Bard W60A S3397 (2012 11) User Manual To The E3cd462f D3d6 4c77 A720 7d0f37d310a1
User Manual: Bard W60A to the manual
Open the PDF directly: View PDF
.
Page Count: 12
| Download | |
| Open PDF In Browser | View PDF |
THE WALL-MOUNT™ AIR CONDITIONERS - 9.0 EER, (60HZ)
Models W17A to W60A
1.5 to 5 Ton (16,400 to 55,000 Btuh)
Right Side Control Panel
60Hz
GREEN REFRIGERANT
R-410A
The Bard Wall-Mount Air Conditioner is a self contained energy efficient
system, which is designed to offer maximum indoor comfort at a minimal
cost without using valuable indoor floor space or outside ground space.
This unit is the ideal product for versatile applications such as: new
construction, modular offices, school modernization, telecommunication
structures, portable structures or correctional facilities. Factory or field
installed accessories are available to meet specific job requirements.
Engineered Features
Aluminum Finned Copper Coils:
Grooved tubing and enhanced louvered
fin for maximum heat transfer and
energy efficiency.
Twin Blowers:
Move air quietly. Most models feature
multispeed blower motors providing
airflow adjustment for high and low
static operation. Motor overload
protection is standard on all models.
Air Conditioner Compressor:
Scroll Compressors eliminate need for
crankcase heater. Standard on 1½ to
5 ton.
R-410A Refrigerant:
Designed with R-410A (HFC) nonozone depleting refrigerant in
compliance with the Montreal protocol
and 2010 EPA requirements.
Phase Rotation Monitor:
Standard on all 3 phase scroll
compressors. Protects against reverse
rotation if power supply is not properly
connected.
Galvanized 20 Gauge Zinc Coated
Steel Cabinet:
Cleaned, rinsed, sealed and dried
before the polyurethane primer is
applied. The cabinet is handsomely
finished with a baked on textured
enamel, which allows it to withstand
1000 hours of salt spray tests per
ASTM B117-03.
Foil Faced Insulation:
Standard on all units.
Full Length Mounting Brackets:
Built into cabinet for improved
appearance and easy installation.
NOTE: Bottom mounting bracket
included to assist in installation.
Electrical Components:
Are easily accessible for routine
inspection and maintenance through a
right side, service panel opening.
Features a lockable, hinged access
cover to the circuit breaker or toggle
disconnect switch.
Electric Heat Strips:
Features an automatic limit and thermal
cut-off safety control. Heater packages
can be factory or field installed for all 1½
through 5 ton models.
Filter Service Door:
Separate service door provides easy
access for filter change.
One Inch, Disposable Air Filters:
Are standard equipment. Optional one
inch washable filters available and filter
racks permit the addition of 2" pleated
filter. Factory or field installed.
Condenser Fan and Motor
Shroud Assembly:
Slides out for easy access.
Liquid Line Filter Drier:
Standard on all units. Protects system
against moisture.
Barometric Fresh Air Damper:
Standard on all units. Allows up to 25%
outside fresh air. Optional ventilation
packages available.
Compressor Control Module:
Standard on all units. Built-in off-delay
timer adjustable from 30 seconds to 5
minutes. 2-minute on-delay if power
interrupt. 120-second bypass for low
pressure control, and both soft and
manual lockouts for high and low
pressure controls. Alarm output for
alarm relay.
Built-in Circuit Breakers:
Standard on all electric heat versions of
single (230/208 volt) and three phase
(230/208 volt) equipment. Toggle
disconnects are standard on all electric
heat versions of three phase (460 volt)
equipment.
Slope Top:
Standard feature for water run-off.
Top Rain Flashing:
Standard feature on all models.
High & Low Pressure Switches are
Auto-Reset:
Standard on all units. Built-in lockout
circuit resets from the room thermostat.
Provides commercial quality protection to
the compressor.
• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2010.
• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL
1995/CSA 22.2 No. 236-05, Fourth Edition.
• Commercial Product - Not intended for Residential application.
Form No.
S3397-1112
Supersedes S3397-712
Page
1 of 12
Capacity and Efficiency Ratings
MODELS
W17A1 / W18A1
W24A1
W30A1
W36A1
W42A1
W48A1
W60A1
16,400
24,000
29,600
35,400
41,000
47,000
55,000
9.20
9.00
9.00
9.00
9.20
9.00
9.00
Cooling Capacity BTUH 1
EER 2
1 Capacity is certified in accordance with ANSI/ARI Standard 390-2003.
2 EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003.
All ratings based on fresh air intake being 100% closed (no outside air introduction).
Specifications 1-1/2 Ton through 3 Ton
MODELS
W17A1-A
W18A1-A
W24A1-A
W24A1-B
W24A1-C
W30A1-A
W30A1-B
W30A1-C
W36A1-A
W36A1-B
W36A1-C
Electrical Rating--60 Hz
230/208 - 1
230/208 - 1
230/208 - 3
460 - 3
230/208 - 1
230/208 - 3
460 - 3
230/208 - 1
230/208 - 3
460 - 3
197-253
197-253
197-253
414-506
197-253
197-253
414-506
197-253
197-253
414-506
Operating Voltage Range
Compressor--Circuit A
230/208
230/208
230/208
460
230/208
230/208
460
230/208
230/208
460
Rated Load Amps
Voltage
6.5/7.2
11./12.4
7.2/8.1
5.0
11.7/13.3
7.5/8.5
5.3
15.9/17.7
11.8/13.1
6.0
Branch Circuit
Selection Current
9.0
12.9
8.4
5.2
14.2
9.0
5.7
18
13.3
6.0
Lock Rotor Amps
48/48
64/64
58/58
28
78/78
71/71
38
112/112
88/88
44
Compressor Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
1/5 - 1075
1/5 - 1075
1/5 - 1075
1/5 - 1075
1/5 - 1075
1/5 - 1075
1/5 - 1075
1/5 - 1075
1/5 - 1075
1/5 - 1075
1.2
1.2
1.2
1.4
1.5
1.5
1.4
1.5
1.5
1.4
18" - 1600
18" - 1600
18" - 1600
18" - 1600
20" - 2100
20" - 2100
20" - 2100
20" - 1900
20" - 1900
20" - 1900
1/6-1100-2
1/6-1100-1
1/6-1100-1
1/3-1100-2
1/3-1100-2
1/3-1100-2
1/3-1100-2
1/3-1100-2
1/3-1100-2
1/3-1100-2
Fan Motor & Condenser
Fan Motor--HP--RPM
Fan Motor--Amps
Fan--DIA/CFM
Blow er Motor & Evap.
Blower Motor--HP-RPM-SPD
Blower Motor--Amps
1.0
1.0
1.0
1.1
2.2
2.2
1.1
2.2
2.2
1.1
CFM Cooling & E.S.P.
w/Filter (Rated-Wet Coil)
600 - .20
800 - .20
800 - .20
800 - .20
1000 - .40
1000 - .40
1000 - .40
1100 - .30
1100 - .30
1100 - .30
Filter Sizes (inches) STD.
16x25x1
16x25x1
16x25x1
16x25x1
16x30x1
16x30x1
16x30x1
16x30x1
16x30x1
16x30x1
335
335
335
335
375
375
375
375
375
375
Shipping Weight --LBS.
Specifications 3-1/2 Ton through 5 Ton
MODELS
W42A1-A
W42A1-B
W42A1-C
W48A1-A
W48A1-B
W48A1-C
W60A1-A
W60A1-B
Electrical Rating--60 Hz
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
197-253
197-253
414-506
197-253
197-253
414-506
197-253
197-253
414-506
Voltage
230/208
230/208
460
230/208
230/208
460
230/208
230/208
460
Rated Load Amps
16.7/18.9
11/12.5
5.8
20/21.9
13.9/15.2
6.8
22.6/25.5
13.5/15.2
7.6
7.8
Operating Voltage Range
W60A1-C
Compressor--Circuit A
Branch Circuit
Selection Current
19.9
13.2
6.1
23.1
16.1
7.1
26.3
15.7
Lock Rotor Amps
109/109
83.1/83.1
41
134/134
91/91
46
134/134
110/110
52
Compressor Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
1/3-825-2
1/3-825-2
1/3-825-1
1/3-825-2
1/3-825-2
1/3-825-1
1/3-825-2
1/3-825-2
1/3-825-1
2.5
2.5
1.3
2.5
2.5
1.3
2.5
2.5
1.3
24" - 2600
24" - 2600
24" - 2600
24" - 2600
24" - 2600
24" - 2600
24" - 2600
24" - 2600
24" - 2600
1/2-1070-2
1/2-1070-2
1/2-1070-2
1/2-1070-2
1/2-1070-2
1/2-1070-2
1/2-1070-2
1/2-1070-2
1/2-1070-2
3.3
3.3
1.9
3.3
3.3
1.9
3.3
3.3
1.9
1400 - .30
1400 - .30
1400 - .30
1550 - .20
1550 - .20
1550 - .20
1700 - .30
1700 - .30
1700 - .30
20x30x1
20x30x1
20x30x1
20x30x1
20x30x1
20x30x1
20x30x1
20x30x1
20x30x1
525
525
525
525
525
525
525
525
525
Fan Motor & Condenser
Fan Motor--HP-RPM-SPD
Fan Motor--Amps
Fan--DIA/CFM
Blow er Motor & Evap.
Blower Motor--HP-RPM-SPD
Blower Motor--Amps
CFM Cooling & E.S.P.
w/Filter (Rated-Wet Coil)
Filter Sizes (inches) STD.
Shipping Weight --LBS.
Form No.
S3397-1112
Supersedes S3397-712
Page
2 of 12
Ventilation System Packages
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All
units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the
factory or field-installed at a later date.
BAROMETRIC FRESH AIR DAMPER - BFAD
STANDARD
The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service
door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the
air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and
closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into
the building and can be easily locked closed if required.
Barometric Fresh Air Damper
BLANK OFF PLATE - BOP
OPTIONAL
A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any
outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not
required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD
OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air,
up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed
with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered
open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower
operation or can be field connected to be managed based on building occupancy.
Motorized Fresh Air Damper
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require
separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing
dampers in the return air grille may be required to achieve specified amount of outdoor air intake.
COMMERCIAL ROOM VENTILATOR - CRV
OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside
ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings.
It includes a built-in exhaust air damper.
Commercial Room Ventilator
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by
providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the
amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled
based on room occupancy. Two versions available (except on 1.5 and 2-Ton models). The CRV and CRVS are
power open - spring return on power loss, and CRVP is power open and power close. Complies with ANSI/ASHRAE
Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.
ECONOMIZER - ECONWM-Series
OPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be
introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and
settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide
“free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running
the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
• ECONWMT Equipment Building versions have extended air intake hood to deliver up to 100% of cooling rated airflow.
16" for ECONWMT-E2 or T2, and E3 or T3
18" for ECONWMT-E5 or T5
• ECONWMS Classroom versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.
Economizer
Standard Features:
• Fully modulating
• Honeywell Direct Drive Hi-Torque Actuator
• No linkage required
• Simple single blade design
• Positive shut-off with non-stick gaskets
• Electronic DB and/or Enthalpy sensors depending upon version
• Honeywell JADE electronic economizer module with precision settings and diagnostics
• DB or Enthalpy economizer versions available
WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF
OPTIONAL
The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality
ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM
(depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and
humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs.
Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.
Energy Recovery Ventilator
The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat
transfer capabilities during summer and winter conditions. Various control schemes are addressed including
limiting ventilation during building occupancy only.
The ERV is designed to be internally mounted behind the service door in the W**A, W**H or W**L model wallmount units. It can be built-in at the factory or field installed as an option. ERVF-*3 and ERVF-*5 can be
independently adjusted for intake and exhaust rates.
Form No.
S3397-1112
Supersedes S3397-712
Page
3 of 12
Airflow (cfm)
Airflow (cfm)
A
B
C
Vent Position
D
E
F
W17A/W18A & W24A TOTAL AND VENTILATION AIRFLOW
Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP
Total Air 0 ESP
Total Air .15 ESP
0
100
A
B
C
Vent Position
D
E
F
0
100
200
200
300
400
500
600
300
Total Air 0 ESP
Total Air .15 ESP
Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP
700
800
900
1000
A
B
C
Vent Position
D
E
F
Total Air 0 ESP
Total Air .15 ESP
Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP
W30A & W36A LOW SPEED TOTAL AND VENTILATION AIRFLOW
400
500
600
700
800
900
1000
1100
1200
W30A & W36A HIGH SPEED TOTAL AND VENTILATION AIRFLOW
Commercial Room Ventilator Performance Data - CRVS-3 and CRVP-3
0
100
200
300
400
500
600
700
800
900
1000
1100
Commercial Room Ventilator Performance Data - CRV-2
Airflow (cfm)
Form No.
S3397-1112
Supersedes S3397-712
Page
4 of 12
Form No.
S3397-1112
Supersedes S3397-712
Page
5 of 12
A
B
C
Vent Position
D
E
F
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
A
B
C
Vent Position
D
E
F
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
W42A & W48A LOW SPEED TOTAL AND VENTILATION AIRFLOW
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
B
C
Vent Position
D
E
F
A
B
C
Vent Position
D
E
F
W60A LOW SPEED TOTAL AND VENTILATION AIRFLOW
A
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
W60A HIGH SPEED TOTAL AND VENTILATION AIRFLOW
2100
2200
W42A & W48A HIGH SPEED TOTAL AND VENTILATION AIRFLOW
2100
Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5
Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5
Airflow (cfm)
Airflow (cfm)
Airflow (cfm)
Airflow (cfm)
Performance and Application Data- ERVF-A2
SUMMER COOLING PERFORMANCE
(INDOOR DESIGN CONDITIONS 75°DB/62°WB)
Ambient
O.D.
D B/
WB
F
75
105
100
95
90
85
80
75
VENTILATION RATE -- 250 CFM
62% EFFICIENCY
VENTILATION RATE -- 225 CFM
63% EFFICIENCY
VENTILATION RATE -- 200 CFM
63% EFFICIENCY
VLT
V LS
V LL
HRT
HRS
HRL
VLT
V LS
V LL
HRT
HRS
HRL
VLT
V LS
V LL
HRT
HRS
HRL
11925
8100
1325
7394
5022
822
10727
7287
3441
6758
4591
2168
9540
6480
3060
6010
4082
1928
0
70
8100
8100
0
5022
5022
0
7287
7287
0
4591
4591
0
6480
6480
0
4082
4082
65
8100
8100
0
5022
5022
0
7287
7287
0
4591
4591
0
6480
6480
0
4082
4082
0
80
17550
6750
10800
10881
4185
6696
15788
6072
9716
9946
3826
6121
14040
5400
8640
8845
3402
5443
75
11925
6750
5175
7394
4185
3209
10727
6072
4655
6758
3826
2933
9540
5400
4140
6010
3402
2608
70
6863
6750
113
4255
4185
70
6173
6072
101
3889
3826
64
5490
5400
90
3458
3402
56
65
6750
6750
0
4185
4185
0
6072
6072
0
3826
3826
0
5400
5400
0
3402
3402
0
60
6750
6750
0
4185
4185
0
6072
6072
0
3826
3826
0
5400
5400
0
3402
3402
0
80
17550
5400
12150
10881
3348
7533
15788
4858
10930
9946
3060
6886
14040
4320
9720
8845
2722
6124
75
11925
5400
6525
7394
3348
4046
10727
4858
5870
6758
3060
3698
9540
4320
5220
6010
2722
3289
70
6863
5400
1463
4255
3348
907
6173
4858
1315
3889
3060
829
5490
4320
1170
3458
2722
737
65
5400
5400
0
3348
3348
0
4858
4858
0
3060
3060
0
4320
4320
0
2722
2722
0
60
5400
5400
0
3348
3348
0
4858
4858
0
3060
3060
0
4320
4320
0
2722
2722
0
80
17550
4050
13500
10881
2511
8370
15788
3643
12145
9946
2295
7651
14040
3240
10800
8845
2041
6804
75
11925
4050
7875
7394
2511
4883
10727
3643
7084
6758
2295
4463
9540
3240
6300
6010
2041
3969
70
6863
4050
2813
4255
2511
1744
6173
3643
2530
3889
2295
1594
5490
3240
2250
3458
2041
1417
65
4050
4050
0
2511
2511
0
3643
3643
0
2295
2295
0
3240
3240
0
2041
2041
0
60
4050
4050
0
2511
2511
0
3643
3643
0
2295
2295
0
3240
3240
0
2041
2041
0
80
17550
2700
14850
10881
1674
9207
15788
2429
13359
9946
1530
8416
14040
2160
11880
8845
1361
7484
75
11925
2700
9225
7394
1674
5720
10727
2429
8298
6758
1530
5228
9540
2160
7380
6010
1361
4649
70
6863
2700
4163
4255
1674
2581
6173
2429
3744
3889
1530
2359
5490
2160
3300
3458
1361
2098
65
2700
2700
0
1674
1674
0
2429
2429
0
1530
1530
0
2160
2160
0
1361
1361
0
60
2700
2700
0
1674
1674
0
2429
2429
0
1530
1530
0
2160
2160
0
1361
1361
0
75
11925
1350
10575
7394
837
6557
10727
1214
9513
6758
765
5993
9540
1080
8460
6010
680
5330
70
6863
1350
5513
4255
837
3418
6173
1214
4959
3889
765
3124
5490
1080
4410
3458
680
2778
65
2363
1350
1013
1465
837
628
2125
1214
911
1339
765
547
1890
1080
810
1190
680
510
60
1350
1350
0
837
837
0
1214
1214
0
765
765
0
1080
1080
0
680
680
0
70
6863
0
6863
4255
0
4255
6173
0
6173
6889
0
3889
5490
0
5490
3458
0
3458
65
2363
0
2363
1465
0
1465
2125
0
2125
1339
0
1339
1890
0
1890
1190
0
1190
60
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
ERVF-A2 WINTER HEATING PERFORMANCE
(INDOOR DESIGN CONDITIONS 70°F DB)
VENTILATION RATE
Ambient
250 C F M
225 C F M
200 C F M
O.D.
74% EFF.
75% EFF.
75% EFF.
DB/°F
WVL
WHR
WVL
WHR
WVL
WHR
65
1350
999
1214
911
1080
810
60
2700
1998
2429
1822
2160
1620
55
4050
2997
3643
2733
3240
2430
50
5400
3996
4858
3643
4320
3240
45
6750
4995
6072
4554
5400
4050
40
8100
5994
7287
5465
6480
4860
35
9450
6993
8501
6376
7560
5670
30
10800
7992
9716
7287
8640
6480
25
12150
8991
10930
8198
9720
7290
20
13500
9990
12145
9108
10800
8100
15
14850
10989
13359
10019
11880
8910
NOTE: Sensible performance only is show n for w inter application.
Form No.
S3397-1112
Supersedes S3397-712
Page
6 of 12
LEGEND:
VLT =
VLS =
VLL =
HRT =
HRS =
HRL =
WVL =
WHR =
Ventilation Load - Total
Ventilation Load - Sensible
Ventilation Load - Latent
Heat Recovery - Total
Heat Recovery - Sensible
Heat Recovery - Latent
Winter Ventilation Load
Winter Heat Recovery
Form No.
S3397-1112
Supersedes S3397-712
Page
7 of 12
75
80
85
90
95
100
105
D B/
WB
2160
2160
60
6917
5443
5443
6917
4082
4082
2721
2721
6917
10980
3780
0
0
1620
8820
6917
2381
0
1360
2381
6917
16920 12020
0
0
6660
14760 12020
23760 17690
0
0
4500
12600 12020
21600 17690
0
0
2340
10440 12020
19440 17690
0
0
0
1360
1360
1360
1360
2721
2721
2721
2721
2721
4082
4082
4082
4082
4082
5443
5443
5443
5443
5443
8164
6804
6804
6804
6804
6804
8164
8164
HRS
V LS
10530 10530
15502 10530
VLT
0
4972
V LL
6739
9921
HRT
7020
7020
8921
15502
5265
5265
8921
15502
3 5 10
3 5 10
8921
15502
6917
2380
0
0
1020
5556
8921
3071
0
1755
3071
8921
10659 15502
0
0
4195
9298
14968 22815
0
0
2835
7938
13608 22815
0
0
1474
6577
12247 22815
0
0
0
1755
1755
1755
1755
3510
3510
3510
3510
3510
5265
5265
5265
5265
5265
7020
7020
7020
7020
7020
6739
5616
5616
5616
5616
5616
6739
6739
HRS
4492
4492
4492
4492
5709
4492
4492
9921
3369
3369
5709
9921
8921
3071
0
0
1316
7166
13747
0
0
5411
11992
5709
1965
0
1123
1965
5709
9921
2246
2246
5709
9921
19305 14601
0
0
3656
10237
0
0
0
1123
1123
1123
1123
2246
2246
2246
2246
2246
3369
3369
3369
3369
17550 14601 3369
0
0
1901
8 48 2
15795 14601 4492
0
10530 10530
0
6739
10886 22815 8775 14040 14601
5216 15502 8775 6727 9921
113
8921 8775
146
5709
0
8775 8775
0
5616
0
8775 8775
0
5616
0
3855
HRL
VENTILATION RATE -- 325 CFM
64% EFFICIENCY
8100
17550
11925
6862
6750
6750
8100
11925
VLT
5400
5400
6862
11925
4050
4050
6862
11925
5709
1965
0
0
842
4586
8798
0
0
3463
7675
6862
2362
0
1350
2362
6862
11925
2700
2700
6862
11925
12355 17550
0
0
2340
6552
11232 17550
0
0
1216
5428
10108 17550
0
8985
4305
93
0
0
0
3182
HRL
0
0
0
1350
1350
1350
1350
2700
2700
2700
2700
2700
4050
4050
4050
4050
4050
5400
5400
5400
5400
5400
8100
6750
6750
6750
6750
6750
8100
8100
V LS
5265
7751
HRT
3510
3510
4460
7751
2632
2632
4460
7751
6862
2362
0
0
1012
5512
10575
0
0
4162
9225
0
0
0
877
877
877
877
1755
1755
1755
1755
1755
2632
2632
2632
2632
2632
3510
3510
3510
3510
3510
5265
4387
4387
4387
4387
4387
5265
5265
HRS
VLT =
VLS =
VLL =
HRT =
HRS =
HRL =
WVL =
WHR =
4460
1535
0
0
658
3583
6873
0
0
2705
5996
9652
0
0
1828
5118
8774
0
0
950
4241
7897
0
7019
3363
73
0
0
0
2486
HRL
75
80
85
90
95
100
105
D B/
WB
7897
9720
9720
65
60
7290
7290
2430
70 12352
0
0
0
65 4252
0
60
70 12352
2430
2430
2430
75 21465
60
4860
60 4860
2430
4860
65 4860
65 4252
4860
4860
75 21465
4860
7290
7290
7290
7290
7290
70 12352
80 31590
60
65
70 12352
75 21465
80 31590
9720
70 12352
9720
9720
9720
75 21465
7897
7897
8029
6318
6318
8029
4738
4738
8029
3159
3159
8029
0
4252
0
2764
8029
1579
2764
8029
0
0
0
1579
1579
1579
1579
3159
3159
3159
3159
3159
4738
4738
4738
4738
4738
6318
6318
6318
6318
6318
7897
7897
HRL
VLT
V LS
12150 12150
12150 12150
17887 12150
V LL
0
0
5737
HRT
8 0 18
8 0 18
11805
17887
8100
8100
10293
6075
6075
10293
17887
4050
4050
10293
0
2764
8029
0
1184
6449
0
3543
10293
2025
3543
10293
12372 17887
0
0
4870
10793 17887
17374 26325
0
0
3290
9213
15794 26325
0
0
1711
7634
0
0
0
2025
2025
2025
2025
4050
4050
4050
40 5 0
4050
6075
6075
6075
6075
6075
8100
8100
8100
8100
8100
10125 10125
10125 10125
10293 10125
17887 10125
14215 26325
0
0
131
6054
6682
6682
6793
11805
5345
5345
6793
11805
4009
4009
6793
2672
2672
6793
0
3543
10293
0
1518
8268
0
2338
6793
1336
2338
6793
15862 11805
0
0
6243
13837 11805
22275 17374
0
0
4218
11812 11805
20250 17374
0
0
2193
9787
18225 17374
0
0
168
7762
12635 26325 10125 16200 17374
0
0
4475
0
0
0
1336
1336
1336
1336
2672
2672
2672
2672
2672
4009
4009
4009
4009
4009
5345
5345
5345
5345
5345
6682
6682
6682
6682
6682
8018
8018
8018
HRS
VENTILATION RATE 375 CFM
66% EFFICIENCY
HRL
VLT
9720
9720
14310
8100
8100
8235
14310
6480
6480
8235
14310
4860
4860
8235
14310
3240
3240
8235
14310
0
2338
6793
0
1002
5457
0
2835
8235
1620
2835
8235
10469 14310
0
0
4120
9132
14701 21060
0
0
2784
7796
13365 21060
0
0
1447
6459
12028 21060
0
0
111
5123
10692 21060
0
0
3786
0
0
0
1620
1620
1620
1620
3240
3240
3240
3240
3240
4860
4860
4860
4860
4860
6480
6480
6480
6480
6480
8100
8100
8100
8100
8100
9720
9720
9720
V LS
HRT
6512
6512
9587
5427
5427
5517
9587
9587
4341
4341
5517
3256
3256
5517
9587
0
2835
8235
0
1215
6615
12690
0
0
4995
11070
0
1899
5517
1085
1899
5517
9587
2170
2170
5517
9587
17820 14110
0
0
3375
9450
16200 14110
0
0
1755
7830
14580 14110
0
0
135
6210
12960 14110
0
0
4590
V LL
0
0
0
1085
1085
1085
1085
2170
2170
2170
2170
2170
3256
3256
3256
3256
3256
4341
4341
4341
4341
4341
5427
5427
5427
5427
5427
6512
6512
6512
HRS
VENTILATION RATE 300 CFM
67% EFFICIENCY
ERVF-*5 WINTER HEATING PERFORMANCE
(INDOOR DESIGN CONDITIONS 70°F DB)
VENTILATION RATE
Ambient
450 C F M
375 C F M
300 C F M
O.D.
80% EFFICIENCY
81% EFFICIENCY
82% EFFICIENCY
DB/°F
WVL
WHR
WVL
WHR
WVL
WHR
65
2430
1944
2025
1640
1620
1328
60
4860
3888
4050
3280
3240
2656
55
7290
5832
6075
4920
4860
3985
50
9720
7776
8100
6561
6480
5313
45
12150
9720
10125
8201
8100
6642
40
14580
11664
12150
9841
9720
7970
35
17010
13608
14175
11481
11340
9298
30
19440
15552
16200
13122
12960
10627
25
21870
17496
18225
14762
14580
11955
20
24300
19440
20250
16402
16200
13284
15
26730
21384
22275
18042
17820
14612
NOTE: Sensible performance only is show n for w inter application.
12352
0
1822
9922
19035 13952
0
0
7492
16605 13952
26730 20533
0
0
5062
14175 13952
24300 20533
0
0
2632
11744 13952
21870 20533
0
60 12150 12150
9720
0
65 12150 12150
80 31590
202
70 12352 12150
7897
7897
75 21465 12150
13952
80 31590 12150 19440 20533
9314
9477
9477
0
65 14580 14580
HRS
9477
9477
0
70 14580 14580
HRT
13952
9477
V LL
6884
V LS
VLT
VENTILATION RATE 450 CFM
65% EFFICIENCY
75 21465 14580
F
Ambient
O.D.
SUMMER COOLING PERFORMANCE
(INDOOR DESIGN CONDITIONS 75°DB/62°WB)
Performance and Application Data- ERVF-*5
Ventilation Load - Total
Ventilation Load - Sensible
Ventilation Load - Latent
Heat Recovery - Total
Heat Recovery - Sensible
Heat Recovery - Latent
Winter Ventilation Load
Winter Heat Recovery
LEGEND:
4460
1535
0
877
1535
4460
7751
1755
1755
4460
7751
14850 11407
0
0
2812
7875
13500 11407
0
0
1462
6525
12150 11407
0
5265
10800 11407
5175 7751
112
4460
0
4387
0
4387
0
3825
V LL
VENTILATION RATE -- 250 CFM
65% EFFICIENCY
ERVF-*3 WINTER HEATING PERFORMANCE
(INDOOR DESIGN CONDITIONS 70°F DB)
VENTILATION RATE
Ambient
400 C F M
325 C F M
250 C F M
O.D.
75% EFFICIENCY
76% EFFICIENCY
77% EFFICIENCY
DB/°F
WVL
WHR
WVL
WHR
WVL
WHR
65
2160
1620
1755
1333
1350
1039
60
4320
3240
3510
2667
2700
2079
55
6480
4860
5265
4001
4050
3118
50
8640
6480
7020
5335
5400
4158
45
10800
8100
8775
6669
6750
5197
40
12960
9720
10530
8002
8100
6237
35
15120
11340
12285
9336
9450
7276
30
17280
12960
14040
10670
10800
8316
25
19440
14580
15795
12004
12150
9355
20
21600
16200
17550
13338
13500
10395
15
23760
17820
19305
14671
14850
11434
NOTE: Sensible performance only is show n for w inter application.
0
0
0
2160
2160
3780
2160
75 19080
65
4320
70 10980
4320
60 4320
4320
75 19080
65 4320
4320
80 28080
4320
6480
6480
60
70 10980
6480
75 19080
6480
6480
80 28080
6480
6480
8640
60
65
8640
8640
70 10980
8640
8640
70 10980
65
8640
75 19080
70 10980
65 3780
60
0
8164
12020
HRT
12960
0
8164
10800 17280 17690
10800 8280 12020
10800 180
6717
10800
0
6804
10800
0
6804
8640
12960
28080
19080
10980
10800
10800
80 28080
65
80
75
70
65
60
0
6120
75 19080 12960
70 12960 12960
V LL
VLT
VENTILATION RATE -- 400CFM
63% EFFICIENCY
V LS
F
Ambient
O.D.
SUMMER COOLING PERFORMANCE
(INDOOR DESIGN CONDITIONS 75°DB/62°WB)
Performance and Application Data- ERVF-*3
HRL
0
1899
5517
0
814
4432
8502
0
0
3346
7416
11939
0
0
2261
6331
10854
0
0
1175
5246
9768
0
0
90
4160
8683
0
0
3075
Electrical Specifications
Single Circuit
Model
W17A1/W18A1 - A00, A0Z
A 05
A 08
A 10
W24A1 - A00, A0Z
A 04
A 05
A 08
A 10
W24A1 - B00, B0Z
B 06
W24A1 - C00, C0Z
C 06
W30A1 - A00*, A0Z*
A 05*
A 08
A 10*
A 15
W30A1 - B00*, B0Z*
B 06
B 09*
B 15
W30A1 - C00*, C0Z*
C 06
C 09*
C 15
W36A1 - A00*, A0Z*
A 05*
A 08
A 10*
A 15
W36A1 - B00*, B0Z*
B 06
B 09*
B 15
W36A1 - C00*, C0Z*
C 06
C 09*
C 15
W42A1 - A00, A0Z 4
A 05 4
A 10 4
A 15
A 20
W42A1 - B00, B0Z 4
B 09 4
B 15
B 18 4
W42A1 - C00, C0Z 4
C 09 4
C 15
W48A1 - A00, A0Z 4
A 05 4
A 10 4
A 15
A 20
W48A1- B00, B0Z 4
B 09 4
B 15
B 18 4
W48A1 - C00, C0Z 4
C 09 4
C 15
W60A1 - A00, A0Z 4
A 05 4
A 10 4
A 15
A 20
W60A1 - B00, B0Z 4
B 09 4
B 15 4
B 18 4
W60A1 - C00, C0Z 4
C 09 4
C 15
Rated
Volts
and Phase
2 Field
No. Field 3 Minimum 1 Maximum
Circuit
External Fuse
Power
Power
Ampacity or Ckt. Brkr. Wire Size
Circuits
230/208-1
1
1
1
1
230/208-1
1
1
1
1
230/208-3
460-3
230/208-1
1
230/208-3
460-3
230/208-1
1
230/208-3
460-3
230/208-1
1
1
230/208-3
460-3
230/208-1
1
1
230/208-3
460-3
230/208-1
1
1
230/208-3
460-3
1
1
1
1
1
1
1
1
or 2
1
1
1
1
1
1
1
1
1
1
1
1
or 2
1
1
1
1
1
1
1
1
1
1
1
or 2
or 2
1
1
1
2
1
1
1
1
1
1
or 2
or 2
1
1
1
2
1
1
1
1
1
1
or 2
or 2
1
1
1
2
1
1
1
16
30
46
56
21
25
30
46
56
15
22
10
12
24
32
48
58
84
18
24
33
51
11
12
17
26
29
32
48
58
84
23
24
33
51
12
12
17
26
33
33
59
85
111
25
34
53
N/A
13
18
27
37
37
59
85
111
29
34
53
N/A
14
18
27
41
41
59
85
111
29
34
53
N/A
15
18
27
20
30
50
60
30
30
30
50
60
20
25
15
15
35
35
50
60
90
20
25
35
60
15
15
20
30
35
35
50
60
90
30
30
35
60
15
15
20
30
50
50
60
90
125
35
35
60
N/A
15
20
30
50
50
60
90
125
40
40
60
N/A
20
20
30
60
60
60
90
125
40
40
60
N/A
20
20
30
12
10
8
6
10
10
10
8
6
14
10
14
14
8
8
8
6
4
12
10
8
8
14
14
12
10
8
8
8
6
4
10
10
8
6
14
14
10
10
8
8
6
4
2
8
8
6
N/A
14
12
10
8
8
6
4
2
8
8
6
N/A
12
12
10
8
8
6
4
2
8
8
6
N/A
12
12
10
2 Ground
Wire
12
10
10
10
10
10
10
10
10
14
10
14
14
10
10
10
10
8
12
10
10
10
14
14
12
10
10
10
10
10
8
10
10
10
10
14
14
10
10
10
10
10
8
6
10
10
10
N/A
14
12
10
10
10
10
8
6
10
10
10
N/A
12
12
10
10
10
10
8
6
10
10
10
N/A
12
12
10
Dual Circuit
3 Minimum
1 Maximum
2 Field
2 Ground
Circuit
External Fuse
Power
Wire Size
Ampacity
or Ckt. Brkr.
Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
58
26
60
30
6
10
10
10
58
26
60
30
6
10
10
10
59
59
26
52
60
60
30
60
6
6
10
6
10
10
10
10
34
28
35
30
8
10
10
10
59
59
26
52
60
60
30
60
6
6
10
6
10
10
10
10
34
28
40
30
8
10
10
10
59
59
26
52
60
60
30
60
6
6
10
6
10
10
10
10
34
28
40
30
8
10
10
10
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
4 These models are available with dehumidification with hot gas reheat.
Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment
Factors when more than three (3) current carrying conductors are in a raceway.
* Top outlet supply option is available only factory installed and only on the selected models.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.
Form No.
S3397-1112
Supersedes S3397-712
Page
8 of 12
Indoor Blower Performance - CFM at Rated Volts
ESP
in
H2O
W17A1
W18A1
W30A1
W36A1
W24A1
W42A1
W48A1
W60A1
High Speed
Dry/Wet Coil
Low Speed
Dry/Wet Coil
Single Speed
Dry/Wet Coil
High Speed
Dry/Wet Coil
Low Speed
Dry/Wet Coil
High Speed
Dry/Wet Coil
Low Speed
Dry/Wet Coil
High Speed
Dry/Wet Coil
Low Speed
Dry/Wet Coil
0
925/885
670/655
1020/975
1395/1315
950/935
1885/1800
1650/1600
2200/2000
1600/1450
.1
875/845
650/630
960/905
1340/1270
930/915
1770/1665
1550/1500
2100/1900
1525/1375
.2
825/795
625/600
865/800
1285/1190
910/885
1635/1550
1450/1400
2000/1800
1465/1200
.3
775/740
575/555
820/735
1205/1100
855/830
1500/1400
1350/1300
1875/1700
-/-
.4
710/670
525/500
735/650
1110/1000
800/755
1370/1285
1300/1175
1775/1600
-/-
.5
635/600
465/440
615/535
1005/870
-/-
1250/1150
-/-
1650/1475
-/-
Above data is with 1" standard throwaway filter and 1" washable filter.
For optional 2" pleated filter - reduce ESP by .15 in.
See installation instructions for maximum ESP information on various KW application.
Speeds marked “bold” above
are Factory Connected.
Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model
At 240V (1)
Nominal
KW
Kw
5.0
5.0
6.0
6.0
8.0
8.0
1-Ph Amps 3-Ph Amps
20.8
14.4
33.3
9.0
9.0
10.0
10.0
41.7
21.7
15.0
15.0
62.5
18.0
18.0
20.0
20.0
83.3
At 208V (1)
Btuh
Kw
17,065
3.75
20,478
4.50
27,304
6.00
30,717
6.75
34,130
7.50
36.1
54.1
36.1
51,195
11.25
43.3
61,434
13.50
68,260
15.00
1-Ph Amps 3-Ph Amps
18.0
At 480V (2)
Btuh
At 460V (2)
Kw
3-Ph Amps
Btuh
Kw
3-Ph Amps
Btuh
6.0
7.2
20,478
5.52
6.9
18,840
9.0
10.8
30,717
8.28
10.4
28,260
12,799
12.5
28.8
15,359
20,478
18.7
23,038
25,598
31.2
38,396
15.0
18.0
51,195
13.80
17.3
47,099
37.5
46,076
18.0
21.7
61,434
16.56
20.8
56,519
72.1
51,195
(1) These electric heaters are available in 230/208V units only.
(2) These electric heaters are available in 480V units only.
Heater Packages - Field Installed
• Designed for adding Electric Heat to 0 KW Units
• Circuit Breaker Standard on 230/208V Models
-A00 Models
Air Conditioner
230/208-1
Models
Heater Model #
EHWA02-A05
W17A1
EHW02A-A08
W18A1
EHWA02A-A10
EHWA02-A05
W24A1
EHW02A-A08
EHWA02A-A10
EHWA03-A05
EHWA03-A08
W30A1
EHWA03-A10
EHWA03-A15
EHWA03-A05
EHWA03-A08
W36A1
EHWA03-A10
EHWA03-A15
EHWA05-A05 1
W42A1
EHWA05-A10 1
W48A1
EHWA05-A15
EHWA05-A20
EHWA60-A05 1
EHWA05-A10 1
W60A1
EHWA05-A15
EHWA05-A20
KW
5
8
10
5
8
10
5
8
10
15
5
8
10
15
5
10
15
20
5
10
15
20
• ETL US & Canada Listed
• Toggle Disconnect Standard on 460V Models
-B00 Models
-C00 Models
230/208-3
460-3
Heater Model #
KW
Heater Model #
N/A
KW
N/A
EHWA24-B06
6
EHWH24B-C06
6
EHWA03-B06
EHWA03-B09
EHWA37-B15
6
9
15
EHWC03A-C06
EHWC03A-C09
EHWA03A-C15
6
9
15
EHW36A-B06
EHWA03-B09
EHWA37-B15
6
9
15
EHWC03A-C06
EHWC03A-C09
EHWA03A-C15
6
9
15
EHWA05-B09 1
EHWA05-B15
EHW05A-B18 1
9
15
18
EHWA05A-C09 1
EHWA05A-C15
9
15
EHW60A-B09 1
EHWA05-B15 1
EHW05A-B18 1
9
15
18
EHWA05A-C09 1
EHWA05A-C15
9
15
NOTE: Field installed Heater Packages are not approved for use with top supply opening models.
1 These heater packages approved for use in dehumidification versions with hot gas reheat.
Form No.
S3397-1112
Supersedes S3397-712
Page
9 of 12
Cooling Application Data - Outdoor Temperature 1
Model
W17A1
W18A1
W24A1
W30A1
W36A1
W42A1
W48A1
W60A1
D.B./W.B.
2
Cooling
Capacity
75oF
80oF
85oF
90oF
95oF
100oF
105oF
110oF
115oF
120oF
75/
62
Total Cooling
Sensible Cooling
17,500
13,900
16,700
13,500
15,900
13,200
15,100
12,800
14,300
12,500
13,600
12,200
12,900
11,800
12,200
11,500
11,600
11,100
10,800
10,700
80/
67
Total Cooling
Sensible Cooling
18,600
13,400
18,100
13,200
17,600
13,000
17,000
12,800
16,400
12,600
15,800
12,400
15,200
12,100
14,500
11,800
13,900
11,500
13,100
11,200
85/
72
Total Cooling
Sensible Cooling
22,200
13,800
21,200
13,400
20,200
13,100
19,200
12,800
18,300
12,400
17,300
12,000
16,400
11,600
15,500
11,100
14,600
10,600
13,700
10,200
75/
62
Total Cooling
Sensible Cooling
26,000
20,100
24,500
19,700
23,300
19,200
22,100
18,800
20,900
18,400
20,000
17,900
19,100
17,400
18,400
16,900
17,600
16,400
17,100
15,900
80/
67
Total Cooling
Sensible Cooling
27,700
19,500
26,700
19,300
25,800
19,000
24,900
18,800
24,000
18,500
23,300
18,200
22,500
17,800
21,900
17,400
21,200
17,000
20,700
16,600
85/
72
Total Cooling
Sensible Cooling
33,000
20,000
31,200
19,600
29,700
19,100
28,100
18,700
26,700
18,200
25,500
17,600
24,300
17,000
23,300
16,300
22,300
15,700
21,500
15,000
75/
62
Total Cooling
Sensible Cooling
31,100
24,500
29,700
24,000
28,300
23,500
27,000
22,900
25,800
22,400
24,700
21,800
23,700
21,300
22,700
20,700
21,700
20,100
20,900
19,500
80/
67
Total Cooling
Sensible Cooling
33,200
23,700
32,300
23,500
31,400
23,200
30,400
22,900
29,600
22,600
28,600
22,200
27,800
21,800
27,000
21,400
26,100
20,900
25,300
20,400
85/
72
Total Cooling
Sensible Cooling
39,600
24,300
37,800
23,900
36,100
23,300
34,500
22,800
32,900
22,200
31,500
21,500
30,100
20,800
28,800
20,100
27,500
19,300
26,300
18,500
75/
62
Total Cooling
Sensible Cooling
38,100
28,500
35,900
27,800
34,100
27,100
32,300
26,400
30,800
25,800
29,600
25,200
28,600
24,700
27,700
24,200
26,900
23,700
26,400
23,200
80/
67
Total Cooling
Sensible Cooling
40,600
27,600
39,100
27,200
37,800
26,800
36,500
26,400
35,400
26,000
34,500
25,600
33,700
25,300
33,000
25,000
32,400
24,600
32,000
24,300
85/
72
Total Cooling
Sensible Cooling
48,400
28,300
45,700
27,600
43,400
26,900
41,200
26,200
39,300
25,500
37,800
24,800
36,400
24,100
35,100
23,500
34,100
22,700
33,300
22,000
75/
62
Total Cooling
Sensible Cooling
43,600
35,500
41,500
34,500
39,600
33,600
37,600
32,700
35,700
31,800
33,900
31,000
32,100
30,100
30,400
29,200
28,700
28,400
27,000
27,000
80/
67
Total Cooling
Sensible Cooling
46,500
34,400
45,200
33,800
43,900
33,300
42,500
32,700
41,000
32,100
39,500
31,500
37,900
30,900
36,200
30,200
34,500
29,500
32,700
28,800
85/
72
Total Cooling
Sensible Cooling
55,400
35,200
52,900
34,300
50,400
33,500
48,000
32,500
45,600
31,500
43,200
30,500
40,900
29,500
38,500
28,300
36,300
27,200
34,000
26,000
75/
62
Total Cooling
Sensible Cooling
49,600
39,900
47,300
39,100
45,100
38,200
43,000
37,300
40,900
36,400
39,000
35,500
37,100
34,500
35,100
33,600
33,300
32,700
31,400
31,400
80/
67
Total Cooling
Sensible Cooling
52,900
38,700
51,500
38,300
50,100
37,800
48,600
37,300
47,000
36,700
45,400
36,100
43,700
35,400
41,900
34,700
40,000
34,000
38,100
33,100
85/
72
Total Cooling
Sensible Cooling
63,000
39,600
60,200
38,900
57,500
38,000
54,900
37,100
52,200
36,000
49,700
34,900
47,100
33,800
44,600
32,500
42,000
31,300
39,600
29,900
75/
62
Total Cooling
Sensible Cooling
59,200
45,200
56,200
43,800
53,300
42,300
50,500
41,000
47,900
39,700
45,400
38,500
43,100
37,300
40,800
36,100
38,600
35,000
36,600
33,900
80/
67
Total Cooling
Sensible Cooling
63,200
43,800
61,200
42,900
59,200
41,900
57,100
41,000
55,000
40,100
52,900
39,200
50,800
38,300
48,700
37,300
46,500
36,400
44,300
35,500
85/
72
Total Cooling
Sensible Cooling
75,300
44,900
71,600
43,600
68,000
42,100
64,500
40,700
61,100
39,300
57,900
37,900
54,800
36,500
51,800
35,000
48,900
33,500
46,000
32,100
Capacity Multiplier Factors
% of Rated Airflow
Total BTUH
Sensible BTUH
1 Below 65°F (18.3C), unit requires a factory or field installed low ambient control.
2 Return air temperature.
Form No.
S3397-1112
Supersedes S3397-712
Page
10 of 12
-10
Rated
+10
0.975
0.950
1.0
1.0
1.02
1.05
Air Conditioning Wall-Mount Model Nomenclature
W
36 A
1
A
10
X
X
X
X
X
X
| CONTROL MODULES
(See Chart Below)
SERIES |
REVISION
KW 1
TYPE
Air Conditioner
NOMINAL
CAPACITY |
17 - 1½ Ton
18 - 1½ Ton
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
Specialty Products 2
(Non-Standard)
VENTILATION OPTIONS
(See Table Below)
VOLTS & PHASE |
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
FILTER OPTIONS
X - 1-inch Throwaway (Standard)
W - 1-inch Washable
P - 2-inch Pleated (MERV 8)
| COIL OPTIONS
X - Standard
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator
and Condenser
COLOR OPTIONS
X - Beige (Standard)
1 - White
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
A - Aluminum
S - Stainless Steel
| OUTLET OPTIONS
X - Front (Standard)
T - Top (on W30A and
W36A Models)
1 For 0KW and circuit breakers (230/208 Volt) or toggle disconnects (460 Volt) applications, insert 0Z in the KW field of the model number.
See Page 8 for available Factory Installed KW options and Page 9 for Field Installed Heater Packages.
2 Insert “D” for dehumidification with hot gas reheat — Models W42 - 60 only. See Form 7960-572 for complete details.
Ventilation Options
Models
Description
Barometric Fresh Air Damper - Standard
Blank-Off Plate
Motorized Fresh Air Damper
Commercial Ventilator - Spring Return w/Exhaust
Commercial Ventilator - Power Return w/Exhaust
Economizer - School Versions, Enthalpy 4
Economizer - Equipment Bldg., Enthalpy 5
Economizer - Equipment Bldg., DB Temp 5
Energy Recovery Ventilator - 230 Volt 3
Energy Recovery Ventilator - 460 Volt 3
Door Kit for ERVF (Required)
1
2
3
4
5
6
W17A1, W18A1, W24A1
Factory Installed
Field Installed
Code No.
Part No.
X
BFAD-2
B
BOP-2
MFAD-2
M
V
CRV-2
----S
ECONWMS-E2 23
W
ECONWMT-E2 2
T
ECONWMT-T2 2
R
ERVF-A2
N/A
ERVF-C2 6
N/A
WMDK2- 3
W30A1, W36A1
Factory Installed
Field Installed
Code No.
Part No.
X
BFAD-3
B
BOP-3
M
MFAD-3
V
CRVS-3
P
CRVP-3
S
ECONWMS-E3 23
W
ECONWMT-E3 2
T
ECONWMT-T3 2
R
ERVF-A3 1
R
ERVF-C3 1
N/A
WMDK3- 3
W42A1, W48A1, W60A1
Factory Installed
Field Installed
Code No.
Part No.
X
BFAD-5
B
BOP-5
M
MFAD-5
V
CRVS-5
P
CRVP-5
S
ECONWMS-E5 23
W
ECONWMT-E5 2
T
ECONWMT-T5 2
R
ERVF-A5 1
R
ERVF-C5 1
N/A
WMDK5- 3
Intake and exhaust can be independently adjusted.
Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)
WMDK Door Kit must be ordered in addition to ERVF Assembly and ECONWMS & color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)
Partial Full Flow (75% of Rated Cooling CFM). All ECONWMS versions have 3" deep intake hood.
Full Flow (100% of Rated Cooling CFM). ECONWMT 2 and 3 have 16" deep intake hood; ECONWMT- 5 has 18" deep intake hood.
Model W24A1-C only.
Air Conditioning Control M odules
HPC 1
LP C 2
CCM 3
STD
STD
STD
LAC 4 11
STD
STD
STD
z
STD
STD
STD
z
STD
STD
STD
z
STD
STD
STD
z
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
STD
A LR 5
SK 6
SK 7
ODT 8
DDC 9
Field Installed Part
X
N/A
N/A
E
11
CMA-28
N/A
J
11
Factory Only
J
K
11
CMC-15 and CMA-28
N/A
M
11
z
z
z
z
z
Factory Only
M
N/A
N/A
Field Installed Only
CMC-15
CMC-15
Field Installed Only
CMA-14
N/A
N, W18A Only
z
z
z
Factory Installed Code
W17A1
Factory
Only
All Models Except As Noted
z
z
z
z
12
Factory Only
N/A
Field Installed Only
CMA-23 for W18-36A
CMA-24 for W42-60A
N/A
Field Installed Only
SK111
SK111
V
11
STD = Standard equipment for these specified models.
1 HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3.
2 LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3.
3 CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for
high and/or low-pressure controls, and a 2-minute timed bypass for low-pressure control.
4 LAC. Low ambient control permits cooling operation down to 0°F. LAC is fan-cycling control for outdoor fan motor on all models except W17A1, which is modulating control.
5 ALR. The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls.
6 SK. PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 is used.
7 SK. Start capacitor and potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if
CMC-15 is used.
8 ODT. Outdoor thermostat is adjustable from 0 to 50°F. It is suitable for use as a compressor cut-off thermostat.
9 DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data
such as temperature, as well as digital data such as airflow, compressor status or filter status. Special economizer required; consult factory.
“V” control module should be ordered in conjunction with direct digital controller (DDC) model TCS24. Refer to DDC specification sheet S3280 for more information.
11
Option not available for Model W18A.
12
Form No.
S3397-1112
Use option N for Alarm Relay on Model W18A only.
Supersedes
Page
S3397-712
11 of 12
Clearances Required for Service Access
and Adequate Condenser I nlet Airflow
M inimum Clearances Required to
Combustible M aterials
MODELS
MODELS 1
LEFT SIDE
RIGHT SIDE
W17A, W18A, W24A, W30A, W36A
15"
20"
W42A, W48A, W60A
20"
20"
SUPPLY AIR DUCT
FIRST THREE FEET
W17A, W18A, W24A
NOTE: For side by side installation of two (2) WA models there
must be 20" between units. This can be reduced to 15" by using a
WL model (left side compressor and controls) for the left unit and
WA (right side compressor and controls) for right unit.
See WL Specifications S3400.
CABINET
0"
0"
W30A, W36A
1/4"
0"
W42A, W48A, W60A
1/4"
0"
1 Refer to the Installation Manual for more detailed information.
Dimensions of Basic Unit for Architectural and I nstallation Requirements (Nominal)
MODEL
WIDTH DEPTH HEIGHT SUPPLY
(W)
(D)
(H)
A
B
RETURN
C
B
E
F
G
I
J
K
L
M
N
O
P
Q
W17A
W18A 33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 10.88 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55
W24A
W30A
38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 10.88 25.75 17.93 26.75 28.75 29.25 27.00 2.75 39.13 22.75 9.14
W36A
W42A
W48A 42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00
W60A
R
S1
S2
T
4.19 12.00 12.00 5.00
4.19 12.00 12.00 5.00
1.44 16.00 16.00 1.88
All dimensions are in inches. Dimensional drawings are not to scale.
Built In
Rain Hood
4° Pitch
Heater
Access
Panel
Electric
Heat
C. Breaker/
Disconnect
Access Panel
(Lockable)
W
D
1
1
7.88
1.00
F
Filter Access Panel
Standard flush
vent door for
non-ERV/Econ.
models
1
.44
2.13
A
I
ERV and ECONWMS
only hood
5.88
E
O
31.88
3"
C H
Side Wall
Mounting
Brackets
(Built In)
Supply Air Opening
R
S1
B
Top Rain
Flashing
Shipping
Location
S1
Optional
Electrical
Entrances
Return Air Opening
S1
Ventilation Air
S2
G
Condenser
Air Outlet
Low Voltage
Electrical
Entrance
High Voltage
Electrical
Entrance
K
Cond.
Air
Inlet
J
Equipment Building Hood
ECONWMT-E2, -T2, -E3, -T3 is 16"
ECONWMT-E5, -T5 is 18"
M
S2
P
T
Drain
Front View
L
Side View
N
Q
Back View
Bottom Installation
Bracket
MIS-3122
1 Optional top outlet (factory installed only) for W30A and W36A models only.
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Since 1914 . . . Moving ahead, just as planned.
Form No.
S3397-1112
Supersedes S3397-712
Page
12 of 12
Due to our continuous product improvement policy,
all specifications subject to change without notice.
Before purchasing this appliance, read important energy cost
and efficiency information available from your retailer.
Form No.
S3397
November, 2012
Supersedes: S3397-712
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Create Date : 2013:12:04 14:38:26-05:00 Keywords : W17A1-A, W18A1-A, W24A1-A, W24A1-B, W24A1-C, W30A1-A, W30A1-B, W30A1-C, W36A1-A, W36A1-B, W36A1-C, W42A1-A, W42A1-B, W42A1-C, W48A1-A, W48A1-B, W48A1-C, W60A1-A, W60A1-B, W60A1-C Modify Date : 2013:12:04 16:29:53-05:00 XMP Toolkit : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04 Producer : Acrobat Distiller 7.0 (Windows) Creator Tool : Adobe PageMaker 7.0 Metadata Date : 2013:12:04 16:29:53-05:00 Format : application/pdf Title : S3397 (2012 11) Creator : Description : S Subject : W17A1-A, W18A1-A, W24A1-A, W24A1-B, W24A1-C, W30A1-A, W30A1-B, W30A1-C, W36A1-A, W36A1-B, W36A1-C, W42A1-A, W42A1-B, W42A1-C, W48A1-A, W48A1-B, W48A1-C, W60A1-A, W60A1-B, W60A1-C Document ID : uuid:1df19085-787c-4f5b-b93a-8dd4fab53d7c Instance ID : uuid:fb191203-6e2e-4156-8f8e-a7c109912f8a Page Layout : OneColumn Page Count : 12EXIF Metadata provided by EXIF.tools