Cerberus� PRO
252-Point and 504-Point Addressable Fire Alarm Control Panel Models FC922 I FC924

Architect & Engineer Specifications
 Addressable fire alarm control panel (FACP) intended for mid-size building applications
 Comprised of the following system components:  Operating units  Periphery boards  Power supplies  System enclosures `Walk Test'
 System features:  Supports 252-to-504 addressable devices: - One (1) to four (4) `Class B'; one (1) to two (2) `Class A' for Model FC922 - One (1) to eight (8) `Class B'; one (1) to four (4) `Class A' for Model FC924
 10,000-event history-logging capability
 Includes one (1) `Class A' or two (2) `Class B' notification appliance circuits (NACs)
 Resettable and non-resettable 24VDC, [nominal] auxiliary power
 Connectivity to a leased-line / city-tie module
 Releasing module supports activation of releasing valves in pre-action / deluge systems / agent release
 Off-normal warning message prior to reset
 Fast and easy set-up with auto-configuration feature
 Networkable up to 32 panels using SafeDLink / CV Web
 Cerberus� DMS Danger Management Station can monitor and control up to 32 Models FC922 and FC924 FACPs
 Supports multiple global displays
 Digital alarm communication transmitter (DACT)
 UL 864 10th Edition Listed, ULC Listed
 FM, CSFM & NYC Fire Department Approved

Product Overview
The Cerberus PRO 252-point (Model FC922) / 504-point (Model FC924) addressable FACP is designed to meet the fire-protection needs of mid-size buildings. This advanced FACP offers features typically required in mid-size buildings in a package that is easy to install and competitively priced.
Additionally, Models FC922 and FC924 are networkable, allowing the systems to fulfill the growing fire-protection needs of the building. The programming software for the 252/ 504-point fire systems is held in flash electrically erasable programmable read-only memory (EEPROM).
The following Cerberus PRO system components are used in the 252-point / 504-point FACP:
� Operating units � Periphery boards � Power supplies � System enclosures
Other options are available to meet specific needs. Models FC922 and FC924 are FM (#3010); CSFM(#7165-0067:0259) and FDNY (#6104) Approved.
Model FC922
Specifications
Operating Interface Unit The Operating Interface Unit (Model FCM2018-U3 or Model FCM2019-U3) functions as the operating interface and central microprocessor for Models FC922 and FC924 with up to 10,000 event history log.
Either operating interface unit provides multi-use capability for each end-user to efficiently `Acknowledge' events; to quickly control the NACs of the FACP, and to permit a manual reset of the respective system. Detailed data about the nature and location of the events can also be displayed, via a backlit, 2"x 4-3/4" (5.1 cm. x 12.1 cm.) LCD screen and the four-way navigation push button at the top of the FACP.
Periphery Boards The periphery boards (Models FCI2016-U1 and FCI2017-U1) serve as the main operating components for the 252 / 504-point FACP. Each module operates and monitors input-device identity; as well as controls the signalingline circuits that communicate with smoke detectors and other field devices (i.e. -C-NET).

Siemens Smart Infrastructure � Building Products

Data Sheet 9815
usa.siemens.com/fire

Specifications (Cont.)
Power Supplies
All functions are supported by the power supplies (Model FP2011-U1 or Model FP2012-U1), which therefore eliminate the need for external power supplies.
Further, the 170-Watt power supply (Model FP2011-U1) and 300-Watt power supply (Model FP2012-U1) provide primary, 24VDC nominal power for normal operation to Models FC922 and FC924. Both power supplies are filtered and regulated. Model FP2011-U1 is rated at 6.5 Amps, and the rating for Model FP2012-U1 is 11.5A.
The 170-Watt power supply incorporates a 4.0A, nonresettable slow-blow fuse on the primary input, and includes a built-in AC-line filter for surge and noise suppression. Model FP2011-U1 mounts in the FACP enclosure, and there are no serviceable Cerberus PRO parts to be maintained.
The 300-Watt power supply incorporates two (2) 6.3A replaceable, non-resettable slow-blow fuses on the primary input and includes a built-in AC line filter for surge and noise suppression. Model FP2012-U1 mounts in the FACP's enclosure, and there are no serviceable Cerberus PRO parts to be maintained.
System Enclosures
The Cerberus PRO fire-alarm enclosures and their accessories provide a complete set of hardware for mounting all Cerberus PRO main-system and remote terminal cards and modules.
The hardware allows this Cerberus PRO system to be configured for a variety of applications, as well as for future system upgrades. Included in the enclosure series are back box and door sets; removable mounting plates and clear lenses, as well as blank plates for use with the enclosure doors.
All enclosures come with ground straps for the inner and outer doors, shield termination lugs, grounding lugs, and tie wrap lances for securing wire. All Cerberus PRO two height-unit (2HU) enclosures can also mount system backup batteries to 33AH in capacity.
Models FC922 and FC924 utilize a two-height-unit enclosure. The following components comprise a complete two-height-unit enclosure:
� One (1) back box, (Model FHB2002-U1 / R1)
� One (1) or two (2) inner doors, (Models FHD2004U1 or FHD2005-U1)
� One (1) outer door, (Model FHD2002-U3 / R3 or FHD2003-U3 / R3)
� One (1) or two (2) clear windows, (Model FHD2006-U1)
Note: One (1) window is installed for Model FHD2002U3 / R3 outer door, and two (2) windows are required for Model FHD2003-U3 / R3
The approximate size for each two-height-unit enclosure is: 27.5" (70cm.) high; 21.5" (54.6cm.) wide, and 5.75" (14.6cm.) deep. The weight, without any attached components, is approximately 6.3 Lbs. (2858 g).

System Enclosures (cont.)
Additionally, the two-height-unit enclosure supports the following optional components:
� Enclosure trim kit (for flush-mounting)
� Battery bracket (to comply with seismic certification)
� DIN rail kit (provides connection between internal-system wiring and field wiring)
Optional Accessories
Digital Alarm Communication Transmitter(DACT)
The DACT is used to provide communication between Models FC922 and FC924 and with either a central or remote monitoring station. The Model FCA2015-U1 module mounts directly on the back enclosure and connects to the periphery boards. The DACT enables remote transmission of alarms and events via a public telephone line.
Releasing Module
The releasing module (Model XCI2001-U1) supports activation of releasing valves in pre-action / deluge systems (including double-interlock pre-action systems, or Sinorix� Engineered Fire Suppression systems). Activation can be event-controlled or performed by addressable manual pull stations. The releasing module is installed on the periphery board, and supports `Class B' releasing circuits. When installed on Models FC922 / FC924, the releasing module contains an integral manual-disconnect switch for releasing circuits. This essential feature protects the releasing circuits from accidental discharge during maintenance.
Battery Disconnect Module
The Battery Disconnect Module (Model FCA2032-U1)is specifically designed to disconnect the backup battery on the Cerberus PRO 252 / 504-point addressable FACP when its voltage drops below 19VDC. Model FCA2032-U1's cutoff capability prevents the battery from operating beyond its normal power level for basic system operation.
Hardware Migration Kit The Cerberus PRO 922/924 panel offers support for Siemens legacy addressable and conventional systems.
Model FHA2056-series kits are specifically designed for the seamless transition of an existing Siemens FS-250 (FireSeeker) or MPC6000 control panel into a fully operational 50 | 252 or 504-point addressable Cerberus PRO fire-alarm FACP, [FC901 | FC922 or FC924], respectively. Each shipment of the Model FHA2056-series kits contains the following pieces of equipment:
 One (1) outer door  One (1) inner door  One (1) hinge-assembly bracket  One (1) back plate  One (1) inner-door bracket
NOTE: The five (5) items that comprise one (1) Model FHA2056series hardware-migration kit cannot be ordered individually.

Siemens

Smart Infrastructure � Building Products

�2�

usa.siemens.com/fire

Specifications (cont.)
Hardware Migration Kit (cont.)
Model FHA-MIQKIT-04/-05 offers support for legacy MXL and MXL-IQ peripherals using the FCL2004 device interface module. This allows the user to configure a Cerberus PRO panel to communicate to older addressable devices, offering a seamless migration solution to the latest technology system
Network Module The C-WEB network module (Model FN2001-U1) is used to network up to 16 FACPs, or one (1) fire terminal, via the CNET system bus. Model FN2001-U1 is plugged into the Operating Units (Models FCM2018-U3 /R3 and FCM2019-U3 /R3).
Model FN2001-U1, which connects to a system input / output bus, has ground-fault monitoring, as well as an integrated degrade-mode feature. Redundant networking is done with one (1) network module per FACP [Simple-Loop Trouble].There is electrical isolation between the system bus and FACP.
Remote Display Terminals
The Remote Display Terminals (Models FT2014-U3 /R3and FT2015-U3 /R3) are remote annunciators that's how the existing status of Models FC922 / FC924. The remote display terminals (Models FT2014-U3/R3 and FT2015-U3/R3) are remote annunciators which can be configured as global displays, and indicate real-time system status.
Light-emitting diodes (LEDs) will illuminate for any given Alarm, Supervisory and Trouble Cerberus PRO-system event. The LCD screen will give details of the event in alphanumeric form. The display screen can be scrolled, via the four-way navigation button, to reveal additional events.
Model FT2014-U3 /R3 is a display-only remote annunciator that has one (1) button used to silence the local sounder. Model FT2015-U3 /R3 has three (3) control buttons for `acknowledging' events, `silencing' audible circuits and `resetting' the system. Additionally, there are three (3) userprogrammable buttons available. Model FT2015-U3 /R3 has an integral key switch that enables the control buttons to operate.
The remote display terminals are remotely connected to Models FC922 and FC924, via the RS485 interface. Models FC922 and FC924 require the Model FCA2016-U1 RS485 module to provide communication to the remote display terminals. Model FCA2016-U1 supports Style 4 or Style 6 wiring. Up to eight (8) modules can be supported on a RS485 bus.
The remote display terminals require 24VDC [nominal] power, and the necessary power can be provided from this Cerberus PRO FACP or from another UL Listed, 24VDC power source.
Note: A Model FHD2012-U1 inner door can be optionally purchased in UL markets. The inner door mounts with the optional Model FT201 x-series Remote Display terminals. Having a Model FHD2012-U1 inner door installed can assist in preventing unauthorized access to the RDT.

S-series License Keys The S1 license key (Model FCA2033-A1) allows for virtual monitoring and control between a 252 / 504-point addressable fire-only panel and a personal computer. The S2 license key (Model FCA2034-A1) is a BACnet output, and is used for monitoring-only purposes by a 3rd-party system for life-safety objects. The S3 license key (Model FCA2035-A1) is a combination license key that allows for virtual monitoring and control, as well as for distribution of BACnet (monitoring-only) communications. A four-digit personal identification number (PIN) must be used in order to prevent unauthorized access.
Tabular Annunciators
Tabular annunciators allow system events sent from Cerberus PRO addressable panels to be displayed remotely in real-time. The Model FT2008 series of tabular annunciators has 16 zones, and the Model FT2009 series uses 96 LEDs for 32 zones. Up to two(2) light-emitting diodes (LEDs) can be used per zone. Tabular annunciators provide outputs for system and zone status, and are orderable in either black or red.
LED Annunciator Driver
The Model FT2007-U1 LED Annunciator Driver provides custom graphic annunciators on addressable Cerberus PRO FACPs. This optional system module provides 96highly programmable outputs to drive LED indicators.
There are 16 inputs to accommodate user-system commands: Silence, Unsilence, Reset, Acknowledge and Lamp Test.
Model FT2007-U1 is supervised via aRS-485 interface. A maximum eight (8) modules are allowed on each RS-485 communication bus.
NAC Expansion Module
The NAC expansion module (Model FCI2011-U1)provides either of the following additional NACs to a Cerberus PRO 252 / 504-point FACP:
 one (1)`Class A', or  two (2)`Class B' NACs
Each NAC is rated at 3 Amps. Each NAC expansion module is monitored for open-line and short-circuit conditions.
Temperature and Humidity Range
Models FC922 and FC924 are UL 864 10th Edition Listed for indoor dry locations within a temperature range of 120+/3�F (49+/-2�C) to 32+/-3�F (0+/-2�C) and a relative humidity of 93+/-2% at a temperature of 90+/-3�F (32+/-2�C).

Siemens

Smart Infrastructure � Building Products

�3�

usa.siemens.com/fire

MODEL OR TYPE
FCI2020-U1
FCM2018-U3

Details for Ordering

PART NUMBER

PRODUCT

S54400-A57-A1

Leased-Line / City -Tie Module

S54400-C40-A2

Operating Interface Unit

FP2011-U1 FP2012-U1 FT2007-U1 FT2008-U1 FT2008-R1 FT2009-U1 FT2009-R1 FT2014-U3 FT2014-R3 FT2015-U3 FT2015-R3 FTI2001-U1 FCA2015-U1 FN2001-U1 FCA2016-U1 FCA2018-U1 FCA2032-U1
FCA2033-U1
FCA2034-U1
FCA2035-U1
FCI2011-U1

500-450222

170-Watt Power Supply

S54400-Z60-A1 S54400-A142-A1 S54400-A143-A1 S54400-A144-A1 S54400-A145-A1 S54400-A146-A1 S54400-B80-A1 S54400-B73-A1 S54400-B88-A1 S54400-B16-A1 S54400-A58-A1 S54400-A63-A1 S54400-A60-A1 S54400-A39-A1 S54400-A65-A1 S54400-B145-A1

300-Watt Power Supply
LED Annunciator Driver 16-Zone Tabular Annunciator, Black
16-Zone Tabular Annunciator, Red
32-Zone Tabular Annunciator, Black
32-Zone Tabular Annunciator, Red
Remote Display Terminal, Black
Remote Display Terminal, Red
Remote Display Terminal, Black
Remote Display Terminal, Red
Fire Terminal Board Digital Alarm Communication
Transmitter C-WEB Network Module C-WEB Network Module
RS485 Interface C-WEB Network Module Remote Peripheral Module
Battery Disconnect Module

S54400-P154-A1

License Key (S1) for remote access | remote view | remote operation

S54400-P155-A1

License Key (S2) for BACnet output (monitoring only)

S54400-P156-A1

License Key (S3) for remote access | remote view | remote operation | BACnet output

S54400-A54-A1

NAC Expansion Module

FCI2016-U1 S54400-A55-A1

252-Pt. Periphery Board

FCI2017-U1 S54400-A56-A1

504-Pt. Periphery Board

XCI2001-U1 FCM2019-U3 FCM2022-U3

S54400-A69-A1 S54400-C41-A2 S54400-C44-A2

FCM2023-U3 S54400-C45-A2

FCM2034-U3 S54400-C138-A1

Releasing Module
Operating Interface Unit [with LED]
Blank Option Module
LED Option Module [ Red / Yellow bi-color LED; one
(1)Yellow LED ]
LED Option Module: [ Red / Yellow bi-color LED; one
(1)Yellow LED ]

Siemens

Smart Infrastructure � Building Products

�5�

MODEL OR TYPE

Details for Ordering (cont.)

PART NUMBER

PRODUCT

FN2006-U1 S54400-A61-A1 Single-Mode Fiber-Optic Module

FN2007-U1

S54400-A62-A1

Multi-Mode Fiber-Optic Module

FHB2001-U1 S54400-B47-A1 One-Height-Unit Back Box, Black

FHB2001-R1 S54400-B47-A2 One-Height-Unit Back Box, Red

FHB2002-U1 S54400-B48-A1 Two-Height-Unit Back Box, Black

FHB2002-R1 S54400-B48-A2 Two-Height-Unit Back Box, Red

FHD2001-U3 S54400-B45-A1 One-Height-Unit Outer Door, Black

FHD2001-R3 S54400-B40-A1 One-Height-Unit Outer Door, Red

FHD2002-U3 S54400-B32-A1

Two-Height-Unit Outer Door [with one (1) window], Black

FHD2002-R3 S54400-C53-A1

Two-Height-Unit Outer Door [with one (1) window], Red

FHD2003-U3 S54400-C42-A1

Two-Height-Unit Outer Door [with two (2) windows], Black

FHD2003-R3 S54400-B46-A1

FHD2004-U1 FHD2005-U1 FHD2006-U1

S54400-B52-A1 S54400-B53-A1 S54400-C46-A1

FHD2012-U1 S54400-C135-A1

FHA2056-U1 S54400-B18-A1
FHA2056-R1 S54400-B19-A1
FHAMIQKIT-04 S54400-C24-A1
FHAMIQKIT-05 S54400-C25-A1
FHAMIQKIT-03 S54400-K1-A1
FHAMIQKIT-01 S54400-A66-A1 FHAMIQKIT-02 S54400-A67-A1 FCL-MXLPLATE S54400-B153-A1
FH2072-UA S54433-A5- A1 FTH2073-UA S54433-A6- A1 FH2072-UA S54433-A5- A1 FTH2073H-UouAsin S54433-A6- A1 g for Battery-up to
34 Ah

Two-Height-Unit Outer Door [with two (2) windows], Red
Inner door, Black
Inner door, Solid Black
Clear-lens window
Optional inner door [for housing a Model FT201-series
display terminal], Black
Cerberus PRO Hardware Migration Kit, Black
Cerberus PRO Hardware Migration Kit, Red
MXL-IQ Mechanical Migration Kit, Black
MXL-IQ Mechanical Migration Kit, Red
One (1) PMI cable & One (1) Expansion Cable One (1) FCL2004 Module
with PMI Cable One (1) FCL2004 Module
with Expansion Cable Mounting Bracket for FCL2004 (2HU/USCG)
Universal Battery Cabinet
Universal Annunciator Cabinet
Universal Battery Cabinet
Universal Annunciator Cabinet

usa.siemens.com/fire

MODEL OR TYPE

Electronics Package

PART NUMBER

PRODUCT

252-Point Fire System with 170 Watt FC922-US S54400-C14-A1 Power Supply and standard operator
interfaces.

Includes:  FP2011-U1 (1 Qty.)  FCI2016-U1 (1 Qty.)  FCM2018-U3 (1 Qty.)

504-Point Fire System with 170 Watt FC924-US S54400-C15-A1 Power Supply and standard operator
interfaces.
Includes:  FP2011-U1 (1 Qty.)  FCI2017-U1 (1 Qty.)  FCM2018-U3 (1 Qty.)

FC922-UE FC924-UE

S54400-C16-A1

252-Point Fire System with 170 Watt Power Supply and standard operator
interfaces. (with 24-zone LEDs)

Includes:  FP2011-U1 (1 Qty.)  FCI2016-U1 (1 Qty.)  FCM2019-U3 (1 Qty.)

S54400-C17-A1

504-Point Fire System with 170 Watt Power Supply and standard operator
interfaces. (with 24-zone LEDs)

Includes:  FP2011-U1 (1 Qty.)  FCI2017-U1 (1 Qty.)  FCM2019-U3 (1 Qty.)

FT924-US

S54400-C18-A1

Network Terminal w/ standard operator interface

Includes:  FTI2001-U1 (1 Qty.)  FCM2018-U3 (1 Qty.)

FT924-UE

Network Terminal w/ standard

S54400-C19-A1

operator interface

(with 24-zone LEDs)

Includes:  FTI2001-U1 (1 Qty.)  FCM2019-U3 (1 Qty.)

252-Point Fire System with 300 Watt FC922-UT S54400-C20-A1 Power Supply and standard operator
interfaces

Includes:  FP2012-U1 (1 Qty.)  FCI2016-U1 (1 Qty.)  FCM2018-U3 (1 Qty.)

504-Point Fire System with 300 Watt FC924-UT S54400-C21-A1 Power Supply and standard operator
interfaces

Includes:  FP2012-U1 (1 Qty.)  FCI2017-U1 (1 Qty.)  FCM2018-U3 (1 Qty.)

MODEL OR TYPE

Electronics Package (Cont.)

PART NUMBER

PRODUCT

252-Point Fire System with 300 Watt FC922-UF S54400-C22-A1 Power Supply and standard operator
interfaces(with 24-zone LEDs)
Includes:  FP2012-U1 (1 Qty.)  FCI2016-U1 (1 Qty.)  FCM2019-U3 (1 Qty.)

FC924-UF

504-Point Fire System with 300 Watt S54400-C23-A1 Power Supply and standard operator
interfaces(with 24-zone LEDs)
Includes:  FP2012-U1 (1 Qty.)  FCI2017-U1 (1 Qty.)  FCM2019-U3 (1 Qty.)

Related Documentation

Product

Datasheet Number

Cerberus PRO Operating Interface Units

9801

Cerberus PRO System Periphery Boards

9802

Cerberus PRO Fire Terminal and Equipment

9803

Cerberus PRO Digital Alarm Communicator Transmitter (DACT)

9804

C-WEB Network Module

9805

170-Watt and 300-Watt Power Supplies

9806

Cerberus PRO Fire-Alarm Enclosures and Equipment

9807

NAC Expansion Module

9808

Releasing Module

9809

Leased-Line / City-Tie Module

9810

Cerberus PRO Remote Peripheral Module

9811

Cerberus PRO Remote Display Terminals

9812

Single / Multi-Mode Fiber-Optic Modules

9814

LED / Blank Option Modules

9816

Battery Disconnect Module

9819

S-series license keys

9820

Cerberus PRO Marine Fire and Detection Equipment

9822

Cerberus PRO LED Annunciator Driver

9824

Cerberus PRO 16 & 32 -Zone Tabular Annunciators

9825

Cerberus PRO Migration Hardware Kit

9826

Siemens

Smart Infrastructure � Building Products

�4�

usa.siemens.com/fire

NOTICE � The information contained in this data-sheet document is intended only as a summary, and is subject to change without notice. The product(s) described here has/have a specific instruction sheet(s) that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets � as well as the General Product Warning and Limitations document, which also contains important data, are provided with the product, and are available from the Manufacturer.

Data contained in the aforesaid type of documentation should be consulted with a fire-safety professional before specifying or using the product.

Any further questions or assistance concerning particular problems that might arise, relative to the proper functioning of the equipment, please contact the Manufacturer.

Cerberus� PRO
Siemens Industry, Inc. Smart Infrastructure - Building Products 8 Fernwood Road � Florham Park, NJ 07932
Tel: (973) 593-2600
July - 2021 (Rev. 7)