User Guide
Switched Rack Power Distribution
Unit

AP89xx

Contents
Introduction ..................................................................... 1
Product Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Access Priorities for Logging on. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Types of User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Watchdog Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Network interface watchdog mechanism . . . . . . . . . . . . . . . . . . . . . 3
Resetting the network timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Network Port Sharing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
About the Network Port Sharing Feature . . . . . . . . . . . . . . . . . . . . . 3
Display ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Establish Network Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INI file utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
DHCP and BOOTP configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Command Line Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Recovering from a Lost Password . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Rack PDU Front Panel .................................................... 8
Network Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
10/100 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Load indicator LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Command Line Interface .............................................. 11
About the Command Line Interface . . . . . . . . . . . . . . . . . . . . . . . . . 11
Log on to the Command Line Interface . . . . . . . . . . . . . . . . . . . . . . 11
Remote access to the command line interface . . . . . . . . . . . . . . . 11
Local access to the command line interface . . . . . . . . . . . . . . . . . 12

Metered Rack PDU User Guide

i

About the Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Using the Command Line Interface. . . . . . . . . . . . . . . . . . . . . . . . . . 13
Command Syntax . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Command Response Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Network Management Card Command Descriptions . . . . . . . . . . . 16
about . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
alarmcount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
appcli . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
boot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
cd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
clrrst . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
dir . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
dns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
eventlog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
FTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
netstat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
ntp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
ping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
portSpeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
prompt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
quit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
radius . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
reboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
resetToDef . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
snmp, snmpv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
tcpip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
tcpip6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
web . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
xferINI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
xferStatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Metered Rack PDU User Guide

ii

Device Command Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
bkLowLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
bkNearOver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
bkOverLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
bkReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
bkRestrictn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
devLowLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
devNearOver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
devOverLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
devReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
devStartDly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
humLow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
humMin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
humReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
olAssignUsr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
olCancelCmd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
olDlyOff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
olDlyOn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
olDlyReboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
olGroups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
olName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
olOff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
olOffDelay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
olOn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
olOnDelay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
olRbootTime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
olRboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
olStatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
olUnasgnUsr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
ph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
phNearOver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
phOverLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
phReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
phRestrictn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
prodInfo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
sensorName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
tempHigh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
tempMax . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
tempReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
userAdd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
userDelete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
userList . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
userPasswd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
whoami . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Network Port Sharing Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Metered Rack PDU User Guide

iii

Web Interface................................................................. 46
Supported Web Browsers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Logging On to the Web Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
URL address formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Web Interface Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Tabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Device status icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Quick Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Other Web interface features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

About the Home Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
The Overview view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
The Alarm Status view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Device Management...................................................... 51
About the Device Manager Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Viewing the Load Status and Peak Load . . . . . . . . . . . . . . . . . . . . . 51
Configuring Load Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Configure the Name and Location of the Rack PDU . . . . . . . . . . . . 52
Set the Coldstart Delay for the Rack PDU . . . . . . . . . . . . . . . . . . . . 52
Reset Peak Load and kWh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Set the Overload Outlet Restrictions . . . . . . . . . . . . . . . . . . . . . . . . 53
Configure and Control Outlet Groups. . . . . . . . . . . . . . . . . . . . . . . . 53
Group Control using Network Port Sharing . . . . . . . . . . . . . . . . . . 53
Outlet group terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Purpose and benefits of outlet groups . . . . . . . . . . . . . . . . . . . . . . 54
System requirements for outlet groups . . . . . . . . . . . . . . . . . . . . . 54
Rules for configuring outlet groups . . . . . . . . . . . . . . . . . . . . . . . . 55
Enable outlet groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Create a local outlet group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Create multiple global outlet groups . . . . . . . . . . . . . . . . . . . . . . . 57
Edit or delete an outlet group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Typical outlet group configurations . . . . . . . . . . . . . . . . . . . . . . . . 58
Verify your setup and configuration for global outlet groups . . . 59

Metered Rack PDU User Guide

iv

Outlet Settings for Outlets and Outlet Groups. . . . . . . . . . . . . . . . . 59
Initiate a control action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Configure outlet settings and the outlet name . . . . . . . . . . . . . . . 61

Scheduling Outlet Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Actions you can schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Schedule an outlet event . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Edit, disable, enable, or delete a scheduled outlet event . . . . . . . 63

Outlet Manager Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Configure an outlet user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Outlet Manager and Network Port Sharing . . . . . . . . . . . . . . . . . . . 63

Environment .................................................................. 64
Configure Temperature and Humidity Sensors . . . . . . . . . . . . . . . . 64

Logs................................................................................ 65
Use the Event and Data Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Event log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Data log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Use FTP or SCP to retrieve log files . . . . . . . . . . . . . . . . . . . . . . . . 68

Network Port Sharing Event Logs and Traps. . . . . . . . . . . . . . . . . . 69
Data Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Administration: Security .............................................. 70
Local Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Setting user access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

Remote Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Authentication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
RADIUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Configure the RADIUS Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Summary of the configuration procedure . . . . . . . . . . . . . . . . . . . 72
Configuring a RADIUS server on UNIX® with shadow passwords 72
Supported RADIUS servers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Inactivity Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Metered Rack PDU User Guide

v

Administration: Network Features............................... 73
TCP/IP and Communication Settings . . . . . . . . . . . . . . . . . . . . . . . . 73
TCP/IP settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
DHCP response options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

Port Speed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Ping Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
DNS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Web . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
SNMPv1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
SNMPv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

FTP Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

Administration: Notification ......................................... 83
Event Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Types of notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Configuring event actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

Active, Automatic, Direct Notification . . . . . . . . . . . . . . . . . . . . . . . 85
E-mail notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
SNMP traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
SNMP Trap Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Remote Monitoring Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Syslog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Administration: General Options ................................. 90
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Set the Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Daylight saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Use an .ini File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

vi

Metered Rack PDU User Guide

Event Log and Temperature Units . . . . . . . . . . . . . . . . . . . . . . . . . . .92
Color-code event log text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Change the default temperature scale . . . . . . . . . . . . . . . . . . . . . . . 92

Reset the Rack PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
Configure Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
About the Rack PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93

Device IP Configuration Wizard ...................................94
Capabilities, Requirements, and Installation . . . . . . . . . . . . . . . . . .94
How to use the Wizard to configure TCP/IP settings . . . . . . . . . . . 94
System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

Use the Wizard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
Launch the Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Configure the basic TCP/IP settings remotely . . . . . . . . . . . . . . . . 94
Configure or reconfigure the TCP/IP settings locally . . . . . . . . . . . 95

How to Export Configuration Settings.........................96
Retrieving and Exporting the .ini File . . . . . . . . . . . . . . . . . . . . . . . .96
Summary of the procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Contents of the .ini file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
INI and Network Port Sharing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Detailed procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

The Upload Event and Error Messages. . . . . . . . . . . . . . . . . . . . . . .99
The event and its error messages . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Messages in config.ini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Errors generated by overridden values . . . . . . . . . . . . . . . . . . . . . . 99

Related Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99

File Transfers ...............................................................100
How to Upgrade Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Benefits of upgrading firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Firmware module files (Rack PDU) . . . . . . . . . . . . . . . . . . . . . . . . . 100

Metered Rack PDU User Guide

vii

Firmware File Transfer Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Using the Firmware Upgrade Utility . . . . . . . . . . . . . . . . . . . . . . . . 101
Use FTP or SCP to upgrade one Rack PDU . . . . . . . . . . . . . . . . . 101
Use XMODEM to upgrade one Rack PDU . . . . . . . . . . . . . . . . . . . 102
How to upgrade multiple Rack PDUs . . . . . . . . . . . . . . . . . . . . . . . 102
Using the Firmware Upgrade Utility for multiple upgrades . . . . . 103
Using a USB flash drive to upgrade one Rack PDU . . . . . . . . . . . 103

Verifying Upgrades and Updates . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Verify the success or failure of the transfer . . . . . . . . . . . . . . . . . 104
Last Transfer Result codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Verify the version numbers of installed firmware. . . . . . . . . . . . . 104

Troubleshooting .......................................................... 105
Rack PDU Access Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
For problems that persist or are not described here, see the back cover of this
manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

Appendix A: List of Supported Commands .............. 106
Network Management Card Command Descriptions . . . . . . . . . . 106
Device Command Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

viii

Metered Rack PDU User Guide

Introduction
Product Features
The APC by Schneider Electric Switched Rack Power Distribution Unit (PDU) may be used as a standalone, network-manageable power distribution device or up to 4 devices can be connected together with
one network connection. The Rack PDU provides real-time remote monitoring of connected loads. Userdefined alarms warn of potential circuit overloads. The Rack PDU provides full control over outlets
through remote commands and user interface settings.
Your unit comes with one terminator installed. It is not needed for stand-alone operation of this unit. To
use Network Port Sharing between up to four units, a terminator must be installed in the In port at one
end of the group and another on the Out port at the other end of the group.
You can manage a Rack PDU through its Web interface, its command line interface (CLI), StruxureWare
Data Center Expert, or Simple Network Management Protocol (SNMP). (To use the PowerNet MIB with
an SNMP browser, see the PowerNet SNMP Management Information Base (MIB) Reference Guide,
available at www.apc.com.) Rack PDUs have these additional features:
• Peak load, and power and energy monitoring for all connected loads.
• Voltage, current, and power monitoring for phases.
• Current monitoring for outlet banks.
• Configurable alarm thresholds that provide network and visual alarms to help avoid overloaded
circuits.
• Four levels of user access accounts: Administrator, Device User, Read-Only User, and Outlet User
• Independent outlet control.
• Configurable power delays.
• Up to twenty-four independent outlet user accounts.
• Event and data logging. The event log is accessible by Telnet, Secure CoPy (SCP), File Transfer
Protocol (FTP), serial connection, or Web browser (using HTTPS access with SSL, or using
HTTP access). The data log is accessible by Web browser, SCP, or FTP.
• E-mail notifications for Rack PDU and system events.
• SNMP traps, Syslog messages, and e-mail notifications based on the severity level or category of
the Rack PDU and system events.
• Security protocols for authentication and encryption.
• Network Port Sharing: Up to four Rack PDUs can be connected using the In and Out ports so that
only one network connection is necessary.
Note: The Rack PDU does not provide power surge protection. To ensure that the device is protected
from power failure or power surges, connect the Rack PDU to an APC Uninterruptible Power Supply
(UPS).

1

Switched Rack PDU User Guide

Access Priorities for Logging on
Only one user at a time can log on to the Rack PDU. The priority for access, beginning with the highest
priority, is as follows:
• Local access to the command line interface from a computer with a direct serial connection to the
Rack PDU
• Telnet or Secure SHell (SSH) access to the command line interface from a remote computer
• Web access, either directly or through StruxureWare Data Center Expert
Note: See “SNMP” on page 87 for information about how SNMP access to the Rack PDU is
controlled.

Types of User Accounts
The Rack PDU has four levels of access (Administrator, Device User, Read-Only User, and Outlet User),
which are protected by user name and password requirements.
• An Administrator can use all of the menus in the Web interface and all of the commands in the
command line interface. The default user name and password are both apc.
• A Device User can access only the following:
– In the Web interface, the menus on the Device Manager tab, the Environment tab, and the
event and data logs, accessible under the Events and Data headings on the left navigation
menu of the Logs tab. The event and data logs display no button to clear the log.
– In the command line interface, the equivalent features and options.
The default user name is device, and the default password is apc.
• A Read-Only User has the following restricted access:
– Access through the Web interface only.
– Access to the same tabs and menus as a Device User, but without the capability to change
configurations, control devices, delete data, or use file transfer options. Links to configuration
options are visible but disabled. The event and data logs display no button to clear the log.
The default user name is readonly, and the default password is apc. To set User Name and
Password values for the three account types above, see “Setting user access” on page 77.
• An Outlet User has the following restricted access:
– Access through the Web interface and command line interface.
– Access to the same menus as a Device User, but with limited capability to change
configurations, control devices, delete data, or use file transfer options. Links to configuration
options are visible but are disabled. The Outlet User has access to the Outlet Control menu
option that allows the user to control the outlets assigned by the Administrator. Outlet Users
cannot clear the event or data logs.
The user name and password are defined by the Administrator during the process of adding a
new Outlet User.

Switched Rack PDU User Guide

2

Watchdog Features
Overview
To detect internal problems and recover from unanticipated inputs, the Rack PDU uses internal, systemwide watchdog mechanisms. When it restarts to recover from an internal problem, a System:
Warmstart event is recorded in the event log.

Network interface watchdog mechanism
The Rack PDU implements internal watchdog mechanisms to protect itself from becoming inaccessible
over the network. For example, if the Rack PDU does not receive any network traffic for 9.5 minutes
(either direct traffic, such as SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP]
request), it assumes that there is a problem with its network interface and restarts.

Resetting the network timer
To ensure that the Rack PDU does not restart if the network is quiet for 9.5 minutes, the Rack PDU
attempts to contact the default gateway every 4.5 minutes. If the gateway is present, it responds to the
Rack PDU, and the response restarts the 9.5-minute timer. If your application does not require or have a
gateway, specify the IP address of a computer that is running on the network and is on the subnet. The
network traffic of that computer will restart the 9.5-minute time frequently enough to prevent the Rack
PDU from restarting.

Network Port Sharing
About the Network Port Sharing Feature
You can use the Network Port Sharing feature to view the status of and configure and manage up to four
Rack PDUs using only one network connection. This is made possible by connecting the Rack PDUs via
the "In" and "Out" ports on the Rack PDU front panel.
Note: All Rack PDUs in the group must be using the same Rack PDU firmware revision, 5.1.5 or later
(excluding v6.0.5 EnergyWise), in order to support the Network Port Sharing Feature.

Display ID
The display ID is a number, 1 to 4, used to uniquely identify the Rack PDUs in a group. After two or
more Rack PDUs are connected to one another in a group, they can be identified on the various
interfaces by the use of this "Display ID". This Display ID is viewable on the LCD by selecting the
Display Settings > Display ID > Show option on the LCD keypad.

Installation Instructions
Connect up to four Rack PDUs. Insert an RJ45 terminator (included) in the unused "In"/"Out" ports on
each end of the chain.
Note: Failure to use terminators may cause a loss of communication on the Rack PDUs.
Note: To reduce the possibility of communication issues, the maximum total length of cabling
connecting Rack PDUs in a group should not exceed 10 meters. All Rack PDUs in a Network Port
Sharing group should reside in the same rack enclosure.
Connect the "Network" port of one of the grouped Rack PDUs to a network hub or switch. This unit
will be the "Host" for the Rack PDU group. A Host is defined as a Rack PDU that is connected to the
network and is part of a Rack PDU group. Set up network functionality for this Host Rack PDU as
specified in the Establish Network Settings section. The Host will automatically discover any "Guest"
PDUs connected via In/Out ports. The Rack PDU group is now available via the Host's IP address.

3

Switched Rack PDU User Guide

Specific assignment of Display IDs. Follow the instructions below before powering up any of the
Rack PDUs in the group.

If it is desired to have a specific assignment of Display IDs, this can be achieved by powering up the
units for the first time in the desired order, 1 to 4. For example, before powering up any of the Rack
PDUs connected in a group, determine the Display ID order that you would like. Then, first power up
the unit that you would like to have Display ID 1. After that unit has initialized and the LCD has started
displaying its screens, power on the unit that you would like to have Display ID 2. Continue in the same
way for units 3 and 4, if applicable for your setup.
Note: The Display ID can be configured from the web interface via the "Device Manager > Load
Management > device load > Display ID" field.

Getting Started
To start using the Rack PDU:
1. Install the Rack PDU using the Rack Power Distribution Unit Installation Instructions that were
shipped with your Rack PDU.
2. Apply power and connect to your network. Follow the directions in the Rack Power Distribution
Unit Installation Instructions.
3. Establish network settings. (See “Establish Network Settings” on page 5.)
4. Begin using the Rack PDU by way of one of the following:
– “Web Interface” on page 52
– “Command Line Interface” on page 14
– “Rack PDU Front Panel” on page 9

Switched Rack PDU User Guide

4

Establish Network Settings
Note: Disregard the procedures described in this section if you have StruxureWare Data Center Expert
as part of your system. See the documentation for your StruxureWare Data Center Expert for more
information.
You must configure the following TCP/IP settings before the Rack PDU can operate on a network:
• IP address of the Rack PDU
• Subnet mask
• Default gateway
Note: If a default gateway is unavailable, use the IP address of a computer that is located on the
same subnet as the Rack PDU and that is usually running. The Rack PDU uses the default
gateway to test the network when traffic is very light.
Note: Do not use the loopback address (127.0.0.1) as the default gateway address for the Rack
PDU. It disables the card and requires you to reset TCP/IP settings to their defaults using a local
serial login.
See “Watchdog Features” on page 3 for more information about the watchdog role of the default
gateway.

TCP/IP configuration methods
Use one of the following methods to define the TCP/IP settings needed by the Rack PDU:
• “Device IP Configuration Wizard” on page 102
• “DHCP and BOOTP configuration” on page 5
• “Command Line Interface” on page 7

INI file utility
You can use the INI file export utility to export INI file settings from configured Rack PDUs to one or
more unconfigured Rack PDUs. For more information, see “Use an .ini File” on page 99.

DHCP and BOOTP configuration
The default TCP/IP configuration setting, DHCP, assumes that a properly configured DHCP server is
available to provide TCP/IP settings to Rack PDU. You can also configure the setting for BOOTP.
A user configuration (INI) file can function as a BOOTP or DHCP boot file. For more information, see
“Use an .ini File” on page 99.
If neither of these servers is available, see “Device IP Configuration Wizard” on page 102 or “Command
Line Interface” on page 7.
BOOTP. For the Rack PDU to use a BOOTP server to configure its TCP/IP settings, it must find a
properly configured RFC951-compliant BOOTP server.

In the BOOTPTAB file of the BOOTP server, enter the Rack PDU’s MAC address, IP address, subnet
mask, and default gateway, and, optionally, a bootup file name. Look for the MAC address on the bottom
of the Rack PDU or on the Quality Assurance slip included in the package.

5

Switched Rack PDU User Guide

When the Rack PDU reboots, the BOOTP server provides it with the TCP/IP settings.
• If you specified a bootup file name, the Rack PDU attempts to transfer that file from the BOOTP
server using TFTP or FTP. The Rack PDU assumes all settings specified in the bootup file.
• If you did not specify a bootup file name, you can configure the other settings of the Rack PDU
remotely through its “Web Interface” on page 52 or “Command Line Interface” on page 7; the
user name and password are both apc, by default. To create a bootup file, see your BOOTP server
documentation.
DHCP. You can use an RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for
the Rack PDU.

This section summarizes the Rack PDU’s communication with a DHCP server. For more detail about
how a DHCP server can configure the network settings for a Rack PDU, see “DHCP response options”
on page 82.
1. The Rack PDU sends out a DHCP request that uses the following to identify itself:
– A Vendor Class Identifier (APC by default)
– A Client Identifier (by default, the MAC address of the Rack PDU)
– A User Class Identifier (by default, the identification of the application firmware installed on
the Rack PDU)
– A Host Name (by default, apcXXYYZZ with XXYYZZ being the last six digits of the PDU).
This is known as DHCP Option 12.
2. A properly configured DHCP server responds with a DHCP offer that includes all the settings
that the Rack PDU needs for network communication. The DHCP offer also includes the Vendor
Specific Information option (DHCP option 43). The Rack PDU can be configured to ignore
DHCP offers that do not encapsulate the APC cookie in DHCP option 43 using the following
hexadecimal format. (The Rack PDU does not require this cookie by default.)
Option 43 = 01 04 31 41 50 43

Where:
– The first byte (01) is the code.
– The second byte (04) is the length.
– The remaining bytes (31 41 50 43) are the APC cookie.
See your DHCP server documentation to add code to the Vendor Specific Information option.
Note: By selecting the Require vendor specific cookie to accept DHCP Address check box
in the Web interface, you can require the DHCP server to provide an “APC” cookie, which
supplies information to the Rack PDU: Administration > Network>TCP/IP>ipv4 settings.

Switched Rack PDU User Guide

6

Command Line Interface
1. Log on to the command line interface. See “Log on to the Command Line Interface” on page 14.
2. Contact your network administrator to obtain the IP address, subnet mask, and default gateway
for the Rack PDU.
3. Use these three commands to configure network settings. (Text in italics indicates a variable.)
a. tcpip -i yourIPaddress
b. tcpip -s yourSubnetMask
c. tcpip -g yourDefaultGateway
For each variable, type a numeric value that has the format xxx.xxx.xxx.xxx.
For example, to set a system IP address of 156.205.14.141, type the following command
and press ENTER:
tcpip -i 156.205.14.141

4. Type exit. The Rack PDU restarts to apply the changes.

7

Switched Rack PDU User Guide

Recovering from a Lost Password
You can use a local computer (a computer that connects to the Rack PDU or other device through the
serial port) to access the command line interface.
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Connect the serial cable (APC part number 940-0144A) to the selected port on the computer and
to the Serial port at the Rack PDU.
3. Run a terminal program (such as HyperTerminal®) and configure the selected port for 9600 bps,
8 data bits, no parity, 1 stop bit, and no flow control.
4. Press ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to
display the User Name prompt, verify the following:
– The serial port is not in use by another application.
– The terminal settings are correct as specified in step 3.
– The correct cable is being used as specified in step 2.
5. Press the Reset button. The Status LED will flash alternately orange and green. Press the Reset
button a second time immediately while the LED is flashing to reset the user name and password
to their defaults temporarily.
6. Press ENTER, repeatedly if necessary, to display the User Name prompt again, then use the
default, apc, for the user name and password. (If you take longer than 30 seconds to log on after
the User Name prompt is re-displayed, you must repeat step 5 and log on again.)
7. At the command line interface, use the following commands to change the User Name and
Password settings, both of which are now apc:
user -an yourAdministratorName
user -ap yourAdministratorPassword

For example, to change the Administrator user name to Admin, type:
user -an Admin

8. Type quit or exit to log off, reconnect any serial cable you disconnected, and restart any service
you disabled.

Switched Rack PDU User Guide

8

Rack PDU Front Panel

Note: Your APC product is configured so the display backlight turns off after 10 minutes of inactivity.
The backlight can be turned on by depressing any button below the display.

Item

9

Function



Display

Shows information about the Rack PDU. In normal operation,
input voltage, current, and power refreshes every five seconds. To
reverse the text, press and hold simultaneously for five seconds
the Main Menu (), Scroll (), and Select () buttons.



Main Menu button

Press to view the Rack PDU electrical input.



Scroll button

Press once to display the menu. Press
additional times to highlight the desired
menu option.



Select button

With a menu option highlighted, press the
Select button to display Rack PDU
information. Network information is shown.

Switched Rack PDU User Guide

Item

Function



OK, Warning, Overload LED

Indicates the status of the Rack PDU load. See “Load indicator
LED” on page 13.



Temp/Humidity port

Port for connecting an APC Temperature Sensor (AP9335T) or an
APC Temperature/Humidity Sensor (AP9335TH).



In and Out ports

For use with the Network Port Sharing feature.



USB port

(For use with a flash drive for firmware upgrades - 5V @ 100ma.)



Outlet status LED

Illuminates green when the outlet is energized. (Each outlet has an
outlet LED.)



RJ-12 Serial Port

Port for connecting the Rack PDU to a terminal emulator program
for local access to the command line interface. Use the supplied
serial cable (APC part number 940-0144A).



10/100 Base-T Connector

Connects the Rack PDU to the network.



Network status LED

See “Network Status LED” on page 13.

10/100 LED

See “10/100 LED” on page 13.

Reset button

Resets the Rack PDU without affecting the outlet status.

!

Switched Rack PDU User Guide

10

Display Tree Example 1

11

Switched Rack PDU User Guide

Display Tree Example 2

Switched Rack PDU User Guide

12

Network Status LED
Condition

Description

Off

One of the following situations exists:
• The Rack PDU is not receiving input power.
• The Rack PDU is not operating properly. It may need to be repaired or
replaced. Contact APC Customer Support.

Solid Green

The Rack PDU has valid TCP/IP settings.

Solid Orange

A hardware failure has been detected in the Rack PDU. Contact APC
Customer Support.

Flashing Green

The Rack PDU does not have valid TCP/IP settings.

Flashing Orange

The Rack PDU is making BOOTP requests.

Alternately flashing green and
orange

If the LED is flashing slowly, the Rack PDU is making DHCP2 requests1.
If the LED is flashing rapidly, the Rack PDU is starting up.

1. If you do not use a BOOTP or DHCP server, see “Establish Network Settings” on page 5 to configure the
TCP/IP settings of the Rack PDU.
2. To use a DHCP server, see “TCP/IP and Communication Settings” on page 81.

10/100 LED
Condition

Description

Off

One or more of the following situations exists:
• The Rack PDU is not receiving input power.
• The cable that connects the Rack PDU to the network is disconnected or
defective
• The device that connects the Rack PDU to the network is turned off.
• The Rack PDU itself is not operating properly. It may need to be repaired or
replaced. Contact APC Customer Support.

Solid green

The Rack PDU is connected to a network operating at 10 Megabits per second
(Mbps).

Solid orange

The Rack PDU is connected to a network operating at 100 Mbps.

Flashing green

The Rack PDU is receiving or transmitting data packets at 10 Mbps.

Flashing orange

The Rack PDU is receiving or transmitting data packets at 100 Mbps.

Load indicator LED
The load indicator LED identifies overload and warning conditions for the Rack PDU.
Condition

Description

Solid Green

OK. No load alarms (warning or critical) are present.

Solid Yellow

Warning. At least one load warning alarm is present, but no critical alarms are
present.

Flashing Red

Overload. At least one load critical alarm is present.

13

Switched Rack PDU User Guide

Command Line Interface
About the Command Line Interface
You can use the command line interface to view the status of and configure and manage the Rack PDU
(and any connected Rack PDUs if using the Network Port Sharing Feature). In addition, the command
line interface enables you to create scripts for automated operation. An Administrator has full access to
the command line interface, a Device user and Outlet User have limited access, and a Read-Only user is
completely restricted.
You can configure all parameters of a Rack PDU (including those for which there are not specific CLI
commands) by using the CLI to transfer an INI file to the Rack PDU. The CLI uses XMODEM to
perform the transfer. However, you cannot read the current INI file through XMODEM.

Log on to the Command Line Interface
To access the command line interface, you can use either a local (serial) connection or a remote (Telnet
or SSH) connection with a computer on the same network as the Rack PDU.

Remote access to the command line interface
You can access the command line interface through Telnet or SSH. Telnet is enabled by default. Enabling
SSH disables Telnet.
To enable or disable these access methods, use the Web interface. On the Administration tab, select
Network on the top menu bar, and then the access option under Console on the left navigation menu.
Telnet for basic access. Telnet provides the basic security of authentication byuser name and
password, but not the high security benifits of encryption.

To use Telnet to access the command line interface:
1. From a computer that has access to the network on which the Rack PDU is installed, at a
command prompt, type telnet and the IP address for the Rack PDU (for example, telnet
139.225.6.133, when the Rack PDU uses the default Telnet port of 23), and press ENTER.
If the Rack PDU uses a non-default port number (from 5000 to 32768), you must include a colon
or a space, depending on your Telnet cliet, between the IP address (or DNS name) and the port
number. (These are commands for general usage. Some clients do not allow you to specify the
port as an argument and some types of Linux might want extra commands).
2. Enter the user name and password (by default, apc and apc for an Administrator, or device and
apc for a Device User).
If you cannot remember your user name or password, see “Recovering from a Lost Password” on
page 8.
SSH for high-security access. If you use the high security of SSL for the Web interface, use SSH for
access to the command line interface. SSH encrypts user names, passwords, and transmitted data. The
interface, user accounts, and user access rights are the same whether you access the command line
interface through SSH or Telnet, but to use SSH, you must first configure SSH and have an SSH client
program installed on your computer.

Switched Rack PDU User Guide

14

Local access to the command line interface
For local access, use a computer that connects to the Rack PDU through the serial port to access the
command line interface:
1. Select a serial port at the computer and disable any service that uses that port.
2. Connect the serial cable (APC part number 940-0144A) from the selected serial port on the
computer to the Serial port on the Rack PDU.
3. Run a terminal program (e.g., HyperTerminal) and configure the selected port for 9600 bps, 8
data bits, no parity, 1 stop bit, and no flow control.
4. Press ENTER. At the prompts, enter your user name and password.

About the Main Screen
Following is an example of the main screen, which is displayed when you log on to the command
line interface of a Rack PDU.
American Power Conversion
Network Management Card AOS vx.x.x
(c)Copyright 2012 All Rights Reserved RPDU 2g PPPP
vx.x.x
-------------------------------------------------------------------------Name
: Test Lab
Date : 10/30/2012
Contact : Don Adams
Time : 5:58:30
Location : Building 3
User : Administrator
Up Time : 0 Days, 21 Hours, 21 Minutes
Stat : P+ N4+ N6+ A+
APC>

• Two fields identify the APC operating system (AOS) and application (APP) firmware versions.
The application firmware name identifies the type of device that connects to the network. In the
example above, the application firmware for the Rack PDU is displayed.
Network Management Card AOS
RPDU 2g

vx.x.x
vx.x.x

• Three fields identify the system name, contact person, and location of the Rack PDU.
Name
: Test Lab
Contact : Don Adams
Location : Building 3

• An Up Time field reports how long the Rack PDU has been running since it was last turned on or
reset.
Up Time : 0 Days, 21 Hours, 21 Minutes

• Two fields identify when you logged in, by date and time.
Date : 10/30/2012
Time : 5:58:30

• The User field identifies whether you logged in through the Administrator or Device Manager
account. (The Read Only User account cannot access the command line interface.)
User : Administrator
15

Switched Rack PDU User Guide

• A Stat field reports the Rack PDU status.
Stat : P+ N4+ N6+ A+
The APC operating system (AOS) is functioning properly.

P+

IPv4
only

IPv6
only

IPv4 and
IPv6*

Description

N+

N+

N4+ N6+

The network is functioning properly.

N?

N6?

N4? N6?

A BOOTP request cycle is in progress.

N–

N6-

N4- N6-

The Rack PDU failed to connect to the network.

N!

N6!

N4! N6!

Another device is using the Rack PDU IP address.

* The N4 and N6 values can be different from one another: you could, for example, have
N4- N6+.

A+

The application is functioning properly.

A–

The application has a bad checksum.

A?

The application is initializing.

A!

The application is not compatible with the AOS.

Note: If P+ is not displayed, contact APC support staff.

Using the Command Line Interface
At the command line interface, use commands to configure the Rack PDU. To use a command, type the
command and press ENTER. Commands and arguments are valid in lowercase, uppercase, or mixed case.
Options are case-sensitive.
While using the command line interface, you can also do the following:
• Type ? and press ENTER to view a list of available commands, based on your account type.
• To obtain information about the purpose and syntax of a specified command, type the command, a
space, and ? or the word help. For example, to view RADIUS configuration options, type:
radius ?

or
radius help

• Press the UP arrow key to view the command that was entered most recently in the session. Use
the UP and DOWN arrow keys to scroll through a list of up to ten previous commands.
• Type at least one letter of a command and press the TAB key to scroll through a list of valid
commands that match the text you typed in the command line.
• Type exit or quit to close the connection to the command line interface.

Switched Rack PDU User Guide

16

Command Syntax
Item

Description

-

Options are preceded by a hyphen.

<>

Definitions of options are enclosed in angle brackets. For example:
-dp 

[]

If a command accepts multiple options or an option accepts mutually exclusive
arguments, the values may be enclosed in brackets.

|

A vertical line between items enclosed in brackets or angle brackets indicates that
the items are mutually exclusive. You must use one of the items.

Example of a command that supports multiple options:
user [-an ] [-ap ]

In this example, the user command accepts the option -an, which defines the Administrator user name,
and the option -ap, which defines the Administrator password. To change the Administrator user name
and password to XYZ:
1. Type the user command, one option, and the argument XYZ:
user -ap XYZ

2. After the first command succeeds, type the user command, the second option, and the argument
XYZ:
user -an XYZ

Example of a command that accepts mutually exclusive arguments for an option:
alarmcount -p [all | warning | critical]

In this example, the option -p accepts only three arguments: all, warning, or critical. For example, to
view the number of active critical alarms, type:
alarmcount -p critical

The command will fail if you type an argument that is not specified.

17

Switched Rack PDU User Guide

Command Response Codes
The command response codes enable scripted operations to detect error conditions reliably without
having to match error message text:
The CLI reports all command operations with the following format:
E [0-9] [0-9] [0-9] : Error message

Code

Message

E000

Success

E001

Successfully Issued

E002

Reboot required for change to
take effect

E100

Command failed

E101

Command not found

E102

Parameter Error

E103

Command Line Error

E104

User Level Denial

E105

Command Prefill

E106

Data Not Available

E107

Serial communication with the
Rack PDU has been lost

Switched Rack PDU User Guide

18

Network Management Card Command Descriptions
Access: Administrator, Device User, Outlet User
Description: View a list of all the CLI commands available to your account type. To view help text for
a specific command, type the command followed by a question mark.
Example: To view a list of options that are accepted by the alarmcount command, type:
alarmcount ?

about
Access: Administrator, Device User, Outlet User
Description: View hardware and firmware information. This information is useful in troubleshooting
and enables you to determine if updated firmware is available at the APC Web site.

alarmcount
Access: Administrator, Device User, Outlet User
Description:

Option

Arguments

Description

-p

all

View the number of active alarms reported by the Rack PDU. Information
about the alarms is provided in the event log.

warning

View the number of active warning alarms.

critical

View the number of active critical alarms.

Example: To view all active warning alarms, type:
alarmcount -p warning

appcli
Access: Administrator, Device User, Outlet User
Description: Access the Rack PDU Command Line Interface.

19

Switched Rack PDU User Guide

boot
Access: Administrator only
Description: Define how the Rack PDU will obtain its network settings, including the IP address,
subnet mask, and default gateway. Then configure the BOOTP or DHCP server settings.

Option

Argument

Description

-b


dhcp | bootp | manual Define how the TCP/IP settings will be configured when the Rack PDU turns
on, resets, or restarts. See “TCP/IP and Communication Settings” on page 81
for information about each boot mode setting.

-c

enable | disable

dhcp and dhcpBootp boot modes only. Enable or disable the requirement
that the DHCP server provide the APC cookie.

The default values for these three settings generally do not need to be changed:
-v : APC
-i : The MAC address of the Rack PDU, which uniquely identifies it on the network
-u : The name of the application firmware module

Example: To use a DHCP server to obtain network settings:

1. Type boot -b dhcp
2. Enable the requirement that the DHCP server provide the APC cookie:
boot -c enable

cd
Access: Administrator, Device User, Outlet User
Description: Navigate to a folder in the directory structure of the Rack PDU.
Example 1: To change to the ssh folder and confirm that an SSH security certificate was uploaded to
the Rack PDU:

1. Type cd ssh and press ENTER.
2. Type dir and press ENTER to list the files stored in the SSH folder.
Example 2: To return to the main directory folder, type:
cd ..

clrrst
Access: Administrator, Device User, Outlet User
Description: Clear reset reason.

Switched Rack PDU User Guide

20

console
Access: Administrator only
Description: Define whether users can access the command line interface using Telnet, which is
enabled by default, or Secure SHell (SSH), which provides protection by transmitting user names,
passwords, and data in encrypted form. You can change the Telnet or SSH port setting for additional
security. Alternately, disable network access to the command line interface.

Option

Argument

Description

-S

disable | telnet | ssh

Configure access to the command line interface, or use the disable
command to prevent access. Enabling SSH enables SCP and disables Telnet.

-pt



Define the Telnet port used to communicate with the Rack PDU (23 by
default).

-ps



Define the SSH port used to communicate with the Rack PDU (22 by
default).

-b

2400 | 9600 | 19200 |
38400

Configure the speed of the serial port connection (9600 bps by default).

Example 1: To enable SSH access to the command line interface, type:
console -S ssh
Example 2: To change the Telnet port to 5000, type:
console -pt 5000

21

Switched Rack PDU User Guide

date
Access: Administrator only
Definition: Configure the date used by the Rack PDU.

To configure an NTP server to define the date and time for the Rack PDU, see “Set the Date and Time”
on page 98.
Option

Argument

Description

-d

<“datestring”>

Set the current date. Use the date format specified by the date -f
command.

-t

<00:00:00>

Configure the current time, in hours, minutes, and seconds. Use the 24-hour
clock format.

-f

mm/dd/yy |
dd.mm.yyyy |
mmm-dd-yy |
dd-mmm-yy |
yyyy-mm-dd

Select the numerical format in which to display all dates in this user interface.
Each letter m (for month), d (for day), and y (for year) represents one digit.
Single-digit days and months are displayed with a leading zero.

-z


Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Language                        : en
XMP Toolkit                     : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27
Creator Tool                    : FrameMaker 11.0.1
Modify Date                     : 2012:10:05 14:57:57-05:00
Create Date                     : 2012:10:05 14:50:09Z
Metadata Date                   : 2012:10:05 14:57:57-05:00
Format                          : application/pdf
Title                           : untitled
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Document ID                     : uuid:9356bf45-8a25-4b20-8cf0-8489646d6ec8