Fire Alarm Systems | D9124 Addressable Fire Alarm Control Panel (FACP)

D9124 Addressable Fire Alarm Control
Panel (FACP)
▶ 24 VDC, 4 A power for initiation circuits and NACs;
12 VDC, 1.4 A power for system accessories
▶ Up to eight supervised or 32 unsupervised remote
annunciators
▶ One-man Fire Test Mode
▶ Schedules (Skeds function) service reminder for local
systems
▶ Low battery, AC power supply, and battery lead
supervision
▶ Dual phone line monitor

The D9124 FACP controls complex alarm systems used in
schools, universities, manufacturing plants, and health care
facilities. Program it for fire, fire supervisory, intrusion, or
access control applications. Program it locally using the
D5200CE hand-held programmer or remotely using RPS
over telephone lines or local-area or wide-area networks
(LAN or WAN).
The D9124 FACP is a modular assembly, installed in a red
steel enclosure, which can be surface- or flush-mounted.
The enclosure has keyed controller access making it
suitable for installation in public access areas.

Functions
Alarm Verification
The alarm verification feature reduces potential false alarms
by requiring a reset and a second alarm signal from the
device before the control panel raises an alarm condition.
Auxiliary and Standby Power
The 4 A, 24 VDC power supply charges the standby batteries
and powers auxiliary devices. The power supply responds
to low battery or battery disconnect conditions with a
Trouble LED and a Trouble Relay for sounders or lights.

Five system power trouble conditions are selected by DIP
switches. They can be individually linked to a central
station, or grouped to activate a trouble relay, allowing a
single supervised address to monitor the power supply.
A pair of 12 V batteries provides standby power. Two
additional batteries provide standby power for initiating
devices and notification appliances. All four batteries are
housed within the panel enclosure.
Note

Batteries are not included in the D9124 and
must be purchased separately.

Central Station Communication
Events can be communicated to a central station by the
digital communicator or by adding an optional Ethernet
interface module. The optional Bosch D6500 or D6600
NetCom Receiver and Modem IIIa2 reporting format provide
individual point reporting to monitoring facilities.
The D5500 Remote Programming Software (RPS) allows
the following to be controlled from a central station:

•
•
•
•
•
•
•

Resetting notification appliances
Activating or deactivating remote annunciation
Activating or deactivating relays
Supervising battery condition
Setting point status and armed status
Enabling or disabling reporting functions
Shunting reporting points during servicing

www.boschsecurity.com

2 | D9124 Addressable Fire Alarm Control Panel (FACP)

Event Log Storage, Viewing, and Printing
The D9124's memory log stores time, date, point, and user
ID for up to 1000 events. Programming options allow
restricting specific event reports to the central station
receiver. A programming option allows the log to record
certain functions entered at command centers.

Certifications and Approvals
Region

Certification

USA

UL

AMCX: Central Station Alarm Units
(UL1610, UL1635), APAW: Police Station
Alarm Units (UL365, UL464), UOJZ:
Control Units, System (UL864)

Display the 1000 events in memory at the fire system
controller(s) or retrieve them with a single phone call by a
central station using Bosch RPS version 3.7.025 or higher.

FM

The D9131A Parallel Printer Interface Module allows an onsite parallel printer to print events as they are stored in the
log: recording time, date, account number, event, point ID,
point text, and if the message was transmitted to a receiver.

CSFM

7165-1615: 113 and 7170-1615:
144 July 2008

NYC-MEA

12-92-E, Vol. IV 12-92-E, Vol. IV

Inputs
The D9124 Control Panel is a 127-point addressable system
that is expandable to 246 addressable points. The control
panel receives information from alarm initiating points
through integrated devices over a two-wire multiplex zone
expansion system. Each addressable point accommodates
both normally-open and normally-closed devices with endof-line (EOL) resistor supervision. Each point is
programmable for fire, fire supervisory, intrusion, or access
control applications.
Outputs
System notification appliance capacity can be extended
beyond the two supervised circuits by adding D8129 Octorelay Modules. Up to 128 relay outputs can be operated
through the controller or the central station, or they can be
programmed for automatic operations.
Notification appliances can be programmed for steady,
pulsed, California March Time, or Temporal Code 3
patterns. Temporal Code 3 patterns can be synchronized
using the appropriate synchronization modules.

12-92-E, Vol. X11 12-92-E, Vol. 12
Hong Kong

HKFSD

Installation/Configuration Notes
Compatible Products
The following products are compatible with the D9124
FACP:
Category

Product ID

Product Description

Batteries and
Power Supply
Products

BATB-40

Battery box

BATB-80

Battery box

D126

12 V, 7 Ah standby battery

D1218

12 V, 18 Ah standby battery

D7038

Power supply address circuit module

D285

Photoelectric smoke head

D285TH

Photoelectric smoke head with heat

D298M

Zonex smoke master base

Detectors

D298S

Zonex smoke single base

Notification Appliance Circuits (NACs)

FMM-462

Manual station

The D9124 FACP has two supervised, on-board NACs with
individual circuit silencing.

D603

Rate-of-rise heat detector head

D604

Fixed (135°F) heat detector head

User Interface

D605

Fixed (190°F) heat detector head

D720B/R

Security and fire keypads

D1255B/R

Security and fire keypads

D1256

Fire command center

D1257

Remote fire alarm annunciator

D1260

ATM keypad

D125B

Powered loop interface module
(Dual, Class B)

D129

Initiation circuit module
(Dual, Class A)

D130

Relay module

D136

Plug-in relay

D192C

Bell supervision module

D192E

Bell supervision module

A D1256 Fire Alarm keypad is visible and accessible behind
a locked, clear sliding panel located on the enclosure door.
It displays programmable text identifying specific initiating
and supervisory devices. It also provides point
annunciation, signal silence, trouble silence, detector reset,
and annunciator reset. The sliding panel lock is keyed to
match the Bosch manual pull stations for resetting the
system.
Also available as options are:

•
•
•

D1255R Security/Fire Keypad
D1257 Remote Fire Alarm Annunciator
D1260 Keypad

Keypads and
Annunciators

Modules

D9124 Addressable Fire Alarm Control Panel (FACP) | 3

Category

Programming
Products

Product ID

Product Description

Technical Specifications

D192G

Bell supervision module

D8125

POPEX module

Environmental Considerations

D8125MUX

Zonex to dual multiplex interface

D8128D

OctoPOPIT module

D8129

Octo-relay module

Inputs

D8130

Release module

D9127U

POPIT module (no tamper)

Sensor Circuits:

Up to two 8125 POPEX modules,
119 addresses per module

D9127T

POPIT module (tamper)

Sensor Circuit Protection:

D9131A

Parallel printer interface module

DX4020

Ethernet interface module

Power limited to 4 A; short circuit, reverse
polarity, thermal overload and current overload protection on-board

D5200CE

Handheld programmer

Sensor Loop Technology:

Four-wire addressable circuits

RPS

Remote Programming Software

RPS-LITE

Remote Programming Software

RPS-INTL

Remote Programming Software

Relative Humidity:

Up to 85%; non-condensing

Temperature (operating):

+32°F to +122°F (0°C to +50°C)

Mechanical Properties

Parts Included
The D9124 Addressable Control Panel is shipped in three
boxes. One box contains:
Quant.

Component

1

D9412GLTB Control Panel (less terminal blocks)

Another box contains:
Quant.

Component

1

D9101 Enclosure Assembly with Door

The third box contains a D9100 Accessory Module Carrier
that includes the following:
Quant.

Component

2

D192C Indicating Circuit Supervision Modules

1

D928 Dual Phone Line Switcher

1

D8125 POPEX Module (additional optional)

1

D9142LC 24 VDC Power Supply

The third box also contains:
Quant.

Component

1

D1256 Fire Alarm Keypad

1

D1601 Transformer

1

Wiring Harness

1

Wiring Harness for the D8125 POPEX Module

2

560 Ω Resistors (for D192C Modules)

2

D161 Dual Modular Telephone Cords

1

D162 Dual Modular Telephone Cord

1

Literature pack

Color:

Red

Material:

16-gauge (1.5 mm) steel

Dimensions (H x W x D)
Enclosure Box:

36.1 in. x 22.1 in. x 3.2 in.
(92 cm x 56 cm x 8.1 cm)

Removable Door:

37.1 in. x 23.3 in. x 1.1 in.
(94 cm x 59 cm x 2.8 cm)

Outputs
Off-board relays:

Up to 16 optional D8129 Relay Modules (eight relay outputs per module)

On-board NACs:

Two; 1.8 A maximum per circuit

Power Requirements
Current (operating)
Alarm + sensor load:

874 mA

Idle:

412 mA

Power (auxiliary):

24 VDC nominal at 1.8 A

Power (primary):

120 VAC, 60 Hz, 360 VA

Ordering Information
D9124 Addressable Fire Alarm Control
Panel (FACP)
Up to eight supervised or 32 unsupervised remote annunciators

D9124

Accessories
D113 Battery Lead Supervision Module
Supervises wiring connections for two 12 V
batteries connected to the same set of charging
terminals.

D113

D122 Dual Battery Harness
Harness with circuit breaker. Connects two
batteries to a compatible control panel.

D122

D135A Low‑battery Disconnect Module
Disconnects the control panel from the battery
when the battery level drops to 9.5 VDC.

D135A

www.boschsecurity.com

4 | D9124 Addressable Fire Alarm Control Panel (FACP)

Ordering Information
D127 Reversing Relay Module
Reports two separate alarm conditions to the
central station.

D127

D136 Plug‑In Relay
Maximum rating is 1 A at 24 VDC or 2 A at
12 VDC. Available individually (D136) or in a
package of 25 (D136‑25).

D136

D138 Mounting Bracket, Right Angle
Used to mount accessory modules in D8103,
D8108A, and D8109 enclosures.

D138

Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us

Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com

© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1113332363 | Cur: en-US, V5, 4 Jul 2010

Asia-Pacific:
Represented by
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
apr.securitysystems@bosch.com
www.boschsecurity.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Author                          : Bosch Security Systems
Create Date                     : 2010:07:04 13:25:50+01:00
Modify Date                     : 2010:07:04 13:25:50+01:00
Creator                         : XSL Formatter V4.3 MR3 (4,3,2008,0819) for Windows
Producer                        : Antenna House PDF Output Library 2.6.0 (Windows)
Title                           : D9124 Addressable Fire Alarm Control Panel (FACP)
Trapped                         : False
Page Count                      : 4
Page Mode                       : UseOutlines
EXIF Metadata provided by EXIF.tools

Navigation menu