AVEVATM ArchestrA Alarm Control Guide

� 2020 AVEVA Group plc and its subsidiaries. All rights reserved.
No part of this documentation shall be reproduced, stored in a ret rieval system, or transmitted by any means, electronic, mechanical, photocopying, rec ording, or otherwise, without the prior written permission of AVEVA. No liability is assumed with respect to the use of the information contained herein.
Although precaution has been taken in the preparation of this documentation, AVEVA assumes no responsibility for errors or omissions. The information in this documentation is subject to change without notice and does not represent a commitment on the part of AVEVA. The soft ware described in this documentation is furnished under a license agreement. This s oft ware may be used or copied only in accordance with the terms of such license agreement.
ArchestrA, Aquis, Avantis, Citect, DYNSIM, eDNA, EYESIM, InBatch, InduSoft, InStep, Int elaTrac, InTouch, OASyS, PIPEPHASE, PRiSM, PRO/II, PROV ISION, ROMeo, SIM4ME, S imCentral, SimSci, Skelta, SmartGlance, Spiral Software, Termis, WindowMaker, WindowViewer, and Wonderware are trademarks of AVEVA and/or its subsidiaries. An extensive listing of AVEVA trademarks can be found at: https://sw.aveva.com/legal. All other brands may be trademarks of their respective owners.
Publication date: Thursday, November 19, 2020
Contact Information
AVEVA Group plc High Cross Madingley Road Cam brid ge CB3 0HB. UK
https://sw.aveva.com/
For information on how to cont act sales and customer training, see https://sw.aveva.com/contact.
For information on how to cont act technical support, see https://sw.aveva.com/support.

AVEVATM ArchestrA Alarm Control Guide
Contents
Chapter 1 About the ArchestrA Alarm Control ................................................................ 11
About the ArchestrA Alarm Control Working with the ArchestrA Alarm Control .......................... 11 Client Modes .......................................................................................................................... 11
InTouch Alarm Manager .................................................................................................... 11 Current Alarms ............................................................................................................ 11 Recent Alarms and E vents ........................................................................................... 11
Alarm and E vent Storage ................................................................................................... 11 Switching Between Client Modes........................................................................................ 12 Using the Alarm Control in Industrial Graphics .......................................................................... 12 Alarm Acknowledgement ......................................................................................................... 12 Current Value and Quality Display ............................................................................................ 13 Working With Alarm Queries and Filters ................................................................................... 13 Alarm Queries......................................................................................................................... 13 Alarm Query Syntax when Register Using Galaxy_<GalaxyName> is Enabled ...................... 14 Alarm Filtering ........................................................................................................................ 15 Alarm Queries to Filters Translation .................................................................................... 15 Alarm Shelving ....................................................................................................................... 15 Shelving Alarms During Run Time ...................................................................................... 16 Unshelving Alarms During Run Time .................................................................................. 16 Alarm Hiding ........................................................................................................................... 16 Alarm Control Grid Freezing .................................................................................................... 16 Alarm Sorting.......................................................................................................................... 17 Support for a Redundant Historian Server ................................................................................. 17 Status Bar .............................................................................................................................. 17
Chapter 2 Configure the Alarm Control ............................................................................19
About Configuring the Alarm Control ........................................................................................ 19 Placing the Alarm Control into an Industrial Graphic .................................................................. 19 Setting Alarm Control Properties .............................................................................................. 21 Showing Current Alarms or Recent Alarms and E vents ............................................................. 21 Showing Historical Alarms and/or E vents.................................................................................. 23 Set Alarm Control Colors ......................................................................................................... 26
Set Event Record Colors ................................................................................................... 26 Set Alarm Return To Normal Record Colors ........................................................................ 27 Set Heading, Grid, and Window Color................................................................................. 28 Set Alarm Shelving Colors ................................................................................................. 28 Set Priority Ranges for Alarm Rec ords ................................................................................ 29
3

AVEVATM ArchestrA Alarm Control Guide

Contents

Set Colors for Acknowledged Alarms .................................................................................. 30 Set Colors for Unacknowledged Alarms .............................................................................. 30 Set Unacknowledged Alarms to Flash................................................................................. 31
Rename, Resize, and Reorder Column Headers ....................................................................... 32 Rename Column Headers.................................................................................................. 32 Resize Columns ................................................................................................................ 33 Change the Order of Columns ............................................................................................ 34
Sort Alarms ............................................................................................................................ 35
Filter Alarms ........................................................................................................................... 37
Using Wildcards in Queries ................................................................................................ 37 Use an Existing Query or Filter........................................................................................... 37 Add a New Query or Filter.................................................................................................. 38 Construct Filters ................................................................................................................ 40 Modify an Existing Query or Filter ....................................................................................... 41 Delet e a Query or Filter Favorit e ........................................................................................ 41 Export Query and Filter Favorites ....................................................................................... 42 Import Query and Filter Favorites ....................................................................................... 42
Setting Time Zone and Format ................................................................................................. 43
Set the Time Zone............................................................................................................. 43 Set a Time Format............................................................................................................. 44 Set a .NET Datetime Format .............................................................................................. 45
Configuring Run-Time B ehavior ............................................................................................... 46 Show Heading, Grid, or Status Bar ..................................................................................... 47 Automatic Query for Alarms on Start Up ............................................................................. 48 Scroll Automatically to New Alarms .................................................................................... 48 Hide Errors, Warnings, and Status Messages ..................................................................... 48 Restrict User Access to Rows and Columns ........................................................................ 49 Retain Hiding when Changing Alarm Query Filter ................................................................ 49 Override the Frozen Grid ................................................................................................... 49 Customize the "No Records" Message ............................................................................... 50 Changing the Language of the "No Records" Message .................................................. 50 Configure the Alarm Control to Require an ACK Signature ................................................... 50 Configuring the Alarm Control to Require a SHE LVE Signature ............................................ 52 Configuring the Run-Time Shortcut Menu ........................................................................... 53
Chapter 3 Use the Alarm Control at Run Time ............................................................... 55
Refresh the Alarm Control Grid ................................................................................................ 55
View Status Bar Information..................................................................................................... 55 Using Status Bar Information of Current Modes ................................................................... 55 Using Status Bar Information of Historical Modes ................................................................ 56
Acknowledge Alarms ............................................................................................................... 57 Provide a Signature to Acknowledge Alarms ....................................................................... 57 Providing a Signature to Acknowledge Alarms Using Smart Cards ....................................... 58
Shelve and Unshelve Alarms at Run Time ................................................................................ 59 Shelving Alarms ................................................................................................................ 60 Show Shelved Alarms .................................................................................................. 61
Unshelve Alarms ............................................................................................................... 62
Sort Alarms at Run Time ......................................................................................................... 63
Filter Alarms at Run Time ........................................................................................................ 63

4

Contents

AVEVATM ArchestrA Alarm Control Guide

Use an Existing Query Filter............................................................................................... 64 Adding a New Query or Filter at Run Time .......................................................................... 64 Modifying an Existing Query or Filter at Run Time ............................................................... 64 Saving Run-Time Modifications to Queries and Filters ......................................................... 65 Deleting a Query or Filter at Run Time ................................................................................ 65 Importing Query and Filter Favorites at Runtime .................................................................. 66 Exporting Query and Filter Favorites at Runtime.................................................................. 66 Filtering Alarms with Client-B ased Filtering ......................................................................... 66
Reset the Grid ........................................................................................................................ 69
Hide Alarms ............................................................................................................................ 69
Freez e and Unfreeze the Alarm Control Grid ............................................................................ 70
Show Alarm Statistics.............................................................................................................. 71
Switching between Client Modes .............................................................................................. 72
Switching Run-Time Languages ............................................................................................... 73
Chapter 4 Scripting the Alarm Control.............................................................................. 75
Alarm Control Properties ......................................................................................................... 75
AckComment.DefaultValue Property................................................................................... 75 AckComment.UseDefault Property ..................................................................................... 75 AckSignature.MaxPriority Property ..................................................................................... 75 AckSignature.MinPriority Property ...................................................................................... 76 AckSignature. Required Property ........................................................................................ 76 AlarmColor.Ack.BackGround Property ................................................................................ 77 AlarmColor.Ack.ForeGround Property................................................................................. 77 AlarmColor.Ack.RTN.BackGround Property ........................................................................ 78 AlarmColor.Ack.RTN.ForeGround Property ......................................................................... 79 AlarmColor.Range Property ............................................................................................... 79 AlarmColor.RTN.BackGround Property ............................................................................... 80 AlarmColor.RTN.ForeGround P roperty ............................................................................... 80 AlarmColor.UnAck.BackGround Property ............................................................................ 81 AlarmColor.UnAck.Flash.BackGround Property................................................................... 81 AlarmColor.UnAck.Flash.ForeGround Property ................................................................... 82 AlarmColor.UnAck.ForeGround Property ............................................................................ 83 AlarmColor.UnAck.RTN.BackGround Property .................................................................... 84 AlarmColor.UnAck.RTN.ForeGround P roperty .................................................................... 84 AlarmQuery Property ......................................................................................................... 85 AllowColumnResize Property ............................................................................................. 85 AutoRes umeDuration Property ........................................................................................... 85 AutoScroll Property ........................................................................................................... 85 ClientMode P roperty .......................................................................................................... 86 ConnectStatus Property ..................................................................................................... 86 Cont extMenu.AckAll Property............................................................................................. 86 Cont extMenu.AckOthers Property ...................................................................................... 87 Cont extMenu.AckSelected Property ................................................................................... 87 Cont extMenu.AckSelectedGroups Property ........................................................................ 87 Cont extMenu.AckSelectedP riorities Property ...................................................................... 87 Cont extMenu.AckSelectedTags Property ............................................................................ 87 Cont extMenu.AckVisible Property ...................................................................................... 88 Cont extMenu.Favorites Property ........................................................................................ 88 Cont extMenu.Freez e Property ........................................................................................... 88 Cont extMenu. Hidden Property ........................................................................................... 88 Cont extMenu. HideAll Property ........................................................................................... 88 Cont extMenu. HideOthers Property ..................................................................................... 89

5

AVEVATM ArchestrA Alarm Control Guide

Contents

Cont extMenu. HideS elected Property .................................................................................. 89 Cont extMenu. HideS electedGroups Property ....................................................................... 89 Cont extMenu. HideS electedP riorities Property ..................................................................... 89 Cont extMenu. HideS electedTags Property........................................................................... 90 Cont extMenu. HideVisible Property ..................................................................................... 90 Cont extMenu. Requery Property ......................................................................................... 90 Cont extMenu. Reset Property ............................................................................................. 90 Cont extMenu.ShelveAll Property ........................................................................................ 90 Cont extMenu.ShelveOthers Property.................................................................................. 91 Cont extMenu.ShelveSelected Property ............................................................................... 91 Cont extMenu.ShelveSelectedGroups Property .................................................................... 92 Cont extMenu.ShelveSelectedPriorities Property .................................................................. 92 Cont extMenu.ShelveSelectedSeverities Property ................................................................ 92 Cont extMenu.ShelveSelectedTags Property ....................................................................... 93 Cont extMenu.ShelveVisible Property .................................................................................. 93 Cont extMenu.Sort Property ................................................................................................ 93 Cont extMenu.Statistics Property ........................................................................................ 94 Cont extMenu. UnhideAll Property........................................................................................ 94 Cont extMenu. UnshelveAll Property .................................................................................... 94 Cont extMenu. UnshelveOthers Property .............................................................................. 94 Cont extMenu. UnshelveSelected Property ........................................................................... 95 Cont extMenu. UnshelveSelectedGroups Property ................................................................ 95 Cont extMenu. UnshelveSelectedPriorities Property .............................................................. 96 Cont extMenu. UnshelveSelectedSeverities Property ............................................................ 96 Cont extMenu. UnshelveSelectedTags Property.................................................................... 96 Cont extMenu. UnshelveVisible Property .............................................................................. 97 Database.Authentication Property ...................................................................................... 97 Database.Name Property .................................................................................................. 97 Database.Password Property ............................................................................................. 98 Database.ServerName Property ......................................................................................... 98 Database.Us erID Property ................................................................................................. 98 DisableFileBrowsing Property ............................................................................................ 98 Domain Property ............................................................................................................... 98 Enabled Property .............................................................................................................. 99 E vent Color.BackGround Property....................................................................................... 99 E vent Color.ForeGround Property ....................................................................................... 99 Favorite Property............................................................................................................. 100 FlashUnAckAlarms Property ............................................................................................ 100 GridColor Property .......................................................................................................... 100 HeadingColor.BackGround Property ................................................................................. 101 HeadingColor.ForeGround Property ................................................................................. 101 Height Property ............................................................................................................... 102 HiddenAlarms Property.................................................................................................... 102 HideE rrors Property ......................................................................................................... 102 MaxDatabaseRecords Property........................................................................................ 102 NewAlarmE ventMode Property ........................................................................................ 102 NoRecordsMessage.Enabled Property ............................................................................. 103 NoRecordsMessage.Message Property ............................................................................ 103 SaveUserQueryFilter Property ......................................................................................... 103 QueryStartup Property ..................................................................................................... 104 RequiresShel veSignature Property ................................................................................... 104 RetainHidden Property .................................................................................................... 104 RowCount Property ......................................................................................................... 105 RowSelection Property .................................................................................................... 105 SelectedCount Property ................................................................................................... 105 ShelveColor.BackGround Property ................................................................................... 106 ShelveColor.ForeGround Property.................................................................................... 106

6

Contents

AVEVATM ArchestrA Alarm Control Guide
ShowContextMenu Property ............................................................................................ 107 ShowGrid Property .......................................................................................................... 107 ShowGroupBy Header Property ........................................................................................ 107 ShowHeading Property .................................................................................................... 107 ShowStat usBar Property.................................................................................................. 107 SortColumn.First Property................................................................................................ 107 SortColumn.Sec ond Property ........................................................................................... 108 SortColumn. Third Property .............................................................................................. 108 SortColumn.Fourth Property ............................................................................................ 108 SortOrder.First Property................................................................................................... 108 SortOrder.Second Property .............................................................................................. 109 SortOrder.Third Property ................................................................................................. 109 SortOrder.Fourth Property ............................................................................................... 109 Time.Format Property ...................................................................................................... 110 Time.Ty pe Property ......................................................................................................... 110 TimeSelector Property ..................................................................................................... 111 TimeSelector.DurationMS Property .................................................................................. 111 TimeSelector.EndDate Property ....................................................................................... 111 TimeSelector.StartDate Property ...................................................................................... 112 TimeSelector.TimeDuration Property ................................................................................ 112 TimeZone. TimeZone Property.......................................................................................... 114 TotalRowCount Property.................................................................................................. 114 UnAckAlarms Property .................................................................................................... 114 UpdateToCurrent Time Property ....................................................................................... 115 UserQueryFilterFil ePath Property ..................................................................................... 115 Visible Property ............................................................................................................... 115 Width Property ................................................................................................................ 116 WindowColor Property ..................................................................................................... 116 X Property ...................................................................................................................... 116 Y Property ...................................................................................................................... 116
Alarm Control Methods .......................................................................................................... 116
AboutBox() Method ......................................................................................................... 117 Ack.All() Method.............................................................................................................. 117 Ack.Group() Method ........................................................................................................ 117 Ack.Priority() Method ....................................................................................................... 117 Ack.Selected() Method .................................................................................................... 118 Ack.SelectedGroup() Method ........................................................................................... 118 Ack.SelectedPriority () Method ......................................................................................... 118 Ack.SelectedTag() Method............................................................................................... 119 Ack.Tag() Method............................................................................................................ 119 Ack.Visible() Method........................................................................................................ 119 Connect() Method ........................................................................................................... 120 Disconnect() Method ....................................................................................................... 120 Favorites.Export () Method................................................................................................ 120 Favorites.Import() Met hod ................................................................................................ 120 Freez eDisplay() Met hod................................................................................................... 121 GetItem() Method ............................................................................................................ 121 GetLastError() Met hod ..................................................................................................... 121 GetSelectedItem() Met hod ............................................................................................... 122 Hide.All() Method ............................................................................................................ 122 Hide. Group() Method ....................................................................................................... 122 Hide.Priority() Method...................................................................................................... 123 Hide.Selected() Method ................................................................................................... 123 Hide.SelectedGroup() Method .......................................................................................... 123 Hide.SelectedPriority() Method......................................................................................... 123 Hide.SelectedTag() Method ............................................................................................. 123
7

AVEVATM ArchestrA Alarm Control Guide

Contents

Hide. Tag() Method .......................................................................................................... 124 Hide.Visible() Method ...................................................................................................... 124 LoadQueryFilterFile ......................................................................................................... 124 MoveWindow() Method .................................................................................................... 125 Requery() Method ........................................................................................................... 125 Reset() Method ............................................................................................................... 126 ResetSortCriteria() Met hod .............................................................................................. 126 RunQuery() Method......................................................................................................... 126 RunQueryFromFile() Method............................................................................................ 126 Select.All() Method .......................................................................................................... 127 Select.Group() Method .................................................................................................... 127 Select.Item() Method ....................................................................................................... 127 Select.Priority() Met hod ................................................................................................... 127 Select.Tag() Method ........................................................................................................ 128 SetSort() Method............................................................................................................. 128 SetSortCriteria() M ethod .................................................................................................. 129 Shelve.All() Met hod ......................................................................................................... 130 Shelve.Group() Method ................................................................................................... 130 Shelve.Priority() Method .................................................................................................. 131 Shel ve.Selected() M ethod ................................................................................................ 131 Shelve.SelectedGroup() Method ...................................................................................... 132 Shelve.SelectedP riority() Method ..................................................................................... 132 Shelve.SelectedS everity() Method .................................................................................... 133 Shelve.SelectedTag() Method .......................................................................................... 134 Shelve.Severity() Method................................................................................................. 134 Shelve. Tag() Method ....................................................................................................... 135 Shel ve.Visible() Method ................................................................................................... 136 Show. Context() Method ................................................................................................... 136 Show.Favorite() Met hod................................................................................................... 136 Show. Hidden() Met hod .................................................................................................... 136 Show.Sort() Method ........................................................................................................ 136 Show.Statistics() Method ................................................................................................. 137 TimeSelector.GetStartAndEndTimes() Method .................................................................. 137 TimeSelector.RefreshTimes() Met hod ............................................................................... 137 TimeSelector.SetStartAndE ndTimes() Met hod .................................................................. 137 Toggle.All() Met hod ......................................................................................................... 138 Toggle.Item() Method ...................................................................................................... 138 UnhideAll() Method.......................................................................................................... 138 UnSelectAll() Method....................................................................................................... 138 Unshelve.All() Method ..................................................................................................... 138 Unshel ve.Group() M ethod ................................................................................................ 139 Unshelve.Priority() Method............................................................................................... 139 Unshelve.Selected() Method ............................................................................................ 140 Unshelve.SelectedGroup() Met hod ................................................................................... 141 Unshelve.SelectedP riority() Method .................................................................................. 141 Unshelve.SelectedS everity() Method ................................................................................ 141 Unshelve.SelectedTag() Method ...................................................................................... 142 Unshel ve.Severity() M ethod ............................................................................................. 142 Unshelve.Tag() Met hod ................................................................................................... 143 Unshelve.Visible() Method ............................................................................................... 144
Configuring E vents ................................................................................................................ 144
Configuring the NewAlarm E vent ...................................................................................... 144
.NET Colors .......................................................................................................................... 145
Chapter 5 Transferring Alarm Configuration from InTouch .........................................149
Trans ferring the InTouch Alarm Viewer Control Configuration .................................................. 149
8

Contents

AVEVATM ArchestrA Alarm Control Guide

Trans ferring Configuration of the Control Name Tab .......................................................... 149 Trans ferring Configuration of the General Tab ................................................................... 150 Trans ferring Configuration of the Color Tab....................................................................... 152 Trans ferring Configuration of the Time Format Tab ............................................................ 153 Trans ferring Configuration of the Query Tab ..................................................................... 154 Trans ferring Configuration of the Properties Tab ............................................................... 155 Trans ferring Script Configuration on the E vents Tab .......................................................... 155
Trans ferring the InTouch Alarm DB View Control Configuration ................................................ 156
Trans ferring Configuration of the Alarm DB View Control Name Tab................................... 156 Trans ferring Configuration of the InTouch Alarm DB View General Tab .............................. 157 Trans ferring Configuration of the InTouch Alarm DB View Color Tab .................................. 158 Trans ferring Configuration of the Database Tab ................................................................ 159 Trans ferring Configuration of the Selection Tab ................................................................. 160 Trans ferring Configuration of the Time/Sort Tab ................................................................ 161 Trans ferring Configuration of the Query Filter Tab ............................................................. 162 Trans ferring Configuration of the InTouch Alarm DB View Properties Tab ........................... 163 Trans ferring Scripts Configuration on the E vents Tab ........................................................ 163
Trans ferring Query Favorites Configuration ............................................................................ 163
Mapping Properties and Methods ........................................................................................... 164
Index.......................................................................................................................................173

9

AVEVATM ArchestrA Alarm Control Guide
CHAPTER 1
About the ArchestrA Alarm Control
Working with the ArchestrA Alarm Control
The ArchestrA Alarm Control is a graphical element you can use in your Industrial Graphics to show current and historical alarms and events. The ArchestrA Alarm Control replaces the Alarm Viewer control and Alarm DB View control in the InTouch� HMI and extends alarm visualiz ation to the Industrial graphics environment. You can plac e the ArchestrA Alarm Control directly from the Tool s panel in the Industrial Graphic Editor onto the canvas. You can customize it to your needs by adding further graphics, interactions, and scripts. You can deploy a managed InTouch application containing ArchestrA Alarm Controls to a remote node and visualize and interact with alarms at run time with InTouch WindowViewer. For this documentation, the ArchestrA Alarm Control is simply referred to as "Al arm Control." We recommend you have a basic understanding of the InTouch Alarm system before continuing. For more information, see the InTouch HMI Alarms and E vents Guide.
Client Modes
The Alarm Control supports five different client modes, which can be grouped depending on their data source. The Alarm Control supports an ArchestrA Database (A 2ALMDB), and the Historian History Blocks.
InTouch Alarm Manager
The Alarm Control manages currently active alarms (summary alarms) and recent alarms (historical alarms). These types of alarms are saved to internal alarm memory.
Current Alarms
When the Alarm Control is showing alarms in "Current Alarms" mode, it is showing currently active alarms directly from the Alarm Manager.
Recent Alarms and Events
When the Alarm Cont rol is showing alarms in "Recent Alarms and E vents" mode, it is showing historical alarms and events stored in Alarm Manager. Unlike the "Current Alarms" mode, the "Recent Alarms and E vents mode" shows time point data, such as alarm transitions and events, instead of continuous conditions.
Alarm and Event Storage
Alarms and events can be stored to the ArchestrA alarm database (A2A LMDB) or the Historian history blocks. When the Alarm Control is configured in "Historical Alarms" mode, only alarms stored in the Alarm Database are shown.
11

AVEVATM ArchestrA Alarm Control Guide

About the ArchestrA Alarm Control

When the Alarm Control is configured in "Historical E vents" mode, only events stored in the Alarm Database are shown. When the Alarm Control is configured in "Historical Alarms and E vents" mode, both alarms and events stored in the Alarm Database are shown.
Switching Between Client Modes
The client mode and many other features are cont rolled by properties and methods.
By default, the Alarm Control is set to show current alarms. You can als o change the client mode at run time by using the Alarm Control properties.
Using the Alarm Control in Industrial Graphics
You can use the Arc hestrA Alarm Cont rol as a faceplate so that when the operator clicks an icon, an ArchestrA Alarm control showing a specific alarm area opens.

You can also configure the ArchestrA Alarm Control to interact with the Galaxy namespace and ot her Industrial graphics by mapping its properties to ArchestrA attributes and symbol elements.
The Alarm Control can be placed into Industrial Graphics hosted by Automation Object templates and instances. You can configure them to retrieve alarms from their hosting Area object or their hosting Automation object.
Alarm Acknowledgement
You can configure the Alarm Control to require an alarm to be acknowledged even if the condition causing the alarm has passed. This ensures that an operat or is aware of events that caused a t emporary alarm state but have ret urned to normal. You acknowledge alarms at run time using a shortcut menu or through script methods.
12

About the ArchestrA Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Current Value and Quality Display
The Alarm Control in one of the current client modes shows continuously the current value and quality of a tag or attribute in alarm state.

You can see the current value and quality of tags or attributes in alarm from:  InTouch running on the local computer  Galaxy namespace Note: You cannot see current value and quality data from InTouc h tags running on a remote computer.

Working With Alarm Queries and Filters
Queries and filters are two methods to retrieve data at RunTime, with queries being a superset of filters. You can run a query at run time to retrieve dat a, then run another query to narrow the search criteria without re-running the query or retrieving the same data. This allows the Alarm Control to use data from a current subscription without re-subscribing. For more information, see Filtering Alarms on page 37.
Alarm Queries
The Alarm control supports standard Galaxy alarm query formats, such as: \galaxy!Area_001
Alarm query syntax is the same for both Current Alarms Mode and Recent Alarms and E vents Mode. Queries in Historical Alarms, Historical E vents, and Historical Alarms and E vents Modes are actually Alarm Database queries, which follow rules and syntax for SQL Server dat abas e queries.
The alarm query syntax changes when you use the run-time alarm comment language switching feature. For more information, see Alarm Query Syntax when Register Using Galaxy_<GalaxyName> is Enabled on page 14.
The Alarm control also supports relative references for Galaxy alarms in alarm queries. For all alarm modes, relative references are resolved at run time at the point of query to the Alarm Manager or Alarm Database.
You must put the reference part of the alarm query bet ween less-than (<) and greater-than (>) characters.
The following table shows examples of alarm queries.

Alarm Query \provider!group
\provider!group!t agname

Description
Shows all alarms from the given provider and group. For example: \intouch!Group_A
Shows all alarms from the given provider, group and tag. For example: \galaxy!Mixing_Area!RotorCtrl

13

AVEVATM ArchestrA Alarm Control Guide Alarm Query \\node\provider!group \\node\provider!group!tagname
HotBackup Nam e

About the ArchestrA Alarm Control
Description
Shows all alarms from the given provider and group from a given node. For example: \\remote\intouch!Group_B
Shows all alarms from the given provider, group and tag from a given node. For example: \\grnode\galaxy!Packaging_Area!Wrappe r1
Shows all alarms from primary or backup alarm provider as configured in the Hot Backup Manager.

\galaxy!<me.Area> !<me.tagname>.*

Shows all alarms from the Aut omation Object. Alarms from other Automation Objects in the same area are ignored.

\galaxy!<myArea.tagname> or \galaxy!<me.Area>

Shows all alarms from the A rea object hosting the Automation Object

\galaxy!<myPlatform.tag nam e>

Shows all alarms from the Winplatform object hosting the Automation Object.

\galaxy!<me.a re a>!<myC ontai ne r.tagn a me>.*

Shows all alarms from the container Automation Object. At run-time the Alarm Control resolves the Cont ainer attribute to detect the container.

\galaxy!<myEngi ne.tag nam e>

Shows all alarms from the AppEngine object h osting the Automation Object. At run-time the Alarm Cont rol resolves the MyEngine attribut e to detect the host.

Alarm Query Syntax when Register Using Galaxy_<GalaxyName> is Enabled
The run-time alarm c omment language s witching feature requires slightly different alarm query syntax. In the WinPlatform object, when you enable InTouch alarm provider, you can enable Register using Galaxy_<GalaxyName> instead of Galaxy. This option will register the plat form to the alarm subsystem using the Galaxy name preferred by "Galaxy_" instead of just the word "Galaxy". This allows an InTouch application to monitor alarms from multiple Galaxies and avoid name conflicts. Syntax changes slightly when G alaxy_GalaxyName is enabled:
o Use \\ for computer name
o Use \ for Galaxy or Galaxy_<GalaxyName> o Use ! for Area For example: \\Galaxy\MyGalaxy!A rea001
14

About the ArchestrA Alarm Control

AVEVATM ArchestrA Alarm Control Guide

If Galaxy_GalaxyName is not enabled in WinPlatform, then the default behavior described in Alarm Queries on page 13 applies.
You can det ermine if Galaxy_<GalaxyName> has been enabled by monitoring the run -time attribute of the platform ITAlarmProvider.ProviderNameAsGalaxyNameEnabled.
Alarm Filtering
The Query Favorites of InTouch Alarm Viewer control define a set of alarm provider, alarm group, an optional node name, and a priority range under one name. The alarm provider, alarm group, and the node name are used for subscribing to a specific alarm group. The priority range on the other hand is used to filter the alarms from the given alarm group.
The Filter Favorites of InTouch Alarm DB View control define a set of any number of criteria you want to filter from the Alarm Database under one name.
In summary, Filter Favorites fulfill a purely filtering function whereas Query Favorites fulfill a subscription and a filtering function at the same time.
The Alarm Control filtering feature unites both these concepts by exclusively using filter conditions an d subscribing to the necessary alarm providers on demand.
Filters can be saved and us ed in both run time and historical modes.
The filter conditions can be re-used between different client modes. For example, if you define node name, provider name, alarm group, and a priority range for t he current alarms, you can als o use this filter to retrieve the historized alarm data of the same source from the Alarm Database instead.
Filter definitions will be saved per user so operators working on the same server can access different saved filters.
Alarm Queries to Filters Translation
You can define queries for current alarms in the \\node\provider!group format, but they are translated by the Alarm Control to a filter aft er you save.
For example, the query string \\GRNode\galaxy!MixingArea is translated to the following filter string:
Node = `GRNode' AND Provider='galaxy' AND Group='MixingA rea'
You can modify the filter in a tree to query only alarms in the priority range 1 to 250, suc h as: AND
Node = `GRNode' Provider = `Galaxy' Group = `MixingArea' Priority >= `1' Priority <= `250'
Alarm Shelving
Operators can temporarily shelve selected alarms from the list of an Alarm Control's active alarms. A shelved alarm is suppressed and removed from the list of active alarms. Typically, operators shelve lower severity nuisance alarms becaus e they provide little diagnostic value and interfere with the operator's ability to manage a plant process.
An alarm is shelved for a specified period. After the period ends, alarms are automatically unshelved and appear again in the list of active alarms. Operators can also manually unshelve an alarm before the end of the specified shelved period.
By default, Medium and Low severity alarms are enabled for shelving. Critical and High severity alarms are not because of the potential risk of shelving and ignoring alarms that repres ent serious operating states. For more information about enabling shelving based on alarm severity, see "Configuring Alarm Severity to Priority Mapping" in the Application Server Us er Guide.
15

AVEVATM ArchestrA Alarm Control Guide

About the ArchestrA Alarm Control

Shelving Alarms During Run Time
When shelving an alarm from the Alarm Cont rol, operators set an associated time period in which the alarm remains shelved and enter a mandatory comment. Operators can select from a list of Alarm Cont rol Context commands during run -time to:
 Shelve one or more selected alarms
 Shelve all alarms
 Shelve only those alarms visible in the Alarm Control
 Shelve all alarms within the same alarm group as an alarm selected from the Alarm Control
 Shelve alarms by selected tags or attributes
 Shelve alarms by selected alarm priorities
 Shelve all alarms that have the same severity as an alarm selected from the Alarm Control For more information about configuring shelve Context commands, see Configuring the Run-Time Shortcut Menu on page 53.
When application security is used, alarms can be shelved and unshelved only by operators with proper authorization. For more information about setting shelving authorization, see Configuring the Alarm Cont rol to Require a S HELVE Signature on page 52.
Unshelving Alarms During Run Time
Alarms are unshelved automatically at the end of the shelving time period. An unshelved alarm reappears in the Alarm Cont rol active list and resumes its state at the time it was shelved. Operat ors can manually unshelve a shelved alarm before t he end of the shelved period and enter an optional comment.
Alarm Hiding
The "hiding" and "unhiding" of alarm records is known in the corres ponding InTouc h alarm controls as "suppressing" and "unsuppressing".
When the Alarm Control is hiding alarms, it ignores certain alarms. If an alarm matches the exclusion criteria, it is not visible. The actual alarm generation is completely unaffected by hiding. Alarm records are still logged into the alarm history. As in the InTouch HMI, you can unhide specific alarms and also use properties and methods to interact with the alarm hiding feature at run time.
Alarm Control Grid Freezing
You can freeze the Alarm Control to prevent the Alarm control tree from being updated wit h any further changes.
For example, if new alarms occur while the Alarm Control is frozen, the new alarms are only shown after you unfreeze the Alarm Control. You can configure a time period after which the Alarm Control automatically unfreezes to avoid the Alarm Cont rol being unk nowingly frozen. For example, the operator leaves the workstation and returns without realizing that the Alarm Control is still frozen. The Alarm Control unfreezes automatically if one of the following changes:
 Alarm Mode
 Alarm Query
16

About the ArchestrA Alarm Control

AVEVATM ArchestrA Alarm Control Guide

 Filter
Alarm Sorting
Like InTouch alarm controls, you can sort the alarms in ascending or descending direction for selected columns.
The Alarm Control s upports alarm sorting for up to four columns at design time and run time. At run -time, the operator can configure sorting of even more columns by clicking on the column headers of the Alarm Cont rol while pressing the S hift key.
Support for a Redundant Historian Server
A Historian may be configured to have a symmetrical "partner" Historian that can be used as a backup if the primary, or main, historian is not available. This is known as a " redundant historian" setup. No control configuration is required to take advantage of a redundant historian.
When the primary historian is unavailable, the Alarm Control automatically switches over to the configured partner historian. The control remains connected to the partner historian, even when the primary historian becomes available again. The Alarm Control switches back to an available primary historian if it fails to connect to the partner or during a new attempt to connect to the primary historian. One example of this would be restarting the Trend Control, which initiates a new connection to the primary historian. For a redundant historian setup, bot h historians must be configured to store events to the same location, either to history blocks or the A2ALMDB database.
When the Alarm Control successfully connects to either the primary historian or its partner, the following columns are updated with the connected historian server name in the tags list of the selected tags:
 Server
 I/O Address
The historian name shown in the Tag Picker is always the name of the primary historian, even when the control is connected to the partner.
There is no automatic synchronization built in to the redundant historian setup; it is up to the historian server administrator to make sure that the two historians in the pair are symmetrical and synchronized.
If the SQL Server Service is running while Historian Service is not running, this is not recogniz ed by the Alarm Control as a scenario in which the Historian Server is unavailable.
Status Bar
The status bar of the Alarm Control resembles the status bars of the InTouch alarm controls, with the following differences:
 Alarm Control also shows the alarm client time zone
 Alarm Control querying the Alarm Database has a Requery button to more easily retrieve data from the Alarm Database
 Alarm Control shows the current client mode as an icon

17

AVEVATM ArchestrA Alarm Control Guide
CHAPTER 2
Configure the Alarm Control
This section shows you how to plac e an Alarm Control onto the canvas and configure it. You can configure it either with the Edit Animations dialog box, or by changing individual properties in the Properties Editor.
About Configuring the Alarm Control
After placing the Alarm Control onto the canvas, you can configure the:  Client Mode to show current alarms, recent alarms and events, or historical alarms and/or events.  Colors for the Alarm Control grid, window, heading, and alarm records.  Order and width of the grid columns and their headers.  Sorting order of alarm records.  Filtering for alarm records and save the filt ers as favorites for re -use.  Time format and zone for the alarm record time stamps.  Run-time behavior for the Alarm Control, such as:
o If the operat or can resize columns or select multiple records at run time. o Access to specified options of the shortcut menu at run time.
Placing the Alarm Control into an Industrial Graphic
You can easily place the ArchestrA Alarm Control into an Industrial Graphic by placing it onto the c anvas.
To place the Alarm Control into an Industrial Graphic
1. Open the Industrial graphic in the Industrial Graphic Editor. 2. On the Tool s panel, click the Arche strA Alarm Control icon. The cursor appears in insert mode.
19

AVEVATM ArchestrA Alarm Control Guide 3. Click the canvas where you want to place the Alarm Control.

Configure the Alarm Control

20

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Setting Alarm Control Properties
Like all other graphic al objects in the Industrial GraphicEditor, you can set some of the properties of the selected Alarm Cont rol directly in the Properties Editor.

We recommend you configure the Alarm Control with the Edit Animations dialog box and only use the Properties Editor to edit the configuration aft erward.
Showing Current Alarms or Recent Alarms and Events
You can set the Alarm Cont rol to show either of the following:  Current alarms  Recent alarms and events You use the ClientMode P roperty integer property in scripting to switch the Alarm Control to show current alarms or recent alarms and events at run time. You can also configure a comment to use when alarms are acknowledged at run time. Use the AckComment.UseDefault Property Boolean property and AckComment.DefaultValue Property string property in scripting to use a default acknowledgement comment at run time.
21

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

To show current alarms
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears.

2. If necessary, click Alarm Mode. The Alarm Mode page appears.
3. In the Client Mode list, click Current Alarms. 4. In the Alarm Query box, type the alarm query. To create a new line in the Alarm Query box, press
Ctrl + Enter. For more information on the valid syntax, see Alarm Queries on page 13. 5. If you want to use a default acknowled gement comment, select the Use Default Ack Comment
check box and type a comment in the text box. 6. Click OK.
To show recent alarms and events
1. Double-click Alarm Cont rol on the canvas. The Edit Animations dialog box appears. 2. Click Alarm Mode. The Alarm Mode page appears.
22

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

3. In the Client Mode list, click Recent Alarms and Events.

4. In the Alarm Query box, type the alarm query. To create a new line in the Alarm Query box, press Ctrl + Enter. The alarm query must follow one of the following syntax: o \\node\provider!group o \provider!group o HotBackupName For example: \galaxy!Area_001 For Alarm Cont rols hosted by Automation Object templates or instances, you can specify one of the following alarm queries: o \galaxy!<myArea. Tagname> to retrieve alarms and events from the Area object hosting t he Automation Object templat e or instanc e. o \galaxy!<me.Area> !<me. Tagname>.* to retrieve alarms and events from the Automation Object template or instance. For more information on alarm queries, see Alarm Queries on page 13.
5. If you want to use a default acknowledgement comment, select the Use Default Ack Comment check box and type a comment in the text box.
6. Click OK.
Showing Historical Alarms and/or Events
You can set the Alarm Cont rol to show one of the following:  Historical alarms from the Alarm Databas e
 Historical events from the Alarm Database  Historical alarms and events from the Alarm Dat abas e  Historical events from History Blocks  Historical alarms from History Blocks
23

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

 Historical alarms and events from History Blocks When you configure the Alarm Control to show historical alarms and/or events, you also configure the following:  Server name hosting the Alarm Database  Authentication information to connect to the Alarm Database  Maximum number of records to retrieve from the Alarm Database  Time range or duration to show in the Alarm Control  If the Alarm Cont rol should update to the current client time Alarm Control works with both the Arc hestrA Dat abas e (A2ALMDB) and with History Blocks. Use the following properties in scripting t o switch the client mode and configure the database connection, such as:  Client Mode P ropert y on page 86  Database.Authentication Property on page 97  Database.Name Propert y on page 97  Database.Pass word Propert y on page 98  Database.ServerName Propert y on page 98  Database.Us erID Property on page 98  Domain Property on page 98
To show historical alarms and/or events
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Alarm Mode. The Alarm Mode page appears. 3. In the Client Mode list, click:
o Hi storical Alarms to only show alarms from the Alarm Database. No events are shown o Hi storical Events to only show events from the Alarm Database. No alarms are shown

24

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

o Hi storical Alarms and Events to show both alarms and events from the Alarm Database

4. In the Authenti cation Mode list, click one of the following: o Windows Integrated to use the authentication of the currently logged-on Windows user o Windows Account to use a given Windows user aut hentication o SQL Server to use SQL Server authentication mode
5. In the Server Name list, either select or type the name of the server hosting the Alarm Database. 6. In the Database Name box, type the name of the Alarm Database. For the ArchestrA Database,
enter A2A LMDB, and for Historian block storage enter History Blocks. For the History Blocks option to function correctly, the InSight/RES T TCP port (Default 32569) on the Historian Server needs to be opened in the firewall, and configured for both inbound and outbound traffic.
Note: For History Blocks, select Windows Integ rated or Windows Account as the authentication mode.
7. If you are using Windows Account authentication mode, type the domain, user name, and password in the Domain, User Name and Password boxes.
8. If you are using SQL Server authentication mode, type user nam e and password in the User Name and Pa ssword boxes.
9. Click Test Connection. The connection to the Alarm Database is tested and a result message appears. If necessary, check your authentication information.
10. Click OK.
To set maximum records and time range
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Alarm Mode. The Alarm Mode page appears. 3. Make sure the Client Mode is set to Historical Alarms, Hi storical Events, or Hi storical Alarms
and Events.
25

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

4. In the Maximum Records box, type the number of records to view from the cont rol at one instance. The valid range of maximum records is from 1 to 32766.
You can also use the MaxDatabaseRec ords Property in scripting to set the maximum records at run time.
5. To use a pre-defined time interval, select an interval from the middle list of the Time Range pickers.

6. To use a specific start time and end time, clear Update to Current Time, and select the start time from the list at the left and the end time from the list at the right of the Time Range pickers.
You can also use the TimeSelector.* methods and properties in scripting to set the start date, end date, or duration at run time. For more information, see 7. Click OK.
Set Alarm Control Colors
You can show different types of alarm records with different colors to more easily identify certain types of alarms. You can configure the Alarm Control with priority breakpoints to show alarm records within the res ulting priority ranges in different colors. You can also configure the control background color, the grid color, and the heading colors.
Set Event Record Colors
You can s et text color and background color for event records. Us e the E ventColor.ForeGround Property and E ventColor.BackGround Property properties in scripting to set the event alarm record text color and background color at run time.
To set text and background colors for event records
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears.
26

Configure the Alarm Control 2. Click the Colors. The Colors page appears.

AVEVATM ArchestrA Alarm Control Guide

3. Configure the event record text color. Do the following: a. Click the color field next to Event and under Text. The color picker appears. b. Select a color and click OK.
4. Configure the event record background color. Do the following: a. Click the color field next to Event and under Background. The color picker appears. b. Select a color and click OK.
5. Click OK.
Set Alarm Return To Normal Record Colors
You can set text color and background color for "return to normal" alarm records. Use the AlarmColor.Ack.RTN.ForeGround Property and AlarmColor.Ack.RTN.BackGround Property properties in scripting to set the "return to normal" alarm record text color and background color at run time.
To set text and background colors for "return to normal" records
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Colors. The Colors page appears. 3. Configure the "ret urn to normal" record text color. Do the following:
a. Click the color field next to Alarm RTN and under Text. The color picker appears. b. Select a color and click OK. 4. Configure the "ret urn to normal" record background color. Do the following: a. Click the color field next to Alarm RTN and under Background. The color picker appears. b. Select a color and click OK.
27

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

5. Click OK.
Set Heading, Grid, and Window Color
You can set text color and background color for the heading, the grid color, and the Alarm Control window color. Use the corresponding HeadingColor.ForeGround Property, HeadingColor.BackGround Property, GridColor Property, and WindowColor Property properties in scripting to set the colors for heading, grid, and window.
To set heading, grid, and window color for the Alarm Control
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Colors. The Colors page appears.

3. Do one of the following: a. Configure the heading text color by clicking the color box next to Heading and under Text. If the color box does not open, you need to select the Show Heading option on the Run-Time Behavior page first. b. Configure the heading background color by clicking the color box next to Heading and under Background. If the color box does not open, you need to select the Show Heading option on the Run-Time Behavior page first. c. Configure the grid color by clicking the color box next to Grid. If the color box does not open, you need to select the Show Grid option on the Run-Time Behavior page first. d. Configure the window color by clicking the color box next to Window.
Set Alarm Shelving Colors
You can set text color and background color for alarms that are temporarily shelved.
To set alarm shelved colors
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Colors. The Colors page appears. 3. Configure the shelve record text color. Do the following:
28

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

a. Click the color field next to Shelve and under Text. The color picker appears. b. Select a color and click OK. 4. Configure the shelve record background color. Do the following: a. Click the color field next to Shelve and under Background. The color picker appears. b. Select a color and click OK. 5. Click OK.
Set Priority Ranges for Alarm Records
You can use alarm priority ranges to filter alarms. The Alarm Control can show alarms within a given range wit h a different text and background color. Use the AlarmColor.Range Property group in scripting to set the breakpoints at run time. The Alarm Control supports four alarm ranges defined by three breakpoints: 1 < breakpoint 1 < breakpoint 2 < breakpoint 3 < 999
To set priority ranges for alarm records
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Colors. The Colors page appears. 3. In the From Pri column in the list at the right, locate the break point you want to change. Thes e are
values except 1 or 999. 4. Click the value and type a new value in the range bet ween the previous breakpoint and the next
bre akpoi nt.

5. Press Enter. All priority values in the list are updated. 6. Click OK.
29

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

Example
If you use the color configuration in the procedure above, the Alarm Control at run time could have following appearance:

Set Colors for Acknowledged Alarms
You can set the text and background colors for records of acknowledged alarms. For each of the priority ranges, you can set a text color and a background color. Use the AlarmColor.Ack.ForeGround Property and AlarmColor.Ack.BackGround P roperty property groups in scripting to set the text color and background color for acknowledged alarms in each priority range at run time.
To set colors for acknowledged alarm records
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Colors. The Colors page appears. 3. In the list at the right, locate the Ack record and priority range for which you want to change the text
or background color. 4. Click the color box in the Text or Background column of the line. The color picker appears. 5. Select a color and click OK. 6. Click OK.
Set Colors for Unacknowledged Alarms
You can set the text and background colors for rec ords of unacknowledged alarms. For each of the priority ranges, you can set a text color and a background color. Use the AlarmColor.UnAck.ForeGround Property and AlarmColor.UnAck.BackGround Property property groups in scripting to set the text color and background color for unacknowledged alarms in each priority range at run time.
To set colors for unacknowledged alarm records
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Colors. The Colors page appears. 3. In the list at the right, locate the Unack record and priority range for which you want to change the
text or background color. 4. Click the color box in the Text or Background column of the line. The color picker appears.
30

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

5. Select a color and click OK.
Set Unacknowledged Alarms to Flash
Instead of showing unacknowledged alarm records in predefined constant text and background color, you can configure the Alarm Control to flas h unacknowledged alarms in another text and background colors.
Note: The Flash Unack Alarms setting is checked by default for instances of the Alarm Control that are embedded in Situational Awareness Library symbols.
The unacknowledged alarm rec ords flash bet ween the colors of the Unack alarms and the colors of the Flash Unack alarms. Use the Flas hUnAckAlarms Property Boolean property in scripting to set unacknowledged alarm records to flash at run time.
Use the AlarmColor. UnAck.Flash.ForeGround Property and AlarmColor.UnAck.Flash.BackGround Property property groups in scripting to set the text color and background color for flashing unacknowledged alarms in eac h priority range at run time.
To set flashing and colors for unacknowledged alarm records
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Colors. The Colors page appears. 3. Select the Flash Unack Alarm s check box.
Note: You cannot select the Flash UnAck Alarm s check box if the client mode is set to one of the historical modes.
4. In the list on the right, locate the Unack record and priority range for which you want to change the text or background color. Do the following:
a. Click the color box in the Text or Background column of the line. The color picker appears. b. Select a color and click OK. 5. Locate the Fla sh Unack record and priority range for which you want to change the text or background color. Do the following: a. Click the color box in the Text or Background column of the line. The color picker appears. b. Select a color and click OK. 6. Click OK.

31

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

Rename, Resize, and Reorder Column Headers
You can rename, resize, and change the order of column headers in the Alarm Control.

All changes you mak e in the Column Details list are shown in the grid preview. You can also use the grid preview to resize columns or change their order with the pointer. Column headers can be localized along with other symbol text when you export, translate, and reimport language files. The translated language files must be imported to the InTouch HMI for run-time language switching. For further information, see Chapter 11 Working with Languages in the Application Server User's Guide. Important: If you rename or reorder column headers, you must repeat the symbol text translation procedures. If you do not, your changes will not be available for run-time language switching.
Rename Column Headers
You can rename the column headers in the Alarm Control.
To rename column headers
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Column Details tab. The Column Details page appears. 3. In the Column Details list, locate the column header you want to rename and click on it.
32

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

4. Type a new name and press Enter. The Column Details list and the grid preview are updated wit h the new name.

5. Click OK.
Resize Columns
You can resize the column headers in the Alarm Control either by:  Typing in a numeric value  Dragging the column header boundary widt h with the pointer in the grid preview
To resize the column numerically
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Column Details. The Column Details page appears. 3. In the Column Details list, locate the name of the column you want to resize and click on the Width
value in the row.
33

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

4. Type a new width in pixels and press Enter. The Column Details list and the grid preview are updated.

5. Click OK.
To resize the column graphically
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Column Details. The Column Details page appears. 3. In the grid preview, locate the column you want to resize and drag the column boundary to resize the
column. The width value of the Column Details list is updated. 4. Click OK.
Change the Order of Columns
You can change the order of the columns in the Alarm Control by:  Moving column names up and down in the Column Details list using buttons  Dragging the column header with the pointer in the grid preview You also can reset the column widths and order to their default values. Resetting the column widths and order also resets the names to their default values.
To change the column order
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Column Details. The Column Details page appears. 3. Do one of the following:
34

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

o Click arrow up and arrow down to reposition the columns
o In the grid preview, drag the name of the column you want to reposition and drop it to the left of another column to reposition it

The grid preview and the Column Details list shows the new column order. 4. Click OK.
To reset column widths and order
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Column Details. The Column Details page appears. 3. Click Reset. The column widths, names, and order are reset to their default values. 4. Click OK.
Sort Alarms
You can configure how the Alarm Control sorts alarm rec ords at run time. By default, the Alarm Control lists alarm records by time in ascending order.
35

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

You can sort alarm records in ascending or descending order based on a first sort criteria, an optional second sort criteria, an optional third sort criteria, and and optional fourt h sort criteria.

You can configure the sorting columns and directions either in lists or with the grid preview. Us e the SortColumn.First Property, SortColumn.Second Property, and Sort Column. Third Property properties in scripting to set the columns to be sorted at run time. Use the S ortOrder.First Property, SortOrder.S econd Property, and SortOrder. Third Property properties in scripting to set the sort direction for each at run time.
To set sorting columns and directions with lists
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Column Details. The Column Details page appears. 3. In the Sorting area, do the following:
a. Select the primary sort column in the First Sort Column list and a sorting direction in the list to its right.
b. Optionally, select the secondary sort column in the Second Sort Column list and a sorting direction in the list to its right.
c. If you set the Second Sort Column, optionally select the tertiary sort column in the Third Sort Column list and a sorting direction in the list to its right.
The grid preview is updated and shows arrows for the sorted columns and their sort directions.
To set sorting columns and directions with the grid preview
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Column Details. The Column Details page appears. 3. In the grid preview, click on a column to select it for sorting. An arrow appears on the column header
and the change is also shown in the Sorting area lists. 4. To change t he sorting direction, click on the column header again. The arrow changes on the c olumn
header and the change is also shown in the Sorting area lists.
36

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Note: If you click on a column header after releasing the Shift key, all sorting information is lost and the selected column is the new primary sorting criteria.
5. To set second, third, and fourth sorting, hold the Shift key and repeat from step 3.
6. Release the Shift key.
7. Click OK.
Filter Alarms
You can filter current and historical alarms by using queries and filters. Queries and filters are collections of filter criteria in a logic al construct.
For example, you can filter alarms by defining a query or a filt er that only shows alarms with priorit ies larger than 500 and smaller than 750.
You can re-use the filters and queries you define for historical alarms for current alarms and vice versa. You can also re-use filters and queries you define at design time at run time and vice versa.
Important: Queries and filters for current alarms and recent alarms and events require at least a Provider and Group as filter criteria. These must use the equals sign or a message asking for those fields will appear.
When you use TimeLCT, TimeOA T, or TimeLCTOA T as filter criteria for historical alarm modes, you need make sure that the TimeS elector.Start Date and TimeSelector.EndDate properties do not limit the query. Otherwise the Alarm Control can possibly not return all alarm and event records.
Set the TimeSelector.StartDat e property earlier than any time filtering requirement, and the TimeSelector.EndDate later than any time filtering requirement.
Using Wildcards in Queries
In current alarm queries, you can use wildcards only in the Tagname part of t he query and not in the Provider, Group, or Node part of the query. A valid ex ample is: \galaxy!Mixing!RotorBlade*
In query filters that are used for current queries, the same restrictions apply.
In query filters that are used for historical queries, you must convert the operat or and wildcard to SQL syntax according to the following table:

Current Query

Hi storical Query

Operator

=

Like

Wildcard

*

%

For example: Provider = `galaxy' AND Group = `Mixing' AND Name Like `RotorBlade%'
If y ou want to use a query filter cont aining a wildcard for a current query and a historical query, create two separate query filters. If a column cont ains null data, it cannot be retrieved using the Like operator.

Use an Existing Query or Filter
You can use an existing query filter to filter the alarms shown in the ArchestrA Alarm Control. You can also use the Favorite Property string property in scripting to switch to an existing query fi lter at run-time.

37

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

To use an existing query filter
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Queries and Filters. The Query and Filter Favorites page appears. 3. In the Query and Filter Favorites list, select a query or filter by clicking the check box before each
query or filter name.

4. Click OK. Note: In Current Alarms mode, if you try to proceed from Queries and Filters page with no query or filter selected, you will be prompted with a message to confirm you want to continue. Upon click of Yes the default query will be selected and you can continue. Upon click of No, you will be returned to the Queries and Filters page. If a query is selected but no filter, no message will display. In Historical Alarms mode, if you proceed without a query selected but have selected a filter, the filter will be applied. If neither query nor filter is selected, you will be prompted with the same message.
Add a New Query or Filter
You can define a new query filter to filter the alarms shown in the ArchestrA Alarm Control. The new query filter is saved as a favorite in the Query Filter Favorites list.
To add a new query filter
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears.
38

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

2. Click Queries and Filters. The Query and Filter Favorites page appears.

3. Click the Add New Query button above the saved query favorites box or click the Add New Filter button above the saved filter favorites box. The Add Query or Filter dialog box appears.
4. Construct queries or filters as needed. For more information, see Construct Filters on page 40.
39

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

Construct Filters
You use the Add Query or Filter dialog box to creat e or edit a filter graphically.

To construct a filter
1. If you want to change the filt er name, type a new unique name in the Filter Name box. 2. Add filt er criteria to the construction area by selecting a column name on the left and clicking the right
arrow button. When you add filter criteria to the construction area, they are automatically logically connected by AND.
3. If nec essary, remove filter criteria by selecting them in the filter construction area and clicki ng the left arrow button.
4. To change the logical operator, select it in the filter construction area, and then either: o Click AND or OR o Right -click and select AND or OR from the shortcut menu
5. To group filter criteria logically, either: o Drag a filt er criteria in the construction area over another filter criteria o Select one filt er criteria, click Group, and then click the other filter criteria By default, the filter criteria are logically grouped with AND. If necessary, you can select the AND item in the tree and click OR to change it to an OR grouping.
6. Assign values to filter criteria.
40

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Note: If you are using the Value column as a filt er criteria, you may get unexpected results at run time. The items in the Value column are sorted alphabetically, not numerically. This is becaus e the Value column can contain strings.
Do the following:
a. Select a filter criteria in the construction area. b. Select an operat or from the Operator list. c. Type or select a value in the Value box.

d. Click Set. The filter criteria is updated in the construction area. 7. To cut, copy, or paste individual filter criteria or filte r criteria branches, right-click on the filter criteria
and select the appropriate option from the shortcut menu. 8. When you are done, click OK.
Modify an Existing Query or Filter
You can modify an existing query or filt er using the Modify Query or Filter dialog box.
To modify an existing query or filter
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Queries and Filters. The Queries and Filters page appears. 3. Select an existing query or filter in the Query and Filter Favorites list by clicking on the check box
before each query or filter name. 4. Click the ellipsis button. The Modify Query or Filter dialog box appears. For more information, see
Construct Filters on page 40. 5. Click OK.
Delete a Query or Filter Favorite
You can delete any non-default query or filter favorite.
To delete a query or filter favorite
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Queries and Filters. The Queries and Filters page appears. 3. Select an existing query or filter in the Queries and Filter Favorites list by clicking on the check box
before each query or filter name. 4. Click the Delete selected query button or click the Delete selected filter button. 5. When a message appears, click Yes.
41

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

Export Query and Filter Favorites
You can export the query and filter favorites lists to an XML file. The XML file containing the query and filter favorites can be imported to other Alarm Control in design time or run time. Do not edit this file directly. The default query is also exported to the XML file.
To export the query and filter favorites lists
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Queries and Filters. The Queries and Filters page appears. 3. Select an existing query or filter in the Query and Filter Favorites list by selecting the check box
before each query or filter name. 4. Click the Export button. Select a location and a name for the XML file and click Save.
Import Query and Filter Favorites
You can import the query filt er favorites list from an XML file.
To import the query filter favorites list
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Queries and Filters. The Queries and Filters page appears. 3. Click Import. Navigate to the XML file you want to import.

4. In the Import Option list, click either: o Append to append the imported query filters to the existing query filters. If query filter names in the imported XML conflict with existing query filters, you are prompted to confirm the import for each filter o Overwrite to replace all existing query filters with the imported query filters
5. Select the XML file and click Open.
42

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Setting Time Zone and Format
You can set the time zone in which the client shows the alarm and event records. By default, the time zone is set to the client computer's current time zone at design time. Use the TimeZone. TimeZone Property, Time. Type Property, and Time.Format Property properties in scripting to set the time zone, time type, and time format at run time.
You can also set the time format of the alarm and event records. You can select bet ween two different time format sets:
 Default Time Format: same as the InTouch Alarm Viewer control and InTouch Alarm DB View control of InTouch version 10.0 and lat er
 .NET Time Format: defined by Microsoft .NE T Framework time format conventions

Set the Time Zone
You can set the time zone in which the Alarm Control shows the alarm and event records. You can either set the time display to a predefined time zone, or to the client time zone. The client time zone is the time zone of the computer on which the Alarm Control is running. The Client Time Zone setting is useful if you are deploying an application usin g the Alarm Control to a different time zone. For example, if you develop your applic ation in the Pacific Time zone and deploy it to two computers in the time zones Central Time and Eastern Time, you can ens ure the Alarm Cont rol shows the local time for each deployment by setting the time zone to Client Time Zone.
To set the time zone
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Time Settings. The Time Settings page appears.
43

AVEVATM ArchestrA Alarm Control Guide 3. In the Time Zone list, select a time zone.

Configure the Alarm Control

4. Click OK.

Set a Time Format
You can set the time format in which the Alarm Control shows the alarm and event records. You can either us e a predefined datetime format, or compose one.
To set the time format
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears.
2. Select Time Settings. 3. In the Time Format area, do the following:
a. Make sure Use .NET Time Format is cleared.
b. Select date format codes from the list at the right. The equivalent dat e format code appears in the box above.
c. Select time format codes from the list at the right. The equivalent time format code is appended to the date format string.
4. If you want to customize the datetime format, modify the codes in the box as follows:

Code

Purpo se

Example

%m

Two-digit month

%b

Three-letter month

%B

Full month name

%d

Two-digit day

%Y

Four-digit year

%y

Two-digit year

%#x

Full day and date

03 Mar March 17 2008 08 Tuesday, March 11, 2008

44

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Code

Purpo se

Example

%H

Hours in 24 hour format

14

%I

Hours in 12 hour format

2

%M

Minutes

55

%S

Seconds

34

%s

Milliseconds

223

%p

AM or PM

PM

5. Click OK.

Set a .NET Datetime Format
You can set the .NE T datetime format in which the Alarm Control shows the alarm and event records. You can either use a predefined datetime format, or compos e one. The predefined date format is based on the short date format setting of the operating system and may vary from computer to computer.
To set the .NET datetime format
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears.
2. Click Time Settings. The Time Settings page appears.
3. In the Time Format area, do the following:
a. Select the Use .NET Time Format check box.
b. Select date format codes from the list at the right. The equivalent dat e format code appears in the box above.
c. Select time format codes from the list at the right. The equivalent time format code is appended to the time format string.
4. If you want to customize the datetime format, modify the codes in the box as in the table below. For more information, see the Microsoft Knowledge database on .NE T datetime formats.

Code

Purpo se

Example

M MM MMM MMMM

Single-digit month Two-digit month Three-letter month Full month name

9 09 Sep September

d dd ddd dddd

Single-digit day Two-digit day Abbreviated day of the week Day of the week

8 08 Mon. Monday

45

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

Code

Purpo se

Example

yyyy

Four-digit year

2008

yy

Two-digit year

08

HH

Hours in 24 hour format

14

hh

Hours in 12 hour format

2

mm

Minutes

55

ss

Seconds

34

fff

Milliseconds

223

tt

AM or PM

PM

5. Click OK.
Configuring Run-Time Behavior
You can configure the behavior and appearance of the Alarm Control at run time, for example:  Showing and Hiding parts of the Alarm Control  Specifying if the Alarm Control queries the alarm database when it starts up  Scrolling to new alarms  Hiding warnings, errors, and messages  Restricting operator access to parts of the Alarm Control  Specifying Alarm Control freez e behavior  Customizing the "no rec ords" message  Configuring alarms to require an ACK signature  Configuring alarms to require a SHE LVE signature

46

Configure the Alarm Control  Customizing the run-time shortcut menu

AVEVATM ArchestrA Alarm Control Guide

Show Heading, Grid, or Status Bar
You can show and hide parts of the Alarm Control at run time, such as the heading, grid, or status bar. Use the ShowHeading Property, ShowGrid Property, and ShowStatusBar Property properties in scripts to show or hide the heading, grid, and status bar at run time.
To show the heading, grid, or status bar at run time
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. To show or hide parts of the Alarm Control during run time, do any of the following:
o Select the Show Heading check box to show the heading at run time, or clear it to hide the heading at run time.
o Select the Show Grid check box to show the grid at run time, or clear it to hide the grid at run time.
47

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

o Select the Show Status Bar check box to show the status bar at run time, or clear it to hide the status bar at run time.
Caution: If you hide the status bar, you will not be able to see important indicators, such as the New Alarms, Hidden Alarms, and Frozen Grid indicators.
4. Click OK.
Automatic Query for Alarms on Start Up
You can configure the Alarm Control to aut omatically query the Alarm Database when the control starts up at run time. Use the QueryStart up Property in scripts to control query behavior when the Alarm Cont rol starts. By default, current alarms and recent alarms and events are automatically queried when the Alarm Cont rol starts at run time. You can disable the automatic query if the Alarm Control is:  Configured to mainly use query filters  Cont rolled mainly by scripts
To query the Alarm Database automatically on start up
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. Select the Query on Startup check box. 4. Click OK.
Scroll Automatically to New Alarms
If an operator views multiple pages of alarms, new alarms may go unnoticed. You can configure the Alarm Control to scroll automatically to show new alarms. Use the AutoScroll Boolean property in scripts to scroll automatically to new alarms. However, if the Alarm Control scrolls automatically to new alarms, it may be hard for the operat or to view and analyze older alarms if new alarms occur. If the Alarm Control is frozen, it will not scroll aut omatically to new alarms.
To scroll automatically to new alarms
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. Select the Auto Scroll to New Alarms check box. 4. Click OK.
Hide Errors, Warnings, and Status Messages
You can prevent a message dialog box from opening when errors, warnings, or status messages occur in the Alarm Cont rol. E ven if you hide errors, warnings and status messages are sent to the ArchestrA Logger. Use the HideErrors property in scripts to hide error, warning, and status messages at run time.
To hide error and warning messages
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. Select the Hide Errors and Warnings check box. 4. Click OK.

48

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Restrict User Access to Rows and Columns
You can prevent the operator from:  Resizing columns  Selecting rows  Selecting multiple rows Use this feat ure for interfac es where it is easy to accidentally resize columns or select rows. For example, if the Alarm Cont rol is running on a small display, use the AllowColumnResize Property and RowSelection Property properties in scripting to control the ability to resize columns and select rows at run time.
To prevent the operator from resizing columns
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. Clear the Allow Column Re sizing check box. 4. Click OK.
To prevent the operator from selecting rows
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. In the Row Selection list, click:
o No to prevent operator from selecting rows o Single to allow operator to only select one row o Multiple to allow operator select multiple rows 4. Click OK.
Retain Hiding when Changing Alarm Query Filter
You can configure the Alarm Control to hide alarms even if the alarm query filter changes. Use the RetainHidden Property in scripts to retain the hiding of alarms at run time.
To retain hiding when change the alarm query filter
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. Select the Retain Hidden check box. 4. Click OK.
Override the Frozen Grid
You can configure the Alarm Control to unfreeze the grid after a given time in seconds. Use this option to make sure that new alarms appear on the grid after a specified time. Use the AutoResumeDuration Property in scripts to unfreeze the Alarm Control after a cert ain duration at run time. The Alarm Control also unfreezes if you change one of the following:  Alarm Mode  Alarm Query

49

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

 Query Filter
To override the frozen grid
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears.
3. Select the Auto Re sume after check box and type the number of seconds after which the grid unfreezes.
4. Click OK.
Customize the "No Records" Message
You can customize the message that appears when there are no rec ords to show in the grid. Use the NoRecordsMessage.Enabled Property and NoRec ordsMessage.Message Property in scriptw to customize the "no records" message at run time.
To customize the "no records" message
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. Select the Show Custom `No Records' Message check box and type a message you want to show
in the Alarm Cont rol when there are no alarm records. 4. Click OK.
Changing the Language of the "No Records" Message
You can change the language of the message that appears when there are no records to show in the Alarm Control grid.
To change the language of the "No Records" Message
1. Right -click on the canvas and click Scripts. The Edit Scripts dialog box appears. 2. Click the Add icon and give the script a name, for example ChangeLanguage.
3. In the Expre ssion box, type: intouch:$Language
4. In the Trigger list, click DataChange. 5. In the script area, type the following:
If intouch:$Language == 1033 then ' Switch to English AlarmClient1.NoRecordsMessage.Message = "No Records";
else If intouch:$Language == 1031 then ' Switch to German AlarmClient1.NoRecordsMessage.Message = "Keine Eintr�ge";
else if intouch:$Language == 1036 then ' Switch to French AlarmClient1.NoRecordsMessage.Message = "Aucun enregistrement"; endif; endif; endif;
6. Click OK.
Configure the Alarm Control to Require an ACK Signature
E ven if you are logged into the InTouch application, acknowledging the alarms that fall within a specific priority range may need to be authenticated by you if required by your company or industry. You can configure the Alarm Control to provide such functionality by selecting the Require s ACK Signature check box in the Object Properties dialog of the Alarm Cont rol.
50

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

After the Alarm Control has been configured to require a signature for acknowledgement, you need t o set its minimum and maximum priority values. The valid range of the minimum and maximum priority values is 1 to 999.
To configure the Alarm Control to require ACK signature
1. Place an Alarm Control in the drawing canvas.
2. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears.

3. Click Run-Time Behavior. The Run-Time Behavior page appears. 4. Select the Requires ACK Signature check box. The Min Priority and Max Priority boxes are
enabled. 5. Enter the minimum and maximum priority values for the alarm range that will require aut hentication. 6. Click OK. You can configure the alarm signature requirement as well as the minimum and maximum values in run time using the Object Editor. For more information about using the Object Editor, see the Application Server User's Guide, Chapt er 3, Working with Objects. For more information about configuring the Alarm Control in run time to require an alarm acknowledgement signature, see the "SignedAlarmAck() Applied Examples" topic in the Creating and Managing Industrial Graphics User's Guide. Note: If your computer supports Smart Cards, you can use them for alarm authentication at run time. You need to have the Smart Card mapped to your user account in the domain. If the Smart Card is already in the reader and you enter the correct PIN, the system will allow you to acknowledge the alarms.
51

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

Configuring the Alarm Control to Require a SHELVE Signature
Operators can temporarily shelve selected alarms from the list of an Alarm Control's active alarms. A shelved alarm is suppressed and removed from the list of active alarms. Typically, operators shelve lower severity nuisance alarms becaus e they provide little diagnostic value and interfere with the operator's ability to manage a plant process.
An alarm is shelved for a specified period. After the period ends, alarms are automatically unshelved and appear again in the list of active alarms. Operators can also manually unshelve an alarm before the end of the specified shelved period.
By default, Medium and Low severity alarms are enabled for shelving. Critical and High severity alarms are not because of the potential risk of shelving and ignoring alarms that repres ent serious operating states. For more information about enabling shelving based on alarm severity, see "Configuring Alarm Severity to Priority Mapping" in the Application Server Us er Guide.
The Alarm Control provides a configuration option to restrict alarm shelving only to operators authorized by application security. When an operator selects one or more alarms and attempts to shelve them, the Alarm Control verifies if a shelve signature is required.
 If no SHE LVE signature is required
The Alarm Control shows a simple Shelve Comment dialog box with a Duration field to select the number of hours (1, 2, 4, 8, 12) to shelve the alarm and a Reason field to enter a mandatory comment.

 If a SHELVE signat ure is required and application security is active
The Alarm Control shows a Shelve Comment dialog box with fields for the operator to enter user credentials (name, password, domain) in addition to selecting a shelve duration and entering a mandatory comment.

By default, the logged-in user appears in the Username field. If the application security type is Arche strA, then ArchestrA appears in the Domain field and cannot be edited. If the credentials are valid, the Alarm Control attempts to shelve the selected alarms.
52

Configure the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

The Alarm Control shows an error message if the operat or enters invalid credentials. When the operator clicks OK on the error message, the Shelve Comment dialog appears again with the entered user name, comment, and duration. The Password (or PIN) is blank. The operator can attempt to authenticate again or cancel.
To configure the Alarm Control to require a SHELVE signature
1. Place an Alarm Control in the drawing canvas.
2. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears.
3. Click Run-Time Behavior. The Run-Time Behavior page appears.
4. Select or clear Requires SHELV E Signature based on whether operators need to enter their credentials to shelve alarms or not.
5. Click OK.
Configuring the Run-Time Shortcut Menu
You can configure the Alarm Control's shortcut menu to show only selected options at run time. The shortcut menus showing historical alarms (or events) and current alarms (or recent alarms and events) are different.

For the current alarms Cont ext menu, you can also show or hide entire shortcut submenus. Use the Cont extMenu and the ShowContextMenu Property in scripting to control if shortcut menu items appear or not at run time.
To hide the Context menu
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. Clear the Show Context Menu check box. 4. Click OK.
53

AVEVATM ArchestrA Alarm Control Guide

Configure the Alarm Control

To show or hide Context menu options
1. Double-click the Alarm Control on the canvas. The Edit Animations dialog box appears. 2. Click Run-Time Behavior. The Run-Time Behavior page appears. 3. Make sure the Show Context Menu check box is selected.In the shortcut menu lists, do the
following: a. Select the options you want to appear on the run-time Context menu (if applicable for the
selected client mode).
b. Clear the options you want to hide from the operator on the run-time Context menu. 4. Click OK.

54

AVEVATM ArchestrA Alarm Control Guide
CHAPTER 3
Use the Alarm Control at Run Time
During run time, users can show a shortcut menu containing options to monitor and manage alarms. Also, other options enable users to sort and filter alarms shown by the Alarm control.
Refresh the Alarm Control Grid
You can refresh the Alarm Control grid at run time. The Alarm Control retrieves alarm record data based on the Alarm Dat abase time range settings.
To refresh the alarm control
1. Right -click the Alarm Cont rol grid at run time. The shortcut menu appears. 2. Click Requery.
View Status Bar Information
The status bar shows you information about the current Alarm Control grid. Depending on the client mode, the status bar information shows different information.
Using Status Bar Information of Current Modes
If the Alarm Cont rol is showing current alarms or recent alarms and events, the status bar shows the following:

Element

Icon(s) Description

Client Mode New Alarms Hidden Alarms

Indicates the Alarm Cont rol is showing current alarms (or rec ent alarms and events).
Appears if new alarms have occurred. If you move the pointer over the indicator, the tooltip shows how many alarms are unacknowledged.
Appears if any alarms are currently hidden. If you move t he pointer over the indicator, the tooltip shows how many alarms are hidden.

Frozen Grid Alarm Records
Query Filter

Appears if the Alarm Control is currently frozen.
Shows the total number of alarm records and which alarms are currently shown.
Shows the name of the current query filter favorite. 55

AVEVATM ArchestrA Alarm Control Guide

Use the Alarm Control at Run Time

Element Retri e val
Time Zone

Icon(s) Description
Shows the percentage of alarms retrieved from all alarm providers. If this percentage is less than 100%, not all alarm providers are providing alarm data. Use the Alarm Statistics dialog box to detect which alarm providers are not providing alarm dat a.
Shows the current time zone of the Alarm Control. Move the pointer over the time zone to show the full information in a tool tip.

Using Status Bar Information of Historical Modes
If the Alarm Cont rol shows historical alarms or events, the status bar shows the following fields:

Element Client Mode

Description Indicates the Alarm Cont rol is showing historical alarms and/or events.

Alarm Records Alarm Database Connection Status Time Zone Requery

Shows the total number of alarm records and the number of alarms shown by the Alarm Control.
Shows the name of the server hosting the Alarm Dat abas e and the Alarm Database name.
Shows the connection status to the Alarm Database.
Shows the current time zone of the Alarm Control. Move the pointer over the time zone to show complete time zone information in a tool tip.

Click this button to retrieve latest alarm records from the Alarm Database.

56

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

Acknowledge Alarms
You can configure the Alarm Control to require an alarm to be acknowledged even if the condition causing the alarm has passed. This ensures that an operat or is aware of events that caused a t emporary alarm state, but have returned to normal. You acknowledg e alarms at run time using a shortcut menu or by script methods.
You can acknowledge alarm records directly from the Alarm Control. You can acknowledge:
 One or more selected alarms
 All alarms, including alarms not visible due to the limited space of the A larm Control
 All visible alarms
 All alarms with common values, such as provider names, group names, priority ranges, and tag names. You can simplify alarm acknowledgement for the operat or by using methods in scripting. For more information, see the Ack .All() Method on page 117.
To acknowledge selected alarms using the Alarm Control grid
1. Select one or more alarms in alarm state.
2. Right -click on an alarm shown in the Alarm Control and click Ack Selected.
If no default acknowledgement statement is configured for the Alarm Control, the Ack Comment dialog box appears.
3. Type an alarm acknowledgement comment and click OK.
To acknowledge other alarms using the Alarm Control grid
1. Select one or more alarms in alarm state.
2. Right -click the Alarm Cont rol grid, point to Ack Others, and click one of the following:
o Ack All to acknowledge all alarms in alarm state
o Ack Vi sible to acknowledge all visible alarms
o Ack Selected Group to acknowledge alarms with the same provider names and group names of one or more selected alarms in alarm state.
o Ack Selected Tag to acknowledge alarms wit h the same provider names, group names, and tag names within the priority ranges of one or more selected alarms in alarm state.
o Ack Selected Priority to acknowledge alarms with the same provider names, group names, and within the priority ranges of one or more selected alarms in alarm state.
3. If no default acknowledgement statement is configured for the Alarm Control, the Ack Comment dialog box appears.
4. Type an alarm acknowledgement comment and click OK.
Provide a Signature to Acknowledge Alarms
You must provide your signature in the Ack Alarm s dialog box to acknowledge alarms. A signature is required when the Require ACK Signature check box is selected and any of the selected alarms falls within the configured priority range, or if no one is logged on to the InTouch application. You a re not required to be logged on to the InTouch application to acknowledge alarms. However, if you are logged on, the Username box displays the username.
When you select the Require ACK Signature check box, the acknowledgment comment is prefixed in the updated Alarm Record. If one or more of the selected alarms falls within the configured priority range, the comment is prefixed with "Signed ACK -" indicating that it is a signed acknowledgment. Otherwise, it is prefixed with "Std ACK -" indicating that it is a standard acknowledgment.
57

AVEVATM ArchestrA Alarm Control Guide

Use the Alarm Control at Run Time

Note: If the selected alarms do not require a signature, then the Ack Alarms dialog box displays the Comment box. You can enter a comment before acknowledging the alarm.
To provide a signature to acknowledge alarms with user name
1. Select one or more alarms in the alarm state.
2. Right -click the Alarm Control grid and click Ack Selected.
3. If the selected alarms require a signature, or if you are not logged on to InTouch, then the Ack Alarms dialog box appears. If the Smart Card authentication system is not configured on your computer, the following dialog appears:

4. In the Comment box, enter or modify the alarm comment. 5. In the Username box, enter your user name. 6. In the Pa ssword box, enter your password. 7. In the Domain box, enter the domain and click OK.
Note: If you enter invalid credentials, the Alarm Control displays an error message. When you click OK, the ACK Alarm s dialog box appears again with the user name and the comment you had provided. You must enter the correct password.
Providing a Signature to Acknowledge Alarms Using Smart Cards
You can use a Smart Card to provide the authentication to acknowledge alarms if your comput er supports Smart Card authentication. In that case, the Alarm Control displays the Ack Alarm s dialog box with the Smart Card aut hentication dialog. You must have the Smart Card inserted in the Smart Card reader attached to your computer.
To provide a signature to acknowledge alarms using Smart Cards
1. Select one or more alarms in an alarm state. 2. Right -click the Alarm Cont rol grid and click Ack Selected.
58

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

3. If the selected alarms are configured to require a signature and if Smart Card Authentication is selected in InTouch, the Ack Alarm s dialog box appears where the Smart Card button under Mode is disabled.

4. In the Comment box, enter or modify the comment. 5. From the Certificate list, select the Smart Card currently inserted into the reader in your system.
Note: If a card is newly-inserted or removed from the reader, you can update the list of cards by selecting the appropriate Smart Card from the Certificate list. 6. In the PIN box, enter the personal identification number and click OK. a. If you enter an invalid PIN, the system displays an error message. When you click OK, the ACK
Alarms dialog box appears again with the user credential and the comment you had pr ovided. You must enter the correct PIN. b. If you need to provide your log on credentials instead of the Smart Card det ails to verify your signature, click the User Name Authentication button under Mode. A different version of the Ack Alarms dialog box appears where the Smart Card button under Mode is enabled.
Shelve and Unshelve Alarms at Run Time
Operators can shelve alarms to temporarily suppress them for a fixed period. Shelving an alarm means temporarily removing it from the Alarm Control's main alarm list and placing it on a shelved list. Shelvi ng is normally controlled by an operator to handle irrelevant nuisance alarms that have not been caught by filtering or alarm suppression mechanisms.
59

AVEVATM ArchestrA Alarm Control Guide

Use the Alarm Control at Run Time

When shelving an alarm from the Alarm Cont rol, operators set an associated time period in which the alarm remains shelved and enter a mandatory comment. Operators can select from a list of Alarm Cont rol Context commands during run time to:
 Shelve one or more selected alarms
 Shelve all alarms
 Shelve only those alarms visible in the Alarm Control
 Shelve all alarms within the same alarm group as an alarm selected from the Alarm Control
 Shelve alarms by selected tags or attributes
 Shelve alarms by selected alarm priorities
 Shelve all alarms that have the same severity as an alarm selected from the Al arm Control When application security is used, alarms can be shelved and unshelved only by operators with proper authorization. For more information about setting shelving authorization, see Configuring the Alarm Cont rol to Require a S HELVE Signature on page 52.
Shelved alarms are aut omatically unshelved at the end of the specified time period.Operators can also manually unshelve alarms and return them to an active state. Alarms are uns helved automatically at the end of the shelving time period. An unshelved alarm reappears in the Alarm Control active list and resumes its state at the time it was shelved. Operators can manually unshelve a shelved alarm before the end of the shelved period and enter an optional comment.
Shelving Alarms
You can shelve alarms directly from the Alarm Control by selecting commands from the Alarm Control's Cont ext menu.
To shelve selected alarms using the Alarm Control
1. Select one or more alarms in alarm state.
2. Right -click the Alarm Cont rol grid and click Shelve Selected from the shortcut menu.
The Shelve Comment dialog box appears to set a shelf duration and enter a comment.

Note: If the application runs under security and the Alarm Control has been configured to require a SHELVE signature, operators must authenticate themselves. The Shelve Comment dialog box includes additional fields for an operator to enter a username, password, and domain. 3. Select an alarm shelving duration from the Duration field. 4. Type a mandatory alarm shelving comment in the Rea son field and click OK.
To shelve other alarms using the Alarm Control
1. Select one or more alarms in alarm state. 2. Right -click the Alarm Cont rol, point to Shelve Others, and click one of the following shortcut
commands: o Shelve All to shelve all alarms in alarm state
60

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

o Shelve Visible to shelve all visible alarms
o Shelve Selected Groups to shelve alarms with the same provider names and group names of one or more selected active alarms
o Shelve Selected Tags to shelve alarms with the same provider names, group names, and tag names of one or more selected active alarms
o Shelve Selected Priorities to shelve alarms with the same provider names, group names, and within the same priority ranges of one or more selected active alarms
o Shelve Selected Severities to shelve alarms with the same provider names, group names, and within the same severity ranges of one or more selected active alarms
The Shelve Comment dialog box appears with fi elds to set a shelf duration and ent er a comment.
3. Select an alarm shelving duration from the Duration field.
4. Type an alarm shelving comment in the Reason field and click OK.
Show Shelved Alarms
After alarms are shelved, they no longer appear as active alarms in an Alarm Control. Filters only filter active alarms, so applying only a filter will not ret urn shelved alarms. To show shelved alarms, you must use a query and apply a filter that is configured for shelved alarms.
For example:
(Provider = 'Galaxy' AND Group = 'Area_Name' AND (State = 'S HELVE_A CK_RTN' OR State = 'SHELVE _UNACK ' OR State = 'SHELVE_UNACK_RTN' OR State = 'SHELVE _ACK '))"

For more information about configuring queries to filter alarms, see Filter Alarms on page 37. 61

AVEVATM ArchestrA Alarm Control Guide

Use the Alarm Control at Run Time

Unshelve Alarms
Manually unshelving alarms follows a similar sequence of steps to shelve alarms using Context menu commands. You should have created a query that shows the current shelved alarms.

To unshelve selected alarms using the Alarm Control
1. Select one or more shelved alarms. 2. Right -click the Alarm Cont rol grid and click Unshelve Selected from the Context menu.
The Unshelve Comment dialog box appears.
3. Type an optional alarm unshelving comment in the Rea son field and click OK.
To unshelve other alarms using the Alarm Control
1. Select one or more alarms in alarm state. 2. Right -click the Alarm Cont rol, point to Unshelve Others, and click one of the following shortcut
commands: o Unshelve All to unshelve all shelved alarms o Unshelve Visible to unshelve all visible shelved alarms o Unshelve Selected Groups to unshelve alarms with the same provider names and group
names of one or more selected shelved alarms o Unshelve Selected Tags to unshelve alarms with the same provider names, group names, and
tag names of one or more selected shelved alarms o Unshelve Selected Priorities to unshelve alarms with the same provider names, group names,
and within the same priority ranges of one or more selected shelved alarms o Unshelve Selected Severities to unshelve alarms with the same provider names, gr oup
names, and within the same severity ranges of one or more selected shelved alarms The Unshelve Comment dialog box appears. 3. Type an optional alarm unshelving comment in the Rea son field and click OK.
62

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

Sort Alarms at Run Time
The Alarm Control supports alarm sorting for up to three columns at design time and run time. At run time, operators can configure sorting of even more columns by clicking on the column headers of the Alarm Control. You can sort alarms in ascending or desc ending direction for selected columns.
You can sort alarms at run time in similar way as design time. Any changes you make to t he sorting at run time are lost when you switch back to design time.
Note: If you are sorting by the Value column, the items in the column are sorted alphabetically, not numerically. This is becaus e the Value column can contain strings.
To set sorting columns and directions with lists at run time
1. Right -click the Alarm Control grid and click Sort. The Sort dialog box appears.

2. In the First Sort Criteria list, select the first sort column and a sorting direction in the list to its right. 3. Optionally, select the second sort column in the Second Sort Criteria list and a sorting direction in
the list to its right. 4. If you set the Second Sort Column, optionally select the third sort column in the Third Sort Criteria
list and a sorting direction in the list to its right. 5. Click OK.
To set sorting columns and directions in the grid at run time
1. In the Alarm Control grid, click on a column header to set sorting for the column. An arrow appears on the column header.
2. To change the sorting direction, click on the column header again. The arrow changes direction on the header.
Note: If you click on a column header after releasing the Shift key, all sorting information is lost and the selected column is the new primary sorting criteria.
3. To set sorting for second and third columns, repeat step 3 while pressing the Shift key. 4. Release the Shift key.
Filter Alarms at Run Time
You can filter alarms at run time by using the filters you defined at design time. If you did not define a filter according to your needs at design time, you can still create new filt ers at run time, or modify existing filters. If you saved filters to an XML file, you can load them from a file at run time. Filters you define at run-time are not saved for use at design-time. To re-use filters you create or modify at run-time, export the filter list to an XML file, and import the XML file at design -time.
63

AVEVATM ArchestrA Alarm Control Guide

Use the Alarm Control at Run Time

Naming conflicts may occur between the run-time and design-time XML lists. To resolve naming conflicts between the XML files, leave the Overwrite design time queries and filters option checked in the Run-Time Behaviors tab of the Edit Animations dialog box. The run-time query or filter list will overwrite the design-time list and resolve the naming conflict.
If you are showing historical alarms or events, you can use the filtering mec hanism provided by the grid technology instead of using filter favorites.
Use an Existing Query Filter
At run time, you can use any filt er you defined at design time, regardless if you defined it for the current modes or historical modes. You can also use scripting to switch to an existing query filter. For more information, see Favorite Property on page 100.
To use an existing query filter
1. Right -click the Alarm Control grid and click Queries and Filters. The Queries and Filters dialog box appears.
2. Select the filter from the list and click OK. The alarm records are filtered and the current filter name appears in the status bar.

Adding a New Query or Filter at Run Time
At run time, you can create new queries or filters to limit the number of alarm records.
New queries or filters are saved and can be reused for future sessions.Upon close and restart of either the Alarm Control window or WindowViewer, added queries or filters will be available. For details see Saving Run-Time Modifications to Queries and Filters on page 65.
To add a new query or filter at run time
1. Right -click the Alarm Control grid and click Queries and Filters. The Queries and Filters dialog box appears.
2. The configuration is the same as in design time. For more inf ormation, see Adding a New Query or Filter on page 38.
Modifying an Existing Query or Filter at Run Time
At run time, you can modify a query filter.
The modification of query filters is not saved for future use and is only valid for the current session. If you want to save the modific ations, you must also export the query filters to an XML file. For more information, see Exporting Query and Filter Favorites at Runtime on page 66
To modify an existing query filter
1. Right -click the Alarm Cont rol grid and click Query Filters. The Query Filters dialog box appears.
2. The configuration is the same as in design time. For more information, see Modif y an Existing Query or Filter on page 41.

64

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

Saving Run-Time Modifications to Queries and Filters
You can save modifications made to queries and filters at run time. There is an option to save user queries and filters in the Run-Time Behavior tab of the Edit Animations dialog box. It is selected by default, as shown below:

When this option is selected, modifications made to queries or filters at run-time are saved on a per user and alarm control instance to a XML file. For example, a saved query will save as UserQueryFilter_001.xml. Modifications are saved in the following default directory: C:\Users\<OS Login Name>\AppData\Local\Wonderware
The map bet ween the Alarm Control instance and the above XML file is saved in a map file, "InstancesMap.dat". Modified queries and filters will be available upon closing and restarting the alarm control window or W indowVi ew er. If you uncheck the Save User Queries and Filters option, updates made to queries and filters during run-time will not be saved.
Note: When the Save User Queries and Filter option is checked, the Overwrite Design Time Queries and Filters option is enabled and checked by default. When checked, this option resolves naming conflicts between design-time queries and filters and run-time queries and filters loaded from the XML file. Naming conflicts will be resolved by overwriting the design time queries and filters.
Deleting a Query or Filter at Run Time
At run time, you can delete a query filter. After you delete a query or filter at run time, it is only deleted for the current session. If you want to save the list of query filters without the deleted query filter, you must export the query filters to an XML file. For more information, see Export Query and Filter Favorit es on page 42.
To delete an existing query or filter at RunTime
1. Right -click the Alarm Control grid and click Queries and Filters. The Queries and Filters dialog box appears.
65

AVEVATM ArchestrA Alarm Control Guide

Use the Alarm Control at Run Time

2. The configuration is the same as in design time. For more information, see Delete a Query or Filter Favorite on page 41.

Importing Query and Filter Favorites at Runtime

At run time, you can import the list of query filters from an XML file.
To import Query Filter Favorites
1. Right -click the Alarm Cont rol grid and click Query and Filters. The Query and Filters dialog box appears.
2. The configuration is the same as in design time. For more information, see Import Query and Filter Favorites on page 42.

Exporting Query and Filter Favorites at Runtime
At run time, you can export the list of query filters to an XML file for future use. After ex porting, you can import the query filter from the XML into design time.
Note: The default query filter favorite is not exported to the XML file.
To export Query Filter Favorites
1. Right -click the Alarm Cont rol grid and click Query and Filters. The Query and Filters dialog box appears.
2. The configuration is the same as in design time. For more information, see Export Query and Filter Favorites on page 42.

Filtering Alarms with Client-Based Filtering

The grid technology used in the Alarm Control enables you to filter the grid contents after the data has been retrieved from the dat a source.
You can filter historical alarms and/or events in the following ways for any selected column:

Filter

Description

(All) (Custom )
(Blanks) (Non Bla nk s) Values

No filt ering, all records are shown for the selected column. Lets you configure a more complex filter for the selected column, for example a filter that can compare values of different columns. Filters by showing blank values only. Filters by showing non blank values only.
Filters by the selected value.

66

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

If a filter is applied to any column in the Alarm Control, the filter icon in the column header appears in blue.

To filter alarms with client-based filtering
1. Click the filter icon on the column you want to filter by. A menu appears.
2. Select one of the following: o (All) to switch off filt ering o (Custom ) to define a more complex filter o (Blanks) to filter by blank values o (NonBlanks) to filter by non blank values o A value to filter by the value

67

AVEVATM ArchestrA Alarm Control Guide If you selected (Custom), a dialog box appears.

Use the Alarm Control at Run Time

3. Do one of the following: o Select a different operator for the current condition
o Type or select a different operand for the current condition. The operand can be a value, or the value of a different column in the same row
68

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

o Click Add a condition to add more conditions to the filter

o Click Delete Condition to delete one or more selected conditions (You can mark the condition by clicking on the button to the left of each condition.)
4. Click OK.
Reset the Grid
You can reset the Alarm Control's column widt hs, column order, and names to their last design-time values. When you reset the grid, the query filter is also reset to its default. You can also reset the grid by using the Reset() Method on page 126 in scripting.
To reset the grid
 Right -click the Alarm Cont rol grid and click Reset
Hide Alarms
The "hiding" and "unhiding" of alarm records is known in the corres ponding InTouc h alarm controls as "suppressing" and "unsuppressing". When the Alarm Control is hiding alarms, it ignores certain alarms. If an alarm matches the exclusion criteria, it is not visible. The actual alarm generation is completely unaffected by hiding. Alarm records are still logged into the alarm history. You can hide:  All alarms, including alarms not visible due to the limited space of the Alarm Control  All visible alarms  One or more selected alarms  All alarms with the same provider names and group names of one or more selected al arms  All alarms with the same provider names, group names, and within the priority ranges of one or more
selected alarms
69

AVEVATM ArchestrA Alarm Control Guide

Use the Alarm Control at Run Time

 All alarms with the same provider names, group names, and tag names wit hin the priority ranges of one or more selected alarms
You can also view which alarms are hidden and unhide them.
To hide all alarms
 Right -click the Alarm Cont rol grid, point to Hide Others, and click Hide All
To hide all visible alarms
 Right -click the Alarm Cont rol grid, point to Hide Others, and click Hide Visible
To hide selected alarms
1. Select one or more alarms in alarm state. 2. Right -click the Alarm Cont rol grid and click Hide Selected.
To hide alarms with common parameters
1. Select one or more alarms.
2. Right -click the Alarm Cont rol grid, point to Hide Others, and click one of the following: o Hide Selected Groups to hi de al arms with the sam e provider names and group nam es of one or more selected alarms
o Hide Selected Tags to hide alarms with the same provider names, group names, and tag names within the priority ranges of one or more selected alarms
o Hide Selected Priorities to hide alarms with the same provider names, group names, and within the priority ranges of one or more selected alarms
To unhide alarms
1. Right -click the Alarm Cont rol grid and click Hidden. The Hidden Alarm s dialog box appears. 2. Select the alarms you want to unhide and click Unhide. 3. Click Close.
Freeze and Unfreeze the Alarm Control Grid
You can freeze the Alarm Control to prevent the Alarm control tree from being updated wit h any further changes.
For example, if new alarms occur while the Alarm Control is frozen, the new alarms are only shown after you unfreeze the Alarm Control. You can configure a time period after which the Alarm Control automatically unfreezes to avoid the Alarm Cont rol being unk nowingly frozen. For example, the operator leaves the workstation and returns without realizing that the Alarm Control is still frozen. The Alarm Control unfreezes automatically if one of the following changes:
 Alarm Mode
 Alarm Query
 Query Filter After you unfreeze the Alarm Control, the grid updates with t he new alarm records and any other updates while the grid was frozen. You can also use scripting t o freeze and unfreeze t he Alarm Control grid at run time. For more information, see Freez eDisplay() Met hod on page 121.

70

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

To freeze or unfreeze the Alarm Control grid
1. Right -click the Alarm Cont rol grid. The shortcut menu appears.

A check mark next to the Freeze option indicat es if the grid is currently frozen. 2. Click Freeze. The Alarm Control grid is either frozen or unfrozen.
Show Alarm Statistics
You can view alarm statistics at run time to see which alarm providers are providing the alarm data. For more information, see Show.Statistics() Method on page 137.
To show alarm statistics
1. Right -click the Alarm Cont rol grid and click Statistics. The Alarm Stati stics dialog box appears.
2. If you use an Alarm Hotbackup name as alarm query, you can expand the Hotbackup name in the Alarm Statistics dialog box to show the individual percentages of retrieval for the configured primary and backup alarm provider.
3. Click Update to update the statistics. 4. Click Close.
71

AVEVATM ArchestrA Alarm Control Guide

Use the Alarm Control at Run Time

Switching between Client Modes
You can switch bet ween client modes at run time by changing the Alarm Control ClientMode property. The easiest way to do this, is to configure an ArchestrA script to interact with the Alarm Control ClientMode property at design time.
To switch between client modes
1. Place the Alarm Control on the Industrial graphic.
2. Paste a button on the canvas and change its caption to Current Alarm s. 3. Double-click the button and configure it with the following action script:
AlarmControlGrid1.ClientMode = 1;
4. Click OK.
5. Repeat steps 2 to 4 for the following buttons:

Button Caption Recent Alarms and E vents Historical Alarms Historical E vents Historical Alarms and E vents

Action script AlarmControlGrid1.ClientMode = 2; AlarmControlGrid1.ClientMode = 3; AlarmControlGrid1.ClientMode = 4; AlarmControlGrid1.ClientMode = 5;

6. Save and close the Industrial graphic. 7. Create a new managed InTouch application and open it in WindowMaker. 8. Place the Industrial graphic on a new InTouch window. 9. Switch to WindowViewer to test your applic ation.

10. Click Hi stori cal Alarms to show historical alarms instead of current alarms. By default, the Alarm Control tries to connect to the alarm database (either the InTouc h Database called WWALMDB or the ArchestrA Database called A2ALMDB) on the local computer using the currently logged on user. If you are using a different configuration, you can use value input links or action script to set the following properties:  Database.ServerName Property  Database.Us erID Property  Database.Password Property  Domain Property  Database.Name Property  Database.Authentication Property
72

Use the Alarm Control at Run Time

AVEVATM ArchestrA Alarm Control Guide

Switching Run-Time Languages
You can switch the language of the Alarm Cont rol in the same way as other parts of your InTouch application. When you switch language, the alarm state, alarm class, alarm type, the various alarm comment fields, and the column headers are switched to the selected language.
To switch the language
Do one of the following:
o In WindowViewer on the Special menu, point to Languages, and then click the language you want to switch to

o In WindowMaker, use the InTouch QuickScript SwitchDi splayLanguage in a button action script to switch the language. At run time, click the button to switch the language
o In WindowMaker, use the system tag $Language in a button action script and assign it to the language code you want to switch to. At run time, click the button to switch the language
For more information about run-time language switching, see Chapter 11, Working with Languages, in the Application Server User's Guide.
Important: If you rename or reorder column headers, you must repeat the symbol text translation procedures. If you do not, your changes will not be available for run-time language switching.

73

AVEVATM ArchestrA Alarm Control Guide
CHAPTER 4
Scripting the Alarm Control
This section describes the script properties, methods, and events of the Alarm Control.
Alarm Control Properties
This section describes the properties available for scripting in the Alarm Control.
AckComment.DefaultValue Property
The AckComment.DefaultValue property is a read -write string property that gets or sets the default acknowledgement comment when the AckComment.UseDefault property is TRUE.
Syntax
result = AlarmClient.AckComment.DefaultValue; AlarmClient.AckComment.DefaultValue = ackComment;
Example
AlarmClient1.AckComment.UseDefault = 1; AlarmClient1.AckComment.DefaultValue = "This alarm is acknowledged by John Smith";
Remarks
For more information, see Showing Current Alarms or Recent Alarms and Events on page 21.
AckComment.UseDefault Property
The AckComment.UseDefault property is a read-writ e Boolean property that gets or sets the usage of the default acknowledgement comment.
Syntax
result = AlarmClient.AckComment.UseDefault; AlarmClient.AckComment.UseDefault = useComment;
Example
AlarmClient1.AckComment.UseDefault = 1; AlarmClient1.AckComment.DefaultValue = "This alarm is acknowledged by John Smith";
Remarks
For more information, see Showing Current Alarms or Recent Alarms an d Events on page 21.
AckSignature.MaxPriority Property
The AckSignature.MaxPriority property is a read-write integer property, which gets or sets the maximum priority value for alarms that require a signature to be acknowledged. The value must range between 1 and 999, and must be great er than or equal to the AckSignature.MinPriority value. The default value of AckSignature.MaxPriority is 999.
Syntax
To Set: <EAC instance name>.<Property Name> = <integer value>;
75

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Example
AlarmClient1.AckSignature.MaxPriority = 500;
Syntax:
To Get: integer <variable name> = <EAC instance name>.<Property Name>;
Example
dim iMax as integer; iMax = AlarmClient1.AckSignature.MaxPriority;
Remarks
For more information, see Provide a Signature to Ack nowledge Alarms on page 57.
AckSignature.MinPriority Property
The AckSignature.MinP riority property is a read -write integer property, which gets or sets the minimum priority value for alarms that require a signature to be acknowledged. The value must range between 1 and 999, and must be less than or equal to the AckSignature.MaxPriority value. The default value of AckSignature.MinPriority is 1.
Syntax
To Set: <EAC instance name>.<Property Name> = <integer value>;
Example
AlarmClient1.AckSignature.MinPriority = 100;
Syntax
To Get: To Get: integer <variable name> = <EAC instance name>.<Property Name>;
Example
dim iMin as integer; iMin = AlarmClient1.AckSignature.MinPriority;
Remarks
For more information, see Provide a Signature to Ack nowledge Alarms on page 57.
AckSignature.Required Property
The AckSignature.Required property is a read -write Boolean property, indicating whether a signature is required for acknowledging the alarms. The default value of AckSignature.MinPriority is True.
Syntax
To Set: <EAC instance name>.<Property Name> = <boolean value>;
Example
AlarmClient1.AckSignature.Required = true;
Syntax
To Get: boolean <variable name> = <EAC instance name>.<Property Name>;
Example
dim bIsACKSigned as boolean; bIsACKSigned = AlarmClient1.AckSignature.Required;

76

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Remarks
For more information, see Configuring the Alarm Control to Require a SHELVE Signature on page 52.
AlarmColor.Ack.BackGround Property
The AlarmColor.Ack.BackGround property is an array of read-writ e integer properties that get or set the background colors of all acknowledged alarm records.

Index Purpose

0

Sets the background color of all acknowledged alarm rec ords in all priority ranges.

1

Gets or sets the background color of acknowledged alarm records in the priority

range 1 to AlarmColor. Range[1].

2

Gets or sets the background color of acknowledged alarm records in the priority

range AlarmColor.Range[1] to AlarmColor.Range[2].

3

Gets or sets the background color of acknowledged alarm records in the priority

range AlarmColor.Range[2] to AlarmColor.Range[3].

4

Gets or sets the background color of acknowledged alarm records in the priority

range AlarmColor.Range[3] to 999.

Syntax
Color = AlarmClient.AlarmColor.Ack.BackGround[n]; AlarmClient.AlarmColor.Ack.BackGround[n] = Color;
Parameters
n Index from 0 to 4.
Color Color of background.
Examples
AlarmClient1.AlarmColor.Ack.BackGround[0] = Color.Red; AlarmClient1.AlarmColor.Ack.BackGround[1] = Color.FromARGB(0,128,0); AlarmClient1.AlarmColor.Ack.BackGround[2] = Color.Grey; AlarmClient1.AlarmColor.Ack.BackGround[3] = Color.Yellow; AlarmClient1.AlarmColor.Ack.BackGround[4] = Color.Black;
Remarks
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.

AlarmColor.Ack.ForeGround Property
The AlarmColor.Ack.ForeGround property is an array of read-write integer properties that get or set the text colors of all acknowledged alarm records.

77

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Index Purpose

0

Sets the text color of all acknowledged alarm records in all priority ranges.

1

Gets or sets the text color of acknowledged alarm rec ords in the priority

range 1 to AlarmColor. Range[1].

2

Gets or sets the text color of acknowledged alarm rec ords in the priority

range AlarmColor.Range[1] to AlarmColor.Range[2].

3

Gets or sets the text color of acknowledged alarm rec ords in the priority

range AlarmColor.Range[2] to AlarmColor.Range[3].

4

Gets or sets the text color of acknowledged alarm rec ords in the priority

range AlarmColor.Range[3] to 999.

Syntax
Color = AlarmClient.AlarmColor.Ack.ForeGround[n]; AlarmClient.AlarmColor.Ack.ForeGround[n] = Color;
Parameters

n Index from 0 to 4.

Color Color of text.
Examples
AlarmClient1.AlarmColor.Ack.ForeGround[0] = Color.Black; AlarmClient1.AlarmColor.Ack.ForeGround[1] = Color.Blue; AlarmClient1.AlarmColor.Ack.ForeGround[2] = Color.Green; AlarmClient1.AlarmColor.Ack.ForeGround[3] = Color.Yellow; AlarmClient1.AlarmColor.Ack.ForeGround[4] = Color.FromARGB(0,128,0);

Remarks

Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().

For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.

For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.

AlarmColor.Ack.RTN.BackGround Property
The AlarmColor.Ack.RTN.BackGround property is a read-write color property that gets or sets the background color of acknowledged alarm records that "return to normal" (ACK _RTN).
Syntax
Color = AlarmClient.AlarmColor.Ack.RTN.BackGround; AlarmClient.AlarmColor.Ack.RTN.BackGround = Color;
Parameters
Color Color of background.
Return Value
Returns the background color of acknowledged alarms that "return to normal".

78

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Example
AlarmClient1.AlarmColor.Ack.RTN.BackGround = Color.Blue;
Remarks
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.

AlarmColor.Ack.RTN.ForeGround Property
The AlarmColor.Ack.RTN.ForeGround property is a read-write color property that gets or sets the text color of acknowledged alarm records that "return to normal" (ACK_RTN).
Syntax
Color = AlarmClient.AlarmColor.Ack.RTN.ForeGround; AlarmClient.AlarmColor.Ack.RTN.ForeGround = Color;
Parameters
Color Color of text.
Example
AlarmClient1.AlarmColor.Ack.RTN.ForeGround = Color.Black;
Remarks
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.

AlarmColor.Range Property

The AlarmColor.Range property is an array of read-writ e integer properties that get or set the boundaries of the priority ranges.
You can use priority ranges to classify, group, and emphasize alarms and events belonging to a certain priority range.

The boundaries must fulfill the following condition:

1 < Range[1] < Range[2] < Range[3] < 999 By default, the boundaries are set as follows:

 AlarmColor.Range[1]

250

 AlarmColor.Range[2]

500

 AlarmColor.Range[3]

750

Syntax
RangeN = AlarmClient.AlarmColor.Range[N]; AlarmClient.AlarmColor.Range[1] = RangeN;

79

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Parameters
N Range index 1, 2, or 3.
Example
The following example defines four priority ranges (1 to 50, 51 to 600, 601 to 800, and 801 to 999): AlarmClient1.AlarmColor.Range[1] = 50; AlarmClient1.AlarmColor.Range[2] = 600; AlarmClient1.AlarmColor.Range[3] = 800;
Remarks
For more information, see Setting Priority Ranges for Alarm Rec ords on page 29.
AlarmColor.RTN.BackGround Property
The AlarmColor. RTN.BackGround property is a read-writ e color property that gets or sets the background color of alarm records that "return to normal" (ACK _RTN and UNA CK_RTN).
Syntax
Color = AlarmClient.AlarmColor.RTN.BackGround; AlarmClient.AlarmColor.RTN.BackGround = Color;
Parameters
Color Color of background.
Example
AlarmClient1.AlarmColor.RTN.BackGround = Color.Blue;
Remarks
For more information, see Setting Return To Normal Rec ord Colors on page 27.
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName(). For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
AlarmColor.RTN.ForeGround Property
The AlarmColor.RTN.ForeGround property is a read -write color property that gets or sets the text color of alarm records that "return to normal" (A CK_RTN and UNA CK_RTN).
Syntax
Color = AlarmClient.AlarmColor.RTN.ForeGround; AlarmClient.AlarmColor.RTN.ForeGround = Color;
Parameters
Color Color of text.
Example
AlarmClient1.AlarmColor.RTN.ForeGround = Color.Yellow;
Remarks
For more information, see Setting Return To Normal Rec ord Colors on page 27.
80

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName(). For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
AlarmColor.UnAck.BackGround Property
The AlarmColor. UnAck.BackGround property is an array of read -write integer properties that get or set the background colors of all unacknowledged alarm records.
Index Purpose

0

Sets the background color of all unacknowledged alarm records in all priority

ranges.

1

Gets or sets the background color of unacknowledged alarm records in the priority

range 1 to AlarmColor. Range[1].

2

Gets or sets the background color of unacknowledged alarm records in the priority

range AlarmColor.Range[1] to AlarmColor.Range[2].

3

Gets or sets the background color of unacknowledged alarm records in the priority

range AlarmColor.Range[2] to AlarmColor.Range[3].

4

Gets or sets the background color of unacknowledged alarm records in the priority

range AlarmColor.Range[3] to 999.

Syntax
Color = AlarmClient.AlarmColor.UnAck.BackGround[n]; AlarmClient.AlarmColor.UnAck.BackGround[n] = Color;
Parameters

n Index from 0 to 4.

Color Color of background.
Example
AlarmClient1.AlarmColor.UnAck.BackGround[0] = Color.Blue; AlarmClient1.AlarmColor.UnAck.BackGround[1] = Color.ARGB(223,113,76); AlarmClient1.AlarmColor.UnAck.BackGround[2] = Color.Yellow; AlarmClient1.AlarmColor.UnAck.BackGround[3] = Color.Green; AlarmClient1.AlarmColor.UnAck.BackGround[4] = Color.White;
Remarks

Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK no wnColor(), and FromName().

For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.

For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.

AlarmColor.UnAck.Flash.BackGround Property
The AlarmColor. UnAck.Flash.BackGround property is an array of read -write color properties that get or set the background colors of all flas hing unacknowledged alarm records.

81

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Index Purpose

0

Sets the background color of all flashing unacknowledged alarm records in all

priority ranges.

1

Gets or sets the background color of flashing unacknowledged alarm records in

the priority range 1 to AlarmColor. Range[ 1].

2

Gets or sets the background color of flashing unacknowledged alarm records in

the priority range AlarmColor.Range[1] to AlarmColor.Range[2].

3

Gets or sets the background color of flashing unacknowledged alarm records in

the priority range AlarmColor.Range[2] to AlarmColor.Range[3].

4

Gets or sets the background color of flashing unacknowledged alarm records in

the priority range AlarmColor.Range[3] to 999.

Syntax
Color = AlarmClient.AlarmColor.UnAck.Flash.BackGround[n]; AlarmClient.AlarmColor.UnAck.Flash.BackGround[n] = Color;
Parameters

n Index from 1 to 4.

Color Color of background.

Example
AlarmClient1.AlarmColor.UnAck.Flash.BackGround[1] = Color.ARGB(223,113,76); AlarmClient1.AlarmColor.UnAck.Flash.BackGround[2] = Color.Yellow; AlarmClient1.AlarmColor.UnAck.Flash.BackGround[3] = Color.Green; AlarmClient1.AlarmColor.UnAck.Flash.BackGround[4] = Color.White;
Remarks

Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().

For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.

For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.

AlarmColor.UnAck.Flash.ForeGround Property

The AlarmColor. UnAck.Flash.ForeGround property is an array of read -write color properties that get or set the text colors of all flashing unacknowledged alarm records.
Index Purpose

0

Sets the text color of all flas hing unacknowledged alarm records in all priority

ranges.

1

Gets or sets the text color of flashing unacknowledged alarm records in the

priority range 1 to AlarmColor. Range[1].

2

Gets or sets the text color of flashing unacknowledged alarm records in the

priority range AlarmColor. Range[1] to AlarmColor. Range[ 2].

82

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Index Purpose

3

Gets or sets the text color of flashing unacknowledged alarm records in the

priority range AlarmColor. Range[2] to AlarmColor. Range[ 3].

4

Gets or sets the text color of flashing unacknowledged alarm records in the

priority range AlarmColor. Range[3] to 999.

Syntax
Color = AlarmClient.AlarmColor.UnAck.Flash.ForeGround[n]; AlarmClient.AlarmColor.UnAck.Flash.ForeGround[n] = Color;
Parameters

n Index from 1 to 4.

Color Color of text.
Examples
AlarmClient1.AlarmColor.UnAck.Flash.ForeGround[1] = Color.ARGB(223,113,76); AlarmClient1.AlarmColor.UnAck.Flash.ForeGround[2] = Color.Yellow; AlarmClient1.AlarmColor.UnAck.Flash.ForeGround[3] = Color.Green; AlarmClient1.AlarmColor.UnAck.Flash.ForeGround[4] = Color.White;

Remarks

Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().

For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.

For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.

AlarmColor.UnAck.ForeGround Property

The AlarmColor. UnAck.ForeGround property is an array of read-writ e integer properties that get or set the text colors of all unacknowledged alarm records.
Index Purpose

0

Sets the text color of all unacknowledged alarm records in all priority ranges.

1

Gets or sets the text color of unacknowledged alarm records in the priority range 1

to AlarmColor.Range[1].

2

Gets or sets the text color of unacknowledged alarm records in the priority range

AlarmColor.Range[1] to AlarmColor.Range[2].

3

Gets or sets the text color of unacknowledged alarm records in the priority range

AlarmColor.Range[2] to AlarmColor.Range[3].

4

Gets or sets the text color of unacknowledged alarm records in the priority range

AlarmColor.Range[3] to 999.

Syntax
Color = AlarmClient.AlarmColor.UnAck.ForeGround[n]; AlarmClient.AlarmColor.UnAck.ForeGround[n] = Color;

83

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Parameters
n Index from 0 to 4.
Color Color of text.
Example
AlarmClient1.AlarmColor.UnAck.ForeGround[0] = Color.Blue; AlarmClient1.AlarmColor.UnAck.ForeGround[1] = Color.ARGB(223,113,76); AlarmClient1.AlarmColor.UnAck.ForeGround[2] = Color.Yellow; AlarmClient1.AlarmColor.UnAck.ForeGround[3] = Color.Green; AlarmClient1.AlarmColor.UnAck.ForeGround[4] = Color.White;
Remarks
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
AlarmColor.UnAck.RTN.BackGround Property
The AlarmColor. UnAck.RTN.BackGround property is a read-writ e color property that gets or sets the background color of unacknowledged alarm records that "return to normal" (UNACK _RTN).
Syntax
Color = AlarmClient.AlarmColor.UnAck.RTN.BackGround; AlarmClient.AlarmColor.UnAck.RTN.BackGround = Color;
Parameters
Color Color of background.
Example
AlarmClient1.AlarmColor.UnAck.RTN.BackGround = Color.Blue;
Remarks
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
AlarmColor.UnAck.RTN.ForeGround Property
The AlarmColor.UnAck.RTN.ForeGround property is a read-write color property that gets or sets the text color of unacknowledged alarm records that "return to normal" (UNACK_RTN).
Syntax
Color = AlarmClient.AlarmColor.UnAck.RTN.ForeGround; AlarmClient.AlarmColor.UnAck.RTN.ForeGround = Color;
Parameters
Color Color of text.
84

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Example
AlarmClient1.AlarmColor.UnAck.RTN.ForeGround = Color.FromARGB(0,0,0);
Remarks
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), an d FromName(). For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
AlarmQuery Property
The AlarmQuery property is a read-write string property that gets or sets the alarm query.
Syntax
result = AlarmClient.AlarmQuery; AlarmClient.AlarmQuery = AlmQry;
Parameters
AlmQry Alarm query string in format \\node\provider!group where node is optional.
Example
AlarmClient.AlarmQuery = "\intouch!GroupA";
Remarks
After you write a new value to the AlarmQuery property, the Alarm Control is updated. If you are using the default query, the query is updated with the new node, provider, and group name.
AllowColumnResize Property
The AllowColumnResize property is a read-write Boolean property that gets or sets the ability to resize the columns at run time.
Syntax
result = AlarmClient.AllowColumnResize; AlarmClient.AllowColumnResize = allowColResizing;
AutoResumeDuration Property
The AutoResumeDuration property is a read-write integer property that gets or sets the time in seconds after whic h the grid becomes unfrozen and resumes showing alarms.
Set this value to 0 to disable aut o resume.
Syntax
result = AlarmClient.AutoResumeDuration; AlarmClient.AllowColumnResize = timeout;
AutoScroll Property
The AutoScroll property is a read-write Boolean property that gets or sets automatic scrolling to new alarms.
Syntax
result = AlarmClient.AutoScroll; AlarmClient.AutoScroll = allowAutoscroll;

85

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

ClientMode Property
The ClientMode property is a read-write int eger property that gets or sets the client mode for the Alarm Cont rol. Use one of the following values:

Value

Client Mode

1

Current Alarms

2

Recent Alarms and E vents

3

Historical Alarms

4

Historical E vents

5

Historical Alarms and E vents

Syntax
result = AlarmClient.ClientMode; AlarmClient.ClientMode = clientMode;
Example
AlarmClient1.ClientMode = 2; LogMessage("Alarm client set to Recent Alarms and Events");
Remarks
For more information, see Showing Current Alarms or Recent Alarms and Events on page 21.

ConnectStatus Property
The ConnectStatus property is a read-only string property that gets the status of the connection to the Alarm Database.
Syntax
result = AlarmClient.ConnectStatus;
Return Value
Returns the status of the connection to the alarm database. Can be "Connected," "Not connected," or "In progress."
Example
alive = AlarmClient1.ConnectStatus; if alive == "Connected" then
LogMessage("The Alarm Control is currently connected to the Alarm Database"); else
LogMessage("The Alarm Control is either currently connecting to the Alarm Database or not connected."); endif;

ContextMenu.AckAll Property
The ContextMenu.AckAll property is a read -write Boolean property that gets or sets the appear ance of the Ack All option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.AckAll; AlarmClient.ContextMenu.AckAll = AckAllVis;

86

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.AckOthers Property
The ContextMenu.AckOthers property is a read-writ e Boolean property that gets or sets the appearance of the Ack Others option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.AckOthers; AlarmClient.ContextMenu.AckOthers = AckOthersVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.AckSelected Property
The ContextMenu.AckSelected property is a read-write Boolean property that gets or sets the appearance of the Ack Selected option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.AckSelected; AlarmClient.ContextMenu.AckSelected = AckSelectedVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.AckSelectedGroups Property
The ContextMenu.AckSelectedGroups property is a read -write Boolean property that gets or sets the appearance of the Ack Selected Groups option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.AckSelectedGroups; AlarmClient.ContextMenu.AckSelectedGroups = AckSelGrpsVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.AckSelectedPriorities Property
The ContextMenu.AckSelectedPriorities property is a read -write Boolean property that gets or sets the appearance of the Ack Selected Priorities option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.AckSelectedPriorities; AlarmClient.ContextMenu.AckSelectedPriorities = AckSelPriVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.AckSelectedTags Property
The ContextMenu.AckSelectedTags property is a read -write Boolean property that gets or sets the appearance of the Ack Selected Tags option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.AckSelectedTags;
87

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

AlarmClient.ContextMenu.AckSelectedTags = AckSelTagsVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.AckVisible Property
The ContextMenu.AckVisible property is a read-write Boolean property that gets or sets the appearance of the Ack Visible option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.AckVisible; AlarmClient.ContextMenu.AckVisible = AckVisVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.Favorites Property
The ContextMenu.Favorites property is a read -write Boolean property that gets or sets the appearance of the Query and Filter Favorites option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.Favorites; AlarmClient.ContextMenu.Favorites = FavsVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.Freeze Property
The ContextMenu.Freeze property is a read-write Boolean property that gets or sets the appearance of the Freeze option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.Freeze; AlarmClient.ContextMenu.Freeze = FreezeVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.Hidden Property
The ContextMenu.Hidden property is a read-write Boolean property that gets or sets the appearance of the Hidden option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.Hidden; AlarmClient.ContextMenu.Hidden = HiddenVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.HideAll Property
The ContextMenu.HideAll property is a read-write Boolean property that gets or sets the appearance of the Hide All option on the shortcut menu.

88

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Syntax
result = AlarmClient.ContextMenu.HideAll; AlarmClient.ContextMenu.HideAll = HideAllVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.HideOthers Property
The Cont extMenu. HideOthers property is a read -write Boolean property that gets or sets the appearance of the Hide Others option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.HideOthers; AlarmClient.ContextMenu.HideOthers = HideOthersVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.HideSelected Property
The ContextMenu.HideSelected property is a read-write Boolean property that gets or sets the appearance of the Hide Selected option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.HideSelected; AlarmClient.ContextMenu.HideSelected = HideSelVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.HideSelectedGroups Property
The ContextMenu.HideSelectedGroups property is a read -write Boolean property that gets or sets the appearance of the Hide Selected Groups option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.HideSelectedGroups; AlarmClient.ContextMenu.HideSelectedGroups = HideSelGrpsVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.HideSelectedPriorities Property
The ContextMenu.HideSelectedPriorities property is a read -write Boolean property that gets or sets the appearance of the Hide Selected Priorities option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.HideSelectedPriorities; AlarmClient.ContextMenu.HideSelectedPriorities = HideSelPrisVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.

89

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

ContextMenu.HideSelectedTags Property
The ContextMenu.HideSelectedTags property is a read -write Boolean property that gets or sets the appearance of the Hide Selected Tags option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.HideSelectedTags; AlarmClient.ContextMenu.HideSelectedTags = HideSelTagsVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.HideVisible Property
The ContextMenu. HideVisible property is a read-write B oolean property that gets or sets the appearance of the Hide Visible option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.HideVisible; AlarmClient.ContextMenu.HideVisible = HideVisVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.Requery Property
The ContextMenu.Requery property is a read -write Boolean property that gets or sets the appearance of the Requery option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.Requery; AlarmClient.ContextMenu.Requery = RequeryVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.Reset Property
The ContextMenu.Reset property is a read -write Boolean property that gets or sets the appearance of the Re set option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.Reset; AlarmClient.ContextMenu.Reset = ResetVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.ShelveAll Property
CntextMenu.ShelveAll is a read-write Boolean property that gets or sets the appearance of the Shelve All option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.ShelveAll = boolean_value;
Example
AlarmClient1.ContextMenu.ShelveAll = true;
90

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Syntax
To Get: boolean_name = AlarmClient.ContextMenu.ShelveAll;
Example
dim ShlvAll as boolean; ShlvAll = AlarmClient1.ContextMenu.ShelveAll;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.ShelveOthers Property
Cont extMenu.ShelveOthers is a read-write Boolean property that gets or sets the appearance of the Shelve Others option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.ShelveOthers = boolean_value;
Example
AlarmClient1.ContextMenu.ShelveOthers = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.ShelveOthers;
Example
dim ShlvOthrs as boolean; ShlvOthrs = AlarmClient1.ContextMenu.ShelveOthers;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.ShelveSelected Property
Cont extMenu.ShelveSelected is a read-write Boolean property that gets or sets the appearanc e of the Shelve Selected option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.ShelveSelected = boolean_value;
Example
AlarmClient1.ContextMenu.ShelveSelected = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.ShelveSelected;
Example
dim ShlvSlctd as boolean; ShlvSlctd = AlarmClient1.ContextMenu.ShelveSelected;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.

91

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

ContextMenu.ShelveSelectedGroups Property
Cont extMenu.ShelveSelectedGroups is a read -write Boolean property that gets or sets the appearance of the Shelve Selected Groups option on the Alarm Cont rol's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.ShelveSelectedGroups = boolean_value;
Example
AlarmClient1.ContextMenu.ShelveSelectedGroups = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.ShelveSelectedGroups;
Example
dim ShlvSlctdGrp as boolean; ShlvSlctdGrp = AlarmClient1.ContextMenu.ShelveSelectedGroups;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.ShelveSelectedPriorities Property
Cont extMenu.ShelveSelectedPriorities is a read-write B oolean property that gets or sets the appearance of the Shelve Selected Priorities option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.ShelveSelectedPriorities = boolean_value;
Example
AlarmClient1.ContextMenu.ShelveSelectedPriorities = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.ShelveSelectedPriorities;
Example
dim ShlvSlctdPri as boolean; ShlvSlctdPri = AlarmClient1.ContextMenu.ShelveSelectedPriorities;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.ShelveSelectedSeverities Property
Cont extMenu.ShelveSelectedSeverities is a read -write Boolean property that gets or sets the appearance of the Shelve Selected Severities option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.ShelveSelectedSeverities = boolean_value;
Example
AlarmClient1.ContextMenu.ShelveSelectedSeverities = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.ShelveSelectedSeverities;
92

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Example
dim ShlvSlctdSev as boolean; ShlvSlctdSev = AlarmClient1.ContextMenu.ShelveSelectedSeverities;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.ShelveSelectedTags Property
Cont extMenu.ShelveSelectedTags is a read -write Boolean property that gets or sets the appearance of the Shelve Selected Tags option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.ShelveSelectedTags = boolean_value;
Example
AlarmClient1.ContextMenu.ShelveSelectedTags = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.ShelveSelectedTags;
Example
dim ShlvSlctdTag as boolean; ShlvSlctdTag = AlarmClient1.ContextMenu.ShelveSelectedTags;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.ShelveVisible Property
Cont extMenu.ShelveVisible is a read-write Boolean property that gets or sets the appearance of the Shelve Visible option appears in the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.ShelveSelectedVisible = boolean_value;
Example
AlarmClient1.ContextMenu.ShelveSelectedVisible = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.ShelveSelectedVisible;
Example
dim ShlvSlctdVis as boolean; ShlvSlctdVis = AlarmClient1.ContextMenu.ShelveSelectedVisible;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.Sort Property
The ContextMenu.Sort property is a read-write Boolean property that gets or sets the appearance of the Sort option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.Sort;

93

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

AlarmClient.ContextMenu.Sort = SortVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.Statistics Property
The Cont extMenu.Statistics property is a read -write Boolean property that gets or sets the appearance of the Stati stics option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.Statistics; AlarmClient.ContextMenu.Statistics = StatsVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.UnhideAll Property
The ContextMenu.UnhideAll property is a read -write Boolean property that gets or sets the appearance of the Unhide All option on the shortcut menu.
Syntax
result = AlarmClient.ContextMenu.UnhideAll; AlarmClient.ContextMenu.UnhideAll = UnhideAllVis;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.UnshelveAll Property
Cont extMenu. UnshelveAll is read-write Boolean property that gets or sets the appearance of the Unshelve All option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.UnshelveAll = boolean_value;
Example
AlarmClient1.ContextMenu.UnshelveAll = true;
Syntax
To Get: boolean_variable_name = AlarmClient.ContextMenu.UnshelveAll;
Example
dim ShlvAll as boolean; ShlvAll = AlarmClient1.ContextMenu.UnshelveAll;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.UnshelveOthers Property
Cont extMenu. UnshelveOthers is read -write Boolean property that gets or sets the appearance of the Unshelve Others option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.UnshelveOthers = boolean_value;

94

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Example
AlarmClient1.ContextMenu.UnshelveOthers = true;
Syntax
To Get: boolean_variable_name = AlarmClient.ContextMenu.UnshelveOthers;
Example
dim ShlvOthrs as boolean; ShlvOthrs = AlarmClient1.ContextMenu.UnshelveOthers;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.UnshelveSelected Property
Cont extMenu. UnshelveSelected is read -write Boolean property that gets or sets the appearance of the Unshelve Selected option on the Alarm Cont rol's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.UnshelveSelected = boolean_value;
Example
AlarmClient1.ContextMenu.UnshelveSelected = true;
Syntax
To Get: boolean_variable_name = AlarmClient.ContextMenu.UnshelveSelected;
Example
dim ShlvSlctd as boolean; ShlvSlctd = AlarmClient1.ContextMenu.UnshelveSelected;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.UnshelveSelectedGroups Property
Cont extMenu. UnshelveSelectedGroups is read-write Boolean property that gets or sets the appearance of the Unshelve Selected Groups option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.UnshelveSelectedGroups = boolean_value;
Example
AlarmClient1.ContextMenu.UnshelveSelectedGroups = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.UnshelveSelectedGroups;
Example
dim UnshlvSlctdGrp as boolean; UnshlvSlctdGrp = AlarmClient1.ContextMenu.UnshelveSelectedGroups;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.

95

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

ContextMenu.UnshelveSelectedPriorities Property
Cont extMenu. UnshelveSelectedPriorities is read -write Boolean property that gets or sets the appearance of the Unshelve Selected Priorities option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.UnshelveSelectedPriorities = boolean_value;
Example
AlarmClient1.ContextMenu.UnshelveSelectedPriorities = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.UnshelveSelectedPriorities;
Example
dim UnshlvSlctdPri as boolean; UnshlvSlctdPri = AlarmClient1.ContextMenu.UnshelveSelectedPriorities;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.UnshelveSelectedSeverities Property
Cont extMenu. UnshelveSelectedSeverities is read-write B oolean property that gets or sets the appearance of the Unshelve Selected Severities option on the Alarm Cont rol's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.UnshelveSelectedSeverities = boolean_value;
Example
AlarmClient1.ContextMenu.UnshelveSelectedSeverities = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.UnshelveSelectedSeverities;
Example
dim UnshlvSlctdSev as boolean; UnshlvSlctdSev = AlarmClient1.ContextMenu.UnshelveSelectedSeverities;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.UnshelveSelectedTags Property
Cont extMenu. UnshelveSelectedTags is read-write Boolean property that gets or sets the appearance of the Unshelve Selected Tags option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.UnshelveSelectedTags = boolean_value;
Example
AlarmClient1.ContextMenu.UnshelveSelectedTags = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.UnshelveSelectedTags;
96

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Example
dim UnshlvSlctdTag as boolean; UnshlvSlctdTag = AlarmClient1.ContextMenu.UnshelveSelectedTags;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
ContextMenu.UnshelveVisible Property
Cont extMenu. UnshelveVisible is read-write Boolean property that gets or sets the appearance of the Unshelve Visible option on the Alarm Control's shortcut menu.
Syntax
To Set: AlarmClient.ContextMenu.UnshelveSelectedVisible = boolean_value;
Example
AlarmClient1.ContextMenu.UnshelveSelectedVisible = true;
Syntax
To Get: boolean_name = AlarmClient.ContextMenu.UnshelveSelectedVisible;
Example
dim UnshlvSlctdVis as boolean; UnshlvSlctdVis = AlarmClient1.ContextMenu.UnshelveSelectedVisible;
Remarks
For more information, see Configuring the Run-Time Shortcut Menu on page 53.
Database.Authentication Property
The Database.Authentication property is a read -write string property that gets or sets the authentication mode to connect to the Alarm Database. Possible values are:
 Windows Integrated
 Windows Account
 SQL Server The default value is "Windows Integrat ed".
Syntax
result = AlarmClient.Database.Authentication; AlarmClient.Database.Authentication = AuthMode;
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
Database.Name Property
The Database.Name property is a read-write string property that gets or sets the name of the Alarm Database. The default value is "WWALMDB". WWALMDB is the name of the InTouch Dat abas e and A2ALMDB is the name of the ArchestrA Database.
If you change the Database. Name property at run time, you need to call the Connect method to connect to the new alarm database.
Syntax
result = AlarmClient.Database.Name;

97

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

AlarmClient.Database.Name = AlmDBName;
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
Database.Password Property
The Database.Password property is a read-write string property that gets or sets the password associated with the user name to connect to the Alarm Database.
Syntax
result = AlarmClient.Database.Password; AlarmClient.Database.Password = Psswrd;
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
Database.ServerName Property
The Database.ServerName property is a read-write string property that gets or sets the name of the server that hosts the Alarm Database.
Syntax
result = AlarmClient.Database.ServerName; AlarmClient.Database.ServerName = SrvName;
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
Database.UserID Property
The Database.UserID property is a read-write string property that gets or sets the name of user authorized to access the Alarm Database.
Syntax
result = AlarmClient.Database.UserID; AlarmClient.Database.UserID = UserName;
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
DisableFileBrowsing Property
Specify True to get/set the option to access the file browser when importing or exporting files.
Syntax
result = AlarmClient.DisableFileBrowsing; AlarmClient.DisableFileBrowsing = boolean_value;
Example
AlarmClient.DisableFileBrowsing = true;
Remarks Default is True.
Domain Property
The Domain property is a read-write string property that gets or sets the domain name of the user to connect to the Alarm Database.

98

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Syntax
result = AlarmClient.Domain; AlarmClient.Domain = DomName;
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
Enabled Property
The Enabled property is a read-write B oolean property that gets or sets the enablement of Alarm Control. When the Alarm Cont rol is disabled, alarm records are still updated, but the operator cannot interact with the control.
The operator can still use scripting to interact with the control.
Syntax
result = AlarmClient.Enabled; AlarmClient.Enabled = EnableFlag;
EventColor.BackGround Property
The E ventColor.BackGround property is a read-write color property that gets or sets the background color of event records.
Syntax
Color = AlarmClient.EventColor.BackGround; AlarmClient.EventColor.BackGround = Color;
Parameters
Color Color of background.
Example
AlarmClient1.EventColor.BackGround = Color.Blue;
Remarks
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
EventColor.ForeGround Property
The E ventColor.ForeGround property is a read-write color property that gets or sets the text color of event records.
Syntax
Color = AlarmClient.EventColor.ForeGround; AlarmClient.EventColor.ForeGround = Color;
Parameters
Color Color of text.
Example
AlarmClient1.EventColor.ForeGround = Color.Blue;

99

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Remarks
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
Favorite Property
The Favorite property is a read-writ e string property that gets or sets the name of the current query filter favorite.
Syntax
QueryFilterName = AlarmClient.Favorite; AlarmClient.Favorite = QueryFilterName;
Parameters
QueryFilt erName The name of a query filter favorite.
Example
The following example sets the current Alarm Control grid to the Query Filter Favorite with the name "All Hi Priority Alarms". AlarmClient1.Favorite = "All Hi Priority Alarms";
Remarks
You can also use this property to reset the currently used query filter to its default with the following script: AlarmClient.Favorite = "Default";
The Favorite property executes as a query to retain previous release default behavior. If you want to execute the query/filt er as a filter only, then us e the RunQuery() met hod.
FlashUnAckAlarms Property
The FlashUnAckAlarms property is a read-write Boolean property that gets or sets the flashing of unacknowledged alarm records.
Syntax
result = AlarmClient.FlashUnAckAlarms; AlarmClient.FlashUnAckAlarms = FlashUnAckRecs;
Remarks
For more information, see Setting Unack nowledged Alarms to Flash on page 31.
GridColor Property
The GridColor property is a read-write color property that gets or sets the color of the grid lines.
Syntax
Color = AlarmClient.GridColor; AlarmClient.GridColor = Color;
Parameters
Color Color of the grid lines.

100

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Example
AlarmClient1.GridColor = Color.Black;
Remarks
For more information, see Setting Heading, Grid, and Window Color on page 28.
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
HeadingColor.BackGround Property
The HeadingColor.BackGround property is a read-write color property that gets or sets the background color of the heading.
Syntax
Color = AlarmClient.HeadingColor.BackGround; AlarmClient.HeadingColor.BackGround = Color;
Parameters
Color Color of background.
Example
AlarmClient1.HeadingColor.BackGround = Color.Blue;
Remarks
For more information, see Setting Heading, Grid, and Window Color on page 28.
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
HeadingColor.ForeGround Property
The HeadingColor.ForeGround property is a read -write color property that gets or sets the text color of the heading.
Syntax
Color = AlarmClient.HeadingColor.ForeGround; AlarmClient.HeadingColor.ForeGround = Color;
Parameters
Color Color of text.
Example
AlarmClient1.HeadingColor.ForeGround = Color.Blue;
Remarks
For more information, see Setting Heading, Grid, and Window Color on page 28.

101

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName(). For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
Height Property
The Height property is a read-write int eger property that gets or sets the height of the Alarm Control in pixels.
Syntax
result = AlarmClient.Height; AlarmClient.Height = Hght;
HiddenAlarms Property
The HiddenAlarms property is a read-only integer property that gets the number of hidden alarms.
Syntax
Result = AlarmClient.HiddenAlarms;
Example
LogMessage("There are " + Text(AlarmClient1.HiddenAlarms,"#")+" hidden alarms.");
HideErrors Property
The HideErrors property is a read-writ e Boolean property that gets or sets the Hide Errors option.
 TRUE - Run-time errors, warnings, and status messages are written to the ArchestrA Logger. No pop-ups appear
 FALSE - Run-time errors, warnings, and status messages pop-up and are also written to the ArchestrA Logger
Syntax
result = AlarmClient.HideErrors; AlarmClient.HideErrors = SilentMode;
Remarks
For more information, see Hiding Errors, Warnings, and Status Messages on page 48.
MaxDatabaseRecords Property
The Max DatabaseRecords property is a read -write integer property that gets or sets the maximum database rec ords to ret rieve. The valid range is 1 to 32766.
Syntax
result = AlarmClient.MaxDatabaseRecords; AlarmClient.MaxDatabaseRecords = MaxRecs;
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
NewAlarmEventMode Property
The NewAlarmE ventMode property is an read -write int eger property that gets or sets the t rigger behavior of the New Alarm event.
102

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Syntax
EMode = AlarmClient.NewAlarmEventMode; AlarmClient.NewAlarmEventMode = EMode;
Parameters
EMode E vent mode with following possible values:
Value Description

0

The NewAlarm event cannot be triggered. (default ).

1

The NewAlarm event is triggered only one time the first time a new alarm occurs.

2

The NewAlarm event is triggered every time a new alarm occurs.

NoRecordsMessage.Enabled Property
The NoRecordsMessage.Enabled property is a read-write B oolean property that gets or sets the visibility of a custom message when no alarm records are available.
Syntax
result = AlarmClient.NoRecordsMessage.Enabled; AlarmClient.NoRecordsMessage.Enabled = showMessage;
Example
AlarmClient1.NoRecordsMessage.Enabled = 1; AlarmClient1.NoRecordsMessage.Message = "There are no alarm records available";
Remarks
Use this property in combination with the NoRecordsMes sage.Message property.
NoRecordsMessage.Message Property
The NoRecordsMessage.Message property is a read-writ e string property that gets or sets the custom message text when no alarm records are available and the NoRecordsMe ssage.Enabled property value is TRUE.
Syntax
result = AlarmClient.NoRecordsMessage.Message; AlarmClient.NoRecordsMessage.Message = myCustomMessage;
Example
AlarmClient1.NoRecordsMessage.Enabled = 1; AlarmClient1.NoRecordsMessage.Message = "There are no alarm records available";
Remarks
Use this property in combination with the NoRecordsMessage.Enabled property.
SaveUserQueryFilter Property
Gets/Sets the option to save runtime user queries and filters. If false, then user modified queries or filters will not be saved to file. If true, user modification will be saved to file.
103

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Syntax
result = AlarmClient.SaveUserQueryFilter; AlarmClient.SaveUserQueryFilter = boolean_true;
Example
AlarmClient.SaveUserQueryFilter = true;
Remarks
Default is True.
QueryStartup Property
The QueryStart up property is a read-write Boolean property that gets or sets or sets the automatic update of the Alarm Control on startup.
Syntax
result = AlarmClient.QueryStartup; AlarmClient.QueryStartup = AutoQry;
Remarks
For more information, see Automatically Querying for Alarms on Start Up on page 48.
RequiresShelveSignature Property
The RequiresShelveSignature property is a read-write Boolean property to specify if a user signature is required to shelve an alarm.
Syntax
To Set: AlarmClient.RequiresShelveSignature = boolean_value;
Example
AlarmClient1.RequiresShelveSignature = true;
Syntax
To Get: boolean_variable_name> = AlarmClient.RequiresShelveSignature;
Example
dim bIsShlvSigned as boolean; bIsShlvSigned = AlarmClient1.RequiresShelveSignature;
Remarks
For more information, see Configuring the Alarm Control to Require a SHELVE Signature on page 52.
RetainHidden Property
The RetainHidden property is a read-write Boolean property that gets or sets the retention of hidden alarms or events when the alarm query or query filter to retrieve recor ds changes at run time.
Syntax
result = AlarmClient.RetainHidden; AlarmClient.RetainHidden = RetainHddn;
Remarks
For more information, see Ret ain Hiding when Changing Alarm Query Filter on page 49.

104

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

RowCount Property
The RowCount property is a read-only integer property that gets the number of records shown in the Alarm Control grid.
For current alarms (and recent alarms and events), the RowCount property value is always the same as the TotalRowCount property value.
For historical alarms, if the Alarm Control retrieves more alarm records than specified by the MaxDatabaseRecords property value, it splits these into multiple pages.
The RowCount property shows how many alarm records are currently shown on the current page. The RowCount property value is the same as the MaxDatabaseRecords property value, with exception of the last page.
Syntax
Result = AlarmClient.RowCount;
Example
NRows = AlarmClient1.RowCount; LogMessage("There are " + Text(NRows, "#") + " alarm records on the retrieved page.");

RowSelection Property
The RowS election property is a read-write string property that determines if row selection is allowed at run time. The following values are possible:

Value

Description

No

Operator cannot select rows.

Single Multiple

Operator can only select one row at a time. Operator can select one or more rows.

The default value is "Multiple".
Syntax
Result = AlarmClient.RowSelection; AlarmClient.RowSelection = RwSel;
Example
AlarmClient1.RowSelection = "Multiple";
Remarks
For more information, see Restricting User Access to Rows and Columns on page 49.
SelectedCount Property
The SelectedCount property is a read-only integer property that gets the total number of selected alarm records.
Syntax
Result = AlarmClient.SelectedCount;
Return Value
Returns the number of selected alarm records.

105

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Example
NSelRows = AlarmClient1.SelectedCount; If NSelRows > 5 Then
LogMessage("There are more than 5 rows selected."); Endif;
ShelveColor.BackGround Property
ShelveColor.BackGround is an integer property to set the background color of shelved alarm records in the Alarm Control.
Syntax
Color= AlarmClient.ShelveColor.Background; AlarmClient.ShelveColor.BackGround = Color
Parameters
Color Background color of a shelved alarm record.
Example
AlarmClient1.ShelveColor.BackGround = Color.FromARGB(255,0,128);
Remarks
For more information, see Setting Heading, Grid, and Window Color on page 28.
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
ShelveColor.ForeGround Property
ShelveColor.ForeGround is an integer property to set the foreground or text color of shelved alarm records in the Alarm Control.
Syntax
Color= AlarmClient.ShelveColor.Foreground; AlarmClient.ShelveColor.Foreground = Color
Parameters
Color Foreground color of a shelved alarm record.
Example
AlarmClient1.ShelveColor.Foreground = Color.FromARGB(255,255,255);
Remarks
For more information, see Setting Heading, Grid, and Window Color on page 28.
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, see .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.

106

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

ShowContextMenu Property
The ShowContextMenu property is a read -write Boolean property that gets or sets the ability to open the shortcut menu at run time.
Syntax
result = AlarmClient.ShowContextMenu; AlarmClient.ShowContextMenu = ContxtMnuAvail;
ShowGrid Property
The ShowGrid property is a read-write Boolean property that gets or sets the appearance of grid lines.
Syntax
result = AlarmClient.ShowGrid; AlarmClient.ShowGrid = showGrid;
ShowGroupByHeader Property
The ShowGroupByHeader property is a read-writ e Boolean property to show or hide the column grouping label at the top of the run-time Alarm Control in the historical mode. Set the ShowGroupBy Header property to true to show the label "Drag a column header here to group by that column".
Syntax
result = AlarmClient.ShowGroupByHeader; AlarmClient.ShowGroupByHeader = ShowGroupByHeader;
ShowHeading Property
The ShowHeading property is a read -write Boolean property that gets or sets the visibility of the grid heading at run time.
Syntax
result = AlarmClient.ShowHeading; AlarmClient.ShowHeading = showHeading;
ShowStatusBar Property
The ShowStatusBar property is a read-write Boolean property that gets or sets the visibility of the status bar at run time.
Syntax
result = AlarmClient.ShowStatusBar; AlarmClient.ShowStatusBar = showStatusBar;
SortColumn.First Property
The Sort Column.First property is a read -write string property that gets or sets the first sort column.
The default value is "Time (LCT)".
Syntax
result = AlarmClient.SortColumn.First; AlarmClient.SortColumn.First = sortByFirst;
Example
AlarmClient1.SortColumn.First = "Class";

107

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Remarks
Use this property in connection wit h the SortOrder.First to determine the sorting direction.

SortColumn.Second Property
The SortColumn.Sec ond property is a read-write string property that gets or s ets the second s ort column.
The default value is blank.
Syntax
result = AlarmClient.SortColumn.Second; AlarmClient.SortColumn.Second = sortBySecond;
Example
AlarmClient1.SortColumn.Second = "Type";
Remarks
Use this property in connection wit h the SortOrder.Second to det ermine the sorting direction.

SortColumn.Third Property
The Sort Column. Third property is a read-write string property that gets or sets the third sort column.
The default value is blank.
Syntax
result = AlarmClient.SortColumn.Third; AlarmClient.SortColumn.Third = sortByThird;
Example
AlarmClient1.SortColumn.Third = "State";
Remarks
Use this property in connection wit h the SortOrder. Third to determine the sorting direction.

SortColumn.Fourth Property
The Sort Column.Fourth property is a read-writ e string property that gets or sets the fourth sort column.
The default value is blank.
Syntax
result = AlarmClient.SortColumn.Fourth; AlarmClient.SortColumn.Fourth = sortByFourth;
Example
AlarmClient1.SortColumn.Fourth = "Priority";
Remarks
Use this property in connection wit h the SortOrder.Fourth to determine the sorting direction.

SortOrder.First Property

The SortOrder.First property is a read-write Boolean property that gets or sets the sorting direction of the first sort column. The following values are possible:

Value

Description

FALSE

Ascending sorting direction

108

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Value

Description

TRUE

Descending sorting direction

The default value is FALSE (Ascending).
Syntax
result = AlarmClient.SortOrder.First; AlarmClient.SortOrder.First = sortDirFirst;
Remarks
Use this property in connection wit h the Sort Column.First to determine which column is sorted.

SortOrder.Second Property
The SortOrder.Second property is a read -write Boolean property that gets or sets the sorting direction of the second sort column. The following values are possible:

Value

Description

FALSE

Ascending sorting direction

TRUE

Descending sorting direction

The default value is FALSE (Ascending).
Syntax
result = AlarmClient.SortOrder.Second; AlarmClient.SortOrder.Second = sortDirSecond;
Remarks
Use this property in connection wit h the Sort Column.Second to determine which column is sorted.

SortOrder.Third Property
The SortOrder. Third property is a read-write Boolean property that gets or sets the sorting direction of the third sort column. The following values are possible:

Value

Description

FALSE

Ascending sorting direction

TRUE

Descending sorting direction

The default value is FALSE (Ascending).
Syntax
result = AlarmClient.SortOrder.Third; AlarmClient.SortOrder.Third = sortDirThird;
Remarks
Use this property in connection wit h the Sort Column. Third to det ermine which column is sorted.

SortOrder.Fourth Property
The Sort Order.Fourt h property is a read-write Boolean property that gets or sets the sorting direction of the fourth sort column. The following values are possible:

109

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Value

Description

FALSE

Ascending sorting direction

TRUE

Descending sorting direction

The default value is FALSE (Ascending).
Syntax
result = AlarmClient.SortOrder.Fourth; AlarmClient.SortOrder.Fourth = sortDirFourth;
Remarks
Use this property in connection wit h the Sort Column. Fourth to determine which column is sorted.

Time.Format Property
The Time.Format property is a read-write string property that gets or sets the date and time formats of the alarm records in the Alarm Control.
You can either use the . NE T time fo rmat or the default format. Set the Time. Type property to determine which time format type to use.
Syntax
result = AlarmClient.Time.Format; AlarmClient.Time.Format = TmFormat;
Example
This example shows the time format in French format (day/month/year) us ing the .NE T datetime type. AlarmClient1.Time.Type = 1; AlarmClient1.Time.Format = "dd/MM/yyyy";
Remarks
For more information about the .NE T time format, see Setting the .NET Datetime Format on page 45.
For more information about the default time format, see Setting the Time Format on page 44.

Time.Type Property

The Time. Type property is a read-write Boolean property that gets or sets the time format type of the alarm records. The following values are possible:

Value

Description

FALSE

Default time format

TRUE

.NET time format (default)

Syntax
result = AlarmClient.Time.Type; AlarmClient.Time.Type = TmType;
Example
This example shows the time format in German format (day.month.year) using the default datetime type. AlarmClient1.Time.Type = 0; AlarmClient1.Time.Format = "%d.%m.%Y %H:%M:%S";

110

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Remarks
For more information about the .NE T time format, see Setting the .NET Datetime Format on page 45.
For more information about the default time format, see Setting the Time Format on page 44.
TimeSelector Property
The TimeSelector property gets the Time Range Picker object used in the Alarm Control. You can use it in scripting to shorten the code using its properties and methods.
For the individual properties and methods, see the following properties , or the methods starting at TimeSelector.GetStartAndEndTimes() Method on page 137.
Example 1
dim TRP as object; TRP = AlarmClient1.TimeSelector; Timeselect = TRP; StartDate = TRP.StartDate; EndDate = TRP.EndDate; duration = TRP.TimeDuration;
Example 2
dim TRP as object; TRP = AlarmClient1.TimeSelector; TRP.SetStartAndEndTimes(StartDate, EndDate, Duration);
TimeSelector.DurationMS Property
The TimeS elector. DurationMS property is a read-writ e integer property that gets the time duration measured in milliseconds.
The start time of the Alarm cont rol (TimeSelector.StartDate) is calculated as the end time (TimeSelector.EndDate) minus the new time duration (TimeS elector. DurationMS).
When you set the value of the TimeSelector.DurationMS property, the TimeSelector. TimeDuration property is set to 0.
The default value is 3600000.
Syntax
result = AlarmClient.TimeSelector.DurationMS; AlarmClient.TimeSelector.DurationMS = Value;
Example
AlarmClient1.TimeSelector.DurationMS = 1800000; // The Alarm Control now retrieves alarms from the last 30 minutes.
TimeSelector.EndDate Property
The TimeSelector.EndDate property is a read-only string property that gets the end date and time of the Alarm Control.
The default value is the time the Alarm Control is placed on the canvas. If the Update to Current Time option is enabled, the TimeSelector.EndDate property is updated with the current time.
Note: To set the end dat e and time of the Alarm Control, use the TimeS elector.GetStartAndE ndTimes() Method on page 137.
Syntax
result = AlarmClient.TimeSelector.EndDate;

111

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Example
LogMessage(AlarmClient1.TimeSelector.EndDate);

TimeSelector.StartDate Property
The TimeSelector.StartDate property is a read -only string property that gets the start date and time of the Alarm Control.
The default value is the time the Ala rm Control is placed on the canvas. If the Update to Current Time option is enabled, the TimeSelector.Start Date property is updated as current time minus duration.
Note: To set the start date and time of the Alarm Cont rol, use the TimeSelector.SetStartAndE ndTimes() Met hod on page 137.
Syntax
result = AlarmClient.TimeSelector.StartDate;
Example
LogMessage(AlarmClient1.TimeSelector.StartDate);

TimeSelector.TimeDuration Property
The TimeS elector. TimeDuration property is a read-write integer property that gets or sets the time duration. The start time of the Alarm control (TimeS elector.Start Date) is calculated as the end time (TimeSelector.EndDate) minus the new time duration.
The TimeS elector. TimeDuration can have one of the following values:

Value

Description

0

Custom

1

The last minute.

2

The last five minutes.

3

The last ten minutes.

4

The last 15 minutes.

5

The last 30 minutes.

6

The last hour.

7

The last two hours.

8

The last four hours.

9

The last eight hours.

10

The last 12 hours.

11

The last 24 hours.

12

The last two days.

13

The last week.

112

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Value

Description

14

The last two weeks.

15

The last month.

16

The last three months.

17

One minute.

18

Five minutes.

19

Ten minutes.

20

15 minut es.

21

30 minut es.

22

One hour.

23

Two hours.

24

Four hours.

25

Eight hours.

26

12 hours.

27

24 hours.

28

Two days.

29

One week.

30

Two weeks.

31

One month.

32

Three months.

33

Yesterday: 0:00: 00 of the previous day to 0:00:00 of

the current day.

34

Current day: 0:00:00 of the current day to the current

time.

35

Previous hour: The start of the previous hour to the

start of the current hour.

36

Current hour: The start of the current hour to the

current time.

The default value is 6 (Last Hour).
Syntax
result = AlarmClient.TimeSelector.TimeDuration;

113

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

AlarmClient.TimeSelector.TimeDuration = Value;
Example
AlarmClient1.TimeSelector.TimeDuration = 5; // The Alarm Control now retrieves alarms from the last 30 minutes.
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
TimeZone.TimeZone Property
The TimeZone. TimeZone property is a read-write string property that gets or sets the time zone of the Alarm Control.
The default value depends on the current setting of the operating system.
If you want to show time stamps using the local time of the computer, set the TimeZone. TimeZone property to an empty string.
Syntax
result = AlarmClient.TimeZone.TimeZone; AlarmClient.TimeZone.TimeZone = TimeZone;
Example
AlarmClient1.TimeZone.TimeZone = "(GMT-09:00) Alaska";
Remarks
For more information, see Setting Time Zone and Format on page 43.
TotalRowCount Property
The TotalRowCount property is a read -only integer property that gets the total number of alarm records in the Alarm Cont rol.
For current alarms (and recent alarms and events), the RowCount property value is always the same as the TotalRowCount property value.
For historical alarms, if the Alarm Control retrieves more alarm records than specified by the MaxDatabaseRecords property value, it splits these into multiple pages.
The RowCount property value shows how many alarm records are c urrently s hown on the current page, whereas the TotalRowCount property value shows how many alarm records are retrieved from the alarm database.
Syntax
Result = AlarmClient.TotalRowCount;
Return Value
Returns the end dat e and time of the Alarm Control in historical mode.
Example
NTRows = AlarmClient1.TotalRowCount; If (NTRows > 1000) then
LogMessage("More than 1000 records are currently in the Alarm Control"); Endif;
UnAckAlarms Property
The UnAckAlarms property is a read-only integer property that gets the number of unacknowledged alarm records in the Alarm Control.

114

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Syntax
Result = AlarmClient.UnackAlarms;
Return Value
Returns the number of unacknowledged alarm records in the Alarm Control.
Example
NUnack = AlarmClient1.UnAckAlarms; If NUnack > 10 Then
LogMessage("There are more than 10 unacknowledged alarms in the grid!"); Endif;
UpdateToCurrentTime Property
The UpdateToCurrent Time property is a read-writ e Boolean property that gets or sets the Update to Current Time option.
If you set this property to TRUE, the Alarm Control end time is set to the current time and the start time is calculated as the difference of end time and duration. Whenever you refresh the Alarm Control, the end time is set as current time.
If y ou set this property to FALSE, the Alarm Control uses the end time, duration, and start time as defined by the Time Range Picker control.
The default value is TRUE.
Syntax
result = AlarmClient.UpdateToCurrentTime; AlarmClient.UpdateToCurrentTime = UpdToCurrTime;
Example
AlarmClient1.UpdateToCurrentTime = 1; AlarmClient1.Requery();
Remarks
For more information, see Showing Historical Alarms and/or Events on page 23.
UserQueryFilterFilePath Property
Gets/Sets the file path of the runtime user queries and filters. The file path excludes the file name.
Syntax
result = AlarmClient.UserQueryFilterFilePath; AlarmClient.UserQueryFilterFilePath = myUserQueryFilterFilePath;
Example
AlarmClient1.UserQueryFilterFilePath = "C:\Users\Public\AppData\Wonderware";
Remarks
Default is %Userprofile%\Wonderware;
Visible Property
The Visible property is a read-write Boolean property that gets or sets the visibility of the Alarm Control.
Syntax
result = AlarmClient.Visible; AlarmClient.Visible = Boolean;

115

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Width Property
The Width property is a read-write integer property that gets or sets the width of the Alarm Control in pixels.
Syntax
result = AlarmClient.Width; AlarmClient.Width = Wdth;
WindowColor Property
The WindowColor property is a read-write color property that gets or sets the color of the Alarm Control background.
Syntax
Color = AlarmClient.WindowColor; AlarmClient.WindowColor = Color;
Parameters
Color Color of background.
Example
AlarmClient1.WindowColor = Color.FromARGB(240,200,198);
Remarks
For more information, see Setting Heading, Grid, and Window Color on page 28.
Color is a .NET Framework dat a type. You can use various Color methods to set the color, such as a predefined color name, FromA RGB (), FromK nownColor(), and FromName().
For a list of the .NE T color names and the hex adecimal codes, s ee .NET Colors on page 145.
For more information on the color methods, see the online Microsoft documentation for .NE T Framework De vel opme nt.
X Property
The X property is a read-write integer property that gets or sets the horizontal position of the Alarm Cont rol in relation to the left edge of the InTouc h window in which it appears.
Syntax
result = AlarmClient.X; AlarmClient.X = LeftPos;
Y Property
The Y property is a read-write integer property that gets or sets the vertical position of the Alarm Control in relation to the top edge of the InTouc h window in which it appears.
Syntax
result = AlarmClient.Y; AlarmClient.Y = TopPos;
Alarm Control Methods
This section describes the scripting methods available for the Alarm Control.

116

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

AboutBox() Method
The AboutBox method shows the About dialog box of the Alarm Control.
Syntax
AlarmClient.AboutBox();
Ack.All() Method
The Ack.All method acknowledges all alarms in the Alarm Control, including those not shown.
Syntax
AlarmClient.Ack.All(AckComment);
Parameters
Ack Comment A string indicating the alarm acknowledgement comment.
Example
AlarmClient1.Ack.All("Alarm is acknowledged");
Ack.Group() Method
The Ack.Group method acknowledges all alarms for a given alarm source and group. The alarm source and group names are case -insensitive.
Syntax
AlarmClient.Ack.Group(AlarmSource, Group, AckComment);
Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
Group The name of the alarm group. For example, $system. Ack Comment A string indicating the alarm acknowledgement comment.
Example
AlarmClient1.Ack.Group("\\machine1\galaxy", "Area_001", "All alarms in Area_001 acknowledged");
Ack.Priority() Method
The Ack.Priority method acknowledges all alarms for a given alarm source, group, and priority range. The alarm source and group names are case -insensitive.
Syntax
AlarmClient.Ack.Priority(AlarmSource, Group, FromPriority, ToPriority, AckComment);
Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
117

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Group The name of the alarm group. For example, $system.
FromPriorit y Starting priority of alarms. For example, 100.
ToPriority End priority of alarms. For example, 900.
Ack Comment A string indicating the alarm acknowledgement comment.
Example
GrpName = "ValveGroup"; AlarmClient1.Ack.Priority("\intouch", GrpName, 250, 500, "All local InTouch alarms in the ValveGroup alarm group with priorities from 250 to 500 are now acknowledged.");
Ack.Selected() Method
The Ack.Selected method acknowledges all selected alarms.
Syntax
AlarmClient.Ack.Selected(AckComment);
Parameters
Ack Comment A string indicating the alarm acknowledgement comment.
Example
AlarmClient1.Ack.Selected("This selected alarm is acknowledged");
Ack.SelectedGroup() Method
The Ack.SelectedGroup method acknowledges all alarms that have the same alarm sources and groups as one or more selected alarms.
Syntax
AlarmClient.Ack.SelectedGroup(AckComment);
Parameters
Ack Comment A string indicating the alarm acknowledgement comment.
Example
AlarmClient1.Ack.SelectedGroup("Alarm acknowledged");
Ack.SelectedPriority () Method
The Ack.SelectedPriority method acknowledges all alarms that have the same alarm sources, groups, and within the priority ranges as one or more selected alarms.
Syntax
AlarmClient.Ack.SelectedPriority(AckComment);
Parameters
Ack Comment A string indicating the alarm acknowledgement comment.
Example
AlarmClient1.Ack.SelectedPriority("Alarm acknowledged");
118

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Ack.SelectedTag() Method
The Ack.SelectedTag method acknowledges all alarms that have the same alarm sources, groups, tags, and within the priority ranges as one or more selected alarms.
Syntax
AlarmClient.Ack.SelectedTag(AckComment);
Parameters
Ack Comment A string indicating the alarm acknowledgement comment.
Example
AlarmClient1.Ack.SelectedTag("Alarm acknowledged");
Ack.Tag() Method
The Ack.Tag method acknowledges all alarms for a given alarm source, group, tag name, and priority range.
The alarm source, group names, and tag names are case-ins ensitive.
Syntax
AlarmClient.Ack.Tag(AlarmSource, Group, Tag, FromPriority, ToPriority, AckComment);
Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
Group The name of the alarm group. For example, $system.
Tag The name of the alarm tag. For example, ValveTag1.
FromPriorit y Starting priority of alarms. For example, 100.
ToPriority End priority of alarms. For example, 900.
Ack Comment A string indicating the alarm acknowledgement comment.
Example
AckComment = "All ArchestrA alarm records of the attribute Valve17 in the group (area) Vessel_25B of the galaxy on machine25 with prioriti es from 1 to 99 are now acknowledged."; AlarmClient1.Ack.Tag("\\machine25\galaxy", "Vessel_25B", "Valve17", 1, 99, AckComment);
Ack.Visible() Method
The Ack.Visible method acknowledges all alarms currently visible in the Alarm Control.
Syntax
AlarmClient.Ack.Visible(AckComment);

119

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Parameters
Ack Comment A string indicating the alarm acknowledgement comment.
Example
AlarmClient1.Ack.Visible("Alarm acknowledged");
Connect() Method
The Connect method connects the Alarm Control to the Alarm Database.
Syntax
AlarmClient.Connect();
Disconnect() Method
The Disconnect method disconnects the Alarm Control from the Alarm Dat abas e.
Syntax
AlarmClient.Disconnect();
Favorites.Export() Method
The Favorites.Export method exports the list of query and filter favorites list to an XML file.
Syntax
AlarmClient.Favorites.Export(FilePath, FileName);
Parameters
FilePath Name of the path to export the query and filter favorites file. FileName Name of the query and filter favorites file to ex port.
Example
AlarmClient1.Favorites.Export("c:\", "MyFavorites.xml");
Favorites.Import() Method
The Favorites.Import method imports the list of query and filter favorites list from an XML file. You can either overwrite the existing query and filter favorites with the new favorites, or append them.
Syntax
AlarmClient.Favorites.Import(FilePath, FileName, OverwriteAppend);
Parameters
FilePath Name of the path to the query and filter favorites file to import. FileName Name of the query and filter favorites file to import. OverwriteAppend String determining if the import of the query filter favorites overwrites existing favorites, or appends to existing favorites. Set to one of the following: o Overwrite to overwrite existing query filter favorites o Append to append to existing query filter favorites. If a query filter with the same name already
exists, it is not overwritten by the query filter in the file
120

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Example
AlarmClient1.Favorites.Import("c:\MyFavs\", "Favs.xml", "Overwrite");

FreezeDisplay() Method
The FreezeDisplay method freezes or unfreezes the Alarm Cont rol. The following values are possible:

Value

Description

TRUE

Freez es the Alarm Control.

FALSE

Unfreezes the Alarm Control.

Syntax
AlarmClient.FreezeDisplay(FreezeFlag);
Parameters
Freez eFlag Boolean value or expression (TRUE = freeze control, FALSE = unfreeze control)
Example
AlarmClient1.FreezeDisplay($hour > 17 OR $hour<9 ); LogMessage("The Alarm Control is frozen between 6 PM and 8 AM.");

GetItem() Method

The Get Item met hod returns the data at the given row and column. The row is given as a zero -bas ed index. You need to specify 0 to retrieve data from the 1st row. The column name can either be the original column name, or the displayed column name.
Syntax
Result = AlarmClient.GetItem(RowNumber, ColumnName);
Parameters
RowNumber An integer row number for the alarm record containing the value you want to fetch.
Colu mn Nam e Name of the column.
Return Value
Returns the data at the given row and column as a string value.
Example
Data1 = AlarmClient1.GetItem(5, "Current Value"); LogMessage("The current value of the 6th alarm record is " + Data1);
Remarks
To get alarm rec ord data from the currently selected row in a given column name, use the GetSelectedItem method.

GetLastError() Method
The Get LastError method returns the last error message. This is useful if the Hide Errors option is selected.
Syntax
ErrMsg = AlarmClient.GetLastError();

121

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Return Value
Returns the last error message.
Example
ErrMsg = AlarmClient1.GetLastError(); ComboBox1.AddItem(ErrMsg);
GetSelectedItem() Method
The GetS electedItem method returns the data at the currently selected row and specified column. The column name can eit her be the original column name, or the displayed column name.
Syntax
Result = AlarmClient.GetSelectedItem(ColumnName);
Parameters
Colu mn Nam e Name of the column.
Return Value
Returns the data in the currently selected row and specified column as a string value.
Example
Data2 = AlarmClient1.GetSelectedItem ("State"); LogMessage("The current state of the selected alarm record is " + Data2);
Remarks
To get alarm rec ord data from a given column name and row index, use the GetItem method.
Hide.All() Method
The Hide.All method hides all current alarms in the Alarm Control, including future alarms.
Syntax
AlarmClient.Hide.All();
Hide.Group() Method
The Hide.Group method hides all alarms for a given alarm source and group. The alarm source and group names are case -insensitive.
Syntax
AlarmClient.Hide.Group(AlarmSource, Group);
Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
Group The name of the alarm group. For example, $system.
Example
AlarmClient1.Hide.Group("\\machine1\galaxy", "Area_001"); LogMessage("All alarms in Area_001 hidden.");

122

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Hide.Priority() Method
The Hide.Priority method hides all alarms for a given alarm source, group, and priority range.
The alarm source and group names are case -insensitive.
Syntax
AlarmClient.Hide.Priority(AlarmSource, Group, FromPriority, ToPriority);
Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
Group The name of the alarm group. For example, $system.
FromPriorit y Starting priority of alarms. For example, 100.
ToPriority End priority of alarms. For example, 900.
Example
GrpName = "ValveGroup"; AlarmClient1.Hide.Priority("\intouch", GrpName, 250, 500); LogMessage("All local InTouch alarms in the ValveGroup alarm group with priorities from 250 to 500 are now hidden.");
Hide.Selected() Method
The Hide.Selected method hides all selected alarms.
Syntax
AlarmClient.Hide.Selected();
Hide.SelectedGroup() Method
The Hide.SelectedGroup method hides all alarms that have the same alarm sources and groups as one or more selected alarms.
Syntax
AlarmClient.Hide.SelectedGroup();
Hide.SelectedPriority() Method
The Hide.SelectedP riority met hod hides all alarms that have the s ame alarm sources, groups, and within the priority ranges as one or more selected alarms.
Syntax
AlarmClient.Hide.SelectedPriority();
Hide.SelectedTag() Method
The Hide.SelectedTag method hides all alarms that have the same alarm sources, groups, tag names, and within the priority ranges as one or more selected alarms.
Syntax
AlarmClient.Hide.SelectedTag();

123

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Remarks
None
Hide.Tag() Method
The Hide. Tag method hides all alarms for a given alarm source, group, tag name, and priority range.
The alarm source, group name, and tag names are case-insensitive.
Syntax
AlarmClient.Hide.Tag(AlarmSource, Group, Tag, FromPriority, ToPriority);
Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
Group The name of the alarm group. For example, $system. Tag The name of the alarm tag. For example, ValveTag1. FromPriorit y Starting priority of alarms. For example, 100.
ToPriority End priority of alarms. For example, 900.
Example
AlarmClient1.Hide.Tag("\\machine25\galaxy", "Vessel_25B", "Valve17", 1, 99); LogMessage("All ArchestrA alarm records of the attribute Valve17 in the group (area) Vessel_25B of the galaxy on machine25 with priorities from 1 to 99 are now hidden.");
Hide.Visible() Method
The Hide.Visible method hides all alarms currently shown in the Alarm Control.
Syntax
AlarmClient.Hide.Visible();
LoadQueryFilterFile
Load from an xml file wit h query and filter favorites ent ries wit h different override options. Return false for any error. Syntax AlarmClient.LoadQueryFilterFile(FilePath, OverrideOption);
Parameters
FilePath Name of the path to the query filter favorites file to import. Ove rri de Option
 Append: Add to the query and filter favorites. If a duplicate entry is already present, it will not append.
 Overwrite: Delete all current query and filter favorite ent ries and add the new entries from the file.

124

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

 Replace: Append and replace any duplicated entries with the contents from the file. Example AlarmClient. LoadQueryFilterFile("c:\users\public\file1.xml","Append")
MoveWindow() Method
The MoveWindow method scrolls the alarm records in the control in a given direction.
Syntax
AlarmClient.MoveWindow(ScrollDir, Repeat);
Parameters
ScrollDir String indicating the direction to scroll. This pa rameter is case-insensitive. See the following table.
ScrollDir Description

LineDn

Line down. The Repeat parameter cont rols the number of lines to be scrolled.

LineUp PageDn

Line up. The Repeat parameter controls the number of lines to be scrolled.
Page down. The Repeat parameter controls the number of pages to be scrolled.

PageUp

Page up. The Repeat parameter controls the number of pages to be scrolled.

Top Bottom PageRt

To the top of the cont rol
To the bottom of the control.
Page to the right. The Repeat parameter controls the number of pages to be scrolled.

PageLf

Page to the left. The Repeat parameter controls the number of pages to be scrolled.

Right

Scrolls right. The Repeat parameter controls the number of columns to be scrolled.

Left

Scrolls left. The Repeat parameter cont rols the number of columns to be

scrolled.

Hom e

Scrolls to the top row and left most column of the control.

Repeat Number of times to repeat the scroll action.
Example
AlarmClient1.MoveWindow ("Bottom", 0);

Requery() Method
The Requery method refres hes the alarm records in the Alarm Control. For current alarms and recent alarms and events, the control requeries the Alarm Manager. For historical alarms or events, the control retrieves alarm records from the Alarm Database.
125

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Syntax
AlarmClient.Requery();
Reset() Method
The Reset method resets column widths and the column order to their last known design-time settings. The Reset method also res ets the current query filter to the default query.
Syntax
AlarmClient.Reset();
ResetSortCriteria() Method
Reset the sorting criteria back to the design time settings and apply the sorting criteria. Syntax AlarmClient.ResetSortCriteria();
RunQuery() Method
Execute the query or filter available on the ArchestrA Alarm Control by name. If the ApplyAsFilter option is true, then execute the query as a filter only. Note the following behaviors:  If ApplyAsFilter is true, the parameter QueryName needs to be a valid Filter.
 If ApplyAsFilter is false, the parameter QueryName needs to be a valid Query.  In all other scenarios, the RunQuery() will not execute. Syntax AlarmClient.RunQuery(QueryName, ApplyAsFilter);
Parameters Que ryNam e The name of the query or filter available on the ArchestrA Alarm Control. ApplyAsFilter Specify True to execute a query as a filter using the filter criteria and retain the existing alarm subscription. Example AlarmClient.RunQuery ("High Alarms", true)
RunQueryFromFile() Method
Execute the query or filter by name defined in a file. This does not impact the current list of queries and filters. If ApplyAsFilter option is true, then execute the query as filter only. Note the following beha viors:  If ApplyAsFilter is true, the parameter QueryName needs to be a valid Filter.  If ApplyAsFilter is false, the parameter QueryName needs to be a valid Query.  In all other scenarios, the RunQuery() will not execute. Syntax AlarmClient.RunQueryFromFile(FilePath, QueryName, ApplyAsFilter); Parameters FilePath The file path to the query filter favorites file to execut e.

126

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Que ryNam e The name of the query or filter defined in the user provided file. ApplyAsFilter
Specify True to execute a query as a filter using the filter criteria and retain the existing alarm subscription. Example AlarmClient.RunQueryFromFile("c:\UserQueryFilter.xml", "User High Alarms", true)
Select.All() Method
The Select.All method selects all alarms in the Alarm Control.
Syntax
AlarmClient.Select.All();
Select.Group() Method
The Select.Group method selects all alarms for a given provider and group.
Syntax
AlarmClient.Select.Group(AlarmSource, Group);
Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
Group The name of the alarm group. For example, $system.
Example
AlarmClient1.Select.Group("\\machine1\galaxy", "Area_001"); LogMessage("All galaxy alarms of group Area_001 from machine1 are now selected.");
Select.Item() Method
The Select.Item method selects an alarm record at a given zero -bas ed row number.
Syntax
AlarmClient.Select.Item(RowNumber);
Parameters
RowNumber An integer row number for the alarm record to select. The first row in the control is 0.
Example
AlarmClient1.Select.Item(5); LogMessage("The alarm record in the 6th row (index 5) is now selected.");
Select.Priority() Method
The Select.Priority method selects all alarms for a given alarm source, group, and priority range.
Syntax
AlarmClient.Select.Priority(AlarmSource, Group, FromPriority, ToPriority);
127

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
Group The name of the alarm group. For example, $system.
FromPriorit y Starting priority of alarms. For example, 100.
ToPriority End priority of alarms. For example, 900.
Example
GrpName = "ValveGroup"; AlarmClient1.Select.Priority("\intouch", GrpName, 250, 500); LogMessage("All local InTouch alarms in the ValveGroup alarm group with priorities from 250 to 500 are now selected.");
Select.Tag() Method
The Select.Tag met hod selects all alarms for a given alarm source, group, tag name, and priority range.
Syntax
AlarmClient.Select.Tag(AlarmSource, Group, Tag, FromPriority, ToPriority);
Parameters
AlarmSource The name of the provider and optionally node providing alarms including backslash. For example: \\node1\galaxy \intouch
Group The name of the alarm group. For example, $system.
Tag The name of the alarm tag. For example, ValveTag1.
FromPriorit y Starting priority of alarms. For example, 100.
ToPriority End priority of alarms. For example, 900.
Example
AlarmClient1.Select.Tag("\\machine25\galaxy", "Vessel_25B", "Valve17", 1, 99); LogMessage("All ArchestrA alarm records of the attribute Valve17 in the group (area) Vessel_25B of the galaxy on machine25 with priorities from 1 to 99 are now selected.");
SetSort() Method
The SetSort met hod sets the level of sorting according to the defined sort columns and sort orders.
Syntax
AlarmClient.SetSort(Level);

128

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Parameters
Level The level of sorting:

Value

Description

1

Only use the first sort column.

2

Use first and second sort columns.

3

Use first, second, and third sort columns.

4

Use first, second, third, and fourth sort columns.

Example
AlarmClient1.SetSort(2);
Remarks
Use the Show.Sort method to open the Sort dialog box instead.

SetSortCriteria() Method

Set the sorting criteria by supplying a string of which columns to sort and their order. Then apply the sort criteria. Ret urn false if any error.
Syntax AlarmClient.SetSortCriteria(SortCriteriaString);
Parameters SortCriteriaSt ring
The string containing the sorting criteria to be executed. The syntax of the sort criteria string is: [CriteriaName]:[1|-1];
where:
CriteriaName is the name of the sorting criteria Colon is separator for sort order int eger Use 1 for Ascending order
Use -1 for Descending order Semicolon is separator for the next sorting criteria If ordering integer is not supplied, then default to ascending order
Example Example1: Sort by time ascending order and then by Priority ascending order AlarmClient.SetSortCriteria("TimeLCT:1; Priority:1");

Example2: Sort by time ascending order using default value and then by Priority descending order AlarmClient.SetSortCriteria("TimeLCT; Priority:-1");

Example3: Sort by ascending order in sequence of InAlarm, AckState, Priority, and Time. AlarmClient.SetSortCriteria("InAlarm;AckState;Priority;TimeLCT");

129

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Shelve.All() Method
The Shelve.All() method shelves all active alarms shown in the Alarm Control.
Syntax
AlarmClient.Shelve.All(Duration=Duration;Reason="Reason");
Parameters
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example: Duration=0.5
Reas on Explanation up to 200 characters for shelving all active alarms shown in the Alarm Control. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient1.Shelve.All("Duration=0.1;Reason='Shelve all alarms';");
Remarks
For more information about shelving alarms, see Shelving Alarms on page 60.
Shelve.Group() Method
The Shelve. Group() met hod shelves all alarms belonging to a specified provider and alarm group.
Syntax
AlarmClient.Shelve.Group("ProviderName", "GroupName",Duration=Duration;Reason="Reason");
Parameters
Provi de rN ame Node and provider name combination that specifies the origin of alarm monitoring.
Gro up Nam e Alarm group or area name whose alarms are monitored by the Alarm Cont rol.
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example: Duration=0.5
Reas on Explanation up to 200 characters for shelving alarms by groups shown in the Alarm Control. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Examples
AlarmClient1.Shelve.Group("\\TankServer1\Galaxy","Area_001", Duration=0.1;Reason=" + """" + "Shelved"+ """" + ";");

130

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

AlarmClient1.Shelve.Group("\Galaxy","Area_001",Duration=0.1; Reason=" + """" + "Shelved"+ """" + ";");
Remarks
For more information about specifying provider and group names, see Alarm Queries on page 13.
Shelve.Priority() Method
The Shelve.Priority() method shelves all active alarms within a specified alarm priority range that belong to the same specified provider and alarm group.
Syntax
AlarmClient.Shelve.Priority("ProviderName","GroupName", FromPriority,ToPriority,Duration=Duration;Reason="Reason");
Parameters
Provi de rN ame Node and provider name combination that specifies the origin of alarm monitoring.
Gro up Nam e Alarm group or area name whose alarms are monitored by the Alarm Cont rol.
FromPriorit y Starting point of the alarm priority range (1-999). The FromPriority value must be less than the ToPriority value.
ToPriority Three-digit end point of the alarm priority range (2-999). The ToPriority value must be greater than the FromPriority value.
Duration Length of time in hours that selected alarms are shelved. Durat ion can be specified as an int eger or a floating point number greater than 0.
Example: Duration=0.5
Reas on Explanation up to 200 characters for shelving alarms by priority range that are shown in the Alarm Cont rol. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient1.Shelve.Priority("\Galaxy","Area_001",100,600, Duration=0.1;Reason=" + """" + "Shelved"+ """" + ";");
Remarks
For more information about setting an alarm priority range, see Setting Priority Ranges for Alarm Records on page 29.
Shelve.Selected() Method
The Shelve.S elected() method shelves one or more active alarms selected by the user from the Alarm Cont rol.
Syntax
AlarmClient.Shelve.Selected(Duration=Duration;Reason="Reason");

131

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Parameters
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example: Duration=0.5
Reas on Explanation up to 200 characters for shelving active alarms selected by the user from the Alarm Cont rol. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient.Shelve.Selected(Duration=1.0; Reas on="Nuisance alarms");
Remarks
For more information about selecting alarms to shelve.see Shelving Alarms on page 60.
Shelve.SelectedGroup() Method
The Shelve.S elected.Group method shelves all active alarms that belong to the same alarm groups as the alarms selected by the user from the Alarm Control.
Syntax
AlarmClient.Shelve.SelectedGroup(Duration=Duration; Reason="Reason");
Parameters
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example: Duration=0.5
Reas on Explanation up to 200 characters for shelving alarms in the same group as the alarms selected by the user from the Alarm Control. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient.Shelve.SelectedGroup(Duration=1.0;Reason="Low severity nuisance alarms");
Remarks
For more information about selecting alarms to shelve.see Shelving Alarms on page 60.
Shelve.SelectedPriority() Method
The Shelve.S electedPriority method shelves all active alarms that belong to the same alarm priority as the alarms selected by the user from the Alarm Control.

132

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Syntax
AlarmClient.Shelve.SelectedPriority(Duration=Duration; Reason="Reason");
Parameters
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example: Duration=0.5
Reas on Explanation up to 200 characters for shelving alarms in the same priority range as the alarms selected by the user from the Alarm Control. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient.Shelve.SelectedPriority(Duration= 1.0;Reason="Low priority nuisance alarms");
Remarks
For more information about selecting alarms to shelve.see Shelving Alarms on page 60.
Shelve.SelectedSeverity() Method
The Shelve.S elected.Severity method shelves all active alarms for a given alarm group, tag name, and severity as the alarms selected by the user from the Alarm Control.
Syntax
AlarmClient.Shelve.SelectedSeverity(Duration=Duration; Reason="Reason");
Parameters
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example:
Duration=0.5
Reas on Explanation up to 200 characters for shelving alarms at the same severity as the alarms selected by the user from the Alarm Control. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient.Shelve.SelectedSeverity(Duration=1.0;Reason="Low severity nuisance alarms");
Remarks
For more information about selecting alarms to shelve.see Shelving Alarms on page 60.

133

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Shelve.SelectedTag() Method
The Shelve.S electedTag method shelves all active alarms all active alarms for a given provider, alarm group, and tag name as the alarms selected by the us er from the Alarm Control.
Syntax
AlarmClient.Shelve.SelectedTag(Duration=Duration; Reason="Reason");
Parameters
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example:
Duration=0.5
Reas on Explanation up to 200 characters for shelving alarms from the same tags as the alarms selected by the user from the Alarm Control. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient.Shelve.SelectedTag(Duration=1.0;Reason="Nuisance alarms");
Remarks
For more information about selecting alarms to shelve.see Shelving Alarms on page 60.
Shelve.Severity() Method
The Shelve.S everity() met hod shelves all active alarms of a specified alarm severity that belong to the same specified provider and alarm group.
Syntax
AlarmClient.Shelve.Severity("ProviderName","GroupName", Severity,Duration=Duration;Reason="Reason");
Parameters
Provi de rN ame Node and provider name combination that specifies the origin of alarm monitoring.
Gro up Nam e Alarm group or area name whose alarms are monitored by the Alarm Cont rol.
Severity Single-digit (1-4) alarm severity.
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example:
Duration=0.5
Reas on Explanation up to 200 characters for shelving alarms at a specified severity from the Alarm Control.

134

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient1.Shelve.Severity("\Galaxy","Area_001",3, Duration=0.1;Reason=" + """" + "Shelved"+ """" + ";");
Remarks
For more information about selecting alarms to shelve.see Shelving Alarms on page 60.
Shelve.Tag() Method
The Shelve.tag() method shelves all active alarms that originate from the same tag and belong to the same provider and alarm group within the same alarm priority range.
Syntax
AlarmClient.Shelve.Tag("ProviderName","GroupName","Tag" FromPriority,ToPriority,Duration=Duration;Reason="Reason");
Parameters
Provi de rN ame Node and provider name combination that specifies the origin of alarm monitoring.
Gro up Nam e Alarm group or area name whose alarms are monitored by the Alarm Cont rol.
Tag Name of the tag whose active alarms have been selected to be shelved.
FromPriorit y Starting point of the alarm priority range (1-998). The FromPriority value must be less than the ToPriority value.
ToPriority End point of the alarm priority range (2-999). The ToPriority value must be greater than the FromPriority value.
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example:
Duration=0.5
Reas on Explanation up to 200 characters for shelving alarms from the same tags. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Example
AlarmClient1.Shelve.Tag("\Galaxy","Area_002", "UserDefined_002.Analog_003",1,999,"Duration=1.5;Reason=" + """" + "Shelved"+ """" + ";");
Remarks
For more information about selecting alarms to shelve.see Shelving Alarms on page 60.

135

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Shelve.Visible() Method
The Shelve.Visible() method shelves only those alarms that are currently visible from the Alarm Control.
Syntax
AlarmClient.Shelve.Visible("Duration=<Duration Hrs>;Reason="+"<Reason>"+"Shelved"+"<Description>"+";");
Parameters
Duration Length of time in hours that selected alarms are shelved. Duration can be specified as an int eger or a floating point number greater than 0.
Example: Duration=0.5 Reas on Explanation up to 200 characters for shelving all alarms that are visible from the Alarm Control. An explanation can be delimited by double or single quotation marks. Quotation marks and back slashes (\) can appear within the text of an explanation. If an explanation is delimited by double quotation marks, a single quotation mark is simply a character in the string. If an explanation is delimited by single quotation marks, a double quotation mark is simply a character in the string.
Examples
AlarmClient1.Shelve.Visible("Duration=1.0; Reason="+""""+"Shelved"+""""+";");
Remarks
For more information about selecting alarms to shelve.see "Shelving Alarms" on page 74 on page 60.
Show.Context() Method
The Show.Context method opens the shortcut menu at run time. This method ignores the ShowContextMenu property setting and always shows the context menu.
Syntax
AlarmClient.Show.Context();
Show.Favorite() Method
The Show.Favorite method opens the Query Filters dialog box.
Syntax
AlarmClient.Show.Favorite();
Show.Hidden() Method
The Show.Hidden method opens the Hidden Alarms dialog box.
Syntax
AlarmClient.Show.Hidden();
Show.Sort() Method
The Show.Sort method opens the Sort dialog box.
Syntax
AlarmClient.Show.Sort();

136

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Show.Statistics() Method
The Show.Statistics method opens the Alarm Statistics dialog box.
Syntax
AlarmClient.Show.Statistics();
TimeSelector.GetStartAndEndTimes() Method
The TimeS elector.GetStartAndE ndTimes method gets the start and end times for the query.
Syntax
AlarmClient.GetStartAndEndTimes(StartTime, EndTime);
Parameters
StartTime String attribute, custom property, or element property to retrieve the start time.
EndTime String attribute, custom property, or element property to retrieve the end time.
Example
dim SDate as string; dim EDate as string; AlarmClient1.TimeSelector.GetStartAndEndTimes(SDate, EDate); StartDate = SDate; EndDate = EDate;
TimeSelector.RefreshTimes() Method
The TimeS elector. RefreshTimes method sets the time period for the query by updating the end time to current time and recalculat es the start time based on the new end time and duration.
If you set the Boolean parameter to TRUE, the OnChange event is triggered if the time is updated. Only use this method, if the Update to Current Time option is cleared or the UpdateToCurrentTime property is FALSE.
Note: This method does not work if the UpdatetoCurrentTime property value is TRUE.
Syntax
AlarmClient.TimeSelector.RefreshTimes(TriggerEvent);
Example
dtag = 1; AlarmClient.TimeSelector.RefreshTimes(dtag);
TimeSelector.SetStartAndEndTimes() Method
The TimeS elector.SetStartAndEndTimes method sets the start and end times for a query. To customize start time, duration, and end time you must set the UpdateToCurrentTime property to FALSE and specify one of the following parameter combinations:
 Start time and end time. Set the Duration parameter to 0.  Start time and duration. Set the EndTime parameter to "".  End time and duration. Set the StartTime parameter to "".
 Start time, duration, and end time. The Alarm Cont rol shows an error message if start time plus duration is not equal to end time.
137

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Syntax
AlarmClient.SetStartAndEndTimes(StartTime, EndTime, Duration);
Parameters
StartTime String value or expression indicating the start time. EndTime String value or expression indicating the end time. Duration Duration enum. For more information on possible values, see TimeSelector.TimeDuration Property page 112.
Example
AlarmClient1.TimeSelector.SetStartAndEndTimes("08/31/2008 15:33:43","09/01/2009 15:33:43",0);
Toggle.All() Method
The Toggle.All method reverses the selection of all alarm records. Selected alarms are cleared, and unselected alarms are selected.
Syntax
AlarmClient.Toggle.All();
Toggle.Item() Method
The Toggle. Item method revers es the selection of a given alarm record. If the given alarm record is selected, the selection is cleared; otherwise, it is selected.
Syntax
AlarmClient.Toggle.Item(RowNumber);
Parameters
RowNumber An integer row number for the alarm record to reverse the selection. The first row in the control is 0.
Example
AlarmClient1.Toggle.Item(5); LogMessage("The selection of the alarm record in the 6th row (index 5) is now reversed.");
UnhideAll() Method
The UnhideAll method unhides all hidden alarms.
Syntax
AlarmClient.UnhideAll();
UnSelectAll() Method
The UnSelectAll method unselects all alarm records.
Syntax
AlarmClient.UnSelectAll();
Unshelve.All() Method
The Unshelve.All() method uns helves all alarms that are currently shelved.

138

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Syntax
AlarmClient.Unshelve.All(Duration=0;Reason="Reason");
Parameters
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving all alarms. An explanation is optional to unshelve alarms and the Reason parameter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient1.Unshelve.All(Duration=0;Reason="");
Remarks
For more information about uns helving alarms, see Unshelving Alarms on page 62.
Unshelve.Group() Method
The Unshelve.Group() method unshelves all currently shelved alarms belonging to a specified provider and alarm group.
Syntax
AlarmClient.Unshelve.Group("ProviderName","GroupName", Duration=0;Reason="Reason");
Parameters
Provi de rN ame Node and or provider name combination that specifies the origin of alarm monitoring.
Gro up Nam e Alarm group or area name whose alarms are monitored by the Alarm Cont rol.
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving all alarms belonging to a specified group and provider.
An explanation is optional to unshelve alarms and the Reason parameter can be specified as Reason="" to indicate a null explanation.
Examples
AlarmClient1.Unshelve.Group("\\TankServer1\Galaxy","Area_001", Reason=" + """" + "Shelved"+ """" + ";"); AlarmClient1.Unshelve.Group("\Galaxy","Area_001",Reason=" + """" + "Shelved"+ """" + ";");
Remarks
For more information about specifying provider and group names, see Alarm Queries on page 13.
Unshelve.Priority() Method
The Unshelve.Priority() method unsh elves currently shelved alarms within a specified alarm priority range that belong to the same specified provider and alarm group.

139

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Syntax
AlarmClient.Unshelve.Priority("ProviderName","GroupName",FromPriority,ToPrio rity,"Duration=<Duration>;Reason="+"<Reason>"+"UnShelved"+"<Description>"+"; ");
Parameters
Provi de rN ame Node and provider name combination that specifies the origin of alarm monitoring.
Gro up Nam e Alarm group or area name whose alarms are monitored by the Alarm Cont rol.
FromPriorit y Three-digit starting point of the alarm priority range. The FromPriority value must be less than the ToPriority value.
ToPriority Three-digit end point of the alarm priority range. The ToPriority value must be great er than the FromPriority value.
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving all alarms belonging to a specified alarm priority range.
An explanation is optional to unshelve alarms and the Reason parameter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient1.Unshelve.Priority("\Galaxy","Area_001",100,600,"Duration=0;Reas on="+""""+"UnShelved"+""""+";");
Remarks
For more information about uns helving alarms, see "Unshelving Alarms" on page 75 on page 62.
Unshelve.Selected() Method
The Unshelve.Selected() method unshelves currently shelved alarms selected by the user from the Alarm Control.
Syntax
AlarmClient.Unshelve.Selected(Duration=0;Reason="Reason");
Parameters
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving alarms selected by the user.
An explanation is optional to unshelve alarms and the Reason param eter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient.Unshelve.Selected(Duration=0;Reason="Maintenance finished");
Remarks
For more information about uns helving alarms, see Unshelving Alarms on page 62.

140

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Unshelve.SelectedGroup() Method
The Unshelve.SelectedGroup() method unshelves all alarms that belong to the same provider and alarm groups as the alarms selected by the user from the Alarm Control.
Syntax
AlarmClient.Unshelve.SelectedGroup(Duration=0;Reason="Reason");
Parameters
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving alarms that belong to the same alarm groups as the alarms selected by the user.
An explanation is optional to unshelve alarms and the Reason parameter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient.Unshelve.SelectedGroup(Duration=0;Reason="");
Remarks
For more information about uns helving alarms, see Unshelving Alarms on page 62.
Unshelve.SelectedPriority() Method
The Unshelve.SelectedPriority method unshelves all alarms within the same alarm priority range as the alarms selected by the user from the Alarm Cont rol.
Syntax
AlarmClient.Unshelve.SelectedPriority(Duration=0;Reason="Reason");
Parameters
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving the alarms within the same alarm priority range as the alarms selected by the user.
An explanation is optional to unshelve alarms and the Reason parameter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient.Unshelve.SelectedPriority(Duration=0; Reason="Maintenance finished");
Remarks
For more information about uns helving alarms, see Unshelving Alarms on page 62.
Unshelve.SelectedSeverity() Method
The Unshelve.SelectedSeverity method unshelves all shelved alarms within the same alarm severities as the alarms selected by the user from the Alarm Control.
Syntax
AlarmClient.Unshelve.SelectedSeverity(Duration=0;Reason="Reason");

141

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Parameters
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving the shelved alarms that belong to the same alarm severities as the alarms selected by the user.
An explanation is optional to unshelve alarms and the Reason parameter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient.Unshelve.SelectedSeverity(Duration=0;Reason="Low severity alarms");
Remarks
For more information about uns helving alarms, see Unshelving Alarms on page 62.
Unshelve.SelectedTag() Method
The Unshelve.SelectedTag method unshelves all shelved alarms that originate from the same tags as the alarms selected by the user from the Alarm Control.
Syntax
AlarmClient.Unshelve.SelectedTag(Duration=0;Reason="Reason");
Parameters
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving the active alarms from the same tags as the alarms selected by the user.
An explanation is optional to unshelve alarms and the Reason parameter can be sp ecified as Reason="" to indicate a null explanation.
Example
AlarmClient.Unshelve.SelectedTag(Duration=0;Reason="");
Remarks
For more information about uns helving alarms, see Unshelving Alarms on page 62.
Unshelve.Severity() Method
The Unshelve.Severity() method unshelves all shelved alarms of a specified alarm severity that belong to the same specified provider and alarm group.
Syntax
AlarmClient.Unshelve.Severity("ProviderName","GroupName",Severity,"Duration= <Duration>;Reason="+"<Reason>"+"UnShelved"+"<Description>"+";");
Parameters
Provi de rN ame Node and provider name combination that specifies the origin of alarm monitoring.
Gro up Nam e Alarm group or area name whose alarms are monitored by the Alarm Cont rol.

142

Scripting the Alarm Control

AVEVATM ArchestrA Alarm Control Guide

Severity Single-digit (1-4) alarm severity.
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for unshelving the active ala rms of the specified severity.
An explanation is optional to unshelve alarms and the Reason parameter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient1.Unshelve.Severity("\Galaxy","Area_001",3,"Duration=0;Reason="+" """+"UnShelved"+""""+";");
Remarks
For more information about uns helving alarms, see "Unshelving Alarms" on page 75 on page 62.
Unshelve.Tag() Method
The Uns helve. Tag() method unshelves all shelved alarms that have the same tag names from the same provider and alarm groups and are within the same priority range.
Syntax
AlarmClient.UnShelve.Tag("ProviderName","GroupName","Tag",FromPriority,ToPri ority,"Duration=<Duration>;Reason="+"<Reason>"+"UnShelved"+"<Description>"+" ;");
Parameters
Provi de rN ame Node and provider name combination that specifies the origin of alarm monitoring.
Gro up Nam e Alarm group or area name whose alarms are monitored by the Alarm Cont rol.
Tag Name of the tag whose active alarms have been selected to be unshelved.
FromPriorit y Three-digit starting point of the alarm priority range. The FromPriority value must be less than the ToPriority value.
ToPriority Three-digit end point of the alarm priority range. The ToPriority value must be great er than the FromPriority value.
Duration Duration must be set to 0 to unshelve alarms.
Reas on Explanation up to 200 characters for shelving the active alarms that belong to the same alarm severities as the alarms selected by the user.
An explanation is optional to unshelve alarms and the Reason parameter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient1.UnShelve.Tag("\Galaxy","Area_001","User_Defined_001.Attribute00 4.LoLo",1,999,"Duration=0;Reason="+""""+"UnShelved"+""""+";");

143

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Remarks
For more information about uns helving alarms, see "Unshelving Alarms" on page 75 on page 62.
Unshelve.Visible() Method
Th Unshelve.Visible() method unshelves only those alarms that are currently visible from the Alarm Cont rol.
Syntax
AlarmClient.Unshelve.Visible("Duration=<Duration>;Reason="+"<Reason>"+"UnShe lved"+"<Description>"+";");
Parameters
Duration Duration must be set to 0 to unshelve alarms. Reas on Explanation up to 200 characters for unshelving the alarms currently shown from the Alarm Control. An explanation is optional to unshelve alarms and the Rea son parameter can be specified as Reason="" to indicate a null explanation.
Example
AlarmClient1.Unshelve.Visible("Duration=0;Reason="+""""+"UnShelved"+""""+";" );
Remarks
For more information about uns helving alarms, see "Unshelving Alarms" on page 75 on page 62.
Configuring Events
You can execute an action script when the Alarm Cont rol triggers an event. Examples of basic events are:
 Click: The us er clicks the Alarm Control
 DoubleClick: The user double-clicks the Alarm Control
 Startup: The Alarm Control opens at run time
 Shutdown: The Alarm Cont rol closes at run time The Click, Double Click, Start up, and Shutdown events are standard for all .NE T client controls. For more information, see the Creating and Managing Industrial Graphics Users Guide.
The Alarm Control has one event of its own that is triggered when a new alarm occurs, the NewAlarm event.
Configuring the NewAlarm Event
You can configure the NewAlarm event to execute an Industrial graphic script whenever a new alarm occurs. You can control the trigger behavior with the NewAlarmE ventMode property. For more information, see NewAlarmEvent Mode Property on page 102.
To configure the NewAlarm event
1. Double-click the Alarm Control. The Edit Animations dialog box appears. 2. Click Event. The Event page appears.

144

Scripting the Alarm Control 3. In the Event list, click NewAlarm.

AVEVATM ArchestrA Alarm Control Guide

4. In the script area, type the script you want to execute when a new alarm occurs, for example: AlertIcon.Visible = true;
5. You must also s et the NewAlarmE ventMode property to 1 or 2 t o enable the NewAlarm event trigger. Do the following: a. On the Special menu, click Scripts. The Edit Scripts dialog box appears.
b. Make sure Trigger type is set to On Show. c. In the script area, type the following:
AlarmClient1.NewAlarmEventMode = 1;
d. If you want the script to be executed every time a new alarm occurs, set the NewAlarmE ventMode property to 2 instead.
e. Click OK.
.NET Colors
The following table is an overview of the color .NE T color names with hexadecimal code.

Color with Hex Code AliceBlue #F0F8FF Aquamarine #7FFFD4 Bisque #FFE 4C4

Color with Hex Code AntiqueWhite #FAEBD7 Azure #F0FFFF Black #000000

Color with Hex Code Aqua #00FFFF Beige #F5F5DC BlanchedAlmond #FFEB CD

Blue #0000FF BurlyWood #DEB887 Choc olate #D2691E

BlueViolet #8A2BE2 CadetBlue #5F9EA 0 Coral #FF7F50

Brown #A52A2A Chartreuse #7FFF00 CornflowerBlue #6495E D

145

AVEVATM ArchestrA Alarm Control Guide

Scripting the Alarm Control

Color with Hex Code Cornsilk #FFF8DC DarkBlue #00008B Dark Gray #A 9A9A9 DarkMagenta #8B008B Dark Orchid #9932CC DarkSeaGreen #8FBC8B Dark Turquoise #00CE D1 DeepSkyBlue #00BFFF Firebrick #B22222 Fuchsia #FF00FF Gold #FFD700 Green #008000 HotPink #FF69B4 Ivory #FFFFF0 LavenderBlush #FFF0F5 LightBlue #ADD8E 6 LightGoldenrodY ellow #FAFAD2 LightPink #FFB 6C1 LightSkyBlue #87CE FA LightYellow #FFFFE0 Linen #FAF0E 6 MediumA quamarine #66CDAA MediumP urple #9370DB

Color with Hex Code Crimson #DC143C Dark Cyan #008B8B Dark Green #006400 Dark OliveGreen #556B2F Dark Red #8B0000 DarkSlat eBlue #483D8B DarkViolet #9400D3 DimGray #696969 FloralWhite #FFFAF0 Gainsboro #DCDCDC Goldenrod #DAA520 GreenYellow #A DFF2F IndianRed #CD5C5C Khaki #F0E68C LawnGreen #7CFC00 Light Coral #F08080 LightGray #D3D3D3

Color with Hex Code Cyan #00FFFF Dark Goldenrod #B8860B DarkKhaki #BDB 76B Dark Orange #FF8C00 DarkSalmon #E9967A DarkSlat eGray #2F4F4F DeepPink #FF1493 DodgerBlue #1E90FF ForestGreen #228B 22 GhostWhite #F8F8FF Gray #808080 Honeydew #F0FFF0 Indigo #4B0082 Lavender #E6E6FA LemonChiffon #FFFACD Light Cyan #E 0FFFF LightGreen #90EE90

LightSalmon #FFA07A LightSlateGray #778899 Lime #00FF00 Magenta #FF00FF MediumBlue #0000CD

LightSeaGreen #20B2AA LightSteelBlue #B0C4DE LimeGreen #32CD32 Maroon #800000 MediumOrchid #BA55D3

MediumS eaGreen #3CB 371 MediumSlateBlue #7B68EE

MediumS pringGreen #00FA 9A MidnightBlue #191970
146

MediumTurquoise #48D1CC MediumVioletRed #C71585

MintCream #F5FFFA

MistyRose #FFE4E1

Scripting the Alarm Control

Color with Hex Code Moccasin #FFE4B5 OldLace #FDF5E6 Orange #FFA500 PaleGoldenrod #EEE8AA PaleViolet Red #DB 7093 Peru #CD853F PowderBlue #B0E 0E6 RosyBrown #B C8F8F Salmon #FA8072 SeaShell #FFF5EE SkyBlue #87CEEB Snow #FFFAFA Tan #D2B48C Tomato #FF6347 Violet #EE82EE WhiteSmoke #F5F5F5

Color with Hex Code NavajoWhite #FFDEAD Olive #808000 OrangeRed #FF4500 PaleGreen #98FB98 PapayaWhip #FFEFD5 Pink #FFC0CB Purple #800080 RoyalBlue #4169E1 SandyBrown #F4A 460 Sienna #A0522D SlateBlue #6A5ACD SpringGreen #00FF7F Teal #008080 Trans parent #FFFFFF Wheat #F5DEB3 Yellow #FFFF00

AVEVATM ArchestrA Alarm Control Guide
Color with Hex Code Navy #000080 OliveDrab #6B8E23 Orchid #DA70D6 PaleTurquoise #AFEEEE PeachPuff #FFDAB9 Plum #DDA0DD Red #FF0000 SaddleBrown #8B4513 SeaGreen #2E 8B57 Silver #C0C0C0 SlateGray #708090 SteelBlue #4682B4 Thistle #D8B FD8 Turquoise #40E 0D0 White #FFFFFF YellowGreen #9ACD32

147

AVEVATM ArchestrA Alarm Control Guide
CHAPTER 5
Transferring Alarm Configuration from
InTouch
You can transfer the configuration of the InTouch Alarm Viewer control and the InTouch Alarm DB View control to the configuration of the ArchestrA Alarm Control. You can also map the InTouch alarm control properties and methods to the properties and methods of the ArchestrA Alarm Control.
Transferring the InTouch Alarm Viewer Control Configuration
You can transfer the configuration of the InTouch Alarm Viewer cont rol tabs options to the ArchestrA Alarm Control.
Transferring Configuration of the Control Name Tab
You can transfer the configuration of the Control Name tab options of the InTouch Alarm Viewer control to the ArchestrA Alarm Cont rol.

InTouch option Alarm Control option

Cont rolName
Left, Top, Width, and Height

You can rename the ArchestrA Alarm Control the same way as any other elements on the canvas. For more information, see the Creating and Managing Industrial Graphics User's Guide.
You can directly edit the positioning options in the same way as any other element on the canvas. Edit the following properties in the Properties Editor: X, Y, Width, and Height.

149

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

InTouch option Visible
GUID

Alarm Control option
You can directly edit the visibility option in the same way as any other element on the canvas. In the Properties Editor, edit the Vi sible property.
This option has no meaning in the ArchestrA Alarm Control.

Transferring Configuration of the General Tab
You can trans fer the configuration of the General tab options of the InTouch Alarm Viewer control to the ArchestrA Alarm Control.

InTouch option Alarm Control option

Perform Query on Startup
Show Context Sensitive Menu

In the Arc hestrA Alarm Cont rol, this option is called Query on Startup. You can configure this option on the Run-Time Behavior page.
In the Arc hestrA Alarm Cont rol, this option is called Show Context Menu. You can configure this option on the Run-Time Behavior page.

Configure Context Menus

In the Arc hestrA Alarm Cont rol, you can configure the availability of individual shortcut menu options at run -time directly on t he Run-Time Behavior page.

Use Default Ack Comm ent

In the Arc hestrA Alarm Cont rol, you can configure the availability of the Query Filters shortcut menu option on the Run-Time Behavior page.

Retain Suppression In the Arc hestrA Alarm Cont rol, this option is called Retain Hidden. You can configure it on the Run-Time Behavior page.

150

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

InTouch option Alarm Control option

Show Status Bar Show Heading Row Selection Use Extended Selection Show Grid Retrieve Buttons
Silent Mode

In the Arc hestrA Alarm Cont rol, you can configure the Show Grid option on the Run-Time Behavior page.
In the Arc hestrA Alarm Cont rol, you can configure the Show Status Bar option on the Run-Time Behavior page.
In the Arc hestrA Alarm Cont rol, this option is called Row Selection. You can configure it on the Run-Time Behavior page.
In the Arc hestrA Alarm Cont rol, this option is called Row Selection. You can configure it on the Run-Time Behavior page.
In the Arc hestrA Alarm Cont rol, you can config ure the Show Grid option on the Run-Time Behavior page.
In the ArchestrA Alarm Control, the retrieve buttons are not available. The underlying grid technology handles the alarm retrieval from the alarm database.
In the ArchestrA Alarm Control, this option is called Hide Errors and Warnings. You can configure it on the Run-Time Behavior page.

Flash Unack Alarms In the Arc hestrA Alarm Cont rol, you can configure the Flash Unack Alarms option on the Colors page.

Show Message

In the Arc hestrA Alarm Cont rol, this option is called Show Custom `No Records' Me ssage. You can configure it on the Run-Time Behavior page.

Font

You can configure this option from the Industrial Graphic Editor page.

Select the ArchestrA Alarm Control on the canvas and select an

appropriate font type, size, and style on the menu bars.

Column Details

In ArchestrA Alarm control, you can configure the column details directly on the Column Details page.

151

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

Transferring Configuration of the Color Tab
You can transfer the configuration of the Color tab options of the InTouch Alarm Viewer control to the ArchestrA Alarm Control.

All the options of the Color tab in the InTouch Alarm Viewer control can be s et on the Colors page of the ArchestrA Alarm Control. The following table shows you some minor differences in wording:
InTouch Alarm View control Arche strA Alarm Control

Title Bar Text

Heading Text

Title Bar Back

Heading Background

Alarm Return

Alarm RTN

you can also set he background color in addition to the text color for most of the alarm records. You can set the alarm priority range breakpoints directly in the table in the From Pri column.

152

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

Transferring Configuration of the Time Format Tab
You can trans fer t he configuration of the Time Format tab options of the InTouch Alarm Viewer control to the ArchestrA Alarm Control.

InTouch option Time Format Displayed Time
Displayed Time Zone

Alarm Control option
In the ArchestrA Alarm Control, you can configure the Time Format option on the Time Settings page.
This option has no meaning in the ArchestrA Alarm Control. All alarm records are shown with the following time stamps in the Alarm Cont rol grid:
 Time (OAT): Original Alarm Time  Time (LCT): Last Changed Time  Time (LCT, OAT): Last Changed Time, but Original Alarm Time
if the alarm record is unacknowledged
In the ArchestrA Alarm Control, this option is called Time Zone. You can configure it on the Time Settings page. You need to explicitly configure the time zone for the correct time stamp.

153

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

Transferring Configuration of the Query Tab
You can transfer the configuration of the Query tab options of the InTouc h Alarm Viewer control to the ArchestrA Alarm Control.

InTouch option From Priority, To Priority Alarm State Query Type
Alarm Query

Alarm Control option
In the Arc hestrA Alarm Cont rol, you can only set the priority limits as part of a query filter on the Query Filters page. For more information, see "Filtering Alarms" on page 46.
In the Arc hestrA Alarm Cont rol, you can only set the alarm state limitation as part of a query filter on the Query Filters page. for more information, see "Filtering Alarms" on page 37.
In the ArchestrA Alarm Control, you can set the Client Mode option on the Alarm Mode page as follow:
 For query type "Summery", set the client mode to Current Alarms
 For query type "Historical", set the client mode to Recent Alarms and Events
In the ArchestrA Alarm Cont rol, you can configure t he Alarm Query option on the Alarm Mode page.

Query Favorites File, Edit Query Favorites

In the Arc hestrA Alarm Cont rol, all query favorites and filter favorites are managed on one page and are interchangeable between different client modes. To access the Query Filter Favorites, open the Query Filters page.

154

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

InTouch option Sort Column

Alarm Control option
In the Arc hestrA Alarm Cont rol, you can configure the sorting of alarm records on the Column Details page.

Auto Scroll to New In the Arc hestrA Alarm Cont rol, you can configure the Auto Scroll

Alarms

to New Alarms on the Run-Time Behavior page.

Secondary Sort Column, Sort Direction

In the Arc hestrA Alarm Cont rol, you can configure the sorting of alarm records on the Column Details page.

Transferring Configuration of the Properties Tab
You can set the properties of the ArchestrA Alarm Control in the Properties Editor when the Alarm Cont rol is selected on the canvas.

For more information on the exact mapping between the InTouch Alarm Viewer control properties and ArchestrA Alarm Control properties, see Mapping Properties and Methods on page 164.
The advanced property filtering feature does not exist in the ArchestrA Alarm Cont rol. However, when you browse for properties of the ArchestrA Alarm Control from other elements with the Galaxy Browser, you can filter the properties. Also, the properties of the ArchestrA Alarm Control are logically grouped in the Properties Editor.

Transferring Script Configuration on the Events Tab

You can configure scripts for events of the ArchestrA Alarm Control on the Event animation page. The events are the same as the events for the InTouch Alarm Viewer Control:

 Click

 Shutdown

 DoubleClick

 StartUp

 New Alarm

155

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

Transferring the InTouch Alarm DB View Control Configuration
You can transfer the configuration of the InTouch Alarm DB View control tabs options to the ArchestrA Alarm Control.
Transferring Configuration of the Alarm DB View Control Name Tab
You can transfer the configuration of the Control Name tab options of the InTouch Alarm DB View control to the ArchestrA Alarm Control.

InTouch option Cont rolName
Left, Top, Width, and Height Visible

Alarm Control option
You can rename the ArchestrA Alarm Control the same way as any other elements on the canvas. For more information, see the Creating and Managing Industrial Graphics User's Guide.
You can directly edit the positioning options in the same way as any other element on the canvas. Edit the following properties in the Properties Editor: X, Y, Width, and Height.
You can directly edit the visibility option in the same way as any other element on the canvas. In the Properties Editor, edit the Visible property.

GUID

This option has no meaning in the ArchestrA Alarm Control.

156

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

Transferring Configuration of the InTouch Alarm DB View General Tab
You can transfer the configuration of the General tab options of the InTouch Alarm DB View control to the ArchestrA Alarm Control.

InTouch option Alarm Control option

Enable Refresh Menu

In the Arc hestrA Alarm Cont rol, you can configure the availability of the Requery shortcut menu option on the Run-Time Behavior page.

Enable Sort Menu In the Arc hestrA Alarm Cont rol, you can configure the availability of the Sort shortcut menu option on the Run-Time Behavior page.

Enabled Reset Menu

In the Arc hestrA Alarm Cont rol, you can configure the availability of the Reset shortcut menu option on the Run-Time Behavior page.

Enabled Filter Menu In the Arc hestrA Alarm Cont rol, you can configure the availability of the Query Filters shortcut menu option on the Run-Time Behavior page.

Display Mode
Column Details Show Grid Show Heading

In the ArchestrA Alarm Control, set the Client Mode on the Alarm Mode page to the same setting as the Di splay Mode setting in the InTouch Alarm DB View control.
In the Arc hestrA Alarm Cont rol, you can configure the column details directly on the Column Details page.
In the ArchestrA Alarm Control, you can configure the Show Grid option on the Run-Time Behavior page.
In the Arc hestrA Alarm Cont rol, you can configure the Show Heading option on the Run-Time Behavior page.

157

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

InTouch option Row Selection Resize Column Show Status Bar Retrieve Buttons
Silent Mode Font
Show Message

Alarm Control option
In the ArchestrA Alarm Control, this option is called Row Selection. You can configure it on the Run-Time Behavior page.
In the Arc hestrA Alarm Cont rol, this option is called Allow Column Resizing. You can configure it on the Run-Time Behavior page.
In the ArchestrA Alarm Control, you can configure the Show Status Bar option on the Run-Time Behavior page.
In the Arc hestrA Alarm Cont rol, the ret rieve buttons are not available. The underlying grid technology handles the alarm retrieval from the alarm database.
In the Arc hestrA Alarm Cont rol, this option is called Hide Errors and Warnings. You can configure it on the Run-Time Behavior page.
You can configure this option from the Industrial Graphic Editor page. Select the ArchestrA Alarm Control on the canvas and select an appropriate font type, size, and style on the menu bars.
In the Arc hestrA Alarm Cont rol, this option is called Show Custom `No Records' Me ssage. You can configure it on the Run-Time Behavior page.

Transferring Configuration of the InTouch Alarm DB View Color Tab
You can transfer the configuration of the Color tab options of the InTouch Alarm DB View cont rol to the ArchestrA Alarm Control.

All the options of the Color tab in the InTouch Alarm DB View control can be set on the Colors page of the ArchestrA Alarm Control.
158

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

The following table shows you some minor differences in wording:

InTouch Alarm DB View control

Arche strA Alarm Control

Forec olor

Text

Backcolor

Background

Alm

n/a

Return

RTN

You can set the alarm priority range breakpoints directly in the table in the From Pri column.

Transferring Configuration of the Database Tab
You can trans fer the configuration of the Database tab options of the InTouch Alarm DB View control to the ArchestrA Alarm Control.

In the Arc hestrA Alarm Cont rol, you can configure the following options on the Alarm Mode page:

 Server Name

 Database Name

 User

 Password

 Test Connection

In the ArchestrA Alarm Control, the Auto Connect option is called Query on Startup. You can configure it on the Run-Time Behavior page.

The configuration for the Alarm Database only appears if the Client Mode is set to Historical Alarms, Hi storical Events, or Hi storical Alarms and Events.

159

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

Transferring Configuration of the Selection Tab
You can trans fer the configuration of the Selection tab options of the InTouch Alarm DB View control to the ArchestrA Alarm Control.

InTouch option

Alarm Control option

Use Specific Time, Start Time, End Time
Duration
UnAck Duration, Alarm Duration

In the Arc hestrA Alarm Cont rol, you can set these options directly in the Time Range Picker control on the Alarm Mode page.
When you select a time from either the start time or end time part of the Time Range Picker control, the Alarm Control is automatically set to use a specific time.
To keep the specific start and end time, you must also clear Update to Current Time. When you refresh the Alarm Control grid at run time, the time range stays fixed to the given start and end time.
In the Arc hestrA Alarm Cont rol, you can set this option directly in the Time Range Picker control on the Alarm Mode page.
When you select a duration from t he cent er part of the Time Range Picker control, the Alarm Control is automatically set to use a time offset.
To keep the duration, you must also select the Update to Current Time check box. When you refresh the Alarm Control grid at run time, the end time is set to the current time and the Alarm Control shows the alarms within the set duration.
In the Arc hestrA Alarm Cont rol, you cannot configure the Unack Duration and Alarm Duration settings. The Alarm Control grid shows both UnAck Duration and Alarm Duration in separate

160

Transferring Alarm Configuration from InTouch

InTouch option

Alarm Control option columns.

AVEVATM ArchestrA Alarm Control Guide

Query Time Zone Maximum Records

In the Arc hestrA Alarm Cont rol, you can configure the Time Zone setting on the Time Settings page.
In the Arc hestrA Alarm Cont rol, you can configure the Maximum Records setting on the Alarm Mode page.

Transferring Configuration of the Time/Sort Tab
You can trans fer the configuration of the Time/Sort tab options of the InTouch Alarm DB View control to the ArchestrA Alarm Control.

InTouch option Alarm Control option

Time Format

In the Arc hestrA Alarm Cont rol, you can configure the Time Format setting on the Time Settings page.

Displayed Time Zone

In the ArchestrA Alarm Control, you can configure the Time Zone setting on the Time Settings page.

Primary Sort Column, Secondary Sort Column, Sort Order

In the Arc hestrA Alarm Cont rol, you can configure the sorting options on the Column Details page.

161

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

Transferring Configuration of the Query Filter Tab
You can trans fer the configuration of the Query Filter tab options of the InTouch Alarm DB View control to the ArchestrA Alarm Cont rol.

In the ArchestrA Alarm Control, all query favorites and filter favorites are managed on one page and are interchangeable bet ween different client modes. To access the Query Filter Favorites, open the Query Filters page.

162

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

Transferring Configuration of the InTouch Alarm DB View Properties Tab
You can set the properties of the ArchestrA Alarm Control in the Properties Editor when the Alarm Cont rol is selected on the canvas.

For more information on the exact mapping between the InTouch Alarm DB View control properties and ArchestrA Alarm Control properties, see Mapping Properties and Methods on page 164.
The advanced property filtering feature does not exist in the ArchestrA Alarm Cont rol. However, when you browse for properties of the ArchestrA Alarm Control from other elements with the Galaxy Browser, you can filter the properties. Also, the properties of the ArchestrA Alarm Cont rol are logically grouped in the Properties Editor.

Transferring Scripts Configuration on the Events Tab

You can configure scripts for events of the ArchestrA Alarm Control on the Event animation page. The events are the same as the events for the InTouch Alarm DB View control:

 Click

 Shutdown

 DoubleClick

 StartUp

 NewAlarm

For more information, see Configuring Events on page 144.

Transferring Query Favorites Configuration

You can only transfer query favorit es configuration from InTouch to the ArchestrA Alarm Control by recreating the filters on the Query Filters page.
If you intend to use a the query filter in one of the current client modes, make sure you also include Provider and Group as filter criteria.

163

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

Mapping Properties and Methods
The following table shows all properties and methods of the InTouch Alarm Viewer control and InTouch Alarm DB View controls and their corresponding properties and methods of the ArchestrA Alarm Control.

InTouch alarm control property

or method

Arche strA Alarm Control property or method

AboutBox()
AckAll()
AckAllMenu AckAlmBackColor AckAlmBackColorRange1 AckAlmBackColorRange2 AckAlmBackColorRange3
AckAlmBackColorRange4 AckAlmColorRange1 AckAlmColorRange2 AckAlmColorRange3 AckAlmColorRange4
AckAlmForeColor AckAlmForeColorRange1 AckAlmForeColorRange2 AckAlmForeColorRange3
AckAlmForeColorRange4 AckGroup() AckOthersMenu AckPriority() AckRtnBackColor AckRtnFore Col or AckSelected() AckSelectedGroup() AckSelectedGroupsMenu AckSelectedMenu AckSelectedPrioritiesM enu AckSelectedPriority()

AboutBox() Method on page 117
Ack .All() Method on page 117
Cont ext Menu.Ack All Property on page 86 AlarmColor.Ack.Back Ground Propert y on page 77 AlarmColor.Ack.Back Ground Propert on page 77 AlarmColor.Ack.Back Ground Propert y on page 77 AlarmColor.Ack.Back Ground Propert y on page 77
AlarmColor.Ack.Back Ground Propert y on page 77 AlarmColor.Ack.ForeGround Property on page 77 AlarmColor.Ack.ForeGround Property on page 77 AlarmColor.Ack.ForeGround Property on page 77 AlarmColor.Ack.ForeGround Property on page 77
AlarmColor.Ack.ForeGround Property on page 77 AlarmColor.Ack.ForeGround Property on page 77 AlarmColor.Ack.ForeGround Property on page 77 AlarmColor.Ack.ForeGround Property on page 77
AlarmColor.Ack.ForeGround Property on page 77 Ack .Group() Method on page 117 Cont ext Menu.Ack Others Property on page 87 Ack .Priority() Method on page 117 AlarmColor.RTN.Back Ground Propert y on page 80 AlarmColor.RTN.ForeGround P ropert y on page 80 Ack .Selected() Method on page 118 Ack .SelectedGroup() Method on page 118 Cont ext Menu.Ack SelectedGroups Property on page 87 Cont ext Menu.Ack Selected Property on page 87 Cont ext Menu.Ack SelectedPriorities Property on page 87 Ack .SelectedPriority () Method on page 118

164

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

InTouch alarm control property

or method

Arche strA Alarm Control property or method

AckSelectedTag() AckSelectedTagsMenu AckTag() AckVisible() AckVisibleMenu AlarmQuery AlarmState
AlmRtnBackCol or AlmRtnColor AlmRtnFo re Col or ApplyDefaultQuery() ApplyQuery()
AutoConnect AutoScroll

Ack .SelectedTag() Method on page 119
Cont ext Menu.Ack SelectedTags Property on page 87 Ack .Tag() Method on page 119 Ack .Visible() Method on page 119 Cont ext Menu.Ack Visible Propert y on page 88 AlarmQuery Property on page 85
No corresponding property. Configure a Query Filter favorite at design time instead and use the Favorit e property. For more information, see Favorite Property on page 100 AlarmColor.RTN.Back Ground Propert y on page 80 AlarmColor.RTN.ForeGround P ropert y on page 80 AlarmColor.RTN.ForeGround P ropert y on page 80
Favorite Property on page 100
No corresponding property. Configure a Query Filter favorite at design time instead and use the Favorit e property. For more information, see Favorite Property on page 100. QueryStartup Property on page 104
AutoScroll Property on page 85

Colo rPri orityRa ng e1 Colo rPri orityRa ng e2 Colo rPri orityRa ng e3 ColumnResize Connect()
ConnectStatus CustomMessage DefaultAckComment DisplayedTime

AlarmColor.Range Propert y on page 79 AlarmColor.Range Propert y on page 79 AlarmColor.Range Propert y on page 79 AllowColumnResize Propert y on page 85
Connect() Method on page 120
ConnectStatus Propert y on page 86 NoRecords Message. Message Propert y on page 103 Ack Comment.DefaultValue Property on page 75
This option has no meaning in the ArchestrA Alarm Cont rol. All three times are shown in the Alarm Control: Original Alarm Time Last Changed Time Last Changed Time, but Original Alarm Time for unacknowledged alarms

DisplayedTimeZone

TimeZone.TimeZone Property on page 114

165

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

InTouch alarm control property

or method

Arche strA Alarm Control property or method

DisplayMode Duration EndTime E ventBackColor E vent Color E ventForeColor ExtendedS election FilterFavoritesFile
FilterMenu FilterName FlashUnackAlarms FlashUnAckAlmColorRange1 FlashUnAckAlmColorRange2 FlashUnAckAlmColorRange3 FlashUnAckAlmColorRange4 Font Freez eDisplay() Freez eMenu FromPri ority
GetItem () GetLastError() GetNext()
GetPrevious()

Client Mode P ropert y on page 86
TimeSelector.TimeDuration Property page 112 TimeSelector.EndDate Property on page 111
Event Color.Back Ground Property on page 99
Event Color.ForeGround Propert y on page 99
Event Color.ForeGround Propert y on page 99
RowSelection Propert y on page 105
No corresponding property. The file name is used as a parameter for the Favorites.Export() Method on page 120 and Favorites.Import() Met hod on page 120 methods.
Cont ext Menu.Favorites Property on page 88
Favorite Property on page 100
FlashUnAck Alarms Propert y on page 100
AlarmColor.UnAck .Flash.ForeGround Propert y on page 82 AlarmColor.UnAck .Flash.ForeGround Propert y on page 82 AlarmColor.UnAck .Flash.ForeGround Propert y on page 82 AlarmColor.UnAck .Flash.ForeGround Propert y on page 82 You can only set the font at design time, not at run time.
Freez eDisplay() Met hod on page 121
Cont ext Menu.Freez e Propert y on page 88
No corresponding property. Configure a Query Filter favorite at design time instead and use the Favorit e property. For more information, see Favorite Property on page 100. GetItem() Method on page 121
GetLastError() Met hod on page 121
No corresponding property. Alarm records are retrieved one by one from t he Alarm Database after the initial set of alarm records is retrieved. The initial set is defined by the Maximum Records setting. No corresponding property. Alarm records are retrieved one by one from t he Alarm Database after the initial set of alarm records is retrieved. The initial set is defined by the

166

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

InTouch alarm control property

or method

Arche strA Alarm Control property or method

Maximum Records setting.

GetSelected Item () Grid Col or GroupExactMatch
Gro up Nam e
MaxRecords MoveWindow() NewAlarmE ventMode Password PrimarySort Pro vi de rExactMatch
Pro vi de rN ame
QueryFavorit esFile
QueryFavorit esMenu Que ryNam e QueryStartup Que ryTi me Zone QueryTy pe Refresh() RefreshMenu Requery() RequeryMenu

GetSelectedItem() Met hod on page 122
GridColor Property on page 100 No corresponding property. Configure a Query Filter favorite at design time instead and use the Favorit e property. For more information, see Favorite Property on page 100. No corresponding property. Configure a Que ry Filter favorite at design time instead and use the Favorit e property. For more information, see Favorite Property on page 100. MaxDatabaseRecords Property
MoveWindow() Method on page 125 NewAlarmEvent Mode Property on page 102 Database.Authentication Property on page 97 SortOrder.First Property on page 108
No corresponding property. Configure a Query Filter favorite at design time instead and use the Favorit e property. For more information, see Favorite Property on page 100. No corresponding property. Configure a Query Filter favorite at design time instead and use the Favorit e property. For more information, see Favorite Property on page 100. No corresponding property. The file name is used as a parameter for the Favorites.Export() Method on page 120 and Favorites.Import() Met hod on page 120 methods.
Cont ext Menu.Favorites Property on page 88 Favorite Property on page 100
QueryStartup Property on page 104 TimeZone.TimeZone Property on page 114 Client Mode P ropert y on page 86
Requery() Method on page 125 Cont ext Menu. Requery P ropert y on page 90 Requery() Method on page 125
Cont ext Menu. Requery P ropert y on page 90
167

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

InTouch alarm control property

or method

Arche strA Alarm Control property or method

Reset() ResetMenu Retai nSup pr ession RowCount RowSelection SecondarySort Second arySo rtCol umn SelectAll()
SelectedCount SelectGroup() SelectItem()
SelectPriority()

Reset() Method on page 126 Cont ext Menu. Reset Property on page 90 RetainHidden Property on page 104
RowCount Property on page 105
RowSelection Propert y on page 105 SortColumn.Sec ond Propert y on page 108
SortColumn.Sec ond Propert y on page 108
To select all records, see Select.All() Method on page 127. To reverse the selection of all records, see Toggle.All() Method on page 138. SelectedCount Propert y on page 105
Select.Group() Method on page 127
To select a given alarm record, see Select.Item() Method on page 127. To reverse the selection of a given alarm record, see Toggle.Item() Method on page 138. Select.Priority() Met hod on page 127

SelectQuery() SelectTag() Ser ver Nam e SetQue ryByNam e

Favorite Property on page 100 Select.Tag() Method on page 128 Database.ServerName Propert y on page 98 Favorite Property on page 100

SetSort() ShowContext()

SetSort() Method on page 128 Show. Context() Method on page 136

ShowContextMenu ShowDat e ShowFetch
ShowFilter() Show Gri d

ShowContextMenu Propert y on page 107
There is no equivalent functionality in the ArchestrA Alarm Control. No corresponding property. The buttons for retrieving sets of alarm records from the Alarm Dat abas e do not exist in the ArchestrA Alarm Control.
Show.Favorite() Met hod on page 136
ShowGrid Propert y on page 107

Show He adi ng

ShowHeading Property on page 107

168

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

InTouch alarm control property

or method

Arche strA Alarm Control property or method

ShowM essage ShowQueryFavorites() ShowS ort() ShowStatistics() ShowStat usBar ShowS uppression() SilentMode SortColumn
SortMenu

NoRecords Message.Enabled Propert y on page 103 Show.Favorite() Met hod on page 136 Show.Sort() Method on page 136
Show.Statistics() Method on page 137 ShowStat usBar Property on page 107 Show. Hidden() Met hod on page 136 HideE rrors Propert y on page 102
You can set three sort columns in the ArchestrA Alarm Cont rol. To set the first column, see SortColumn.First Property on page 107.
Cont ext Menu.Sort Propert y on page 93

SortOn Col ()

To set the first sort column, see SortColumn.First Property on page 107. To set the sort order of the first sort column, see SortOrder.First Property on page 108.

SortOrder Specific Time StartTim e

SortOrder.First Property on page 108 UpdateToCurrentTime Propert y on page 115 TimeSelector.EndDate Property on page 111

StatsMenu SuppressAll() SuppressAllMenu

Cont ext Menu.Statistics Propert y on page 94 Hide.All() Method on page 122 Cont ext Menu. HideAll Property on page 88

SuppressedAlarms SuppressGroup() Supp ressionM en u

HiddenAlarms Property on page 102 Hide. Group() Method on page 122 Cont ext Menu. Hidden Property on page 88

SuppressOthersMenu

Cont ext Menu. HideOthers Propert y on page 89

SuppressPriority()

Hide.Priorit y() Method on page 123

SuppressSelected() SuppressSelectedGroup()

Hide.Selected() Method on page 123 Hide.SelectedGroup() Method on page 123

SuppressSelectedGroupsMenu Cont ext Menu. HideS electedGroups Property on page 89

Supp ressSelectedM en u

Cont ext Menu. HideS elected Propert y on page 89

SuppressSelectedP rioritiesMenu Cont ext Menu. HideS electedP riorities Property on page 89

SuppressSelectedP riority()

Hide.SelectedPriorit y() Method on page 123

169

AVEVATM ArchestrA Alarm Control Guide

Transferring Alarm Configuration from InTouch

InTouch alarm control property

or method

Arche strA Alarm Control property or method

SuppressSelectedTagsMenu SuppressSelectedTag() Suppress Tag() SuppressVisible() SuppressVisibleMenu Tim e
Tim eFo rmat
TitleB ackColor TitleF or eC olo r ToPriority
TotalAlarms TotalRowCount UnAckAlarms UnAckAlmBackColor UnAckAlmBackColorRange1 UnAckAlmBackColorRange2 UnAckAlmBackColorRange3 UnAckAlmBackColorRange4 UnAckAlmCol or Ra nge 1 UnAckAlmCol or Ra nge 2 UnAckAlmCol or Ra nge 3 UnAckAlmCol or Ra nge 4 UnAckAlmForeColor UnAckAlmForeColorRange1 UnAckAlmForeColorRange2 UnAckAlmForeColorRange3 UnAckAlmForeColorRange4 UnAckOrAla rm Dur ation
UnSel ectAll()

Cont ext Menu. HideS electedTags Property on page 90 Hide.SelectedTag() Method on page 123 Hide.Tag() Method on page 124 Hide.Visible() Method on page 124
Cont ext Menu. HideVisible Property on page 90
Time.Type Property on page 110 and Time.Format Property on page 110 Time.Format Propert y on page 110 and Time.Type Property on page 110 HeadingColor.Back Ground Propert y on page 101 HeadingColor.ForeGround Property on page 101
No corresponding property. Configure a Query Filter favorite at design time instead and use the Favorit e Property. For more information, see Favorit e Propert y on page 100. TotalRowCount Property on page 114 TotalRowCount Property on page 114 UnAck Alarms Property on page 114 AlarmColor.UnAck .Back Ground Propert y on page 81
AlarmColor.UnAck .Back Ground Propert y on page 81 AlarmColor.UnAck .Back Ground Propert y on page 81 AlarmColor.UnAck .Back Ground Propert y on page 81 AlarmColor.UnAck .Back Ground Propert y on page 81 AlarmColor.UnAck .ForeGround Property on page 83 AlarmColor.UnAck .ForeGround Property on page 83 AlarmColor.UnAck .ForeGround Property on page 83
AlarmColor.UnAck .ForeGround Property on page 83 AlarmColor.UnAck .ForeGround Property on page 83 AlarmColor.UnAck .ForeGround Property on page 83 AlarmColor.UnAck .ForeGround Property on page 83 AlarmColor.UnAck .ForeGround Property on page 83 AlarmColor.UnAck .ForeGround Property on page 83
No corresponding property. UnAck Duration and Alarm Duration are shown in the Alarm Control grid. UnSelectAll() Method on page 138

170

Transferring Alarm Configuration from InTouch

AVEVATM ArchestrA Alarm Control Guide

InTouch alarm control property

or method

Arche strA Alarm Control property or method

UnSuppressAll() UnsuppressAllMenu UseD efaultAckCom ment UserID Visible W indow Col or

UnhideAll() Method on page 138 Cont ext Menu. UnhideAll Property on page 94 Ack Comment.UseDefault Propert y on page 75 Database.Us erID Property on page 98 Visible Property on page 115 WindowColor Property on page 116

171

AVEVATM ArchestrA Alarm Control Guide

Index
A
alarm manager � 11 Alarms at run-time, Sorting � 58 alarms, historical � 11
C
Cont extMenu.ShelveAll � 90 Cont extMenu.ShelveOthers � 90 Cont extMenu.ShelveSelected � 91 Cont extMenu.ShelveSelectedGroups � 92 Cont extMenu.ShelveSelectedPriorities � 92 Cont extMenu.ShelveSelectedSeverities � 92 Cont extMenu.ShelveSelectedTags � 93 Cont extMenu.ShelveVisible � 93 Cont extMenu. UnshelveAll � 94 Cont extMenu. UnshelveOthers � 94 Cont extMenu. UnshelveSelected � 95 Cont extMenu. UnshelveSelectedGroups � 95 Cont extMenu. UnshelveSelectedPriorities � 96 Cont extMenu. UnshelveSelectedSeverities � 96 Cont extMenu. UnshelveSelectedTags � 96 Cont extMenu. UnshelveVisible � 97
E
events historical � 11
H
historical alarms � 11 historical events � 11
R
RequiresShelveSignature � 104 run-time
sorting alarms � 58

S
Shelve.SelectedS everity � 133 Shelve.SelectedTag � 134 Shelve.Severity � 134 Shelve. Tag � 135 Shelve.Visible � 136 ShelveColor.Backgroun � 106 ShelveColor.Foreground � 106 shel vi ng
description � 15
during run time � 15, 60
setting colors � 28
U
Unshelve.All � 138 Unshelve.Group � 139 Unshelve.Priority � 139 Unshelve.Selected � 140 Unshelve.SelectedGroup � 141 Unshelve.SelectedP riority � 141 Unshelve.SelectedS everity � 141 Unshelve.SelectedTag � 142 Unshelve.Severity � 142 Unshelve.Tag � 143 Unshelve.Visible. � 144 unshel vin g
during run time � 16

173