Ademco 8DLCOMSR COMBO 5800 User Manual

Honeywell International Inc. COMBO 5800 Installation Instructions

a href="https://usermanual.wiki/Ademco" itemprop="url"> Ademco >

Contents

Installation Instructions

 This is intended for use with Honeywell control panels that support 5800 series devices. Install •  Remove Battery Pull tabs to activate device and begin enrollment. •  The detector will run through its Power-Up mode: Green LED Blinks every 2 secs  / Sounder is Silent.  The detector will prompt for language selection. Important Note: CO and SMOKE each have unique serial numbers and must to be enrolled separately. CO TestLEDSmoke Test5800combo-ii 001(    )  (  )  5800COMBO               5800combo-ii 002Pull Battery TabOpenTop                    Open Enroll                                                                        1.  Press the Smoke (•) test button to select English or the CO (••) test button to select Spanish language settings.   2.  On the Honeywell compatible control panel, log in Programming Mode > Zones > New > Serial Number.  3.  Enter the zone number to be programmed for Smoke. 4.  Enter zone type when prompted. Program:  • Loop 1 (Heat/Smoke) as a Fire zone (type 9 or 16),  • Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type 19),  • Loop 3 (Freeze Warning Sensor) as a 24-Hr. Aux. zone (type 8).  NOTE: Loop 2 High/Low Maintenance is supported only on commercial control panels such as the Vista-128FBP. 5. When prompted, enter Input Type 03 (3 on some controls) – Supervised  RF Transmitter.  6. When prompted for the serial number, activate the sensor (press for 1 sec.) or enter the serial number found on the label located on the unit. The unit will speak, then beep and the serial number will be transmitted to the panel. (This will take approx. 40 secs.) Repeat this step to complete enrollment. 7. The current loop number (4) will begin to flash. 8. Manually change the loop number to the desired loop number for the zone, loop (1) is for Heat/Smoke. 9. When programming for the Heat/Smoke Loop 1 zone type is complete, program other zones for the types as necessary in additional zones (except for Tamper Loop 4, which does not require programming).  WARNING: The fire protection zone enrolled must always be Loop 1. Otherwise, fire annunciations will not be reported by the control. 10.  Enter the zone number to be programmed for CO. 11.  Enter the applicable zone type. Use zone type 14 for Honeywell residential controls.  12.  Enter Input Type 03 (3 on some controls)–Supervised RF Transmitter.  13. When prompted for the serial number, activate the sensor (press for 1 sec.) or enter the serial number found on the label located on the unit. The unit will speak, then beep and the serial number will be transmitted to the panel. (This will take approx. 40 secs.) Repeat this step to complete enrollment. 14.  Check that the CO detector is enrolled as loop 1. 15.  Exit Programming mode and test the detector. Refer   to the Testing Section. 2Serial Number Loop NumberZone Description 1 Zone Description 2Zone nSave5Programming Mode Zones > New > Serial Numbers.LED Flashes3a) Test CO 3b) Test Smoke 5800 combo-ii-0031Power -Up mode (    ) English(    ) Spanish        French  Transmission announcment >  Beep > Serial # sent to panel   (approx. 40 secs)● Repeat Step 3. 4Press Test button for < 1.5 secs3 Testor2 TimesEnter the unique Serial number(s)found on the label located on theunit.  See Important Note above. Visible Annunciation The 5800COMBO Smoke/CO series detector has a multi-color top LED; Green, Red, Blue and Amber. The LED is green for supervisory indication; it blinks during power on, reset, and during normal operation. The LED is amber to signal maintenance and trouble events.  The detector utilizes the side LED windows to indicate alarm events; red for smoke and blue for CO.    Table 1: Operation Modes MODE  Status LED (Top) LED Windows (Side)  Sounder  Speaker  Power Up Blink Green, every 2 secs Dark  Silent Voice welcome, instructions follow POR for language selection, enrollment, testing Normal (Standby) Single Blink Green every 10 secs Dark  Silent  Silent Smoke Alarm Blink Red every 10 secs  Blink red  Temp-3 Voice smoke warning Thermal Alarm  Dark  Blink red  Temp-3 Voice smoke warning CO Alarm Blink Red every 10 secs  Blink blue  Temp-4 Voice CO warning Powered Down  Dark  Dark  Silent  Silent   Model: 5800COMBO with voice and 360 degree viewable LED ring Combination Smoke/Carbon Monoxide (CO) Detector with Built-in Wireless Transmitter INSTALLATION AND SETUP GUIDE
2 Mounting After enrolling and before mounting permanently, conduct Go/No Go test (see controller’s instructions) to verify adequate signal strength.  Adjust the device location as necessary. Physically mount the smoke detector in the desired location;  1. Using two supplied screws and anchors, mount the base.  2. Attach the smoke detector to the mounting base with a clockwise motion.   3. Test each detector as described in the Testing section. 4. Confirm all desired signals have been received by the Central Station. NOTE: NFPA 72 recommends the installation of detectors only after completing construction or any other dust producing activity. 5800 combo-QG-004 Testing Test communications between the detector and the control panel.  The detector mode has two test buttons; one for smoke testing and one for CO testing.  The detector may also be functionally tested using canned smoke and canned CO.  If the detector fails any of the test methods, the detector should be replaced. NOTE: Testing the detector will activate the alarm and send a signal to the panel. Before testing, notify the proper authorities to avoid any false alarms.  Smoke Test   Press and hold the Smoke Test button for 3 to 5 seconds. The detector will sound and illuminate per Table 2 and send a smoke alarm signal to the control panel.   Verify that the smoke alarm signal was received at the control panel.  To functionally test the smoke sensor see Smoke Entry Test section. CO Test  Press and hold the CO Test button for 3 to 5 seconds to enter a functional gas test mode.  See Functional Gas Test section.   The control panel alarm and all auxiliary functions should be verified for a complete test of the system. Smoke Entry Test 1.  With the detector in standby mode, spray canned smoke into the detector. The canned smoke that can be used and is approved for test include: Home Safeguard Industries 25S, SDi CHEK02 and CHEK06, SDi SOLOA4, and SDi SMOKESABRE. 2.  The detector will sound and illuminate per Table 2 and a smoke alarm signal will be sent to the panel.   3.  Verify the smoke alarm signal was received by the control panel. Smoke Sensitivity Reading When the Smoke Test button is pressed for 3 to 5 seconds, the detector will vocally annunciate its smoke sensitivity along with diagnostic information.   Replace Battery 5800combo QG-0062311 54300452010Panasonic CR123A~ 10sec / seg Caution:  The batteries used in this device may present a fire or chemical burn hazard if mistreated.  Do not recharge, disassemble, heat above 100°C (212°F) or dispose of in fire.  Use only Panasonic CR123A Lithium batteries.  Remove old batteries.  Wait 10 seconds and then replace with four new batteries.  Use of other batteries may present a risk of fire or explosion. Keep used batteries away from children.  Dispose of used batteries properly.   Restore Factory Settings Press and hold both the Smoke and CO test switch simultaneously for 10 seconds, then release. The green light will flash rapidly. Press and hold both buttons again for one second and release. The sensor will begin speaking.    Table 2: LED Indication & Sounder during Test and Maintenance MODE  Status LED (Top) Side LED Windows  Sounder  Speaker  Smoke Alarm System Test    Dark  Dark  Temp-3 Warning of  alarm signal  transmission.  Voice smoke warning RealTest™  Functional CO  gas entry test - Waiting for gas entry Blink Red once a second Dark  Silent Voice instructions for testing; warning of alarm signal RealTest™  Functional CO  gas entry test  -Upon successful gas entry Blink Red every  10 secs Blink blue every  10 secs Modified Temp-4 Voice carbon monoxide warning Low Battery Blink Amber every 10 secs Dark  Chirp every 45 seconds after 7 days Voice instructions when chirp is hushed by pressing either test button Smoke Maintenance Blink Amber every 5 secs  Dark  Silent Voice smoke maintenance instructions if either test button is pressed CO Trouble  Blink  Amber  every 5 secs  Dark  Silent   CO End of Life - First 29 days Blink Amber  every 3 secs  Dark  Silent Voice end of life instructions;  press either test button  CO End of Life - after 30 days  Blink Amber every 3 secs  Dark Chirp every 45 Seconds Voice end of life instructions;  press either test button  Power Up  Blink Green, every 2 secs  Dark  Silent Voice welcome, instructions follow POR for language selection, enrollment, testing Normal (Standby) Single Blink Green every 10 sec Dark  Silent  Silent
Download:
Mirror Download [FCC.gov]
Document ID3188678
Application IDo2Wih/OjZ+/6YaDzHIJ7Sw==
Document DescriptionInstallation Instructions
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize89.5kB (1118780 bits)
Date Submitted2016-11-07 00:00:00
Date Available2017-05-06 00:00:00
Creation Date2016-10-18 07:31:15
Producing SoftwareGPL Ghostscript 8.15
Document Lastmod2016-10-21 12:00:17
Document TitleMicrosoft Word - I56-6250-001_5800COMBO_ii_800-22142
Document CreatorPScript5.dll Version 5.2.2
Document Author: e311757
FCC ID Filing: CFS8DLCOMSR

Navigation menu