Accutech Security IGWT-662008 S-TAD User Manual Install Manual v2 36 ES IS BR July 2007

Innovative Control Systems Inc S-TAD Install Manual v2 36 ES IS BR July 2007

User Manual 4 of 4

Download: Accutech Security IGWT-662008 S-TAD User Manual Install Manual  v2 36    ES IS BR   July 2007
Mirror Download [FCC.gov]Accutech Security IGWT-662008 S-TAD User Manual Install Manual  v2 36    ES IS BR   July 2007
Document ID983437
Application IDulNL7pW/ZzBdIQalUQK3Ww==
Document DescriptionUser Manual 4 of 4
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize223.32kB (2791458 bits)
Date Submitted2008-08-11 00:00:00
Date Available2008-09-25 00:00:00
Creation Date2008-08-05 20:41:40
Producing SoftwareAcrobat Distiller 5.0.5 (Windows)
Document Lastmod2008-08-05 20:41:52
Document TitleInstall Manual (v2.36) - ES/IS/BR - July 2007
Document CreatorAcrobat PDFMaker 5.0 for Word
Document Author: DerekU

Installation Manual
Appendix B-1
JP3 (Scan Lock Select)
JUMPERS
Factory Default N/A
This section contains the functions and
default positions of all 16 jumpers within the
Controller.
This jumper was removed from REV F
boards.
Refer to Figure B.1 for a Jumper-only
Controller PCB graphic.
JP4 (Antenna Scan Select)
JP1 (Tx Frequency Select)
Factory Default IN; Position 2
This jumper selects the frequency of the Tx
Activation Field. Leave this jumper in
Position 2. Positions 1 and 3 are only used if
they are needed as an alternate TX
frequency for adjacent zone rejection (see
Stagger Tuning).
Table B.1 JP1
Factory Default OUT
This jumper
systems.
allows
for
multi-antenna
Table B.2 JP4
Position
For use with:
Off
Single-antenna system (X)
2-3
Two-antenna system (X, Y)
1-2
Three-antenna system (X, Y, Z)
JP5 (Supervise Interval Select)
Position
Frequency
130 KHZ
Factory Default IN; Position 6
131 KHZ
132 KHZ
This jumper selects the time interval for Rx
supervisor.
Table B.3 JP5 Positions and Results
JP2 (Gain Boost)
Factory Default OUT
This jumper controls the intensity of a signal
required for tag detection.
With this jumper OUT, signal is at
factory default setting.
With this jumper IN and the Tx
Gain pot (R6) is set for reduced Tx
output, a Tag being detected will
force the Tx gain to full output to
assure best detection. However, if
the Tx Gain pot (R6) is set to
maximum Tx gain, JP2 has no
effect.
Position
Result
(Check system Once/Time Interval)
Test
(testing purposes only)
Demo; Once/min
(demonstration purposes only)
Once/ 2 Hours
Once/ 4 Hours
Once/ 8 Hours
Once/16 Hours
Disable
B-2 Appendix
To test the Rx Supervise function, use the
following instructions:
Installation Manual
JP8 (Detection Delay)
Factory Default IN; Position 1-2
1. At JP5, place the Jumper
in Position 1.
If LEDs 4, 5, and 14 blink once
every eight seconds, then the Rx
Supervise function is working
properly.
If LEDs 4, 5, and 14 do not blink
once every eight seconds, then the
Rx Supervise function is NOT
working properly (see Appendix D-1)
This jumper extends the time required for
valid Tag detection. Keep the default setting.
JP9 (External Reset)
Factory Default IN
This jumper selects which device will
control the resetting of the lock.
Table B.4 JP9
2. When done testing, at JP5, place the
Jumper in the desired interval
position.
JP6 (Scan Rate)
Position
Lock is reset using:
In
Door (Egress) Alarm
Out
Time setting of switch S1
JP10 (Loiter Reset)
Factory Default IN
Factory Default IN; Position 1-2
This jumper will set the Controller’s scan
speed for sequencing the Tx wand antennas.
Position 1-2 is better suited for detecting
persons who walk slowly through a zone.
Position 2-3 is better suited for detecting
persons who walk briskly through a zone.
For single antenna systems it is
recommended to use position 1-2.
JP7 (Extended Detection Delay)
Factory Default IN
This jumper will increase the time that a
valid Tag signal must be received before a
system response is initiated.
This jumper controls whether or not the
Loiter Alarm will be automatically reset.
Table B.5 JP10
Position
Alarm Automatically Resets?
In
Yes
Out
No
JP11 (Door Timer Extend Disable)
Factory Default IN
This jumper determines the timing range of
the Door Ajar Time potentiometer (R97).
B.6 JP11
Position
Time Range
In
10-60 seconds
Out
65-110 seconds
Installation Manual
Appendix B-3
JP12 (Loiter Time Extend Disable)
JP16 (Door Ajar Reset)
Factory Default IN
This jumper determines the timing range of
the Loiter Timer potentiometer (R110)
Factory Default IN
This jumper will determine whether the
Door Ajar alarm automatically resets.
Table B.7 JP12
Table B.9 JP16
Position
Time Range
Position
Door Ajar Automatically Resets?
In
10-60 seconds
In
Yes
Out
65-110 seconds
Out
No
JP13 (Piezo Enable)
Factory Default IN
This jumper controls whether the piezo is
enabled or disabled.
Table B.8 JP13
Position
Piezo is:
In
Enabled
Out
Disabled
JP14 (Bar Display Enable)
Factory Default IN
This jumper will enable the bar display
LED 13 to function for installing or testing
purposes.
JP15 (TX Output LED Enable)
Factory Default IN
This jumper will enable the Tx Output LEDs
(LED1, LED2 and LED3) for installing or
testing purposes.
B-4 Appendix
Figure B.1
Jumper-only Controller PCB
Installation Manual
Installation Manual
Appendix B-5
LEDs
LED1
(X Antenna Indicator; Steady Green)
This section contains the functions and
colors of all 14 LEDs on the Controller.
This LED indicates the status of the “X” Tx
Wand antenna.
Refer to Figure B.4 for a LED-only
Controller PCB graphic.
In a one Tx Wand antenna system, this LED
will be on at all time provided that the Tx
Gain pot it set high enough and the Tx
Wand antenna is properly tuned.
Special Considerations on
LED1, LED2 and LED3
LEDs 1, 2, and 3 are Tx Wand antenna
output indicators.
They are enabled/disabled with jumper
JP15.
The brightness of these LEDs depends upon
the setting of the Tx Gain potentiometer
(R6) and the proper tuning of each Tx Wand
antenna.
In addition, the brightness of LEDs 2 & 3 is
dependant upon the setting of the Y & Z
Balance potentiometers (R4 & R12
respectively).
When more than one Tx Wand antenna is
connected at any one zone and jumper JP4 is
installed, LEDs 1 & 2, or LEDs 1, 2, & 3
will illuminate in sequence.
If the LEDs are not illuminating in
sequence:
NOTE: Even if the “X” Tx Wand antenna is
properly tuned, this LED can be dim or even
completely out if the Tx Wand antenna is
mounted too close to metal or if a metal
object is placed too close to it.
LED2
(Y Antenna Indicator; Steady Green)
This LED indicates the status of the “Y” Tx
Wand antenna.
In a two Tx Wand antenna system, this LED
will illuminate in sequence with LED1.
NOTE: Even if the “Y” Tx Wand antenna is
properly tuned, this LED can be dim or even
completely out if the Tx Wand antenna is
mounted too close to metal or if a metal
object is placed too close to it.
Check to see if a Tag is in the zone
LED3
(Z Antenna Indicator; Steady Green)
Check the position of jumpers JP4
& JP15
This LED indicates the status of the “Z” Tx
Wand antenna.
Check the settings of
potentiometers R4, R6, & R12
In a three Tx Wand antenna system, this
LED will illuminate in sequence with LED1
& LED2.
Check the Tx Wand antenna
connections
NOTE: Even if the “Z” Tx Wand antenna is
properly tuned, this LED can be dim or even
completely out if the Tx Wand antenna is
B-6 Appendix
Installation Manual
mounted too close to metal or if a metal
object is placed too close to it.
LED4
(Valid Tag Detected; Steady Yellow)
This LED indicates the presence of a Tag in
a zone.
Table B.10
LED4 status
Signals
Off
No Tag(s) Present
On, steady Yellow
Tag(s) Detected
LED5
(Rx Signal Indicator; Steady Green)
This LED indicates the presence of a Tag,
418 mHZ interference in a zone or Band
Removal.
This LED is lit dimly when a Tag is in the
zone. If this LED lights very brightly (and
there are no Tags in the zone) the Receiver
is being interfered with or is misadjusted.
Table B.11
LED5 status
Signals
Off
No Tag(s) Present
On, dimly,
steady Green
Tag(s) Detected
On, brightly,
steady Green
Zone Receiver problem
LED6
(Lock Indicator; Steady Yellow)
This LED indicates the status of the Lock(s)
or
Elevator
Deactivation
Relay.
NOTE: Voltage from the Fire Panel
Interface (FPI) must be present for this LED
to function.
Table B.12
LED6 status
Signals
Off
No Tag(s) present
On,
steady Yellow
Tag(s) present in zone,
Lock or Elevator
Deactivation Relay is
engaged
NOTE: LED6 will remain on (and the Locks
or Elevator Deactivation Relay will remain
engaged) after the Tag leaves the zone for as
long as the delay time has been set.
LED7
(Alarm Indicator; Flashing Red)
This LED indicates an “open door”
condition after a Tag as been detected.
Table B.13
LED7 Status
Signals
Off
No Tag(s) present
On, flashing Red
Tag(s) detected
and an “open
door” condition
NOTES:
This LED will continue to flash red until the
“open door” condition is corrected (close the
door and enter a valid code into the
Keypad). In hallway situations, a triggered
Passive Infrared Reader (PIR) is also an
“open door” condition.
LED8
(Door Ajar Indicator; Steady Red)
This LED indicates a Door Ajar condition.
Table B.14
LED8 Status
Signals
Off
No Tag(s) Present
On, steady Red
Door Ajar condition
Installation Manual
Appendix B-7
NOTES:
A Door Ajar condition occurs after a door
has been open for a period of time (set by
potentiometer R97 and jumper JP11).
To override this delay and make this alarm
occur the moment the door is opened,
connect a +12V signal to P6-pin 2 (Door
Timer Override) of the Controller.
This LED will continue to illuminate steady
Red until the Door Ajar condition is
corrected (close the door and enter an
authorized code into the Keypad).
LED9
(Loiter Indicator; Steady Yellow)
This LED indicates a Loiter condition.
Table B.15
LED9 status
Signals
Off
No Tag(s) present
On, steady Yellow
Loiter condition
NOTES:
A Loiter condition is when a Tag lingers in
the Tx Activation Field for longer than the
set period of time (adjustable with
potentiometer R110 and jumper JP12).
This LED will continue to illuminate steady
Yellow until the Loiter condition is
corrected (remove the Tag from the Field
and enter an authorized code into the
Keypad).
LED 10 (12V DC)
LED is lit steady Green when 12 VDC
power is present.
LED 11 (6V DC)
LED is lit steady Green when 6 VDC is
present.
LED 12 (28V DC)
LED is lit steady Green when 28 VDC is
present.
LED 13 (Bar Display)
This LED’s indication depends on the
position of switch S3.
With switch S3 in the left position, this LED
displays the received signal (with a steady
Green bar) and Tag detection threshold
(with a flashing Green bar).
With switch S3 in the right position, this
LED displays the relative Tx power (with a
steady Green bar) and supervisor threshold
(with a flashing Green bar).
Table B.16
S3 Position
LED13 displays:
Left
(Figure B.2)
Received signal
(steady Green bar)
Tag detection threshold
(flashing Green bar)
Right
(Figure B.3)
Tx Power
(steady Green bar)
Supervisor threshold
(flashing Green bar)
Appendix B-8
Installation Manual
B.2 LED13 Normal Operation
B.3 LED13 during tuning
LED 14 (Supervisor Indicator)
This LED indicates if there is a problem
with the Tx Wand antenna(s) and/or
Receiver(s).
Table B.17
LED status
Signals
Off
No problems
On,
steady Red
Tx Wand antenna-related
problem
On,
steady Green
Zone Receiver-related
problem
On,
steady Yellow
Tx Wand antenna
and Zone Receiver-related
problem
Installation Manual
Figure B.4
LED-only Controller PCB
Appendix B-9
B-10 Appendix
Installation Manual
R26 (Supervisor Threshold)
Potentiometers
This section contains the functions of the 7
potentiometers on the Controller.
Refer to Figure B.5 for a potentiometer-only
Controller PCB graphic.
Set the flashing bar of LED13 at the second
bar from the bottom.
NOTE:
R26 (Supervisor Threshold) must always be
set lower than R6 (Tx Gain) on LED13.
Therefore, if you reduce the R6, you must
reduce the R26 accordingly.
R4 (Y Balance)
R59 (Detect Threshold)
Factory Set to Maximum (clockwise)
Adjust for minimal bounce of bar display
LED13 when switch S3 is in right position.
When S3 is in the left position, set R59 so
that the flashing bar in LED13 is at about
the 5th or 6th bar from the bottom.
R6 (Tx Gain)
If interference noise is present, the steady
bar(s) will bounce. Be sure to set the
flashing bar above the highest bouncing
steady bar.
Factory Set to Maximum (clockwise)
For normal
maximum.
operation,
leave
R6
at
For single doors or if loop Tx antennas are
used, you may need to reduce the R6 to
minimize overlap into hallways and/or
adjacent rooms.
NOTE:
R6 (Tx Gain) must always be set higher than
R26 (Supervisor Threshold) on LED13.
Therefore, if you increase R26, you must
increase the R6 accordingly.
R12 (Z Balance)
Factory Set to Maximum (clockwise)
Adjust for minimal bounce of bar display
LED13 when switch S3 is in right position.
R97 (Door Ajar Delay)
Factory Set to 15 seconds
Set mid scale or as desired to delay onset of
Door Ajar alarm.
R110 (Loiter Delay)
Factory Set to 15 seconds
Set mid scale or as desired to delay onset of
Loiter alarm.
Installation Manual
Figure B.5
Potentiometer-only Controller PCB
Appendix B-11
B-12 Appendix
Installation Manual
Switches and
Fuse Replacement
S2 (Reset Switch)
This section contains the functions of the 3
Switches on the Controller as well as Fuse
Replacement specifications.
Refer to Figure B.8 for a Switch and Fuse-only
Controller PCB graphic.
Resets the system. Used during system testing to
clear alarms, equivalent to a Keypad Reset.
S3 (Controls function of LED13)
Tx Gain/Supervisor Adjustments
Detection Level/Threshold Adjustments
Switches
S3 is linked to LED 13 (page B-7), which is a
visual indicator during tuning Tx wand antennas
(page 4-7).
S1 (Lock Elevator Delay)
Tx Gain/Supervisor Threshold Adjustments
Factory Set from 5 to 15 seconds
Sets the delay time for how long the Magnetic
Lock or Elevator Deactivation will remain
engaged after a Tag leave the Tx Activation
Field.
When the switches are ON, the time setting is 0
(zero) seconds. As switches are turned off, the
time setting increases. The maximum time delay
is approximately 120 seconds.
Table B.18
Switch 1
1 2 3
Added Delay
(seconds)
1 5 10 15 30 50
For example, to set the delay time for
approximately 25 seconds, turn OFF switches 3
and 4.
With S3 to the right, and the Tx Gain set at, or
near maximum, LED13 will indicate two things:
the Tx Gain (Power Level) adjusted by pot R6,
and the Supervisor Threshold, adjusted by pot
R26.
Keep in mind that if the Tx Gain is reduced, the
Supervisor Threshold should also be reduced, so
that the flashing bar is always below the steady
bar(s). If this is not set properly, the Supervisor
peizo will sound. For more information, see
page B-7.
Detection Level/Threshold Adjustments
With S3 to the left, LED13 indicates how
closely a received signal resembles a valid Tag,
and the threshold where the decision is made
that it is a valid Tag. (Figure B.6) When a valid
Tag enters the zone, the detect level will
increase past the detection threshold, to indicate
a Tag is in the zone (Figure B.7).
Installation Manual
Appendix B-13
Fuse Replacement
Use the following fuses when replacing:
F1 (12-14V AC)
Replace with 120V, 2.5A, Slo-Blo, 3AG Fuse
F2 (28V AC)
Replace with 250V, 1A, Slo-Blo, 3AG Fuse
Figure B.6
LED13 Normal Operation (S3 to the Left)
F3 (Incoming Power)
Replace with 250V, 1A, Slo-Blo, 3AG Fuse
Figure B.7 LED13 Tag in Zone
B-14 Appendix
Figure B.8 Switch and Fuse Controller PCB
Installation Manual
Installation Manual
Appendix C:
Block Diagrams
Accutech LC 1200/ES 2200/IS 3200/BR 4200 systems
Overview Packet Contents
‰
‰
‰
‰
LC
LC
LC
LC
1200
1200
1200
1200
Single Door Kit (LCSD)
4’ Elevator (LCHL)
Double Door Kit (LCDD)
Hallway (LCHL)
‰
‰
‰
‰
ES 2200 - 4’ Single Door Unit (ESI4)
ES 2200 – 4’ Single Door Unit (ESR4)
IS 3200 – 4’ Single Door Unit (ESI4 + IS components)
IS 3200 – 4’ Single Door Unit (ESR4 + IS components)
‰ ES 2200 – 6’-8’ Double Door Unit (ESI68)
‰ IS 3200 – 6’-8’ Double Door Unit (ESI68 + IS components)
‰ ES 2200 – 6’ Elevator Unit (ESI68E) with Elevator Deactivation
‰ IS 3200 - 6’ Elevator Unit (ESI68E + IS Components) with Elevator Deactivation
‰ ES 2200 – 6’ Elevator Unit with PIR (ESI68E)
‰
‰
‰
‰
‰
‰
Double Elevator Unit (ESI68DE) with Elevator Deactivation
ES 2200 – Hallway Unit (ESI68H)
BR 4200 Generic Facility Floor Plan
BR Lockdown Configuration
ES 2200 / IS 3200 Wiring Guide
BR 4200 Wiring Guide
800-356-2671 |
Accutech | www.accutech-ics.com
Power
Outlet
PIR
Power
Outlet
(Passive Infrared Reader;
focused downward)
Part # 300302
(Drop Ceiling)
(Drop Ceiling)
Magnetic
Door Lock
Keypad
Part # 700228
Part # 650202
Magnetic Door
Position Switch
Keypad
Part # 650202
Elevator
Call Buttons
Part # 650514
4’
Door
LC Controller
4’
Elevator
Part # 700098
LC Controller
Part # 700098
LCSD - LC 1200 Single Door Kit
LCHL - LC 1200 Elevator (or Hallway) Kit
Part # 800121 includes:
Part # 800123 includes:
1 LC Controller (700098)
1 Keypad (650202)
1 Magnetic Contact (650514)
1 Cable Kit (700150)
1 LC Controller (700098)
1 Keypad (650202)
1 PIR (300302)
1 Cable Kit (700150)
800-356-2671 |
Accutech | www.accutech-ics.com
DOC.970088
Power
Outlet
PIR
Power
Outlet
(Passive Infrared Reader;
focused downward)
Part # 300302
(Drop
Ceiling)
(Drop Ceiling)
Optional Magnetic
Door Lock
Part # 700228
Optional Magnetic
Door Lock
Part # 700228
Magnetic Door
Position Switch
Part # 650514
Keypad
Keypad
Part # 650202
Part # 650202
LC Controller
LC Controller
Double Door
Part # 700098
Part # 700098
Hallway
LCDD - LC 1200 Double Door Kit
LCHL - LC 1200 Hallway (Elevator) Kit
Part # 800122 includes:
Part # 800123 includes:
1 LC Controller (700098)
1 Keypad (650202)
2 Magnetic Contact (650514)
1 Cable Kit (700150)
1 LC Controller (700098)
1 Keypad (650202)
1 PIR (300302)
1 Cable Kit (700150)
800-356-2671 |
Accutech | www.accutech-ics.com
DOC.970089
FPI
Dry Contacts
to Facility’s Fire Panel
(Fire Panel Interface)
Part # 700013
22/6
Receiver
Power
Outlet
Controller
(Drop Ceiling)
22/6
22/2
18/2 Shld
(Drop Ceiling)
22/2
18/6
22/6
22/4
Magnetic
Door Lock
Part # 700228
Magnetic Door
Position Switch
SAP
Multi-tone
Local Alert
(Staff Alert Panel)
Part # 700080
Part # 300150
Part # 650514
Keypad
Part # 650202
4’
Door
Transmit (Tx)
Wand antenna
Nurse’s Station
Part # 700068
Part # 800104 includes:
ES 2200 - Internal 4’ Single Door Unit (ESI4)
The Controller is mounted at the door.
Dashed lines represent wire path; numbers indicate gauge and conductor respectively.
800-356-2671 |
1 Controller + RX Antenna
1 Keypad (650202)
1 Magnetic Contact (650514)
1 Cable Kit (700150)
1 Transmit Wand (700068)
Accutech | www.accutech-ics.com
DOC.970070
REV.B
Controller
(remotely located)
EQUIPMENT ROOM
Composite Cable
Dry Contacts
to Facility’s Fire Panel
22/6
Power
Outlet
FPI
(Fire Panel Interface)
Part # 700013
External Receiver
Junction Box
22/2
22/2
18/6
22/12
22/6
(Drop Ceiling)
Part # 700228
Magnetic Door
Position Switch
Part # 650514
SAP
22/4
18/2 Shld
Magnetic
Door Lock
Multi-tone
Local Alert
(Staff Alert Panel)
Part # 700080
Part # 300150
Keypad
Part # 650202
4’
Door
Transmit (Tx)
Wand antenna
Nurse’s Station
Part # 700068
Part # 800110 includes:
ES 2200 - Remote 4’ Single Door Unit (ESR4)
The Controller is mounted remotely such as in an equipment room or utility closet.
Dashed lines represent wire path; numbers indicate gauge and conductor respectively.
800-356-2671 |
1 Controller + RX Antenna
1 Keypad (650202)
1 Magnetic Contact (650514)
1 Cable Kit (700150)
1 Transmit Wand (700068)
Accutech | www.accutech-ics.com
DOC.970071
REV.B
Controller
Receiver
18/2
22/6
Multiplexer
Part # 770177
Part # 770277
22/6
18/2
18/2
Power Supply
Part # 500250
(Drop Ceiling)
22/3 + # of Controllers
18/2
Part # 650514
22/4
18/2 Shld
Magnetic Door
Position Switch
GDP
Computer
Part # 650127
(Graphic Display
Panel)
Multi-tone
Local Alert
18/2
(Drop Ceiling)
COAX CABLE
22/2
22/2
18/6
22/6
Controller
Receiver
Part # 700228
Part # 700013
Power
Outlet
Dry Contacts
to Facility’s Fire Panel
Power
Outlet
Magnetic
Door Lock
FPI
(Fire Panel Interface)
Tag Test
Station
Part # 700050
Part # 300150
Part # 700020
Software
Part # 700169
Keypad
4’
Door
Transmit (Tx)
Wand antenna
Part # 700068
CAT 5
Part # 650202
Nurse’s Station
IS 3200 - Internal 4’ Single Door Unit (ESI4 + IS components)
The Controller is mounted at the door.
Dashed lines represent wire path; numbers indicate gauge and conductor respectively.
800-356-2671 |
Part # 800104 includes:
1 Controller + RX Antenna
1 Keypad (650202)
1 Magnetic Contact (650514)
1 Cable Kit (700150)
1 Transmit Wand (700068)
Accutech | www.accutech-ics.com
DOC.970072
REV.B
EQUIPMENT ROOM
22/6
22/6
Controller
Controller
FPI
Power Supply
(Fire Panel Interface)
Part # 500250
Part # 700013
Multiplexer
Part # 770177
Part # 770277
18/2
Dry Contacts
to Facility’s Fire Panel
18/2
External Receiver
Junction
Box
22/12
Composite Cable
Composite Cable
Power Outlet
(Drop Ceiling)
22/2
Part # 700228
Magnetic Door
Position Switch
(Graphic Display
Panel)
Multi-tone
Local Alert
Computer
Part # 650127
Tag Test
Station
Part # 700050
Part # 300150
Part # 650514
18/2
GDP
22/4
Magnetic
Door Lock
COAX CABLE
22/3 + # of Controllers
18/2 Shld
(Drop Ceiling)
22/2
18/6
External Receiver
Part # 700020
Software
Keypad
Part # 700169
Part # 650202
4’
Door
Transmit (Tx)
Wand antenna
CAT 5
Part # 700068
IS 3200 - Remote 4’ Single Door Unit (ESR4 + IS components)
The Controller is mounted remotely such as in an equipment room or utility closet.
Dashed lines represent wire path; numbers indicate gauge and conductor respectively.
800-356-2671 |
Accutech | www.accutech-ics.com
Nurse’s Station
Part # 800110 includes:
1 Controller + RX Antenna
1 Keypad (650202)
1 Magnetic Contact (650514)
1 Cable Kit (700150)
1 Transmit Wand (700068)
DOC.970073
REV.B
FPI
(Fire Panel Interface)
Part # 700013
22/6
Power
Outlet
Controller
(Drop Ceiling)
22/6
Receiver
Dry Contacts
to Facility’s Fire Panel
22/6
18/2 Shld
Part # 700228
Magnetic Door
Position Switch
18/6
(In Parallel)
22/2
(In Series)
22/4
Magnetic
Door Lock
18/2 Shld
22/2
(Drop
Ceiling)
SAP
Multi-tone
Local Alert
(Staff Alert Panel)
Part # 700080
Part # 300150
Part # 650514
Keypad
Part # 650202
Tx
antenna
Part # 700068
Double Door
Transmit (Tx)
Wand antenna
Nurse’s Station
Part # 700068
ES 2200 - Internal 6’- 8’ Double Door Unit (ESI68)
For double doors, two Transmit (Tx) Wand antennas are required to cover the larger opening
and Magnetic Door Locks and Magnetic Door Position Switches are wired so either door
opening will sound an alarm. Dashed lines represent wire path; numbers indicate gauge and
conductor respectively.
800-356-2671 |
Accutech | www.accutech-ics.com
Part # 800107 includes:
1 Controller + RX Antenna
1 Keypad (650202)
1 Magnetic Contact (650514)
1 Cable Kit (700150)
1 Transmit Wand (700068)
DOC.970074
REV.B
Controller
Receiver
18/2
22/6
Multiplexer
Part # 700177
Part # 700277
Power
Outlet
18/2
FPI
(Fire Panel Interface)
Part # 700013
18/2
22/6
Receiver
Power
Outlet
Power Supply
Controller
Part # 500250
(Drop Ceiling)
18/6
(In Parallel)
18/2 Shld
Part # 770228
Magnetic Door
Position Switch
22/2
(In Series)
22/4
Magnetic
Door Lock
18/2 Shld
GDP
Multi-tone
Local Alert
Computer
Part # 650127
(Graphic Display
Panel)
18/2
22/2
(Drop
Ceiling)
COAX CABLE
22/3 + # of Controllers
Tag Test
Station
Part # 700050
Part # 300150
Part # 700020
Software
Part # 650514
Part # 700169
Keypad
Part # 700068
Double Door
Transmit (Tx)
Wand antenna
CAT 5
Tx
antenna
Part # 650202
Part # 700068
Nurse’s Station
IS 3200 - Internal 6’- 8’ Double Door Unit (ESI68 + IS components)
For double doors, two Transmit (Tx) Wand antennas are required to cover the larger opening and
Magnetic Door Locks and Magnetic Door Position Switches are wired so either door opening will
sound an alarm. Dashed lines represent wire path; numbers indicate gauge and conductor
respectively.
800-356-2671 |
Accutech | www.accutech-ics.com
Part # 800127 includes:
1 Controller + RX Antenna
1 Keypad (650202)
2 Magnetic Contact (650514)
1 Cable Kit (700150)
2 Transmit Wands (700068)
DOC.970075
REV.B
ELEVATOR PENTHOUSE
22/6
Elevator
Deactivation
Part # 700027
Controller
22/6
Receiver
Power
Outlet
22/6
22/4
22/2
PIR
(Passive Infrared Reader;
focused downward)
Part # 300302
18/2 Shld
18/2 Shld
22/4
(Drop
Ceiling)
Tx
antenna
Part # 700068
SAP
Multi-tone
Local Alert
(Staff Alert Panel)
Part # 700080
Part # 300150
Keypad
Part # 650202
Elevator
Elevator
Call Buttons
Transmit (Tx)
Wand antenna
Part # 700068
ES 2200 - Internal 6’ Elevator Unit (ESI68E) with Elevator Deactivation
For elevators, two Transmit (Tx) Wand antennas are required to cover the larger opening and Elevator
Deactivation renders an elevator inoperative during an alarm event. Dashed lines represent wire path;
numbers indicate gauge and conductor respectively.
800-356-2671 |
Accutech | www.accutech-ics.com
Nurse’s Station
Part # 800108 includes:
1 Controller + RX Antenna
1 Keypad (650202)
1 PIR (300302)
1 Cable Kit (700150)
2 Transmit Wands (700068)
DOC.970076
REV.B
ELEVATOR PENTHOUSE
22/6
Controller
Elevator
Deactivation
Receiver
18/2
22/6
Part # 700027
Multiplexer
Part # 700177
Part # 700277
18/2
Receiver
FPI
(Fire Panel Interface)
Power
Outlet
Part # 700013
18/2
Dry Contacts
to Facility’s Fire Panel
22/6
Power
Outlet
Power Supply
Controller
Part # 500250
(Drop Ceiling)
22/2
PIR
18/2 Shld
18/2 Shld
22/4
(Passive Infrared Reader;
focused downward)
Part # 300302
Tx
antenna
Part # 700068
Multi-tone
Local Alert
GDP
Part # 300150
Transmit (Tx)
Wand antenna
Part # 700020
Software
Elevator
Call Buttons
Part # 700169
IS 3200 - Internal 6’ Elevator Unit (ESI68E + IS components)
with Elevator Deactivation
For elevators, two Transmit (Tx) Wand antennas are required to cover the larger opening and
Elevator Deactivation renders an elevator inoperative during an alarm event. Dashed lines
represent wire path; numbers indicate gauge and conductor respectively.
800-356-2671 |
Tag Test
Station
Part # 700050
Keypad
Part # 700068
Part # 650127
(Graphic Display
Panel)
Part # 650202
Elevator
Computer
CAT 5
(Drop
Ceiling)
18/2
22/4
COAX CABLE
22/3 + # of Controllers
Accutech | www.accutech-ics.com
Nurse’s Station
Part # 800108 includes:
1 Controller + RX Antenna
1 Keypad (650202)
1 PIR (300302)
1 Cable Kit (700150)
2 Transmit Wands (700068)
DOC.970077
REV.B
Receiver
Power
Outlet
Controller
22/6
22/4
(Passive Infrared Reader;
focused downward)
Part # 300302
18/2 Shld
18/2 Shld
Tx
antenna
Part # 700068
ES 2200 Zone
or
IS 3200 Zone
Nurse’s Station
22/2
PIR
22/4
(Drop
Ceiling)
Multi-tone
Local Alert
Part # 300150
Keypad
Part # 650202
Elevator
Elevator
Call Buttons
Transmit (Tx)
Wand antenna
Part # 700068
ES 2200 or IS 3200 Internal 6’ Elevator Unit (ESI68E)
with PIR (Passive Infrared Reader) installed
As an alternative to Elevator Deactivation, a PIR mounted on the ceiling focused
downward can cover an elevator.
800-356-2671 |
Accutech | www.accutech-ics.com
Part # 800108 includes:
1 Controller + RX Antenna
1 Keypad (650202)
1 PIR (300302)
1 Cable Kit (700150)
2 Transmit Wands (700068)
DOC.970078
REV.B
ELEVATOR PENTHOUSE
Elevator
Deactivation
22/6
Part # 700027
Power
Outlet
Controller
Receiver
(Drop Ceiling)
22/4
22/2
(Drop Ceiling)
Tx
antenna
Elevator
Call
Buttons
Part # 700068
18/2 Shld
Part # 300150
18/2 Shld
18/2 Shld
Multi-tone
Local Alert
Tx
antenna
Keypad
Part # 650202
Part # 700068
Tx
antenna
Part # 700068
Elevator
Elevator
4’ Maximum
Internal Double Elevator Unit (ESI68DE) with Elevator Deactivation
Part # 800120 includes:
For multiple elevators in close proximity to each other, three Transmit (Tx) Wand antennas are
required to cover the larger opening. Elevator Deactivation renders an elevator inoperative during an
alarm event. Dashed lines represent wire path; numbers indicate gauge and conductor respectively.
1 Controller + RX Antenna
1 Keypad (650202)
2 PIR (300302)
1 Cable Kit (700150)
3 Transmit Wands (700068)
800-356-2671 |
Accutech | www.accutech-ics.com
DOC.970079
REV.B
PIR
Remote
Zone
Receiver
(Passive Infrared Reader)
Part # 300302
Multi-tone
Local Alert
Part # 300150
Raceway
Raceway
Keypad
Part # 650202
Transmit (Tx )
Wand Antenna
Transmit (Tx )
Wand Antenna
Part # 700068
Part # 700068
ES 2200 or IS 3200 Remote Hallway Unit (ESR68H)
Part # 800115 includes:
Using a remote Zone Receiver and/or PIR, a hallway opening (or any other passageway) can be a
monitored zone. Wiring can be run from components to the Controller (not shown) through panduit,
PVC, or plastic raceway (shown) but not metal conduit.
1 Controller + RX Antenna
1 Keypad (650202)
1 PIR (300302)
1 Cable Kit (700150)
2 Transmit Wands (700068)
800-356-2671 |
Accutech | www.accutech-ics.com
DOC.970080
REV.B
RX
BR Rx
RX
AUXILIARY
RECEIVERS
BR
BR Rx
Rx
< 70 feet
BR Rx
BR Rx
< 70 feet between Rx
BR Rx
BR Rx
BR Rx
Controller
< 70 feet
< 70 feet between Rx
Rx
EXIT
Controller
Rx
Rx
MAIN ENTRANCE
ZONE
RECEIVERS
BR 4200 Generic Facility Floor Plan
In a BR 4200 system, Zone Receivers (Rx) and Auxiliary Receivers (BR Rx) are placed strategically throughout a facility. Receivers monitor 40 feet
outward in every direction; therefore, they should be positioned approximately 70 feet apart. The distance between BR Receivers is also dependant
upon a facility’s structure (e.g. concrete/metal lathe as opposed to drywall walls). Zone Receivers monitor both zone events and Band Removal events.
Auxiliary Receivers only monitor Band Removal events.
800-356-2671 |
Accutech | www.accutech-ics.com
BR Rx
Part # 670076
DOC.970081
REV.C
BR LOCKDOWN CONFIGURATION (see Chapter 21 for more information)
Part # 700038
Controller
Receiver
22/2
18/2
BR Lockdown
Relay Board
22/6
Power
Outlet
Multiplexer
Part # 770177
Part # 770277
18/2
FPI
(Fire Panel Interface)
Part # 700013
18/2
22/12
Receiver
Power
Outlet
Power Supply
Controller
Part # 500250
(Drop Ceiling)
18/6
(In Parallel)
18/2 Shld
Part # 770228
Magnetic Door
Position Switch
22/2
(In Series)
22/4
Magnetic
Door Lock
18/2 Shld
GDP
Multi-tone
Local Alert
Computer
Part # 650127
(Graphic Display
Panel)
18/2
22/2
(Drop
Ceiling)
COAX CABLE
22/3 + # of Controllers
Tag Test
Station
Part # 700050
Part # 300150
Part # 700020
Software
Part # 650514
Part # 700169
Keypad
Part # 700068
Double Door
Transmit (Tx)
Wand antenna
CAT 5
Tx
antenna
Part # 650202
Part # 700068
Nurse’s Station
BR LOCKDOWN - Internal 6’- 8’ Double Door Unit (ESI68 + IS components)
Part # 800107 includes:
For double doors, two Transmit (Tx) Wand antennas are required to cover the larger opening and Magnetic
Door Locks and Magnetic Door Position Switches are wired so either door opening will sound an alarm.
Dashed lines represent wire path; numbers indicate gauge and conductor respectively.
1 Controller + RX Antenna
1 Keypad (650202)
2 Magnetic Contacts (650514)
1 Cable Kit (700150)
800-356-2671 |
Accutech | www.accutech-ics.com
DOC.970084
REV.B
ES 2200 / IS 3200 Wiring Guide
ES 2200 / IS 3200 Tag
(interacts with Zone)
Zone Receiver
FPI
(Fire Panel Interface)
(if mounted remote
from Controller)
22 / 2
22 / 12
Part # 700013
Multi-tone
Local Alert/
Strobe
Multi-tone
Central Alert
22 / 2
Magnetic
Door Locks
Part # 300150
22 / 2
18 / 6
Voice Alert
Part # 770228
22 / 2
Part # 700019
Magnetic Door
Position Switch
CONTROLLER
22 / 2
Part # 650514
- OR -
Zone Receiver
(Built-in; pre-wired)
PIR
(Passive Infrared Reader)
22 / 4
Tag Test Station
Transmit (Tx)
or
(TTS)
Antenna(s)
(Wand or Multi-axis)
18 / 2 shielded per antenna
Part # 700068
22 / 6
Part # 300302
Timer
Keypad
(Access Control Device)
22 / 4
Part # 605202
Multiplexer
PBO
Part # 770177
Part # 770277
GDP
(Graphic Display Panel)
Part # 700050
22 / 4
Elevator
Deactivation
Part # 700000
22 / 6
Part # 700027
(Push Button Override)
Basic System
components
22 / 4
CAT5
Part # 700023
Computer
Part # 650127
800-356-2671 |
Accutech | www.accutech-ics.com
LEGEND
# of conductors =
# of zones + 3
Part # 700020
Optional System
components
XX / X
gauge/conductor
*Depending on zone configuration,
some cable may be multi-sourced
DOC.970082
REV.B
BR 4200 Wiring Guide
BR42 Tag
or
Cut Band Tag
(interacts with Zone)
Zone Receiver
FPI
(if mounted remote
from Controller)
(Fire Panel Interface)
22 / 2
22 / 12
Part # 700013
Multi-tone
Local Alert/
Strobe
22 / 2
Multi-tone
Central Alert
Part # 300150
Magnetic
Door Locks
22 / 2
18 / 6
Voice Alert
Part # 770228
22 / 2
Part # 700019
Magnetic Door
Position Switch
22 / 2
CONTROLLER
Part # 650514
Tag Test Station
Transmit (Tx)
or
(TTS)
Antenna(s)
- OR Zone Receiver
(Built-in; pre-wired)
PIR
(Wand or Multi-axis)
18 / 2 shielded per antenna
(Passive Infrared Reader)
22 / 4
Part # 700068
Part # 300302
22 / 6
Timer
Keypad
(Access Control Device)
22 / 4
22 / 4
BR Lockdown
Relay Board
22 / 6
(as needed)
Part # 670076
22 / 2
Multiplexer
Part # 770177
Part # 770277
# of conductors =
# of zones + 5
GDP
(Graphic Display Panel)
Part # 700050
Part # 650202
PBO
Part # 700038
(Push Button Override)
22 / 4
22 / 6
Part # 700027
Part # 700023
CAT5
Computer
Part # 650127
Part # 700000
Elevator
Deactivation
800-356-2671 |
Accutech | www.accutech-ics.com
LEGEND
BR 4200
Auxiliary Receivers
Part # 700020
Basic System
components
XX / X
Optional System
components
gauge/conductor
*Depending on zone configuration,
some cable may be multi-sourced
DOC.970083
REV.B
Installation Manual
Appendix D:
Troubleshooting
Installation Manual
Appendix D-1
Troubleshooting
This section contains solutions to possible system problems. As many system components (and
therefore functions) are interrelated you may be referred back and forth to different sections to
complete the troubleshooting.
Use the headings to locate your problem. Follow the solution list down until the problem is
remedied. You may not need to perform all solutions.
KEY:
Heading
Question(s)
Solution(s)
BEFORE YOU START…
Check all connections and wiring of
affected component(s)
Verify 110V AC power to the Controller
Verify Controller unit is in On position
No Tx indicator (LED 1, 2 or 3 is out)
Is antenna tuned correctly?
See Tuning procedure (page 4-7)
Is Tx Gain set too low?
Increase the Tx Gain (pot R6)
Is antenna mounted on or near metal?
Move antenna minimum 3 inches from any
metal or install a spacer block
Is antenna damaged?
Replace antenna (from another zone or a spare)
Is cable broken or pinched?
Check for broken or pinched cable
If still no Tx indicator…
Tx may be blown on Controller board
No Rx (LED14 is Green)
Is the Receiver tuned correctly?
See Tuning procedure (page 5-6)
Is the cable broken or pinched?
Check for broken or pinched cable
Is the Receiver damaged?
Replace Receiver (from another zone or a spare)
Is the Receiver antenna damaged?
Replace Receiver antenna
Is Receiver getting power?
(from another zone or a spare)
Verify 12V DC (or 6V DC if ES 2000 Receiver)
If still no Rx indicator…
Rx may be blown on Controller board
D-2 Appendix
Tags (no detection)
Tag is not detected
Tag (turned on, functioning) is not detected
Installation Manual
Use a TAD to verify Tag is turned on and
functioning properly
See “No Tx indicator” section
See “No Rx” section
False Tag Detection (nuisance alarms)
Is another zone setting this zone into alarm?
Implement Stagger Tuning (page 4-6)
Are patient rooms adjacent to monitored zone?
Reduce Tx wand antenna sensitivity (page 4-7)
Reduce Receiver sensitivity (page 5-6)
Keypad
Does not reset
Verify code
Was incorrect code entered 3 times?
If so, Keypad will lockout user for 90 seconds
(Green LED blinks during this time)
Verify proper wiring and voltage
Replace Keypad
(from another zone or a spare)
Tx Supervise alarming (LED14, steady Red)
Are metal carts in front of antennas?
Remove metal carts from area
Is antenna damaged?
Replace antenna (from another zone or a spare)
Is cable broken or pinched?
Check for broken or pinched cable
Is the antenna(s) tuned properly?
See Tuning procedure (page 4-7)
Is Tx Supervise threshold set too high?
See Tuning procedure (page 4-7)
Installation Manual
Appendix D-3
Door Ajar indicator alarming (LED8, steady Red)
Is door propped open?
Check
Is door traffic high zone?
Extend Door Ajar delay time (see page 22-1)
Is monitored zone an Elevator/Hallway
with a PIR ?
Disconnect Door Ajar feature by removing
wire to Receiver on both ends
Loiter indicator alarming (LED9, steady Yellow)
Is patient in monitored zone?
Address situation
Is patient in room next to monitored zone?
Reduce Tx wand antenna sensitivity (page 4-7)
No functions working
If none of these features are working…
Check output on Controller with DMM.
If outputs are good, check wiring and
connections.
If any outputs are not functioning, Controller
may need replacing.
D-4 Appendix
Lock Operation Verification
From Controller:
Installation Manual
1. Verify 12V AC output at P10
2. Label and remove wires in P4
connector
3. Jumper “Fire +V In” to “Fire +V Out)
4. With a Tag in monitored zone, use an
ohmmeter to check for a closed contact
across “Lock N.O.” and “Lock Comm”
5. When you remove Tag from zone, this
contact should then open
6. If these actions do not occur then the
Controller board is defective
7. If board tests good, continue to
“At Lock:”
At 3101 Lock:
1. Verify 12V AC at Pins 1 & 2
(Green LED1 should be on in nonenergized state)
2. Using a jumper wire or needle-nose
pliers, jumper Pin 3 to Pin 4.
(This should energize the Lock; the
Green LED1 will change to Red)
3. Use a jumper wire or needle-nose
pliers to short Pins 5 & 6.
(This will de-energize or reset Lock;
LED1 will turn off for as long as pins 5
& 6 see a closed contact)
4. NOTE: LED2 should be lit at all times,
if it is flashing or not illuminated then
the Lock board is defective.
Installation Manual
Appendix D-5
LED14 (Supervisor Indicator)
LED14 (Supervisor Indicator) indicates if there is a problem with the system’s Tx wand antenna(s)
and/or Receiver(s).
LED14 is a visual indicator of supervisor status; therefore you can troubleshoot without having to
listen to the piezo buzzer alarm. You may silence the piezo buzzer alarm by removing jumper
JP13 on the Controller.
NOTE: If LED14 indicates any sort of problem, before moving to more advanced troubleshooting
steps, first check all wire connections on the Controller, the Tx wand antenna(s), the Receiver(s)
and any splices at junction boxes.
LED14 Status, Color
Type of Problem
Refer to
n/a
n/a
On, Yellow
Tx wand antenna
and Receiverrelated problem
Yellow
section
Improper Wiring
Improper Tuning
Tag in the zone
Metal Nearby
Improper setting of pots
(R4, R6, R12, R26)
Faulty Tx wand antenna
or Receiver
On, Green
Receiver-related
problem
Green
section
Improper Wiring
Tag in the zone
Improper setting of pots
(R4, R6, R12, R26)
Faulty Receiver
Tx wand antennarelated problem
Red
section
Metal Nearby
Improper Wiring
Improper Tuning
Faulty Tx wand antenna
Off
On, Red
Caused By
n/a
D-6 Appendix
Installation Manual
LED14 Status: Yellow
When LED14 displays Yellow it indicates a Tx wand antenna problem and a Receiver-related
problem. Follow the Green section first (to rule out a Tx wand antenna problem) and then, if
necessary, the Red section second.
LED14 Status: Green
When LED14 displays Green it indicates a Receiver-related problem.
To remedy this condition, use the following instructions:
1. Check for and remove any Tags that are in the zone or adjacent zones
2. On the Controller, move jumper JP5 to position 1 and wait 20 seconds
NOTE:
If system is working properly, LED14 will flash Green once every 8 seconds.
If the system in not working properly, LED 14 will be steady Green for 8 seconds and
then off for one second.
If LED14 continues to be Green for 8 seconds and then off for one second:
4.
On the Receiver, check potentiometer R19 for proper setting (page 5-6)
If LED14 continues to be Green for 8 seconds and then off for one second:
5.
Receiver may be faulty; swap with known working or spare
6.
If still a problem, consult your Accutech Representative
Installation Manual
Appendix D-7
LED14 Status: Red, one Tx Wand antenna
If LED1 is dim or off:
1. Check the “X” Tx Wand antenna for:
Damage
Proper Wiring (page 4-4)
Metal nearby (in wall or objects)
Proper Tuning (page 4-7)
If LED1 is bright:
2. On the Controller, reconnect P2 (Receiver)
3. Move jumper JP5 to position 1 and wait 20 seconds
If LED1 goes off, reset jumper JP5 and potentiometer R26 to their proper settings (see Appendix
for info on JP5 and R26)
If LED1 remains Red, Tx wand antenna may be faulty; swap with known working or spare
If still a problem, consult your Accutech Representative
D-8 Appendix
Installation Manual
LED14 Status: Red, two Tx Wand antennas
In a two Tx wand antenna system, LED1 and LED2 should illuminate alternatively.
1. Make sure jumper JP4 is in position 2-3
If LED1 (“X” antenna indicator) and LED2 (“Y” antenna indicator) are not illuminating
alternatively:
2. Check the “X” and “Y” Tx Wand antennas for:
Metal nearby (in wall or objects)
Damage
Proper Wiring (page 4-4)
Proper Tuning (page 4-7)
If LED1 and LED2 are not illuminating alternatively and LED2 is bright:
4. Reconnect P2 (Receiver) on the Controller
5. Move jumper JP5 to position 1 and wait 20 seconds
If LED2 goes off, reset jumper JP5 and potentiometer R26 to their proper settings (see Appendix
for info on JP5 and R26)
If LED2 remains Red, Consult your Accutech Representative.
Installation Manual
Appendix D-9
LED14 Status: Red, three Tx wand antennas
In a three Tx Wand antenna system, LED1, LED2 and LED3 should illuminate alternatively.
1. Make sure jumper JP4 is in position 1-2
If LED1 (“X” antenna indicator), LED2 (“Y” antenna indicator) and LED3 (“Z” antenna
indicator) are not illuminating alternatively:
2. Check the “X”, “Y” and “Z” Tx Wand antennas for:
Metal nearby (in wall or objects)
Damage
Proper Wiring (page 4-4)
Proper Tuning (page 4-7)
If LED 1, 2 and 3 are not illuminating alternatively and LED3 is bright:
3. Reconnect P2 (Receiver) on the Controller
4. Move jumper JP5 to position 1 and wait 20 seconds
If LED3 goes off, reset jumper JP5 and potentiometer R26 to their proper settings (see Appendix
for info on JP5 and R26)
If LED3 remains Red, Consult your Accutech Representative.
Installation Manual
Notes
Notes
Installation Manual
Installation Manual
Notes
Notes
Installation Manual
Installation Manual
Appendix E:
Product Cut Sheets
Security Systems made for Life.
CUT SHEETS
3000 Magnetic Lock
Accutech 3101 Magnetic Lock
Accutech Software
Automatic Door Deactivation
BR 4200 Auxiliary Receiver
BR42 Tag
Central Alarm
Composite cable
Controller
Elevator Deactivation
ES 2200 System Tags
Fire Panel Interface (FPI)
Graphic Display Panel (GDP)
IS 3200 System Tags
Keypad
LED Tag
Local Alarm
Magnetic Switch
Multi-Tone Local Alarm (MTLA)
Multiplexer
Push Button Override (PBO)
Passive Infrared Reader (PIR)
Power Supply
PTAD
Staff Alert Panel (SAP)
Speakers
Tag Activator/Deactivator (TAD)
Tag Test Station (TTS)
Timer
Tx wand antenna
Voice Alarm
Zone Receiver
Innovative Control Systems Inc.
10125 South 52nd Street Franklin, WI 53132
[800.356.2671] [Fax 414.423.4448]
www.accutech-ics.com
CUT SHEET: 3000 Magnetic Lock
The 3000 Magnetic Lock will engage when the zone Controller detects a Tag in the Tx Activation Field. The Lock will
remain engaged as long as the Tag is in the Tx Activation Field. When the Tag leaves the Tx Activation Field, the Lock will
disengage after an adjustable period of time (0-120 seconds).
SAFETY FEATURES:
The Lock will NOT engage (or will disengage) when the facility’s Fire Alarm is activated or power is lost.
ELECTRICAL:
Operating Voltage: 12 or 24V AC/DC
Current Consumption at 12V: .42 amp
Current Consumption at 24V: .21 amp
Cable: non-shielded 18-gauge, 2-conductor
MECHANICAL:
Lock Size: 1-1/2” x 2-3/4” x 11”
Armature Size: 1-1/2” x 2-3/8” x 3-5/8”
Finish: US28 Satin Aluminum with clear anodize
Mounting Hardware: 5 #10 PNHD Self Tapping Screws 1” long
Weight: 9 US pounds
OPERATING CHARACTERISTICS:
Holding Force: 1500 pounds
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
3000 Magnetic Lock
UL Listed:
GWXT.R15538
Model Number: ML
Part Number: 700218
Due to existing UL listing (above), not
required to be listed under UL 294
(BP9480)
DUTY CYCLE:
Rated for continuous use.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Accutech 3101 Magnetic Lock
The Accutech 3101 Magnetic Lock is custom-designed to our specifications and should not be purchased directly
from the manufacturer.
WARNING:
The 3101 Magnetic Lock will engage when the zone Controller detects a Tag in the Tx Activation Field. The Lock will
remain engaged as long as the Tag is in the Tx Activation Field. When the Tag leaves the Tx Activation Field, the Lock will
disengage after an adjustable period of time (0-120 seconds).
SAFETY FEATURES:
The Lock will NOT engage (or will disengage) when the facility’s Fire Alarm is activated or power is lost.
The 3101 Magnetic Lock also incorporates Delayed Egress Circuitry that complies with N.F.P.A. 101 Life Safety Codes 52.1.6.1. If engaged, the Lock will release within 15 seconds (after 1-3 second nuisance delay) whenever a maintained force
(less than 15 pounds required) is applied to the door. An audible tone enunciates both countdown and release. When the Lock
releases, the red LED will turn solid green and the alarm will sound continuously.
ELECTRICAL:
Operating Voltage: 12 V AC
Current Consumption: 450 mA
Cable: non-shielded 18-gauge, 6-conductor
MECHANICAL:
Lock Size: 3” x 2 ¾” x 11”
Armature Size ½” x 2-5/16” x 7-3/8”
Standard Finish: Satin Aluminum-US28
Mounting Hardware: 5 #10 PNHD Self Tapping Screws 1” long
Weight: 11 US pounds
OPERATING CHARACTERISITICS:
Holding Force: 1200 pounds
Once locked, the Lock will disengage when any of the
following conditions occur:
All Tags leave the Tx Activation Field
A Keypad Reset
A PBO is activated
The facility’s fire alarm is activated.
Power is removed from the Lock.
The Central Override is activated.
When a maintained force (less than 15 pounds required)
is applied to the door for an adjustable period of time
(1-3 seconds).
Accutech 3101 Magnetic Lock
Model Number: MLE
Part Number: 700228
UL Listed:
FWAX.SA9532
Auxiliary Locks listed 2N98
Special Arrangements listed 1M59
Due to existing UL listing (above), not
required to be listed under UL 294
(BP9480)
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Lock LED status during normal operation:
Green – Power indicator
Red – Lock engaged (Tag detected in zone)
Red blinking – Egress countdown (15-30 seconds adjustable)
No Power To LED – Escort function or Reset
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Accutech Software
Accutech Security Systems are NOT computer-dependant.
The Software is for reporting purposes only and does not affect nor control the physical Accutech Security System.
The Accutech Software is installed on each monitoring PC and is used to display incoming event information. Using the
facility’s floor plan as the background, zone-specific icons (i.e., doors, elevators, stairwells, hallways, and BR 4200
Auxiliary Receivers) are placed at each monitored zone’s location and become animated when an alarm occurs.
KEY FEATURES:
Floor plans can be monitored locally or remotely.
Customizable event handling (displaying, logging, clearing)
Password protected operations
Tags are assigned to specific patients, residents, infants, or assets.
Customizable printable Reports (sort by start/end date, event type, zone, and/or patient)
ƒ
ƒ
ƒ
ƒ
ƒ
MINIMUM SYSTEM REQUIREMENTS:
ƒ
1.80 GHz processor
ƒ
17” CRT Monitor (capable of displaying 1024x768
pixels in 16-bit high color)
ƒ
20 GB Hard Drive
ƒ
1 GIG DDR2 RAM
ƒ
Integrated Video
ƒ
32x CD-ROM Drive
ƒ
Keyboard
ƒ
Mouse
ƒ
Mouse Pad
ƒ
Speakers (or integrated sound)
ƒ
Windows 2000 SP4 or Windows XP SP2
ƒ
1 Serial 9pin COM PORT
RECOMMENEDED:
ƒ
2.33 GHz processor or higher, 1333 FSB
ƒ
17” LCD Flat Panel Monitor (capable of displaying
1280 x1024 pixels in 32-bit high color)
ƒ
80 GB Hard Drive
ƒ
2 GIG DDR2 RAM, Non-ECC, 887 MHz
ƒ
Integrated Video
ƒ
24x CD-RW/DVD Combo Drive
ƒ
USB Keyboard
ƒ
USB Mouse
ƒ
Mouse Pad
ƒ
Speakers (or integrated sound)
ƒ
Windows XP SP2
ƒ
1 Serial 9pin COM PORT
Software Screenshot example
Model Number: SW
Part Number: 700169
If networking multiple computers:
ƒ 10/100 Network Interface Card (NIC) in each PC
ƒ Cross over cable, if networking only 2 Accutech
PCs10/100 Workgroup Switch or Hub, if
networking more than 2 Accutech PCs
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Automatic Door Deactivation
In automatic door applications (doors that open via a motion sensor or push paddle), the Accutech System can deactivate this
feature when a Tag enters a monitored zone’s Tx Activation Field.
ELECTRICAL:
Operating Voltage: 12V DC
Current Consumption: 120 mA maximum
Contact Rating: 100 mA / 12V DC
Cable: need minimum 22-gauge, 6-conductor
MECHANICAL:
Construction: Metal case
Enclosure size: 6.00” x 6.00” x 4.00”
Enclosure weight: 3.85 US pounds
OPERATING CHARACTERISTICS
Dry contacts are provided for the automatic door
company’s use.
ENVIRONMENAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Automatic Door Deactivation
Model Number: ADD
Part Number: 700033
UL Listed 294 (BP9480)
Access Control Accessory
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: BR 4200 Auxiliary Receiver
BR 4200 Auxiliary Receivers only monitor Band Removal and Band Compromise events. They monitor approximately 40
feet outward in every direction; therefore, they should be positioned 70 feet apart to avoid confusion about the location of a
Band Removal alarm.
When choosing the location and number of Auxiliary Receivers, be sure to consider the following:
the facility’s structure (i.e., concrete/metal lathe as opposed to drywall walls or foil-backed ceiling tiles).
keep a minimum distance of 4 feet away from fluorescent lighting and air handling equipment.
Band Removal alarms can be generated anywhere within a facility, not just exit points; this includes bathrooms,
visiting areas, storage rooms, and laundry rooms.
ELECTRICAL:
Operating Voltage: 12V DC regulated
Current Consumption: 50 mA maximum
Cable: needs minimum 22-gauge, 6-conductor
MECHANICAL:
Size: Mounted in a 4” x 4” x 2” electrical box.
*Allow 7” depth for clearance of the BNC Rubber
Duck antenna
Weight: 1 lb. 4.5 oz. total (Rx + Box + Duck)
OPERATING CHARACTERISTICS:
Transmit Frequency: 418 MHz
Receive Frequency: 418 MHz
Frequency range: 40 feet radius (360º)
BR 4200 Auxiliary Receiver
Model Number: ESRR
Part Number: 670076
Jumpers settings:
JP1 (SS)
Off
JP2 (Rx Test)
Off
JP3 (Tag D)
Off
JP4 (BR)
On
JP5 (Reset)
Off
UL Listed 294 (BP9480)
Access Control Accessory
ENVIRONMETNAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
BR 4200 Auxiliary Receiver (PCB)
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: BR42 Tag
BR42 Tags, only used in BR 4200 Systems, are small wristwatch-sized devices worn by an infant.
They feature Intelli-Band Technology, which will alarm if the band is loosened, cut, saturated, removed, or tampered with.
BR42 Tags are assigned to a specific infant via the Tag Test Station and Accutech Software. Once assigned, the computer
associates a name, room number, and any other pertinent information about the infant with that Tag.
ELECTRICAL:
BR42 Tags operate by internal battery.
The Tags have been engineered for greater than 12 months usage and
can be activated/deactivated with a TAD.
MECHANICAL:
Size: 1¼” x 1¾” x ¾”
Weight (with band): 1 ounce
OPERATING CHARACTERISTICS:
Transmit Frequency: 418 MHZ
Receive Frequency: 128-133 kHz
ATTACHMENT:
BR42 Tags are attached to infants with an elastic cloth band (Latexfree). The BR42 band has conductive fiber stripes that must be in
contact with both the infant’s skin and the gold contacts on the Tag.
The band must be routed properly through the Tag case for the
system to function properly. Tags are typically attached to a wrist or
ankle. For smaller infants, placing the Tag around the thigh is also
acceptable.
Model Number: BR
Part Number: 670015
UL Listed 294 (BP9480)
Access Control Accessory
MAINTENANCE:
BR42 Tags are reusable but they must be thoroughly cleaned
and sanitized between applications.
Acceptable cleaning methods:
Antibacterial wipes or Hydrogen peroxide (wipe, do not soak)
BR42 Tag bands are for one-time use only.
If the band becomes soiled, replace the band and clean the Tag.
TESTING:
There are 4 ways that you can test BR42 Tags:
Enter a monitored zone (Alarm may sound)
Remove the band (Alarm will sound)
With a TAD
With a PTAD
STORING:
To preserve battery life and prevent nuisance alarms, BR42 Tags
should be turned off with a TAD, stored away from sources of
electrical noise, and stored in a metal container with lid. Extra Tag
bands should be stored in a clean and dry environment.
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Central Alarm
The Central Alarm is a multi-tone alarm. It consists of a Tone Generator that drives speakers located throughout the facility.
There are eight different tones available. You may choose to assign a separate tone for each zone, or multiple zones to just
one tone. The Central Alarm is located in its own enclosure and contains its own power supply, a Tone board, a Relay board
and terminal strips.
ELECTRICAL:
Power Requirements: 120V AC, 15 amp circuit
Current Consumption: 1.3 amps maximum
Zone alarm input: 12V DC
MECHANICAL:
Construction: Metal case
Enclosure size: 12.50” x 12.50” x 3.75”
Weight (including enclosure): 12 US pounds
OPERATING CHARACTERISITICS:
Alarm Output: up to 115db at 10 feet with
12V DC/variable
Speakers: 8 ohms, 15 watts
Maximum Load: 5 speakers
Eight Distinctive Channels and Sounds
Rapid Yelp
Standard Yelp
Hi-Lo sweep
European Hi-Lo
Steady
Pulsing Horn
Steady Horn
Unique Synthesized Bell
Central Alarm
Model Number: CA3
Part Number: 700026
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
8 ohm Speaker with Mounting Plate
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Composite Cable
Accutech Composite Cable is designed for wire runs from the Controller to a junction box when the Controller is mounted
away from the zone and is plenum rated.
SPECIFICATIONS:
A four-element Plenum-rated composite cable
Element 1: 18 gauge 4 conductor shielded Mid-Cap
(Color code: orange, yellow, white, green)
Element 2: 18 gauge 4 conductor non-shielded
(Color code: red, black, blue, brown)
Element 3: 24 gauge 2 conductor shielded (Color
code: gray, violet)
Element 4: 25 gauge 14 conductor non-shielded
(Color code: white, green, beige, brown, orange,
blue, pink, yellow, red, black, white/blue,
white/brown, white/red, white/green)
Each element is individually wrapped with a clear
mylar binder and all elements are cabled together
Jacket Material: Low Smoke Polyvinylchloride
(PVC)
Jacket color: yellow
Jacket Ripcord: Yes
Jacket Print: “18 AWG 4C SHIELDED + 18 AWG
4C + 24 AWG 2C + 24 AWG E171202 (UL) CL3P
OR CMP C (UL) 75 º www.accutech-ics.com
800-356-2671”
Ascending/Descending Footage Markers
Diameter: nominal 0.386”
Made in accordance with UL Subject 444, NEC
Type CMP
Model Number: CC
Part Number: 200371
Composite Cable
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Controller
The Controller coordinates and controls all of the devices and functions of the Accutech Systems. It can be located at the
zone (above the drop ceiling) or remotely (in an equipment room).
ELECTRICAL:
Power Requirements: 120V AC, 1.0 amp
*A dedicated 15-amp circuit with emergency backup is
recommended.
MECHANICAL:
Construction: Metal Case
Enclosure size: 16.00” x 9.60” x 3.25”
Weight (including enclosure/Receiver): 11 US pounds
OPERATING CHARACTERISITICS:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Model Number: ESI or ESR
Part Number: 700035
UL Listed 294 (BP9480)
Access Control Unit
Controller Dimensions
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Elevator Deactivation
Elevator Deactivation Circuitry is designed to prevent someone (or an asset) wearing an Accutech Tag from using an elevator
to leave a monitored floor. Using Relays enclosed in the Elevator Deactivation Relay Cabinet, the Elevator Company is able
to interface with the Accutech System.
Therefore:
If a Tag enters a monitored elevator zone, the elevator’s call button on that floor will be deactivated
(Call buttons on other floors are unaffected and no one is restricted from coming to the floor).
When a Tag is in the zone (or approaches the zone) and the elevator doors are open, an alarm will sound and the
elevator doors will remain open.
If the elevator car is en route to the floor when a Tag approaches the zone, the elevator will arrive on the floor, the
door(s) will open, and the system will alarm.
ELECTRICAL:
Operating Voltage: 12V DC
Current Consumption: 120 mA maximum
Contact Rating: 100 mA / 12V DC
Cable: need minimum 22-gauge, 6-conductor
MECHANICAL:
Construction: Metal case
Enclosure size: 7.80” x 8.25” x 3.75”
Enclosure weight: 3.5 US pounds
OPERATING CHARACTERISITICS:
Dry Contacts supplied by Elevator Company for
door switch
12V DC Alarm Voltage energizes K1 Relay to
deactivate the Car when a Tag is detected and the
elevator door is open.
12V DC Tag Detect Voltage energizes K2 Relay
to deactivate the Call Button when a Tag is
detected.
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Elevator Deactivation
Model Number: ED
Part Number: 700027
UL Listed 294 (BP9480)
Access Control Accessory
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: ES 2200 System Tags
ES 2200 System Tags are small wristwatch-sized devices worn by a resident or attached to an asset. When a resident or
patient enters a Tx Activation Field, the Tag sends a signal to the zone Controller via the Receiver. The zone Controller
processes this information for appropriate control action or response (e.g., sounding alarms, locking doors).
Available in LT (Long Term) or SB (Slotted Back) cases. LT Tags are used for resident care. SB Tags are used on small
infants and assets. “22” and “32” refer to the program running inside the Tag. The 22 program is meant strictly for ES
systems. The 32 program can be used in either ES or IS systems and displays a low battery condition.
ELECTRICAL:
ES 2200 System Tags operate by internal battery.
The Tags have been engineered for greater than 12
months usage and can be activated/deactivated with a
TAD.
MECHANICAL:
LT Size: 1¼” x 1½” x ½”
SB Size: 1½” x 1½” x ½”
LT/SB Weight (with band): 0.5 ounce
OPERATING CHARACTERISTICS:
Transmit Frequency: 418 MHZ
Receive Frequency: 128-133 kHz
ATTACHMENT:
ES 2200 System Tags are attached with a nylon-meshreinforced vinyl band. The band is designed to resist
tearing caused by pulling or chewing on the band.
However, if the band becomes frayed or torn it will
need to be replaced. In long-term applications, the
band should be replaced periodically for cleanliness.
Tags are typically attached to a wrist or ankle.
MAINTENANCE:
ES 2200 System Tags are reusable but they must
be thoroughly cleaned and sanitized between
applications.
Acceptable cleaning methods:
Antibacterial wipes or Hydrogen peroxide
(wipe, do not soak)
ES 2200 Tag bands are for one-time use only.
In long-term applications, periodically replace the
bands and clean the Tags.
TESTING:
There are 3 ways that you can test ES 2200 System
Tags:
Enter a monitored zone (Alarm may sound)
With a TAD
With a PTAD
STORING:
Ideally, to preserve battery life and prevent nuisance
alarms, ES 2200 System Tags should be turned off
with a TAD, stored away from sources of electrical
noise, and stored in a metal container with lid. Extra
Tag bands should be stored in a clean and dry
environment.
Model Number: LTY
Part Number: 77E018
Model Number SBY
Part Number 77EO16
UL Listed 294 (BP9480)
Access Control Accessory
VISUAL PULSE LED:
The Visual Pulse LED indicates the Tag’s current mode
off
on
Tag LED Status
LED Light Pattern
LT, SB Tags
None
Tag is off.
Active, not in zone
Active, in zone
BR, CB Tags
None
Tag is off.
Active, not in zone,
non-Band Alarm
Active, in zone
(may be in Band Alarm)
Active, not in zone
Band Alarm mode,
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Fire Panel Interface (FPI)
The Fire Panel Interface (FPI) ensures, in the event of a fire, the Magnetic Lock(s) and/or Elevator Deactivation Circuitry
will be disengaged. Accutech follows NFPA codes and regulations. Therefore, in the event of a fire, all Accutech restraints
will be disabled (audial and visual alarms remain intact).
For each FPI unit used, one set of dry contacts will be needed from the facility’s fire panel.
Each FPI unit provides dry contact outputs for up to eight Controllers.
ELECTRICAL:
Operating Voltage: 12V DC
Current Consumption: 120 mA maximum
Contact Rating: 2 amps/24V DC
Cable: needs minimum 22-gauge, 2-conductor
non-shielded to each Controller
MECHANICAL:
Enclosure size: 6.29” x 5.68” x 2.00”
Weight: 25 ounces
OPERATING CHARACTERISTICS:
Fire Panel Alarm State: Open contacts
Contact State: N.O. during alarm state
N.C. during operating state
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
Fire Panel Interface (FPI)
Model Number: FPI
Part Number: 700013
UL Listed 294 (BP9480)
Access Control Accessory
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Graphic Display Panel (GDP)
A Graphic Display Panel (GDP) provides the staff with a visual representation of the floor being monitored. GDPs are
custom-made to a facility’s floor plan and notify staff when an alarm or event occurs in a monitored zone through a piezo
buzzer and alarm-specific LEDs. Each monitored zone is labeled and marked with an LED that will light to indicate that an
Alarm Condition has occurred for that particular zone. In addition, a “Fire Alarm” LED will light on the display if the fire
circuit is activated.
ELECTRICAL:
Operating Voltage: 12V DC
Current Consumption: 60 mA per 8-zone board
Cable: Dependant on number of zones + 3
MECHANICAL:
Sizes available: 11”x17”, 13”x19”, custom
Weight: dependant on size, number of zone
(approximately 5 US pounds)
OPERATING CHARACTERISTICS:
Pre-selected color themes or custom color matching
available.
Built-in Sounder
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Graphic Display Panel (GDP) example
Model Number: GDP
Part Number:
700050 (1-16 zone; 11”x17”)
700052 (17-32 zone; 11”x17”)
700061 (1-16 zone; 13”x19”)
700062 (17-32 zone; 13”x19”)
700063 (33-48 zone; 13”x19”)
UL Listed 294 (BP9480)
Access Control Accessory
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: IS 3200 System Tags
IS 3200 System Tags are small wristwatch-sized devices worn by a resident, infant, or attached to an asset. When a resident
or patient enters a Tx Activation Field, the Tag sends a signal to the zone Controller via the Receiver. The zone Controller
processes this information for appropriate control action or response (e.g., sounding alarms, locking doors).
IS 3200 System Tags are assigned to a specific infant via the Tag Test Station and Accutech Software. Once assigned, the
computer associates a name, room number, and any other pertinent information about the infant with that Tag.
Available in a LT (Long Term) case. “22” and “32” refer to the program running inside the Tag. The 22 program is meant
strictly for ES systems. The 32 program can be used in either ES or IS systems and displays a low battery condition.
ELECTRICAL:
IS 3200 System Tags operate by internal battery.
The Tags have been engineered for greater than 12 months usage and
can be activated/deactivated with a TAD.
UL Listed 294 (BP9480)
Access Control Accessory
MECHANICAL:
Size: 1¼” x 1½” x ½”
Weight (with band): 0.5 ounce
OPERATING CHARACTERISTICS:
Transmit Frequency: 418 MHZ
Receive Frequency: 128-133 kHz
ATTACHMENT:
IS 3200 System Tags are attached with a nylon-mesh-reinforced
vinyl band. The band is designed to resist tearing caused by pulling
or chewing on the band. However, if the band becomes frayed or
torn it will need to be replaced. In long-term applications, the band
should be replaced periodically for cleanliness. Tags are typically
attached to a wrist or ankle.
Model Number: LTY
Part Number: 77I018 (LTY)
UL Listed 294 (BP9480)
Access Control Accessory
MAINTENANCE:
IS 3200 System Tags are reusable but they must be thoroughly
cleaned and sanitized between applications.
Acceptable cleaning methods:
Antibacterial wipes or Hydrogen peroxide (wipe, do not soak)
IS 3200 Tag bands are for one-time use only.
In long-term applications, periodically replace the bands and
clean the Tags.
TESTING:
There are 3 ways that you can test IS 3200 System Tags:
Enter a monitored zone (Alarm may sound)
With a TAD
With a PTAD
STORING:
Ideally, to preserve battery life and prevent nuisance alarms, IS
3200 System Tags should be turned off with a TAD, stored away
from sources of electrical noise, and stored in a metal container with
lid. Extra Tag bands should be stored in a clean and dry
environment.
Model Number: SBY
Part Number: 77I016 (SBY)
UL Listed 294 (BP9480)
Access Control Accessory
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Keypad
The Keypad is used to escort residents through a monitored zone and to reset zone equipment once an alarm has occurred.
Up to 56 different (3 to 8 digit) user codes can be used to reset the alarm and to activate the Escort function.
ELECTRICAL:
Operating Voltage:
UL rated at 12V DC
Manufacturer rated at 9 to 16V DC
Stand-by Current Drain: 15 mA typical
Current Drain with outputs active: 55 mA typical
Contacts: 10 A / 30V AC/DC
Cable: minimum 22-gauge, 4-conductor
MECHANICAL:
Size: 4-5/8” x 2-7/8” x 1-3/8”
Weight: 4.3 ounces
Mounting: Flush or Surface Mount
*Metal box not recommended
OPERATING CHARACTERISTICS:
Power Failure: EEPROM retains programmed data
during power failures.
Relay Control: Programmable 1-98 seconds
Keypad (Flush Mount)
(box not included)
Model Number: KD
Part Number: 650202
LED Status:
Green – Escort or Reset
Yellow – Power
Red - Alarm
UL Listed 294 (BP9480)
Access Control Accessory
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Keypad (Surface Mount)
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: LED Tag
DISCLAIMER: Due to each facility’s unique environment, a LED Tag cannot give an exact measurement of zone coverage;
it can only give an estimation of zone coverage. Furthermore, at this time, the LED Tag is not able to test Auxiliary Band
Removal Receivers.
A LED Tag is used to verify proper zone coverage during installation, adjustment, or testing of a monitored zone.
Proper zone coverage fully protects the intended area (door, elevator, hallway, or any other passageway) without extending
into other areas (in front, in back, on sides, above, and beneath the intended area).
Monitored zones emit a Tag-activating signal called the Tx Activation Field. When a Tag enters a zone’s Tx Activation
Field, the system will detect the Tag and take appropriate action response.
A LED Tag can enter and detect a zone’s Tx Activation Field without causing alarms making it a quick and easy way to
verify proper zone coverage. This is not only useful in ensuring complete zone coverage but also in locating areas where a Tx
Activation Field may be extending into common areas and causing nuisance alarms.
ELECTRICAL:
LED Tags operate by internal battery.
The Tags have been engineered for greater than 12 months usage
and can be activated/deactivated with a TAD.
MECHANICAL:
Size: 1½” x 1½” x ½ “
Weight: 1 ounce
OPERATING CHARACTERISTICS:
LED on: Indicates 131 kHz signal present
(Tx Activation Field)
MAINTENANCE:
Keep the Tags dry and never submerge them.
Acceptable cleaning methods:
Antibacterial wipes or Hydrogen peroxide (wipe, do not soak)
TESTING:
There are 3 ways that you can test LED Tags:
Enter a monitored zone (LED will light)
With a TAD
With a PTAD
LED Tag
Model Number: LED
Part Number: 660008
STORING
Ideally, to preserve battery life, LED Tags should be turned off with
a TAD, stored away from sources of electrical noise, and stored in a
metal container with lid.
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Local Alarm
The Local alarm, a sounder, is intended to attract attention near the monitored zone.
ELECTRICAL:
Operating Voltage: 12V DC nominal
Alarm Signal Current: 20.8 mA
Cable: needs minimum 22-gauge, 2-conductor
MECHANICAL:
Mounting variations (not provided):
Handy box: 4” x 2-1/8” (approx.)
Switch box: 3” x 2” (approx.) with conduit knockouts.
Masonry box: 3-3/4” (approx.) with ½” and ¾”
concentric knockouts.
Nonmetallic Switch box: 3-3/4” x 2-5/16” (approx.)
OPERATING CHARACTERISTICS:
Sound Pressure Level at 10 feet: 85 db
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Local Alarm
Model Number: LA
Part Number: 700216
UL Listed:
ULSZ.S4011
Due to existing UL listing (above), not
required to be listed under UL 294 (BP9480)
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Magnetic Switch
The Magnetic Switch is used on doors when alarm activation is not desired unless the door is opened.
ELECTRICAL:
Operating Voltage: 150V DC maximum
Contact Rating: 3 watts
Maximum Switch Voltage: 30V AC/DC
Switching Current: 0.5 amps DC
Cable: needs minimum 22-gauge, 2-conductor
MECHANICAL:
Size: 2.50” x 0.80” x 0.60”
Weight: 1.2 ounces
Color: Brown
Surface mounted (Flush available)
OPERATING CHARACTERISITICS:
Contacts: N.O., N.C., and Common
Initial contact resistance: 100 ohms maximum
Operating Time: 1.0 ms maximum
Bounce Time: N.C. leg 1.5 ms maximum
N.O. leg 1.0 ms maximum
Release Time 0.5 ms maximum
Maximum Operating Frequency: 200 Hz
Insulation resistance: 1 x 10 ohms maximum
Electrostatic capacitance: 1.5 pF maximum
Magnetic Switch
Model Number: MCSM
Part Number: 650514
UL Listed:
AMQV.BP2343
Due to existing UL listing (above), not required
to be listed under UL 294 (BP9480)
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Magnetic Switch Placement
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Multi-Tone Local Alarm (MTLA)
A Multi-Tone Local Alarm (MTLA), a wall-mount electronic chime, is intended to attract attention and offers sixteen
different field-selectable chime tones, each with three volume settings and can be used to replace the Local Alarm.
ELECTRICAL:
Operating Voltage: 12 or 24V DC
Current Consumption Range*:
18-31 mA @ 12V DC
31-61 mA @ 24V DC
*Dependant upon tone selection and voltage
Cable: needs minimum 22-gauge, 2-conductor
MECHANICAL:
Size: 5.00” x 5.63” x 2.25” (with mounting plate)
Weight: 0.5 US pounds
Mounting: 2” x 4” or 4” x 4” back box
OPERATING CHARACTERISITICS:
Sound Output: 12V DC - 54dBA
24V DC – 60dBA
Field-selectable tones
Repeating 1 second chime
Repeating ¼ second chime
Temporal 3 chime
Single stroke chime
Continuous / 3kHz
Continuous / 500 kHz
Temporal 3 / 3kHz
Temporal 3 / 500 Hz
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
Multi-Tone Local Alarm
Model Number: MTLA
Part Number: 300150
UL Listed:
ULSZ.54011
Meets UL 464 requirements for private mode
Due to existing UL listing (above), not required
to be listed under UL 294 (BP9480)
DUTY CYCLE:
Rated for continuous use.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Multiplexer
The Multiplexer, used only in IS 3200 and BR 4200 Systems, relays event information sent from the Controller and
Receivers to Graphic Display Panel(s) and to PCs with the Accutech Software. The Multiplexer comes inside a Controller
case; this case can accommodate up to 2 Multiplexer boards (16 Zones).
ELECTRICAL:
Operating Voltage: External 12V DC regulated power
supply, Emergency backup located within 6 feet of the
Multiplexer recommended
Current Consumption: 350 mA per 8-zone board
Output: RS232
MECHANICAL:
Construction: Metal case
Size: 16.00” x 9.60” x 3.25”
Weight: 10 US pounds (2 Multiplexers in enclosure)
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Multiplexer
Model Number: MX18, MX916
Part Number:
770177 (MX18),770277 (M916)
UL Listed 294 (BP9480)
Access Control Accessory
A Multiplexer board
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Push Button Override (PBO)
The Push Button Override (PBO) triggers the Keypad’s Escort or Reset function; this option allows access through a
monitored door from the non-Keypad side of the door.
ELECTRICAL:
Operating Voltage Range: 2 to 13V DC
Stand-by Current Drain: 15mA typical
Current Drain with outputs active: 55 mA typical
Cable: needs minimum 22-gauge, 4-conductor
MECHANICAL:
Size: 4-5/8” x 2-7/8” x 1-3/8”
Weight: 4.3 ounces
Mounting: Flush or Surface mount
*Metal box not recommended
OPERATING CHARACTERISTICS
LEDs:
Green – Reset status
Red - Alarm status
Yellow – Power status
Push Button Override (PBO)
Model Number: PBO
Part Number: 700022
ENVIRONMENAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Passive Infrared Reader (PIR)
The Passive Infrared Reader (PIR) is a device that uses an infrared sensor to monitor elevators, hallways, corridors, and
passageways. Like the Magnetic Switch, the PIR is used in areas where alarm activation is not desired immediately upon Tag
detection. It can also be used in hallways or other areas where a Magnetic Switch would not be feasible.
ELECTRICAL:
Operating Voltage: 12V DC
Current: Stand-by 10 mA
Relay Output: N.O./N.C. 2A/28V AC/DC maximum
Cable: needs minimum 22-gauge 4-conductor stranded,
non-shielded
MECHANICAL:
Dimensions: 2.50” x 4.40” x 1.40”
Weight: 3 ounces
Color: White
OPERATING CHARACTERISTICS
Beam Coverage: Vertical curtain up to 15 x 15 feet.
*The beam is adjustable from its normal 0º setting
(perpendicular to the unit) up to 12º.
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Passive Infrared Reader (PIR)
Model Number: PIR
Part Number: 300302
UL Listed:
ANSR.BP6082
Due to existing UL listing (above), not required
to be listed under UL 294 (BP9480)
PIR Ceiling Mounted Coverage Area Example
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Power Supply
Some installations of the Accutech System peripherals require more power than the Controller can provide. In these cases, a
Power Supply is added to the system to meet the additional power requirements.
ELECTRICAL:
Operating Voltage: 120V AC, 2 amp
Output: 12V DC, 5.1 or 6.8 amps
MECHANICAL:
Construction: Metal Case
Enclosure size: 12.00” x 12.00” x 4.00”
Weight (including enclosure): 12 US pounds
OPERATING CHARACTERISITICS:
Provides 12V DC to multiple system components
including:
Staff Alert Panel (SAP)
Graphic Display Panel (GDP)
Multiplexer
BR 4200 Auxiliary Receivers
Fire Panel Interface (FPI)
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Power Supply
Model Number: PS51 or PS68
Part Number: 500250 (PS51), 500251 (PS68)
UL Listed 294 (BP9480)
Access Control Accessory
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: PTAD
DISCLAIMER: A PTAD reading is in no way meant to be a replacement for taking a Tag to an active zone to test the range
capability of the Tag. When you use a PTAD all you really know is that the Tag has enough power to respond; it is NOT an
indication of the range capability. In order to test the range capability of a Tag, you must take it to an active zone.
The PTAD is used to check the functionality of an Accutech Tag. Accutech Tags operate by internal battery. Over the course
of normal operation, Tags eventually lose battery power and the Tags will need to be replaced. The PTAD is used to
determine if a Tag has sufficient battery power to respond to an activating signal.
NOTE: A PTAD does NOT activate or deactivate Tags.
ELECTRICAL:
A PTAD requires a 9-volt battery to operate.
MECHANICAL:
Size: approximately 4.75” x 2.25” x 1.25”
Weight: 4.7 ounces
OPERATING CHARACTERISTICS:
Transmit Frequency: 128 kHz
Receive Frequency: 418 MHz
The “Active Band Removal or Low Battery on Tag” LED
A PTAD can detect a BR42 Tag in active Band Removal alarm;
the “Active Band Removal or Low Battery on Tag” LED will
illuminate blink slowly. This may help locate lost BR42 Tags
that are alarming.
A PTAD can also detect the low battery bit of yellow Tags.
Simply turn on the PTAD and place a Tag behind the PTAD
within 6 inches. If the Tag’s battery is low (e.g., low enough
that the Tag’s operation is diminished below an acceptable
level) the “Active Band Removal or Low Battery on Tag” LED
will blink rapidly. The Tag should then be replaced.
Model Number: PTAD
Part Number: 680021
UL Listed 294 (BP9480)
Access Control Accessory
The “WAIT” LED
No function in PTAD.
The “Signal Strength” LEDs
The “Signal Strength” LEDs of the PTAD indicate:
The current state of a Tag (on or off)
Tag is Very Near (within approx. 1 foot*)
Tag in Area (within approx. 20 feet*)
*Inexact due to variations of the remaining Tag battery power, remaining
PTAD battery power, and if the Tag is alarming in Band Removal.
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Staff Alert Panel (SAP)
The Staff Alert Panel (SAP) notifies staff when an alarm occurs in a monitored zone through a piezo buzzer and alarmspecific LEDs. Each monitored zone is labeled and marked with an LED that will light to indicate that an Alarm Condition
has occurred for that particular zone. In addition, a “Fire Alarm” LED will light on the display if the fire circuit is activated.
ELECTRICAL:
Operating Voltage: 10 to 13V DC
Current Consumption: 300 mA Max
Cable: needs minimum 22-gauge, 6-conductor from
each Controller
MECHANICAL:
Size: 11” x 5-3/8” x 1-3/8”
Weight: 1 US pound
OPERATING CHARACTERISTICS
LED Alarm indicators:
Flashing Red – ALARM
Steady Red – DOOR AJAR
Flashing Yellow – CHECK SYSTEM
Steady Yellow – LOITER
Fire Alarm LED
Power LED
Built-in Piezo buzzer
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Staff Alert Panel (SAP)
Model Number: SAP
Part Number: 700080
UL Listed 294 (BP9480)
Access Control Accessory
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Speakers
The Speakers provided by Accutech are 8-ohm speakers and are used in conjunction with the Central Alarm. They are
located strategically so they can be heard from any location on the monitored floor.
ELECTRICAL:
Operating Voltage: 12V DC
Cable: needs minimum 22-gauge, 2-conductor
Voice coil impedance: 8 ohms
MECHANICAL:
Dimensions: 6.63” x 4.70” x 2.25”
OPERATING CHARACTERISTICS:
Speakers should be located where they can be heard in
several directions (such as hallway intersections) to
allow staff to hear alarms as they occur.
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Speakers
Model Number: AS3
Part Number: 300002
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Tag Activator/Deactivator (TAD)
DISCLAIMER: A TAD reading is in no way meant to be a replacement for taking a Tag to an active zone to test the range
capability of the Tag. When you use a TAD all you really know is that the Tag has enough power to respond; it is NOT an
indication of the range capability. In order to test the range capability of a Tag, you must take it to an active zone.
The Tag Activator/Deactivator (TAD) is used to check the functionality of an Accutech Tag. Accutech Tags operate by
internal battery. Over the course of normal operation, Tags eventually lose battery power and the Tags will need to be
replaced. The TAD is used to determine if a Tag has sufficient battery power to respond to an activating signal.
NOTE: A TAD CAN activate or deactivate Tags, preserving Tag battery life and preventing nuisance alarms.
ELECTRICAL:
A TAD requires a 9-volt battery to operate.
MECHANICAL:
Size: approximately 4.75” x 2.25” x 1.25”
Weight: 4.7 ounces
OPERATING CHARACTERISTICS:
Transmit Frequency: 128 kHz
Receive Frequency: 418 MHz
The “Active Band Removal or Low Battery on Tag” LED
A TAD can detect a BR42 Tag in active Band Removal alarm;
the “Active Band Removal or Low Battery on Tag” LED will
illuminate blink slowly. This may help locate lost BR42 Tags
that are alarming.
A TAD can also detect the low battery bit of yellow Tags.
Simply turn on the TAD and place a Tag in the Tag receptacle.
If the Tag’s battery is low (e.g., low enough that the Tag’s
operation is diminished below an acceptable level) the “Active
Band Removal or Low Battery on Tag” LED will blink rapidly.
The Tag should then be replaced.
The “WAIT” LED
The “WAIT” LED illuminates briefly during Tag
activation/deactivation.
Model Number: TAD
Part Number: 660021
UL Listed 294 (BP9480)
Access Control Accessory
The “Signal Strength” LEDs
The “Signal Strength” LEDs of the TAD indicate:
The current state of a Tag (on or off)
Tag is Very Near (within approx. 1 foot*)
Tag in Area (within approx. 20 feet*)
*Inexact due to variations of the remaining Tag battery power, remaining
TAD battery power, and if the Tag is alarming in Band Removal.
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Tag Test Station (TTS)
The Tag Test Station (TTS) is used for Tag assignments. In a similar fashion to a Tx wand antenna, the TTS emits a small Tx
Activation Field that activates Tags. Once activated a Tag sends a signal to the Receiver. The Receiver sends this
information to the Multiplexer, which sends it to the computer with the Accutech Software. The Tag Reader Status dialog
box appears on the PC screen where it can be assigned or unassigned.
The TTS is connected to a Controller, which is connected to a Multiplexer.
ELECTRICAL:
Operating Voltage: 30V AC (provided by Controller)
Cable: required minimum 18-gauge, 2-conductor
MECHANICAL:
Size: 5.00” x 7.00” x 1.50”
Weight: 10 ounces
OPERATING CHARACTERISITICS:
Transmits at 132 Khz continuously
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Tag Test Station (TTS)
Part Number:
700010 (I)
700020 (R)
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Timer
A Timer allows the user to engage or disengage certain system functions on a time schedule. A typical application of a Timer
would be at a perimeter door that has high traffic during the day but almost no traffic at night. During the day it may make
sense to allow the free ingress and egress of staff and visitors, but at night, locking the door would mean added security for
staff and residents.
ELECTRICAL:
Operating Voltage: 6 to 12V AC/DC
Relay Inactive: 14 mA
Relay Active: 40 mA
Contacts: N.O. & N.C.
Contact Rating: 1A @ 26V DC
0.5A @ 115V AC
MECHANICAL:
Size: 8.25” x 8.25” x 4.00” (includes enclosure
Weight: 6 US pounds (includes enclosure)
OPERATING CHARACTERISTICS
Internal 10-year Lithium Battery will provide clock
memory backup for 6 months continuously
Relay Hold in Time Adjustment: 1 to 60 seconds
Time format: 24 hour (military) format
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
Timer
Model Number: DNT
Part Number: 700018
DUTY CYCLE:
Rated for continuous use.
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Tx wand antenna
A Tx wand antenna located at a zone generates a Tag-activating radio frequency signal called the “Tx Activation Field.”
When a Tag is activated it sends a signal to the Receiver. The Receiver then sends the signal to the Controller, which
validates the signal before initiating any action such as locking a door, deactivating an elevator, or triggering system alarms.
Due to its ferrite bar, the Tx wand antenna must be mounted a minimum of 3 inches away from any metal. This includes door
frames, conduit, and lathe.
ELECTRICAL:
Operating Voltage: 30V AC (provided by Controller)
Wire Connections: Terminal Block
Cable: required minimum 18-gauge, 2-conductor,
shielded
MECHANICAL:
Construction: Vacuum molded ABS
Size: 13.25” x 2.50” x 2.25"
Weight: 1.5 US pounds
Mounting Surface: Four 3/16” screws
OPERATING CHARACTERISTICS:
Tuning Frequency: Nominal 131 kHz,
129-133 kHz for Stagger
Output Impedance: 300 ohms nominal
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Tx wand antenna (without cover)
Model Number: TW
Part Number: 700068
UL Listed 294 (BP9480)
Access Control Accessory
Tx wand antenna PCB
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Voice Alarm
A Voice Alarm, usually located at a monitored zone, will repeat a recorded message (up to 20 seconds) continuously when an
alarm occurs.
ELECTRICAL:
Operating Voltage: 12V DC
Current Consumption: 300 mA maximum
MECHANICAL:
Size: 6.63” x 4.13” x 1.75”
Weight: 1.5 US pounds
OPERATING CHARACTERISITICS:
Recording Duration: 20 seconds (maximum)
Speaker Output: 8-ohm
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Voice Alarm
Model Number: VA
Part Number: 700019
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
CUT SHEET: Zone Receiver
The Zone Receiver is used to detect signals from an activated Tag. The Zone Receiver is always located near the monitored
zone. When the Controller is mounted at the zone, the Zone Receiver is housed in the Controller enclosure. When the
Controller is mounted away from the zone, the Zone Receiver is mounted externally in a 4”x4”x2” electrical box at the zone.
Zone Receivers monitor both zone events and Band Removal events while BR 4200 Auxiliary Receivers only monitor Band
Removal events.
ELECTRICAL:
Operating Voltage: 12V DC regulated
Cable: needs minimum 22-gauge, 12-conductor
MECHANICAL:
Size: If the Controller is located away from the zone,
the Receiver is mounted in a 4.00” x 4.00” x 2.00”
electrical box at the zone.
*Allow 7” depth for clearance of the BNC Rubber
Duck antenna
Zone Receiver (Internal)
Model Number: ESRI
Part Number: 660076
OPERATING CHARACTERISTICS:
Transmit Frequency: 418 MHz
Receive Frequency: 418 MHz
Frequency range: 40 feet radius (360º)
UL Listed 294 (BP9480)
Access Control Accessory
Jumpers settings:
JP1 (SS)
Off
JP2 (Rx Test)
Off
JP3 (Tag D)
Off
JP4 (BR)
On
JP5 (Reset)
Off
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Zone Receiver (External)
Model Number: ESRR
Part Number: 670076
800-356-2671 | Accutech | www.accutech-ics.com
Accutech reserves the right to substitute comparable components without notice.
Installation Manual
Glossary G-1
Glossary
Accutech Software
Displays events in real-time on a facility’s custom floor plan.
BR 4200 System Tag
A small wristwatch-sized device that is worn by an infant.
In addition to the functionality of an IS 3200 System Tag, the
BR 4200 System Tag will alarm if the band is removed or
tampered with in any way.
Central Alarm
An alarm triggered by the Accutech Security System; can
create up to 8 distinct tones and drive up to 5 speakers.
Controller
Coordinates and controls all of the devices and functions of the
Accutech IS 3200/BR 4200 System.
Delayed Egress Circuitry
Allows free egress after 15 pounds of constant force for 3
seconds due; due to fire and life safety codes.
Door Ajar alarm
An alarm condition; occurs when a door is open longer than
the preset time period allows.
Egress
The act of entering or exiting, especially from an enclosed
place.
Egress alarm
An alarm condition occurs while a Tag is in the Tx activation
field and door is opened.
Elevator Deactivation
Circuitry that prevents a resident wearing a Tag from calling or
using an Elevator to leave a floor.
ES 2200 System Tag
ES 2200 System Tags are small wristwatch-sized devices worn
by a resident or attached to an asset. When a resident or patient
enters a Tx Activation Field, the Tag sends a signal to the zone
Controller, via the Receiver. The zone Controller processes this
information for appropriate control action or response (e.g.
sounding alarms, locking doors, etc.).
Escort Function
A function of the Keypad; used to escort residents through a
monitored zone and to reset zone equipment once an alarm has
occurred.
G-2 Glossary
Fire Panel Interface
(FPI)
Installation Manual
The unit used to connect multiple IS 3200/BR 4200 Systems to
the facility’s fire panel.
During this time, the Magnetic locks are deactivated, allowing
a resident wearing a Tag to leave the facility.
The IS 3200/BR 4200 System will still alarm provided there is
still power to the system.
Graphic Display Panel
(GDP)
Provides staff with a visual representation of the floor being
monitored. GDPs are custom-made to a facility’s floor plan
and notify staff when an alarm condition occurs in a monitored
zone through a piezo buzzer and alarm-specific LEDs
Ingress
The act of coming and going, especially from an enclosed
place.
IS 3200 System Tag
A small wristwatch-sized device that is worn by a resident or
attached to an asset.
IS 3200 System Tags are assigned to a specific resident or
asset (via the Tag Test Station and Accutech Software). Once
assigned, the computer associates a name, room number and
any other pertinent information about the resident/asset with
that Tag.
Keypad
A 12-button device used to reset the system when the alarm is
activated and to provide visual indicators for Tag detection,
alarms and escorts.
Local Alarm
A single tone alarm that is usually mounted near the monitored
zone.
Loiter Alarm
An alarm condition, occurs when a Tag remains in the Tx
activation field for longer than a preset period of time.
Magnetic Lock
As a general term, it describes the device used to lock a door
when a Tag is detected.
Specifically, it describes a Lock that remains engaged as long
as a Tag is within the Tx activation field and for an adjustable
amount of time afterwards.
Magnetic Switch
Used on a door when alarm activation is not desired unless the
door is opened when a monitored resident is near that door.
Masking
In PIR applications, limiting the beam by placing stripes of
tape over the lens.
Installation Manual
Glossary G-3
Master Code
User Number 1 code for the Keypad, used for Keypad
programming purposes only.
Monitored Zone
Any door, hallway, elevator, or other passageway that has a
Transmit (Tx) antenna or Zone Receiver associated to it.
Multiplexer
Relays event information from the Controller to Graphic
Display Panels (GDPs) and the Accutech Software.
Passive Infrared Reader
(PIR)
A device that uses an infrared light to detect motion. Used in
place of a Magnetic Switch in hallway applications.
Push Button Override
(PBO)
A switch (push button) that temporarily overrides a Magnetic
Lock, allowing someone on the outside of the locked door to
enter.
Receiver
A device that detects the signal of an activated Tag, usually
mounted in the Controller above the drop ceiling or on the wall
next to the door being monitored. For centrally located
systems, the Receiver is mounted separately at the door. A
short rubber antenna protrudes from the cover.
Remote BR Receiver
Receiver designed to detect BR 4200 events.
Staff Alert Panel
(SAP)
A display panel used to indicate to staff where an Alarm, Door
Ajar, Loiter, or Supervise warning condition has occurred;
employs bi-color LEDs, an adjustable Piezo Buzzer and digital
logic to control its outputs.
Supervisor
A built-in self-diagnostic circuit that continuously monitors the
Tx Activation Field and periodically simulates a Tag in the
zone.
Tag Activator/Deactivator
(TAD)
Turns IS 3200/BR 4200 system Tags on and off.
Tag
A wristwatch-sized device that, upon activation in a monitored
zone, transmits back the Controller through the Receiver.
Tag Test Station
(TTS)
Used with the Accutech Software for Tag assignments.
Tx wand antenna
Generates a tag-activating radio frequency signal near a
monitored zone. This signal is referred to as the “Tx activation
field.”
G-4 Glossary
Tx activation field
Installation Manual
A radio frequency field created by a Transmit (Tx) antenna to
detect Tags.
Installation Manual
Index I-1
Installation Manual
Index
Automatic Door Deactivation
definition
wiring
16-1
16-1,16-2
Alarm
Definitions
band removal
door Ajar
egress
loiter
supervisor
1-4
1-3
1-3
1-4
1-4
Alarm Output Devices
central alarm
definitions
GDP
local alarm
output capability
output connector
SAP
speakers
13-3
13-1
13-8
13-2
13-1
13-2
13-6
13-4
Band Removal Lockdown
operation
wiring
21-1
21-1
Block diagrams
C-1
BR 4200
System
operation
(How Accutech Systems Work)
overview
1-2
1-2
cleaning
definition
overview
storage
testing
6-3
1-6
6-3
6-3
6-3
Tag
Cable
Cable Door Kit
SAP & GDP
Fire Panel Interface
Composite Cable
Wire Gauge Table
Central Alarm
connecting
definition
mounting
specifications
2-1
2-1
2-1
2-2
2-4
13-4
1-9
13-3
13-3
Controller
definition
fuses
hard wiring
jumpers
LEDs
mounting
potentiometers
power loss supervisor alarm
remote mounting
specifications
switches
system supervisor
tamper switch
Discontinued Components
ES 2100 Receiver
Composite Cable (Part# 200355)
Door Ajar
reset
setup
Elevator Deactivation
definition
mounting
positioning
specifications
summary for the elevator company
what to expect
wire and cable
wiring
working with the elevator company
1-7
B-12
3-4
B-1
B-5
3-2
B-10
3-7
3-4
3-1
B-12
3-6
3-8
A-1
A-1
A-5
9-4, 22-1
9-3, 22-1
1-11
14-2
14-2
14-1
14-4
14-1
14-2
14-3
14-1
ES 2200
System
operation
(How Accutech Systems Work)
overview
1-2
1-1
cleaning
definition
overview
storage
testing
6-3
1-5
6-2
6-3
6-2
Tag
FPI
before connecting
connecting
definition
overview
positioning
specifications
12-2
12-3
1-11
12-1
12-2
12-2
I-2 Index
GDP
connecting
definition
mounting
overview
positioning
specifications
Installation Manual
13-9
1-10
13-8
13-8
13-8
13-8
IS 3200
System
operation
(How Accutech Systems Work)
overview
1-2
1-2
definition
testing
cleaning
storage
overview
1-5
6-2
6-3
6-3
6-2
Jumpers
Controller
Lock
Multiplexer
Receiver
B-1
11-2
17-3
5-4
Tag
Keypad
connecting
definition
mounting, flush
mounting, surface
positioning
programming
adjusting the escort time
deleting user codes
programming user codes
resetting the master code
overview
specifications
Local Alarm
connecting
definition
mounting
specifications
connecting
definition
mounting
nuisance delay
operation
specifications
3101 Series
adjusting the Sensor pin
connecting
definition
jumper
mounting
nuisance delay
specifications
operation
perimeter door applications
Magnetic Switch
connecting
definition
double door applications
mounting
positioning
specifications
Multiplexer
board setting
definition
jumpers
mounting
positioning
specifications
wiring
to
to
to
to
to
GDP
other Multiplexers
PC
Power Supply
Receiver
22-2
22-1
9-3
1-8
9-3
9-2
9-1
9-1
17-11
1-9
17-3
17-1
17-1
17-1
17-6
17-9
17-7
17-3
17-3
PBO
7-4
1-7
7-3
7-2
7-2
7-8
7-7
7-6
7-8
7-1
7-1
13-2
1-9
13-2
13-2
Lock
3000 Series
Loiter
reset
setup
11-7
1-11
11-7
11-7
11-1
11-6
11-4
11-2
1-11
11-2
11-3
11-5
11-2
11-1
11-1, 15-4
connecting
to Controller
to Keypad
definition
mounting
positioning
specifications
8-3
8-2
1-8
8-2
8-1
8-1
Perimeter Functions
door ajar (timer override)
lock
system
timer
15-1
15-1
15-4
15-1
PIR
adjusting
connecting
definition
masking
mounting
positioning
specifications
10-3
10-3
1-8
10-5
10-2
10-2
10-1
Power Loss Supervise
3-7
Power Supply
connecting
to FPI
to GDP
to Multiplexer
to Receiver
definition
mounting
positioning
specifications
Product Cut Sheets
18-1
18-1
18-1
18-1
1-10
18-1
18-1
18-1
E-1
Installation Manual
Receiver
adjusting
BR 4200 Auxiliary Receivers
connecting
definition
internal vs. external
jumpers
mounting
positioning
specifications
Index I-3
5-6
5-3
5-4
1-7
5-2
5-4
5-2
5-2
5-1
SAP
connecting
definition
mounting
specifications
13-7
1-10
13-7
13-6
Software
definition
example system configuration
installing
minimum system requirements
recommended system components
uninstalling
1-6
19-2
19-1
19-1
19-1
19-2
Speakers
connecting
definition
mounting
positioning
specifications
volume control
13-5
1-9
13-5
13-5
13-4
13-6
Supervisor
System supervise
power loss
Threshold
3-6, 22-2
3-7
3-7, B-12
Stagger Tuning
4-6
TAD
activating/deactivating Tags
new technology Tags and
the battery flag
6-4
6-1
Tag Test Station (TTS)
connecting
definition
mounting
positioning
Tag
activating/deactivating Tags
BR 4200
ES 2200
IS 3200
new technology Tags
and the battery flag
storage
20-1
1-6
20-1
20-1
6-4
6-3
6-2
6-2
6-1
6-3
Timer
connecting
definition
mounting
positioning
programming
specifications
15-2
1-11
15-2
15-2
15-3
15-1
Troubleshooting
D-1
Tuning
Tx wand antenna
Stagger Tuning
4-7
4-6
Tx wand antenna
adjusting the Tx Activation Field
connecting
definition
double door applications
mounting
tuning
single door applications
spacing
specifications
stagger tuning
why re-tune
UL Addendum
4-13
4-4
1-7
4-2
4-3
4-7
4-2
4-2
4-1
4-6
4-7
iii
User-Defined Settings
Door ajar
Door ajar reset
Loiter
Loiter reset
System Supervise
Power Loss Supervise
9-3, 22-1
9-4, 22-1
22-1
22-2
3-6, 22-2
3-7, 22-2
Zone layout examples
C-1


Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 93
Has XFA                         : No
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:325f3a8e-fec2-434f-8e53-16735a5a47d1
Modify Date                     : 2008:08:05 20:41:52-05:00
Create Date                     : 2008:08:05 20:41:40-05:00
Metadata Date                   : 2008:08:05 20:41:52-05:00
Document ID                     : uuid:1a5b74ef-a2c9-43ee-a897-521947672fe9
Format                          : application/pdf
Title                           : Install Manual (v2.36) - ES/IS/BR - July 2007
Creator                         : Acrobat PDFMaker 5.0 for Word
Author                          : DerekU
Producer                        : Acrobat Distiller 5.0.5 (Windows)
EXIF Metadata provided by EXIF.tools
FCC ID Filing: JM7-IGWT-662008

Navigation menu