File info: application/pdf · 6 pages · 789.18KB
CERUS X-DRIVE with DISCONNECT
Cerus X-Drive with Disconnect Datasheet
kele.com | Franklin Control Systems CXD1-DISC0650-4V-75 | Motor Controls | Variable Frequency Drives
Kele | X-Drive Disconnect Series | VFD with UL Type 1 Enclosed MMS Disconnect
Extracted Text
Project Date Rep Firm CERUS X-DRIVE with DISCONNECT 1/2�30HP (200/208/230VAC), 1/2�75HP (460VAC), 1/2�60HP (575VAC), 3-Phase Input UL Type 1 Enclosed VFD with Disconnect SPECIAL INSTRUCTIONS: Contractor Engineering SIZING INFORMATION TABLES 200VAC 208VAC Part Number HP FLA KAIC HP FLA KAIC HP CXD1-DISC0025-2V-2-5 1/2 2.5 100 1/2 2.4 100 1/2 CXD1-DISC0037-2V-4 3/4 3.7 100 3/4 3.5 100 3/4 CXD1-DISC0060-2V-6 1 4.8 100 1 4.6 100 1.5 CXD1-DISC0078-2V-8 2 7.8 100 2 7.5 100 2 CXD1-DISC096-2V-10 2 7.8 100 2 7.5 100 3 CXD1-DISC0110-2V-13 3 11 100 3 10.6 100 3 CXD1-DISC0152-2V-17 3 11 100 3 10.6 100 5 CXD1-DISC0220-2V-22 5 17.5 100 5 16.7 100 7.5 CXD1-DISC0253-2V-26 7.5 25.3 100 7.5 24.2 100 7.5 CXD1-DISC0280-2V-32 7.5 25.3 100 7.5 24.2 100 10 CXD1-DISC0322-2V-40 10 32.2 100 10 30.8 100 10 CXD1-DISC0483-2V-50 15 48.30 100 15 46.2 100 15 CXD1-DISC0594-2V-63 - - - 20 59.4 100 20 CXD1-DISC0680-2V-75 20 62.1 100 20 59.4 100 25 CXD1-DISC0782-2V-90 25 78.2 100 25 74.8 100 25 CXD1-DISC0920-2V-100 30 92 100 30 88 100 30 Part Number HP CXD1-DISC0011-4V-1 1/2 CXD1-DISC0016-4V-1-6 3/4 CXD1-DISC0021-4V-2-5 1 CXD1-DISC0034-4V-4 2 CXD1-DISC0048-4V-6 3 CXD1-DISC0076-4V-8 5 CXD1-DISC0110-4V-13 7.5 CXD1-DISC0140-4V-17 10 CXD1-DISC0210-4V-22 15 CXD1-DISC0270-4V-32 20 CXD1-DISC0340-4V-40 25 CXD1-DISC0400-4V-40 30 CXD1-DISC0520-4V-63 40 CXD1-DISC0650-4V-75 50 CXD1-DISC0770-4V-90 60 CXD1-DISC0960-4V-100 75 460VAC FLA KAIC 1.1 65 1.6 65 2.1 65 3.4 65 4.8 65 7.6 65 11 65 14 30 21 30 27 30 34 50 40 50 52 50 65 50 77 50 96 50 Part Number HP CXD1-DISC0009-6V-1 1/2 CXD1-DISC0013-6V-1-6 3/4 CXD1-DISC0024-6V-2-5 1.5 CXD1-DISC0039-6V-4 3 CXD1-DISC0061-6V-6 5 CXD1-DISC0090-6V-10 7.5 CXD1-DISC0110-6V-13 10 CXD1-DISC0170-6V-17 15 CXD1-DISC0220-6V-22 20 CXD1-DISC0270-6V-32 25 CXD1-DISC0320-6V-40 30 CXD1-DISC0410-6V-50 40 Option Descriptions Ethernet IP and Modbus TCP/IP Communications Card 3% Line Reactor1 5% Line Reactor1 Output Reactor (in lieu of line reactor)2 1 Available for 200, 208, 230, and 460VAC models only. 2 Output reactors come standard on all 575VAC packages and do not need to be selected for these models. 230VAC FLA 2.2 3.2 6 6.8 9.6 9.6 15.2 22 22 28 28 42 54 68 68 80 575VAC FLA 0.9 1.3 2.4 3.9 6.1 9 11 17 22 27 32 41 KAIC 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 KAIC 25 25 25 25 25 25 25 10 10 10 10 10 Note: HP rating is based on standard NEMA B, 4-pole motor design as represented in NEC table 430.150 full-load current, 3-phase alternating current motors. Project Date Rep Firm Contractor Engineering SPECIFICATION TABLE Motor Controls Operation Cooling method Short Circuit Rating Agency Approvals Control Methods Control Type Frequency Setting Resolution Frequency Accuracy V/F Control Curve Speed Control Ratio Maximum Output Frequency Overload Capacity Starting Torque Torque Limit (Stall level) Operation Method Frequency Setting By Digital Inputs Outputs Start Signal Digital Inputs Multi-Step Accel/Decel Time and Presets Emergency Stop Jog Fault Reset Safety Inputs Three Multi-Function Relays Two Analog Outputs General Operation Functions Pump Operation Functions/Protections VFD Fault Trips Motor Overload Overcurrent Overvoltage Overtemperature Restart After IPF VFD Alarm Operation Information Fault History Operating Temperature Storage Temperature Ambient Humidity Altitude Vibration and Impact Environmental Conditions Drive Frame 200/208/230VAC 460VAC 575VAC Frame A 96 96 97 Forced air cooling by internal fans 100kA UL and cUL listed, CE marked 200/208/230VAC and 460VAC models: V/F control, SVC (Sensorless Vector Control) 575/690VAC models: V/F and SVC PWM (Pulse Width Modulation) Digital Reference: 0.01 Hz (Below 100 Hz), 0.1 Hz (Over 100 Hz) Analog Reference: [Max. output frequency]x 0.03/60Hz (�11 bit) Digital: 0.01 % of Max. Output Frequency Analog: 0.1 % of Max. Output Frequency 12 preset V/F curves and four-point square curve 1:12 (5Hz-60Hz) at 60Hz maximum frequency 200/208/230VAC models: 599Hz (55kW and above: 400Hz); 460VAC models: 599Hz (90kW and above: 400Hz); 575/690VAC models: 599Hz Variable Torque: 120% of VFD rated current for 1 minute during every 5 minutes of operation. Constant Torque: 150% of VFD rated current for 1 minute during every 5 minutes of operation and 160% for 3 seconds during every 25 seconds of operation. Up to 150% or higher at 0.5Hz (Torque Accuracy �5%). Variable Torque: Max. 130% torque current; Constant Torque: Max. 160% torque current Keypad / Terminals / Communication (Built-in Modbus and BACnet) Two Analog Inputs 0- 10VDC/ 4- 20mA and One AI 0-10VDC. Digital: Keypad or Communication Forward, Reverse and Jog (some features can start and stop VFD based on analog signal). 8 programmable digital inputs can be set to any selection from long list of functions. Up to 17 Speeds can be set including Jog by Programmable Digital Inputs. 0.00- 600.00/0.0- 6000.0 seconds. Three ACC/DEC preset values switched by digital inputs or one by frequency. Additional adjustable Accel/Decel S-Curve pattern. Ext. Trip and Shutdown immediately interrupt VFD output in any control method. Jog operation with adjustable Jog frequency. Resets VFD faults via keypad, digital input or communication. Some critical faults can only be reset by cycling the VFD power. SCM and STO terminals for safety circuit wiring. One relay with Form C: 250VAC 3A/30VDC 3A contact; Two relays with Form A: 250VAC 1.2A/30VDC 3A. Each relay can be programmed to any selection from the functions list. Selections: Output Frequency, Output Current, Output Voltage, Output kW, DC Link Voltage, V1 or I input signal level. Both outputs are 0-10VDC scalable from 10 to 200%. DC Braking, Frequency Limit, Jump Frequencies, 2nd ACC/DEC, Auto Restart, Auto-Tuning, PID w/sleep, Flying Start, Speed Search, DC Braking, Slip Compensation, Motor Pre-heat, Temperature Foldback, Damper Control, Fireman's Override, Shutdown, etc. Pipe Fill, 2nd PID, Trigger by AI, Overpressure, ULD (Underload), HLD (High Load), Dual Demand, Pipe Leak, Broken Pipe, MMC, Multi-VFD with Lead/Lag/Standby and Jokey, Transducer redundancy, Lubrication, Screen Clean, etc. Over Voltage, Low Voltage, Over Current, Overload, Short Circuit, Ground Fault, VFD Overheat, Input Phase Loss, Output Phase Open, CPU Communication Error, Signal Loss, Hardware Fault, etc. Adjustable electronic motor overload protection. 200/208/230/460VAC Variable Torque: At 200% of VFD rated current, 200/208/230/460VAC Constant Torque: At 240% of VFD rated current, Current clamp: Variable Torque: 130- 135%, Constant Torque 170- 175% 575/690VAC models: At 225% VFD rated current Current clamp: Variable Torque: 128- 141%, Constant Torque: 170- 175% 230VAC models: At 410VDC DC bus voltage 460VAC models: At 820VDC DC bus voltage 575VAC models: At 1016VDC DC bus voltage 690VAC models: At 1189VDC DC bus voltage Built-in IGBT and Capacitor Bank temperature sensors Adjustable power loss duration up to 20 sec. Leakage current is greater than 50% of rated current of the drive. Stall Prevention at ACC and DEC, Overload, Thermal Sensor Fault, Capacitors High Temperature, Signal Loss, Overpressure, Underload, High Load, etc. Output Frequency, Output Current, Output Voltage, Frequency Reference, Operating Speed, DC Voltage, kWattmeter, Run-time, Last Trip Time, Pressure, etc. The VFD stores 5 last faults. NEMA 1: 14�F ~ 104�F (-10�C ~ 40�C), Open Type: 14�F ~ 122�F (-10�C ~ 50�C) -13�F ~ 158�F (-25�C ~ 70�C) Up to 95% RH. (Non-Condensing) Normal up to 3,300ft (1,000m). At altitude up to 2,000 m, de-rate by 1% of rated current or lower 0.5 �C of temperature for every 100m above 1,000m. Maximum altitude for Corner Grounded TN system is 2,000m. For application over 2,000m, please contact FELE for more details. 1mm peak to peak value from 2Hz to 13.2Hz; 0.7G- 1.0G from 13.2Hz to 55Hz; 1.0G from 55Hz to 512Hz. Comply with IEC 60068-2-6 and IEC/EN60068-2-27. Pollution degree 2. No Corrosive Gas, Combustible Gas, Oil Mist or Dust. IEC60721-3-3/ IEC60364-1/ IEC60664-1 Frame B Frame C Frame D0 Frame D Frame E Frame F Frame G Frame H 96.5 96.5 - 97 97 - - - 96.5 96.5 97 97 97 97 97.5 97.5 98 97 - 97 97 97 98 98 Protection Keypad Display Environment Inputr Efficiency (>=X%) Input Voltage Project Date Rep Firm SUBMITTED EQUIPMENT SCHEDULE QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** QTY Tag Part # HP 1325746/.0505524 Line Reactor or Output Reactor 35O�%utLpiunteRReeaaccttoorr(*non-575V drive)** * 3% and 5% Line Reactors are not available on 575V VFD packages. ** Output reactors come standard on all 575V packages and do not need to be selected for these models. Contractor Engineering Voltage Phase 2450376508 3 Voltage Phase 2450376508 3 Voltage Phase 2450376508 3 Voltage Phase 2450376508 3 Voltage Phase 2450376508 3 Voltage Phase 2450376508 3 Voltage Phase 2450376508 3 Voltage Phase 2450376508 3 Voltage Phase 2450376508 3 Communication Card �Ethernet IP + Modbus Communication Card �Ethernet IP + Modbus Communication Card �Ethernet IP + Modbus Communication Card �Ethernet IP + Modbus Communication Card �Ethernet IP + Modbus Communication Card �Ethernet IP + Modbus Communication Card �Ethernet IP + Modbus Communication Card �Ethernet IP + Modbus Communication Card �Ethernet IP + Modbus Project Date Rep Firm WIRING DIAGRAM Contractor Engineering Project Date Rep Firm Contractor Engineering MMS DISCONNECT SPECIFICATIONS The following section details the MMS Disconnect sizing and ratings. To locate the part number for your X-Drive Disconnect panel, reference the sizing information table below. 200/208/230VAC X-Drive Panel Bypass Part Number Contactor Part Number CXD1-DISC0025-2V-2-5 CMS-32HI-2-5 CXD1-DISC0037-2V-4 CMS-32HI-4 CXD1-DISC0060-2V-6 CMS-32HI-6 CXD1-DISC0078-2V-8 CMS-32HI-8 CXD1-DISC0096-2V-10 CMS-32HI-10 CXD1-DISC0110-2V-13 CMS-32HI-13 CXD1-DISC0152-2V-17 CMS-32HI-17 CXD1-DISC0220-2V-22 CMS-32HI-22 CXD1-DISC0253-2V-26 CMS-32HI-26 CXD1-DISC0280-2V-32 CMS-32HI-32 CXD1-DISC0322-2V-40 CMS-32HI-40 CXD1-DISC0483-2V-50 CMS-63HI-50 CXD1-DISC0594-2V-63 CMS-63HI-63 CXD1-DISC0680-2V-75 CMS-100HI-75 CXD1-DISC0782-2V-90 CMS-100HI-90 CXD1-DISC0920-2V-100 CMS-100HI-100 (MCP) DISCONNECT SIZING TABLE Rated Frame Size Part # operational current Ie (A) CMS-32HI-1 1 CMS-32HI-1-6 1.6 CMS-32HI-2-5 2.5 CMS-32HI-4 4 CMS-32HI-6 6 CMS-32HI-8 8 32AF CMS-32HI-10 10 CMS-32HI-13 13 CMS-32HI-17 17 CMS-32HI-22 22 CMS-32HI-26 26 CMS-32HI-32 32 CMS-32HI-40 40 CMS-63HI-32 32 CMS-63HI-40 40 63AF CMS-63HI-50 50 CMS-63HI-63 63 CMS-100HI-75 75 100AF CMS-100HI-90 90 CMS-100HI-100 100 Magnetic release operating current (A) 13 20.8 32.5 52 78 104 130 169 221 286 338 416 520 416 520 650 819 975 1170 1300 460VAC X-Drive Panel Bypass Part Number Contactor Part Number CXD1-DISC0011-4V-1 CMS-32HI-1 CXD1-DISC0016-4V-1-6 CMS-32HI-1-6 CXD1-DISC0021-4V-2-5 CMS-32HI-2-5 CXD1-DISC0034-4V-4 CMS-32HI-4 CXD1-DISC0048-4V-6 CMS-32HI-6 CXD1-DISC0076-4V-8 CMS-32HI-8 CXD1-DISC0110-4V-13 CMS-32HI-13 CXD1-DISC0140-4V-17 CMS-32HI-17 CXD1-DISC0210-4V-22 CMS-32HI-22 CXD1-DISC0270-4V-32 CMS-32HI-32 CXD1-DISC0340-4V-40 CMS-32HI-40 CXD1-DISC0400-4V-40 CMS-63HI-40 CXD1-DISC0520-4V-63 CMS-63HI-63 CXD1-DISC0650-4V-75 CMS-100HI-75 CXD1-DISC0770-4V-90 CMS-100HI-90 CXD1-DISC0960-4V-100 CMS-100HI-100 KAIC Ratings [kA] 240V 480V 600V 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 50 10 100 30 10 100 30 10 100 30 10 100 30 10 100 50 10 100 50 10 100 50 10 100 50 10 100 50 10 100 50 10 100 50 10 Disconnect Device 575VAC X-Drive Panel Bypass Part Number Contactor Part Number CXD1-DISC0009-6V-1 CMS-32HI-1 CXD1-DISC0013-6V-1-6 CMS-32HI-1-6 CXD1-DISC0024-6V-2-5 CMS-32HI-2-5 CXD1-DISC0039-6V-4 CMS-32HI-4 CXD1-DISC0061-6V-6 CMS-32HI-6 CXD1-DISC0090-6V-10 CMS-32HI-10 CXD1-DISC0110-6V-13 CMS-32HI-13 CXD1-DISC0170-6V-17 CMS-32HI-17 CXD1-DISC0220-6V-22 CMS-32HI-22 CXD1-DISC0270-6V-32 CMS-63HI-32 CXD1-DISC0320-6V-40 CMS-63HI-40 CXD1-DISC0410-6V-50 CMS-63HI-50 CXD1-DISC0520-6V-63 CMS-100HI-63 CXD1-DISC0620-6V-65 CMS-100HI-65 - - - - Project Date Rep Firm Contractor Engineering PANEL VFD SPECIFICATIONS The following table details the Cerus X-Drive VFD model of the panel. To locate your panel's VFD, reference your bypass part-number and the column directly to the right of it. Panel VFD Reference Table 200/208/230VAC X-Drive Panel Bypass Part Number VFD Part Number CXD1-BYP0025-2V-2-5 CXD1-BYP0037-2V-4 CXD1-BYP0060-2V-6 CXD1-BYP0078-2V-8 CXD1-BYP0096-2V-10 CXD1-BYP0110-2V-13 CXD1-BYP0152-2V-17 CXD1-BYP0220-2V-22 CXD1-BYP0253-2V-26 CXD1-BYP0280-2V-32 CXD1-BYP0322-2V-40 CXD1-BYP0483-2V-50 CXD1-BYP0594-2V-63 CXD1-BYP0680-2V-75 CXD1-BYP0782-2V-90 CXD1-BYP0920-2V-100 CXD1-BYP1200-2V-200 CXD1-BYP1300-2V-225 CXD1-BYP1540-2V-250 CXD-005-2V CXD-005-2V CXD-007-2V CXD-010-2V CXD-010-2V CXD-015-2V CXD-021-2V CXD-031-2V CXD-031-2V CXD-031-2V CXD-046-2V CXD-061-2V CXD-061-2V CXD-075-2V CXD-090-2V CXD-105-2V CXD-105A-2V CXD-146A-2V CXD-180A-2V 460VAC X-Drive Panel Bypass Part Number VFD Part Number CXD1-BYP0011-4V-1 CXD1-BYP0016-4V-1-6 CXD1-BYP0021-4V-2-5 CXD1-BYP0034-4V-4 CXD1-BYP0048-4V-6 CXD1-BYP0076-4V-8 CXD1-BYP0110-4V-13 CXD1-BYP0140-4V-17 CXD1-BYP0210-4V-22 CXD1-BYP0270-4V-32 CXD1-BYP0340-4V-40 CXD1-BYP0400-4V-40 CXD1-BYP0520-4V-63 CXD1-BYP0650-4V-75 CXD1-BYP0770-4V-90 CXD1-BYP0960-4V-100 CXD1-BYP1240-4V-200 CXD1-BYP1560-4V-250 - CXD-003-4V CXD-003-4V CXD-003-4V CXD-004-4V CXD-008-4V CXD-010-4V CXD-013-4V CXD-018-4V CXD-024-4V CXD-032-4V CXD-038-4V CXD-045-4V CXD-060-4V CXD-073-4V CXD-091-4V CXD-110-4V CXD-150A-4V CXD-180A-4V - 575VAC X-Drive Panel Bypass Part Number VFD Part Number CXD1-BYP0009-6V-1 CXD1-BYP0013-6V-1-6 CXD1-BYP0024-6V-2-5 CXD1-BYP0039-6V-4 CXD1-BYP0061-6V-6 CXD1-BYP0090-6V-10 CXD1-BYP0110-6V-13 CXD1-BYP0170-6V-17 CXD1-BYP0220-6V-22 CXD1-BYP0270-6V-32 CXD1-BYP0320-6V-40 CXD1-BYP0410-6V-50 CXD1-BYP0520-6V-63 CXD1-BYP0620-6V-65 - CXD-003-6V CXD-003-6V CXD-003-6V CXD-006-6V CXD-006-6V CXD-009-6V CXD-012-6V CXD-018-6V CXD-024-6V CXD-030A-6V CXD-036A-6V CXD-045A-6V CXD-054A-6V CXD-067A-6V - CERUS X-DRIVE WITH DISCONNECT DIMENSIONS *All measurements in inches* UL TYPE 1 200/208/230VAC X-Drive with Disconnect CXD1-DISC0025-2V-2-5 CXD1-DISC0037-2V-4 CXD1-DISC0060-2V-6 CXD1-DISC0078-2V-8 CXD1-DISC096-2V-10 CXD1-DISC0110-2V-13 CXD1-DISC0152-2V-17 CXD1-DISC0220-2V-22 CXD1-DISC0253-2V-26 CXD1-DISC0280-2V-32 CXD1-DISC0322-2V-40 CXD1-DISC0483-2V-50 CXD1-DISC0594-2V-63 CXD1-DISC0680-2V-75 CXD1-DISC0782-2V-90 CXD1-DISC0920-2V-100 H x W x D Frame Size 43.1" x 8.1" x 10.5" 1 51.5" x 10.4" x 11.2" 2 57.6" x 12.5" x 13.0" 3 460VAC X-Drive with Disconnect CXD1-DISC0011-4V-1 CXD1-DISC0016-4V-1-6 CXD1-DISC0021-4V-2-5 CXD1-DISC0034-4V-4 CXD1-DISC0048-4V-6 CXD1-DISC0076-4V-8 CXD1-DISC0110-4V-13 CXD1-DISC0140-4V-17 CXD1-DISC0210-4V-22 CXD1-DISC0270-4V-32 CXD1-DISC0340-4V-40 CXD1-DISC0400-4V-40 CXD1-DISC0520-4V-63 CXD1-DISC0650-4V-75 CXD1-DISC0770-4V-90 CXD1-DISC0960-4V-100 H x W x D Frame Size 43.1" x 8.1" x 10.5" 1 51.5" x 10.4" x 11.2" 2 57.6" x 12.5" x 13.0" 3 575AC X-Drive with Disconnect CXD1-DISC0009-6V-1 CXD1-DISC0013-6V-1-6 CXD1-DISC0024-6V-2-5 CXD1-DISC0039-6V-4 CXD1-DISC0061-6V-6 CXD1-DISC0090-6V-10 CXD1-DISC0110-6V-13 CXD1-DISC0170-6V-17 CXD1-DISC0220-6V-22 CXD1-DISC0270-6V-32 CXD1-DISC0320-6V-40 CXD1-DISC0410-6V-50 H x W x D Frame Size 43.1" x 8.1" x 10.5" 1 51.5" x 10.4" x 11.2" 2