Bosch ENO 0000 B Fire Service Interface Module Data Sheet En US 1220737675

User Manual: Bosch Data Sheet ENO 0000 B External notification module

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadBosch ENO 0000 B Fire Service Interface Module Data Sheet En US 1220737675
Open PDF In BrowserView PDF
Fire Alarm Systems | ENO 0000 B Fire Service Interface Module

ENO 0000 B Fire Service Interface Module
▶ Connection of Fire Service Systems according to DIN
14675
▶ Ready to go thanks to plug-and-play technology and
pluggable terminal blocks

The ENO 0000 B enables the connection of fire service
equipment in compliance with DIN 14675:

System Overview

•
•
•
•
•

Transmission unit to fire service (AT 2000)
SD key deposit
Signal light (BEGA light, BL 200)
Monitoring of a release device
4 freely-programmable relays.
The ENO 0000 B module is only used in Germany.

Pos.

Description

Connector

1

A

Ground

2

B

Transmission unit control

3

C

Feedback contact

4

ÜE

AWUG fault

www.boschsecurity.com

2 | ENO 0000 B Fire Service Interface Module

Pos.

Description

Connector

5

NQuit

Acknowledge

6

GND

Ground

7/8

ÜE + / -

Transmission unit power supply

9

1

Monitoring of key deposit

10

Mechanics

Jumper from position 10 to 11 for the door release magnet of a 12 V key deposit.

11

2

Ground

12

5

Door release magnet, 24 V, approx. 10 W

13

8

14

6/7

15
16

ABS plastic, Polylac PA‑766 (UL94 V‑0)

Housing color

Satin finish, anthracite, RAL 7016

Dimensions

Approx. 127 x 96 x 60 mm

Weight

Approx. 150 g

Environmental conditions
Permitted operating tempera- -5 °C to 50 °C
ture
-20 °C to 60 °C

Lock monitoring

Permitted storage temperature

Ground

Permitted relative humidity

95 %, non-condensing

9

Heat system, 24 V, approx. 8 W

IP 30

10

Ground

Protection class as per
IEC 60529

17 / 18 FSE + / -

Monitoring of the release device

19 / 20 ⊗ + / -

Signal light, 24 V, approx. 10 W

21 - 32 1/2/3/4

Relays 1-4

Ordering Information
ENO 0000 B Fire Service Interface Module
for connecting fire service equipment in compliance with DIN 14675

Installation/Configuration Notes

•

Housing material

For a fire system operation according to EN 54-2, the
transmission units (FMA‑AT2000‑GSM/-ISDN/-IP) must
be installed directly next to or within the fire panel. If
the installation is remote, the feedback line to the fire
panel must be monitored.

Accessories
CPA 0000 A Cable Set AT 2000
Used to connect an AT 2000 to the MPC and
the ENO 0000 B.

Parts Included
Qty.

Components

1

ENO 0000 B Fire Service Interface Module

2

Labeling strips

Technical Specifications
Electrical
Input voltage

20 V DC to 30 V DC
5 V DC ± 5%

Max. current consumption

•
•

Standby

25 mA (at 24 V DC)

All relays triggered

60 mA (at 24 V DC)

Contact load relay

1 A / 30 V DC

Max. lead resistance transmission unit (ÜE)

2 x 10 Ω

Max. cable length key deposit 10 m
Cable type key deposit

Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us

LiYY 10 x 0.5 mm2

Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com

© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T4830620427 | Cur: en-US, V17, 30 Sep 2010

ENO 0000 B

Asia-Pacific:
Represented by
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
apr.securitysystems@bosch.com
www.boschsecurity.com

CPA 0000 A



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Author                          : Bosch Security Systems
Create Date                     : 2010:09:30 10:07:28+01:00
Modify Date                     : 2010:09:30 10:07:28+01:00
Creator                         : AH Formatter V5.0 MR2a (5,0,2009,0623) for Windows
Producer                        : Antenna House PDF Output Library 2.6.0 (Windows)
Title                           : ENO 0000 B Fire Service Interface Module
Trapped                         : False
Page Count                      : 2
Page Mode                       : UseOutlines
EXIF Metadata provided by EXIF.tools

Navigation menu