Sound Levels

Short-term overload is designed into
transformers as required by ANSI.
dry-type distribution transformers
will deliver 200% nameplate load for
one-half hour; 150% load for one-hour;
and 125% load for four-hours without
being damaged provided that a constant 50% load precedes and follows
the overload. See ANSI C57.96-01.250
for additional limitations.
Continuous overload capacity is not
deliberately designed into a transformer because the design objective is
to be within the allowed winding temperature rise with nameplate loading.

Insulation System and Temperature Rise
Industry standards classify insulation
systems and rise as shown below:
Table 44-69. Insulation System Classification
Ambient

+
Winding
Rise

+
Hot
Spot

=
Temp.
Class

40°C
40°C
40°C
40°C

55°C
80°C
115°C
150°C

10°C
30°C
30°C
30°C

105°C
150°C
185°C
220°C

The design life of transformers having
different insulation systems is the
same — the lower temperature systems
are designed for the same life as the
higher temperature systems.

For more information visit: www.eaton.com

Series-multiple windings consist of
2 similar coils in each winding which
can be connected in series or parallel
(multiple). Transformers with seriesmultiple windings are designated with
an “X” or “/” between the voltage
ratings, such as voltages of “120/240”
or “240 X 480.” If the series-multiple
winding is designated by an “X,” the
winding can be connected only for a
series or parallel. With the “/” designation, a mid-point also becomes available in addition to the series or parallel
connection. As an example, a 120 X
240 winding can be connected for
either 120 (parallel) or 240 (series), but
a 120/240 winding can be connected
for 120 (parallel), or 240 (series), or 240
with a 120 mid-point.

44

Distribution & Control Transformers and Power Supplies
Industrial Control Transformers

44-62

April 2009

Type AP

Product Selection
Additional Product Selection information begins on Page 44-63.
Table 44-70. Type AP
kVA

Mounting Dimensions (Inches)
Height

Width

Depth

Weight Dimensions (mm)
Lbs.
Height
Width
Depth

Weight
kg

Frame Wiring
Style
Diagram  Number

Price
U.S. $

240/480 Volts to 120/240 Volts, 60 Hz
3
5
7.5
10
15

Bottom
Bottom
Bottom
Bottom
Bottom

8-5/16
10-3/4
10-3/4
10-3/4
12

9-9/16
10-3/4
10-3/4
10-3/4
13-3/16

8-13/16
8 -11/16
10-3/16
11-3/8
10-7/16

65
104
129
148
197

227
273
273
273
305

243
273
273
273
335

224
221
259
289
265

29.5
47.2
58.6
67.2
89.4

FR133
FR99
FR100
FR101
FR134

5
5
5
5
5

C0003P7GB
C0005P7GB
C0007P7GB
C0010P7GB
C0015P7GB

3
5
7.5
10
15

Side/Wall
Side/Wall
Side/Wall
Side/Wall
Side/Wall

9-3/4
11-5/8
11-5/8
11-5/8
12-7/8

8-13/16
8-11/16
10-13/16
11-3/8
10-7/16

9-9/16
10-3/4
10-3/4
10-3/4
13-3/16

65
104
129
148
197

248
295
295
295
327

224
221
275
289
265

243
273
273
273
335

29.5
47.2
58.6
67.2
89.4

FR292
FR256
FR257
FR258
FR259

5
5
5
5
5

C0003P7GS
C0005P7GS
C0007P7GS
C0010P7GS
C0015P7GS



See Page 44-34 for Wiring Diagrams.

Note: For additional information, refer to the Cutler-Hammer Industrial Control Transformer Binder B1228A.

44

For other ratings or styles not shown, or for
special enclosure types (including stainless
steel), refer to Eaton.

For more information visit: www.eaton.com

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

Distribution & Control Transformers and Power Supplies 44-63
General Purpose & Industrial Control Transformers
April 2009

Technical Data and Specifications

Product Selection

Table 44-71. Single-Phase ac Motors
Horsepower

Full Load Amperes

Single-Phase Transformers

115 Volts

How to Select Single-Phase Units
1. Determine the primary (source)
voltage — the voltage presently
available.

— If the load rating is given in
amperes, determine the load kVA
from the below chart. To determine
kVA when volts and amperes are
known, use the formula:
kVA = Volts x Amperes
1000
— If the load is an ac motor, determine the minimum transformer
kVA from the chart at the right.
— Select a transformer rating
equal to or greater than the
load kVA.
4. Define tap arrangements needed.
5. Define temperature rise.
Using the above procedure, select
the transformer from the listings in
this catalog.

CA08102001E

220 Volts

230 Volts

Minimum
Transformer kVA 

1/6
1/4
1/3

4.4
5.8
7.2

2.4
3.2
4.0

2.3
3.0
3.8

2.2
2.9
3.6

.53
.70
.87

1/2
3/4

5.4
7.6
8.8

5.1
7.2
8.4

4.9
6.9
8

1.18
1.66
1.92

1

9.8
13.8
16

1-1/2
2
3

20
24
34

11.0
13.2
18.7

10.4
12.5
17.8

10
12
17

2.40
2.88
4.10

5
7-1/2
10

56
80
100

30.8
44
55

29.3
42
52

28
40
50

6.72
9.6
12.0

2. Determine the secondary (load)
voltage — the voltage needed at
the load.
3. Determine the kVA load:
— If the load is defined in kVA, a
transformer can be selected from
the tabulated data.

208 Volts



If motors are started more than once per hour, increase minimum transformer kVA by 20%.

Note: When motor service factor is greater than 1, increase full load amperes proportionally.
Example: If service factor is 1.15, increase above ampere values by 15%.

Table 44-72. Full Load Current in Amperes — Single-Phase Circuits
kVA

Voltage
120

2400

4160

2.0
4.2
6.3

1.2
2.4
3.6

1.1
2.3
3.4

1.0
2.1
3.1

.9
1.8
2.7

.5
1.0
1.6

.4
.8
1.3

.10
.21
.31

.06
.12
.18

1
1.5
2

8.3
12.5
16.7

4.8
7.2
9.6

4.5
6.8
9.1

4.2
6.2
8.3

3.6
5.4
7.2

2.1
3.1
4.2

1.7
2.5
3.3

.42
.63
.83

.24
.36
.48

3
5
7.5

25
41
62

14.4
24.0
36

13.6
22.7
34

12.5
20.8
31

10.8
18.0
27

6.2
10.4
15.6

5.0
8.3
12.5

1.2
2.1
3.1

.72
1.2
1.8

20.8
31
52

16.7
25
41

4.2
6.2
10.4

2.4
3.6
6.0

.25
.50
.75

208

220

240

277

480

600

10
15
25

83
125
208

48
72
120

45
68
114

41
62
104

36
54
90

37.5
50
75

312
416
625

180
240
360

170
227
341

156
208
312

135
180
270

78
104
156

62
83
125

15.6
20.8
31.3

9.0
12.0
18.0

833
1391

480
802

455
759

416
695

361
602

208
347

166
278

41.7
69.6

24.0
40.1

100
167

For more information visit: www.eaton.com

44

44-64

Distribution & Control Transformers and Power Supplies
General Purpose & Industrial Control Transformers
April 2009

Technical Data and Specifications

Three-Phase Transformers
How to Select Three-Phase Units

Table 44-73. Three-Phase ac Motors
Horsepower

1. Determine the primary (source)
voltage — the voltage presently
available.

— If the load is an ac motor, determine the minimum transformer
kVA from the chart at the right.

44

— Select a transformer rating
equal to or greater than the
load kVA.

Using the above procedure, select
the transformer from the listings in
this catalog.

460 Volts

575 Volts

Minimum
Transformer kVA 

2.0
2.8
3.6

1.2
1.7
2.2

1.0
1.4
1.8

.8
1.1
1.4

.9
1.2
1.5

1-1/2
2
3

5.7
7.5
10.7

5.2
6.8
9.6

3.1
4.1
5.8

2.6
3.4
4.8

2.1
2.7
3.9

2.1
2.7
3.8

5
7-1/2
10

16.7
24
31

15.2
22
28

9.2
14
17

7.6
11
14

6.1
9
11

6.3
9.2
11.2

15
20
25

46
59
75

42
54
68

26
33
41

21
27
34

17
22
27

16.6
21.6
26.6

30
40
50

88
114
143

80
104
130

48
63
79

40
52
65

32
41
52

32.4
43.2
52

60
75
100

170
211
273

154
192
248

93
116
150

77
96
124

62
77
99

64
80
103

125
150
200

342
396
528

312
360
480

189
218
291

156
180
240

125
144
192

130
150
200

1



If motors are started more than once per hour, increase minimum transformer kVA by 20%.

Note: When motor service factor is greater than 1, increase full load amperes proportionally.
Example: If service factor is 1.15, increase above ampere values by 15%.

Table 44-74. Full Load Current in Amperes — Three-Phase Circuits
kVA

Voltage
208

4. Define tap arrangements needed.
5. Define temperature rise.

380 Volts

2.2
3.1
4.0

3. Determine the kVA load:
— If the load is defined in kVA, a
transformer can be selected from
the tabulated data.

kVA = Volts x Amperes x 1.732
1000

230 Volts

1/2
3/4

2. Determine the secondary (load)
voltage — the voltage needed at
the load.

— If the load rating is given in
amperes, determine the load kVA
from the below chart. To determine
kVA when volts and amperes are
known, use the formula:

Full Load Amperes
208 Volts

240

380

480

600

2400

4160

3
6
9

8.3
16.6
25

7.2
14.4
21.6

4.6
9.1
13.7

3.6
7.2
10.8

2.9
5.8
8.6

.72
1.4
2.2

.42
.83
1.2

15
22.5
30

41.7
62.4
83.4

36.1
54.1
72.3

22.8
34.2
45.6

18.0
27.1
36.1

14.4
21.6
28.9

3.6
5.4
7.2

2.1
3.1
4.2

57.0
68.4
76

45.2
54.2
60.1

36.1
43.4
48.1

9.0
10.8
12.0

5.2
6.3
6.9

37.5
45
50

104
124
139

90.3
108
120

75
112.5
150

208
312
416

180
270
360

114
171
228

90
135
180

72
108
144

18.0
27.1
36.1

10.4
15.6
20.8

225
300
500

624
832
1387

541
721
1202

342
456
760

270
360
601

216
288
481

54.2
72.2
120

31.3
41.6
69.4

750
1000

2084
2779

1806
2408

1140
1519

903
1204

723
963

180
241

For more information visit: www.eaton.com

104
139

CA08102001E

Distribution & Control Transformers and Power Supplies 44-65
Power Supplies
April 2009

PSG Series

Contents
Description

Page

Power Supply Selection Guide
PSG Series . . . . . . . . . . . . .
PSS Series . . . . . . . . . . . . .
ELC Series . . . . . . . . . . . . .
EZ Power Series . . . . . . . .
Sensor Power Supplies . .

44-65
44-71
44-77
44-80
44-81

Table 44-75. Power Supply Selection Guide
Power Supply
Series

Features

PSG

PSS

■ General purpose

■ 24V DC control for high

24V DC control
■ Rugged metal housing
■ DIN-rail mount
■ 150% current boost for
1 sec (outrush)
■ Single-phase
(85 – 264V AC/120 – 375V DC)
or 3-phase (320 – 575V AC/
450 – 800V DC) inputs
■ Class 1, Division 2 qualified
(February 2009)
■ Conformal coated
electronics

CA08102001E

ELC

■ Compact, low cost
start-up loads
24V DC control for
loads up to 2A
■ Peak current surge
■ Plastic enclosure
(boost/outrush) up to
can be DIN-rail or
6 times nominal current
panel mounted
■ Semi 47 approved
■ Class 1, Division 2
■ Long ride-through
qualified
capability
■ Single-phase
■ Pluggable terminal
(85 – 264V AC)
connections
input
■ Single-phase and 3-phase
inputs up to 600V AC

For more information visit: www.eaton.com

EZ Power Series

Sensor Power Supplies

■ Shallow-depth power

■ 27V DC supplies

supplies for 12V DC or
24V DC applications
■ Low-power output —
up to 1.25A
■ EZ Relay styling
provides optimal
panel aesthetics
■ Plastic enclosure can
be DIN-rail or panel
mounted (with
optional kit)
■ Class 1, Division 2
qualified
■ Single-phase
(85 – 264V AC) input

for tough sensor
applications
■ Rugged housings
with integrated
junction box for
mounting outside of
electrical enclosures
■ Advanced diagnostic
features

44

Distribution & Control Transformers and Power Supplies
Power Supplies

44-66

April 2009

PSG Series

PSG Series

Application Description
The PSG series is a line of generalpurpose power supplies for use in a
wide variety of industrial control applications. Applications include communication networks, sensors, PLCs, and
many other electrical systems.
Each model is equipped with a rugged
metal housing, heavy-duty screw
terminals, and a variety of protection
features, making the PSG one of the
most versatile industrial power supply
lines on the market.

Product Description
Eaton’s PSG Series of power supplies
is designed to be a high-performance,
high-quality line of products covering
a majority of 24V DC control applications. With global certifications, compact size, and an impressive operating
temperature range, the PSG series fits
a wide variety of applications at a
competitive price.

■
■

■
■

■
■

Features, Benefits
and Functions
Universal input voltages:
85 – 264V AC for single-phase units,
320 – 575V AC for 3-phase units.
■ Rugged aluminum housing stands
up to harsh environments.
■ Current surge (power boost) of
1.5 times nominal current for
1 sec. allows branch protection
and powering of high pick-up loads.
■ Wide operating temperature range:
-20°C to +75°C (derating above 50°C).
■

Adjustable DC voltage output.
LED indicating light for DC OK
simplifies troubleshooting.
Compact size, with common depth
and height across all models allows
for common panel depths and
family consistency.
MTBF up to 800,000 hours ensures
uptime and reliability.
Heavy duty screw terminals with
finger-safe protective cover allow
use of ring-lug terminals.
All-metal DIN-rail mounting
hardware.
Class 1, Division 2 hazardous
location rated (February 2009).

Standards and Certifications
UL/cUL Listed – UL 508.
CSA Certified (contact Eaton for
certification dates and status).
■ CE Marked.
■ RoHS Compliant.
■
■

Product Selection
Table 44-76. Product Selection
Description

Catalog Number

Power Supply – Single-phase 85 – 264V AC input, 24V DC / 2.5A output

PSG60E

Power Supply – 3-phase 320 – 575V AC input, 24V DC / 2.5A output

PSG60F

Power Supply – Single-phase 85 – 264V AC input, 24V DC / 5A output

PSG120E

Power Supply – 3-phase 320 – 575V AC input, 24V DC / 5A output

PSG120F

Power Supply – Single-phase 85 – 264V AC input, 24V DC / 10A output

PSG240E

Power Supply – 3-phase 320 – 575V AC input, 24V DC / 10A output

PSG240F

Power Supply – Single-phase 85 – 264V AC input, 24V DC / 20A output

PSG480E

Power Supply – 3-phase 320 – 575V AC input, 24V DC / 20A output

PSG480F

0

10 20

30 40 50 60

70 80 85

Ambient Temperature (°C)

Figure 44-55. Power Derating Curve Vertical
Mounting Position PSG60E

110
100
90
80
70
60
50
40
30
20
10
0
-20 -10

Price U.S. $

Load (%)

110
100
90
80
70
60
50
40
30
20
10
0
-20 -10

Load (%)

110
100
90
80
70
60
50
40
30
20
10
0
-20 -10

Load (%)

44

Eight models are offered, from 2.5A up
to 20A with both single and 3-phase
input voltage models available.

■

0

10 20

30 40 50 60

70 80 85

Ambient Temperature (°C)

Figure 44-56. Power Derating Curve Vertical
Mounting Position PSG60F, PSG120E,
PSG120F, PSG480E, PSG480F

0

10 20

30 40 50 60

70 80 85

Ambient Temperature (°C)

Figure 44-57. Power Derating Curve Vertical
Mounting Position PSG240E, PSG240F

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-67
Power Supplies
April 2009

PSG Series

Technical Data and Specifications
Table 44-77. PSG Technical Specifications
Capacity

PSG60E

PSG120E

PSG240E

PSG480E

PSG60F

PSG120F

PSG240F

PSG480F

60W

120W

240W

480W

60W

120W

240W

480W

Input
Nominal Voltage

100 – 240V AC

Voltage Range

85 – 264V AC (DC input range 120 – 375V DC)

3 x 400 – 500V AC

Frequency

320 – 575V AC (DC input range 450 – 800V DC)
47-63 Hz (0 Hz at DC input)

Nominal Current 

1.1A

1.4A

2.9A

5.7A

0.3A

0.5A

0.8A

Inrush Current Limitation 

30A

<80A

N/A

N/A

<30A

<30A

<40A

<50A

Mains Buffering @ Nominal
Load (Typ.) 

>20 ms

>35 ms

>20 ms

>20 ms

>30 ms

>35 ms

>35 ms

>20 ms

Turn-on Time

<2.5 sec

<1 sec

<1 sec

<1 sec

<2 sec

<1 sec

<1 sec

<1 sec

Internal Fuse

T3.15 AH/250V

T6.3AH/250V

F10H/250V

3.15AH/500V

External Fusing

6A, 10A, or 16A

10A or 16A

Leakage Current

<1 mA

<3.5 mA

<1 mA

<3.5 mA

<1 mA

1.6A

3 x circuit breakers 6A, 10A or 16A

Output
Nominal Output Voltage

24V DC +/- 2%

Adjustment Range

22 – 28V DC

Nominal Current

2.5A

5A

10A

20A

Startup With Capacitive Loads

Max. 8,000 F Max. 10,000 F

2.5A

5A

10A

20A

Max. Power Dissipation Idling/
Nominal Load Approx.

10 W

22.5 W

42.5 W

72 W

9W

18 W

36 W

72 W

Efficiency (@ 400V AC and
Nominal Values)

>85% typ

>84% typ

>84% typ

>86% typ

>86% @ 3 x 400V AC
>85% @ 3 x 500V AC

>87% @ 3 x 400V AC
>86% @ 3 x 500V AC

Current Surge (@ 24V DC)

3.75A

7.5A

15A

30A

3.75A

15A

Current Surge Time/Cycle

7.5A

30A

44

1 second (at 10-second intervals)

Residual Ripple/Peak Switching
(20 Mhz)

<50 mV/<240mVpp

Parallel Operation

With Oring Diode

Galvanic Isolation
Input/Output

4 kVAC (type test)/3 kVAC (routine test)

Input/Ground

1.5 kVAC (type test)/1.5 kVAC (routine test)

Output/Ground

1.5 kVAC (type test)/500V AC (routine test)

General/Physical Data
Housing Material

Aluminum (Al5052)

Signals

Green LED for DC OK

MTBF

>800,000 hrs

Dimensions (L)

121 mm

Dimensions (W)

32 mm

50 mm

85 mm

160 mm

70 mm

70 mm

85 mm

Dimensions (H)

120 mm

115 mm

118.5 mm

115 mm

118.5 mm

118.5 mm

120.5 mm

115 mm

Weight (kg)

0.37

0.54

1.04

1.8

0.56

0.72

0.77

1.71

Operating Temperature

>300,000 hrs

>500,000 hrs

Vibration (Operating)

-25°C to +85°C
<95% RH, non-condensing
10 to 150 Hz, 0.35 mm acc. 50 m/s/s, single amplitude (5 G max) for 90 min. in each X, Y, Z direction, in acc. with IEC 68-2-6

Pollution Degree
Climatic Class

160 mm

-20°C to +75°C (>50°C derating)

Storage Temperature
Operating Humidity

>300,000 hrs

2
3K3 according to EN 60721

Approvals/Certifications
UL/cUL Listed-UL508 (Industrial Control Equipment), cURus-UL60950-1, CSA, CE, IEC, EN, German Safety, RoHS

Safety & Protection
Transient Surge Voltage

Varistor

Surge Voltage Protection
Against Interal Surge

Yes

Safety Class
Shock


Class I with ground connection
30 G (300 m/s/s) in all directions according to IEC 68-2-27

Ratings for single-phase models are at 115V AC; 3-phase models are at 400V AC.

CA08102001E

For more information visit: www.eaton.com

44-68

Distribution & Control Transformers and Power Supplies
Power Supplies
April 2009

PSG Series

Dimensions
120.5 ±0.5
105.2 ±0.5

32.0 ±0.5
Catalog Number:
PSG60E
24V
2.5A

CAUTION
HOT SURFACE

Adjust
DC OK

121.0 ±0.5

SPEC LABEL

100-240V~1.5A
50-60Hz

Note: Dimensions are
for reference only.

5.0 ±0.2

Figure 44-58. PSG60E — Approximate Dimensions in mm
111.4 ±0.5
96.5 ±0.5

44
121.0 ±0.5
SPEC LABEL

Note: Dimensions are
for reference only.

6.6 ±0.1

70.0 ±0.5

Figure 44-59. PSG60F — Approximate Dimensions in mm
50.0 ±0.2
DC 24V 5A

Adjust
DC OK

121.0 ±0.2

AC 100-240V 2A
50-60 Hz

Note: Dimensions are
for reference only.

13.0
5.5

115.0 ±0.6

4.0

Figure 44-60. PSG120E — Approximate Dimensions in mm

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-69
Power Supplies
April 2009

PSG Series

Dimensions
111.3 ±0.5
96.4 ±0.5

Adjust
DC OK

121.0 ±0.5

6.6 ±0.1
SPEC LABEL

Note: Dimensions are
for reference only.

70.0 ±0.5

Figure 44-61. PSG120F — Approximate Dimensions in mm
118.5 ±0.5
105.2 ±0.5

44
CAUTION
HOT SURFACE

24V

10A

Adjust
DC OK

121.0 ±0.5

Catalog Number:
PSG240E

SPEC LABEL

5.0 ±0.2

100-240V~5A
50-60Hz

Note: Dimensions are
for reference only.

85.0 ±0.5

Figure 44-62. PSG240E — Approximate Dimensions in mm
120.5 ±0.5
105.2 ±0.5

CAUTION
HOT SURFACE

24V

10A

Adjust
DC OK

121.0 ±0.5

Catalog Number:
PSG240F

SPEC LABEL

5.0 ±0.2
3-Phase 400-500V~0.8A 50-60Hz

Note: Dimensions are
for reference only.

85.0 ±0.5

Figure 44-63. PSG240F — Approximate Dimensions in mm

CA08102001E

For more information visit: www.eaton.com

44-70

Distribution & Control Transformers and Power Supplies
Power Supplies
April 2009

PSG Series

Dimensions
160.0 ±0.5

121.0 ±0.5

7.1

Catalog Number:
PSG480E

6.6 ±0.1
N

L

Adjust

DC OK

100-240V~

24V

7A 50-60Hz

20A

96.6 ±0.5

Note: Dimensions are
for reference only.

111.4 ±0.5

Figure 44-64. PSG480E — Approximate Dimensions in mm
160.0 ±0.5

121.0 ±0.5

44

7.1

Catalog Number:
PSG480F

6.6 ±0.1
Adjust

DC OK

3-Phase 400-500V~1.4A 50-60Hz

24V

20A

96.6 ±0.5

Note: Dimensions are
for reference only.

111.4 ±0.5

Figure 44-65. PSG480F — Approximate Dimensions in mm

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-71
Power Supplies
April 2009

PSS Series

PSS Series

Features
■
■
■
■
■
■

PSS Supplies

Product Description
Eaton’s PSS Series of power supplies is
designed to work in a variety of applications, including the power supply to
the IT. line of power control products.
They also work in most control applications that require 24V DC. All of the
PSS power supplies are designed to
provide the highest “outrush” current
in the industry for units of their size.
It is also the only line to provide 110 –
480V AC input voltage down to the
smallest current units.

■
■
■
■
■

Wide range voltage input
(110 – 480V AC operating).
High current outrush capability
in all units.
Semiconductor F47 approved.
Long ride-through capability
designed in.
Wide operating temperature range.
Power supplies can be used in
parallel (6.5A and greater).
Multiple 24V DC terminals for
easy wiring.
DIN-rail and panel mount available
in most units.
Removable terminal connections.
IP20 fingerproof design.
Larger units have —
❑ Active power factor correction
❑ Adjustable output voltages
❑ Fault contacts
❑ Analog outputs

■
■
■

■

■

■

24V DC control enhances personnel
and equipment safety.
IP20 design improves personnel
safety.
Removable terminal connectors
make installation and repair quick
and easy.
Wide operating temperature range
allows for installation in most areas
where standard control products
can be installed today.
High current outrush capability
allows use of smaller power
supplies in many applications
and ensures stable output during
high power demand cycles.
Due to long ride-through time, the
Power Supply can maintain the
control power system during brown
out and black out conditions.

Standards and Certifications
UL Listed 508.
CSA Certified.
■ CE Marked.
■ F47 Certified.
■
■

Application Description
The PSS line of power supplies is
specifically designed to work with the
S801, S811, MV811 and IT. electromechanical devices. They can also
serve in a variety of other applications,
including support of sensors, operator
interfaces, PLCs, communication networks, heaters and lights and in many
other industrial applications where
24V DC power supplies are required.
With the widest operating temperature
range in the industry, rugged design
and a long list of advanced features,
they can be applied in a very wide range
of applications.
The higher input voltage ranges are
designed to allow users to eliminate
the need for a control power transformer in the enclosure or cabinet,
thus saving space, wiring and money.

CA08102001E

Benefits

For more information visit: www.eaton.com

44

Distribution & Control Transformers and Power Supplies
Power Supplies

44-72

April 2009

PSS Series

Catalog Number Selection

Accessories

Table 44-78. PSS Catalog Numbering System

DIN-Rail Mounting Kit
Table 44-81. Kits

PSS 55 A

Description

Model

Nominal Input Voltage Rating

PSS = Power Supply Switcher

Catalog
Number

Price
U.S. $

DIN-Rail Mounting Kit PSSDIN

A = 115V AC
D = 480 – 600V AC
B = 230V AC
E = 110 – 240V AC
C = 360 – 480V AC F = 380 – 480V AC
(3-phase)

Wattage Rating
10 = 10 Watts
25 = 25 Watts
55 = 55 Watts

160 = 160 Watts
300 = 300 Watts
600 = 600 Watts
1000 = 1000 Watts

Product Selection
Table 44-79. Power Supply Product Selection
Steady State
Current (Amps)

Steady State
Wattage

Input
Voltage

Catalog
Number

.4

10W

110 – 240
380 – 480

PSS10E
PSS10F

1.0

25W

110 – 240
380 – 480

PSS25E
PSS25F

2.3

55W

110 – 240
190 – 264
360 – 480
480 – 600

PSS55A
PSS55B
PSS55C
PSS55D

6.5

160W

110 – 240
380 – 480

PSS160E
PSS160C

12.5

300W

90 – 264
380 – 480

PSS300E
PSS300C

25.0

600W

380 – 480

PSS600C

40.0

1000W

380 – 480

PSS1000C

44

Price
U.S. $

Table 44-80. PSS Sizing Chart
Frame
Size

IEC
Size

NEMA
Size

Steady State
Current

Inrush
Amps

Durahon

27 mm

A

N/A

.83A

.83A

30 mS

45 mm

B

00, 0

.13A

3.30A

50 mS

54 mm

C

1

.15A

3.80A

50 mS

76 mm

D

2

.21A

5.40A

65 mS

105 mm

E

3, 4

.23A

5.80A

85 mS

140 mm

F

5

.54A

8.30A

250 mS

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-73
Power Supplies
April 2009

PSS Series

Technical Data and Specifications

Table 44-82. Power Supply Specifications
Capacity

PSS10E

PSS10F

PSS25E

PSS25F

PSS55A

PSS55B

PSS55C

PSS55D

10W

10W

25W

25W

55W

55W

55W

55W

Input
Voltage

110 to 240V AC 380 to 480V AC 110 to 240V AC 380 to 480V AC 115V AC

230V AC

380 to 480V AC
3-Phase

480 to 600V AC
3-Phase

Input Current
(RMS)

.19A

.54A

.20A/Phase

.07A/Phase

.1A

.45A

.17A

.9A

Frequency

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

Voltage Range

± 10%

± 10%

± 10%

± 10%

± 15%

± 15%

± 10%

± 15%

Inrush Current

25A

25A

35A

35A

16A

32A

15A

15A

Overvoltage

330V AC

550V AC

330V AC

550V AC

Varistor

Varistor

Varistor

Varistor

T2A @ 250V

T4A @ 250V

T2A @ 250V

T2A @ 250V

T2A @ 250V

3 x T2A @ 250V

Internal Input Fuse T2A @ 250V
External Fusing

Not Required 2A 250V AC Slow Blow

—
3 x 1A 600V AC
Slow Blow

Output
Voltage Nominal

24V DC

24V DC

24V DC

24V DC

24V DC

24V DC

24V DC

Voltage Regulation ±10%

24V DC

±10%

±10%

±10%

±3.5%

±3.5%

±3.5%

±3.5%

Current Nominal

2.3A

.4A

1.0A

1.0A

2.3A

2.3A

2.3A

Voltage Adj. Range None

.4A

None

None

None

None

None

None

None

Current Surge

1A

1A

6.8A

6.8A

10A

10A

10A

10A

Current Surge
Time

35 mS

35 mS

85 mS

85 mS

180 mS

180 mS

180 mS

180 mS

10 sec

10 sec

10 sec

10 sec

Hold Up Time

100 mS

100 mS

100 mS

100 mS

70 mS

70 mS

24 mS

30 mS

Max. Load
Capacitance

10,000 µF

10,000 µF

10,000 µF

10,000 µF

10,000 µF

10,000 µF

10,000 µF

10,000 µF

Switching
Frequency

60k Hz

60k Hz

100k Hz

100k Hz

100k Hz

100k Hz

100k Hz

61k Hz

Efficiency @
Max. Load

80%

75%

80%

80%

80%

80%

80%

85%

Output Ripple

±1%

±1%

±1%

±1%

±1%

±1%

±1%

±1%

Surge Cycle Time

CA08102001E

For more information visit: www.eaton.com

44

Distribution & Control Transformers and Power Supplies
Power Supplies

44-74

April 2009

PSS Series
Table 44-82. Power Supply Specifications (Continued)
Capacity

PSS10E

PSS10F

PSS25E

PSS25F

PSS55A

PSS55B

PSS55C

PSS55D

10W

10W

25W

25W

55W

55W

55W

55W

Protection
Short Circuit

Auto restart

Auto restart

Auto restart

Auto restart

Auto restart

Auto restart

Auto restart

Auto restart

Over Voltage

No

No

No

No

No

No

No

No

Under Voltage

No

No

No

No

No

No

No

No

10A typical
@ 24V for
>300 mS

10A typical
@ 24V for
>300 mS

10A typical
24V for
>300 mS

Over
Temperature
Over Current

None. Software in Micro Controller
0.8A typical
@ 24V for
>100 mS

0.8A typical
@ 24V for
>160 mS

6.8 A typical
@ 24V for
>160 mS

6.8A typical
@ 24V for
>160 mS

10A typical
@ 24V for
>300 mS

Galvanic Isolation
Input to Output

1.5 kV

2 kV

1.5 kV

2 kV

3 kV

3 kV

3 kV

4 kV

Input/Output to
Rail

1.5 kV

2 kV

1.5 kV

2 kV

3 kV

3 kV

3 kV

4 kV

Input to Ground 1.5 kV

2 kV

1.5 kV

2 kV

1.5 kV

1.5 kV

1.5 kV

2.0 kV

Output to
Ground

200V

200V

200V

200V

200V

200V

250V

200V

Special Features
Cooling

Convection

Convection

Convection

Convection

Convection

Convection

Convection

Convection

Load Sharing

None

None

None

None

None

None

None

None

Redundancy

None

None

None

None

None

None

None

None

Analog Outputs

None

None

None

None

None

None

None

None

Fault Relay

None

None

None

None

None

None

None

None

Input

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

Output

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

20 – 14 AWG

I/O

None

None

None

None

None

None

None

None

Wire Size

44

Indications
Indicators

Green LED (DC on)

Physical Data
Dimensions
Length x Width
x Depth in
inches (mm)

4.49 x 1.97 x 4.49 4.49 x 1.97 x 4.49 4.49 x 1.97 x 4.49 4.49 x 1.97 x 4.49 2.09 x 3.86 x 5.59 2.09 x 3.86 x 5.59 2.32 x 4.21 x 6.73 2.32 x 6.19 x 6
(114 x 50 x 114) (114 x 50 x 114) (114 x 50 x 114) (114 x 50 x 114) (53 x 98 x 142)
(53 x 98 x 142)
(59 x 107 x 171) (59 x 157 x 154)

Weight (kg)

.57 (.26)

.64 (.29)

.73 (.33)

.81 (.37)

Mounting and
TS35 rail or chassis; leave 4 in. (10 cm) free space on venting sides.
Recommended
Clearance

1.06 (.48)

1.06 (.48)

1.17 (.53)

2.45 (1.1)

TS35 Rail (with optional PSSDIN Kit) or Chassis;
Leave 4 in. (10 cm) free space on venting sides.

—

Environmental Performance
Storage
Temperature

-25 to 80°C

-25 to 80°C

-25 to 80C

-25 to 80C

-40 to 85°C

-40 to 85°C

-40 to 85°C

-40 to 85°C

Operating
Temperature

-5 to 50°C

-5 to 50°C

-5 to 50°C

-5 to 50°C

-25 to 50°C

-25 to 50°C

-25 to 50°C

-25 to 50°C

Storage
Humidity

5 to 95%

5 to 95%

5 to 95%

5 to 95%

5 to 95%

5 to 95%

5 to 95%

5 to 95%

Operating
Humidity

<95% RH noncondensing

<95% RH noncondensing

<95% RH noncondensing

<95% RH noncondensing

20 to 85% noncondensing

20 to 85% noncondensing

20 to 85% noncondensing

20 to 85% noncondensing

UL, IEC, CSA

UL, IEC, CSA

UL, IEC, CSA

Approvals/Certifications
UL, IEC, CSA

cULus 1950 Recognized, cULus 508 Listed, CE

For more information visit: www.eaton.com

cCSAus

CA08102001E

Distribution & Control Transformers and Power Supplies 44-75
Power Supplies
April 2009

PSS Series

PSS160E

PSS300E

Table 44-82. Power Supply Specifications (Continued)
Capacity

PSS160E

PSS160C

PSS300E

PSS300C

PSS600C

PSS1000C

160W

160W

300W

300W

600W

1000W

Voltage

115 to 230V AC

380 to 480V AC
3-Phase

115 to 230V AC

380 to 480V AC
3-Phase

380 to 480V AC
3-Phase

380 to 480V AC
3-Phase

Input Current
(RMS)

2.3A/1.4A

.43A/Phase

3.3A/1.65A

.75A/Phase

1.4A/Phase

1.9A/Phase

Input

Frequency

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

47 – 63 Hz

Voltage Range

± 10%

± 10%

± 10%

± 10%

± 10%

± 10%

Inrush Current

16/32A

5.7A

30A

40A

40A

40A

Over Voltage

Varistor

Varistor

Varistor

Varistor

Varistor

Varistor

Internal Input Fuse

T6.3A @ 250V

3 x T2A @ 500V

T5A @ 250V

No

No

No

External Fusing

Not Required
3A 250V AC
Slow Blow

Not Required
2A 480V AC
Slow Blow

Not Required
6A 250V AC
Slow Blow

3 x T2A @ 480V AC
Slow Blow

Required 3 x 6A @ 480V AC Slow Blow

Output
Voltage Nominal

24V DC

24V DC

24V DC

24V DC

24V DC

24V DC

Voltage Regulation

±3.5%

±3.5%

±6%

±5%

±6%

±6%
40A

Current Nominal

6.5A

6.5A

12.5A

12.5A

25A

Voltage Adj. Range

22.5 to 28.5V DC

22.5 to 28.5V DC

23 to 28V DC

23 to 28V DC

23 to 28V DC

23 to 28V DC

Current Surge

13A

20A

18A

25A

50A

80A

Current Surge Time

1 sec

1 sec

1 sec

1 sec

1 sec

1 sec

Surge Cycle Time

10 sec

10 sec

10 sec

60 sec

60 sec

60 sec

Hold Up Time

50 mS

15 mS

30 mS

25 mS @ 480V AC

12 mS

>14 mS

Max. Load
Capacitance

10,000 µF

10,000 µF

10,000 µF

10,000 µF

10,000 µF

10,000 µF

Switching
Frequency

65k Hz

100k Hz

100k Hz

100k Hz

65k Hz

65k Hz

Efficiency @
Max. Load

85%

83%

80%

83%

87%

90%

Output Ripple

±1%

±1%

±.1%

±.1%

±.1%

±.1%

CA08102001E

For more information visit: www.eaton.com

44

Distribution & Control Transformers and Power Supplies
Power Supplies

44-76

April 2009

PSS Series
Table 44-82. Power Supply Specifications (Continued)
Capacity

PSS160E

PSS160C

PSS300E

PSS300C

PSS600C

PSS1000C

160W

160W

300W

300W

600W

1000W

Protection
Short Circuit

Auto restart

Auto restart

Auto restart

Auto restart

Auto restart

Auto restart

Over Voltage

No

Yes

Yes

Yes

Under Voltage

No

Yes

Yes

Yes

Vout > 30V DC
Vout < 20V DC

Vout > 30.5V DC
Vout < 20V DC

20A typical @ 24V
for >1 sec

Vout heatsink temp. is greater than 100°C
20A typical @ 24V
26.5A typical @ 24V
for >1 sec
for >1 sec

Over Temperature
Over Current

None. Software in Micro Controller
13A typical @ 24V
for >1 sec

13A typical @ 24V
for >1 sec

43A typical @ 24V for
>1 sec

Galvanic Isolation
3 kV

3 kV

3 kV

3 kV

3 kV AC

3 kV AC

Input/Output to Rail 3 kV

Input to Output

3 kV

3 kV

3 kV

1.5 kV AC

1.5 kV AC

Input to Ground

1.5 kV

1.5 kV

1.5 kV

1.5 kV

1.5 kV AC

1.5 kV AC

Output to Ground

500V

500V

500V

500V

500V AC

500V AC

Special Features

44

Cooling

Convection

Convection

Fan cooled

Convection

Fan cooled

Fan cooled

Load Sharing

Maximum 2 units

Maximum 2 units

Maximum 3 units
(active)

Maximum 2 units

Maximum 2 units

Maximum 2 units

Redundancy

Maximum 2 units

Maximum 2 units

Maximum 2 units

Maximum 2 units

Maximum 2 units

Maximum 2 units

Analog Outputs

None

None

VDC Out = 3 x V
analog, T = 10 x V
analog, IOUT = 10 x
V analog

None

VDC OUT = 3 x V analog, T = 10 x V analog,
IOUT = 10 x V analog

Fault Relay

Form C, 125V AC
and 30V DC @ 1A
rating

Form C, 125V AC
and 30V DC @ 1A
rating

Form C contacts (1A Form C contacts (1A Form C contacts (1A Form C contacts (1A
@ 30V DC or 30V AC) @ 30V DC or 30V AC) @ 30V DC or 30V AC) @ 30V DC or 30V AC)

Input

26 – 12 AWG

26 – 12 AWG

22 – 12 AWG

22 – 12 AWG

22 – 12 AWG

22 – 12 AWG

Output

26 – 12 AWG

26 – 12 AWG

22 – 6 AWG

22 – 6 AWG

22 – 6 AWG

22 – 6 AWG

I/O

26 – 12 AWG

26 – 12 AWG

22 – 12 AWG
(.08 – 2.5 mm2)

22 – 12 AWG
(.08 – 2.5 mm2)

22 – 12 AWG
(.08 – 2.5 mm2)

22 – 12 AWG
(.08 – 2.5 mm2)

Wire Size

Indications
Indicators

Green LED (DC on)

Physical Data
Dimensions
Length x Width x
Depth in Inches
(mm)

5.0 x 2.2 x 6.8
(127 x 57 x 175)

5.44 x 2.3 x 7
4.1 x 9.53 x 6.1
(138.2 x 58.4 x 177.8) (104 x 242 x 155)

6.25 x 3.16 x 6.35
(159 x 80 x 161)

6.8 x 9.4 x 5.3
(173 x 238 x 135)

7.2 x 10.6 x 5.3
(182 x 268 x 133)

Weight Lbs. (kg)

1.94 (.88)

2.2 (.99)

3.0 (1.4)

6.6 (3)

8.35 (3.8)

Mounting and
Recommended
Clearance

2.6 (1.18)

TS35 Rail with optional PSSDIN Kit or Chassis (hardware included); leave 4 in. (10 cm) free space on venting sides.

Environmental Performance
Storage
Temperature

-40 to +85°C

-40 to +85°C

-40 to +85°C

-40 to +85°C

-40 to +85°C

-40 to +85°C

Operating
Temperature

-20 to 50°C

-20 to 50°C

-20 to 50°C

-20 to 50°C

-10 to +50°C
(Full Power)

-10 to +50°C
(Full Power)

Storage Humidity

5 to 95%

Operating Humidity 20 to 85% noncondensing

5 to 95%

4 to 95%

4 to 95%

5 to 95%

5 to 95%

20 to 85% noncondensing

19 to 85% noncondensing

19 to 85% noncondensing

20 to 85% noncondensing

20 to 85% noncondensing

Approvals/Certifications
CE, cULus 508 Listed CE, cULus 508 Listed CE, cULus 508 Listed CE, cULus 508 Listed CE, cULus 508 Listed CSA 22.2 #950-95,
cULus 508 Listed, CE

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-77
Power Supplies
April 2009

ELC Power Supply

ELC Power Supply

Product Description
Eaton’s ELC power supplies are the
perfect products for those applications
requiring a very compact and low-cost
source for 24V DC power. While these
products were developed to be a
perfect match for our Eaton Logic
Controllers, they can be used in a
variety of applications.
The lightweight, DIN-rail mounted
enclosures, wide input voltage range,
and robust screw terminals make
these power supplies easy to install
and use. They are available in 1A and
2A models.

Features, Benefits
and Functions
ELC Power Supply

Universal input voltage: 85-264V AC.
■ Compact size, with common depth
and height across models allows for
common panel depths and family
consistency.
■ ELC styling provides maximum
aesthetic appeal when used with the
Eaton Logic Controllers.
■

Front-mounted pressure plate screw
terminals for a robust connection.
■ Removable finger-safe protective
cover for terminals.
■ Power On indication LED.
■ Integrated mounting hardware
for panel mounting or DIN-rail
mounting.
■

Standards and Certifications
UL / cUL Listed – UL 508.
CE Marked.
■ RoHS Compliant.
■ Class I, Division II for groups A, B,
C, D.
■
■

Product Selection
Table 44-83. ELC Product Selection
Description

Catalog
Number

24 Watt, 1 Amp
Power Supply

ELC-PS01

48 Watt, 2 Amp
Power Supply

ELC-PS02

Price
U.S. $

44
Technical Data and Specifications
Table 44-84. Technical Specifications
Capacity

ELC-PS01

ELC-PS02

24W

48W

Input
Nominal Voltage

100 – 240V AC

Voltage Range

85 – 264V AC

Frequency

47 – 63 Hz

Output
Nominal Output Voltage

24V DC +/- 3%

Nominal Current

1A

Efficiency

78% to 87% typical at full load

Residual Ripple/Peak Switching (20 MHz)

< 100 mV typical @ full load

2A
< 240 mV typical @ full load

General/Physical Data
Housing Material

Plastic

Dimensions (D)

60 mm

Dimensions (W)

36.5 mm

Dimensions (H)

90 mm

Weight (g)

158

Operating Temperature

0°C to +55°C

Storage Temperature

-25°C to +70°C

Operating Humidity

50% to 95% RH, non-condensing

Pollution Degree

2

55 mm
250

Approvals/Certifications
UL508, CE, RoHS, EMC directive 89/336/EEC, Low voltage directive 73/23/EEC

Safety and Protection
Overload/Short Circuit Protection

Auto recovery

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

44-78

Distribution & Control Transformers and Power Supplies
Power Supplies
April 2009

ELC Power Supply

Dimensions

L
3.54
(90.0)

N

24V
0V
POWER
ELC-PS01

0.12
(3.0)

1.44
(36.5)

2.36
(60.0)

13.3
(0.52)

Figure 44-66. ELC-PS01 Power Supply — Approximate Dimensions in Inches (mm)
2.17
(55.0)

44

13.3
(0.52)

2.36
(60.0)

0.12
(3.0)

L
N

3.94
(100.0)
3.54
(90.0)

24V
0V
POWER
ELC-PS02

0.12
(3.0)

1.28
(32.5)

Figure 44-67. ELC-PS02 Power Supply — Approximate Dimensions in Inches (mm)

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-79
Power Supplies
April 2009

EZ Power Supply

EZ Power Supply

Features, Benefits
and Functions
■
■

■

■

Product Description
Eaton’s EZ power supplies are the
perfect products for those applications
requiring a low-amperage 24V DC
power source. While these products
were developed to be a perfect match
for our EZ Relay products, they can be
used in a variety of applications.

■
■

■

Universal input voltage:
85 – 264V AC.
Compact size, with common depth
and height across models allows for
common panel depths and family
consistency.
EZ styling provides maximum
aesthetic appeal when used with
the Eaton EZ Relay products.
Wide operating temperature range
(-25°C to 55°C).
Power On indication LED.
Optional mounting hardware for
panel mounting (EZB4-101-GF1) or
standard DIN-rail mounting.
Finger-safe, side-entry screw clamp
terminals for clean wiring.

Standards and Certifications
UL Listed.
CSA Certified.
■ CE Marked.
■ Class I, Division II rated for groups
A, B, C, D.
■ RoHS Compliant.
■
■

Product Selection
Table 44-85. EZ/EZD-CPs Power Supplies
Description

Catalog
Number

100 – 240V AC Input to
12V DC at 20 mA/24V DC
at 250 mA

EZ200-POW

100 – 240V AC Input to
24V DC at 1.25A

EZ400-POW

Price
U.S. $

Technical Data and Specifications
Table 44-86. Technical Specifications
Capacity

EZ200-POW

EZ400-POW

6W

30W

Input
Nominal Voltage

100 – 240V AC

Voltage Range

85 – 264V AC

Frequency

47 – 63 Hz

Output
Nominal Output Voltage

24V DC +/- 3%

Nominal Current

.25 A

1.25 A

General/Physical Data
Housing Material

Plastic

Dimensions (D)

56.5 mm

Dimensions (W)

35.5 mm

Dimensions (H)

90 mm

Operating Temperature

-25°C to +55°C

Storage Temperature

-40°C to +70°C

Pollution Degree

2

Connection Cables

71.5 mm

0.2-4.0 mm^2 (AWG 22-12), Solid
0.2-2.5 mm^2 (AWG 221-12), Flexible

Approvals/Certifications
UL, CE, RoHS, CSA, EN 50178m IEC/EN 60947

Safety and Protection
Overload/Short Circuit Protection

Yes

Over Current Limitation Form

0.3A

Degree of Protection

IP20

RFI Suppression

EN 55011, EN 55022 Class B, IEC 61000-6-1, 2, 3, 4

Potential Isolation (prim./sec.)

Yes, SELV, (to EN 600950, VDE 805)

1.4A

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

44

44-80

Distribution & Control Transformers and Power Supplies
Power Supplies
April 2009

EZ Power Supply

Dimensions
EZ200-POW
EZ256-HCI

EZ400-POW
0.42
(10.8)

0.30
(7.5)

1.97
(50.0)

3.54
(90.0)

3.54
(90.0)

4.02
(102.0)

1.77
(45.0)

4.02
(102.0)

4.33
(110.0)

4.33
(110.0)

0.18
(4.5)
1.87
(47.5)
2.22
(56.5)

44

(M4)

1.41
(35.8)

.157
DIA.
(3.9)

2.81
(71.5)

0.30
(7.5)
1.40
(35.5)

Figure 44-68. EZ200-POW/EZ256-HCI and EZ400-POW Series Dimensions in Inches (mm)

For more information visit: www.eaton.com

CA08102001E

Distribution & Control Transformers and Power Supplies 44-81
Power Supplies
April 2009

Sensor Power Supply

Sensor Power Supply

Accumulation Systems, but is also
suitable for use in a wide variety of
applications. The unit delivers 100W
output at 27V DC and supports easy,
Class II wiring. The power supply is a
tamper-proof, rugged component easily mounted to a conveyor side-channel
or support. Internal components are
fully encapsulated in a strong die-cast
housing to stand up to rugged handling,
ensuring flawless performance in any
material handling environment.

■

Built-in slug-release input converts
an AC or DC input to the appropriate
DC signal for integration with the
200 Series and E68 Series Zero
Pressure Accumulation Systems.

■

Dual output connection terminals
to make it easy and convenient to
locate the power supply at the
center of the cable run.

■

Power switch protected against
accidental operation.
Power in and out indicators show
status at a glance.
Conduit entry box for NEC
compliance.
Simple mounting with two
1/4-inch bolts.
Rugged die-cast housing.
Fully encapsulated electronics.

■

Features, Benefits
and Functions

■

Integrated AC junction box for onestep mounting and wiring without
the need for additional accessories.
■ Built-in DC power health contact
allows easy monitoring of power
supply status.
■ Unitized design features a tamperproof encapsulated construction to
reduce the risk of damage associated with conventional open
control-panel type construction.
■

Product Description
The Cutler-Hammer® Sensor Power
Supply by Eaton Corporation was
specially designed to be used with the
200 Series and E68 Series Zero Pressure

■
■
■

Standards and Certifications
■
■

UL Listed.
CSA Approved.

44

Product Selection
Table 44-87. Model Selection
Operating
Voltage

Output

105 – 132V AC 27V DC, 100W; short
circuit, overload and
overvoltage protection
(cycle power to reset)




Slug Input

Type

Slug Output

Catalog
Number

15 – 132V AC/DC
3 mA minimum

Standard
For use with 200 series
and E68 systems

Sinking or Sourcing, switch select- PS256A-01B1 
able; 80 mA maximum; short
circuit protection for loads less
than 32V AC or DC (auto reset)

High Current Slug
For use with solenoid valve
systems requiring full current
slug signals

Sinking only; 100W output; short
PS256A-04B1 
circuit, overload and overvoltage

protection (cycle power to reset)

Price
U.S. $

Total output power of supply is 100W. Total supply output power (100W) = main output power + slug output power.
Stocked product, typical order quantities guaranteed in stock.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
CA08102001E

For more information visit: www.eaton.com

Distribution & Control Transformers and Power Supplies
Power Supplies

44-82

April 2009

Sensor Power Supply

Technical Data and Specifications
Table 44-88. Sensor Power Supply Specifications
Description

PS256A-01B1

PS256A-04B1

Input Power

144W, Maximum inrush 30A from cold start

Input Voltage

105 – 132V AC

Input Current (Full Load)

105V AC – 1.92A, 115V AC – 1.65A, 132V AC – 1.5A

Output Power

100W

Output Voltage

27V DC

Output Protection

Short circuit, overload and overvoltage protection (cycle power to reset), diode protected

Regulation

±3%

Slug Input

15 – 132V AC/DC

Slug Output

Sinking or Sourcing, switch selectable; 80 mA maximum; short
circuit protection for loads less than 32V AC or DC (auto reset)

Indicators

Red LED: AC In; Green LED: DC Out

DC Fail Indication Output

N.O. contact, solid-state relay, 80 mA maximum

Temperature Range

-13° to 131°F (-25° to 55°C)

Vibration

20g

Enclosure Material

Die-cast aluminum

Sinking only; 100W output; short circuit, overload and

overvoltage protection (cycle power to reset)

Enclosure Rating

NEMA 1

Connections

Main Output/Slug Output: Two three-position finger protected barrier strips;
AC Line Input, DC Fail Indication and Slug Input: 8-position screw terminal strip inside conduit entry box



Total output power of supply is 100W. Total supply output power (100W) = main output power + slug output power.

Dimensions

44

Wiring Diagram
4.6
(117)

4.6
(117)

Slug
V+ Output Com

Slug
V+ Output Com

Junction
Box

9.0
(229)
8.2
(208)

9.7
(246)

PS256A-01B1 only

Power Monitor 15-132 VAC/
15-132 VDC
Slug In
L1
L2
GND
L1
L2

AC Input Power
Chassis internally
connected to AC GND

L1

3.0
(76)

Sinking Slug
Sourcing Slug

L2

Not
Used

Hole for 1/4 Inch Hardware

Figure 44-69. Dimensions in Inches (mm)

Figure 44-70. Wiring Diagram

For more information visit: www.eaton.com

CA08102001E



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Producer                        : Acrobat Distiller 5.0.5 for Macintosh
Create Date                     : 2009:04:24 13:56:12Z
Modify Date                     : 2009:04:24 15:54:13-04:00
Metadata Date                   : 2009:04:24 15:54:13-04:00
Format                          : application/pdf
Title                           : TB04400001E
Description                     : Distribution & Control Transformers and Power Supplies
Creator                         : Zoltun
Document ID                     : uuid:14a0725a-50a3-487b-8e18-eb516f4dc382
Instance ID                     : uuid:c4a47331-7a6d-424a-8309-a9163aa587b8
Page Count                      : 82
Page Layout                     : SinglePage
Subject                         : Distribution & Control Transformers and Power Supplies
Author                          : Zoltun
EXIF Metadata provided by EXIF.tools

Navigation menu