Apc Mge Galaxy 9000 Users Manual

9000 to the manual 5f86bdca-5723-4170-985f-9fca29ca873a

2015-02-03

: Apc Apc-Mge-Galaxy-9000-Users-Manual-471087 apc-mge-galaxy-9000-users-manual-471087 apc pdf

Open the PDF directly: View PDF PDF.
Page Count: 62

DownloadApc Apc-Mge-Galaxy-9000-Users-Manual-  Apc-mge-galaxy-9000-users-manual
Open PDF In BrowserView PDF
MGETM GalaxyTM 9000
50, 60 Hz
800 - 900 kVA

User manual
Single-unit UPS
Modular UPS
Parallel UPS with SSC
Frequency converter
Static Switch Cubicle

34006452EN/AC

- Page 2

Contents
1. Introduction
1.1 System performance ................................................................................................................... 5
1.2 System description ...................................................................................................................... 5
1.3 Different types of MGETM GalaxyTM 9000 systems ................................................................. 6
1.4 Isolation and protection devices ................................................................................................. 8
UPS or converter cubicles (figure 8) ...............................................................................................................8
Static Switch Cubicle (figure 9)

.......................................................................................................................8

External maintenance bypass cubicle (figure 10) ............................................................................................9

1.5 Main operating modes .................................................................................................................. 9
Normal operation .............................................................................................................................................9
Operation with Mains 1 down (figure 12) .......................................................................................................10
Battery time ....................................................................................................................................................10
Operation with Mains 1 restored (figure 13) ..................................................................................................11
Installation with an engine generator set (figure 15)

...................................................................................12

Output voltage quality and continuity .............................................................................................................13

2. Description of MGETM GalaxyTM 9000 cubicles
2.1 Inverter cubicle .......................................................................................................................... 14
2.2 Static Switch Cubicle ................................................................................................................ 15
2.3 External maintenance bypass cubicle .................................................................................... 15

3. Control panel
3.1 Visible control panel .................................................................................................................. 17
3.2 Hidden control panel ................................................................................................................. 20

4. Start-up
4.1 System start-up ........................................................................................................................... 23
Single-unit or modular UPS ...........................................................................................................................23
Multi-bypass modular UPS ............................................................................................................................24
Modular UPS with external maintenance bypass ..........................................................................................25
Frequency converters ....................................................................................................................................26
Parallel UPS systems with a Static Switch Cubicle ........................................................................................27

4.2 Start-up of a unit ......................................................................................................................... 27
Start-up of a rectifier/charger .........................................................................................................................27
Start-up of an inverter ....................................................................................................................................27

5. Shutdown
5.1 Shutdown of a unit ...................................................................................................................... 28
Shutdown of an inverter .................................................................................................................................28
Shutdown of an rectifier/charger ....................................................................................................................29

5.2 System shutdown ....................................................................................................................... 29
Single-unit or single modular UPS .................................................................................................................29
Modular UPS with external maintenance bypass ..........................................................................................30
Multi-bypass modular UPS .............................................................................................................................30
Frequency converters (no Mains 2) ..............................................................................................................30
Parallel UPSs with SSC (with Mains 2) ..........................................................................................................31

5.3 Buzzer reset ................................................................................................................................ 31

6. Alarms
6.1 Maintenance bypass .................................................................................................................. 32

7. Environment information
7.1 Standard information Media Contacts 9 .................................................................................. 33
Signal reception .............................................................................................................................................33
Signal transmission ........................................................................................................................................33
34006452EN/AC

- Page 3

Contents
7.2 "LED" signalling box (optional) ..................................................................................................34
7.3 Additional information "Media Contacts 15" ..........................................................................34
Signal reception ............................................................................................................................................. 35
Signal transmission ....................................................................................................................................... 35

8. Maintenance
8.1 Maintenance configuration .........................................................................................................36
Single-unit or single modular UPS (figure 25) .............................................................................................. 36
Multi-bypass modular UPS (figure 26)

......................................................................................................... 36

Modular UPS with external maintenance bypass (figure 27) ........................................................................ 37
Frequency converter or parallel UPS with SSC (figure 28) ............................................................................ 38
Static Switch Cubicle (figure 29) ..................................................................................................................... 38

8.2 Battery maintenance ..................................................................................................................39
8.3 Autodiagnostics ..........................................................................................................................39
8.4 Visual check ................................................................................................................................39
8.5 Functional check ........................................................................................................................39
8.6 Training centres ...........................................................................................................................40

9. "Monitor" alphanumeric display
9.1 General ........................................................................................................................................41
Display ........................................................................................................................................................... 41

9.2 Control panel ...............................................................................................................................42
9.3 Lights 1 to 8 .................................................................................................................................43
9.4 Alarm display and buzzer reset .................................................................................................44
List of general alarms .................................................................................................................................... 44
List of secondary alarms ............................................................................................................................... 45

9.5 Measurement system .................................................................................................................50
9.6 Voltage measurements ...............................................................................................................51
9.7 Current measurements ..............................................................................................................52
9.8 Frequency and power measurements ......................................................................................53
9.9 Battery measurements ...............................................................................................................54
9.10 Inverter On/Off commands ......................................................................................................56
9.11 Language, display contrast and buzzer volume settings .....................................................57
9.12 Display system configuration ..................................................................................................58

10. Options
10.1 "LED" signalling box ................................................................................................................59
10.2 "Tele-Monitor" remote indications unit ..................................................................................59
10.3 "GTC link" communications system .......................................................................................59
10.4 "Vision" display ........................................................................................................................60
10.5 "Remote vision" display ..........................................................................................................60
10.6 Insulating and Mains 1, Mains 2 and load voltage matching transformer ...........................60
10.7 Double bridge rectifier-charger ...............................................................................................61
10.8 Battery "Temperature Monitor" ...............................................................................................61
10.9 Empty cubicles

34006452EN/AC

- Page 4

........................................................................................................................61

1. Introduction
1.1 System performance
A MGETM GalaxyTM 9000 uninterruptible power supply (UPS) delivers 3-phase power with the following characteristics:
– stable voltage (±0.5 % under steady state conditions and +/-5% under transient conditions for load step changes of 25
to 100 % or of 100 to 25 %);
– stable frequency (±0.05Hz without Mains 2);
– or frequency synchronized with Mains 2 to 50/60 Hz ±2 Hz (value may be configured in 0.25 Hz steps);
– free of micro-breaks and outages for the duration of the battery time (10, 15 or 30 minutes);
– less than 4 % distortion in all system configurations with linear loads;
– less than 5 % distortion for a 100 % non-linear load with a peak factor of up to 3.5.
The acoustic noise level of a MGETM GalaxyTM 9000 UPS is under 75 dBA.

Single-line diagram of the MGETM GalaxyTM 9000 system

B
maintenance
bypass
mains 2
(bypass input)

mains 1
(normal input)

emergency
bypass

isolation

isolation
and
protection

AC/DC
conversion

isolation
and
protection

load

DC/AC
conversion

isolation and
protection
battery
A

1.2 System description
– a rectifier-charger (RC) module converts 3-phase AC power from the Mains 1 supply into DC power for the normal inverter
input and float charges or recharges the batteries;
– a battery unit provides backup power for the inverter in the event of a voltage drop or a Mains 1 failure;
– an inverter module converts the DC power supplied by the rectifier-charger module or the battery unit into 3-phase AC
power for the load;
– an emergency bypass module ensures the instantaneous transfer of the load via the static switch to the Mains 2 bypass
line in the event of an inverter shutdown (initiated by the user or by a protective device) or a sudden overload;
– a maintenance bypass which isolates the UPS for maintenance and transfers the load without interrupting the supply of
power. The maintenance bypass is made up of three manual switches.
Note:
– the Mains 1 normal input and the Mains 2 bypass input have different functions and, depending on the installation, may be
protected differently upstream and/or come from different sources;
– frequency converters are available without backup batteries;
– the emergency bypass line and the maintenance bypass line do not exist in installations where the load frequency and the
Mains 2 frequency are different (for example in frequency converters);
– for reasons of redundancy and/or increased power, the rectifier-charger, inverter and battery modules (the UPS, part A in
the MGETM GalaxyTM 9000 schematic diagram above) may be arranged in parallel lines. In this case, an isolation function is
added to the output of each UPS for maintenance without disrupting the load.
In this type of system, the components of part B in the diagram are located in a separate cubicle referred to as the "Static
Switch Cubicle".
The system may also include:
– an isolating transformer on the Mains 2 line;
– a harmonics filter on the Mains 1 input;
– different remote control, indication and display systems;
– a double bridge rectifier-charger module.

34006452EN/AC

- Page 5

Introduction
1.3 Different types of MGE Galaxy 9000 systems
TM

TM

– Single-unit or modular UPS: (figure 1)

static switch

Q3BP
mains 2
rectifiercharger

inverter
load

mains 1
battery

Fig. 1
– Multi-bypass modular UPSs: (figure 2)
Note:
2 modular UPSs (identical ratings) can be parallel-connected in this way.

static switch

Q3BP
mains 2
rectifiercharger

inverter

mains 1
battery
load

static switch

Q3BP
mains 2
rectifiercharger

inverter

mains 1
battery

Fig. 2
– Modular UPSs with external maintenance bypass: (figure 3)
Note:
Up to 4 UPS (identical ratings) can be parallel-connected.

Q3BP

static switch
mains 2
rectifiercharger

inverter

mains 1
battery
load
static switch
mains 2
rectifiercharger

inverter

mains 1
battery

Fig. 3

34006452EN/AC

- Page 6

Q5N

Introduction

– Frequency converter with battery backup power: (figure 4)
rectifiercharger

inverter
load

mains 1
battery

Fig. 4
– Frequency converter without backup power: (figure 5)
rectifiercharger

inverter

mains 1

load

Fig. 5
– Frequency converters with backup power: (figure 6)
rectifiercharger

inverter

battery
rectifiercharger

inverter

mains 1

load
battery
rectifiercharger

inverter

battery

Fig. 6
– Parallel UPSs with SSC: (figure 7)
Note:
Up to 6 UPS (identical ratings) can be parallel-connected in this way.

Q3BP
mains 2
Static Switch Cubicle
rectifiercharger

inverter

battery
mains 1

rectifiercharger

inverter

load

battery

Fig. 7

34006452EN/AC

- Page 7

Introduction
1.4 Isolation and protection devices
UPS or converter cubicles (figure 8)
– Q1 (switch):
isolation from Mains ,
RC start-up;
– QF1 (circuit breaker):
battery protection and isolation;
– Q5N (switch):
isolation of the inverter, frequency converter or static switch module from the load;
– Q4S (switch):
isolation of the static switch from Mains 2;
– Q3BP (switch):
bypass switch for maintenance;
– FU1-2-3 (fuses):
protection of the RC from Mains 1;
– FU5-6-7 (fuses):
protection of the inverter from the load.
Note:
– switches Q4S and Q3BP do not exist on frequency converters,
– circuit breaker QF1 does not exist on frequency converters without a battery.

Example of a single-unit UPS or single modular UPS
Q3BP

Q4S

mains 2

mains 1

Q1

rectifiercharger

FU1-2-3

static switch

inverter

Q5N

load

FU5-6-7

QF1

battery

Fig. 8

Static Switch Cubicle (figure 9)
– Q4S (switch) :
isolation of the static switch (and mechanical contactor K2S) from Mains 2;
– Q3BP (switch) :
bypass switch for maintenance;
– Q5N (switch) :
isolation of the load from the parallel UPSs;
– Q1 (fuse switch) :
protection of the cubicle control electronics from the parallel-connected inverter outputs;
– Q2 (fuse switch) :
protection of the cubicle control electronics from Mains 2.
Q3BP

Q4S

mains 2

parallel
UPSs

Q5N
Q2
Q1

Fig. 9

34006452EN/AC

- Page 8

static switch

control
electronics

load

Introduction
External maintenance bypass cubicle

(figure 10)

– Q3BP (switch) :
bypass switch for maintenance;
– Q5N (switch) :
isolation of the load from the parallel-connected UPSs.
Q3BP

maintenance
bypass line

Q5N

parallel
modular UPSs

load

Fig. 10

1.5 Main operating modes
Normal operation
Mains 1 power is available: (see figure 11).
The green "load protected" light 5 on the control panel is on.
!

!

I

+–

O

5
légend :

off

on

The power necessary for the load is provided by Mains 1 through the rectifier-charger and the inverter.
The rectifier-charger also supplies the power to float charge and recharge the battery (1).
The rectifier-charger output voltage (DC) is regulated for the different battery types and charging modes:
– vented lead-acid or Ni/Cd batteries: two different voltages, one for float charging and one for recharging;
– sealed lead-acid batteries: a single voltage for both charge functions.
The voltages depend on the number of battery cells and the battery manufacturer. They can be factory set and are adjustable
by the after-sales support technicians.
An optional electronic board may be used to continuously measure the battery temperature and automatically adjust the
voltages.
Parallel UPS systems:
the power drawn by the load is equally shared between the different UPSs.
(1) Except for frequency converters without a battery
static switch
mains 2
rectifiercharger

inverter

mains 1

load

battery

Fig. 11

34006452EN/AC

- Page 9

Introduction
Operation with Mains 1 down

(figure 12)

In the event of a Mains 1 failure or Mains 1 voltage outside specified tolerance of –10 % in amplitude (–15 % optionally), the
rectifier-charger stops and the battery supplies the necessary backup power to the load via the inverter. The battery, floatconnected between the rectifier-charger and the inverter, discharges during this operating mode.
The green "load protected" light 5 on the control panel is on.
The user is warned of battery operation by a buzzer and the orange "load on battery" light 4 on the control panel.
beep...beep...

!

!

I

+–

4

O

5

This information is also available via volt-free changeover contacts for remote control devices.
In this case, there is a 30 seconds delay.
Note:
In the event of a Mains 1 failure, frequency converters without a battery shut down and the load is no longer supplied.

static switch
mains 2
rectifiercharger

inverter

mains 1

load

battery

Fig. 12

Battery time
The available battery time during a Mains 1 outage depends on the:
– rated capacity of the battery;
– power consumed by the load;
– temperature of the battery;
– age of the battery.
The specified battery time corresponds to a minimum duration at full rated load.
The actual backup time can therefore be greater if the system operates below its full rated load during the Mains 1 outage.
Operation on battery power can be extended beyond the specified time by reducing the load power consumption
(by disconnecting non-critical loads).
A "low battery shutdown" warning signal is sent via volt-free changeover contacts for remote control devices when the battery
voltage reaches a level slightly above the minimum level. This signal warns the user of the imminent end of battery power.
On the device itself, the buzzer beeps increasingly rapidly and loudly.
Battery power stops when the voltage supplied by the battery reaches the voltage minimum (340 V). This results in inverter
shutdown and transfer of the load without interruption to Mains 2. The red "load not protected" light 2 on the control
panel is on.
beep...beep...

!

!

+–

I

O

2

If Mains 2 also fails, the load is no longer supplied. Normally, the inverter shuts down when the time on the battery power
exceeds three times the specified backup time.
Note:
As an optional function (battery time estimator), the "low battery shutdown" warning signal can be sent with an adjustable time
delay prior to the effective end of battery power.

34006452EN/AC

- Page 10

Introduction
Operation with Mains 1 restored

(figure 13)

When Mains 1 power is restored or its voltage returns to within specified tolerances, the system automatically returns to its
normal operating mode described above (on the condition it did not reach the end of battery power).
If the end of battery power was reached (with the resulting inverter shutdown), the RC restarts automatically, but the inverter
must be restarted manually, either locally or remotely in systems equipped with a remote-control unit.
The rectifier-charger recharges the battery which was discharged during the Mains outage.
Note:
In frequency converters without battery power, the return of Mains 1 power results in the automatic restart of the RC and the
inverter.

Battery charge cycle
static switch
mains 2
rectifiercharger

inverter

mains 1

load

battery

Fig. 13
The battery charge cycle takes place in two steps (see figure 14):
– step 1: the battery is recharged at a constant current limited to 0.1C10 (i.e. 1/10th of the battery capacity specified
for a 10 hour discharge). The DC voltage increases with the battery charge until the charge level is reached;
– step 2: the battery is recharged at constant voltage equal to the charge level (maximum value 463 V).
The charging current gradually decreases until reaching a specified low value (floating current).
For vented lead-acid batteries, the rectifier-charger supplies the charging voltage for 0 to 255 hours (parameter defined by
the after-sales support department) and then the floating voltage. For sealed lead-acid batteries, the charging and floating
voltages are the same.
Note:
If the Mains 1 failure is shorter than 0 to 255 seconds (parameter defined by the after-sales support department), the charger
does not initiate a complete charge cycle but automatically supplies the floating voltage.
U/I

voltage

U charge/floating
(sealed batteries)
U "floating"
(vented batteries)

0.1 C10
current
current
limiting

constant voltage
decreasing current

t

Fig. 14

34006452EN/AC

- Page 11

Introduction
Installation with an engine generator set

(figure 15)

If a stand-by generator is included in the installation, it is generally started automatically in the event of a Mains failure and
connected to the main low voltage switchboard.
It is disconnected when Mains power is restored.
With such a system, the required battery time may be reduced to the time necessary for starting and bringing on line the
stand-by generator.
The battery supplies power to the inverter during the transfers: Mains - generator and generator - Mains.
The transfer sequences described: Mains - battery - generator and generator - battery - Mains are fully automatic.
They in no way affect the load and require no manual operation by the user.
Note:
To avoid load surges on the generator, the rectifier/charger is started with a 10 second maximum current consumption walk-in.

Example of an installation with an engine generator set
generator

main LV
switchboard

Galaxy
mains 2

G

mains 1

HV
network

Fig. 15

UPS shutdown or overload (systems with a static switch module) (figure 16)
Single-unit UPSs, modular UPSs or UPSs with an SSC:
– in the event of a UPS shutdown (initiated by the user or by an internal protective device), the load is automatically
transferred to the Mains 2 bypass line. If transfer conditions are correct, transfer takes place instantly, without interruption to
the load.
Note:
Transfer conditions are not correct when Mains 2 characteristics are outside tolerances (voltage: ±10 %; frequency as per
personalization; phase sync with inverter ±3°);
– in the event of a major transient overload (greater than 160 % of the full load), immediate transfer takes place as above,
without interruption to the load.
When the overload disappears, the load is automatically returned to the inverter depending on the configured value of the
re-transfer counter: no return to inverter, or 1 to 255 (personalized value) overloads accepted before the load is permanently
transferred to Mains 2. This operating mode allows start-up of load devices causing high inrush currents.
This system requires correct transfer conditions. If the conditions are not correct, the inverter will current limit to 150 % of its
rated current for 1 second before stopping;
– in the event of a small but extended overload (i.e. a continuous level of power exceeding the full rated load), the inverter
will continue to supply power for a period depending on the magnitude of the overload (10 minutes for a 125 % overload,
1 minute for a 150 % overload). See figure 17 (Overload curve);
– in all three of the above cases, the inverter shutsdown and supplies the load via Mains 2 with the following information
on the control panel:
– green "load protected" light 5 off,
– buzzer 1 on,
– red "load not protected" light 2 on.
beep...beep...

!
1

!

I

+–

O

2

static switch
mains 2
rectifiercharger

inverter

mains 1

load

battery

Fig. 16
34006452EN/AC

- Page 12

Introduction
Frequency converters without redundancy
– in the event of a shutdown, the load is no longer supplied with power;
– in the event of a major transient overload (greater than 160 % of the rated load), the inverters will current limit to 160 %
of their rated current for 1 second before stopping;
– in the event of a small but extended overload (i.e. a continuous level of power exceeding the full rated load), the inverters
will continue to supply power for a period depending on the magnitude of the overload (10 minutes for a 125 % overload,
1 minute for a 150 % overload, see figure 17), and then stop;
– in all three of the above cases, inverter shutdown results in the following on the control panel of the concerned unit:
– green "load protected" light 5 off,
– buzzer 1 on,
– red "load not protected" light 2 on.

Frequency converters with redundancy
– the shutdown of one unit is of no consequence for the load. The other lines each take up an equal amount of load power
and the load continues to be supplied normally;
Inverter shutdown results in the following on the control panel of the concerned unit:
– green "load protected" light 5 off,
– buzzer 1 on,
– red "load not protected" light 2 on.
– in the event of an overload, the system only loses its redundancy as long as the overload is less than the total rated power
of the functioning units. If the overload is greater, the operating mode is that previously described for systems without
redundancy.

Overload curve
I
1,5 In

1,35 In
1,25 In

1,10 In
1,05 In
In

1

2

3

4

5

6

7

8

9 10

30

120 t (minutes)

Fig. 17

Output voltage quality and continuity
The output voltage is stable in amplitude and frequency and is free of interruptions or transients outside specified tolerances,
irrespective of Mains 1 or load disturbances (outages, load step changes, etc.).

Steady state voltage regulation:
For stable or slowly varying load conditions, the inverter output voltage is regulated to within ±0.5 % in amplitude.
The frequency of the output voltage can theoretically be regulated to within 0.1 % of the rated value, however the output
frequency range may be intentionally extended to a maximum of ±2 Hz so that the inverter can remain synchronized with
Mains 2 and its inherent frequency fluctuations, thus enabling transfer of the load to the bypass line at any time.

Note:
The output frequency range can be personalized and if necessary modified on the customer site by a qualified support
technician from ±0.25 Hz to ±2 Hz in 0.25 Hz steps.
When the Mains 2 voltage moves outside this frequency range, the inverter is desynchronized and operates in "free running"
mode, with the output frequency regulated to a high level of accuracy by a quartz oscillator.
When the Mains 2 frequency returns to within the specified tolerances, the inverter is gradually re-synchronized to the bypass
line at a rate of 0.5 Hz to 2 Hz/s (as per the value personalized by the after-sales support department), thus avoiding exposing
the load to sudden frequency variations.

Transient voltage regulation:
The inverter output voltage is not notably affected by instantaneous major variations in load characteristics.
This is due to the PWM (Pulse Width Modulation) chopping technique and the microprocessor-based regulation system that
instantly compensates for any variation. In particular, the inverter output voltage remains within ±5 % of the rated voltage for
load step changes of 25 to 100 % or of 100 to 25 %.
34006452EN/AC

- Page 13

2. Description of MGETM GalaxyTM 9000 cubicles
2.1 Inverter cubicle
The rated outputs for MGETM GalaxyTM 9000 UPS’s (without parallel connection) or frequency converters
are 800, 900 kVA.
Legend for figure 18
1 - rectifier-charger (RC) module
2 - inverter stack modules
3 - rack for electronic control boards
4 - static switch module (Single-unit or modular UPS)
4' - output static switch module (modular UPS, frequency converter or parallel UPS with SSC)
5 - RC input fuses FU1-2-3
6 - Mains 1 input switch Q1
7 - protection fuses FU8 for the Mains 2 resistance/capacitance voltage surge protection network
8 - Mains 2 input switch Q4S (Single-unit or modular UPS)
9 - maintenance bypass switch Q3BP (Single-unit or modular UPS)
10 - output switch Q5N
11 - inverter output fuses FU 5-6-7
12 - "Media Contacts 9" remote indications board
13 - additional "Media Contacts 15" remote indications board (optional).

UPS or frequency converter
front view, doors open, protective covers removed

2

1

2

2

2

4'

2

2

3
5

11
12 13
7

6
4

Fig. 18

34006452EN/AC

- Page 14

8

9

10

Description of MGETM GalaxyTM 9000 cubicles
2.2 Static Switch Cubicle
Static Switch Cubicles are rated 500, 800, 1200 and 2000 kVA. Figure 19 presents the layout of components in these cubicles.

Legend for figure 19:

front view, doors open, protective covers removed

5

6

7

2

5
8

9

10
11

3

5

2

7

3

8

9

6

4

4
11

500 or 800kVA cubicle

10

1200kVA cubicle

2 - Mains 2 input switch Q4S,
3 - maintenance bypass switch Q3BP,
4 - output switch Q5N,
5 - static switch module,
6 - electronic control boards for the backup
function,
7 - protection fuses FU1 for the Mains 2
resistance/capacitance voltage surge
protection network,
8 - fuse switch Q1 (protection of the control
electronics power supply against Mains 1),
9 - fuse switch Q2 (protection of the control
electronics power supply against Mains 2),
10 - "Media Contacts 9" remote indications
board,
11 - additional "Media Contacts 15" remote
indications board (optional).

2

5
7
8
6

9

3

10
11

4

2000kVA cubicle

Fig. 19

2.3 External maintenance bypass cubicle
Legend for figure 20:
1 - connection of auxiliary wires to indicate the positions of switches Q5N and Q3BP,
2 - maintenance bypass switch Q3BP,
3 - output switch Q5N.

2
1
3

1200kVA cubicle

Fig. 20

34006452EN/AC

- Page 15

3. Control panel
MGETM GalaxyTM 9000 control panels (see figure 21) are made up of:
– a visible panel with the basic controls and indications required to check the general status of the system;
– a hidden panel with more detailed indications and more sophisticated control functions including an autodiagnostic system.
Note:
The information on the Mains 2 provided below does not concern frequency converters. Information on batteries does not
concern frequency converters without batteries.

MGETM GalaxyTM 9000 control panel

visible
panel

125 kVA120%
0 Hour

XY 6000
GALA IQ
SALLE

50 Min.
100%

80%

50%

0
Load

100%

50%

400 kVA

protected

Available

Backup

Time

Q5N

Home

Load

0
level

Load
nt
equipme

Alarms
Q1
Online
Trend

Monitor

Statistics

cover

Fig. 21

34006452EN/AC

- Page 16

Normal

AC

Rectifier
Q4S

Battery
Inverter
Bypass
Output
Set up

hidden
panel

QF1

Bypass

AC

15:24:32
Q3BP

30/05/200

5

Control panel
3.1 Visible control panel
Located in the upper left part of the cubicle front, the visible panel is designed to provide an easy and rapid overview of system
status (see figures 22 and 23).
Interpretation of symbols is very simple and requires no particular training.
The information concerns only the cubicle on which the panel is located.
The panel indicates:
– normal operation (load protected);
– abnormal situations (operating problem);
– dangerous situations (load not protected);
– operation with load on battery power.
The control panel on the Static Switch Cubicle provides important information for the load:
– normal operation (load protected and supplied by the UPSs);
– abnormal situations (system malfunction);
– dangerous situations (load not protected).

Visible control panel (Inverter or frequency converter cubicle)

1

!

!

+–

2

3

4

O

I

5

6

7

Fig. 22

Legend for figure 22:
1 - buzzer,
2 - "load not protected" light
3 - "operating problem" light
4 - "load on battery" light
5 - "load protected" light
6 - "inverter on" button
7 - "inverter off" button

Visible control panel (Static Switch Cubicle)

1

!

!

2

3

5

Legend for figure 23:
1 - buzzer,
2 - "load not protected" light
3 - "operating problem" light
5 - "load protected" light

Fig. 23

34006452EN/AC

- Page 17

Control panel
Buzzer 1
beep...beep...

!

!

+–

I

O

1
The buzzer sounds in the following situations:
– load supplied by Mains 2;
– load on battery;
– operating problems.
It beeps at a low decibel level and slow rate for minor problems and when the load is supplied from battery power.
When the "low battery shutdown imminent" warning is received, the beeps increase in decibel level and rate.
Finally, if the inverter shuts down, the beep is loud and continuous. A buzzer reset button is located on the hidden control
panel. If the buzzer is reset, a higher level alarm will set it on again.

"Load not protected" light
!

!

+–

I

O

2
This red light 2 signals that:
– the load is supplied by Mains 2 following inverter shutdown (initiated by the user or by a protective device or a sudden
overload) or the opening of the inverter output switch Q5N;
– battery circuit breaker QF1 has opened, thus making battery power unavailable.
Note:
In a parallel system, this light concerns only the specific UPS. The load may still be protected by the other lines.

"Operating problem" light
!

!

+–

I

O

3
This orange light 3 signals an operating problem or an environment fault, however the load is still supplied by the inverter.
– operating problems:
static switch ventilation fault,
static switch control system fault;
– environment faults:
battery temperature outside tolerances,
overload greater than 5 %;
– Mains 2 up but with voltage, frequency or phase characteristics outside tolerances with regards to the inverter.

"Battery operation" light
!

!

+–

I

O

4
This blinking orange light 4 signals that the load is on battery power following:
– a Mains 1 outage or voltage drop;
– insufficient power on Mains 1, for example power supplied by an engine generator set requiring additional battery power;
– battery problem.

34006452EN/AC

- Page 18

Control panel
"Load protected" light
!

!

I

+–

O

5
This green light 5 signals that the load is supplied by the inverter and that the specified battery time is available in the event
of a Mains 1 outage. In short, it signals that the system is operating normally.
Note:
In parallel systems, this light concerns only the specific UPS.
The load may not be protected if it depends on the other lines. It is necessary to take into account all the "load protected"
lights 5 for the different system lines or the light on the control panel of the Static Switch Cubicle, if it exists.

"Inverter on" button
!

!

I

+–

O

6
This green button 6 is used to locally start the inverter. When it is pushed, the green "load protected" light 5 blinks for
3 seconds, indicating that the start-up order has been received. When the inverter has synchronized with Mains 2, it supplies
the load and the green "load protected" light 5 remains on. The load is supplied by the UPS and the system is functioning
normally. If the transfer to Mains 2 conditions are not correct (Mains 2 voltage, frequency or phase conditions outside
tolerances), the inverter will not start and the system awaits a special order (see the "Hidden control panel" section).
Note:
– for modular UPSs with external maintenance bypass or parallel UPSs with SSC, transfer of the load to the inverters takes
place only when the number of operating lines required to supply the load has been reached;
– for frequency converters, inverter start-up must take place with the load off or drawing a quantity of power equal to or less
than that supplied by a single UPS.

"Inverter off" button
!

!

+–

O

I

7
This gray button 7 turns the inverter off.
– press the "inverter off" button 7 for 3 seconds;
– if the transfer to Mains 2 conditions are correct:
– the load is transferred without interrupting to Mains 2,
– the inverter shuts down,
– the green "load protected" light 5 goes off and the red "load not protected" light 2 goes on.
– if the transfer to Mains 2 conditions are not correct, the button produces no effect. A special function on the hidden panel
may be used to force the transfer.
Caution:
If the transfer is forced, the load will be subjected to a 0.8 second interruption in the supply of power.
Note:
– for Modular UPSs or parallel UPSs with SSC, the shutdown of an inverter may or may not result in the transfer of the load
to Mains 2, depending on redundancy conditions;
– if the transfer to Mains 2 conditions are not correct or if the system does not have a Mains 2, the shutdown of a single
inverter will result in the shutdown of the entire system if there is no redundancy.

34006452EN/AC

- Page 19

Control panel
3.2 Hidden control panel
The hidden panel, located behind the hinged cover, offers the following indications and control functions:
– environment faults;
– general faults in system modules;
– special control buttons (see figure 24).
This panel is identical for all types of cubicles, however, the controls or indications 8 that do not concern a given cubicle
are not activated.

Hidden control panel
(cellules onduleur et "Normal-secours")
8

A B C D E F G H I J K L M N
fault

9

10

1

11

12

2

13

3

14

15

4

16

5

17

Fig. 24

Clear fault log
This button 10 clears the alarms stored in memory. The memory may not be cleared until the cause of the alarms
has ceased.

Buzzer reset
This button 11 stops the buzzer. A new fault starts the buzzer again.

Battery charge cycle
This button 12 starts a battery charge cycle (vented lead-acid batteries only). The cycle duration may be programmed
(default value is 24 hours). Then the RC automatically shifts to "floating" mode.

Return to float charge
This button 13 can be used during a charge cycle to force the RC to return to "floating" mode.

Security button
This button 14 avoids inadvertent operation of the remaining three control buttons:
– Mains 2 synchronization or desynchronization;
– forced transfer to inverter with load interruption;
– forced inverter shutdown with load interruption;
When pressing one of the above three buttons, the security button must also be pressed at the same time.

Mains 2 synchronization or desynchronization
This button 15 desynchronizes or resynchronizes the inverter output frequency with that of Mains 2.
Note:
– for parallel-connected modular UPSs, this function must be carried out on all the UPSs.

34006452EN/AC

- Page 20

Control panel
Forced transfer to inverter with load interruption
This button 16 transfers the load to the inverter. If the transfer conditions (Mains 2 characteristics outside tolerances) are
not correct, the transfer will result in a 0.8 second interruption in the supply of power to the load.
Note:
– for parallel-connected modular UPSs, forced transfer of the load will not take place if the number of operating UPSs
required by the load is greater than one;
– for parallel UPSs with centralised SSC, this function is available only on the SSC.

Forced inverter shutdown with load interruption
This button 17 :
– transfers the load to Mains 2;
– shuts down the inverter.
It may be used if the transfer conditions (Mains 2 characteristics outside tolerances) are not correct, in which case the "inverter
off" button 7 on the visible control panel produces no effect;
– is disabled on the SSC.

Light A - emergency shutdown
This red light signals that the remote "emergency shutdown" button was pressed (external information received and stored
in memory).

Light B - rectifier-charger on
This green light indicates that the rectifier-charger is on.

Light C - rectifier-charger fault
This red light is an alarm stored in memory signaling a rectifier-charger fault. It can signify one or several of the following faults:
– input switch Q1 open;
– RC input protection fuse (FU1-2-3) blown;
– RC internal over-temperature;
– battery charge over-current;
– battery over-voltage;
– RC electronic control board faulty, not calibrated or not personalized;
– power supply board fault.

Light D - Mains 1 outside tolerances
This yellow light signals that the Mains 1 voltage and/or frequency characteristics are outside tolerances.

Light E - battery room ventilation fault and/or harmonics filter temperature outside tolerances
This yellow light is an alarm stored in memory signaling a battery room ventilation fault (external information that must be
supplied from the room).
If the installation includes a harmonics filter, this light will also signal an overtemperature of the filter’s inductor (information
supplied).

Light F - battery temperature outside tolerances
This yellow light signals that the battery temperature is outside tolerances (external information supplied by special board
("Temperature Monitor" option).

Light G - battery charging
This yellow light signals that the battery is being recharged (vented batteries only). This light is deactivated in systems with
sealed lead-acid batteries.

34006452EN/AC

- Page 21

Control panel
Light H - inverter fault
This red light is an alarm stored in memory signaling an inverter fault. It can signify one or several of the following faults:
– inverter shutdown due to inverter output voltage outside tolerances;
– inverter output protection fuse (FU5-6-7) blown;
– inverter stack subassembly protection fuse blown (parallel systems);
– inverter leg fault;
– inverter output transformer over-temperature;
– inverter leg over-temperature;
– phase or output voltage fault (parallel systems only);
– internal clock fault;
– inverter control board faulty, not calibrated or not personalized;
– power supply board fault.

Light I - battery discharged
This yellow light signals that the battery has reached its minimum voltage level, resulting in inverter shutdown.

Light J - inverter desynchronized with Mains 2
This light signals that the inverter output frequency has been voluntarily desynchronized with that of Mains 2.

Light K - transfer to inverter function fault
This red light is an alarm stored in memory signaling a fault in the systems for load transfer from Mains 2 to the inverter.
It can signify one or several of the following faults:
– inverter output switch K3N fault;
– parallel-connection relay fault (parallel systems only);
– static switch internal over-temperature;
– static switch ventilation fault;
– static switch power supply fault;
– transfer function control board fault;
– inverter control board not calibrated or not personalized;
– power supply board fault.

Light L - overload
This yellow light is an alarm signaling one or several of the following faults:
– inverter stack current more than 5 % above rated current;
– inverter output current more than 5 % above rated current;
– Mains 2 line current more than 5 % above rated current;
– inverter shutdown due to current limiting of output current.

Light M - Mains 2 outside tolerances
This yellow light signals that the Mains 2 voltage or frequency characteristics are outside tolerances.

Light N - maintenance position
This yellow light signals that devices QF1, Q4S, Q5N and Q3BP are set to the maintenance configuration. The UPS system
is not available for load protection.

Test connector
This 9-pin connector is reserved for after-sales support technicians.
It is used for connection to a microcomputer for:
– system calibration;
– personalization;
– computer-aided diagnostics.

34006452EN/AC

- Page 22

4. Start-up
4.1 System start-up
Single-unit or modular UPS
Proceed in the following order:
– close the upstream switches supplying Mains 1 and 2 power (on the LV switchboard);
– close Mains 1 input switch Q1.
The system powers up:
Q1

Q4S

Q3BP

Q5N

OFF ON

OFF
(0)

ON
(I)

OFF
(0)

(0)

(I)

– red "load not protected" light 2 on the control panel goes on,
– the rectifier/chargers automatically starts;
– close Mains 2 input Q4S:
Q1

Q4S

Q3BP

Q5N

ON
(I)

OFF ON

ON
(I)

OFF
(0)

(0)

(I)

– close inverter output switch Q5N:
Q1

Q4S

Q3BP

Q5N

ON
(I)

ON
(I)

ON
(I)

OFF ON
(0)

(I)

– close battery circuit breaker QF1:
QF1
OFF ON
(0)

(I)

– open maintenance bypass switch Q3BP:
Q1

Q4S

Q3BP

Q5N

ON
(I)

ON
(I)

ON OFF

ON
(I)

(I)

(0)

– press the inverter on button 6 on the control panel:
!

!

I

+–

O

6

green "load protected" light 5 blinks for 3 seconds,
the inverter starts and if transfer to Mains 2 conditions are correct, the load is supplied by the inverter,
red "load not protected" light 2 goes off,
green "load protected" light 5 remains on, without blinking.

34006452EN/AC

- Page 23

Start-up
Multi-bypass modular UPS
Proceed in the following order:
– check that switches Q1, Q4S, Q5N and QF1 on the UPSs are open and that switches Q3BP are closed, otherwise set them
to the required position;
– close the upstream switches (on the low-voltage switchboard) supplying power to the Mains 1 and Mains 2 inputs
on the UPSs, the load is supplied with power;
– close the Mains 1 input switch Q1 on the UPSs to supply them with power:
Q1

Q4S

Q3BP

Q5N

OFF ON

OFF
(0)

ON
(I)

OFF
(0)

(0)

(I)

– red "load not protected" light 2 on the control panels of the UPSs goes on:
!

!

I

+–

O

2

– the rectifier/chargers automatically start;
– close the Mains 2 input switch Q4S on the UPSs:
Q1

Q4S

Q3BP

Q5N

ON
(I)

OFF ON

ON
(I)

OFF
(0)

(0)

(I)

– close inverter output switch Q5N on the UPSs:
Q1

Q4S

Q3BP

Q5N

ON
(I)

ON
(I)

ON
(I)

OFF ON
(0)

(I)

– close battery circuit breaker QF1 on the UPSs:
QF1
OFF ON
(0)

(I)

– open maintenance bypass switch Q3BP on the UPSs:
Q1

Q4S

Q3BP

Q5N

ON
(I)

ON
(I)

ON OFF

ON
(I)

(I)

(0)

– the load is now supplied by the Mains 2 input via the static switches of the UPSs.
– press the "inverter on" button 6 on the control panel of each UPSs:
!

!

I

+–

O

6

green "load protected" light 5 flashes for three seconds,
the inverter starts and, if transfer conditions with the Mains 2 input are correct, the load is transferred to the inverter,
red "load not protected" light 2 goes off,
green "load protected" light 5 on the control panel goes on.

34006452EN/AC

- Page 24

Start-up
Galaxy UPS 1

Q3BP

Q4S

static switch

mains 2

Q1

rectifiercharger

inverter

mains 1

Q5N

QF1

battery

Galaxy UPS 2

load
Q3BP

Q4S

static switch

mains 2

Q1

mains 1

rectifiercharger

inverter

Q5N

QF1

battery

Modular UPS with external maintenance bypass
Proceed in the following order:
– check that all lines supplying the load are off or that the load is disconnected;
– in the maintenance bypass cubicle, open output switch Q5N, then close bypass switch Q3BP;
– close the upstream switch (on the low-voltage switchboard) supplying power to the Mains 1 inputs on the UPSs;
– close the Mains 1 input switch Q1 on the UPSs to supply them with power:
Q1

Q4S

Q5N

OFF ON

OFF
(0)

OFF
(0)

(0)

(I)

– the rectifier/chargers automatically start;
– red "load not protected" light 2 on the control panels of the UPSs goes on:
!

!

I

+–

O

2

– close battery circuit breaker QF1 on the UPSs:
QF1
OFF ON
(0)

(I)

– close the upstream switches (on the low-voltage switchboard) supplying power to the Mains 2 inputs on the UPSs, then
close the Mains 2 input switch Q4S on the UPSs:
Q1

Q4S

Q5N

ON
(I)

OFF ON

OFF
(0)

(0)

(I)

34006452EN/AC

- Page 25

Start-up
– close inverter output switch Q5N on the UPSs:
Q1

Q4S

Q5N

ON
(I)

ON
(I)

OFF ON
(0)

(I)

– close output switch Q5N in the maintenance bypass cubicle;
– open bypass switch Q3BP in the maintenance bypass cubicle;
– press the "inverter on" button 6 on the control panel of a UPS:
!

!

I

+–

O

6

green "load protected" light 5 flashes for three seconds,
the inverter starts and waits for the start of the other units;
– proceed in the same manner for each unit. When the number of running units is sufficient, the inverter output switches close
and the load is supplied by the inverters:
red "load not protected" light 2 goes off,
green "load protected" light 5 on the control panel goes on.

Frequency converters
Proceed in the following order:
– check that all lines supplying the load are off or that the load is disconnected;
– close the upstream switch supplying Mains 1 power (on the LV switchboard);
– close Mains 1 input switch Q1.
The system powers up:
Q1

Q5N

OFF ON

OFF
(0)

(0)

(I)

red "load not protected" light 2 on the control panel goes on,
the rectifier-charger automatically starts;
– close battery circuit breaker QF1 (systems equipped with a battery);
QF1
OFF ON
(0)

(I)

– close inverter output switch Q5N:
Q1

Q5N

ON
(I)

OFF ON
(0)

(I)

– press the "inverter on" button 6 on the control panel:
!

!

I

+–

O

6

green "load protected" light 5 blinks for 3 seconds,
the inverter starts and awaits the start of the other inverters;
– proceed in the same manner for each line:
when they are all on or enough have been started to supply the rated load, the output switch for each running line closes.
The load is supplied and the connected devices can be started,
red "load not protected" light 2 goes off,
green "load protected" light 5 remains constant, on the control panel of each line supplying the load.

34006452EN/AC

- Page 26

Start-up
Parallel UPS systems with a Static Switch Cubicle
Proceed in the following order:
– check that all lines supplying the load are off or that the load is disconnected;
– close the upstream switches supplying Mains 1 and 2 power (on the LV switchboard);
– close fuse switch Q2 in the Static Switch Cubicle (see figure 19);
– close Mains 2 input switch Q4S in the Static Switch Cubicle;
– close switch Q5N in the Static Switch Cubicle;
– open maintenance bypass switch Q3BP in the Static Switch Cubicle;
– close fuse switch Q1 in the Static Switch Cubicle;
– close input switch Q1 on an UPS line.
The line powers up;
– red "load not protected" light 2 on the line control panel goes on,
– the RC automatically starts;
– close the line battery circuit breaker QF1;
– close inverter output switch Q5N for the line;
– press the "inverter on" button 6 on the line control panel;
– green "load protected" light 5 blinks for 3 seconds,
– the inverter starts and awaits the start of the other inverters;
– proceed in the same manner for each line;
– when they are all on or enough have been started to supply the rated load power, the output switch for each running line
closes and the load is supplied with power;
– red "load not protected" light 2 goes off,
– green "load protected" light 5 remains on, without blinking, on the control panel of each line supplying the load.

4.2 Start-up of a unit
Start-up of a rectifier/charger
– it is recommended not to stop the rectifier/charger because the battery will no longer be charged. Rectifier/charger start-up
is automatic when Mains 1 input switch Q1 is closed;
– red "load not protected" light 2 on the control panel goes on;
– close battery circuit breaker QF1.

Start-up of an inverter
When the rectifier/charger is on:
– press the "inverter on" button 6 on the control panel;
– green "load protected" light 5 blinks for 3 seconds;

Single-unit or modular UPS system:
– the inverter starts and if the transfer to Mains 2 conditions are correct, the load is supplied by the inverter;
– red "load not protected" light 2 goes off,
– green "load protected" light 5 becomes constant.

Frequency converter or multi-bypass UPS:
– the inverter starts and awaits the start of the other inverters;
– when they are all on or enough have been started to supply the rated load power, the output switch for each running line
closes and the load is supplied with power;
– red "load not protected" light 2 goes off,
– green "load protected" light 5 becomes constant, on the control panel of each line supplying the load.

Modular UPS with external maintenance bypass or parallel UPS with SSC:
– the inverter starts and awaits the start of the other inverters;
– when they are all on or enough have been started to supply the rated load power, the output switch for each running line
closes and the load is supplied with power;
– red "load not protected" light 2 goes off,
– green "load protected" light 5 remains on, without blinking, on the control panel of each line supplying the load and on
the control panel of the Static Switch Cubicle.

Frequency converter without a battery:
– Start-up of the rectifier/charger automatically leads to start-up of the inverter.

34006452EN/AC

- Page 27

5. Shutdown
5.1 Shutdown of a unit
Shutdown of an inverter
– press the "inverter off" button 7 on the control panel for 3 seconds;
!

!

I

+–

O

7

Single-unit UPS
– green "load protected" light 5 goes off,
– red "load not protected" light 2 on the control panel goes on,
– the inverter stops;
– if transfer to Mains 2 conditions are correct, the inverter shuts down and the load is transferred to Mains 2;
– if transfer to Mains 2 conditions are not correct, the inverter does not shut down;
– special action on the hidden control panel is required to force inverter shutdown,
– to force inverter shutdown, press simultaneously the security button 14 and button 5 "Forced inverter shutdown" 17 on
the hidden control panel,
– the load is transferred to Mains 2 with a 0.8 second interruption in the supply of power.

Multi-bypass modular UPS:
– the UPS shuts down (the other parallel-connected unit can supply the entire load):
green "load protected" light 5 goes off,
red "load not protected" light 2 on the control panel goes on.
The load is not affected and continues to be supplied by the other unit.

Modular UPS with external maintenance bypass:
– all the UPSs shut down:
green "load protected" light 5 goes off,
red "load not protected" light 2 on the control panel of each unit goes on,
orange "operating problem" light 3 on the other units goes on, all shut down due to the overload.

Frequency converter:
– if the system is redundant, i.e. the other parallel-connected inverters can supply the load on their own, the inverter shuts
down:
green "load protected" light 5 goes off,
red "load not protected" light 2 lights on the control panel of the line;
The load is not affected in that the other inverters continue to supply it normally;
if the system is not redundant, all the inverters shut down;
green "load protected" light 5 goes off,
red "load not protected" light 2 on the control panel of each line goes on,
orange "operating problem" light 3 on the control panel of the other lines goes on, all shut down due to the overload.

Parallel UPS with SSC:
– if the system is redundant, i.e. the other parallel-connected inverters can supply the load on their own, the inverter shuts
down:
green "load protected" light 5 goes off,
red "load not protected" light 2 lights on the control panel of the line.
The load is not affected in that the other inverters continue to supply it normally;
– if the system is not redundant and the transfer to Mains 2 conditions are correct, all the inverters shut down:
green "load protected" light 5 goes off,
red "load not protected" light 2 lights on the control panel of each line,
orange "operating problem" light 3 "on the control panel of the other lines goes on (all shut down due to the overload),
the load is transferred to Mains 2 without an interruption in the supply of power;
– if the system is not redundant and the transfer to Mains 2 conditions are not correct, the inverter does not shut down:
special action on the hidden control panel is required to force inverter shutdown,
to force inverter shutdown, press simultaneously the security button 14 and button 5 "Forced inverter shutdown" 17 on
the hidden control panel,
the load is transferred to Mains 2 with a 0.8 second interruption in the supply of power.

34006452EN/AC

- Page 28

Shutdown
Shutdown of an rectifier/charger
Except in frequency converters without a battery, it is recommended not to stop the rectifier/charger because the battery will
no longer be charged. Except in the case of a test of the inverter on battery power, the rectifier/charger should be shutdown
after the inverter to avoid unnecessary battery discharge.
Proceed in the following order:
– open battery circuit breaker QF1;
– open Mains 1 input switch Q1;
– the rectifier/charger shuts down,
– all control panel lights go off because the device is powered down.
Note:
In a frequency converter without a battery, rectifier/charger shutdown automatically results in inverter shutdown.

5.2 System shutdown
Single-unit or single modular UPS
– shutdown the inverter (see the "shutdown of a module" section);
– carry out operations in the following order:
– close maintenance bypass switch Q3BP:
Q1

Q4S

Q3BP

Q5N

ON
(I)

ON
(I)

OFF ON

ON
(I)

(0)

(I)

– open output switch Q5N:
Q1

Q4S

Q3BP

Q5N

ON
(I)

ON
(I)

ON
(I)

ON OFF
(I)

(0)

– open Mains 2 input switch Q4S:
Q1

Q4S

Q3BP

Q5N

ON
(I)

ON OFF

ON
(I)

OFF
(0)

(I)

(0)

– open battery circuit breaker QF1:
QF1
ON OFF
(I)

(0)

– open Mains 1 input switch Q1:
Q1

Q4S

Q3BP

Q5N

ON OFF

OFF
(0)

ON
(I)

OFF
(0)

(I)

(0)

– the UPS is powered down (except the Mains cables upstream from switches Q1, Q4S and Q3BP) and the load is supplied
by Mains 2. All the lights on the control panel are off. A full powering down requires load shutdown and the opening of the
upstream protection devices on Mains 1 and 2.

34006452EN/AC

- Page 29

Shutdown
Modular UPS with external maintenance bypass
– shutdown each UPS (see section "shutdown of
a unit");
– transfer to the maintenance bypass in the order
indicated below (the load is supplied directly by
Mains 2 via bypass
switch Q3BP):
– in the maintenance bypass cubicle, close
switch Q3BP, then open switch Q5N;
– open output switch Q5N for each UPS;
– cut the Mains 2 supply to each UPS by opening
the upstream protection devices;
– open battery circuit breaker QF1 on each UPS;
– open input switch Q1 on each UPS;
– the UPSs are de-energised once the capacitors
have discharged.

External maintenance bypass
Q3BP

Modular UPS 1
static switch

Q4S

mains 2

Q1

mains 1

rectifiercharger

inverter

Q5N

QF1

battery

Modular UPS 2
Q4S

load

Q5N

static switch

mains 2

Q1

rectifiercharger

inverter

mains 1

Q5N

QF1

battery

Multi-bypass modular UPS
Modular UPS 1
Q4S

Q1

mains 1

– shutdown each UPS (see section "shutdown of
a unit");
– the load is supplied via the Mains 2 of each
UPS;
– close switch Q3BP on each UPS, the load is
supplied by the Mains 2, via the bypass lines
(Q3BP) of each UPS;
– open switches Q5N, Q4S, Q1 and QF1 on each
UPS, the situation is that shown in the figure
opposite;
– the UPSs are de-energised once the capacitors
have discharged.

Q3BP

rectifiercharger

static switch

inverter

Q5N

QF1

mains 2

battery

Modular UPS 2

Q3BP

Q4S

Q1

mains 1

rectifiercharger

load

static switch

inverter

Q5N

QF1

battery

Frequency converters (no Mains 2)
Shutdown of the inverters results in the interruption of the load;
– shut down each inverter (see the "shutdown of a unit" section);
– open battery circuit breaker QF1 and Mains 1 input switch Q1 on each unit;
QF1
ON OFF
(I)
Q1

Q5N

ON OFF
(I)

(0)

(0)

ON
(I)

– the system is powered down (except the Mains 1 cables upstream from switch Q1). A full powering down requires the
opening of the upstream protection device on Mains 1.
34006452EN/AC

- Page 30

Shutdown
Parallel UPSs with SSC (with Mains 2)
– shut down each inverter (see the "shutdown of a unit" section);
– carry out the maintenance bypass operation in the Static Switch Cubicle (the load will be directly supplied by Mains 2
via maintenance bypass switch Q3BP);
– close switch Q3BP and open switches Q5N and Q4S in the "static switch" cubicle;
– open fuse switches Q1 and Q2 in the Static Switch Cubicle;
– open battery circuit breaker QF1 in each UPS (except for frequency converters without a battery);
– open input switch Q1 for each UPS;
– the UPSs are powered down (except the Mains cables upstream from switches Q1, Q4S and Q3BP) and the load
is supplied by Mains 2.
All the lights on the control panel are off. A full powering down requires load shutdown and the opening of the upstream
protection devices on Mains 1 and 2.

5.3 Buzzer reset
– first determine the cause of the alarm;
– press the "buzzer reset" button 11 on the hidden control panel on the concerned cubicle.
The buzzer stops, but a new alarm will set it off again.
ABCD E F GH I J K LMN
1

2

3

4

5

11

34006452EN/AC

- Page 31

6. Alarms
The autodiagnostic system considers any system status other than normal as a problem.
Prior to any other action, note any lights (A to N) on the hidden control panel that may be on.
Also note any messages on the screen.
Certain problems may result in the control panel not functioning.
In this case, it is strongly recommended to call the after-sales support department.
– if the load is still correctly supplied with power, it has probably been transferred to Mains 2 (static switch) and is therefore
no longer protected;
– if the load is no longer supplied with power, transfer it manually to the maintenance bypass (see section below).

6.1 Maintenance bypass
This operation is possible only if the system includes a Mains 2. It results in the load being directly supplied by Mains 2 via
maintenance bypass switch Q3BP, thus ensuring a higher level of security in the event of a malfunction.
Important:
Prior to beginning the bypass operation, shut down all system inverters (press the "inverter off" button 7 on each UPS
control panel). If an inverter remains operating and the Mains 2 transfer conditions are not correct, the load will suffer a 0.8
second interruption.
Switching procedures are explained on a drawing next to each switch. It is imperative that the operation proceed in the
following order:
– shut down any inverters that may still be running;
!

!

I

+–

O

7

– 1 : close maintenance bypass switch Q3BP;
– 2 : open inverter output switch Q5N;
– 3 : open Mains 2 input switch Q4S:
bypass
Q1

Q4S

Q3BP

Q5N

1

ON
(I)

ON
(I)

OFF ON

ON
(I)

2

ON
(I)

ON
(I)

ON
(I)

ON OFF

3

ON
(I)

ON OFF

ON
(I)

OFF
(0)

(I)

(0)

(0)

(I)

(I)

(0)

Note:
– in systems with a Static Switch Cubicle, the above operation is carried out in the Static Switch Cubicle;
– the operation with the three switches is carried out in reverse order (3, 2, 1) to return to normal status;
– in an installation comprising modular UPSs with an external maintenance bypass, the operation is carried out in the external
maintenance bypass. The cubicle is not equipped with a Q4S switch and it is therefore necessary to open the protection
devices upstream on the maintenance-bypass line.

34006452EN/AC

- Page 32

7. Environment information
7.1 Standard information Media Contacts 9
Terminals XR1, XR2, XR3 and XR4 on the remote transmission board of each type of unit can be used for the input of data
from the operating environment and for the transmission of signals on the operational status of the device (see figure 18 for
the position of the board).

Remote transmission board

XR1

XR2

XR3

XR4

Signal reception
The signals should be provided by volt-free contacts.
– emergency shutdown. An NC contact causes:
rapid shutdown of the inverter and the RC,
opening of battery circuit breaker QF1,
transfer of the load to Mains 2 (generally without interruption in the supply of power);
– battery room ventilation fault: a NO contact causes the shutdown of the RC;
– battery circuit breaker QF1 closed: a NO contact inhibits inverter start-up when the breaker is open;
– battery temperature: an optional PC-board may be connected to the remote transmission board. It supplies information
on the battery temperature, thus enabling the RC to regulate the battery voltage.
Note:
The Static Switch Cubicle does not receive any of the above signals.

Signal transmission
– an auxiliary 24V power supply, isolated and backed up, is used to supply:
the undervoltage coil release for the battery circuit breaker(s) QF1,
an optional board that measures the temperature in the battery room;
– "general alarm" information (2 volt-free changeover contacts) which includes:
internal faults,
information on temperatures outside tolerances in the battery room (optional),
overload information (I > In),
static switch ventilation and power-supply faults;
– "low battery shutdown" warning signal (2 volt-free changeover contacts) indicating that battery time is about to run out.
The warning threshold may be personalized;
– "load on inverter" signal (2 volt-free changeover contacts) indicating that the load is supplied by the inverter. In singleunit UPS systems, one volt-free changeover contact may be used to indicate that the load is supplied by Mains 2;
– "load on battery" signal (2 volt-free changeover contacts) indicating that the inverter is supplied by the battery in the
following cases:
Mains 1 outage or voltage drop,
RC shutdown,
RC current limiting;
This signal, which may be used to initiate process saving and shutdown procedures, is time-delayed by 30 seconds to avoid
unnecessary operations following micro-breaks;
– "maintenance position" signal (2 volt-free changeover contacts) indicating that:
maintenance bypass switch Q3BP is closed,
Mains 2 input switch Q4S is open,
inverter output switch Q5N is open,
battery circuit breaker QF1 is open;
– signal to open battery circuit breaker(s) QF1 in the event the "emergency shutdown" button being pressed or to avoid
an excessive battery discharge (more than 3 rated time).
Note:
– the maximum breaking capacity of the changeover contacts is 5 A at 250 V;
– information on the battery is not supplied to frequency converters without a battery or to the Static Switch Cubicle;
– in systems with a Static Switch Cubicle, the "load on inverter" and "maintenance position" signals must be directed to the
Static Switch Cubicle.

34006452EN/AC

- Page 33

Environment information
7.2 "LED" signalling box (optional)

test

A basic "LED" signalling box with four indication
lights may be supplied as an option with the
MGETM GalaxyTM 9000 system.
It supplies the following signals:
– load on battery;
– low battery shutdown warning;
– inverter stop;
– general alarm.
It connects to the terminals presented on the
preceding page and draws its power from the
external 220 V AC, 50 Hz or
60 Hz power supply not connected to a UPS.

7.3 Additional information "Media Contacts 15"
Terminals XR5 to XR9 on the board may be used to receive additional information from the environment and supply more
precise information on system status (see figures 18, 19 for the position of the board).

Additional remote transmission board

XR8 XR9

34006452EN/AC

- Page 34

XR5

XR6

XR7

Environment information
Signal reception
The signals should be provided by volt-free contacts.
– "desynchronization with Mains 2" signal inhibits the inverter from synchronizing its output frequency with that of
Mains 2. The inverter supplies a stable frequency and the load may no longer be correctly transferred from the inverter to
Mains 2. In the event of a malfunction or an overload, the transfer will take place with a 0.8 second interruption in the supply
of power to the load;
– "gradual rectifier/charger shutdown" signal makes the rectifier/charger shut down progressively to avoid excessive step
load variations in the event of a low output engine generator set replacing Mains 1;
– "generator current limiting" signal makes the rectifier/charger current limit the power drawn when a low output engine
generator set has replaced Mains 1. The additional power required for the inverter is supplied by the battery;
– "battery charge current limiting" signal reduces the battery charge current (programmable parameter) in the event a low
output engine generator set has replaced Mains 1;
– "transfer to Mains 2 disabled" signal blocks transfer of the load from the inverter to Mains 2. In the event the inverter
shuts down (overload, etc.), the load is no longer supplied (for modular UPSs, this information is disabled and transferred to
an auxiliary output);
– "transfer to Mains 2 with interruption disabled" signal blocks transfer of the load from the inverter to Mains 2 if it would
result in an interruption in the supply of power to the load. Only no-break transfers are allowed, i.e. transfer to Mains 2
conditions must be correct or the transfer is disabled (for modular UPSs, this information is disabled and transferred to an
auxiliary output);
– "auxiliary" signal can be used to provoke (depending on personalization):
a forced shutdown of the inverter (regardless of the status of Mains 2),
a protected inverter shutdown (transfer of the load to Mains 2 without interruption only if it is within tolerances),
modification of the inverter output frequency (50 Hz or 60 Hz);
– "remote inverter on" signal can be used to remotely start the inverter;
– "remote inverter off" signal can be used to remotely shut down the inverter.
Note:
In a system with a Static Switch Cubicle, the following signals must be directed to the Static Switch Cubicle:
– desynchronization with Mains 2,
– transfer to Mains 2 disabled,
– transfer to Mains 2 with interruption disabled.

Signal transmission
These signals are each transmitted by two volt-free changeover contacts with a maximum breaking capacity of 5 A 250 V.
– "overload" signal indicates that an overload has taken place (Pload > Pnominal in kVA);
– "rectifier/charger function fault" signal indicates that:
– a fault has taken place in the rectifier/charger module,
– Mains 1 input switch Q1 is open;
– "inverter function fault" signal indicates that a fault has taken place in the inverter module;
– "transfer to inverter fault" signal indicates that the load transfer conditions from Mains 2 to the inverter are incorrect;
– "transfer to Mains 2 fault" signal indicates that the transfer to Mains 2 conditions (voltage, frequency or phase) are
incorrect and a forced transfer will result in a 0.8 second interruption in the supply of power to the load;
– "rectifier/charger on" signal indicates the status of the module.
Note:
A Static Switch Cubicle receives only the following signals:
– overload,
– transfer to inverter fault,
– transfer to Mains 2 fault.

34006452EN/AC

- Page 35

8. Maintenance
8.1 Maintenance configuration
Single-unit or single modular UPS (figure 25)
Q3BP

mains 2

mains 1

static switch

Q4S

Q1

rectifiercharger

inverter

Q5N

load

QF1

battery

Fig. 25

During maintenance, the UPS must be isolated
from Mains 1 and 2, the battery and the load.
– inverter isolation
Proceed in the following order:
– shut down the inverter (press the "inverter off"
button 7 for 3 seconds),
– close bypass switch Q3BP,
– open isolating switches Q5N, Q4S, QF1 and
Q1.
The UPS is powered down once the capacitors
have discharged (a few minutes);
– start-up
Following servicing, proceed in the following
order:
– close switch Q1, then after approximately ten
seconds, switches QF1, Q5N and Q4S,
– open bypass switch Q3BP,
start the inverter (press the "inverter on"
button 6 ).

Caution:
- work should be carried out in accordance with applicable safety regulations;
- to avoid interrupting the load, the various switching operations must be carried out in the correct order. Operations
are explained in diagrams placed next to the switches.

Multi-bypass modular UPS (figure 26)
Modular UPS 1

Q3BP

Q4S

static switch

mains 2

mains 1

Q1

rectifiercharger

inverter

Q5N

QF1

battery

Modular UPS 2

Q3BP

load
Q4S

mains 2

mains 1

Q1

rectifiercharger

static switch

inverter

Q5N

Prior to servicing a given UPS, it must be isolated
from Mains 1, Mains 2, its battery and the load
outputs of the other UPSs (in this case, never
operate the Q3BP switches in the units).
– isolate the UPS
Proceed in the following order:
– shut down the inverter (press the "inverter off"
button 7 for three seconds);
– open isolating switches Q5N, QF1, Q4S and
Q1 in the unit.
The UPS is de-energised once the capacitors
have discharged (a few minutes).
– start-up
Once servicing is completed, proceed in the
following order:
– close Q1, then QF1, Q4S and Q5N;
– start the inverter (press the “inverter on”
button 6 ).

QF1

battery

Fig. 26
Note:
It is strongly advised to call on our after-sales support department for these operations.

34006452EN/AC

- Page 36

Maintenance
Modular UPS with external maintenance bypass (figure 27)
To service a number of modular UPSs with an external maintenance bypass, it is necessary to isolate them.
– isolate the UPSs
Proceed in the following order:
– shut down each inverter (press the "inverter off" button 7 for three seconds),
– switch to the maintenance bypass whereby the load will be directly supplied by Mains 2 via Q3BP (close Q3BP, then open
Q5 in the maintenance bypass cubicle),
– open input switch Q4S on each UPS;
– isolate each UPS from Mains 2 by opening the upstream protection devices,
– open input switch Q1 on each UPS,
– open output switch Q5N on each UPS.
The UPSs are de-energised (except the Mains 1 cables upstream of the Q1 switches on each UPS), but the load is supplied
with Mains 2 power via the maintenance bypass. Complete isolation of the installation requires opening of the upstream
protection devices on both Mains 1 and Mains 2.
– start-up
Once servicing is completed, proceed in the following order:
– close the input switches Q1 and Q4S on each UPS,
– close output switch Q5N on each UPS,
– close output switch Q5N in the maintenance bypass cubicle,
– open switch Q3BP in the maintenance bypass cubicle,
– close battery circuit breaker Q1 on each UPS,
– start all the inverters (press the "inverter on" button 6 ).
The UPSs all come on line at the same time if they are sufficient in number to supply the load.
Note:
It is strongly advised to call on our after-sales support department for these operations.

External maintenance bypass
Q3BP

Modular UPS 1
static switch

Q4S

mains 2

mains 1

Q1

rectifiercharger

inverter

Q5N

QF1

battery

Modular UPS 2
Q5N

static switch

Q4S

load

mains 2

Q1

rectifiercharger

inverter

mains 1

Q5N

QF1

battery

Fig. 27

34006452EN/AC

- Page 37

Maintenance
Frequency converter or parallel UPS with SSC (figure 28)

mains 1

Q1

Q5N
QF1

mains 1

Q1

Q5N

load

QF1

mains 1

Q1

Q5N
QF1

Fig. 28: frequency converter exemple

During maintenance, the concerned UPS or
converter must be isolated from Mains 1, its
battery and the output circuits of the other units.
– inverter isolation
Proceed in the following order:
– shut down the inverter (press the "inverter off"
button 7 for 3 seconds),
– open isolating switches Q5N, QF1 and Q1 for
that line.
The unit is powered down once the capacitors
have discharged (a few minutes).
In redundant systems with at least one redundant
UPS, the other UPSs (or converters) ensure
continuity of power to the load.
In non-redundant systems with a Mains 2, the
load is supplied by the Mains 2 and the Static
Switch Cubicle.
In non-redundant systems without a Mains 2, the
entire system must be shut down.
– start-up
Following servicing, proceed in the following
order:
– close switch Q1, then switches QF1, Q5N and
Q4S,
start the inverter (press the "inverter on"
button 6 ).

Note:
We recommend that you call on the after-sales support department to carry out these operations.

Static Switch Cubicle (figure 29)
Q3BP
Q5N

Q4S

load

mains 2

mains 1

Q1

Q5N
QF1

mains 1

Q5N

Q1
QF1

Fig. 29

During maintenance, the Static Switch Cubicle
must be isolated from Mains 2, the load and the
parallel UPSs.
– if work is required on the control electronics
alone, open cubicle switch Q4S (but not Q5N) and
cubicle fuse switches Q1 and Q2. The load can
then remain supplied by the UPSs. After
servicing, reclose fuse switches Q1, Q2 and
switch Q4S.
Caution:
When the Static Switch Cubicle is powered down
using the above procedure, only the control
electronics are in fact powered down. The power
circuits remain energized. Maintenance on the
static switch power circuits requires shutdown of
the UPSs and transfer of the load to the
maintenance bypass line.
– open switch Q5N, then the disconnector-fuses
Q1 and Q2 in the SSC;
– open switches Q5N, then switch Q4S on all the
UPSs (figure 29).
Caution:
Even in the maintenance bypass
configuration, the cubicle is only partially
shut down and the supply of power to the load
continues via switch Q3BP.
more extensive maintenance work on the Static
Switch Cubicle requires the entire system to be
shut down.

Note:
We recommend that you call on the after-sales support department to carry out these operations.
34006452EN/AC

- Page 38

Maintenance
8.2 Battery maintenance
Consult the instructions supplied by the battery manufacturer. Below are a few general indications:
– sealed lead-acid batteries.
These batteries require no maintenance:
but check the terminals of each cell from time to time and clean if necessary;
– vented lead-acid batteries:
check the electrolyte level regularly and add water if necessary,
check the voltage of each cell to determine if it is necessary to equalize the battery,
check the terminals of each cell and clean if necessary.
Caution:
Battery maintenance is undertaken with the system powered up. Operations must be carried out in accordance with applicable
safety regulations by qualified personnel using insulated tools, gloves and safety goggles.
Batteries contain dangerous substances that will harm the environment if thrown away. If you change the batteries yourself,
call on qualified organizations for battery disposal and recycling.

Pb

Pb

8.3 Autodiagnostics
Note the indications supplied on the hidden control panel (lights A to N 8 ). See the "control panel" section.
In systems with one or several alphanumeric displays, check the list of alarms.
If there is a true malfunction, note the indications and alarms and call the after-sales support department.

8.4 Visual check
– after-sales support technicians will power down the system prior to any maintenance operations.
Note:
In redundant, parallel UPS systems and frequency converters, the check may be carried out successively on each UPS or
converter without interrupting the load. In other configurations and for the Static Switch Cubicle, the load must be supplied via
the maintenance bypass (see the "Alarm" section).
– clean the system regularly, particularly the air inlet and outlet grills. Check that the air circulates freely in the cubicles.
– Use a vacuum cleaner if necessary;
– check that nothing hinders the ventilation at the top of the system;
– check that all the fans operate correctly.

8.5 Functional check
– check that lights J, K, M and N on the hidden control panel are not on to avoid an interruption in the supply of power to
the load due to incorrect transfer conditions or a battery problem;
– press the "inverter off" button and check that the buzzer and control panel lights function correctly (see the "main operating
modes" section);
– press the "inverter on" button and check again that the control panel lights function correctly;
– run a transfer to battery test. With the inverter on, open input switch Q1.
The orange "battery" light on the control panel should light. After two minutes on battery power, close input switch Q1.
The rectifier/charger should automatically restart and the orange "battery" light on the control panel should go off;
– in parallel systems, run these tests on each UPS or converter.

34006452EN/AC

- Page 39

Maintenance
8.6 Training centres
To allow you to use APC by Schneider Electric products effectively and carry out basic maintenance, we offer a complete
range of technical training courses in English and French.

Schneider Critical Power & Cooling Services 50
Hz training centres

Schneider Critical Power & Cooling Services 5060 Hz training centre

France Training Centre
140, Avenue Jean Kuntzmann
Innovallée
38334 - St Ismier Cedex - FRANCE

United States Training Centre
132 Fairgrounds Road
West Kingston - RI02892
U.S.A

Tél : +33 (0)4 76 18 34 14
Fax : +33 (0)4 76 18 45 21

Tél : +1 877 800 4272

Singapore Training Centre
10 Ang MO Kio Street 65, #03-06/10
Techpoint Building
Singapore 569059
Singapore
Tél : +65 6389 6792
China Training Centre
N° 999, Shen Fu Road
Min Hang District
Shanghai 201108
P.R. China
Tél : +86 21 3407 3365
Fax: +86 21 3407 4526

http://powerlearning.apc.com
Catalogue and registration available on line.

34006452EN/AC

- Page 40

9. "Monitor" alphanumeric display
9.1 General
– local operation. The "Monitor" alphanumeric display (see figure 30) may be installed behind the hinged cover of the hidden
panel (see figure 21) on the control panel in all types of cubicles (UPS or Static Switch Cubicle).
– remote operation. Installed in a special enclosure, the "Tele Monitor" provides the user with remote indications on system
status. Two "Tele Monitor" units may be connected to the same system, one as a master for indications and remote control,
the other as a slave for indications only.
The "Monitor" can operate in two different modes:
– mono-cubicle: the option monitors only the cubicle in which it is installed;
– multi-cubicle: "Monitor" can monitor all system cubicles (up to eight maximum). In this mode, the system is equipped with
only one "Monitor" which may be installed in any of the cubicles.
The alphanumeric display screen 18 is made up of two lines with 20 characters each. The control panel is made up of:
– nine display control buttons,
– eight selection lights for the concerned cubicle,
– eight alarm lights for the cubicles.

Alphanumeric display screen and control panel
18

19

20

1 2 3 4 5 6 7 8

load protected
power supply OK
V

21

A

22

W.Hz

23

+–

24

!

25

*
26

27

Fig. 30

Display
A message indicating the general status of the cubicle or system is continuously displayed. If there is no alarm or problem
and the load is normally supplied, the message on the screen is:

LOAD PROTECTED
POWER SUPPLY OK

34006452EN/AC

- Page 41

"Monitor" alphanumeric display
9.2 Control panel
"Settings" button 19 .
This button can be used to select the display language, adjust screen contrast to local conditions and, for the "Tele Monitor"
option, adjust the volume level of the buzzer.
"V" button 21 .
Provides access to voltage measurements:
– Mains 1 phase-to-phase voltages;
– Mains 2 phase-to-neutral and phase-to-phase voltages;
– inverter output phase-to-neutral and phase-to-phase voltages;
– load phase-to-neutral and phase-to-phase voltages.
"A" button 22 .
Provides access to current measurements:
– currents on the Mains 1 and 2 lines and the load;
– percent current drawn by the load;
– percent load with regards to the rated value;
– load current peak factor.
"W.Hz" button 23 .
Provides access to measurements:
– Mains 1 and 2 and inverter frequency;
– active and apparent power drawn by the load;
– load power factor.
"Battery" button 24 .
Provides access to battery measurements:
– battery voltage (or DC voltage for frequency converters without a battery);
– battery current (charge or discharge);
– battery temperature (optional);
– remaining battery time.
"Alarms" button 25 .
Displays current or logged alarms and stops the buzzer for the "Tele Monitor" option.
A blinking character ("!", "A" or "kW") at the end of the line indicates that the user must press the "alarms" 25 "A" 22 or
"W.Hz" 23 button respectively to display the remaining alarms or further information.
"I/O" button 26 .
Provides access to On/Off controls. This button is active only on remote, master "Tele Monitor" units.
"*" button 27 .
This button has a number of functions depending on the displayed messages (confirmation, positive response, etc.). Pressing
this button followed immediately by the "V" button 21 (less than one second) provides access to the display configuration
function. In "Monitor" multi-cubicles mode, this button can also be used to display the type of cubicle concerned by the
displayed message. The information disappears when the button is released. For example:

CUBICLE NUMBER 1 =
STATIC SWITCH MODULE
">" button 20
This button has a number of functions depending on the displayed messages (selection, negative response, etc.).
In "Monitor" multi-cubicles mode, this button can also be used to select one of the eight cubicles that may be connected to
the "Monitor" unit, in which case any action on the control panel and the messages or measurements displayed concern only
the selected cubicle.
In the event the selected cubicle does not respond, the following message is displayed:

CUBICLE NUMBER XX
UNAVAILABLE
In the event of no reply from the display screen, the following message appears:

DISPLAY NUMBER XX
UNAVAILABLE
Which corresponds to a communications fault.
In the event of invalid data, the following message is displayed:

CUBICLE NUMBER XX
FAULT

34006452EN/AC

- Page 42

"Monitor" alphanumeric display
Note:
– most functions may be directly accessed. For example, when voltage measurements are currently displayed, it is possible
to directly access current measurements by pressing the "A" button;
– in "Monitor" multi-cubicles mode, it is possible to access the same measurement in another cubicle by simply pressing
the ">" button. For example, if the battery voltage of a cubicle is currently displayed, it is possible to directly display the battery
voltages of the other cubicles by pressing the ">" button once for each other cubicle.

General display function organization
Initial screen, display of general alarms
This is the normal display which systematically reappears
when the control panel has not been used for ten minutes.

!

Alarm display and buzzer reset

V

Voltage measurements

A

Current measurements

W.Hz

Frequency and power measurements

+–

Battery measurements
On/Off controls

*

to
confirm

Language, screen contrast and
buzzer volume settings
to
set

*

to
confirm

Cubicle selection for display of measurements
(multi-cubicle mode only)

*
*

Information on type of cubicle
(multi-cubicle mode only)
V

Display configuration
to select
or answer
no

*

to confirm
or answer
yes

9.3 Lights 1 to 8
These lights are useful particularly in multi-cubicle mode.
Green lights
Only one of these lights is on at a time, indicating the number of the cubicle concerned by the current display.
Red lights
These lights provide an indication on system status by signaling alarms and problems in the concerned cubicles. They light
if maintenance is carried out on a cubicle or if the communication link with a cubicle breaks down.

34006452EN/AC

- Page 43

"Monitor" alphanumeric display
9.4 Alarm display and buzzer reset
When the control panel has not been used for ten minutes, the alphanumeric display presents a general message indicating
the general status of the cubicle or the system.
If there are no alarms or problems, and the load is correctly supplied by the inverter, the display indicates:

LOAD PROTECTED
POWER SUPPLY OK
If there is a problem, the screen first displays a general alarm, then if applicable, a list of secondary alarms may be obtained
by successively pressing the "alarms" button ("!").
See the lists below.
For the local "Monitor" option, button 11 on the hidden control panel stops the buzzer.
For the remote "Monitor" option ("Tele Monitor"), the "!" button stops the buzzer.
Note:
The existence of another alarm in the list is indicated by the blinking "!" character at the end of a message.
The last alarm in the list is not followed by the blinking "!" character at the end. If the "alarms" button is pressed again,
the system returns to the initial screen.

Display of alarms
general alarm
on the initial screen

!

(ALARM MESSAGE NUMBER 1)
!

This message is displayed only if the buzzer has been activated.
It is a prompt to consult the list of current alarms by pressing the
"alarms" ("!") button after having read each message.

!

(ALARM MESSAGE NUMBER 2)
!
!

(LAST ALARM MESSAGE)

The last alarm message is not followed by the blinking
"!" character. If the "alarms" ("!") button is pressed again,
the system returns to the initial screen.

!

initial screen

List of general alarms
LOAD PROTECTED
POWER SUPPLY OK
This is the normal display when there are no alarms or problems and the load is correctly supplied by the inverter.

LOAD PROTECTED
PROBLEM...

!

The load is supplied by the inverter, but a minor problem requiring servicing has occurred. The cause of the problem is
contained in the list of secondary alarms (see next page).

MAINS 1 PROBLEM
LOAD ON BATTERY

!

The load is supplied by the inverter, but Mains 1 is down or outside tolerances and power is supplied by the battery.

34006452EN/AC

- Page 44

"Monitor" alphanumeric display
REMAINING BAT. TIME
__MN %KW LOAD =___
This message is automatically displayed for five seconds, alternating with the preceding. It indicates the remaining battery
time in minutes prior to inverter shutdown. The calculation takes into account:
– the percentage of full rated load power being drawn;
– the type of battery;
– battery temperature;
– battery age.

LOW BATTERY
SHUTDOWN IMMINENT

!

This message replaces the "Mains 1 problem, load on battery" message when battery voltage reaches the "low battery
shutdown" warning level. It alternates with the message described above, "remaining battery time…".
The user must then rapidly take measures to secure the load (load shedding, file saves and shutdown, etc.). In the next one
to two minutes at most, the inverter will shutdown and the load will be interrupted.
Two low battery thresholds exist:
– a battery voltage threshold, which is slightly above the threshold causing an inverter shutdown (this threshold can be
disabled);
– a time threshold, which refers to an adjustable value of the time remaining before effective end of battery power.

ALARM ...
!
This message signifies that the battery circuit breaker is open and the inverter shut down. The cause of the alarm is in the list
of secondary alarms (see next page).

List of secondary alarms
These alarm messages may be consulted by pressing the "alarms" ("!") button when the "!" character appears at the end of
a general alarm message.
The "alarms" ("!") button can then be used to read the other alarms from the list.

EMERGENCY SHUTDOWN
AUXILIARY COMMAND

!

The remote emergency-shutdown button has been pressed with as a result:
– shutdown of the inverter;
– shutdown of the rectifier/charger;
– opening of battery circuit breaker QF1;
– transfer of the load to Mains 2.
To ensure full powering down of the system, this button must also open the external upstream circuit breakers supplying
Mains 1 and 2.

LOAD ON
MAINS 2

!

The load has been transferred to Mains 2 and is no longer protected.

MAINS 2 PROBLEM
CHECK FREQUENCY

!

Mains 2 voltage is outside tolerances. Transfer of the load from the inverter to Mains 2 or vice-versa will result in
an interruption of the supply of power to the load.

MAINS 2 PROBLEM
CHECK VOLTAGE

!

Mains 2 voltage is outside tolerances. Transfer of the load from the inverter to Mains 2 or vice-versa will result in
an interruption of the supply of power to the load.

34006452EN/AC

- Page 45

"Monitor" alphanumeric display
FREQUENCY IMPOSED
DESYNCH. COMMAND

!

The inverter has received an external command to desynchronize its output frequency with that of Mains 2.

INVERTER IMPOSED
AUXILIARY COMMAND

!

The inverter has received an auxiliary command inhibiting transfer to Mains 2. In the event of an inverter malfunction and
shutdown, the load will no longer be supplied.

BATTERY OVERTEMP.
CHECK FANS

!

This message is displayed only if the "Temperature Monitor" option has been installed. It signals that the battery temperature
is outside tolerances.

BATT. HOUSING VENT
OR HARM FILTER FAULT
A fault requiring servicing has occurred in the battery room ventilation system. The rectifier-charger stops after 30 seconds.
If the installation includes a harmonics filter, this light will also signal an overtemperature of the filter’s inductor.

MAINS 1 PROBLEM
CHECK FREQUENCY

!

Mains 1 frequency is outside tolerances and the RC has shut down. The inverter is on battery power.

MAINS 1 PROBLEM
CHECK VOLTAGE

!

Mains 1 is down or its voltage is outside tolerances and the rectifier/charger has shut down. The inverter is on battery power.

CHARGER SHUTDOWN
AUXILIARY COMMAND

!

The rectifier/charger has received an external command to progressively shut down (for example, for a progressive transfer
to an engine generator set).

INPUT KVA LIMITED
AUXILIARY COMMAND

!

The rectifier/charger has received an external command to limit the power drawn on Mains 1. The remaining power required
for the load is supplied by the battery. This situation is encountered, for example, when the system operates on power supplied
by an undersized engine generator set.

I BATTERY LIMITED
AUXILIARY COMMAND

!

The rectifier/charger has received an external command to limit the charge current supplied to the battery. The normal
charge current will be supplied when Mains 1 returns. This situation is encountered, for example, when the system operates
on power supplied by an undersized engine generator set.
Note:
The battery charge current limit value may be programmed.

34006452EN/AC

- Page 46

"Monitor" alphanumeric display
BATTERY BREAKER
QF1 OPEN

!

QF1 battery circuit breaker has tripped or is open. The load is no longer protected because battery power in unavailable in
the event of a Mains 1 outage.

LOW BATTERY
!
The inverter has shut down at the end of battery power.

CHARGER OFF
...

!

The rectifier/charger has shut down.

CHARGER FAULT
CALL SUPPORT DEPT.

!

A fault has occurred in the rectifier/charger module requiring servicing by the after-sales support department.

MAINS 1 SWITCH
Q1 OPEN

!

Mains 1 input switch Q1 is open. It must be closed for rectifier/charger start-up.

I INVERTER > IN
CHECK P.F. KW
An inverter overload has occurred due to a load power factor greater than 0.9. The blinking "kW" sign at the end of the
message is a prompt to read the load power factor.

INVERTER FAULT
CALL SUPPORT DEPT.

!

A fault has occurred in the inverter module requiring servicing by the after-sales support department.

INVERTER SHUTDOWN
OVERLOAD > IMAX

!

An overload greater than 1.6 In has occurred on the load, resulting in inverter shutdown.

INVERTER SHUTDOWN
OVERLOAD > IN

A

An overload between In and 1.6 In has occurred on the load, resulting in inverter shutdown. The blinking "A" at the end of the
message is a prompt to read the load current measurement.

AUXILIARY CONTROL
SIGNAL RECEIVED

!

An auxiliary "Media Contacts 15" option signal has been received. The next display will indicate which of the four possible
functions was set.

FORCED UPS SHUTDOWN
AUXILIARY CONTROL
The UPS has received a forced shutdown command. This corresponds to an auxiliary control signal received via a "Media
Contacts 15" option set for this function.

34006452EN/AC

- Page 47

"Monitor" alphanumeric display
PROTECT.UPS SHUTDOWN
AUXILIARY CONTROL
The UPS has received a shutdown command. This command will only be executed if load transfer conditions on Mains 2
are satisfied. This corresponds to an auxiliary signal received via a "Media Contacts 15" option set for this function.

FREQUENCY REVERSAL
AUXILIARY CONTROL
The UPS has received a command to change its output frequency (50 or 60 Hz).
This command is only executed if the inverter is off. The frequency will be changed the next time the inverter is started.
The command corresponds to an auxiliary control signal received via a "Media Contacts 15" option set for this function

I LOAD > IN
CHECK LOAD

A

The power drawn by the load is greater than the rated value. The blinking "A" at the end of the message is a prompt to read
the load current measurement.

TRANSFER FAULT
CALL SUPPORT DEPT.

!

A fault has occurred in the static switch which ensures transfer of the load between the inverter and Mains 2. Servicing by
the after-sales support department is required.

PHASE OUT OF LIMITS
!
For a single-unit UPS or Static Switch Cubicle, the phase shift between the inverter and Mains 2 is outside tolerances.
Transfer of the load between the inverter and Mains 2 will result in an interruption in the supply of power to the load.
For a parallel UPS, the phase shift between this inverter and the other inverters is outside tolerances, and the corresponding
UPSs has therefore been disconnected.

MAINS 2 SWITCH
Q4S OPEN

!

Mains 2 input switch Q4S is open, i.e. transfer of the load from the inverter is impossible.

OUTPUT SWITCH
Q5N OPEN

!

Inverter output switch Q5N is open, i.e. the load cannot be supplied by the inverter.

MAINT. BYPASS SWITCH
Q3BP CLOSED
!
Maintenance bypass switch Q3BP is closed. The system is in maintenance configuration and the load is supplied by Mains 2.

EMERGENCY OFF
OVERLOAD > IN

!

The load is no longer supplied by Mains 2 following an extended overload.

34006452EN/AC

- Page 48

"Monitor" alphanumeric display
BATTERY
CHARGING

!

The battery is currently being recharged.

INDEPENDENT
INVERTER FREQUENCY

!

The inverter frequency is stable and accurate to 0.05Hz, but no longer synchronous with that of Mains 2.

NUMBER OF INVERTERS
READY INSUFFICIENT !
This message is valid only for parallel UPS systems. The number of UPSs ready for connection to the load is insufficient for
the required power level. Another UPS must be started before all the lines together may supply the load. Until another line is
started, the load will remain supplied by Mains 2.

BATTERY MAINTENANCE
CALL AFTER-SALES
Indicates that the battery has probably reached the end of its service life (based on the estimated average service life since
its installation).

TRANSFER DISABLED
AUXILIARY CONTROL
Transfer of the load to Mains 2 is inhibited due to:
– certain transfer conditions not satisfied;
– "transfer to Mains 2 with interruption disabled" auxiliary contact of the "Media Contacts 15" option closed.

UPS IMPOSED
TRANSFER DISABLE

!

Cannot transfer the load to Main 2 due to:
– transfer conditions not satisfied;
– UPS operating on an independent frequency;
– UPS operating with current limitation;
– internal fault;
– auxiliary control inhibits switching to Mains 2.

34006452EN/AC

- Page 49

"Monitor" alphanumeric display
9.5 Measurement system
The "Monitor" system displays a number of input and output measurements at different points in the system.
– Mains 1
– phase-to-phase voltages,
– currents of the three phases,
– frequency;
– Mains 2
– phase-to-neutral voltage,
– phase-to-phase voltages,
– frequency;
– battery
– voltage,
– charge or discharge current,
– remaining battery time (calculated for each UPS);
– inverter output
– phase-to-neutral voltage,
– phase-to-phase voltages,
– currents of the three phases,
– frequency,
– active and apparent power,
– ratio peak current / rated current rms;
– total load
– phase-to-neutral voltage,
– phase-to-phase voltages,
– currents of the three phases,
– frequency,
– active and apparent power;
– option
– battery temperature.
Note:
Frequency converters without batteries are not concerned by the battery measurements. The displayed battery voltage
corresponds to the DC voltage at the RC output.

Single-unit or modular UPS
Q3BP
mains 2
U-F

mains 2

mains 1

Q4S

Q1

K3N

Q5N

load

QF1
charger
U -I-F

battery
U-I

inverter
U-F

inverter
I-P

load
U-I-F-P

Frequency converter
mains 1

Q1

K3N

Q5N

common
load

QF1
charger
U -I-F

34006452EN/AC

- Page 50

battery
U-I

inverter
U-F

inverter
I-P

load
U-I-F-P

"Monitor" alphanumeric display
Static Switch Cubicle
Q3BP
mains 2
U-F

K2S

Q4S

mains 2

Q5N

RCIB line(s)

load

load
U-I-F-P

9.6 Voltage measurements
These measurements may be accessed in two manners:
– pressing the "V" button displays the series of screens in the figure opposite;
– in "Monitor" multi-cubicle mode, pressing the ">" button when the screen already displays the voltage measurements
of a cubicle.
The system shifts to the voltage measurements of the next cubicle.
Note:
– Mains 2 measurements are not displayed on converters and parallel UPS with SSC;
– Mains 1 and inverter output measurements are not displayed on Static Switch Cubicles.
Caution:
For installations comprising a number of modular UPSs connected in parallel, the absence of load (UPS output) voltage
indicated on a display is only valid if it also indicated on the displays of all the other parallel-connected UPSs. Before carrying
out any work on a UPS, always check the absence of voltage using a method complying with applicable safety rules for work
on electrical equipment.

Display of voltage measurements
V

MNS.1
V RMS

Direct access to the function by pressing the "V" button.

U12

U23

U31

V1

V2

V3

U12

U23

U31

Mains 2 input phase-to-phase voltages in V rms.

V1

V2

V3

Inverter output phase-to-neutral voltage in V rms.

U12

U23

U31

V1

V2

V3

U12

U23

U31

Mains 1 input phase-to-phase voltages in V rms (RC input).

V

MNS.2
V RMS

Mains 2 input phase-to-neutral voltage in V rms.

V

MNS.2
V RMS
V

INV.
V RMS
V

INV.
V RMS

Inverter output phase-to-phase voltages in V rms.

V

LOAD
V RMS

Load phase-to-neutral voltage in V rms.

V

LOAD
V RMS

Load phase-to-phase voltages in V rms.

V

34006452EN/AC

- Page 51

"Monitor" alphanumeric display
9.7 Current measurements
These measurements may be accessed in two manners:
– pressing the "A" button displays the series of screens in the figure opposite;
– in "Monitor" multi-cubicle mode, pressing the ">" button when the screen already displays the current measurements of a
cubicle.
The system shifts to the current measurements of the next cubicle.
Note:
– Mains 2 measurements are not displayed on UPS cubicles in parallel UPS systems;
– Mains 1 and inverter output measurements are not displayed on Static Switch Cubicles.

Display of current measurements

A

MNS.1
A RMS

Direct access to the function by pressing the "A" button.

I1

I2

I3

Currents of the three phases at Mains 1 input in A rms
(RC input).

I1

I2

I3

Currents of the three phases at Mains 2 input in A rms.

I1

I2

I3

Currents of the three phases at inverter output input in A rms.

I1

I2

I3

A

MNS.2
A RMS
A

INV.
A RMS
A

LOAD
A RMS

Currents of the three load phases in A rms.

A

I LOAD / IN
=
% (IN =

A)

Percentage of the current drawn on the most heavily loaded load
phase with regards to the rated current (in parentheses).

A

LOAD
I1
PEAK F.
A

34006452EN/AC

- Page 52

I2

I3

Peak factor for each phase of the load current with regards to a sine
current.

"Monitor" alphanumeric display
9.8 Frequency and power measurements
These measurements may be accessed in two manners:
– pressing the "W.Hz" button displays the series of screens in the figure opposite;
– in "Monitor" multi-cubicle mode, pressing the ">" button when the screen already displays the frequency and power
measurements of a cubicle. The system shifts to the frequency and power measurements of the next cubicle.
Note:
– Mains 2 measurements are not displayed on UPS cubicles in parallel UPS systems;
– Mains 1 output measurements are not displayed on Static Switch Cubicles.

Display of power and frequency measurements
W. Hz

FREQ. MNS1
HZ

Direct access to the function by pressing the "W.Hz" button.

MNS2

INV.

P2

P3

Frequency value for Mains 1, Mains 2 and the inverter output in Hz
with one decimal figure values valid only for concerned cubicle).

W. Hz

LOAD
KW

P1

Active power drawn by the load in kW on each phase.

W. Hz

P LOAD / Pn
=
% (PN=

KW)

Percentage of the power drawn by the load with regards
to the rated unit output (in parentheses).

W. Hz

LOAD
KVA

P1

P2

P3

Apparent power drawn by the load in kVA on each phase.

W. Hz

P. TOTAL
LOAD

P.KW

P.KVA

Active power (in kW) and apparent power
(in total kVA drawn by the load (total of the three phases)).

W. Hz

POWER FACTOR
LOAD P.F.
=

Load power factor (active power / apparent power).

W. Hz

34006452EN/AC

- Page 53

"Monitor" alphanumeric display
9.9 Battery measurements
These measurements may be accessed in two manners:
– pressing the "battery" button displays the series of screens in the figure opposite;
– in "Monitor" multi-cubicle mode, pressing the ">" button when the screen already displays the battery measurements of a
cubicle. The system shifts to the battery measurements of the next cubicle.
Note:
– these measurements do not concern the Static Switch Cubicle. The "battery" button on the Static Switch Cubicle will display
the following message for a few seconds:

COMMAND INVALID
STATIC SWITCH MODUL
– the available battery time value blinks to attract attention;
– the battery temperature is displayed only if the "Temperature Monitor" option is installed.
Note:
Stars appear in the battery backup time display if the battery time estimator function has not been validated by the after-sales
support technicians.
– battery test: see figure opposite.

Display of battery measurements
+–

UBAT.
V

Direct access to the function by pressing the "battery" button.

IBAT.
A

*

+–

T°BAT.
°C

Battery voltage, charge current (+ sign)
or discharge current (- sign),
battery temperature (optional).

ou

AVAILABLE BAT.TIME
MN %KW
LOAD =

If Mains 1 is up - available battery time in the event
of a Mains 1 outage.

+–

REMAINING BAT.TIME
MN %KW LOAD =
+–

see figure on next page

34006452EN/AC

- Page 54

If Mains 1 is down or outside tolerances - remaining battery time in
minutes (real time calculation).

"Monitor" alphanumeric display
Display of battery measurements (cont.)

+–

The screen opposite is displayed when a battery test is requested.
It indicates the battery charge status and the remaining service life.
A manual or automatic test may be requested.

BATTERY CHARGE
LEVEL=_ _ _%
+–

BATTERY LIFE
EXPECTANCY=_ _YEAR(S)
+–

MANUAL TEST?
*=YES =NO

*
AUTOMATIC TEST?
*=YES =NO

*
LAST TEST _W _D _H
BATTERY OK

The screen opposite is displayed following a positive,
automatic battery test. It indicates the time since the last test
and provides access to test settings.

+–

PARAMETERS?
*=YES =NO

*
WEEKS=_ _
=CONTINU *=VALID

The screen opposite is displayed when the user requests
access to the automatic test settings. It is possible to modify
the interval between two automatic tests.

*
DAYS=_ _
=CONTINU *=VALID

*
HOURS=_ _
=CONTINU *=VALID

*
BATTERY TEST ON
U DC=_ _ _V

The screen opposite is displayed during a battery test,
whether manual or automatic.

BATTERY OK

BATTERY NON OK

TEST ABANDONNED
CHECK THE ALARMS

The screen opposite is displayed when the battery test
cannot be completed.

34006452EN/AC

- Page 55

"Monitor" alphanumeric display
9.10 Inverter On/Off commands
These commands may be accessed only via the master display. When the "I/O" button is pressed, the series of screens in
the figure opposite is displayed.
Note:
– these commands do not concern the Static Switch Cubicle. The "I/O" button on the "static switch" cubicle produces the
message:

COMMAND INVALID
STATIC SWITCH MODUL
– the "I/O" button on a slave display monitor produces the message:

COMMAND INVALID
ON SLAVE DISPLAY
– if the On/Off commands have not been validated (by the after-sales support technicians), pressing the "I/O" button
produces the message:

COMMAND INVALID
CONFIGURATION
– if a "Soft Tunor" session is in progress (initiated by after-sales support technicians), pressing the "I/O" button produces the
message:

COMMAND INVALID
SOFT TUNOR

Display for the inverter On/Off commands
or

START
=YES

*

INVERTER ?
>=ESCAPE

*

Direct access to the function by pressing the "I/O" button .
This screen is displayed if the inverter is already off.
It is a prompt to press the "*" button to confirm start-up.
During start-up, the following screen is displayed:

PROCESSING
...

initial screen

STOP INVERTER ?
=YES
>=ESCAPE

*

This screen is displayed if the inverter is on. It is a prompt to press
the "*" button to confirm shutdown.
If the transfer to Mains 2 conditions are not correct, the following
screen is displayed a few seconds:

COMMAND REFUSED
TRANSFER IMPOSSIBLE

*

initial screen

34006452EN/AC

- Page 56

Following confirmation of the command, the system automatically
returns to the initial screen.

"Monitor" alphanumeric display
9.11 Language, display contrast and buzzer volume settings
These settings may be accessed by pressing the "settings" button.
The series of screens in the figure opposite is displayed.

Display of the settings selection screens

Direct access to the function by pressing the "settings" button.

LANGUAGE = ENGLISH
=CONFIRM.

*

Selection of the display language:
English, French, German, Italian, Spanish,
Dutch, Swedish, Finnish, Portuguese.

*
DISPLAY CONTRAST
>=SELECT
=CONFIRM.

*

This screen is a prompt to set the display contrast
by successively pressing the ">" button.
When the setting is confirmed by pressing
the "*" button, the system goes on to the buzzer.

*
BUZZER VOLUME
>=SELECT
=CONFIRM.

*

*

When this screen is displayed, the buzzer
automatically turns on. Press the ">" button
several times to adjust the volume. After confirmation
of the buzzer volume by the "*" button,
the system automatically returns to the initial screen.

initial screen

34006452EN/AC

- Page 57

"Monitor" alphanumeric display
9.12 Display system configuration
This function may be accessed from the initial screen. Press the "*" button, followed by the "V" button in less than one second.
Note:
– ensure that two "Monitor" or "Tele Monitor" units do not receive the same number;
– only one master "Tele Monitor" may be installed on the display network;
– this function may be accessed only with a password.

Display system configuration
initial screen

*

V

PASSWORD ?
=

This function may be accessed from the initial screen.
Press the "*" button, followed by the "V" button in less
than one second.
Enter the password (a combination of four buttons
among the control panel buttons). If the password
is incorrect, the system displays the following screen
for a few seconds:
INCORRECT
PASSWORD

then automatically returns to the initial screen.

DISPLAY = LOCAL
>=SELECT
=CONFIRM.

Selection of the type of display: local ("Monitor")
or distant ("Tele Monitor"). If the display is distant,
the local buzzer is deactivated.

DISPLAY = MASTER
>=SELECT
=CONFIRM.

Selection of display role on the network: master
(only one display may be the master) or slave.

*

*

if display
is master

if display
is slave

DISPLAY NUMBER =
>=SELECT
=CONFIRM.

*

CUBICLE N°
= YES
>=SELECT
=CONFIRM.

*

initial screen

Selection of the numbers of the slave displays controlled
by the master display. Ten display number are successively
presented. Select "yes" if the master display is to control
the slave display or "no" if it does not control the display
or if the display does not exist. Confirm using the "*" button.
The system goes on to the next display.

CUBICLE N°
= YES
>=SELECT
=CONFIRM.

Selection of the numbers of the cubicles controlled
by the display. Eight cubicle number are successively
presented. Select "yes" if the display is to control the cubicle
or "no" if it does not control the cubicle or if the cubicle does
not exist. Confirm using the "*" button. The system goes
on the next screen.

GIANT DISPLAY =YES
>=SELECT
=CONFIRM.

Confirmation as to whether the installation is equipped
with a giant screen. Following confirmation using
the "*" button, the system automatically returns
to the initial screen.

*

*

initial screen

- Page 58

Selection of the numbers of the cubicles that the display
must control. Ten cubicle numbers are successively presented.
Select "yes" if the display is to control the cubicle or "no"
if it does not control the cubicle or if the cubicle does not exist.
Confirm using the "*" button. The system goes on to the next
cubicle number. Following confirmation of the last cubicle
number, the system automatically returns to the initial screen.

DISPLAY N°
= YES
>=SELECT
=CONFIRM.

*

34006452EN/AC

Selection of the slave display number (multi-display installation)
from 1 to 10.

10. Options
10.1 "LED" signalling box
This unit remotes the basic elements of information on system status:
– load on battery;
– low battery shutdown warning;
– inverter stop;
– general alarm.
Used for basic remote monitoring, it includes a buzzer with a reset button and an indication light test button.
It is also equipped with a battery to ensure correct operation in the event of a power supply problem.

test

10.2 "Tele-Monitor" remote indications unit
This unit is the remote version of the optional alphanumeric display installed on the UPS or Static Switch Cubicles.
It offers the same functions (see the "Monitor alphanumeric display" section).
Two units may be remotely installed, in which case:
– one unit is the master with all the indications and control functions;
– the other is the slave with only indications functions.

10.3 "GTC link" communications system
The "GTC link" is a communications system comprising both hardware and software for transmission to a computer system,
such as a Building and Energy Management (BEM) system, of information on the MGETM GalaxyTM 9000 operating status and
reception of the On/off and self-test remote controls.

34006452EN/AC

- Page 59

Options
10.4 "Vision" display
The "Vision" display may be installed in all types of cubicles (UPS or Static Switch Cubicle).
The "Vision" display can operate in two different modes:
– mono-cubicle: the "Vision" display monitors only the cubicle in which it is installed;
– multi-cubicle: "Vision" display can monitor all system cubicles (up to eight maximum). In this mode, the system is equipped
with only one "Vision" display which may be installed in any of the cubicles.

0 Hour 50 Min.
100%

MGE GALAXY 9000 800 kVA
SALLE IQ

125 kVA
120%
100%
80%

50%

Home

0
Available Backup Time

Online
Trend
Statistics

50%

Load protected

Alarms

Q1

0
Load level

Q5N

Normal AC

Load
equipment

Rectifier

QF1

Battery
Inverter
Bypass

Q4S
Bypass AC

Output
Q3BP

Set up

15:24:32 30/05/2005

10.5 "Remote vision" display
Installed in a special enclosure, the "Remote vision" display provides the user with remote indications on system status.

0 Hour 50 Min.
100%

MGE GALAXY 9000 800 kVA
SALLE IQ

125 kVA
120%
100%
80%

50%

Home
Alarms

0
Available Backup Time

Online
Trend
Statistics

50%

Load protected

Q1

0
Load level

Q5N

Normal AC

Load
equipment

Rectifier

QF1

Battery
Inverter
Bypass

Q4S
Bypass AC

Output
Set up

Q3BP

15:24:32 30/05/2005

10.6 Insulating and Mains 1, Mains 2 and load voltage matching transformer
This transformer may be used to match Mains 2 voltage to that of the inverter, to create galvanic insulation between the load
and the Mains or to create the appropriate neutral system.

34006452EN/AC

- Page 60

Options
10.7 Double bridge rectifier-charger
This option reduces the reinjection of harmonic disturbances into Mains 1, but to a lesser extent than the harmonics filter.
The double bridge rectifier-charger replaces the MGETM GalaxyTM 9000 UPS's standard input rectifier-charger.

10.8 Battery "Temperature Monitor"
An electronic PC-board measures the battery temperature. The rectifier/charger uses this information to adjust the battery
charge current to the temperature in view of:
– optimizing battery recharge;
– obtaining maximum battery time;
– ensuring maximum battery life.

10.9 Empty cubicles
Cubicles may be supplied empty, thus enabling users to make up their own auxiliary cubicles (battery cubicles or other) or
panels and meet the particular demands of each installation. In this way, the entire electrical installation will have a uniform
appearance.

34006452EN/AC

- Page 61

34006452EN/AC



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
Page Count                      : 62
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:39b088db-f831-426d-9e03-920c1454856b
Producer                        : Acrobat Distiller 6.0 (Windows)
Create Date                     : 2008:11:06 11:34:08+01:00
Modify Date                     : 2008:11:06 11:34:08+01:00
Document ID                     : uuid:09aa436d-69f7-4ecb-ba96-e07194f2eb25
Format                          : application/pdf
Title                           : untitled
EXIF Metadata provided by EXIF.tools

Navigation menu