How To Use This Manual. This manual contains an overview of the 1794-AENT adapter. It describes how to install and configure the adapter, ...
CAMBIA AUTOMATION LIMITED .cn Allen Bradley 1794-IB16 bia DATASHEET cam Cambia Group Email: sales@ 2018/10/18 Contact email: sales@cambia.cn Urgent consult: 86 13599507613 FLEX I/O EtherNet/IP n Adapter Module cambia.c 1794-AENT Email: sales@ User Manual Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability n (to include intellectual property liability) for actual use based upon the examples shown in this publication. .c Allen-Bradley publication SGI-1.1, Safety Guidelines for the ia Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some b important differences between solid-state equipment and electromechanical devices that should be taken into consideration m when applying products such as those described in this publication. ca Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is Email: sales@ prohibited. Throughout this manual we use these notes to make you aware of safety considerations: WARNING Identifies information about practices or circumstances that have the potential to create an ! explosion hazard. ia.cn ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss. ! camb Warning and Attention statements help you to: · identify a hazard · avoid a hazard @ · recognize the consequences les IMPORTANT Identifies information that is critical for successful application and understanding of the product. saAllen-Bradley, ControlLogix, and FLEX I/O are trademarks of Rockwell Automation. il:Ethernet is a trademark of Digital Equipment Corporation, Intel, and Xerox Corporation. RSLinx and RSLogix 5000 are trademarks of Rockwell Software. Ema Windows NT is a trademark of Microsoft Corporation. European Communities (EC) If this product has the CE mark it is approved for installation within Directive Compliance the European Union and EEA regions. It has been designed and tested to meet the following directives. EMC Directive This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards: .cn · EN 50081-2 EMC -- Generic Emission Standard, Part 2 -- Industrial Environment ia · EN 50082-2 EMC -- Generic Immunity Standard, Part 2 -- Industrial Environment camb This product is intended for use in an industrial environment. Low Voltage Directive @ This product is tested to meet Council Directive 73/23/EEC Low s Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and le Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the Allen-Bradley apublication Industrial Automation Wiring and Grounding Guidelines, spublication 1770-4.1. il:Open style devices must be provided with environmental and safety protection by proper mounting in enclosures designed for specific a application conditions. See NEMA Standards publication 250 and IEC publication 529, as applicable, for explanations of the degrees of Em protection provided by different types of enclosure. Rockwell Automation Support Rockwell Automation offers support services worldwide, with over 75 sales/support offices, 512 authorized distributors and 260 authorized systems integrators located throughout the United States alone, as well as Rockwell Automation representatives in every major country in the world. Local Product Support Contact your local Rockwell Automation representative for: .cn · sales and order support · product technical training ia · warranty support b · support service agreements cam Technical Product Assistance If you need to contact Rockwell Automation for technical assistance, call your local Rockwell Automation representative, or call Rockwell @ directly at: 1 440 646-6800. les For presales support, call 1 440 646-3NET. aYou can also obtain technical assistance online from the following Rockwell Automation WEB sites: il: s· www.ab.com/mem/technotes/kbhome.html (knowledge base) · www.ab.com/networks/eds (electronic data sheets) Ema Your Questions or Comments on this Manual If you find a problem with this manual, please notify us of it on the enclosed Publication Problem Report. cambia.cn Email: sales@ About This User Manual Preface What this Preface Contains This preface describes how to use this manual. The following table lists where to find specific information within this chapter. For information about See page ambia.cn Who Should Use c This Manual les@ Common Techniques Email: sa Used in This Manual Who Should Use This Manual P-1 Common Techniques Used in This Manual P-1 How To Use This Manual P-2 About the Example Applications P-2 System Components P-3 Where to Find More Information P-4 Terminology P-5 This manual is intended for control engineers and technicians who are installing, configuring, and maintaining an EtherNet/IP control system that communicates with FLEX I/O through a 1794-AENT adapter. We assume you have a good understanding of Ethernet and the TCP/IP protocol. The following conventions are used throughout this manual: · Numbered lists provide sequential steps. · Bulleted lists provide information, not procedural steps. · Information in bold text identifies menu windows, screen options, screen names, or areas of the screen, such as dialog boxes, status bars, radio buttons, and parameters. The screen captures shown in this manual are pictures of the software's actual screens. TIP This symbol identifies helpful tips. 1 Publication 1794-UM006A-EN-P - July 2001 P-2 About This User Manual How To Use This Manual This manual contains an overview of the 1794-AENT adapter. It describes how to install and configure the adapter, and provides examples showing how to use the adapter to communicate with FLEX I/O over an EtherNet/IP network. About the Example Applications This manual presents two example applications that demonstrate the procedures for configuring and communicating with FLEX I/O using n the 1794-AENT adapter: The example applications are intended as .c building blocks to help you get your own system up and running. We recommend that you set up and run the example applications and use them as guides. ia Here is the type of system you'll be setting up: camb Local Slot 0 1 1794-AENT 130.130.130.3 Data FLEX I/O Slot 0 1 Chassis @ Logix5550 Email: sales Controller 1756-ENBT 130.130.130.2 Switch 130.130.130.1 Programming Terminal 1794-OB16 Digital Output 1794-IB16 Digital Input Publication 1794-UM006A-EN-P - July 2001 About This User Manual P-3 System Components We used the following components for the example applications. You will need the same or similar components to set up your own control system using FLEX I/O on EtherNet/IP. Quantity Product Name Catalog Number 1 1 1 1 1 1 1 1 1 Hardware FLEX I/O EtherNet/IP Adapter n FLEX I/O Digital Input Module .c FLEX I/O Digital Output Module FLEX I/O Analog Input Module ia FLEX I/O Analog Output Module b FLEX I/O Power Supply DIN Rail m ControlLogix chassis ca ControlLogix power supply 1794-AENT 1794-IB16 1794-OB16 1794-IF41 1794-OF41 1794-PS1 199-DR1 or equivalent 1756-A4, (or -A7, -A13, -A13, -A17) 1756-PA72, (or -PB72) 1 1 1 1 Email:11 sales@ Logix5550 controller ControlLogix EtherNet/IP Bridge Module Personal computer that supports RSLogix 5000 software Ethernet switch Associated media and connectors as needed Software RSLinx communications software, V2.3 or higher RSLogix 5000 programming software, V8.1 or higher 1756-L1 1756-ENBT Any appropriate model running Windows NT 4.0, Service Pack 5 or higher Refer to manufacturer's specifications 9355-WAB, -WABOEM, -WABC 9324-RLD300ENE Publication 1794-UM006A-EN-P - July 2001 P-4 About This User Manual Where to Find More Information Refer to the following Rockwell publications as needed for additional help when setting up and using your EtherNet/IP network. For information about See this publication Publication number Using EtherNet/IP for industrial control EtherNet/IP Performance and Application Guide ENET-AP001 EtherNet/IP media EtherNet/IP Media Planning and Installation Guide ENET-IN001 1794-AENT Adapter FLEX I/O EtherNet/IP Adapter Installation Instructions 1794-IN082 FLEX I/O input and output modules ControlLogix chassis ControlLogix power supplies Logix5550 programmable controllers ControlLogix EtherNet/IP Bridge Module RSLogix 5000 programming software RSLinx communications software FLEX I/O and FLEX Integra Technical Data Manual ControlLogix Chassis Installation instructions n ControlLogix Power Supplies Installation Instructions .c Logix5550 Controller User Manual ia ControlLogix EtherNet/IP Bridge Module Installation Instructions ControlLogix EtherNet/IP Bridge Module User Manual b Getting Results with RSLogix5000 m RSLinx Lite User's Guide 1794-2.1 1756-5.80 (Series B) 1756-5.67 (PA72/PB72) 1756-5.78 (PA75/PB75) 1756-6.5.12 1756-IN082 1756-UM050 9399-RLD300GR 9399-WAB32LUG ca TIP Many of the above publications are available online from The Automation Bookstore: http://www.theautomationbookstore.com. les@ TIP Rockwell Software products contain extensive tutorials and online help. We recommend that you a use the tutorials and help screens to learn about these products. s For more information about Rockwell Software il: products, visit the Rockwell Software internet site: Ema http://www.software.rockwell.com. Publication 1794-UM006A-EN-P - July 2001 About This User Manual P-5 Terminology This term Means bandwidth The transmission capacity of the network, expressed in bits per second. Traditional Ethernet has a 10Mbit bandwidth. Fast Ethernet is 100Mbit. BootP BootP (Bootstrap Protocol) is a low-level protocol that provides configurations to other nodes on a TCP/IP network. BootP configuration files let you automatically assign IP addresses to an Ethernet module (you can also obtain subnet masks and gateway addresses from BootP). bridge CIP The 1794-AENT factory default is BootP enabled. Upon powerup, the module sends a message containing its hardware address to n the BootP server on the network. The server is a computer with BootP server software installed. The server compares that .c hardware address to those in its lookup table in the configuration file and sends a message back to the module with the appropriate IP address. ia A node between two similar communication subnets where b protocol translation is minimal. Control and Information Protocol, the EtherNet/IP application m layer. CIP uses the "producer/consumer" networking model. In this model one producer broadcasts (multicasts) the data once to a all the consumers. All consumers see the data simultaneously, cand may choose whether to consume (receive) the data or not. @ consumer s CSMA/CD il: sale determinism Ema DHCP Delivery time is consistent, no matter how many consumers there are. A destination device in the CIP networking model. See CIP. Carrier Sense Multiple Access/Collision Detection. The access method used in Ethernet. When a device wants to gain access to the network, it checks to see if the network is quiet (senses the carrier). If it is not, it waits a random amount of time before retrying. If the network is quiet and two devices access the line at exactly the same time, their signals collide. When the collision is detected, they both back off and each waits a random amount of time before retrying. The ability to predict when information will be delivered. Important in time critical applications. The Dynamic Host Configuration Protocol (DHCP) is an Internet protocol, similar to BootP, for automating the configuration of computers that use TCP/IP. DHCP can be used to automatically assign IP addresses, to deliver IP stack configuration parameters such as the subnet mask and default router, and to provide other configuration information such as the addresses for printer, time and news servers. DNS The Domain Name System (DNS) is a hierarchical, distributed method of organizing the name space of the Internet. The DNS administratively groups hosts into a hierarchy of authority that allows addressing and other information to be widely distributed and maintained. A big advantage to the DNS is that using it eliminates dependence on a centrally-maintained file that maps host names to addresses. Ethernet A physical layer standard using Carrier Sense Multiple Access with Collision Detection (CSMA/CD) methods. Publication 1794-UM006A-EN-P - July 2001 P-6 About This User Manual This term Means Ethernet network A local area network designed for the high-speed exchange of information between computers and related devices. EtherNet/IP Ethernet Industrial Protocol. EtherNet/IP applies a common application layer (CIP) over Ethernet by encapsulating messages in TCP/UDP/IP. explicit messaging Non-time critical messaging used for device configuration and data collection, such as downloading programs or peer-to-peer messaging between two PLCs. fast Ethernet full duplex fully qualified domain name Ethernet operating at 100Mbps/second. n A mode of communication that allows a device to send and receive information at the same time, effectively doubling the .c bandwidth. A Fully Qualified Domain Name (FQDN) is a domain name that ia includes all higher level domains relevant to the entity named. If you think of the DNS as a tree-structure with each node having b its own label, a Fully Qualified Domain Name for a specific node would be its label followed by the labels of all the other nodes between it and the root of the tree. For example, for a host, a m FQDN would include the string that identifies the particular host, plus all domains of which the host is a part up to and including a the top-level domain (the root domain is always null). For cexample, PARIS.NISC.SRI.COM is a Fully Qualified Domain gateway s@ host name Email: sale hub Name for the host at 192.33.33.109. A module or set of modules that allows communications between nodes on dissimilar networks. The Host Name is the unique name for a computer within its domain. It's always the first element of a full name, and, with its domain and top-level domain suffix, creates the unique name of that computer on the Internet. For example, let's say the foobar website is www.foobar.com. The Host Name is "www", which is not unique on the web, but is unique within the foobar domain. The Host Name can also refer to the Fully Qualified Domain Name, or in this example, www.foobar.com. Both naming methods seem to be used interchangeably in various documents. For the purposes of this document, the Host Name will refer to the FQDN, or as in this example, www.foobar.com. A central connecting device that joins devices together in a star configuration. Hubs are generally not suitable for use in I/O control systems, since they are time critical applications that cannot tolerate lost packets. implicit messaging Real time messaging of I/O data. IP Internet Protocol that provides the routing mechanism for messages. All messages contain not only the address of the destination station, but the address of a destination network, which allows messages to be sent to multiple networks within an organization or around the world. Publication 1794-UM006A-EN-P - July 2001 About This User Manual P-7 This term Means IP address 32-bit identification number for each node on an Internet Protocol network. These addresses are represented as four sets of 8-bit numbers (numbers from 0 to 255), with periods between them. Each node on the network must have a unique IP address. latency The time between initiating a request for data and the beginning of the actual data transfer. module address A six-bit number used to uniquely identify any module on the multicast producer rack star configuration subnet mask switch local and extended ControlLogix backplane. In the CIP producer/consumer model one producer multicasts (broadcasts) the data once to all the consumers. n The source of information in the CIP networking model. See CIP. .c A physical and logical collection of application modules sharing a common power supply and backplane for module to module ia communication. A network configuration in which the devices are connected to a b central hub or switch. An extension of the IP address that allows a site to use a single m net ID for multiple networks. a A network device that cross connects devices or network csegments. A switch provides each sender/receiver the full @ TCP les TCP/IP satransaction Email:UDP network bandwidth (2x in full duplex mode), reduces collisions, and increases determinism. Transport Control Protocol. More reliable but slower transport protocol than UDP. Used for explicit (not time critical) messaging in EtherNet/IP. Transmission Control Protocol/Internet Protocol (TCP/IP). A transport-layer protocol (TCP) and a network-layer protocol (IP) commonly used for communication within networks and across internetworks. An exchange of request and data and response and data. User Datagram Protocol. Transport protocol that provides a very simple, but fast capability to send datagrams between two devices. Used for I/O (implicit) messaging in EtherNet/IP. Publication 1794-UM006A-EN-P - July 2001 P-8 About This User Manual cambia.cn Email: sales@ Publication 1794-UM006A-EN-P - July 2001 Table of Contents Chapter 1 About the 1794-AENT What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Adapter Adapter Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Hardware/Software Compatibility . . . . . . . . . . . . . . . . . . . . . . 1-2 What the Adapter Does . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Use of the Control and Information Protocol (CIP) . . . . . . . . . 1-2 Understanding the Producer/Consumer Model. . . . . . . . . . . . . 1-3 Installing the 1794-AENT Adapter Specifying the Requested Packet Interval (RPI) . . . . . . . . . . . . 1-3 Support of Rack Optimized and Direct Connections. . . . . . . . . 1-4 Mixing Rack Optimized and Direct Connections. . . . . . . . . 1-5 n What's Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5 .c Chapter 2 ia What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Identifying Module Components . . . . . . . . . . . . . . . . . . . . . . . 2-1 b Mounting the Adapter on a DIN Rail Before Installing Modules 2-2 Mounting (or Replacing) the Adapter on an Existing System. . . 2-3 m Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 a Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 c What's Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 @ Configuring the 1794-AENT s Adapter for Your EtherNet/IP Email: sale Network Chapter 3 What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Configuration Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Using the Rockwell BootP Utility . . . . . . . . . . . . . . . . . . . . . . 3-6 Using Force IP Renew To Reconfigure a Device. . . . . . . . . 3-8 Saving the Relation List . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Using a Third Party BootP Server . . . . . . . . . . . . . . . . . . . . . 3-11 Using DHCP Software to Configure Your Adapter . . . . . . . . . 3-13 What's Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 Chapter 4 Using Rack Optimized About the Example Application . . . . . . . . . . . . . . . . . . . . . . . 4-1 Discrete I/O Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . 4-3 Configure the I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4 Add the Local EtherNet/IP Bridge to the I/O Configuration. 4-4 Add the FLEX I/O Adapter to the I/O Configuration . . . . . . 4-6 Add the FLEX I/O Modules to the I/O Configuration . . . . . 4-8 Add the Digital Input Module . . . . . . . . . . . . . . . . . . . 4-8 Add the Digital Output Module . . . . . . . . . . . . . . . . . 4-10 Edit the Controller Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12 i Publication 1794-UM006A-EN-P - July 2001 Table of Contents ii Chapter 4 (continued) Create the Ladder Program . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13 Download the Program to the Controller . . . . . . . . . . . . . 4-14 Test the Example Application . . . . . . . . . . . . . . . . . . . . . . . . 4-15 What's Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16 Chapter 5 Using Analog I/O with About the Example Application . . . . . . . . . . . . . . . . . . . . . . . 5-1 Direct Connection LED Status Indicators Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . 5-3 Add the Analog Modules to the I/O Configuration . . . . . . . . . . 5-4 n Add the Analog Input Module to the I/O Configuration . . . 5-4 .c Add the Analog Output Module to the I/O Configuration . . 5-7 Edit the Controller Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11 ia Modify the Ladder Program . . . . . . . . . . . . . . . . . . . . . . . . . 5-12 Download the Program . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13 b Test the Example Application . . . . . . . . . . . . . . . . . . . . . . . . 5-14 m Appendix A a Interpreting the Status Indicators. . . . . . . . . . . . . . . . . . . . . . . A-1 c Module Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Network Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 Link Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 les@ 1794-AENT Adapter ail: sa Web Pages Appendix B Web Page Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1 Module Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2 TCP/IP Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2 Diagnostic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3 Connection Manager . . . . . . . . . . . . . . . . . . . . . . . . . . B-3 Network Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4 Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4 Miscellaneous (continued) . . . . . . . . . . . . . . . . . . . . . . B-5 m Appendix C E Configuring the RSLinx Ethernet What This Appendix Contains. . . . . . . . . . . . . . . . . . . . . . . . . C-1 Communication Driver Installing the RSLinx Software . . . . . . . . . . . . . . . . . . . . . . . . . C-1 Configuring the AB_ETH Driver . . . . . . . . . . . . . . . . . . . . . . . C-2 Index Publication 1794-UM006A-EN-P - July 2001 1 Chapter About the 1794-AENT Adapter What This Chapter Contains This chapter provides an overview of the 1794-AENT FLEX I/O EtherNet/IP adapter, its primary features, and how to use it. You will need to understand the concepts discussed in this chapter to configure your adapter and use it in an EtherNet/IP control system. The following table lists where to find specific information in this chapter. n . .c For information about ia Adapter Features Hardware/Software Compatibility b What the Adapter Does Use of the Control and Information Protocol (CIP) m Understanding the Producer/Consumer Model a Specifying the Requested Packet Interval (RPI) c Support of Rack Optimized and Direct Connections See page 1-1 1-2 1-2 1-2 1-3 1-3 1-4 Email: sales@ Adapter Features Mixing Rack Optimized and Direct Connections 1-5 The 1794-AENT adapter's features include: · use of EtherNet/IP messages encapsulated within standard TCP/UDP/IP protocol · common application layer with ControlNet and DeviceNet · interfacing via Category 5 rated twisted pair cable · half/full duplex 10 Mbit or 100 Mbit operation · DIN rail mounting · communication to and from other FLEX I/O modules on the same DIN rail · communication supported by RSLinx software · IP address assigned via standard BootP tools · I/O configuration via RSLogix 5000 software · no network scheduling required · no routing tables required 1 Publication 1794-UM006A-EN-P - July 2001 1-2 About the 1794-AENT Adapter Hardware/Software Compatibility The 1794-AENT adapter and the applications described in this manual are compatible with the following firmware versions and software releases. Contact Rockwell Automation if you need software or firmware upgrades to use this equipment. Product Firmware Version/ Software Release 1794-AENT Adapter 1.xx or higher What the Adapter Does Logix 5550 Controller RSLogix 5000 software n RSLinx software 8.1 or higher 8.1 or higher 2.3 or higher ia.c The 1794-AENT adapter performs two primary tasks: b 1. Control of real time I/O data (also known as "implicit messaging"). The 1794-AENT adapter serves as a bridge between I/O modules cam and the network. LE 5N 5 5 @ 0 B T EtherNet/IP lesA E FLEX a N I/O T E N ControlLogix B I/O T Other Network Devices il: s2. Support of messaging data for configuration and programming information (also known as "explicit messaging."). ma Use of the Control and E Information Protocol (CIP) The 1794-AENT adapter uses the Control and Information Protocol (CIP). CIP is the application layer protocol specified for EtherNet/IP, the Ethernet Industrial Protocol, as well as for ControlNet and DeviceNet. It is a message-based protocol that implements a relative path to send a message from the "producing" device in a system to the "consuming" devices. The producing device contains the path information that steers the message along the proper route to reach its consumers. Since the producing device holds this information, other devices along the path simply pass this information; they do not need to store it. Publication 1794-UM006A-EN-P - July 2001 About the 1794-AENT Adapter 1-3 This has two significant benefits: 1. You do not need to configure routing tables in the bridging modules, which greatly simplifies maintenance and module replacement. 2. You maintain full control over the route taken by each message, which enables you to select alternative paths for the same end device. Understanding the Producer/Consumer Model n The CIP "producer/consumer" networking model replaces the old .c source/destination ("master/slave") model. The producer/consumer model reduces network traffic and increases speed of transmission. In ia traditional I/O systems, controllers poll input modules to obtain their input status. In the CIP system input modules are not polled by a b controller. Instead, they produce ("multicast") their data either upon a change of state (COS) or periodically. The frequency of update m depends upon the options chosen during configuration and where on the network the input module resides. The input module, therefore, is ca a producer of input data and the controller is a consumer of the data. The controller can also produce data for other controllers to consume. The produced and consumed data is accessible by multiple controllers @ over the EtherNet/IP network. This data exchange conforms to the s producer/consumer model. ale Specifying the Requested Email: s Packet Interval (RPI) The RPI is the update rate specified for a particular piece of data on the network. The RPI can be specified for the adapter and include all of the I/O modules communicating through it (using a rack optimized connection) or specified for a particular module (using direct connection). When you add a module or an adapter to the I/O configuration of a controller, you must enter the RPI as a parameter. `This value specifies how often to produce the data for that device. For example, if you specify an RPI of 50ms, it means that every 50ms the device should send its data to the controller or the controller should send its data to the device. RPIs are only used for devices that produce data. For example, a ControlLogix EtherNet/IP bridge module in the same chassis as the controller does not require an RPI because it is not a data-producing member of the system; it is used only as a bridge to remote racks. Publication 1794-UM006A-EN-P - July 2001 1-4 About the 1794-AENT Adapter Support of Rack Optimized and Direct Connections The 1794-AENT adapter supports both direct and rack optimized connections. A direct connection is a "real-time" data transfer link between the controller and the device that the configuration data references. Direct connection messaging occurs at a cyclic rate specified by the RPI during configuration. A rack optimized connection is a grouping of data from more than one I/O module into a single block of data sent over a single connection at the same data rate. Rack optimized connections reduce the total number of connections needed to transfer data when using many I/O modules in a system. n The following example illustrates the benefit of rack optimized connections. .c Assume you have set up a system that contains 8 discrete I/O modules ia interfaced to a 1794-AENT adapter. If you use direct connections to transfer data to each of the these I/O modules, you need 8 b connections to transfer all of the data, one to each of the 8 I/O modules. If you use a rack-optimized connection to transfer the data, m you only need a single connection the connection to the 1794-AENT ca adapter. @ IMPORTANT Although rack optimized connections offer an efficient way to use resources, there are a few limitations on their use: les· You can only use rack optimized connections to send data to and from discrete I/O modules. a Analog I/O requires direct connections. s · Rack optimized connections can contain I/O data il: and status information only. Additional module information, such as diagnostics, is not available through a rack-optimized connection. a · All data is sent at the same time at the RPI rate of Em the 1794-AENT adapter. See the EtherNet/IP Performance and Application Guide, publication number ENET-AP001, for more information on connections. Publication 1794-UM006A-EN-P - July 2001 About the 1794-AENT Adapter 1-5 Mixing Rack Optimized and Direct Connections You can mix communication formats for different I/O modules communicating through the same adapter. I/O modules set up to use rack optimization will communicate at the rate of the RPI (requested packet interval) configured for the 1794-AENT adapter. I/O modules configured for direct communication will communicate at their own set RPIs and ignore the 1794-AENT adapter's RPI. What's Next? n The following chapter describes how to physically install the cambia.c 1794-AENT adapter and connect it to the EtherNet/IP network. Email: sales@ Publication 1794-UM006A-EN-P - July 2001 1-6 About the 1794-AENT Adapter cambia.cn Email: sales@ Publication 1794-UM006A-EN-P - July 2001 2 Chapter Installing the 1794-AENT Adapter What This Chapter Contains This chapter describes how to physically install the 1794-AENT adapter on the DIN rail and connect it to the EtherNet/IP network. ambia.cn Identifying Module Email: sales@c Components The following table lists where to find specific information. Topic Identifying Module Components Mounting the Adapter on a DIN Rail Before Installing Modules Mounting (or Replacing) the Adapter on an Existing System Wiring Mounting Dimensions See Page 2-1 2-2 2-3 2-5 2-6 Use the following illustration to identify the external features of the FLEX I/O EtherNet/IP adapter. 1 8 2 3 7 6 4 5 Component Identification 1 EtherNet/IP Adapter Module 2 Indicators 3 MAC ID Label 4 Network cable RJ-45 connector (underside) 5 Module locking tab location 6 +24V dc connections 7 24V common connections 8 Flexbus connector 1 Publication 1794-UM006A-EN-P - July 2001 2-2 Installing the 1794-AENT Adapter Mounting the Adapter on a DIN Rail Before Installing Modules Use the following procedure to mount the adapter on a new system before any I/O modules have been installed. A B nC .c 1. Position the EtherNet/IP adapter module (A) on a 35 x 7.5mm DIN ia rail (B) (A-B pt. no. 199-DR1; 46277-3; EN 50022) with the bottom rotated outward at a slight angle. b 2. Hook the lip on the top rear of the adapter (A) onto the top of the m DIN rail (B), and rotate the bottom of the adapter module onto the rail. ca 3. Press the adapter module down onto the DIN rail until flush. Locking tab (C) will snap into position and lock the adapter module to the DIN rail. s@ 4. If the adapter module does not lock in place, use a screwdriver or similar device to pull the locking tab down while pressing the le adapter module flush onto the DIN rail. Then release the locking tab to secure the adapter module in place. If necessary, push up on athe locking tab. il: s5. Connect the adapter wiring as shown under "Wiring" later in this Ema document. Publication 1794-UM006A-EN-P - July 2001 Installing the 1794-AENT Adapter 2-3 Mounting (or Replacing) the Adapter on an Existing System Use the following procedure to mount or replace the adapter on an existing system. 1. If present, disconnect the RJ-45 connector from the bottom of the old adapter. 2. Disconnect any wiring jumpered to the adjacent terminal base. 3. Using a screwdriver or similar tool, open the locking tab on the back of the adjacent I/O module and remove the I/O module from its terminal base. n 4. Push the flexbus connector toward the right side of the terminal .c base to unplug the backplane connection. iaTerminal base of I/O module cambadjacent to 1794-AEN adapter 31244-M ales@ ATTENTION Make certain that the flexbus connector is completely clear of the adapter. The slide must be completely to the right and the raised spot on the slide visible. il: s!5. Release the locking tab on the back of the old adapter module and a remove the old adapter from its terminal base. m 6. Before installing the new adapter, note the notch on the right rear of the adapter. This notch accepts the hook on the terminal base of E the I/O module mounted next to the adapter. The notch is open at the bottom. The hook and adjacent connection point keep the terminal base and adapter tight together, reducing the possibility of a break in communication over the backplane. Publication 1794-UM006A-EN-P - July 2001 2-4 Installing the 1794-AENT Adapter 7. Complete the adapter mounting as shown below. Push down and in at the same time to lock the adapter on the DIN rail. When the adapter is locked onto the DIN rail, gently push the flexbus connector into the adapter to complete the backplane. .cn C 31244-M ia 8. If the adapter module does not lock into place, use a screwdriver b or similar device to pull locking tab C down while pressing the adapter module flush onto the DIN rail. Then release the locking m tab to lock the adapter module in place. If necessary, push up on ca the locking tab to lock. Email: sales@ 9. Reinstall the I/O module onto its terminal base unit. Publication 1794-UM006A-EN-P - July 2001 Wiring Installing the 1794-AENT Adapter 2-5 WARNING ! If you connect or disconnect the Ethernet cable with power applied to the adapter or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. B D A mbia.cn C E ca 31246-M 1. Connect the Ethernet network cable to the RJ-45 connector (A) on the underside of the adapter. il: sales@ A a 31247-M Em IMPORTANT We recommend connecting the module to the network via a 100MB full duplex switch, which will reduce collisions and lost packets and increase network bandwidth. For detailed EtherNet/IP connection information, see the following publications: · EtherNet/IP Performance and Application Guide, publication ENET-AP001 · EtherNet/IP Media Planning and Installation Guide, publication number ENET-IN001 Publication 1794-UM006A-EN-P - July 2001 2-6 Installing the 1794-AENT Adapter 2. Connect 24V common to the left side of the upper connector, terminal B. IMPORTANT When connecting wiring, torque terminal screws B, C, D and E to 5-7 inch-pounds. 3. Connect +24V dc input power to the left side of the lower connector, terminal C. Mounting Dimensions 4. Use connectors D and E to pass 24V common (D) and 24V dc n power (E) to the next module in the series). ia.c IMPORTANT The 1794-AENT requires a minimum load of approximately 100mA (e.g., two FLEX I/O modules) on the Flex rail. camb inches (millimeters) les@ 3.2 a(80) s3.4 Email: (87) 3.7 (94) 1794-AENT B 2.0 (50) 1.2 (30) A 3.4H x 3.7W x 2.7D (87H x 94W x 69D) A = DIN rail B = Secure DIN rail approximately every 200mm What's Next? The following chapter describes how to configure the adapter to communicate on your EtherNet/IP network by providing an IP address, Gateway address, and Subnet mask. Publication 1794-UM006A-EN-P - July 2001 3 Chapter Configuring the 1794-AENT Adapter for Your EtherNet/IP Network What This Chapter Contains Before you can use your 1794-AENT adapter in an EtherNet/IP network you must configure it with an IP address, and optional Gateway address and Subnet mask. This chapter describes these n configuration requirements and the procedures for providing them. .c There are several way you can do this: ia 1. Using the Rockwell BootP utility that ships with RSLogix 5000 software. You can also use this utility to reconfigure a device b whose IP address is unknown or must be changed. 2. Using a third party BootP server. am 3. Having your network administrator configure the adapter via the c network server. The following table lists where to find specific information within this @ chapter. s For information about le Configuration Requirements IP Address aGateway Address sSubnet Mask il:Using the Rockwell BootP Utility Using Force IP Renew To Reconfigure a Device a Saving the Relation List Using a Third Party BootP Server Em Using DHCP Software to Configure Your Adapter See page 3-2 3-2 3-3 3-4 3-6 3-8 3-10 3-11 3-13 1 Publication 1794-UM006A-EN-P - July 2001 3-2 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network Configuration Requirements Before you can use your 1794-AENT adapter, you must configure its IP address, and optionally, its subnet mask and gateway address. You can use the Rockwell BootP utility to perform the configuration. You can also use generic BootP software or, within some limitations, a DHCP server. IMPORTANT When using the BootP protocol, you must enter the Ethernet hardware address of your adapter. Rockwell Ethernet Address (MAC) assigns each 1794-AENT adapter a unique 48-bit hardware address at the factory. The address is printed on a label on the front of your 1794-AENT n adapter as shown in the figure at left. It consists of .c six hexadecimal digits separated by colons. This address is fixed by the hardware and cannot be ia changed. If you change or replace the 1794-AENT adapter, you b must enter the new Ethernet hardware address of the cam adapter when you configure the new adapter. IP Address @ The IP address identifies each node on the IP network (or system of s connected networks). Each TCP/IP node on a network (including the le 1794-AENT adapter) must have a unique IP address. aThe IP address is 32 bits long and has a Net ID part and a Host ID spart. Networks are classified A, B, C, (or other). The class of the network determines how an IP address is formatted. il: 0 aClass A 0 0 mClass B 1 0 E0 89 Net ID Net ID 31 Host ID 16 17 31 Host ID 24 25 31 Class C 1 1 0 Net ID Host ID You can distinguish the class of the IP address from the first integer in its dotted-decimal IP address as follows: Range of first integer 0 -127 128 -191 Class A B Range of first integer 192 - 223 224 - 255 Class C other Publication 1794-UM006A-EN-P - July 2001 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network 3-3 Each node on the same physical network must have an IP address of the same class and must have the same Net ID. Each node on the same network must have a different Host ID thus giving it a unique IP address. IP addresses are written as four decimal integers (0-255) separated by periods where each integer gives the value of one byte of the IP address. EXAMPLE For example, the 32-bit IP address: n 10000000 00000001 00000000 00000001 is written as 128.1.0.1. .c TIP Contact your network administrator or the Network Information Center for a unique fixed IP ia address to assign to your module. b Tip cam Gateway Address The Gateway Address is the default address of a network. It provides @ a single domain name and point of entry to the site. Gateways connect individual physical networks into a system of networks. s When a node needs to communicate with a node on another network, le a gateway transfers the data between the two networks. The following figure shows gateway G connecting Network 1 with Network 2. saA ail: 128.1.0.1 Network 1 Em B C 128.1.0.2 G 128.2.0.3 128.2.0.1 128.2.0.2 Network 2 When host B with IP address 128.2.0.1 communicates with host C, it knows from C's IP address that C is on the same network. In an Ethernet environment, B can then resolve C's IP address into a hardware address (MAC address) and communicate with C directly. Publication 1794-UM006A-EN-P - July 2001 3-4 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network When host B communicates with host A, it knows from A's IP address that A is on another network (the net IDs are different). In order to send data to A, B must have the IP address of the gateway connecting the two networks. In this example, the gateway's IP address on Network 2 is 128.2.0.3. The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be used by hosts on Network 1 and the second must be used by hosts on Network 2. To be usable, a host's gateway must be addressed EXAMPLE using a net ID matching its own. .cn Subnet Mask ia The Subnet Mask is used for splitting IP networks into a series of subgroups, or subnets. The mask is a binary pattern that is matched b up with the IP address to turn part of the Host ID address field into a field for subnets. am Take Network 2 (a Class B network) in the previous example and add c another physical network. Selecting the following subnet mask would add two additional Net ID bits allowing for four physical networks: @ 11111111 11111111 11000000 00000000 = 255.255.192.0 sThese two bits of the Host ID le used to extend the Net ID aTwo bits of the Class B host ID have been used to extend the Net ID. sEach unique combination of bits in the part of the Host ID where Email:subnet mask bits are 1 specifies a different physical network. Publication 1794-UM006A-EN-P - July 2001 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network 3-5 The new configuration is: A 128.1.0.1 Network 1 128.1.0.2 G B n 128.2.64.1 C 128.2.64.2 Network 2.1 128.2.64.3 ia.c D b 128.2.128.1 E 128.2.128.2 Network 2.2 G2 128.2.128.3 cam A second network with Hosts D and E has been added. Gateway G2 connects Network 2.1 with Network 2.2. Hosts D and E will use Gateway G2 to communicate with hosts not on Network 2.2. Hosts B and C will use Gateway G to communicate with hosts not on @ Network 2.1. When B is communicating with D, G (the configured Email: sales Gateway for B) will route the data from B to D through G2. Publication 1794-UM006A-EN-P - July 2001 3-6 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network Using the Rockwell BootP Utility The Rockwell BootP utility is a stand alone program that incorporates the functionality of standard BootP software with a user friendly graphical interface. It is located in the Utils directory on the RSLogix 5000 installation CD. The 1794-AENT adapter must have BootP enabled (factory default) to use the utility. To configure your adapter using the BootP utility, perform the following steps: 1. Run the BootP software. In the BOOTP Request History panel you will see the hardware addresses of devices issuing BootP cambia.cn requests. il: sales@ 2. Double-click on the hardware address of the device you want to configure. You will see the New Entry pop-up window with the Ema device's Ethernet Address (MAC). 3. Enter the IP Address, Subnet Mask, and Gateway you want to assign to the device, and click on OK. Publication 1794-UM006A-EN-P - July 2001 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network 3-7 The device will be added to the Relation List, displaying the Ethernet Address (MAC) and corresponding IP Address, Subnet Mask, and Gateway (if applicable). cambia.cn 4. If you want to permanently assign this configuration to the device, highlight the device and click on the Disable BOOTP button. @ When power is recycled to the device, it will use the configuration s you assigned and not issue a BootP request. le Note: To enable BootP for a device that has had BootP disabled, Email: sahighlight the device and click on the Enable BOOTP button. Publication 1794-UM006A-EN-P - July 2001 3-8 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network Using Force IP Renew To Reconfigure a Device The Force IP Renew feature can be used to reconfigure a device that has Bootp disabled. This can be useful: · if you do not know the IP address of a configured device (e.g., the address is not written on the label or the label is missing), or · if you know the IP address but want to change the configuration. n To use this feature perform the following steps: cambia.c 1. Connect the device to your network and run the Bootp utility. ail: sales@ 2. Click on the New button. The New Entry pop-up window will Em open. 3. Enter the fixed Ethernet Address (MAC) of your device. Publication 1794-UM006A-EN-P - July 2001 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network 3-9 4. Enter the IP Address, Subnet Mask, and Gateway you want to assign to the device, and click on OK. The device will appear in the Relation List. cambia.cn 5. Select the device from the Relation List and click on the Force IP Renew button. Then cycle power to the device. s@ The device will perform its power-up diagnostics and issue a Bootp request. The Bootp utility will respond by assigning it the Email: sale configuration you just specified. The device is now able to communicate over the network, using the new configuration. Publication 1794-UM006A-EN-P - July 2001 3-10 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network Saving the Relation List You can save the Relation List to be used later. To save the Relation List perform the following steps: cambia.cn @ 1. Select Save As... from the File menu. You will see the following Email: sales window. 2. Select the folder you want to Save in: 3. Enter a File name for the Relation List (e.g., "Control System Configuration") and click on Save. You can leave the Save as type at the default setting: "Bootp Config Files (*.bpc)". Publication 1794-UM006A-EN-P - July 2001 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network 3-11 You can then open the file containing the Relation List at a later session. mbia.cn Using a Third Party a BootP Server Email: sales@c EXAMPLE The following is an example BootP tab file that can be used with a third party BootP server: # Example /etc./bootptab: database for bootp server (/etc./bootpd). # # Format: # nodename:tag=value:tag=value: . . . .:tag=value # # first field nodename (hostname) of terminal followed by colon # (should be full domain name) # # Blank lines and lines beginning with '#' are ignored. # Make sure you include a colon and a backslash to continue a line. # Don't put any spaces in the tagvalue string. # The ht tag MUST precede the ha tag. # # The options below are specified as tag=value and delimited by colons # These are the options used by the 1794-AENT adapter: # # gw gateway IP address # ha hardware address (link level address) (hex) # ht hardware type (either) (must precede the ha tag) # ip IP address # sm network subnet mask # tc template for common defaults (should be the first option listed) # # vm vendor magic cookie selector (MUST be rfc1048 for 1794-AENT) # Publication 1794-UM006A-EN-P - July 2001 3-12 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network #- # default values for 1794-AENT icp.defaults:\ ht=ether:\ vm=rfc1048:\ sm=255.255.254.0:\ gw=130.151.132.1 #- zappa0:\ tc=icp.defaults:\ ha=0000bc03404f:\ ip=130.151.132.121 zappa1:\ tc=icp.defaults:\ ha=0000bc034073:\ ip=130.151.132.122 zappa2:\ tc=icp.defaults:\ ha=0000bc034022:\ ip=130.151.132.123 cambia.cn To use a third party BootP server to configure the 1794-AENT adapter @ perform the following steps: s 1. Access and open the BootP tab file using a text editor. le 2. Enter the IP address you want to use for your adapter. If you need amore information on setting IP addresses, refer to page 3-2. s3. Use the text editor to enter the Ethernet hardware address il: (MAC ID) of your adapter. You must enter all digits, including zeroes. a 4. Enter the Gateway Address. If you need more information on assigning gateway addresses, refer to page 3-3. Em 5. Enter the Subnet Mask. If you need more information on selecting subnet masks, refer to page 3-4. 6. After you have entered all the configuration data, save the file in a directory where the BootP server can access it. Publication 1794-UM006A-EN-P - July 2001 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network 3-13 Using DHCP Software to Configure Your Adapter DHCP (Dynamic Host Configuration Protocol) software automatically assigns IP addresses to client stations logging onto a TCP/IP network. DHCP is based on BootP and maintains some backward compatibility. The main difference is that BootP was designed for manual configuration, while DHCP allows for dynamic allocation of network addresses and configurations to newly attached devices. Be cautious about using DHCP software to configure your adapter. A BootP client, such as the 1794-AENT adapter, can boot from a DHCP server only if the DHCP server is specifically written to also handle BootP queries. This is specific to the DHCP software package you use. n Check with your system administrator to see if your DHCP package supports BootP commands and manual IP allocation. ! cambia.c ATTENTION The 1794-AENT adapter must be assigned a fixed network address. The IP address of this adapter must not be dynamically provided. Failure to observe this precaution may result in unintended machine motion or loss of process control. Email: sales@ What's Next? The following chapter describes an example application in which you configure discrete I/O using a rack optimized connection. Publication 1794-UM006A-EN-P - July 2001 3-14 Configuring the 1794-AENT Adapter for Your EtherNet/IP Network cambia.cn Email: sales@ Publication 1794-UM006A-EN-P - July 2001 4 Chapter Using Rack Optimized Discrete I/O About the Example In this example a ControlLogix processor communicates with FLEX Application I/O via the 1794-AENT adapter using a rack optimized connection. The processor reads data from all digital input modules and sends data to all digital output modules configured in a rack connection simultaneously. .cn What you will do Set Up the Hardware ia Create the Example Application b Configure the I/O Add the Local EtherNet/IP Bridge to the I/O Configuration m Add the FLEX I/O Adapter to the I/O Configuration Add the FLEX I/O Modules to the I/O Configuration ca Add the Digital Input Module See page 4-2 4-3 4-4 4-4 4-6 4-8 4-8 Add the Digital Output Module Edit the Controller Tags @ Create the Ladder Program s Download the Program to the Controller Email: sale Test the Example Application 4-10 4-12 4-13 4-14 4-15 1 Publication 1794-UM006A-EN-P - July 2001 4-2 Using Rack Optimized Discrete I/O Set Up the Hardware In this example, a ControlLogix chassis contains the Logix 5550 processor in slot 0 and a 1756-ENBT bridge module in slot 1. The 1794-AENT adapter is mounted on a DIN rail with a 1794-IB16 digital input module and 1794-OB16 digital output module. You will also need a power supply (not shown) for the FLEX I/O. Slot 0 1 1794-AENT 130.130.130.3 FLEX I/O Local Chassis Logix5550 Controller Slot 0 1 Data n 1756-ENBT .c 130.130.130.2 Switch ia 130.130.130.1 1794-OB16 Digital Output 1794-IB16 Digital Input bProgramming cam Terminal To work along with this example set up your system as shown above. s@ · Note that in the example application, the Logix5550 controller leand 1756-ENBT module are assumed to be in the slots shown above. a· Verify the IP addresses for your programming terminal, s1756-ENBT module, and 1794-AENT adapter. il: · Verify the position (slot) of the I/O modules on the DIN rail. a · Verify that all wiring and cabling is properly connected. m · Make sure your communication driver (e.g., AB_ETH-1) is E configured in RSLinx as described in Appendix C. Publication 1794-UM006A-EN-P - July 2001 Create the Example Application Using Rack Optimized Discrete I/O 4-3 Perform the following steps to create the example application: 1. Start RSLogix5000. The RSLogix 5000 Main Window will open. ambia.cn 2. From the File menu, select New. The New Controller pop-up c window will open. Email: sales@ 3. Enter an appropriate Name for the Controller, e.g., "FLEX_IO_Controller." 4. Select the correct Chassis Type and Slot number of the Logix5550 controller, and the folder where you want to save the RSLogix 5000 file (Create In). The Description is optional. 5. Click on OK. Publication 1794-UM006A-EN-P - July 2001 4-4 Using Rack Optimized Discrete I/O Configure the I/O You now add the FLEX I/O modules to the controller's I/O configuration. To do this you first add the local 1756-ENBT module to the I/O configuration. Next you add the 1794-AENT adapter as a "child" of the 1756-ENBT module. Then you add the I/O modules as "children" of the 1794-AENT adapter. IMPORTANT Click on the Help buttons on the configuration screens shown in this section if you need assistance in selecting and setting the parameters. .cn Add the Local EtherNet/IP Bridge to the I/O Configuration ia 1. Select the IO Configuration folder in the project window and camb click the right mouse button. Email: sales@ The following pop-up window will open. 2. Click on New Module. Publication 1794-UM006A-EN-P - July 2001 Using Rack Optimized Discrete I/O 4-5 The Select Module Type window will open. mbia.cn 3. Select the 1756-ENBT EtherNet/IP Bridge and click on OK. The ca Module Properties window will open. ail: sales@ 4. Enter or select the following parameters: Name, IP Address, Slot, m and Electronic Keying. We used the following values: E Name Local_ENB IP Address 130.130.130.2 Slot 1 Electronic Keying Compatible Module 5. Click on Finish to accept the configuration. Publication 1794-UM006A-EN-P - July 2001 4-6 Using Rack Optimized Discrete I/O Add the FLEX I/O Adapter to the I/O Configuration Next, you must add the 1794-AENT adapter as a "child" of the local 1756-ENBT module. bia.cn 1. In the Project window, right click on the local 1756-ENBT module m under the I/O Configuration folder and select New Module from ca the pop-up window. The Select Module Type window will open. Email: sales@ 2. Select the 1794-AENT/A Ethernet adapter from the list and click on OK. Publication 1794-UM006A-EN-P - July 2001 Using Rack Optimized Discrete I/O 4-7 The Module Properties window will open. ia.cn 3. Enter or select the following parameters (the values we used are b listed in the table): m Name ca IP Address FLEX_IO_Adapter 130.130.130.3 Comm Format Chassis Size @ Electronic Keying Rack Optimization 8 (default) Compatible Module Email: sales 4. Click on Next. The following page will open: 5. Verify that the Requested Packet Interval (RPI) is appropriate for your system (10ms for this example). This will be used for the rack optimized connection to the I/O modules. 6. Click on the Finish button to accept the configuration. Publication 1794-UM006A-EN-P - July 2001 4-8 Using Rack Optimized Discrete I/O The 1794-AENT adapter will appear indented under the local 1794-ENBT in the I/O Configuration folder. Add the FLEX I/O Modules to the I/O Configuration n You must now add the FLEX I/O modules to the I/O Configuration .c List under the 1794-AENT adapter. In this example, you will add a a 17946-IB16 digital input module and ia a 1756-OB16 digital output module with standard configurations. Use these steps as a guide when you are configuring different I/O b modules for your system. m TIP This example application uses the I/O modules' a default configurations. For more information see c publications 1794-IN071 and 1794-IN072. Email: sales@ Add the Digital Input Module 1. Right click on the remote 1794-AENT adapter under the I/O Configuration folder and select New Module. Publication 1794-UM006A-EN-P - July 2001 Using Rack Optimized Discrete I/O 4-9 2. The Select Module Type window will open. mbia.cn 3. Select the 1794-IB16/A digital input module from the list and click ca on OK. The Module Properties window will open. mail: sales@ 4. Enter or select the following parameters (the values we used are E listed in the table): Name Slot Comm Format Electronic Keying FLEX_Digital_Input 0 Rack Optimization Compatible Module 5. Click on the Finish button to save the configuration. Publication 1794-UM006A-EN-P - July 2001 4-10 Using Rack Optimized Discrete I/O The digital input module will appear in the I/O configuration indented under the 1794-AENT adapter. cambia.cn Add the Digital Output Module 6. Right click on the 1794-AENT adapter and again select New Email: sales@ Module. The Select Module Type window will open. 7. Select the 1756-OB16/A digital output module from the list. Publication 1794-UM006A-EN-P - July 2001 Using Rack Optimized Discrete I/O 4-11 The Module Properties window will open. bia.cn 8. Enter or select the following parameters (the values we used are listed in the table): am Name c Slot FLEX_Digital_Output 1 Comm Format Electronic Keying Rack Optimization Compatible Module s@ 9. Click on the Finish button to accept the configuration. The I/O le Configuration in the Project window should look similar to the one Email: sashown below. Publication 1794-UM006A-EN-P - July 2001 4-12 Using Rack Optimized Discrete I/O Edit the Controller Tags When you add modules to the I/O configuration the system creates tags for those modules to use in the application program. For the example application you need to add one more Controller Tag. Tags created by the system Enter the new tag here 1. Double-click on the Controller Tags folder in the project window. The Controller Tags window will open. You will see the tags cambia.cn created for the 1794-AENT and digital I/O modules. il: sales@ 2. Make sure the Edit Tags tab at the bottom of the Controller Tags window is selected and create the following tag: a Tag Em Parts_Count Type Counter Publication 1794-UM006A-EN-P - July 2001 3. Close the Controller Tags window. Using Rack Optimized Discrete I/O 4-13 Create the Ladder Program Next create the example ladder program to test the IO. n 1. Double-click on Main Routine under the Main Program folder, .c and enter the following ladder program, using the tags previously cambia created. Email: sales@ 2. Save the program. Publication 1794-UM006A-EN-P - July 2001 4-14 Using Rack Optimized Discrete I/O Download the Program to the Controller To download the program to the controller do the following: 1. Click on the Communications menu and select Who Active. The Who Active window will open (Your window will show the drivers and devices you have installed). cambia.cn les@ 2. Select your Ethernet driver (e.g., AB_ETH-1) and expand the tree through the backplane of the local ControlLogix chassis. sa3. Highlight the Logix 5550 controller and click on the Download Email: button. You will see a message similar to the following: 4. Click on the Download button. The program will be downloaded to the controller. 5. Minimize RSLogix5000. Publication 1794-UM006A-EN-P - July 2001 Using Rack Optimized Discrete I/O 4-15 Test the Example Application You will test the example application by using a momentary switch to simulate a parts sensor. 1. Remove power from the FLEX I/O and wire inputs 0 and 2 of the the 1794-IB16 FLEX I/O input module as shown in the following figure: Reset Count .cn + bia 24V 02 16 (COM) 1794-IB16 cam 2. Restore power to the FLEX I/O. 3. Restore the RSLogix5000 software and place the controller in Run mode. s@ 4. Repeatedly press and release the momentary switch at Input 0 (Count) on the 1794-IB16 input module. Each time you press the le switch you should see the Parts_Count accumulated value increment on the screen and the LEDs of the 1794-OB16 output amodule increment in binary. il: s Accumulated Value will increment and move to Output a Allen-Bradley Em 24 VDC SOURCE OUTPUT 1794±OB16 2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 LEDs on Output Module will increment in binary. 5. Press and release the momentary switch at Input 2 (Reset) on the 1794-IB16 input module. You should see the accumulated value of the Parts_Count reset to zero and all of the LEDs on the 1794-OB16 output module turn off. Publication 1794-UM006A-EN-P - July 2001 4-16 Using Rack Optimized Discrete I/O TIP Refer to the FLEX I/O Digital I/O Modules Installation Instructions, publications 1794-IN071 and 1794-IN072, for assistance in wiring and debugging the I/O modules. This completes the Rack Optimized Discrete I/O example. What's Next? The following chapter describes an example application in which you add an analog output adapter to the I/O configuration using a direct cambia.cn connection. Email: sales@ Publication 1794-UM006A-EN-P - July 2001 5 Chapter Using Analog I/O with Direct Connection About the Example In this example you add analog input and output modules to the Email: sales@cambia.cn Application FLEX I/O configured with two digital I/O modules in the previous chapter. Analog modules default to direct connection, so you will open a direct connection to each analog module while still using a single rack optimized connection for the two digital I/O modules. To test the system, the example of the previous chapter is modified to send a signal to one of the analog output channels and read the signal back in through one of the analog input channels. What you will do Set Up the Hardware Create the Example Application Add the Analog Modules to the I/O Configuration Add the Analog Input Module to the I/O Configuration Add the Analog Output Module to the I/O Configuration Edit the Controller Tags Modify the Ladder Program Download the Program Test the Example Application See page 5-2 5-3 5-4 5-4 5-7 5-11 5-12 5-13 5-14 1 Publication 1794-UM006A-EN-P - July 2001 5-2 Using Analog I/O with Direct Connection Set Up the Hardware Change the system hardware setup of the previous chapter to that shown below, adding the FLEX analog input and output modules to the DIN rail with the 1794-AENT adapter and digital I/O modules. Local Chassis Slot 0 1 1794-AENT 130.130.130.3 FLEX I/O Slot 0 1 2 3 Data Logix5550 Controller 1756-ENBT .cn 130.130.130.2 Switch 130.130.130.1 1794-OB16 1794-OF41 Digital Output Analog Output 1794-IB16 1794-IF41 Digital Input Analog Input bia Programming camTerminal · Note that in the example application, the Logix5550 controller and 1756-ENBT module are in the slots shown above in the @ ControlLogix chassis. s · Verify that the IP addresses for the 1756-ENBT module, le1794-AENT adapter, and programming terminal are correct. a· Verify the position (slot) of the I/O modules on the DIN rail. s· Verify that all wiring and cabling is properly connected. il: · Make sure you have your communication driver a (e.g., AB_ETH-1) is configured in RSLinx as described in Em Appendix C. Publication 1794-UM006A-EN-P - July 2001 Create the Example Application Using Analog I/O with Direct Connection 5-3 Perform the following steps to create the example application: 1. Start RSLogix5000. The RSLogix 5000 Main Window will open. Open cambia.cn 2. Open the project file from the previous chapter (i.e., Email: sales@ "FLEX_IO_Controller"). 3. Save the file using a different name (e.g., "FLEX_IO_Controller_2"). Publication 1794-UM006A-EN-P - July 2001 5-4 Using Analog I/O with Direct Connection Add the Analog Modules to the I/O Configuration You must now add the analog I/O modules to the I/O Configuration. In this example, you add a 1794-IF41 analog input module and a 1794-OF41 analog output module. Use these steps as a guide when you are configuring different I/O modules for your system. IMPORTANT Click on the Help buttons on the configuration screens shown in this section if you need assistance in selecting and setting the parameters. cambia.cn Add the Analog Input Module to the I/O Configuration s@ 1. Right click on the 1794-AENT adapter under the I/O Configuration le folder and select New Module from the pop-up window. The Email: saSelect Module Type window will open. Publication 1794-UM006A-EN-P - July 2001 2. Select the 1794-IF41/A analog input module from the list and click on OK. Using Analog I/O with Direct Connection 5-5 The Module Properties window will open. bia.cn 3. Enter the following parameters: m Name Slot ca Comm Format FLEX_Analog_Input 2 Input Data(1) Electronic Keying Compatible Module (1) All analog Comm Formats use direct connection. The default here is Input Data. Email: sales@ 4. Click on the Next button. The following page will open: 5. This window allows you to adjust the Requested Packet Interval (RPI) to meet your system's requirements. For this example you can leave it at the default 50 ms rate shown above. This RPI will be used for the direct connection to this analog module. The two rack connected digital I/O modules will continue to communicate at the RPI of the rack connection. Publication 1794-UM006A-EN-P - July 2001 5-6 Using Analog I/O with Direct Connection 6. Click on Next. This page is used during online monitoring but not during initial configuration. . bia.cn 7. Click on Next to move to the channel configuration page. m The choices available on the channel configuration page vary a according to the module being configured. The page below opens c for the 1794-IF41 module. Email: sales@ 8. Use the pull-down list to set the Voltage/Current Range for Channel 0 to "0 to 10V - Binary". (This range allows you to easily monitor the output with a voltmeter when you test the application.) You can leave the other channels at their default values. 9. Click on Finish to save the configuration. Publication 1794-UM006A-EN-P - July 2001 Using Analog I/O with Direct Connection 5-7 The I/O Configuration in the Project Window should now look similar to the one shown below. cambia.cn Add the Analog Output Module to the I/O Configuration @ 1. Right click on the 1794-AENT adapter under the I/O Configuration s folder and select New Module from the pop-up window. The Email: sale Select Module Type window will open. 2. Select the 1794-OF41/A analog output module from the list and click on OK. Publication 1794-UM006A-EN-P - July 2001 5-8 Using Analog I/O with Direct Connection The Module Properties window will open. bia.cn 3. Enter the following parameters: m Name Slot ca Comm Format FLEX_Analog_Output 3 Output Data(1) Electronic Keying Compatible Module (1) All analog Comm Formats use direct connection. The default here is Output Data. Email: sales@ 4. Click on the Next button. The following page will open: 5. This window allows you to adjust the Requested Packet Interval (RPI) to meet your system's requirements. For this example you can leave it at the default 50ms rate shown above. This RPI will be used for the direct connection to this analog module. The other analog module will communicate at the RPI selected for its connection. The two rack connected digital I/O modules will continue to communicate at the RPI of their rack connection. Publication 1794-UM006A-EN-P - July 2001 Using Analog I/O with Direct Connection 5-9 6. Click on Next to open the next page. This page is used during online monitoring but not during initial configuration. . cambia.cn 7. Click on Next. The page below opens for the 1794-OF41 module. il: sales@ For this example you can leave these parameters at the default a setting shown above. For an explanation of these parameters click on the Help button. Em 8. Click on the Next button. Publication 1794-UM006A-EN-P - July 2001 5-10 Using Analog I/O with Direct Connection The channel configuration page will open. bia.cn 9. Use the pull-down list to set the Voltage/Current Range for Channel 0 to "0 to 10V - Binary" to match the input configuration m of the 1794-IF41 module. You can leave the other parameters at their default values. ca 10.Click on Finish to save the configuration. The I/O Configuration Email: sales@ should now look similar to the one shown below. Publication 1794-UM006A-EN-P - July 2001 Edit the Controller Tags Using Analog I/O with Direct Connection 5-11 When you add modules to the I/O configuration the system creates Controller Tags for those modules. For the example program you need to add one more Controller Tag. New tags created by the system for the analog modules 1. Double-click on the Controller Tags folder in the project window. cambia.cn Note that new tags have been added for the analog I/O modules. ales@ 2. Make sure the Edit Tags tab at the bottom of the Controller Tags swindow is selected and create the following tag: il: Tag Ema Analog_Test_Signal Type Timer Publication 1794-UM006A-EN-P - July 2001 5-12 Using Analog I/O with Direct Connection Modify the Ladder Program Make the following change to the ladder program to test the new configuration. .cn 1. Double-click on Main Routine under the Main Program folder, cambia and add rungs 3 and 4 to the ladder program. Email: sales@ 2. Save the program. Publication 1794-UM006A-EN-P - July 2001 Using Analog I/O with Direct Connection 5-13 Download the Program To download the program to the controller do the following: 1. Click on the Communications menu and select Who Active. The Who Active window will open (Your window will display the drivers and devices you have configured on your system). cambia.cn s@ 2. Select your Ethernet driver (e.g., AB_ETH-1) and expand the tree le through the backplane of the local ControlLogix chassis. a3. Highlight the controller and click on the Download button to sdownload the program to the Logix5550 controller. Email: You will see a message similar to the following: 4. Click on the Download button. The program will be downloaded to the controller. 5. Minimize RSLogix5000. Publication 1794-UM006A-EN-P - July 2001 5-14 Using Analog I/O with Direct Connection Test the Example Application Use the following procedure to test the operation of the FLEX analog input and output modules: 1. Connect analog output channel 0 on the 1794-OF41/A module to analog input channel 0 on the 1794-IF41/A input module. VR 23 n 1794-IF41 VR 23 1794-OF41 ia.c 2. Restore RSLogix5000 and place the controller in Run mode. b 3. Double-click on the Controller Tags folder and select the cam Monitor tab. il: sales@ 4. Monitor channel 0 of the 1794-IF41/A input module (FLEX_IO_Adapter:2.I.Ch0Data above). You should see the value a slowly rise to approximately 32000, reset to zero, start rising again, etc., as the output of the timer is received from the 1794-OF41/A Em output module. TIP Refer to the FLEX I/O Analog I/O Module Installation Instructions, publications 1794-IN037 and 1794-IN038, for assistance in wiring and debugging the I/O modules. This completes the Direct Connect Analog I/O example. Publication 1794-UM006A-EN-P - July 2001 LED Status Indicators A Appendix Interpreting the Status The faceplate of the 1794-AENT adapter is provided with LED Indicators indicators that display the Module Status, Network Status, and Link Status. Module Status Network Status Link Status cambia.cn The following tables describe the states of the LED status indicators: s@ Module Status le State Off saFlashing Green il: Green Flashing Red Ema Red Status No Power Standby Operational Minor Fault Major Fault Description Module does not have 24V DC power. Make sure power is being supplied to the module. Module not configured. Module operating correctly. A recoverable fault has been detected. This could be caused by an incorrect or inconsistent configuration. An unrecoverable fault has been detected. Recycle power to the module. If this does not clear the fault, replace the module. Flashing Red and Green Self Test Module performing power-up self test. 1 Publication 1794-UM006A-EN-P - July 2001 A-2 LED Status Indicators Network Status State Status Description Off Not Powered, Module is not powered, or does not No IP Address have an IP address. · Verify there is power and the module is correctly wired to the supply. · Make sure the module is configured Flashing Green Green Flashing Red Red Flashing Red and Green Link Status No Connections n CIP Connections .c Connection Timeout ia Duplicate IP b Address cam Self Test Module has obtained an IP address, but has no established connections. Module has an IP address and at least one established connection. One or more of the connections in which the module is the target has timed out. Module has detected that its IP address is already in use. Module performing power-up self test. State Off s@ Green Email: sale Flashing Green Status No data transmission Ready Data transmission in progress Description Module not ready to communicate. Module is ready to communicate. Module is communicating over the network. Publication 1794-UM006A-EN-P - July 2001 B Appendix 1794-AENT Adapter Web Pages Web Page Diagnostics The 1794-AENT adapter's Web pages offer extensive internal and network diagnostics. To view the Web pages, enter the adapter's IP address into Netscape or Microsoft Internet Explorer. You will see the cambia.cn following Web page: il: sales@ The adapter's Web pages provide the following information: a · Module Information · TCP/IP Configuration Em · Diagnostic Information Some examples of these pages are shown in the following figures. 1 Publication 1794-UM006A-EN-P - July 2001 B-2 1794-AENT Adapter Web Pages Module Information mbia.cn The Module Information page provides specific information about ca your AEN adapter, such as its serial number and firmware version. Email: sales@ TCP/IP Configuration The TCP/IP Configuration page provides the EtherNet/IP configuration of your adapter, including IP Address, Gateway Address, Subnet Mask, etc. Publication 1794-UM006A-EN-P - July 2001 Diagnostic Information 1794-AENT Adapter Web Pages B-3 bia.cn The 1794-AENT adapter provides advanced diagnostic information via this page. This information may be useful to systems administrators and other experienced information technology personnel. Several m examples of this information are shown in the following figures. ca Connection Manager Email: sales@ Publication 1794-UM006A-EN-P - July 2001 B-4 1794-AENT Adapter Web Pages Network Statistics Miscellaneous cambia.cn Email: sales@ Publication 1794-UM006A-EN-P - July 2001 Miscellaneous (continued) 1794-AENT Adapter Web Pages B-5 cambia.cn Email: sales@ Publication 1794-UM006A-EN-P - July 2001 B-6 1794-AENT Adapter Web Pages cambia.cn Email: sales@ Publication 1794-UM006A-EN-P - July 2001 C Appendix Configuring the RSLinx Ethernet Communication Driver What This Appendix Contains In order to communicate with your 1794-AENT adapters over your network you must configure the RSLinx Ethernet communication driver (AB_ETH). You can configure the AB_ETH driver with the IP n addresses of all the Ethernet devices on your system. You will need .c this driver to download the example application programs in this manual. ia The following table lists the contents of this appendix and where to b find specific information: For information about m Installing the RSLinx Software ca Configuring the AB_ETH Driver See page C-1 C-2 @ Installing the RSLinx Email: sales Software Use the following procedure to install RSLinx software on your computer. 1. Insert the CD in the CD-ROM drive. Note: The CD-ROM supports Windows Autorun. Once inserted into the CD-ROM drive, if you have Autorun configured, the installation will automatically start at the first setup screen. If Autorun is not configured for your CD-ROM drive, go to step 2. 2. From the Start menu, choose Run. You will see the Run pop-up window. 3. Type d:/setup (if it doesn't appear automatically), where d: is your CD-ROM driver letter. 4. Click on OK. You will see the progress bar, followed by the welcome screen. 1 Publication 1794-UM006A-EN-P - July 2001 C-2 Configuring the RSLinx Ethernet Communication Driver Configuring the AB_ETH Driver To configure the AB-ETH Ethernet communication driver perform the following steps: 1. Start RSLinx. mbia.cn 2. From the Communications menu, select Configure Drivers. ca 3. Click on the arrow to the right of the Available Driver Types box. The Available Driver Types list will appear. mail: sales@ 4. Select Ethernet Devices and click on Add/New. You will be E prompted to name the driver. 5. Select the default driver name (e.g., AB_ETH-1) or type in your own name and click on OK. Publication 1794-UM006A-EN-P - July 2001 Configuring the RSLinx Ethernet Communication Driver C-3 The Configure driver window will appear with the Station Mapping page open. mbia.cn 6. Click on Add New and enter the IP address or Host Name of your ca Ethernet device (e.g., 130.130.130.2, "Pump1", etc.). 7. Repeat step 6 for each additional Ethernet device you need to Email: sales@ access. 8. When you are done entering the IP addresses, click on Apply. Then click on OK to close the Configure driver window. Publication 1794-UM006A-EN-P - July 2001 C-4 Configuring the RSLinx Ethernet Communication Driver The new driver will appear in the list of configured drivers. (Your list will display the drivers you have configured on your workstation.) 9. Close RSLinx cambia.cn Email: sales@ Publication 1794-UM006A-EN-P - July 2001 Index A diagnostics about the 1794-AENT adapter 1-1 to 1-3 adapter features 1-1 control and information protocol (CIP) 1-2 to 1-3 mixing rack optimized and direct connections 1-5 producer/consumer model 1-3 rack optimized and direct connections 1-4 to 1-5 diagnostic information B-3 to B-5 module information B-2 TCP/IP configuration B-2 web pages B-1 to B-5 direct connection see analog I/O with direct connection requested packet interval (RPI) 1-3 what the 1794-AENT adapter does 1-2 E about this user manual P-1 to P-7 adapter features 1-1 n analog I/O with direct connection 5-1 to 5-14 .c add I/O module to configuration 5-4 to 5-10 create the example application 5-3 to 5-13 download program 5-13 ia edit controller tags 5-11 to 5-12 modify ladder program 5-12 to 5-13 b set up the hardware 5-2 test example application 5-14 am B c BootP see Rockwell Bootp utility using a third party BootP server 3-11 to 3-12 s@ C le change 3-8 change the configuration 3-8 a common techniques used in this manual P-1 s configuration requirements 3-2 to 3-5 gateway address 3-3 to 3-4 il: IP address 3-2 to 3-3 subnet mask 3-4 to 3-5 a configuring Ethernet communication drivers C-1 to C-4 m AB_ETH driver C-2 to C-4 installing the software C-1 E configuring the module 3-1 to 3-13 example applications about the example applications P-2 system components P-3 F finding more information P-4 Force IP Renew 3-8 to 3-9 G gateways 3-3 to 3-4 H how to use this manual P-2 to P-3 I I/O configuration analog I/O 5-4 to 5-10 digital I/O 4-8 to 4-11 FLEX I/O adapter 4-6 to 4-8 local ENBT module 4-4 to 4-5 if you do not know the IP address 3-8 installing the 1794-AENT adapter 2-1 to 2-6 interpreting status indicators A-1 to A-2 IP address 3-2 to 3-3 L ladder program 4-13 to 4-14, 5-12 to 5-13 using a third party BootP server 3-11 to 3-12 LED status indicators A-1 to A-2 using DHCP software 3-13 using the Rockwell BootP utility 3-6 to 3-11 link status A-2 module status A-1 control and information protocol (CIP) 1-2 to 1-3 network status A-2 controller tags link status indicator A-2 editing 4-12, 5-11 to 5-12 D DCHP software using to configure the module 3-13 M module status indicator A-1 Publication 1794-UM006A-EN-P - July 2001 2 Index N network status indicator A-2 P producer/consumer model 1-3 Rockwell BootP utility 3-6 to 3-11 Force IP Renew 3-8 to 3-9 saving the relation list 3-10 to 3-11 RSLinx communication drivers C-1 to C-4 AB_ETH driver C-2 to C-4 installing the software C-1 R S rack optimized and direct connections 1-4 to 1-5 mixing rack optimized and direct connections 1-5 rack optimized I/O 4-1 to 4-16 n add FLEX I/O adapter to I/O configuration 4-6 to 4-8 .c add local ENBT module to I/O configuration 4-4 to 4-5 add remote I/O modules to I/O configuration 4-8 to ia 4-11 create example application 4-3 to 4-14 b create ladder program 4-13 download program to controller 4-14 m edit controller tags 4-12 set up the hardware 4-2 a test example application 4-15 to 4-16 c reconfiguring a device 3-8 to 3-9 related publications P-4 Email: sales@ requested packet interval (RPI) 1-3 status indicators A-1 subnet mask 3-4 to 3-5 T terminology P-5 to P-7 W web pages B-1 to B-5 diagnostic information B-3 to B-5 module information B-2 TCP/IP configuration B-2 what the adapter does 1-2 who should use this manual P-1 Publication 1794-UM006A-EN-P - July 2001 How Are We Doing? Your comments on our technical publications will help us serve you better in the future. Thank you for taking the time to provide us feedback. You can complete this form and mail it back to us, visit us online at www.ab.com/manuals, or email us at RADocumentComments@ra.rockwell.com Pub. Title/Type FLEX I/O EtherNet/IP Adapter Module User Manual Cat. No. 1794-AENT Pub. No. 1794-UM006A-EN-P Pub. Date July 2001 Part No. 957445-30 Please complete the sections below. Where applicable, rank the feature (1=needs improvement, 2=satisfactory, and 3=outstanding). Overall Usefulness 1 2 3 How can we make this publication more useful for you? Completeness 123 (all necessary information is provided) .cn Can we add more information to help you? procedure/step illustration ia example guideline camb explanation definition feature other Technical Accuracy 1 2 3 (all provided information @ is correct) Can we be more accurate? text illustration ales Clarity 123 s (all provided information is easy to understand) How can we make things clearer? Email: Other Comments You can add additional comments on the back of this form. Your Name Location/Phone Your Title/Function Would you like us to contact you regarding your comments? ___No, there is no need to contact me ___Yes, please call me ___Yes, please email me at __________________________ ___Yes, please contact me via ________________________ Return this form to: Allen-Bradley Marketing Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705 Phone: 440-646-3176 Fax: 440-646-3525 Email: RADocumentComments@ra.rockwell.com Publication ICCG-5.21- January 2001 PN 955107-82 Other Comments PLEASE FASTEN HERE (DO NOT STAPLE) PLEASE REMOVE cambia.cn PLEASE FOLD HERE ail: sales@ BUSINESS REPLY MAIL FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH EmPOSTAGE WILL BE PAID BY THE ADDRESSEE NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES 1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705 cambia.cn Email: sales@ Back Cover cambia.cn Email: sales@ Publication 1794-UM006A-EN-P - July 2001 2 PN 957445-30 Copyright © 2001 Rockwell Automation. All rights reserved. Printed in USA.Acrobat Distiller 3.01 for Windows