Adt Security Services Aps 6R Users Manual

50935 50935 AlarmHow.net Library

ADT-APS-6R 50935

ADT-APS-6R to the manual 8439a172-fbd6-4824-803d-8795ee33a19f

2015-02-02

: Adt-Security-Services Adt-Security-Services-Adt-Aps-6R-Users-Manual-413048 adt-security-services-adt-aps-6r-users-manual-413048 adt-security-services pdf

Open the PDF directly: View PDF PDF.
Page Count: 26

DownloadAdt-Security-Services Adt-Security-Services-Adt-Aps-6R-Users-Manual-  Adt-security-services-adt-aps-6r-users-manual
Open PDF In BrowserView PDF
ADTAPS-6R__INSTENGLB0.fm Page 1 Tuesday, November 21, 2000 11:30 AM

ADT Security Services, Inc.
1750 Clint Moore Road
Boca Raton, FL 33431
(561) 988-3600

ADT-APS-6R Auxiliary Power Supply
Installation Instructions

Document 50935
07/21/2000
PN 50935:B

Revision:

B

ECN 00-317

Fire Alarm System Limitations
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control with
remote notification capability–can provide early warning
of a developing fire. Such a system, however, does not
assure protection against property damage or loss of life
resulting from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of
the National Fire Protection Association Standard 72
(NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the
Guide for Proper Use of System Smoke Detectors, which
is made available at no charge to all installing dealers.
A study by the Federal Emergency Management Agency
(an agency of the United States government) indicated
that smoke detectors may not go off in as many as 35%
of all fires. While fire alarm systems are designed to
provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke
cannot reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second-floor
detector, for example, may not sense a first-floor or
basement fire.
Particles of combustion or "smoke" from a developing
fire may not reach the sensing chambers of smoke
detectors because:
• Barriers such as closed or partially closed doors,
walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors
by air outlets.
• Smoke detectors may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to
alarm smoke detectors. Smoke detectors are designed
to alarm at various levels of smoke density. If such
density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have
sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are
often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may
not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide
adequate warning of fires caused by arson, children
playing with matches (especially in bedrooms), smoking
in bed, and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).

LimWarSm.p65

01/10/2000

While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in
the same room as the control panel and in rooms used
by the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal. It is the
property owner's responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission
systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the
requirements of Chapter 7 of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance. A maintenance agreement should be arranged through the local
manufacturer's representative. Maintenance should be
scheduled monthly or as required by National and/or
local fire codes and should be performed by authorized
professional fire alarm installers only. Adequate written
records of all inspections should be kept.

Installation Precautions
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and
associated equipment may be damaged by removing
and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is
read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this
product must be tested in accordance with NFPA 72
Chapter 7 after any programming operation or change in
site-specific software. Reacceptance testing is required
after any change, addition or deletion of system components, or after any modification, repair or adjustment to
system hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested. In addition, to ensure that other operations
are not inadvertently affected, at least 10% of initiating
devices that are not directly affected by the change, up
to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation
at 0-49° C/32-120° F and at a relative humidity of 85%
RH (non-condensing) at 30° C/86° F. However, the
useful life of the system's standby batteries and the
electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore,
it is recommended that this system and all peripherals
be installed in an environment with a nominal room
temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.

Adherence to the following will aid in problem-free
installation with long-term reliability:
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected
to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning
strikes. Consult with the Technical Services Department
if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit
board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains staticsensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that
static charges are removed from the body. Use staticsuppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating,
and programming manuals. These instructions must
be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.

FCC Warning
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not installed and used in accordance with the instruction
manual, may cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a
residential area is likely to cause interference, in
which case the user will be required to correct the
interference at his own expense.

Canadian Requirements
This digital apparatus does not exceed the
Class A limits for radiation noise emissions from
digital apparatus set out in the Radio Interference Regulations of the Canadian Department
of Communications.
Le present appareil numerique n'emet pas de
bruits radioelectriques depassant les limites
applicables aux appareils numeriques de la
classe A prescrites dans le Reglement sur le
brouillage radioelectrique edicte par le
ministere des Communications du Canada.

LimWarSm.p65

01/10/2000

ADTAPS-6R__INSTENGLB0TOC.fm Page 4 Tuesday, November 21, 2000 12:56 PM

Table of Contents

Table of Contents
1. Overview
Introduction ..................................................................................................... 5
Description ....................................................................................................... 5
Specifications ................................................................................................... 7

2. Installation
Introduction ..................................................................................................... 9
Mounting an ADT-APS-6R in a ADT-CAB-400AA Backbox................... 10
Mounting in ADT-CAB-3 Series Cabinets .................................................. 11
Instructions for mounting: ......................................................................... 11
CHS-4 Series Chassis Mounting................................................................ 11
Wiring the ADT-APS-6R.............................................................................. 12
Field Wiring an ADT-APS-6R .................................................................. 12
Connecting Multiple ADT-APS-6R Power Supplies ................................ 13
Wiring Applications ...................................................................................... 14
Connecting the ADT-APS-6R to an ICM-4/ICE-4 Module ...................... 14
Supplying Power to a M300CADT Module .............................................. 15
Configuring the ADT-APS-6R ..................................................................... 16
Servicing the ADT-APS-6R .......................................................................... 17

Appendix A - Unimode 4-16
Connecting the ADT-APS-6R to an MPS-24B............................................ 19

Appendix B - Unimode 300/400
Connecting the ADT-APS-6R to an MPS-400 ............................................ 21

Appendix C - Unimode II & Unimode 2020
Connecting the ADT-APS-6R to an MPS-24A ........................................... 23
Connecting the ADT-APS-6R to an MPS-24B............................................ 24

4

ADT-APS-6R Installation PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 5 Tuesday, November 21, 2000 11:30 AM

1. Overview
Introduction
This document contains information for installing, servicing, and
configuring the ADT-APS-6R Auxiliary Power Supply. The table below
contains a list of document sources for supplemental information:
Control Panels

Refer to...

Part Number

Unimode 4-16

Unimode 4-16 Installation
Manual

A15019

Unimode II Series

Unimode II Installation
Manual

A15583

Unimode 400 Series

Unimode 400 Installation
Manual

50710

Unimode 2020

Unimode 2020 Installation
Manual

51167

ADT Transponder
Series

ADT Transponder Manual

50928

All

ADT Device Compatibility
Document

51352

Table 1 Supplemental Documentation

Description

APS-6Risoview.cdr

The ADT-APS-6R Auxiliary Power Supply is a 150W cabinet-mounted
power supply, designed to power devices that require filtered, regulated,
non-resettable power, such as XP Transponder modules, Notification
Appliance Circuit Modules and Control Modules. The ADT-APS-6R
provides three 24 VDC (filtered) output circuits.

Figure 1 ADT-APS-6R Auxilliary Power Supply

ADT-APS-6R Instruction PN 50935:B 7/21/00

5

ADTAPS-6R__INSTENGLB0.fm Page 6 Tuesday, November 21, 2000 11:30 AM

1. Overview

Description

The figures below identify the features of the ADT-APS-6R power
supply:
Trouble In (J4) - Trouble Out (J3)
“P” style connectors for internal cabinet
connections
Three 24 VDC output circuits
Two (2) power-limited
One (1) non power-limited

Fuse F2 for battery protection
(10A, 3AG, slow blow)

APS-6Rsidebrd.cdr

J9

JP2 JP3

J2

TB2

J3

J1

LED Status Indicators:
Green LED – Indicates AC power on
Yellow LED – Indicates loss of AC or battery

Jumpers JP2 and JP3 for
selecting 8-hour or 16-hour
delay for AC loss reporting
(default is immediate)

Fuse F1 for AC protection
(4A, 3AG, slow blow)

APS-6Rboard.cdr

JP 1

Figure 2 ADT-APS-6R Control Board

Jumper JP1 for selecting AC input voltage
(120 VAC default)
Figure 3 ADT-APS-6R Main Board

6

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 7 Tuesday, November 21, 2000 11:30 AM

1. Overview

Specifications

Specifications
The ADT-APS-6R is compatible with the Unimode II, Unimode 300/400,
Unimode 4-16 and Unimode 2020 control panels. Specifications for the
ADT-APS-6R are:
Electrical Specifications
AC Primary Input Power
Wire Size: #14 AWG with
600 VAC insulation

120 VAC, 60 Hz, 2.5 A
240 VAC, 50 Hz, 1.2 A

24 VDC Secondary Input Power
(lead-acid batteries only)

25 mA DC standby current
16 mA DC standby current (with AC fail delay
operating)

Note: Batteries are charged by the system power supply.
24 VDC output power
Circuit 1
Circuit 2
Circuit 3

Total 6 A (4 A continuous)
3 A @24 VDC power-limited (+10, –15%)
3 A @24 VDC power-limited (+10, –15%)
6 A @24 VDC non power-limited (+10, –15%)

Fuses
F1 (AC supervision)
F2 (battery supervision)

250 VAC, 4A, 3 AG, slow blow
32 VAC, 10 A, 3 AG, slow blow

Trouble supervision bus
J3 output
J4 input
Note: J3 and J4 can be
interchanged.
Loss of AC Indication

Form A contact (open collector)
Form A contact (open collector)

Immediate indication (default)
8 or 16 hour delay

Mechanical Specifications
Size of ADT-APS-6R in enclosure

6.09 in. x 4.23 in. x 2.92 in.

Cabinets for mounting

ADT-CAB-3 Series, using CHS-4 and CHS-4L
chassis, for Unimode 400, unimode II and
Unimode 2020 control panels.
ADT-CAB-400AA for Unimode 300/400
control panel; accepts one APS-6R.
Unimode 4-16 can accept one ADT-APS-6R.

Note: An optional module (such as an ICM-4) without an expansion card can
mount above an ADT-APS-6R in a CHS-4, a Unimode 4-16, and a
ADT-CAB-400AA.
Table 2 ADT-APS-6R Specifications

ADT-APS-6R Instruction PN 50935:B 7/21/00

7

ADTAPS-6R__INSTENGLB0.fm Page 8 Tuesday, November 21, 2000 11:30 AM

1. Overview

Specifications

NOTES

8

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 9 Tuesday, November 21, 2000 11:30 AM

2. Installation
!

WARNING: Use extreme caution when working with the APS-6R.
High voltage and AC line-connected circuits are present. Turn off and
remove all power sources. To reduce the risk of electric shock make
sure to properly ground the unit.

Introduction
This section contains instructions for mounting, wiring, configuring and
servicing the ADT-APS-6R.
Installation topics covered in detail:
Topic

Refer to...

Mounting to a ADT-CAB-400AA
Backbox

"Mounting an ADT-APS-6R in a
ADT-CAB-400AA Backbox" on
page 10

Mounting to a ADT-CAB-3 Series
Cabinet

"Mounting in ADT-CAB-3 Series
Cabinets" on page 11

Field Wiring

"Field Wiring an ADT-APS-6R" on
page 12

Wiring Multiple ADT-APS-6Rs

"Connecting Multiple ADT-APS-6R
Power Supplies" on page 13

Connecting to an ICM/ICE

"Connecting the ADT-APS-6R to an
ICM-4/ICE-4 Module" on page 14

Powering an M300CADT

"Supplying Power to a M300CADT
Module" on page 15

Configuring

"Configuring the ADT-APS-6R" on
page 16

Servicing

"Servicing the ADT-APS-6R" on
page 17

ADT-APS-6R Instruction PN 50935:B 7/21/00

9

ADTAPS-6R__INSTENGLB0.fm Page 10 Tuesday, November 21, 2000 11:30 AM

2. Installation

Mounting an ADT-APS-6R in a ADT-CAB-400AA Backbox

Mounting an ADT-APS-6R in a ADT-CAB-400AA Backbox
An Auxiliary Power Supply is mounted as shown in the figure below.
To mount the ADT-APS-6R, follow these instructions:
Step

Action

1

Remove plastic cover from APS-6R.

2

If 240 VAC is to be used, cut JP1 jumper at this time. See "Configuring the
ADT-APS-6R" on page 16.

3

Place the APS-6R onto the mounting studs in the backbox.

4

Insert a standoff through each of the printed circuit board mounting holes,
threading each standoff to the mounting studs.

5

Tighten the standoffs until the APS-6R is securely fastened to the backbox.

6

Reinstall the plastic chassis cover.

ADT-CAB-400AA
Backbox

Mounting
Studs

ADT-APS-6R
Assembly

APS-6R to CAB-AA.cdr

Standoff
(2 places)

Figure 4 Mounting an ADT-APS-6R to a ADT-CAB-400AA Backbox

10

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 11 Tuesday, November 21, 2000 11:30 AM

2. Installation

Mounting in ADT-CAB-3 Series Cabinets

Mounting in ADT-CAB-3 Series Cabinets
This section contains instructions for the installation of the Auxiliary
Power Supply into a ADT-CAB-3 Series cabinet (ADT-CAB-A3, ADTCAB-B3, ADT-CAB-C3 and ADT-CAB-D3).
These cabinets use a CHS-4L or CHS-4 Chassis to mount the
ADT-APS-6R.
Instructions for mounting:
Step

Action

1

Remove plastic cover from APS-6R.

2

If 240 VAC is to be used, cut JP1 jumper at this time. See "Configuring the
ADT-APS-6R" on page 16.

3

Place the APS-6R onto the mounting studs of the chassis (Figure 5 on page
11).

4

Insert a standoff through each of the printed circuit board mounting holes,
threading each standoff to the mounting studs on the chassis.

5

Tighten the standoffs until the APS-6R is securely fastened to the chassis.

6

Reinstall the plastic chassis cover.

CHS-4 Series Chassis Mounting
The illustration below shows an ADT-APS-6R being mounted in a CHS4L chassis. Mounting in a CHS-4 chassis is accomplished in the same
way.
CHS-4L Chassis

ADT-APS-6R
Assembly

Standoff
(2 places)

APS-6R to CHS-4L.cdr

Mounting Studs

Figure 5 Mounting an ADT-APS-6R to a CHS-4L Chassis

ADT-APS-6R Instruction PN 50935:B 7/21/00

11

ADTAPS-6R__INSTENGLB0.fm Page 12 Tuesday, November 21, 2000 11:30 AM

2. Installation

Wiring the ADT-APS-6R

Wiring the ADT-APS-6R
This section contains instructions for wiring the Auxiliary Power Supply
as follows:
• Typical field wiring from an ADT-APS-6R to a control panel and
optional devices.
• Wiring multiple ADT-APS-6R power supplies.
Field Wiring an ADT-APS-6R
You can use J1 and J2 in place of TB2 when the ADT-APS-6R is
powering internal modules (such as an ICM-4, ICE-4, ADT-UZC-256,
XPC-8) with compatible connectors.
Output Circuit 3 (J9) can be used as a source of power for the XPIQ Audio
Transponder only.
Note: When using the J9 connector do not use the J2 connector. This will satisfy the
0.25 (6.35mm) requirement for separation between power-limited and nonpowerlimited circuits.

Primary and Secondary Power Connections - See appendix for your
specific system information.

!

Caution: When finished wiring AC connections, install the press-fit
terminal block cover over TB1 AC connections.
Output Circuit 3: Non Power-limited, 6 A @24 VDC (+10, –15%)
Output Circuit 2 (24 VDC)
Output Circuit 1 (24 VDC)

– + – + – +
J1

J2

+
–
+
–

TB2
J3

Output Circuit 1: Power-limited
3 A @24 VDC (+10, –15%)
Output Circuit 2: Power-limited
3 A @24 VDC (+10, –15%)

Trouble Bus In/Out

BATT (+)
BATT (–)
HOT
JP2 JP3

NEUTRAL
EARTH

Secondary Power
24 VDC batteries.
Primary Power
120 VAC or 240 VAC.

APS-6Rsidebrd.cdr

J9

Earth Ground - Connects to chassis or
ground terminal on main power
supply. If two or more units are connected,
secondary units connect to earthground
on the previous ADT-APS-6R in the chain.
EARTH

Figure 6 Typical Wiring for an ADT-APS-6R

12

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 13 Tuesday, November 21, 2000 11:30 AM

2. Installation

Wiring the ADT-APS-6R

Connecting Multiple ADT-APS-6R Power Supplies
Typical trouble bus connections for multiple ADT-APS-6R power
supplies using trouble connectors J3 and J4.
Use Cable 71033 or 75098 (same cables; different lengths) for all wiring.
See appendix on your system for specific “Trouble Input” connection.
Note: J3 and J4 can be interchanged.
To trouble input on main power
supply or control panel

J1

J2

J9

TB2

J1

J2

J9

TB2
J3

JP2 JP3

First APS-6R

J1

J2

TB2
J3

JP2 JP3

J3

JP2 JP3

APS-6Rmultiple.cdr

J9

Last APS-6R

Figure 7 Trouble Bus Connections for Multiple ADT-APS-6R Configurations

ADT-APS-6R Instruction PN 50935:B 7/21/00

13

ADTAPS-6R__INSTENGLB0.fm Page 14 Tuesday, November 21, 2000 11:30 AM

2. Installation

Wiring Applications

Wiring Applications
This section contains instructions for wiring the ADT-APS-6R assembly
as follows:
• Connecting the ADT-APS-6R to an ICM-4/ICE-4 module
• Supplying notification appliance power to a FCM module
Connecting the ADT-APS-6R to an ICM-4/ICE-4 Module
All four (4) NACs on the ICM-4 are powered from the ADT-APS-6R
output circuit 2 (J2) and the four (4) NACs on the ICE-4 are powered from
circuit 1 (J1). The NACs share the total 3A available from each circuit.
Typical connections for wiring:
J5 J 6

ICM-4
J5 J 6

ICE-4
Blue

Black
Auxiliary Power
Harness
PN 71091

Blue
Black

J9

J1

J2

TB2
J3

ADT-APS-6R

APS-6Ricm.cdr

JP2 JP3

Figure 8 Typical ADT-APS-6R Wiring to an ICM-4/ICE-4 Module

14

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 15 Tuesday, November 21, 2000 11:30 AM

2. Installation

Wiring Applications

Supplying Power to a M300CADT Module
The circuit is supervised and power-limited.
Typical connections for wiring:
J9

J1

J2

SLC loop
TB2
J3

8
7
6
JP2 JP3

5
LLOO
OOPP

NAC

6 7 8 9 10
11
12
13
1 0 1514
TEN S
6 7 89
5
4
3
2
10
5
4
3
2

ON ES

0
1
2
3
4

AA DD
DDRE
RESSSS

To next device
on SLC loop
Figure 9 Typical ADT-APS-6R Wiring to a M300CADT Module

ADT-APS-6R Instruction PN 50935:B 7/21/00

APS-6Rfcm.cdr

9

15

ADTAPS-6R__INSTENGLB0.fm Page 16 Tuesday, November 21, 2000 11:30 AM

2. Installation

Configuring the ADT-APS-6R

Configuring the ADT-APS-6R
The ADT-APS-6R may be configured for the following:
• 8-hour delay for reporting loss of AC: cut jumper JP2.
• 16-hour delay for reporting loss of AC: cut jumper JP2 and JP3.
• 240 VAC operation: cut jumper JP1.

J9

JP2 JP3

J2

TB2

J3

J1

The figure below illustrates the location of the jumpers:

JP2

JP3

APS-6Rconfig.cdr

JP1

JP1

Figure 10 Configuring the ADT-APS-6R

16

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 17 Tuesday, November 21, 2000 11:30 AM

2. Installation

Servicing the ADT-APS-6R

Servicing the ADT-APS-6R
The only serviceable components on the ADT-APS-6R are fuses F1 and
F2. If a fuse fails, replace it with a fuse of the same type and rating:
• F1 AC protection - 4A, 3 AG
• F2 Battery protection - 10A, 3 AG
To replace either fuse remove the vertical PC board as follows:
1.

Turn off and remove all power sources.

2.

Remove plastic cover.

3.

Remove the two retaining screws securing vertical board.

4.

Unplug the vertical PC board from the connectors.

5.

Replace fuses as required.

6.

Reinstall board in reverse order, install plastic cover and connect all
power.

The figure below illustrates the location of the fuses.
F2 Fuse

J9

JP2 JP3

J2

TB2

J3

J1

Retaining Screw (typ)

Connector (typ)

APS-6Rservice.cdr

F1 Fuse

Main Circuit Board
Figure 11 Servicing the ADT-APS-6R

ADT-APS-6R Instruction PN 50935:B 7/21/00

17

ADTAPS-6R__INSTENGLB0.fm Page 18 Tuesday, November 21, 2000 11:30 AM

2. Installation

Servicing the ADT-APS-6R

NOTES

18

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 19 Tuesday, November 21, 2000 11:30 AM

Appendix A - Unimode 4-16
Connecting the ADT-APS-6R to an MPS-24B
Make the following connections as shown in the figure below.
• Connect primary power from TB1 to MPS-24B terminal block
TB1, Pin 3(NEUT) and Pin 4(HOT)
• Connect secondary power from TB3 to MPS-24B terminal block
TB3, Pin 1(+) and Pin 2(–)
• Connect trouble input from J3 to MPS-24B terminal block P4

TB1
J9

EARTH

AC NEUT

2

3

AC HOT

R55 1 2 3 4 6 7 8

+2 4 VRESET

CO MMON +2 4 VPOW ER CO MMON

BATT +

BATT -

TB3

J1

J2

CB1

4

P2

TB2

1

2

3

1

4

AC

P3

2

TRO UBLES
BATT
+EF

-EF

7 P1

TB2
J3

5

JP3

P4

3
2
1

APS-6R to MPS-24B.cdr

MPS-24BPCC
REV ___

JP2 JP3

Figure 12 Wiring to MPS-24B

ADT-APS-6R Instruction PN 50935:B 7/21/00

19

ADTAPS-6R__INSTENGLB0.fm Page 20 Tuesday, November 21, 2000 11:30 AM

Appendix A - Unimode 4-16

Connecting the ADT-APS-6R to an MPS-24B

NOTES

20

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 21 Tuesday, November 21, 2000 11:30 AM

Appendix B - Unimode 300/400
Connecting the ADT-APS-6R to an MPS-400
Make the following connections as shown in the figure below.
• Connect primary power from TB1 to MPS-400 terminal block TB1
(NEU and HOT)
• Connect secondary power from TB3 to MPS-400 terminal block
TB1 (+ and –)
• Connect trouble input from J3 to MPS-400 terminal block J4

B ATT+

BATT-

TB9

2BT

HOT

5BT
7BT

EARTH

J1

J2

3BT

POWER IN PUT- 120V, 60 Hz, and 24 V BATT
NEUTRAL

J9

+ - + - + TB1

B+

B-

A+

A-

01BT

SE CURITY

6BT

SUPERVISORY

8BT

4BT

To Transform er Assembly T2
B+

B-

A+

A-

To Transformer Assembly T1

TB2

J6

J3
R E W OP U P C
SEI R OSS E CCA
J2

R OT CE NNOC 0 0 4- P F A

JP2 JP3

JP2

S2
S2

APS-6R to MPS-400.cdr

J1

Figure 13 Wiring to MPS-400

ADT-APS-6R Instruction PN 50935:B 7/21/00

21

ADTAPS-6R__INSTENGLB0.fm Page 22 Tuesday, November 21, 2000 11:30 AM

Appendix B - Unimode 300/400

Connecting the ADT-APS-6R to an MPS-400

NOTES

22

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0.fm Page 23 Tuesday, November 21, 2000 11:30 AM

Appendix C - Unimode II & Unimode 2020
Connecting the ADT-APS-6R to an MPS-24A
Make the following connections as shown in the figure below.
• Connect primary power from TB1 to MPS-24A terminal block
TB1, Pin 5(NEUT) and Pin 7(HOT)
• Connect secondary power from TB3 to MPS-24A terminal block
TB2, Pin 1(+) and Pin 2(–)
• Connect trouble input from J3 to MPS-24A terminal block P5

TB2

J9

J1

J2

TB1

EA RTH G ND

A C NE U TRA L

BAT +

BAT -

+ 24 R

POW ER L IM ITE D
CO MM ON
+24
COMMON

A C HOT

P2
P5

CB1

F1

P3

P4
R27

JP5

TB2

APS-6R to MPS-24A.cdr

J3

JP2 JP3

Figure 14 Wiring to MPS-24A

ADT-APS-6R Instruction PN 50935:B 7/21/00

23

ADTAPS-6R__INSTENGLB0.fm Page 24 Tuesday, November 21, 2000 11:30 AM

Appendix C - Unimode II & Unimode 2020

Connecting the ADT-APS-6R to an MPS-24B

Connecting the ADT-APS-6R to an MPS-24B
Make the following connections as shown in the figure below.
• Connect primary power from TB1 to MPS-24B terminal block
TB1, Pin 3(NEUT) and Pin 4(HOT)
• Connect secondary power from TB3 to MPS-24B terminal block
TB3, Pin 1(+) and Pin 2(–)
• Connect trouble input from J3 to MPS-24B terminal block P4

TB1
J9

EARTH

AC NEUT

2

3

AC HOT

R55 1 2 3 4 6 7 8

+2 4 VRESET

CO MMON +2 4 VPOW ER CO MMON

BATT +

BATT -

TB3

J1

J2

CB1

4

P2

TB2

1

2

3

1

4

AC

P3

2

TRO UBLES
BATT
+EF

-EF

7 P1

TB2
J3

JP3

5

P4

3
2
1

APS-6R to MPS-24B.cdr

MPS-24BPCC
REV ___

JP2 JP3

Figure 15 Wiring to MPS-24B

24

ADT-APS-6R Instruction PN 50935:B 7/21/00

ADTAPS-6R__INSTENGLB0IX.fm Page 25 Tuesday, November 21, 2000 12:57 PM

Index

Index
Numerics

I

16-hour delay 16
240 VAC
operation 16
use of 10, 11
8-hour delay 16

ICM/ICE-4 12, 14
connections to 14
Installation topics 9
internal modules 12

A

J1 connection 12
J2 connection 12
J3 connection 13
J4 connection 13
J9 connection 12
JP1 jumper 10, 11, 16
JP2 jumper 16
JP3 jumper 16
jumpers, location of 16

J

AC protection 17
ADT-CAB-3 Series cabinet 11
ADT-CAB-400AA 10
ADT-UZC-256 12

B
backbox 10
Battery protection

17

C
cable 13
chassis 11
mounting 11
CHS-4 11
CHS-4L 11
configuring 16
connections
MPS-24A 23
MPS-24B 24
MPS-24BPCA
MPS-400 21
Control Modules 5

M
M300CADT Module, connections to 15
Mechanical Specifications 7
MPS-24A 23
MPS-24B 19, 24
MPS-400 21
multiple power supplies 13

N
NAC Modules 5
NACs 14
Non Power-limited circuit

19

O

D
5

document sources, list of

E
Earth Ground 12
Electrical Specifications

Output Circuit
Non Power-limited
Power-limited 12

12

P
7

F
features of the APS-6R
field wiring 12
fuses 17

12

6

PC board, vertical 17
Power-limited circuit 12
Primary Power 12
primary power 19, 21, 23, 24

H
High Voltage Warning

9

ADT-APS-6R Instruction PN 50935:B 7/21/00

25

ADTAPS-6R__INSTENGLB0IX.fm Page 26 Tuesday, November 21, 2000 12:57 PM

Index

S
Secondary Power 12
secondary power 19, 21, 23,
serviceable components 17
Specifications 7
standoff 10, 11

24

T
TB2 12
terminal block cover 12
Trouble Bus 12
trouble connectors 13
trouble input 19, 21, 23,

24

U
Unimode 300/400 21
Unimode 4-16 19
Unimode II 23
Unimode2020 23

W
Warning, High Voltage 9
wiring 12

X
XP Transponder
XPC-8 12

26

5

ADT-APS-6R Instruction PN 50935:B 7/21/00



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Fill forms, Extract, Assemble, Print high-res
Create Date                     : 2000:11:21 11:32:47
Producer                        : Acrobat Distiller 4.05 for Windows
Modify Date                     : 2000:11:29 14:47:38-05:00
Page Count                      : 26
EXIF Metadata provided by EXIF.tools

Navigation menu