800-B-1006-A

Commercial Gas
Ultra High Efficiency Water Heater
The Ultra High Efficiency Water Heater Models Feature:
■ Thermal Efficiency Up To 99.1%.
■ 60 Gallon Tank Capacity in 125,000, 150,000 and 199,999

BTU/hr Inputs.
■ 100 Gallon Tank Capacity in 150,000, 199,999, 250,000, 300,000

and 399,999 BTU/hr Inputs.
■ Flexible Venting—Conventional, Through-the-Wall or Direct Vent.
■ Three Pass Flue System.
■ Low NOx Premix Power Burner.
■ Ultra Quiet Operation.
■ Submerged Combustion Chamber.
■ 1" NPT Side Connection For Hydronic Applications.
■ Electronic Controls.
■ Zero Inch Clearance To Combustibles.
■ Vitraglas® Lined Tank.
■ Four Protective Magnesium Anode Rods (except EF-100T-399).
■ Powered Anode Rods (only EF-100T-399).
■ Hand Hole Cleanout—Allows inspection of tank interior.
■ Factory Installed Hydrojet® Sediment Reduction System.
■ Factory Installed Dielectric Fittings.
■ Non-CFC Foam Insulation.
■ 3" Optional Concentric Vent Kit.
■ ASME Construction Available.
■ NSF Construction Available With Optional Kit.
■ Brass Drain Valve.
■ T&P Relief Valve Factory Installed.
■ Three Year Limited Warranty On Steel Tank.
■ One Year Limited Warranty On Parts.

Photo is of
EF-100T-199

3 or 5-Year Limited Tank Warranties / 1-Year Limited Warranty on Component Parts.
For more information on warranty, please visit www.bradfordwhite.com
For products installed in USA, Canada and Puerto Rico. Some states do not allow limitations on warranties.
See complete copy of the warranty included with the heater.
MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING U.S. PATENTS: 7,063,133 B2; 5,954,492; 5,954,492; 5,761,379; 5,943,984; 5,081,696; 5,988,117; 6,142,216; 5,199,385; 5,574,822; 5,372,185;
5,485,879; 5,277,171; (B1)5,341,770; 5,660,165; 5,596,952; 5,682,666; 4,904,428; 5,023,031; 5,000,893; 4,669,448; 4,829,983; 4,808,356; 5,115,767; 5,092,519; 5,052,346; 4,416,222; 4,628,184; 4,861,968;
4,672,919; Re. 34,534. OTHER U.S. AND FOREIGN PATENT APPLICATIONS PENDING. CURRENT CANADIAN PATENTS: 1,272,914; 1,280,043; 1,289,832; 2,045,862; 2,112,515; 2,108,186; 2,107,012; 2,092,105.
Vitraglas® and Hydrojet® are registered trademarks of Bradford White® Corporation. ©2006, Bradford White Corporation. All rights reserved. Printed in U.S.A.

Ultra High Efficiency Water Heaters
eF Series® Standard Equipment Features:
Thermal Efficiency up to 99.1%—Fully condensing design.
Three Pass Flue System—The three pass flue system
keeps the hot combustion gases moving at a high velocity.
The combination of high turbulence and velocity causes an
enormous rate of heat transfer into the water.
Low NOx Premix Power Burner—Developed for the
eFSeries®, a turbulent flame shoots down the submerged
combustion chamber. This turbulence causes a thorough
mixing of the gas and air for optimum combustion and high
heat transfer efficiencies. — Far exceeds California
emission requirements.

Flexible Venting—The eF Series® can vent vertically or
horizontally with either 3" or 4" PVC, CPVC or ABS vent
pipe, and is approved for direct vent closed combustion
applications, or those applications that require inside air for
combustion. Foam Core pipe is permitted on the entire
venting system. The eF Series® is also approved for
unbalanced venting, which means the air intake pipe
doesn't have to be vented the same distance as the
exhaust.
(NOTE: Air intake cannot exceed exhaust by more than
30 feet.)

Model
Number

Submerged Combustion Chamber—Submerging the
combustion chamber in the center of the water storage
tank minimizes radiant heat loss and improves efficiency.

EF-60T-125
EF-60T-150
EF-60T-199
EF-100T-150
EF-100T-199
EF-100T-250
EF-100T-300
EF-100T-399

Non-CFC Foam Insulation—Surrounds the tank surface,
saving energy by retarding loss of heat.
Electronic Controls—Adjustable electronic thermostat for
control between 80°F and 180°F. The recycling Energy Cut
Off (ECO) shuts off all gas flow in an event of an overheat
condition.
Zero Inch Clearance—The eFSeries® jacket is cool to the
touch and is approved for zero inch clearance to
combustibles for unsurpassed installation flexibility.
Vitraglas® Lined Tank—Bradford White’s water heater
tanks are protected from the corrosive effects of hot water
by an exclusive ceramic porcelain-like coating. Our high
silica Vitraglas® lining provides a tough interior surface for
Bradford White’s water heater tanks.
Protective Magnesium Anode Rods—Employed to
provide an extra measure of corrosion protection for longer
life. Each eF heater has 4 anodes, except the EF-100T-399
which has 2 powered anode rods and one non-powered
anode rod.
Factory Installed Hydrojet® Sediment Reduction
System—Cold inlet sediment reduction device made of
stainless steel for increased durability. Helps prevent
sediment build up in tank.
Factory Installed Dielectric Fittings—All heaters equipped
with special water heater nipples for longer heater life. No
special dielectric fittings to buy.

Max. 3" PVC, Max. 4" PVC,
ABS & CPVC ABS & CPVC
120 ft.
100 ft.
80 ft.
120 ft.
100 ft.
80 ft.
60 ft.
50 ft.

170 ft.
150 ft.
130 ft.
170 ft.
150 ft.
130 ft.
110 ft.
100 ft.

Determining required vent length
1. Determine the total length of straight vent pipe (in feet)
required for both the intake and the exhaust.
2. Add 5 feet of venting for every 90˚ elbow.
3. Add 2 1⁄2 feet of venting for every 45˚ elbow.
4. Total vent length cannot exceed "Max Length" in the
above venting table.
5. Air intake cannot exceed exhaust by more than 30 feet
in any venting situation.
NOTICE: Do not include the 3" exhaust elbow or vent
terminals in determining maximum vent length.
Three year limited warranty on steel tank — Heavy
gauge steel automatically formed, rolled and welded to
assure a continuous seam for glass lining.
One year limited warranty on parts

eF Series® Optional Equipment Features:
Maxitrol Gas Pressure Regulating valve—Ensures
proper supply pressure to eF unit of 7" to 11" W.C.
(provided incoming pressure is between 1/2 and 2 psi).
This can be ordered as a separate part, or as part of
the heater. For the separate part, please use
p/n 243-45517-00 (not available for use with the
EF-100T-399).
Concentric Vent Terminal Kit—3" termination fitting
provides for only one exit opening through wall or roof
(p/n 239-44069-01).
NSF Compliance Kit—p/n 265-44542-04.

Intake/
Combustion
Air

Rain Cap

Vent
Exhaust

46 3/4"

p/n 239-44069-01

Ultra High Efficiency Water Heaters
Gas Inlet
81⁄4
Exhaust
81⁄4
Air Intake

T & P Valve
B
281⁄4

⁄4" NPT Gas Inlet

3

3" PVC Air Inlet

T & P Valve

B

11⁄2" NPT
Outlet

A
H

Cleanout
3" PVC
EXHAUST

Drain

E

1" NPT Space
Heating Outlet

G

1" NPT Space
Heating Return

C

11⁄2" NPT Inlet

D
2 ⁄8"
3

F

⁄2" NPT CONDENSATE
CONNECTION

1

3" PVC Exhaust

NOTE: Diagrams are for both the 60 and 100 gallon models.

eF Series Commercial Ultra High Efficiency Water Heater
®

Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed
Includes Installed T&P Valve and Electronic Ignition

NATURAL GAS AND LIQUID PROPANE GAS
Model
Number

V
V
V
V
V
V
V
V

●
●
●
●
●
●
●
●

★
★
★
★
★
★
★
★

EF-60T-125E-3N(A)
EF-60T-150E-3N(A)
EF-60T-199E-3N(A)
EF-100T-150E-3N(A)
EF-100T-199E-3N(A)
EF-100T-250E-3N(A)
EF-100T-300E-3N(A)
EF-100T-399E-3N(A)
Model
Number

V
V
V
V
V
V
V
V

●
●
●
●
●
●
●
●

★
★
★
★
★
★
★
★

Input

1ST Hour
Delivery
at 100°F
Rise

BTU

Gal.

125,000
150,000
199,999
150,000
199,999
250,000
300,000
399,999

187
211
265
250
309
364
405
521

Input

1ST Hour
Delivery
at 56°C
Rise

kW

Liters

EF-60T-125E-3N(A)
36.6
EF-60T-150E-3N(A)
43.9
EF-60T-199E-3N(A)
58.6
EF-100T-150E-3N(A) 43.9
EF-100T-199E-3N(A) 58.6
EF-100T-250E-3N(A) 73.2
EF-100T-300E-3N(A) 87.9
EF-100T-399E-3N(A) 117.2

708
799
1003
946
1170
1378
1533
1972

B
C
D
A
Stg. Therm.
Water Gas Relief Approx.
E
H
F
G
Capacity Eff. Floor to Jacket HW Cold Floor to Floor to Floor to Floor to Conn. Conn. Valve Shipping
Dia. Dia. Open Weight
Top of Dia. Out In
Gas
T&P
Vent
Air
Heater
Conn. Outlet Intake Conn.
U.S.
40°F 100°F 140°F
%
in.
in. in.
in.
in.
Gal.
in.
in.
in.
lbs.
in.
in.
in.
Recovery GPH
at Degree Rise

364
423
558
450
597
735
836
1127

145
169
223
180
239
294
335
451

104
121
159
129
171
210
239
322

Recovery LPH
at Degree Rise

22°C 56°C
1378
1601
3112
1703
2260
2782
3165
4266

545
640
844
681
905
1113
1268
1707

60
60
60
100
100
100
100
100

96.0
93.0
92.0
99.1
98.5
97.0
92.0
93.0

57
57
57
775/8
775/8
775/8
775/8
775/8

281/4
281/4
281/4
281/4
281/4
281/4
281/4
281/4

42
42
42
63
63
63
63
63

13
13
13
13
13
13
13
13

531/2
531/2
531/2
743/4
743/4
743/4
743/4
731/4

5
5
5
5
5
5
5
5

521/2
521/2
521/2
731/8
731/8
731/8
731/8
731/8

40
40
40
60
60
60
60
60

11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2

/
/
3/4
3/4
3/4
3/4
3/4
1

/
/
3/4
3/4
3/4
1
1
1

3 4

3 4

3 4

3 4

570
570
570
900
900
900
900
950

A
E
F
Stg. Therm.
B
C
D
G
H
Water Gas Relief Approx.
Capacity Eff. Floor to Jacket HW Cold Floor to Floor to Floor to Floor to Conn. Conn. Valve Shipping
Top of Dia. Out In
Gas
Vent
Air
T&P
Dia. Dia. Open Weight
Heater
Conn. Outlet Intake Conn.

78°C

Liters

%

mm.

mm. mm. mm.

mm.

mm.

mm.

mm.

394
458
602
488
647
795
905
1219

227
227
227
379
379
379
379
379

96.0
93.0
92.0
99.1
98.5
97.0
92.0
93.0

1448
1448
1448
1972
1972
1972
1972
1972

718
718
718
718
718
718
718
718

1359
1359
1359
1899
1899
1899
1899
1861

128
128
128
128
128
128
128
128

1324
1324
1324
1857
1857
1857
1857
1857

994
994
994
1527
1527
1527
1527
1524

For propane gas models change suffix “N” to “X” and remove “E” from the model number.
Example: EF-100T-150-3X
V - 115V A.C. Required
• - Electronic Ignition
★ - Listed with California Energy Commission
(A) ASME - All models are available with ASME construction. To order ASME
construction add the (A) to the end of the model number. Example: EF-60T-125E-3NA

1067
1067
1067
1600
1600
1600
1600
1600

330
330
330
330
330
330
330
330

mm. mm. mm.
38
38
38
38
38
38
38
38

19
19
19
19
19
19
19
25

19
19
19
19
19
25
25
25

Note: The weight is the same for both ASME and Non-ASME models.
NSF Construction Available with optional kit
Complies with SCAQMD low NOx requirements — 10.39 ng/joule
Design certified by CSA International (formerly AGA/CGA)
Amp Draw range = 1.0 to 1.8 amps and 7.0 amps for EF-100T-399
150 PSI Working Pressure (1034 kPa), 300 PSI Test Pressure (2068 kPa)

kgs.
259
259
259
408
408
408
408
431

Ultra High Efficiency Water Heaters
All models are design certified by CSA International (formerly AGA/CGA) for up to 180°F (82°C) application as an Automatic
Storage Heater, and an Automatic Circulating Tank Heater.
As an Automatic Storage Heater, all models are complete self-contained water heating systems. It needs no separate
storage tank, pump, wiring or elaborate piping network. When equipped with a mixing valve, it will supply 180°F (82°C)
sanitizing and 140°F (60°C) general purpose hot water simultaneously. These models can be used either as a single unit or
as multiples connected in parallel.
Sample Specification
The water heater shall be a Bradford White model EF-_____ with a rated storage capacity of not less than _____ gallons/
liters, a minimum gas input of __________ BTU/hr, a minimum recovery of _____ GPH/LPH at 100°F (56°C) temperature rise,
and a Thermal Efficiency Rating of ____%. It shall be design certified by CSA International (formerly AGA and CGA) for
180°F (82°C) application, either with or without a separate storage tank. The tank shall be lined with Vitraglas® vitreous
enamel and shall have a bolted hand hole cleanout. The tank shall have four extruded magnesium anode rods installed in
separate head couplings (up to 300,000 BTU/hr input) or two powered anode rods and one extruded magnesium anode rod
(for 399,999 BTU/hr input). This water heater shall be equipped with stainless steel cold water inlet, Hydrojet® Sediment
Reduction System. The heater shall be insulated with Non-CFC foam. This water heater shall be equipped with an electronic
ignition system, an ASME rated T&P relief valve and a premix closed combustion system for direct venting using either 3"
(76mm) or 4" (102mm) PVC, CPVC or ABS vent pipe. (115V AC required). The water heater shall be factory assembled and
tested. The water heater shall be approved for zero inch clearance to combustibles. The control shall be an adjustable
electronic thermostat to any temperature up to 180°F (82°C). A recycling Energy Cut Off (E.C.O.) shuts off all gas in the
event of an overheat condition. The entire installation shall be made in compliance with state and local codes and
ordinances.
Dimensions and specifications subject to change without notice in accordance with our policy of continuous
product improvement.

Ambler, PA
For U.S. and Canada field service, contact your professional installer or local Bradford White sales representative.

Sales 800-523-2931 ● Fax 215-641-1670 / Technical Support 800-334-3393 ● Fax 269-795-1089 ● Warranty 800-531-2111 ● Fax 269-795-1089
International: Telephone 215-641-9400 ● Telefax 215-641-9750 / Fax on Demand 888-538-7833 / www.bradfordwhite.com
Sales / Technical Support 866-690-0961 / 905-238-0100 ● Fax 905-238-0105 / www.bradfordwhitecanada.com

©2006, Bradford White Corporation. All rights reserved.

800-B-1006-A

Printed in U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
XMP Toolkit                     : 3.1-701
Create Date                     : 2006:10:16 12:24:48Z
Creator Tool                    : QuarkXPress(tm) 6.5
Modify Date                     : 2006:10:16 12:26:01-04:00
Metadata Date                   : 2006:10:16 12:26:01-04:00
Producer                        : QuarkXPress(tm) 6.5
X Press Private                 : %%DocumentProcessColors:.%%EndComments
Format                          : application/pdf
Title                           : 15808_251b_1005_5.qxd
Document ID                     : uuid:00085208-5d33-11db-ab13-0014510bb2fc
Instance ID                     : uuid:03167df7-5d33-11db-ab13-0014510bb2fc
Page Count                      : 4
Creator                         : QuarkXPress(tm) 6.5
EXIF Metadata provided by EXIF.tools

Navigation menu