SENTINEL-PROX SR—2400
DOORFRAME PROXIMITY READER
Installation & Operation Manual - 002-98-A
Your best option for Proximity Access Control
Last Update: February 4, 1999
APPLIED menus m
“Hub Applied Wireless Identifications Group, Inc.
Table of Contents
1.0 Introduction .................
1.1 General Description.
12 Special Features ......
1.3 Suggested Applications, 0
20 Principal of Operation.
3.0 Specifications ............
3.1 Measuring Read Distance.
4.0 Preparation for Installation ..........
4.1 Site Survey .........................
4.2 General Good Reader Installation notice,
4.3 Metal Mounting ...................
4.4 General Wiring Requirements.
4.5 Power Supply..
46 Grounding ......
4.7 Wiring Diagrams.
5.0 Installation Prowdurm .
5.1 PansList.
52 Installation Steps.
5,3 Verification.
5.4 Mounting,
6.0 Warranty ...........
70 Return Material Authorization (RMA).
8.0 Troubleshooting ...........
9.0 Patents and Approvals .....
wmmwwflqmmomommmhaaauwwww
NOTE: READ AND USE THIS MANUAL.
FAILURE TO D0 80 MAY RESULT IN POOR READER PERFORMANCE OR EVEN
PERMANENT DAMAGE TO READER, WHICH COULD VOID THE READER
WARRANTY.
List of Table
Table 44-1: Data Line’s Wiring Distance Requirement .................................. Page 5
List of Figures
Figure 5.2—1: Wiring Diagram for Wiegmd Output Format ............................... Page 7
upueo winsz in AWID PROPRIETARY
1.0 INTRODUCTION:
AWl D's Sentinel—Prox SR-2400 Reader is one of the best performing Proximity Readers in the
industry. This Reader is designed to send out Vtfiegand format output and is pre-compensated
for mounting on metal. Its primary application is for access control.
1.1 General Descriptions:
. ADA oompliantdesign . LED visual indicator
. Indoor or outdoor installation . Audible feedback
1.2 Special Features:
. Pre—compensated for mounting on metal with minimum impact on read range
. Slim housing design
- Permanently sealed electronics for outdoor application
- UV stabilized plastic housing
1.3 Suggested Applications
~ Access Control . Time & Attendance
Asset Management 0 RFID
2.0 PRINCIPAL OF OPERATION
This Radio Frequency Identification (RFID) reader or proximity reader uses radio frequency to
identify, locate and track people and objects that carry the appropriate transponders. Proximity
reader can work in none Iine—of-sight situations and in darkness, bright sun light or through din,
grimes and smudges.
A typical proximity system consists of three components — an interrogator or a reader, a
transponder or a card and a data processing panel and/or computer combination. Most RFID
reader has an internal micro-controller, a transmitter, a receiver and a shared transmit/receive
antenna. The card is usually passive (without an internal battery) and consists of an antenna
and an RFID ASIC (Application Specific lC). During operation, the transmitter sends out an
electromagnetic wave to establish a zone of surveillance. When a cord enters this zone, the
electromagnetic energy from the reader begins to energize the IC in the tag Once the IC is
energized, it goes through an initialization process and begins to broadcast its identity. This
process utilizes a low energy back-scattenng technology that selectively reflects or back-
scatters the electromagnetic energy back to the reader. The receiving circuits in the reader
senses and decodes this back»scattered signal and hence determines the identity of the tag.
APPLIED MEL!“ 1: AWID PROPRIETARY
3.0 SPECIFICATIONS
— input voltage... ___ +5V to +12V
- input current... ...40 to 80 mA typical
— Read range:
Prox—Linc-GR.... ..Up to 4 inches (20 cm)
Prox-Linc-CS. ..Up to 4 inches (20 cm)
- Transmit frequency. 125KHz (CW)
- Receiver frequency ......... .125KHz (Amplitude Modulated)
-30° C to +65” C
.Dark Gray or Beige
. ...Wregand (Standard)
(Others are available upon request)
- Operating temperature range.
— Color .....
- Output forma s avar a e...
3.1 Measuring Read Distance
To measure the read range between Reader and card, grasp the card by the corner or near the
slot and move the card slowly toward the Reader, with the card surface parallel to the Reader,
until a BEEP occurs. The BEEP indicates that the Radar detects and reads the card. In order
to read again, the card must be fully withdrawn from the Reader’s read field and then re-
approached again. During normal operation, the card can be presented at any angle relative to
the Reader, however this will result in slight variation of read range.
Note: Do not "waved" the card in front of the Reader. “Waving" the card in front of the
Reader will cause diminishing read range.
NOTE: FAILURE TO FOLLOW THE INSTALLATION GUIDE MAY RESULT IN POOR
PERFORMANCE OR EVEN CAUSE PERMANENT DAMAGE TO THE READER.
THUS, VOIDING THE PRODUCT WARRANTY.
4.0 PREPARATION FOR INSTALLATION
4.1 Site Survey:
Always conduct a site survey before starting installation, avoid any possible sources of
interference. If the Reader is not installed properly, the performance will be degraded or more
seriously the Reader may be damaged. The following is a list of installation procedures that
should be followed during installation:
0 Do not install the Reader in the vicinity where sources of broadband noise may exist.
Examples of broadband noise sources are motors, pumps, generators, DC-AC or DC-AC
converters, non-intenuptible power supplies, AC switching relays, light dimmers, CRT's,
induction heater etc.
0 Do not let the Reader wiring bundle togemer in one conduit with the AC power cables,
lock power, and other signal wiring.
APPLIED WIRELESS ID AWID PROPRIETARY
. Keep all the Reader wiring at least 12 inches (30 cm) away from all other wiring, which
include but not limited to, AC power, computer data wiring, telephone wiring and wiring to
electrical locking devices.
. Do not install the reader within 12 inches (30 cm) of a computer CRT terminal.
4.2 General Good Reader Installation Practice
. Make sure that the supply voltage of the Reader is within specification. As a rule of
thumb, higher supply voltage (not to exceed 12V) results in longer read range but at the
expense of higher power consumption.
Use cables with over-all shield (Screen).
For best result, run the cable in an individual conduit with at least 12 inches distance
away from the Ac power, computer data cables and cables for electrical locking devices.
Use recommended cable. Do not use any Lin-shielded "Twisted Pair" type cable.
Use the largest wire gauge possible.
Use dedicated and linearly regulated power supply, where applicable.
Use Single Point Grounding (Earthing). No ground loops.
4.3 Metal Mounting
The Reader is pre-compensated for mounting on metal; they can be mounted on any materials,
including metals such as aluminum and steel door-frame with minimum loss in performance.
However, the Reader should not be framed within or surrounded by metal of any kinds. lf the
Reader is installed in a metal enclosure, such as a parking station, ensure that the metal stands
off at least 2.0 inches (5 em) on all sides and does not cover up the front face.
4.4 General Wiring Requirements
All the Reader wiring must be continuously shielded. AWID recommends using #22 AWG up to
#18 AWG, six or seven-conductor shielded cables. Longer distances and higher current
consumption on the power supply line will require larger gauge wires. Refer to Table 4.4-1 and
Figure 52-1 and Figure 52-2 on the following pages to determine your data lines” wiring
requirement. Due to system data termination differences, contact your panel manufacturer for
their specific requirements.
TABLE 4.44: Data Line’s Wiring Distance
WIRE SIZE #22 AWG (0.6mm Big) #18 AWG (1.2mm Dia)
WElGAND 270ft 85meters 980ft 300 meters
RS—232 m- 45“ 15W--. . .
APPLIED wmsLess n AWID PROPRIETARY
NOTE: WHEN USING AN EXTERNAL POWER SUPPLY, ALWAYS USE A LINEAR POWER
SUPPLY, DO NOT USE SWITCHING POWER SUPPLY.
4.5 Power Supply
The operating frequency of a typical switching power supply ranges from 15 KHz to 50 KHz. It
will usually generate vvideband switching noises plus some of its harmonics may fall on or near
125 KHz, the operating frequency of the Reader. Therefore, avoid using a switching power
supply at all times. AVOID using a single power supply for Reader and the magnetic look.
Doing so will affect the Reader operation and an damage the Reader.
4.6 Grounding
Grounding is critical for proper operation of the Reader. When installing the Reader, it is crucial
to assure that the earth ground is the best ground available. If you elect to use the AC main
power ground, conduct a test by measuring its resistance relative to a known good ground, such
as a cold water pipe or a structural steel that is in direct contact with the ground. The resistance
should be less than 50 ohms. If you find that the AC main power does not provide adequate
earth ground, try using a solid connection to a cold water pipe.
For multiple Readers installation, it is critical that all Readers are connected to the sarrre
grounding system. Using different grounding systems will create secondary current paths or
ground loops that can affect the performance and cause damage to the Reader.
4.7 Wiring Diagrams
The Reader is designed for Wiegand and RS-232 standard communication formats; use Figure
5.2-1 for Wiegand format installation and Figure 5.2-2 for RS—232 format installation. If an
external power supply is being used, leave the Panel’s Ground and Power terminals open and
connect the Reader's Ground (Black) and 5—12VDC (Red) terminals to the external power
supply.
5.0 INSTALLATION PROCEDURE
Check to verify that every item listed under Section 5.1 of this manual is present before starting
the installation.
5.1 Pans List
a. Installation sheet, PIN: 002-97-A QTY=1
b. Sentinel-Prox SR-2400 Reader. PIN: 002—20—A QTY=1
c. #8-32x1” Thread-cutting screw, Type 23, PIN: 616PPN23ZP QTY=2
d. Screw hole plug, PIN: 002-27—A QTY=3 (1 spare)
Apmspwrwsrsss ID AWID PROPRIETARY
5.2 Installation Steps
FTP-“53.09.55“
Position the Reader (Item b on Parts List) at the appropriate mounting position
Use Figure 1 of the Installation sheet (Item a. on Parts List) as template for drilling holes.
Position the template at the same location as the Reader.
Drill two 7/64 (0.109)-inch holes as shown on the template.
Drill one clearance hole for the mole and wiring lugs.
Install a bushing or grommet to provide a smooth edge around the clearance hole.
Guide the open end of the Panel‘s control cable through the clearance hole.
Connect the Reader and the Panel together according to Figure 52-1.
5.3 Verification
a.
b.
Power up the PANEL, the LED on the Reader should show RED.
Place a “good" card in front of the Reader. The reader will give out “ONE” audible BEEP
and the LED will change from RED to AMBER momentarily and than flashing between
RED & GREEN. The reader will stay flashing until the panel sends an acknowledgement
or until the card is removed from the reader. You can repeat this action by placing the
card in front of the reader after the LED turned RED. If the Panel did not send a logic
"HIGH" LED (brown) command to the reader, the reader will “latched” and must be
powered off to re initialize.
Fig. 5.2-1 Wring Diagram for Wlegand Output Format
(ORANGE)
(VIOLET)
(BLUE)
(BROWN) LED
(WHITE) DATA]
(GREEN) DATAO
(BLACK) GROUND
(RED) POWER
(DRAIN) CHASSIS GROUND
GROUND
n I" I D AWID PROPRIETARY
nun MREIESS m
5.4 Mounting
a. Mount the Reader to the doorframe with the #6—32x1' Thread—cutting screw, Type 23
(Item 0 on Parts List).
b. Insert the Screw hole plug (Item d on Parts List) into the screw clearance holes to
conceal the screws.
6.0 WARRANTY
AWID‘s products are warranted to the original purchaser to be free of defects in material and
workmanship for the life of the product. Any tampering or modification to the product will void
this product warranty. AWID does not warrant any product as to its merchantability or suitability
of use. AVWD's sole and complete responsibility under this warranty is expressly limited to
repair or replacement of the warranted product.
7.0 RETURN MATERIAL AUTHORIZATION (RMA)
AWID monitors and tracks the life cycle performance of our product through our RMA system.
All customers must obtain a RMA number from AINID Customer Service Department prior to
returning the merchandise. After the customer provides AWID Customer Service Department
with the serial number and a description of the returning item, a RMA numberwill be issued.
This RMA number must be clearty merited on the outside of the returned package and
noted on the papenrvork attached to the returned merchandise.
When obtaining a RMA number for RFID tags, please provide AWID Customer Service
Department with the serial numbers, card identification numbers, facility codes and etc. If exact
duplicates of returned cards or tags are requested, the customer must provide AWID with the
numbers needed. AWID reserves the option to replace or repair returned merchandise.
Items returned to AWID without the proper authorization will be returned to the originators at
their own expense.
8.0 TROUBLESHOOTING
This unit, if not installed in strict compliance with AWID’s installation instmctions, may not
function to specifications. Use the checklist below to identify the problem:
Is the card valid and working? - Try some different cards!
Is the reader wired correctly? - RED-BLK :5-12V, BWN—BLK: 5V, reader should work
Is the unit grounded properly? - DRAIN-EARTH: less than 50 Ohms
Is the card presented correctly? - Card face parallel to reader face
Is a power supply correct? - No switching power supply please!
ls reader voltage/current correct? — 5—12V @ 40-100mA typical
Is the environment free from electromagnetic interference? » Run cable away from other
data carrying cables, reader away from electromagnetic interference sources!
APPLIED wlRELEss p AWID PROPRIETARY
When troubleshooting, try to identify the source of the problem to a unit level. “Is the problem
from the panel?" or “is the problem originated from the Reader? “ Maybe the problem “is the
power supply?"
All AWlD’s readers will need only a power supply and a valid card to work properly. If the
reader is only connected with RED (+5-12V) and BLACK (Ground), the reader will BEEP and
momentarily turned AMBER, when a valid card is presented. If the Card stays within the reader
zone of surveillance, the LED on the reader will become flashing GREEN. When the card is
removed, the LED will return to RED, signifying it has returned to stand—by mode. When the
reader works according to the tests above, the reader is working properly.
To check the validity of the output data in the absence of a panel, you will need to build a patch
cable between the reader and a PC. Call AWID’s technical support for details.
If problem persists, consult the system manufacturer. If problem is the reader, consult AWID’s
Technical Assistance Department. AWID help desk is opened from 8:00 AM to 8:00 PM
Eastern Standard Time, and can be reached by dialing 1-800-369-5533.
9.0 PATENTS AND APPROVALS
AWID products are covered by United States patent #5594384.
AWID logo is a registered trademark of Applied Wireless Identifications Group, Inc.
Where required, AWID’s products will be approved by the appropriate regulatory agendas:
U. 8. Federal Communications Commission: Part 15
Underwriter Laboratory: UL 294
Designed to Comply with: CE, UL, VDE, BZT, DTI 8. PTT
Information To The User
This device complies with part 15 of the FCC Rules. Operation is subject to the following tow
conditions: (1) this device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired operation,
Arman ”REL-“5 no AWID PROPRIETARY

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : Yes
Create Date                     : 2001:06:28 15:06:57
Producer                        : Acrobat Distiller 4.0 for Windows
Modify Date                     : 2001:06:28 15:06:59-04:00
Page Count                      : 9
EXIF Metadata provided by EXIF.tools
FCC ID Filing: OGSSR2400

Navigation menu