Home›Danfoss›Danfoss Troubleshooting Guide for Supermarket Electronics
ℹ️ Document Conversion Notice:
This page was converted from the original file for easier reading. Diagrams/images may appear only in the original PDF below.
File info: application/pdf · 8 pages · 567.50KB
Danfoss Troubleshooting Guide for Supermarket Electronics
AK-SM 800
Keypad not Responsive
Reset unit
Remove keypad from AK-SM 800 and reconnect
Ensure excessive wiring does not exist behind keypad
If so, shorten cables where possible
Replace AK-SM 800
IO Offline
Verify Power to modules, Complete rescan
Power supply to comm modules should be 24V DC (can be a little higher in AC)
Verify daisy chain comm wiring
Verify 'Channel Lonworks' enabled on Network Nodes screen
If not, update and rescan afterwards
Verify term resistor switch position at AK-SM 800 is correct
If 1 loop from plug, switch = 'On' position
If 2 loops from plug, switch = 'Off' position
Verify EOL resistor in place at end of loop(s)
120ohm resistor or term switch in On position
If term switches exist on modules in middle of loop, need to be in Off position
Verify comm module addresses via rotary switches
Verify that there is no hairline shorts on the comm loop terminal
Verify comm cable type
EIA RS 485 (max 4000') for LON RS485
120 ohms impedance, 42-75.5 pF/m capacitance, typically 22-24 AWG
Isolate loop in sections, rescan
Identifies where comm problem may be introduced
Database will not load via USB
Verify filename ends in '.s55' extension
Verify filename is 8 characters or less, no special characters
Verify file is on root drive of USB, not subfolder
Verify controller firmware version equal or higher than database version
Database version can be verified in RMT
If database is 255 database being converted, must be v2.191 or higher.
Reset AK-SM 800 and attempt to load again
Case Controller 'Mismatch' Issue
Go to Network Nodes->Scan Status->Controllers
Locate address in list
Note controller version, part #, type shown
Go to Configuration->Control->Refrigeration->Circuits->Type
Confirm type matches info from #1 above
If not, change selection in list to proper choice
Rescan after updating
Common mistakes
For AK-CC 550A, parameter 061 not set to match program.
Typically 061=2 for most setups
Recommendations
Use 'Show only scanned devices' option at top of Circuits screen to limit choices
If correct choice is missing from list, update system manager to latest version of firmware
AK-SM 800 Stuck on 'Verifying Nodes'
Go to Network Nodes, verify only channels being used are enabled
Disable any channels not being used
Reset AK-SM 800
Missing License
Did MAC address revert back to 00:0B:2D:00:4B:00?
If yes, AK-SM 800 must be replaced
If no, please contact Danfoss Tech Support and supply the MAC address. Tech Support will help reinsert the license.
The controller will still operate regularly, but you won't be able to make any changes to configuration
In need of immediate assistance, you may load in the back-up/old database to bring the license back.
Host Comm/Host Count Error
Verify the comm configuration (config -> comm)
Make sure to have same master IP addresses for every controller and distinctive slave IP addresses for each slave controllers
If DHCP is set to no, verify default gateway and network mask. Every controller will share the same default gateway and network mask
Verify # of SM's on network
Verify rotary dial addresses
Master unit needs have address 0
Each controller must have distinctive address
Verify connection from AK-SM 800 to switch, and switch to network
Could be the issue with the cable
Power cycle network switch, router, or cell modem
Reset AK-SM 800
Make sure to reset all slave controllers before resetting master
Slowness in AK-SM 800
Verify firmware version is above v8.074
If running an older firmware version, it is recommended to upgrade (latest version is v8.091)
Is slowness present when viewing case controller only or any other screen?
If only present to case controller info, it could indicate an issue with case controller comm loop
Try temporarily breaking loop to few case controllers and see if results are better. You may also choose to unplug Modbus plug and see if it speeds up
Start adding case controllers back to the loop one-by-one and see at what point slowness returns. This will indicate where the issue is.
DNS Failure Alarm
DNS stands for domain name server, in which allows you to type domain name (i.e. google.com) instead of server IP. If you know the server IP, you may choose to type in the IP and turn DNS off.
DNS failure alarm indicates that an alarm transmitted, or attempted to transmit via email from the AK-SM 800, and there was no feedback from the email server to the AK-SM 800 saying the alarm was received.
Sometimes the server is simply not setup to send this feedback, so if the user did in fact receive the initial alarm via email, it is nothing more than a nuisance and DNS alarm can be disabled.
AK-CC 550A
AKV Not Opening
Is proper voltage going into terminal 5 and 6 (should match coil voltage spec)?
Is case controller calling for valve to be open? (parameter u23 > 0%)
If yes, verify voltage on terminals 5 and 6
If power to 5 but not 6, it could indicate a bad relay
If no power to 5, check voltage source
If power to both 5 and 6 are okay
Check voltage at AKV coil (possibly a bad solenoid)
Check system for blockage
If no
Is superheat reading correct? (see 'incorrect superheat' below to troubleshoot)
If u21
Is saturated suction temp above MOP temp setting (parameter u26 vs. n11)
MOP should be 59 dF for non-CO2 sites
Is main switch on (r12)?
Verify 'close EEV during rack shutdown' setting at rack controller is not exceeded
Verify shutdown schedule in rack controller not enabled
Incorrect Superheat
Is coil outlet sensor (s2) accurate?
Check parameter u20. If reading inaccurately, the sensor would need to be replaced as inaccuracy could lead to floodback.
Is pressure transducer accurate?
Check parameter 020 (-15psi)
Check parameter 021 (174psi-HFC, 855psi-CO2)
Pe Error (E20)
Verify transducer wiring
If using 060G1034 connector, terminals 30, 31, 32 wired black, blue, brown.
Measure voltage across terminals 30, 31. Should be 5 V DC
Measure voltage across terminals 31, 32. Should be in range of 0.5 – 4.5 V DC.
Verify transducer type. Label of transducer should say AKS32R (HFC) or AKS 2050 (CO2)
S3 Error (E25)
If no return air (s3) sensor exists, verify the following parameters:
R15 = 100%
A36 = 100%
O17 = 100%
R61 = 100%
If return air sensor does exist, verify ohm reading of sensor, and confirm wired to terminals 37, 38.
AK-CC 550A Case Controllers Offline
Complete rescan
Verify if loop is Modbus or Lon
If LON, is comm card installed?
If Modbus, verify polarity on all units is consistent
Verify 'Channel Lonworks' or 'Channel Modbus' enabled appropriately on Network Nodes screen
If not, update and rescan afterwards
Verify term resistor switch position at AK-SM 800 is correct
If 1 loop from plug, switch = 'On' position
If 2 loops from plug, switch = 'Off' position
Verify EOL resistor in place at end of loop(s)
120ohm resistor
Verify # of devices on system manager is less than 120.
Verify total loop distance less than 4000 ft.
If longer, repeater must be added.
Verify no Duplicates on System Manager
Found under Duplicates tab in Network Nodes
If duplicates exist, identify controllers sharing address and correct
Verify wire type ok
Should be EIA485 rated cable
Refer to Danfoss comm guidelines document as needed
Isolate loop in sections, rescan
Identifies where comm problem may be introduced
Mismatch Error during v2.0 Firmware Install
Refer to AK-CC 550A application guide, "Installing AK-CC 550A with the new v2.0 firmware"