Bryant 580J 08 14D Users Manual 580Jp1 32

580J*08--14D sm580j-02

580J*08--14D to the manual 9d7fc823-d260-4f27-90f0-92bcbd57a057

2015-02-02

: Bryant Bryant-580J-08-14D-Users-Manual-411725 bryant-580j-08-14d-users-manual-411725 bryant pdf

Open the PDF directly: View PDF PDF.
Page Count: 85

580J*08--14D,F (2--COMPRESSOR)
NOMINAL 7.5 to 12.5 TONS
WITH PURONR(R--410A) REFRIGERANT
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1....................
UNIT ARRANGEMENT AND ACCESS 2...........
SUPPLY FAN (BLOWER) SECTION 4..............
COOLING 6....................................
PURONR(R--410A) REFRIGERANT 8..............
COOLING CHARGING CHARTS 10................
CONVENIENCE OUTLETS 16....................
SMOKE DETECTORS 17.........................
PROTECTIVE DEVICES 24.......................
GAS HEATING SYSTEM 25......................
CONDENSER COIL SERVICE 35..................
RTU--MP CONTROL SYSTEM 35..................
ECONOMI$ER SYSTEMS 50......................
WIRING DIAGRAMS 59.........................
PRE--START--UP 62..............................
START--UP, GENERAL 62........................
START--UP, RTU--MP CONTROL 64................
OPERATING SEQUENCES 67.....................
FASTENER TORQUE VALUES 71.................
APPENDIX I. MODEL NUMBER SIGNIFICANCE 72.
APPENDIX II. PHYSICAL DATA 73................
APPENDIX III. FAN PERFORMANCE 75...........
APPENDIX IV. WIRING DIAGRAM LIST 82........
APPENDIX V. MOTORMASTER SENSOR
LOCATIONS 83.................................
UNIT START-UP CHECKLIST 85..................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install, repair, or service air-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguishers available for all brazing
operations.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert
symbol . When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert
symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
2
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in
personal injury, death and/or property damage.
Refer to the Users Information Manual provided
with this unit for more details.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
DO NOT try to light any appliance.
DO NOT touch any electrical switch, or use any
phone in your building.
IMMEDIATELY call your gas supplier from a
neighbors phone. Follow the gas suppliers
instructions.
If you cannot reach your gas supplier, call the fire
department.
!WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit. Electrical
shock and rotating equipment could cause injury.
!WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
!WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
PuronR(R--410A) refrigerant systems operate at
higher pressures than standard R--22 systems. Do not
use R--22 service equipment or components on Puron
refrigerant equipment.
!WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect gas piping from unit when pressure testing
at pressure greater than 0.5 psig. Pressures greater
than 0.5 psig will cause gas valve damage resulting in
hazardous condition. If gas valve is subjected to
pressure greater than 0.5 psig, it must be replaced
before use. When pressure testing field-supplied gas
piping at pressures of 0.5 psig or less, a unit connected
to such piping must be isolated by closing the manual
gas valve(s).
!WARNING
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning units.
CAUTION
!
UNIT ARRANGEMENT AND ACCESS
General
Fig. 1 and Fig. 2 show general unit arrangement and
access locations.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
C06023
Fig. 1 -- Typical Access Panel Locations (Back)
580J
3
BLOWER
ACCESS
PANEL
CONTROL BOX
COMPRESSORS
C09239
Fig. 2 -- Typical Access Panel Location (Front)
Routine Maintenance
These items should be part of a routine maintenance
program, to be checked every month or two, until a
specific schedule for each can be identified for this
installation:
Quarterly Inspection (and 30 days after initial start)
SReturn air filter replacement
SOutdoor hood inlet filters cleaned
SBelt tension checked
SBelt condition checked
SPulley alignment checked
SFan shaft bearing locking collar tightness checked
SCondenser coil cleanliness checked
SCondensate drain checked
Seasonal Maintenance
These items should be checked at the beginning of each
season (or more often if local conditions and usage
patterns dictate):
Air Conditioning
SCondenser fan motor mounting bolts tightness
SCompressor mounting bolts
SCondenser fan blade positioning
SControl box cleanliness and wiring condition
SWire terminal tightness
SRefrigerant charge level
SEvaporator coil cleaning
SEvaporator blower motor amperage
Heating
SHeat exchanger flue passageways cleanliness
SGas burner condition
SGas manifold pressure
SHeating temperature rise
Economizer or Outside Air Damper
SInlet filters condition
SCheck damper travel (economizer)
SCheck gear and dampers for debris and dirt
Air Filters and Screens
Each unit is equipped with return air filters. If the unit has
an economizer, it will also have an outside air screen. If a
manual outside air damper is added, an inlet air screen
will also be present.
Each of these filters and screens will need to be
periodically replaced or cleaned.
Return Air Filters
Return air filters are disposable fiberglass media type.
Access to the filters is through the small lift--out panel
located on the rear side of the unit, above the
evaporator/return air access panel. (See Fig. 1.)
To remove the filters:
1. Grasp the bottom flange of the upper panel.
2. Lift up and swing the bottom out until the panel dis-
engages and pulls out.
3. Reach inside and extract the filters from the filter
rack.
4. Replace these filters as required with similar replace-
ment filters of same size.
To re--install the access panel:
1. Slide the top of the panel up under the unit top panel.
2. Slide the bottom into the side channels.
3. Push the bottom flange down until it contacts the top
of the lower panel (or economizer top).
IMPORTANT: DO NOT OPERATE THE UNIT
WITHOUT THESE FILTERS!
Outside Air Hood
Outside air hood inlet screens are permanent
aluminum--mesh type filters. Check these for cleanliness.
Remove the screens when cleaning is required. Clean by
washing with hot low--pressure water and soft detergent
and replace all screens before restarting the unit. Observe
the flow direction arrows on the side of each filter frame.
Economizer Inlet Air Screen
This air screen is retained by spring clips under the top
edge of the hood. (See Fig. 3.)
580J
4
22 3/8 (569 mm)
HOOD
DIVIDER
OUTSIDE
AIR
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF FILTER
CAP
FILTER
C08634
Fig. 3 -- Filter Installation
To remove the filter, open the spring clips. Re--install the
filter by placing the frame in its track, then closing the
spring clips.
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the
top edge of the hood. (See Fig. 4.)
C07156
Fig. 4 -- Screens Installed on Outdoor--Air Hood
(Sizes 7-1/2 to 12-1/2 Tons Shown)
To remove the screen, loosen the screws in the top retainer
and slip the retainer up until the filter can be removed.
Re-install by placing the frame in its track, rotating the
retainer back down and tighten all screws.
SUPPLY FAN (BLOWER) SECTION
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on the fan system, shut off all unit power and tag--out
the unit disconnect switch. Do not reach into the fan
section with power still applied to unit.
!WARNING
Supply Fan (Belt--Drive)
The supply fan system consists of a forward--curved
centrifugal blower wheel on a solid shaft with two
concentric type bearings, one on each side of the blower
housing. A fixed--pitch driven pulley is attached to the fan
shaft and an adjustable--pitch driver pulley is on the
motor. The pulleys are connected using a “V” type belt.
(See Fig. 5.)
C07087
Fig. 5 -- Belt Drive Motor Mounting
Belt
Check the belt condition and tension quarterly. Inspect the
belt for signs of cracking, fraying or glazing along the
inside surfaces. Check belt tension by using a spring-force
tool (such as Browning’s Part Number “Belt Tension
Checker” or equivalent tool). Tension should be 6-lbs at a
5/8-in. (16 mm) deflection when measured at the
centerline of the belt span. This point is at the center of
the belt when measuring the distance between the motor
shaft and the blower shaft.
NOTE: Without the spring--tension tool, place a straight
edge across the belt surface at the pulleys, then deflect the
belt at mid--span using one finger to a 1/2-in. (13 mm)
deflection.
Adjust belt tension by loosening the motor mounting plate
front bolts and rear bolt and sliding the plate toward the
fan (to reduce tension) or away from fan (to increase
tension). Ensure the blower shaft and the motor shaft are
parallel to each other (pulleys aligned). Tighten all bolts
when finished.
580J
5
To replace the belt:
1. Use a belt with same section type or similar size. Do
not substitute a “FHP” type belt. When installing the
new belt, do not use a tool (screwdriver or pry--bar) to
force the belt over the pulley flanges, this will stress
the belt and cause a reduction in belt life.
2. Loosen the motor mounting plate front bolts and rear
bolts.
3. Push the motor and its mounting plate towards the
blower housing as close as possible to reduce the cen-
ter distance between fan shaft and motor shaft.
4. Remove the belt by gently lifting the old belt over
one of the pulleys.
5. Install the new belt by gently sliding the belt over
both pulleys and then sliding the motor and plate
away from the fan housing until proper tension is
achieved.
6. Check the alignment of the pulleys, adjust if neces-
sary.
7. Tighten all bolts.
8. Check the tension after a few hours of runtime and
re--adjust as required.
Adjustable--Pitch Pulley on Motor
The motor pulley is an adjustable--pitch type that allows a
servicer to implement changes in the fan wheel speed to
match as--installed ductwork systems. The pulley consists
of a fixed flange side that faces the motor (secured to the
motor shaft) and a movable flange side that can be rotated
around the fixed flange side that increases or reduces the
pitch diameter of this driver pulley. (See Fig. 6.)
As the pitch diameter is changed by adjusting the position
of the movable flange, the centerline on this pulley shifts
laterally (along the motor shaft). This creates a
requirement for a realignment of the pulleys after any
adjustment of the movable flange. Also reset the belt
tension after each realignment.
Check the condition of the motor pulley for signs of wear.
Glazing of the belt contact surfaces and erosion on these
surfaces are signs of improper belt tension and/or belt
slippage. Pulley replacement may be necessary.
To change fan speed:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts.
(See Fig. 5.)
3. Loosen movable pulley flange setscrew. (See Fig. 6.)
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified.
5. Set movable flange at nearest keyway of pulley hub
and tighten setscrew to torque specifications.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft. Make angular align-
ment by loosening motor from mounting.
3. Tighten fan pulley setscrews and motor mounting
bolts to torque specifications.
4. Recheck belt tension.
C07075
Fig. 6 -- Supply--Fan Pulley Adjustment
Bearings
This fan system uses bearings featuring concentric split
locking collars. The collars are tightened through a cap
screw bridging the split portion of the collar. The cap
screw has a Torx T25 socket head. To tighten the locking
collar: Hold the locking collar tightly against the inner
race of the bearing and torque the cap screw to 65--70
in-lb (7.4--7.9 Nm). (See Fig. 7.)
C08121
Fig. 7 -- Tightening Locking Collar
Motor
When replacing the motor, also replace the external--tooth
lock washer (star washer) under the motor mounting base;
this is part of the motor grounding system. Ensure the
teeth on the lock washer are in contact with the motors
painted base. Tighten motor mounting bolts to 120 +/-- 12
in--lbs. (13.5 +/-- 1.3 Nm).
580J
6
Changing the Fan Wheel Speed by Changing Pulleys
The horsepower rating of the belt is primarily dictated by
the pitch diameter of the smaller pulley in the drive
system (typically the motor pulley in these units). Do not
install a replacement motor pulley with a smaller pitch
diameter than provided on the original factory pulley.
Change fan wheel speed by changing the fan pulley
(larger pitch diameter to reduce wheel speed, smaller
pitch diameter to increase wheel speed) or select a new
system (both pulleys and matching belt(s).)
Before changing pulleys to increase fan wheel speed,
check the fan performance at the target speed and airflow
rate to determine new motor loading (bhp). Use the fan
performance tables or use the Packaged Rooftop Builder
software program. Confirm that the motor in this unit is
capable of operating at the new operating condition. Fan
shaft loading increases dramatically as wheel speed is
increased.
To reduce vibration, replace the motor’s adjustable pitch
pulley with a fixed pitch pulley (after the final airflow
balance adjustment). This will reduce the amount of
vibration generated by the motor/belt--drive system.
COOLING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
This system uses PuronRrefrigerant which has higher
pressures than R--22 and other refrigerants. No other
refrigerant may be used in this system. Gauge set,
hoses, and recovery system must be designed to
handle Puron refrigerant. If unsure about equipment,
consult the equipment manufacturer.
!WARNING
Condenser Coil
The condenser coil is new NOVATION Heat Exchanger
Technology. This is an all--aluminum construction with
louvered fins over single--depth crosstubes. The
crosstubes have multiple small passages through which
the refrigerant passes from header to header on each end.
Tubes and fins are both aluminum construction.
Connection tube joints are copper. The coil may be
one--row or two--row. Two--row coils are spaced apart to
assist in cleaning. (See Fig. 8.)
TUBES
FINS
MANIFOLD
MICROCHANNELS
C07273
Fig. 8 -- NOVATION Heat Exchanger Coils
Evaporator Coil
The evaporator coil is traditional round--tube, plate--fin
technology. Tube and fin construction is of various
optional materials and coatings (see Model Number
Format). Coils are multiple--row.
Coil Maintenance and Cleaning Recommendation
Routine cleaning of coil surfaces is essential to maintain
proper operation of the unit. Elimination of contamination
and removal of harmful residues will greatly increase the
life of the coil and extend the life of the unit. The
following maintenance and cleaning procedures are
recommended as part of the routine maintenance activities
to extend the life of the coil.
Remove Surface Loaded Fibers
Surface loaded fibers or dirt should be removed with a
vacuum cleaner. If a vacuum cleaner is not available, a
soft non--metallic bristle brush may be used. In either
case, the tool should be applied in the direction of the fins.
Coil surfaces can be easily damaged (fin edges can be
easily bent over and damage to the coating of a protected
coil) if the tool is applied across the fins.
NOTE: Use of a water stream, such as a garden hose,
against a surface loaded coil will drive the fibers and dirt
into the coil. This will make cleaning efforts more
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.
Periodic Clean Water Rinse
A periodic clean water rinse is very beneficial for coils
that are applied in coastal or industrial environments.
However, it is very important that the water rinse is made
with very low velocity water stream to avoid damaging
the fin edges. Monthly cleaning as described below is
recommended.
580J
7
Routine Cleaning of NOVATION Condenser Coil
Surfaces
To clean the NOVATION condenser coil, chemicals are
NOT to be used; only water is approved as the cleaning
solution. Only clean potable water is authorized for
cleaning NOVATION condensers. Carefully remove any
foreign objects or debris attached to the coil face or
trapped within the mounting frame and brackets. Using a
high pressure water sprayer, purge any soap or industrial
cleaners from hose and/or dilution tank prior to wetting
the coil.
Clean condenser face by spraying the coil core steadily
and uniformly from top to bottom, directing the spray
straight into or toward the coil face. Do not exceed 900
psig or a 45 degree angle; nozzle must be at least 12 in.
(30 cm) from the coil face. Reduce pressure and use
caution to prevent damage to air centers (fins). Do not
fracture the braze between air centers and refrigerant
tubes. Allow water to drain from the coil core and check
for refrigerant leaks prior to start--up.
NOTE: Please see the NOVATION Condenser Service
section for specific information on the coil.
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal
injury or equipment damage.
Chemical cleaning should NOT be used on the
aluminum NOVATION condenser. Damage to the coil
may occur. Only approved cleaning is recommended.
CAUTION
!
Routine Cleaning of Evaporator Coil Surfaces
Monthly cleaning with Totaline®environmentally sound
coil cleaner is essential to extend the life of coils. This
cleaner is available from Bryant Replacement parts
division as part number P902--0301 for one gallon
container, and part number P902--0305 for a 5 gallon
container. It is recommended that all round tube coil
cleaner as described below. Coil cleaning should be part
of the unit’s regularly scheduled maintenance procedures
to ensure long life of the coil. Failure to clean the coils
may result in reduced durability in the environment.
Avoid the use of
Scoil brighteners
Sacid cleaning prior to painting
Shigh pressure washers
Spoor quality water for cleaning
Totaline environmentally sound coil cleaner is
non--flammable, hypoallergenic, non--bacterial, and a
USDA accepted biodegradable agent that will not harm
coil or surrounding components such as electrical wiring,
painted metal surfaces, or insulation. Use of
non--recommended coil cleaners is strongly discouraged
since coil and unit durability could be affected.
Totaline Environmentally Sound Coil Cleaner Application
Equipment
S2-1/2 gallon garden sprayer
Swater rinse with low velocity spray nozzle
PERSONAL INJURY HAZARD
Failure to follow this caution may result in corrosion
and damage to the unit.
Harsh chemicals, household bleach or acid or basic
cleaners should not be used to clean outdoor or indoor
coils of any kind. These cleaners can be very difficult
to rinse out of the coil and can accelerate corrosion at
the fin/tube interface where dissimilar materials are in
contact. If there is dirt below the surface of the coil,
use the Totaline environmentally sound coil cleaner as
described above.
CAUTION
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in reduced
unit performance.
High velocity water from a pressure washer, garden
hose, or compressed air should never be used to clean
a coil. The force of the water or air jet will bend the
fin edges and increase airside pressure drop.
CAUTION
!
Totaline Environmentally Sound Coil Cleaner application
Instructions
1. Proper eye protection such as safety glasses is recom-
mended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacu-
um cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and
a low velocity garden hose, being careful not to bend
fins.
4. Mix Totaline environmentally sound coil cleaner in a
2 1/2 gallon garden spryer according to the instruc-
tions included with the cleaner. The optimum solution
temperature is 100°F(38°C).
NOTE: Do NOT USE water in excess of 130°F(54°C),
as the enzymatic activity will be destroyed.
5. Thoroughly apply Totaline®environmentally sound
coil cleaner solution to all coil surfaces including
finned area, tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up--and--down motion.
Avoid spraying in horizontal pattern to minimize po-
tential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned
areas.
8. Interior and exterior finned areas must be thoroughly
cleaned.
580J
8
9. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10--minute satur-
ation is achieved.
11. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
Evaporator Coil Metering Devices
The metering devices are multiple fixed--bore devices
(Acutrolt) swaged into the horizontal outlet tubes from
the liquid header, located at the entrance to each
evaporator coil circuit path. These are non--adjustable.
Service requires replacing the entire liquid header
assembly.
To check for possible blockage of one or more of these
metering devices, disconnect the supply fan contactor
(IFC) coil, then start the compressor and observe the
frosting pattern on the face of the evaporator coil. A frost
pattern should develop uniformly across the face of the
coil starting at each horizontal liquid tube. Failure to
develop frost at an outlet tube can indicate a plugged or a
missing orifice.
Refrigerant System Pressure Access Ports
There are two access ports in each compressor--circuit
system -- on the suction tube near the compressor and on
the discharge tube near the compressor. These are brass
fittings with black plastic caps. The hose connection
fittings are standard 1/4 SAE male flare couplings.
The brass fittings are two--piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring-closed check valve core screwed into the base. (See
Fig. 9.) This check valve is permanently assembled into
the core body and cannot be serviced separately. Replace
the entire core body if necessary. Service tools are
available from RCD that allow the replacement of the
check valve core without having to recover the entire
system refrigerant charge. Apply compressor refrigerant
oil to the check valve cores bottom O-ring. Install the
fitting body with 96 +/-- 10 in-lbs (Nm) of torque; do not
overtighten.
PURONR(R--410A) REFRIGERANT
This unit is designed for use with Puron (R--410A)
refrigerant. Do not use any other refrigerant in this
system.
Puron (R--410A) refrigerant is provided in pink (rose)
colored cylinders. These cylinders are available with and
without dip tubes; cylinders with dip tubes will have a
label indicating this feature. For a cylinder with a dip
tube, place the cylinder in the upright position (access
valve at the top) when removing liquid refrigerant for
charging. For a cylinder without a dip tube, invert the
cylinder (access valve on the bottom) when removing
liquid refrigerant.
Because Puron (R--410A) refrigerant is a blend, it is
strongly recommended that refrigerant always be removed
from the cylinder as a liquid. Admit liquid refrigerant into
the system in the discharge line. If adding refrigerant into
the suction line, use a commercial metering/expansion
device at the gauge manifold; remove liquid from the
cylinder, pass it through the metering device at the gauge
set and then pass it into the suction line as a vapor. Do not
remove Puron (R--410A) refrigerant from the cylinder as a
vapor.
Refrigerant Charge
Amount of refrigerant charge is listed on the unit’s
nameplate. Refer to GTAC2--5 Charging, Recovery,
Recycling and Reclamation training manual and the
following procedures.
Unit panels must be in place when unit is operating during
the charging procedure. To prepare the unit for charge
adjustment.
No Charge
Use standard evacuating techniques. After evacuating
system, weigh in the specified amount of refrigerant.
Low--Charge Cooling
Using Cooling Charging Charts (Fig. 10, 11, 12, and 13),
vary refrigerant until the conditions of the appropriate
chart are met. Note the charging charts are different from
the type normally used. Charts are based on charging the
units to the correct superheat for the various operating
conditions. Accurate pressure gauge and temperature
sensing device are required. Connect the pressure gauge to
the service port on the suction line. Mount the temperature
sensing device on the suction line and insulate it so that
outdoor ambient temperature does not affect the reading.
Indoor--air cfm must be within the normal operating range
of the unit.
To Use Cooling Charging Charts
Select the appropriate unit charging chart from Fig. 10,
11, 12, and 13.
SSizes 08D,F and 12D,F each have one cooling charging
chart
SSize 14D,F has two cooling charging charts: Circuit A
and Circuit B
Take the outdoor ambient temperature and read the
suction pressure gauge. Refer to chart to determine what
suction temperature should be. If suction temperature is
high, add refrigerant. If suction temperature is low,
carefully recover some of the charge. Recheck the suction
pressure as charge is adjusted.
For 14D,F size, perform this procedure once for Circuit A
(using the Circuit A chart) and once for Circuit B (using
the Circuit B chart).
580J
9
1/2-20 UNF RH
30
0.596
.47
5/8” HEX
SEAT CORE
WASHER DEPRESSOR PER ARI 720
+.01/-.035
FROM FACE OF BODY
7/16-20 UNF RH
O-RING
45
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
1/2" HEX
This surface provides a metal to metal seal when
o
o
(Part No. EC39EZ067)
C08453
Fig. 9 -- CoreMax Access Port Assembly
EXAMPLE:
Model 580J*14D
Circuit 1:
Outdoor Temperature 85_F(29_C)..................
Suction Pressure 125 psig (860 kPa).................
Suction Temperature should be 58_F(14_C)..........
Circuit 2:
Outdoor Temperature 85_F(29_C)..................
Suction Pressure 120 psig (830 kPa).................
Suction Temperature should be 60_F(16_C)..........
580J
10
COOLING CHARGING CHARTS
C09221
Fig. 10 -- Cooling Charging Charts (08D,F -- Both Circuits)
580J
11
COOLING CHARGING CHARTS
C09222
Fig. 11 -- Cooling Charging Charts (12D,F -- Both Circuits)
580J
12
COOLING CHARGING CHARTS
12.5 TON CIRCUIT 1
C09240
Fig. 12 -- Cooling Charging Charts (14D,F -- Circuit 1)
580J
13
COOLING CHARGING CHARTS
12.5 TON CIRCUIT 2
C09241
Fig. 13 -- Cooling Charging Charts (14D,F -- Circuit 2)
580J
14
Table 1 – Cooling Service Analysis
PROBLEM CAUSE REMEDY
Compressor and Condenser
Fan Will Not Start.
Power failure. Call power company.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay. Replace component.
Insufficient line voltage. Determine cause and correct.
Incorrect or faulty wiring. Check wiring diagram and rewire correctly.
Thermostat setting too high. Lower thermostat setting below room temperature.
Compressor Will Not Start But
Condenser Fan Runs.
Faulty wiring or loose connections in
compressor circuit. Check wiring and repair or replace.
Compressor motor burned out, seized, or
internal overload open. Determine cause. Replace compressor.
Defective run/start capacitor, overload, start
relay. Determine cause and replace.
Onelegofthree---phasepowerdead. Replace fuse or reset circuit breaker. Determine
cause.
Compressor Cycles (other
than normally satisfying
thermostat).
Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge
to nameplate.
Defective compressor. Replace and determine cause.
Insufficient line voltage. Determine cause and correct.
Blocked condenser. Determine cause and correct.
Defective run/start capacitor, overload, or start
relay. Determine cause and replace.
Defective thermostat. Replace thermostat.
Faulty condenser---fan motor or capacitor. Replace.
Restriction in refrigerant system. Locate restriction and remove.
Compressor Operates
Continuously.
Dirty air filter. Replace filter.
Unit undersized for load. Decrease load or increase unit size.
Thermostat set too low. Reset thermostat.
Low refrigerant charge. Locate leak; repair and recharge.
Leaking valves in compressor. Replace compressor.
Air in system. Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted. Clean coil or remove restriction.
Excessive Head Pressure.
Dirty air filter. Replace filter.
Dirty condenser coil. Clean coil.
Refrigerant overcharged. Recover excess refrigerant.
Air in system. Recover refrigerant, evacuate system, and recharge.
Condenser air restricted or air short---cycling. Determine cause and correct.
Head Pressure Too Low.
Low refrigerant charge. Check for leaks; repair and recharge.
Compressor valves leaking. Replace compressor.
Restrictioninliquidtube. Remove restriction.
Excessive Suction Pressure.
High head load. Check for source and eliminate.
Compressor valves leaking. Replace compressor.
Refrigerant overcharged. Recover excess refrigerant.
Suction Pressure Too Low.
Dirty air filter. Replace filter.
Low refrigerant charge. Check for leaks; repair and recharge.
Metering device or low side restricted. Remove source of restriction.
Insufficient evaporator airflow. Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area. Reset thermostat.
Outdoor ambient below 25° F. Install low---ambient kit.
Evaporator Fan Will Not Shut
Off. Time off delay not finished. W a i t f o r 3 0 --- s e c o n d o f f d e l a y.
Compressor Makes Excessive
Noise. Compressor rotating in wrong direction. Reversethe3---phasepowerleads.
580J
15
Compressors
Lubrication
Compressors are charged with the correct amount of oil at
the factory.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to
components.
The compressor is in a PuronRrefrigerant system and
uses a polyolester (POE) oil. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE
oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Avoid
exposure of the oil to the atmosphere.
CAUTION
!
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
!WARNING
Replacing Compressor
The compressor used with Puron refrigerant contains a
POE oil. This oil has a high affinity for moisture. Do not
remove the compressors tube plugs until ready to insert
the unit suction and discharge tube ends.
Compressor mounting bolt torque is 65--75 in-lbs
(7.3--8.5 N-m).
Compressor Rotation
1. Connect service gauges to suction and discharge pres-
sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start--up.
NOTE: If the suction pressure does not drop and the
discharge pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating
in the wrong direction.
2. Turn off power to the unit.
3. Reverse any two of the unit power leads.
4. Reapply power to the compressor.
The suction and discharge pressure levels should now
move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong
direction, the unit makes an elevated level of noise and
does not provide cooling.
Filter Drier
Replace whenever refrigerant system is exposed to
atmosphere. Only use factory specified liquid--line filter
driers with working pressures no less than 650 psig. Do
not install a suction--line filter drier in liquid line. A
liquid--line filter drier designed for use with Puron
refrigerant is required on every unit.
Condenser--Fan Adjustment (08D--12D,F size)
1. Shut off unit power supply. Install lockout tag.
2. Remove condenser-fan assembly (grille, motor, and
fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 14.
5. Tighten setscrews to 84 in-lbs (9.5 N-m).
6. Replace condenser-fan assembly.
CONDUIT
0.14 in +0.0/-0.03
C08448
Fig. 14 -- Condenser Fan Adjustment (08D--12D,F)
Condenser--Fan Adjustment (14D,F size)
1. Shut off unit power supply. Install lockout tag.
2. Remove condenser fan grille.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 15.
5. Tighten setscrews to 84 in-lbs (9.5 N-m).
6. Replace fan grille.
C09094
Fig. 15 -- Condenser Fan Adjustment (14D,F)
Troubleshooting Cooling System
Refer to Table 1 for additional troubleshooting topics.
580J
16
CONVENIENCE OUTLETS
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
!WARNING
Two types of convenience outlets are offered on 580J
models: Non--powered and unit--powered. Both types
provide a 125-volt GFCI (ground--fault circuit--interrupter)
duplex receptacle rated at 15-A behind a hinged
waterproof access cover, located on the end panel of the
unit. (See Fig. 16.)
Pwd-CO Transformer
Conv Outlet
GFCI
Pwd-CO
Fuse
Switch
C08128
Fig. 16 -- Convenience Outlet Location
Installing Weatherproof Cover
A weatherproof while--in--use cover for the
factory--installed convenience outlets is now required by
UL standards. This cover cannot be factory--mounted due
to its depth. It must be installed at unit installation. For
shipment, the convenience outlet is covered with a blank
cover plate.
The weatherproof cover kit is shipped in the units control
box. The kit includes the hinged cover, a backing plate
and gasket.
IMPORTANT: Disconnect all power to unit and
convenience outlet.
1. Remove the blank cover plate at the convenience out-
let; discard the blank cover.
2. Loosen the two screws at the GFCI duplex outlet, un-
til approximately 1/2--in (13 mm) under screw heads
are exposed.
3. Press the gasket over the screw heads. Slip the back-
ing plate over the screw heads at the keyhole slots
and align with the gasket. Tighten the two screws un-
til snug (do not over--tighten).
4. Mount the weatherproof cover to the backing plate as
shown in Fig. 17.
COVER - WHILE-IN-USE
WEATHERPROOF
BASE PLATE FOR
GFCI RECEPTACLE
C09244
Fig. 17 -- Weatherproof Cover Installation
5. Remove two slot fillers in the bottom of the cover to
permit service tool cords to exit the cover. Check for
full closing and latching.
Non--Powered Type
This type requires the field installation of a
general--purpose 125--volt 15--A circuit powered from a
source elsewhere in the building. Observe national and
local codes when selecting wire size, fuse or breaker
requirements and disconnect switch size and location.
Route 125--v power supply conductors into the bottom of
the utility box containing the duplex receptacle.
Unit--Powered Type
A unit--mounted transformer is factory--installed to
stepdown the main power supply voltage to the unit to
115--v at the duplex receptacle. This option also includes a
manual switch with fuse, located in a utility box and
mounted on a bracket behind the convenience outlet;
access is through the unit’s control box access panel. (See
Fig. 16.)
The primary leads to the convenience outlet transformer
are not factory--connected. Selection of primary power
source is a customer--option. If local codes permit, the
transformer primary leads can be connected at the
line--side terminals on a unit--mounted non--fused
disconnect or circuit--breaker switch; this will provide
service power to the unit when the unit disconnect switch
or circuit--breaker is open. Other connection methods will
result in the convenience outlet circuit being de--energized
when the unit disconnect or circuit--breaker is open. (See
Fig. 18.)
580J
17
C08283
UNIT
VOLTAGE
CONNECT
AS
PRIMARY
CONNECTIONS
TRANSFORMER
TERMINALS
208,
230 240 L1: RED +YEL
L2: BLU + GRA
H1 + H3
H2 + H4
460 480
L1: RED
Splice BLU + YEL
L2: GRA
H1
H2 + H3
H4
575 600 L1: RED
L2: GRA
H1
H2
Fig. 18 -- Powered Convenience Outlet Wiring
Duty Cycle
The unit--powered convenience outlet has a duty cycle
limitation. The transformer is intended to provide power
on an intermittent basis for service tools, lamps, etc; it is
not intended to provide 15--amps loading for continuous
duty loads (such as electric heaters for overnight use).
Observe a 50% limit on circuit loading above 8--amps
(i.e., limit loads exceeding 8--amps to 30 minutes of
operation every hour).
Maintenance
Periodically test the GFCI receptacle by pressing the
TEST button on the face of the receptacle. This should
cause the internal circuit of the receptacle to trip and open
the receptacle. Check for proper grounding wires and
power line phasing if the GFCI receptacle does not trip as
required. Press the RESET button to clear the tripped
condition.
Fuse On Powered Type
The factory fuse is a Bussman “Fusetron” T--15,
non--renewable screw--in (Edison base) type plug fuse.
Using Unit--Mounted Convenience Outlets
Units with unit--mounted convenience outlet circuits will
often require that two disconnects be opened to
de--energize all power to the unit. Treat all units as
electrically energized until the convenience outlet power
is also checked and de--energization is confirmed. Observe
National Electrical Code Article 210, Branch Circuits, for
use of convenience outlets.
SMOKE DETECTORS
Smoke detectors are available as factory--installed options
on 580J models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Return
Air. Return Air smoke detectors are arranged for vertical
return configurations only. All components necessary for
operation are factory--provided and mounted. The unit is
factory--configured for immediate smoke detector
shutdown operation; additional wiring or modifications to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
System
The smoke detector system consists of a four--wire
controller and one or two sensors. Its primary function is
to shut down the rooftop unit in order to prevent smoke
from circulating throughout the building. It is not to be
used as a life saving device.
Controller
The controller includes a controller housing, a printed
circuit board, and a clear plastic cover. (See Fig. 19.) The
controller can be connected to one or two compatible duct
smoke sensors. The clear plastic cover is secured to the
housing with a single captive screw for easy access to the
wiring terminals. The controller has three LEDs (for
Power, Trouble and Alarm) and a manual test/reset button
(on the cover face).
580J
18
Duct smoke sensor
controller
Fastener
(2X)
Controller cover
Conduit nuts
(supplied by installer)
Conduit support plate
Cover gasket
(ordering option)
Conduit couplings
(supplied by installer)
Terminal block cover
Controller housing
and electronics
Alarm Power
Tes t/ re se t
switch
Trouble
C08208
Fig. 19 -- Controller Assembly
Sensor
The sensor includes a plastic housing, a printed circuit
board, a clear plastic cover, a sampling tube inlet and an
exhaust tube. (See Fig. 20.) The sampling tube (when
used) and exhaust tube are attached during installation.
The sampling tube varies in length depending on the size
of the rooftop unit. The clear plastic cover permits visual
inspections without having to disassemble the sensor. The
cover attaches to the sensor housing using four captive
screws and forms an airtight chamber around the sensing
electronics. Each sensor includes a harness with an RJ45
terminal for connecting to the controller. Each sensor has
four LEDs (Power, Trouble, Alarm and Dirty) and a
manual test/reset button (on the left--side of the housing).
Air is introduced to the duct smoke detector sensors
sensing chamber through a sampling tube that extends into
the HVAC duct and is directed back into the ventilation
system through a (shorter) exhaust tube. The difference in
air pressure between the two tubes pulls the sampled air
through the sensing chamber. When a sufficient amount of
smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically
takes the appropriate action to shut down fans and
blowers, change over air handling systems, notify the fire
alarm control panel, etc.
The sensor uses a process called differential sensing to
prevent gradual environmental changes from triggering
false alarms. A rapid change in environmental conditions,
such as smoke from a fire, causes the sensor to signal an
alarm state but dust and debris accumulated over time
does not.
Duct smoke sensor
See
Detail A
Exhaust tube
Plug
Sampling tube
(ordered separately)
Intake
gasket Cover gasket
(ordering option)
TSD-CO2
(ordering option)
Sensor housing
and electronics
Exhaust gasket
Coupling
Sensor cover
Detail A
Magnetic
test/reset
switch
Alarm
Trouble
Power
Dirty
C08209
Fig. 20 -- Smoke Detector Sensor
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
Smoke Detector Locations
Supply Air
The Supply Air smoke detector sensor is located to the
left of the unit’s indoor (supply) fan. (See Fig. 21.) Access
is through the fan access panel. There is no sampling tube
used at this location. The sampling tube inlet extends
through the side plate of the fan housing (into a high
pressure area). The controller is located on a bracket to
the right of the return filter, accessed through the lift--off
filter panel.
Smoke Detector Sensor
C08245
Fig. 21 -- Typical Supply Air Smoke Detector
Sensor Location
580J
19
Return Air Without Economizer
The sampling tube is located across the return air opening
on the unit basepan. (See Fig. 22.) The holes in the
sampling tube face downward, into the return air stream.
The sampling tube is connected via tubing to the return air
sensor that is mounted on a bracket high on the partition
between return filter and controller location. (This sensor
is shipped in a flat--mounting location. Installation
requires that this sensor be relocated to its operating
location and the tubing to the sampling tube be connected.
See installation steps.)
Return Air Detector Sampling Tube
Controller module
Return Air Detector module
(shipping position shown)*
*RA detector must be moved from shipping position to operating position by installer
C07307
Fig. 22 -- Typical Return Air Detector Location
Return Air With Economizer
The sampling tube is inserted through the side plates of
the economizer housing, placing it across the return air
opening on the unit basepan. (See Fig. 23.) The holes in
the sampling tube face downward, into the return air
stream. The sampling tube is connected via tubing to the
return air sensor that is mounted on a bracket high on the
partition between return filter and controller location.
(This sensor is shipped in a flat--mounting location.
Installation requires that this sensor be relocated to its
operating location and the tubing to the sampling tube be
connected. See installation steps.)
Return Air
Sampling Tube
C08129
Fig. 23 -- Return Air Sampling Tube Location
Completing Installation of Return Air Smoke
Sensor
1. Unscrew the two screws holding the Return Air
Sensor detector plate. (See Fig. 24.) Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-
wards and the sampling tube connection is on the bot-
tom. (See Fig. 25.)
SCREWS
EXHAUST
TUBE
FLEXIBLE
EXTENSION
TUBE
SAMPLING
C08126
Fig. 24 -- Return Air Detector Shipping Position
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bottom and the ex-
haust tube is on the top. (See Fig. 24.)
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
6. For units with an economizer, the sampling tube is in-
tegrated into the economizer housing but the connec-
tion of the flexible tubing to the sampling tube is the
same.
C08127
Fig. 25 -- Return Air Sensor Operating Position
FIOP Smoke Detector Wiring and Response
All Units
FIOP smoke detector is configured to automatically shut
down all unit operations when smoke condition is
detected. See Fig. 26, Smoke Detector Wiring.
Highlight A
JMP 3 is factory--cut, transferring unit control to smoke
detector.
580J
20
A
E
F
C
D
B
C08246
Fig. 26 -- Typical Smoke Detector System Wiring
Highlight B
Smoke detector NC contact set will open on smoke alarm
condition, de--energizing the ORN conductor.
Highlight C
24--v power signal via ORN lead is removed at Smoke
Detector input on LCTB; all unit operations cease
immediately.
RTU--MP Controls
Unit operating functions (fan, cooling and heating) are
terminated as described above. In addition:
Highlight D
On smoke alarm condition, the smoke detector NO Alarm
contact will close, supplying 24--v power to GRA
conductor.
Highlight E
GRA lead at Smoke Alarm input on LCTB provides 24--v
signal to FIOP DDC control.
RTU--MP
The 24--v signal is conveyed to RTU--MP’s J1--10 input
terminal. This signal initiates the FSD sequence by the
RTU--MP control. FSD status is reported to connected
BAS network.
Using Remote Logic
Five conductors are provided for field use (see Highlight
F) for additional annunciation functions.
Additional Application Data — Refer to Catalog No.
HKRNKA--1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordination. (See Fig. 26.)
Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensors ability to signal an
alarm state. This test requires that you use a field provided
SD--MAG test magnet.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system, notify the proper authorities before
performing the test.
CAUTION
!
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for seven seconds.
2. Verify that the sensors Alarm LED turns on.
3. Reset the sensor by holding the test magnet against
the sensor housing for two seconds.
4. Verify that the sensors Alarm LED turns off.
580J
21
Controller Alarm Test
The controller alarm test checks the controllers ability to
initiate and indicate an alarm state.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
This test places the duct detector into the alarm state.
Disconnect all auxiliary equipment from the controller
before performing the test. If the duct detector is
connected to a fire alarm system, notify the proper
authorities before performing the test.
CAUTION
!
Controller Alarm Test Procedure
1. Press the controllers test/reset switch for seven
seconds.
2. Verify that the controller’s Alarm LED turns on.
3. Reset the sensor by pressing the test/reset switch for
two seconds.
4. Verify that the controller’s Alarm LED turns off.
Dirty Controller Test
The dirty controller test checks the controllers ability to
initiate a dirty sensor test and indicate its results.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
Pressing the controllers test/reset switch for longer
than seven seconds will put the duct detector into the
alarm state and activate all automatic alarm responses.
CAUTION
!
Dirty Controller Test Procedure
SPress the controllers test/reset switch for two seconds.
SVerify that the controllers Trouble LED flashes.
Dirty Sensor Test
The dirty sensor test provides an indication of the sensors
ability to compensate for gradual environmental changes.
A sensor that can no longer compensate for environmental
changes is considered 100% dirty and requires cleaning or
replacing. You must use a field provided SD--MAG test
magnet to initiate a sensor dirty test. The sensor’s Dirty
LED indicates the results of the dirty test as shown in
Table 2.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
Holding the test magnet against the sensor housing for
more than seven seconds will put the duct detector
into the alarm state and activate all automatic alarm
responses.
CAUTION
!
Tabl e 2 – Dirty LED Test
FLASHES DESCRIPTION
10--- 25% dirty. (Typical of a newly installed detector)
225--- 50% dirty
351--- 75% dirty
476--- 99% dirty
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for two seconds.
2. Verify that the sensors Dirty LED flashes.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
Changing the dirty sensor test operation will put the
detector into the alarm state and activate all automatic
alarm responses. Before changing dirty sensor test
operation, disconnect all auxiliary equipment from the
controller and notify the proper authorities if
connected to a fire alarm system.
CAUTION
!
Changing the Dirty Sensor Test
By default, sensor dirty test results are indicated by:
SThe sensors Dirty LED flashing.
SThe controllers Trouble LED flashing.
SThe controllers supervision relay contacts toggle.
The operation of a sensors dirty test can be changed so
that the controllers supervision relay is not used to
indicate test results. When two detectors are connected to
a controller, sensor dirty test operation on both sensors
must be configured to operate in the same manner.
To Configure the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of
the sensor housing until the sensors Alarm LED turns
on and its Dirty LED flashes twice (approximately 60
seconds).
2. Reset the sensor by removing the test magnet then
holding it against the sensor housing again until the
sensors Alarm LED turns off (approximately 2
seconds).
Remote Station Test
The remote station alarm test checks a test/reset station’s
ability to initiate and indicate an alarm state.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system, notify the proper authorities before
performing the test.
CAUTION
!
580J
22
SD--TRK4 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns
on.
3. Reset the sensor by turning the key switch to the
RESET/TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns
off.
Remote Test/Reset Station Dirty Sensor Test
The test/reset station dirty sensor test checks the test/reset
stations ability to initiate a sensor dirty test and indicate
the results. It must be wired to the controller as shown in
Fig. 27 and configured to operate the controllers
supervision relay. For more information, see “Changing
the Dirty Sensor Test.”
1
12
14
13
19
15
2
20
3
Reset/Test
Trouble
Power
Alarm
Supervision relay
contacts [3]
5
4
1
3
2
SD-TRK4
2
1
TB3
18 Vdc ( )
+
18 Vdc ( )
Auxiliary
equipment
+
Wire must be
added by installer
Smoke Detector Controller
C08247
Fig. 27 -- Remote Test/Reset Station Connections
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
If the test/reset station’s key switch is left in the
RESET/TEST position for longer than seven seconds,
the detector will automatically go into the alarm state
and activate all automatic alarm responses.
CAUTION
!
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
Holding the test magnet to the target area for longer
than seven seconds will put the detector into the alarm
state and activate all automatic alarm responses.
CAUTION
!
Dirty Sensor Test Using an SD--TRK4
1. Turn the key switch to the RESET/TEST position for
two seconds.
2. Verify that the test/reset station’s Trouble LED
flashes.
Detector Cleaning
Cleaning the Smoke Detector
Clean the duct smoke sensor when the Dirty LED is
flashing continuously or sooner if conditions warrant.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
If the smoke detector is connected to a fire alarm
system, first notify the proper authorities that the
detector is undergoing maintenance then disable the
relevant circuit to avoid generating a false alarm.
CAUTION
!
1. Disconnect power from the duct detector then remove
the sensors cover. (See Fig. 28.)
Airow
HVAC duct
Sampling
tube
Retainer
clip
Optic
plate
Optic
housing
Sensor
housing
C07305
Fig. 28 -- Sensor Cleaning Diagram
2. Using a vacuum cleaner, clean compressed air, or a
soft bristle brush, remove loose dirt and debris from
inside the sensor housing and cover.
Use isopropyl alcohol and a lint--free cloth to remove
dirt and other contaminants from the gasket on the
sensors cover.
3. Squeeze the retainer clips on both sides of the optic
housing then lift the housing away from the printed
circuit board.
4. Gently remove dirt and debris from around the optic
plate and inside the optic housing.
5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a
sensor alarm test.
580J
23
INDICATORS
Normal State
The smoke detector operates in the normal state in the
absence of any trouble conditions and when its sensing
chamber is free of smoke. In the normal state, the Power
LED on both the sensor and the controller are on and all
other LEDs are off.
Alarm State
The smoke detector enters the alarm state when the
amount of smoke particulate in the sensors sensing
chamber exceeds the alarm threshold value. (See Table 3.)
Upon entering the alarm state:
SThe sensors Alarm LED and the controllers Alarm LED
turn on.
SThe contacts on the controllers two auxiliary relays
switch positions.
SThe contacts on the controllers alarm initiation relay
close.
SThe controllers remote alarm LED output is activated
(turned on).
SThe controllers high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
The SuperDuct duct smoke detector enters the trouble
state under the following conditions:
SA sensors cover is removed and 20 minutes pass before
it is properly secured.
SA sensors environmental compensation limit is reached
(100% dirty).
SA wiring fault between a sensor and the controller is
detected.
An internal sensor fault is detected upon entering the
trouble state:
SThe contacts on the controllers supervisory relay switch
positions. (See Fig. 29.)
SIf a sensor trouble, the sensors Trouble LED the
controllers Trouble LED turn on.
SIf 100% dirty, the sensors Dirty LED turns on and the
controllers Trouble LED flashes continuously.
SIf a wiring fault between a sensor and the controller, the
controllers Trouble LED turns on but not the sensors.
Alarm Power
Test/reset
switch
Trouble
C07298
Fig. 29 -- Controller Assembly
NOTE: All troubles are latched by the duct smoke
detector. The trouble condition must be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
Resetting Alarm and Trouble Condition Trips
Manual reset is required to restore smoke detector systems
to Normal operation. For installations using two sensors,
the duct smoke detector does not differentiate which
sensor signals an alarm or trouble condition. Check each
sensor for Alarm or Trouble status (indicated by LED).
Clear the condition that has generated the trip at this
sensor. Then reset the sensor by pressing and holding the
reset button (on the side) for 2 seconds. Verify that the
sensors Alarm and Trouble LEDs are now off. At the
controller, clear its Alarm or Trouble state by pressing and
holding the manual reset button (on the front cover) for 2
seconds. Verify that the controllers Alarm and Trouble
LEDs are now off. Replace all panels.
Troubleshooting
Controllers Trouble LED is On
1. Check the Trouble LED on each sensor connected to
the controller. If a sensors Trouble LED is on, de-
termine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.
Controllers Trouble LED is Flashing
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean
that sensor assembly as described in the detector
cleaning section.
Sensors Trouble LED is On
1. Check the sensor’s Dirty LED. If it is flashing, the
sensor is dirty and must be cleaned.
2. Check the sensors cover. If it is loose or missing, se-
cure the cover to the sensor housing.
3. Replace sensor assembly.
Sensors Power LED is Off
1. Check the controllers Power LED. If it is off, de-
termine why the controller does not have power and
make the necessary repairs.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.
580J
24
Table 3 – Detector Indicators
CONTROL OR INDICATOR DESCRIPTION
Magnetic test/reset switch Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in
the normal state.
Alarm LED Indicates the sensor is in the alarm state.
Trouble LED Indicates the sensor is in the trouble state.
Dirty LED Indicates the amount of environmental compensation used by the sensor
(flashing continuously = 100%)
Power LED Indicates the sensor is energized.
Controller’s Power LED is Off
1. Make sure the circuit supplying power to the control-
ler is operational. If not, make sure JP2 and JP3 are
set correctly on the controller before applying power.
2. Verify that power is applied to the controllers supply
input terminals. If power is not present, replace or re-
pair wiring as required.
Remote Test/Reset Station’s Trouble LED Does Not
Flash When Performing a Dirty Test, but the
Controllers Trouble LED Does
1. Verify that the remote test/station is wired as shown
in Fig. 27. Repair or replace loose or missing wiring.
2. Configure the sensor dirty test to activate the control-
lers supervision relay. See “Changing Sensor Dirty
Test Operation.
Sensors Trouble LED is On, But the Controllers
Trouble LED is OFF
Remove JP1 on the controller.
PROTECTIVE DEVICES
Compressor Protection
Overcurrent
Each compressor has internal linebreak motor protection.
Reset is automatic after compressor motor has cooled.
Overtemperature
Each compressor has an internal protector to protect it
against excessively high discharge gas temperatures. Reset
is automatic.
High Pressure Switch
Each system is provided with a high pressure switch
mounted on the discharge line. The switch is
stem--mounted and brazed into the discharge tube. Trip
setting is 630 psig +/-- 10 psig (4344 +/-- 69 kPa) when
hot. Reset is automatic at 505 psig (3482 kPa).
Low Pressure Switch
Each system is protected against a loss of charge and low
evaporator coil loading condition by a low pressure switch
located on the suction line near the compressor. The
switch is stem--mounted. Trip setting is 54 psig +/-- 5 psig
(372 +/-- 34 kPa). Reset is automatic at 117 +/-- 5 psig
(807 +/-- 34 kPa).
Supply (Indoor) Fan Motor Protection
Disconnect and lockout power when servicing fan motor.
The supply fan motor is equipped with an overcurrent
protection device. The type of device depends on the
motor size. (See Table 4.)
Table 4 – Supply Fan Motor Protection Devices
Motor Size
(bhp) Overload Device Reset
1.7 Internal Linebreak Automatic
2.4 Internal Linebreak Automatic
2.9 Thermik Automatic
3.7 Thermik Automatic
5.2 External
(Circuit Breaker) Manual
The Internal Linebreak type is an imbedded switch that
senses both motor current and internal motor temperature.
When this switch reaches its trip setpoint, the switch
opens the power supply to the motor and the motor stops.
Reset is automatic when the motor windings cool down.
The Thermik device is a snap--action overtemperature
protection device that is imbedded in the motor windings.
It is a pilot--circuit device that is wired into the unit’s 24--v
control circuit. When this switch reaches its trip setpoint,
it opens the 24--v control circuit and causes all unit
operation to cease. This device resets automatically when
the motor windings cool. Do not bypass this switch to
correct trouble. Determine the cause and correct it.
The External motor overload device is a
specially--calibrated circuit breaker that is UL recognized
as a motor overload controller. It is an overcurrent
device. When the motor current exceeds the circuit
breaker setpoint, the device opens all motor power leads
and the motor shuts down. Reset requires a manual reset
at the overload switch. This device (designated IFCB) is
located on the side of the supply fan housing, behind the
fan access panel.
580J
25
Troubleshooting Supply Fan Motor Overload Trips
The supply fan used in 580J units is a forward--curved
centrifugal wheel. At a constant wheel speed, this wheel
has a characteristic that causes the fan shaft load to
DECREASE when the static pressure in the unit--duct
system increases and to INCREASE when the static
pressure in the unit--duct system decreases (and fan
airflow rate increases). Motor overload conditions
typically develop when the unit is operated with an access
panel removed, with unfinished duct work, in an
economizer--open mode, or a leak develops in the duct
system that allows a bypass back to unit return opening.
Condenser Fan Motor Protection
The condenser fan motor is internally protected against
overtemperature.
Control Circuit, 24--V
The control circuit is protected against overcurrent
conditions by a circuit breaker mounted on control
transformer TRAN. Reset is manual.
GAS HEATING SYSTEM
General
The heat exchanger system consists of a gas valve feeding
multiple inshot burners off a manifold. The burners fire
into matching primary tubes. The primary tubes discharge
into combustion plenum where gas flow converges into
secondary tubes. The secondary tubes exit into the
induced draft fan wheel inlet. The induced fan wheel
discharges into a flue passage and flue gases exit out a
flue hood on the side of the unit. The induced draft fan
motor includes a Hall Effect sensor circuit that confirms
adequate wheel speed via the Integrated Gas Control
(IGC) board. Safety switches include a Rollout Switch (at
the top of the burner compartment) and a limit switch
(mounted through the fan deck, over the tubes). (See Fig.
30 and 31.)
INDUCED-
DRAFT
MOTOR
MOUNTING
PLATE
BURNER
SECTION
INDUCED-
DRAFT MOTOR
MANIFOLD
PRESSURE
TAP
ROLLOUT
SWITCH
FLUE
EXHAUST
VESTIBULE
PLATE
BLOWER
HOUSING
GAS
VALVE
C09153
Fig. 30 -- Burner Section Details
Limit Switch
and Shield
C08284
Fig. 31 -- Limit Switch Location
Fuel Types and Pressures
Natural Gas
The 580J unit is factory--equipped for use with Natural
Gas fuel at elevation under 2000 ft (610 m). See section
Orifice Replacement for information in modifying this
unit for installation at elevations above 2000 ft (610 m).
Gas line pressure entering the unit’s main gas valve must
be within specified ranges. (See Table 5.) Adjust unit gas
regulator valve as required or consult local gas utility.
Table 5 – Natural Gas Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE MIN MAX
580J All 4.0 in. wg
(996 Pa)
13.0 in. wg
(3240 Pa)
Manifold pressure is factory--adjusted for NG fuel use.
(See Table 6.) Adjust as required to obtain best flame
characteristic.
Table 6 – Natural Gas Manifold Pressure Ranges
UNIT
MODEL
UNIT
SIZE
HIGH
FIRE
LOW
FIRE RANGE
580J All 3.5 in. wg
(872 Pa)
1.7 in. wg
(423 Pa)
2.0--- 5.0 in. wg (Hi)
(498--- 1245 Pa)
Liquid Propane
Accessory packages are available for field--installation
that will convert the 580J unit to operate with Liquid
Propane (LP) fuels. These kits include new orifice spuds,
new springs for gas valves and a supply line low pressure
switch. See section on Orifice Replacement for details on
orifice size selections.
Fuel line pressure entering unit gas valve must remain
within specified range. (See Table 7.)
580J
26
Table 7 – Liquid Propane Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE MIN MAX
580J All 11.0 in. wg
(2740 Pa)
13.0 in. wg
(3240 Pa)
Manifold pressure for LP fuel use must be adjusted to
specified range. (See Table 8.) Follow instructions in the
accessory kit to make initial readjustment.
Table 8 – Liquid Propane Manifold Pressure Ranges
UNIT MODEL UNIT SIZE HIGH FIRE LOW FIRE
580J All 10.0 in. wg
(2490 Pa)
5.0 in. wg
(1245 Pa)
Supply Pressure Switch
The LP conversion kit includes a supply low pressure
switch. The switch contacts (from terminal C to terminal
NO) will open the gas valve power whenever the supply
line pressure drops below the setpoint. (See Fig. 32 and
33.) If the low pressure remains open for 15 minutes
during a call for heat, the IGC circuit will initiate a
Ignition Fault (5 flashes) lockout. Reset of the low
pressure switch is automatic on rise in supply line
pressure. Reset of the IGC requires a recycle of unit
power after the low pressure switch has closed.
580JD08 only C08238
All 580J*D except DD08
C08239
Fig. 32 -- LP Low Pressure Switch (Installed)
PNK
W2
TSTAT
GRA
BRN
IGC
J2-12
IGC
J2-11
BRN
CNO
MGV
C
LP LPS
C08285
Fig. 33 -- LP Supply Line Low Pressure Switch Wiring
This switch also prevents operation when the propane tank
level is low which can result in gas with a high
concentration of impurities, additives, and residues that
have settled to the bottom of the tank. Operation under
these conditions can cause harm to the heat exchanger
system. Contact your fuel supplier if this condition is
suspected.
Flue Gas Passageways
To inspect the flue collector box and upper areas of the
heat exchanger:
1. Remove the combustion blower wheel and motor as-
sembly according to directions in Combustion--Air
Blower section. (See Fig. 34.)
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
Combustion--Air Blower
Clean periodically to assure proper airflow and heating
efficiency. Inspect blower wheel every fall and
periodically during heating season. For the first heating
season, inspect blower wheel bi--monthly to determine
proper cleaning frequency.
To access burner section, slide the sliding burner partition
out of the unit.
To inspect blower wheel, shine a flashlight into draft hood
opening. If cleaning is required, remove motor and wheel
as follows:
1. Slide burner access panel out.
2. Remove the 7 screws that attach induced--draft motor
housing to vestibule plate. (See Fig. 34.)
3. The blower wheel can be cleaned at this point. If ad-
ditional cleaning is required, continue with Steps 4
and 5.
4. To remove blower from the motor shaft, remove 2
setscrews.
5. To remove motor, remove the 4 screws that hold the
motor to mounting plate. Remove the motor cooling
fan by removing one setscrew. Then remove nuts that
hold motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
580J
27
HEATER TUBE
ASSEMBLY
SEAL STRIPS,
SPONGE RUBBER
REGULATOR
GASKET
REGULATOR
RETAINER
WIND CAP
ASSEMBLY
(SHOWN
INVERTED,
AS SHIPPED)
BURNER ASSEMBLY
INDUCER FAN-MOTOR ASSEMBLY
SUPPORT INSULATION ASSEMBLY
C08227
Fig. 34 -- Heat Exchanger Assembly
Burners and Igniters
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
When working on gas train, do not hit or plug
orifice spuds.
CAUTION
!
Main Burners
To access burners, remove burner access panel and slide
out burner partition. At the beginning of each heating
season, inspect for deterioration or blockage due to
corrosion or other causes. Observe the main burner flames
and adjust, if necessary.
Orifice Projection
Refer to Fig. 35 for maximum projection dimension for
orifice face to manifold tube.
ORIFICE
1.00-in
(25.4 mm)
M
ANIFOLD
PIPE
C08211
Fig. 35 -- Orifice Projection
Removal and Replacement of Gas Train
See Fig. 30, 34, and 36.
1. Shut off manual gas valve.
2. Shut off power to unit.
3. Slide out burner partition.
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each
wire.
580J
28
MANIFOLD PRESSURE TAP
GAS
VALVE
BURNERS
C09154
Fig. 36 -- Burner Tray Details
6. Remove igniter wires and sensor wires at the Integ-
rated Gas Unit Controller (IGC). (See Fig. 37.)
7. Remove the 2 screws that attach the burner rack to
the vestibule plate. (See Fig. 34.)
8. Slide the burner tray out of the unit. (See Fig. 36.)
9. To reinstall, reverse the procedure outlined above.
Cleaning and Adjustment
1. Remove burner rack from unit as described in Re-
moval and Replacement of Gas Train section.
2. Inspect burners; if dirty, remove burners from rack.
(Mark each burner to identify its position before re-
moving from the rack.)
3. Use a soft brush to clean burners and cross--over port
as required.
4. Adjust spark gap. (See Fig. 38.)
5. If factory orifice has been removed, check that each
orifice is tight at its threads into the manifold pipe
and that orifice projection does not exceed maximum
valve. (See Fig. 35).
6. Reinstall burners on rack in the same locations as
factory--installed. (The outside crossover flame re-
gions of the outermost burners are pinched off to pre-
vent excessive gas flow from the side of the burner
assembly. If the pinched crossovers are installed
between two burners, the flame will not ignite prop-
erly.)
RACEWAY INTEGRATED GAS UNIT
CONTROLLER (IGC)
HOLE IN END PANEL (HIDDEN)
C08454
Fig. 37 -- Unit Control Box/IGC Location
7. Reinstall burner rack as described in Removal and
Replacement of Gas Train section, above.
Gas Valve — All unit sizes are equipped with 2--stage gas
valves. See Fig. 39 for locations of adjustment screws and
features on the gas valves.
To adjust gas valve pressure settings:
IMPORTANT: Leak check all gas connections including
the main service connection, gas valve, gas spuds, and
manifold pipe plug. All leaks must be repaired before
firing unit.
Check Unit Operation and Make Necessary
Adjustments
NOTE: Gas supply pressure at gas valve inlet must be
within specified ranges for fuel type and unit size. (See
Table 5, 6, 7, and 8.)
1. Remove manifold pressure tap plug from manifold
and connect pressure gauge or manometer. (See Fig.
36.)
2. Turn on electrical supply.
3. Turn on unit main gas valve.
4. Set room thermostat to call for heat. Verify high--
stage heat operation before attempting to adjust mani-
fold pressure.
5. When main burners ignite, check all fittings, mani-
fold, and orifices for leaks.
6. Adjust high--stage pressure to specified setting by
turning the plastic adjustment screw clockwise to in-
crease pressure, counter--clockwise to decrease pres-
sure.
7. Set room thermostat to call for low--stage heat. Adjust
low--stage pressure to specified setting.
8. Replace regulator cover screw(s) when finished.
9. With burner access panel removed, observe unit heat-
ing operation in both high stage and low stage opera-
tion. Observe burner flames to see if they are blue in
appearance, and that the flames are approximately the
same for each burner.
10. Turn off unit, remove pressure manometer and re-
place the 1/8 in. pipe fitting on the gas manifold. (See
Fig. 36.)
Limit Switch
Remove blower access panel. Limit switch is located on
the fan deck. (See Fig. 31.)
580J
29
125,000/90,000 BTUH INPUT
180,000/120,000 BTUH INPUT
240,000/180,000 BTUH INPUT
250,000/200,000 BTUH INPUT
C08447
Fig. 38 -- Spark Adjustment (08--14)
Burner Ignition
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is located in
the control box. (See Fig. 37.) The IGC contains a
self--diagnostic LED (light--emitting diode). A single LED
on the IGC provides a visual display of operational or
sequential problems when the power supply is
uninterrupted. (See Fig. 40.) When a break in power
occurs, the IGC will be reset (resulting in a loss of fault
history) and the indoor (evaporator) fan ON/OFF times
will be reset. The LED error code can be observed
through the viewport. During servicing refer to the label
on the control box cover or Table 9 for an explanation of
LED error code descriptions.
If lockout occurs, unit may be reset by interrupting power
supply to unit for at least 5 seconds.
Table 9 – LED Error Code Description*
LED INDICATION ERROR CODE
DESCRIPTION
ON Normal Operation
OFF Hardware Failure
2Flashes Limit Switch Fault
3Flashes Flame Sense Fault
4Flashes 4 Consecutive Limit Switch Faults
5Flashes Ignition Lockout Fault
6Flashes Induced--- Draft Motor Fault
7Flashes Rollout Switch Fault
8Flashes Internal Control Fault
9Flashes Software Lockout
LEGEND
LED --- L i g h t E m i t t i n g D i o d e
* A 3 – second pause exists between LED error code flashes. If
more than one error code exists, all applicable codes will be
displayed in numerical sequence.
IMPORTANT: Refer to Troubleshooting Table 13 and 14
for additional information.
580J
30
C08240
C08241
580J08(D,F)150 only
All 580J*D,F except 150
Fig. 39 -- Gas Valve
Orifice Replacement
This unit uses orifice type LH32RFnnn (where nnn
indicates orifice reference size). When replacing unit
orifices, order the necessary parts via Bryant RCD. See
Table 11 for available orifice sizes. See Table 12 for
orifice sizes for Natural Gas and LP fuel usage at various
elevations above sea level.
Check that each replacement orifice is tight at its threads
into the manifold pipe and that orifice projection does not
exceed maximum value. (See Fig. 35.)
580J
31
Red LED-Status
C08452
Fig. 40 -- Integrated Gas Control (IGC) Board
Table 10 – IGC Connections
TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O CONNECTION
PIN NUMBER
INPUTS
RT, C Input power from TRAN 1 control box 24 VAC
SS Speed sensor gas section analog input J1, 1-3
FS, T1 Flame sensor gas section switch input
WHeat stage 1 LCTB 24 VAC J2, 2
RS Rollout switch gas section switch input J2, 5-6
LS Limit switch fan section switch input J2, 7-8
CS Centrifugal switch (not used) switch input J2, 9-10
OUTPUTS
L1, CM Induced draft combustion motor gas section line VAC
IFO Indoor fan control box relay J2, 1
GV Gas valve (heat stage 1) gas section relay J2, 11-12
580J
32
Table 11 – Orifice Sizes
ORIFICE
DRILL SIZE
BRYANT
PART NUMBER
DRILL
DIA. (in.)
#30 LH32RF129 0.1285
1/8 LH32RF125 0.1250
#31 LH32RF120 0.1200
#32 LH32RF116 0.1160
#33 LH32RF113 0.1130
#34 LH32RF111 0.1110
#35 LH32RF110 0.1100
#36 LH32RF105 0.1065
#37 LH32RF104 0.1040
#38 LH32RF102 0.1015
#39 LH32RF103 0.0995
#40 LH32RF098 0.0980
#41 LH32RF096 0.0960
#42 LH32RF094 0.0935
#43 LH32RF089 0.0890
#44 LH32RF086 0.0860
#45 LH32RF082 0.0820
#46 LH32RF080 0.0810
#47 LH32RF079 0.0785
#48 LH32RF076 0.0760
#49 LH32RF073 0.0730
#50 LH32RF070 0.0700
#51 LH32RF067 0.0670
#52 LH32RF065 0.0635
#53 LH32RF060 0.0595
#54 LH32RF055 0.0550
#55 LH32RF052 0.0520
#56 LH32RF047 0.0465
#57 LH32RF043 0.0430
#58 LH32RF042 0.0420
Table 12 -- Altitude Compensation* (08--14)
ELEVATION
ft (m)
125,000
BTUH Nominal
250,000
BTUH Nominal
180,000, 224,000
BTUH Nominal
NG Orifice
Size
LP Orifice
Size
NG Orifice
Size
LP Orifice
Size
NG Orifice
Size
LP Orifice
Size
0 --- 2000 (610) 311493†30 463311483
2000 (610) 321503†30 473321493
3000 (914) 321503311473321493
4000 (1219) 331503311483331493
5000 (1524) 331514311483331503
6000 (1829) 341514311483341503
7000 (2134) 351514321493351503
8000 (2438) 361524331493361514
9000 (2743) 372524341503372514
10000 (3048) 382524351503382524
11000 (3353) 392534361514392524
12000 (3658) †41 534372514†41 534
13000 (3962) †42 544382524†42 534
14000 (4267) †43 544†40 534†43 544
LEGEND
NG = Natural Gas LP = Liquid Propane
* As the height above sea level increases, there is less oxygen
per cubic ft. of air. Therefore, heat input rate should be reduced
at higher altitudes.
{Not included in kit. May be purchased separately through
dealer.
1 = CRLPELEV001A00
2 = CRLPELEV002A00
3 = CRLPELEV003A00
4 = CRLPELEV004A00
580J
33
Minimum Heating Entering Air Temperature
When operating on first stage heating, the minimum
temperature of air entering the dimpled heat exchanger is
50_F continuous and 45_F intermittent for standard heat
exchangers and 40_F continuous and 35_F intermittent for
stainless steel heat exchangers. To operate at lower
mixed--air temperatures, a field--supplied outdoor--air
thermostat must be used to initiate both stages of heat
when the temperature is below the minimum required
temperature to ensure full fire operation. Wire the
outdoor--air thermostat OALT (part no. HH22AG106) in
series with the second stage gas valve. (See Fig. 41.) Set
the outdoor--air thermostat at 35_F for stainless steel heat
exchangers or 45_F for standard heat exchangers. This
temperature setting will bring on the second stage of heat
whenever the ambient temperature is below the thermostat
setpoint. Indoor comfort may be compromised when
heating is initiated using low entering air temperatures
with insufficient heating temperature rise.
LCTB
W2
Thermostat
TH1
TH2
W1
W1
W2
OALT
C08442
Fig. 41 -- OATL Connections
Troubleshooting Heating System
Refer to Table 13 and 14 for additional troubleshooting
topics.
Table 13 – Heating Service Analysis
PROBLEM CAUSE REMEDY
Burners Will Not Ignite.
Misaligned spark electrodes. Check flame ignition and sensor electrode positioning.
Adjust as needed.
No gas at main burners.
Check gas line for air, purge as necessary. After purging
gas line of air, allow gas to dissipate for at least 5 minutes
before attempting to relight unit.
Check gas valve.
Water in gas line. Drain water and install drip leg to trap water.
No power to furnace. Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control
circuit.
Check transformer. Transformers with internal overcurrent
protection require a cool down period before resetting.
Miswired or loose connections. Check all wiring and wire nut connections.
Burned ---out heat anticipator in
thermostat. Replace thermostat.
Broken thermostat wires. Run continuity check. Replace wires, if necessary.
Inadequate Heating.
Dirty air filter. Clean or replace filter as necessary.
Gas input to unit too low.
Check gas pressure at manifold. Clock gas meter for input.
If too low, increase manifold pressure, or replace with
correct orifices.
Unit undersized for application. Replace with proper unit or add additional unit.
Restricted airflow. Clean filter, replace filter, or remove any restrictions.
Blower speed too low. Use high speed tap, increase fan speed, or install optional
blower, as suitable for individual units.
Limitswitchcyclesmainburners. Check rotation of blower, thermostat heat anticipator
settings, and temperature rise of unit. Adjust as needed.
Too much outdoor air. Adjust minimum position.
Check economizer operation.
Poor Flame
Characteristics.
Incomplete combustion (lack of
combustion air) results in:
Aldehyde odors, CO, sooting
flame, or floating flame.
Check all screws around flue outlets and burner
compartment. Tighten as necessary.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Burners Will Not Turn
Off.
Unit is locked into Heating mode
for a one minute minimum.
Wait until mandatory one---minute time period has elapsed
or reset power to unit.
580J
34
Table 14 – IGC Board LED Alarm Codes
LED
FLASH
CODE
DESCRIPTION ACTION TAKEN BY
CONTROL RESET METHOD PROBABLE CAUSE
On Normal Operation — —
Off Hardware Failure No gas heating.
Loss of power to the IGC. Check 5 amp
fuse on IGC, power to unit, 24V circuit
breaker, transformer, and wiring to the
IGC.
2
Flashes Limit Switch Fault
Gas valve and igniter
Off.
Indoor fan and inducer
On.
Limit switch closed,
or heat call (W) Off.
High temperature limit switch is open.
Check the operation of the indoor
(evaporator) fan motor.
Ensure that the supply-air temperature
rise is within the range on the unit
nameplate. Check wiring and limit switch
operation.
3
Flashes Flame Sense Fault Indoor fan and inducer
On.
Flame sense normal.
Power reset for LED
reset.
The IGC sensed a flame when the gas
valve should be closed. Check wiring,
flame sensor, and gas valve operation.
4
Flashes
Four Consecutive Limit
Switch Fault No gas heating.
Heat call (W) Off.
Power reset for LED
reset.
4 consecutive limit switch faults within a
single call for heat. See Limit Switch Fault.
5
Flashes Ignition Fault No gas heating.
Heat call (W) Off.
Power reset for LED
reset.
Unit unsuccessfully attempted ignition for
15 minutes. Check igniter and flame
sensor electrode spacing, gaps, etc.
Check flame sense and igniter wiring.
Check gas valve operation and gas
supply.
6
Flashes
Induced Draft Motor
Fault
If heat off: no gas
heating.
If heat on: gas valve
Off and inducer On.
Inducer sense
normal, or heat call
(W) Off.
Inducer sense On when heat call Off, or
inducer sense Off when heat call On.
Check wiring, voltage, and operation of
IGC motor. Check speed sensor wiring to
IGC.
7
Flashes Rollout Switch Lockout
Gas valve and igniter
Off.
Indoor fan and inducer
On.
Power reset.
Rollout switch has opened. Check gas
valve operation. Check induced-draft
blower wheel is properly secured to motor
shaft.
8
Flashes Internal Control Lockout No gas heating. Power reset.
IGC has sensed internal hardware or
software error. If fault is not cleared by
resetting 24 v power, replace the IGC.
Check gas valve connections to IGC
terminals. BRN lead must be on Pin 11.
9
Flashes
Temporary Software
Lockout No gas heating. 1 hour auto reset, or
power reset.
Electrical interference is disrupting the
IGC software.
LEGEND
IGC --- Integrated Gas Unit Control
LED --- L i g h t --- E m i t t i n g D i o d e
NOTES:
1. There is a 3---second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
580J
35
CONDENSER COIL SERVICE
Condenser Coil
The condenser coil is new NOVATION Heat Exchanger
Technology. This is an all--aluminum construction with
louvered fins over single--depth crosstubes. The crosstubes
have multiple small passages through which the
refrigerant passes from header to header on each end.
Tubes and fins are both aluminum construction.
Connection tube joints are copper. The coil may be
one--row or two--row. Two--row coils are spaced apart to
assist in cleaning.
Repairing NOVATION Condenser Tube Leaks
RCD offers service repair kit Part Number 50TJ660007
for repairing tube leaks in the NOVATION coil crosstubes.
This kit includes approved braze materials (aluminum flux
core braze rods), a heat shield, a stainless steel brush,
replacement fin segments, adhesive for replacing fin
segments, and instructions specific to the NOVATION
aluminum coil. See EPIC for instruction sheet
99TA526379.
The repair procedure requires the use of MAPP gas and
torch (must be supplied by servicer) instead of
conventional oxyacetylene fuel and torch. While the
flame temperature for MAPP is lower than that of
oxyacetylene (and thus provides more flexibility when
working on aluminum), the flame temperature is still
higher than the melting temperature of aluminum, so user
caution is required. Follow instructions carefully. Use the
heat shield.
Replacing NOVATION Condenser Coil
The service replacement coil is preformed and is equipped
with transition joints with copper stub tubes. When
brazing the connection joints to the unit tubing, use a wet
cloth around the aluminum tube at the transition joint.
Avoid applying torch flame directly onto the aluminum
tubing.
RTU--MP CONTROL SYSTEM
The RTU--MP controller provides expanded stand--alone
operation of the HVAC system plus connection and
control through communication with several Building
Automation Systems (BAS) through popular third--party
network systems. (See Fig. 42.) The available network
systems are BACnet MP/TP, Modbus and Johnson J2.
Communication with LonWorks is also possible by adding
an accessory interface card to the RTU--MP. Selection of
the communication protocol and baud rate are made at
on--board DIP switches.
Bryant’s diagnostic display tools BACviewer6 Handheld
and Virtual BACview (loaded on a portable PC) must be
used with the RTU--MP controller. Connection to the
RTU--MP board is at the J12 access port. (See Fig. 42.)
The RTU--MP control is factory--mounted in the 48TC
unit’s main control box, to the left of the LCTB. (See Fig.
43.) Factory wiring is completed through harnesses
connected to the LCTB. Field connections for RTU--MP
sensors will be made at the Phoenix connectors on the
RTU--MP board. The factory--installed RTU--MP control
includes the supply--air temperature (SAT) sensor. The
outdoor air temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er 2 package.
Refer to Table 15, RTU--MP Controller Inputs and
Outputs, for locations of all connections to the RTU--MP
board.
580J
36
C07129
Fig. 42 -- RTU--MP Multi--Protocol Control Board
580J
37
C09163
Fig. 43 -- Typical RTU--MP System Control Wiring Diagram
580J
38
Table 15 – RTU--MP Controller Inputs and Outputs
POINT NAME BACnet OBJECT
NAME TYPE OF I/O CONNECTION PIN
NUMBERS
INPUTS
Space Temperature Sensor sptsens AI (10K Thermistor) J 2 0 --- 1 , 2
Supply Air Temperature sat AI (10K Thermistor) J 2 --- 1 , 2
Local Outside Air Temperature Sensor oatsens AI (10K Thermistor) J 2 --- 3 , 4
Space Temperature Offset Pot sptopot AI (100K Potentiometer) J 2 0 --- 3
Indoor Air Quality iaq A I ( 4 --- 2 0 m a ) J 4 --- 2 , 3
Outdoor Air Quality oaq A I ( 4 --- 2 0 m a ) J 4 --- 5 , 6
Safety Chain Feedback safety DI (24 VAC) J 1 --- 9
Compressor Safety compstat DI (24 VAC) J 1 --- 2
Fire Shutdown firedown DI (24 VAC) J 1 --- 1 0
Enthalpy Switch enthalpy DI (24 VAC) J 2 --- 6 , 7
Humidistat Input Status humstat DI (24 VAC) J 5 --- 7 , 8
CONFIGURABLE INPUTS*
Space Relative Humidity sprh A I ( 4 --- 2 0 m a ) J4---2,3 or J4---5,6
Outside Air Relative Humidity oarh A I ( 4 --- 2 0 m a )
Supply Fan Status fanstat DI (24 VAC) J 5 --- 1 , 2 o r J 5 --- 3 , 4 o r
J5 5,6 or J5 --- 7,8
Filter Status filtstat DI (24 VAC)
Remote Occupancy Input remocc DI (24 VAC)
OUTPUTS
Economizer Commanded Position econocmd 4 --- 2 0 m a J 2 --- 5
SupplyFanRelayState sf DO Relay (24VAC , 1A) J 1 --- 4
Compressor 1 Relay State comp_1 DO Relay (24VAC , 1A) J 1 --- 8
Compressor 2 Relay State comp_2 DO Relay (24VAC , 1A) J 1 --- 7
Heat Stage 1 Relay State heat_1 DO Relay (24VAC , 1A) J 1 --- 6
Heat Stage 2 Relay State heat_2 DO Relay (24VAC , 1A) J 1 --- 5
Power Exhaust Relay State aux_2 DO Relay (24VAC , 1A) J 1 1 --- 3
Dehumidification Relay State humizer DO Relay (24VAC, 1A) J 1 1 --- 7 , 8
LEGEND
AI --- A n a l o g I n p u t
AO --- A n a l o g O u t p u t
DI --- D i s c r e t e I n p u t
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
P a r a l l e l p i n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a r e u s e d f o r f i e l d --- i n s t a l l a t i o n .
Refer to the input configuration and accessory sections for more detail.
NOTE: Refer to RTU--MP Controls, Start-Up, Operation,
and Troubleshooting Instructions (Form 48--50H--T--2T)
for complete configuration of RTU--MP, operating
sequences and troubleshooting information. Refer to
RTU--MP 3rd Party Integration Guide for details on
configuration and troubleshooting of connected networks.
Have a copy of these manuals available at unit start--up.
The RTU--MP controller requires the use of a Bryant
space sensor. A standard thermostat cannot be used with
the RTU--MP system.
Supply Air Temperature (SAT) Sensor
On FIOP--equipped 580J unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches (12.7
mm) in length. It is a nominal 10--k ohm thermistor. See
Table 16 for temperature--resistance characteristic.
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
codes). Drill or punch a 1/2--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizontal orientation. (See Fig. 43.)
Outdoor Air Temperature (OAT) Sensor
The OAT is factory--mounted in the EconoMi$er 2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring. See Table 16 for
temperature--resistance characteristic.
580J
39
Table 16 – Thermistor Resistance vs Temperature
Values for Space Temperature Sensor, Supply Air
Temperature Sensor, and Outdoor Air Temperature
Sensor
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
--- 4 0 --- 4 0 335,651
--- 3 5 --- 3 1 242,195
--- 3 0 --- 2 2 176,683
--- 2 5 --- 1 3 130,243
--- 2 0 --- 4 96,974
--- 1 5 572,895
--- 1 0 14 55,298
--- 5 23 42,315
032 32,651
541 25,395
10 50 19,903
15 59 15,714
20 68 12,494
25 77 10,000
30 86 8,056
35 95 6,530
40 104 5,325
45 113 4,367
50 122 3,601
55 131 2,985
60 140 2,487
65 149 2,082
70 158 1,752
SUPPLY AIR RETURN AIR
SUPPLY AIR
TEMPERATURE
SENSOR
ROOF
CURB
C08200
Fig. 44 -- Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
EconoMi$er 2
The RTU--MP control is used with EconoMi$er2 (option
or accessory) for outdoor air management. The damper
position is controlled directly by the RTU--MP control;
EconoMi$er 2 has no internal logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
SEnthalpy control (outdoor air or differential sensors)
SSpace CO2sensor
SOutdoor air CO2sensor
Field Connections -- Field connections for accessory
sensors and input devices are made the RTU--MP, at plugs
J1, J2, J4, J5, J11 and J20. All field control wiring that
connects to the RTU--MP must be routed through the
raceway built into the corner post as shown in Fig. 37.
The raceway provides the UL required clearance between
high-- and low--voltage wiring. Pass the control wires
through the hole provided in the corner post, then feed the
wires thorough the raceway to the RTU--MP. Connect to
the wires to the removable Phoenix connectors and then
reconnect the connectors to the board.
Space Temperature (SPT) Sensors
A field--supplied Bryant space temperature sensor is
required with the RTU--MP to monitor space temperature.
There are 3 sensors available for this application:
S33ZCT55SPT, space temperature sensor with override
button
S33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment
S33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three--conductor shielded cable for the sensor and setpoint
adjustment connections. If the setpoint adjustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two--conductor, twisted pair cable may be used.
Connect T--55
See Fig. 45 for typical T--55 internal connections. Connect
the T--55 SEN terminals to RTU--MP J20--1 and J20--2.
(See Fig. 46.)
2345 61
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-) CCN COM
SENSOR WIRING
C08201
Fig. 45 -- T--55 Space Temperature Sensor Wiring
580J
40
SEN
SEN
J20-1
J20-2
C08460
Fig. 46 -- RTU--MP T--55 Sensor Connections
Connect T--56
See Fig. 47 for T--56 internal connections. Install a jumper
between SEN and SET terminals as illustrated. Connect
T--56 terminals to RTU--MP J20--1, J20--2 and J20--3 per
Fig. 48.
2345 61
SW1
SEN SET
Cool Warm
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-) CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
BLK
(T56)
C08202
Fig. 47 -- T--56 Internal Connections
SEN J20-1
J20-2
SEN
SET
Jumper
J20-3
SET
C08461
Fig. 48 -- RTU--MP T--56 Sensor Connections
Connect T--59
The T--59 space sensor requires a separate, isolated power
supply of 24 VAC. See Fig. 49 for internal connections at
the T--59. Connect the SEN terminal (BLU) to RTU--MP
J20--1. Connect the COM terminal (BRN) to J20--2.
Connect the SET terminal (STO or BLK) to J20--3.
OR SET SEN
OPB COM- PWR+
BLU (SPT)
BLK (STO)
24 VAC
SENSOR
WIRING
POWER
WIRING
BRN (COM)
NOTE: Must use a separate isolated transformer.
C07132
Fig. 49 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Economizer Controls
Outdoor Air Enthalpy Control (PNO HH57AC077)
The enthalpy control (HH57AC077) is available as a
field--installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field--installed
accessory return air enthalpy sensor (HH57AC078) is
required for differential enthalpy control.)
Locate the enthalpy control in the economizer hood.
Locate two GRA leads in the factory harness and connect
these leads to enthalpy control sensors 2 and 3. (See Fig.
50.) Connect the enthalpy control power input terminals to
economizer actuator power leads RED (connect to TR)
and BLK (connect to TR1).
6
7
LCTB
ECON
3
2
Enthalpy
Switch
GRA
GRA
Factory Wiring Harness
C08218
Fig. 50 -- Enthalpy Switch (HH57AC077) Connections
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
580J
41
The enthalpy control receives the outdoor air enthalpy
from the outdoor air enthalpy sensor and provides a dry
contact switch input to the RTU--MP controller. A closed
contact indicates that outside air is preferred to the return
air. An open contact indicates that the economizer should
remain at minimum position.
Differential Enthalpy Control
Differential enthalpy control is provided by sensing and
comparing the outside air and return air enthalpy
conditions. Install the outdoor air enthalpy control as
described above. Add and install a return air enthalpy
sensor.
Return Air Enthalpy Sensor
Mount the return--air enthalpy sensor (HH57AC078) in the
return--air duct. The return air sensor is wired to the
enthalpy controller (HH57AC077). (See Fig. 51.)
LED
ABC
D
TR TR1
SO
SR
23
1
+
+
BRN
RED
GRAY/ORN
GRAY/RED
WIRE HARNESS
IN UNIT
BLK
RED
S
+(RETURN AIR
ENTHALPY
SENSOR)
S
+
(OUTDOOR
AIR
ENTHALPY
SENSOR)
ENTHALPY CONTROLLER
NOTES:
1. Remove factory-installed jumper across SR and + before connecting
wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3
close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in outside air-
stream.
C06019
Fig. 51 -- Outside and Return Air Enthalpy
Sensor Wiring
To wire the return air enthalpy sensor, perform the
following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the
enthalpy controller.
2. At the enthalpy control remove the factory--installed
resistor from the (SR) and (+) terminals.
3. Connect the field--supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(SR+) terminal on the enthalpy controller. Connect
the BLK wire to (S) spade connector on the return air
enthalpy sensor and the (SR) terminal on the enthalpy
controller.
NOTE: The enthalpy control must be set to the “D”
setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return
enthalpy from the outdoor and return air enthalpy sensors
and provides a dry contact switch input to the RTU--MP
controller. A closed contact indicates that outside air is
preferred to the return air. An open contact indicates that
the economizer should remain at minimum position.
Indoor Air Quality (CO2Sensor)
The indoor air quality sensor accessory monitors space
carbon dioxide (CO2) levels. This information is used to
monitor IAQ levels. Several types of sensors are available,
for wall mounting in the space or in return duct, with and
without LCD display, and in combination with space
temperature sensors. Sensors use infrared technology to
measure the levels of CO2present in the space air.
The CO2sensors are all factory set for a range of 0 to
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO2sensor for electrical
requirements and terminal locations. See Fig. 52 for
typical CO2sensor wiring schematic.
C07134
Fig. 52 -- Indoor/Outdoor Air Quality (CO2)Sensor
(33ZCSENCO2) -- Typical Wiring Diagram
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return--air
grille (if present) so it senses the concentration of CO2
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor
For each sensor, use two 2--conductor 18 AWG (American
Wire Gauge) twisted--pair cables (unshielded) to connect
the separate isolated 24 vac power source to the sensor
and to connect the sensor to the control board terminals.
580J
42
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. (See Fig. 52.) Connect the 4--20 mA terminal to
RTU--MP J4--2 and connect the SIG COM terminal to
RTU--MP J4--3. (See Fig. 53.)
SEN
COM
J4-2
J4-3
IAQ Sensor
24 VAC
C08462
Fig. 53 -- RTU--MP / Indoor CO2Sensor
(33ZCSENCO2) Connections
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
Weatherproof Enclosure)
The outdoor air CO2sensor is designed to monitor carbon
dioxide (CO2) levels in the outside ventilation air and
interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. (See
Fig. 54.) The outdoor air CO2sensor must be located in
the economizer outside air hood.
COVER REMOVED SIDE VIEW
C07135
Fig. 54 -- Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO2Sensor
A dedicated power supply is required for this sensor. A
two--wire cable is required to wire the dedicated power
supply for the sensor. The two wires should be connected
to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. (See Fig. 52.) Connect the 4 to 20 mA
terminal to RTU--MP J4--5. Connect the SIG COM
terminal to RTU--MP J4--6. (See Fig. 55.)
SEN
COM
J4-5
J4-6
OAQ Sensor/RH Sensor
24 VAC
C08463
Fig. 55 -- RTU--MP / Outdoor CO2Sensor
(33ZCSENCO2) Connections
On 580J units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s LCTB input. The FSD function is initiated via the
smoke detectors Alarm NO contact set. The RTU--MP
controller communicates the smoke detectors tripped
status to the BAS building control. See Fig. 26 for unit
smoke detector wiring.
The Fire Shutdown Switch configuration,
MENU
Config
Inputs
input 5, identifies the
normally open status of this input when there is no fire
alarm.
Alarm state is reset when the smoke detector alarm
condition is cleared and reset at the smoke detector in the
unit.
Connecting Discrete Inputs
Filter Status
The filter status accessory is a field--installed accessory.
This accessory detects plugged filters. When installing
this accessory, the unit must be configured for filter status
by setting MENU
Config
Inputs
input3,5,8,or9
to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 42 and 43 for wire terminations
at J5.
Fan Status
The fan status accessory is a field--installed accessory.
This accessory detects when the indoor fan is blowing air.
When installing this accessory, the unit must be
configured for fan status by setting
MENU
Config
Inputs
input3,5,8,or9to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 42 and 43 for wire terminations at J5.
580J
43
Remote Occupancy
The remote occupancy accessory is a field--installed
accessory. This accessory overrides the unoccupied mode
and puts the unit in occupied mode. When installing this
accessory, the unit must be configured for remote
occupancy by setting MENU
Config
Inputs
input 3,
5, 8, or 9 to Remote Occupancy and normally open (N/O)
or normally closed (N/C).
Also set MENU
Schedules
occupancy source to DI
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 42 and Table 15 for wire
terminations at J5.
Power Exhaust (output)
Connect the accessory Power Exhaust contactor coil(s) per
Fig. 56.
Power Exhaust
J11-3
C
THERMOSTAT
PEC TAN
GRA
LCTB
C08464
Fig. 56 -- RTU--MP Power Exhaust Connections
Space Relative Humidity Sensor
Space Relative Humidity Sensor -- The RH sensor is not
used with 580J models at this time.
Communication Wiring -- Protocols
General
Protocols are the communication languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
The RTU--MP can be set to communicate on four different
protocols: BACnet, Modbus, N2, and LonWorks. Switch 3
(SW3) on the board is used to set protocol and baud rate.
Switches 1 and 2 (SW1 and SW2) are used to set the
boards network address. See Fig 57 for the switch setting
per protocol. The 3rd party connection to the RTU--MP is
through plug J19. Refer to the RTU--MP 3rd Party
Integration Guide for more detailed information on
protocols, 3rd party wiring, and networking.
NOTE: Power must be cycled after changing the SW1--3
switch settings.
BACnet MS/TP
BACnet Master Slave/Token Passing (MS/TP) is used for
communicating BACnet over a sub--network of
BACnet--only controllers. This is the default Bryant
communications protocol. Each RTU--MP module acts as
an MS/TP Master. The speed of an MS/TP network can
range from 9600 to 76.8K baud. Physical Addresses can
be set from 01 to 99.
Modbus
The RTU--MP module can speak the Modicon Modbus
RTU Protocol as described in the Modicon Modbus
Protocol Reference Guide, PI--MBUS--300 Rev. J. The
speed of a Modbus network can range from 9600 to 76.8K
baud. Physical Addresses can be set from 01 to 99.
Johnson N2
N2 is not a standard protocol, but one that was created by
Johnson Controls, Inc. that has been made open and
available to the public. The speed of N2 network is
limited to only 9600 baud. Physical Addresses can be set
from 01 to 99.
LonWorks
LonWorks is an open protocol that requires the use of
Echelon’s Neuron microprocessor to encode and decode
the LonWorks packets. In order to reduce the cost of
adding that hardware on every module, a separate
LonWorks Option Card (LON--OC) was designed to
connect to the RTU--MP.
This accessory card is needed for LonWorks and has to be
ordered and connected using the ribbon cable to plug J15.
The RTU--MP’s baud rate must be set to 38.4k to
communicate with the LON--OC. The address switches
(SW1 & SW2) are not used with LonWorks.
Local Access
BACview6Handheld
The BACview6is a keypad/display interface used to
connect to the RTU--MP to access the control information,
read sensor values, and test the RTU. (See Fig. 58.) This is
an accessory interface that does not come with the MP
controller and can only be used at the unit. Connect the
BACview6to the RTU--MPs J12 local access port. There
are 2 password protected levels in the display (User and
Admin). The user password defaults to 0000 but can be
changed. The Admin password is 1111 and cannot be
changed. There is a 10 minute auto logout if a screen is
left idle. See RTU--MP Controls, Start--Up, Operation, and
Troubleshooting Instructions (Form 48--50H--T--2T),
Appendix A for navigation and screen content.
580J
44
SW3 Protocol Selection
PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1
BACnet MS/TP
(Master) Unused OFF OFF OFF ON OFF Select Baud Select Baud
Modbus
(Slave) Unused OFF OFF ON ON OFF Select Baud Select Baud
N2
(Slave) Unused OFF OFF OFF ON ON OFF OFF
LonWorks Unused ON ON OFF ON OFF OFF OFF
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE DS2 DS1
9600 OFF OFF
19,200 ON OFF
38,400 OFF ON
76,800 ON ON
C07166
Fig. 57 -- RTU--MP SW3 Dip Switch Settings
Virtual BACview
Virtual BACview is a freeware computer program that
functions as the BACview6Handheld. The USB Link
interface (USB--L) is required to connect a computer to
the RTU--MP board. The link cable connects a USB port
to the J12 local access port. This program functions and
operates identical to the handheld.
RTU--MP Troubleshooting
Communication LEDs
The LEDs indicate if the controller is speaking to the
devices on the network. The LEDs should reflect
communication traffic based on the baud rate set. The
higher the baud rate the more solid the LEDs will appear.
C07170
Fig. 58 -- BACview6Handheld Connections
580J
45
Table 17 – LEDs
The LEDs on the RTU--MP show the status of certain functions
If this LED is on... Status is...
Power The RTU MP has power
Rx The RTU MP is receiving data from the network segment
Tx The RTU MP is transmitting data over the network segment
DO# The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows... And Error LED shows... Status is...
2 flashes per second Off Normal
2 flashes per second 2flashes,
alternating with Run LED
Five minute auto---restart delay after
system error
2 flashes per second 3flashes,
then off
Control module has just been
formatted
2 flashes per second 4flashes,
then pause
Two or more devices on this network
havethesameARC156networkaddress
2 flashes per second On Exec halted after frequent system errors
or control programs halted
5 flashes per second On Exec start--- up aborted, Boot is running
5 flashes per second Off Firmware transfer in progress, Boot is
running
7 flashes per second 7 flashes per second, alternating with
Run LED
Ten second recovery period after
brownout
14 flashes per second 14 flashes per second,
alternating with Run LED Brownout
On On
Failure. Try the following solutions:
STurn the RTU---MP off, then on.
SF o r m a t t h e R T U --- M P.
SDownload memory to the RTU---MP.
SReplace the RTU---MP.
580J
46
Table 18 – Troubleshooting Alarms
POINT NAME
BACnet
OBJECT
NAME
ACTION TAKEN BY
CONTROL
RESET
METHOD PROBABLE CAUSE
Safety Chain Alarm safety_chain
Alarm Generated
Immediate
Shutdown
Automatic Over load Indoor Fan or Electric Heater overheat.
Fire Shutdown Alarm fire_alarm
Alarm Generated
Immediate
Shutdown
Automatic Smoke detected by smoke detector or
configuration incorrect
Space Temp Sensor
Failure spt_alarm
Alarm Generated
Immediate
Shutdown
Automatic Faulty, shorted, or open thermistor caused by
wiring error or loose connection.
SAT Sensor Alarm sat_alarm
Alarm Generated
Immediate
Shutdown
Automatic Faulty, shorted, or open thermistor caused by
wiring error or loose connection.
High Space Temp Alarm spt_hi Alarm Generated Automatic Thespacetemperaturehasrisenabovethecool
setpoint by more than the desired amount.
Low Space Temp Alarm spt_lo Alarm Generated Automatic The space temperature has dropped below the
heat setpoint by more than the desired amount.
High Supply Air Temp sat_hi Alarm Generated Automatic SAT is greater then 160 degrees for more than 5
minutes.
Low Supply Air Temp sat_lo Alarm Generated Automatic Thesupplyairtemperatureisbelow35_Ffor
more than 5 minutes.
Supply Fan Failed to
Start sf_fail
Alarm Generated
Immediately
disable Operation
Automatic
Tripped Circuit Breaker, Broken belt, Bad indoor
fan motor, Configuration incorrect, Bad fan status
switch.
Supply Fan in Hand sf_hand
Alarm Generated
Ramp down
Operations
Automatic Bad Fan Status Switch, Configuration incorrect.
Compressor Safety
Alarm dx_compstat Alarm Generated Automatic Compressor would not start.
Setpoint Slider Alarm slide_alarm Alarm Generated
Offset set to zero Automatic STOsensorisopenorshortedformorethen5
seconds.
Dirty Filter Alarm filter Alarm Generated
Automatic/re
set timer
when
configured
with or
without
switch
Dirty Filter, supply fan run time exceeded, filter
switch configuration wrong.
Switch Configuration
Alarm sw_cfg_alarm
Alarm Generated
Disable
misconfigured switch
functions
Configure
correctly
More than one binary input is configured for the
same purpose. More then one discrete input is
configured to provide the same function.
Misconfigured Analog
Input an_cfg_alarm
Alarm Generated
Disable 4 selectable
analog inputs
Configure
correctly
More then one analog input is configured to
provide the same function.
OAT Sensor Alarm oat_alarm
Alarm Generated
Economizer and Low
ambient DX cooling
lockout disabled.
Automatic Faulty, shorted, or open thermistor caused by
wiring error or loose connection.
Space RH Sensor Alarm sprh_alarm
Alarm Generated
Dehumidification
disabled
Automatic Sensor reading is out of range. Bad sensor, bad
wiring, or sensor configured incorrectly.
Outdoor RH Sensor
Alarm oarh_alarm Alarm Generated Automatic Sensor reading is out of range. Bad sensor, bad
wiring, or sensor configured incorrectly.
High Space Humidity sprh_hi Alarm Generated Automatic IRH is greater then 70% for more then 10
minutes.
Low Space Humidity sprh_lo Alarm Generated Automatic IRH is less then 35% for more then 10 minutes.
IAQ Sensor Alarm iaq_alarm
Alarm Generated
Disables IAQ
Operation
Economizer moves
to minimum position
Automatic Sensor reading is out of range. Bad sensor, bad
wiring, or sensor configured incorrectly.
OAQ Sensor Alarm oaq_alarm Alarm Generated Set
OAQ to 400 Automatic Sensor reading is out of range. Bad sensor, bad
wiring, or sensor configured incorrectly.
High Carbon Dioxide
Level co2_hi Alarm Generated Automatic CO2 reading is above 1200ppm.
Supply Fan Runtime
Alarm sf_rntm Alarm Generated clear the
timer Supply fan run time exceeded user defined limit.
Compressor 1 Runtime
Alarm dx1_rntm Alarm Generated clear the
timer Compressor run time limit is exceeded.
Compressor 2 Runtime
Alarm dx2_rntm Alarm Generated clear the
timer Compressor run time limit is exceeded.
580J
47
Alarms
Alarms can be checked through the network and/or the
local access. All the alarms are listed in Table 18 with
name, object name, action taken by control, reset method,
and probable cause. There are help screens for each alarm
on the local access display and listed in RTU--MP
Controls, Start--Up, Operation, and Troubleshooting
Instructions (Form 48--50H--T--2T), Appendix A: Help
Screens. Some alarms are explained in detail below.
Safety Chain Alarm
This alarm occurs immediately if the supply--fan internal
overload trips or if an electric--heat limit switch trips. The
Unit Status will be Shutdown and the System Mode will
be Disable. When this happens LCTB (R terminal) will
not have 24 VAC, but the RTU--MP board will still be
powered. All unit operations stop immediately and will
not restart until the alarm automatically clears. There are
no configurations for this alarm; it is all based on internal
wiring. This alarm will never occur if Fire Shutdown
Alarm is active.
Fire Shutdown Alarm
This alarm occurs immediately when the smoke detector
senses smoke. The Unit Status will be Shutdown and the
System Mode will be Disable. All unit operations stop
immediately and will not restart until the alarm
automatically clears. If there is not a smoke detector
installed or the smoke detector did not trip, check input
configurations.
Space Temp Sensor Failure
This alarm occurs if the space sensor wired to the
RTU--MP is disconnected or shorted for more then 10
seconds. When this occurs the Unit Status will be
Shutdown and the System Mode will be Run. Sensor,
sensor connections, wiring, board connection, and
configurations should be checked for faults or errors.
Alarm will reset automatically when cause is fixed.
SAT Sensor Alarm
This alarm occurs immediately when the supply air
temperature sensor wired to the RTU--MP is disconnected
or shorted. When this occurs the Unit Status will be
Shutdown and the System Mode will be Run. Sensor,
sensor connections, wiring, board connection, and
configurations should be checked for faults or errors.
Alarm will reset automatically when cause is fixed.
Switch Configuration Alarm
This occurs if more than one binary input (inputs 3, 5, 8,
and 9) is configured for the same function. When this
happens the two inputs (or more) configured wrong will
be disabled as an inputs. This alarm will automatically be
cleared when configuration is corrected.
An example of this would be: Input 3 = Compressor
Safety, input 5 = Fan Status, input 8 = Fan Status, and
input 9 = Humidistat; the alarm would be active, unit
would run, compressor safety and humidistat would
function normally, and Fan Status (inputs 5 & 8) will be
interpreted as “No Function.”
Misconfigured Analog Input
This occurs if more than one analog input (inputs 1 & 2)
is configured for the same sensor. When this happens the
two inputs will be disabled as inputs. This alarm will
automatically be cleared when configuration is corrected.
An example of this would be: Input 1 = IAQ Sensor, input
2 = IAQ Sensor; the alarm would be active, unit would
run, but the IAQ Sensor (inputs 1 & 2) will be interpreted
as “No Function.”
Third Party Networking
Third party communication and networking
troubleshooting should be done by or with assistance from
the front end 3rd party technician. A Module Status
Report (Modstat) can be run from the BACview6,see
Table 19 to perform. This lists information about the
board status and networking state. For basic
troubleshooting, see Table 20. Refer to the RTU--MP 3rd
Party Integration Guide for additional information.
BACnet MS/TP
1. Verify that the BAS and controller are both set to
speak the BACnet MS/TP protocol. The protocol of
the controller is set via SW3 (switches 3, 4, 5, and 6).
The protocol can also be verified by getting a Modstat
of the controller through the BACview. Hit the “FN”
key and the ’.’ key at the same time to pull up a
Modstat. Scroll to the bottom of the page and there is
a section entitled “Network Communications.” The
active protocol and baud rate will be shown in this
section.
2. Verify that the BAS and controller are set for the
same baud rate. The baud rate of the controller is set
via SW3 (switches 1 and 2). The baud rate can also
be verified via the BACview by obtaining a Modstat.
(See Fig. 59.)
3. Verify that the BAS is configured to speak 2--wire
EIA--485 to the controller. The BAS may have to
configure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same
communication settings (8 data bits, No Parity, and 1
stop bit).
5. Verify that the controller has a unique MAC address
on the MS/TP bus. The controllers MS/TP MAC
address is set by its rotary address switches.
6. Verify proper wiring between the BAS and the
controller.
7. Verify that the BAS is reading or writing to the proper
BACnet objects in the controller. Download the latest
points list for the controller to verify.
8. Verify that the BAS is sending his requests to the
proper MS/TP MAC address of our controller.
9. Present the BAS company with a copy of our
controllers BACnet PICS so that they know which
BACnet commands are supported.
580J
48
Device Instance: 0160001
1 PRGs loaded. 1 PRGs running.
Module status:
Firmware sections validated in flash memory
============================================
Boot16-H - v2.06:001 Jun 19 2007
RTU-MP DRIVER - v2.09:050 Jun 26 2007
Reset counters:
11 Power failures
0 Brownouts
18 Commanded warm boots
22 Commanded cold boots
0 System errors
0 Watchdog timeouts
System error message history: Type Specific
Warning message history:
Information message history:
POWERUP: BACnet reinitialize warmstart 06/29/07 10:49:40
Menu file not found. 06/29/07 10:48:35
ARC156 reconfigurations during the last hour (cleared upon reset):
Total ....................... 0
Initiated by this node ...... 0
Core board hardware:
Type=147, board=34, manufactured on 05/14/2007, S/N 21A740188N
RAM: 1024 kBytes; FLASH: 1024 kBytes, type = 3
Base board hardware:
Type=147, board=71, manufactured on 05/14/2007, S/N RMP750037N
Largest free heap space = 65536.
Database size = 742082 , used = 352162, free = 389920.
Raw physical switches: 0x01280000
Module Communications:
Network Protocol=BACnet MSTP Master
Network Baud Rate=9600 bps
C07195
Fig. 59 -- Module Status Report (Modstat) Example
10. In certain situations, it may be necessary to tweak the
MS/TP Protocol timing settings through the
BACview6. There are two settings that may be
tweaked:
SMax Masters: Defines the highest MS/TP Master
MAC address on this MS/TP network. For example, if
there are 3 master nodes on an MS/TP network, and
their MAC addresses are 1, 8, and 16, then Max
Masters would be set to 16 (since this is the highest
MS/TP MAC address on the network). This property
optimizes MS/TP network communications by
preventing token passes and “poll for master” requests
to non--existent Master nodes (i.e., in the above
example, MAC address 16 would know to pass the
token back to MAC address 1 instead of counting up to
MAC address 127).
Each MS/TP master node on the network must have
their Max Masters set to this same value. The default is
127.
SMaxInfo Frames: This property defines the maximum
number of responses that will be sent when our
controller gets the token. A valid number is any
positive integer. The default is 10 and should be ideal
for the majority of applications. In cases where the
controller is the target of many requests, this number
could be increased as high as 100 or 200.
NOTE: MS/TP networks can be comprised of both
Master and Slave nodes. Valid MAC addresses for Master
nodes are 0 -- 127 and valid addresses for Slave nodes are
0 -- 254.
NOTE: See RTU--MP 3rd Party Integration Guide (or
alternatively RTU--MP Controls, Start--Up, Operation, and
Troubleshooting Instructions (Form 48--50H--T--2T)
Appendix) for Protocol Maps.
580J
49
Table 19 – Manufacture Date
When troubleshooting, you may need to know a control modules manufacture date
Obtain the manufacture date from
a...
Notes
Module status report (modstat) To obtain a modstat with BACview6:
1. Press Function (FN) key and hold.
2. Then press period (.)
3. Release both buttons.
ThereportshowsthedateunderMain board hardware.
Sticker on the back of the main control
module board
”Serial No: RMPYMxxxxN”
(Bar Coded & Typed Number)
The serial numbers are unique and contain embedded information:
“RMP” --- These first three digits are unique to RTU--- MP and are used as an identifier.
“YM” --- These two digits identify the last digit of the year and month (in hex, A=10/Oct)
of manufacture. ”74” would represent a date of manufacture of ”April 2007”.
xxxx” --- These four digits represent the sequential number of units produced for a given
product for the mentioned manufacturing time period.
“N” --- This final digit represents the decade and toggles between ”N” and ”M” every
ten years.
Table 20 – Basic Protocol Troubleshooting
Problem Possible cause Corrective action
No communication with 3rd
party vendor
Incorrect settings on SW1, SW2 and SW3 Verify and correct switch settings. Cycle
powertoRTU---MPafterchangingswitch
settings.
RS485 Port has no voltage output Verify RTU--- MP has correct power supply
(check with RTU---MP disconnected from RS485
communication bus)
Possible bad driver on board.
Bacnet @ 9600/19.2K --- .01 to .045vdc Check RS485 bus for external before
reconnecting to the bus
Bacnet @ 38.4K --- .06 to .09vdc Voltage, shorts or grounding
Bacnet @ 76.8K --- .1vdc before reconnecting to the bus
Modbus @ 9600 --- 76.8K --- .124vdc
N2 @ 9600 --- .124vdc
Verify devices are daisy chained and repeaters and bias
terminators are correctly installed
Check 3rd party vendor RS485
communication wiring guidelines and
troubleshooting procedures
Table 21 – Modbus Exception Codes that May be
Returned From This Controller
CODE NAME MEANING
01 Illegal Function
The Modbus function code used
in the query is not supported by
the controller.
02 Illegal Data Address
The register address used in the
query is not supported by the
controller.
04 SlaveDeviceFailure
The Modbus Master has
attempted to write to a
non--- existent register or a
read--- only register in the
controller.
Modbus
1. Verify that the BAS and controller are both set to
speak the Modbus RTU protocol. The protocol of the
controller is set via SW3 (switches 3, 4, 5, and 6).
The protocol can also be verified by getting a Modstat
of the controller through the BACview. Hit the ”FN”
key and the ’.’ key at the same time to pull up a
Modstat. Scroll to the bottom of the page and there is
a section entitled “Network Communications.” The
active protocol and baud rate will be shown in this
section.
2. Verify that the BAS and controller are set for the
same baud rate. The baud rate of the controller is set
via SW3 (switches 1 and 2). The baud rate can also
be verified via the BACview by obtaining a Modstat
(See Fig. 59).
3. Verify that the BAS is configured to speak 2--wire
EIA--485 to the controller. The BAS may have to
configure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same
communication settings (8 data bits, No Parity, and 1
stop bit).
5. Verify that the controller has a unique Modbus slave
address. The controllers Modbus slave address is set
by its rotary address switches.
6. Verify that the BAS is using the proper Modbus
function codes to access data from our controller.
Supported function codes are shown above.
7. Verify proper wiring between the BAS and the
controller.
8. Verify that the BAS is reading or writing to the proper
Modbus register numbers on the controller. Download
the latest points list for the controller to verify.
9. Verify that the BAS is sending his requests to the
proper slave address of our controller.
580J
50
NOTE: See RTU--MP 3rd Party Integration Guide (or
alternatively RTU--MP 3rd Party Integration Guide (or
alternatively RTU--MP Controls, Start--Up, Operation, and
Troubleshooting Instructions (Form 48--50H--T--2T),
Appendix) for Modbus Protocol Conformance Statement.
N2
1. Verify that the BAS and controller are both set to
speak the N2 protocol. The protocol of the controller
is set via SW3 (switches 3, 4, 5, and 6). The protocol
can also be verified by getting a Modstat of the
controller through the BACview. Hit the “FN” key
and the ’.’ key at the same time to pull up a Modstat.
Scroll to the bottom of the page and there is a section
entitled ”Network Communications.” The active
protocol and baud rate will be shown in this section.
2. Verify that the BAS and controller are set for 9600
baud. The baud rate of the controller is set via SW3
(switches 1 and 2). The baud rate can also be verified
via the BACview by obtaining a Modstat. (See Fig.
59.)
3. Verify that the BAS is configured to speak 2--wire
EIA--485 to the controller. The BAS may have to
configure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same
communication settings (8 data bits, No Parity, and 1
stop bit).
5. Verify that the controller has a unique N2 slave
address on the N2 bus. The controllers N2 slave
address is set by its rotary address switches.
6. Verify proper wiring between the BAS and the
controller.
7. Verify that the BAS is reading or writing to the proper
network point addresses on the controller. Download
the latest points list for the controller to verify.
8. Verify that the BAS is sending his requests to the
proper slave address of our controller.
NOTE: See RTU--MP 3rd Party Integration Guide (or
alternatively RTU--MP 3rd Party Integration Guide (or
alternatively RTU--MP Controls, Start--Up, Operation, and
Troubleshooting Instructions (Form 48--50H--T--2T)
Appendix) for N2 Protocol Conformance Statement.
ECONOMI$ER SYSTEMS
The 580J units may be equipped with a factory--installed
or accessory (field--installed) economizer system. Two
types are available: with a logic control system
(EconoMi$er IV) and without a control system
(EconoMi$er2, for use with external control systems). See
Fig. 60 and Fig. 61 for component locations on each type.
See Fig. 62 and Fig. 63 for economizer section wiring
diagrams.
Both EconoMi$ers use direct--drive damper actuators.
ECONOMI$ER IV
CONTROLLER
WIRING
HARNESS
ACTUATOR
(HIDDEN)
LOW TEMPERATURE
COMPRESSOR
LOCKOUT SWITCH
OUTSIDE AIR
TEMPERATURE SENSOR
(OPERATING LOCATION)
C07367
Fig. 60 -- EconoMi$er IV Component Locations
ECONOMI$ER2
PLUG
BAROMETRIC
RELIEF
DAMPER
OUTDOOR
AIR HOOD
HOOD
SHIPPING
BRACKET
GEAR DRIVEN
DAMPER
C06022
Fig. 61 -- EconoMi$er2 Component Locations
580J
51
C09023
Fig. 62 -- EconoMi$er IV Wiring
4
3
5
2
8
6
7
1
10
11
9
12
PINK
VIOLET
BLACK
BLUE
YELLOW
NOTE 1
NOTE 3
RUN
500 OHM
RESISTOR
50HJ540573
ACTUATOR
ASSEMBLY
RED
WHITE
ECONOMISER2 PLUG
DIRECT DRIVE
ACTUATOR 4-20mA SIGNAL
OAT SENSOR 24 VAC
TRANSFORMER
GROUND
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
2.
Fig. 63 -- EconoMi$er2 with 4 to 20 mA Control Wiring
C09223
580J
52
Table 22 – EconoMi$er IV Input/Output Logic
INPUTS OUTPUTS
Demand Control
Ventilation (DCV)
Enthalpy*
Y1 Y2
Compressor NTerminal
Outdoor Return Stage
1
Stage
2
Occupied Unoccupied
Damper
Below set
(DCV LED Off)
High
(Free Cooling LED
Off)
Low
On On On On
Minimum position ClosedOn Off On Off
Off Off Off Off
Low
(Free Cooling LED
On)
High
On On On Off Modulating** (between
min. position and
full-open)
Modulating**
(between closed and
full-open)
On Off Off Off
Off Off Off Off Minimum position Closed
Above set
(DCV LED On)
High
(Free Cooling LED
Off)
Low
On On On On Modulating†† (between
min. position and DCV
maximum)
Modulating††
(between closed and
DCV
maximum)
On Off On Off
Off Off Off Off
Low
(Free Cooling LED
On)
High
On On On Off
Modulating*** Modulating†††On Off Off Off
Off Off Off Off
* For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
** Modulation is based on the supply-air sensor signal.
†† Modulation is based on the DCV signal.
*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV)
or fully open (supply-air signal).
†† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
C06053
Fig. 64 -- EconoMi$er IV Functional View
EconoMi$er IV
Table 22 provides a summary of EconoMi$er IV.
Troubleshooting instructions are enclosed.
A functional view of the EconoMi$er is shown in Fig. 64.
Typical settings, sensor ranges, and jumper positions are
also shown. An EconoMi$er IV simulator program is
available from Bryant to help with EconoMi$er IV
training and troubleshooting.
EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10
to 20 mA device used to measure the outdoor-air
temperature. The outdoor-air temperature is used to
determine when the EconoMi$er IV can be used for free
cooling. The sensor is factory-installed on the
EconoMi$er IV in the outdoor airstream. (See Fig. 60.)
The operating range of temperature measurement is 40_to
100_F(4_to 38_C). (See Fig. 67.)
580J
53
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. (See Fig. 65.) This
sensor is factory installed. The operating range of
temperature measurement is 0°to 158_F(--18_to 70_C).
See Table 16 for sensor temperature/resistance values.
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
C06033
Fig. 65 -- Supply Air Sensor Location
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp
end” and is sealed from moisture.
Outdoor Air Lockout Sensor
The EconoMi$er IV is equipped with an ambient
temperature lockout switch located in the outdoor
airstream which is used to lock out the compressors below
a42_F(6_C) ambient temperature. (See Fig. 60.)
EconoMi$er IV Control Modes
IMPORTANT: The optional EconoMi$er2 does not
include a controller. The EconoMi$er2 is operated by a 4
to 20 mA signal from an existing field-supplied controller.
See Fig. 63 for wiring information.
Determine the EconoMi$er IV control mode before set up
of the control. Some modes of operation may require
different sensors. (See Table 22.) The EconoMi$er IV is
supplied from the factory with a supply-air temperature
sensor and an outdoor-air temperature sensor. This allows
for operation of the EconoMi$er IV with outdoor air dry
bulb changeover control. Additional accessories can be
added to allow for different types of changeover control
and operation of the EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory
configured for outdoor dry bulb changeover control. The
outdoor air and supply air temperature sensors are
included as standard. For this control mode, the outdoor
temperature is compared to an adjustable setpoint selected
on the control. If the outdoor-air temperature is above the
setpoint, the EconoMi$er IV will adjust the outside air
dampers to minimum position. If the outdoor-air
temperature is below the setpoint, the position of the
outside air dampers will be controlled to provided free
cooling using outdoor air. When in this mode, the LED
next to the free cooling setpoint potentiometer will be on.
The changeover temperature setpoint is controlled by the
free cooling setpoint potentiometer located on the control.
(See Fig. 66.)
The scale on the potentiometer is A, B, C, and D. See Fig.
63 for the corresponding temperature changeover values.
C06034
Fig. 66 -- EconoMi$er IV Controller Potentiometer
and LED Locations
LED ON
LED ON
LED ON
LED ON
LED OFF
19
18
LED OFF
LED OFF
LED OFF
17
16
15
14
13
12
11
10
9
40 45 50 55 60 65 70 75 80 85 90 95 100
DEGREES FAHRENHEIT
mA
D
C
B
A
C06035
Fig. 67 -- Outside Air Temperature Changeover
Setpoints
0
5
10
15
20
25
30
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
C06031
Fig. 68 -- Outdoor--Air Damper Leakage
580J
54
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional
accessory dry bulb sensor (part number
CRTEMPSN002A00). The accessory sensor must be
mounted in the return airstream. (See Fig. 69.) Wiring is
provided in the EconoMi$er IV wiring harness. (See Fig.
62.)
ECONOMI$ERIV
ECONOMI$ERIV
CONTROLLER
GROMMET
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
C07085
Fig. 69 -- Return Air Temperature or Enthalpy Sensor
Mounting Location
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower
temperature airstream is used for cooling. When using this
mode of changeover control, turn the enthalpy setpoint
potentiometer fully clockwise to the D setting. (See Fig.
66.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part
number HH57AC078) is required. Replace the standard
outdoor dry bulb temperature sensor with the accessory
enthalpy sensor in the same mounting location. (See Fig.
69.) When the outdoor air enthalpy rises above the
outdoor enthalpy changeover setpoint, the outdoor-air
damper moves to its minimum position. The outdoor
enthalpy changeover setpoint is set with the outdoor
enthalpy setpoint potentiometer on the EconoMi$er IV
controller. The setpoints are A, B, C, and D. (See Fig. 70.)
The factory-installed 620-ohm jumper must be in place
across terminals SRand SR+ on the EconoMi$er IV
controller.
CONTROL
CURVE
A
B
C
D
CONTROL POINT
APPROX.
deg. F (deg. C)
AT 50% RH
73 (23)
70 (21)
67 (19)
63 (17)
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
90
100
80
70
60
50
40
30
20
10
ENTHALPY BTU PER POUND DRY AIR
85
(29)
90
(32)
95
(35)
100
(38)
105
(41)
110
(43)
35
(2)
35
(2)
40
(4)
40
(4)
105
(41)
110
(43)
45
(7)
45
(7)
50
(10)
50
(10)
55
(13)
55
(13)
60
(16)
60
(16)
65
(18)
65
(18)
70
(21)
70
(21)
75
(24)
75
(24)
80
(27)
80
(27)
85
(29)
90
(32)
95
(35)
100
(38)
A
A
B
B
C
C
D
D
RELATIVE HUMIDITY (%)
HIGH LIMIT
CURVE
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
C06037
Fig. 70 -- Enthalpy Changeover Setpoints
580J
55
TR1
24 Vac
COM
TR
24
Va c
HOT
12
34
5
EF EF1
+_
P1
T1
P
T
N
EXH
2V 10V
EXH
Set
Set
2V 10V
2V 10V
DCV
DCV
Free
Cool
BC
AD
SO+
SR+
SR
SO
AQ1
AQ
DCV
Min
Pos
Open
Max
N1
C06038
Fig. 71 -- EconoMi$er IV Control
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV
controller uses two enthalpy sensors (HH57AC078 and
CRENTDIF004A00), one in the outside air and one in the
return air duct. The EconoMi$er IV controller compares
the outdoor air enthalpy to the return air enthalpy to
determine EconoMi$er IV use. The controller selects the
lower enthalpy air (return or outdoor) for cooling. For
example, when the outdoor air has a lower enthalpy than
the return air, the EconoMi$er IV opens to bring in
outdoor air for free cooling.
Replace the standard outside air dry bulb temperature
sensor with the accessory enthalpy sensor in the same
mounting location. (See Fig. 60.) Mount the return air
enthalpy sensor in the return air duct. (See Fig. 69.)
Wiring is provided in the EconoMi$er IV wiring harness.
(See Fig. 62.) The outdoor enthalpy changeover setpoint is
set with the outdoor enthalpy setpoint potentiometer on
the EconoMi$er IV controller. When using this mode of
changeover control, turn the enthalpy setpoint
potentiometer fully clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation
control based on the level of CO2measured in the space
or return air duct.
There is both a factory-installed (FIOP) CO2option
(sensor 8001B with no display, which is mounted on the
side of the EconoMi$er) and a field-installed CO2option
(sensor 8002 with display, which is mounted on the return
air duct). While performing the same function, they differ
in their ability to be configured. The FIOP version is
preset and requires no changes in most applications. If a
configuration change is required, service kit #UIP2072
(software CD, cables, and instructions) and a laptop PC
are required. The field-installed version with display can
be configured stand-alone. (See section “CO2Sensor
Configuration”).
Mount the accessory IAQ sensor according to
manufacturer specifications. The IAQ sensor should be
wired to the AQ and AQ1 terminals of the controller.
Adjust the DCV potentiometers to correspond to the DCV
voltage output of the indoor air quality sensor at the
user-determined setpoint. (See Fig. 72.)
0
1000
2000
3000
4000
5000
6000
2345678
800 ppm
900 ppm
1000 ppm
1100 ppm
RANGE CONFIGURATION (ppm)
DAMPER VOLTAGE FOR MAX VENTILATION RATE
CO SENSOR MAX RANGE SETTING
2
C06039
Fig. 72 -- CO2Sensor Maximum Range Settings
If a separate field-supplied transformer is used to power
the IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for
VOC (volatile organic compounds) ventilation
requirements. The maximum demand ventilation position
is used for fully occupied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand
ventilation position should be turned fully clockwise.
Exhaust Setpoint Adjustment
The exhaust setpoint will determine when the exhaust fan
runs based on damper position (if accessory power
exhaust is installed). The setpoint is modified with the
Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig.
66.) The setpoint represents the damper position above
which the exhaust fans will be turned on. When there is a
call for exhaust, the EconoMi$er IV controller provides a
45 ±15 second delay before exhaust fan activation to
allow the dampers to open. This delay allows the damper
to reach the appropriate position to avoid unnecessary fan
overload.
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. (See Fig. 66.) The minimum
damper position maintains the minimum airflow into the
building during the occupied period.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for
VOC (volatile organic compound) ventilation
requirements. The maximum demand ventilation position
is used for fully occupied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand
ventilation position should be turned fully clockwise.
580J
56
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local
codes, to enter the building. Make minimum position
adjustments with at least 10_F temperature difference
between the outdoor and return-air temperatures.
To determine the minimum position setting, perform the
following procedure:
1. Calculate the appropriate mixed air temperature
using the following formula:
(TOx
OA )+(TRxRA )=T
M
100 100
TO= Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR= Return-Air Temperature
RA = Percent of Return Air
TM= Mixed-Air Temperature
As an example, if local codes require 10% outdoor
air during occupied conditions, outdoor-air
temperature is 60_F, and return-air temperature is
75_F.
(60 x .10) + (75 x .90) = 73.5_F
2. Disconnect the supply air sensor from terminals T
and T1.
3. Ensure that the factory-installed jumper is in place
across terminals P and P1. If remote damper
positioning is being used, make sure that the
terminals are wired according to Fig. 62 and that the
minimum position potentiometer is turned fully
clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position
potentiometer until the measured mixed air
temperature matches the calculated value.
6. Reconnect the supply air sensor to terminals T and
T1.
Remote control of the EconoMi$er IV damper is desirable
when requiring additional temporary ventilation. If a
field-supplied remote potentiometer (Honeywell part
number S963B1128) is wired to the EconoMi$er IV
controller, the minimum position of the damper can be
controlled from a remote location.
To control the minimum damper position remotely,
remove the factory-installed jumper on the P and P1
terminals on the EconoMi$er IV controller. Wire the
field-supplied potentiometer to the P and P1 terminals on
the EconoMi$er IV controller. (See Fig. 62.)
Damper Movement
Damper movement from full open to full closed (or vice
versa) takes 2-1/2minutes.
Thermostats
The EconoMi$er IV control works with conventional
thermostats that have a Y1 (cool stage 1), Y2 (cool stage
2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er IV control does not support space
temperature sensors. Connections are made at the
thermostat terminal connection board located in the main
control box.
Demand Control Ventilation (DCV)
When using the EconoMi$er IV for demand controlled
ventilation, there are some equipment selection criteria
which should be considered. When selecting the heat
capacity and cool capacity of the equipment, the
maximum ventilation rate must be evaluated for design
conditions. The maximum damper position must be
calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the
required ventilation rate means the equipment can
condition air at a maximum ventilation rate that is greater
than the required ventilation rate for maximum
occupancy. A proportional-anticipatory strategy will cause
the fresh air supplied to increase as the room CO2level
increases even though the CO2setpoint has not been
reached. By the time the CO2level reaches the setpoint,
the damper will be at maximum ventilation and should
maintain the setpoint.
In order to have the CO2sensor control the economizer
damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation
is the ventilation required to remove contaminants during
unoccupied periods. The following equation may be used
to determine the percent of outside air entering the
building for a given damper position. For best results there
should be at least a 10 degree difference in outside and
return-air temperatures.
(TOx
OA )+(TRxRA )=T
M
100 100
TO= Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR= Return-Air Temperature
RA = Percent of Return Air
TM= Mixed-Air Temperature
Once base ventilation has been determined, set the
minimum damper position potentiometer to the correct
position.
580J
57
The same equation can be used to determine the occupied
or maximum ventilation rate to the building. For example,
an output of 3.6 volts to the actuator provides a base
ventilation rate of 5% and an output of 6.7 volts provides
the maximum ventilation rate of 20% (or base plus 15 cfm
per person). Use Fig. 72 to determine the maximum
setting of the CO2sensor. For example, an 1100 ppm
setpoint relates to a 15 cfm per person design. Use the
1100 ppm curve on Fig. 72 to find the point when the CO2
sensor output will be 6.7 volts. Line up the point on the
graph with the left side of the chart to determine that the
range configuration for the CO2sensor should be 1800
ppm. The EconoMi$er IV controller will output the 6.7
volts from the CO2sensor to the actuator when the CO2
concentration in the space is at 1100 ppm. The DCV
setpoint may be left at 2 volts since the CO2sensor
voltage will be ignored by the EconoMi$er IV controller
until it rises above the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been
determined, set the maximum damper demand control
ventilation potentiometer to this position. Do not set to the
maximum position as this can result in over-ventilation to
the space and potential high humidity levels.
CO2Sensor Configuration
The CO2sensor has preset standard voltage settings that
can be selected anytime after the sensor is powered up.
(See Table 23.)
Use setting 1 or 2 for Bryant equipment. (See Table 23.)
1. Press Clear and Mode buttons. Hold at least 5
seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
Table23–CO
2Sensor Standard Settings
SETTING EQUIPMENT OUTPUT
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
CO2
CONTROL
RANGE
(ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
1
Interface w/Standard
Building Control System
Proportional Any 0 --- 1 0 V
4 --- 2 0 m A 0---2000 1000 50
2Proportional Any 2 --- 1 0 V
7 --- 2 0 m A 0---2000 1000 50
3Exponential Any 0 --- 1 0 V
4 --- 2 0 m A 0---2000 1100 50
4
Economizer
Proportional 15 0 --- 1 0 V
4 --- 2 0 m A 0---1100 1100 50
5Proportional 20 0 --- 1 0 V
4 --- 2 0 m A 0 --- 9 0 0 900 50
6Exponential 15 0 --- 1 0 V
4 --- 2 0 m A 0---1100 1100 50
7Exponential 20 0 --- 1 0 V
4 --- 2 0 m A 0 --- 9 0 0 900 50
8Health & Safety Proportional 0 --- 1 0 V
4 --- 2 0 m A 0---9999 5000 500
9Parking/Air Intakes/
Loading Docks Proportional 0 --- 1 0 V
4 --- 2 0 m A 0---2000 700 50
580J
58
Table 24 – EconoMi$er IV Sensor Usage
APPLICATION
ECONOMI$ER IV WITH OUTDOOR AIR DRY
BULB SENSOR
Accessories Required
Outdoor Air
Dry Bulb
None. The outdoor air dry bulb sensor is
factory installed.
Differential
Dry Bulb CRTEMPSN002A00*
Single Enthalpy HH57AC078
Differential
Enthalpy HH57AC078 and CRENTDIF004A00*
CO2for DCV
Control using a
Wall-Mounted
CO2Sensor
33ZCSENCO2
CO2for DCV
Control using a
Duct-Mounted
CO2Sensor
33ZCSENCO2† and
33ZCASPCO2**
O
RCRCBDIOX005A00††
* CRENTDIF004A00 and CRTEMPSN002A00 accessories are
used on many different base units. As such, these kits may
contain parts that will not be needed for installation.
33ZCSENCO2 is an accessory CO2sensor.
** 33ZCASPCO2 is an accessory aspirator box required for
duct-mounted applications.
†† CRCBDIOX005A00 is an accessory that contains both
33ZCSENCO2 and 33ZCASPCO2 accessories.
3. Use the Up/Down button to select the preset
number. (See Table 23.)
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO2sensor can be changed
anytime after the sensor is energized. Follow the steps
below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5
seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
Dehumidification of Fresh Air with DCV (Demand
Controlled Ventilation) Control
If normal rooftop heating and cooling operation is not
adequate for the outdoor humidity level, an energy
recovery unit and/or a dehumidification option should be
considered.
EconoMi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9--v battery, 1.2
kilo--ohm resistor, and a 5.6 kilo--ohm resistor which are
not supplied with the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all
potentiometers before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should
be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo--ohm
resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and +.
Connect 1.2 kilo--ohm 4074EJM checkout resistor
across terminals SO and +.
8. Put 620--ohm resistor across terminals SR and +.
9. Set minimum position, DCV setpoint, and exhaust
potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential Enthalpy
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Place 620--ohm resistor across SO and +.
3. Place 1.2 kilo--ohm resistor across SR and +. The
Free Cool LED should be lit.
4. Remove 620--ohm resistor across SO and +. The Free
Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Single Enthalpy
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The
Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
DCV (Demand Controlled Ventilation) and Power
Exhaust
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator
should be fully closed.
3. Connect a 9--v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between
90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator
should remain in position.
580J
59
5. Turn the DCV setpoint potentiometer CW until the
DCV LED turns off. The DCV LED should turn off
when the potentiometer is approximately 9--v. The
actuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until
the Exhaust LED turns on. The exhaust contacts will
close 30 to 120 seconds after the Exhaust LED turns
on.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Connect a 9--v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20
and 80% open.
4. Turn the DCV Maximum Position potentiometer to
fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to
midpoint. The actuator should drive to between 20
and 80% open.
6. Turn the Minimum Position Potentiometer fully CW.
The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator
should drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Supply--Air Sensor Input
To check supply--air sensor input:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool
LED turns on. The actuator should drive to between
20 and 80% open.
3. Remove the 5.6 kilo--ohm resistor and jumper T to
T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator
should drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to
operation. No troubleshooting or testing is done by
performing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to
previous setting.
4. Set minimum position, DCV setpoint, and exhaust
potentiometers to previous settings.
5. Remove 620--ohm resistor from terminals SR and +.
6. Remove 1.2 kilo--ohm checkout resistor from
terminals SO and +. If used, reconnect sensor from
terminals SO and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo--ohm resistor from T and T1.
Reconnect wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P
and P1.
11. Apply power (24 vac) to terminals TR and TR1.
WIRING DIAGRAMS
See Fig. 73 and 74 for typical wiring diagrams.
580J
60
C09156
Fig. 73 -- 580J Typical Unit Wiring Diagram -- Power (08D,F, 208/230--3--60)
580J
61
C09157
Fig. 74 -- 580J Typical Unit Wiring Diagram -- Control (08--12D,F, 208/230--3--60)
580J
62
PRE--START--UP
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal
injury or death.
1. Follow recognized safety practices and wear
protective goggles when checking or servicing
refrigerant system.
2. Do not operate compressor or provide any electric
power to unit unless compressor terminal cover is
in place and secured.
3. Do not remove compressor terminal cover until
all electrical sources are disconnected.
4. Relieve all pressure from system before touching
or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor
terminals.
5. Never attempt to repair soldered connection while
refrigerant system is under pressure.
6. Do not use torch to remove any component.
System contains oil and refrigerant under
pressure. To remove a component, wear
protective goggles and proceed as follows:
a. Shut off electrical power and then gas to unit.
b. Recover refrigerant to relieve all pressure from
system using both high--pressure and low
pressure ports.
c. Cut component connection tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs
when necessary. Oil can ignite when exposed
to torch flame.
!WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
The unit must be electrically grounded in accordance
with local codes and NEC ANSI/NFPA 70 (American
National Standards Institute/National Fire Protection
Association).
!WARNING
Proceed as follows to inspect and prepare the unit for
initial start--up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to,
or shipped with, unit.
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
!WARNING
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected
wires, etc.
b. Inspect for oil at all refrigerant tubing
connections and on unit base. Detecting oil
generally indicates a refrigerant leak. Leak--test
all refrigerant tubing connections using
electronic leak detector, halide torch, or
liquid--soap solution.
c. Inspect all field--wiring and factory--wiring
connections. Be sure that connections are
completed and tight. Be sure that wires are not
in contact with refrigerant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin
comb.
4. Verify the following conditions:
a. Make sure that condenser--fan blade are correctly
positioned in fan orifice. See Condenser--Fan
Adjustment section for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START--UP, GENERAL
Unit Preparation
Make sure that unit has been installed in accordance with
installation instructions and applicable codes.
Gas Piping
Check gas piping for leaks.
580J
63
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect gas piping from unit when leak testing at
pressure greater than 1/2 psig. Pressures greater than
1/2 psig will cause gas valve damage resulting in
hazardous condition. If gas valve is subjected to
pressure greater than 1/2 psig, it must be replaced
before use. When pressure testing field--supplied gas
piping at pressures of 1/2 psig or less, a unit connected
to such piping must be isolated by manually closing
the gas valve.
!WARNING
Return--Air Filters
Make sure correct filters are installed in unit (see
Appendix II -- Physical Data). Do not operate unit without
return--air filters.
Outdoor--Air Inlet Screens
Outdoor--air inlet screen must be in place before operating
unit.
Compressor Mounting
Compressors are internally spring mounted. Do not loosen
or remove compressor hold down bolts.
Internal Wiring
Check all factory and field electrical connections for
tightness. Tighten as required.
Refrigerant Service Ports
Each unit system has two 1/4” SAE flare (with check
valves) service ports: one on the suction line, and one on
the compressor discharge line. Be sure that caps on the
ports are tight.
Compressor Rotation
On 3--phase units with scroll compressors, it is important
to be certain compressor is rotating in the proper
direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect service gauges to suction and discharge
pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start--up.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating
in the wrong direction.
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Re--energize to the compressor. Check pressures.
The suction and discharge pressure levels should now
move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong
direction, the unit will make an elevated level of noise
and will not provide cooling.
Cooling
Set space thermostat to OFF position. To start unit, turn on
main power supply. Set system selector switch at COOL
position and fan switch at AUTO. position. Adjust
thermostat to a setting approximately 5_F(3_C) below
room temperature. Both compressors start on closure of
contactors.
Check unit charge. Refer to Refrigerant Charge section.
Reset thermostat at a position above room temperature.
Both compressors will shut off. Evaporator fan will shut
off immediately.
To shut off unit, set system selector switch at OFF
position. Resetting thermostat at a position above room
temperature shuts unit off temporarily until space
temperature exceeds thermostat setting.
Main Burners
Main burners are factory set and should require no
adjustment.
To check ignition of main burners and heating controls,
move thermostat setpoint above room temperature and
verify that the burners light and evaporator fan is
energized. Check heating effect, then lower the thermostat
setting below the room temperature and verify that the
burners and evaporator fan turn off.
Refer to Table 11 for the correct orifice to use at high
altitudes.
Heating
1. Purge gas supply line of air by opening union ahead
of the gas valve. If gas odor is detected, tighten union
and wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating
temperature lever above room temperature.
4. The induced--draft motor will start.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then
there is a 22--second delay before another 5--second
try. If the burner still does not light, the time delay is
repeated. If the burner does not light within 15
minutes, there is a lockout. To reset the control, break
the 24 v power to W1.
6. The evaporator--fan motor will turn on 45 seconds
after burner ignition.
7. The evaporator--fan motor will turn off in 45 seconds
after the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate.
580J
64
NOTE: The default value for the evaporator--fan motor
on/off delay is 45 seconds. The Integrated Gas Unit
Controller (IGC) modifies this value when abnormal limit
switch cycles occur. Based upon unit operating conditions,
the on delay can be reduced to 0 seconds and the off delay
can be extended to 180 seconds.
If the limit switch trips at the start of the heating cycle
during the evaporator on delay, the time period of the on
delay for the next cycle will be 5 seconds less than the
time at which the switch tripped. (Example: If the limit
switch trips at 30 seconds, the evaporator--fan on delay for
the next cycle will occur at 25 seconds.) To prevent
short--cycling, a 5--second reduction will only occur if a
minimum of 10 minutes has elapsed since the last call for
heating.
The evaporator--fan off delay can also be modified. Once
the call for heating has ended, there is a 10--minute period
during which the modification can occur. If the limit
switch trips during this period, the evaporator--fan off
delay will increase by 15 seconds. A maximum of 9 trips
can occur, extending the evaporator-fan off delay to 180
seconds.
To restore the original default value, reset the power to the
unit.
To shut off unit, set system selector switch at OFF
position. Resetting heating selector lever below room
temperature will temporarily shut unit off until space
temperature falls below thermostat setting.
Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF
positions, respectively. Evaporator fan operates
continuously to provide constant air circulation. When the
evaporator-fan selector switch is turned to the OFF
position, there is a 30--second delay before the fan turns
off.
START--UP, RTU--MP CONTROL
Field Service Test, explained below, will assist in proper
start--up. Configuration of unit parameters, scheduling
options, and operation are also discussed in this section.
Field Service Test
The Field Service Test function can be used to verify
proper operation of compressors, heating stages, indoor
fan, power exhaust fans, economizer, and
dehumidification. Use of Field Service Test is
recommended at initial system start up and during
troubleshooting. See RTU--MP Controls, Start--Up,
Operation, and Troubleshooting Instructions (Form
48--50H--T--2T), Appendix A for Field Service Test Mode
table.
Field Service Test mode has the following changes from
normal operation:
SOutdoor air temperature limits for cooling circuits,
economizer, and heating are ignored.
SNormal compressor time guards and other staging delays
are ignored.
SThe status of Alarms (except Fire and Safety chain) is
ignored but all alerts and alarms are still broadcasted on
the network.
Field Service Test can be turned ON/OFF at the unit
display or from the network. Once turned ON, other
entries may be made with the display or through the
network. To turn Field Service Test on, change the value
of Test Mode to ON, to turn Field Service Test off, change
the value of Test Mode to OFF.
NOTE: Service Test mode is password protected when
accessing from the display. Depending on the unit model,
factory--installed options, and field--installed accessories,
some of the Field Service Test functions may not apply.
The independent outputs (IndpOutputs) submenu is used
to change output status for the supply fan, economizer,
and Power Exhaust. These independent outputs can
operate simultaneously with other Field Service Test
modes. All outputs return to normal operation when Field
Service Test is turned off.
The Cooling submenu is used to change output status for
the individual compressors and the dehumidification relay.
Compressor starts are not staggered. The fans and heating
service test outputs are reset to OFF for the cooling
service test. Indoor fans and outdoor fans are controlled
normally to maintain proper unit operation. All normal
cooling alarms and alerts are functional.
NOTE: Circuit A is always operated with Circuit B due
to outdoor fan control on Circuit A. Always test Circuit A
first, and leave it on to test other Circuits.
The Heating submenu is used to change output status for
the individual heat stages, gas or electric. The fans and
cooling service test outputs are reset to OFF for the
heating service test. All normal heating alarms and alerts
are functional.
Configuration
The RTU--MP controller configuration points affect the
unit operation and/or control. Review and understand the
meaning and purpose of each configuration point before
changing it from the factory default value. The submenus
containing configuration points are as follows: Unit,
Cooling, Heating, Inputs, Economizer, IAQ, Clock--Set,
and User Password (USERPW). Each configuration point
is described below under its according submenu. See
RTU--MP Controls, Start--Up, Operation, and
Troubleshooting Instructions (Form 48--50H--T--2T),
Appendix for display tables.
Unit
Start Delay
This refers to the time delay the unit will wait after power
up before it pursues any specific operation.
Factory Default = 5 sec
Range = 0--600 sec
580J
65
Filter Service Hours
This refers to the timer set for the Dirty Filter Alarm.
After the number of runtime hours set on this point is
exceeded the corresponding alarm will be generated, and
must be manually cleared on the alarm reset screen after
the maintenance has been completed. The timer will then
begin counting its runtime again for the next maintenance
interval.
Factory Default = 600 hr
NOTE: Setting this configuration timer to 0, disables the
alarm.
Supply Fan Service Hours
This refers to the timer set for the Supply Fan Runtime
Alarm. After the number of runtime hours set on this point
is exceeded the corresponding alarm will be generated,
and must be manually cleared on the alarm reset screen
after the maintenance has been completed. The timer will
then begin counting its runtime again for the next
maintenance interval.
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the
alarm.
Compressor1 Service Hours
This refers to the timer set for the Compressor 1 Runtime
Alarm. After the number of runtime hours set on this point
is exceeded the corresponding alarm will be generated,
and must be manually cleared on the alarm reset screen
after the maintenance has been completed. The timer will
then begin counting its runtime again for the next
maintenance interval.
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the
alarm.
Compressor2 Service Hours
This refers to the timer set for the Compressor 2 Runtime
Alarm. After the number of hours set on this point is
exceeded the corresponding alarm will be generated, and
must be manually cleared on the alarm rest screen after
the maintenance has been completed. The timer will then
begin counting its runtime again for the next maintenance
interval
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the
alarm.
Cooling
Number of Compressor Stages
This refers to the number of mechanical cooling stages
available on a specific unit. Set this point to “One Stage”
if there is one compressor in the specific unit, set to “Two
Stage” if there are two compressors in the unit, and set to
“None” if economizer cooling ONLY is desired.
Factory Default = One Stage for 1 compressor units
Two Stage for 2 compressor units
Cooling/Econ SAT Low Setpt
The supply air temperature must remain above this value
to allow cooling with the economizer and/or compressors.
There is 5_F plus and minus deadband to this point. If the
SAT falls below this value during cooling, all compressors
will be staged off. The economizer will start to ramp
down to minimum position when the SAT = this
configuration +5_F.
Factory Default = 50_F
Range = 45--75_F
Cooling Lockout Temp
This defines the minimum outdoor air temperature that
cooling mode can be enabled and run. If the OAT falls
below this threshold during cooling, then compressor
cooling will not be allowed.
Factory Default = 45_F
Range = 0--65_F
Heating
Heating SAT High Setpt
The supply air temperature must remain below this value
to allow heating. There is 5_F plus and minus deadband to
this point. If the SAT rises above this value during heating
the heat stages will begin to decrease until the SAT has
dropped below this value.
Factory Default = 120_F
Range = 95--150_F
Heating Lockout Temp
This defines the maximum outdoor air temperature that
heating mode can be enabled and run. If the OAT rises
above this threshold during heating, then heating will not
be allowed.
Factory Default = 65_F
Range = 49--95_F
Inputs
NOTE: For installation of inputs and field installed
accessories, refer to the appropriate sections.
Input 3
This input is a discrete input and can be configured to be
one of five different inputs: No Function, Compressor
Safety, Fan Status, Filter Status, or Remote Occupancy.
This input can also be configured to be either Normally
Open (N/O) or Normally Closed (N/C). Input 3 is factory
wired to pin J1--2. Field accessories get wired to its
parallel pin J5--5. Do not connect inputs to both locations,
one function per input.
Factory Default = Compressor Safety and N/O
NOTE: Compressor Safety input comes from the CLO
board. J1--2 is always factory wired to TB1--8 (X) terminal
on the unit. If the unit has a CLO board, do not configure
input 3 for anything but Compressor Safety.
580J
66
Input 5
This input is a discrete input and can be configured to be
one of five different inputs: No Function, Fire Shutdown,
Fan Status, Filter Status, or Remote Occupancy. This
input can also be configured to be either Normally Open
(N/O) or Normally Closed (N/C). Input 5 is factory wired
to pin J1--10. Field accessories get wired to its parallel pin
J5--3. Do not connect inputs to both locations, one
function per input.
Factory Default = Fire Shutdown and N/C
NOTE: Fire Shutdown input comes from TB4--7. J1--10
is always factory wired to TB4--7. Only change input 5s
function if absolutely needed.
Input 8
This input is a discrete input and can be configured to be
one of five different inputs: No Function, Enthalpy
Switch, Fan Status, Filter Status, or Remote Occupancy.
This input can also be configured to be either Normally
Open (N/O) or Normally Closed (N/C). Input 8 is factory
wired to pin J2--6. Field accessories get wired to its
parallel pin J5--1. Do not connect inputs to both locations,
one function per input.
Factory Default = No Function and N/O
Input 9
This input is a discrete input and can be configured to be
one of five different inputs: No Function, Humidistat, Fan
Status, Filter Status, or Remote Occupancy. This input can
also be configured to be either Normally Open (N/O) or
Normally Closed (N/C). Input 9 is factory and field wired
to pin J5--7. Do not connect inputs to both locations, one
function per input.
Factory Default = Humidistat and N/O
Space Sensor Type
This tells the controller what type of space sensor is
installed to run the unit. The three types that can be used
are the T55 space sensor, the T56 space sensor, or the RS
space sensor.
Factory Default = T55 Type
Input 1 Function
This input is an analog input and can be configured to be
one of five different inputs: No Sensor, IAQ Sensor, OAQ
Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 1
iswiredtopinJ4--5.
Factory Default = No Sensor
Input 2 Function
This input is an analog input and can be configured to be
one of five different inputs: No Sensor, IAQ Sensor, OAQ
Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 2
iswiredtopinJ4--2.
Factory Default = No Sensor
Setpoint Slider Range
This sets the slider range of the space sensor (with this
built in function). The slider is used to offset the current
control setpoint.
Factory Default = 5 n_F
Range = 0--15 n_F
T55/56 Override Duration
This sets the occupancy override duration when the
override button is pushed on the space sensor.
Factory Default = 1 hr
Range = 0--24 hr
IAQ Low Reference @ 4mA
This is used when an IAQ sensor is installed on Input 1 or
2. This value is displayed and used when 4mA is seen at
the input.
Factory Default = 0 PPM
Range = 0--400 PPM
IAQ High Reference @ 20mA
This is used when an IAQ sensor is installed on Input 1 or
2. This value is displayed and used when 20mA is seen at
the input.
Factory Default = 2000 PPM
Range = 0--5000 PPM
NOTE: IAQ low Reference @ 4mA and IAQ High
Reference @ 20mA are used to set the linear curve of mA
vs. PPM.
OAQ Low Reference @ 4mA
This is used when an OAQ sensor is installed on Input 1
or 2. This value is displayed and used when 4mA is seen
at the input.
Factory Default = 0 PPM
Range = 0--400 PPM
OAQ High Reference @ 20mA
This is used when an OAQ sensor is installed on Input 1
or 2. This value is displayed and used when 20mA is seen
at the input.
Factory Default = 2000 PPM
Range = 0--5000 PPM
NOTE: OAQ low Reference @ 4mA and OAQ High
Reference @ 20mA are used to set the linear curve of mA
vs. PPM.
Economizer
Economizer Exists
This point tells the controller if there is an economizer
installed on the unit.
Factory Default = NO if no economizer
YES if there is an economizer installed
Economizer Minimum Position
This defines the lowest economizer position when the
indoor fan is running and the building is occupied.
Factory Default = 20%
Range = 0--100 %
Economizer High OAT Lockout
If the outdoor air temperature rises above this value,
economizer cooling will be disabled and dampers will
return and stay at minimum position.
Factory Default = 75_F
Range = 55--80_F
580J
67
Power Exhaust Setpt
When the economizer damper position opens above this
point the power exhaust operation will begin. When the
damper position falls 10% below the setpoint, the power
exhaust will shutdown.
Factory Default = 50%
Range = 20--90 %
NOTE: This point is only used when Continuous Occ
Exhaust = NO
Continuous Occ Exhaust
This point tells the controller when to run the power
exhaust if equipped on the unit. If set to YES, the power
exhaust will be on all the time when in occupied mode
and will be off when in unoccupied mode. If set to NO the
power exhaust will be controlled by the Power Exhaust
Setpoint.
Factory Default = NO
IAQ
Max Differential CO2Setpt
If the difference between indoor an outdoor air quality
becomes greater then this value the damper position will
stay at the IAQ Greatest Min Dmpr Pos. configuration
point
Factory Default = 650 PPM
Range = 300--950 PPM
IAQ Greatest Min Dmpr Pos.
This is the greatest minimum position the economizer will
open to while trying to control the indoor air quality, CO2
differential.
Factory Default = 50% open
Range = 10--60% open
Clockset
This submenu screen allows you to set the date and time
manually. The Daylight Savings Time (DST) can also be
changed here. The date and time is automatically set when
ever software is downloaded. The clock is a 24 hour clock
and not am/pm. The time should be verified (and maybe
changed) according to unit location and time zone.
Factory Default = Eastern Standard Time
USERPW
This submenu screen allows you to change the user
password to a four number password of choice. The User
password change screen is only accessible with the
Administrator Password (1111). The ADMIN password
will always override the user password.
OPERATING SEQUENCES
Base Unit Controls
Cooling, Units Without Economizer
When thermostat calls for Stage 1 cooling, terminals G
and Y1 are energized. The indoor--fan contactor (IFC),
outdoor fan contactor (OFC) and Compressor 1 contactor
(C1) are energized and indoor-fan motor, outdoor fan and
Compressor 1 start. The outdoor fan motor runs
continuously while unit is in Stage 1 or Stage 2 cooling.
(08D,F and 12D,F units have two outdoor fans; both run
while unit is in Stage 1 or Stage 2 cooling.)
If Stage 1 cooling does not satisfy the space load, the
space temperature will rise until thermostat calls for Stage
2 cooling (Y2 closes). Compressor 2 contactor (C2) is
energized; Compressor 2 starts and runs.
Heating, Units Without Economizer
When the thermostat calls for heating, terminal W1 is
energized. To prevent thermostat short-cycling, the unit is
locked into the Heating mode for at least 1 minute when
W1 is energized. The induced-draft motor is energized
and the burner ignition sequence begins. The indoor
(evaporator) fan motor (IFM) is energized 45 seconds
after a flame is ignited.
If Stage 1 heating does not satisfy the space load, the
space temperature will fall until thermostat calls for Stage
2 heating (W2 closes). Terminal W2 is energized and the
high-fire solenoid on the main gas valve (MGV) is
energized. Firing rate increases to high-fire. When space
load is partially satisfied, terminal W2 is de--energized;
the high-fire solenoid is de--energized and heating
operation continues on low--fire.
When the space heating load is fully satisfied, thermostat
terminal W1 is also deenergized. All heating operations
cease. The IFM stops after a 45-second time off delay.
Cooling, Unit With EconoMi$er IV
For Occupied mode operation of EconoMi$er IV, there
must be a 24-v signal at terminals TR and N (provided
through PL6-3 from the unit’s IFC coil). Removing the
signal at N places the EconoMi$er IV control in
Unoccupied mode.
During Occupied mode operation, indoor fan operation
will be accompanied by economizer dampers moving to
Minimum Position setpoint for ventilation. If indoor fan is
off, dampers will close. During Unoccupied mode
operation, dampers will remain closed unless a Cooling
(by free cooling) or DCV demand is received.
When free cooling using outside air is not available, the
unit cooling sequence will be controlled directly by the
space thermostat as described above as Cooling, Unit
Without Economizer. Outside air damper position will be
closed or Minimum Position as determined by occupancy
mode and fan signal.
580J
68
When free cooling is available as determined by the
appropriate changeover command (dry bulb, outdoor
enthalpy, differential dry bulb or differential enthalpy), a
call for cooling (Y1 closes at the thermostat) will cause
the economizer control to modulate the dampers open and
closed to maintain the unit supply air temperature at 50 to
55_F. Compressor will not run.
During free cooling operation, a supply air temperature
(SAT) above 50_F will cause the dampers to modulate
between Minimum Position setpoint and 100% open. With
SAT from 50_Fto45_F, the dampers will maintain at the
Minimum Position setting. With SAT below 45_F, the
outside air dampers will be closed. When SAT rises to
48_F, the dampers will re-open to Minimum Position
setting.
Should 100% outside air not be capable of satisfying the
space temperature, space temperature will rise until Y2 is
closed. The economizer control will call for compressor
operation. Dampers will modulate to maintain SAT at 50
to 55_F concurrent with Compressor 1 operation. The
Low Ambient Lockout Thermostat will block compressor
operation with economizer operation below 42_F outside
air temperature.
When space temperature demand is satisfied (thermostat
Y1 opens), the dampers will return to Minimum Damper
position if indoor fan is running or fully closed if fan is
off.
If accessory power exhaust is installed, the power exhaust
fan motors will be energized by the economizer control as
the dampers open above the PE-On setpoint and will be
de--energized as the dampers close below the PE-On
setpoint.
Damper movement from full closed to full open (or vice
versa) will take between 1-1/2 and 2-1/2 minutes.
Heating With EconoMi$er IV
During Occupied mode operation, indoor fan operation
will be accompanied by economizer dampers moving to
Minimum Position setpoint for ventilation. If indoor fan is
off, dampers will close. During Unoccupied mode
operation, dampers will remain closed unless a DCV
demand is received.
When the room temperature calls for heat (W1 closes), the
heating controls are energized as described in Heating,
Unit Without Economizer above.
Demand Controlled Ventilation
If a field-installed CO2sensor is connected to the
Economize IV control, a Demand Controlled Ventilation
strategy will operate automatically. As the CO2 level in
the space increases above the setpoint (on the EconoMi$er
IV controller), the minimum position of the dampers will
be increased proportionally, until the Maximum
Ventilation setting is reached. As the space CO2level
decreases because of the increase in fresh air, the
outdoor-damper will follow the higher demand condition
from the DCV mode or from the free-cooling mode.
DCV operation is available in Occupied and Unoccupied
periods with EconoMi$er IV. However, a control
modification will be required on the 580J unit to
implement the Unoccupied period function.
Supplemental Controls
Compressor Lockout Relay (CLO) -- The CLO is available
as a factory-installed option or as a field--installed
accessory. Each compressor has a CLO. The CLO
compares the demand for compressor operation (via a
24-v input from Y at CLO terminal 2) to operation of the
compressor (determined via compressor current signal
input at the CLO’s current transformer loop); if the
compressor current signal is lost while the demand input
still exists, the CLO will trip open and prevent the
compressor from restarting until the CLO has been
manually reset. In the lockout condition, 24-v will be
available at terminal X. Reset is accomplished by
removing the input signal at terminal 2; open the
thermostat briefly or cycle the main power to the unit.
Phase Monitor Relay (PMR) -- The PMR protects the unit
in the event of a loss of a phase or a reversal of power line
phase in the three--phase unit power supply. In normal
operation, the relay K1 is energized (contact set closed)
and red LED indicator is on steady. If the PMR detects a
loss of a phase or a phase sequence reversal, the relay K1
is energized, its contact set is opened and unit operation is
stopped; red LED indicator will blink during lockout
condition. Reset of the PMR is automatic when all phases
are restored and phase sequence is correct. If no 24--v
control power is available to the PMR, the red LED will
be off. Smoke Detectors -- Factory--installed smoke
detectors are discussed in detail starting on page 17.
RTU--MP Sequence of Operation
The RTU--MP will control the compressor, economizer
and heating outputs based on its own space temperature
input and setpoints. An optional CO2IAQ sensor mounted
in the space can influence the economizer minimum
position. The RTU--MP has its own hardware clock that is
set automatically when the software is installed on the
board. The RTU--MP’s default is to control to occupied
setpoints all the time, until a type of occupancy control is
set. Occupancy types are described in the scheduling
section. The following sections describe the operation for
the functions of the RTU--MP. All point objects that are
referred to in this sequence will be in reference to the
objects as viewed in BACview6Handheld.
580J
69
Scheduling
Scheduling is used to start heating or cooling (become
occupied) based upon a day of week and a time period and
control to the occupied heating or cooling setpoints.
Scheduling functions are located under occupancy
determination and the schedule menu accessed by the
Menu softkey (see Appendix -- for menu structure). Your
local time and date should be set for these functions to
operate properly. Five scheduling functions are available
by changing the Occupancy Source to one of the
following selections:
Always Occupied (Default Occupancy)
The unit will run continuously. RTU--MP ships from the
factory with this setting.
Local Schedule
The unit will operate according to the schedule configured
and stored in the unit. The local schedule is made up of
three hierarchy levels that consist of two Override
schedules, twelve Holiday and four Daily schedules, and
are only accessible by the BACview screen (handheld or
virtual).
The Daily schedule is the lowest schedule in the hierarchy
and is overridden by both the Holiday and Override
schedule. It consists of a start time, a stop time (both in 24
hour mode) and the seven days of the week, starting with
Monday and ending in Sunday. To select a daily schedule
scroll to the Schedules menu off of the Menu selection.
Enter the User password and change the Occupancy
Source to Local Schedule. Scroll down and over to the
Daily menu and press enter. Choose one of the four Daily
schedules by pressing the Next softkey and change the
Use? point from NO to YES by selecting the point and
pressing the INCR or DECR softkey. Press the OK softkey
and scroll to the start and stop times. Edit these times
following the same steps as the Use? point. Finally scroll
down to the Days: section and highlight the days required
for the Daily schedule by INCR or DECR softkeys and
press OK softkey.
The Holiday schedule is created to override the Daily
schedule and identify a specific day and month of the year
to start and stop the unit and change control to the
unoccupied heating and cooling setpoints. Follow the
same steps to turn on one of the twelve Holiday schedules
and start and stop times. Next, select one out of the twelve
months and one out of the thirty--one days of that month.
The RTU--MP will now ignore the Daily schedule for the
specific day and time you selected and follow the Holiday
Schedule for this period.
The Override schedules primary purpose is to provide a
temporary change in the occupied heating and cooling
setpoints and force the unit to control to the unoccupied
heating and cooling setpoints. This would occur on a set
day in a particular month and last during the start and stop
time configured. The Override schedule is enabled by
following the same steps to create the Holiday schedule.
NOTE: Push button override is only available when
running a local or BACnet Schedule.
BACnet Schedule
For use with a Building Automation System that supports
native BACnet scheduling is scheduling the unit. With the
Occupancy Source set to BACnet schedule the BAS will
control the unit through network communication and it’s
own scheduling function.
BAS On/Off
The Building Automation System is scheduling the unit
via an On/Off command to the BAS ON/OFF software
point. The Building Automation System can be speaking
BACnet, Modbus, or N2 and is writing to the BAS On/Off
point in the open protocol point map.
NOTE: If the BAS supports NATIVE BACnet
scheduling, then set the Occupancy Source to BACnet
schedule. If the BAS is BACnet but does NOT support
NATIVE BACnet scheduling, then set the Occupancy
Source to BAS On/Off.
DI On/Off
A hard--wired input on the RTU--MP will command the
unit to start/stop. Inputs 3, 5, 8, and 9 on plug J5 can be
hard--wired to command the unit to start/stop.
NOTE: Scheduling can either be controlled via the unit
or the BAS, but NOT both.
Indoor Fan
The indoor fan will be turned on whenever any one of the
following conditions is true:
SIt is in the occupied mode. This will be determined by its
own internal occupancy schedule.
SWhenever there is a demand for cooling or heating in the
unoccupied mode.
SWhenever the remote occupancy switch is closed during
DI On/Off schedule type or if occupancy is forced
occupied by the BAS during BAS On/Off schedule type.
When transitioning from unoccupied to occupied, there
will be a configured time delay of 5 to 600 seconds before
starting the fan. The fan will continue to run as long as
compressors, heating stages, or the dehumidification
relays are on when transitioning from occupied to
unoccupied with the exception of Shutdown mode. If Fire
Shutdown, safety chain, SAT alarm or SPT alarm are
active; the fan will be shutdown immediately regardless of
the occupancy state or demand.
The RTU--MP has an optional Supply Fan Status input to
provide proof of airflow. If this is enabled, the point will
look for a contact closure whenever the Supply Fan Relay
is on. If it is not enabled then it will always be the same
state as the Supply Fan Relay. The cooling, economizer,
heating, dehumidification, CO2and power exhaust
routines will use this input point for fan status.
580J
70
Cooling
The compressor outputs are controlled by the Cooling
Control PID Loop and Cooling Stages Capacity algorithm.
They will be used to calculate the desired number of
stages needed to satisfy the space by comparing the Space
Temperature (SPT) to the Occupied Cool Setpoint plus the
T56 slider offset when occupied and the Unoccupied Cool
Setpoint (UCSP) plus the T56 slider offset, if unoccupied.
The economizer, if available, will be used for cooling in
addition to the compressors. The following conditions
must be true in order for this algorithm to run:
SIndoor Fan has been ON for at least 30 seconds.
SHeat mode is not active and the time guard between
modes equals zero.
SIf occupied and the SPT >(occupied cool setpoint plus
the T56 slider offset).
SSpace Temperature reading is available.
SIf it is unoccupied and the SPT > (unoccupied cool
setpoint plus the T56 slider offset). The indoor fan will be
turned on by the staging algorithm.
SIf economizer is available and active and economizer
open > 85% and SAT > (SAT low limit + 5_F) and SPT >
effective setpoint + 0.5_F.
OR
Economizer is available, but not active
OR
Economizer is not available
SOAT > DX Lockout temperature.
If all of the above conditions are met, the compressors
will be energized as required, otherwise they will be
de--energized.
There is a fixed 3--minute minimum on time and a
5--minute off time for each compressor output and a
3--minute minimum time delay between staging up or
down.
Any time the compressors are running the RTU--MP will
stage down the compressors if the SAT becomes less than
the cooling low supply air setpoint.
After a compressor is staged off, it may be started again
after a normal time--guard period and the supply air
temperature has increased above the low supply air
setpoint.
Economizer
The Economizer dampers are used to provide free cooling
and Indoor Air Quality, if optional CO2sensor is installed,
when the outside conditions are suitable.
The following conditions must be true for economizer
operation:
SIndoor Fan has been on for at least 30 seconds.
SEnthalpy is Low if the Enthalpy input is enabled.
SSAT reading is available.
SOAT reading is available.
SSPT reading is available.
SOAT <= High OAT economizer lockout configuration
(default = 75).
SOAT <= SPT
If any of the mentioned conditions are not true, the
economizer will be set to its configured minimum
position. The minimum damper position can be
overridden by the IAQ routine described later in this
section.
If the above conditions are true, the Economizer Control
Master Loop will calculate a damper position value based
on the following calculation:
Damper Position = minimum position + PID (SPT -- econ
setpoint). Econ setpoint is half way between the effective
cool and heat setpoints. If the SAT drops below the
cooling low supply air setpoint (+ 5_F), the economizer
will ramp down to minimum position.
Power Exhaust
If RTU--MP is also controlling an exhaust fan, it can be
enabled based on damper position or by occupancy. If
configured for continuous occupied operation, it will be
energized whenever the controller is in the occupied mode
and disabled when in the unoccupied mode. If configured
for damper position control, it will be energized whenever
the economizer exceeds the power exhaust setpoint and
disabled when the economizer drops below the setpoint by
a fixed hysteresis of 10%.
Heating
The heating outputs are controlled by the Heating Control
PID Loop and Heating Stages Capacity algorithm. They
will be used to calculate the desired number of stages
needed to satisfy the space by comparing the SPT to the
Occupied Heat Setpoint plus the T56 slider offset when
occupied and the Unoccupied Heat Setpoint plus the T56
slider offset if unoccupied. The following conditions must
be true in order for this algorithm to run:
SIndoor Fan has been ON for at least 30 seconds.
SCool mode is not active and the time guard between
modes equals zero.
SIf occupied and SPT <(occupied heat setpoint plus T56
slider offset)
SSPT reading is available
SIf it is unoccupied and the SPT < (unoccupied heat
setpoint plus T56 slider offset). The indoor fan will be
turned on by the staging algorithm.
SOAT <High OAT lockout temperature.
If all of the above conditions are met, the heating outputs
will be energized as required, otherwise they will be
de--energized. If the SAT begins to exceed the high supply
air setpoint, a ramping function will cause the Heat Stages
Capacity algorithm to decrease the number of stages until
the SAT has dropped below the setpoint.
There is a fixed one minute minimum on time and a one
minute off time for each heat output. Heat staging has a 3
minute stage up and 30 second stage down delay.
580J
71
Indoor Air Quality
If the optional indoor air quality sensor is installed, the
RTU--MP will maintain indoor air quality within the space
at the user configured differential setpoint. The setpoint is
the difference between the indoor air quality and an
optional outdoor air quality sensor. If the outdoor air
quality is not present then a fixed value of 400ppm is
used. The following conditions must be true in order for
this algorithm to run:
SThe mode is occupied.
SIndoor Fan has been ON for at least 30 seconds.
SIndoor Air Quality sensor has a valid reading
As air quality within the space changes, the minimum
position of the economizer damper will be changed thus
allowing more or less outdoor air into the space depending
on the relationship of the indoor air quality to the
differential setpoint. If all the above conditions are true,
the IAQ algorithm will run and calculates an IAQ
minimum position value using a PID loop. The IAQ
minimum damper position is then compared against the
user configured economizer minimum position and the
greatest value becomes the final minimum damper
position of the economizer output.
If the calculated IAQ minimum position is greater than
the IAQ maximum damper position configuration then it
will be clamped to the configured value.
Demand Limit
If the RTU--MP receives a level 1 (one degree offset), 2
(two degree offset), or a 3 (4 degree offset) to the BACnet
demand limit variable, the controller will expand the
heating and cooling setpoints by the configured demand
limit setpoint value and remain in effect until the BACnet
demand limit variable receives a 0 value.
FASTENER TORQUE VALUES
See Table 25 for torque values.
Table 25 – Torque Values
Supply fan motor mounting 120 ¦12 in --- lbs 13.5 ¦1.4 Nm
Supply fan motor adjustment plate 120 ¦12 in ---lbs 13.5 ¦1.4 Nm
Motor pulley setscrew 72 ¦5 i n --- l b s 8.1 ¦0.6 Nm
Fan pulley setscrew 72 ¦5 i n --- l b s 8.1 ¦0.6 Nm
Blower wheel hub setscrew 72 ¦5 i n --- l b s 8.1 ¦0.6 Nm
Bearing locking collar setscrew 65 to 70 in---lbs 7.3 to 7.9 Nm
Compressor mounting bolts 65 to 75 in--- lbs 7.3 to 7.9 Nm
Condenser fan motor mounting bolts 20 ¦2 i n --- l b s 2.3 ¦0.2 Nm
Condenser fan hub setscrew 84 ¦1 2 i n --- l b s 9.5 ¦1.4 Nm
580J
72
APPENDIX I. MODEL NUMBER SIGNIFICANCE
Model Number Nomenclature
123456789101112131415161718
5 8 0 J E 0 8 D 1 2 5 A 1 A 0 A A --
____________ ______ ________ ______
Unit Type Design Revision
580J = Cooling/Gas Heat RTU --- = First Revision
Voltage Packaging
E = 4 6 0 --- 3 --- 6 0 A=Standard
P = 208/230--- 3--- 60 B=LTL
T = 5 7 5 --- 3 --- 6 0
Factory Installed Options
Cooling Tons 0A = None
08 = 7.5 Ton
12 = 10 Ton Intake/Exhaust Options
14 = 12.5 Ton A=None
B=Tempeconow/barorelief
Refrig. System/Gas Heat Options E=Tempeconow/barorelief&CO
2
D = 2 --- S t a g e C o m p r e s s o r / A l H X H = Enthalpy econo w/ baro relief
F = 2 --- S t a g e C o m p r e s s o r / S S H X L = Enthalpy econo w/ baro relief & CO2
Q = Motorized 2 pos damper
Heat Level
125 = 125,000 Indoor Fan Options
150 = 150,000 1 = Standard static option
180 = 180,000 2 = Medium static option
224 = 224,000 3 = High static option
250 = 250,000
2 --- S t a g e C o o l i n g C o i l O p t i o n s ( O u t d o o r --- I n d o o r )
G = Al/Al --- Al/ Cu
T = A l / A l --- A l/ C u --- L o u v e r e d H a i l G u a r d s
Serial Number Format
POSITION NUMBER 12345678910
TYPICAL 1209G12345
POSITION DESIGNATES
1--- 2 Week of manufacture (fiscal calendar)
3--- 4 Year of manufacture (“09” = 2009)
5 Manufacturing location (G = ETP, Texas, USA)
6--- 10 Sequential number
580J
73
APPENDIX II. PHYSICAL DATA
Physical Data (Cooling) 7.5 -- 12.5TONS
580J*08D,F 580J*12D,F 580J*14D,F
Refrigeration System
#Circuits/#Comp./Type 2/2/Scroll 2/2/Scroll 2/2/Scroll
PuronRrefrig. (R--- 410A) charge per
c i r c u i t A / B ( l b s --- o z ) 4 --- 6 / 4 --- 6 6 --- 0 / 6 --- 0 7 --- 6 / 8 --- 0
Oil A/B (oz) 42 / 42 42 / 42 56 / 56
Metering Device Accutrol Accutrol Accutrol
High---press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505
Low---press. Trip / Reset (psig) 54 / 117 54 / 117 54 / 117
Evaporator Coil
Material Cu / Al Cu / Al Cu / Al
Coil type 3/8” RTPF 3/8” RTPF 3/8” RTPF
Rows / FPI 3 / 15 4/15 4/15
To t al Fa c e A r ea ( f t 2)8.9 11.1 11.1
Condensate Drain Conn. Size 3/4” 3/4” 3/4”
Evaporator Fan and Motor
Standard Static
3phase
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt
Max BHP 1.7 2.4 2.9*
RPM Range 489--- 747 591---838 652--- 843
Motor Frame Size 56 56 56
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 15 x 15 15 x 15 15 x 15
Medium Static
3phase
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt
Max BHP 2.9* 3.7 3.7
RPM Range 733--- 949 838---1084 838--- 1084
Motor Frame Size 56 56 56
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 15 x 15 15 x 15 15 x 15
High Static
3phase
Motor Qty / Drive Type 1/Belt 1/Belt 1/Belt
Max BHP 4.7 4.7 4.7
RPM Range 909---1102 1022--- 1240 1022---1240
Motor Frame Size 145TY 145TY 145TY
Fan Qty / Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter (in) 15 x 15 15 x 15 15 x 15
Condenser Coil
Material Al / Al Al / Al Al / Al
Coil type NOVATION NOVATION NOVATION
Rows / FPI 1 / 20 1/20 2/20
To t al Fa c e A r ea ( f t 2) 20.5 25.1 25.1
Condenser fan / motor
Qty / Motor Drive Type 2/ Direct 2/Direct 1/ Direct
Motor HP / RPM 1/4 / 1100 1/4 / 1100 1 / 1175
Fan diameter (in) 22 22 30
Filters
RAFilter#/Size(in) 4/16x20x2 4/20x20x2 4/20x20x2
OA inlet screen # / Size (in) 1/20x24x1 1/20x24x1 1/20x24x1
AI / AI: Aluminum Tube / Aluminum Fin
Cu / AI: Copper Tube / Aluminum Fin
RTPF: Round Tube / Plate Fin
*575V motor utilizes 3.7 BHP
580J
74
APPENDIX II. PHYSICAL DATA (cont.)
Physical Data (Heating) 7.5 -- 12.5TONS
580J**08 580J**12 580J**14
Gas Connection
#ofGasValves 111
Nat. gas supply line press (in. w.g.)/(PSIG) 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7 4 --- 1 3 / 0 . 1 8 --- 0 . 4 7
LP supply line press (in. w.g.)/(PSIG) 11--- 13 / 0.40---0.47 11--- 13 / 0.40---0.47 11--- 13 / 0.40---0.47
Heat Anticipator Setting (Amps)
1st stage 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14
Natural Gas Heat, Liquid Propane Heat
#ofstages/#ofburners(total) 1/3 2/4 2/4
LOW
Connection size 1/2” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 20 --- 50 25 --- 65 25 --- 65
#ofstages/#ofburners(total) 2/4 2/5 2/5
MED
Connection size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 35 --- 65 30 --- 65 25 --- 65
#ofstages/#ofburners(total) 2/5 2/5 2/5
HIGH
Connection Size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 45 --- 75 35 --- 70 35 --- 70
580J
75
APPENDIX III. FAN PERFORMANCE
580J**08 3 PHASE 7.5 TON HORIZONTAL SUPPLY
CFM
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
2250 505 0.52 586 0.73 657 0.97 722 1.22 782 1.50
2438 533 0.62 610 0.85 679 1.09 742 1.36 800 1.65
2625 562 0.74 635 0.98 701 1.23 762 1.51 819 1.81
2813 591 0.88 661 1.13 725 1.39 783 1.68 839 1.98
3000 621 1.03 688 1.29 749 1.57 806 1.87 859 2.18
3188 652 1.21 715 1.48 774 1.77 829 2.07 881 2.40
3375 682 1.40 743 1.68 800 1.98 853 2.30 903 2.63
3563 713 1.61 772 1.91 826 2.22 878 2.55 927 2.89
3750 745 1.85 801 2.15 853 2.48 903 2.82 951 3.18
CFM
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
2250 838 1.81 891 2.12 941 2.46 988 2.82 1033 3.19
2438 854 1.96 906 2.28 955 2.63 1001 2.99 1046 3.37
2625 872 2.12 922 2.46 970 2.81 1016 3.17 1060 3.56
2813 890 2.31 940 2.65 986 3.01 1031 3.38 1074 3.77
3000 910 2.51 958 2.86 1004 3.23 1048 3.61 1090 4.01
3188 930 2.74 977 3.10 1022 3.47 1065 3.86 1107 4.261
3375 951 2.99 997 3.35 1041 3.74 1083 4.13 1124 4.54
3563 973 3.26 1018 3.63 1061 4.02 1103 4.43 -- --
3750 996 3.55 1040 3.93 1082 4.34 -- -- -- --
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field--supplied drive is required.
1. Recommend using field--supplied fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).
580J**08 3 PHASE 7.5 TON VERTICAL SUPPLY
CFM
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
2250 513 0.54 595 0.76 665 1.01 728 1.27 786 1.56
2438 541 0.65 620 0.89 688 1.14 750 1.42 806 1.71
2625 570 0.77 645 1.02 712 1.29 772 1.58 827 1.88
2813 600 0.91 672 1.18 736 1.46 794 1.76 848 2.07
3000 629 1.07 699 1.35 761 1.64 818 1.95 871 2.28
3188 660 1.25 726 1.54 787 1.85 842 2.17 894 2.51
3375 690 1.45 754 1.75 813 2.07 867 2.41 917 2.76
3563 721 1.67 783 1.98 840 2.32 892 2.67 941 3.03
3750 752 1.91 812 2.24 867 2.59 918 2.95 966 3.32
CFM
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
2250 839 1.86 889 2.18 935 2.52 980 2.87 1022 3.23
2438 858 2.02 907 2.35 953 2.70 997 3.06 1039 3.43
2625 878 2.20 926 2.54 972 2.89 1015 3.26 1056 3.64
2813 899 2.40 946 2.75 991 3.11 1033 3.49 1074 3.88
3000 920 2.62 966 2.98 1010 3.35 1052 3.74 1093 4.14
3188 942 2.86 987 3.23 1031 3.61 1072 4.01 1112 4.421
3375 964 3.12 1009 3.50 1052 3.89 1093 4.30 -- --
3563 988 3.41 1032 3.80 1074 4.20 1114 4.61 -- --
3750 1011 3.71 1054 4.11 1096 4.53 -- -- --- ---
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field--supplied drive is required.
1. Recommend using field--supplied fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).
580J
76
FAN PERFORMANCE (cont.)
580J**12 3 PHASE 10 TON HORIZONTAL SUPPLY
CFM
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
F i e l d --- S u p p l i e d D r i v e 1Standard Static Option Medium Static Option
3000 579 0.70 660 0.89 732 1.09 799 1.29 860 1.50
3250 613 0.85 690 1.06 760 1.27 823 1.49 883 1.71
3500 648 1.03 721 1.25 788 1.48 850 1.71 907 1.95
3750 683 1.23 753 1.47 817 1.71 877 1.96 933 2.21
4000 719 1.45 786 1.71 848 1.97 905 2.23 959 2.50
4250 756 1.71 819 1.98 879 2.26 934 2.53 987 2.81
4500 792 1.99 853 2.28 910 2.57 964 2.87 1015 3.16
4750 830 2.31 888 2.62 943 2.92 995 3.23 1044 3.54
5000 867 2.66 923 2.98 976 3.30 1026 3.63 1074 3.95
CFM
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
3000 917 1.70 970 1.91 1021 2.13 1070 2.34 1117 2.56
3250 938 1.93 991 2.16 1041 2.38 1089 2.61 1134 2.85
3500 961 2.18 1013 2.42 1062 2.66 1108 2.91 1153 3.15
3750 985 2.46 1035 2.71 1083 2.97 1129 3.23 1173 3.49
4000 1011 2.76 1059 3.03 1106 3.30 1151 3.58 1194 3.85
4250 1037 3.09 1084 3.38 1130 3.66 1174 3.95 1216 4.24
4500 1064 3.46 1110 3.76 1155 4.06 1198 4.36 1239 4.66
4750 1091 3.85 1137 4.16 1180 4.48 -- -- -- --
5000 1120 4.28 1164 4.61 -- -- --- --- --- ---
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field--supplied drive is required.
1. Recommend using field--supplied fan pulley (part no. KR11AD912) and belt (part no. KR29AF051).
2. Recommend using field--supplied motor pulley (part no. KR11HY410).
580J**12 3 PHASE 10 TON VERTICAL SUPPLY
CFM
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
3000 616 0.79 689 0.97 757 1.16 821 1.36 882 1.57
3250 655 0.96 724 1.16 788 1.37 849 1.58 907 1.80
3500 695 1.17 760 1.38 821 1.60 879 1.83 934 2.06
3750 736 1.41 797 1.63 855 1.86 910 2.10 963 2.35
4000 777 1.68 834 1.91 889 2.16 942 2.41 993 2.67
4250 818 1.98 873 2.23 925 2.49 976 2.75 1025 3.02
4500 860 2.32 912 2.58 962 2.85 1010 3.13 1057 3.41
4750 902 2.69 951 2.97 999 3.26 1046 3.55 1091 3.84
5000 944 3.11 991 3.40 1037 3.70 1082 4.00 1125 4.31
CFM
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
3000 939 1.79 994 2.01 1047 2.24 1098 2.47 1147 2.71
3250 962 2.03 1015 2.26 1066 2.50 1115 2.75 1163 3.00
3500 987 2.30 1038 2.54 1088 2.80 1135 3.05 1181 3.32
3750 1014 2.60 1063 2.86 1111 3.12 1157 3.39 1202 3.66
4000 1042 2.93 1090 3.20 1136 3.48 1180 3.76 1224 4.04
4250 1072 3.30 1118 3.58 1162 3.87 1205 4.16 -- --
4500 1103 3.70 1147 4.00 1190 4.29 1232 4.60 -- --
4750 1135 4.14 1177 4.45 -- -- -- -- --- ---
5000 1167 4.63 -- -- --- --- --- --- --- ---
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field--supplied drive is required.
1. Recommend using field--supplied motor pulley (part no. KR11HY410).
580J
77
580J**14 3 PHASE 12.5 TON HORIZONTAL SUPPLY
CFM
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
3438 639 0.98 713 1.20 781 1.43 843 1.65 901 1.88
3750 683 1.23 753 1.47 817 1.71 877 1.96 933 2.21
4063 728 1.52 794 1.78 855 2.04 912 2.31 966 2.57
4375 774 1.85 836 2.13 894 2.41 949 2.70 1001 2.98
4688 820 2.23 879 2.53 935 2.83 987 3.14 1037 3.44
5000 867 2.66 923 2.98 976 3.30 1026 3.63 1074 3.95
5313 914 3.15 967 3.49 1018 3.83 1066 4.17 1112 4.52
5625 962 3.69 1012 4.05 1061 4.42 -- -- -- --
5938 1009 4.30 1058 4.68 -- -- -- -- -- --
6250 -- -- -- -- -- -- -- -- -- --
CFM
Available External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
3438 955 2.12 1007 2.35 1056 2.59 1103 2.83 1148 3.08
3750 985 2.46 1035 2.71 1083 2.97 1129 3.23 1173 3.49
4063 1017 2.84 1066 3.12 1112 3.39 1157 3.67 1200 3.95
4375 1050 3.27 1097 3.56 1142 3.86 1186 4.15 1228 4.45
4688 1084 3.75 1130 4.06 1174 4.37 1216 4.68 1257 5.00
5000 1120 4.28 1164 4.61 -- -- 1248 5.27 1288 5.60
5313 -- -- -- -- -- -- -- -- -- --
5625 -- -- -- -- -- -- -- -- -- --
5938 -- -- -- -- -- -- -- -- -- --
6250 -- -- -- -- -- -- -- -- -- --
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field--supplied drive is required.
580J
78
580J**14 3 PHASE 12.5 TON VERTICAL SUPPLY
CFM
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
3438 685 1.12 751 1.32 813 1.54 871 1.76 927 1.99
3750 736 1.41 797 1.63 855 1.86 910 2.10 963 2.35
4063 787 1.75 844 1.99 898 2.24 951 2.49 1001 2.75
4375 839 2.14 892 2.40 943 2.67 993 2.94 1041 3.21
4688 891 2.60 941 2.87 990 3.15 1037 3.44 1082 3.73
5000 944 3.11 991 3.40 1037 3.70 1082 4.00 1125 4.31
5313 997 3.69 1042 4.00 1085 4.32 1128 4.64 -- --
5625 1051 4.34 1093 4.67 -- -- -- -- -- --
5938 -- -- -- -- -- -- -- -- -- --
6250 -- -- -- -- -- -- -- -- -- --
CFM
Available External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
3438 981 2.23 1032 2.47 1082 2.72 1130 2.97 1177 3.23
3750 1014 2.60 1063 2.86 1111 3.12 1157 3.39 1202 3.66
4063 1049 3.02 1097 3.29 1142 3.57 1186 3.85 1230 4.14
4375 1087 3.49 1132 3.78 1176 4.08 1218 4.37 1260 4.68
4688 1126 4.03 1169 4.33 1211 4.64 -- -- -- --
5000 1167 4.63 -- -- -- -- -- -- -- --
5313 -- -- -- -- -- -- -- -- -- --
5625 -- -- -- -- -- -- -- -- -- --
5938 -- -- -- -- -- -- -- -- -- --
6250 -- -- -- -- -- -- -- -- -- --
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field--supplied drive is required.
General fan performance notes:
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static
pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories
may add static pressure losses. Selection software is available, through your salesperson, to help you select the best
motor/drive combination for your application.
4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would
work, Bryant recommended the lower horsepower option.
5. For information on the electrical properties of Bryant motors, please see the Electrical information section of this
book.
6. For more information on the performance limits of Bryant motors, see the application data section of this book.
580J
79
APPENDIX III. FAN PERFORMANCE (cont.)
Pulley Adjustment
UNIT MOTOR/DRIVE
COMBO
MOTOR PULLEY TURNS OPEN
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
08
3phase
Standard Static 747 721 695 670 644 618 592 566 541 515 489
Medium Static 949 927 906 884 863 841 819 798 776 755 733
High Static 1102 1083 1063 1044 1025 1006 986 967 948 928 909
12
3phase
Standard Static 838 813 789 764 739 715 690 665 640 616 591
Medium Static 1084 1059 1035 1010 986 961 936 912 887 863 838
High Static 1240 1218 1196 1175 1153 1131 1109 1087 1066 1044 1022
14
3phase
Standard Static 838 813 789 764 739 715 690 665 640 616 591
Medium Static 1084 1059 1035 1010 986 961 936 912 887 863 838
High Static 1240 1218 1196 1175 1153 1131 1109 1087 1066 1044 1022
NOTE: Do not adjust pulley further than 5 turns open.
-- Factory settings
580J
80
ELECTRICAL INFORMATION
580J*08D,F 2---Stage Cooling 7.5 Tons
V --- P h --- H z
VOLTAGE
RANGE
COMP (Cir 1) COMP (Cir 2) OFM (ea) IFM
RLA LRA RLA LRA WATTS FLA TYPE Max
WATTS
Max
AMP Draw EFF at Full Load FLA
MIN MAX
2 0 8 --- 3 --- 6 0 187 253 13.6 83 13.6 83 325 1.5
STD 1448 5.5 80% 5.2
MED 2278 7.9 81% 7.5
HIGH 4400 15.0 81% 15.0
2 3 0 --- 3 --- 6 0 187 253 13.6 83 13.6 83 325 1.5
STD 1448 5.5 80% 5.2
MED 2278 7.9 81% 7.5
HIGH 4400 15.0 81% 15.0
4 6 0 --- 3 --- 6 0 414 506 6.1 41 6.1 41 325 0.8
STD 1448 2.7 80% 2.6
MED 2278 3.6 81% 3.4
HIGH 4400 7.4 81% 7.4
5 7 5 --- 3 --- 6 0 518 633 4.2 33 4.2 33 325 0.6
STD 1379 2.5 80% 2.4
MED 3775 2.9 81% 2.8
HIGH 4400 5.9 81% 5.6
580J*12D,F 2---Stage Cooling 10 Tons
V --- P h --- H z
VOLTAGE
RANGE
COMP (Cir 1) COMP (Cir 2) OFM (ea) IFM
RLA LRA RLA LRA WATTS FLA TYPE Max
WATTS
Max
AMP Draw EFF at Full Load FLA
MIN MAX
2 0 8 --- 3 --- 6 0 187 253 15.6 110 15.9 110 325 1.5
STD 2120 5.5 80% 5.2
MED 3775 10.5 81% 10.0
HIGH 4400 15.0 81% 15.0
2 3 0 --- 3 --- 6 0 187 253 15.6 110 15.9 110 325 1.5
STD 2120 5.5 80% 5.2
MED 3775 10.5 81% 10.0
HIGH 4400 15.0 81% 15.0
4 6 0 --- 3 --- 6 0 414 506 7.7 52 7.7 52 325 0.8
STD 2120 2.7 80% 2.6
MED 3775 4.6 81% 4.4
HIGH 4400 7.4 81% 7.4
5 7 5 --- 3 --- 6 0 518 633 5.8 39 5.7 39 325 0.6
STD 1390 2.1 80% 2.0
MED 3775 2.9 81% 2.8
HIGH 4400 5.9 81% 5.6
580J*14D,F 2---Stage Cooling 12.5 Tons
V --- P h --- H z
VOLTAGE
RANGE
COMP (Cir 1) COMP (Cir 2) OFM (ea) IFM
RLA LRA RLA LRA WATTS FLA TYPE Max
WATTS
Max
AMP Draw EFF at Full Load FLA
MIN MAX
2 0 8 --- 3 --- 6 0 187 253 19.0 123 22.4 149 1288 6.2
STD 2615 7.9 81% 7.5
MED 3775 10.5 81% 10.0
HIGH 4400 15.0 81% 15.0
2 3 0 --- 3 --- 6 0 187 253 19.0 123 22.4 149 1288 6.2
STD 2615 7.9 81% 7.5
MED 3775 10.5 81% 10.0
HIGH 4400 15.0 81% 15.0
4 6 0 --- 3 --- 6 0 414 506 9.7 62 10.6 75 1288 3.1
STD 2615 3.6 81% 3.4
MED 3775 4.6 81% 4.4
HIGH 4400 7.4 81% 7.4
5 7 5 --- 3 --- 6 0 518 633 7.4 50 7.7 54 1288 2.5
STD 3775 2.9 81% 2.8
MED 3775 2.9 81% 2.8
HIGH 4400 5.9 81% 5.6
580J
81
MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.
UNIT
NOM.
V --- P h --- H z
IFM
TYPE
COMBUSTION
FAN MOTOR
FLA
POWER
EXHAUST
FLA
NO C.O. or UNPWRD C.O.
NO P.E. w/ P.E. (pwrd fr/ unit)
MCA MOCP DISC. SIZE MCA MOCP DISC. SIZE
FLA LRA FLA LRA
580J*08D,F
208/230--- 3--- 60
STD
0.48 3.8
43.6 50 46 198 47.4 60 51 202
MED 45.9 50 49 235 49.7 60 53 239
HIGH 53.8 60 58 261 57.6 70 62 265
4 6 0 --- 3 --- 6 0
STD
0.25 1.8
20.1 25 21 97 21.9 25 23 99
MED 20.9 25 22 116 22.7 25 24 118
HIGH 25.3 30 27 129 27.1 30 29 131
5 7 5 --- 3 --- 6 0
STD
0.24 3.8
14.8 20 16 79 18.6 20 20 83
MED 15.2 20 16 94 19.0 25 21 98
HIGH 18.3 20 19 108 22.1 25 24 112
580J*12D,F
208/230--- 3--- 60
STD
0.48 3.8
48.5 60 51 263 52.3 60 56 267
MED 53.3 60 57 306 57.1 70 61 310
HIGH 58.3 70 62 315 62.1 70 67 319
4 6 0 --- 3 --- 6 0
STD
0.25 1.8
23.7 30 25 125 25.5 30 27 127
MED 25.5 30 27 147 27.3 30 29 149
HIGH 28.5 35 31 151 30.3 35 33 153
5 7 5 --- 3 --- 6 0
STD
0.24 3.8
17.9 20 19 95 21.7 25 23 99
MED 18.7 25 20 106 22.5 25 24 110
HIGH 21.5 25 23 120 25.3 30 27 124
580J*14D,F
208/230--- 3--- 60
STD 0.48 3.8 65.5 80 69 365 69.3 80 73 369
MED 68.0 80 72 382 71.8 80 76 386
HIGH Model not available due to high amperage draw.
4 6 0 --- 3 --- 6 0
STD
0.25 1.8
31.7 40 33 183 33.5 40 35 185
MED 32.7 40 35 192 34.5 45 37 194
HIGH 35.7 45 38 196 37.5 45 40 198
5 7 5 --- 3 --- 6 0
STD
0.24 3.8
24.0 30 25 144 27.8 30 30 148
MED 24.0 30 25 144 27.8 30 30 148
HIGH 26.8 30 29 158 30.6 35 33 162
LEGEND:
CO --- Convenient outlet
DISC --- Disconnect
FLA --- Full load amps
IFM --- Indoor fan motor
LRA --- Locked rotor amps
MCA --- Minimum circuit amps
MOCP --- Maximum over current protection
P E --- P o w e r e x h a u s t
UNPWRD CO --- Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to
determine the percentage of voltage imbalance.
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 + 231 + 226)
=
681
33
= 227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
580J
82
APPENDIX IV. WIRING DIAGRAM LIST
Wiring Diagrams
580J
SIZE VOLTAGE CONTROL POWER
08D,F
208/230---3---60 48TM501325 48TM501326
460---3---60 48TM501325 48TM501326
575---3---60 48TM501325 48TM501327
12D,F
208/230---3---60 48TM501325 48TM501326
460---3---60 48TM501325 48TM501326
575---3---60 48TM501325 48TM501327
14D,F
208/230---3---60 48TM501379 48TM501380
460---3---60 48TM501379 48TM501380
575---3---60 48TM501379 48TM501381
All RTU---MP* 48TM500988
NOTE: Component arrangement on Control; Legend on Power Schematic
* RTU--MP control labels overlay a portion of the base unit control label. The base unit label drawing and the control option drawing are required to
provide a complete unit control diagram.
580J
83
APPENDIX V. MOTORMASTER SENSOR LOCATIONS
580/558J-D08
580/558J-D12
C09226
Fig. 75 -- 580J*08--12D,F Outdoor Circuiting
NOTE: The low ambient kit for the 12.5 ton unit utilizes a pressure transducer, and therefore there is no Motormaster
temperature sensor location for this unit.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
E2009 Bryant Heating & Cooling Systems D7310 W. Morris St. DIndianapolis, IN 46231 Printed in U.S.A. Edition Date: 5/09
Replaces: NEW
Catalog No.SM580J---02
580J
84
580J
85
UNIT START-UP CHECKLIST
I. PRELIMINARY INFORMATION:
MODEL NO.:
DATE: ______________
SERIAL NO: _____________________________________
TECHNICIAN: ___________________________________
BUILDING LOCATION:____________________________
II. PRE-START-UP (insert check mark in box as each item is completed):
jVERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT
jVERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
jVERIFY THAT FLUE HOOD IS INSTALLED
jCHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
jCHECK TO ENSURE NO WIRES ARE TOUCHING REFRIGERANT TUBING OR SHARP EDGES
jCHECK GAS PIPING FOR LEAKS
jCHECK THAT RETURN--AIR FILTER IS CLEAN AND IN PLACE
jVERIFY THAT UNIT INSTALLATION IS LEVEL
jCHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND VERIFY SETSCREW IS TIGHT
jVERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1
COMPRESSOR 1 L1 L2 L2
COMPRESSOR 2 L1 L2 L2
INDOOR FAN AMPS L1 L2 L2
TEMPERATURES
OUTDOOR-AIR TEMPERATURE DB WB
RETURN-AIR TEMPERATURE DB WB
COOLING SUPPLY AIR DB WB
GAS HEAT SUPPLY AIR DB
PRESSURES
GAS INLET PRESSURE IN. WG
GAS MANIFOLD PRESSURE IN. WG (LOW FIRE) IN. WG (HI FIRE)
REFRIGERANT SUCTION CIR 1 PSIG TEMP _F
CIR 2 PSIG TEMP _F
REFRIGERANT DISCHARGE CIR 1 PSIG TEMP _F
CIR 2 PSIG TEMP _F
jVERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
jVERIFY THAT 3--PHASE SCROLL COMPRESSORS ARE ROTATING IN CORRECT DIRECTION
580J

Navigation menu