THE WALL-MOUNT™ AIR CONDITIONERS - 9.0 EER, (60HZ)
Models W17A to W60A
1.5 to 5 Ton (16,400 to 55,000 Btuh)
Right Side Control Panel
60Hz

GREEN REFRIGERANT
R-410A

The Bard Wall-Mount Air Conditioner is a self contained energy efficient
system, which is designed to offer maximum indoor comfort at a minimal
cost without using valuable indoor floor space or outside ground space.
This unit is the ideal product for versatile applications such as: new
construction, modular offices, school modernization, telecommunication
structures, portable structures or correctional facilities. Factory or field
installed accessories are available to meet specific job requirements.

Engineered Features
Aluminum Finned Copper Coils:
Grooved tubing and enhanced louvered
fin for maximum heat transfer and
energy efficiency.
Twin Blowers:
Move air quietly. Most models feature
multispeed blower motors providing
airflow adjustment for high and low
static operation. Motor overload
protection is standard on all models.
Air Conditioner Compressor:
Scroll Compressors eliminate need for
crankcase heater. Standard on 1½ to
5 ton.
R-410A Refrigerant:
Designed with R-410A (HFC) nonozone depleting refrigerant in
compliance with the Montreal protocol
and 2010 EPA requirements.
Phase Rotation Monitor:
Standard on all 3 phase scroll
compressors. Protects against reverse
rotation if power supply is not properly
connected.
Galvanized 20 Gauge Zinc Coated
Steel Cabinet:
Cleaned, rinsed, sealed and dried
before the polyurethane primer is
applied. The cabinet is handsomely
finished with a baked on textured
enamel, which allows it to withstand
1000 hours of salt spray tests per
ASTM B117-03.
Foil Faced Insulation:
Standard on all units.
Full Length Mounting Brackets:
Built into cabinet for improved
appearance and easy installation.
NOTE: Bottom mounting bracket
included to assist in installation.

Electrical Components:
Are easily accessible for routine
inspection and maintenance through a
right side, service panel opening.
Features a lockable, hinged access
cover to the circuit breaker or toggle
disconnect switch.
Electric Heat Strips:
Features an automatic limit and thermal
cut-off safety control. Heater packages
can be factory or field installed for all 1½
through 5 ton models.
Filter Service Door:
Separate service door provides easy
access for filter change.
One Inch, Disposable Air Filters:
Are standard equipment. Optional one
inch washable filters available and filter
racks permit the addition of 2" pleated
filter. Factory or field installed.
Condenser Fan and Motor
Shroud Assembly:
Slides out for easy access.

Liquid Line Filter Drier:
Standard on all units. Protects system
against moisture.

Barometric Fresh Air Damper:
Standard on all units. Allows up to 25%
outside fresh air. Optional ventilation
packages available.

Compressor Control Module:
Standard on all units. Built-in off-delay
timer adjustable from 30 seconds to 5
minutes. 2-minute on-delay if power
interrupt. 120-second bypass for low
pressure control, and both soft and
manual lockouts for high and low
pressure controls. Alarm output for
alarm relay.

Built-in Circuit Breakers:
Standard on all electric heat versions of
single (230/208 volt) and three phase
(230/208 volt) equipment. Toggle
disconnects are standard on all electric
heat versions of three phase (460 volt)
equipment.
Slope Top:
Standard feature for water run-off.
Top Rain Flashing:
Standard feature on all models.

High & Low Pressure Switches are
Auto-Reset:
Standard on all units. Built-in lockout
circuit resets from the room thermostat.
Provides commercial quality protection to
the compressor.

• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2010.
• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL
1995/CSA 22.2 No. 236-05, Fourth Edition.
• Commercial Product - Not intended for Residential application.
Form No.
S3397-1112
Supersedes S3397-712
Page
1 of 12

Capacity and Efficiency Ratings
MODELS

W17A1 / W18A1

W24A1

W30A1

W36A1

W42A1

W48A1

W60A1

16,400

24,000

29,600

35,400

41,000

47,000

55,000

9.20

9.00

9.00

9.00

9.20

9.00

9.00

Cooling Capacity BTUH 1
EER 2

1 Capacity is certified in accordance with ANSI/ARI Standard 390-2003.
2 EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003.

All ratings based on fresh air intake being 100% closed (no outside air introduction).

Specifications 1-1/2 Ton through 3 Ton
MODELS

W17A1-A
W18A1-A

W24A1-A

W24A1-B

W24A1-C

W30A1-A

W30A1-B

W30A1-C

W36A1-A

W36A1-B

W36A1-C

Electrical Rating--60 Hz

230/208 - 1

230/208 - 1

230/208 - 3

460 - 3

230/208 - 1

230/208 - 3

460 - 3

230/208 - 1

230/208 - 3

460 - 3

197-253

197-253

197-253

414-506

197-253

197-253

414-506

197-253

197-253

414-506

Operating Voltage Range
Compressor--Circuit A

230/208

230/208

230/208

460

230/208

230/208

460

230/208

230/208

460

Rated Load Amps

Voltage

6.5/7.2

11./12.4

7.2/8.1

5.0

11.7/13.3

7.5/8.5

5.3

15.9/17.7

11.8/13.1

6.0

Branch Circuit
Selection Current

9.0

12.9

8.4

5.2

14.2

9.0

5.7

18

13.3

6.0

Lock Rotor Amps

48/48

64/64

58/58

28

78/78

71/71

38

112/112

88/88

44

Compressor Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

1/5 - 1075

1/5 - 1075

1/5 - 1075

1/5 - 1075

1/5 - 1075

1/5 - 1075

1/5 - 1075

1/5 - 1075

1/5 - 1075

1/5 - 1075

1.2

1.2

1.2

1.4

1.5

1.5

1.4

1.5

1.5

1.4

18" - 1600

18" - 1600

18" - 1600

18" - 1600

20" - 2100

20" - 2100

20" - 2100

20" - 1900

20" - 1900

20" - 1900

1/6-1100-2

1/6-1100-1

1/6-1100-1

1/3-1100-2

1/3-1100-2

1/3-1100-2

1/3-1100-2

1/3-1100-2

1/3-1100-2

1/3-1100-2

Fan Motor & Condenser
Fan Motor--HP--RPM
Fan Motor--Amps
Fan--DIA/CFM
Blow er Motor & Evap.
Blower Motor--HP-RPM-SPD
Blower Motor--Amps

1.0

1.0

1.0

1.1

2.2

2.2

1.1

2.2

2.2

1.1

CFM Cooling & E.S.P.
w/Filter (Rated-Wet Coil)

600 - .20

800 - .20

800 - .20

800 - .20

1000 - .40

1000 - .40

1000 - .40

1100 - .30

1100 - .30

1100 - .30

Filter Sizes (inches) STD.

16x25x1

16x25x1

16x25x1

16x25x1

16x30x1

16x30x1

16x30x1

16x30x1

16x30x1

16x30x1

335

335

335

335

375

375

375

375

375

375

Shipping Weight --LBS.

Specifications 3-1/2 Ton through 5 Ton
MODELS

W42A1-A

W42A1-B

W42A1-C

W48A1-A

W48A1-B

W48A1-C

W60A1-A

W60A1-B

Electrical Rating--60 Hz

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

197-253

197-253

414-506

197-253

197-253

414-506

197-253

197-253

414-506

Voltage

230/208

230/208

460

230/208

230/208

460

230/208

230/208

460

Rated Load Amps

16.7/18.9

11/12.5

5.8

20/21.9

13.9/15.2

6.8

22.6/25.5

13.5/15.2

7.6
7.8

Operating Voltage Range

W60A1-C

Compressor--Circuit A

Branch Circuit
Selection Current

19.9

13.2

6.1

23.1

16.1

7.1

26.3

15.7

Lock Rotor Amps

109/109

83.1/83.1

41

134/134

91/91

46

134/134

110/110

52

Compressor Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

1/3-825-2

1/3-825-2

1/3-825-1

1/3-825-2

1/3-825-2

1/3-825-1

1/3-825-2

1/3-825-2

1/3-825-1

2.5

2.5

1.3

2.5

2.5

1.3

2.5

2.5

1.3

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

1/2-1070-2

1/2-1070-2

1/2-1070-2

1/2-1070-2

1/2-1070-2

1/2-1070-2

1/2-1070-2

1/2-1070-2

1/2-1070-2

3.3

3.3

1.9

3.3

3.3

1.9

3.3

3.3

1.9

1400 - .30

1400 - .30

1400 - .30

1550 - .20

1550 - .20

1550 - .20

1700 - .30

1700 - .30

1700 - .30

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

525

525

525

525

525

525

525

525

525

Fan Motor & Condenser
Fan Motor--HP-RPM-SPD
Fan Motor--Amps
Fan--DIA/CFM
Blow er Motor & Evap.
Blower Motor--HP-RPM-SPD
Blower Motor--Amps
CFM Cooling & E.S.P.
w/Filter (Rated-Wet Coil)
Filter Sizes (inches) STD.
Shipping Weight --LBS.

Form No.
S3397-1112
Supersedes S3397-712
Page
2 of 12

Ventilation System Packages
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All
units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the
factory or field-installed at a later date.
BAROMETRIC FRESH AIR DAMPER - BFAD

STANDARD

The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service
door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the
air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and
closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into
the building and can be easily locked closed if required.

Barometric Fresh Air Damper

BLANK OFF PLATE - BOP

OPTIONAL

A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any
outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not
required to be mixed with the conditioned air.

MOTORIZED FRESH AIR DAMPER - MFAD

OPTIONAL

The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air,
up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed
with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered
open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower
operation or can be field connected to be managed based on building occupancy.

Motorized Fresh Air Damper

NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require
separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing
dampers in the return air grille may be required to achieve specified amount of outdoor air intake.

COMMERCIAL ROOM VENTILATOR - CRV

OPTIONAL

The built-in commercial room ventilator is internally mounted behind the service door and allows outside
ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings.
It includes a built-in exhaust air damper.

Commercial Room Ventilator

The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by
providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the
amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled
based on room occupancy. Two versions available (except on 1.5 and 2-Ton models). The CRV and CRVS are
power open - spring return on power loss, and CRVP is power open and power close. Complies with ANSI/ASHRAE
Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.

ECONOMIZER - ECONWM-Series

OPTIONAL

The built-in economizer system is internally mounted behind the service door and allows outdoor air to be
introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and
settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide
“free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running
the compressor. This in turn provides lower operating costs, while extending the life of the compressor.

• ECONWMT Equipment Building versions have extended air intake hood to deliver up to 100% of cooling rated airflow.
™ 16" for ECONWMT-E2 or T2, and E3 or T3
™ 18" for ECONWMT-E5 or T5
• ECONWMS Classroom versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.

Economizer

Standard Features:
• Fully modulating
• Honeywell Direct Drive Hi-Torque Actuator
• No linkage required
• Simple single blade design
• Positive shut-off with non-stick gaskets
• Electronic DB and/or Enthalpy sensors depending upon version
• Honeywell JADE electronic economizer module with precision settings and diagnostics
• DB or Enthalpy economizer versions available
WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF

OPTIONAL

The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality
ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM
(depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and
humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs.
Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.

Energy Recovery Ventilator

The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat
transfer capabilities during summer and winter conditions. Various control schemes are addressed including
limiting ventilation during building occupancy only.
The ERV is designed to be internally mounted behind the service door in the W**A, W**H or W**L model wallmount units. It can be built-in at the factory or field installed as an option. ERVF-*3 and ERVF-*5 can be
independently adjusted for intake and exhaust rates.
Form No.
S3397-1112
Supersedes S3397-712
Page
3 of 12

Airflow (cfm)

Airflow (cfm)

A

B

C
Vent Position

D

E

F

W17A/W18A & W24A TOTAL AND VENTILATION AIRFLOW

Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP

Total Air 0 ESP
Total Air .15 ESP

0

100

A

B

C
Vent Position

D

E

F

0

100

200

200

300

400

500

600

300

Total Air 0 ESP
Total Air .15 ESP
Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP

700

800

900

1000

A

B

C
Vent Position

D

E

F

Total Air 0 ESP
Total Air .15 ESP
Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP

W30A & W36A LOW SPEED TOTAL AND VENTILATION AIRFLOW

400

500

600

700

800

900

1000

1100

1200

W30A & W36A HIGH SPEED TOTAL AND VENTILATION AIRFLOW

Commercial Room Ventilator Performance Data - CRVS-3 and CRVP-3

0

100

200

300

400

500

600

700

800

900

1000

1100

Commercial Room Ventilator Performance Data - CRV-2

Airflow (cfm)

Form No.
S3397-1112
Supersedes S3397-712
Page
4 of 12

Form No.
S3397-1112
Supersedes S3397-712
Page
5 of 12

A

B

C
Vent Position

D

E

F

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

A

B

C
Vent Position

D

E

F

Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP

W42A & W48A LOW SPEED TOTAL AND VENTILATION AIRFLOW

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

B

C
Vent Position

D

E

F

A

B

C
Vent Position

D

E

F

W60A LOW SPEED TOTAL AND VENTILATION AIRFLOW

A

Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP

Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP

W60A HIGH SPEED TOTAL AND VENTILATION AIRFLOW
2100

2200

W42A & W48A HIGH SPEED TOTAL AND VENTILATION AIRFLOW

2100

Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5

Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5

Airflow (cfm)

Airflow (cfm)

Airflow (cfm)

Airflow (cfm)

Performance and Application Data- ERVF-A2
SUMMER COOLING PERFORMANCE
(INDOOR DESIGN CONDITIONS 75°DB/62°WB)
Ambient
O.D.
D B/
WB

F
75

105

100

95

90

85

80

75

VENTILATION RATE -- 250 CFM
62% EFFICIENCY

VENTILATION RATE -- 225 CFM
63% EFFICIENCY

VENTILATION RATE -- 200 CFM
63% EFFICIENCY

VLT

V LS

V LL

HRT

HRS

HRL

VLT

V LS

V LL

HRT

HRS

HRL

VLT

V LS

V LL

HRT

HRS

HRL

11925

8100

1325

7394

5022

822

10727

7287

3441

6758

4591

2168

9540

6480

3060

6010

4082

1928
0

70

8100

8100

0

5022

5022

0

7287

7287

0

4591

4591

0

6480

6480

0

4082

4082

65

8100

8100

0

5022

5022

0

7287

7287

0

4591

4591

0

6480

6480

0

4082

4082

0

80

17550

6750

10800

10881

4185

6696

15788

6072

9716

9946

3826

6121

14040

5400

8640

8845

3402

5443

75

11925

6750

5175

7394

4185

3209

10727

6072

4655

6758

3826

2933

9540

5400

4140

6010

3402

2608

70

6863

6750

113

4255

4185

70

6173

6072

101

3889

3826

64

5490

5400

90

3458

3402

56

65

6750

6750

0

4185

4185

0

6072

6072

0

3826

3826

0

5400

5400

0

3402

3402

0

60

6750

6750

0

4185

4185

0

6072

6072

0

3826

3826

0

5400

5400

0

3402

3402

0

80

17550

5400

12150

10881

3348

7533

15788

4858

10930

9946

3060

6886

14040

4320

9720

8845

2722

6124

75

11925

5400

6525

7394

3348

4046

10727

4858

5870

6758

3060

3698

9540

4320

5220

6010

2722

3289

70

6863

5400

1463

4255

3348

907

6173

4858

1315

3889

3060

829

5490

4320

1170

3458

2722

737

65

5400

5400

0

3348

3348

0

4858

4858

0

3060

3060

0

4320

4320

0

2722

2722

0

60

5400

5400

0

3348

3348

0

4858

4858

0

3060

3060

0

4320

4320

0

2722

2722

0

80

17550

4050

13500

10881

2511

8370

15788

3643

12145

9946

2295

7651

14040

3240

10800

8845

2041

6804

75

11925

4050

7875

7394

2511

4883

10727

3643

7084

6758

2295

4463

9540

3240

6300

6010

2041

3969

70

6863

4050

2813

4255

2511

1744

6173

3643

2530

3889

2295

1594

5490

3240

2250

3458

2041

1417

65

4050

4050

0

2511

2511

0

3643

3643

0

2295

2295

0

3240

3240

0

2041

2041

0

60

4050

4050

0

2511

2511

0

3643

3643

0

2295

2295

0

3240

3240

0

2041

2041

0

80

17550

2700

14850

10881

1674

9207

15788

2429

13359

9946

1530

8416

14040

2160

11880

8845

1361

7484

75

11925

2700

9225

7394

1674

5720

10727

2429

8298

6758

1530

5228

9540

2160

7380

6010

1361

4649

70

6863

2700

4163

4255

1674

2581

6173

2429

3744

3889

1530

2359

5490

2160

3300

3458

1361

2098

65

2700

2700

0

1674

1674

0

2429

2429

0

1530

1530

0

2160

2160

0

1361

1361

0

60

2700

2700

0

1674

1674

0

2429

2429

0

1530

1530

0

2160

2160

0

1361

1361

0

75

11925

1350

10575

7394

837

6557

10727

1214

9513

6758

765

5993

9540

1080

8460

6010

680

5330

70

6863

1350

5513

4255

837

3418

6173

1214

4959

3889

765

3124

5490

1080

4410

3458

680

2778

65

2363

1350

1013

1465

837

628

2125

1214

911

1339

765

547

1890

1080

810

1190

680

510

60

1350

1350

0

837

837

0

1214

1214

0

765

765

0

1080

1080

0

680

680

0

70

6863

0

6863

4255

0

4255

6173

0

6173

6889

0

3889

5490

0

5490

3458

0

3458

65

2363

0

2363

1465

0

1465

2125

0

2125

1339

0

1339

1890

0

1890

1190

0

1190

60

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

ERVF-A2 WINTER HEATING PERFORMANCE
(INDOOR DESIGN CONDITIONS 70°F DB)
VENTILATION RATE
Ambient
250 C F M
225 C F M
200 C F M
O.D.
74% EFF.
75% EFF.
75% EFF.
DB/°F
WVL
WHR
WVL
WHR
WVL
WHR
65
1350
999
1214
911
1080
810
60
2700
1998
2429
1822
2160
1620
55
4050
2997
3643
2733
3240
2430
50
5400
3996
4858
3643
4320
3240
45
6750
4995
6072
4554
5400
4050
40
8100
5994
7287
5465
6480
4860
35
9450
6993
8501
6376
7560
5670
30
10800
7992
9716
7287
8640
6480
25
12150
8991
10930
8198
9720
7290
20
13500
9990
12145
9108
10800
8100
15
14850
10989
13359
10019
11880
8910
NOTE: Sensible performance only is show n for w inter application.

Form No.
S3397-1112
Supersedes S3397-712
Page
6 of 12

LEGEND:
VLT =
VLS =
VLL =
HRT =
HRS =
HRL =
WVL =
WHR =

Ventilation Load - Total
Ventilation Load - Sensible
Ventilation Load - Latent
Heat Recovery - Total
Heat Recovery - Sensible
Heat Recovery - Latent
Winter Ventilation Load
Winter Heat Recovery

Form No.
S3397-1112
Supersedes S3397-712
Page
7 of 12

75

80

85

90

95

100

105

D B/
WB

2160

2160

60

6917

5443

5443

6917

4082

4082

2721

2721

6917

10980
3780
0

0

1620

8820

6917
2381
0

1360

2381

6917

16920 12020

0

0

6660

14760 12020

23760 17690

0

0

4500

12600 12020

21600 17690

0

0

2340

10440 12020

19440 17690

0
0
0

1360

1360

1360

1360

2721

2721

2721

2721

2721

4082

4082

4082

4082

4082

5443

5443

5443

5443

5443

8164
6804
6804
6804
6804
6804

8164

8164

HRS

V LS

10530 10530

15502 10530

VLT

0

4972

V LL

6739

9921

HRT

7020

7020

8921

15502

5265

5265

8921

15502

3 5 10

3 5 10

8921

15502

6917
2380
0

0

1020

5556

8921
3071
0

1755

3071

8921

10659 15502

0

0

4195

9298

14968 22815

0

0

2835

7938

13608 22815

0

0

1474

6577

12247 22815

0
0
0

1755

1755

1755

1755

3510

3510

3510

3510

3510

5265

5265

5265

5265

5265

7020

7020

7020

7020

7020

6739
5616
5616
5616
5616
5616

6739

6739

HRS

4492

4492

4492

4492

5709

4492

4492

9921

3369

3369

5709

9921

8921
3071
0

0

1316

7166

13747

0

0

5411

11992

5709
1965
0

1123

1965

5709

9921

2246

2246

5709

9921

19305 14601

0

0

3656

10237

0
0
0

1123

1123

1123

1123

2246

2246

2246

2246

2246

3369

3369

3369

3369

17550 14601 3369

0

0

1901

8 48 2

15795 14601 4492

0
10530 10530
0
6739
10886 22815 8775 14040 14601
5216 15502 8775 6727 9921
113
8921 8775
146
5709
0
8775 8775
0
5616
0
8775 8775
0
5616

0

3855

HRL

VENTILATION RATE -- 325 CFM
64% EFFICIENCY

8100
17550
11925
6862
6750
6750

8100

11925

VLT

5400

5400

6862

11925

4050

4050

6862

11925

5709
1965
0

0

842

4586

8798

0

0

3463

7675

6862
2362
0

1350

2362

6862

11925

2700

2700

6862

11925

12355 17550

0

0

2340

6552

11232 17550

0

0

1216

5428

10108 17550

0
8985
4305
93
0
0

0

3182

HRL

0
0
0

1350

1350

1350

1350

2700

2700

2700

2700

2700

4050

4050

4050

4050

4050

5400

5400

5400

5400

5400

8100
6750
6750
6750
6750
6750

8100

8100

V LS

5265

7751

HRT

3510

3510

4460

7751

2632

2632

4460

7751

6862
2362
0

0

1012

5512

10575

0

0

4162

9225

0
0
0

877

877

877

877

1755

1755

1755

1755

1755

2632

2632

2632

2632

2632

3510

3510

3510

3510

3510

5265
4387
4387
4387
4387
4387

5265

5265

HRS

VLT =
VLS =
VLL =
HRT =
HRS =
HRL =
WVL =
WHR =

4460
1535
0

0

658

3583

6873

0

0

2705

5996

9652

0

0

1828

5118

8774

0

0

950

4241

7897

0
7019
3363
73
0
0

0

2486

HRL

75

80

85

90

95

100

105

D B/
WB

7897

9720
9720

65
60

7290

7290

2430

70 12352

0
0

0

65 4252

0

60

70 12352

2430

2430

2430

75 21465

60

4860

60 4860

2430

4860

65 4860

65 4252

4860
4860

75 21465

4860

7290

7290

7290

7290

7290

70 12352

80 31590

60

65

70 12352

75 21465

80 31590

9720

70 12352
9720

9720
9720

75 21465

7897

7897

8029

6318

6318

8029

4738

4738

8029

3159

3159

8029

0

4252

0

2764

8029

1579

2764

8029

0

0

0

1579

1579

1579

1579

3159

3159

3159

3159

3159

4738

4738

4738

4738

4738

6318

6318

6318

6318

6318

7897

7897

HRL

VLT

V LS

12150 12150

12150 12150

17887 12150

V LL

0

0

5737

HRT

8 0 18

8 0 18

11805

17887

8100

8100

10293

6075

6075

10293

17887

4050

4050

10293

0

2764

8029

0

1184

6449

0

3543

10293

2025

3543

10293

12372 17887

0

0

4870

10793 17887

17374 26325

0

0

3290

9213

15794 26325

0

0

1711

7634

0

0

0

2025

2025

2025

2025

4050

4050

4050

40 5 0

4050

6075

6075

6075

6075

6075

8100

8100

8100

8100

8100

10125 10125

10125 10125

10293 10125

17887 10125

14215 26325

0

0

131

6054

6682

6682

6793

11805

5345

5345

6793

11805

4009

4009

6793

2672

2672

6793

0

3543

10293

0

1518

8268

0

2338

6793

1336

2338

6793

15862 11805

0

0

6243

13837 11805

22275 17374

0

0

4218

11812 11805

20250 17374

0

0

2193

9787

18225 17374

0

0

168

7762

12635 26325 10125 16200 17374

0

0

4475

0

0

0

1336

1336

1336

1336

2672

2672

2672

2672

2672

4009

4009

4009

4009

4009

5345

5345

5345

5345

5345

6682

6682

6682

6682

6682

8018

8018

8018

HRS

VENTILATION RATE 375 CFM
66% EFFICIENCY
HRL

VLT

9720

9720

14310

8100

8100

8235

14310

6480

6480

8235

14310

4860

4860

8235

14310

3240

3240

8235

14310

0

2338

6793

0

1002

5457

0

2835

8235

1620

2835

8235

10469 14310

0

0

4120

9132

14701 21060

0

0

2784

7796

13365 21060

0

0

1447

6459

12028 21060

0

0

111

5123

10692 21060

0

0

3786

0

0

0

1620

1620

1620

1620

3240

3240

3240

3240

3240

4860

4860

4860

4860

4860

6480

6480

6480

6480

6480

8100

8100

8100

8100

8100

9720

9720

9720

V LS

HRT

6512

6512

9587

5427

5427

5517

9587

9587

4341

4341

5517

3256

3256

5517

9587

0

2835

8235

0

1215

6615

12690

0

0

4995

11070

0

1899

5517

1085

1899

5517

9587

2170

2170

5517

9587

17820 14110

0

0

3375

9450

16200 14110

0

0

1755

7830

14580 14110

0

0

135

6210

12960 14110

0

0

4590

V LL

0

0

0

1085

1085

1085

1085

2170

2170

2170

2170

2170

3256

3256

3256

3256

3256

4341

4341

4341

4341

4341

5427

5427

5427

5427

5427

6512

6512

6512

HRS

VENTILATION RATE 300 CFM
67% EFFICIENCY

ERVF-*5 WINTER HEATING PERFORMANCE
(INDOOR DESIGN CONDITIONS 70°F DB)
VENTILATION RATE
Ambient
450 C F M
375 C F M
300 C F M
O.D.
80% EFFICIENCY
81% EFFICIENCY
82% EFFICIENCY
DB/°F
WVL
WHR
WVL
WHR
WVL
WHR
65
2430
1944
2025
1640
1620
1328
60
4860
3888
4050
3280
3240
2656
55
7290
5832
6075
4920
4860
3985
50
9720
7776
8100
6561
6480
5313
45
12150
9720
10125
8201
8100
6642
40
14580
11664
12150
9841
9720
7970
35
17010
13608
14175
11481
11340
9298
30
19440
15552
16200
13122
12960
10627
25
21870
17496
18225
14762
14580
11955
20
24300
19440
20250
16402
16200
13284
15
26730
21384
22275
18042
17820
14612
NOTE: Sensible performance only is show n for w inter application.

12352

0

1822

9922

19035 13952

0

0

7492

16605 13952

26730 20533

0

0

5062

14175 13952

24300 20533

0

0

2632

11744 13952

21870 20533

0

60 12150 12150
9720

0

65 12150 12150
80 31590

202

70 12352 12150

7897

7897

75 21465 12150

13952

80 31590 12150 19440 20533
9314

9477
9477

0

65 14580 14580

HRS
9477

9477

0

70 14580 14580

HRT
13952
9477

V LL
6884

V LS

VLT

VENTILATION RATE 450 CFM
65% EFFICIENCY

75 21465 14580

F

Ambient
O.D.

SUMMER COOLING PERFORMANCE
(INDOOR DESIGN CONDITIONS 75°DB/62°WB)

Performance and Application Data- ERVF-*5

Ventilation Load - Total
Ventilation Load - Sensible
Ventilation Load - Latent
Heat Recovery - Total
Heat Recovery - Sensible
Heat Recovery - Latent
Winter Ventilation Load
Winter Heat Recovery

LEGEND:

4460
1535
0

877

1535

4460

7751

1755

1755

4460

7751

14850 11407

0

0

2812

7875

13500 11407

0

0

1462

6525

12150 11407

0
5265
10800 11407
5175 7751
112
4460
0
4387
0
4387

0

3825

V LL

VENTILATION RATE -- 250 CFM
65% EFFICIENCY

ERVF-*3 WINTER HEATING PERFORMANCE
(INDOOR DESIGN CONDITIONS 70°F DB)
VENTILATION RATE
Ambient
400 C F M
325 C F M
250 C F M
O.D.
75% EFFICIENCY
76% EFFICIENCY
77% EFFICIENCY
DB/°F
WVL
WHR
WVL
WHR
WVL
WHR
65
2160
1620
1755
1333
1350
1039
60
4320
3240
3510
2667
2700
2079
55
6480
4860
5265
4001
4050
3118
50
8640
6480
7020
5335
5400
4158
45
10800
8100
8775
6669
6750
5197
40
12960
9720
10530
8002
8100
6237
35
15120
11340
12285
9336
9450
7276
30
17280
12960
14040
10670
10800
8316
25
19440
14580
15795
12004
12150
9355
20
21600
16200
17550
13338
13500
10395
15
23760
17820
19305
14671
14850
11434
NOTE: Sensible performance only is show n for w inter application.

0
0
0

2160

2160

3780

2160

75 19080

65

4320

70 10980

4320

60 4320

4320

75 19080

65 4320

4320

80 28080

4320

6480

6480

60

70 10980

6480

75 19080

6480

6480

80 28080

6480

6480

8640

60

65

8640

8640

70 10980

8640

8640

70 10980

65

8640

75 19080

70 10980
65 3780
60
0

8164

12020

HRT

12960
0
8164
10800 17280 17690
10800 8280 12020
10800 180
6717
10800
0
6804
10800
0
6804

8640

12960
28080
19080
10980
10800
10800

80 28080

65
80
75
70
65
60

0

6120

75 19080 12960

70 12960 12960

V LL

VLT

VENTILATION RATE -- 400CFM
63% EFFICIENCY

V LS

F

Ambient
O.D.

SUMMER COOLING PERFORMANCE
(INDOOR DESIGN CONDITIONS 75°DB/62°WB)

Performance and Application Data- ERVF-*3

HRL

0

1899

5517

0

814

4432

8502

0

0

3346

7416

11939

0

0

2261

6331

10854

0

0

1175

5246

9768

0

0

90

4160

8683

0

0

3075

Electrical Specifications
Single Circuit
Model
W17A1/W18A1 - A00, A0Z
A 05
A 08
A 10
W24A1 - A00, A0Z
A 04
A 05
A 08
A 10
W24A1 - B00, B0Z
B 06
W24A1 - C00, C0Z
C 06
W30A1 - A00*, A0Z*
A 05*
A 08
A 10*
A 15
W30A1 - B00*, B0Z*
B 06
B 09*
B 15
W30A1 - C00*, C0Z*
C 06
C 09*
C 15
W36A1 - A00*, A0Z*
A 05*
A 08
A 10*
A 15
W36A1 - B00*, B0Z*
B 06
B 09*
B 15
W36A1 - C00*, C0Z*
C 06
C 09*
C 15
W42A1 - A00, A0Z 4
A 05 4
A 10 4
A 15
A 20
W42A1 - B00, B0Z 4
B 09 4
B 15
B 18 4
W42A1 - C00, C0Z 4
C 09 4
C 15
W48A1 - A00, A0Z 4
A 05 4
A 10 4
A 15
A 20
W48A1- B00, B0Z 4
B 09 4
B 15
B 18 4
W48A1 - C00, C0Z 4
C 09 4
C 15
W60A1 - A00, A0Z 4
A 05 4
A 10 4
A 15
A 20
W60A1 - B00, B0Z 4
B 09 4
B 15 4
B 18 4
W60A1 - C00, C0Z 4
C 09 4
C 15

Rated
Volts
and Phase

2 Field
No. Field 3 Minimum 1 Maximum
Circuit
External Fuse
Power
Power
Ampacity or Ckt. Brkr. Wire Size
Circuits

230/208-1

1
1
1
1

230/208-1

1
1
1
1

230/208-3
460-3

230/208-1
1
230/208-3

460-3

230/208-1
1
230/208-3

460-3

230/208-1
1
1
230/208-3

460-3

230/208-1
1
1
230/208-3

460-3

230/208-1
1
1
230/208-3

460-3

1
1
1
1
1
1
1
1
or 2
1
1
1
1
1
1
1
1
1
1
1
1
or 2
1
1
1
1
1
1
1
1
1
1
1
or 2
or 2
1
1
1
2
1
1
1
1
1
1
or 2
or 2
1
1
1
2
1
1
1
1
1
1
or 2
or 2
1
1
1
2
1
1
1

16
30
46
56
21
25
30
46
56
15
22
10
12
24
32
48
58
84
18
24
33
51
11
12
17
26
29
32
48
58
84
23
24
33
51
12
12
17
26
33
33
59
85
111
25
34
53
N/A
13
18
27
37
37
59
85
111
29
34
53
N/A
14
18
27
41
41
59
85
111
29
34
53
N/A
15
18
27

20
30
50
60
30
30
30
50
60
20
25
15
15
35
35
50
60
90
20
25
35
60
15
15
20
30
35
35
50
60
90
30
30
35
60
15
15
20
30
50
50
60
90
125
35
35
60
N/A
15
20
30
50
50
60
90
125
40
40
60
N/A
20
20
30
60
60
60
90
125
40
40
60
N/A
20
20
30

12
10
8
6
10
10
10
8
6
14
10
14
14
8
8
8
6
4
12
10
8
8
14
14
12
10
8
8
8
6
4
10
10
8
6
14
14
10
10
8
8
6
4
2
8
8
6
N/A
14
12
10
8
8
6
4
2
8
8
6
N/A
12
12
10
8
8
6
4
2
8
8
6
N/A
12
12
10

2 Ground
Wire
12
10
10
10
10
10
10
10
10
14
10
14
14
10
10
10
10
8
12
10
10
10
14
14
12
10
10
10
10
10
8
10
10
10
10
14
14
10
10
10
10
10
8
6
10
10
10
N/A
14
12
10
10
10
10
8
6
10
10
10
N/A
12
12
10
10
10
10
8
6
10
10
10
N/A
12
12
10

Dual Circuit
3 Minimum
1 Maximum
2 Field
2 Ground
Circuit
External Fuse
Power
Wire Size
Ampacity
or Ckt. Brkr.
Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B

58

26

60

30

6

10

10

10

58

26

60

30

6

10

10

10

59
59

26
52

60
60

30
60

6
6

10
6

10
10

10
10

34

28

35

30

8

10

10

10

59
59

26
52

60
60

30
60

6
6

10
6

10
10

10
10

34

28

40

30

8

10

10

10

59
59

26
52

60
60

30
60

6
6

10
6

10
10

10
10

34

28

40

30

8

10

10

10

1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
4 These models are available with dehumidification with hot gas reheat.
Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment
Factors when more than three (3) current carrying conductors are in a raceway.
* Top outlet supply option is available only factory installed and only on the selected models.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.
Form No.
S3397-1112
Supersedes S3397-712
Page
8 of 12

Indoor Blower Performance - CFM at Rated Volts
ESP
in
H2O

W17A1
W18A1

W30A1
W36A1

W24A1

W42A1
W48A1

W60A1

High Speed
Dry/Wet Coil

Low Speed
Dry/Wet Coil

Single Speed
Dry/Wet Coil

High Speed
Dry/Wet Coil

Low Speed
Dry/Wet Coil

High Speed
Dry/Wet Coil

Low Speed
Dry/Wet Coil

High Speed
Dry/Wet Coil

Low Speed
Dry/Wet Coil

0

925/885

670/655

1020/975

1395/1315

950/935

1885/1800

1650/1600

2200/2000

1600/1450

.1

875/845

650/630

960/905

1340/1270

930/915

1770/1665

1550/1500

2100/1900

1525/1375

.2

825/795

625/600

865/800

1285/1190

910/885

1635/1550

1450/1400

2000/1800

1465/1200

.3

775/740

575/555

820/735

1205/1100

855/830

1500/1400

1350/1300

1875/1700

-/-

.4

710/670

525/500

735/650

1110/1000

800/755

1370/1285

1300/1175

1775/1600

-/-

.5

635/600

465/440

615/535

1005/870

-/-

1250/1150

-/-

1650/1475

-/-

Above data is with 1" standard throwaway filter and 1" washable filter.
For optional 2" pleated filter - reduce ESP by .15 in.
See installation instructions for maximum ESP information on various KW application.

Speeds marked “bold” above
are Factory Connected.

Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model
At 240V (1)

Nominal
KW

Kw

5.0

5.0

6.0

6.0

8.0

8.0

1-Ph Amps 3-Ph Amps
20.8
14.4
33.3

9.0

9.0

10.0

10.0

41.7

21.7

15.0

15.0

62.5

18.0

18.0

20.0

20.0

83.3

At 208V (1)
Btuh

Kw

17,065

3.75

20,478

4.50

27,304

6.00

30,717

6.75

34,130

7.50

36.1
54.1

36.1

51,195

11.25

43.3

61,434

13.50

68,260

15.00

1-Ph Amps 3-Ph Amps
18.0

At 480V (2)
Btuh

At 460V (2)

Kw

3-Ph Amps

Btuh

Kw

3-Ph Amps

Btuh

6.0

7.2

20,478

5.52

6.9

18,840

9.0

10.8

30,717

8.28

10.4

28,260

12,799
12.5

28.8

15,359
20,478

18.7

23,038
25,598

31.2

38,396

15.0

18.0

51,195

13.80

17.3

47,099

37.5

46,076

18.0

21.7

61,434

16.56

20.8

56,519

72.1

51,195

(1) These electric heaters are available in 230/208V units only.
(2) These electric heaters are available in 480V units only.

Heater Packages - Field Installed
• Designed for adding Electric Heat to 0 KW Units
• Circuit Breaker Standard on 230/208V Models
-A00 Models
Air Conditioner
230/208-1
Models
Heater Model #
EHWA02-A05
W17A1
EHW02A-A08
W18A1
EHWA02A-A10
EHWA02-A05
W24A1
EHW02A-A08
EHWA02A-A10
EHWA03-A05
EHWA03-A08
W30A1
EHWA03-A10
EHWA03-A15
EHWA03-A05
EHWA03-A08
W36A1
EHWA03-A10
EHWA03-A15
EHWA05-A05 1
W42A1
EHWA05-A10 1
W48A1
EHWA05-A15
EHWA05-A20
EHWA60-A05 1
EHWA05-A10 1
W60A1
EHWA05-A15
EHWA05-A20

KW
5
8
10
5
8
10
5
8
10
15
5
8
10
15
5
10
15
20
5
10
15
20

• ETL US & Canada Listed
• Toggle Disconnect Standard on 460V Models
-B00 Models
-C00 Models
230/208-3
460-3
Heater Model #
KW
Heater Model #
N/A

KW

N/A

EHWA24-B06

6

EHWH24B-C06

6

EHWA03-B06
EHWA03-B09
EHWA37-B15

6
9
15

EHWC03A-C06
EHWC03A-C09
EHWA03A-C15

6
9
15

EHW36A-B06
EHWA03-B09
EHWA37-B15

6
9
15

EHWC03A-C06
EHWC03A-C09
EHWA03A-C15

6
9
15

EHWA05-B09 1
EHWA05-B15
EHW05A-B18 1

9
15
18

EHWA05A-C09 1
EHWA05A-C15

9
15

EHW60A-B09 1
EHWA05-B15 1
EHW05A-B18 1

9
15
18

EHWA05A-C09 1
EHWA05A-C15

9
15

NOTE: Field installed Heater Packages are not approved for use with top supply opening models.
1 These heater packages approved for use in dehumidification versions with hot gas reheat.
Form No.
S3397-1112
Supersedes S3397-712
Page
9 of 12

Cooling Application Data - Outdoor Temperature 1
Model

W17A1
W18A1

W24A1

W30A1

W36A1

W42A1

W48A1

W60A1

D.B./W.B.

2

Cooling
Capacity

75oF

80oF

85oF

90oF

95oF

100oF

105oF

110oF

115oF

120oF

75/
62

Total Cooling
Sensible Cooling

17,500
13,900

16,700
13,500

15,900
13,200

15,100
12,800

14,300
12,500

13,600
12,200

12,900
11,800

12,200
11,500

11,600
11,100

10,800
10,700

80/
67

Total Cooling
Sensible Cooling

18,600
13,400

18,100
13,200

17,600
13,000

17,000
12,800

16,400
12,600

15,800
12,400

15,200
12,100

14,500
11,800

13,900
11,500

13,100
11,200

85/
72

Total Cooling
Sensible Cooling

22,200
13,800

21,200
13,400

20,200
13,100

19,200
12,800

18,300
12,400

17,300
12,000

16,400
11,600

15,500
11,100

14,600
10,600

13,700
10,200

75/
62

Total Cooling
Sensible Cooling

26,000
20,100

24,500
19,700

23,300
19,200

22,100
18,800

20,900
18,400

20,000
17,900

19,100
17,400

18,400
16,900

17,600
16,400

17,100
15,900

80/
67

Total Cooling
Sensible Cooling

27,700
19,500

26,700
19,300

25,800
19,000

24,900
18,800

24,000
18,500

23,300
18,200

22,500
17,800

21,900
17,400

21,200
17,000

20,700
16,600

85/
72

Total Cooling
Sensible Cooling

33,000
20,000

31,200
19,600

29,700
19,100

28,100
18,700

26,700
18,200

25,500
17,600

24,300
17,000

23,300
16,300

22,300
15,700

21,500
15,000

75/
62

Total Cooling
Sensible Cooling

31,100
24,500

29,700
24,000

28,300
23,500

27,000
22,900

25,800
22,400

24,700
21,800

23,700
21,300

22,700
20,700

21,700
20,100

20,900
19,500

80/
67

Total Cooling
Sensible Cooling

33,200
23,700

32,300
23,500

31,400
23,200

30,400
22,900

29,600
22,600

28,600
22,200

27,800
21,800

27,000
21,400

26,100
20,900

25,300
20,400

85/
72

Total Cooling
Sensible Cooling

39,600
24,300

37,800
23,900

36,100
23,300

34,500
22,800

32,900
22,200

31,500
21,500

30,100
20,800

28,800
20,100

27,500
19,300

26,300
18,500

75/
62

Total Cooling
Sensible Cooling

38,100
28,500

35,900
27,800

34,100
27,100

32,300
26,400

30,800
25,800

29,600
25,200

28,600
24,700

27,700
24,200

26,900
23,700

26,400
23,200

80/
67

Total Cooling
Sensible Cooling

40,600
27,600

39,100
27,200

37,800
26,800

36,500
26,400

35,400
26,000

34,500
25,600

33,700
25,300

33,000
25,000

32,400
24,600

32,000
24,300

85/
72

Total Cooling
Sensible Cooling

48,400
28,300

45,700
27,600

43,400
26,900

41,200
26,200

39,300
25,500

37,800
24,800

36,400
24,100

35,100
23,500

34,100
22,700

33,300
22,000

75/
62

Total Cooling
Sensible Cooling

43,600
35,500

41,500
34,500

39,600
33,600

37,600
32,700

35,700
31,800

33,900
31,000

32,100
30,100

30,400
29,200

28,700
28,400

27,000
27,000

80/
67

Total Cooling
Sensible Cooling

46,500
34,400

45,200
33,800

43,900
33,300

42,500
32,700

41,000
32,100

39,500
31,500

37,900
30,900

36,200
30,200

34,500
29,500

32,700
28,800

85/
72

Total Cooling
Sensible Cooling

55,400
35,200

52,900
34,300

50,400
33,500

48,000
32,500

45,600
31,500

43,200
30,500

40,900
29,500

38,500
28,300

36,300
27,200

34,000
26,000

75/
62

Total Cooling
Sensible Cooling

49,600
39,900

47,300
39,100

45,100
38,200

43,000
37,300

40,900
36,400

39,000
35,500

37,100
34,500

35,100
33,600

33,300
32,700

31,400
31,400

80/
67

Total Cooling
Sensible Cooling

52,900
38,700

51,500
38,300

50,100
37,800

48,600
37,300

47,000
36,700

45,400
36,100

43,700
35,400

41,900
34,700

40,000
34,000

38,100
33,100

85/
72

Total Cooling
Sensible Cooling

63,000
39,600

60,200
38,900

57,500
38,000

54,900
37,100

52,200
36,000

49,700
34,900

47,100
33,800

44,600
32,500

42,000
31,300

39,600
29,900

75/
62

Total Cooling
Sensible Cooling

59,200
45,200

56,200
43,800

53,300
42,300

50,500
41,000

47,900
39,700

45,400
38,500

43,100
37,300

40,800
36,100

38,600
35,000

36,600
33,900

80/
67

Total Cooling
Sensible Cooling

63,200
43,800

61,200
42,900

59,200
41,900

57,100
41,000

55,000
40,100

52,900
39,200

50,800
38,300

48,700
37,300

46,500
36,400

44,300
35,500

85/
72

Total Cooling
Sensible Cooling

75,300
44,900

71,600
43,600

68,000
42,100

64,500
40,700

61,100
39,300

57,900
37,900

54,800
36,500

51,800
35,000

48,900
33,500

46,000
32,100

Capacity Multiplier Factors
% of Rated Airflow
Total BTUH
Sensible BTUH

1 Below 65°F (18.3C), unit requires a factory or field installed low ambient control.
2 Return air temperature.

Form No.
S3397-1112
Supersedes S3397-712
Page
10 of 12

-10

Rated

+10

0.975
0.950

1.0
1.0

1.02
1.05

Air Conditioning Wall-Mount Model Nomenclature
W
36 A
1
A
10
X

X

X

X

X

X
| CONTROL MODULES
(See Chart Below)

SERIES |
REVISION

KW 1

TYPE
Air Conditioner

NOMINAL
CAPACITY |
17 - 1½ Ton
18 - 1½ Ton
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton

Specialty Products 2
(Non-Standard)

VENTILATION OPTIONS
(See Table Below)

VOLTS & PHASE |
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3

FILTER OPTIONS
X - 1-inch Throwaway (Standard)
W - 1-inch Washable
P - 2-inch Pleated (MERV 8)

| COIL OPTIONS
X - Standard
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator
and Condenser

COLOR OPTIONS
X - Beige (Standard)
1 - White
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
A - Aluminum
S - Stainless Steel

| OUTLET OPTIONS
X - Front (Standard)
T - Top (on W30A and
W36A Models)

1 For 0KW and circuit breakers (230/208 Volt) or toggle disconnects (460 Volt) applications, insert 0Z in the KW field of the model number.
See Page 8 for available Factory Installed KW options and Page 9 for Field Installed Heater Packages.
2 Insert “D” for dehumidification with hot gas reheat — Models W42 - 60 only. See Form 7960-572 for complete details.

Ventilation Options
Models
Description
Barometric Fresh Air Damper - Standard
Blank-Off Plate
Motorized Fresh Air Damper
Commercial Ventilator - Spring Return w/Exhaust
Commercial Ventilator - Power Return w/Exhaust
Economizer - School Versions, Enthalpy 4
Economizer - Equipment Bldg., Enthalpy 5
Economizer - Equipment Bldg., DB Temp 5
Energy Recovery Ventilator - 230 Volt 3
Energy Recovery Ventilator - 460 Volt 3
Door Kit for ERVF (Required)

1
2
3
4
5
6

W17A1, W18A1, W24A1
Factory Installed
Field Installed
Code No.
Part No.
X
BFAD-2
B
BOP-2
MFAD-2
M
V
CRV-2
----S
ECONWMS-E2 23
W
ECONWMT-E2 2
T
ECONWMT-T2 2
R
ERVF-A2
N/A
ERVF-C2 6
N/A
WMDK2- 3

W30A1, W36A1
Factory Installed
Field Installed
Code No.
Part No.
X
BFAD-3
B
BOP-3
M
MFAD-3
V
CRVS-3
P
CRVP-3
S
ECONWMS-E3 23
W
ECONWMT-E3 2
T
ECONWMT-T3 2
R
ERVF-A3 1
R
ERVF-C3 1
N/A
WMDK3- 3

W42A1, W48A1, W60A1
Factory Installed
Field Installed
Code No.
Part No.
X
BFAD-5
B
BOP-5
M
MFAD-5
V
CRVS-5
P
CRVP-5
S
ECONWMS-E5 23
W
ECONWMT-E5 2
T
ECONWMT-T5 2
R
ERVF-A5 1
R
ERVF-C5 1
N/A
WMDK5- 3

Intake and exhaust can be independently adjusted.
Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)
WMDK Door Kit must be ordered in addition to ERVF Assembly and ECONWMS & color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)
Partial Full Flow (75% of Rated Cooling CFM). All ECONWMS versions have 3" deep intake hood.
Full Flow (100% of Rated Cooling CFM). ECONWMT 2 and 3 have 16" deep intake hood; ECONWMT- 5 has 18" deep intake hood.
Model W24A1-C only.

Air Conditioning Control M odules
HPC 1

LP C 2

CCM 3

STD

STD

STD

LAC 4 11

STD

STD

STD

z

STD

STD

STD

z

STD

STD

STD

z

STD

STD

STD

z

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

STD

A LR 5

SK 6

SK 7

ODT 8

DDC 9

Field Installed Part

X

N/A

N/A

E

11

CMA-28

N/A

J

11

Factory Only

J

K

11

CMC-15 and CMA-28

N/A

M

11

z
z
z

z

z

Factory Only

M

N/A

N/A

Field Installed Only

CMC-15

CMC-15

Field Installed Only

CMA-14

N/A

N, W18A Only

z
z
z

Factory Installed Code

W17A1
Factory
Only

All Models Except As Noted

z

z
z
z

12

Factory Only

N/A

Field Installed Only

CMA-23 for W18-36A
CMA-24 for W42-60A

N/A

Field Installed Only

SK111

SK111

V

11

STD = Standard equipment for these specified models.

1 HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3.
2 LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3.
3 CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for
high and/or low-pressure controls, and a 2-minute timed bypass for low-pressure control.
4 LAC. Low ambient control permits cooling operation down to 0°F. LAC is fan-cycling control for outdoor fan motor on all models except W17A1, which is modulating control.
5 ALR. The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls.
6 SK. PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 is used.
7 SK. Start capacitor and potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if
CMC-15 is used.
8 ODT. Outdoor thermostat is adjustable from 0 to 50°F. It is suitable for use as a compressor cut-off thermostat.
9 DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data
such as temperature, as well as digital data such as airflow, compressor status or filter status. Special economizer required; consult factory.
“V” control module should be ordered in conjunction with direct digital controller (DDC) model TCS24. Refer to DDC specification sheet S3280 for more information.
11
Option not available for Model W18A.
12
Form No.
S3397-1112
Use option N for Alarm Relay on Model W18A only.
Supersedes
Page

S3397-712
11 of 12

Clearances Required for Service Access
and Adequate Condenser I nlet Airflow

M inimum Clearances Required to
Combustible M aterials

MODELS

MODELS 1

LEFT SIDE

RIGHT SIDE

W17A, W18A, W24A, W30A, W36A

15"

20"

W42A, W48A, W60A

20"

20"

SUPPLY AIR DUCT
FIRST THREE FEET

W17A, W18A, W24A

NOTE: For side by side installation of two (2) WA models there
must be 20" between units. This can be reduced to 15" by using a
WL model (left side compressor and controls) for the left unit and
WA (right side compressor and controls) for right unit.
See WL Specifications S3400.

CABINET

0"

0"

W30A, W36A

1/4"

0"

W42A, W48A, W60A

1/4"

0"

1 Refer to the Installation Manual for more detailed information.

Dimensions of Basic Unit for Architectural and I nstallation Requirements (Nominal)
MODEL

WIDTH DEPTH HEIGHT SUPPLY
(W)
(D)
(H)
A
B

RETURN

C
B
E
F
G
I
J
K
L
M
N
O
P
Q
W17A
W18A 33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 10.88 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55
W24A
W30A
38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 10.88 25.75 17.93 26.75 28.75 29.25 27.00 2.75 39.13 22.75 9.14
W36A
W42A
W48A 42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00
W60A

R

S1

S2

T

4.19 12.00 12.00 5.00
4.19 12.00 12.00 5.00
1.44 16.00 16.00 1.88

All dimensions are in inches. Dimensional drawings are not to scale.

Built In
Rain Hood
4° Pitch
Heater
Access
Panel
Electric
Heat
C. Breaker/
Disconnect
Access Panel
(Lockable)

W

D

1
1

7.88

1.00

F

Filter Access Panel

Standard flush
vent door for
non-ERV/Econ.
models

1

.44

2.13
A

I

ERV and ECONWMS
only hood
5.88

E
O
31.88

3"
C H

Side Wall
Mounting
Brackets
(Built In)

Supply Air Opening

R

S1

B

Top Rain
Flashing
Shipping
Location

S1

Optional
Electrical
Entrances

Return Air Opening

S1

Ventilation Air
S2

G

Condenser
Air Outlet

Low Voltage
Electrical
Entrance
High Voltage
Electrical
Entrance

K

Cond.
Air
Inlet

J

Equipment Building Hood
ECONWMT-E2, -T2, -E3, -T3 is 16"
ECONWMT-E5, -T5 is 18"

M

S2

P

T
Drain

Front View

L

Side View

N
Q

Back View

Bottom Installation
Bracket
MIS-3122

1 Optional top outlet (factory installed only) for W30A and W36A models only.

Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Since 1914 . . . Moving ahead, just as planned.
Form No.
S3397-1112
Supersedes S3397-712
Page
12 of 12

Due to our continuous product improvement policy,
all specifications subject to change without notice.
Before purchasing this appliance, read important energy cost
and efficiency information available from your retailer.

Form No.
S3397
November, 2012
Supersedes: S3397-712



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Create Date                     : 2013:12:04 14:38:26-05:00
Keywords                        : W17A1-A, W18A1-A, W24A1-A, W24A1-B, W24A1-C, W30A1-A, W30A1-B, W30A1-C, W36A1-A, W36A1-B, W36A1-C, W42A1-A, W42A1-B, W42A1-C, W48A1-A, W48A1-B, W48A1-C, W60A1-A, W60A1-B, W60A1-C
Modify Date                     : 2013:12:04 16:29:53-05:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Producer                        : Acrobat Distiller 7.0 (Windows)
Creator Tool                    : Adobe PageMaker 7.0
Metadata Date                   : 2013:12:04 16:29:53-05:00
Format                          : application/pdf
Title                           : S3397  (2012 11)
Creator                         : 
Description                     : S
Subject                         : W17A1-A, W18A1-A, W24A1-A, W24A1-B, W24A1-C, W30A1-A, W30A1-B, W30A1-C, W36A1-A, W36A1-B, W36A1-C, W42A1-A, W42A1-B, W42A1-C, W48A1-A, W48A1-B, W48A1-C, W60A1-A, W60A1-B, W60A1-C
Document ID                     : uuid:1df19085-787c-4f5b-b93a-8dd4fab53d7c
Instance ID                     : uuid:fb191203-6e2e-4156-8f8e-a7c109912f8a
Page Layout                     : OneColumn
Page Count                      : 12
EXIF Metadata provided by EXIF.tools

Navigation menu