353AAV Plus 90x
4--Way Multipoise Condensing Gas Furnace
Input Rates: 40,000 Only
Product Data
4--WAY MULTIPOISE DESIGN ALLOWS
MORE APPLICATIONS
the furnace resulting in lower electrical usage. The high
efficiency achieved by superior heat transfer is made only
better—by optimizing the efficient ECM motor speed tap
locations.
A standard media filter cabinet accessory is provided with the
Plus 90x in order to provide an opportunity to enhance indoor air
quality. As with all other Bryant furnaces, this model is designed
to work as a part of the total home comfort system which includes
elements for cooling, air cleaning, humidification, ventilation and
zoning. Boosting the unit’s efficiency with the ECM motor and
Bryant’s deluxe features show the Plus 90x has been designed
with the homeowner in mind.
PLUS 90X FEATURES & BENEFITS
EverlasticTM — Exclusive Everlastic coating, a patented
polypropylene laminate is used on the secondary heat exchanger
and greatly reduces maintenance.
Perfect Light™ Igniter — Bryant’s unique Perfect Light™
igniter is not only physically robust but it is also electrically
robust. It is capable of running at line voltage and does not
require complex voltage regulators as do other brands. This
unique feature further enhances the reliability of the Plus 90x gas
furnace and continues Bryant’s tradition of technology leadership
and innovation in providing a reliable and durable product.
A05085
A UNIQUE SEER SOLUTION
The Plus 90x is an exciting addition to your product line. This
high--efficiency 4--way multipoise design furnace allows more
applications while the ECM motor and Bryant’s control logic
combine to provide a SEER increase of up to 1.5 points.*
Some of Bryant’s best--engineered components contribute to the
efficient performance of this condensing furnace. The Plus 90x
utilizes Power Lightt hot surface ignition (HSI), which ignites
the burners directly. HSI eliminates gas waste that typical
continuous--pilot designs can bring. Hot surface ignition has
proven to contribute to reliable start--up and operation of Bryant
furnaces.
Another deluxe feature included with this furnace is Bryant’s
trusted Everlastict secondary heat exchanger; a patented
polypropylene laminate that provides exceptional heat transfer
and corrosion resistance. Using the exclusive flow--through
design, the secondary heat exchanger reduces the pressure drop in
FanOn™ — Improves comfort all year long by allowing the
homeowner to select different fan speeds during continuous fan
operation to achieve more or less airflow. This is done right at the
thermostat.
SmartEvap™ — This feature allows your system to reduce
summertime humidity levels by nearly 10% over standard
systems.
Media Filter Cabinet — Enhanced indoor air quality in your
home is made easier with our media filter cabinet—a standard
accessory on all Deluxe furnaces. When installed as a part of your
system, this cabinet allows for easy and convenient addition of a
Bryant high--efficiency air filter.
Control Center — Microprocessor controls sequencing and
furnace operation. Equipped with a component test feature and
status indicator light to assist in troubleshooting. Microprocessor
controls blower times to start blower after main burners ignite to
eliminate cold air blowing into rooms.
*as compared to the Air---Conditioning, Heating and Refrigeration Institute’s standard coil---only rating (A/Cs up to 3.5 tons) when paired with selected Bryant
evaporator coils.
1
Casing — One piece, seamless wrap--around construction of
heavy, galvanized steel that resists corrosion.
Direct or Non--direct Venting — The Plus 90x can be installed
as a 1 pipe/Non--Direct vent (except 140 size unit and in
manufactured/mobile home installations) or 2 pipe/Direct vent
furnace. All direct vent Plus 90x models can be installed in a
manufactured (mobile) home when the optional kit is used. This
provides added flexibility to meet diverse installation needs.
Adjustable Blower Speed — For precise airflow selection of
heating or cooling operation.
Monoport Burners — The burners are finely tuned for smooth,
quiet combustion plus economical gas usage.
Insulated Blower Compartment —The acoustical insulation
reduces air and motor noise to promote quiet operation.
Slow Opening Redundant Gas Valve — Shuts off gas to burners
if any of the valves fails to close completely for any reason. The
slow opening feature reduces start--up noise from rapid ignition.
Combustion Products Venting — The combustion--air and vent
pipes can terminate through a side wall or through the roof when
used with a factory--authorized vent termination kit.
Quality Registration — The Plus 90x is engineered and
manufactured under an ISO 9001 registered quality system.
353AAV
Insulation — Foil--faced insulation in heat exchanger section of
the casing minimizes heat loss.
Certifications — The Plus 90x Model units are CSA (A.G.A.
and C.G.A.) design certified for use with natural and propane
gases. The furnace is factory--shipped for use with natural gas. A
CSA (A.G.A./C.G.A.) listed gas conversion kit is required to
convert furnace for use with propane gas. The efficiency is
GAMA efficiency rating certified. The Plus 90x meets California
Air Quality Management District emission requirements. Refer to
Vent Table, for elevation limitations.
Bottom Closure — Factory--installed for side return; easily
removable for bottom return.
Filter — Cleanable filter with retainer is standard.
Blower Access Panel Switch — Shuts off all 115--v power
through furnace components whenever blower access panel is
opened.
BLOWER OFF-DELAY
BLOWER OFF-DELAY
120 180
90 150
T1
DHUM
TWINNING AND/OR
COMPONENT TEST
TERMINAL
G
COM
24V
24-V THERMOSTAT
TERMINALS
W
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP. MAX
)
PLT
TIT2
TEST / TWIN
R
HUH
3-AMP FUSE
SEC-1
COM
24VAC
PL1
LED OPERATION
& DIAGNOSTIC LIGHT
SEC-2
24V
COM
TRANSFORMER
24-VAC CONNECTION
HEAT
COOL
MTR
S
1
FAN
TAPS
BLOWER SPEED
SELECTION
TERMINALS
SPARE 2 SPARE 1
PL1-LOW VOLTAGE
MAIN HARNESS
CONNECTOR
EAC-2
EAC-1
115-VAC (L2)
NEUTRAL
CONNECTIONS
L1
BL-1
PR-1
PL2
EAC-1 TERMINAL
(115-VAC 1.0 AMP. MAX0
115-VAC (LI)
NUETRAL
CONNECTIONS
PL1-HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTION
A08345
A92505
2
A02172
1
2
3
13
4
14
5
6
6
7
8
9
10
15
16
11
12
353AAV
17
18
19
20
A08421
1. Burner sight glass for viewing burner flame.
11. Heavy--duty blower circulates air across the heat
exchangers to transfer heat into the home.
2. Burner assembly (inside), operates with energy--sav-
ing, inshot burners and hot surface igniter for safe,
dependable heating.
12. Air filter and retainer may be used for side or bottom
3. Combustion--air intake connection to ensure contam-
13. Rollout switch (manual reset) to prevent overtemper-
4. Redundant gas valve, safe, efficient, features 1 gas
14. Primary serpentine heat exchanger (inside). Stretches
return application.
inant--free air (right or left side).
ature in burner area.
control with 2 internal shutoff valves.
fuel dollars with the S--shaped heat--flow design. Solid weld--free construction of corrosion--resistant aluminized steel means reliability.
5. Junction box for 115--v electrical power supply.
(right or left side)
15. A 3--amp fuse provides electrical and component
protection.
6. Vent outlet uses sealed PVC pipe to carry vent gases
from the furnace’s combustion system (right or left
side).
16. Light emitting diode (LED) on control center. Code
lights are for diagnosing furnace operation and service requirements.
7. Secondary condensing heat exchanger (inside),
wrings out more heat through condensation of gases.
Constructed with polypropylene--laminated steel to
ensure durability.
17. Control center.
18. Blower access panel safety interlock switch.
8. Pressure switch ensures adequate flow of flue
products through furnace and out vent system.
19. Transformer (24v) behind control center provides
low--voltage power to furnace control center and
thermostat.
9. Inducer motor pulls hot flue gases through the heat
exchangers, maintaining negative pressure for added
safety.
20. Power choke (used with 1 HP and 3/4 HP motors.)
10. Condensate drain connection collects moisture condensed during the combustion process. 1 2 3 4 5 6
3
PHYSICAL DATA
UNIT SIZE
SHIPPING WEIGHT LB. (KG)
LIMIT CONTROL
HEATING BLOWER CONTROL
(Off Delay)
BURNERS (Monoport)
GAS CONNECTION SIZE
GAS VALVE(Redundant)
Manufacturer
Minimum Inlet Pressure
(in. wc)
Maximum Inlet Pressure
(in. wc)
IGNITION DEVICE
DIRECT--- DRIVE MOTOR
(ECM X--- 13)
MOTOR FULL LOAD AMPS
RPM (Nominal) --- SPEEDS
BLOWER WHEEL DIAMETER X
WIDTH --- IN (mm)
FILTER SIZE (Washable) --IN (mm)
DE
C
ER
036040
175 (47)
036060
182 (57)
036080
198 (64)
048080
205 (69)
SPST
TIFIE
060100
232
060120
261 (74)
5
6
1
1
10.9
10.9
11 X 10
(279 X 254)
(1) 20 X 25 X 3/4
(508 X 635 X 19)
11 X 10
(279 X 254)
(1) 24 X 25 X 3/4
(610 X 635 X 19)
Solid---State Time Operation
2
3
4
4
1/2---in. NPT
White---Rodgers
4.5 (Natural Gas)
13.6 (Natural Gas)
Hot Surface
1/2
1/2
1/2
6.8
6.8
6.8
10 X 7
(254 X 178)
3/4
8.4
1050---5
10 X 7
10 X 7
11 X 8
(254 X 178)
(254 X 178)
(279 X 203)
(1) 16 X 25 X 3/4
(406 X 635 X 19)
Always Ask For
S I GN
D
353AAV
**Note: 060--120 Sizes are phasing out.**
CERTIFIED
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
4
BRYANT ACCESSORIES*
ACCESSORIES
THERMOSTAT --NON--- PROGRAMMABLE
THERMOSTAT --PROGRAMMABLE
ZONING CONTROL
KGANP4601ALL
KGANP3901ALL
KGAMH0301KIT
KGASB0301ALL
2 --- IN. --- KGAVT0101BRA
3 --- IN. --- KGAVT0201BRA
2 --- IN. --- KGAVT0701CVT
3 --- IN. --- KGAVT0801CVT
KGAHT01010CFP
P908 --- 0001
Model EACB
Models GAPAAXBB1625, GAPAAXBB2025
Models EZXCAB, FILCAB
Model HUM
Model HRV
Model ERV
Model UVL
KGAET0106ETK
KGBAC0110DGK
KGAWF1301UFR
KGAWF1401UFR
KGAWF1501UFR
For use with 1 --- speed Air Conditioner --- deg. F/C, Auto Changeover --- T6 --- NAC, T2 --- NAC
For use with 1 --- speed Air Conditioner --- deg. F/C, Auto Changeover --- T6 --- NHP--- T2 --- NHP*
For use with 2 --- speed Air Conditioner --- deg. F/C, Auto Changeover --- T6 --- NRH*
For use with multi--- use / stage configurations --- deg. F/C, Auto Changeover/Temperature and
Humidity Control --- T6 --- PRH{
For use with 1 --- speed Air Conditioner --- deg. F/C, Auto Changeover, 7 --- Day Programmable --T6 --- PAC
For use with 1 --- speed Air Conditioner --- deg. F/C, Auto Changeover, 7 --- Day Programmable --T6 --- PHP*
For use with 2 --- speed Air Conditioner --- deg. F/C, Auto Changeover, 7 --- Day Programmable --T6 --- PRH*
For use with 1 --- speed Air Conditioner --- deg. F/C, 5 --- 2 Day Programmable --- T2 --- PAC
For use with multi--- stage applications --- deg. F/C, Auto Changeover, 7 --- Day Programmable --T6 --- PHP}
For multi--- use / stage configurations --- deg. F/C, Auto Changeover, 7 --- Day Programmable/
Temperature and Humidity Control --- T6 --- PRH{
Comfort Series Three--- Zone Zone Kit --- ZONEBB3ZAC01, ZONEBB3ZHP01
2 --- Performance Series Zoning/Temperature and Humidity Control --- ZONEBB2KIT01 --- B
4 --- Performance Series Zoning/Temperature and Humidity Control --- ZONEBB4KIT01 --- B
8 --- Performance Series Zoning/Temperature and Humidity Control --- ZONEBB8KIT01 --- B
*Factory---authorized and field---installed. Gas conversion kits are CSA (A.G.A./C.G.A.) recognized
Required for installation on combustible floors when no coil box is used, or when any coil box other than a Bryant cased coil is used.
*Model HP and 2S thermostat must be field converted to air conditioner operation.
{Thermidistatt Control control can be configured for multiple use and staging. It must be configured for each specific application.
}Dual Fuel thermostat is used with furnace and heat pump application.
5
353AAV
GAS CONVERSION KIT --NATURAL TO PROPANE
GAS CONVERSION KIT --PROPANE TO NATURAL
MANUFACTURED (MOBILE)
HOME KIT
DOWNFLOW BASE
(For Combustible Floors)}
VENT TERMINATION KIT
(Bracket Only for 2 Pipes)
CONCENTRIC TERMINATION
KIT (Single Exit)
CONDENSATE FREEZE
PROTECTION KIT
CONDENSATE NEUTRALIZER
KIT (Obtained thru RCD)
ELECTRONIC AIR CLEANER
(EAC)
AIR PURIFIER
MECHANICAL AIR CLEANER
HUMIDIFIER
HEAT RECOVERY VENTILATOR
ENERGY RECOVERY
VENTILATOR
UV LIGHTS
VENT/EXHAUST PIPE
EXTERNAL TRAP KIT
DOOR GASKET KIT
UNFRAMED FILTER,
PERMANENT WASHABLE 3/4”
(19mm)
16 x 25 (406 x 635 mm)
UNFRAMED FILTER,
PERMANENT WASHABLE 3/4”
(19mm)
16 x 25 (508 x 635 mm)
UNFRAMED FILTER,
PERMANENT WASHABLE 3/4”
(19mm)
16 x 25 (610 x 635 mm)
A93086
353AAV
CONCENTRIC
VENT (DIRECT VENT/
2-PIPE ONLY)
A88202
A96214
DOWNFLOW
SUBBASE
A concentric vent kit allows vent
and combustion-air pipes to
terminate through a single exit
in a roof or side wall.
One pipe runs inside the other
allowing venting through the
inner pipe and combustion air to
be drawn in through the outer
pipe.
BRYANT CASED
N-COIL
One base fits all furnace sizes.
The base is designed to be installed between the furnace and a
combustible floor when no coil
box is used or when a coil box
other than a Bryant cased coil is
used. It is CSA (A.G.A./C.G.A.)
design certified for use with select
Bryant furnaces when installed in
downflow applications.
(as shown)
The Bryant Cased N-Coil or
A-Coil is an upflow/downflow
furnace coil which can also
replace the downflow subbase
when installing select Bryant
furnaces on combustible flooring
in the downflow orientation.
A08450
A97432
CONTROLS:
THERMOSTATS
AND ZONING
Available in programmable and
non-programmable models,
Bryant thermostats maintain a
constant, comfortable temperature level in the home.
For the ultimate in home comfort,
Bryant’s 2, 4, and 8-zone systems
allow temperature control of individual “zones” of the home. This is
accomplished through a series of
electronic dampers and
remote room sensors. The
4-zone system is shown.
C04009
MECHANICAL
OR ELECTRONIC
AIR CLEANER
Cleans the air of smoke, dirt, and
many pollens commonly found.
Saves decorating and cleaning
expenses by keeping carpets,
furniture, and drapes cleaner.
Electronic air cleaner is shown.
A01484
HUMIDIFIER
By adding moisture to winter-dry
air, a Bryant humidifier can often
improve comfort and keep
furniture, rugs, and draperies in
better condition. Moisturizing
household air also helps to retain
normal body heat and provides
comfort at lower temperatures.
ENERGY/HEAT RECOVERY
VENTILATOR
Bryant’s energy or heat recovery
ventilators exhaust stale indoor
air and provide fresh outdoor air
to the home while minimizing
heat loss and humidity level.
Especially useful for today’s
tighter constructed houses.
Energy recovery ventilator
is shown.
A08153
6
A08321
7
11⁄4" (32mm)
1"
(25mm)
14 1⁄2"
TYP
(368mm)
26 15⁄16" TYP (684mm)
23 1⁄4" TYP (591mm)
SIDE INLET
SIDE INLET
DIA THERMOSTAT
ENTRY
(13mm)
22 11 ⁄16"
(576mm)
1⁄2-IN.
2-IN. VENT CONN
(51mm)
DIA
GAS CONN
(13mm)
1⁄2-IN.
26 15⁄16"
(684mm)
26 1⁄4"
(667mm)
1⁄2"
24
(666mm)
22 5⁄16"
(567mm)
2-IN. COMBUSTIONAIR CONN
(51mm)
13⁄16"
(17mm)
11 ⁄16"
E
INLET
OUTLET
D
(17mm)
11 ⁄16"
TYP
(14mm)
DIMPLE LOCATORS
FOR HORIZONTAL
HANGING
CONDENSATE
DRAIN LOCATION
(UPFLOW)
18 1⁄4"
(464mm)
30
(775mm)
1⁄2"
CONDENSATE DRAIN
TRAP LOCATION
(DOWNFLOW &
HORIZONTAL RIGHT)
OR ALTERNATE
1⁄2
-IN. DIA GAS CONN
(21mm)
13⁄16"
9⁄16"
UNIT SIZE
040-12 / 036040
060-12 / 036060
080-12 / 036080
080-16 / 048080
100-20 / 060100
120-20 / 060120
A
17-1/2 (445)
17-1/2 (445)
17-1/2 (445)
17-1/2 (445)
21 (25.4)
24-1/2 (622)
D
15-7/8 (403)
15-7/8 (403)
15-7/8 (403)
15-7/8 (403)
19-3/8 (492)
22-7/8 (581)
353AAV
E
16 (406)
16 (406)
16 (406)
16 (406)
19-1/2 (495)
23 (584)
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer‘s recommendation for equivalent diameters.
2. Minimum return-air opening at furnace:
a. For 800 CFM 16-in . (406mm) round or 14 1 / 2 (368mm) x 12-in. (305mm) rectangle.
b. For 1200 CFM 20-in . (508mm) round or 14 1 / 2 (368mm) x 19 1 / 2-in. (495mm) rectangle.
c. For 1600 CFM 22-in .(559mm) round or 14 1 / 2 (368mm) x 23 1 / 4-in.(591mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the bottom, or the bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM at 0.5 in. W.C. ESP.
CONDENSATE
DRAIN LOCATION
(UPFLOW)
(21mm)
33 1⁄4"
TYP
(845mm)
30
(783mm)
11 ⁄16"
29
DIA (22mm)
TYP
ACCESSORY
(754mm)
POWER ENTRY
32 5⁄8"
27 5⁄8"
TYP
(702mm)
CONDENSATE
(829mm)
DRAIN TRAP
27 9⁄16"
LOCATION
TYP
(700mm)
(ALTERNATE
UPFLOW)
24 1⁄2"
(622mm)
17 5⁄16"
9 7⁄16"
(440mm)
TYP
(240mm)
7⁄8-IN.
DIA (22mm)
POWER CONN
7⁄8-IN.
CONDENSATE DRAIN
TRAP LOCATION
(DOWNFLOW &
HORIZONTAL LEFT)
13⁄16"
A
AIRFLOW
22 1⁄4" TYP
(565mm)
24 3⁄16"
BOTTOM INLET
(614mm)
SIDE INLET
22 11 ⁄16"
2-IN. VENT CONN
DIA
THERMOSTAT ENTRY
1⁄2-IN.
DIA
POWER CONN
7⁄8-IN.
DIA
GAS CONN
1⁄2-IN.
2-IN. COMBUSTIONAIR CONN
OUTLET
19" (483mm)
22 5⁄16" (567mm)
26 1⁄4" (667mm)
26 15⁄16" (694mm)
28 1⁄2" (724mm)
(16mm)
11 ⁄16"
(17mm)
7⁄16" (11mm)
1"
(25mm)
39 7⁄8"
(1013mm)
5⁄16"
(8mm)
5⁄8"
13⁄16" (21mm)
DOWNFLOW SUBBASE DIMENSIONS -- IN. (MM)
PLENUM OPENING
FURNACE
CASING
WIDTH
FURNACE IN DOWNFLOW APPLICATION
17-1/2
(445)
21
(533)
24-1/2
(622)
Furnace with or without Cased Coil Assembly or
Coil Box
Furnace with or without Cased Coil Assembly or
Coil Box
Furnace with or without Cased Coil Assembly or
Coil Box
HOLE NO.
FOR
WIDTH
ADJUST--MENT
FLOOR OPENING
A
B
C
D
15---1/8
(384)
18---5/8
(473)
22-1/8
(562)
19
(483)
19
(483)
16-3/4
(425)
20---1/4
(514)
23-3/4
(603)
20---3/8
(518)
20---3/8
(518)
20---3/8
(518)
19 (483)
3
2
1
*The plenum should be constructed 1/4---in. (6 mm) smaller in width and depth than the plenum dimensions shown above.
LOCATING
TAB
1 1/4″ (32 μμ) TYP
353AAV
PLENUM
OPENING
B
A
D
1
2
4
3
LOCATING
TAB
C
FACTORY-SUPPLIED
FIELD-INSTALLED
INSULATION
4
3
2
1
COMBUSTION--AIR PIPE FOR NON--DIRECT VENT (1--PIPE) APPLICATION
(SIZES 040 THROUGH 120 ONLY)
FIELD-SUPPLIED
2-IN. (51 mm) DIA.
PVC 90° ELBOW
FIELD-SUPPLIED
2-IN. (51 mm) DIA.
PVC PIPE
LENGTH OF STRAIGHT
PIPE PORTION OF COMBUSTION
AIR INLET PIPE ASSEMBLY - IN. (mm)
CASING WIDTH
A
A
17-1/2 (445 mm)
8-1/2 ± 1/2 (216 ± 13 mm)
21 (533 mm)
10-1/2 ± 1/2 (267 ± 13 mm)
24-1/2 (622 mm)
COMBUSTION-AIR DISC
(FACTORY-SUPPLIED IN
LOOSE PARTS BAG)
12 ± 1/2 (305 ± 13 mm)
A96211
CONCENTRIC VENT FOR DIRECT VENT (2--PIPE) APPLICATION (ALL MODEL SIZES)
B IN. (MM) DIA PVC
VENT/EXHAUST
F
E
C IN. (MM) DIA
13/16 (30 mm)
11/2
D
(38 mm)
A
B IN. (MM) DIA PVC
INTAKE/COMBUSTION AIR
KIT PART NO.
KGAVT0701CVT
KGAVT0801CVT
A*
33---3/8 (848)
38---7/8 (987)
B
2 (51)
3 (76)
C
3---1/2 (89)
4---1/2 (114)
D{
16---5/8 (422)
21---1/8 (537)
E
6---1/4 (159)
7---3/8 (187)
F
5---3/4 (146)
6---1/2 (165)
*Dimension A will change accordingly as Dimension D is lengthened or shortened.
{Dimension D may be lengthened to 60---in. (1524 mm) maximum. Dimension D may also be shortened by cutting the pipes provided in the kit to 12--- in. (305
mm) minimum.
8
353AAV
CONDENSATE TRAP
A93026
MEDIA FILTER CABINET
25 5/8" (651 mm)
23 5/8" (600 mm)
24 3/8" (619 mm)
Opening with Flanges Bent
23 3/8" (594 mm)
23 1/8" (587 mm)
Opening
B Opening
A
Duct Side
Furnace Side
23 3/4" (603 mm)
Centerline Screw Slots
5 3/4
(146 mm)
Media
Filter Cabinet
A
B
Shipped with sizes
16" (406)
17" (432) 16" (406)
040-08, 040-12, 060-08, 060-12,
060-16, 080-12, 080-16
20" (508)
21" (533) 20" (508)
080-20, 100-16, 100-20
24" (610)
25" (635) 24" (610)
120-20, 140-20
A05186
9
353AAV
CLEARANCE TO COMBUSTIBLES
335122-201 REV. B LIT TOP
A08435
10
UNIT SIZE
CAPACITY* Direct Vent (2---pipe)
(Shaded capacities are specified on
the rating plate)
CAPACITY* Non---Direct vent (1---pipe)
AFUE* Direct Vent (2---pipe)
Non---weatherized ICS
AFUE* Non---Direct Vent (1---pipe)
Non-weatherized ICS
Upflow
Downflow
Horizontal
Upflow
Downflow
Horizontal
Upflow
Downflow
Horizontal
Upflow
Downflow
Horizontal
Input Btuh {
UNIT SIZE
CERTIFIED TEMPERATURE RANGE --_F (_C)
CERTIFIED EX STATIC PRESSURE
(in. wc)
AIRFLOW (CFM)}
Heating
Cooling
Heating
Cooling
EFFICIENCY
036040
036060
38000
56000
38000
56000
38000
56000
38000
56000
38000
56000
38000
56000
95
93.6
94.4
94.7
93.3
94.1
036080
75000
75000
74000
75000
74000
74000
048080
75000
75000
75000
75000
75000
75000
93
91.5
92.3
92.4
91.4
91.4
060100
94000
94000
93000
94000
93000
93000
060120
113000
113000
112000
113000
112000
112000
40000
60000
80000
80000
100000
120000
036040
20---50
(11---28)
0.10
0.50
845
1260
036060
30---60
(17---33)
0.12
0.50
1040
1250
036080
40---70
(22---39)
0.15
0.50
1180
1240
048080
30---60
(17---33)
0.15
0.50
1450
1620
060100
30---60
(17---33)
0.20
0.50
1890
1635
060120
40---70
(22---39)
0.20
0.50
2065
1925
*Capacity and AFUE in accordance with U.S. Government DOE test procedures.
{Gas input ratings are certified for elevations to 2000 ft. (610 M). For elevations above 2000 ft. (610 M), reduce ratings 2% for each 1000 ft. (305 M) above sea
level. In Canada, derate the unit 5% for elevations 2000 to 4500 ft. (610 to 1372 M) above sea level.
}Airflow shown is for bottom only return---air supply with factory supplied 3/4---in. (19 mm) washable filter(s).
For air delivery above 1800 CFM, see Air Delivery table for other options.
An airflow reduction of up to 7% may occur when using the factory---specified 4 5/16---in. (110 mm) wide, high efficiency media filter.
For best furnace efficiency when using the 4---5/16---in. (110 mm) wide media filter, adjust the blower speed tap to near the mid---point of the rise range.
ICS --- Isolated Combustion System.
11
353AAV
PERFORMANCE DATA
AIR DELIVERY—CFM (WITH FILTER)
UNIT
SIZE
RETURN-AIR
SUPPLY
036040 SIDE/BOTTOM
353AAV
036060 SIDE/BOTTOM
036080 SIDE/BOTTOM
048080 SIDE/BOTTOM
060100 SIDE/BOTTOM
060120 SIDE/BOTTOM
SPEED
EXTERNAL STATIC PRESSURE (in.wc)
0.3
0.4
0.5
0.6
0.7
0.8
0.1
0.2
0.9
1
5(Gry)
1425
1385
1350
1305
1260
1210
1165
1100
995
855
4(Yel)
3(Blu)
2(Org)
1(Red)
1215
1060
890
880
1165
1005
835
675
1130
960
770
570
1085
910
695
475
1025
845
640
425
970
790
570
335
905
715
510
245
840
660
450
-
795
610
355
-
730
560
235
-
5(Gry)
1430
1390
1345
1300
1250
1205
1150
1080
995
845
3(Blu)
4(Yel)
1(Red)
2(Org)
1240
1090
900
805
1200
1030
835
620
1145
980
780
440
1100
935
705
380
1040
850
635
300
975
800
565
-
915
730
490
-
860
665
410
-
790
590
335
-
730
525
200
-
5(Gry)
1400
1360
1325
1285
1240
1205
1160
1125
1075
1000
3(Blu)
4(Yel)
1(Red)
2(Org)
1340
1195
1025
855
1300
1160
980
800
1265
1115
935
745
1215
1065
880
680
1180
1025
835
635
1135
985
795
560
1100
935
745
515
1055
895
685
460
1015
850
635
420
965
800
585
360
5(Gry)
1720
1695
1690
1655
1620
1580
1540
1495
1465
1415
3(Blu)
4(Yel)
2(Org)
1(Red)
1565
1330
1210
1110
1535
1310
1180
1065
1530
1270
1135
1005
1490
1220
1085
960
1450
1180
1035
910
1420
1135
995
865
1375
1095
950
820
1335
1055
910
770
1295
1010
865
720
1255
970
810
670
5(Gry)
2070
2020
1985
1925
1890
1850
1795
1755
1690
1610
3(Blu)
4(Yel)
2(Org)
1(Red)
1815
1580
1380
1170
1775
1535
1325
1105
1730
1480
1275
1055
1690
1440
1220
985
1635
1380
1220
935
1595
1380
1165
870
1555
1340
1105
805
1500
1285
1060
765
1460
1235
1000
705
1410
1185
960
660
5(Gry)
2250
2205
2155
2110
2065
2020
1970
1925
1870
1790
3(Blu)
4(Yel)
1(Red)
2(Org)
2130
1890
1640
1420
2085
1835
1585
1370
2030
1790
1525
1305
1980
1740
1475
1255
1925
1690
1425
1190
1880
1640
1365
1135
1830
1590
1315
1065
1775
1535
1260
1010
1730
1480
1200
940
1675
1435
1140
880
] • Airflow shown is for bottom only return---air supply with factory supplied 3/4---in. (19 mm) washable filter(s).
For air delivery above 1800 CFM, see Air Delivery table for other options.
An airflow reduction of up to 7% may occur when using the factory---specified 4 5/16---in. (110 mm) wide, high efficiency media filter.
For best furnace efficiency when using the 4 5/16---in. (110 mm) wide media filter, adjust the blower speed tap to near the mid---point of the rise range.
For horizontal and downflow applications, use one side or bottom or bottom only as airflow reference.
12
COMBUSTION--AIR AND VENT PIPING FOR DIRECT VENT/2--PIPE (ALL SIZES) AND
NON--DIRECT VENT/1--PIPE (SIZES 040 THROUGH 120 ONLY) APPLICATIONS
UNIT SIZE
(BTUH)
40,000
60,000
0 to 2000
(0 to 610)
80,000
100,000
120,000
ALTITUDE
FT (M)
UNIT SIZE
(BTUH)
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
60,000
2 Pipe or 2-in
Concentric
80,000
2 Pipe or 2-in
Concentric
100,000
2 Pipe or 3-in
Concentric
2001 to 3000
(610 to 914)
2 Pipe or 3-in.
Concentric
NUMBER OF 90° ELBOWS
PIPE DIA
IN. (mm)*
1
2
3
4
5
6
1 (25)
1 (25)
5
(1.5)
NA
NA
NA
NA
NA
1-1/2 (38)
1-1/2 (38)
70
(21.3)
70
(21.3)
65
(19.8)
60
(18.3)
60
(18.3)
55
(16.8)
2 (51)
2 (51)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
1-1/2 (38)
1-1/2 (38)
20
(6.1)
15
(4.6)
10
(3.0)
5
(1.5)
NA
NA
2 (51)
2 (51)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
1-1/2 (38)
1-1/2 (38)
10
(3.0)
NA
NA
NA
NA
NA
2 (51)
2 (51)
55
(16.8)
50
(15.2)
35
(10.7)
30
(9.1)
30
(9.1)
20
(6.1)
2-1/2 (64)
2-1/2 (64)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
2 (51)
2 (51)
5
(1.5)
NA
NA
NA
NA
NA
2-1/2 (64)
2-1/2 (64)
40
(12.2)
30
(9.1)
20
(6.1)
20
(6.1)
10
(3.0)
NA
3 (76)
3 (76)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
2-1/2 (64)
one disk
2-1/2 (64)
10
(3.0)
NA
NA
NA
NA
NA
3 (76)†
NA
45
(13.7)
40
(12.2)
35
(10.7)
30
(9.1)
25
(7.6)
20
(6.1)
3 (76) † no disk
3 (76)†
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
DIRECT VENT (2-PIPE) ONLY
40,000
120,000
PIPE DIA
IN. (mm)*
NON-DIRECT
VENT (1-PIPE)
ONLY
NON-DIRECT
VENT (1-PIPE)
ONLY
NUMBER OF 90° ELBOWS
PIPE DIA
IN. (mm)*
PIPE DIA
IN. (mm)*
1
2
3
4
5
6
1-1/2 (38)
1-1/2 (38)
67
(20.4)
62
(18.9)
57
(17.4)
52
(15.8)
52
(15.8)
47
(14.3)
2 (51)
2 (51)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
1-1/2 (38)
1-1/2 (38)
17
(5.2)
12
(3.7)
7
(2.1)
NA
NA
NA
2 (51)
2 (51)
70
(21.3)
67
(20.4)
66
(20.1)
61
(18.6)
61
(18.6)
61
(18.6)
2 (51)
2 (51)
49
(14.9)
44
(13.4)
30
(9.1)
25
(7.6)
25
(7.6)
15
(4.6)
2-1/2 (64)
2-1/2 (64)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
2-1/2 (64)
2-1/2 (64)
35
(10.7)
26
(7.9)
16
(4.9)
16
(4.9)
6
(1.8)
NA
3 (76)
3 (76)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
66
(20.1)
61
(18.6)
3 (76)
NA
14
(4.3)
9
(2.7)
NA
NA
NA
NA
NA
3 (76)†
63
(19.2)
62
(18.9)
62
(18.9)
61
(18.6)
61
(18.6)
61
(18.6)
3 (76)† no disk
NA
70
(21.3)
70
(21.3)
63
(19.2)
56
(17.1)
50
(15.2)
43
(13.1)
4 (102)† no
disk
4 (102)† no disk
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
See notes at end of table.
13
353AAV
ALTITUDE
FT (M)
DIRECT VENT (2-PIPE) ONLY
COMBUSTION--AIR AND VENT PIPING FOR DIRECT VENT/2--PIPE (ALL SIZES) AND
NON--DIRECT VENT/1--PIPE (SIZES 040 THROUGH 120 ONLY) APPLICATIONS (CON’T.)
353AAV
ALTITUDE
FT (M)
3001 to 4000
(914 to 1219)
UNIT SIZE
(BTUH)
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
40,000
2 Pipe or 2-in
Concentric
60,000
2 Pipe or 2-in
Concentric
80,000
2 Pipe or 2-in
Concentric
100,000
2 Pipe or 3-in
Concentric
120,000
2 Pipe or 3-in.
Concentric
4† no disk
ALTITUDE
FT (M)
4001 to 5000‡
(1219 to 1524)
UNIT SIZE
(BTUH)
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
60,000
2 Pipe or 2-in
Concentric
80,000
2 Pipe or 2-in
Concentric
100,000
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
NUMBER OF 90° ELBOWS
PIPE DIA
IN (mm)*
1
2
3
4
5
6
1-1/2 (38)
1-1/2 (38)
64
(19.5)
59
(18.0)
54
(16.5)
49
(14.9)
48
(14.6)
43
(13.1)
2 (51)
2 (51)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
1-1/2 (38)
1-1/2 (38)
16
(4.9)
11
(3.4)
6
(1.8)
NA
NA
NA
2 (51)
2 (51)
68
(20.7)
63
(19.2)
62
(18.9)
57
(17.4)
57
(17.4)
56
(17.1)
2 (51)
2 (51)
46
(14.0)
41
(12.5)
28
(8.5)
23
(7.0)
22
(6.7)
13
(4.0)
2-1/2 (64)
2-1/2 (64)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
2-1/2 (64)
2-1/2 (64)
33
(10.1)
24
(7.3)
15
(4.6)
14
(4.3)
5
(1.5)
NA
3 (76)
3 (76)
70
(21.3)
70
(21.3)
70
(21.3)
66
(20.1)
61
(18.6)
56
(17.1)
3 (76)† no disk
NA
65
(19.8)
58
(17.7)
51
(15.5)
44
(13.4)
38
(11.6)
31
(9.4)
NA
3 (76)†
59
(18.0)
59
(18.0)
58
(17.7)
57
(17.4)
57
(17.4)
56
(17.1)
4 (102)† no
disk
4 (102) † no disk
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
DIRECT VENT (2-PIPE) ONLY
40,000
120,000
PIPE DIA
IN (mm)*
NON-DIRECT
VENT (1-PIPE)
ONLY
NON-DIRECT
VENT (1-PIPE)
ONLY
NUMBER OF 90° ELBOWS
PIPE DIA
IN. (mm)*
PIPE DIA
IN. (mm)*
1
2
3
4
5
6
1-1/2 (38)
1-1/2 (38)
60
(18.3)
55
(16.8)
50
(15.2)
45
(13.7)
44
(13.4)
39
(11.9)
2 (51)
2 (51)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
1-1/2 (38)
1-1/2 (38)
15
(4.6)
10
(3.0)
5
(1.5)
NA
NA
NA
2 (51)
2 (51)
64
(19.5)
59
(18.0)
58
(17.7)
53
(16.2)
52
(15.8)
52
(15.8)
2 (51)
2 (51)
44
(13.4)
39
(11.9)
26
(7.9)
21
(6.4)
20
(6.1)
11
(3.4)
2-1/2 (64)
2-1/2 (64)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
2-1/2 (64)
2-1/2 (64)
31
(9.4)
22
(6.7)
13
(4.0)
12
(3.7)
NA
NA
3 (76)
3 (76)
70
(21.3)
70
(21.3)
67
(20.4)
62
(18.9)
57
(17.4)
52
(15.8)
3 (76)†
no disk
NA
53
(16.2)
46
(14.0)
40
(12.2)
33
(10.1)
26
(7.9)
20
(6.1)
NA
3 (76)†
56
(17.1)
55
(16.8)
54
(16.5)
53
(16.2)
52
(15.8)
52
(15.8)
4 (102)† no
disk
4 (102)† no disk
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
See notes at end of table.
14
COMBUSTION--AIR AND VENT PIPING FOR DIRECT VENT/2--PIPE (ALL SIZES) AND
NON--DIRECT VENT/1--PIPE (SIZES 040 THROUGH 120 ONLY) APPLICATIONS (CON’T.)
5001 to 6000‡
(1524 to 1829)
UNIT SIZE
(BTUH)
6001 to 7000‡
(1829 to 2134)
TERMINATION
TYPE
40,000
2 Pipe or 2-in
Concentric
60,000
2 Pipe or 2-in
Concentric
80,000
2 Pipe or 2-in
Concentric
100,000
2 Pipe or 3-in
Concentric
120,000
ALTITUDE
FT (M)
DIRECT VENT (2-PIPE) ONLY
UNIT SIZE
(BTUH)
2 Pipe or 3-in.
Concentric
PIPE DIA
IN. (mm)*
40,000
2 Pipe or 2-in
Concentric
60,000
2 Pipe or 2-in
Concentric
80,000
2 Pipe or 2-in
Concentric
100,000
2 Pipe or 3-in
Concentric
120,000
2 Pipe or 3-in.
Concentric
NUMBER OF 90° ELBOWS
PIPE DIA
IN. (mm)*
1
2
3
4
5
6
1-1/2 (38)
1-1/2 (38)
57
(17.4)
52
(15.8)
47
(14.3)
42
(12.8)
40
(12.2)
35
(10.7)
2 (51)
2 (51)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
1-1/2 (38)
1-1/2 (38)
14
(4.3)
9
(2.7)
NA
NA
NA
NA
2 (51)
2 (51)
60
(18.3)
55
(16.8)
54
(16.5)
49
(14.9)
48
(14.6)
47
(14.3)
2 (51)
2 (51)
41
(12.5)
36
(11.0)
23
(7.0)
18
(5.5)
17
(5.2)
8
(2.4)
2-1/2 (64)
2-1/2 (64)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
2-1/2 (64)
2-1/2 (64)
29
(8.8)
21
(6.4)
12
(3.7)
11
(3.4)
NA
NA
3 (76)
3 (76)
70
(21.3)
67
(20.4)
62
(18.9)
57
(17.4)
52
(15.8)
47
(14.3)
3 (76)†
no disk
NA
42
(12.8)
35
(10.7)
29
(8.8)
22
(6.7)
15
(4.6)
9
(2.7)
NA
3 (76)†
53
(16.2)
52
(15.8)
50
(15.2)
49
(14.9)
48
(14.6)
47
(14.3)
4 (102)† no
disk
4 (102)† no disk
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
70
(21.3)
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
NON-DIRECT
VENT (1-PIPE)
ONLY
NON-DIRECT
VENT (1-PIPE)
ONLY
NUMBER OF 90° ELBOWS
PIPE DIA
IN. (mm)*
PIPE DIA
IN. (mm)*
1
2
3
4
5
6
1-1/2 (38)
1-1/2 (38)
53
(16.2)
48
(14.6)
43
(13.1
38
(11.6)
37
(11.3)
32
(9.8)
2 (51)
2 (51)
70
(21.3)
70
(21.3)
68
(20.7)
67
(20.4)
66
(20.1)
64
(19.5)
1-1/2 (38)
1-1/2 (38)
13
(4.0)
8
(2.4)
NA
NA
NA
NA
2 (51)
2 (51)
57
(17.4)
52
(15.8)
50
(15.2)
45
(13.7)
44
(13.4)
43
(13.1)
2 (51)
2 (51)
38
(11.6)
33
(10.1)
21
(6.4)
16
(4.9)
15
(4.6)
6
(1.8)
2-1/2 (64)
2-1/2 (64)
70
(21.3)
70
(21.3)
68
(20.7)
67
(20.4)
66
(20.1)
64
(19.5)
2-1/2 (64)
2-1/2 (64)
27
(8.2)
19
(5.8)
10
(3.0)
9
(2.7)
NA
NA
3 (76)
3 (76)
68
(20.7)
63
(19.2)
58
(17.7)
53
(16.2)
48
(14.6)
43
(13.1)
3 (76)†
no disk
NA
31
(9.4)
24
(7.3)
18
(5.5)
11
(3.4)
NA
NA
NA
3 (76)†
49
(14.9)
48
(14.6)
47
(14.3)
45
(13.7)
44
(13.4)
43
(13.1)
See notes at end of table.
15
353AAV
ALTITUDE
FT (M)
COMBUSTION--AIR AND VENT PIPING FOR DIRECT VENT/2--PIPE (ALL SIZES) AND
NON--DIRECT VENT/1--PIPE (SIZES 040 THROUGH 120 ONLY) APPLICATIONS (CON’T.)
ALTITUDE
FT (M)
UNIT SIZE
(BTUH)
DIRECT VENT (2-PIPE) ONLY
353AAV
TERMINATION
TYPE
7001 to 8000‡
(2134 to 2438)
40,000
2 Pipe or 2-in
Concentric
60,000
2 Pipe or 2-in
Concentric
80,000
2 Pipe or 2-in
Concentric
100,000
2 Pipe or 3-in
Concentric
120,000
ALTITUDE
FT (M)
UNIT SIZE
(BTUH)
2 Pipe or 3-in.
Concentric
40,000
2 Pipe or 2-in
Concentric
60,000
2 Pipe or 2-in
Concentric
80,000
2 Pipe or 2-in
Concentric
100,000
2 Pipe or 3-in
Concentric
120,000
2 Pipe or 3-in.
Concentric
NUMBER OF 90° ELBOWS
PIPE DIA
IN. (mm)*
1
2
3
4
5
6
1-1/2 (38)
1-1/2 (38)
49
(14.9)
44
(13.4)
39
(11.9)
34
(10.4)
33
(10.1)
28
(6.5)
2 (51)
2 (51)
66
(20.1)
65
(19.8)
63
(19.2)
62
(18.9)
60
(18.3)
59
(18.0)
1-1/2 (38)
1-1/2 (38)
12
(3.7)
7
(2.1)
NA
NA
NA
NA
2 (51)
2 (51)
53
(16.2)
48
(14.6)
46
(14.0)
41
(12.5)
40
(12.2)
38
(11.6)
2 (51)
2 (51)
36
(11.0)
31
(9.4)
19
(5.8)
14
(4.3)
12
(3.7)
NA
2-1/2 (64)
2-1/2 (64)
66
(20.1)
65
(19.8)
63
(19.2)
62
(18.9)
60
(18.3)
59
(18.0)
2-1/2 (64)
2-1/2 (64)
25
(7.6)
17
(5.2)
8
(2.4)
7
(2.1)
NA
NA
3 (76)
3 (76)
63
(19.2)
58
(17.7)
53
(16.2)
48
(14.6)
43
(13.1)
38
(11.6)
3 (76)† no disk
NA
20
(6.1)
13
(4.0)
7
(2.1)
NA
NA
NA
NA
3 (76)†
46
(14.0)
44
(13.4)
43
(13.1)
41
(12.5)
40
(12.2)
38
(11.6)
4 (102)† no
disk
4 (102)† no disk
61
(18.6)
56
(17.1)
51
(15.5)
46
(14.0)
41
(12.5)
36
(11.0)
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
8001 to 9000‡
(2438 to 2743)
PIPE DIA
IN. (mm)*
NON-DIRECT
VENT (1-PIPE)
ONLY
PIPE DIA
IN. (mm)*
NON-DIRECT
VENT (1-PIPE)
ONLY
NUMBER OF 90° ELBOWS
PIPE DIA
IN. (mm)*
1
2
3
4
5
6
1-1/2 (38)
1-1/2 (38)
46
(14.0)
41
(12.5)
36
(11.0)
31
(9.4)
29
(8.8)
24
(7.3)
2 (51)
2 (51)
62
(18.9)
60
(18.3)
58
(17.7)
56
(17.1)
55
(16.8)
53
(16.2)
1-1/2 (38)
1-1/2 (38)
11
(3.4)
6
(1.8)
NA
NA
NA
NA
2 (51)
2 (51)
49
(14.9)
44
(13.4)
42
(12.8)
37
(11.3)
35
(10.7)
34
(10.4)
2 (51)
2 (51)
33
(10.1)
28
(8.5)
17
(5.2)
12
(3.7)
10
(3.0)
NA
2-1/2 (64)
2-1/2 (64)
62
(18.9)
60
(18.3)
58
(17.7)
56
(17.1)
55
(16.8)
53
(16.2)
2-1/2 (64)
2-1/2 (64)
23
(7.0)
15
(4.6)
7
(2.1)
5
(1.5)
NA
NA
3 (76)
3 (76)
59
(18.0)
54
(16.5)
49
(14.9)
44
(13.4)
39
(11.9)
34
(10.4)
3 (76)† no disk
NA
10
(3.0)
NA
NA
NA
NA
NA
NA
3 (76)†
43
(13.1)
41
(12.5)
39
(11.9)
37
(11.3)
35
(10.7)
34
(10.4)
4 (102)† no
disk
4† no disk
35
(10.7)
30
(9.1)
25
(7.6)
20
(6.1)
15
(4.6)
10
(3.0)
See notes at end of table.
16
COMBUSTION--AIR AND VENT PIPING FOR DIRECT VENT/2--PIPE (ALL SIZES) AND
NON--DIRECT VENT/1--PIPE (SIZES 040 THROUGH 120 ONLY) APPLICATIONS (CON’T.)
UNIT SIZE
(BTUH)
NON-DIRECT
VENT (1-PIPE)
ONLY
NUMBER OF 90° ELBOWS
TERMINATION
TYPE
PIPE DIA
IN. (mm)*
PIPE DIA
IN. (mm)*
1
2
3
4
5
6
2 Pipe or 2-in
1-1/2 (38)
1-1/2 (38)
42
(12.8)
37
(11.3)
32
(9.8)
27
(8.2)
25
(7.6)
20
(6.1)
Concentric
2 (51)
2 (51)
57
(17.4)
55
(16.8)
53
(16.2)
51
(15.5)
49
(14.9)
47
(14.3)
60,000
2 Pipe or 2-in
Concentric
2 (51)
2 (51)
45
(13.7)
40
(12.2)
38
(11.6)
33
(10.1)
31
(9.4)
29
(8.8)
2 Pipe or 2-in
Concentric
2 (51)
2 (51)
30
(9.1)
25
(7.6)
14
(4.3)
9
(2.7)
7
(2.1)
NA
80,000
2-1/2 (64)
2-1/2 (64)
57
(17.4)
55
(16.8)
53
(16.2)
51
(15.5)
49
(14.9)
47
(14.3)
2 Pipe or 3-in
Concentric
2-1/2 (64)
2-1/2 (64)
21
(6.4)
13
(4.0)
5
(1.5)
NA
NA
NA
100,000
3 (76)
3 (76)
54
(16.5)
49
(14.9)
44
(13.4)
39
(11.9)
34
(10.4)
29
(8.8)
2 Pipe or 3-in.
Concentric
NA
3 (76)†
120,000
39
(11.9)
37
(11.3)
35
(10.7)
33
(10.1)
31
(9.4)
29
(8.8)
4 (102)† no
disk
4 (102)† no disk
10
(3.0)
5
(1.5)
NA
NA
NA
NA
40,000
9001 to 10,000‡
(2743 to 3048)
DIRECT VENT (2-PIPE) ONLY
* Disk usage-Unless otherwise specified, use perforated disk assembly (factory-supplied in loose parts bag).
# If one disk is stated, separate 2 halves of perforated disk assembly and use shouldered disk half. When using shouldered disk half, install screen side toward inlet box.
† Wide radius elbow.
‡ Vent sizing for Canadian installations over 4500 ft (1370 M) above sea level are subject to acceptance by the local authorities having jurisdiction. NA-Not Allowed;
pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes.
3. Assume two 45° elbows equal one 90° elbow. Wide radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft (1.5 M) for all applications.
6. Use 3-in. (76 mm) diameter vent termination kit for installations requiring 4-in (102 mm) diameter pipe.
17
353AAV
ALTITUDE
FT (M)
MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH -- FT (M) WITH AND
WITHOUT INSULATION IN WINTER DESIGN TEMPERATURE AMBIENT*
FURNACE SIZE
040
353AAV
060
080
100
120
WINTER DESIGN
TEMPERATURE
°F 〈°C)
MAX PIPE
DIAMETER
IN (mm)
WITHOUT
INSULATION
FT (M)
WITH 3/8–IN. OR THICKER
INSULATION†
FT (M)
20 (---7)
0 (---18)
---20 (---29)
20 (---7)
0 (---18)
---20 (---29)
20 (---7)
0 (---18)
---20 (---29)
20 (---7)
0 (---18)
---20 (---29)
20 (---7)
0 (---18)
---20 (---29)
20 (---7)
0 (---18)
---20 (---29)
20 (---7)
0 (---18)
---20 (---29)
20 (---7)
0 (---18)
---20 (---29)
20 (---7)
0 (---18)
---20 (---29)
1.5 (38)
1.5 (38)
1.5 (38)
2 (51)
2 (51)
2 (51)
2 (51)
2 (51)
2 (51)
2 (51)
2 (51)
2 (51)
2.5 (64)
2.5 (64)
2.5 (64)
2.5 (64)
2.5 (64)
2.5 (64)
3 (76)
3 (76)
3 (76)
3 (76)
3 (76)
3 (76)
4 (102)
4 (102)
4 (102)
51 (16)
28 (9)
16 (5)
45 (14)
22 (7)
10 (3)
65 (20)
35 (11)
20 (6)
55 (17)
48 (15)
30 (9)
70 (21)
47 (14)
28 (9)
40 (12)
40 (12)
38 (12)
70 (21)
50 (15)
28 (9)
70 (21)
61 (19)
37 (11)
70 (21)
48 (15)
23 (7)
70 (21)
70 (21)
70 (21)
70 (21)
70 (21)
58 (18)
70 (21)
70 (21)
70 (21)
55 (17)
55 (17)
55 (17)
70 (21)
70 (21)
70 (21)
40 (12)
40 (12)
40 (12)
70 (21)
70 (21)
70 (21)
70 (21)
70 (21)
70 (21)
70 (21)
70 (21)
70 (21)
* Pipe length ft (M) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length
as specified in Table.
† Insulation thickness based on R value of 3.5 per in.
18
ELECTRICAL DATA
UNIT SIZE
UNIT VOLTS --- HERTZ --- PHASE
MAXIMUM UNIT AMPS
UNIT AMPACITY
MINIMUM WIRE SIZE
MAXIMUM WIRE LENGTH --- FT (M)
MAXIMUM FUSE OR CKT BKR (Amps)**
TRANSFORMER (24v)
HEATING
EXTERNAL CONTROL
POWER AVAILABLE
COOLING
AIR CONDITIONING BLOWER RELAY
036040
115---60---1
8
10.8
14
34 (10.3)
15
036060
115---60---1
9.4
12.5
14
29 (8.8)
15
036080
048080
115---60---1
115---60---1
9.4
9.6
12.5
12.8
14
14
29 (8.8)
29 (8.8)
15
15
40va
12va
21va
24v Standard
060100
115---60---1
12.1
15.9
12
36 (10.9)
20
060120
115---60---1
12.1
15.9
12
36 (10.9)
20
353AAV
TYPICAL WIRING SCHEMATIC
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
NOTE 2
W
FIVE WIRE
THREE-WIRE
HEATING-ONLY
C
R
G
Y
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE
PHASE
BLOWER DOOR SWITCH
BLK
BLK
WHT
WHT
GND
115-V FIELDSUPPLIED
DISCONNECT
W
GND
AUXILIARY
J-BOX
C
O
N
T
R
O
L
R
208/230-V
SINGLE
PHASE
G
COM
GND
NOTE 1
CONDENSING
UNIT
Y/Y2
24-V
TERMINAL
BLOCK
FURNACE
TWO
WIRE
NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A99440
19
TYPICAL INSTALLATIONS
COMBUSTION AIR PIPE
(DIRECT VENT/2-PIPE APPLICATION)
OUTDOOR UNIT
VENT PIPE
A/C COIL
353AAV
HUMIDIFIER
COMBUSTION
AIR INLET
(NON-DIRECT
1-PIPE APPLICATION)
GAS-FIRED
WATER HEATER
ELECTRONIC
AIR CLEANER
FRONT OF
FURNACE
AIRFLOW
A05064
Upflow Application
ELECTRONIC
AIR CLEANER
VENT
COMBUSTION AIR
INLET (NON-DIRECT
VENT/ 1-PIPE APPLICATION
COMBUSTION
AIR (DIRECT VENT/
2 PIPE APPLICATION
HUMIDIFIER
OUTDOOR
UNIT
A/C COIL
AIRFLOW
FRONT OF
FURNACE
A05065
Downflow Application
20
TYPICAL INSTALLATIONS (CONTINUED)
COMBUSTION-AIR INLET
(NON-DIRECT VENT/1-PIPE APPLICATION)
COMBUSTION–AIR PIPE
DIRECT VENT/2-PIPE APPLICATION)
353AAV
VENT PIPE
ELECTRONIC
AIR CLEANER
FRONT OF FURNACE
FURNACE
CONDENSATE
DRAIN
REFRIGERATION
PIPING
AIR CONDITIONING
COIL
AIRFLOW
A05066
Attic -- Horizontal Application
COMBUSTION– AIR PIPE
(DIRECT VENT/2-PIPE
APPLICATION)
COMBUSTION - AIR INLET
(NON-DIRECT VENT/
1-PIPE APPLICATION)
VENT
PIPE
REFRIGERATION
PIPING
AIR CONDITIONING
COIL
ELECTRONIC
AIR CLEANER
FURNACE CONDENSATE
DRAIN
FRONT OF
FURNACE
A08422
Crawlspace -- Horizontal Application
21
GUIDE SPECIFICATIONS
Filters
Plus 90x
Furnace shall have reusable--type filters. Filter shall be ______ in
(x) ______in. An accessory high efficiency Media Filter is
available as an option. ______________Media Filter.
Single--Stage/Deluxe Gas Furnace
353AAV
GENERAL
System Description
Casing
Casing shall be of .030 in. (.03 mm) thickness minimum,
pre--painted galvanized steel.
Furnish a _________________ (4--way multipoise) fixed
capacity gas--fired condensing furnace for use with natural gas or
propane (factory authorized conversion kit required for propane);
furnish cold air return plenum; furnish external medial cabinet for
use with accessory media filter or standard filter.
353AAV
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI
Z 21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be 3rd party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will carry the CSA Blue Star® and Blue Flame® labels.
Unit efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest GAMA Consumer’s Directory of Certified Efficiency
Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendation.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
request.
Warranty certificate available upon
Inducer motor shall be soft mounted to reduce vibration
transmission.
Primary Heat Exchangers
Primary Heat exchangers shall be 3--Pass 20 gauge corrosion
resistant aluminized steel of fold--and--crimp sectional design,
which operates under negative pressure.
Secondary Heat Exchangers
Secondary Heat exchangers shall be of a flow--through design
having a patented interior laminate coating of polypropylene for
greater corrosion resistance with fold--and--crimp design, which
operates under negative pressure.
Controls
Controls shall include a microprocessor based integrated
electronic control board with at least 11 service troubleshooting
codes displayed via diagnostic flashing LED light on the control,
has ability to store fault codes, when activated a self--test feature
checks all major functions of the furnace within one minute, and
a replaceable automotive--type circuit protection fuse. Multiple
operational settings available including separate blower speeds.
Cooling airflow will be selectable between 350 or 400 CFM per
ton of air conditioning. Features will also include temporary
reduced airflow in the cooling mode for improved
dehumidification when a Thermidistat® is selected as the
thermostat.
Operating Characteristics
PRODUCTS
Equipment
Components shall include: slow--opening gas valve to reduce
ignition noise, regulate gas flow, with electric switch gas
shut--off; flame proving sensor, hot surface igniter, pressure
switch assembly verifies inducer operation; flame rollout switch,
drain tubing and installed condensate drain trap, blower and
inducer assembly, 40va transformer; low--voltage (heating)
(heating/ cooling) thermostat.
Blower Wheel and Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed bearings, of _____ hp, and
shall be multiple--speed direct drive. Blower motor shall be soft
mounted to the blower scroll to reduce vibration transmission.
E2010 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231
Inducer Motor
Heating
Capacity
shall
be_________Btuh
input;____________Btuh output capacity. Fuel Gas Efficiency
shall be 93% AFUE. Air delivery shall be__________ CFM
minimum at 0.50 in. wc. external static pressure. Dimensions
shall be: depth__________in.; width__________in.; height
_________in. (casing only). Height shall be__________in. with
A/C coil and____________in. overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase
(nominal). Minimum wire size shall be_________AWG;
maximum fuse size or HACR--type, designated circuit breaker
shall be _______Amps.
Special Features
Refer to section of the product data sheet identifying accessories
and descriptions for specific features and available enhancements.
Printed in U.S.A.
Edition Date: 09/10
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
22
Catalog No. PDS353AAV--- 03
Replaces: PDS353AAV---02
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Format : application/pdf Creator : BACT559 Title : PDS353AAV-03 Create Date : 2010:09:08 16:31:27-04:00 Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2010:09:08 16:31:27-04:00 Producer : Acrobat Distiller 8.1.0 (Windows) Document ID : uuid:f45aee07-645a-4152-8d71-6d3a40246634 Instance ID : uuid:167aec62-b007-4aa3-9f41-d1ded6bc3f95 Page Count : 22 Author : BACT559EXIF Metadata provided by EXIF.tools