DBC Commercial - Daikin Comfort

9 Product Specifications ... Note: Always check the S&R plate for electrical data on the unit being ... 315. 24CURB180300. 24" Roof Curb. 15-25 tons.

PDF SS-DBC15
DBC Commercial

*AC model pictured above

Base Efficiency AC Packaged Rooftop Unit
DBC Commercial 15-25 Nominal Tons
UP TO 12.8 IEER / 11 EER

SS-DBC15

* Complete warranty details available from your local distributor or manufacturer's representative or at www.daikincomfort.com or www.daikinac.com

www.daikinac.com

04/21
Supersedes 03/21

Our Perfect Package:
Harnessing energy-efficient performance, proven technology, and enhanced comfort for life.
Since becoming the first company in Japan to manufacture packaged air conditioning systems, in 1951, Daikin has supported comfortable indoor living based on the strengths and technologies that have led to the growth of the company becoming one of the world's largest manufacturers of HVAC products, systems and refrigerants.
Today, as a comprehensive global manufacturer of HVAC products and systems, the Daikin brand is committed to being recognized as a truly global and excellent company capable of continually creating new value for its customers. The company plans to pursue sustainable growth and foster business operations that consistently harmonize with the goals of improving indoor comfort.
The group philosophy of the company includes: » Creating new value continuously for customers » Developing world leading energy-saving technology » Being a flexible and dynamic organization » Allowing employees to be the driving force
for the success of the company » Fostering an atmosphere of best practices,
boldness, and innovation » Thinking and acting globally

Contents

2 Introduction

2

4 Nomenclature

4

5 Features and Benefits

5

Applications

8

Serviceability

8

9 Product Specifications

9

Coil Dimensions

11

12 Expanded Cooling Data

12

18 Air Flow Data

18

20 Electrical Data

20

23 Electric Heat

23

24 Wiring Diagrams

24

31 Dimensional Data

31

33 Unit Clearances

33

34 Installation

34

Weights

34

35 Accessories

35

38 Factory Installed Options

38

38 Field Installed Options

38

39 Factory or Field Installed Options

39

3

Nomenclature

D

B

G 300 3 V 400 C S A X X X X X X X

X

A*

1

2

3 4,5,6 7 8 9,10,11 12 13 14 15 16 17 18 19 20 21 22 23 24

Brand D Daikin
Configuration B New Base Efficiency (3- 25 Ton)

Revision Levels Major & Minor

Application C Cooling G Gas Heat
Nominal Cooling Capacity 180 15 Tons 240 20 Tons 300 25 Tons

Voltage 3 208-230/3/60 4 460/3/60

7 575/3/60

Supply Fan/Drive Type/Motor V 2-speed Belt-Drive- Standard Static S 2-speed Belt-Drive- High-Static

Nominal Heating Capacity Gas/Electric 350 350,000 BTU/h 400 400,000 BTU/h

A/C Factory-Installed Electric Heat
XXX No Heat 031 30 kW 046 45 kW 060 60 kW 075 75kW

X No Options

X No Options

X No Options

Service Options
X No Option A Powered convenience outlet B Non-powered convenience outlet C Hinge Panels D Hinged Panels and Powered convenience outlet E Hinged Panels and non-powered convenience outlet

X No Option
A Non-Fused Disconnect B Phase Monitor E Non-Fused Disconnect and Phase Monitor

Electrical

See product specifications for heat size(s) available for each capacity.
Refrigeration Systems C Two-stage cooling modes H Two-stage cooling mode with Low-ambient controller

Heat Exchanger
X No options A Standard Aluminized Exchanger S Stainless Steel Exchanger

Controls A Electromechanical controls B DDC w/ BACnetTM interface

AC Stocking Models

New Daikin 15 ­ 25 Ton

Model Number

Code String

DBC1803V000001S

DBC1803VXXXCXAXXXXXXXX

DBC1804V000001S

DBC1804VXXXCXAXXXXXXXX

DBC1807V000001S

DBC1807VXXXCXAXXXXXXXX

DBC2403V000001S

DBC2403VXXXCXAXXXXXXXX

DBC2404V000001S

DBC2404VXXXCXAXXXXXXXX

DBC2407V000001S

DBC2407VXXXCXAXXXXXXXX

DBC3003V000001S

DBC3003VXXXCXAXXXXXXXX

DBC3004V000001S

DBC3004VXXXCXAXXXXXXXX

DBC3007V000001S

DBC3007VXXXCXAXXXXXXXX

4

Economizer
X No Options B Low-Leak Downflow Economizer w/ Enthalpy Sensor N Low-Leak Downflow Economizer for DDC controls w/ Enthalpy Sensor P Low-Leak Downflow Economizer for DDC controls w/ Dry Bulb Sensor

X No Options
X No Options A RA Smoke Detector B SA Smoke Detector C RA & SA Smoke Detector
www.daikinac.com

Sensors
SS-DBC15

Features and Benefits

Daikin Packaged Rooftop Units (RTUs) are built to perform, with features and options that help provide low installation and operation costs, superior indoor air quality, efficient operation, and longevity.

Installation
Daikin Packaged units are designed with fast and easy installation in mind and are ideal for both new construction and retrofit projects. Our packaged rooftop units are built to be a direct replacement for most rooftop units on the field without the need of a curb adapter, to be able to replace the unit in a shorter time and at a lower cost (compared to the previous design).
Cabinet Construction
Daikin packaged rooftop units are made with high quality galvanized steel with a powder-paint finish to provide higher corrosion resistance.
» The interior surface in the indoor air section is fully insulated to prevent sweating and thermal losses, using our foil face fiberglass insulation which also omits exposed filter fibers into the airstream.
» The full perimeter base rail is built using heavy gauge galvanized steel for a stronger structural installation. The base rails are a minimum of 3 ½" tall and include holes to allow for overhead rigging and lifting with forklifts.
» Condenser hail guards are factory installed as a standard.

Compressor
High performance, low noise scroll compressors with stage control to match the required total load for efficient part load control.
» Resiliently factory-mounted on rubber grommets for vibration isolation.
» Refrigeration circuit includes both a low- and high-pressure transducer, high pressure safety switch and temperature sensors for the suction and discharge lines.
» Unit is factory charged with environmental friendly and sustainable R-410A refrigerant.
» Dual single-stage scroll compressors.
» Compressor location outside the condenser section to avoid air bypass.
» Internal overload protection included with compressor.
» Crankcase heaters and external thermal overload protection are also provided for compressor durability.
Supply Fan
Indoor fan motors are belt-drive as standard to provide easy in the field belt and pulley adjustment for airflow control.
» Slide out forward curb fan for easy maintenance and replacement.
» High-static drive options for applications with high airflow/ static requirements.
» Each fan assembly is dynamically trim balanced at the factory before shipment for quick start-up and efficient operation.
» Motor with thermal overload and phase failure protection is provided for long lasting operation.

Coils
All units use large face area outdoor coils. These coils are constructed with seamless copper tubes, mechanically bonded into aluminum plate-type fins with full drawn collars to completely cover the tubes for high operating efficiencies.

The indoor coil section is installed in a draw through configuration to provide better dehumidification.
» Coils are factory pressure tested to ensure pressure and leak integrity.
» Coils include a Thermal Expansion Valve per circuit, high- and low pressure switches, service ports and high capacity filter drier.
» Aluminum micro-channel indoor coil on 25-ton units

SS-DBC15

www.daikinac.com

5

Features and Benefits

» Low Ambient cooling operation down to 35°F outside air temp as standard, with option to perform down to 0°F when selected with low ambient kit.
» 5mm Smart Coil Technology on all condenser coils for improved performance and reduced refrigerant load.
Controls and Wiring
Packaged rooftop units come equipped with a well-organized, large, easy to use, weatherproof internal control box with easy access, for a better user experience.
» Units are factory-wired with labeled color-coded wires and complete 24-volt Electromechanical controls package.
» Units include single-point power entry as standard and also available with electric heat kits if selected.
» Terminal blocks are provided as standard for easy installation and field power wiring.
» The Daikin iLINQ Controller is a factory-installed solution to provide intelligent control for Daikin Light Commercial rooftop units* (RTUs). iLINQ provides physical inputs and outputs to control and monitor the RTU and features a graphic web interface for remote access (via a computer or tablet). Equipped with built-in BACnetTM IP and MS/TP interface or it can be used with an optional LonWorks® card that is available to integrate the Daikin RTU with building automation systems (BMS).
Filtration
Unit provides a draw-through filter section as standard for better air quality and long lasting component maintenance.
» Filters installed on the units are standard off the shelf sizes for easy replacement.
» One size filter per unit for low maintenance cost and easy replacement.
» 2" deep filters standard on all units with option for up to 4" on large chassis (15 tons and over).
» Easy and fast filter service access.
Heating Section
Wide range of electric heat selections effectively handle most comfort heating demand from morning warm-up control to full heat.

Electric Heat
ETL approved electric heat is factory assembled, installed and tested.
» Heating control is fully integrated into the unit's control system for quick start-up and reliable control.
» Multi-stage capability for application flexibility.
» Durable low watt density, nickel chromium elements provide longer life (compared to units without)..
» Fuses are provided in each branch circuit to a maximum of 48 Amps per NEC requirements.
» Single-point power connection reduces installation cost.
» For operational safeties electric heat includes automatic reset, and high temperature limit safety protection and an airflow safety switch to prevent electric heat operation in the event of no airflow.
Electrical
Units are completely wired and tested at the factory to provide faster commissioning and start-up.
» Wiring complies with NEC requirements and all applicable UL standards.
» For ease of use, wiring and electrical components are number coded and labeled according to the electrical diagram.
» A 115 V GFI convenience outlet requiring independent power supply for the receptacle is optional.
» An optional unit powered 20 amp 115 V convenience outlet, complete with factory mounted transformer, disconnect switch, and primary and secondary overload protection, eliminates the need to pull a separate 115 V power source.
» Supply air fan, compressor, and condenser fan motor branch circuits have individual short circuit protection. Unit includes knockouts in the bottom of the main control panels for field wiring entrance.
» A single-point power connection with power block is standard and a terminal board is provided for connecting low voltage control wiring.
» For better serviceability an optional non-fused disconnect switch is mounted inside the control panel and operated by an externally mounted handle to disconnect the electrical power at the unit.
» For operational safety, electric heat includes automatic reset, high temperature limit safety protection, and an airflow safety switch to prevent electric heat operation in the event of no airflow.

6

www.daikinac.com

SS-DBC15

*AC model pictured above

Applications & Serviceability
Applications
Daikin Rooftop units are intended for comfort cooling applications in normal heating, ventilating, and air conditioning. Consult your local Daikin sales representative for applications involving operations at high ambient temperatures, high altitudes, noncataloged voltages, or for job-specific unit selections that fall outside of the range of the catalog tables.
For proper operation, units should be rigged in accordance with instructions stated on the installation manual. Fire dampers, if required, must be installed in the ductwork according to local and/ or state codes. No space is allowed for these dampers in the unit.
Follow factory check, test and start procedures explicitly to achieve satisfactory start-up and operation.
Most rooftop applications take advantage of the significant energy savings provided with economizer operation. When an economizer system is used, mechanical refrigeration is typically not required below an ambient temperature of 50°F on most cases.
Serviceability
Daikin packaged rooftop units are built with serviceability in mind, designed to make future maintenance and service on the unit easy and accessible.
» Our packaged rooftop units offer a slide out blower to facilitate the access and removal of the fan.
» Independent compressor outside of the air bypass to eliminate component blockage and provide easy access.
» Color coded and continuously marked wire to identify point-to-point component connections.
» Condenser clean out from inside-out. » Easy access to control panel.

8

www.daikinac.com

SS-DBC15

Product Specifications

PHYSICAL DATA COOLING

Model

DBC1803V000001S DBC1804V000001S DBC1807V000001S

REFRIGERATION SYSTEM Total, BTU/h

180,000

180,000

180,000

Sensible BTU/h

134,600

134,600

134,600

EER / IEER

11 / 12.8

11 / 12.8

11 / 12.8

Decibels

88

88

88

AHRI Reference #s EVAPORATOR MOTOR COIL Motor Type (Belt-Drive)

6502018 2-Speed Belt

6502018 2-Speed Belt

6502018 2-Speed Belt

Indoor Nominal CFM

6,000

6,000

6,000

Indoor Motor FLA (Cooling)

9.1

4.3

3.5

Horsepower - RPM (Speed: Full / Low)

3.0 - 1,760/1,165

3.0 - 1,760/1,165

3.0 - 1,760/1,165

Metering Device

TXV

TXV

TXV

Filter Size (#)

20 x 25 x 2 (6)

20 x 25 x 2 (6)

20 x 25 x 2 (6)

Drain Size (NPT)

1"

1"

1"

R-410A Refrigerant Charge Cir #1 (oz)

186.2

186.2

186.2

R-410A Refrigerant Charge Cir #2 (oz)

170.8

170.8

170.8

Evaporator Coil Face Area (ft²)

20

20

20

Rows Deep / Fins per Inch BELT-DRIVE EVAP FAN DATA # of Wheels (D x W)

4 / 16 2 (15" x 12")

4 / 16 2 (15" x 12")

4 / 16 2 (15" x 12")

Motor Sheave

1VP50 x 1"

1VP50 x 1"

1VP50 x 1"

Blower Sheave

BK100 x 1³/"

BK100 x 1³/"

BK100 x 1³/"

Belt

BX44

BX44

BX44

CONDENSER FAN/COIL

Quantity of Condenser Fan Motors

3

3

3

Horsepower - RPM

 - 1,075

 - 1,075

 - 1,075

Fan Diameter / # Fan Blades

22 / 3

22 / 3

22 / 3

Outdoor Nominal CFM

9,000

9,000

9,000

Face Area (ft²)

53.3

53.3

53.3

Rows Deep / Fins per Inch COMPRESSOR Quantity / Type

2 / 27 2 / Scroll

2 / 27 2 / Scroll

2 / 27 2 / Scroll

Compressor RLA / LRA CIR. #1

25 / 164

12.2 / 100

9.0 / 78

Compressor RLA / LRA CIR. #2 ELECTRICAL DATA Voltage / Phase / Frequency Standard Max Static Outdoor Fan FLA / LRA Total Unit Amps Min. Circuit Ampacity¹ Max. Overcurrent Protection (amps)² Entrance Power Supply Entrance Control Voltage OPERATING WEIGHT (LBS.)
SHIPPING WEIGHT (LBS.) Ship Weight (lbs)

25 / 164
208/230-3-60 1.2
2.0/4.4 65.1
71.4 / 71.4 90 / 90 2" "
1965
2080

12.2 / 100
460-3-60 1.2
0.85 / 2.2 31.3 34.3 45 2" "
1965
2080

9.0 / 78
575-3-60 1.2
0.67/1.8 23.5 25.7 30 2" "
1965
2080

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.

15-Tons

SS-DBC15

www.daikinac.com

9

Product Specifications

PHYSICAL DATA COOLING

Model

DBC2403V000001S DBC2404V000001S DBC2407V000001S

REFRIGERATION SYSTEM Total, BTU/h

240,000

240,000

240,000

Sensible BTU/h

181,000

181,000

181,000

EER / IEER

10.0 / 11.6

10.0 / 11.6

10.0 / 11.6

Decibels

88

88

88

AHRI Reference #s EVAPORATOR MOTOR COIL Motor Type (Belt-Drive)

8813880 2-Speed Belt

8813880 2-Speed Belt

8813880 2-Speed Belt

Indoor Nominal CFM

7,000

7,000

7,000

Indoor Motor FLA (Cooling)

14

6.6

5.2

Horsepower - RPM (Speed: Full / Low)

5.0 - 1,775/1,185

5.0 - 1,775/1,185

5.0 - 1,775/1,185

Metering Device

TXV

TXV

TXV

Filter Size (#)

20 x 25 x 2 (6)

20 x 25 x 2 (6)

20 x 25 x 2 (6)

Drain Size (NPT)

1"

1"

1"

R-410A Refrigerant Charge Cir #s 1 & 2 (oz)

177 & 195 ozs.

177 & 195 ozs.

177 & 195 ozs.

Face Area (ft²)

20

20

20

Rows Deep / Fins per Inch BELT-DRIVE EVAP FAN DATA # of Wheels (D x W)

4 / 16 2 (15" x 15")

4 / 16 2 (15" x 15")

4 / 16 2 (15" x 15")

Motor Sheave

1VP60 x 1"

1VP60 x 1"

1VP60 x 1"

Blower Sheave

BK100 x 1/"

BK100 x 1/"

BK100 x 1/"

Belt

BX45

BX45

BX45

CONDENSER FAN/COIL

Quantity of Condenser Fan Motors

3

3

3

Horsepower - RPM

 - 1,075

 - 1,075

 - 1,075

Fan Diameter / # Fan Blades

22 / 3

22 / 3

22 / 3

Outdoor Nominal CFM

9,000

9,000

9,000

Face Area (ft²)

53.3

53.3

53.3

Rows Deep / Fins per Inch COMPRESSOR Quantity / Type

2 / 27 2 / Scroll

2 / 27 2 / Scroll

2 / 27 2 / Scroll

Compressor RLA / LRA CIR. #1

34.0 / 240.0

16.0 / 140.0

12.9 / 107.6

Compressor RLA / LRA CIR. #2 ELECTRICAL DATA Voltage / Phase / Frequency Outdoor Fan FLA / LRA Total Unit Amps Min. Circuit Ampacity¹ Max. Overcurrent Protection (amps)² Entrance Power Supply Entrance Control Voltage OPERATING WEIGHT (LBS.)
SHIPPING WEIGHT (LBS.) Ship Weight (lbs)

34.0 / 240.0
208/230-3-60 2.0 /4.4 88
96.4 / 96.4 125 / 125
2" "
2085
2202

16.0 / 140.0
460-3-60 0.85 / 2.2
41.2 43.5 50 2" "
2085
2202

12.9 / 107.6
575-3-60 0.67 / 1.8
33.0 35.0 45 2" "
2085
2202

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.

20-Tons

10

www.daikinac.com

SS-DBC15

Product Specifications

PHYSICAL DATA COOLING

Model

DBC3003V000001S DBC3004V000001S DBC3007V000001S

REFRIGERATION SYSTEM Total, BTU/h

290,000

290,000

290,000

Sensible BTU/h

196,000

196,000

196,000

EER / IEER

10.2 / 11.8

10.2 / 11.8

10.2 / 11.8

Decibels

92

92

92

AHRI Reference #s EVAPORATOR MOTOR COIL Motor Type (Belt-Drive)

8582013 2-speed Belt-Drive

8582013 2-speed Belt-Drive

8582013 2-speed Belt-Drive

Indoor Nominal CFM

8,200

8,200

8,200

Indoor Motor FLA (Cooling)

21

10.1

8.2

Horsepower - RPM (Speed: Full / Low)

7.5 - 1770/1175

7.5 - 1770/1175

7.5 - 1770/1175

Metering Device

TXV

TXV

TXV

Filter Size (#)

20 x 20 x 2 (8)

20 x 20 x 2 (8)

20 x 20 x 2 (8)

Drain Size (NPT)

1"

1"

1"

R-410A Refrigerant Charge Cir #s 1 & 2 (oz)

215 & 198 ozs.

215 & 198 ozs.

215 & 198 ozs.

Face Area (ft²)

17.2

17.2

17.2

Rows Deep / Fins per Inch BELT-DRIVE EVAP FAN DATA # of Wheels (D x W)

2 / 15 2 (15" x 15")

2 / 15 2 (15" x 15")

2 / 15 2 (15" x 15")

Motor Sheave

1VP60 x 1"

1VP60 x 1"

1VP60 x 1"

Blower Sheave

BK110 x 1/"

BK110 x 1/"

BK110 x 1/"

Belt

BX46

BX46

BX46

CONDENSER FAN/COIL

Quantity of Condenser Fan Motors

2

2

2

Horsepower - RPM

1 - 1145

1 - 1145

1 - 1145

Fan Diameter / # Fan Blades

30 / 2

30 / 2

30 / 2

Outdoor Nominal CFM

15,000

15,000

15,000

Face Area (ft²)

53.3

53.3

53.3

Rows Deep / Fins per Inch COMPRESSOR Quantity / Type

2 / 27 2 / Scroll

2 / 27 2 / Scroll

2 / 27 2 / Scroll

Compressor RLA / LRA CIR. #1

48.1 / 245

18.6 / 125

14.7 / 100

Compressor RLA / LRA CIR. #2 ELECTRICAL DATA Voltage / Phase / Frequency Outdoor Fan FLA / LRA Total Unit Amps Min. Circuit Ampacity¹ Max. Overcurrent Protection (amps)² Entrance Power Supply Entrance Control Voltage OPERATING WEIGHT (LBS.)
SHIPPING WEIGHT (LBS.) Ship Weight (lbs)

48.1 / 245
208/230-3-60 3.7 / 16.9 125 133 / 133 175 / 175 2" "
2119
2387

18.6 / 125
460-3-60 1.85 / 8.5
51.0 53.8 70 2" "
2119
2387

14.7 / 100
575-3-60 1.5 / 6.82
40.6 42.9 50 2" "
2119
2387

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.

Coil Dimensions

Model DBC

Size 15 (top) 15 (bottom) 20 (top) 20 (bottom) 25 (Micro1) 25 (Micro2)

Fin height in. 20 20 20 20 38 38

Fin length in. 72 72 72 72
32.64 32.64

SS-DBC15

www.daikinac.com

25-Tons
11

Expanded Cooling Data

12

Outdoor Ambient Temperature

65

75

85

95

105

115

Entering Indoor Wet Bulb Temperature

IDB

Airflow

59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71

MBh 176.4 182.8 200.3 - 172.3 178.6 195.6 - 168.2 174.3 191.0 - 164.1 170.1 186.3 - 155.9 161.6 177.0 - 144.4 149.7 164.0 S/T 0.75 0.63 0.43 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.82 0.69 0.48 - 0.86 0.71 0.49 - 0.86 0.72 0.50 -

6750 T 18 16 12

-

18 16 12

-

18 16 12

-

18 16 12

-

18 16 12

-

17 15 11

-

HI PR 236 253 268 - 264 284 300 - 301 323 342 - 342 368 389 - 385 414 438 - 425 458 484 LO PR 103 110 120 - 109 116 127 - 114 121 132 - 119 127 139 - 125 133 145 - 129 138 150 -

MBh 171.2 177.5 194.5 - 167.3 173.4 189.9 - 163.3 169.2 185.4 - 159.3 165.1 180.9 - 151.3 156.9 171.9 - 140.2 145.3 159.2 -

S/T 0.72 0.60 0.41 - 0.74 0.62 0.43 - 0.76 0.64 0.44 - 0.79 0.66 0.45 - 0.82 0.68 0.47 - 0.82 0.69 0.48 -

70 6000 T 19 16 12

-

19 16 13

-

19 16 13

-

19 17 13

-

19 16 12

-

18 15 12

-

HI PR 233 251 265 -

262 282 297

-

298 320 338 -

339 365 385

-

381 410 433 -

421 453 479

-

LO PR 102 109 119 -

108 115 126

-

112 120 131 -

118 126 137

-

124 132 144 -

128 136 149

-

MBh 158.1 163.8 179.5 - 154.4 160.0 175.3 - 150.7 156.2 171.1 - 147.0 152.4 167.0 - 139.7 144.8 158.6 - 129.4 134.1 146.9 -

S/T 0.69 0.58 0.40 - 0.72 0.60 0.41 - 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.79 0.66 0.46 - 0.79 0.66 0.46 -

4800 T 21 18 14

-

21 18 14

-

21 18 14

-

21 18 14

-

21 18 14

-

20 17 13

-

HI PR 226 243 257

-

254 273 288 -

289 311 328

-

329 354 374 -

370 398 420

-

409 440 464

-

LO PR 99 106 115

-

105 112 122 -

109 116 127

-

115 122 133

-

120 128 139 -

124 132 144

-

15-Ton AC ­ (Standard Motor and Two-Speed Motor at High Speed)

www.daikinac.com

MBh 179.4 184.7 199.9 214.5 175.2 180.4 195.3 209.6 171.0 176.1 190.6 204.6 166.9 171.8 186.0 199.6 158.5 163.2 176.7 189.6 146.8 151.2 163.6 175.6 S/T 0.85 0.76 0.58 0.37 0.89 0.79 0.60 0.39 0.91 0.81 0.61 0.40 0.94 0.84 0.63 0.41 0.97 0.87 0.66 0.42 0.98 0.88 0.66 0.43 6750 T 21 19 16 11 21 19 16 11 21 19 16 11 21 20 16 11 21 19 16 11 20 18 15 10 HI PR 238 256 270 282 267 287 303 316 304 327 345 360 346 372 393 410 389 419 442 461 430 463 488 509 LO PR 104 111 121 129 110 117 128 137 115 122 133 142 121 128 140 149 126 134 147 156 131 139 152 162 MBh 174.2 179.3 194.1 208.3 170.1 175.1 189.6 203.5 166.1 171.0 185.1 198.6 162.0 166.8 180.5 193.8 153.9 158.5 171.5 184.1 142.6 146.8 158.9 170.5 S/T 0.81 0.73 0.55 0.35 0.84 0.76 0.57 0.37 0.87 0.77 0.59 0.38 0.89 0.80 0.60 0.39 0.93 0.83 0.63 0.40 0.94 0.84 0.63 0.41 75 6000 T 22 20 16 11 22 20 17 11 22 20 17 11 22 20 17 12 22 20 16 11 20 19 15 11 HI PR 236 253 268 279 264 284 300 313 301 323 342 356 342 368 389 406 385 415 438 457 426 458 484 504 LO PR 103 110 120 128 109 116 127 135 114 121 132 141 119 127 139 148 125 133 145 155 129 138 150 160 MBh 160.7 165.5 179.1 192.3 157.0 161.6 175.0 187.8 153.3 157.8 170.8 183.3 149.5 154.0 166.6 178.8 142.0 146.3 158.3 169.9 131.6 135.5 146.6 157.4 S/T 0.79 0.70 0.53 0.34 0.81 0.73 0.55 0.35 0.83 0.75 0.56 0.36 0.86 0.77 0.58 0.38 0.89 0.80 0.61 0.39 0.90 0.81 0.61 0.39 4800 T 24 22 18 13 24 23 18 13 25 23 18 13 25 23 19 13 24 22 18 13 23 21 17 12 HI PR 228 246 260 271 256 276 291 304 292 314 331 346 332 357 377 394 374 402 425 443 413 444 469 489 LO PR 100 107 117 124 106 113 123 131 110 117 128 136 116 123 134 143 121 129 141 150 125 133 146 155

IDB: Entering Indoor Dry Bulb Temperature

Shaded area reflects ACCA (TVA) conditions

High and low pressures are measured at the liquid and suction access fittings.

SS-DBC15

Expanded Cooling Data

SS-DBC15

Outdoor Ambient Temperature

65

75

85

95

105

115

Entering Indoor Wet Bulb Temperature

IDB

Airflow

59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67

71

MBh 182.6 186.5 199.3 213.1 178.3 182.2 194.7 208.1 174.1 177.9 190.0 203.1 169.8 173.5 185.4 198.2 161.3 164.9 176.1 188.3 149.4 152.7 163.2 S/T 0.94 0.88 0.71 0.53 0.97 0.91 0.74 0.55 1.00 0.93 0.76 0.57 1.00 0.96 0.78 0.59 1.00 1.00 0.81 0.61 1.00 1.00 0.82 6750 T 23 22 19 16 24 23 20 16 24 23 20 16 23 23 20 16 22 22 20 16 20 21 18 HI PR 240 259 273 285 270 290 306 320 307 330 349 363 349 376 397 414 393 423 447 466 434 467 493 LO PR 106 112 123 131 112 119 130 138 116 123 135 143 122 130 141 151 128 136 148 158 132 140 153

174.4 0.61 15 515 163

MBh 177.2 180.1 193.5 206.9 173.1 176.9 189.0 202.0 169.0 172.7 184.5 197.2 164.9 168.5 180.0 192.4 156.6 160.1 171.0 182.8 145.1 148.3 158.4 169.3

S/T 0.89 0.84 0.68 0.51 0.93 0.87 0.71 0.53 0.95 0.89 0.72 0.54 0.98 0.92 0.75 0.56 1.00 0.95 0.78 0.58 1.00 0.96 0.78 0.59

80 6000 T 24 23 20 16 25 24 20 16 25 24 20 16 25 24 21 16 24 23 20 16 22 22 19

15

HI PR 238 256 270 282 267 287 303 316 304 327 345 360 346 372 393 410 389 419 442 461 430 463 488 510

LO PR 105 111 121 129 110 117 128 137 115 122 133 142 121 128 140 149 126 134 147 156 131 139 152 162

MBh 163.6 167.2 178.6 190.9 159.8 163.3 174.4 186.5 156.0 159.4 170.3 182.0 152.2 155.5 166.1 177.6 144.6 147.7 157.8 168.7 133.9 136.8 146.2 S/T 0.86 0.81 0.66 0.49 0.89 0.84 0.68 0.51 0.92 0.86 0.70 0.52 0.94 0.89 0.72 0.54 0.98 0.92 0.75 0.56 0.99 0.93 0.75 4800 T 27 26 22 18 27 26 23 18 27 26 23 18 28 26 23 18 27 26 23 18 25 24 21 HI PR 231 248 262 274 259 279 294 307 295 317 335 349 335 361 381 398 377 406 429 447 417 449 474 LO PR 101 108 118 125 107 114 124 132 111 118 129 138 117 124 136 145 123 130 142 152 127 135 147

156.3 0.56 17 494 157

www.daikinac.com

15-Ton AC ­ (Two-Speed Motor at High Speed)

MBh 185.8 189.3 198.3 211.6 180.4 184.9 193.7 206.6 177.1 180.5 189.1 201.7 172.8 176.1 184.5 196.8 164.2 167.3 175.2 187.0 152.1 155.0 162.3 173.2

S/T 0.98 0.95 0.86 0.69 1.00 0.98 0.89 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.97 0.79 1.00 1.00 0.98 0.80

6750 T 25 24 23 20 25 25 23 20 24 25 23 20 24 24 24 20 22 23 23 20 21 21 22

19

HI PR 243 261 276 288 272 293 309 323 310 333 352 367 353 380 401 418 397 427 451 470 439 472 498 520

LO PR 107 113 124 132 113 120 131 139 117 125 136 145 123 131 143 152 129 137 150 159 133 142 155 165

MBh 180.3 183.8 192.5 205.4 176.1 179.6 188.1 200.6 172.0 175.3 183.6 195.8 167.8 171.0 179.1 191.1 159.4 162.5 170.1 180.5 147.6 150.5 157.6 168.1

S/T 0.94 0.90 0.82 0.66 0.97 0.94 0.85 0.69 1.00 0.96 0.87 0.70 1.00 0.99 0.89 0.73 1.00 1.00 0.93 0.75 1.00 1.00 0.94 0.76

85 6000 T 26 25 24 21 26 26 24 21 26 26 24 21 26 26 25 21 24 25 24 21 23 23 23

20

HI PR 240 259 273 285 270 290 306 320 307 330 349 363 349 376 397 414 393 423 447 466 434 467 493 515

LO PR 106 112 123 131 112 119 130 138 116 123 135 143 122 130 141 151 128 136 148 158 132 140 153 163

MBh 166.5 169.7 177.7 189.6 162.6 165.7 173.6 185.2 158.7 161.8 169.4 180.8 154.8 157.8 165.3 176.4 147.1 149.9 157.0 167.5 136.3 138.9 145.5 155.2

S/T 0.90 0.87 0.79 0.64 0.94 0.90 0.81 0.66 0.96 0.93 0.84 0.68 0.99 0.96 0.86 0.70 1.00 0.99 0.90 0.73 1.00 1.00 0.90 0.73

4800 T 29 28 27 23 29 29 27 23 29 29 27 23 29 29 27 24 28 28 27 23 26 27 25

22

HI PR 233 251 265 276 262 281 297 310 297 320 338 353 339 365 385 402 381 410 433 452 421 453 479 499

LO PR 102 109 119 127 108 115 126 134 112 120 131 139 118 126 137 146 124 132 144 153 128 136 149 158

IDB: Entering Indoor Dry Bulb Temperature

Shaded area reflects AHRI (TVA) conditions

High and low pressures are measured at the liquid and suction access fittings.

13

Expanded Cooling Data

14

Outdoor Ambient Temperature

65

75

85

95

105

115

Entering Indoor Wet Bulb Temperature

IDB

Airflow

59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71

MBh 235.2 243.8 267.1 - 229.7 238.1 260.9 - 224.2 232.4 254.6 - 218.8 226.8 248.4 - 207.8 215.4 236.0 - 192.5 199.5 218.6 -

S/T 0.76 0.63 0.44 - 0.78 0.66 0.45 - 0.80 0.67 0.47 - 0.83 0.69 0.48 - 0.86 0.72 0.50 - 0.87 0.73 0.50 -

7875 T 21 18 14

-

21 18 14

-

21 18 14

-

21 18 14

-

21 18 14

-

20 17 13

-

HI PR 259 279 294 - 290 313 330 - 330 356 375 - 376 405 428 - 423 456 481 - 468 503 531 LO PR 100 106 116 - 105 112 122 - 110 117 127 - 115 122 134 - 121 128 140 - 125 133 145 -

MBh 228.3 236.7 259.3 - 223.0 231.2 253.3 - 217.7 225.7 247.2 - 212.4 220.1 241.2 - 201.8 209.1 229.1 - 186.9 193.7 212.3 -

S/T 0.72 0.60 0.42 - 0.75 0.63 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.82 0.69 0.48 - 0.83 0.69 0.48 -

70 7000 T 22 19 14

-

22 19 14

-

22 19 14

-

22 19 15

-

22 19 14

-

20 18 13

-

HI PR 256 276 291 - 288 310 327 - 327 352 372 - 373 401 423 - 419 451 476 - 463 498 526 -

LO PR 99 105 115 - 104 111 121 - 108 115 126 - 114 121 132 - 119 127 139 - 123 131 143 -

MBh 210.7 218.4 239.3 - 205.8 213.4 233.8 - 200.9 208.3 228.2 - 196.0 203.2 222.6 - 186.2 193.0 211.5 - 172.5 178.8 195.9 -

S/T 0.70 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.76 0.64 0.44 - 0.79 0.66 0.46 - 0.80 0.67 0.46 -

5600 T 24 21 16

-

24 21 16

-

24 21 16

-

25 21 16

-

24 21 16

-

23 20 15

-

HI PR 249 268 283 - 279 300 317 - 317 341 361 - 361 389 411 - 407 438 462 - 449 483 510 -

LO PR 96 102 111 - 101 108 118 - 105 112 122 - 110 118 128 - 116 123 134 - 120 127 139 -

www.daikinac.com

20-Ton AC ­ (Two-Speed Motor at High Speed)

MBh 239.2 246.2 266.5 286.1 233.6 240.5 260.3 279.4 228.0 234.8 254.1 272.8 222.5 229.1 247.9 266.1 211.4 217.6 235.5 252.8 195.8 201.6 218.2 234.2 S/T 0.86 0.77 0.58 0.37 0.89 0.80 0.60 0.39 0.91 0.82 0.62 0.40 0.94 0.84 0.64 0.41 0.98 0.88 0.66 0.43 0.99 0.88 0.67 0.43 7875 T 24 22 18 13 24 22 18 13 24 22 18 13 25 23 19 13 24 22 18 13 23 21 17 12 HI PR 262 281 297 310 293 316 333 348 334 359 379 396 380 409 432 451 428 460 486 507 472 508 537 560 LO PR 101 107 117 125 106 113 124 132 111 118 129 137 116 124 135 144 122 130 141 151 126 134 146 156 MBh 232.2 239.1 258.8 277.7 226.8 233.5 252.8 271.3 221.4 228.0 246.7 264.8 216.0 222.4 240.7 258.4 205.2 211.3 228.7 245.4 190.1 195.7 211.8 227.4 S/T 0.82 0.73 0.56 0.36 0.85 0.76 0.58 0.37 0.87 0.78 0.59 0.38 0.90 0.81 0.61 0.39 0.93 0.84 0.63 0.41 0.94 0.84 0.64 0.41 75 7000 T 25 23 19 13 25 23 19 13 25 23 19 13 26 24 19 13 25 23 19 13 24 22 18 12 HI PR 259 279 294 307 291 313 330 344 330 356 376 392 376 405 428 446 423 456 481 502 468 503 532 554 LO PR 100 106 116 123 105 112 122 130 110 117 127 136 115 122 134 142 121 128 140 149 125 133 145 154 MBh 214.3 220.7 238.8 256.3 209.3 215.5 233.3 250.4 204.4 210.4 227.7 244.4 199.4 205.3 222.2 238.5 189.4 195.0 211.1 226.5 175.4 180.6 195.5 209.8 S/T 0.79 0.71 0.54 0.34 0.82 0.73 0.56 0.36 0.84 0.75 0.57 0.37 0.87 0.78 0.59 0.38 0.90 0.81 0.61 0.39 0.91 0.81 0.62 0.40 5600 T 28 26 21 15 28 26 21 15 28 26 21 15 28 26 21 15 28 26 21 15 26 24 20 14 HI PR 251 270 285 298 282 303 320 334 321 345 364 380 365 393 415 433 411 442 467 487 454 488 516 538 LO PR 97 103 112 120 102 109 119 126 106 113 123 131 112 119 130 138 117 124 136 145 121 129 141 150

IDB: Entering Indoor Dry Bulb Temperature

Shaded area reflects ACCA (TVA) conditions

High and low pressures are measured at the liquid and suction access fittings.

SS-DBC15

Expanded Cooling Data

SS-DBC15

Outdoor Ambient Temperature

65

75

85

95

105

115

Entering Indoor Wet Bulb Temperature

IDB

Airflow

59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71

MBh 243.4 248.7 265.7 284.1 237.8 242.9 259.6 277.5 232.1 237.2 253.4 270.9 226.4 231.4 247.2 264.3 215.1 219.8 234.8 251.0 199.3 203.6 217.5 232.5 S/T 0.94 0.89 0.72 0.54 1.00 0.92 0.75 0.56 1.00 0.94 0.77 0.57 1.00 1.00 0.79 0.59 1.00 1.00 0.82 0.61 1.00 1.00 0.83 0.62 7875 T 27 26 22 18 28 26 23 18 27 26 23 18 26 27 23 18 25 26 22 18 23 24 21 17

HI PR 264 284 300 313 296 319 337 351 337 363 383 400 384 413 436 455 432 465 491 512 477 514 542 566 LO PR 102 108 118 126 108 114 125 133 112 119 130 138 117 125 136 145 123 131 143 152 127 135 148 157

MBh 236.3 241.5 258.0 275.8 230.8 235.9 252.0 269.4 225.3 230.3 246.0 263.0 219.8 224.6 240.0 256.6 208.8 213.4 228.0 243.7 193.5 197.7 211.2 225.8 S/T 0.90 0.84 0.69 0.51 0.93 0.88 0.71 0.53 0.96 0.90 0.73 0.55 0.99 0.93 0.75 0.56 1.00 0.96 0.78 0.58 1.00 0.97 0.79 0.59 80 7000 T 28 27 23 19 28 27 24 19 28 27 24 19 29 27 24 19 27 27 23 19 25 25 22 17

HI PR 262 281 297 310 293 316 334 348 334 359 379 396 380 409 432 451 428 460 486 507 473 509 537 560 LO PR 101 107 117 125 106 113 124 132 111 118 129 137 116 124 135 144 122 130 141 151 126 134 146 156

MBh 218.1 222.9 238.1 254.6 213.1 217.7 232.6 248.6 208.0 212.5 227.1 242.7 202.9 207.3 221.5 236.8 192.8 197.0 210.4 225.0 178.6 182.5 194.9 208.4 S/T 0.87 0.81 0.66 0.50 0.90 0.84 0.69 0.51 0.92 0.87 0.70 0.53 0.95 0.89 0.73 0.54 0.99 0.93 0.75 0.56 1.00 0.93 0.76 0.57 5600 T 31 30 26 21 31 30 26 21 32 30 26 21 32 30 26 21 31 30 26 21 29 28 24 19 HI PR 254 273 288 301 285 306 323 337 324 348 368 384 369 397 419 437 415 446 471 492 458 493 521 543 LO PR 98 104 114 121 103 110 120 128 107 114 125 133 113 120 131 139 118 126 137 146 122 130 142 151

www.daikinac.com

20-Ton AC ­ (Two-Speed Motor at High Speed)

MBh 247.7 252.5 264.4 282.1 241.9 246.6 258.3 275.5 236.2 240.7 252.1 269.0 230.4 234.8 246.0 262.4 218.9 223.1 233.7 249.3 202.7 206.7 216.4 230.9 S/T 0.99 0.96 0.86 0.70 1.00 0.99 0.89 0.72 1.00 1.00 0.92 0.74 1.00 1.00 0.95 0.77 1.00 1.00 0.98 0.80 1.00 1.00 0.99 0.80 7875 T 29 28 27 23 28 28 27 23 28 28 27 23 27 27 27 24 26 26 27 23 24 24 25 22 HI PR 267 287 303 316 299 322 340 355 340 366 387 404 388 417 441 460 436 469 496 517 482 519 548 571 LO PR 103 109 119 127 109 116 126 134 113 120 131 140 119 126 138 147 124 132 144 154 129 137 149 159 MBh 240.5 245.1 256.7 273.9 234.9 239.4 250.7 267.5 229.3 233.7 244.8 261.1 223.7 228.0 238.8 254.8 212.5 216.6 226.9 242.0 196.8 200.6 210.1 224.2 S/T 0.94 0.91 0.82 0.67 0.98 0.94 0.85 0.69 1.00 0.97 0.87 0.71 1.00 1.00 0.90 0.73 1.00 1.00 0.94 0.76 1.00 1.00 0.94 0.77 85 7000 T 30 29 28 24 30 30 28 24 30 30 28 24 29 30 28 24 28 28 28 24 26 26 26 23 HI PR 264 284 300 313 296 319 337 351 337 363 383 400 384 413 436 455 432 465 491 512 477 514 542 566 LO PR 102 108 118 126 108 114 125 133 112 119 130 138 117 125 136 145 123 131 143 152 127 135 148 157 MBh 221.9 226.2 236.9 252.8 216.8 221.0 231.4 246.9 211.6 215.7 225.9 241.0 206.5 210.5 220.4 235.1 196.1 199.9 209.4 223.4 180.7 185.2 194.0 206.9 S/T 0.91 0.88 0.79 0.64 0.94 0.91 0.82 0.67 0.97 0.93 0.84 0.68 1.00 0.96 0.87 0.71 1.00 1.00 0.90 0.73 1.00 1.00 0.91 0.74 5600 T 33 33 31 27 34 33 31 27 34 33 31 27 34 33 31 27 32 33 31 27 30 30 29 25 HI PR 256 276 291 304 288 309 327 341 327 352 372 388 372 401 423 441 419 451 476 497 463 498 526 549 LO PR 99 105 115 122 104 111 121 129 108 115 126 134 114 121 132 141 119 127 139 148 123 131 143 153

IDB: Entering Indoor Dry Bulb Temperature

Shaded area reflects AHRI (TVA) conditions

High and low pressures are measured at the liquid and suction access fittings.

15

Expanded Cooling Data

16

Outdoor Ambient Temperature

65

75

85

95

105

115

Entering Indoor Wet Bulb Temperature

IDB

Airflow

59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71

MBh 284.2 294.5 322.7 - 277.6 287.7 315.2 - 271.0 280.8 307.7 - 264.3 274.0 300.2 - 251.1 260.3 285.2 - 232.6 241.1 264.2 -

S/T 0.67 0.56 0.39 - 0.70 0.58 0.40 - 0.72 0.60 0.41 - 0.74 0.62 0.43 - 0.77 0.64 0.44 - 0.77 0.65 0.45 -

T 19 17 13

-

19 17 13

-

19 17 13

-

19 17 13

-

19 17 13

-

18 16 12

-

9202

kW 22.18 22.65 23.36 - 23.88 24.39 25.17 - 25.38 25.93 26.77 - 26.70 27.29 28.19 - 27.83 28.45 29.39 - 28.80 29.44 30.43 -

HI PR 270 290 306 - 303 326 344 - 344 370 391 - 392 422 445 - 441 475 501 - 487 524 554 -

LO PR 102 108 118 - 108 115 125 - 112 119 130 - 118 125 137 - 123 131 143 - 127 136 148 -

MBh 275.9 286.0 313.3 - 269.5 279.3 306.0 - 263.1 272.7 298.7 - 256.7 266.0 291.5 - 243.8 252.7 276.9 - 225.9 234.1 256.5 -

S/T 0.64 0.54 0.37 - 0.67 0.56 0.38 - 0.68 0.57 0.39 - 0.70 0.59 0.41 - 0.73 0.61 0.42 - 0.74 0.62 0.43 -

T 20 17 13

-

20 17 13

-

20 17 13

-

20 18 13

-

20 17 13

-

19 16 12

-

70 8200

kW 22.00 22.47 23.17 - 23.69 24.20 24.97 - 25.17 25.72 26.55 - 26.48 27.07 27.95 - 27.60 28.21 29.14 - 28.56 29.20 30.17 -

HI PR 267 287 303 - 300 322 340 - 341 367 387 - 388 418 441 - 437 470 496 - 482 519 548 -

LO PR 101 107 117 - 107 113 124 - 111 118 129 - 116 124 135 - 122 130 142 - 126 134 147 -

MBh 262.1 271.7 297.6 - 256.0 265.3 290.7 - 249.9 259.0 283.8 - 243.8 252.7 276.9 - 231.6 240.1 263.0 - 214.6 222.4 243.7 -

S/T 0.61 0.51 0.36 - 0.64 0.53 0.37 - 0.65 0.55 0.38 - 0.67 0.56 0.39 - 0.70 0.58 0.40 - 0.71 0.59 0.41 -

T 20 18 13

-

21 18 14

-

21 18 14

-

21 18 14

-

21 18 13

-

19 17 13

-

7257

kW 21.66 22.11 22.80 - 23.31 23.80 24.56 - 24.76 25.30 26.12 - 26.05 26.62 27.49 - 27.14 27.74 28.65 - 28.08 28.71 29.66 -

HI PR 262 282 297 - 294 316 334 - 334 359 379 - 380 409 432 - 428 460 486 - 473 509 537 -

LO PR 99 105 115 - 105 111 121 - 109 116 126 - 114 121 133 - 120 127 139 - 124 132 144 -

www.daikinac.com

25-Ton AC ­ (Two-Speed Motor at High Speed)

MBh 289.0 297.5 322.1 345.7 282.3 290.6 314.6 337.6 275.6 283.7 307.1 329.6 268.8 276.8 299.6 321.5 255.4 262.9 284.6 305.5 236.6 243.6 263.6 283.0

S/T 0.76 0.68 0.52 0.3 0.79 0.71 0.54 0.3 0.81 0.73 0.55 0.4 0.84 0.75 0.57 0.4 0.87 0.78 0.59 0.4 0.88 0.79 0.59 0.4

T 22 20 17 12 22 21 17 12 22 21 17 12 23 21 17 12 22 20 17 12 21 19 16 10.8 9202
kW 22.36 22.83 23.55 24.3 24.07 24.59 25.38 26.2 25.59 26.15 27.00 27.9 26.93 27.52 28.43 29.4 28.07 28.69 29.64 30.6 29.05 29.70 30.69 31.7

HI PR 272 293 310 322.9 306 329 347 362.3 348 374 395 412.0 396 426 450 469.3 445 479 506 528.0 492 530 559 583.3

LO PR 103 110 120 127.4 109 116 126 134.6 113 120 131 139.9 119 126 138 147.0 125 132 145 154.0 129 137 150 159.3

MBh 280.6 288.9 312.7 335.6 274.1 282.2 305.4 327.8 267.5 275.4 298.1 320.0 261.0 268.7 290.9 312.2 248.0 255.3 276.3 296.6 229.7 236.5 256.0 274.7

S/T 0.73 0.65 0.49 0.3 0.76 0.68 0.51 0.3 0.78 0.69 0.52 0.3 0.80 0.72 0.54 0.3 0.83 0.74 0.56 0.4 0.84 0.75 0.57 0.4

T 23 21 17 12 23 21 18 12 23 21 18 12 23 22 18 12 23 21 17 12 22 20 16 11.2 75 8200
kW 22.18 22.65 23.36 24.1 23.88 24.40 25.18 26.0 25.38 25.94 26.78 27.7 26.71 27.30 28.19 29.1 27.83 28.45 29.39 30.4 28.80 29.45 30.43 31.5

HI PR 270 290 307 319.7 303 326 344 358.7 344 370 391 408.0 392 422 446 464.7 441 475 501 522.7 487 524 554 577.6

LO PR 102 108 118 126.1 108 115 125 133.3 112 119 130 138.5 118 125 137 145.5 123 131 143 152.5 128 136 148 157.7

MBh 266.5 274.4 297.1 318.8 260.3 268.1 290.1 311.4 254.1 261.7 283.2 304.0 248.0 255.3 276.3 296.6 235.6 242.5 262.5 281.7 218.2 224.7 243.2 261.0

S/T 0.70 0.63 0.47 0.3 0.72 0.65 0.49 0.3 0.74 0.66 0.50 0.3 0.77 0.69 0.52 0.3 0.80 0.71 0.54 0.3 0.80 0.72 0.54 0.3

T 24 22 18 12 24 22 18 12 24 22 18 12 24 22 18 13 24 22 18 12 22 20 17 11.6 7257
kW 21.83 22.29 22.99 23.7 23.50 24.00 24.77 25.6 24.97 25.51 26.34 27.2 26.27 26.84 27.72 28.6 27.37 27.98 28.90 29.9 28.32 28.95 29.91 30.9

HI PR 264 284 300 313.3 297 319 337 351.5 337 363 383 399.8 384 413 437 455.4 432 465 491 512.3 478 514 543 566.0

LO PR 100 106 116 123.6 106 112 123 130.6 110 117 127 135.7 115 123 134 142.6 121 129 140 149.4 125 133 145 154.6

IDB: Entering Indoor Dry Bulb Temperature

Shaded area reflects ACCA (TVA) Rating Conditions.

kW = Total system power

High and low pressures are measured at the liquid and suction access fittings.

Amps: Unit amps (comp.+ evaporator + condenser fan motors)

Design Subcooling, 16 - 19 °F @ the liquid access fitting connection ARI 95 test conditions. Design Superheat 8 - 12°F @ the compressor suction access fitting connection.

SS-DBC15

Expanded Cooling Data

SS-DBC15

Outdoor Ambient Temperature

65

75

85

95

105

115

Entering Indoor Wet Bulb Temperature

IDB

Airflow

59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71

MBh 294.1 300.6 321.1 343.3 287.3 293.6 313.6 335.3 280.4 286.6 306.2 327.3 273.6 279.6 298.7 319.3 259.9 265.6 283.8 303.3 240.8 246.0 262.9 281.0

S/T 0.84 0.79 0.64 0.5 0.87 0.82 0.66 0.5 0.89 0.84 0.68 0.5 0.92 0.86 0.70 0.5 0.96 0.90 0.73 0.5 0.96 0.90 0.74 0.5

T 25 24 21 16 25 24 21 17 25 24 21 17 25 24 21 17 25 24 21 17 23 22 19 15.4 9202
kW 22.54 23.01 23.74 24.5 24.27 24.79 25.59 26.4 25.80 26.37 27.23 28.1 27.15 27.75 28.67 29.6 28.30 28.93 29.89 30.9 29.29 29.95 30.95 32.0

HI PR 275 296 313 326.1 309 332 351 366.0 351 378 399 416.2 400 430 455 474.0 450 484 511 533.3 497 535 565 589.2

LO PR 104 111 121 128.7 110 117 128 136.0 114 122 133 141.3 120 128 139 148.4 126 134 146 155.6 130 138 151 160.9

MBh 285.6 291.8 311.8 333.3 278.9 285.0 304.5 325.5 272.3 278.2 297.3 317.8 265.6 271.4 290.0 310.0 252.4 257.9 275.5 294.5 233.8 238.9 255.2 272.8

S/T 0.80 0.75 0.61 0.5 0.83 0.78 0.63 0.5 0.85 0.80 0.65 0.5 0.88 0.82 0.67 0.5 0.91 0.85 0.70 0.5 0.92 0.86 0.70 0.5

T 26 25 21 17 26 25 22 17 26 25 22 17 26 25 22 17 26 25 21 17 24 23 20 16.0 80 8200
kW 22.36 22.83 23.55 24.3 24.08 24.59 25.38 26.2 25.59 26.15 27.00 27.9 26.93 27.53 28.43 29.4 28.07 28.69 29.64 30.6 29.05 29.70 30.69 31.7

HI PR 272 293 310 322.9 306 329 347 362.3 348 374 395 412.1 396 426 450 469.4 446 479 506 528.0 492 530 559 583.4

LO PR 103 110 120 127.4 109 116 126 134.6 113 120 131 139.9 119 126 138 147.0 125 132 145 154.0 129 137 150 159.3

MBh 271.3 277.2 296.2 316.6 265.0 270.8 289.3 309.2 258.7 264.3 282.4 301.9 252.4 257.9 275.5 294.5 239.7 245.0 261.7 279.8 222.1 226.9 242.4 259.2

S/T 0.77 0.72 0.59 0.4 0.79 0.74 0.61 0.5 0.81 0.76 0.62 0.5 0.84 0.79 0.64 0.5 0.87 0.82 0.67 0.5 0.88 0.83 0.67 0.5

T 26 25 22 18 27 26 22 18 27 26 22 18 27 26 22 18 27 25 22 18 25 24 21 16.5 7257
kW 22.00 22.47 23.17 23.9 23.69 24.20 24.97 25.8 25.17 25.72 26.55 27.4 26.48 27.07 27.95 28.9 27.60 28.21 29.14 30.1 28.56 29.20 30.17 31.2

HI PR 267 287 303 316.5 300 322 340 355.1 341 367 387 403.8 388 418 441 460.0 437 470 496 517.5 482 519 548 571.7

LO PR 101 107 117 124.9 107 113 124 131.9 111 118 129 137.1 116 124 135 144.0 122 130 142 150.9 126 134 147 156.1

www.daikinac.com

25-Ton AC ­ (Two-Speed Motor at High Speed)

MBh 299.3 305.1 319.5 340.9 292.3 298.0 312.1 332.9 285.3 290.9 304.6 325.0 278.4 283.8 297.2 317.1 264.5 269.6 282.3 301.2 245.0 249.7 261.5 279.0

S/T 0.88 0.85 0.77 0.6 0.91 0.88 0.79 0.6 0.93 0.90 0.81 0.7 0.96 0.93 0.84 0.7 1.00 0.97 0.87 0.7 1.00 0.97 0.88 0.7

T 26 26 24 21 27 26 25 21 27 26 25 21 27 26 25 22 26 26 25 21 24 24 23 19.9 9202
kW 22.72 23.20 23.93 24.7 24.47 25.00 25.80 26.6 26.01 26.58 27.45 28.4 27.38 27.99 28.91 29.9 28.54 29.18 30.15 31.2 29.54 30.20 31.21 32.3

HI PR 278 299 316 329.4 312 336 354 369.6 355 382 403 420.4 404 435 459 478.8 454 489 516 538.6 502 540 571 595.1

LO PR 105 112 122 130.0 111 118 129 137.3 115 123 134 142.7 121 129 141 149.9 127 135 148 157.1 131 140 153 162.5

MBh 290.6 296.2 310.2 330.9 283.8 289.3 303.0 323.2 277.0 282.4 295.8 315.5 270.3 275.5 288.6 307.8 256.8 261.7 274.1 292.4 237.8 242.5 253.9 270.9

S/T 0.84 0.81 0.73 0.6 0.87 0.84 0.76 0.6 0.89 0.86 0.78 0.6 0.92 0.89 0.80 0.7 0.96 0.92 0.83 0.7 0.96 0.93 0.84 0.7

T 27 27 25 22 28 27 26 22 28 27 26 22 28 27 26 22 27 27 26 22 26 25 24 20.7 85 8200
kW 22.54 23.01 23.74 24.5 24.27 24.79 25.59 26.4 25.80 26.37 27.23 28.1 27.15 27.75 28.67 29.6 28.30 28.93 29.89 30.9 29.29 29.95 30.95 32.0

HI PR 275 296 313 326.1 309 332 351 366.0 351 378 399 416.2 400 430 455 474.0 450 484 511 533.3 497 535 565 589.2

LO PR 104 111 121 128.7 110 117 128 136.0 114 122 133 141.3 120 128 139 148.4 126 134 146 155.6 130 138 151 160.9

MBh 276.0 281.4 294.7 314.4 269.6 274.8 287.8 307.1 263.2 268.3 281.0 299.8 256.8 261.7 274.1 292.4 243.9 248.6 260.4 277.8 226.0 230.3 241.2 257.4

S/T 0.80 0.78 0.70 0.6 0.83 0.80 0.73 0.6 0.85 0.82 0.74 0.6 0.88 0.85 0.77 0.6 0.91 0.88 0.80 0.6 0.92 0.89 0.80 0.7

T 28 28 26 23 28 28 26 23 28 28 26 23 29 28 27 23 28 28 26 23 26 26 25 21.3 7257
kW 22.18 22.65 23.36 24.1 23.88 24.39 25.17 26.0 25.38 25.93 26.77 27.7 26.70 27.29 28.19 29.1 27.83 28.45 29.39 30.4 28.80 29.44 30.43 31.5

HI PR 270 290 306 319.6 303 326 344 358.6 344 370 391 407.9 392 422 445 464.6 441 475 501 522.6 487 524 554 577.5

LO PR 102 108 118 126.1 108 115 125 133.3 112 119 130 138.5 118 125 137 145.5 123 131 143 152.5 127 136 148 157.7

IDB: Entering Indoor Dry Bulb Temperature

Shaded area reflects AHRI) Rating Conditions.

kW = Total system power

High and low pressures are measured at the liquid and suction access fittings.

Amps: Unit amps (comp.+ evaporator + condenser fan motors)

Design Subcooling, 16 - 19 °F @ the liquid access fitting connection ARI 95 test conditions. Design Superheat 8 - 12°F @ the compressor suction access fitting connection.

17

Airflow Data 15

ESP (" HO)
0.2 0.4 0.6 0.8 1.0 1.2
ESP (" HO)
0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2

0

CFM BHP

---

---

---

---

---

---

7112 2.96

5983 2.38

4426 1.71

0

CFM BHP

---

---

---

---

---

---

---

---

6685 6.06

6248 5.75

5664 5.31

5053 4.81

Standard Two-Speed Belt-Drive at High Speed -- Down Shot

Turns Open

1

2

3

4

CFM BHP CFM BHP CFM BHP CFM BHP

---

---

---

---

---

---

---

---

---

---

---

--- 7306 2.54 6777 2.14

7477 2.97 6899 2.51 6323 2.10 5716 1.72

6467 2.46 5795 2.01 5101 1.61 ---

---

5190 1.89 ---

---

---

---

---

---

---

---

---

---

---

---

---

---

Two-Speed High-Static Belt-Drive at High Speed -- Down Shot

Turns Open

1

2

3

4

CFM BHP CFM BHP CFM BHP CFM BHP

---

---

---

---

---

---

---

---

---

---

---

--- 6930 5.14 6432 4.53

---

--- 6866 5.52 6382 4.80 5916 4.24

6779 5.80 6417 5.22 5914 4.52 5307 3.89

6391 5.52 5954 4.90 5288 4.18 ---

---

5782 5.09 5261 4.50 ---

---

---

---

5111 4.71 ---

---

---

---

---

---

---

---

---

---

---

---

---

---

5

CFM BHP

7203 2.18

6257 1.80

5103 1.39

---

---

---

---

---

---

5

CFM BHP

6580 4.30

5908 3.98

5370 3.68

---

---

---

---

---

---

---

---

---

---

6

CFM BHP

6718 1.84

5711 1.48

---

---

---

---

---

---

---

---

Airflow Data -- 20 Tons

Standard Two-Speed Belt-Drive at High Speed -- Down Shot

ESP (" HO)

0 CFM BHP

1 CFM BHP

2 CFM BHP

Turns Open 3
CFM BHP

4 CFM BHP

0.2

---

---

---

---

---

---

---

---

---

---

0.4

---

---

---

---

---

---

---

--- 9570 4.08

0.6

---

---

---

---

---

--- 9038 3.82 8460 3.46

0.8

---

--- 8171 2.93 7630 3.70 7068 2.79 ---

---

1.0

---

--- 7901 2.85 7203 3.42 ---

---

---

---

1.2

7344 4.35 ---

---

---

---

---

---

---

---

5

CFM BHP

---

---

9197 3.82

7949 3.14

---

---

---

---

---

---

6

CFM BHP

9664 4.05

8702 3.51

---

---

---

---

---

---

---

---

Two-Speed High-Static Belt-Drive at High Speed -- Down Shot

ESP (" HO)

0 CFM BHP

1 CFM BHP

Turns Open

2

3

CFM BHP CFM BHP

4 CFM BHP

5 CFM BHP

0.8

---

---

---

---

---

---

---

--- 8765 6.05 8225 5.38

1.0

---

---

---

---

---

--- 8663 6.43 8040 5.67 7385 4.97

1.2

---

--- 8978 7.61 8583 6.90 7978 6.00 7395 5.30 6713 4.60

1.4

8845 7.87 8474 7.26 8021 6.52 7393 5.65 6634 4.86 ---

---

1.6

8356 7.58 7989 6.89 7442 6.13 6610 5.22 ---

---

---

---

1.8

7810 7.18 7227 6.37 6576 5.62 ---

---

---

---

---

---

2.0

7080 6.64 6389 5.89 ---

---

---

---

---

---

---

---

2.2

6316 6.02 ---

---

---

---

---

---

---

---

---

---

Notes · Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
· Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Minimum rated SCFM is 350 per ton. · Unit factory shipped with the sheave set at 2.5 turns open.

18

www.daikinac.com

SS-DBC15

Airflow Data 25

Turns Open RPM ESP 0.2 0.4 0.6 0.8 1 1.2

0 972 SCFM BHP --- ----- --10,519 6.20 9,482 5.60 8,446 5.01 7,409 4.41

Standard Two-Speed Belt-Drive at High Speed - Down Shot

1

2

3

4

941

910

877

845

SCFM BHP SCFM BHP SCFM BHP SCFM BHP

--- --- --- --- 10,369 5.07 9,748 4.41

10,802 6.00 10,125 5.30 9,484 4.62 8,905 4.01

9,821 5.47 9,193 4.81 8,599 4.18 8,062 3.61

8,839 4.93 8,261 4.32 7,714 3.74 7,220 3.21

7,857 4.39 7,329 3.83 6,829 3.30 --- ---

6,876 3.85 --- --- --- --- --- ---

5 813 SCFM BHP 9,191 3.82 8,386 3.46 7,582 3.10 6,777 2.74 --- ----- ---

6 781 SCFM BHP 8,683 3.28 7,913 2.95 7,143 2.63 --- ----- ----- ---

Two-Speed High-Static Belt-Drive at High Speed - Down Shot

Turns Open

0

1

2

3

4

5

6

RPM

1254

1208

1163

1124

1085

1046

1007

ESP

SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP

0.6

--- --- --- --- --- --- --- --- --- --- --- --- 11,409 7.12

0.8

--- --- --- --- --- --- --- --- --- --- --- --- 10,302 6.46

1

--- --- --- --- --- --- --- --- --- --- 10,159 6.79 9,195 5.79

1.2

--- --- --- --- --- --- --- --- 9,990 7.11 8,961 6.04 8,087 5.13

1.4

--- --- --- --- --- --- 9,789 7.39 8,686 6.25 7,763 5.29 6,980 4.46

1.6

--- --- --- --- 9,543 7.63 8,357 6.40 7,382 5.39 6,566 4.53 --- ---

1.8

--- --- --- --- 7,957 6.48 6,925 5.41 6,077 4.53 --- --- --- ---

2

--- --- 7,667 6.68 6,370 5.34 --- --- --- --- --- --- --- ---

2.2

7,280 6.78 --- --- --- --- --- --- --- --- --- --- --- ---

· Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%. · Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Minimum rated SCFM is 350 per ton. · Unit factory shipped with the sheave set at 2.5 turns open.

Airflow Pressure Drop of Downflow Economizer for 15- to 25-Ton Rooftop Units (100% Return Air)

CFM

4000 6000 8000 10000

(In. WG)

0.16 0.18 0.27 0.47

Resistance (in. w.g.)

High-Efficiency MERV 13 Air Filter Option
Flanders Pre Pleat M13 Air Velocity vs Resistance (Test Size: 24" x 24" x 2" High Capacity)
0.50

0.45
2" Deep 0.40

0.35

0.30

0.25

0.20

0.15

0.10

0.05

0.00 0

100

200

300

400

500

600

700

Air Velocity (FPM)

Tonnage: 15, 20 25

Filter Nominal Size: 20 x 25 x 2 20 X 20 X 2

Part Number: 0160L00202 0160L00201

Order QTY: 6 8

Crankcase Heater Selection Table

ZP/ZPS...

Compressor Diameter

Compressor Voltage

230V

460V

575V

Crankcase Heater Watts

16-31

5.5" 0163R00002S 0163R00031S 0163R00032S

40

39-83 6.58/7.3" 0130L00017S 0130L00018S 0130L00019S

70

103-137

9.14" 0130L00020S 0130L00021S 0130L00022S

90

DB* Tonnage

Compressor Voltage

230V

460V

575V

Crankcase Heater Watts

15-20 Ton** 0130L00017S 0130L00018S 0130L00019S

70

25 Ton 0130L00020S 0130L00021S 0130L00022S

90

*Includes C,G&H models. **If Compressor Diameter is 9.14" then use 25 Ton Crankcase heaters.

SS-DBC15

www.daikinac.com

19

Electrical Data ­ 15 Ton

MODEL NUMBER

ELECTRICAL RATING

COMPRESSOR CIRCUIT 1

COMPRESSOR CIRCUIT 2

OUTDOOR FAN MOTOR

INDOOR FAN MOTOR

OPTIONAL ELECTRIC HEAT

OPTIONAL POWERED CONVENIENCE
OUTLET

UNIT POWER SUPPLY

RLA DBC1803S 208/230-3-60 25.0 DBC1803V 208/230-3-60 25.0 DBC1804S 460-3-60 12.2 DBC1804V 460-3-60 12.2 DBC1807S 575-3-60 9.0 DBC1807V 575-3-60 9.0

LRA
164.0 164.0 100.0 100.0 78.0 78.0

RLA
25.0 25.0 12.2 12.2 9.0 9.0

LRA
164.0 164.0 100.0 100.0 78.0 78.0

QTY HP
3 0.33 3 0.33 3 0.33 3 0.33 3 0.33 3 0.33

FLA TYPE HP
2-speed 2.0 High-Static 7.50
Belt-Drive

2.0

2-speed BeltDrive

3.00

2-speed 0.9 High-Static 7.50
Belt-Drive

0.9

2-speed Belt-Drive

3.00

2-speed 0.7 High-Static 7.50
Belt-Drive

0.7

2-speed Belt-Drive

3.00

FLA MODEL

-

EHK3-31

EHK3-46

EHK3-60

20.3

-

EHK3-31

EHK3-46

EHK3-60

-

EHK3-31

EHK3-46

EHK3-60

9.1

-

EHK3-31

EHK3-46

EHK3-60

-

EHK4-31

EHK4-46

EHK4-60 9.5
-

EHK4-31

EHK4-46

EHK4-60

-

EHK4-31

EHK4-46

4.3 EHK4-60 -

EHK4-31

EHK4-46

EHK4-60

-

EHK7-31

EHK7-46

EHK7-60 7.5
-

EHK7-31

EHK7-46

EHK7-60

-

EHK7-31

EHK7-46

3.5 EHK7-60 -

EHK7-31

EHK7-46

EHK7-60

KW*
21.6 / 28.8 32.4 / 43.2 43.3 / 57.6
21.6 / 28.8 32.4 / 43.2 43.3 / 57.6
21.6 / 28.8 32.4 / 43.2 43.3 / 57.6
21.6 / 28.8 32.4 / 43.2 43.3 / 57.6
28.8 43.2 57.6
28.8 43.2 57.6
28.8 43.2 57.6
28.8 43.2 57.6
28.8 43.2 57.6
28.8 43.2 57.6
28.8 43.2 57.6
28.8 43.2 57.6

FLA
60.0 / 69.3 90.1 / 104 120 / 139
60.0 / 69.3 90.1 / 104 120 / 139
60.0 / 69.3 90.1 / 104 120 / 139
60.0 / 69.3 90.1 / 104 120 / 139
34.6 52.0 69.3
34.6 52.0 69.3
34.6 52.0 69.3
34.6 52.0 69.3
28.9 43.4 57.8
28.9 43.4 57.8
28.9 43.4 57.8
28.9 43.4 57.8

FLA
7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

MCA MOP

82.6 / 82.6 100 / 100

100 / 112 100 / 125

138 / 155 150 / 175

175 / 164 175 / 175

89.8 / 89.1 110 / 110

109 / 120 110 / 125

147 / 163 150 / 175

184 / 172 200 / 175

71.4 / 71.4 90 / 90

86.4 / 98.0 90 / 100

124 / 141 125 / 150

161 / 150 175 / 175

78.6 / 77.9 100 / 100

95.4 / 106 100 / 110

133 / 149 150 / 150

170 / 158 175 / 175

39.5

50

55.2

60

76.8

80

81.2

90

42.8

50

59.3

60

81.0

90

85.3

90

34.3

45

48.7

50

70.3

80

74.7

80

37.6

45

52.8

60

74.5

80

78.8

90

29.8

35

45.5

50

63.6

70

67.2

80

32.4

40

48.8

50

66.8

70

70.5

80

25.8

30

40.5

45

58.6

60

62.2

70

28.4

35

43.8

45

61.8

70

65.5

70

20

www.daikinac.com

SS-DBC15

Electrical Data ­ 20 Ton

MODEL NUMBER

ELECTRICAL RATING

COMPRESSOR CIRCUIT 1

COMPRESSOR CIRCUIT 2

OUTDOOR FAN MOTOR

INDOOR FAN MOTOR

OPTIONAL ELECTRIC HEAT

OPTIONAL POWERED UNIT POWER CONVENIENCE SUPPLY
OUTLET

RLA DBC2403S 208/230-3-60 34.0 DBC2403V 208/230-3-60 34.0 DBC2404S 460-3-60 16.0 DBC2404V 460-3-60 16.0 DBC2407S 575-3-60 12.9 DBC2407V 575-3-60 12.9

LRA
240.0 240.0 140.0 140.0 107.6 107.6

RLA
34.0 34.0 16.0 16.0 12.9 12.9

LRA
240.0 240.0 140.0 140.0 107.6 107.6

QTY HP FLA TYPE HP FLA MODEL KW* FLA

-

-

-

EHK3-31 21.6 / 28.8 60.0 / 69.3

EHK3-46 32.4 / 43.2 90.1 / 104

EHK3-60 43.3 / 57.6 120 / 139

2-speed

EHK3-75 54.1 / 72.0 150 / 173

3 0.33 2.0 High-Static 7.50 20.3

Belt-Drive

-

-

-

EHK3-31 21.6 / 28.8 60.0 / 69.3

EHK3-46 32.4 / 43.2 90.1 / 104

EHK3-60 43.3 / 57.6 120 / 139

EHK3-75 54.1 / 72.0 150 / 173

-

-

-

EHK3-31 21.6 / 28.8 60.0 / 69.3

EHK3-46 32.4 / 43.2 90.1 / 104

EHK3-60 43.3 / 57.6 120 / 139

3

0.33

2.0

2-speed Belt-Drive

EHK3-75 54.1 / 72.0

5.00 14.0

-

-

150 / 173 -

EHK3-31 21.6 / 28.8 60.0 / 69.3

EHK3-46 32.4 / 43.2 90.1 / 104

EHK3-60 43.3 / 57.6 120 / 139

EHK3-75 54.1 / 72.0 150 / 173

-

-

-

EHK4-31 28.8

34.6

EHK4-46 43.2

52.0

EHK4-60 57.6

69.3

2-speed

EHK4-75 72.0

86.6

3 0.33 0.9 High-Static 7.50 9.5

Belt-Drive

-

-

-

EHK4-31 28.8

34.6

EHK4-46 43.2

52.0

EHK4-60 57.6

69.3

EHK4-75 72.0

86.6

-

-

-

EHK4-31 28.8

34.6

EHK4-46 43.2

52.0

EHK4-60 57.6

69.3

3

0.33 0.9

2-speed Belt-Drive

5.00

6.6

EHK4-75 -

72.0 -

86.6 -

EHK4-31 28.8

34.6

EHK4-46 43.2

52.0

EHK4-60 57.6

69.3

EHK4-75 72.0

86.6

-

-

-

EHK7-31 28.8

28.9

EHK7-46 43.2

43.4

EHK7-60 57.6

57.8

2-speed

EHK7-75 72.0

72.3

3 0.33 0.7 High-Static 7.50 7.5

Belt-Drive

-

-

-

EHK7-31 28.8

28.9

EHK7-46 43.2

43.4

EHK7-60 57.6

57.8

EHK7-75 72.0

72.3

-

-

-

EHK7-31 28.8

28.9

EHK7-46 43.2

43.4

EHK7-60 57.6

57.8

3

0.33

0.7

2-speed Belt-Drive

5.00

5.2

EHK7-75 -

72.0 -

72.3 -

EHK7-31 28.8

28.9

EHK7-46 43.2

43.4

EHK7-60 57.6

57.8

EHK7-75 72.0

72.3

FLA
7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

MCA MOP

103 / 103 125 / 125

103 / 112 125 / 125

138 / 155 150 / 175

175 / 164 175 / 175

175 / 199 200 / 225

110 / 109 125 / 125

110 / 120 125 / 125

147 / 163 150 / 175

184 / 172 200 / 175

184 / 207 200 / 225

96.4 / 96.4 125 / 125

96.4 / 104 125 / 125

130 / 147 150 / 150

168 / 156 175 / 175

168 / 191 200 / 225

104 / 103 125 / 125

104 / 112 125 / 125

139 / 156 150 / 175

177 / 164 200 / 175

177 / 199 200 / 225

48.1

60

55.2

60

76.8

80

81.2

90

98.5

110

51.4

60

59.3

60

81.0

90

85.3

90

103

110

45.2

60

51.6

60

73.2

80

77.5

90

94.9

110

48.5

60

55.7

60

77.3

80

81.7

90

99.0

110

38.7

50

45.5

50

63.6

70

67.2

80

81.7

90

41.3

50

48.8

50

66.8

70

70.5

80

84.9

100

36.4

45

42.6

45

60.7

70

64.3

70

78.8

90

39.0

50

45.9

50

64.0

70

67.6

80

82.0

90

SS-DBC15

www.daikinac.com

21

Electrical Data ­ 25 Ton

MODEL NUMBER

ELECTRICAL RATING

COMPRESSOR CIRCUIT 1

COMPRESSOR CIRCUIT 2

OUTDOOR FAN MOTOR

INDOOR FAN MOTOR

OPTIONAL ELECTRIC HEAT

OPTIONAL POWERED UNIT POWER CONVENIENCE SUPPLY
OUTLET

RLA DBC3003S 208/230-3-60 48.1 DBC3003V 208/230-3-60 48.1 DBC3004S 460-3-60 18.6 DBC3004V 460-3-60 18.6 DBC3007S 575-3-60 14.7 DBC3007V 575-3-60 14.7

LRA
245.0 245.0 125.0 125.0 100.0 100.0

RLA
48.1 48.1 18.6 18.6 14.7 14.7

LRA QTY HP FLA TYPE HP FLA MODEL KW* FLA

-

-

-

EHK3-31 21.6 / 28.8 60.0 / 69.3

EHK3-46 32.4 / 43.2 90.1 / 104

245.0

EHK3-60 43.3 / 57.6 120 / 139

2-speed

EHK3-75 54.1 / 72.0 150 / 173

2 1.00 4.2 High-Static 7.50 21.0

Belt-Drive

-

-

-

EHK3-31 21.6 / 28.8 60.0 / 69.3

EHK3-46 32.4 / 43.2 90.1 / 104

EHK3-60 43.3 / 57.6 120 / 139

EHK3-75 54.1 / 72.0 150 / 173

-

-

-

EHK3-31 21.6 / 28.8 60.0 / 69.3

EHK3-46 32.4 / 43.2 90.1 / 104

EHK3-60 43.3 / 57.6 120 / 139

245.0

2

1.00 4.2

2-speed Belt-Drive

EHK3-75 54.1 / 72.0

7.50 21.0

-

-

150 / 173 -

EHK3-31 21.6 / 28.8 60.0 / 69.3

EHK3-46 32.4 / 43.2 90.1 / 104

EHK3-60 43.3 / 57.6 120 / 139

EHK3-75 54.1 / 72.0 150 / 173

-

-

-

EHK4-31 28.8

34.6

EHK4-46 43.2

52.0

EHK4-60 57.6

69.3

2-speed

EHK4-75 72.0

86.6

125.0 2 1.00 2.1 High-Static 7.50 10.1

Belt-Drive

-

-

-

EHK4-31 28.8

34.6

EHK4-46 43.2

52.0

EHK4-60 57.6

69.3

EHK4-75 72.0

86.6

-

-

-

EHK4-31 28.8

34.6

EHK4-46 43.2

52.0

EHK4-60 57.6

69.3

125.0

2

1.00 2.1

2-speed Belt-Drive

EHK4-75 7.50 10.1
-

72.0 -

86.6 -

EHK4-31 28.8

34.6

EHK4-46 43.2

52.0

EHK4-60 57.6

69.3

EHK4-75 72.0

86.6

-

-

-

EHK7-31 28.8

28.9

EHK7-46 43.2

43.4

EHK7-60 57.6

57.8

2-speed

EHK7-75 72.0

72.3

100.0 2 1.00 1.6 High-Static 7.50 8.2

Belt-Drive

-

-

-

EHK7-31 28.8

28.9

EHK7-46 43.2

43.4

EHK7-60 57.6

57.8

EHK7-75 72.0

72.3

-

-

-

EHK7-31 28.8

28.9

EHK7-46 43.2

43.4

EHK7-60 57.6

57.8

100.0

2

1.00 1.6

2-speed Belt-Drive

7.50

8.2

EHK7-75 -

72.0 -

72.3 -

EHK7-31 28.8

28.9

EHK7-46 43.2

43.4

EHK7-60 57.6

57.8

EHK7-75 72.0

72.3

FLA
7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 7.2 / 6.5 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

MCA MOP

138 / 138 175 / 175

138 / 138 175 / 175

139 / 156 175 / 175

176 / 165 200 / 175

176 / 199 200 / 225

145 / 144 175 / 175

145 / 144 175 / 175

148 / 164 175 / 175

185 / 173 200 / 175

185 / 208 200 / 225

138 / 138 175 / 175

138 / 138 175 / 175

139 / 156 175 / 175

176 / 165 200 / 175

176 / 199 200 / 225

145 / 144 175 / 175

145 / 144 175 / 175

148 / 164 175 / 175

185 / 173 200 / 175

185 / 208 200 / 225

56.1

70

56.1

70

77.6

80

81.9

90

99.2

110

59.4

70

60.1

70

81.7

90

86.0

90

103

110

56.1

70

56.1

70

77.6

80

81.9

90

99.2

110

59.4

70

60.1

70

81.7

90

86.0

90

103

110

44.6

50

46.4

50

64.5

70

68.1

80

82.5

100

47.2

60

49.6

60

67.7

70

71.3

80

85.8

100

44.6

50

46.4

50

64.5

70

68.1

80

82.5

100

47.2

60

49.6

60

67.7

70

71.3

80

85.8

100

22

www.daikinac.com

SS-DBC15

Electrical Heat

Heat Kit Electrical Data (Blower Only, Heat Mode)

DBC1803 @ 208 / 240V ­ 15 Tons

Model
EHK3-31 EHK3-46 EHK3-60

Recommended Airflow Range 5250 - 6750 CFM 5250 - 6750 CFM 5250 - 6750 CFM

DBC1804 @ 480V ­ 15 Tons

Model
EHK4-31 EHK4-46 EHK4-60

Recommended Airflow Range 5250 - 6750 CFM 5250 - 6750 CFM 5250 - 6750 CFM

DBC1807 @575V ­ 15 Tons

Model
EHK7-31 EHK7-46 EHK7-60

Recommended Airflow Range 5250 - 6750 CFM 5250 - 6750 CFM 5250 - 6750 CFM

DBC3003 @ 240 / 240V ­ 25 Tons

Model
EHK3-31 EHK3-46 EHK3-60 EHK3-75

Airflow Range
7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM

DBC3004@ 480V ­ 25 Tons

Model
EHK4-31 EHK4-46 EHK4-60 EHK4-75

airflow range
7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM

DBC2403 @ 208 / 240V ­ 20 Tons

Model
EHK3-31 EHK3-46 EHK3-60 EHK3-75

Recommended Airflow Range 7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM

DBC2404 @ 480V ­ 20 Tons

Model
EHK4-31 EHK4-46 EHK4-60 EHK4-75

Recommended Airflow Range 7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM

DBC2407 @575V ­ 20 Tons

Model

Recommended Airflow Range

EHK7-31

7200 - 8500 CFM

EHK7-46

7200 - 8500 CFM

EHK7-60

7200 - 8500 CFM

EHK7-75

7200 - 8500 CFM

Note: When using electric heat kit, the single-point kit installed in the unit is needed to meet UL requirements.

kW Correction Factors
kW Correction Factor (for 208/230V Units) Supply Voltage 240 230 220 210 208 Correction Factor 1 0.92 0.84 0.77 0.75

kW Correction Factor (for 460V Units)

Supply Voltage

460 440 430

Correction Factor 0.92 0.84 0.8

DBC3007@ 575V ­ 25 Tons

Model
EHK7-31 EHK7-46 EHK7-60 EHK7-75

airflow range
7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM 7200 - 8500 CFM

kW Correction Factor (for 575V Units)

Supply Voltage

560 550 540

Correction Factor

0.95 0.91 0.88

SS-DBC15

www.daikinac.com

23

Wire Diagram

DBC 15 & 20 Tons (230V/460V/575V, Two-Speed Belt-Drive)

CCHR1

1

6

OR

2

4

BK BK

BK

CCHR2

1

6

BL BL
PU YL

2

4

BK

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power 
sourcesmaybepresent.Failuretodosomaycausepropertydamage,personalinjury,ordeath.

RD

OR

BK
BL RD RD
YL

CCH1

T3

COMP

T2

1 T1

CCH2

T3

COMP

T2

2 T1

12

YL

13

YL

11

YL

HIGH EM
LOW

BK

BK BK

2

3

1

YL RD BK

T3

L3

T2

L2

CC1

T1

L1

YL RD BK

T3

L3

T2

L2

CC2

T1

L1

BL

L3 L2 L1 T3 T2 T1 PU

OR RD BK
GY BL YL

L3 L2 L1 T3 T2 T1

CB1 HIGH SPEED
OR RD
BK
CB2 LOW SPEED
GY BL
YL

BL

T3

L3

T2

L2

BC1

T1

L1

T3

L3

T2

L2

BC2

T1

L1

OR BL
BK RD
BK

BL

TR

1

2

3

C

208 460

240 575

24V

GR

PK

BL

YL

BL PU

23

41

BL

HPS2

BL CCR1
YL BL
CCR2

YL

3 NC 5

4

2 NO

1

BL

BR2

BL

GR
SEE NOTE 5 PK

OR BK
OR

BK BK
RD BK

OR RD
BK

OR OR

OR RD

5

GR

3 NC

4

YL

GR

2 NO

1

GR

GR

BR1

GR

BK RD

BK

PB

RD

OR OR

POWER SUPPLY SEE NOTE 4
208V-240V-460V-575V 3 ph - 60Hz
GRND

BK

RD

PU

C

FC1

BR

F

RD

PU

C

FC2

BR

F

PU BR

C FC3
F

RD BK

BR PU BR PU

PU BR

TB2

BK BK
BK BK

CM3

BR PU

CM2

SEE NOTE 3

YL RD

PU

BL

PK

PLF 2
WH 3 6 9
258 BL
147

WH

HPS1

YL

YL

WH PU

23 41

YL LPS2
YL LPS1

RD GR
RD

PU YL

 Warning

0140L03208-A
24

PK PU PU

WH

PLF 1

123

456

789

RD

PU BR RD

BL WH

RD GR

PU

RD

BR

RD RD RD BL

GR BL GR

BL

WH

YL YL

YL

PU

WH BR

PU PU

TB1

S1

S2

R

C

G

W1 W2 Y1

Y2

O

RD

WH

SEE NOTE 4
REPLACE JUMPER WITH SMOKE/FIRE DETECTOR

TO THERMOSTAT BR

RD

GR

G

RD BR

R XFMR-R XFMR-C

EBTDR NOTE #2

BL C
BL
SPEED UP

K1 K1 M1

BR PU

www.daikinac.com

BR PU

CM1

RD

NO COM NC
M2

GR PU

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

SS-DBC15

Wire Diagram

DBC 15 & 20 Tons (230V/460V/575V, Two-Speed Belt-Drive cont.)

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power 
sourcesmaybepresent.Failuretodosomaycausepropertydamage,personalinjury,ordeath.

L1
SUPPLY VOLTAGE 208-240/460/575/3/60

CC1

T1

T2 T1 COMP1
T3

C CF1
F

CM1

T2

CC1

CC1 T3

C

CF2

F

C CF3
F

CM3

CC2

T2 T1
T1 COMP2
T3

T2

CC2

T3

CC2

CM2

L2

L3

COMPONENT LEGEND

BC BR CC CCH
CCHR CCR CM CMR
COMP ECON EBTD EMR
R EM FC GND HPS LPS PB PLF TB1 TB2 TR

BLOWER CONTACTOR BLOWER RELAY
COMPRESSOR CONTACTOR CRANK CASE HEATER CRANK CASE HEATER RELAY COMPRESSOR CONTACTOR RELAY CONDENSER MOTOR CONDENSER MOTOR RELAY
COMPRESSOR ECONOMIZER ELECTRONIC BLOWER TIME DELAY EVAPORATOR MOTOR RELAY RELAY EVAPORATOR MOTOR FAN CAPACITOR EQUPIMENT GROUND HIGH PRESSURE SWITCH LOW PRESSURE SWITCH POWER DISTRUBTION BLOCK FEMALE PLUG / CONNECTOR TERMINAL BLOCK (24V SIGNAL) TERMINAL BLOCK (L1) TRANSFORMER

BC2 BC1

CB2 CB1

HIGH SPEED

CCH1 CCH2

R

PLF1

7

4

8

5

9

6

LOW SPEED EM

CB2 CB2 CB1 CB1

BC2 BC2

BC1 BC1

CCHR1

2

1

EBTDR

2

1

208-240V 2

NOTE 5

CCHR2

3

1

TR 24V

R

G

C

EBTDR EBTDR
HPS1

BR1 2
4
5

BC1 BC2

1 BR1 3 1 BR2 3

BR2 2
4
5

LPS1

LPS2

HPS2

1

3

4

2

CCR1

CC1

CC2 4
1

2 3 CCR2

9

6

8

5

7

4

PLF2 3 2 1

6

4

CCHR2

6

4

CCHR1

SEE NOTE 3

TB1

S1

S2

R

C

G

W1 W2 Y1

Y2

O

RD

WH

THERMOSTAT ++

NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.
2. USE COPPER CONDUCTORS ONLY ++ USE N.E.C. CLASS 2 WIRE
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT, REMOVE MALE PLUG, ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY.
4. FOR TWO STAGE OPERATION REMOVE W1 TO W2 WIRE JUMPER.
5. FOR 208V OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON 240V TRANSFORMER

FACTORY WIRING LINE VOLTAGE LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING HIGH VOLATGE LOW VOLATGE

WIRE CODE

BK BLACK

BL

BLUE

BR BROWN

GR GREEN

OR ORANGE

PK PINK

PU PURPLE

RD RED

WH WHITE

YL YELLOW

YL/PK YELLOW WITH PINK STRIP

BL/PK BLUE WITH PINK STRIP

THERMOSTAT

++

FIELD WIRING

2 STAGE COOLING

W1 G R Y1 Y2 C O W2 TB1

WH GR RD YL PK BL OR BR

W1 G R Y1 Y2 C O W2 STAT

SEE NOTE 4
REPLACE JUMPER WITH SMOKE/FIRE DETECTOR

SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION

0140L02915-A

SS-DBC15

www.daikinac.com

25

 Warning

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

Wire Diagram

DBC 25 Tons (230V/460V/575V, Two-Speed Belt-Drive - Controls Diagram)

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power 
sourcesmaybepresent.Failuretodosomaycausepropertydamage,personalinjury,ordeath.

CLASS 2

FIELD CONTROL
WIRING

W1 W2

G

R

WH

Y2 YI

S2 S1 RD

TB1

C

4

5

WH WH

YL BR GR RD PU YL BK RD BL

BL RD

BK 3

TB3

RD RD

RD

YL YL

THERMOSTAT WIRING 2 STAGE COOLING

W

WH

W

G

GR

G

R

RD

R

Y1

YL

Y1

Y2

PK

Y2

C O TB1

BL

C

OR

O

STAT

CCR1

RD

2

4

BK

OR

5

6

YL

BL

1

3

BL

OR BK

CCR2

OR

2

4

BR

5

6

PU

BL

PU

1

3

BL

SMOKE DETECTOR

24V AC/DC

BL

10

PK

9

Y Y SENSOR 1 R

RD

16 AUX A

B

BR

6

Y

17

SENSOR 2 Y

R

8 AUX B

B

18

7

Y

Y R

SEN1

B

Y

Y R

SEN2

B

SMK DET OPTION

5
SUPPLY (LINE) VOLTAGE
TR1 RD
24 VAC

HPS1

LPS1

YL

YL

YL

YL

GR BL
YL

TB3 3
BL
BL CC1
BL

YL
BL BL
BK

BL

BL

FM1 1 2 3
PU

PLF PLM

RD

1

1

RD

RD

2

2

RD

WH WH
-t°

HPS2

LPS2

PU

PU

CC2

PU

BL

PU

BL

PU
BL BR

FM2
1 2 3

PLF PLM

OR

1

1

OR

OR

2

2

OR

WH WH
-t°

BL YL

BL

BL

YL

PU

CMC1

GY

GY

BL

CMR

PU

2

4

GY

RD

YL

5

6

GY

PU

RD

BL

BL

1

3

GY

WH WH BR GR

YL RD PU YL

RD RD PU YL

PU WH
YL

BR2

2

4

5

6

1

3

WH BR GR

RD PU YL

PU YL GR 3 21

PLM 3

3 2 1 PLF 3 RD RD PU YL GR

WH WH

YL
BL BL

BL GR

GR

BK

BK BR YL
BR

BR1

2

4

5

6

1

3

ECON ECON SHRT

PLF PLM

2

YL

1

PU

2

PU

3

YL 1
PU 2
PU 3

YL

4

YL 4

BL

5

5

GR

6

6

7

7

WH

8

8

RD

9

9

LAM1
1 2 3

PU

PLF PLM

BK

1

BK

2

1

BK

2

BK

WH WH
-t°

GR

BL

BL

BL

BR

BL

BL

CMC2

PU

BL

BL

BL

BL

BC2 LOW SPEED

BR

BL

BC1 HIGH SPEED BK

BL BL

BK BL

2

ECON PLM

1 2 3 4 5

6 7 8 9

GRD LUG

ECON MODULE

1

2 3 4

AUX2-I OCC E-GND

1 EXH1

MAT 1 MAT 2 OAT 1 OAT 2

2 AUX1-O

S-BUS 1

1 Y2-I

S-BUS 2

2 Y2-O 3 Y1-I 4 Y1-O

IAQ 2-10 IAQ COM
IAQ 24V

1 2 3

1C 2R

ACT COM 1 ACT 24V 2 3 4

MAS OD ENTH ECON
ACT
ECON OPTION

BL

BL

BL

RD YL
BK
OR

LAR

2

4

5

6

1

3

OR BK YL
RD

GY
BL BL

WH WH BR GR RD

RD

GR

GR

WH BL BR WH

PU RD

1 23 4 5678 9

HEAT PLF

RD RD RD
GR GR PU
RD
GR BL

EBTDR

XFMR-R 3A
R
G

XFMR-C C
SPEEDUP M1

(NC) COM

6

M2

(NO)

NOTES: 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF
INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY). 2. IF OPTIONAL ECONOMIZER IS INSTALLED, REMOVE ECON SHRT
PLM AND CONNECT ECON PLM TO ECON PLF. 3. TB3 LOW VOLTAGE TERMINAL BLOCK.4 TERMINALS FOR 24VAC
PWR (RD,BK,BR WIRE) AND 6 TERMINALS FOR 24VAC COM (BL WIRE). 4. CONNECTIONS SHOWN ARE FOR 1-STAGE HEAT OPERATION.
WHEN 2-STAGE OPERATION IS REQUIRED REMOVE WH JUMPER WIRE CONNECTING W2 TO W1 ON TB1. 5. IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RD JUMPER WIRE CONNECTING S1 TO S2 ON TB1 AND MAKE THE FOLLOWING WIRE CONNECTIONS: RD WIRE TO S1,BR WIRE TO TB3 (24V/PWR),BL WIRE TO TB3 (24V/COM).

OR BL

BL

GY

8

LAM2 1 2 3

WH WH

PLF 1 2

PLM 1 2

WH WH

LAT

BK

T1 T6

BL

8

YL

T2

9
RD BL

WH WH
-t°

BL

7 BL

LOW AMB OPTION

LA CMC

RD

BL

BL

BL

6. EBTDR RELAY ENERGIZES 7 SEC AFTER 24VAC IS APPLIED TO "G". THE RELAY DE-ENERGIZES 65 SEC AFTER 24VAC IS REMOVED FROM "G".

7. EBDTR RELAY DELAYS WILL DECREASE TO APPROX 3-5 SEC WHEN "SPEEDUP" IS SHORTED TO "C".

8. IF LOW AMBIENT KIT IS INSTALLED, CONNECT GY WIRE FROM LAM2-3 TO CMR-4. ALSO CONNECT BL COM WIRES FROM LAT-T6 AND LAM2 -2 TO TB3 (24V COM).

9. LAT ON/OFF TIME SETTINGS : ON -TIME (LEFT COLUMN) : 2,8 = ON OFF -TIME (RIGHT COLUMN) : 8 = ON ALL OTHER DIP SWITCHES = OFF

CONTROLS DIAGRAM DCC300***(3,4,7) V 2SPD EM

0140L04764-A

 Warning

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

26

www.daikinac.com

SS-DBC15

Wire Diagram

SS-DBC15

www.daikinac.com

BK

BK

OR

OR

TR2 2
3

TR1 2
3

PB L1 L2 L3

LINE VOLTAGE

BK RD OR BK RD OR

GND
BK RD OR

BK RD OR
BK RD OR

BM 3~ GR

BK(1) BK(3) BK(2)
YL(11) YL(13) YL(12)

CB

BK RD OR

LOW SPEED

BC1

YL

T1 L1

YL T1 L1 BK

BL

T2 L2

BL T2 L2 RD

GY

T3 L3

GY T3 L3 OR

BC2

BK

T1 L1

BK T1 L1 BK

RD

T2 L2

RD T2 L2 RD

OR

T3 L3

OR T3 L3 OR

CB HIGH SPEED

CCAS1

OR

L1 T1

GY

BK

CC1

BK

L1 T1

BK

RD

L2 T2

RD

OR

L3 T3

YL

CCAS2 RD

OR

L1 T1

BR

BK

CC2

BK

BK

L1 T1

BK

RD

L2 T2

RD

OR

L3 T3

YL

RD

BK CCH1
BK
GR

L1 L2

M 3~

COMP 1

L3

GR

BK CCH2
BK
GR

L1 L2

M 3~

COMP 2

L3

GR

CF HVTB BK

BK FC1

RD

BR

PU

BK L1 BR CAP PU L3

M 1~

CM1

GR

BK FC2

RD

BR

PU

BK L1 BR CAP PU L3

M 1~

CM2

GR

FC3

RD

BR

PU

BK L1 BR CAP PU L3

M 1~

CM3

GR

NOTES 1 REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION
AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. 2 TR1 & TR2 PRIMARY (HIGH VOLTAGE) CONNECTIONS: ORANGE WIRES CONNECTED TO 240/460/575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL. FOR 208V SUPPLY POWER, MOVE ORANGE WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS. 3 SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS 4 USE COPPER CONDUCTORS ONLY. UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS. THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT

COMPONENT LEGEND

BC

BLOWER CONTACTOR

BM

BLOWER MOTOR

CB

CIRCUIT BREAKER

CC

COMPRESSOR CONTACTOR

CCAS COMPRESSOR CONTACTOR AUXILIARY SWITCH

CCH

CRANKCASE HEATER

CF HVTB CONDENSER FAN HIGH VOLTAGE TERMINAL

BOARD

CM

CONDENSER MOTOR

CMC

CONDENSER MOTOR CONTACTOR

COMP COMPRESSOR

FC GND PB PLF PLM TR

FAN CAPACITOR EQUIPMENT GROUND POWER DISTRIBUTION BLOCK FEMALE PLUG/CONNECTOR MALE PLUG/CONNECTOR TRANSFORMER

WIRE CODE

BK BL BL/PK BR GR GY OR PK PU RD TN WH YL YL/PK

BLACK BLUE BLUE WITH PINK STRIPE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW YELLOW WITH PINK STRIPE

FACTORY WIRING HIGH VOLTAGE OPTIONAL HIGH VOLTAGE LOW VOLTAGE OPTIONAL LOW VOLTAGE CHASSIS GROUND

FIELD WIRING

HIGH VOLTAGE LOW VOLTAGE EARTH GROUND

POWER WIRING DIAGRAM DBC (180-240) ***V LINE VOLTAGE:
208-230/460/575V/3PH/60HZ

0140L07099-A

DDC Power Wiring Diagram DBC 180-240

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

 Warning

 High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.

27

Wire Diagram

28

www.daikinac.com

YL

YL

PK

PU

PU

G G0 U1 U2 U3 GND +VDC U4 GND U5 GND VG VG0 Y1 Y2 Y3 Y4 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 U6 U7 U8 GND ID9 ID10 ID11 ID12 IDC9 ID13H ID13 IDC13 ID14 ID14H

3 EPHLFK 1

2

3

4 BL

5 BR

BR

6 WH WH

7

8

9

2

ECON PLF

1 WH

2 GR

3 BR

4 RD

5

6

WH
BR 2 4 RD ESR

PK

PK WH BR TN PK BK

YL YL

PU PU

4

+ C1 NO1 NO2 NO3 C1 C4 NO4 NO5 NO6 C4 C7 NO7 C7 NO8 C8 NC8 C9 NO9 NO10 NO11 C9 NO12 C12 NC12 NO13 C13 NC13

J25

J12

J1

J2

J3

J13

J14

DDC CONTROLLER J4

J15 J5

J16

J17

J18

J6

J7

J8

GR WH BR RD

RD GR PU BK TN

U1 U3

RD

U2

GY BR U4

RD GRWH

PU PK BK YL PU Y4

BL OR YL WH
U6 U8
U7

BR OR GR GY
ID9 ID11
ID10

BR

WH

GR

YL A1 CC1 A2 BL PU A1 CC2 A2 BL
TN A1 BC1 A2 BL BK A1 BC2 A2 BL PK 1 ESR 0 BL

BL

YL PU

BL

LPS1

YL/PK

YL/PK

YL

YL

HPS1PK

PK

BL/PK

BL/PK

LPS2

YL/PK

YL/PK

PU

PU

HPS2 PK

PK

BL/PK

BL/PK

BCS

BK

BK

BK

RD

5a PLMES PLF

5b RD

1 1 RD 2 2 PK

3 3 RD

4 4 BL

BK

BK

YL

YL

PU

PU

BL

PK

PK

RD

PK

BL

TB1 XS XS ES ES ES ES ES ES ES C C C C C C C

RD RD GR GR

U1 U2 U3 U4 Y4 U6 U7 U8 ID9 ID10 ID11 PU BK TN GY PU OR WH YL BR GY OR

TB2 XS2 XS2 AG AG AG DAT OAT OAH CO2 ALM SPT SPA IAH RSS LDS CFS

COM

RD

TR1

NOTES 1 REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST
105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.

2 IF OPTIONAL ECONOMIZER IS INSTALLED INSERT PLM PLUG PROVIDED BY THE ECONOMIZER KIT

3 IF ELECTRIC HEAT IS INSTALLED, CONNECT EHK PLF TO ACCESSORY HEAT PLUG IN HEAT COMPARTMENT

4 FIELD WIRE BACNET MS/TP TO J25. SEE IO MANUAL FOR ADDITIONAL INFORMATION.

5a

IF OPTIONAL OEM SAFETY EQUIPMENT SUCH AS PHASE MONITOR, FLOAT SWITCH OR SMOKE DETECTOR ARE INSTALLED, UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE.

IF MULTIPLE SAFETIES ARE INSTALLED, PLUG IN THE ADDITIONAL DEVICES IN SERIES. PLUG IN

JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED.

5b IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED, CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT WIRE

6 OPTIONAL FACTORY INSTALLED EQUIPMENT

GR RD BL

COMPONENT LEGEND

ALM ALS BC BCS BM CB CC CFS CO2 CM CMC COMP DAT ECON EHK

ALARM AUXILIARY LIMIT SWITCH BLOWER CONTACTOR BLOWER CURRENT SWITCH BLOWER MOTOR CIRCUIT BREAKER COMPRESSOR CONTACTOR CLOGGED FILTER SWITCH CARBON DIOXIDE SENSOR CONDENSER MOTOR CONDENSER MOTOR CONTACTOR COMPRESSOR DISCHARGE AIR TEMPERATURE ECONOMIZER ELECTRIC HEATER KIT

BL

COM

TR2

GR RD GR

ES

EMERGENCY SHUTDOWN

RS

ROLLOUT SWITCH

ESR

EMERGENCY SHUTDOWN RELAY RSS

REMOTE START/STOP

FPS

FREEZE PROTECTION SWITCH

SPA

SETPOINT ADJUST

FS

FLAME SENSOR

SPT

SPACE TEMPERATURE

GND EQUIPMENT GROUND

TB

TERMINAL BLOCK

GV

GAS VALVE

TR

TRANSFORMER

HPS

HIGH PRESSURE SWITCH

VMC VENT MOTOR CONTACTOR

IAH

INDOOR AIR HUMIDITY

XS

TRANSFORMER POWER

LDS

LOAD SHEDDING

LPS

LOW PRESSURE SWITCH

LS

LIMIT SWITCH

OAT

OUTDOOR AIR TEMPERATURE

OAH OUTDOOR AIR HUMIDITY

PLF

FEMALE PLUG/CONNECTOR

PLM

MALE PLUG/CONNECTOR

PS

PRESSURE SWITCH

RD GR GR GR PU BK TN

OR WH

OAH

DAT

RD

VIN

OR

-t°

GR COM

GR

GR

OAT

TN VOUT

6

WH

WIRE CODE

-t°

BK

BLACK

BL

BLUE

BL/PK BLUE WITH PINK STRIPE

BR

BROWN

GR

GREEN

GY

GRAY

OR

ORANGE

PK

PINK

PU

PURPLE

RD

RED

TN

TAN

WH

WHITE

YL

YELLOW

YL/PK YELLOW WITH PINK STRIPE

FACTORY WIRING FIELD WIRING

HIGH VOLTAGE LOW VOLTAGE EARTH GROUND

SPT SEN + SEN - / SET SET +

OPTIONAL LOW VOLTAGE FIELD WIRING

ALM

RSS

V1 V2 TB2 - ALM

TB2 - AG

CO2

VIN

TB2 - XS2

COM

TB2 - AG

VOUT

TB2 - CO2

TB2 - RSS TB2 - XS2
IAH VIN COM VOUT

LDS
TB2 - LDS TB2 - XS2

CFS TB2 - CFS TB2 - XS2

TB2 - XS2 TB2 - AG TB2 - IAH

CONTROLS WIRING DIAGRAM DBC (180-240) ***V LINE VOLTAGE:
208-230/460/575V/3PH/60HZ 0140L07100-A

DDC Controls Wiring Diagram DBC 180-240

SS-DBC15

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

 Warning

 High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.

Wire Diagram

SS-DBC15

BK CCH1
BK GR
BK CCH2
BK GR

CCAS1

GY

T1 L1 BK

OR

CCAS2

BR

T1 L1

BK

OR

CM1

M 3~

L1 L2

L3 GR

CM1 PLM PLF BK 1 1 BR 2 2
PU 3 3

CMC1 BK T1 L1 BK BR T2 L2 RD YL T3 L3 OR

CM1 PLF

CMC1

12 3

T1 T2 T3

LACMC

4

BK T1 L1 BK BR T2 L2 BR

YL T3 L3 YL

CM2

M 3~

L1 L2

L3 GR

BK 1 1 BR 2 2 PU 3 3
PLM PLF CM2

BK T1 L1 BK BR T2 L2 RD PU T3 L3 OR
CMC2

PB L1 L2 L3

LINE VOLTAGE

BK RD OR

GND

OR

BK

BK

FB2

BK

RD

FB2

RD

OR

FB2

OR

BK RD OR

FB1 FB1 FB1

BK RD OR

BK

RD

OR BK RD

RD

BK

RD

BK

TR1

RD

BK

TR2

2

2

3

3

CC1

BK

L1 T1

BK

RD

L2 T2

RD

OR

L3 T3

YL

CC2

BK

L1 T1

BK

RD

L2 T2

RD

OR

L3 T3

PU

BC1 BK L1 T1 YL

CB LOW SPEED

L1 T1

YL

RD L2 T2 BL

L2 T2

BL

OR L3 T3 GY

L3 T3

GY

BC2 BK L1 T1 BK RD L2 T2 RD OR L3 T3 OR

L1 T1

BK

L2 T2

RD

L3 T3

OR

CB HIGH SPEED

L1

L2

M 3~

COMP 1

L3

GR

L1 L2

M 3~

COMP 2

L3

GR

BK (1) BK (3) BK (2)
YL(11) YL(13) YL(12)

BM 3~ GR

www.daikinac.com

DDC Power Wiring Diagram DBC 300

NOTES 1 REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION
AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. 2 TR1 & TR2 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRES CONNECTED TO 240/460/575V TAP AT THE FACTORY AND BLACK WIRES TO COM TERMINAL. FOR 208V SUPPLY POWER, MOVE RED WIRES FROM 240V TAP TO THE 208V TAP ON BOTH TRANSFORMERS. 3 SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS 4 IF LOW AMBIENT KIT IS INSTALLED, DISCONNECT CONDENSER MOTOR WIRES FROM CMC1(T1, T2, T3) AND CONNECT TO CORRESPONDING (BK, BR, YL) WIRES WITH QUICK CONNECT TERMINALS FROM LACMC (T1, T2, T3). CONNECT (BK, BR, YL) FROM LACMC (L1, L2, L3) TO CMC1 (T1, T2, T3). 5 USE COPPER CONDUCTORS ONLY. UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS. THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT

COMPONENT LEGEND

BC BM CB CC CCAS CCH CCX CM CMC COMP FB

BLOWER CONTACTOR BLOWER MOTOR CIRCUIT BREAKER COMPRESSOR CONTACTOR COMPRESS CONTACTOR AUXILIARY SWITCH CRANKCASE HEATER COMPRESSOR CONTACTOR AUXILIARY CONDENSER MOTOR CONDENSER MOTOR CONTACTOR COMPRESSOR FUSE BLOCK

FC GND LACMC PB PLF PLM TR

FAN CAPACITOR EQUIPMENT GROUND LOW AMBIENT CONDENSER MOTOR CONTACTOR POWER DISTRIBUTION BLOCK FEMALE PLUG/CONNECTOR MALE PLUG/CONNECTOR TRANSFORMER

WIRE CODE

BK BL BL/PK BR GR GY OR PK PU RD TN WH YL YL/PK

BLACK BLUE BLUE WITH PINK STRIPE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW YELLOW WITH PINK STRIPE

FACTORY WIRING HIGH VOLTAGE OPTIONAL HIGH VOLTAGE LOW VOLTAGE OPTIONAL LOW VOLTAGE CHASSIS GROUND

FIELD WIRING

HIGH VOLTAGE LOW VOLTAGE EARTH GROUND

POWER WIRING DIAGRAM DBC (300) ***V LINE VOLTAGE:
208-230/460/575V/3PH/60HZ

0140L07101-A

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

 Warning

 High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.

29

Wire Diagram

30

www.daikinac.com

LAM1 PLM PLF BK 1 1
BK 2 2

BK BK

WH

-t°WH

LAM1 1 2 3 GY
BL PU

3 EPHLFK 1

2

3

4 BL

BL

5 BR

BR

6 WH WH

7

8

9

-t° 3 21

LOW AMBIENT OPTION

LAM

PLM PLF 1 1 WH
2 2 WH

OR BL

WH

WH

LAM

WH

WH

LAR 4 2 RD
YL 4 5 BK

2

ECON PLF

1 WH

2 GR

3 BR

4 RD

5

6

WH GR
BR RD 2 4
ESR

OR 1 LAR 3 BL RD A1LACMCA2 BL
4 LAT YL T2 BK T1 T6 BL

GY GY

CMR 4 2 PU 4 5 YL

PK WH BR TN PK BK

YL YL

PU

5

+ C1 NO1 NO2 NO3 C1 C4 NO4 NO5 NO6 C4 C7 NO7 C7 NO8 C8 NC8 C9 NO9 NO10 NO11 C9 NO12 C12 NC12 NO13 C13 NC13

J25

J12

J1

J2

J3

J13

J14

DDC CONTROLLER J4

J15 J5

J16

J17

J18

J6

J7

J8

PK

BL GR WH BR RD

RD GR PU BK TN

U1 U3

RD

U2

GY BR U4

RD GRWH

PU PK BK YL PU Y4

BL OR YL WH
U6 U8
U7

BR OR GR GY
ID9 ID11
ID10

BL

BR

WH

GR

G G0 U1 U2 U3 GND +VDC U4 GND U5 GND VG VG0 Y1 Y2 Y3 Y4 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 U6 U7 U8 GND ID9 ID10 ID11 ID12 IDC9 ID13H ID13 IDC13 ID14 ID14H

YL PK PU

YL A1 CC1 A2 BL PU A1 CC2 A2 BL PK 1 ESR 0 BL TN A1 BC1 A2 BL BK A1 BC2 A2 BL PU 1 CMR 3 BL GY A1 CMC1A2 BL PU A1CMC2 A2 BL

BL

YL PU

FM1

FM1

YL 1 BL 2 YL 3

PLF PLM RD 1 1 RD
RD 2 2 RD

WH WH -t°

LPS1

YL/PK

YL/PK

YL

YL

HPS1PK

PK

BL/PK

BL/PK

FM2

FM2

PU 1 BL 2 PU 3

PLF PLM OR 1 1 OR OR 2 2 OR

WH WH -t°

LPS2

YL/PK

YL/PK

PU

PU

HPS2 PK

PK

BL/PK

BL/PK

BL

BL GY BCS

BK

BK

BK

RD

6a PLMES PLF

6b RD

1 1 RD 2 2 PK

3 3 RD

4 4 BL

BL

BK

YL

PU

BL

PK

PK

RD

PK

BL

TB1 XS XS ES ES ES ES ES ES ES C C C C C C C

RD RD GR GR

U1 U2 U3 U4 Y4 U6 U7 U8 ID9 ID10 ID11 PU BK TN GY PU OR WH YL BR GY OR

TB2 XS2 XS2 AG AG AG DAT OAT OAH CO2 ALM SPT SPA IAH RSS LDS CFS

COM

RD

NOTES

TR1

1 REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST

105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.

CB

GR

2 IF OPTIONAL ECONOMIZER IS INSTALLED INSERT PLM PLUG PROVIDED BY THE ECONOMIZER KIT

RD BL

3

IF ELECTRIC HEAT IS INSTALLED, CONNECT EHK PLF TO ACCESSORY HEAT PLUG IN HEAT COMPARTMENT

4 LAT ON/OFF TIME SETTINGS: ON-TIME (LEFT COLUMN): 2,8 = ON OFF-TIME (RIGHT COLUMN): 8 = ON ALL OTHER DIP SWITCHES OFF

5 FIELD WIRE BACNET MS/TP TO J25. SEE IO MANUAL FOR ADDITIONAL INFORMATION.

6a IF OPTIONAL OEM SAFETY EQUIPMENT SUCH AS PHASE MONITOR, FLOAT SWITCH OR SMOKE DETECTOR ARE INSTALLED, UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE. IF MULTIPLE SAFETIES ARE INSTALLED, PLUG IN THE ADDITIONAL DEVICES IN SERIES. PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED.

6b IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED, CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT WIRE

7 OPTIONAL FACTORY INSTALLED EQUIPMENT

COMPONENT LEGEND

ALM ALS BC BCS BM CB CC CFS CO2 CM CMC CMR COMP DAT ECON EHK

ALARM AUXILIARY LIMIT SWITCH BLOWER CONTACTOR BLOWER CURRENT SWITCH BLOWER MOTOR CIRCUIT BREAKER COMPRESSOR CONTACTOR CLOGGED FILTER SWITCH CARBON DIOXIDE SENSOR CONDENSER MOTOR CONDENSER MOTOR CONTACTOR CONDENSER MOTOR RELAY COMPRESSOR DISCHARGE AIR TEMPERATURE ECONOMIZER ELECTRIC HEATER KIT

BL

ES ESR FM FPS FS GND GV HPS HTR IAH LAM LAR LAT LACMC LDS

EMERGENCY SHUTDOWN

LPS

EMERGENCY SHUTDOWN RELAY LS

FREEZE STAT MODULE

OAT

FREEZE PROTECTION SWITCH

OAH

FLAME SENSOR

PLF

EQUIPMENT GROUND

PLM

GAS VALVE

PS

HIGH PRESSURE SWITCH

RS

HEATER

RSS

INDOOR AIR HUMIDITY

SPA

LOW AMBIENT

SPT

LOW AMBIENT RELAY

TB

LOW AMBIENT TIMER

TR

LOW AMBIENT CONDENSER MOTOR VMC

CONTACTOR

XS

LOAD SHEDDING

COM
CB RD

TR2
GR GR

LOW PRESSURE SWITCH LIMIT SWITCH OUTDOOR AIR TEMPERATURE OUTDOOR AIR HUMIDITY FEMALE PLUG/CONNECTOR MALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH REMOTE START/STOP SETPOINT ADJUST SPACE TEMPERATURE TERMINAL BLOCK TRANSFORMER VENT MOTOR CONTACTOR TRANSFORMER POWER

RD GR

GR PU BK TN

OR WH

DAT

-t°

GR

OAT

OAH

RD

VIN

GR COM

TN VOUT

7

SPT OR SEN + GR SEN - / SET WH SET +

WIRE CODE

-t°

BK

BLACK

BL

BLUE

BL/PK BLUE WITH PINK STRIPE

BR

BROWN

GR

GREEN

GY

GRAY

OR

ORANGE

PK

PINK

PU

PURPLE

RD

RED

TN

TAN

WH

WHITE

YL

YELLOW

YL/PK YELLOW WITH PINK STRIPE

FACTORY WIRING FIELD WIRING

OPTIONAL LOW VOLTAGE FIELD WIRING

HIGH VOLTAGE OPTIONAL HIGH VOLTAGE LOW VOLTAGE OPTIONAL LOW VOLTAGE CHASSIS GROUND

ALM V1 V2 TB1 - ALM
TB1 - AG CO2

RSS TB1 - RSS TB1 - XS2
IAH

VIN

TB1 - XS2

VIN

COM

TB1 - AG

COM

HIGH VOLTAGE LOW VOLTAGE

VOUT

TB1 - CO2

VOUT

EARTH GROUND

LDS
TB1 - LDS TB1 - XS2

CFS TB1 - CFS TB1 - XS2

TB1 - XS2 TB1 - AG TB1 - IAH

CONTROLS WIRING DIAGRAM DBC (300) ***V LINE VOLTAGE:
208-230/460/575V/3PH/60HZ 0140L07102-A

DDC Controls Wiring Diagram DBC 300

SS-DBC15

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

 Warning

 High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.

31

www.daikinac.com

SS-DBC15

TOP VIEW

50.750

FORK HOLES BOTH SIDES AND CONDENSER END
LIFT SHACKLE HOLES BOTH SIDES AND ENDS

CONDENSATE DRAIN OUTLET THIS SIDE ONLY
133.354

BACK VIEW

35.551

7.017

ALL DIMENSIONS ARE GIVEN IN INCHES ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION

LINE WIRE ENTRANCE
88.116 LEFT END VIEW
DB* 180/240***
15 AND 20 TON COMERCIAL

DISCONNECT SWITCH LOCATION (if applicable)
TSTAT WIRE ENTRANCE
18.579 8.204
3.058 8.949 12.137

Dimensional Data

SS-DBC15

www.daikinac.com

32

TOP VIEW

53.212

FORK HOLES BOTH SIDES AND CONDENSER END
LEFT SHACKLE HOLES BOTH SIDES AND ENDS

CONDENSATE DRAN OUTLET THIS SIDE ONLY
133.354

BACK VIEW

ALL DIMENSION GIVEN ARE IN INCHES ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

50.750

35.551

7.017

88.116 LEFT END VIEW

LINE WIRE ENTRANCE
TSTAT WIRE ENTRANCE

12.125

8.204 3.058

DB *300*** 25-TON COMMERCIAL

Dimensional Data

Unit Clearances
Electrical Entrance Locations

12"

2 x 21" 7"
22" 48"

2 x 60"
Return

3"

High-Voltage

22"

Entrance

Low-Voltage

Entrance

3"

Supply

Service Clearance
Allow for recommended service clearances as shown in the image below. In situations that have multiple units, a 36" minimum clearance is required between the condenser coils. A clearance of 48" is recommended on all sides of the unit to allow service access and to ensure proper ventilation and condenser airflow. The top of the unit should be unobstructed. Provide a roof walkway along the sides of the unit for service and access to controls and components. Contact your Daikin sales representative for service requirements less than those recommended.

75" 6"

48"

3366""MMINIIMNUIMMUM

48"

RROOOOFFOOVEVREHARNHGANG

SS-DBC15

www.daikinac.com

33

Installation

Unit Location

The structural engineer must verify that the roof has adequate support and ability to minimize deflection. Take extreme caution when using on a wooden roof structure. Unit condenser coils should be in a location that avoids any heated exhaust air.

Allow sufficient space around the unit for maintenance/service clearance. Consult your Daikin sales representative if available clearances do not meet minimum recommendations.

Where code considerations, such as the NEC, require extended

clearances, these take precedence.

Provisions for forks have been included in the unit A

C

base frame. No other fork locations are approved.

» Unit must be lifted by the four lifting holes located at the base frame corners.

40Y"

CCOoMmPpRrEeSssSoOrR1 1

Supply EVEAvPapOoRrAaTtOorR CCoiOlILS
Return

» Lifting cables should be attached to the unit

with shackles.

CG

» The distance between the crane hook and the top of

the unit must not be less than 60".

» Two spreader bars must span over the unit to prevent

damage to the cabinet by the lift cables. Spreader

bars must be of sufficient length so that cables do

not come in contact with the unit during transport.

CCOomMpPrReEsSsoSrO2R 2

Remove wood struts mounted beneath unit base

frame before setting unit on roof curb. These struts are intended to protect unit base frame from forklift

B

6X0"

D

damage. To remove the struts, extract the sheet

Corner & Center-of-Gravity Locations

metal retainers and pull the struts through the base of the unit.

Refer to rigging label on the unit.

Important: If using bottom discharge with roof curb, duct-work should be attached to the curb prior to installing the unit. Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual. Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower than the supply air end. Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, take care to center the unit. Check for proper alignment and orientation of supply and return openings with duct. For further and more detailed information please refer to our Daikin Light Commercial Packaged unit IOD.

Roof Curb Installation
The roof curb is field-assembled and must be installed level (within 1/16" per foot side to side). A sub-base must be constructed by the contractor in applications involving pitched roofs. Gaskets are furnished and must be installed between the unit and curb. For proper installation, follow NRCA guidelines. In appCliocrantieorn&s Creeqnuteirri-nogf-pGorsatviatyndLorcaaitlioinnsstallation, an I-beam securely mounted on multiple posts should support the unit on each side. In addition, the insulation on the underside of the unit should be protected from the elements. Applications in geographic areas subjected to seismic or hurricane conditions must meet code requirements for fastening the unit to the curb and the curb to the building structure.

Weights

15-Ton Units Weight A Weight B Weight C Weight D Shipping Weight Operating Weight

Weights (lbs.) 590 482 492 401 2080 1965

20-Ton Units Weight A Weight B Weight C Weight D Shipping Weight Operating Weight

Weights (lbs.) 644 525 504 412 2202 2085

Note: These weights are calculated without installed accessories.

25-Ton Units Weight A Weight B Weight C Weight D Shipping Weight Operating Weight

Weights (lbs.) 626 464 501 518 2377 2109

34

www.daikinac.com

SS-DBC15

Accessories

Daikin Master Item #

Description

Curb

14CURB180300

14" Roof Curb

18CURB180300

18" Roof Curb

24CURB180300

24" Roof Curb

GHRC-180300

Hurricane Restraint Clips Downflow Economizer & Power Exhaust1

0270L02330

Low-Leak (Title 24) Downflow Economizer w/ Enthalpy Sensor

0270L02333

Low-Leak (Title 24) Downflow Economizer w/ Enthalpy Sensor, Hood for 0270L02330

SPE1803002

Downflow Power Exhaust 208/230v

SPE1803004

Downflow Power Exhaust 460v

SPE1803007

Downflow Power Exhaust 575v Horizontal Economizer & Power Exhaust1

SHZECNJ180300B Low-Leak (Title 24) Internal Horizontal Economizer w/ Enthalpy Sensor

SHPE1803002

Horizontal Power Exhaust 208/230v

SHPE1803004

Horizontal Power Exhaust 460v

SHPE1803007

Horizontal Power Exhaust 575v

Downflow Accessories

S25FD180300

25% Manual Fresh Air Damper

S25MFD180300

25% Motorized Fresh Air Damper

S50MFD180300

50% Motorized Fresh Air Damper

DNBBS180300

Burglar Bar Sleeves with Supply and Return

Horizontal Accessories

SBRD180300

Barometric Relief

HZCURB180300EDR Horizontal Curb End Discharge Roofed In

HZCURB180300NSR Horizontal Curb Non-Service Side Discharge Roofed In

HZCURB180300SSR Horizontal Curb Service Side Discharge Roofed In

HZCURB180300EDS Horizontal Curb End Discharge Slab Mount

HZCURB180300NSS Horizontal Curb Non-Service Side Discharge Slab Mount

HZCURB180300SSS Horizontal Curb Service Side Discharge Slab Mount

SHZE25FD180300 Horizontal Fresh Air Damper 25%

SHZRETPNL180300 Horizontal Return Panel

Concentrics

CDK300-530

Concentric Duct Kit Step-Down Diffuser

CDK180

Concentric Duct Kit

CDK240

Concentric Duct Kit

CDK300

Concentric Duct Kit Flush Mount Diffuser

High-Static Kits

High-Static, factory-installed, 230V

High-Static, factory-installed, 460V

High-Static, factory-installed, 575V

High-Static, factory-installed, 230V

High-Static, factory-installed, 460V

High-Static, factory-installed, 575V

High-Static, factory-installed, 25 ton, all voltages

Accessories availability may vary.

Fits Model Sizes

FieldInstalled

15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



15-25 tons



25 tons



15 tons



20 tons



25 tons



15 ton 15 ton 15 ton 20 ton 20 ton 20 ton 25 ton

Factory- Operating Installed Weight (lbs)

285 315 360 2



281



98 98 98

416 200 200 200

34 42 42 60

30 950 950 950 850 850 850 75 50

244 158 197 244



50



50



50



50



50



50



8

SS-DBC15

www.daikinac.com

35

Accessories

Daikin Master Item #
EHK3-31 EHK3-46 EHK3-60 EHK3-75 EHK4-31 EHK4-46 EHK4-60 EHK4-75 EHK7-31 EHK7-46 EHK7-60 EHK7-75
0160L00202 0160L00201
LAKT23 LAKT24 LAKT25 LAKT05 3PMNDK01
FSKT02A DT4272C DT4273C PSPAC-WS 250803400

Description
3-Phase 208-230V Electric Heat Kits 30kw 208-230v 3ph Electric Heat Kit 40kw 208-230v 3ph Electric Heat Kit 60kw 208-230v 3ph Electric Heat Kit 75kw 208-230v 3ph Electric Heat Kit 3-Phase 460V Electric Heat Kits 30kw 460v 3ph Electric Heat Kit 40kw 460v 3ph Electric Heat Kit 60kw 460v 3ph Electric Heat Kit 75kw 460v 3ph Electric Heat Kit 3-Phase 575V Electric Heat Kits 30kw 575v 3ph Electric Heat Kit 40kw 575v 3ph Electric Heat Kit 60kw 575v 3ph Electric Heat Kit 75kw 575v 3ph Electric Heat Kit High-Static Kits High-Static, factory-installed, 230V High-Static, factory-installed, 460V High-Static, factory-installed, 575V High-Static, factory-installed, 230V High-Static, factory-installed, 460V High-Static, factory-installed, 575V High-Static, factory-installed, 25 ton, all voltages High-Efficiency Filters High-Efficiency MERV 13 Air Filter Nom. Size: 20x25x2; (Order Qty 6) High-Efficiency MERV 13 Air Filter Nom. Size: 20x20x2; (Order Qty 8) Misc Accessories Convenience Outlet: Powered 208/230v, 460v Convenience Outlet: Powered 575v Convenience Outlet: Non Powered Disconnect Switch (non-fused) Low-Ambient Kit, 208-230V- non-DDC Low-Ambient Kit, 460V- non-DDC Low-Ambient Kit, 575V- non-DDC Low-Ambient Kit (all voltages)- non-DDC Phase Monitor- Non DDC Smoke Detector (supply and/or return air) Hinged Panels Freeze Stat Kit2 Controls, Thermostats and Sensors Comm Touch Digital Stat w/ WiFi 4h/2c Comm Touch Digital Stat w/ WiFi & Humidity Control 4h/2cc Remote indoor sensor AppStatTM RTU 2H/2C Econ

Fits Model Sizes

FieldInstalled

Factory- Operating Installed Weight (lbs)

15-25 tons



15-25 tons



15-25 tons



20- 25 tons





21



21



21



21

15-25 tons



15-25 tons



15-25 tons



20- 25 tons





21



21



21



21

15-25 tons



15-25 tons



15-25 tons



20- 25 tons





21



21



21



21

15 ton 15 ton 15 ton 20 ton 20 ton 20 ton 25 ton



80



80



80



50



50



50



8

15, 20 tons



9

25 tons



11

15-25 tons

15-25 tons

15-25 tons

15-25 tons

15-20 tons



15-20 tons



15-20 tons



25 tons



15-25 tons



15-25 tons

15-25 tons

25 tons





42



42



2



5



32



32



32



2



2



11



34

1

3-25 ton



1

3-25 ton



1

3-25 ton



1

3-25 ton



1

36

www.daikinac.com

SS-DBC15

Accessories

Daikin Master Item #

Description

D4271C

4h/2c Commercial 7day Programmable Wi-Fi Capable thermostat

D4272C

4h/2c Commercial 7day Programmable Wi-Fi Capable Hum/dehum thermostat

C7232A1024

CO2 Sensor (Wall Mtd)

C7232B1022

CO2 Sensor (Duct Mtd)

D2270C

Mini Wi-Fi Thermostat

TSTATD2152-2

Value Series 2h/1c 5+2 prgm (Heat Pump)

TSTATD2100-2

Value Series 2h/1c No prgm (Heat Pump)

TSTATD1100-2

Value Series 1h/1c No prgm

TSTATD1152-2

Value Series 1h/1c 5+2 prgm

PSPAC-AW

Add-A-Wire

PSPAC-2W

2-Wire Kit

PSPAC-OS

Wired Indoor / Outdoor Remote Sensor

PSPAC-DS

Wired Duct Sensor

PSPAC-WFMS

Wireless Wi-Fi Mini Sensor

PSPAC-LR

Lock Ring for Premium Commercial Thermostats

PSPAC-PWF

Wi-Fi Module

PSPAC-WP

Wall Plate- Premium & Value Series

PSPAC-WPT

Wall Plate Color Touch Screen

PSPAC-WPM-S

Wall Plate Premium Mini- Small

PSPAC-WPM-M

Wall Plate Premium Mini- Medium

PSPAC-WPM-L

Wall Plate Premium Mini- Large

C7400S1000

Differential Enthalpy Sensor

D4120

Smoke Detector- Duct Mounted

D4120W

Smoke Detector- Watertight

DDC Accessories

0130M00584

DDC LonWorks® comm card

0130L00220

DDC Space CO2 Sensor Duct Mounted

0130L00221

DDC Space Enthalpy Sensor Duct Mounted

0130L00222

DDC Space dry-bulb Sensor 4" Duct Mounted

0130L00223

DDC OD Enthalpy Sensor

0130L00224

DDC Space Enthalpy Sensor Wall-mounted

0130L00225

DDC Space CO2 Sensor Wall-Mounted

0130L00226

DDC Space dry-bulb Sensor Wall-Mounted

0130L00228

DDC Space dry-bulb Sensor 8" Wall-Mounted

0270L02252

DDC Low-Leak (Title 24) Downflow Economizer w/ dry-bulb Sensor

DLAKT23

DDC Low Ambient Kit 230V

DLAKT24

DDC Low Ambient Kit 460V

DLAKT25

DDC Low Ambient Kit 575V

LAKT300DDC

DDC Low Ambient Kit

3PMNDK03

Phase Monitor DDC ASSY

1 Use Economizer & Power Exhaust listed within Low-Leak section 2 FSK02A is standard on 2-Speed, V, models. Note: Where multiple variations are available, the heaviest combination is listed.

Accessories availability may vary.

Fits Model Sizes
3-25 ton
3-25 ton
3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton 3-25 ton

FieldInstalled


                     

Factory- Operating Installed Weight (lbs)
1
1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

15-25 ton



1

15-25 ton



1

15-25 ton



1

15-25 ton



1

15-25 ton



1

15-25 ton



1

15-25 ton



1

15-25 ton



1

15-25 ton



1

15-25 ton



281

15-20 ton



32

15-20 ton



32

15-20 ton



32

25 ton



32

15-25 ton



2

SS-DBC15

www.daikinac.com

37

Factory and Field Installed Options

Factory Installed Options
» High-Static Kit: Allows for operation in higher static applications.
» Non-Powered Convenience Outlet: A 120V, 15A, GFCI outlet can be installed in the unit making it easier for technicians to service other units once an electrician runs power to the outlet. Outlet shall be factory-installed and internally mounted with easily accessible 115-v female receptacle. Transformer not included for this option. Outlet shall include a field-installed "While-in-use" cover.
» Powered Convenience Outlet: A 120V, 15A, GFCI outlet can be powered with a step-transformer built into the unit. For use when the unit is not running. When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units; increase by 3.75A for 460V units; and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly. Outlet shall be powered from main line power to the rooftop unit. Outlet shall include a fieldinstalled "While-in-use" cover.
» Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors can be installed in the unit. To safely identify the presence of smoke inside the air conditioning system and shutdown the blower to prevent the smoke to disperse into different zones.
» Disconnect Switch (non-fused): A disconnect switch can be installed in the unit with factory wiring complete from the switch to the unit. Please note that for air conditioner and heat pump units, the appropriate electric heat kit must be ordered along with the disconnect switch (non-fused) to be factoryinstalled. For models with a powered convenience outlet option and a disconnect switch (non-fused) option, the power to the powered convenience outlet will be shut off when the disconnect switch (non-fused) is in the off position. National Electric Code (NEC) and UL approved non-fused switch shall provide unit power shutoff. The switch shall be accessible from outside of the unit and provide local shutdown and lockout capability.
» Hinged Access Panels: Allows access to unit's major components. Combined with latches for easy access to control box, compressor, filters and blower motor.
» Electromechanical Controls: Basic controls that include terminal block for unit connectivity to T-Stat.
» iLINQ DDC Controls: Equipped with built-in BACnetTM IP and MS/TP interface or it can be used with an optional LonWorks® card that is available to integrate the Daikin RTU with building automation systems (BMS).

Field Installed Options
» Power Exhaust: Power exhaust shall be used in conjunction with an integrated economizer. This accessory exhausts return air and may be used in either downflow or horizontal (duct-mounted) applications. Horizontal power exhaust is mounted in return ductwork. Power exhaust shall be controlled by economizer controller operation. Exhaust fans shall be energized when dampers open past the 0-100% adjustable setpoint on the economizer control. (Damper to be field installed, all wiring and accessory set up is factory installed)
» Manual Fresh Air Damper: Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to admit up to 25% outdoor air for year round ventilation.
» Motorized Fresh Air Damper: A two-position damper with rain hood and screen provides 50% outside air when the indoor fan starts and closes when the indoor fan shuts down. Consist of actuator, damper, air inlet screen, and rain hood. Damper shall close upon indoor (evaporator) fan shutoff and/or loss of power. The damper actuator shall plug into the rooftop unit's wiring harness plug. No hard wiring shall be required.
» Horizontal Economizer: Fully modulating between 0 and 100%, contain seals that meet ASHRAE 90.1 requirements. Includes motor and dampers, minimum position settings, preset linkage, wiring harness with plug, mixed air temperature sensor, and enthalpy control. An optional duct-mounted barometric relief damper is available. An optional return enthalpy sensor is available to provide comparative or differential enthalpy control. Damper blades shall be galvanized steel with composite gears. Plastic or composite blades on intake or return shall not be acceptable. Standard leak rate shall be equipped with dampers not to exceed 2% leakage at 1 in. wg pressure differential. Low Leak design meets California Title 24 section 140.4 and ASHRAE 90.1 requirements for 4 cfm per sq. ft. on the outside air dampers and 10 cfm per sq. ft. on the return dampers. Shall be designed to close damper(s) during loss-of-power situations with spring return built into motor. Economizer controller shall accept a 2-10 Vdc CO2 sensor input for IAQ/DCV control. In this mode, dampers shall modulate the outdoor air damper to provide ventilation based on the sensor input.
» Economizer controller shall be Honeywell® JADE® W7220 that provides:
- 2-line LCD interface screen for setup, configuration and troubleshooting.
- On-board Fault Detection and Diagnostics (FDD) that senses and alerts when the economizer is not operating properly, per California Title 24.
- Sensor failure loss of communication identification
- Automatic sensor detection
- Capabilities for use with multiple-speed indoor fan systems
- Utilize digital sensors: Dry bulb and Enthalpy
- Economizer controller shall provide indications when in free cooling mode, in the DCV mode, or the exhaust fan contact is closed.

38

www.daikinac.com

SS-DBC15

Factory or Field Installed Options

» Barometric relief (only when economizer is installed): Allows air pressure relief inside the building to maintain a constant interior pressure.
» Roof curbs: Full perimeter roof curb with exhaust capability providing separate air streams for energy recovery from the exhaust air without supply air contamination. Two different heights 14" and 24", allows proper installation and structure stability. Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.
» Concentric duct kits: designed to provide a single-point air distribution system with the added benefit of having directional air control.
» Restraint mounting clips: Allows for installation reinforcement for Hurricane and/or seismic events.
» Burglar Bar Sleeves: Designed to prevent the access thru the return or supply ducting inside the unit.
» Downflow square to round adapter 18": Installed into a recessed portion of the roof curb, the concentric duct adaptor changes the orientation of the ductwork from square to round for applications utilizing that type of ducting system.
» Side discharge concentric diffuser system: The Concentric diffuser system is an all in one supply and return duct free arrangement for RTU systems. This system comes with two separate duct connections, one for a supply and another for a return.
» Remote indoor sensor: Remote sensor to monitor the temperature on zones away from the main thermostat.
» Drain pan overflow switch: Allows the controls to detect and send an alarm when there is an overflow on the drain pan.
» Filtration: MERV13 filters available for high air filtration requirements.
» Freeze stat: Temperature sensing device that monitors the heat exchange to prevent the coil from freezing.

Factory and Field Installed Options
» Downflow Economizer: Fully modulating between 0 and 100%, contain seals that meet ASHRAE 90.1 requirements. Includes motor and dampers, minimum position settings, a preset linkage, a wiring harness with plug, a mixed air temperature sensor, enthalpy control, and a barometric relief damper. An optional return enthalpy sensor is available to provide comparative or differential enthalpy control. Damper blades shall be galvanized steel with composite gears. Plastic or composite blades on intake or return shall not be acceptable. Standard leak rate shall be equipped with dampers not to exceed 2% leakage at 1 in. wg pressure differential. Low Leak design meets California Title 24 section 140.4 and ASHRAE 90.1 requirements for 4 cfm per sq. ft. on the outside air dampers and 10 cfm per sq. ft. on the return dampers. Shall be designed to close damper(s) during loss-of-power situations with spring return built into motor. Economizer controller shall accept a 2-10 Vdc CO2 sensor input for IAQ/DCV control. In this mode, dampers shall modulate the outdoor air damper to provide ventilation based on the sensor input.
» Economizer controller shall be Honeywell® W7220 that provides:
- 2-line LCD interface screen for setup, configuration and troubleshooting.
- On-board Fault Detection and Diagnostics (FDD) that senses and alerts when the economizer is not operating properly, per California Title 24.
- Sensor failure loss of communication identification
- Automatic sensor detection
- Capabilities for use with multiple-speed indoor fan systems
- Utilize digital sensors: Dry bulb and Enthalpy
- Economizer controller shall provide indications when in free cooling mode, in the DCV mode, or the exhaust fan contact is closed.
» Low Ambient Control: Allows cooling operation to 0°F outdoor ambient temperature for 7½-20 ton units and to 35°F outdoor ambient temperature for 3-6 ton units. For 25 ton units, cooling operation is extended from 24°F ambient temperature to 0°F outside air temperature.
» Electric Heat Kits (AC units): Heater elements are constructed of rust-resistant nickel chromium and are available in 240V-1-phase-60Hz, 240V-3-phase-60Hz, 480V-3-phase-60Hz and 575V-3-phase-60Hz. All heaters have overcurrent protection and high-temperature limit control. A single-point wiring connection is provided through a terminal block. Electric heaters are provided with staged heating as standard.
» Phase Monitor: Phase monitor shall provide protection for motors and compressors against problems caused by phase loss, phase reversal and phase unbalance. Phase monitor is equipped with an LED that provides an ON or FAULT indicator.

SS-DBC15

www.daikinac.com

39