Apollo Fire Detectors SMKT3345 Wireless Smoke Heat Alarm User Manual 2GIG Wireless Smoke Heat Alarm IG 688 Issue A indd

Apollo Fire Detectors Limited Wireless Smoke Heat Alarm 2GIG Wireless Smoke Heat Alarm IG 688 Issue A indd

Users manual

Wireless Smoke Heat AlarmInstallation Guide ATTENTION: This manual should be read prior to use and retained for further information.GENERAL INFORMATIONThe Wireless Smoke Heat Alarm, part number 2GIG-SMKT3-345 is a 3xAAA battery powered wireless detector intended for use with wireless alarm systems. The detector has a built-in wireless transmitter, which communicates with the control panel. When smoke is detected, the alarm sounds a loud local alarm and the built-in transmitter sends a signal to the control panel.The 2GIG-SMKT3-345 contains an integrated fi xed 41°F temperature freeze sensor that will send a warning signal based on temperature detected. This detector is designed to provide protection with 70-foot spacing capability. The detector can send alarm, tamper and battery condition messages to the system’s receiver. Refer to the wireless system’s instruction for the maximum number of transmitters that can be supported.CONTENTS OF BOX:- Wireless Smoke Heat Alarm with base- Installation guide- Pack of screws and fi xings- Stickers as appropriate- 3 AAA PC2400 Duracell Procell batteries (1.5V 1100mAh)  or 3 AAA Energizer E92 batteries (1.5V 1100mAh)1The Wireless Smoke Heat Alarm contains a sounder which generates the ANSI S3.41 temporal 3 pattern in an alarm condition.In alarm, a message is also sent to the control panel and the detector’s ID is displayed at the console. During an alarm condition, pressing the detec-tor’s hush button will silence the sounder (see table below). The mounting base installation is simplifi ed by the incorporation of features compatible for both drywall fasteners (not supplied) and other methods.Tricolored LED (red, yellow, green) and a sounder on the detector provide local visual and audible indication of the detector’s status as listed in Table 1.During initial power-up the LED blinks alternately red, yellow then green. It takes about 8 seconds for the detector to stabilize.After power-up has completed and the detector is functioning normally, the green LED blinks once every 12 seconds.Detector Trouble: When the detector has a general fault, the yellow LED blinks once every four seconds and there is a chirp every 48 seconds. After 12 hours the panel will display a loss of supervision message.Detector Dirty Feature: When the detector has been contaminated, the yellow LED blinks once every 8 seconds and there is a chirp every 48 seconds. Refer to MAINTENANCE section for cleaning your alarm. After 12 hours the panel will display a loss of supervision message.Low Battery Detection: The Wireless Smoke Heat Alarm is powered by 3 AAA Duracell Procell or 3 AAA Energizer E92 batteries (included). The detector regularly checks for a low battery. If a low battery is detected, the transmitter sends a low battery message to the control panel, which displays the detector’s ID at low battery. In addition, the yellow LED of the detector will blink every 12 seconds. The detector’s sounder will chirp every 48 seconds (yellow LED continues to blink) until the batteries are replaced. Pressing the hush button will silence the chirps for 12 hours, if no other trouble conditions exist. The batteries should be replaced WHEN the chirps begin. Be sure to replace the batteries with fresh ones.BATTERY INSTALLATION AND REPLACEMENTTo replace the batteries:1. Remove the detector from its mounting base by twisting the detector counterclockwise. Remove and dispose of the batteries according to your local regulations.2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new batteries.3. Install 3 new AAA batteries (available from your local Duracell or Ener-gizer dealer) in the battery compartment. Follow the polarity diagram inside HUSH/TEST BUTTONBATTERY COMPARTMENTFig 1. Wireless Smoke Heat AlarmTable 1. Detector status and indicationStatus LEDs Sounder(do not pulse the sounderand LED concurrently)2Gig Control Panel responseNormal Green fl ash every 12 seconds Off Normal (None)Heat Alarm Red fl ash every 1 secondANSI S3.41 temporal 3 (press button to hush for 5-10 minutes)On screen and audible Alarm (user code to silence)Heat Test Red fl ash every 1 secondANSI S3.41 temporal 3 (press button to hush for 5-10 minutes)On screen and audible Alarm (user code to silence)Smoke Alarm Red fl ash every 1 secondANSI S3.41 temporal 3 (press button to hush for 5-10 minutes)On screen and audible Alarm (user code to silence)Smoke Test Red fl ash every 1 secondANSI S3.41 temporal 3 (press button to hush for 5-10 minutes)On screen and audible Alarm (user code to silence)Test Alarm Red fl ash every 1 secondANSI S3.41 temporal 3 (press button to hush for 5-10 minutes)On screen and audible Alarm (user code to silence)Freeze Warning 3 yellow fl ashes every 4 seconds Off On screen and audible Alarm (user code to silence)Detector Trouble Yellow fl ash every 4 seconds One chirp every 48 secondsOn Screen Alert shown (after 12 hours) “Device name” - Loss of Supervi-sionLow Battery Yellow fl ash every 12 secondsOne chirp every 48 seconds (press button to hush for 12 hours)On screen Alert shown “Device name “- Battery lowDetector Dirty Yellow fl ash every 8 seconds One chirp every 48 secondsOn Screen Alert shown (after 12 hours) “Device name” - Loss of Supervi-sionPower-up Red, yellow, green fl ash sequence One chirp at the end of power-up sequence Normal (None)TamperRed, yellow, green fl ash sequence every 12 secondsOff On screen Alert shown “Device name “- TamperIF THE ALARM SOUNDS• if the smoke alarm sounds, get out and stay out. Never go back inside for people or pets.• if you have to escape through smoke, get low and go under the smoke to your way out.• Call the fi re department from outside your home.FOR MORE SAFETY INFORMATION SEE THE WEBSITE: www.nfpa.org/educationSPECIFICATIONSTransmitter Frequency: 345.000 MHz (crystal controlled)Transmitter Frequency Tolerance: +- 15 kHzTransmitter Bandwidth: 24 kHzModulation Type: Amplitude Shift Keying - On/Off Keying (ASK-OOK)Unique ID Codes: Over one (1) billion different code combinationsSupervisory Interval: 70 minutesDimensions: Ø 5’’ x 2.5’’ high (Ø 125mm x 63mm high)Weight (including battery): 8.57 oz (243 g)Color: WhiteSpacing rating: 70ftAudible Signal (Temp 4 tone): 85dBA min. in alarmOperating Current: 20 uA maxOperating Temperature: 40°-100°F (4.4°-37.8°C)Relative Humidity: 15-90% Non-CondensingBattery (included): Three (3) AAA PC2400 Duracell Procell or three (3) AAA Energizer E92 batteries Regulatory Listing: UL 217, UL 539 Warranty: Two (2) yearsIncluded Accessories: Mounting Hardware PackageFOR MORE INFORMATION REFER TO TECHNICAL BULLETIN PP 2439.REGULATORY INFORMATIONNOTICE: Unauthorized changes or modifi cations could void the user’s authority to operate the equipment.This device complies with Part 15 of the FCC Rules and Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation of the device.This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particu-lar installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:• Reorient or relocate the receiving antenna.• Increase the separation between the equipment and the receiver• Connect the equipment into an outlet on a circuit different from that to              which the receiver is connected.• Consult the dealer or an experienced radio/television technician for helpLIMITED WARRANTYThis 2GIG Technologies product is warranted against defects in mate-rial and workmanship for two (2) years. This warranty extends only to wholesale customers who buy direct from 2GIG Technologies or through 2GIG Technologies’ normal distribution channels. 2GIG Technologies does not warrant this product to consumers. Consumers should inquire from their selling dealer as to the nature of the dealer’s warranty, if any. There are no obligations or liabilities on the part of 2GIG Technolo-gies for consequential damages arising out of or in connection with use or performance of this product or other indirect damages with respect to loss of property, revenue, or profi t, or cost of removal, installation, or reinstallation. All implied warranties, including implied warranties for merchantability and implied warranties for fi tness, are valid only until warranty expires. This 2GIG Technologies Warranty is in lieu of all other warranties express or implied.All products returned for warranty service require a Return Product Authori-zation Number (RPA#). Contact 2GIG Technologies at 1-866-670-1591 for an RPA# and other important details.Warranty service return address: see below.Technical Support Contact Information Toll Free:1-855-2GIGTECH / 1-855-244-4832Email: techsupport@2gig.comInternet: www.2gig.com2GIG Technologies, Inc.2961 W Maple Loop Drive,Lehi, Utah 84043439214-688/2012/Issue A
23the compartment. If the batteries are incorrectly inserted please remove gently with a non-conductive tool and correctly reinsert.4. Reinstall the detector onto the mounting base by turning the detector clockwise until the mating marks align.5. After the power-up sequence the green LED should blink about once every 12 seconds to indicate normal operation. If the batteries are not installed correctly, the detector will not operate and the batteries may be damaged. If the detector does not  power-up, check for correct batteries installation and for a fully charged batteries6. Test the detector (as described later).CONSTANT EXPOSURES TO HIGH OR LOW TEMPERATURES OR HIGH HUMIDITY MAY REDUCE BATTERY LIFE.PROGRAMMINGBefore testing the detector, the internal wireless transmitter must be pro-grammed into the control panel.1. Refer to the control panel’s instructions to program the receiver with the detector’s serial number (TX ID from the label).2. Press the detector’s ALARM/TEST button for 4 seconds. The detector will perform a sounder test, a sensitivity test, and send a test signal to the control panel.3. Verify that the signal was received by the control panel.4. Exit control panel programming before testing the detector.RECOMMENDED LOCATIONS FOR SMOKE HEAT ALARMAccording to National Fire Protection Association (NFPA) the major threat from fi re in a dwelling unit occurs at night when everyone is asleep. The principal threat to persons in sleeping areas comes from fi res in the remainder of the unit; therefore, a smoke detector(s) is best located between the bedroom areas and the rest of the unit. In units with only one bedroom area on one fl oor, the smoke detector(s) should be located as shown in Figure 2. In dwelling units with more than one bedroom area or with bedrooms on more than one fl oor, more than one smoke detector is required, as shown in Figure 3.In addition to smoke detectors outside of the sleeping areas, the device should be installed on each additional story of the dwelling unit, including the basement. These installations are shown in Figure 4. The living area smoke detector should be installed in the living room or near the stairway to the upper level, or in both locations. The basement smoke detector should be installed in close proximity to the stairway leading to the fl oor above. Where installed on an open-joisted ceiling, the detector should be placed on the bottom of the joists. The detector should be positioned relative to the stairway so as to intercept smoke coming from a fi re in the basement before the smoke enters the stairway.Smoke detectors are optional where a door is not provided between living room and recreation room (Figure 5).The smoke from a fi re generally rises to the ceiling, spreads out across the ceiling surface, and begins to bank down from the ceiling. The corner where the ceiling and wall meet is an air space into which the smoke could have diffi culty penetrating. In most fi res, this dead air space measures about 0.1m (4in.) along the ceiling from the corner and about 0.1m (4in.) down the wall. Detectors should not be placed in this dead air space, see Figure 6,7 and 8.Where NOT to install the alarm:- Directly above a sink, cooker, stove or oven- Do not locate detector within 5 feet (1.5 m) of any cooking appliance- Next to a door or window that would be affected by drafts i.e. extractor fan or air vent- Outside- Do not install in any environment that does not comply with the detector’s environmental specifi cationsBedroomLiving roomRecreation roomBedroomBasementIndicates optional smoke alarm where a dooris not provided between living room and recreation roomIndicates required smoke detectorHallDining roomKitchen BedroomBedroomBedroomLiving roomTV roomDining room KitchenLiving roomBedroomBedroomBedroomBedroom  Living room Dining roomBasementHall BedroomCeilingAcceptable hereNever hereTop of detectoracceptable hereSidewall100 mm (4 in.)100-mm(4-in.) minimum300-mm(12-in.)maximumNote: Measurements shown are to the closest edge of the detector.Anywhere inthis areaNot in this area 900 mm(36 in.)  900 mm(36 in.) 102 mm (4 in.)900 mm (3 ft)102 mm (4 in.)Not in this areaAnywhere inthis areaFig 5. Split level arrangementFig 2. Location of the detectors in units with only one bedroom area on one fl oorFig 3. Location of the detectors in dwelling units with more than one bedroom area or with bedrooms on more than one fl oorFig 4. Detector located on each storyFig 6. Example of proper mounting for detectorsFig 8. Example of proper mounting for                  detectors with peaked ceilingsFig 7. Example of proper mounting for detectors with sloped ceilingsrecommended for verifying system protection capability. Direct Heat Method (Hair dryer of 1000-1500 watts) Direct the heat toward the thermistor. Be sure to hold the heat source about 12 inches from the detector to avoid damage to the plastic. The detector will reset only after it has time to cool. A detector that fails to activate with any of these tests should fi rst be cleaned as outlined in this manual’s MAINTENANCE section. If the detector still fails to activate, return for repair.MAINTENANCETEST ONCE A WEEK.WARNING! USE ONLY BATTERIES SPECIFIED. USE OF DIFFERENT BATTERIES MAY HAVE A DETRIMENTAL EFFECT ON THE SMOKE ALARM.YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR.To clean your alarm, remove it from the mounting base. You can clean the interior of your alarm by using compressed air or vacuum cleaner hose and blowing or vacuuming through the openings around the perimeter of the alarm. The outside of the alarm can be wiped with a damp cloth.After cleaning, reinstall and test your alarm by using the test button. If cleaning does not restore the alarm to normal operation the alarm should be replaced.WARNING: PLEASE READ CAREFULLY AND THOROUGHLY• NFPA 72 states: Fire-warning equipment for residential occupancies are capable of protecting about half of the occupants in potentially fatal fi res. Victims are often intimate with the fi re, too old or too young, or physically or mentally impaired such that they cannot escape even when warned early enough that escape should be possible. For these people, other strategies such as protection-in-place or assisted escape or rescue would be neces-sary. • A battery powered alarm must have a battery of the specifi ed type, in good condition and installed properly.• Smoke alarms must be tested regularly to make sure the batteries and the alarm circuits are in good operating condition.• Smoke alarms cannot provide an alarm if smoke does not reach the detector. Therefore, smoke alarms may not sense fi res starting in chimneys, walls, on roofs, on the other side of a closed door or on a different fl oor• If the alarm is located outside the sleeping room or on a different fl oor, it may not wake up a sound sleeper.• Studies have shown that smoke and heat alarms may not awaken all sleeping individuals, and that it is the responsibility of individuals in the household that are capable of assisting others to provide assistance to those who may not be awakened by the alarm sound or those who may be incapable of safely evacuating the area unassisted.• The use of alcohol or drugs may also impair one’s ability to hear the smoke alarm. For maximum protection, a smoke alarm should be installed in each sleeping area on every level of a home.• Although smoke alarms can help save lives by providing an early warning of a fi re, they are not a substitute for an insurance policy. Home owners and renters should have adequate insurance to protect their properties.FAMILY ESCAPE PLANAccording to National Fire Protection Association (NFPA) there often is very little time between the detection of a fi re and the time it becomes deadly. This interval can be as little as 1 or 2 minutes. Planning and practicing for fi re conditions with a focus on rapid exit from the residence are important. Drills should be held so that all family members know the action to be taken.SAFETY TIPS • Make a home escape plan. Draw a map of your home showing all doors and windows. Discuss the plan with everyone in your home.• Know at least two ways out of every room, if possible. Make sure all doors and windows leading outside open easily.• Have an outside meeting place (like a tree, light pole or mailbox) a safe distance from the home where everyone should meet.• Practice your home fi re drill at night and during the day with everyone in your home, twice a year.• Practice using different ways out.• Teach children how to escape on their own in case you can’t help them.• Close doors behind you as you leave.TESTING THE DETECTORNOTE: Before testing, notify the central station that the detector system is undergoing maintenance in order to prevent unwanted alarms. Testing the detector will activate an alarm and send a signal to the panel. Also, the test function cannot be used if the detector has a trouble condition.Detectors must be tested after installation and following periodic mainte-nance.Testing Detector OperationThis test checks the detector’s sounder, LEDs, and transmitter.1. The test button is located on the detector housing.2. Push and hold the test button for a minimum of 5 seconds. The alarm panel will trigger and then the detector will go into alarm. The sounder begins the temporal 3 pattern and the red LED blinks. The alarm panel’s console should display the detector’s name in alarm.Smoke Test Hold a smouldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit alarms. Canned smoke aerosol is also an acceptable method. Smoke detection testing is - In or below a cupboard- Where air fl ow would be obstructed by curtains or furniture- Where dirt or dust could collect and block the sensor- Where it could be knocked, damaged, or inadvertently removedThis detector shall not be installed in location where the normal ambient temperature is below 40°F (4.4°C) or where it exceeds 100°F (37.8°C).THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION’S STANDARD 72.MOUNTING THE DETECTORNote: These alarm devices should only be installed by a competent engi-neer.This device should not be used with a guard.Once a suitable location is found, mount the detector as follows:1. Refer to the diagram below and install the mounting base on the ceiling or on the wall (if local ordinances permit) using screw locations as required. Use the two screws and anchors provided. Maneuver the base so the screws are at the elbow of the screw slots and secure.2. Fit the detector inside the base by aligning it over the base as shown (detector’s alignment notch should be slightly offset from mounting base tamper release tab), then turn the detector in a clockwise direction until it clicks into place.3. Test the detector after completing the installation (as described in the TESTING THE DETECTOR section of this manual) and refer to the control system’s instructions for additional information concerning the use of wire-less devices.DO NOT attach the detector to removable ceiling panels. 100 mm (4 in.) minimum100 mm (4 in.) minimumFig 9. Mounting the detector

Navigation menu