AC Intermittent duty solenoids are designed to be energized 30 seconds
at a time. Energizing for longer periods will damage the solenoid.
Warning !
The number of wires will vary depending on features of the strike.
The voltage and amperage ratings are marked on all strike labels. The solenoid
wires are not polarized.
Wiring
Fail-Secure Operation - Unlocks when energized. If power fails the strike
remains in a locked condition.
Fail-Safe Operation - Locks when energized. Used in applications requiring
automatic unlocking in case of power failure.
Available Voltages: 12V AC Intermittent duty, 12V AC/DC Continuous duty,
16V AC Intermittent duty, 16V AC/DC Continuous duty,
24V AC Intermittent duty, 24V AC/DC Continuous duty.
Notes:
Monitored strikes contain two, internally mounted, switches: one is activated by
the latch bolt's penetration of the strike and the other indicates that the
strike jaw is either locked or unlocked by the solenoid.
All unused leads from monitor switches should be insulated.
Common contact -Black
Normally open contact (NO) -White
Normally closed contact (NC) -Red
Maximum switching current -7 Amps @ 250 VAC
Monitoring (Optional)
Warning !
Intermittent duty solenoids should not be converted to fail-safe configuration.
Fail-safe units use only continuous duty solenoids.
.744
.431
19.15
6.43
24 VAC INT.
Solenoid Data
.170
.222
.332
1.030
1.420
.170
.222
.332
.636
.813
4.09
3.05
3.81
17.30
17.74
4.09
3.05
3.81
6.60
5.82
141.6
61.8
34.6
16.3
8.8
CURRENT (AMPS)
PEAK INSTANTANEOUS
HOLD CURRENT (AMPS)
CONTINUOUS OR
POWER (WATTS)
PEAK INSTANTANEOUS
HOLD POWER (WATTS)
CONTINUOUS OR
16 VAC INT.
BLUE STRIPE ON BLACK
12 VDC CONT.
RED STRIPE ON BLACK
16 VDC CONT.
GREEN STRIPE ON BLACK
12 VAC INT.
24 VDC CONT.
WHITE STRIPE ON BLACK
YELLOW STRIPE ON BLACK
WIRE COLOR
(OHMS ±5%)
COIL RESISTANCE
DESCRIPTION
not shown
solenoid retaining plate
not shown
solenoid retaining plate
FAIL-SECURE
LUBRICATE STRIKE!
DO NOT
FIELD REVERSIBLE (FAIL-SECURE)
(ARMS & SPRINGS REMOVED)
"FAIL-SECURE" CONFIGURATION
FIG. 2
FIG. 1
"FAIL-SECURE" CONFIGURATION
shuttle
return
spring
solenoid
plunger
blocking arm
return spring
blocking arm
latch arm
not shown
solenoid retaining plate
not shown
solenoid retaining plate
FAIL-SAFE
LUBRICATE STRIKE!
DO NOT
FIELD REVERSIBLE (FAIL-SAFE)
(ARMS & SPRINGS REMOVED)
"FAIL-SAFE" CONFIGURATION
FIG. 1
FIG. 2
"FAIL-SAFE" CONFIGURATION
blocking arm
blocking arm
return spring
latch arm
solenoid
shuttle
return
spring
plunger
AC Continuous duty strikes are supplied with a A/R # 4603 rectifier attached
to the solenoid leads. These are silent operation strikes - without the
"buzzing" sound. They use a DC solenoid with an externally attached,
full-wave bridge rectifier.
TYPICAL ELECTRIC STRIKE WIRING DIAGRAM
INTERMITTENT DUTY FAIL-SECURE 24 VAC
Control Switch (N.O.)
(ex. Pushbutton, keypad,Card Reader)
Control Switch (N.O.)
(ex. Pushbutton, keypad, Card Reader)
DRY CONTACTS!
DRY CONTACTS!
TYPICAL ELECTRIC STRIKE WIRING DIAGRAM
INTERMITTENT/CONTINUOUS DUTY 24 VDC
power leads
solenoid
leads
solenoid status
leads
bolt status
WIRE CODING (MONITORED VERSION)
Black : Common
White : NO
Red : NC
COLOR CODE:
Page of
1 1
Rev.
Appvd: MP
Date:
ECN: 11955D
Date: 07/20/12
H
7100 SERIES (DATA SHEET WIRE CODING FIELD REVERSIBLE)