Bryant 3 383Kav Users Manual

383KAV to the manual d7f4dfc0-f126-4f48-a13a-e1d65e6a7625

2015-02-02

: Bryant Bryant-3-383Kav-Users-Manual-411982 bryant-3-383kav-users-manual-411982 bryant pdf

Open the PDF directly: View PDF PDF.
Page Count: 12

SAFETY CONSIDERATIONS
NOTE: Read the entire instruction manual before performing any
service or maintenance.
This symbol indicates a change since the last issue.
These procedures are for size 45,000 through 155,000 Btuh input
units.
Index Page
SAFETY CONSIDERATIONS..................................................1-2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE...........................................................................2
CARE AND MAINTENANCE................................................2-11
Air Filter Arrangement..........................................................2-3
Blower Motor and Wheel......................................................3-4
Cleaning Heat Exchanger......................................................4-5
Electrical Controls and Wiring .............................................5-6
Troubleshooting...................................................................6-11
Unit Wiring Diagram................................................................8
Service Label ............................................................................9
Troubleshooting Guide......................................................10-11
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified person-
nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA No.
54-1996/ANSI Z223.1-1996 and the Installation Standards, Warm
Air Heating and Air Conditioning Systems (NFPA 90B)
ANSI/NFPA 90B. In Canada, refer to the current edition of the
National Standard of Canada CAN/CGA-B149.1- and .2-M95
Natural Gas and Propane Installation Codes (NSCNGPIC). Wear
safety glasses and work gloves. Have fire extinguisher available
during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol .
When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation. Fig. 3—Model 383KAV
Upflow
A94085
Fig. 2—Model 373LAV
Downflow
A94086
Fig. 1—Model 373LAV Horizontal
A94087
®
ama
CANADIAN GAS ASSOCIATION
APPROVED
R
REGISTERED QUALITY SYSTEM
service and
maintenance procedures
GAS-FIRED
INDUCED-COMBUSTION FURNACES
Cancels: SP04-44 SP04-53
9-98
373LAV
383KAV
Series G
—1—
WARNING: The ability to properly perform mainte-
nance on this equipment requires certain expertise, me-
chanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the User’s Manual. FAILURE TO FOLLOW
THIS WARNING COULD RESULT IN POSSIBLE
DAMAGE TO THIS EQUIPMENT, SERIOUS PER-
SONAL INJURY, OR DEATH.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation
and servicing to protect the furnace electronic control.
Precautions will prevent electrostatic discharges from
personnel and hand tools which are held during the
procedure. These precautions will help to avoid exposing
the control to electrostatic discharge by putting the
furnace, the control, and the person at the same electro-
static potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE
CONTROL PRIOR TO DISCHARGING YOUR BODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the
furnace chassis which is close to the control. Tools held in
a person’s hand during grounding will be satisfactorily
discharged.
3. After touching the chassis you may proceed to service the
control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch un-
grounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before touch-
ing control or wires.
5. Use this procedure for installed and uninstalled (un-
grounded) furnaces.
6. Before removing a new control from its container, dis-
charge your body’s electrostatic charge to ground to protect
the control from damage. If the control is to be installed in
a furnace, follow items 1 through 5 before bringing the
control or yourself into contact with the furnace. Put all
used AND new controls into containers before touching
ungrounded objects.
7. An ESD service kit (available from commercial sources)
may also be used to prevent ESD damage.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip-
ment failure, it is essential that periodic maintenance be performed
on this equipment. Consult your local dealer as to the proper
frequency of maintenance and the availability of a maintenance
contract.
WARNING: Never store anything on, near, or in contact
with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning
compounds, plastic or plastic containers, gasoline, kero-
sene, cigarette lighter fluid, dry cleaning fluids, or other
volatile fluids.
3. Paint thinners and other painting compounds, paper
bags, or other paper products.
A failure to follow this warning could result in corrosion
of the heat exchanger, fire, personal injury, or death.
WARNING: Turn off the gas and electrical supplies to
the unit before performing any maintenance or service.
Follow the operating instructions on label attached to
furnace. A failure to follow this warning could result in
personal injury.
The minimum maintenance that should be performed on this
equipment is as follows:
1. Check and clean air filter each month or more frequently if
required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating
and cooling season. Clean and lubricate as necessary.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as necessary.
CAUTION: As with any mechanical equipment, per-
sonal injury can result from sharp metal edges, etc.,
therefore, be careful when removing parts.
A. Air Filter Arrangement
The air filter arrangement may vary depending on the application.
Refer to Table 1 or 2 for filter size information.
WARNING: Never operate unit without a filter or with
filter access door removed. A failure to follow this
warning could result in fire, personal injury, or death.
TABLE 1—FILTER SIZE INFORMATION FOR
DOWNFLOW/HORIZONTAL FURNACES (IN.)
FURNACE
CASING WIDTH FILTER QUANTITY
AND SIZE FILTER
TYPE
14-3/16 (2) 14 X 20 X 1 Cleanable
17-1/2 (2) 14 X 20 X 1 Cleanable
21 (2) 16 X 20 X 1 Cleanable
24-1/2 (2) 16 X 20 X 1 Cleanable
TABLE 2—FILTER SIZE INFORMATION FOR UPFLOW
FURNACES (IN.)
FURNACE
CASING WIDTH FILTER QUANTITY AND SIZE FILTER
TYPE
Side Return Bottom Return
14-3/16 (1) 16 X 25 X 1* (1) 14 X 25 X 1 Cleanable
17-1/2 (1) 16 X 25 X 1* (1) 16 X 25 X 1 Cleanable
21 (1) 16 X 25 X 1 (1) 20 X 25 X 1* Cleanable
24-1/2 (2) 16 X 25 X 1* (1) 24 X 25 X 1 Cleanable
* Factory-provided with the furnace. Filters may be field modified as required
by cutting to desired size.
—2—
1. Downflow/Horizontal
Each furnace requires 2 filters which are installed in the
return-air duct. (See Fig. 4 and 5.) To remove filters for
cleaning or replacement, proceed as follows:
a. Disconnect electrical power before removing blower
access door.
b. Remove screw from front of door and remove blower
access door.
c. Reach up behind top plate, tilt filters toward center of
return-air plenum, remove filters, and clean as needed.
Replace if torn.
d. Furnaces are equipped with permanent, washable filters.
Clean filters with tap water. Spray water through filter in
opposite direction of airflow.
e. Rinse and let dry. Oiling or coating of filters is not
recommended or required.
f. Reinstall filters.
g. Replace blower access door.
h. Restore electrical power to furnace.
2. Upflow
Each furnace requires 1 or 2 filters which are installed in the
blower compartment. (See Fig. 6.) To remove filters for
cleaning or replacement, proceed as follows:
a. Disconnect electrical power before removing access
doors.
b. Remove blower and control access doors.
c. Release filter retainer from clip at front of furnace
casing. (See Fig. 6.) For side return, clips may be used on
either or both sides of the furnace.
d. Slide filter(s) out.
e. Furnaces are equipped with permanent, washable filters.
Clean filters with tap water. Spray water through filter in
opposite direction of airflow.
f. Rinse and let dry. Oiling or coating of filter is not
recommended or required.
g. Reinstall filter(s).
h. Replace blower and control access doors.
i. Restore electrical power to furnace.
B. Blower Motor and Wheel
For long life, economy, and high efficiency, clean accumulated dirt
and grease from the blower wheel and motor annually.
The following steps should be performed by a qualified service
technician.
Some motors have prelubricated sealed bearings and require no
lubrication. These motors can be identified by the absence of oil
ports on each end of the motor. For those motors with oil ports,
lubricate motor every 5 years if motor is used on intermittent
operation (thermostat FAN switch in AUTO position), or every 2
years if motor is in continuous operation (thermostat FAN switch
in ON position).
NOTE: Remember to disconnect the electrical supply before
removing access doors.
Clean and lubricate as follows:
1. Remove screw from blower access door (downflow/
horizontal furnace only) and remove blower access door.
2. Remove vent pipe enclosure (downflow/horizontal furnace
only) and disconnect short piece of vent pipe from relief
box.
3. Disconnect wires from auxiliary limit on blower housing
(when used on downflow/horizontal furnace only).
4. Remove control.
5. Disconnect electrical leads from control. (See Fig. 6 or 7.)
Note location of wires for reassembly.
6. Remove screws holding blower assembly to blower deck
and slide blower assembly out of furnace.
7. Loosen screw in strap holding motor capacitor to blower
housing and slide capacitor out from under strap.
8. Mark blower wheel, motor, and motor support in relation to
blower housing before disassembly to ensure proper reas-
sembly.
9. Loosen setscrew(s) holding blower wheel on motor shaft.
10. Remove bolts holding motor mount to blower housing and
slide motor and mount out of housing. Disconnect ground
wire attached to blower housing before removing motor.
11. Lubricate motor (when oil ports are provided).
Fig. 4—Horizontal Filter Arrangement
A94307
AIRFLOW
Fig. 5—Downflow Filter Arrangement
A88486
RETURN-AIR
PLENUM
AIRFLOW
ACCESS DOOR
INSTALLATION
POSITION
OF FILTERS
—3—
a. Remove dust caps or plugs from oil ports located at each
end of motor.
b. Use a good grade of SAE 20 nondetergent motor oil and
put 1 teaspoon, 5 cc, 3/16 oz, or 16 to 25 drops in each
oil port. Do not over-oil.
c. Allow time for total quantity of oil to be absorbed by
each bearing.
d. Wipe excess oil from motor housing.
e. Replace dust caps or plugs on oil ports.
12. Remove blower wheel from housing.
a. Mark cutoff location to ensure proper reassembly.
b. Remove screws holding cutoff plate and remove cutoff
plate from housing.
c. Lift blower wheel from housing through opening.
13. Clean blower wheel and motor using a vacuum cleaner with
soft brush attachment. Do not remove or disturb balance
weights (clips) on blower wheel blades. The blower wheel
should not be dropped or bent as balance will be affected.
14. Reinstall blower wheel by reversing items 12 a through c.
Be sure wheel is positioned for proper rotation.
15. Reassemble motor and blower by reversing items 5 through
10. If motor has ground wire, be sure it is connected as
before.
CAUTION: Be sure the motor is properly positioned in
the blower housing. The motor oil ports must be at a
minimum of 45° above the horizontal centerline of the
motor after the blower assembly has been reinstalled in
the furnace.
16. Reinstall blower assembly in furnace.
17. Reinstall control. Connect blower electrical leads to control.
Please note that the common wire connection is 3/16 in. and
all other wire connections are 1/4 in. for assembly. DO
NOT FORCE.
18. Reconnect wires to auxiliary limit switch on blower housing
(downflow/horizontal furnace only).
19. Reinstall vent pipe and enclosure (downflow/horizontal
furnace only).
20. Turn on electrical power and check for proper rotation and
speed changes between heating and cooling.
21. Replace blower access door. Secure with screw (when used
on downflow/horizontal furnace only).
C. Cleaning Heat Exchanger
The following steps should be performed by a qualified service
technician.
NOTE: Deposits of soot and carbon indicate the existence of a
problem which needs to be corrected. Take action to correct the
problem.
If it becomes necessary to clean the heat exchanger because of
carbon deposits, soot, etc., proceed as follows:
1. Turn off gas and electrical power to furnace.
2. Remove screw from front of blower access door
(downflow/horizontal furnace only) and remove control and
blower access doors.
3. Remove vent pipe enclosure (downflow/horizontal furnace
only) and disconnect vent pipe from relief box.
4. Remove 2 screws that secure relief box. (See Fig. 6 or 7.)
5. Disconnect wires to the following components.
a. Blocked vent safeguard
b. Inducer motor
c. Pressure switch
d. Limit overtemperature switch(es)
e. Gas valve
f. Hot surface ignitor
g. Flame-sensing electrode
6. Remove 8 screws that secure flue collector box to center
panel. Be careful not to damage sealant.
7. Remove complete inducer assembly from furnace, exposing
flue openings.
8. Clean cells using field-provided small wire brush, steel
spring cable, reversible electric drill, and vacuum cleaner.
a. Assemble wire brush and steel spring cable.
(1.) Use 48 in. of 1/4-in. diameter high-grade steel
spring cable (commonly known as drain clean-out
or Roto-Rooter cable).
Fig. 6—Model 383KAV Upflow
A98528
C
OM
24V
HUM
GRYW
BLOCKED
VENT
SAFEGUARD
FLUE
COLLECTOR
BOX
MOUNTING
SCREWS
RELIEF
BOX
CONTROL
FILTER
RETAINER
WASHABLE
FILTER
Fig. 7—Model 373LAV Downflow
A98529
VENT PIPE
ENCLOSURE
BLOCKED
VENT
SAFEGUARD
MANUAL
RESET LIMIT
SWITCHES
AUXILIARY
LIMIT
SWITCH
(WHEN USED)
MOUNTING
SCREWS
RELIEF
BOX
C
OM
24V
HUM
GRYW
CONTROL
BOARD
—4—
(2.) Use 1/4-in. diameter wire brush (commonly known
as 25-caliber rifle cleaning brush).
NOTE: The materials needed in items (1.) and (2.) can usually be
purchased at local hardware stores.
(3.) Insert twisted wire end of brush into end of steel
spring cable, and crimp tight with crimping tool or
strike with ball-peen hammer. TIGHTNESS is very
important.
(4.) Remove metal screw fitting from wire brush to
allow insertion into cable.
b. Clean each heat exchanger cell.
(1.) Attach variable-speed, reversible drill to end of
steel spring cable (end opposite brush).
(2.) Insert brush end of cable into upper opening of cell
and slowly rotate with drill. DO NOT force cable.
Gradually insert at least 36 in. of cable into 2 upper
passes of cell. (See Fig. 8.)
(3.) Work cable in and out of cell 3 or 4 times to obtain
sufficient cleaning. DO NOT pull cable with great
force. Reverse drill and gradually work cable out.
(4.) Remove burner assembly and cell inlet plates.
CAUTION: Be very careful when removing the burner
assembly to avoid breaking the ignitor. See Fig. 9 for the
correct ignitor location.
(5.) Replace screws in center panel and cells before
cleaning.
(6.) Insert brush end of cable in lower opening of cell,
and proceed to clean 2 lower passes of cell in same
manner as 2 upper passes.
(7.) Repeat foregoing procedures until each cell in
furnace has been cleaned.
(8.) Remove residue from each cell using vacuum
cleaner.
(9.) Clean burner assembly using vacuum cleaner with
soft brush attachment.
(10.) Clean flame sensor with fine sandpaper.
(11.) Reinstall cell inlet plates and burner assembly.
Care must be exercised to center the burners in the
cell openings.
9. After cleaning flue openings, check sealant on flue collector
to ensure that it has not been damaged. If new sealant is
needed, contact your dealer or distributor.
10. Clean and replace flue collector assembly, making sure all
8 screws are secure.
11. Reinstall relief box.
12. Reconnect wires to the following components.
a. Blocked vent safeguard
b. Inducer motor
c. Pressure switch
d. Limit overtemperature switch(es)
e. Gas valve
f. Hot surface ignitor
g. Flame-sensing electrode
13. Reconnect vent pipe to relief box. Replace vent pipe
enclosure (downflow/horizontal furnace only).
14. Replace blower access door only.
15. Turn on electrical power and gas.
16. Set thermostat and check furnace for proper operation.
WARNING: Never use a match or other open flame to
check for gas leaks. Use a soap-and-water solution. A
failure to follow this warning could result in fire, personal
injury, or death.
17. Check for gas leaks.
18. Replace control access door on upflow furnace.
19. On downflow/horizontal furnaces, remove blower access
door, replace control access door first, then replace blower
access door and secure with screw in front of door.
D. Electrical Controls and Wiring
CAUTION: There may be more than 1 electrical supply
to the unit. Check accessories and cooling unit for
additional electrical supplies.
Fig. 8—Cleaning Heat Exchanger Cell
A91252
Fig. 9—Position of Ignitor to Burner
A93347
BURNER
IGNITOR
11 32"
78"
C
L
C
L
IGNITOR
ASSEMBLY
CELL
PANEL
BURNER
13 32"
HOT
SURFACE
IGNITOR
ASSEMBLY
—5—
The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 10 for field wiring information
and to Fig. 12 for unit wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control center will flash rapidly and prevent the furnace from
operating. The control system also requires an earth ground for
proper operation of the control board and flame sensing.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control board. (See Fig. 11.) Any direct shorts of the 24-v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a fuse of
identical size.
With power to the unit disconnected, check all electrical connec-
tions for tightness. Tighten all screws on electrical connections. If
any smoky or burned connections are found, disassemble the
connection, clean all parts, strip wire, and reassemble properly and
securely.
Reconnect electrical power to the unit and observe unit through 1
complete operating cycle. Electrical controls are difficult to check
without proper instrumentation; if there are any discrepancies in
the operating cycle, contact your dealer and request service.
For an explanation of fault codes, refer to service label located on
blower access door or Fig. 13, and the troubleshooting guide.
The control center stores 1 fault code (the last fault to occur) for a
period of 48 hrs or until the 115- or 24-v power is interrupted.
NOTE: Removing blower access door will open blower access
door switch and terminate 115-v power to control center, and fault
code will be erased. Look into blower access door sight glass for
current LED status.
1. To retrieve fault code, proceed with the following:
NOTE: NO thermostat signal may be present at control center,
and all blower time delay off periods must be completed.
a. Leave 115-v power to furnace turned on.
b. Look into blower access door sight glass for current
LED status.
NOTE: Leave blower access panel installed to maintain power to
control center to view current LED status.
c. Remove control access door.
d. BRIEFLY remove either wire from the main limit switch
until LED goes out, then reconnect it.
NOTE: If wire to main limit is disconnected longer than 4 sec,
main blower starts, and retrieval request is ignored.
2. When above items have been completed, the following will
occur:
a. LED flashes a fault code 4 times. Record this fault code
for further troubleshooting.
b. Inducer motor starts and continues to run the entire
component test.
c. Hot surface ignitor is energized for 15 sec, then de-
energized.
d. Main blower operates at cooling speed for 10 sec, then
turns off.
e. Main blower operates at heating speed for 10 sec, then
turns off.
f. Inducer motor stops.
Items a through e above will assist in furnace troubleshoot-
ing since all components are functionally operated except
the gas valve. This procedure is also referred to as "Com-
ponent Test."
3. Operate furnace through 1 heat cycle to test for proper
operation and check LED status.
4. If furnace is operating properly and LED indicates proper
operation, replace control access door.
5. Component Test can also be initiated by performing the
following:
a. Remove control access door.
b. Remove blower access door.
c. Manually close blower access door switch.
WARNING: Blower access door switch opens 115-v
power to control center. No component operation can
occur. Caution must be taken when manually closing this
switch for service purposes. Failure to follow this warn-
ing could result in personal injury or death.
d. BRIEFLY short (jumper) TEST, 1/4-in. quick-connect
terminal on control center (adjacent to LED diagnostic
light), and Com terminal on thermostat connection
block. (See Fig. 11.)
NOTE: If TEST to Com terminals are jumpered longer than 2 sec,
LED will flash rapidly, and retrieval request will be ignored.
e. Component Test will function as described in item 2
above.
f. Check LED status.
g. If LED status indicates proper operation, release blower
access door switch, replace blower access door, and
replace control access door.
E. Troubleshooting
Refer to the service label. (See Fig. 13.) Pages 10 and 11 contain
a troubleshooting guide. This guide can be a useful tool in isolating
furnace operation problems. Beginning with the word "Start,"
answer each question and follow the appropriate arrow to the next
item.
The guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence.
—6—
Fig. 10—Heating and Cooling Application Wiring Diagram
A98209
115-V
FIELD-SUPPLIED
DISCONNECT
AUXILIARY
J-BOX
CONTROL
BOX
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-
ONLY
FIVE
WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
R
G
C
WCR GY
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
WHT
BLK
WHT
BLK
NOTES: Connect Y-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y
GND
THERMOSTAT
TERMINALS
1.
2.
3.
Fig. 11—Control Board
A95086
C
OM
24V
HUM
GRYW
3-AMP FUSE
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX)
LED OPERATION &
DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24-V TRANSFORMER SEC-2
SPARE-1
SPARE-2
EAC-1
EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX)
EAC-2
115-VAC (L2) NEUTRAL
CONNECTION
24-V THERMOSTAT
TERMINALS
BLOWER SPEED
SELECTION TERMINALS
INDUCER MOTOR
CONNECTOR
115-VAC (L1)
POWER SUPPLY
HOT SURFACE
IGNITOR CONNECTOR
HEAT
COOL
SEC-1
TEST/TWIN
—7—
Fig. 12—Wiring Diagram
A98200e
PCB
BLOWER OFF DELAY
SELECTION CHART
90 SEC
135 SEC
180 SEC
225 SEC
GVR
HI/LO
RELAY
SEC-1 SEC-2
PL1 321
654
987
LED
TEST/TWIN
BLOWER
OFF
DELAY
G
R
Y
W
C
HUM
HSIR IDR BLWR
BLOWER
SPEED
SELECT
FU1
COOL
HEAT
L2
PL3
PL2
VAC
120
L1 PR1 1
2
1
2
3
PR2
24 VAC-3A
FUSE
SPARE-2
SPARE-1
EAC-1
EAC-2
C
1.5 AMP
12
PL5 WHT
BLK
WHT
WHT
BLK
BLK
HSI
BLK
WHT
WHT (COM)
RED (LO)
BLU (MED LO)
NOTE #7
OL
START
BLWM
YEL (MED HI)
BLK (HI)
BRN
BRN
TRAN
BLU
RED
BLK
WHT
WHT (COM)
GRN
CAP
RED
NOTE #5
RED
ORN
FUSED DISCONNECT
SWITCH (WHEN REQ'D)
NOTE #4
FU2
BLK
WHT
GRN
GRN
JB
LEGEND
ALS AUXILIARY LIMIT SWITCH, OVERTEMP. -MANUAL RESET, SPST-(N.C.)
BLWR BLOWER MOTOR RELAY, SPST-(N.O.)
BLWM BLOWER MOTOR
BVSS BLOCKED VENT SHUTOFF SWITCH, SPST - (N.C.)
CAP CAPACITOR
CPU MICROPROCESSOR AND CIRCUITRY
DSS DRAFT SAFEGUARD SWITCH
EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.5 AMP MAX.)
EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON)
FL FUSIBLE LINK
FRS FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.)
FSE FLAME PROVING ELECTRODE
FU1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED
FU2 FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE
(FIELD INSTALLED & SUPPLIED)
GV GAS VALVE-REDUNDANT OPERATORS
GVR GAS VALVE RELAY, DPST-(N.O.)
HI/LO BLOWER MOTOR SPEED CHANGE RELAY, SPDT
HSI HOT SURFACE IGNITOR (115 VAC)
HSIR HOT SURFACE IGNITOR RELAY, SPST-(N.O.)
HUM 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.)
IDM INDUCED DRAFT MOTOR
IDR INDUCED DRAFT RELAY, SPST-(N.O.)
ILK BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.)
JB JUNCTION BOX
LED LIGHT-EMITTING DIODE FOR STATUS CODES
LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.)
LS LIMIT SWITCH, AUTO RESET, SPST(N.C.)
OL AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW.
PCB PRINTED CIRCUIT BOARD
PL1 9-CIRCUIT CONNECTOR
PL2 2-CIRCUIT PCB CONNECTOR
PL3 3-CIRCUIT IDM CONNECTOR
PL5 2-CIRCUIT HSI/PCB CONNECTOR
PRS PRESSURE SWITCH, SPST-(N.O.)
TEST/TWIN COMPONENT TEST & TWIN TERMINAL
TRAN TRANSFORMER-115VAC/24VAC
JUNCTION
UNMARKED TERMINAL
PCB TERMINAL
FACTORY WIRING (115VAC)
FACTORY WIRING (24VAC)
FIELD WIRING (115VAC)
FIELD WIRING (24VAC)
CONDUCTOR ON PCB
FIELD WIRING TERMINAL
FIELD GROUND
EQUIPMENT GROUND
FIELD SPLICE
PLUG RECEPTACLE
L1 NEUTRAL
L1 BLWR
HI/LO
TO 115VAC FIELD DISCONNECT
NOTE #4
EQUIPMENT GROUND
SPARE-2
HEAT
SPARE-1
COOL NOTE #7
COM
HSIR
EAC-1
START
OL
COM
HI
MED HI
MED LO
LO
BLWM
SCHEMATIC DIAGRAM
(NATURAL GAS & PROPANE)
EAC-2
11HSI
2
PL52
PL2
3PL3
PR2
115VAC
PR1
TRAN
24VAC
1
2
IDR
TEST/TWIN
FU1 NOTE #6
CAP
L2
PL1
8
FSE
9
6
5
CPU
HSIR
IDR
BLWR
Y
G
C
R
W
GVR-2
SEC-1
HI/LO
GVR
SEC-2
NOTES:
322869-101 REV. E
1. If any of the original equipment wire is replaced use wire rated for 105˚C.
2. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL).
3. Blower motor speed selections are for average conditions, see installation instructions for details on
optimum speed selection.
4. Use only copper wire between the disconnect switch and the furnace junction box (JB).
5. This wire must be connected to furnace sheetmetal for control to detect flame.
6. Replace only with a 3 amp fuse.
7. Yellow lead not on all motors.
8. Blower-on delay, gas heating 45 seconds, cooling or heat pump 2 seconds.
9. Blower-off delay, gas heating 90, 135, 180 or 225 seconds, cooling or heat pump 90 seconds.
(135 seconds only on some models)
10. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset
after three hours.
11. When used, auxiliary limit switch (ALS) is on some downflow models only. When used, FL is on upflow
models only.
12. Some models may have spade quick connect terminals.
13. Factory connected when LGPS is not used.
14. Factory connected when BVSS is not used. BVSS used when Chimney Adapter Accessory Kit is
installed.
BLK
OM
SW2
SW1
OM
3
4
7
1
OM
HUM
IDM
ILK
DSS BVSS
PRS
ILK
L1
NEUTRAL
IDM
(WHEN USED)
NOTE #14
NOT USED
NOT USED
NOT USED
GRN 2-C
FSE
1-M 3-P
GV
BLU
PRS
DSS
BVSS
(WHEN USED)
NOTE #14
WHT
LS
FL
(NOT ON ALL MODELS)
NOTE #9
FRS1 FRS2
LS FL
NOTE #12
ORN ORN ORN
ALS
(WHEN USED)
ORN
NOTE #11
LGPS
(WHEN USED)
NOTE #13
NOTE #14
NOTE #11
2
GVR-1
NOTE #5
1-M 2-C
GV
3-P
NOTE #14
ALS
(WHEN USED)
(WHEN USED)
NOTE #13 LGPS
(WHEN USED)
NOTE #13
NOTE #11
YEL
FRS1 FRS2
(WHEN USED) NOTE #11
—8—
Fig. 13—Service Label
A96263
SERVICE
11 NO PREVIOUS CODE - Stored status codes are erased when power (115V or 24V)
to control is interrupted or 48 hours after each fault is cleared.
12 BLOWER ON AFTER POWER UP (115V or 24V) - Blower runs for 90 seconds,
if unit is powered up during a call for heat (R-W closed).
13 LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Auto reset after three hours.
For flame roll-out switch or fuse link, refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
21 GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Stuck gas valve relay on control or miswire to gas valve circuit.
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared. Check for:
- Stuck-open gas valve or leaky gas valve.
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure tubing. - Defective pressure switch
(stuck closed).
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for: - Short circuit in secondary voltage (24V) wiring.
31 PRESSURE, DRAFT SAFEGUARD, AUXILIARY-LIMIT (when used), OR
BLOCKED VENT SHUTOFF (when used) SWITCH DID NOT CLOSE OR
REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes
before retry. Check for:
- Proper vent sizing and condensate pitch - Inadequate Combustion air supply.
or sag. - Low inducer voltage.
- Vent restriction or high winds. - Disconnected or obstructed
- Defective inducer motor or start capacitor. pressure tubing.
- Defective pressure switch or connections. If it opens after trial for ignition period,
blower will come on for 90 second recycle delay.
33 LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If open longer than three
minutes,code changes to #13. Check for:
- Defective blower motor or start capacitor. - Dirty filter or restricted duct system.
- Loose blower wheel. - Defective switch or connections.
- Inadequate Combustion air supply Flame Roll-out Switch or fuse link.
- Open Flame Roll-out switch,or fuse link. Manual reset or replace.
34 IGNITION PROVING FAILURE - Control will try three more times before a lockout
#14 occurs. If flame signal lost after trial for ignition period, blower will
come on for 90 second recycle delay. Check for:
- Oxide buildup on flame sensor (clean with fine sandpaper).
- Proper flame sense microamps (.5 microamps D.C. minimum).
- Gas valve turned off. - Manual shut-off valve. - Low inlet gas pressure.
- Green wire MUST be connected to furnace sheet metal.
- Inadequate flame carryover or rough ignition.
COMPONENT TEST
To initiate the component test sequence,shut OFF the room thermostat or disconnect the
"R" thermostat lead. Briefly short the TEST terminal to the ’Com 24V’ terminal. Status
LED will flash code and then turn ON the inducer motor. The inducer motor will run for
the entire component test. The hot surface ignitor, blower motor-heat speed, and blower
motor-cool speed will be turned ON for 10-15 seconds each.
G
R
Y
W
Com
HUM
TEST
STATUS
320615-102 REV. H
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at
SEC-1 and SEC-2.
CONTINUOUS ON - Control has 24V power.
RAPID FLASHING - Line voltage (115V) polarity reversed. If twinned, refer to
twinning kit instructions.
LED CODE
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE
FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE
SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
1
2
3
4
5
6
7
8
9
STATUS
24V
—9—
Is circuit breaker closed?
Close door switch and go to start.Is red LED status light on? Is door switch closed?
Is red LED status light blinking
rapidly without a pause?
Is there 115v going to switch?
Replace door switch.Replace control center.
Replace transformer.
Is red LED status light blinking
ON/OFF slowly with a
combination of short and long
flashes?
Check for correct line voltage
polarity. If units are twinned,
check for proper low-voltage 
(24v) transformer phasing.
Check for previous fault by 
momentarily shorting the TEST
terminal and the C terminal until
the LED goes out. LED will flash
the status code of any previous
fault or the code No. 11 (1 short
and 1 long flash) if no previous
fault. After the control repeats the
code 3 times, the control will go
through a brief component test
sequence. The inducer will start
and run for the entire component
test. The HSI, blower motor heat
speed, and blower motor cool 
speed will run for 10-15 sec each.
Determine status code. The
status code is a 2 digit number
with the first digit determined by
the number of short flashes and
the second digit by the number of
long flashes.
Once status code is determined,
the control will go through a brief
component test sequence. The
inducer will start and run for the
entire component test. The HSI,
blower motor heat speed, and 
blower motor cool speed will run
for 10-15 sec each.
Was there a previous fault code
other than No. 11?
Does control respond to W, Y,
or G 24-vac thermostat signals?
Run system through a heating or
cooling cycle to check operation.
Status codes are erased after 48
hrs or whenever power (115v
or 24v) is interrupted.
Go to section with status code
determined.
Is there 115v at L1 and L2?
Close circuit breaker and
go back to start.
Check for continuity in wire from circuit
breaker to furnace.
NO NO NO
NO NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
NO
YES
YES
YES
START
Is there 24v at SEC-1 and SEC-2?
NO Is 24 vac present at W, Y, or G
terminals on the control?
Replace control if it does not
respond to 24-vac signal at W, Y,
or G screw terminals.
Check room thermostat or
interconnecting cable.
YES
NO
NO
TROUBLESHOOTING GUIDE
—10—
11 NO PREVIOUS FAULT - Faults
are erased after 48 hrs or
whenever power (115V or 24V)
is interrupted. Run system
through a heating or cooling
cycle to recheck system.
12 BLOWER ON AFTER POWER
UP (115V OR 24V) - Normal 
operation. Blower will run for 90
sec when furnace power is
interrupted during a call for heat
and R-W closes.
13 LIMIT OR FLAME ROLLOUT
SWITCH LOCKOUT - Limit
switch was open longer than
3 minutes. Auto-reset will occur
after 3 hrs. Flame rollout switch
requires manual reset.
See No. 33
14 IGNITION LOCKOUT - System
failed to ignite gas and prove
flame in 4 attempts. Control will
auto-reset in 3 hrs.
See No. 34
21 GAS HEATING LOCKOUT - 
Turn off power and wait 5
minutes to retry.
Check for:
Unplug ignitor harness from control
center and inititate another 
component test sequence and check
for 115v between pins 1 and 2 on
the board. Was there 115v present
for the 17 sec period?
Replace control board.
Check for continuity in the harness
and ignitor. Replace defective
component.
Reconnect the R thermostat lead
and set thermostat to call for heat.
Connect voltmeter across gas valve
connections. Does gas valve
receive 24v?
Check connections. If OK, replace
control board.
Does gas valve open and allow gas
to flow?
Check that all gas valves are turned
on. Replace valve.
Do main burners ignite?
Do main burners stay on?
Allow blower to come on and repeat
test to check for intermittent
operation.
Repeat call for heat and check flame
sensor current during trial for ignition
period. Is the dc microamperes
below 0.5?
Check connections including equipment 
ground and retry. Green wire must be
connected to furnace sheet metal. If 
current is near typical value and control 
will not stay on, replace control board.
Clean flame sensor with fine
sandpaper and recheck current. 
Current is nominally 4.0 to 6.0
microamps DC.
Is current near typical value?
Replace electrode.
Will main burner ignite and stay on?
Replace control board.
Fixed.
Stuck closed gas valve relay
on control.
Miswire or short to gas valve
wire.
22 ABNORMAL FLAME PROVING
SIGNAL - Flame was sensed
while gas valve was
de-energized. Inducer will run
until fault is cleared.
Check for:
Stuck open gas valve solenoid
or leak.
Defective control board.
23 PRESSURE SWITCH WILL
NOT OPEN - Check for:
Disconnected or obstructed
pressure tubing.
Defective pressure switch.
24 LOW-VOLTAGE FUSE IS
OPEN - Check for:
Short in low-voltage wiring
including thermostat leads
shorting to ductwork or
furnace cabinet. Disconnect
thermostat leads to isolate
short circuit.
31 PRESSURE, DRAFT 
SAFEGUARD (WHEN USED),
OR AUXILIARY LIMIT (WHEN
USED) SWITCH WILL NOT 
CLOSE OR REOPEN - If open
longer than 5 minutes, inducer 
shuts off for 15 minutes before
retry.
Check for:
Proper vent sizing or pitch or
sag.
Vent restrictions or high winds.
Defective inducer motor.
Low-line voltage (115v).
Motor start capacitor.
Low inlet gas pressure.
Defective pressure switch or
connections. If it opens after
trial for igniton period, blower
will come on for 90 sec
recycle delay.
Inadequate combustion air
(for draft safeguard and
auxiliary limit switches only).
33 LIMIT OR FLAME ROLLOUT
SWITCH IS OPEN - If limit 
switch is open longer than 3
minutes, code changes to No. 13.
Check for:
Blower motor failure.
Motor start capacitor.
Open flame rollout switch,
manual reset.
Dirty or restrictive filter.
Defective limit switch or 
connections.
Loose blower wheel.
34 IGNITION PROVING FAILURE -
If flame is not sensed during the
trial for ignition period, the control
will repeat the ignition sequence
3 more times before going into
lockout, No. 14.
If flame signal is lost after trial for
ignition period, blower will come
on for 90 sec recycle delay.
Check for the following items first
before proceding to the next step.
Gas valve turned off.
Manual shut-off valve.
Green wire must be connected
to furnace sheet metal.
To determine whether the
problem is in the gas valve,
igniter, or flame sensor, the
system can be operated in the
component test mode to check
out the ignitor. First, remove the
R thermostat connection from the
control board and initiate the
component test sequence. Does
the ignitor glow orange/white hot
by the end of the 17 sec warm-up
period?
Check for:
Inadequate flame carryover on
rough ignition.
Low inlet gas pressure.
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
Inadequate combustion air
supply (flame rollout
switch only).
Restricted duct system.
A98523
—11—
A94328
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your
knowledge of the equipment discussed in this manual, including:
 • Unit Familiarization • Maintenance
 • Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular
video-based formats and materials. All include video and/or slides, plus companion
book.
Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
© 1998 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —12— Printed in U.S.A. sp0453 Catalog No. 5337-301

Navigation menu