INTRODUCTION

OVERVIEW
000623001C07

000623001C07

The Network Management Teleservice Card (66124) is
recommended for central UPSs protecting entire networks or for UPS
units backing up critical loads.
With the card installed, the UPS has its own IP address and uses the
local computer capabilities to:
◗ supply web pages (http or https (SSL)) with information on status
conditions and measurements/settings/alarms,
◗ integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli
Netview and Computer Associates Unicenter,
◗ communicate with shutdown modules installed on the protected
servers (Network Shutdown Module),
◗ send e-mail and SMS messages,
◗ control the ON/OFF function of the UPS and the outlets,
◗ monitor the Environment Sensor,
◗ Access the Teleservice solution for remote monitoring and
maintenance services of your UPS.

MAC adress

PHONE port:
Green LED : Phone communication
with the UPS
Orange LED : Modem connection

ETHERNET port:
Green LED : Connection + activity
UPS Da
ta

CD

Orange LED : 10/100 M
ETH

ERN

PHON
E

ET

SENS
OR/R
S 485

ACT

RESE
T

Service port (Sensor/RS485):

100M
( Set

tings)

6612

4

Green LED : Communication with
the UPS

The Network Management Teleservice Card must be
installed and used in accordance with manufacturer
instructions.

Orange LED :RS232 activity

Catalogue number

UNPACKING AND CHECKS
◗
◗
◗
◗
◗

INDICATIONS

One Network Management Teleservice Card (66124),
One serial cable for configuration (3402226700),
One phone cable for teleservice (3402226800),
One installation manual (34022315EN),
One Teleservice information form (3402228500),

PHONE port
LED
UPS Data

Colour
Green

Status

Description

◗ OFF

◗ Card not connected to phone

◗ ON

◗ Card connected to phone

◗ Flashing

◗ Port is sending/receiving

◗ OFF
◗ ON
◗ Flashing

◗ Modem is not connected
◗ Modem is connected
◗ Modem is connecting

network
network, but no activity
CD

Settin
gs/Se
nsor

ETHE

RNET

Setting
s/Sens
or

Orange

Settin
gs/Se
nsor

Settings
/Sensor
Settings
/Sensor

100M

UPS

10M

data

ETHERNET port

RS2

32

6610

8

LED
ACT

Colour
Green

Network
Management
Teleservice Card
(66124)
Settin
gs/Senso
r

Settin
gs/Se
nsor

ETH

Settings/Sen
sor

100M

ERN
ET

Settin
gs/Senso
r

UPS

data

Description
◗ Card not connected to network
◗ Card connected to network, but

◗ Flashing

◗ Port is sending/receiving

◗ OFF
◗ ON

◗ Port operating at 10 Mbits/s
◗ Port operating at 100 Mbits/s

no activity

Installation manual

Settings/Sen
sor

10M

Status
◗ OFF
◗ ON

RS232

66124

100M

Orange

Service port (Sensor/RS485)
LED

Colour

Status

Description

Sensor

Green

◗ OFF
◗ ON
◗ Flashing

◗ Card starting
◗ Card ready
◗ Communication with environment

RS485

Orange

◗ OFF
◗ Flashing
◗ Flashing

◗ Settings mode activated
◗ Port is sending/receiving
◗ Communication fault or

every seconds

configuration errors

Sensor is operational

SWITCHES SETTING
Default settings, sensor configuration :

SA1

SA2
1

3

3

ON

ON

OFF

OFF

8

8

3402231500/AC

1

INSTALLATION

Your network is not equipped with a BOOTP/DHCP server

The Network Management Teleservice Card (66124) can be hotplugged on MGETM GalaxyTM 7000 UPSs. It is not necessary to
shutdown the UPS, disconnect the load or restart the UPS.
◗ A. Remove the plastic cover of the Minislot.
◗ B. Note the MAC address of the card before inserting it.
◗ C. Connect the PHONE cable.
◗ D. Connect the ETHERNET cable (network already connected).
◗ E. Insert and secure the card with the screws.

E

A

UPS Data

CD

ETHE

RNE

UPS
T SENS
OR/RS

485

PHONE
ACT
100M

000623001C07

000623001C07

RESET

( Settings)

66124

C

D

B

◗ Check the ETHERNET port indications.
◗ Wait until the UPS Data LED flashes regularly (approx. two minutes),
indicating that card start-up has terminated correctly.

Once the card has started, proceed as indicated below.
◗ Connect one end of the serial cable to the Service port.
◗ Connect the other end of the cable to the COM (IOIOI) port of a PC.
◗ Run a terminal emulator such as HyperTerminalTM with these settings
Data bits
8

Stop bits
1

1 : Read Network settings
2 : Modify Network settings
3 : Set ethernet speed
0 : Exit
For each of the following questions, you can press "Return" to select
the value shown in braces, or you can enter a new value
Should this target obtain IP settings from the network?[N] N
Static IP address [172.17.16.16]?172.16.1.82
Subnet mask IP address [255.255.0.0]? 255.255.255.0
Gateway address IP address [0.0.0.0]? 172.17.17.1
Done
Wait until "Done" is displayed, indicating that the IP parameters have
been saved.
◗ Press the 0 key (Exit), then press the ↵ key.
◗ Press the 1 key (Reset), then press the ↵ key.
The card restarts with the new IP settings (after approx. two minutes).

ACCESS TO SUPERVISION

IP SETTINGS

Bits per second
38400

Manual configuration is required.
To set the network configuration(from the main configuration menu):
◗ Press the 2 key (Network configuration), then press the ↵ key.
◗ Press the 2 key (Modify Network settings), then press the ↵ key.
◗ Follow the instructions and enter the IP parameters:

Flow control
none

To check whether the Network Management Teleservice Card is
operational after installation and IP settings, proceed as follows.
◗ Run a browser
◗ Enter in the address bar:
http://IP address/ (e.g. http://172.16.1.82/)
◗ The home page is displayed:

"Echo typed characters locally" option: disabled
◗ Press the ↵ key.
◗ press the 1 key (Network configuration menu)
◗ Type MGEUPS (or mgeups), then press the ↵ key.
The main configuration menu is displayed
:
APC by Schneider Electric
NETWORK MANAGEMENT CARD
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
Your network is equipped with a BOOTP/DHCP server (default)
The card is configured by default with this service enabled. No manual
configuration is required.The IP parameters are automatically collected
by the card.
To view the network configuration(from the main configuration
menu):
◗ Press the 2 key (Network configuration), then press the ↵ key.
◗ Press the 1 key(Read Network settings)., then press the ↵ key.
The settings supplied by the server are displayed:
Network configuration :
MAC address : 00:06:23:00:1C:07
Mode : DHCP
IP address : 172.17.23.18
Subnet mask : 255.255.248.0
Gateway : 172.17.17
◗
◗
◗
◗

Note the IP address.
Press the ↵ key
Press the 0 key (Exit), then press the ↵ key.
Press the 0 key (Exit), then press the ↵ key.

◗ Set the time by clicking the Time command.
◗ Continue configuration via the sections in the Settings menu.

Teleservice procedure
◗ Install the Network Management Teleservice Card kit using the
present manual.
◗ Fill in the information form (3402228500).
◗ Send the form to your Teleservice centre (by Fax or Internet).
◗ Your centre will activate this service.
◗ You receive an acknowledgement of receipt.
The information form must be sent back in order to trigger remote
monitoring of your equipment.

USER MANUAL
The manual (34003991EN) provides all the information required to use,
install and configure the Network Management Teleservice Card.
For more information on the supervision, control and configuration
functions offered by the Network Management Teleservice Card, see
the user manual on the www.apc.com web site.
3402231500/AC

SENSOR CONNECTION (option)
The Environment sensor is a Network Management Teleservice
Card option.
The sensor remotely monitors the UPS environment by regularly
measuring the temperature and humidity, and checking the states of
two external contacts. It can also send alarms (e-mail, SNMP trap)
tripped by pre-set thresholds.
Connection is made via the Service port (Settings/Sensor) on the
Network Management Teleservice Card. The sensor is detected
automatically. Configuration and supervision use a menu that may be
accessed directly from the home page. For more information, see the
user manual of the Network Teleservice Management Card.

TECHNICAL CHARACTERISTICS
Physical characteristics
Dimensions (W x D x H)

132 x 66 x 42 mm

Weight

85 g

RoHS

100% compatible

Storage
Storage temperature
range

-10°C to 70°C

Ambient conditions
Operating temperature
range

0°C to 40°C

Relative humidity

90% RH max. without condensation

Card performance
Setings
/Senso
r

ETHE

RNETSe

UPS

data

RS2

32

PHONE

tting

s/Sen

sor
Setings
/Senso
r

100M
On =
Blin Link
k = Act

10M

UPS

data

RS2

ETHE

RNETSe

32

6610

tting

2

s/Sen

sor

Supply voltage

5V ±5%

Supply current (all LEDs
ON and Environment
Sensor connected)

500 mA max.

100M
10M

Functions

ETHERNET

UPS

Web supervision

5 browsers max. (http),
3 browsers max. (https)

Languages

English

Alarms

E-mail, SNMP TRAP, Web page

Log

400 measurements or events

Server protection

Up to 35 servers protected

Network

Fast ETHERNET, 10/100 Mbits, auto-negotiation
HTTP 1.1, SNMP V1, NTP, TFTP, SMTP,
BOOTP/DHCP

Identification

User name and password

Security

SSL 3.0, TLS 1.0

Browsers

Microsoft Internet Explorer 6.x or higher

NMS

Enterprise Power Manager (EPM)
Management-Pac 2

MIB

MIB II standard - MGE V1.7 MIB

Settings (default values)
IP network

BOOTP/DHCP enabled
IP address: 172.17.16.16
Subnet mask: 255.255.0.0
Gateway: 0.0.0.0
NTP server: pool.ntp.org

Web-page access control

User name: MGEUPS
Password: MGEUPS

Service-port menu access
control

Password: MGEUPS or mgeups
(not modifiable)

Date and time

Synchronise with an NTP server (GMT)

Service port

38400 bits/s, 8 bits, 1 bit stop, no parity

Standards
ITE (Information
Technology Equipment)
safety

3402231500/AC

IEC/EN 60950-1 (2005)

R&TTE

99/05/EEC

EMC

EN 61000-6-2 (2005), EN 61000-6-3 (2006)
2004/108/EEC

Low voltage

2006/95/EEC

FCC (Federal
Communication
Commission )

This equipment has been tested and found to
comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC rules. These limits
are designed to provide reasonable protection
against harmful interference when the equipment
is operated in a commercial environment.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
Page Count                      : 4
Page Mode                       : UseNone
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:f4e7e069-f537-4a3d-ad2c-8ad1cb827828
Producer                        : Acrobat Distiller 6.0 (Windows)
Create Date                     : 2006:03:17 09:25:22Z
Creator Tool                    : FrameMaker 7.0
Modify Date                     : 2009:05:13 14:09:51Z
Document ID                     : uuid:56cfd03f-af93-4c71-8513-fd402f62f729
Format                          : application/pdf
Title                           : untitled
Creator                         : FrameMaker 7.0
EXIF Metadata provided by EXIF.tools

Navigation menu