Ademco 8DL5800COXTLF Wireless Carbon Monoxide Transmitter User Manual k14631 ii

Honeywell International Inc. Wireless Carbon Monoxide Transmitter k14631 ii

User Manual

5800CO Carbon Monoxide Detector
with Built-in Wireless Transmitter
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The 5800CO is a 3V battery powered wireless Carbon Monoxide
(CO) detector intended for use with wireless alarm systems that
support 5800 series devices. Refer to control/communicator
installation instructions for compatibility.
The detector consists of an electrochemical carbon monoxide sensor
assembly coupled to a wireless transmitter. The transmitter can
send alarm, trouble, tamper, and battery condition messages to the
system’s receiver. Refer to the wireless system’s instructions for the
maximum number of transmitters that can be supported.
NOTICE: This manual should be left with the owner/user of this
equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements.
WARNING: This product is intended for use in ordinary indoor
locations of dwelling units, including homes, residential buildings,
hotels, schools, dormitories, and day care centers. It is not intended
for use in industrial factories or commercial parking garages.
Detector Description
• Listed to UL standard 2075 (pending)
• Supervised
• Local sounder
• Dual LED’s
• Test/Hush button
• Surface mount to wall or ceiling
• Optional drywall anchors included
The 5800CO contains a piezoelectric horn which generates the
ANSI S3.41 temporal 4 pattern in an alarm condition (see note
below Table 1 for temporal 4 pattern). In alarm, a message is also
sent to the wireless control panel and the detector’s zone number is
displayed at the console. The alarm message is transmitted every 4
seconds until the carbon monoxide condition has cleared and the
detector has reset. During an alarm condition, pressing the
detector’s test button will silence the piezoelectric horn for 5
minutes. Once the detector has reset, a RESTORE message is
transmitted to the control panel and the transmitter’s zone number
can be cleared from the panel. The mounting base installation is
simplified by the incorporation of features compatible with drywall
fasteners or other methods that provide a method for securing the
detector in place.
During initial power-up, the red and green LEDs will blink together
once every 10 seconds up to four times. It takess about 30 seconds
for the detector’s CO sensor to stabilize (see Table 1).
After power-up has completed and the detector is functioning
normally within its listed sensitivity range, the green LED blinks
once every 10 seconds. The LED indication must not be used in
place of the tests specified under TESTING THE DETECTOR. In
a trouble condition, the red LED will blink once every 10 seconds
(refer to Table 1). If the detector senses a low battery condition, the
red LED blinks once every 45 seconds.
Two LEDs and a sounder on the detector provide local visual and
audible indication of the detector’s status as listed in Table 1.
Table 1: Detector LED Modes
Green LED Red LED Sounder
Normal (standby) Blinks every
10 seconds
Off Off
Alarm/Test Off Blinks every
1 second
Temporal 4
Pattern
Low Battery Off Blinks every
45 seconds
Chirp every 45
sec after LED
blinks for 7 days
Communication
Fail
Off Blinks every
5 seconds
Off
Trouble Off Blinks every
5 seconds
One chirp every
45 seconds
Detector End-of-
Life
Off Blinks every
10 seconds
Off
Power Up Blinks every
10 secs††
(w/red LED)
Blinks every
10 secs ††
(w/green LED)
Off
† Temp 4 pattern is repeated pattern of four short beeps followed by
a five second pause. When the detector has been in alarm for 30
minutes, the alarm signal will be given once every minute. If
ambient conditions return to normal, the detector will self-restore
out of alarm and into Normal (standby) mode.
†† Red and green LEDs blink a total of four times, once every 10
seconds.
Hush feature: If required, the audible alarm can be silenced for 5
minutes by pushing the button marked “Test/Hush”. The red alarm
light will continue to flash in temp-4 pattern. If carbon monoxide is
still present after the 5 minute hush period, the audible alarm will
sound. The hush feature will not operate at levels above 350 ppm
(parts per million) carbon monoxide.
Trouble feature: When the sensor supervision is in a trouble
condition, the detector will send a trouble signal to the panel.
Trouble conditions include an open circuit, sensor removal
(tamper), and sensor end of life.
End of Life Timer feature: When the detector has reached the
end of its life, the trouble contact will open. This indicates that the
CO sensor inside the detector has passed the end of its life and
must be replaced. This detector’s lifespan is approximately six
years from the date of manufacture. Refer to Detector Replacement
section
Low Battery Detection: The 5800CO is powered by a single 3-
volt CR123A or DL123A Lithium battery (included). The detector
checks for a low battery at least every 65 minutes. If a low battery
is detected, the transmitter sends a low battery message to the
control panel, which beeps and displays the detector’s zone number.
In addition, the red LED of the detector will blink every 45 seconds
and the test button will be disabled. This condition will exist for a
minimum of 7 days, and then the detector’s horn will “chirp” about
every 45 seconds. Pressing the test button during this time will
silence the chirps for 12 hours. The battery should be replaced
BEFORE the chirps begin. Be sure to replace the battery with a
fresh one.
PLEASE GO TO THE
BOTTOM OF PAGE 4
FOR THE FCC / IC
STATMENTS
– 2 –
BATTERY INSTALLATION AND REPLACEMENT
To replace the battery:
1. Remove the detector from its mounting base by twisting the
detector counterclockwise. Remove the battery, and dispose
properly.
2. To ensure proper power-down sequence, wait a minimum of 20
seconds before installing new battery.
3. Install a new 3-volt CR123A Lithium battery in the battery
compartment. Follow the polarity diagram inside the
compartment.
4. Reinstall the detector onto the mounting base by turning the
detector clockwise.
5. Test the detector as described in the TESTING SIGNAL
STRENGTH section of this manual. The green LED should
blink about once every 10 seconds to indicate normal operation.
If the battery is not installed correctly, the detector will not
operate and the battery may be damaged. If the detector does
not appear to be sending a signal during any of the tests, check
for correct battery installation and for a fully charged battery.
D
O
N
O
T
P
A
I
N
T
TEST BUTTON
GREEN LED
RED LED
5800CO-001-V0
Figure 1. 5800CO Wireless Carbon Monoxide Detector
PROGRAMMING
The detector must be enrolled in the control panel before it can
operate in the system. The detector’s protection zone must be
enrolled as Loop 1 and “Input Type” 3 (supervised RF).
A tamper condition is transmitted as Loop 4, but does not require
programming.
1. Enter the control’s Zone Programming mode.
2. Enter the zone number to be programmed.
3. Enter the applicable zone type when prompted. For
Honeywell residential controls, program loop 1 as carbon
monoxide zone type 14).
4. When prompted, enter Input Type 03 (3 on some controls)
– Supervised RF Transmitter.
5. When prompted for the serial number, transmit from the
detector by activating the tamper switch. To do this, hold
the base of the detector in one hand, and rotate the
detector counter-clockwise on the base until it snaps open.
Then return to clockwise position until the detector snaps
into place.
6. When the serial number is displayed, transmit from the
detector a second time by activating the tamper switch
again as described in Step 5. The current loop number (4)
will begin to flash.
7. Manually change the loop number to the desired loop
number for the zone (according to the application).
WARNING: The carbon monoxide protection zone enrolled
must always be Loop 1. Otherwise, annunciations will not be
reported by the control.
8. Exit Programming mode when programming is complete,
and test the detector. Refer to the Testing Section.
See the control unit’s installation instructions for further
details.
MOUNTING THE DETECTOR
First, determine the best location for the detector, one that provides
proper gas detection (see Figure 4 for suggested detection locations)
and a strong wireless transmission path.
Proper Gas Detection Location
In a wall location, the detector should be at least as high as a light
switch, and at least six inches from the ceiling. In a ceiling location,
the detector should be at least 12 inches from any wall.
Where to install, ideally:
Within 10 feet of all sleeping areas
Inside the bedroom if it contains a fuel burning appliance
• On every floor of the building
Ideally, install in any room that contains a fuel burning
appliance
If the appliance in the room is not normally used, such as the
boiler room, the detector should be placed just outside the room
so the alarm can be heard more easily
Where NOT to install, ideally:
Detectors operate best if not installed within 10 feet of any
cooking appliance
Directly above a sink, cooker, stove or oven
Next to a door or window that would be affected by drafts i.e.
extractor fan or air vent
• Outside
Do not install in any environment that does not comply with the
detector’s environmental specifications
In or below a cupboard
Where air flow would be obstructed by curtains or furniture
Where dirt or dust could collect and block the sensor
Where it could be knocked, damaged, or inadvertently removed
Good Transmission Path
A GOOD TRANSMISSION PATH MUST BE ESTABLISHED
FROM THE PROPOSED MOUNTING LOCATION BEFORE
PERMANENTLY INSTALLING THE DETECTOR. To check,
perform the test described in the TESTING SIGNAL STRENGTH
section. Prior to mounting the detector to the mounting base, you
must “enroll” the detector’s serial number into the system (see the
PROGRAMMING section).
Mounting Procedure
To mount the detector, perform the following steps:
1. Once a suitable location has been determined, install the
mounting base on the ceiling or on the wall (if local ordinances
permit). Use the two screws and anchors provided.
2. Turn the detector in a clockwise direction in the mounting base
until it clicks into place.
3. Test the detector immediately after completing the installation
(as described in the TESTING THE DETECTOR section of
this manual) and refer to the control system’s instructions for
additional information concerning the use of wireless devices.
RED
LED
FLANGE
LOCK
SNIP OFF FOR
TAMPER LOCK
TAMPER RELEASE TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER RESIST FEATURE)
TAMPER
RELEASE TAB
DIRECT
MOUNT
HOLES
5800CO-002-V0
Figure 2. Detector Mounting Base
– 3 –
5800CO-003-V0
Figure 3. Mount Detector Across Ceiling Panel Support
DO NOT attach the detector to removable ceiling panels. Attach
the detector across panel support as shown in Figure 3.
CAUTION
Airborne dust particles can enter the detector. Honeywell
recommends the removal of detectors before beginning construction
or any other dust producing activity. Carbon monoxide detectors
are not to be used with detector guards unless the combination has
been evaluated and found suitable for that purpose.
LIVING
ROOM
BEDROOM BEDROOM
BEDROOM
KITCHEN
TO
BR
CLOSED
DOOR
BASEMENT
GARAGE
CARBON MONOXIDE ALARM
LOCATION FOR MULTI-LEVEL RESIDENCE
5800CO-005-V0
Figure4. Detector Location Diagram
Tamper Protection
This detector has a built-in tamper switch that will cause a CHECK
signal to be displayed at the console of the alarm system if it is
removed from its mounting base. The 5800CO detector includes a
tamper-resistant feature that prevents removal from the mounting
base without the use of a tool. To engage the tamper-resistant
feature, cut the small plastic tab located on the mounting base
(Figure 2), and then install the detector. To remove the detector
from the base once it has been made tamper resistant, use a small
screwdriver to depress the square tamper release tab, located on
the skirt of the mounting base, and turn the detector
counterclockwise.
TESTING THE DETECTOR
NOTE: Before testing, notify the central station that the detector
system is undergoing maintenance, in order to prevent unwanted
alarms. Testing the detector will activate an alarm and send a
signal to the panel.
The manufacturer cannot recommend a specific agent with which
to test the detector.
Detectors must be tested after installation and following periodic
maintenance.
Testing the Sensor
1. A recessed test button is located on the detector housing (see
Figure 5).
2. Push and hold the recessed test button for a minimum of 5
seconds. Use a small screwdriver or Allen key with maximum
diameter of 0.18 inch (the alarm panel will trigger and then
the detector will go into alarm. If the tool is removed from the
recessed button the sounder will shut off.)
If the detector is within the listed sensitivity limits, the LED
on the detector should blink once per second and the horn
should sound within 3 seconds.
5800CO-004-V0
RED
LED
FLANGE
LOCK
SNIP OFF FOR
TAMPER LOCK
RECESSED
TEST
BUTTON
PUSH RECESSED
BUTTON WITH A
0.18" MAX.
DIAMETER TOOL
LEDs
Figure 5. Recessed Test Button Opening
Testing Signal Strength
NOTE: Remove battery tab before installation.
This test should be performed before installation to determine a
strong communication path with the control panel and after
installation is complete. Also, the owner/user should test the unit at
least weekly.
1. Activate the wireless system’s GO/NO GO TEST mode from
the keypad.
2. Depress and hold the detector’s TEST button. If the detector
has not previously detected a low battery condition and it is
within proper sensitivity limits, the detector should
immediately transmit an alarm signal to the control panel.
The built-in horn will start to sound about 2.5 seconds after
depressing the button.
3. The wireless system’s keypad should emit at least three
audible sounds when the alarm transmission is received and
will display the transmitting detector’s zone number.
4. When the console has received the test signal, release the
TEST button. The horn will immediately stop and a few
seconds later the detector’s zone number will clear from the
console display.
5. If the console does not respond as noted, check the polarity of
the battery and be sure it is fresh. If this is an initial
installation, try moving the detector to another location that
provides proper reception. Also be sure that the detector has
been “enrolled” by the control panel (see PROGRAMMING).
Then, repeat the test.
6. Turn off the system’s TEST mode from the keypad (security
code + OFF).
Testing Programmed Loops
This test should be performed before installation to ensure that the
detector has been programmed and is operational in the system.
1. Activate the system’s TRANSMITTER ID SNIFFER mode
from the keypad (see the control panel’s instructions). All
programmed wireless zones will be displayed, one by one, on
the system keypad. Make sure the detector zone is displayed in
the sequence. (If not, recheck that the detector zone has been
properly programmed.)
2. With the detector mounted to the bracket, press the detector’s
TEST button. The zone associated with the detector should
disappear from the keypad on the next display cycle. This
means that the system has received a transmission from the
detector zone you programmed.
3. When testing is complete, enter the Installer code + the OFF
key to exit TEST mode.
When all system testing has been completed, notify the central
station that the system is back on line.
CAUTION: Carbon Monoxide Gas and its Detection
This carbon monoxide detector is designed for indoor use only. Do
not expose to rain or moisture. Do not knock or drop the detector.
Do not open or tamper with the detector as this could cause
malfunction. The detector will not protect against the risk of carbon
monoxide poisoning if not properly installed. The detector will only
indicate the presence of carbon monoxide gas at the sensor.
Carbon monoxide gas may be present in other areas.
This carbon monoxide detector is NOT:
• Designed to detect smoke, fire or any gas other than carbon
monoxide
• To be seen as a substitute for the proper servicing of fuel-burning
appliances or the sweeping of chimneys.
• To be used on an intermittent basis, or as a portable alarm for the
spillage of combustion products from fuel-burning appliances or
chimneys.
Carbon monoxide gas is a highly poisonous gas which is released
when fuels are burnt. It is invisible, has no smell and is therefore
impossible to detect with the human senses. Under normal
conditions in a room where fuel burning appliances are well
maintained and correctly ventilated, the amount of carbon
monoxide released into the room by appliances should not be
dangerous.
Symptoms of carbon monoxide poisoning: Carbon monoxide
bonds to the hemoglobin in the blood and reduces the amount of
oxygen being circulated in the body. The following symptoms are
related to carbon monoxide poisoning and should be discussed with
all members of the household:
Mild exposure: Slight headache, nausea, vomiting, fatigue (often
described as “flu-like” symptoms).
Medium exposure: Sever throbbing headache, drowsiness,
confusion, fast heart rate.
Extreme exposure: Unconsciousness, convulsions, cardio
respiratory failure, death.
Many causes of reported carbon monoxide poisoning indicate that
while victims are aware that they are not well, they become so
disoriented that they are unable to save themselves by either
exiting the building or calling for assistance.
Also young children and pets may be the first to be affected.
What to do if the carbon monoxide detector goes into alarm:
Immediately move to a spot where fresh air is available, preferably
outdoors. Find a phone in an area where the air is safe and call
your security service provider. Tell your provider the detector alarm
status, and that you require professional assistance in ridding your
home of the carbon monoxide.
IMPORTANT: This detector should be tested and maintained
regularly following National Fire Protection Association (NFPA)
720 requirements. (Generally this detector should be tested at least
once per month.)
MAINTENANCE
Occasionally clean the outside casing with a cloth. Ensure that the
holes on the front of the alarm are not blocked with dirt and dust.
Do not paint, and do not use cleaning agents, bleach, or
polish on the detector.
DETECTOR REPLACEMENT
This detector is manufactured with a long-life carbon monoxide
sensor. Over time the sensor will lose sensitivity, and will need to
be replaced with a new carbon monoxide detector. This detector’s
lifespan is approximately six years from the date of manufacture.
Periodically check the detector’s replacement date. Remove the
detector cover and refer to the ID sticker placed on the inside of the
detector. The sticker will indicate the date that the detector should
be replaced.
The detector will also cause a trouble condition once it has reached
the end of its useful life. If this occurs, it is time to replace the
detector.
NOTE: Before replacing the detector, notify the proper authorities
that maintenance is being performed and the system will be
temporarily out of service. Disable the zone or system undergoing
maintenance to prevent any unwanted alarms. Dispose of detector
in accordance with any local regulations.
CAUTION
It should be noted the installation, operation, testing and
maintenance of the 5800CO is different than conventional 4-wire
smoke detectors. Per NFPA 720 section 5.3.7.2 the detector shall
not be connected to a zone that signals a fire condition (i.e. smoke
detector zones). Therefore, the 5800CO detector must be
programmed as a non-fire zone. See the control’s Installation
Instructions for the appropriate carbon monoxide zone type to be
programmed.
SPECIFICATIONS
Power Source: One 3-volt CR123A Lithium Battery
(included). (Replace with Duracell
DL123A, Sanyo CR123A, Panasonic
CR123A or ADEMCO 466.)
Audible Signal (temp 4 tone): 85 dBA min. in alarm (at 10ft)
Height: 2.3 inches (58 mm)
Diameter: 5.3 inches (135 mm) with mounting
base
Weight: 7 oz. (241 g) without battery
Operating Ambient
Temperature Range: 32° to 100°F (0° to 50°C)
Operating Humidity Range: 15% to 95% Relative Humidity, non-
condensing
Agency Listings:
Patent numbers: 5,155,469; 5,004,999
Please refer to insert for the Limitations of Carbon Monoxide Detectors.
FOR WARRANTY INFORMATION AND FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE
INSTALLATION INSTRUCTIONS FOR THE RECEIVER/CONTROL WITH WHICH THIS DEVICE IS USED.
This device complies with Part 15 of the FCC rules and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired
operation.
Unauthorized changes or modifications could void the users authority to operate the equipment.
ÊK14631+Š
K14631 2/07 Rev. A
165 Eileen Way, Syosset, New York 11791
Copyright © 2007 Honeywell International Inc.
www.honeywell.com/security

Navigation menu