FC726 Fire control panel - Data sheet A6V10263277

Fire control panel - Siemens

A6V10263277 i en -- Building Technologies 2018-09-28 Control Products and Systems Cerberus™ PRO Fire control panel FC726 Modular, pre-assembled fire control panel for large applications and the option of

FC726-ZA - SiemensYangın Kontrol Paneli

FC726-ZA - Siemens Yangın Kontrol Paneli

[PDF] FC726 Fire control panel - Data sheet A6V10263277 - Qpket

Sep 28, 2018 · FHA2016-A1 For installation in 19" third-party housing. 22 ... FN2012-A1. Ethernet switch (modular). 0.600 kg. S54400-B152-A1. VN2002 ...

PDF preview unavailable. Download the PDF instead.

01-FC726-ZA-Datasheet
CerberusTM PRO
Fire control panel
FC726

Modular, pre-assembled fire control panel for large applications and the option of gradual migration to Cerberus PRO.
 Fire control panel for a maximum of 1512 addresses  Can be used as a standalone version or networked with up to 64 stations, such as
control panels and terminals  Redundant network node with degraded mode operation according to EN 54  Emergency power supply for emergency operating time of up to 72 hours  Detection and automatic importing (auto-configuration) of all C-NET devices,
ready for operation immediately  Flexible configuration of complex applications and controls  Configuration data can be uploaded/downloaded via remote access  Extensions: Printer, key switches, LED indicators  Card cage for additional module bus cards (line and I/O cards)  Hot plug system: Module bus cards can be changed during operation  Time and situation-dependent changeover of detector parameter sets

A6V10263277_i_en_-2018-09-28

Building Technologies Control Products and Systems

Features and Functions
System
The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039439 Network Security Guidelines document. Contact your Siemens IT security expert for more information.
System overview

System overview
2 Building Technologies Fire Safety

A6V10263277_i_en_-2018-09-28

1

Remote access with Cerberus-Remote

2

FS cloud applications

3

Customer network

4

Management platform

5

Remote access to management platform

6

Remote access with Cerberus Mobile

7

Router + firewall + virtual private network

8

Fire damper with actuator

Transmission of a fault signal

Transmission of an alarm signal

You will find a detailed labeled version of the diagram above along with further information in the A6V10332842 planning guide, see chapter 'Product documentation'.
Optional module bus cards for card cage with 5 slots

Type FCL2001-A1

Designation Line card (FDnet/C-NET)

FCL7201-Z3 Line card (SynoLOOP)

FCI2007-A1 FCI2008-A1
FCI2009-A1

I/O card (RT) I/O card (programmable)
I/O card (horn/monitored)

Properties
4x loops each with 252 addresses, max. of 252 addresses per line card
4x loops each with a maximum of 128 addresses, max. of 512 addresses per line card
Outputs for alarm, fault, local alarm
12x freely programmable inputs/outputs per I/O card
8x monitored horn outputs or monitored outputs

Building Technologies Fire Safety

3 A6V10263277_i_en_--
2018-09-28

Networking of fire control panels
The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039439 Network Security Guidelines document. Contact your Siemens IT security expert for more information.
Up to 32 control panels and terminals can be linked to form one C-WEB network. If the C-WEB network is connected to a danger management system via BACnet, up to 16 control panels and terminals can be networked.

Sub-net

1

Management platform

2

Remote access to management platform

Transmission of a fault signal

Transmission of an alarm signal

4 Building Technologies Fire Safety

A6V10263277_i_en_-2018-09-28

An optical C-WEB/LAN network allows up to 14 sub-nets with up to 16 stations to be operated in one network. A maximum of 64 stations is supported in total.

Backbone

1

Remote access with Cerberus-Remote

2

FS cloud applications

3

Customer network

4

Management platform

5

Remote access to management platform

6

Remote access with Cerberus Mobile

7

Router + firewall + virtual private network

Transmission of a fault signal

Transmission of an alarm signal

You will find a detailed labeled version of the diagram above along with further information in the A6V10332842 planning guide, see chapter 'Product documentation'.

Building Technologies Fire Safety

5 A6V10263277_i_en_--
2018-09-28

Control panels
General features and functions  Fast Ethernet interface for a heterogeneous network  Processes signals from Cerberus PRO as well as from earlier detector series  Siemens danger management system can be connected  Slots for RS232 and RS485 serial interfaces  Floor repeater devices, alarm devices, and mimic displays on the C-NET detector line  All detector lines are monitored for ground faults.  Mixed use of all module bus cards (line and I/O cards) possible.  Integrated degraded mode function  Freely configurable, time-dependent controls with optional weekly switching programs  Time and situation-dependent changeover of detector parameter sets  Controls for synchronous activation of sounders / sounder bases with signal sound,
flash, and voice output  The control panel and the fire detection system are custom-configured using the
'Cerberus-Engineering-Tool' software  Firmware for all processor-controlled control panel components can be updated  Customer texts can be adapted directly on the operating unit of the control panel or with
the 'Cerberus-Engineering-Tool' software  Up to 13000 events can be called up from the event memory and filtered based on
various criteria  Automatic summer/normal time changeover
Control panel-specific features

FC726-ZA

Housing (Large)
C-NET detector line:  Max. 1512 addresses  4 loops/8 stubs  Can be extended up to 28 loops/56 stubs Extra module bus cards (option):  Line card (FDnet/C-NET) FCL2001-A1  Line card (SynoLOOP) FCL7201-Z3  I/O card (programmable) FCI2008-A1  I/O card (horn/monitored) FCI2009A1  I/O card (remote transmission) FCI2007-A1 Features:  Operating unit  Operating add-on (empty)  Card cage (5 slots)  150 W power supply  Max. battery capacity 45 Ah Operating unit options:  Event printer FTO2001-A1  Key switch (Kaba) FTO2005-C1  Key switch (nordic) FTO2006-B1  Operating add-on (2xLED indicator) FCM7213-Y3  Operating add-on (4xLED indicator) FCM7214-Y3

6 Building Technologies Fire Safety

A6V10263277_i_en_-2018-09-28

Extensions FCM7213-Y3

Operating add-on (2xLED indicator)
 Optional operating add-on with 48 indicator groups with one red/green + one yellow LED each

FCM7214-Y3

Operating add-on (4xLED indicator)
 Optional operating add-on with 96 indicator groups with one red/green + one yellow LED each

FH7204-Z3 FH7205-Z3

Housing (Large Extension)  Empty housing for free use  430 x 398 x 283 mm  E.g., for extra batteries, operating add-ons, or event printers  Space for the following battery configurations:
­ 2x FA2007-A1 (45 Ah) or ­ 2x FA2008-A1 (65 Ah)
Housing (Large)  Empty housing for free use  430 x 796 x 283 mm  E.g., for extra batteries, operating add-ons, or event printers  Space for the following battery configurations:
­ 4x BAT12-25 (25 Ah) or ­ 4x FA2007-A1 (45 Ah) or ­ 2x FA2008-A1 (65 Ah)

Building Technologies Fire Safety

7 A6V10263277_i_en_--
2018-09-28

FTO2001-A1 DL3750+

Event printer  Thermal printer for installation in operating units or operating add-ons  Can be controlled via the RS232 module FCA2001-A1 (order separately)  Logs all important events, such as alarms, faults, isolations, and test functions
Matrix printer (external)  External matrix printer recommended by Siemens  Supports monitoring for printing faults  Can be controlled via the RS232 module FCA2001-A1 (order separately)  Can be controlled via Ethernet via the print server PS104 from SEH

8 Building Technologies Fire Safety

A6V10263277_i_en_-2018-09-28

Use
This fire control panel is ideal for large applications, e.g., for use in industrial plants, office complexes, or production halls.
Within the context of modernization, the Station allows a gradual and seamless transition from older systems to Cerberus PRO.

Design

Function elements
Operating unit The following elements are available on the operating unit:  CPU module and electronics  Ethernet connection  Slots for RS232 and RS485 modules and network modules (SAFEDLINK)  Space for 'Kaba' or 'nordic' key switch  Space for event printer (depending on version)  Peripheral data bus connection for optional LED modules
Periphery board The following elements are available on the periphery board:  Connection terminals for:
­ C-NET lines ­ Remote transmission (alarm, fault) ­ Horn output ­ Configurable control inputs and outputs ­ Monitored alarm and fault output ­ Power supply and emergency supply  2x slot for loop extension (C-NET)
Card cage There is a card cage mounted on the rear housing panel for inserting a maximum of five module bus cards.
Power supply unit 150 W, emergency power supply The power supply feeds the hardware and charges the batteries. In the event of a power cut, the batteries provide emergency current.
Housing A pivoting mounting plate can be fitted for the following elements above the periphery board on the rear housing panel:  1x fire brigade periphery module (for Germany)  2x sounder module (as an alternative to mounting on U-rail TS35)
Configuration The following software allows the system to be customized:  Cerberus-Engineering-Tool

Operation

Each control unit has an integrated operating unit. The control panel can also be operated via a separate fire terminal FT724.
You will find details and more information in product data sheet A6V10207898.

Building Technologies Fire Safety

9 A6V10263277_i_en_--
2018-09-28

Setup

Layout of FC726
10 Building Technologies Fire Safety

A6V10263277_i_en_-2018-09-28

Position Designation

Basic equipment

1

Housing (Large)

2

Periphery board (4 loops)

3

Power supply (SV 24 V-150 W)

4

Mains terminals on TS35 DIN rail

5

Operating unit

6

Card cage (5 slots)

7

Space for batteries

Extensions

8

Relay module

9

Event printer

10

Key switch (Kaba)

Key switch (nordic)

11

Mounting plate

12

Loop extension (C-NET)

13

Module bus cards:

Line card (FDnet/C-NET)

Line card (SynoLOOP)

I/O card (programmable)

I/O card (horn/monitored)

I/O card (RT)

14

RS485 module (isolated)

15

RS232 module (isolated)

16

Network module (SAFEDLINK)

17

Repeater (SAFEDLINK)

18

Sounder module

19

Battery (12 V, 25 Ah, VdS)

Battery (12 V, 45 Ah, VDS)

20

Fire brigade periphery module

21

19" mounting kit

22

License key Sx

23

Cable kit (communication)

24

Power supply kit (150 W, B)

25

Relay module/U-rail

Type

Comment

FHA7205-Z3 Items 1-6: Basic equipment

FCI2004-A1

V24230-Z6-A5

-

Space for socket, relay modules, etc.

FCM72xx-xx Operating unit with CPU

FCA2008-A1 For five module bus cards

-

2x 12 V / 17...45 Ah

Z3B171 FTO2001-A1 FTO2005-C1 FTO2006-B1 FHA2007-A1 FCI2003-A1

Relay for fire controls For logging events For operating access authorization
E.g., for fire brigade periphery module For extending the number of loops from two to four, the number of addresses remains the same

FCL2001-A1 FCL7201-Z3 FCI2008-A1 FCI2009-A1 FCI2007-A1 FCA2002-A1 FCA2001-A1 FN2001-A1 FN2002-A1
FCA2005-A1
BAT12-25 FA2007-A1 FCI2001-D1 FHA2016-A1 FCA20xx FCA2014-A1
FP2005-A1 Z3B171

For four extra C-NET lines For four addressable SynoLOOP lines For twelve configurable inputs/outputs For eight monitored horn outputs For extra alarm and fault outputs For peripheral devices with RS485 interface For devices with an RS232 interface For networking several stations For extending the C-WEB system bus, max. 1x repeater (SAFEDLINK) between two stations (mounted directly on a plane surface, on a TS35 U-rail, or in housing FDCH221) For splitting one conventional sounder into four For the emergency power supply
For Germany (FBF, FSD, ÜE, FSE, ÖA, KL) For installation in 19" third-party housing For special functions For flexible connections running to the modules on the operating unit For extra power supply Space for U-rail TS35 L=70 mm with max. four relay modules

Building Technologies Fire Safety

11 A6V10263277_i_en_--
2018-09-28

Type Overview

Housing (Large)

Type Order number Number of C-NET addresses Loops (with loop extension) or Stubs (with loop extension) Power supply Max. battery capacity Max. number of module bus cards in the card cage

FC726 S54400-C87-A1
1512 4 (8) 8 (16) 150 W 45 Ah
5

12 Building Technologies Fire Safety

A6V10263277_i_en_-2018-09-28

Details for ordering Fire terminals
Type FC726-ZA

Designation Fire control panel (modular)

Weight 21.143 kg

Order number S54400-C87-A1

Extensions

Type FCA2001-A1 FCA2002-A1 FCA2005-A1 FCA2014-A1 FCI2001-D1 FCI2003-A1 FCI2007-A1 FCI2008-A1 FCI2009-A1 FCL2001-A1 FCL7201-Z3 FCM7214-Y3
FCM7213-Y3
FH7204-Z3 FH7205-Z3 FHA2007-A1 FHA2016-A1 FN2001-A1 FN2002-A1 FN2006-A1 FN2007-A1 FTO2001-A1 FTO2005-C1 FTO2006-B1 Z3B171

Designation RS232 module (isolated) RS485 module (isolated) Sounder module Cable kit (communication) Fire brigade periphery module Loop extension (C-NET) I/O card (RT) I/O card (programmable) I/O card (horn, monitored) Line card (FDnet/C-NET) Line card (SynoLOOP) Operating add-on (4xLED indicator) Operating add-on (2xLED indicator) Housing (Large Extension) Housing (Large) Mounting plate 19" mounting kit Network module (SAFEDLINK) Repeater (SAFEDLINK) Fiber network module (SM) Fiber network module (MM) Event printer Spare printer reels (10 reels) Key switch (Kaba) Key switch (nordic) Relay module 250 V AC / 10 A (1 relay)

Weight 0.033 kg 0.027 kg 0.100 kg 0.126 kg 0.207 kg 0.030 kg 0.111 kg 0.097 kg 0.109 kg 0.119 kg 0.120 kg 3.905 kg

Order number A5Q00005327 A5Q00009923 A5Q00014866 A5Q00023027 A5Q00013100 A5Q00010136 S54400-A20-A1 S54400-A6-A1 S54400-A21-A1 A5Q00009875 S54400-A116-A1 S54400-B150-A1

2.516 kg S54400-B149-A1

11.729 kg 16.079 kg 0.800 kg 3.000 kg 0.022 kg 0.105 kg 0.792 kg 0.792 kg 0.141 kg 0.090 kg 0.083 kg 0.046 kg 0.042 kg

S54400-B89-A1 S54400-B86-A1 A5Q00010151 A5Q00020179 A5Q00012851 S24236-B2502-A1 S54400-A109-A1 S54400-A110-A1 A5Q00010126 A5Q00017619 A5Q00010113 A5Q00010129 4843830001

Building Technologies Fire Safety

13 A6V10263277_i_en_--
2018-09-28

Auxiliary power supply

Type FP2004-A1
FP2005-A1

Designation

Weight

Power supply kit (150 W, A) for 1.286 kg EN-compliant installation in empty housing

Power supply kit (150 W, B) for extension

1.181 kg

Order number A5Q00020825
A5Q00018779

Network (backbone)

Type FCA2031-A1

Designation Connection module (MoNet)

FHA2029-A1 FN2012-A1 VN2002-A1 VN2003-A1

Mounting kit (switch) Ethernet switch (modular) Ethernet module (MM) Ethernet module (SM)

Weight 0.081 kg incl. cable 1.261 kg 0.600 kg 0.026 kg 0.026 kg

Order number S54400-A153-A1
S54400-B79-A1 S54400-B152-A1 S54400-A43-A1 S54400-A44-A1

Battery
Type FA2005-A1 BAT12-25 FA2007-A1 FA2008-A1 FHA2061-A1

Designation Battery (12 V, 17 Ah, VdS) Battery (12 V, 25 Ah, VdS) Battery (12 V, 45 Ah, VdS) Battery (12 V, 65 Ah, VdS) Mounting kit (batteries)

Weight 5.700 kg 7.8 kg 14.500 kg 21.300 kg 

Order number A5Q00019677 S54302-Z102-A1 A5Q00022897 A5Q00019357 S54400-B91-A1

License keys
Type FCA2033-A1 FCA2034-A1 FCA2035-A1 FCA2036-A1

Designation License key (S1) License key (S2) License key (S3) License key (S4)

Weight 0.010 kg 0.010 kg 0.010 kg 0.010 kg

Order number S54400-P154-A1 S54400-P155-A1 S54400-P156-A1 S54400-P157-A1

External printer

Type DL3750+ -

Designation
Matrix printer (external)
Color ribbon for matrix printer DL3750+

Weight 7.300 kg 0.078 kg

Order number A5Q00023962 A5Q00023963

14 Building Technologies Fire Safety

A6V10263277_i_en_-2018-09-28

Product documentation

Title System documentation System description Product data Planning Mounting/Installation Data sheets FC721 - fire control panel FC722 - fire control panel FC723 - fire control panel for modernization FC724 - fire control panel FC726 - fire control panel (modular) FT724 - fire terminal Fire detection system with integrated single-sector extinguishing Network Security Guidelines Planning overview

Document ID
A6V10210355 A6V10210368 A6V10210362 A6V10210390
A6V10203220 A6V10206525 A6V10379246 A6V10207176 A6V10263277 A6V10207898 A6V10880701
A6V101039439 A6V10332842

Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address:
http://siemens.com/bt/download

Guarantee

Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.

Building Technologies Fire Safety

15 A6V10263277_i_en_--
2018-09-28

Technical data

FC726 in the housing (Large)

Supply

Mains voltage

AC 115/230 V +10/-15 %

Power supply

150 W

Operating voltage

DC 21...28.4 V

Operating current

Max. 5 A

Battery capacity

2x 12 V, 45 Ah

Battery monitoring

Yes

Network monitoring

Yes

Inputs / outputs

Connectable detector series

Cerberus PRO

Other addressable detectors which can SynoLOOP be connected

Number of addresses

Max. 1512

Number of integrated line cards

2

Number of integrated lines:

 Loops (with loop extension) or

4 (8)

 Stubs

8 (16)

Number of additional lines:

 C-NET (4 loops or stubs per line card)

Max. 20 loops/stubs

 SynoLOOP (4 loops or stubs per line card)

Max. 20 loops/stubs

Integrated inputs/outputs:

 Alarm RT relay output

1

 Fault RT relay output

1

 Monitored alarm outputs

1

 Monitored fault outputs

1

 Monitored horn outputs

2

 Freely programmable inputs/outputs 12

Additional I/O cards:

 Programmable

12x configurable inputs/outputs 2x supply outputs 24 V

 Horn/monitored

8x horn output monitored

 RT

1x alarm relay output 1x fault relay output 1x voltage output 24 V 2x GPIO 1x fault output monitored 2x configurable output monitored

16 Building Technologies Fire Safety

A6V10263277_i_en_-2018-09-28

FC726 in the housing (Large)

Interfaces

Operating unit

Integrated

Slots for serial interfaces RS232, RS485 2

Slots for network modules

2

Slots for loop extension

2

Slots for module bus cards (on

5

integrated card cage)

Mounting spaces for cable kit

2

(communication)

Sounder module

Max. 2

Ethernet port RJ45

1

Ambient conditions

Operating temperature

-8...+42 °C

Storage temperature

-20...+60 °C

Air humidity (no condensation permitted)

95 % rel.

Maximum height above sea level

3700 m

Mechanical data

Dimensions (W x H x D):

 Without cover cap

430 x 796 x 260 mm

 With cover cap

430 x 796 x 283 mm

Protection category (IEC 60529)

IP30

Color:

 Housing

~RAL 7035 light gray

 Cover cap

~RAL 000 50 00

Approvals

VdS

G210084

LPCB

126bn/08

FM

3051081

10

0786

FC726-ZA

Siemens Schweiz AG; Theilerstrasse 1a CH-6300 Zug
Technical data: see doc. A6V10210355

FC726 - Control and Indicating Equipment incl. SV24V150W - 150W/24VDC Power Supply Equipment for use in fire detection and fire alarm systems installed in buildings.

305/2011/EU (CPR): EN 54-2 / EN 54-4 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2014/35/EU (LVD): EN 60950-1 ; 2011/65/EU (RoHS): EN 50581

The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EU Declaration of Conformity (DoC), which is obtainable via the Customer Support Center: Tel. +49 89 9221-8000 or http://siemens.com/bt/download

DoP No.: 0786-CPR-20983; DoC No.: CED-FC726

13

0786

SV24V150W

Siemens Schweiz AG; Theilerstrasse 1a CH-6300 Zug
Sinteso technical data: see doc. 008837 CerberusTM PRO technical data: see doc. A6V10210368

SV24V150W - Power Supply Equipment 24VDC/150W for use in fire detection and fire alarm systems installed in buildings.

305/2011/EU (CPR): EN 54-4 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2014/35/EU (LVD): EN 60950-1 ; 2011/65/EU (RoHS): EN 50581

The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EU Declaration of Conformity (DoC), which is obtainable via the Customer Support center: Tel. +49 89 9221-8000 or http://siemens.com/bt/download

DoP No.: 0786-CPD-20775; DoC No.: CED-SV24V150W

Building Technologies Fire Safety

17 A6V10263277_i_en_--
2018-09-28

Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies

18

Building Technologies

Fire Safety Document ID

A6V10263277_i_en_--

Edition

2018-09-28

© Siemens Switzerland Ltd, 2007 Technical specifications and availability subject to change without notice.
A6V10263277_i_en_-2018-09-28 FS720


PDF-XChange Printer V6 (6.0 build 322.7) [Windows 7 Enterprise x64 (Build 7601: Service Pack 1)]