Triple Plus ZBSASOU20 Shutoff Actuator of Cloud Leak Management system User Manual User manual 29260

Triple Plus Shutoff Actuator of Cloud Leak Management system User manual 29260

Contents

Users Manual

TripleplusLtd.|5HamadaSt.,HighTechPark,Yoqneam,2069200,Israel|+972(0)722211370|info@tripleplus.io|www.tripleplus.io
Triple+ZigBeeActuatorUser’sManualv0.1
P/N:ZBSSHAMAP120
Warnings
Pleasereadthroughtheinstructionscarefullyandfollowthestepsofthe
system'sinstallationandcommissioning.
Pleasemaintainthisdocumentinasafeplaceforfuturereference.Whenin
anydoubt,contactyourauthorizeddistributororinstaller.
Warning!Theproductincludesmovingparts.Keepyourfingersorother
objectsawayfrommovingparts.
Warning!Thisproductwasdesignedtopreventwaterleaksandassuch
shouldbeusedforwaterpipingonly.
Actuatorspecification
PartNo.ZBSSHAMAP120
ProductdescriptionThewireless,batteryoperatedwateractuator is
installedonthemainwaterpipe.Itactuatesthe
watersupplywheneverariskyeventisidentifiedor
whenmanuallydonebytheuser.Thesystemcanbe
easilyintegratedwithanexistingalarmandIoT
systems,allowingthepropertyownertomonitor
andcontrolthewaterinfrastructureviaamobile
device.
Dimensions 142x73x92mm(5.6x2.87x3.62)
Weight 640gr(1.41Lbs)
Powersupply4x3Vbatteries(CR123);removablecompartment
cover
Operationvoltage6V
BatterylifespanUptofiveyears,subjecttotheusageprofileand
valveusefrequency
OperatingRF2.4GHz
TransmissionrangeOpenspace‐upto230m(750ft.)
Whenawalliswithinthespace‐upto120m(390
ft.)
Toavoiddamagingthewirelesscommunication,
avoidinstallationwithinmetalcabinets.
Compliantto FCC/IC
IPRatingIEC60529IP68
Workingtemperature‐20to+500C(4to +1220F)
ActuatormountingpadISO5211
Actuatordescription
Thewireless,batteryoperatedwateractuatorisinstalledonanyISO5211
valve.Itwillactuatewheneverariskyeventisidentifiedorwhenmanually
requestedbytheuser.ThisactuatorismountedonaISO5211flangeusing2
screws,providedwiththeinstallationkit.ItisIP68rated,meaningthatits
enclosureisbothdustandwatertightandcanalsobesubmergedintowater,
accordingtoIP68limitations,statedbelow.
Theintegratedballvalvewhosepartscomeincontactwithwatermeetsthe
leadfreerequirementsofNSF372(NSF61).
TheactuatorandtheISO5211valveshouldbeinstalledonthemainwater
line.
Thesystemshouldnotdisconnectafireextinguishinglineorafiresprinkler
line.
Ensureeasyaccesstotheactuatorunitincaseitmightberequiredfor
service.
Theunitcanbeinstalledperpendicularlyorinparallelwiththepipe.
Withtheutilizationofthelockingpin,acomfortableactuatordisconnection
shouldbepossibleafterinstallation.
Donotpositionactuatorswithinmetalcabinets.
Donotimmersetheproductinwaterdeeperthan1.5metersanddonot
keepitsubmergedinwaterlessthan1.5metersdeepformorethan30
minutes.
Donotexposetheproducttowatermovingwithforce,suchaswaterrunning
fromatap.
Iftheproductisexposedtofreshwater,dryitthoroughlywithaclean,soft
cloth.
Iftheproductisexposedtoanyliquidotherthanfreshwater,gentlyrinseit
withstillfreshwaterimmediatelyanddryitthoroughlywithacleansoft
cloth.Failuretogentlyrinsethedeviceinstillfreshwateranddryitas
instructedmaycausetheproducttosufferfromoperabilityorcosmetic
issues.
Iftheproductisdroppedorreceivesanimpact,thewateranddust‐resistant
featuresofthedevicemaybedamaged.
FCC/ICStatement
TocomplywithFCCandICRFexposurecompliancerequirements,the
deviceshouldbelocatedatadistanceofatleast20cmfromallpersons
duringnormaloperation.Theantennasusedforthisproductmustnot
becolocatedoroperatedinconjunctionwithanyotherantennaor
transmitter.
Ledispositifdoitêtreplacéàunedistanced'aumoins20cmàpartirde
touteslespersonnesaucoursdesonfonctionnementnormal.Les
antennesutiliséespourceproduitnedoiventpasêtresituésou
exploitésconjointementavecuneautreantenneoutransmetteur.
Warrantyinstructions
Pleasevisitwww.tripleplus.io/supportforwarranty,technical
support,andselfsolvingtools.