Bryant 394Had Users Manual
394HAD to the manual 5f1fcab9-8ae2-4f48-bf65-1b78f880b70d
2015-02-02
: Bryant Bryant-394Had-Users-Manual-411935 bryant-394had-users-manual-411935 bryant pdf
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
service and maintenance procedures 394HAD 396HAD Series C GAS-FIRED INDUCED-COMBUSTION FURNACES Cancels: SP04-13 SP04-19 11-1-93 NOTE: Read the entire instruction manual before starting the installation. → These procedures are for sizes 65,000 through 150,000 Btuh units. Index ® Page ama CANADIAN GAS ASSOCIATION A PP R O VED R SAFETY CONSIDERATIONS .....................................................1 CARE AND MAINTENANCE..................................................1-5 Air Filter Arrangement..........................................................2-3 Blower Motor and Wheel......................................................3-4 Cleaning Heat Exchanger......................................................4-5 Electrical Controls and Wiring.................................................5 Pilot ...........................................................................................5 Troubleshooting ........................................................................5 Unit Wiring Diagram ............................................................6-7 Troubleshooting Chart ..............................................................8 SAFETY CONSIDERATIONS Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply. A92058 Fig. 1—Model 396HAD Downflow Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code NFPA No. 541992/ANSI Z223.1-1992 (NFGC). In Canada, refer to the current edition of the National Standard of Canada CAN/CGA-B149.1and .2-M91 Natural Gas and Propane Gas Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls. A92057 Fig. 2—Model 394HAD Upflow WARNING: The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS PERSONAL INJURY, OR DEATH. Recognize safety information. This is the safety-alert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand the signal word DANGER, WARNING, or CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard that could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions that will result in enhanced installation, reliability, or operation. CARE AND MAINTENANCE For continuing high performance and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. Consult your local dealer as to the proper frequency of maintenance and the availability of a maintenance contract. —1— WARNING: Turn off the gas and electrical supplies to the unit before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace. A failure to follow this warning could result in personal injury. WARNING: Never operate unit without a filter or with filter access door removed. A failure to follow this warning could result in fire, personal injury, or death. 1. Downflow Each furnace requires 2 filters which are installed in the return-air duct. (See Fig. 3.) WARNING: Never store anything on, near, or in contact with the furnace, such as: 1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools. 2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids. 3. Paint thinners and other painting compounds, paper bags or other paper products. A failure to follow this warning could result in corrosion of the heat exchanger, fire, personal injury, or death. AIRFLOW INSTALLATION POSITION OF FILTERS RETURN-AIR PLENUM The minimum maintenance that should be performed on this equipment is as follows: 1. Check and clean air filter each month or more frequently if required. Replace if torn. 2. Check blower motor and wheel for cleanliness and lubrication each heating and cooling season. Clean and lubricate as necessary. 3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary. CAUTION: As with any mechanical equipment, personal injury can result from sharp metal edges, etc., therefore, be careful when removing parts. ACCESS DOOR A88486 A. Fig. 3—Filter Positions Air Filter Arrangement The air filter arrangement may vary depending on the application. Refer to Table 1 or 2 for filter size information. To remove filters for cleaning or replacement, proceed as follows: a. Disconnect electrical power before removing access door. TABLE 1—FILTER SIZE INFORMATION FOR DOWNFLOW FURNACE (IN.) b. Remove blower access door after removing 2 screws. FURNACE CASING WIDTH 14-3/16 17-1/2 21 24-1/2 FILTER QUANTITY AND SIZE (2) 16 X 20 X 1 (2) 16 X 20 X 1 (2) 16 X 20 X 1 (2) 16 X 20 X 1 c. Reach up behind top plate, tilt filters toward center of return-air plenum, remove filters, and clean as needed. Replace if torn. FILTER TYPE Cleanable Cleanable Cleanable Cleanable d. Furnaces are equipped with permanent, washable filters. Clean filters with tap water. Spray water through filter in opposite direction of airflow. e. Rinse and let dry. Oiling or coating of filters is not recommended or required. f. Reinstall filters. TABLE 2—FILTER SIZE INFORMATION FOR UPFLOW FURNACE (IN.) FURNACE CASING WIDTH 14-3/16 17-1/2 21 24-1/2 FILTER QUANTITY AND SIZE Side Return Bottom Return (1) 16 X 25 X 1* (1) 14 X 25 X 1 (1) 16 X 25 X 1* (1) 16 X 25 X 1 (1) 16 X 25 X 1 (1) 20 X 25 X 1* (2) 16 X 25 X 1* (1) 24 X 25 X 1 g. Replace access door and secure with 2 screws. h. Restore electrical power to furnace. FILTER TYPE 2. Upflow Each furnace requires 1 or 2 filters which are installed in the blower compartment. (See Fig. 4.) To remove filters for cleaning or replacement, proceed as follows: a. Disconnect electrical power before removing access doors. Cleanable Cleanable Cleanable Cleanable * Factory provided with the furnace. Filters may be field modified by cutting as required. —2— MOUNTING SCREWS DRAFT SAFEGUARD SWITCH RELIEF BOX FLUE COLLECTOR BOX SPEED SELECTOR GAS VALVE MOUNTING SCREWS AUXILIARY LIMIT SWITCH (NOT VISIBLE) VENT PIPE ENCLOSURE CONTROL BOX PILOT CONTROL BOX DRAFT SAFEGUARD SWITCH RELIEF BOX SPEED SELECTOR FLUE COLLECTOR BOX FILTER RETAINER WASHABLE FILTER A92178 A92179 Fig. 5—Model 396HAD Downflow Fig. 4—Model 394HAD Upflow b. Remove blower and control access doors. 3. Disconnect wires from auxiliary limit on blower housing (downflow furnace only). c. Release filter retainer from clip at front of furnace casing. (See Fig. 4.) For side return, clips may be used on either or both sides of the furnace. 4. Remove control box. 5. Remove electrical leads from numbered side of blower speed selector. (See Fig. 4 and 5.) Note location of wires for reassembly. d. Slide filter out. e. Furnaces are equipped with permanent, washable filters. Clean filters with tap water. Spray water through filter in opposite direction of airflow. 6. Remove screws holding blower assembly to blower deck and slide blower assembly out of furnace. f. Rinse and let dry. Oiling or coating of filter is not recommended or required. 7. Squeeze side tabs of blower speed selector and pull it out of blower housing. g. Reinstall filter. 8. Loosen screw in strap holding motor capacitor to blower housing and slide capacitor out from under strap. h. Replace access doors. i. Restore electrical power to furnace. 9. Mark blower wheel, motor, and motor support in relation to blower housing before disassembly to ensure proper reassembly. B. Blower Motor and Wheel For long life, economy, and high efficiency, clean accumulated dirt and grease from the blower wheel and motor annually. The following steps should be performed by a qualified service technician: Some motors have prelubricated sealed bearings and require no lubrication. These motors can be identified by the absence of oil ports on each end of the motor. For those motors with oil ports, lubricate motor every 5 years if motor is used on intermittent operation (thermostat FAN switch in AUTO position), or every 2 years if motor is in continuous operation (thermostat FAN switch in ON position). Remember to disconnect the electrical supply before removing access doors. 10. Loosen setscrew holding blower wheel on motor shaft. 11. Remove bolts holding motor mount to blower housing and slide motor and mount out of housing. Disconnect ground wire attached to blower housing before removing motor. 12. Lubricate motor (when oil ports are provided). a. Remove dust caps or plugs from oil ports located at each end of motor. b. Use a good grade of SAE 20 nondetergent motor oil and put 1 teaspoon, 5 cc, 3/16 oz, or 16 to 25 drops in each oil port. Do not over-oil. c. Allow time for total quantity of oil to be absorbed by each bearing. Clean and lubricate as follows: d. Wipe excess oil from motor housing. 1. Remove 2 screws from blower access door (downflow furnace only). Remove blower access door. e. Replace dust caps or plugs on oil ports. 13. Remove blower wheel from housing. a. Mark cutoff location to ensure proper reassembly. 2. Remove vent pipe enclosure (downflow furnace only) and disconnect short piece of vent pipe from relief box. —3— b. Remove screws holding cutoff plate and remove cutoff plate from housing. a. Assemble wire brush and steel spring cable. (1.) Use 48 in. of 1/4-in. diameter high-grade steel spring cable (commonly known as drain clean-out or Roto- Rooter cable). c. Lift blower wheel from housing through opening. 14. Clean blower wheel and motor using a vacuum cleaner with soft brush attachment. Do not remove or disturb balance weights (clips) on blower wheel blades. The blower wheel should not be dropped or bent as balance will be affected. (2.) Use 1/4-in. diameter wire brush (commonly known as 25-caliber rifle cleaning brush). NOTE: The items needed in steps (1.) and (2.) can usually be purchased at local hardware stores. (3.) Insert twisted wire end of brush into end of steel spring cable, and crimp tight with crimping tool or strike with ball-peen hammer. TIGHTNESS is very important. 15. Reinstall blower wheel by reversing steps 13 a. through c. Be sure wheel is positioned for proper rotation. 16. Reassemble motor and blower by reversing steps 5 through 11. If motor has ground wire, be sure it is connected as before. (4.) Remove metal screw fitting from wire brush to allow insertion into cable. b. Clean each heat exchanger cell. CAUTION: Be sure the motor is properly positioned in the blower housing. The motor oil ports must be at a minimum of 45° above the horizontal centerline of the motor after the blower assembly has been reinstalled in the furnace. (1.) Attach variable-speed, reversible drill to end of steel spring cable (end opposite brush). (2.) Insert brush end of cable into upper opening of cell and slowly rotate with drill. DO NOT force cable. Gradually insert at least 36 in. of cable into 2 upper passes of cell. (See Fig. 6.) 17. Reinstall blower assembly in furnace. Connect electrical leads to blower speed selector. Please note that connections are polarized for assembly. DO NOT FORCE. 18. Reinstall control box. 19. Reconnect wires to auxiliary limit switch on blower housing (downflow furnaces only). 20. Reinstall vent pipe and enclosure (downflow furnaces only). 21. Turn on electrical power and check for proper rotation and speed changes between heating and cooling. 22. Replace blower access door and secure with 2 screws (downflow furnace only). C. Cleaning Heat Exchanger The following steps should be performed by a qualified service technician: NOTE: Deposits of soot and carbon indicate the existence of a problem which needs to be corrected. Take action to correct the problem. If it becomes necessary to clean the heat exchanger because of carbon deposits, soot, etc., proceed as follows: A91252 Fig. 6—Cleaning Heat Exchanger Cell (3.) Work cable in and out of cell 3 or 4 times to obtain sufficient cleaning. DO NOT pull cable with great force. Reverse drill and gradually work cable out. (4.) Remove burner assembly and cell inlet plates. 1. Turn off gas and electrical power to furnace. (5.) Replace screws in center panel and cells before cleaning. 2. Remove 2 screws from blower access door (downflow furnace only). Remove control and blower access doors. (6.) Insert brush end of cable in lower opening of cell, and proceed to clean 2 lower passes of cell in same manner as 2 upper passes. 3. Remove vent pipe enclosure (downflow furnace only) and disconnect vent pipe from relief box. 4. Remove 2 screws that secure relief box. (See Fig. 4 or 5.) (7.) Repeat foregoing procedures until each cell in furnace has been cleaned. 5. Disconnect wires to the following components: a. Draft safeguard switch (8.) Remove residue from each cell using vacuum cleaner. b. Inducer motor (9.) Clean burner assembly using vacuum cleaner with soft brush attachment. c. Pressure switch d. Limit overtemperature switch (10.) Reinstall cell inlet plates and burner assembly. Care must be exercised to center the burners in the cell openings. e. Gas valve f. Edge connector leading to control box 6. Remove 8 screws that secure flue collector box to center panel. Be careful not to damage sealant. 9. After cleaning flue openings, check sealant on flue collector to ensure that it has not been damaged. If new sealant is needed, contact your dealer or distributor. 7. Remove complete inducer assembly from furnace, exposing flue openings. 10. Clean and replace flue collector assembly, making sure all 8 screws are secure. 8. Clean cells using field-provided small wire brush, steel spring cable, reversible electric drill, and vacuum cleaner. 11. Reinstall 2 screws in relief box. —4— 12. Reconnect wires to the following components: a. Draft safeguard switch PILOT HEAD V–NOTCH FALLS DIRECTLY BELOW FRONT EDGE OF BURNER CARRYOVER. b. Inducer motor c. Pressure switch d. Limit overtemperature switch e. Gas valve f. Edge connector leading to control box 1/8″ 13. Reconnect vent pipe to relief box. Replace vent pipe enclosure (downflow furnace only). 14. Replace blower access door only and secure with 2 screws (downflow furnace only). 15. Turn on electrical power and gas. 16. Set thermostat and check furnace for proper operation. A91249 WARNING: Never use a match or other open flame to check for gas leaks. Use a soap-and-water solution. A failure to follow this warning could result in fire, personal injury, or death. Fig. 7—Position of Pilot to Burner E. Pilot Check the pilot and clean if necessary at the beginning of each heating season. The pilot flame should be high enough for proper impingement of the flame sensing element (or thermocouple) and to light the burners. Remove the accumulation of soot and carbon from the flame sensing element (or thermocouple). Refer to Fig. 7 for proper location of pilot on burner assembly. 17. Check for gas leaks. 18. Replace control access door. D. Electrical Controls and Wiring NOTE: There may be more than 1 electrical supply to unit. The electrical ground for 115-v wiring must be maintained properly. Refer to Fig. 8 for field wiring information and to Fig. 9 for unit wiring information. With power disconnected to unit, check all electrical connections for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are noticed, disassemble the connection, clean all parts and stripped wire, and reassemble properly and securely. Electrical controls are difficult to check without proper instrumentation; therefore, reconnect electrical power to unit and observe unit through 1 complete operating cycle. The 24-v circuit contains an automotive-type, 3-amp fuse located on the main control board. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse of identical size. F. Troubleshooting Page 8 contains a troubleshooting chart. This chart can be a useful tool in isolating furnace operation problems. Beginning with the word "Start," answer each question and follow the appropriate arrow to the next item. The chart will help identify the problem or failed component. After replacing any component, verify correct operating sequence as indicated by bold arrows. —5— FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING W FOUR WIRE R G Y THERMOSTAT TERMINALS FIELD-SUPPLIED FUSED DISCONNECT TWO-WIRE HEATINGONLY BLK BLK W WHT WHT R GND GND 115-VOLT FIELD- AUXILIARY J-BOX SUPPLIED CONTROL FUSED BOX DISCONNECT 208/230- OR 460-VOLT THREE PHASE G C GND CONDENSING UNIT Y 24-VOLT TERMINAL BLOCK FURNACE 208/230VOLT SINGLE PHASE TWO WIRE NOTE: Connect Y-terminal as shown for proper operation. NOTE: If any of the original wire, as supplied, must be replaced, use same type or equivalent wire. A78461 Fig. 8—Heating and Cooling Application Wiring Diagram —6— —7— BLWM CAP CFR DSS EAC-1 EAC-2 FU1 FU2 FL GV HFR IDM IDR ILK JB LS PCB PL1 PL2 PL4 PRS TRAN LEGEND ALS CAP BRN BLWM FU2 JB ILK NOTE #5 EAC-2 W EAC-1 HI L1 Y R NOTE #10 HFR TRAN CFR LO COM PR2 L2 PL2 BLK 1 2 WHT AUX. LIMIT SWITCH (OVER TEMP), SPST-(N.C.), MANUAL RESET BLOWER MOTOR CAPACITOR COOLING FAN RELAY, SPDT DRAFT SAFEGUARD SWITCH, SPST-(N.C.), MANUAL RESET ELECTRONIC AIR CLEANER CONNECTION (115VAC) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE FUSE, FIELD INSTALLED FUSIBLE LINK GAS VALVE, (REDUNDANT) HEATING FAN RELAY, SPST (N.O.) INDUCED DRAFT MOTOR INDUCER DRAFT RELAY, DPST-(N.O.) BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) JUNCTION BOX LIMIT SWITCH (OVER TEMP), SPST-(N.C.), AUTO RESET PRINTED CIRCUIT BOARD (FURNACE CONTROL) 9-CIRCUIT CONNECTOR (PCB1) 2-CIRCUIT CONNECTOR (L1, L2) 5-CIRCUIT PLUG CONNECTOR (BLWM) PRESSURE SWITCH, SPDT TRANSFORMER (115VAC/24VAC) BRN GRN NOTE #4 PL4 4 3 RED 2 BLK 1 WHT C LO MED LO MED HI HI COM GRN WHT BLK FUSED DISCONNECT SWITCH (WHEN REQ'D) IDM RED WHT BLK WHT WHT (WHEN USED) NOTE #7 ALS BLU FL C NOTE #9 PR1 BLK PILOT BLK TH LS DSS IDR 3AMP FUSE NOTE #8 FU1 PL1 1 4 7 2 5 8 3 6 9 NC NO GROUND SCREW REQ'D SEC-1 SEC-2 BLU BRN ORN PLUG RECEPTACLE FIELD SPLICE EQUIPMENT GROUND PCB HFR L2 NOTE #1 PL1-6 FL CFR PRS EAC-2 PL1-4 COM IDR C DSS NOTE #10 4 3 2 1 C FU1 PR-1 TRAN 115VAC BLWM TH HFR PILOT IDR TR MGV GV TIME DELAY LOGIC PL1-8 SEC-2 PR-2 IDM SCHEMATIC DIAGRAM 3A SEC-1 24VAC FUSE NOTE#8 PL1-1 PL1-3 CAP LO MED LO MED HI HI COM PL4 NOTE#4 PL1-2 (WHEN USED) NOTE #7 ALS EAC-1 CFR EQUIPMENT GROUND TO 115V AC FIELD DISCONNECTIONS NOTE #5 PL1-9 NO NC LS IDR NOTE#10 L1 L2 A92176 NOTES: 1. INTERNALLY CONNECTED TO EQUIPMENT GROUND THROUGH MOUNTING SCREW. 2. IF ANY OF THE ORIGINAL EQUIPMENT WIRE IS REPLACED, USE WIRE RATED FOR 105° C. 3. BLOWER MOTOR (BLWM) & INDUCER MOTOR (IDM) CONTAIN AUTO-RESET THERMAL OVERLOAD SWITCH. 4. BLOWER MOTOR FACTORY SPEED SELECTIONS (PL4) ARE FOR AVERAGE CONDITIONS. SEE INSTALLATION INSTRUCTIONS FOR DETAILS ON OPTIMUM SPEED SELECTIONS. 5. USE ONLY COPPER WIRE BETWEEN THE DISCONNECT SWITCH AND THE FURNACE JUNCTION BOX (JB). 6. SYMBOLS ARE ELECTRICAL REPRESENTATIONS ONLY. 7. AUXILIARY LIMIT SWITCH (ALS) USED ON DOWNFLOW MODELS ONLY. 8. THE TRANSFORMER 24VAC WINDING IS PROTECTED BY A 3 AMP AUTOMOTIVE BLADE TYPE FUSE ON THE CONTROL BOARD. A 24VAC SHORT TO GROUND DURING INSTALLATION, CHECKOUT, OPERATION, SERVICE OR MAINTENANCE COULD CAUSE THIS FUSE TO OPEN. DO NOT REPLACE THE 3 AMP FUSE WITH ANY OTHER SIZE FUSE. 9. BLOWER MOTOR (BLWM) ADJUSTABLE OFF-DELAY. FACTORY SET: 120 SECS. CUT RESISTOR: 180 SECS. 10. WHEN CFR RELAY IS ENERGIZED, HFR RELAY IS ALSO ENERGIZED. 319593-401 REV. C C G W Y R PL1-7 L1 PL2 ILK Fig. 9—Unit Wiring Diagram FIELD WIRING SCREW TERMINAL FIELD GROUND C NOTE #1 PRS JUNCTION TERMINAL PCB TERMINAL FACTORY POWER WIRING (120VAC) FACTORY CONTROL WIRING (120VAC) FIELD POWER WIRING (120VAC) CONDUCTOR ON PCB G BRN BLK GV MGV BLU RED TR WHT RED RED CONNECTION DIAGRAM YEL START Turn on 115-VAC power to unit. Disconnect all thermostat wires from board. Turn off 115-VAC power to unit. NO Is blower running? Is 24VAC across screws R & C? YES NO NO Is 115VAC across HI & COM? NO YES Replace board. NO YES NO YES Replace board. YES NO YES Is 115VAC across L1 & L2? YES NO Replace board. YES Is 24VAC across pressure switch N/O contact & screw C on board? Repair wire harness. NO Check/Replace: 1. Vent systems 2. Induce wheel 3. Flue choke 4. Inducer voltage 5. Inducer motor bearings Jumper across screws R & W. NO NO Is heat exchanger pressure drop greater than 0.35-in. wc? YES Check/Replace: 1. 3-amp board fuse 2. Transformer Is 24VAC across PL1-2 & screw C on board? YES Does blower turn off? NO Check/Replace: 1. Unit power 2. Door switch 3. Power harness Check pressure tube for leak or crimp; otherwise, replace pressure switch Remove R & G jumper. Is 24VAC across screws R & C? YES NO Replace blower motor and/or start capacitor. Is 115VAC across EAC-1 & COM? YES NO Is 24VAC across screws W & C or G & C? Check/Replace: 1. Limit switch 2. Limit shield (if used) 3. Fuse link 4. Auxillary limit switch (if used) 5. Wire harness Jumper across screws R & G. Is blower running on cooling speed? YES Are all thermostat wires to board disconnected? Is 24VAC across pressure switch N/O contact & screw C on board? YES Check/Replace: 1. Draft safeguard switch 2. Wire harness NO Is inducer motor on? YES Is unit lit? NO Replace inducer motor. YES Check/Repair wire harness; otherwise, replace pressure switch. Is 24VAC across gas valve? YES Check/Replace: 1. Pilot 2. Thermocouple 3. Gas valve YES Is blower running on heat speed 45 sec after unit lights? Is 115VAC across inducer motor connector? NO NO NO NO NO YES Is 24VAC across PL-1 & screw C on board? Is 115VAC across EAC-1 & COM? Replace blower motor and/or start capacitor. YES Replace board. NO YES Replace board. YES NO YES Is 24VAC across PL-2 & screw C on board? Is 115VAC across inducer motor connector? Remove R & M jumper. Check/Replace thermostat and/or thermostat wiring. Repair wire harness. NO NO After off-delay does blower turn off? YES Reconnect all thermostat wires. Does unit operate? NOTE: After replacing any component, verify correct operating sequence as indicated by bold arrows. YES END OF TEST. A91253 © 1993 BDP Co. • P.O. Box 70 • Indianapolis, IN 46206 Printed in U.S.A. —8— 35001b Catalog No. BDP-3339-432
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes XMP Toolkit : 3.1-701 Creation Date--Text : Tuesday, 23 August, 1994 at 03:51pm Producer : Acrobat Distiller 1.02 for Windows Keywords : Format : application/pdf Title : Description : Creator : Carrier Corporation Subject : Modify Date : 2005:11:10 11:32:29-05:00 Create Date : 2005:11:10 11:32:29-05:00 Metadata Date : 2005:11:10 11:32:29-05:00 Document ID : uuid:598d41bd-a1f5-4cab-8a5a-e2eb9c17c49d Instance ID : uuid:42b4fa81-ef73-4341-9018-23cec9cceb94 Page Count : 8 Author : Carrier CorporationEXIF Metadata provided by EXIF.tools