Fire Alarm Systems | Fire Monitoring System

Fire Monitoring System
www.boschsecurity.com

The Fire Monitoring System is a graphical user
interface for displaying and monitoring small to
medium fire alarm systems with up to 5000 detection
points. It is compatible with the fire alarm panels
FPA-5000 and FPA-1200.
System overview
The fire panels FPA-1200 or FPA-5000 can be
connected to the Fire Monitoring System via an
Ethernet connection. The connection must be enabled
with an ADC-5000-OPC license key. For each Fire
Monitoring System only one license key is needed.

u

Monitoring of single or networked panels

u

Management of up to 5000 detection points

u

Simultaneous connection of up to 10 clients

u

Extensive logging of events and operations

u

User friendly installation and configuration

An exclusive Ethernet network in order to set up a
central fire alarm network (1) is required. For security
and reliability reasons, no networks used for any other
purpose (2) may be part of this special network
environment. The Fire Monitoring System has to be part
of this exclusive fire alarm Ethernet network without
direct access to the Internet (3). If an internet
connection is established to receive the Fire Monitoring
System license, this internet connection must be
removed before the fire alarm network is put into
operation. Only recommended accessories may be
used.

2 | Fire Monitoring System

Single panel connection
TX Ethernet cable (copper)

2

Peer-to-Peer connection (100 m max.)

3

Fire Monitoring System: server

4

Fire Monitoring System: clients

Panel network connection
FX Ethernet cable (fiber optic)

1

2

3

1

Fire Alarm Panel (incl. ADC-5000-OPC license key)

2

Peer-to-Peer connection (100 m max.)

3

Fire Monitoring System: server

4

Fire Monitoring System: clients

4

1

Single panel connection
FX Ethernet cable (fiber optic)

2

3

4

5

6

1

Ethernet network (incl. ADC-5000-OPC license key in 1 panel)

2

Ethernet switch

3

Singlemode (SM)/Multimode (MM) Fiber (40 km/2 km max.)

4

Media Converter

5

Fire Monitoring System: server

6

Fire Monitoring System: clients

Functions

1

2

3

4

5

6

1

Fire Alarm Panel (incl. ADC-5000-OPC license key)

2

Media converter

3

Singlemode (SM)/Multimode (MM) Fiber (40 km/2 km max.)

4

Media converter

5

Fire Monitoring System: server

6

Fire Monitoring System: clients

Importing floor plans
The Fire Monitoring System supports an easy import of
various file formats, including dwg and dxf. The
software automatically allocates the detector list of
the fire panel to the floor plan.

Panel network connection
TX Ethernet cable (copper)

1
1

2

User friendly installation and operation
A wizard guides through the installation as well as the
configuration in a few steps. Automatic transfer of the
panel configuration to the software allows comfortable
object management (e.g. predefined sensors). To add
an object, the operator simply clicks on the desired
position on the map. System devices can be allocated
to objects through a drop down menu.

Extended map management
In each map, specific areas can be defined to create
sub-maps. In case of event there is an automatic zoom
into the relevant sub-map. The operator can manually
zoom into maps or sub-map and a pan function allows
to move the map in any direction.

3

4

CAN Network (incl. ADC-5000-OPC license key in 1 panel)

Object management on the map
A single sensor or a group of devices can be selected
and be moved into another map by a simple Drag &
Drop operation. Copy and paste of objects in different
maps is supported as well.

3 | Fire Monitoring System

User rights management
The authorizations are based on customizable groups.
The rights to access to e.g. different sources, maps,
alarm zones and devices are managed at group level.
Each user can be part of one or more groups.

Accessories

E-mail notification
Events can be forwarded by e-mail to users according
to their user settings.

Order number ADC-5000-OPC

Event logging
In the event log all procedures and actions are
recorded. You can search according to various criteria,
cluster and generate statistics, make backups or print
the event log. The reports can be exported to Excel.
Connectivity
A standalone fire alarm panel or a panel network with
up to 5000 detection points in total can be connected
to the Fire Monitoring System.
Language versions
The Fire Monitoring System is available in following
languages: English, German, Italian, Polish, Dutch,
French, Russian, Spanish, Turkish, Portuguese,
Romanian.
The user interface language can be individually defined
by the user.
Installation/configuration notes
Hardware Preconditions
•
•
•
•
•

Processor: dual core (1,8 GHz or more)
RAM: Minimum 2 GB
Free Disk Space: Minimum 1 GB
Network card 100 Mbps
Monitor resolution: Minimum 1366x768 pixel

Software Preconditions
•
•
•
•
•

Windows 7 (32 bit and 64 bit)
Windows 8 (32 bit and 64 bit)
Windows 10 (32 bit and 64 bit)
Microsoft Office (Release 2007 / 2010 / 2013)
.NET Framework from version 3.5.1

Ordering information
Fire Monitoring System FSM-2500

Monitoring Software to manage up to 2500 detection
points.
Order number FSM-2500
Fire Monitoring System FSM-5000

Monitoring Software to manage up to 5000 detection
points.
Order number FSM-5000
Evolution pack FSM-2500

Yearly maintenance agreement for upgrades.
Order number FSM-2500-EP
Evolution pack FSM-5000

Yearly maintenance agreement for upgrades.
Order number FSM-5000-EP

Licence Key OPC

Enables reliable communication between the OPC
server and the FPA‑1200 panel or FPA‑5000 panel or
networks.
Ethernet Switch MM
Order number BPA-ESWEX-RSR20
Ethernet Switch SM
Order number RSR20-0800S2S2T
Media Converter MM
Order number EL1141-10B-BH
Media Converter SM
Order number EL1141-B0B-BH

4 | Fire Monitoring System

Represented by:
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us

Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com

© Bosch Security Systems 2015 | Data subject to change without notice
19131121675 | en, V2, 28. Sep 2015

Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia

China:
America Latina:
Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
203 Building, No. 333 Fuquan Road
Via Anhanguera, Km 98
North IBP
CEP 13065-900
Changning District, Shanghai
Campinas, Sao Paulo, Brazil
200335 China
Phone: +55 19 2103 2860
Phone +86 21 22181111
Fax: +55 19 2103 2862
Fax: +86 21 22182398
latam.boschsecurity@bosch.com
www.boschsecurity.com.cn
www.boschsecurity.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Create Date                     : 2015:09:28 16:39:12+01:00
Modify Date                     : 2015:09:28 16:39:12+01:00
Creator                         : AH Formatter V5.3 MR3 (5,3,2011,1116) for Windows (x64)
Producer                        : Antenna House PDF Output Library 2.6.0 (Windows (x64))
Title                           : Fire Monitoring System
Trapped                         : False
Page Count                      : 4
EXIF Metadata provided by EXIF.tools

Navigation menu