BECKETT Burner, Furnace Manual L0805076
User Manual: BECKETT BECKETT Burner, Furnace Manual BECKETT Burner, Furnace Owner's Manual, BECKETT Burner, Furnace installation guides
Open the PDF directly: View PDF .
Page Count: 32
Download | |
Open PDF In Browser | View PDF |
Fire, Explosion and Asphyxiation Hazards Failure to follow these instructions exactly could lead to fire or explosion death, severe personal injury or property damage. and result in 1. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appli= ance. 2. What to do if you smefl gas: • Do not try to light any appliance. • Do not touch any electrical switch. • Do not use any phone in your building. • Immediately call your gas supplier from a telephone outside the building. • Follow the gas supplier's instructions. • Call the fire department if you cannot contact your supplier. 3. Installation and service must be performed by a qualified installer, service agency, or the gas supplier. 6104 BOGS0 RoB 11 Table of Contents Please...read this page first Hazard Definitions ............................................................................................................................................................. To the Owner ..................................................................................................................................................................... To the Installer ................................................................................................................................................................... Warranty 3 Pre-instatlation checklist ......................................................................................................................................................... Indoor Installation .............................................................................................................................................................. Combustion air supply ....................................................................................................................................................... Clearances ........................................................................................................................................................................ Fuel gas supply ................................................................................................................................................................. Flue vent system ............................................................................................................................................................... Electrical supply ................................................................................................................................................................. Figure 1 - Burner nameplate ............................................................................................................................................. Verify burner components .................................................................................................................................................. Verify firing input range ...................................................................................................................................................... Figure 2 - Minimum combustion chamber dimensions ..................................................................................................... Verify burner air tube assembly ......................................................................................................................................... Figure 3 - Maximum capacity vs furnace pressure, Step spud ......................................................................................... Figure 4 - Maximum capacity vs furnace pressure, Swirler head ..................................................................................... Figure 5 - Burner dimensions ........................................................................................................................................... Mount the burner .................................................................................................................................................................... Figure 6 - Custom mounting plate .................................................................................................................................... Connect gas piping ................................................................................................................................................................. Figure 7 - Typical gas piping layout .................................................................................................................................. Table 1 - Gas supply piping capacity ................................................................................................................................ Gas trains 9 Figure 8 - UL gas train configuration ................................................................................................................................ Wire the burner ..................................................................................................................................................................... Figure 9- Typical burner wiring ...................................................................................................................................... Sequence of operation .......................................................................................................................................................... Prepare the burner for start-up ............................................................................................................................................. Start-up checklist ............................................................................................................................................................. General ........................................................................................................................................................................ Gas supply piping ............................................................................................................................................................ Electrical 11 Boiler or appliance ........................................................................................................................................................... Burner ........................................................................................................................................................................ Figure 10 - CG10 Component familiarization ................................................................................................................. Test instruments .............................................................................................................................................................. Start the Burner .................................................................................................................................................................... Burner start procedure ..................................................................................................................................................... Figure 11 - Shutter and band location ............................................................................................................................. Table 2 - Initial burner settings ......................................................................................................................................... Verify input firing rate ....................................................................................................................................................... Figure 12 - Manifold to furnace pressure drop vs rate, Stepped spud ............................................................................ Figure 13 - Manifold to furnace pressure drop vs rate, Swirl vane head ........................................................................ Check operation and safety controls ............................................................................................................................... Use test instruments to set combustion ........................................................................................................................... Recommended combustion test sequence ..................................................................................................................... Maintenance and Service Annual maintenance ........................................................................................................................................................ Figure 14A- Gas Gun assembly .................................................................................................................................... Figure 14B - Gas Gun assembly ................................................................................................................................... Figure 15 - Gas Gun assembly installation ..................................................................................................................... For the operator .................................................................................................................................................................... Table 3 - Periodic inspection checklist ............................................................................................................................ Replacement Parts Burner exploded view ...................................................................................................................................................... Burner Configurations ........................................................................................................................................................... Low Rate Burner Configuration; 300 to 800 MBH Applications ....................................................................................... High Rate Burner Configuration; 600 to 1200 MBH Applications .................................................................................... Burner Configuration Table .............................................................................................................................................. 2 6104 BCGSO 3 3 3 4 4 4 4 4 5 5 5 5 5 5 6 6 6 7 7 8 8 8 9 9 10 10 11 11 11 11 11 12 12 12 12 13 14 14 15 15 15 16 17 18 18 19 20 20 21 22 22 23 24 24 24 25 R08 hera| Hazard rrn ion Definitions: indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or property damage. indicates a potentially hazardous situation, which, if not avoided, could result in death, severe personal injury, and/or substantial property damage. To the Owner: Thank you for purchasing a Beckett burner for use with your heating appliance. Please pay attention to the Safety Warnings contained within this instruction manual. Keep this manual for your records and provide it to your qualified service agency for use in professionally setting up and maintaining your burner. Your burner will provide years of efficient operation if it is professionally installed and maintained by a qualified service technician. If at any time the burner does not appear to be operating properly, immediately__ contact v_o_M_Lqualifiedservice_ o for consultation. We recommend annual inspection/service of your gas heating system by a qualified service agency. Owner's indicates a potentially hazardous situation, which, if not avoided, may result in personal injury or property damage. Within the boundaries of the hazard warning, there will be information presented describing consequences if the warning is not heeded and instructions on how to avoid the hazard. Intended to bring special attention to information, but not related to personal injury or property damage. 61 04 BCGSO RoB Responsibility Failure to follow these instructions, misuse, or incorrect adjustment of the burner could lead to equipment malfunction and result in asphyxiation, explosion or fire, Contact a professional, qualified service agency for the installation, adjustment and service of your gas burning system. Thereafter, have your equipment adjusted and inspected at least annually to ensure reliable operation. This work requires technical training, trade experience, licensing or certification in some states and the proper use of special combustion test instruments. Please carefully read and comply with the following instructions: • See the front cover for 'What to do if you smell gas'. • Never store or use gasoline or other flammable liquids or vapors near this burner or appliance. • Never attempt to burn garbage or refuse in this appliance. • Never attempt to light the burner/appliance by throwing burning material into the appliance. • Never attempt to burn any fuel not specified and approved for use in this burner. • Never restrict the air inlet openings to the burner or the combustion air ventilation openings in the room. 3 General Professional nforrn Ir|staller's Follow ion Responsibility these Pre-installation indoor instructions checklist Installation exactly. Failure could lead to equipment malfunction and result in asphyxiation, explosion or fire. • • • Protect against Moisture to follow these instructions Please read all instructions before proceeding. Follow all instructions completely. This equipment must be installed, adjusted and started by a qualified service agency that is licensed and experienced with all applicable codes and ordinances and responsible for the installation and commissioning of the equipment. The installation must comply with all local codes and ordinances having jurisdiction and the latest edition of the National Fuel Gas Code ANSI Z223.1 (NFPA 54) and CAN1=B149.1 in Canada. Concealed damage - If you discover damage to the burner or controls during unpacking, notify the carrier at once and file the appropriate claim forms. High altitude installations- Accepted industry practice requires no derate of burner capacity up to 2000 feet above sea level. For altitudes higher than 2000 feet, derate the burner capacity 2% for each 1000 feet above the 2000 feet. 50 Hz motors - The burner ratings, air settings and other adjustments are based on 60 hz motors at 3450 rpm. De= rate firing capacity 20% when using 50 hz motors. Consult factory for specific application data. Dust and Wet or dusty environments could lead to blocked air passages, corrosion damage to components, impaired combustion performance and result in asphyxiation, • • • • [3 explosion or fire. This burner is designed for clean, dry installations. Electrical controls are not protected against rain or sprayed liquids. Keep the installation clear of dust, dirt, corrosive vapors, and moisture. Protective covers and more frequent maintenance may be required. Combustion air supply The burner requires combustion air and ventilation air for reliable operation. Assure that the building and/or com= bustion air openings comply with the latest edition of the National Fuel Gas Code ANSI Z223.1 (NFPA 54). For appliance/burner units in confined spaces, the room must have an air opening near the top of the room, plus one near the floor, each with a free area at least one square inch per 1000 Btu/hr input for all fuel-burning equipment in the room. For Canadian installations, refer to latest edition of CAN1- B149.1 standard. If there is risk of the space being under negative pressure, or of exhaust fans or other devices depleting available air for combustion and ventilation, the appliance/burner should be installed in an isolated room provided with outside combustion air. [3 Clearances With the burner installed in the appliance, there must be adequate space in front of and on the sides of the burner to allow access and operation. Verify that the clearance dimensions comply with local codes and with the appliance manufacturer's recommendations. [3 Fuel gas supply Verify that the gas supply piping complies with all appli= cable local codes and the latest edition of the National Fuel Gas Code ANSI Z223.1 (NFPA 54). Insure that the supply gas pipe size is capable of providing at least the minimum pressure required to the burner gas train inlet at the burner's full capacity rating. Refer to Table 1. 4 6104 BCGSO RoB Table 1 = Burner Specifications CG25 I CGS0 input firing range: High Fire (Max.) High Fire (Min.) Low Fire (Max.) Low Fire (Min.) Fuel: 1500 MBH 800 MBH 560 MBH 350 MBH 2700 MBH 1300 MBH 990 MBH 550 MBH i 5000 MBH 2000 MBH 1400 MBH 730 MBH Natural gas z 0.6 Specific gravity typical Gas Train: Standard Options U.L. Listed / CSD-1 configuration IRI, FM Gas Train inlet Pressure: Minimum Maximum 10 PSi 10 PSi &5!' WC* 10 PSi Manifold pressure: Highest High Fire Lowest High Fire 3.7" WC 2.7" WC 3.5" WC 2.5" WC 3.5" WC 2.5" WC HighiLow Modulation Standard Flame Safeguard: Low Fire Start RM7895A High / Low Modulation RM7895C RM7895C HighiL0w Modulation Modulation RM7895C RM7840L RM7895C RM7840L Standard Standard Flame Detector: Standard Optional Airflow Proving Gas pressure UV Switch: - Standard switches: i Standard high and low ignition: Direct ignition of Main Flame Standard Voltage Current Draw OptionalVo!tages 1i2HP 3450 RPM 120 volt, i phl 60 Hz 6.4 Amps @! 20 volt AC 208/230V ! ph 60Hz 208/230VI 3 ph; 60 Hz 460V, 3 phl 60 Hz 575v, 3 phl 60 HZ 120 vo!t, ! phl 60 HZ !0.4 Amps @!20 vo!t AC 208/230v i ph 60Hz 2081230V, 3 ph, 60 Hz 460V, 3 phl 60 Hz 575v, 3 ph 60Hz 125 lbs. 145 lbs. Weight: Dimensions: *See 165 Ibs. Refer to Figures manufacturer's nameplate settings for specific minimum gas pressure 3450 RPM 208!230v, 1 ph, 60 Hz 1&4 Amps @230 volt AC 208!230V, 3Phi60Hz 460V, 3 ph, 60 Hz 4 & 5. requirements. Figure 1. Burner label location General model information Serial number, including date code _ _._,_ CC50 M 1: }.................. _ _.:_!_ .................... :¢* _ 4. 0 :' ":_'_ I HWii Rating information Approval agency symbols _*_ i_:_c:_::_"_-_'_ _', (i!i'i_/4 i:_t_: _ R.W. Beckett construction and setting data R.W. Beckett specification .......................................... *; ............ ,c : _ and revision Boiler manufacturer (when applicable) Primary group and fuel _ ::" ; ,: ,)4 61 04 BCGSO RoB number _. Additional codes 1 and model Test For Gas Pipe Leaks Leaking gas could result in asphyxiation, sion, or fire hazard. * * * [3 explo- The gas supply piping must be absolutely leak-free. Pressure test the gas piping with air that is at least three times greater than the gas pressure being used. Verify that there are no leaks before proceeding. Flue vent Electrical Figure 2. Minimum Combustion Chamber Dimensions Minimum Inside Dimensions Wdth 'W! (inches) Height 'H' Length 'L' at Min H & W* Burner Head Centerline to floor 'A' CG15.1S 15 16 42 7 CG15.2S 16 17 45 8 CGIS.3S 17 18 47 8 CGIS.4S 18 19 50 9 supply Check the nameplate on the burner to verify that the power connections available are correct for the burner. Refer to Figure 1. All power must be supplied through fused disconnect switches and comply with the latest edition of National Electric Code NFPA 70 (Canada CSA C22.1) and all other local or applicable codes. [3 Verify burner components Burner model can be checked from burner carton or rating label on burner Flange mounting arrangement (Includes hightemperature gasket and/or fiber rope for pressure firing) system The flue gas vent system must be in good condition and must comply with National Fuel Gas Code ANSI Z223.1 (NFPA 54) and all other applicable codes having jurisdiction for vent construction, capacity, and sizing. Burner Model [3 [3 Verify firing input range Refer to appliance manufacturer's instructions (if available) for the firing input range. Otherwise the maximum recommended firing range for the burner depends on the length and width of the firing chamber and the distance from the burner center to the chamber floor. Verify that the chamber dimensions are at least as large as the minimum values given in Figure 2. If the appliance dimensions are smaller, reduce the firing rate accordingly. Flames are shaped by their furnaces and by its flue locations. Increased height and width can decrease the length requirement. When shaping is too severe flames impinge on the walls. Impingement causes CO and carbon deposits and may damage the wall. Maintaining these minimum dimensions should prevent impingement, but smaller furnaces may be acceptable depending upon the results of applications testing. We recommend factory testing of all new burner/furnace combinations by the furnace manufacturer and/or R. W. Beckett Corp. NOTICE CGS0.1S 21 23 55 10 CGS0.2S 22 24 58 11 CGS0.3S 24 26 62 12 CGS0.4S 25 27 65 12 CGS0.SS 27 29 70 13 j NOTICE ] Dimensions shown are for cast iron sectional boilers with uptakes between sections. For minimum dimensions of other furnace types consult R.W. Beckett Corporation. 6 j The volume of the furnace also influences the combustion process. R. W. Beckett Corp. recommends at least 1 cubic foot of furnace volume for each 150,000 BTU/Hr of firing rate. [3 Verify e burner air tube assembly The information in this section may be disregarded if the burner supplied by the appliance manufacturer is a matched component. Maximum firing capacity depends on the furnace pressure. Use the charts shown in Figure 3A, Figure 3B, and Figure 3C, to verify the correct burner configuration for the input rate. Refer to Figures 4 & 5 to verify the air tube assembly length and mounting insertion dimensions. 61 04 80G50 RoB Figure 3A. Maximum Capacity (at 3% 02) vs Furnace Pressure - CG15 1500 L 1400 1300 L = 4, "3" m = A C G 15.4S i - 1200 _CG15.3S = A -CG15.2S t ¢,t-' m A _:: _ CG15.1S 1100 lOOO 9OO 0 0.2 0.4 0.6 Furnace Figure 3B. Maximum Pressure, 0.8 In. WC Capacity (at 3% 02) vs Furnace Pressure - CG25 26OO 2500 2400 2300 I m --'._-2200 CG25.5S _CG25.4S _ CG25.39 2100 _':: 2000 _ CG25.2S --_¢: - CG25.1S 1900 - ÷ 1800 1700 0 0.2 0.4 Furnace Figure 3C. Maximum 0.6 Pressure, 0.8 In. WC Capacity (at 3% 02) vs Furnace Pressure = CGSO 5OOO 4500 _CG50.59 -1- _ 6G50.4S 4000 A = CGS0 -""_:- 3S CG50,28 - CGS0,1S 35OO 3OOO 0 0.2 0.4 Furnace 61 04 BOGS0 R08 0.6 Pressure, 0.8 In. WC 7 Figure 4. Burner Dimensions F E _I_ LL HPL I tI_Li_U _i)l_£t',_S_©_S ARE bi_!N_:HE$ Figure 5. Panel and Modulating Valve Dimensions THREAD 15 6104 BOGS0 R08 U urneF Figure 6. Custom Mounting Plate Mount the burner to the appliance. The burner specified for packaged equipment will have a flange welded for the required insertion. Follow the appliance manufacturer's instructions for mounting. In the absence of instructions, or for retrofits, make sure that the air tube insertion dimension, measured along the side of the air tube from the welded flange to the end of burner air tube, is correct. _! ___________________________________________________________________________________________________________ Overheating Key: Overheating could cause damage to the air tube A Burner mouning flange and other combustion components leading to B Gasket equipment malfunction and impaired combusC Appliance mounting plate tion performance. • • • The end of the air tube must not extend into the combustion chamber unprotected unless it has been factory-tested and specified by the appliance manufacturer. The end of the air tube should be set back ¼" from flush with the refractory inside wall to prevent damage from overheating. Refer to the instructions outlined in this section for methods of additional protection. If this dimension cannot be achieved, protect the end of the air tube by installing a suitable ceramic refractory material such as a refractory mill board capable of withstanding at least 2300 degrees F. The entry hole diameter in the appliance should be 1" larger than the air tube to facilitate ease of installation and provide adequate protection. Referring to Figure 6, if the front plate opening (C) in the boiler is larger than the burner flange bolt circle, then a custom mounting plate (A) of at least 1/4" thickness must be used with a suitable high-temperature refractory material anchored on the fire-side. A suitable high-temperature gasket (B) must be used for an effective seal. Connect NOTICE The gas supply system must be sized to deliver at least the minimum required pressure to the gas train inlet. Contact your local gas utility for verification of gas pressures, allowable pressure drops, and any local piping code requirements. Refer to Figure 7 for an illustration of a gas piping layout and refer to Table 1 for pipe sizing. Do Not Use Teflon on Gas Piping Damage ies could to gas valve cutoff cause ation, explosion • • Verify that the air tube is ¼" back from flush (see Figure 2), and there is nothing blocking the flame zone that could cause flame impingement. • RoB 1 All gas piping installation must comply with the latest edition of the National Fuel Gas Code ANSI Z223.1 (NFPA 54) and other applicable local codes. Attach the plate and gasket to the boiler and tighten the mounting nuts or bolts securely. 61 04 80G50 ipin! as Tape seals and valve bod- gas leaks and result in asphyxi- or fire. Pieces of tape can be cut loose during installation and lodge in gas valves causing cutoff seal problems. Teflon tape 'lubricates' pipe threads, allowing iron pipes to penetrate too deeply into aluminum valve bodies causing distortion and leakage. Use only pipe sealant compounds that are resistant to the gas being used. 9 Install Optional - Gas trains for IRI and FM are available and must be specified when ordering a burner. a Drip Leg in Gas Supply Piping Verify- Verify that the train components are not damaged and all piping and fittings are clean inside and out. The gas train is normally shipped as components and must be assembled and installed at the site. Foreign matter could lodge in gas valve cutoff seals, resulting in gas leak-through, explosion or fire. Install a full-size drip leg or dirt pocket in the piping directly ahead of the main shutoff valve to capture foreign matter. O Gas Vent lines - Install vent lines to any gas valve component that requires atmospheric air pressure to balance a diaphragm. Vent lines must be run to the outdoors, with the termination point away from fresh air intakes and windows. The terminal opening must be fitted with a wire mesh screen to block insects and other contaminants from entering the vent and must be mounted in such a position that water, ice, dirt, or any other foreign matter cannot infiltrate and block the vent piping. Make sure the final assembly is anchored securely. Trains Standard -An Underwriters Laboratories (UL) listed gas train is standard for the CGI0 gas burner. This configuration also meets CSD-1 requirements. See Figures 8A and 8B for typical component layout. Figure 7. Typical Gas Piping Layout ABBREV, HGPS LGPS MSC MLTC PG S SSOV1 TC U 2PRV LGPS REGULATOR PG DRIP LEG ITEM DESCRIPTION HIGH GAS PRESSURE SWITCH LOW GAS PRESSURE SWITCH MAIN SHUTOFF COCK MAIN LEAK TEST COCK PRESSURE GAUGE STRAINER SAFETY SHUTOFF VALVE #1 TEST COCK UNION TWO POSITION REGULATING VALVE HGPS s (IF USED) Table 1. Gas supply piping capacity Schedule 40 metallic pipe with 0:50 psi or less inlet pressure and 0:30" w.c: pressure drOp Maximum capacity in cubic feet of gas per hour (CFH). Natural gas with 0:60 specific gravity. Pipe size (inches) IPS -F;Tr;e:ien;i777 (feet) 0175" 10 278 30 50 90' 90 125 72 15o 64 175 11O i70 59 55 160 " 130 "120 110 i00 1100 2.5' 3050 2100 800 1650 760 1450" 3!0;' 4800 x 3300 2700 4:0' 8500 " 5900 4700 2300 00 67O 1270 2000 3600 610 ,1150 i850 3250 370 560 1050 1700 3000 350 530 320 490 400 180 !50 730 44O ! 95 84 79 1600 590 215 96 1050 500 245 lO5 80 2oo 285 115 70 1oo 520 152 13o :77777:-77-T::7 ==================== 1;5" 90"350 20 60 ::::::::::::::: 305 275 250 460 990 930 ' 870 410 780 380 225 350 210 320 710 _ 1600 2800 17500 " t2000 9700 8300 7400 "i 6800 6200 5800 1500 2600 ,1400 2500 5100 1250 2200 4500 2000 4,1oo 3800 ,1130" 650 1050 1850 6i0 980 1700 5400 3500 61 04 BCGSO RoB Figure 8A. UL gas train - High/Low and Low Fire Start LGP_ MSC U HGPS 8SOV_ TC 2PRV TC MLTC U LGPS MSC ABBREV. HGPS LGPS MSC MLTC PG S SSOV1 SSOV2 TC U 2PRV TC HGPS ITEM DESCRIPTION HIGH GAS PRESSURE SWITCH LOW GAS PRESSURE SWITCH MAIN SHUTOFF COCK MAIN LEAK TEST COCK PRESSURE GAUGE STRAINER SAFETY SHUTOFF VALVE #1 SAFETY SHUTOFF VALVE #2 TEST COCK UNION TWO POSITION REGULATING VALVE U j Figure 8B. UL gas train =Modulating i ;i!ili!i!iiiii!iliiiiiiiiii ili!i U PRV _OV_ TC _0_ TC M_YC: U M'V TC Pipe Size 1" 1-1/4" 1-1/2" 2" Install the burner and all wiring in accordance with the National Electric Code ANSI/NFPA 70 (Canada CSA C22.1) and all applicable codes and requirements. Wire the burner in compliance with all instructions and diagrams provided by the appliance manufacturer. Verify operation of all controls in accordance with the appliance manufacturer's guidelines. Do Not Bypass Controls Safety Electrical Electrical personal • • Tampering with, or bypassing safety controls could lead to equipment malfunction and result in asphyxiation, • • Maximum Length 12" 15" 18" 24" rner re • i When pressure reducing safety shutoff valves are used, the distance from the final shutoff valve (2PRV in Fig. 8) to the burner manifold must be kept to a minimum for good light-off reliability• R.W. Beckett recommends the following maximum lengths: • _ NOTICE explosion or fire. Safety controls are designed and installed to provide protection. Do NOT tamper with or bypass any safety control. If a safety control is not functioning properly, shut off all main electrical power and gas supply to the burner and call a qualified service agency immediately. • shock injury Shock can Hazard cause severe or death. Disconnect electrical power before installing or servicing the burner. Provide ground wiring to the burner, metal control enclosures and accessories. (This may also be required to aid proper control system operation.) Perform all wiring in compliance with the National Electrical Code ANSI/NFPA 70 (Canada CSA C22.1) Keep Covers Service Access Securely installed These covers must be securely in place to prevent electrical shock, damage from external elements, and protect against injury from moving parts. i NOTICE j See Figures 9A & 9B for typical wiring diagrams, with the flame safeguard control, for reference purposes only. Check the literature that was packaged with the burner for the primary control manufacturer's instructions and the exact wiring diagram for your specific burner. 61 04 BCGSO RoB All covers or service access plates must be in place at all times except during maintenance and service. This applies to all controls, panels, enclosures, switches, and guards or any component with a cover as part of its design. 11 11 Sequence - (typica| . . for RM7895C of Operation flame safeguard primary . control) Initiate-The primary control enters the INITIATE sequence when the control is first powered on or power returns after an interruption. The initiate sequence is a ten second delay during which the control verifies line voltage stability. 6. Flame Stabilization - The burner will operate in low fire for 10 seconds before initiating high fire. Standby - The control enters STANDBY until the limits, operating limit control, burner switch, and all microcomputer-monitored circuits are in the correct state. . Prepurge - The control will signal the PREPURGE sequence when the airflow interlock and all switches are in the correct state. The Prepurge sequence is the amount of time the blower motor runs prior to the ignition start sequence. Timing for the Prepurge sequence is determined by a card mounted inside the control module (typically 30 seconds). Run - With a flame established and the control continuing to detect a flame, the burner will operate in the RUN mode until the load demand is satisfied or a limit opens. 3. Load demand - Operating limit control contacts close on drop in temperature (or pressure) and initiates the start sequence. . Trial for ignition (TFI) - After the Prepurge sequence has timed out, the ignition and main gas valves will be energized. Because the burner has direct spark ignition for the main flame, the flame must be established and detected by the control within 4 seconds or lockout will occur. . Load Satisfied - The burner switches to idle until the next call for operation. I I This operation sequence is typical and for reference only. The primary control could vary, depending on the customer specification and code requirements. For the specific operating sequence that applies to your installation, consult the appliance manufacturer's directions, wiring instructions, and control manufacturer's literature supplied with your burner. Figure 9A. Typical wiring using Model RM7897C for High/Low Control (for reference only) L£G_ND: Ii i| | | I 2 if717Sl_.f _ I | @_ _ G_4@ _OVl_}# _'_ & _04:_ ¸ $ _,_ 6104 80G50 RoB Figure 9B. Typical wiring using Model RM7840L for Modulating Control (for reference only) ++7+++L Prepare burner for start-up , Professional Incorrect and Service Required installation and mishan- dling of start-up ment malfunction asphyxiation, • • • Installation CI could lead to equipand result in explosion Start-up check|ist - Verify the following fore attempting to start the burner. !:tO8 Carefully read and become familiar with the manual, flame safeguard control instructions, sequence of operation, pertinent wiring diagrams, gas system layout, insurance requirements, other controls and valve literature pertinent to the installation. or fire. This burner must be installed and prepared for startup by a qualified service technician who is trained and experienced in commercial gas burner system installation and operation. Carefully follow the wiring diagrams, control instruction sheets, flame safeguard sequence of operation, test procedures and all appliance manufacturer's directions that pertain to this installation. If any of these items are not clear or are unavailable, call Beckett at 1-800-645-2876 for assistance. 61 04 BCGSO General be- [El Follow the appliance manufacturer's cedures (when available). 2. start-up pro- CI Inspect the combustion air supply and exhaust venting and verify that they are free of obstructions and installed and sized in accordance with all applicable codes. CI Notify appropriate personnel to schedule startup (gas utility, owner, operators, subcontractors, etc.). Gas Supply Piping [El Insure that the gas piping is properly sized and has been inspected by the gas utility, leak tested at all joints, and purged. [El To protect the gas train and controls, insure that a drip leg or dirt pocket has been properly installed. 113 CI Insure that the fuel gas being supplied is compatible with the burner specification and is available at the correct regulated pressure. (See burner name plate and specification sheets). CI Insure that the vent lines for the diaphragm valves have been run to the outside and properly terminated. Electrical = E3 Insure that all wiring has been completed and complies with the National Electric Code NFPA 70 and local requirements. E3 Refer to Figure 1 and verify that the electrical supply to the burner matches the voltage specification on the label. 4. Boiler or Appliance CI Fill the appliance with water (boilers). CI Check all safety and operating controls for correct application, installation, wiring, and operation. CI 5. Insure that the maximum capacity of the appliance is compatible with the specified burner input firing rate. Burner - See Figure 10 for familiarization CI CI 114, Refer to Table 2 and Figures 11A and 11B to insure that the burner air damper is positioned for initial start-up preliminary settings. CI Insure that the burner is securely mounted in the appliance with the pressure firing plate and all gaskets in place for pressurized chamber applications. CI Before operating insure that all protective cover plates, enclosures and guards are in place and securely fastened. CI When available, refer to the appliance manufacturer's instructions and install the burner accordingly. Test instruments CI Insure that the flue passages and combustion area have been thoroughly cleaned and are in good condition. CI Set the breech damper to the required position for system operation. CI 6. CI Insure that the gas burner model and capacity meet the requirements for the installation. Insure that the gas train meets operating specifications, all safety codes and insurance requirements. The following calibrated test equipment is required to properly install the appliance. Whether these are included in one kit or are individual test components, they should be calibrated and in good working order. CI A combustion analyzer capable of measuring oxygen (or carbon dioxide), carbon monoxide, stack temperature, ambient temperature, and appliance efficiency. CI Electrical multi-meter capable of measuring voltage, ohms, amps, and DC micro-ammeter for measuring the flame signal. These could be included in one meter or separate meters, but should be calibrated and accurate. CI Calibrated manometers and gauges capable of measuring all pressure ranges in the gas supply and appliance draft. This could typically range from a few psi to 0.01" W. C. Having several manometers or U tubes with the correct range can simplify the testing and set up procedures. 6104 BOG50 R08 Start the Burner Professional installation and Service Incorrect installation dling of start=up ment malfunction asphyxiation, • • • • • [:3 Burner start procedure= (Before proceeding, turn off and lock out electrical power and close the main leak test cock to shut off gas to the burner.) 1. With the power and main gas supply to the burner turned off, make sure gas has not accumulated in the boiler or flues. Required and mishan= could lead to equip= and result in explosion . or fire. This burner must be installed and prepared for startup by a qualified service technician who is trained and experienced in commercial gas burner system installation and operation. Do not attempt to start the burner unless you are fully qualified. Do not continue with this procedure until all items in the 'Prepare the Burner for Start-up' section have been verified. Carefully follow the wiring diagrams, control instruction sheets, flame safeguard sequence of operation, test procedures and all appliance manufacturer's directions that pertain to this installation. If any of these items are not clear or are unavailable, call Beckett at 1-800-645-2876 for assistance. Figure 10. Component Famifiarization (CG50 shown, . . Check the initial air settings for the input firing rate. Check the manufacturer's settings either on the nameplate shown in Figure 1 or listed in Table 2. If adjustment is necessary refer to Figures 11A& 11B and set the damper motor cam so that the indicator points to the values shown on the nameplate or listed in Table 2. With the main gas supply valve closed. Set the limit or controller to call for heat then apply power to start the burner. Reset the high and low gas pressure switches if necessary. In order to check the function of each component (i.e: flame safeguard sequence, airflow proving switch, ignition transformer, gas valves, safety lockout timing, etc.), with the gas supply closed off, monitor a complete burner run sequence. Note that the flame safeguard control will lock out since the fuel supply has been closed off. CG15 & CG25 similar.) Major Components: 1. 2. 3. 4. 5. Damper Motor Primary Control Blower Motor Ignition Transformer Gas Gun Assembly 61 04 BOG50 R08 6. Air Flow Proving Switch 7. High Gas Pressure Switch 8. Test Connection 9. UV Scanner 115 . If component operation sequence and function is correct, reset the flame safeguard and initiate a new cycle. Monitor the start-up cycle and manually open the main leak test cock as soon as the flame safeguard powers the safety shutoff valves. If the boiler room is quiet you may be able to hear the valve open, if not you can generally place your hand on the valve and feel it open. After you have observed main flame for a brief time, trip any of the switches in the limit string to shut the burner down. Monitor the flame and safety shutoff valves to assure that shutdown is controlled by the valves and that they operate properly. With this test passed you may safely initiate automatic start-ups on subsequent cycles. Initial air settings Figure 11A. Damper Motor with Cover B A Figure 11B. Damper Motor The following steps outline the procedure for initially setting the damper. Refer to Figures 11Aand 11B and Table 2 for this procedure. C G FE 1. Remove the cover screw (A) then the cover (B) and place to one side. . Using the wrench (C) supplied with the damper motor, adjust the blue Low fire cam (D) to the initial setting listed in Table 2. The appliance manu= facturer's literature will provide furnace pressure data. 3. Using the same wrench, adjust the red High fire cam (H) to the initial setting listed in Table 2. 4. Ensure the damper plate is in the correct position. The cam notch (E) should align with the Low fire setting on the damper motor scale (F). . . D Legend (Figures 11A& 11B) If the damper plate is not in the correct position, disengage the motor by pushing in on the motor pin (G), then rotating the damper plate until the cam notch and motor scale setting are aligned. Re-engage the pin. On High/Low units only, use a small straight edge screw driver, turn the white adjustment screw, located in the orange transition cam, either clockwise or counterclockwise until the cam indicator is half way between the high and low settings on the scale. NOTICE H A B C D E F G H J Cover screw Cover Wrench Low fire cam (blue) Cam notch Damper motor scale Disengaging pin High fire cam (red) Transition cam (orange) 1 The damper plate is attached by screws to its shaft, and bears against a flat on the shaft for alignment. The shaft is secured to the damper motor by a sleeve coupling with two setscrews bearing against the damper shaft and two more against the motor shaft. The motor shaft has a flat matching the one on the damper shaft. The flats on the damper shaft and the motor shaft should be aligned so that the position indicator in the damper motor reads accurately. The best way to align the flats is to tighten the setscrews that bear against the flats on the shafts first, and then tighten the ones that bear against the round surface of the shafts afterward. The test for proper alignment is to disengage the damper motor from its shaft using the disengaging pin (Item G in Figure 11B) and rotate the damper plate to its full closed position. The position indicator should point to 0° within +/- 5° tolerance. 116 6104 BCGSO RoB Optional Modulation instructions Linkage Adjustment Figure 12B. Modulation Assembly LEFT HANDED The optional modulation linkage assembly has been designed as an economic means to adjust the damper and the butterfly valve to maintain air to gas ratios. When the optional Modulation linkage assembly is supplied with the burner, initial adjustments will be made at the factory. To ensure optimum operation, minor additional adjustments must be made after the burner is fired on a boiler. GAS ENTRY Sta_da_ Construction *CG_ SHOWN o C@25 AND CG15 ARE 8_MtLAR ' Valve Shaft The following adjustment will be pre-set at the factory, but may require minor adjustment at start-up: • The damper motor high fire and low fire cams will be preset • The linkage between the damper and the butterfly valve will be preset as illustrated in the manual. • The butterfly valve shaft will be set to a nominal position. Figure 12A. Modulation RIGHT HANDED Assembly GAS, ENTRY Opt_ona! Censtructien _CGS0 SHOWN o CG25 AND CGt5 ARE SIMILAR !utterly Va|ve Sha_ O Adjustment Procedure: Referring to the appliance manufacturer's literature, insure that all preliminary adjustments and calibrations required for the burner and appliance have been performed. A) Prior to starting the burner 1. Verify that the damper motor high fire and low fire cam settings match the nameplate (Figure 1) or Table 2. 2. Examine the linkage for signs of damage. 3. Referring to the illustrations in Figures 12A or 12B, verify that the linkage is installed as shown. 4. Prior to adjusting the burner, have available all the necessary test equipment. • A manometer to check pressures downstream of the gas pressure regulator; at the manifold pressure test connection and in the furnace • A draft gauge to check breeching pressure • A flue gas analyzer that can measure 02 (or CO2) and CO. 61 04 BOGS0 RoB 11"2' 5. Adjustthegaspressureregulator toabout½"WC higherthantheanticipated highfiregaspressure (seeTable2). iVlodulation 6. Topreventthe burnerfrommodulatingto high fire,setthe modulation controllerto the manual controlmode. If necessary, referto the manual suppliedwiththe modulation controller. Control Figure 13C. Manual Operation Figure 13A. Display Meaning Operation mode: Once in Manual Mode, the damper motor can be driven from high to low using the up/down arrows. ACTUAL VALUE (CURRENT OPERATION SET BURNER RELEASED WHEN LIT DAMPER OPENING DAMPER CLOSING (MODULATE DOWN • (MODULATE UP) INCREASE VALUE Modulation of the burner's firing rate is accomplished by driving the damper motor in small increments to either increase or decrease rate in response to boiler demand. A pressure transducer (for steam boilers) or temperature sensor (for water boilers) senses boiler demand and communicates it to the controller. Display and programming functions for the Siemens RWF40 controller are shown in Figure 13Awith the controller in the basic display mode. Figure 13B. Manual Mode Putting - in manual light will The damper motor can be manually operated for set-up and service of the burner by placing the controller in the manual mode, as shown in Figure 13B. Press and hold the EXIT button for 10 seconds to enter the manual mode. The manual operation light will illuminate. To return to the automatic mode, press and hold exit button for ten seconds. The damper motor can be driven from low to high or high to low by pressing the up and down arrows as shown in Figure 13C. Pressing EXIT for 10 seconds returns the controller to the automatic mode. Figure 13D. Operation Set Point Setting operation set point: • From the original display, press program button once. (user level) • Set point 1 is displayed • Use up/down arrows to change setting. • When finished, press exit mode: Press and hold exit button for 10 seconds. Manual operation uliminate. 118 in manual The operating set point can be changed as shown in Figure 13D. Pressing the PGM button accesses the User Level of the software, where this change is made. The up and down arrow buttons raise and lower the operating set point. Pressing EXIT returns the control to the Basic Display level and saves your changes. Programming functions within the software are used to match its settings to the connected hardware, and to adjust the control's response to unusual job site requirements if necessary. A manual for the controller is provided with the burner to allow programming at that level. 6104 BCGSO R08 B) At burner start=up - Note, as soon as the burner lights, be prepared to adjust the butterfly valve to set the low fire rate adjustment. . . Monitor the flame through the observation port. If it appears to be too rich (yellow-orange flame), move the butterfly valve shaft slot setting toward a more vertical position. (This adjustment is made by turning the nut holding the spring-loaded swivel on the butterfly valve arm. If insufficient adjustment is available by this method the butterfly valve shaft can be repositioned in the arm. Care must be taken to make only small changes.) Use a flue gas analyzer to check the flue gas rat= ings for 02 and CO. Your target should be 4% 02 and CO should be well below 50PPM. (Note that the CO is usually near 0 at 4% 02. ) 3. If the 02 and CO levels are not on target, turn the low fire adjustment nut as required to meet the target listed in Step 2. . Check the low fire rate. Either clock the meter or compare the manifold pressure drop to factory standards. Adjust the low fire cam setting in the damper motor (if necessary refer to the Initial Air Setting procedure described previously) and the butterfly valve shaft slot position as described in Step 1. Refer to Step 2 and double check the 02 and CO readings. 5. When low fire is set, use the modulation controller to manually step the burner up to its high fire rate. . 6104 Check flue gas 02 and CO. Your target should be 3% 02. CO should be well below 50PPM, and is usually near 0 for that 02. Adjust the regulated gas pressure as required to meet the target. . Check the high fire rate and adjust the high fire cam setting and regulated gas pressure as re= quired to meet the target. (If necessary, refer to the Initial Air Setting procedure described previously.) . Using the modulation controller, manually step the burner back down to low fire and verify the 02 and CO ratings. If the high fire adjustments were significant they may have affected the low fire settings as well. Refer to Step 4 in this procedure to make adjustments as necessary. BCGS0 ROB . Using the modulation controller, manually step the burner through its range, stopping at several points to check 02 and CO measurements. 10. After you are satisfied with the modulation linkage adjustments secure all linkage fasteners and continue the start-up procedure. It is acceptable for a burner with linkage control of the fuel to show 2% variation in 02 through the range as long as 02 stays above the target points. If the 02 drops below the target points it may lead to a CO problem. Moving the damper arm position on the damper shaft changes midrange 02 . Loosening the clamping screws and moving the swivel end of the arm downward increases midrange 02 , upward decreases it. This change will affect the low fire 02 setting, and you'll need to re-set it. Verify input firing rate: . Clock the meter, correct for pressure and termperature to get SCFH and calculate the input firing rate. Compare the calculated rate to the specified input for the boiler found on the specification sheets and on the rating plates for the burner and boiler. Do not exceed the specified maximum input for the boiler. . Attach a manometer to the manifold test port, clock the meter, and adjust the regulated pressure until the specified input level is achieved. Refer to Table 2. 3. Be sure to set the breech or furnace pressure to the correct value, since this will have an effect on the manifold pressure. 119 Table 2. Initial burner settings ............................................................................................... L;ur P=ssu ce at,,0h e F, e ........... O" W.C. 0.25" W.C. 0.50" W.C. 1.00" W.C. 8 E C_3 800 900 468 " 950 1050 CG15.1S I 548 i 548 1150 'i250 468 641 1300 750 750 0:9 CG15.2S I " 64i 1400 0.9 I CG15.1S 0.9 II CG15.2S 0.9 i350 "669 9 2.6 12 '312 1700 2.9 i3 1.1 I 34 33 314' 1.1 1.0 0.9 17 3.1 49 1.0 52 _ 0:9 u 17 316 68 I i10 0.9 I CG15.4S 019 20 I 20 CG25.2S 017 20 2.7 I 1:0 "2.7j 38 0.7 3.1i 2.7 20 3.2 23 '217 2000 896 CG25.3S 0.7 23 3.3 cG25.4s 1037 CG25.4S 017 0.7 I 1.0 66 I i037 51 31i 41 48 ' 2.8 66 27 3.4 84 li 0.6 30 2.5 CG25.5S 0.6 30 3.0 mmm 0.7 0.7 I I 0.7 0.7 '0i7 100 3.3 3.0 3.4 20 0.7 66 2.9 I 17 017 54 21 i7 0.7 i 27 CG25.5S 21 I 0.7 9 I 9 66 I 1.0 13 27 I 3.1 1.3 I 37 36 3.7 58 17 I i7 22 3.3 56 318 112 10 0.8 41 219 3.6 4!2 19 3.8 74 317 4i 1.2 . I 42 84 . 80 39 '&9 0.8 i7 17 3.2 3.6 42 0.9 018 21 I 3.2 I 43 18 4.1 41 I 0.9 I 23 I 3.7 " 46 4.2 56 3.7 60 49 0.8 21 3.7 51 0.9 23 2.9 55 .... 0.8 24 3.2 56 0.9 26 23 3.6 68 0.8 24 3.8 70 0.9 26 71'018 93 43 14 3.4 3.1 31 I i4 20 27 414 1.2 23 i 3.7 I 1.1 85 3.2 10 I I 100 38 3.2 3.9 'i:o' 42 0:7 1200 13 o:9 26 I 3.7 3.3 0.7 2500 0.9 2.9 Ii 9 2.8 I 12400 i2oo 9 I 16 CG25.3S 2300 30 110 16 896 '2100 1.0 II 0.9 CG25.2S 774 32 0.9 1800 I 25 I CG15.3S cc25._s o.7 774 314 12 1450 669 CG25.!sI0.ZI!T i550 2.7 i CG15.3S CG15.4S I 9 I 28 27 3.6 0.8 28 30 2!8 ioo 08 31 30 3.2 3.3 3.9 ' 4.3 I 76 0.9 30 78 I 3.8 90 102 310 ii5 115 mmmmmmmmm mmmm CG50.1S CG50AS CG50.2S cG5oi2s CG50.3S CG50.3S CG50.4S CG5&4S CG50.5S CG5O15S CG50.5S Gas pressures are as measured at the manifold test connection. Notice: The settings in this merit by the fully qualified 20 chart are for reference and experienced only. start=up The actual conditions at the installation may require further adjust- technician. 6104 80G50 R08 Estimating Rate Manifold to Furnace Pressure information can be used to estimate the burner's firing rate when it is not possible to clock a meter for the rate. To estimate the burner's firing rate: • Measure the furnace pressure over fire • Measure the manifold pressure (at the manifold pressure test connection in Figure 10). • Subtract the furnace pressure from the manifold pressure • Compare the result to the data in Figures 14A, 14B or 14C as appropriate for your burner. Clocking a gas meter Before you clock the meter you must make sure that the burner is operating at a steady rate, and that it is the only thing that is using gas that would flow through the meter. Uncorrected flow rate • Locate the dial that moves the fastest and determine how many cubic feet are represented by one revolution of its dial. • Use your watch for timing and observe how many cubic feet are used in one minute. • Multiply by 60 Example: The dial is a one cubic foot dial, and goes around 7 ½ times in one minute. That gives 7.5 cubic feet per minute. Multiply by 60 to get 450 cubic feet per hour (CFH) as your uncorrected flow rate. Pressure correction Gas is compressible, the higher the pressure on it, the smaller the number of cubic feet it occupies. To correct for that you will need to know the gas pressure at the meter. • If there's a gauge at the meter, read it while the gas is flowing. (If not, measure the gas pressure in the line downstream of the meter before any valves or regulators, with no gas flowing.) • Convert the gas pressure to PSI if you measure it in any other units. (1 PSI = 27.7 inches water column) • Add 14.7 to the meter pressure, divide their sum by 14.7, and multiply that result times the uncorrected flow rate to obtain the pressure corrected flow rate. Example: The meter in the example above is operating at 14" WC. 14 / 27.7 = 0.5 PSI at the gauge; 14.7 + 0.5 =15.2; 15.2 / 14.7 = 1.034 correction factor; 1.034 x 450 = 465 CFH corrected for pressure Temperature correction Gas volume also changes with the temperature of the gas. Most gas meters are temperature compensated. They say so on the face of the index and don't require temperature correction. The temperature we correct to is 60 ° F. That's close to the temperature of the ground, so usually it's not necessary to correct for temperature from underground lines. • Measure the gas temperature at the meter. • Add 460 to the gas temperature and divide 520 by the result to obtain the correction factor. • Multiply the pressure corrected flow rate times the temperature correction factor. Example: The meter in the example is connected to an above ground line on a hot day and shows 100 ° F gas temperature. 460 + 100 = 560; 520 / 560 = 0.929; 465 x 0.929 = 432 CFH corrected for pressure and temperature. NOTICE BTU's and i MBH The BTU content of natural gas varies from one location to another, and even from day to day at a fixed location. For firing estimates it is usually assumed to be 1000 BTU's per standard cubic foot. To calculate BTU/Hr firing rates multiply SCFH times 1000. Example: 432 SCFH x 1000 = 432,000 BTU/Hr. MBH stands for thousands of BTU's per hour. Since 1 cubic foot of natural gas contains 1000 BTU, 1 MBH equals 1 SCFH of gas flow. Example: 432 SCFH = 432 MBH 61 04 BCGSO ROB 2 11 Figure 14A. Manifold to Furnace Pressure Drop vs Rate CG15 1800 1600 I I 1400 .4J I I 1200 f m" "IW 1000 m -CG15.4S - @° 'CG15.3S CG15.2S 800 CG15.1S 600 A _g 4OO 2OO 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 Pressure Drop, In. WC Figure 14B. Manifold to Furnace Pressure Drop vs Rate CG25 3500 3000 I 2500 "CG25.5S "IW 2000 F" ° _ "CG25.4S j_ I w m 1500 r_ " _ 14 °CG25.2S "CG25.1S 4 1000 I 500 0 0.5 1 1.5 2 2.5 3 3.5 4.5 Pressure Drop, In. WC 22 6104 BCGSO RoB Figure 14C. Manifold to Furnace Pressure Drop vs Rate CG50 6000 5000 ,.4 f I 4000 .Ira "CG50.5S _A w °CG50.4S V 3000 _ °CG50.3S °CG50.2S tY 2OOO 4 I 1000 0.5 1 1.5 2 Pressure Check operation and safety to properly test and verify the function of operation and safety controls lead to equipment malfunction and result phyxiation, explosion or fire, • Drop, • • . 6104 BCGSO RoB 4.5 . Low water cutoff (LWCO) - With the burner firing, open the blow down valve on the low water cutoff, if applicable. As the water level drops, the LWCO switch contacts open and shut the burner off. When the water level rises, the LWCO contacts close and restart the burner. Monitor the LWCO switch operation in relation to the water level in the sight-glass for synchronization. . Airflow proving switch - With the burner firing at its lowest rate, loosen the tubing connection to the airflow proving switch. A loss in air pressure at the tubing should immediately cause the diaphragm in the switch to open and recycle or lockout the safeguard control. . Low gas pressure switch - With the burner firing and a manometer attached to a test port near the low pressure switch, gradually close the main leak test cock to shut off the gas supply. Note the pressure at which the low gas pressure switch opens and shuts the burner off. Manually reset the switch. The low gas pressure switch should be set at half of the normal supply pressure in the line. correct could in as- High limit - To check the High Limit, raise the temperature or pressure of the operating control to a higher level and lower the limit to a setting less than the operating control. Run the burner until the high limit opens and shuts the burner off. Adjust the controls back to the desired settings. 4 Operating control - Run the burner until the operating control shuts it off. If necessary, make adjustments to ensure the control cycles the burner in the desired temperature or pressure range. If instructions are not available, use the following recommended procedures and record all results in a start-up log. Refer to Figure 7 for typical test points and component locations. • 3.5 . Tech- The testing of operation and safety controls requires technical training and experience with commercial gas burning systems. Carefully follow the manufacturer's instructions supplied with the controls. Verify the correct function of all operation and safety controls used in the installation. • 3 In. WC controls: Testing by Qualified nician Required. Failure 2.5 23 results in the start-up log for future reference. . . . . High gas pressure switch - With the burner firing and a manometer attached to the test port nearest the high pressure switch, gradually increase the gas pressure until the high pressure switch opens and shuts the burner off. Note the pressure and manually reset the switch. The high gas pressure switch should be set at one and one half times the high fire manifold pressure (see nameplate data in Figure 1 or set switch as determined by testing). Leak-test valve - With the burner firing and manometer attached to the leak-test valve port, turn the burner electrical switch off and observe that the gas pressure does not increase after several minutes. This proves total closure of the main gas valve. CI Draft - Set the breech or furnace pressure to the level specified by the appliance manufacturer. Typical example: +0.10" W. C. CI Oxygen - It is recommended that you measure the oxygen (02) early in the test sequence because high levels of carbon monoxide can be created at very low or even very high 02 levels. The typical operating range is between 2.5% - 4.5 %. The equivalent carbon dioxide (CO2) operating range is 9% - 10.5%. CI Carbon monoxide (CO) -An operating range of 0 -50 PPM is recommended for the burner. The maximum carbon monoxide (CO)level permitted in the flue gas by the UL 795 Standard is 400 PPM (0.04%). CI Stack Temperature - The stack temperature should be within the range specified by the appliance manufacturer. It is influenced by input firing rate, flame shape, excess air ratio, and cleanliness of boiler flue passages. This temperature, combined with the ambient temperature, and 02% (or CO2) is used in calculating the appliance efficiency. Flame safeguard safety lockout - Simulate a flame failure by turning the main gas supply off. The control should shut the burner off on safety within the safety lockout time. Flame sensor circuit (flame rod) - With the burner power switch turned off, refer to the wiring diagram supplied with the control and locate the sensor connection terminals. Place DC voltmeter probes in the flame amplifier test jacks. With the burner firing, the flame signal should be steady and at least 1.25 VDC. 10. Flame sensor circuit (UV scanner) - With the burner power switch turned off, refer to the wiring diagram supplied with the control and locate the sensor connection terminals. Place DC voltmeter probes in the flame amplifier test jacks. With the burner firing, the flame signal should be steady and at least 1.25 VDC. Recommended test instruments to set Verify that all boiler sections, canopy, and access plates or doors are fully equipped with gaskets and sealed against any leakage, which could affect the combustion test results. Before making these tests, operate the burner for several minutes to allow the heating system temperature to stabilize or nearly reach steady-state levels. Record all 24, sequence: 2. Measure the carbon monoxide level and adjust air settings, if necessary, to regulate it to about 50 PPM for a starting point. 3. Measure the 02 or CO2 at the 50 PPM CO level. For this discussion, assume the 02 is 1.5% (11% CO2). combustion: Always use calibrated test instruments to set combustion levels. Verify that test instruments are calibrated and in good working condition. If not already provided, drill test access holes in the flue pipe near the breech (or upstream of the boiler breech damper, if applicable) and in the front mounting plate area for firebox pressure. Be careful not to damage any water-backed surface. test 1. Adjust the draft or breech pressure to the appliance manufacturer's recommended level. . Use combustion Open the air adjustment until the 02 level is increased by at least 1% or to 3% 02 (whichever is higher). This should reduce the CO level and provide a margin of reserve air to accommodate variable conditions. 5. Sample the CO level again. It should be in the 0 to 20 PPM range. 6. Check the draft to ensure it still meets specifications. If a major change in draft is required, repeat the above steps. . Perform any final adjustments and lock the air settings securely. Run the burner through several cycles to verify prompt ignition and stable burner operation. 6104 80G50 RoB Maintenance and Service Annual vice Tampering Professional tion, explosion or making could lead to equipment and result in asphyxia- • To ensure continued reliable operation, a qualified service technician must service this burner annually. More frequent service intervals may be required in dusty or adverse environments. Operation and adjustment of the burner requires technical training and skillful use of combustion test instruments and other test equipment. Turn Off Electric Supply Before and Gas Servicing Failure to turn off electric and gas supply result in electrical shock, gas leakage, sion, or fire hazards. • could explo- Turn main gas valves and electric power off before performing any maintenance. If a maintenance procedure requires electrical power, use extreme caution. • Annual maintenance (The following should be performed by a qualified service technician only.) [3 Burner; . . 6104 . or fire. Do not tamper with the burner or controls or make any adjustments unless you are a trained and qualified service technician. • Clean the inside surfaces of the burner housing scroll and especially the air intake area and airflow proving switch suction tube. incorrect • • . Required with adjustments malfunction Ser- Run the burner and perform a complete combustion test using the proper instruments before proceeding. If necessary refer to the section labeled Start the Burner. Record the results for reference. Inspect and clean all dirt accumulation from the gas train, burner exterior, burner air damper, and surrounding area. . . . If the blower motor does not have permanently lubricated bearings, oil the motor. Clear any debris from the air vents on the motor body. Clean the ignition transformer, baseplate, and terminal bushings. Inspect the ignition leads for signs of deterioration and loose terminals. If the burner flame detection is a UV scanner, in= spect the mounting and clean the lens according to the component manufacturer's recommendations. Remove the gas gun assembly and clean the entire unit, paying special attention to the air diffuser and spuds. 10. Inspect the flame rod (if used) for oxidation or distortion. Clean all surfaces, set the probe position, and insure that the flame rod is securely fastened. Refer to Figures 15A, and 15B. 11. Inspect the ignition electrode for any damage. Clean all surfaces, set the proper electrode gap, and make sure it is securely fastened. 12. Clean the inside of the air tube and inspect the combustion end for any deterioration. Referring to Figure 2, check the recess dimension from refractory. 13. Inspect gas tube O-ring condition and replace if damaged. Install gas gun assembly back into the burner and use the jacking screw to tighten the gas gun securely in place. (Automotive chassis or bearing grease is suitable for o-ring lubrication.) 14. Inspect the condition of the appliance mounting plate and burner mounting flange gaskets and replace any damaged materials. See Figure 6. . Remove the blower motor and clean any accumulated matter from the blower wheel and motor end bell. 15. Inspect all burner control wiring and the burner control panel for damaged insulation and loose terminals/connections. . Check wheel for damage and the hub setscrew for tightness. If the blower wheel must be removed from the motor shaft, insure that clear= ance specifications are maintained (blower wheel hub to motor clearance should be .020"). 16. Verify that the source voltage to the burner and control panel is within 10% of the burner rating as listed on the nameplate. (Figure 1) BCGSO RoB 25 O Appliance - (Follow appliance manufacturer's service procedures. The following steps are emphasized because they relate to burner operation) O 3. Check barometric damper or draft hood for proper operation. 2. Verify that the combustion air supply is functioning properly, adequately sized, clean, and properly lubricated. [] 5. Check all operating and safety controls on the boiler for proper installation and operation. . O Gas Perform all maintenance and tests according to the burner control manufacturer's instructions (limits, controllers, low water cutoff, relief valves, feed valves, etc.) supply piping: the burner for proper combustion: Flame safeguard: Follow the control manufacturer's instructions and verify that the control is functioning to specifications. See Page 12 for typical sequence of operation and Items 8 through 10 on Page 24 for control system checks. [] Manual shutdown for ion@ periods: 1. Close all gas valves in the gas supply piping system. 2. Turn off all electrical power to the burner. Inspect all piping for leakage and proper installation. form necessary repairs to comply with all codes. Figure 15B- Adjust Follow the guidelines under "Start the Burner" to set the combustion levels using test instruments. [] 4. Inspect boiler sections and system load piping for possible leaks. Make all necessary repairs. area: 1. Insure that there are no combustible materials, flammable liquids or vapors in the vicinity of the heating appliance. 1. Check the condition of the combustion chamber refractory, the front-plate insulation, and all gaskets and seals. Repair or replace as necessary 2. Insure that the flue passages, flue vent pipes, and chimney flues are clean and unobstructed. Installation Per- 3. Protect the burner and controls from moisture and dirt. Gas Gun Assembly SPUDS AIR DIFFUSER FLAME ROD (CROSSES CENTERLINE OF HEAD ASSEMBLY)'-........\ / ELECTRODES 26 VERIFY O-RING IS LUBRICATED* AND IN P_CE BEFORE P_CING ASSEMBLY" INTO BURNER. 6104 BCGSO RoB Figure 15B- Gas Gun Assembly VERIFY ALIGNMENT VERIFY BURNER MODEL ON ADJUSTMENT SCALE BURNER MODEL ON HEAD * Automotive chassis or bearing grease is a satisfactory - Disassembly of gas gun is not required for cleaning, VERIFY O-RING IN PLACE AND LUBRICATED * o-ring lubricant. Burner Head Adjustment - There is an optimum gas orifice size and burner head setting for each firing rate of the burner. The gas orifice size sets the gas flow velocity; the head setting establishes the airflow velocity. When those velocities are properly matched the burner provides its best performance and stability. The gas orifice size is built into the burner head. You can verify the correct selection by looking for the burner model number stamped on the top centerline of the stainless steel tube that forms the base of the burner head. It should match the model number on the Beckett burner data label on the blower housing. The head setting is established by a notched sleeve on the gas tube that can be rotated to positions on a scale marked by the burner's model number. The scale should normally be set to the model number on the Beckett burner data label. (If specific application requirements dictate an alternate head setting it will be noted by a label on the gun assembly.) For normal service requirements it is not necessary to disassemble the head from the gas tube. If you disassemble the gas gun, make sure that when you re-assemble it: 1) The adjustment scale is set to the correct position as indicated by the burner model number or Gun Label. 2) The alignment marks on the head, scale and stop are in alignment. 3) The O-ring between the head and the adjustment scale is in place, is lubricated with grease, and is compressed between the head and scale as the setscrews that retain the head are tightened. 6104 8CGSO R08 27 inspect Heating System Regularly Lack of regular inspections and maintenance could lead to equipment malfunction sion or fire. The gunassemblyis securedinsidethe air tubeby a spring-loaded jackingscrew. It is springloadedin orderto controlthe forceit canimposeon the gun assembly.The screwcan be tightenedfirmlywithout puttingexcessivepressureon thegunassembly thatmightdistortthegunor damageitsO-ringseals. Wheninstallingthejackingscrewlookinsidethe air tubeto verifythatthe pointedtip of thejackingscrew pinisseatedintothesmallholeonthelocatingpadon top of thegun. Thereis alsoanexternalverification of correctassembly: whenthescrewis fullytightened, the e-clipon the top on the centerpinshouldcome flushwiththetopofthescrew. 28 and result inadequate in asphyxiation, explo- (Always follow the appliance manufacturer's recommended service instructions, when available.) * The following checklist is intended to be used as a minimum reference guide only and does not supersede or replace the heating appliance manufacturer's recommended service and maintenance instructions or any code requirements. * Consult the installation and service instructions provided by the individual control or component manufacturer and carefully follow their directions. * Maintenance and testing may be required more frequently due to dusty or severe operating conditions. * If unusual or questionable performance is observed, shut the system down and contact your qualified service agency immediately. 6104 BCGSO R08 Table 3. Periodic inspection Sheet Frequency Inspect area surrounding heating plant Daily Keep area clean and free of clutter Inspect gas supply System for leakS DailY Use ViSual and electronic leak detection Inspect appliance & piping for water leaks Daily Keep burner and controls dry at all times u Inspect gauges: indicators, monitors Check temperature and pressure levels Make visual inspection of flame Daily Note condition. Replace defective parts Daily Compare to manufacturer's Daily Monitor burner start-up Daily M0nit0r stack temperature Daily Test low water cutoff and alarm Daily specifications Look for changes in shape, size, and color: Verify prompt ignition and flame stability. _Compare to start,up and trend level. Follow control manufacturer's instructions & procedures in ASME Boiler & pressure vessel Code, Section Vl Recommended rules for care and operation of heating boilers. li calculate fuel gas input firing rate Weekly Compare to appliance manufacturer s Specifications Check flame safeguard sequence of operation. Weekly Follow control manufacturer's Flame failure resp0nse &loCkout timing! weekly instructions FollOW control manUfactUrer's instructiOns Flame sensor signal level (if meter is hardwired) Weekly Compare to control manufacturer's specifications Main fuel gas valves Weekly open high limit and verify cut0ff 0perati0n Inspect exhaust vent system for blockage Weekly Remove any restrictions inpect combUstion air supply Check high and low gas pressure interlocks CheCk safety ValVes Monthly Monthly As needed RemOve any restficti0ns Follow control manufacturer's instructions Foliow control manufactUrei,s instructions &proCedures in Recommended ASME Boiler Pressure Codeoperation Section VI for Vessel care and of Heating Boilers: 6104 BOGS0 Roe 29 p|acement For best performance specify genuine __ Parts replacement parts. Note 1: See Burner Configuration 30 6104 Table. BOGS0 R08 -°'itern -'!'_=_DesCription 1 CGt5 Part No, °°7°=_ CG25 Part No: "_ " Air Proving Switch Ii 2 3 UV Sensor ( f not us ngF ame Rod) RearAccess 5 2190901U Door* CG50 Part No, 2190901U 2190901U 5201304U 5201302U 5201304U 5201302U 7247U for UV for Flame Rod 5201303U 5201301U spring Latch (Dzus fastener) 32444u Sight Glass** 31346U 32444U " 32444U 31346U 31346U Refer to UL Label for MOdel Numbers 7 Control Subbase 8 Ignition Transformer 7503U 7503U 9 High Gas Pressure Switch 2190903 U 2190903 U 10 Damper Motor ' 11 Refer to UL Label for Model Numbers Mounting Flange 14 / Blower Wheel 15 Flame Rod ¸¸¸¸¸¸¸¸¸16 1 ¸¸¸¸ GrOUnd 17 N/A 21268U 219!106U 19 nO panel panel 31449U 2t528U 2191302U 2!91108U 5990480U 5990360u 3226402U Gas Tube, Welded Assembly 5193202BKU Cable, Ignition Electrode 5990184U 22 Jacking Screw Assembly 5!93402U 23 Air Tube 24 *Includes sight glass, label, gaskets, and fasteners. 3226404U H 5193203BKU 5990184U 5193403U 5193204BKU 5990184U 5193403U Specify Application 4474U Ignition Electrode 5990360u 3226403U _ 21 RoB 31347U 2191107U 5990480U 5990360u O-ring set (2 included) 61 04 BCGSO 32294U 2i527U 21547 21733U Specify Model u 25 32294U 21402U 21499U 21734U 2191302U ...... Head, Welded Assembly /18¸¸¸¸¸¸¸¸ Cable, Flame Rod(if used) i 75060iU 750603U 2t267U 2191302U Electrode 2190903 U 750601U 750603U 32294U Nylon Bushing (Damper Rod) 13 iiii 75060iU 750603U LoiH! Modulation 7503U 2191206U 4474U 4474U 2191207U 2191208U **Includes Beckett label and window gasket. 3 11 Limited Warranty information Limited WARRANTY For Residential, Commercial and Specialty Burners The R. W. BECKETT CORPORATION ("Beckett") warrants to persons who purchase its Beckett burners from Beckett _r resale or _r incorporation into a product _r resale ("Customers") that its equipment is free from defects in material and workmanship under normal use and service t\_r 60 months from the date of manufacture t_r Residential Burners and 18 months from the date of manufacture _r Commercial and Specialty Burners. Residential bz_rner models, inclz_de: AF, AFG, AFII, NX, SF, SR and SMG. Commercial bz_rner models ineh_de: CF375, CF500, CFS00, CF1400, CF2300A, CF2500, CF3500A, CG10, CG15, CG25 and CG50. 3_eeia[ O bzcrner models' inch€de: ADC, ADCP, ARV, SDC and SM. The provisions of this wan'anty are extended to individual major burner components as t\_llows: a) b) 60 months 18 months Note: THIS Normal from date of manut:acture from date of manufacture ser',ice WARRANTY items DOES £\_r all Beckett-branded major components, except £\_r 12 Vdc components. t\_r all non-Beckett-branded major components and Beckett branded 12 Vdc components. t\_und to be defccti'_ e upon receipt NOT EXTEND TO EQUIPMENT by the customer SUBJECTED TO MIS[ are co'_ ered by this warranty. SE, NEGLECT, OR ACCIDENT: NOR DOES THIS _2&RRANTY APPLY UNLESS THE PRODUCT COVERED BY IT IS PROPERLY INSTALLED BY A QUALIFIED, COMPETENT TECHNICIAN, 'WHO IS LICENSED WHERE STATE AND LOCAL CODES REQ[ IRE, AND WHO IS EXPERIENCED IN MAKING SUCH INSTALLATIONS, IN ACCORDANCE 'WITH THE LATEST EDITION OF NFPA NO. 31 OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE LATEST EDITION OF THE NATIONAL FILL GAS CODE (NFPA NO. $4) AND IN ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE AND NATIONAL (;ODES HA_TNG 31TRISDICTIONAL AUTHORITY. Equipment, which is detective in material or workmanship and within the warranty period, may be returned for credit as follows: Beckett Burners, Beckett-branded major components and non-Beckett-branded major components that came as original equipment on a Beckett burner or were sold as a replacement part by Beckett should be returned, freight prepaid, to Beckett's home office. Credit will be issued to the customer unless the returned equipment is detemlined by Beckett to be out of warranty or damaged by user, in which case the equipment will be scrapped. Note: Beckett is not responsible for any labor cost for removal and replacement of equipment. THIS WARRANTY REMEDIES AND PURPOSE. IS LIMITED TO THE PRECISE TERMS SET FORTH ABOVE, AND PROVIDES IN PARTICULAR THERE SHALL BE EXCLUDED THE IMPLIED WARRANTIES IN NO EVENT authorizes any exclusive remedy person WILL to assume being limited BECKETT BE LIABLE _\_r Beckett to credit any other FOR ANY INCIDENTAL liability or obligation EXCLUSI_'E REMEDIES OF MERCHANT_MBILITY OR CONSEQUENTIAL in colmection with DAMAGE the sale EXPRESSLY IN LIEU OF ALL OTHER AND FITNESS FOR A PARTICULAR OF ANW NATURE. of this equipmenL Beckett's Beckett neither liability assumes nor and Customer's as set _\)rth above. Form No61545 R72905 R.W. BECKETT CORPORATION U.S.A.: P.O. Box 1289. Elyria, Ohio 44036 www.beckettcorp.com Canada: R.W. Beckett Canada, Ltd.. Unit #3,430 Laird Road • Guelph, Ontario N1G 3X7 *6104BCG50* Printed in U.S.A. 3_ 7 © 2006 R.W. Beckett Corporation 61 04 BCGSO R08
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 32 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Thu May 22 04:14:26 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools