Bryant Puron 213A Users Manual PDS 213A.18.1

213A to the manual b86e83c6-2b90-429c-8347-040b45b9c51e

2015-02-02

: Bryant Bryant-Puron-213A-Users-Manual-412051 bryant-puron-213a-users-manual-412051 bryant pdf

Open the PDF directly: View PDF PDF.
Page Count: 32

Product Data
Model 213A
Legacyt-- RNC Series Heat Pump
with PuronrRefrigerant
Sizes 018 to 060
1 - - 1 / 2 To 5 N o m i n a l To n s
Fig. 1 – 213A
Bryant’s heat pumps with Puronrrefrigerant provide a collection
of features unmatched by any other family of equipment. The
213A has been designed utilizing Bryant’s Puron refrigerant. The
environmentally sound refrigerant allows consumers to make a
responsible decision in the protection of the earth’s ozone layer.
As an Energy StarrPartner, Bryant Heating & Cooling Systems
has determined that this product meets the Energy Star r
guidelines for energy efficiency. Refer to the combination ratings
in the Product Data for system combinations that meet Energy
Starrguidelines.
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
S13 SEER/ 10.1 -- 10.8 EER/ 7.7 -- 8.3 HSPF (nominal)
SMicrotube Technologytrefrigeration system
SIndoor air quality accessories available
Sound
SSound level as low as 74 dBA
Comfort
SSystem supports Thermidistattor standard thermostat
controls
Reliability
SPuronrrefrigerant -- environmentally sound, won’t
deplete the ozone layer and low lifetime service cost.
SFront--seating service valves
SScroll compressor
SInternal pressure relief valve
SInternal thermal overload
SHigh pressure switch
SLoss of charge switch
SFilter drier
SBalanced refrigeration system for maximum reliability
Durability
DuraGuardtprotection package:
SSolid, Durable sheet metal construction
SDense wire coil guard
SBaked--on, complete coverage, powder paint
Applications
SLong--line -- up to 250 feet total equivalent length, up
to 200 feet condenser above evaporator, or up to 80 ft.
evaporator above condenser (See Longline Guide for
more information.)
SLow ambient (down to --20_F) with accessory kit
Warranty
S5 year limited compressor warranty
S5 year limited parts warranty
2
MODEL NUMBER NOMENCLATURE
1234 5 678910111214
N N N A A/N N N N N A/N A/N N A
21 3 A N A 036 0 0 0 0
Product
Family
Tier SEER Major
Series
Voltage Variations Cooling Capacity Open Open Open Minor
Series
2=HP 1=
Legacy
RNC
3=13 SEER A=Puron N= 208---230 ---1
or 208/230---1
A = Standard 0=Not
Defined
0=Not
Defined
0=Not
Defined
A=
Original
Series
the environmentally sound refrigerant
REGISTERED
ISO 9001:2000
As an Energy Star®Partner, Bryant Heating
& Cooling systems has determined that this
product meets the ENERGY STAR®
guidelines for energy efficiency.
Refer to the combination ratings in Product
Data for system combinations that meet
Energy Star guidelines.
STANDARD FEATURES
Feature 18 24 30 36 42 48 60
Puron Refrigerant XXXXXXX
13 SEER XXXXXXX
Scroll Compressor XXXXXXX
DenseWireCoilGuard XXXXXXX
FieldInstalledFilterDrier XXXXXXX
Front Seating Service Valves XXXXXXX
Internal Pressure Relief Valve XXXXXXX
Internal Thermal Overload XXXXXXX
Long Line capability XXXXXXX
Low Ambient capability with Kit XXXXXXX
Suction Line Accumulator XXXXXXX
High Pressure Switch XXXXXXX
Loss of Charge Switch XXXXXXX
213A
3
PHYSICAL DATA
UNIT SIZE SERIES 018---A 024---A 030---A 036---A 042---A 048---A 060---A
Operating Weight (lb) 146 162 203 207 246 263 279
Shipping Weight (lb) 169 189 235 239 278 293 311
Compressor Type Scroll
REFRIGERANT Puron®(R---410A)
Control TXV (Puron Hard Shutoff)
Charge (lb) 5.25 5.9 7.6 7.65 8.4 11.75 12.35
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty. (CFM) 2196 2614 2614 3365 3810 4046 4046
Motor HP 1/10 1/10 1/10 1/4 1/5 1/5 1/5
Motor RPM 1100 1100 1100 1100 800 800 800
COND COIL
Face Area (Sq. ft.) 13.13 15.09 25.87 25.87 25.15 20.12 22.63
Fins per In. 25 20 20 20 20 20 20
Rows 1111122
Circuits 4566688
VALVECONNECT.(In.ID)
Vapor 5/8 5/8 3/4 3/4 7/8 7/8 7/8
Liquid 3/8
REFRIGERANT TUBES* (In. OD)
Vapor (0---80 ft. Tube Length) 5/8 5/8 3/4 3/4 7/8 7/8 1 --- 1 / 8
Liquid (0---80 ft. Tube Length) 3/8
* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.
Note: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
PURON 1--STAGE HEAT PUMP APPLICATIONS
LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80
ft. or when there is more than 20 ft. vertical separation between
indoor and outdoor units. These applications require additional
accessories and system modifications for reliable system
operation. The maximum allowable total equivalent length is 250
ft. The maximum vertical separation is 200 ft. when outdoor unit
is above indoor unit, and 80 ft. when the outdoor unit is below
the indoor unit. Refer to Accessory Usage Guideline below for
required accessories. See Longline Application Guideline for
required piping and system modifications. Also, refer to the table
below for the acceptable vapor tube diameters based on the total
length to minimize the cooling capacity loss.
Unit Nominal Size (Btuh)
Acceptable
Vapor Line
Diameters
(In. OD)
Cooling Capacity Loss (%)Total Equivalent Line Length (ft.)
Standard Application Long Line Application Requires Accessories
25 50 80 80+ 100 125 150 175 200 225 250
18000
1 --- S t a g e P u r o n H P
1/2 1 2 3 3 4 6 7 8 9 10 12
5/8 0 0 1 1 1 1 2 2 3 3 3
24000
1 --- S t a g e P u r o n H P
5/8 0 1 1 1 2 3 3 4 4 5 6
3/4 0 0 0 0 0 1 1 1 1 1 2
30000
1 --- S t a g e P u r o n H P
5/8 1 2 3 3 3 4 5 6 7 8 9
3/4 0 0 1 1 1 1 2 2 2 3 3
7/8 0 0 0 0 0 1 1 1 1 1 1
36000
1 --- S t a g e P u r o n H P
5/8 1 2 4 4 5 6 7 9 10 11 13
3/4 0 0 1 1 1 2 2 3 3 4 4
7/8 0 0 0 0 0 1 1 1 1 2 2
42000
1 --- S t a g e P u r o n H P
3/4 0 1 2 2 2 3 4 4 5 6 6
7/8 0 0 1 1 1 1 2 2 2 3 3
48000
1 --- S t a g e P u r o n H P
3/4 0 1 2 2 3 4 5 5 6 7 8
7/8 0 0 1 1 1 2 2 2 3 3 4
60000
1 --- S t a g e P u r o n H P
3/4 1 2 4 4 5 6 7 9 10 11 12
7/8 0 1 2 2 2 3 4 4 5 5 6
11/8 0 0 0 0 1 1 1 1 1 1 2
Standard Length = 80 ft. or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See
Long Line Application Guidelines
213A
4
ACCESSORIES
ORDER NUMBER DESCRIPTION 018---A 024---A 030---A 036---A 042---A 048---A 060 ---A
HC34GE239 BALL BEARING MOTOR X
HC34GE240 BALL BEARING MOTOR X X
HC38GE228 BALL BEARING MOTOR X
HC40GE226 BALL BEARING MOTOR X
HC40GE228 BALL BEARING MOTOR X X
KAACH1201AAA CRANKCASE HTR X S S
KAACH1401AAA CRANKCASE HTR XXXX
KSACY0101AAA CYCLE PROTECTOR XXXXXXX
KAAFT0101AAA FREEZE THERMOSTAT XXXXXXX
KSAHS1701AAA HARD START XXXXXXX
KHAIR0101AAA ISOLATION RELAY XXXXXXX
KSALA0301410 LOW AMBIENT PSW XXXXXXX
KSALA0601AAA MOTORMASTER 230V XXXXXXX
KHAOT0201SEC OUTDOOR THERMOSTAT XXXXXXX
KHAOT0301FST OUTDOOR THERMOSTAT XXXXXXX
KHALS0401LLS SOLENOID VALVE XXXXXXX
KSASH0601COP SOUND BLKT XXXXXX
KSASH2101COP SOUND BLKT X
KAACS0201PTC STARTASSISTPTC XXXXXXX
KSASF0101AAA SUPPORT FEET XXXXXXX
KAATD0101TDR TIME DELAY RELAY XXXXXXX
KSATX0201PUR TXV PURON HSO XXX
KSATX0301PUR TXV PURON HSO X X
KSATX0401PUR TXV PURON HSO X
KSATX0501PUR TXV PURON HSO X
x = Accessory S = Standard
ACCESSORY THERMOSTATS
THERMOSTAT / SUBBASE
PKG. DESCRIPTION
TSTATBBPRH01--- B* ThermidistattControl — Non---Programmable/Programmable Thermostat with Humidity Control (For use in
Dual Fuel, AC, HP, and 2S applications. Includes Outdoor Air Temperature Sensor.)
TSTATBBPHH01--- B* Hybrid Heatt(Dual Fuel) Thermostat — Auto Changeover, 7--- Day Programmable, °F/°C, Includes Outdoor
Sensor (TSTATXXSEN01--- B)
TSTATBBPHP01--- B Thermostat — Auto Changeover, 7--- Day Programmable, °F/°C , 2 --- S t a g e H e a t , 1 --- S t a g e C o o l
TSTATBBNHP01--- C Thermostat — Auto Changeover, Non--- Programmable, °F/°C , 2 --- S t a g e H e a t , 1 --- S t a g e C o o l
TSTATBBSHP01 Standard Programmable Thermostat—Manual Changeover, 5--- 2 Day Programmable, °F/°C , 1 --- S t a g e H e a t /
1 --- S t a g e C o o l
TSTATBBBHP01--- B* Builder’s Thermostat — Heat Pump, Non --- Programmable, °F/°C , 2 --- S t a g e H e a t , 1 --- S t a g e C o o l , M a n u a l
Changeover
TSTATXXSEN01--- B** Outdoor Air Temperature Sensor
TSTATXXNBP01 Backplate for Non --- Programmable Thermostat
TSTATXXPBP01 Backplate for Programmable Thermostat and ThermidistattControl
TSTATXXSBP01 Backplate for Standard Programmable Thermostat
TSTATXXBBP01 Backplate for Builder’s Thermostat
TSTATXXCNV10{Thermostat Conversion Kit (4 to 5 Wire) — 10 Pack
* Do not use in zoning heat pump applications.
** Outdoor temperature sensor is an accessory for all Bryant electronic thermostats, except the non ---programmable air conditioner version and builder;s
thermostats. It allows the temperature at a remote location (outdoors) to be displayed on the thermostat. The outdoor air temperature sensor must be used
with the dual fuel thermostat.
{Thermostat conversion kit is a 24 ---vac accessory that can turn a 4 ---wire thermostat application into a 5---wire application. This kit can also be used to
replace a broken thermostat wire, or add an extra wire when needed.
The outdoor air temperature sensor is included with the Thermidistat Control and dual fuel thermostat.
213A
5
ACCESSORY USAGE GUIDELINE
ACCESSORY
REQUIRED FOR LOW---AMBIENT
COOLING APPLICATIONS (Below 55°
F)
REQUIRED FOR
LONG LINE
APPLICATIONS*
(Over 80 Ft.)
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 miles)
Crankcase Heater Yes Yes No
Evaporator Freeze Thermostat Yes No No
Accumulator Standard Standard Standard
Compressor Start Assist Capacitor and Relay Yes Yes No
Motor Master®Control or
Low---ambient Pressure Switch Yes No No
Support Feet Recommended No Recommended
Liquid Line Solenoid Valve No S e e L o n g --- L i n e A p -
plication Guideline No
Ball Bearing Fan Motor Yes{No No
* For tubing line sets between 80 and 200 ft. and/or 20 ft. vertical differential, refer to Residential Split---System Longline Application Guideline.
{Required for Low---Ambient Controller (full modulation feature) and MotorMasterrControl only.
Accessory Description and Usage (Listed Alphabetically)
1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction
while maintaining bearing lubrication.
Usage Guideline:
Required on all units when using MotorMasterr
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor
motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the
following applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the
following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of
low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.
Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
6. Isolation Relay
An SPDT relay which switches the low--ambient controller out of
the outdoor fan motor circuit when the heat pump switches to
heating mode.
Usage Guideline:
Required in all heat pumps where low ambient kit has
been added.
7. Liquid--Line Solenoid Valve (LLS)
An electrically operated shutoff valve which stops and starts
refrigerant liquid flow in response to compressor operation. It is
to be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.
Usage Guideline:
An LLS is required in all long line heat pump
applications to control refrigerant off cycle migration in
the heating mode. See Long Line Guideline.
8. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in
order to maintain head pressure within normal operating limits.
The control will maintain working head pressure at low--ambient
temperatures down to 0_F when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Low--Ambient Controller must be used when cooling operation is
used at outdoor temperatures below 55_F (12.8_C).
9. MotorMasterrLow--Ambient Controller
A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C),
it maintains condensing temperature at 100_F±10_F (37.8_C±
-- 1 2 _C).
Usage Guideline:
A MotorMasterrLow Ambient Controller or
Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested for all commercial applications.
213A
6
Accessory Description and Usage (Listed Alphabetically) -- CONTINUED
10. Outdoor Air Temperature Sensor
Designed for use with Bryant Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also is required to enable
special thermostat features such as auxiliary heat lock out.
Usage Guideline:
Suggested for all Bryant thermostats listed in this
publication.
11. Outdoor Thermostat
An SPDT temperature--actuated switch which turns on
supplemental electric heaters when outdoor air temperature drops
below a user--selected set point.
Usage Guideline:
Electric supplemental heat applications in non--variable
speed indoor units when electric heat staging is desired.
12. Secondary Outdoor Thermostat
An SPDT temperature--actuated switch which turns on
third--stage of supplemental electric heaters when outdoor air
temperature drops below the second--stage set point.
Usage Guideline:
Outdoor thermostat applications where electric heater is
capable of 3--stage operation.
13. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces
the sound level by about 2 dBA.
Usage Guideline:
Suggested when unit is installed closer than 15 ft. to
quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less
than 10 ft. apart.
14. Thermostatic Expansion Valve (TXV) Bi--Flow
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Usage Guideline:
Accessory required to meet ARI rating and system
reliability, where indoor not equipped.
Required in all heat pump applications designed with
Puron refrigerant.
15. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor
cycles off.
Note: Most indoor unit controls include this feature. For those
that do not, use the guideline below.
Usage Guideline:
Accessory required to meet ARI rating, where indoor
not equipped.
213A
7
ELECTRICAL DATA
UNIT SIZE V/PH OPER VOLTS* COMPR FAN MCA
MIN WIRE
SIZE{
MIN
WIRE
SIZE{
MAX
LENGTH
(ft.)}
MAX
LENGTH
(ft.)}
MAX FUSE**
or CKT BRK
AMPS
MAX MIN LRA RLA FLA 60°C75°C60°C75°C
018---A
208--- 230/1 253 197
48 9.0 0.75 12 14 14 66 62 20
024---A 58.3 12.8 0.75 16.8 14 14 47 45 25
030---A 77 14.1 0.75 21.4 12 12 58 56 30
036---A 79 16.7 1.4 22.2 12 12 56 54 35
042---A 109 19.9 1.2 26 10 10 77 73 40
048---A 117 21.8 1.2 35.4 8 8 88 84 50
060---A 134 26.3 1.2 34.1 8 8 91 87 50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{If wire is applied at ambient greater than 30°C(86°F), consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable
(NM), trade name ROMEX, shall be that of 60°C (140°F) conditions, per the NEC (ANSI/NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60
or 75°C (140 or 167°C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables
of the NEC (ANSI/NFPA 70).
}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
F L A --- F u l l L o a d A m ps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All
motors/compressors contain internal overload protection.
A--WEIGHTED SOUND LEVEL (DBA)
UNIT SIZE STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
018---A 75 54 63 68.5 71.5 68 63.5 57
024---A 75 54.5 64 69 69.5 67.5 64 58
030---A 74 52 62.5 66.5 68.5 65 63.5 59
036---A 76 60 64 69.5 70 68.5 65.5 60.5
042---A 77 55.5 60 63.5 71.5 65 62.5 59
048---A 78 57 64 68 74 67 63 58.5
060---A 76 58.5 63 68 70.5 66.5 64.5 59.5
A--WEIGHTED SOUND LEVEL (DBA) WITH SOUND SHIELD
UNIT SIZE STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
018---A 74 53.5 63.0 68.0 70.0 67.5 63.0 56.5
024---A 74 54.0 63.5 69.0 69.0 67.5 63.5 57.5
030---A 74 51.5 62.0 66.5 67.5 64.5 62.0 57.5
036---A 76 58.5 63.5 69.5 70.5 69.0 65.5 60.5
042---A 75 55.0 60.5 63.5 69.0 64.5 61.5 56.0
048---A 75 57.5 63.0 67.5 71.5 65.5 60.5 54.5
060---A 75 58.5 62.5 67.5 69.0 64.5 61.5 56.0
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---SERIES REQUIRED SUBCOOLING (_F)
018---A 10
024---A 12
030---A 11
036---A 10
042---A 11
048---A 11
060---A 12
213A
8
DIMENSIONS
213A
9
213ANA BALANCE POINT WORKSHEET
0
10
20
30
40
50
60
70
80
--100 1020304050607080
OUTDOOR TEMPERATURE, ºF
BUILDING HEAT LOSS, UNIT INTEGRATED
HEATING CAPACITY, MBTUH
0.0
2.9
5.9
8.8
11.7
14.6
17.6
20.5
23.4
kW
213ANA024A
FY4ANF024
213RNA030A
FY4ANF030
213RNA036A
FY4ANF042
A05007
213ANA042A
FY4ANF042
213ANA060A
FY4ANB060
213ANA048A
FY4ANF048
BASED ON INDOOR ENT. AIR AT 70 ºF
AND AT RATED CFM
213ANA018A
FY4ANF018
213A
10
COMBINATION RATINGS
Unit
S i z e ---
Series
Indoor Model Cooling
Capacity
ARI Standard Ratings
Cooling Heating
Furnace ModelFactory
Enhance
Standard
Rating
SEER
TDR EER
High Temp Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
018---A
*FY4ANF018 17,100 TDR&TXV 13.00 10.50 18,000 3.36 10,900 2.24 7.7
FF1ENP018 17,100 TDR&TXV 13.00 10.50 18,000 3.38 10,900 2.26 7.7
FF1ENP024 17,400 TDR&TXV 13.20 10.70 17,900 3.44 10,900 2.28 7.7
FV4BNF002 17,700 TDR&TXV 14.00 12.00 17,200 3.64 10,500 2.48 8.2
FX4CNF018 17,500 TDR&TXV 14.00 11.70 17,600 3.60 10,500 2.38 8.0
FX4CNF024 17,700 TDR&TXV 14.00 12.00 17,400 3.66 10,500 2.42 8.1
FY4ANF024 17,200 TDR&TXV 13.00 10.50 17,900 3.38 11,000 2.26 7.7
CAP**1814A** 17,000 TDR&TXV 14.00 11.70 17,100 3.34 10,200 2.30 7.7 315(A,J)AV036070
CAP**1814A** 17,000 TXV 13.00 10.50 18,000 3.32 10,900 2.24 7.7
CAP**2414A** 17,300 TDR&TXV 14.00 11.70 17,300 3.50 10,300 2.36 7.8 315(A,J)AV036070
CAP**2414A** 17,400 TXV 13.00 10.80 18,000 3.48 11,000 2.30 7.7
CAP**2417A** 17,400 TDR&TXV 14.00 12.00 17,200 3.54 10,300 2.38 7.8 315(A,J)AV048090
CAP**2417A** 17,300 TDR&TXV 14.00 11.70 17,300 3.52 10,300 2.36 7.9 355AAV042060
CAP**2417A** 17,400 TXV 13.00 10.80 18,000 3.48 11,000 2.30 7.7
CNPF*2418A** 17,400 TXV 13.00 10.80 18,000 3.54 11,000 2.30 7.8
CNPH*2417A** 17,300 TDR&TXV 14.00 11.70 17,300 3.54 10,300 2.38 7.8 315(A,J)AV036070
CNPH*2417A** 17,400 TDR&TXV 14.00 11.70 17,300 3.58 10,300 2.38 7.9 315(A,J)AV048090
CNPH*2417A** 17,300 TDR&TXV 14.00 11.70 17,300 3.56 10,300 2.38 7.9 355AAV042040
CNPH*2417A** 17,300 TDR&TXV 14.00 11.70 17,300 3.58 10,300 2.38 7.9 355AAV042060
CNPH*2417A** 17,400 TDR&TXV 14.00 11.70 17,300 3.58 10,300 2.38 7.9 355AAV042080
CNPH*2417A** 17,400 TXV 13.00 10.80 18,000 3.54 11,000 2.30 7.8
CNPV*1814A** 17,000 TDR&TXV 14.00 11.70 17,100 3.48 10,300 2.34 7.7 315(A,J)AV036070
CNPV*1814A** 17,000 TXV 13.00 10.80 18,000 3.48 10,900 2.28 7.7
CNPV*2414A** 17,300 TDR&TXV 14.00 11.70 17,300 3.54 10,300 2.38 7.8 315(A,J)AV036070
CNPV*2414A** 17,400 TXV 13.00 10.80 18,000 3.54 11,000 2.30 7.8
CNPV*2417A** 17,400 TDR&TXV 14.00 11.70 17,300 3.60 10,300 2.38 7.9 315(A,J)AV048090
CNPV*2417A** 17,300 TDR&TXV 14.00 11.70 17,300 3.56 10,300 2.38 7.9 355AAV042060
CNPV*2417A** 17,400 TXV 13.00 10.80 18,000 3.54 11,000 2.30 7.8
CSPH*2412A** 17,300 TDR&TXV 14.00 11.70 17,300 3.56 10,300 2.38 7.9 315(A,J)AV036070
CSPH*2412A** 17,300 TDR&TXV 14.00 12.00 17,300 3.58 10,300 2.38 7.9 315(A,J)AV048090
CSPH*2412A** 17,300 TDR&TXV 14.00 11.70 17,300 3.58 10,300 2.38 7.9 355AAV042040
CSPH*2412A** 17,300 TDR&TXV 14.00 12.00 17,300 3.58 10,300 2.38 7.9 355AAV042060
CSPH*2412A** 17,300 TDR&TXV 14.00 11.70 17,300 3.58 10,400 2.38 7.9 355AAV042080
CSPH*2412A** 17,400 TXV 13.00 10.80 17,800 3.50 11,000 2.32 7.8
024---A
*FY4ANF024 22,600 TDR&TXV 13.00 10.50 24,000 3.54 15,000 2.48 8.2
FF1ENP024 22,800 TDR&TXV 13.00 10.70 24,000 3.56 15,200 2.46 8.2
FF1ENP030 22,800 TDR&TXV 13.00 10.40 24,200 3.56 15,100 2.48 8.0
FV4BNF002 23,200 TDR&TXV 14.00 11.70 23,200 3.80 14,400 2.66 8.5
FV4BNF003 23,400 TDR&TXV 14.00 12.00 23,000 3.78 14,300 2.66 8.5
FX4CNF024 23,000 TDR&TXV 14.00 11.40 23,800 3.72 14,600 2.60 8.3
FX4CNF030 23,400 TDR&TXV 14.00 11.70 23,600 3.84 14,600 2.66 8.5
FY4ANF030 23,000 TDR&TXV 13.20 10.60 24,000 3.64 15,100 2.52 8.4
CAP**2414A** 22,600 TDR&TXV 14.00 11.50 23,400 3.62 14,300 2.58 8.3 315(A,J)AV036070
CAP**2414A** 22,800 TXV 13.00 10.50 24,400 3.60 15,100 2.50 8.3
CAP**2417A** 22,800 TDR&TXV 14.00 11.70 23,400 3.66 14,300 2.60 8.4 315(A,J)AV048090
CAP**2417A** 22,800 TDR&TXV 14.00 11.70 23,400 3.64 14,300 2.58 8.4 355AAV042060
CAP**2417A** 22,800 TXV 13.00 10.50 24,400 3.60 15,100 2.50 8.3
CAP**3014A** 23,000 TDR&TXV 14.00 11.70 23,000 3.64 14,400 2.60 8.4 315(A,J)AV036070
CAP**3014A** 23,000 TXV 13.00 10.60 23,400 3.56 15,200 2.52 8.3
CAP**3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.68 14,300 2.62 8.5 315(A,J)AV048090
CAP**3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.68 14,300 2.62 8.5 355AAV042060
CAP**3017A** 23,000 TXV 13.00 10.60 23,400 3.56 15,200 2.52 8.3
CNPF*2418A** 22,800 TXV 13.00 10.50 24,400 3.68 15,200 2.52 8.5
CNPH*2417A** 22,600 TDR&TXV 14.00 11.50 23,600 3.68 14,400 2.58 8.4 315(A,J)AV036070
Seenoteonpg.17
213A
11
COMBINATION RATINGS CONTINUED
Unit
S i z e ---
Series
Indoor Model Cooling
Capacity
ARI Standard Ratings
Cooling Heating
Furnace Model
Factory
Enhance
Standard
Rating
SEER
TDR EER
High Temp Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
024---A
CNPH*2417A** 22,800 TDR&TXV 14.00 11.60 23,600 3.72 14,400 2.62 8.5 315(A,J)AV048090
CNPH*2417A** 22,800 TDR&TXV 14.00 11.50 23,600 3.70 14,400 2.60 8.5 315(A,J)AV060110
CNPH*2417A** 22,800 TDR&TXV 14.00 11.50 23,600 3.70 14,400 2.60 8.5 315(A,J)AV066135
CNPH*2417A** 22,800 TDR&TXV 14.00 11.50 23,600 3.72 14,400 2.60 8.5 315(A,J)AV066155
CNPH*2417A** 22,800 TDR&TXV 14.00 11.50 23,600 3.70 14,400 2.60 8.5 355AAV042040
CNPH*2417A** 22,800 TDR&TXV 14.00 11.50 23,600 3.70 14,400 2.60 8.5 355AAV042060
CNPH*2417A** 22,800 TDR&TXV 14.00 11.50 23,600 3.70 14,400 2.60 8.5 355AAV042080
CNPH*2417A** 22,800 TDR&TXV 14.00 11.50 23,600 3.70 14,400 2.60 8.5 355AAV060080
CNPH*2417A** 22,800 TDR&TXV 14.00 11.50 23,600 3.72 14,400 2.60 8.5 355AAV060100
CNPH*2417A** 22,600 TDR&TXV 14.00 11.50 23,600 3.66 14,400 2.58 8.4 355AAV060120
CNPH*2417A** 22,800 TXV 13.00 10.50 24,400 3.68 15,200 2.52 8.5
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.66 14,300 2.60 8.5 315(A,J)AV036070
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.70 14,300 2.62 8.5 315(A,J)AV048090
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.70 14,400 2.62 8.5 315(A,J)AV060110
CNPH*3017A** 2,300 TDR&TXV 14.00 11.70 23,000 3.70 14,400 2.62 8.5 315(A,J)AV066135
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.70 14,300 2.64 8.5 315(A,J)AV066155
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.68 14,400 2.62 8.5 355AAV042040
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.68 14,300 2.62 8.5 355AAV042060
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.68 14,400 2.62 8.7 355AAV042080
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.68 14,400 2.62 8.5 355AAV060080
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.70 14,400 2.62 8.5 355AAV060100
CNPH*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.66 14,300 2.60 8.5 355AAV060120
CNPH*3017A** 23,000 TXV 13.00 10.60 23,400 3.56 15,200 2.52 8.3
CNPV*2414A** 22,600 TDR&TXV 14.00 11.50 23,400 3.68 14,400 2.58 8.4 315(A,J)AV036070
CNPV*2414A** 22,800 TXV 13.00 10.50 24,400 3.68 15,200 2.52 8.5
CNPV*2417A** 22,800 TDR&TXV 14.00 11.50 23,400 3.72 14,400 2.62 8.5 315(A,J)AV048090
CNPV*2417A** 22,800 TDR&TXV 14.00 11.50 23,400 3.70 14,400 2.60 8.5 355AAV042060
CNPV*2417A** 22,800 TXV 13.00 10.50 24,400 3.68 15,200 2.52 8.5
CNPV*3014A** 23,000 TDR&TXV 14.00 11.70 23,000 3.66 14,400 2.60 8.4 315(A,J)AV036070
CNPV*3014A** 23,000 TXV 13.00 10.60 23,400 3.56 15,200 2.52 8.3
CNPV*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.70 14,300 2.62 8.5 315(A,J)AV048090
CNPV*3017A** 23,000 TDR&TXV 14.00 11.70 23,000 3.68 14,300 2.62 8.5 355AAV042060
CNPV*3017A** 23,000 TXV 13.00 10.60 23,400 3.56 15,200 2.52 8.3
CSPH*2412A** 22,600 TDR&TXV 14.00 11.60 23,400 3.70 14,400 2.60 8.5 315(A,J)AV036070
CSPH*2412A** 22,600 TDR&TXV 14.00 11.70 23,400 3.74 14,400 2.62 8.6 315(A,J)AV048090
CSPH*2412A** 22,600 TDR&TXV 14.00 11.50 23,400 3.72 14,500 2.60 8.5 315(A,J)AV060110
CSPH*2412A** 22,600 TDR&TXV 14.00 11.70 23,400 3.74 14,500 2.60 8.6 315(A,J)AV066135
CSPH*2412A** 22,600 TDR&TXV 14.00 11.70 23,400 3.74 14,400 2.62 8.6 315(A,J)AV066155
CSPH*2412A** 22,600 TDR&TXV 14.00 11.50 23,400 3.72 14,500 2.60 8.5 355AAV042040
CSPH*2412A** 22,600 TDR&TXV 14.00 11.70 23,400 3.72 14,400 2.60 8.5 355AAV042060
CSPH*2412A** 22,600 TDR&TXV 14.00 11.50 23,400 3.74 14,500 2.60 8.5 355AAV042080
CSPH*2412A** 22,600 TDR&TXV 14.00 11.60 23,400 3.72 14,400 2.60 8.5 355AAV060080
CSPH*2412A** 22,600 TDR&TXV 14.00 11.70 23,400 3.74 14,500 2.62 8.6 355AAV060100
CSPH*2412A** 22,600 TDR&TXV 14.00 11.50 23,400 3.70 14,400 2.58 8.5 355AAV060120
CSPH*2412A** 22,800 TXV 13.00 10.60 24,200 3.68 15,200 2.54 8.5
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.64 14,400 2.60 8.4 315(A,J)AV036070
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.68 14,400 2.62 8.5 315(A,J)AV048090
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.68 14,400 2.62 8.5 315(A,J)AV060110
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.68 14,400 2.62 8.5 315(A,J)AV066135
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.68 14,400 2.62 8.5 315(A,J)AV066155
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.66 14,400 2.60 8.5 355AAV042040
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.66 14,400 2.60 8.5 355AAV042060
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.66 14,400 2.60 8.5 355AAV042080
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.66 14,400 2.60 8.5 355AAV060080
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.68 14,400 2.62 8.5 355AAV060100
CSPH*3012A** 23,000 TDR&TXV 14.00 11.70 22,800 3.64 14,400 2.60 8.4 355AAV060120
CSPH*3012A** 23,000 TXV 13.00 10.60 23,200 3.56 15,200 2.52 8.3
030---A
*FY4ANF030 29,200 TDR&TXV 13.00 10.10 31,800 3.46 21,200 2.56 8.3
FF1ENP030 29,000 TDR&TXV 13.00 10.00 31,800 3.42 21,200 2.54 8.2
FF1ENP036 29,600 TDR&TXV 13.00 10.20 32,000 3.48 21,400 2.58 8.3
FV4BNF002 29,600 TDR&TXV 14.00 11.00 31,000 3.56 20,600 2.66 8.4
FV4BNF003 29,800 TDR&TXV 14.00 11.20 30,800 3.56 20,400 2.68 8.5
FV4BNF005 30,600 TDR&TXV 14.00 11.60 30,800 3.80 20,600 2.78 8.9
FX4CN(B,F)036 30,000 TDR&TXV 14.00 10.90 31,600 3.64 21,000 2.68 8.6
Seenoteonpg.17
213A
12
COMBINATION RATINGS CONTINUED
Unit
S i z e ---
Series
Indoor Model Cooling
Capacity
ARI Standard Ratings
Cooling Heating
Furnace Model
Factory
Enhance
Standard
Rating
SEER
TDR EER
High Temp Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
030---A
FX4CNF030 29,600 TDR&TXV 14.00 10.80 31,400 3.60 21,000 2.66 8.5
FY4ANF036 29,600 TDR&TXV 13.00 10.00 32,200 3.48 21,600 2.56 8.3
CAP**3014A** 29,200 TDR&TXV 13.50 10.80 30,800 3.44 20,600 2.60 8.2 315(A,J)AV036070
CAP**3014A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.56 8.3
CAP**3017A** 29,400 TDR&TXV 14.00 11.00 30,800 3.46 20,400 2.62 8.3 315(A,J)AV048090
CAP**3017A** 29,200 TDR&TXV 14.00 10.90 30,800 3.44 20,400 2.62 8.2 355AAV042060
CAP**3017A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.56 8.3
CAP**3614A** 29,400 TDR&TXV 13.50 10.90 31,000 3.46 20,600 2.62 8.3 315(A,J)AV036070
CAP**3614A** 29,600 TXV 13.00 10.10 32,200 3.50 21,600 2.58 8.4
CAP**3617A** 29,400 TDR&TXV 14.00 11.10 30,800 3.50 20,400 2.64 8.3 315(A,J)AV048090
CAP**3617A** 29,400 TDR&TXV 14.00 11.00 30,800 3.48 20,400 2.62 8.3 355AAV042060
CAP**3617A** 29,600 TXV 13.00 10.10 32,200 3.50 21,600 2.58 8.4
CAP**3621A** 29,600 TDR&TXV 14.00 11.10 30,800 3.52 20,400 2.66 8.4 315(A,J)AV060110
CAP**3621A** 29,400 TDR&TXV 14.00 11.00 30,800 3.50 20,600 2.64 8.3 355AAV042080
CAP**3621A** 29,400 TDR&TXV 14.00 11.00 30,800 3.50 20,400 2.64 8.3 355AAV060080
CAP**3621A** 29,400 TDR&TXV 14.00 11.10 30,800 3.50 20,400 2.64 8.3 355AAV060100
CAP**3621A** 29,600 TXV 13.00 10.10 32,200 3.50 21,600 2.58 8.4
CNPF*3618A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.58 8.3
CNPH*3017A** 29,400 TDR&TXV 13.50 10.90 30,800 3.46 20,400 2.62 8.3 315(A,J)AV036070
CNPH*3017A** 29,400 TDR&TXV 14.00 11.00 30,800 3.48 20,400 2.64 8.3 315(A,J)AV048090
CNPH*3017A** 29,400 TDR&TXV 14.00 11.00 30,800 3.48 20,400 2.64 8.3 315(A,J)AV060110
CNPH*3017A** 29,400 TDR&TXV 14.00 11.00 30,800 3.50 20,400 2.64 8.3 315(A,J)AV066135
CNPH*3017A** 29,400 TDR&TXV 14.00 11.10 30,800 3.50 20,400 2.64 8.3 315(A,J)AV066155
CNPH*3017A** 29,400 TDR&TXV 13.50 10.80 30,800 3.44 20,600 2.60 8.2 355AAV042040
CNPH*3017A** 29,200 TDR&TXV 14.00 10.80 30,800 3.44 20,600 2.62 8.2 355AAV042060
CNPH*3017A** 29,400 TDR&TXV 13.50 10.90 31,000 3.46 20,600 2.62 8.3 355AAV042080
CNPH*3017A** 29,400 TDR&TXV 14.00 10.90 30,800 3.46 20,600 2.62 8.3 355AAV060080
CNPH*3017A** 29,400 TDR&TXV 14.00 10.90 30,800 3.48 20,600 2.62 8.3 355AAV060100
CNPH*3017A** 29,400 TDR&TXV 14.00 11.00 30,800 3.46 20,400 2.62 8.2 355AAV060120
CNPH*3017A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.58 8.3
CNPH*3617A** 29,400 TDR&TXV 13.50 10.90 30,800 3.46 20,600 2.62 8.3 315(A,J)AV036070
CNPH*3617A** 29,400 TDR&TXV 14.00 11.00 30,800 3.48 20,400 2.64 8.3 315(A,J)AV048090
CNPH*3617A** 29,400 TDR&TXV 14.00 11.00 30,800 3.50 20,400 2.64 8.3 315(A,J)AV060110
CNPH*3617A** 29,400 TDR&TXV 14.00 11.00 30,800 3.50 20,400 2.64 8.3 315(A,J)AV066135
CNPH*3617A** 29,400 TDR&TXV 14.00 11.10 30,800 3.50 20,400 2.64 8.3 315(A,J)AV066155
CNPH*3617A** 29,400 TDR&TXV 13.50 10.80 30,800 3.44 20,400 2.62 8.2 355AAV042040
CNPH*3617A** 29,200 TDR&TXV 14.00 10.90 30,800 3.44 20,400 2.62 8.2 355AAV042060
CNPH*3617A** 29,400 TDR&TXV 13.50 10.90 30,800 3.46 20,600 2.62 8.3 355AAV042080
CNPH*3617A** 29,400 TDR&TXV 14.00 10.90 30,800 3.46 20,400 2.62 8.3 355AAV060080
CNPH*3617A** 29,400 TDR&TXV 14.00 10.90 30,800 3.48 20,400 2.62 8.3 355AAV060100
CNPH*3617A** 29,400 TDR&TXV 14.00 11.00 30,800 3.46 20,400 2.62 8.2 355AAV060120
CNPH*3617A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.58 8.3
CNPV*3014A** 29,200 TDR&TXV 13.50 10.80 30,800 3.44 20,600 2.60 8.2 315(A,J)AV036070
CNPV*3014A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.58 8.3
CNPV*3017A** 29,400 TDR&TXV 14.00 11.00 30,800 3.48 20,400 2.64 8.3 315(A,J)AV048090
CNPV*3017A** 29,200 TDR&TXV 14.00 10.90 30,800 3.44 20,400 2.62 8.2 355AAV042060
CNPV*3017A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.58 8.3
CNPV*3617A** 29,400 TDR&TXV 14.00 11.00 30,800 3.48 20,400 2.64 8.3 315(A,J)AV048090
CNPV*3617A** 29,200 TDR&TXV 14.00 10.90 30,800 3.44 20,400 2.62 8.2 355AAV042060
CNPV*3617A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.58 8.3
CNPV*3621A** 29,400 TDR&TXV 14.00 11.00 30,800 3.50 20,600 2.64 8.3 315(A,J)AV060110
CNPV*3621A** 29,400 TDR&TXV 14.00 10.90 30,800 3.46 20,400 2.62 8.3 355AAV042080
CNPV*3621A** 29,400 TDR&TXV 14.00 10.90 30,800 3.46 20,600 2.62 8.3 355AAV060080
CNPV*3621A** 29,400 TDR&TXV 14.00 11.00 30,800 3.48 20,400 2.62 8.3 355AAV060100
CNPV*3621A** 29,600 TXV 13.00 10.10 32,000 3.48 21,400 2.58 8.3
CSPH*3012A** 29,200 TDR&TXV 13.50 10.90 31,000 3.46 20,600 2.62 8.3 315(A,J)AV036070
CSPH*3012A** 29,200 TDR&TXV 14.00 11.00 30,800 3.48 20,600 2.64 8.3 315(A,J)AV048090
CSPH*3012A** 29,200 TDR&TXV 14.00 11.00 31,000 3.50 20,600 2.64 8.3 315(A,J)AV060110
Seenoteonpg.17
213A
13
COMBINATION RATINGS CONTINUED
Unit
S i z e ---
Series
Indoor Model Cooling
Capacity
ARI Standard Ratings
Cooling Heating
Furnace Model
Factory
Enhance
Standard
Rating
SEER
TDR EER
High Temp Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
030---A
CSPH*3012A** 29,200 TDR&TXV 14.00 11.00 30,800 3.50 20,600 2.64 8.3 315(A,J)AV066135
CSPH*3012A** 29,200 TDR&TXV 14.00 11.00 30,800 3.50 20,600 2.64 8.3 315(A,J)AV066155
CSPH*3012A** 29,200 TDR&TXV 13.50 10.80 31,000 3.46 20,600 2.62 8.3 355AAV042040
CSPH*3012A** 29,200 TDR&TXV 14.00 10.90 30,800 3.46 20,600 2.62 8.3 355AAV042060
CSPH*3012A** 29,200 TDR&TXV 13.50 10.80 31,000 3.48 20,600 2.62 8.3 355AAV042080
CSPH*3012A** 29,200 TDR&TXV 14.00 10.90 31,000 3.48 20,600 2.62 8.3 355AAV060080
CSPH*3012A** 29,200 TDR&TXV 14.00 10.90 31,000 3.48 20,600 2.62 8.3 355AAV060100
CSPH*3012A** 29,200 TDR&TXV 14.00 11.00 30,800 3.46 20,400 2.62 8.3 355AAV060120
CSPH*3012A** 29,600 TXV 13.00 10.20 32,200 3.52 21,400 2.58 8.4
CSPH*3612A** 29,400 TDR&TXV 14.00 11.10 30,800 3.58 20,600 2.68 8.5 315(A,J)AV036070
CSPH*3612A** 29,400 TDR&TXV 14.00 11.20 31,000 3.60 20,600 2.70 8.5 315(A,J)AV048090
CSPH*3612A** 29,400 TDR&TXV 14.00 11.20 30,800 3.62 20,600 2.70 8.6 315(A,J)AV060110
CSPH*3612A** 29,400 TDR&TXV 14.00 11.30 31,000 3.62 20,600 2.70 8.6 315(A,J)AV066135
CSPH*3612A** 29,400 TDR&TXV 14.00 11.30 31,000 3.64 20,600 2.70 8.6 315(A,J)AV066155
CSPH*3612A** 29,400 TDR&TXV 14.00 11.10 30,800 3.58 20,600 2.66 8.5 355AAV042040
CSPH*3612A** 29,400 TDR&TXV 14.00 11.10 30,800 3.58 20,600 2.68 8.5 355AAV042060
CSPH*3612A** 29,400 TDR&TXV 14.00 11.10 30,800 3.60 20,600 2.68 8.5 355AAV042080
CSPH*3612A** 29,400 TDR&TXV 14.00 11.10 30,800 3.58 20,600 2.68 8.5 355AAV060080
CSPH*3612A** 29,400 TDR&TXV 14.00 11.20 31,000 3.60 20,600 2.68 8.5 355AAV060100
CSPH*3612A** 29,400 TDR&TXV 14.00 11.20 31,000 3.58 20,600 2.68 8.5 355AAV060120
CSPH*3612A** 29,600 TXV 13.00 10.30 32,000 3.64 21,600 2.64 8.6
036---A
*FY4ANF042 34,000 TDR&TXV 13.00 10.60 35,800 3.56 22,200 2.42 8.1
FF1ENP036 33,600 TDR&TXV 13.00 10.70 35,400 3.44 21,800 2.40 7.9
FV4BNF002 33,400 TDR&TXV 13.50 11.20 34,800 3.54 21,200 2.46 8.1
FV4BNF003 33,800 TDR&TXV 14.00 11.50 34,400 3.56 20,800 2.50 8.1
FV4BNF005 35,000 TDR&TXV 14.00 12.00 33,800 3.76 21,000 2.58 8.6
FX4CN(B,F)036 34,000 TDR&TXV 13.50 11.20 35,200 3.62 21,400 2.50 8.3
FX4CN(B,F)042 34,800 TDR&TXV 14.00 11.50 35,200 3.76 21,600 2.54 8.5
FY4ANF036 33,000 TDR&TXV 13.00 10.50 35,200 3.36 21,600 2.34 7.7
CAP**3614A** 32,400 TDR&TXV 13.50 11.00 34,600 3.44 21,000 2.42 7.9 315(A,J)AV036070
CAP**3614A** 32,400 TXV 13.00 10.50 35,200 3.40 21,800 2.38 7.8
CAP**3617A** 33,400 TDR&TXV 14.00 11.50 34,400 3.48 21,000 2.46 8.0 315(A,J)AV048090
CAP**3617A** 33,400 TDR&TXV 13.50 11.20 34,400 3.46 21,000 2.44 7.9 355AAV042060
CAP**3617A** 33,400 TXV 13.00 10.50 35,600 3.46 22,000 2.40 7.9
CAP**3621A** 33,600 TDR&TXV 14.00 11.50 34,400 3.50 21,000 2.46 8.0 315(A,J)AV060110
CAP**3621A** 33,200 TDR&TXV 13.50 11.20 34,400 3.44 21,000 2.42 7.9 355AAV042080
CAP**3621A** 33,400 TDR&TXV 13.50 11.30 34,400 3.48 21,000 2.44 8.0 355AAV060080
CAP**3621A** 33,400 TDR&TXV 14.00 11.40 34,400 3.48 21,000 2.46 8.0 355AAV060100
CAP**3621A** 33,400 TXV 13.00 10.50 35,600 3.46 22,000 2.40 7.9
CAP**4221A** 33,800 TDR&TXV 14.00 11.50 34,600 3.56 21,000 2.48 8.1 315(A,J)AV060110
CAP**4221A** 33,400 TDR&TXV 13.50 11.20 34,600 3.48 21,000 2.44 8.0 355AAV042080
CAP**4221A** 33,600 TDR&TXV 14.00 11.50 34,600 3.52 21,000 2.46 8.0 355AAV060080
CAP**4221A** 33,600 TDR&TXV 14.00 11.50 34,600 3.54 21,000 2.46 8.1 355AAV060100
CAP**4221A** 33,800 TXV 13.00 10.60 35,800 3.52 22,000 2.42 8.0
CAP**4224A** 33,800 TDR&TXV 14.00 11.50 34,400 3.58 20,800 2.50 8.1 315(A,J)AV066135
CAP**4224A** 33,800 TDR&TXV 14.00 11.70 34,400 3.60 20,800 2.52 8.2 315(A,J)AV066155
CAP**4224A** 33,600 TDR&TXV 13.50 11.20 34,600 3.50 21,000 2.44 8.0 355AAV042040
CAP**4224A** 33,600 TDR&TXV 14.00 11.50 34,400 3.54 21,000 2.48 8.1 355AAV060120
CAP**4224A** 33,800 TXV 13.00 10.60 35,800 3.52 22,000 2.42 8.0
CNPF*3618A** 33,400 TXV 13.00 10.50 35,600 3.44 22,000 2.38 7.9
CNPH*3617A** 33,200 TDR&TXV 13.50 11.20 34,400 3.42 21,000 2.42 7.9 315(A,J)AV036070
CNPH*3617A** 33,400 TDR&TXV 13.50 11.20 34,400 3.46 21,000 2.44 7.9 315(A,J)AV048090
CNPH*3617A** 33,400 TDR&TXV 13.50 11.20 34,400 3.46 21,000 2.44 8.0 315(A,J)AV060110
CNPH*3617A** 33,400 TDR&TXV 13.50 11.20 34,400 3.46 21,000 2.44 8.0 315(A,J)AV066135
CNPH*3617A** 33,400 TDR&TXV 14.00 11.50 34,400 3.48 21,000 2.46 8.0 315(A,J)AV066155
CNPH*3617A** 33,200 TDR&TXV 13.50 11.10 34,400 3.42 21,200 2.40 7.8 355AAV042040
CNPH*3617A** 33,200 TDR&TXV 13.50 11.20 34,400 3.44 21,000 2.42 7.9 355AAV042060
CNPH*3617A** 33,000 TDR&TXV 13.50 11.00 34,400 3.40 21,200 2.40 7.8 355AAV042080
CNPH*3617A** 33,200 TDR&TXV 13.50 11.20 34,400 3.44 21,000 2.42 7.9 355AAV060080
CNPH*3617A** 33,200 TDR&TXV 13.50 11.20 34,400 3.44 21,000 2.44 7.9 355AAV060100
CNPH*3617A** 33,200 TDR&TXV 13.50 11.20 34,400 3.44 21,000 2.42 7.9 355AAV060120
Seenoteonpg.17
213A
14
COMBINATION RATINGS CONTINUED
Unit
S i z e ---
Series
Indoor Model Cooling
Capacity
ARI Standard Ratings
Cooling Heating
Furnace Model
Factory
Enhance
Standard
Rating
SEER
TDR EER
High Temp Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
036---A
CNPH*3617A** 33,400 TXV 13.00 10.50 35,600 3.44 22,000 2.38 7.9
CNPH*4221A** 33,600 TDR&TXV 14.00 11.50 34,600 3.54 21,000 2.48 8.1 315(A,J)AV036070
CNPH*4221A** 33,600 TDR&TXV 14.00 11.70 34,400 3.58 20,800 2.50 8.2 315(A,J)AV048090
CNPH*4221A** 33,800 TDR&TXV 14.00 11.70 34,400 3.60 20,800 2.52 8.2 315(A,J)AV060110
CNPH*4221A** 33,800 TDR&TXV 14.00 11.70 34,400 3.62 20,800 2.52 8.2 315(A,J)AV066135
CNPH*4221A** 33,800 TDR&TXV 14.00 11.70 34,400 3.62 20,800 2.54 8.3 315(A,J)AV066155
CNPH*4221A** 33,400 TDR&TXV 14.00 11.50 34,600 3.54 21,000 2.48 8.1 355AAV042040
CNPH*4221A** 33,600 TDR&TXV 14.00 11.60 34,400 3.56 21,000 2.50 8.1 355AAV042060
CNPH*4221A** 33,400 TDR&TXV 14.00 11.50 34,400 3.54 21,000 2.48 8.1 355AAV042080
CNPH*4221A** 33,600 TDR&TXV 14.00 11.50 34,600 3.56 21,000 2.48 8.1 355AAV060080
CNPH*4221A** 33,600 TDR&TXV 14.00 11.50 34,400 3.58 21,000 2.50 8.2 355AAV060100
CNPH*4221A** 33,600 TDR&TXV 14.00 11.70 34,400 3.58 20,800 2.50 8.2 355AAV060120
CNPH*4221A** 33,800 TXV 13.00 10.60 35,800 3.54 22,000 2.42 8.1
CNPV*3617A** 33,400 TDR&TXV 13.50 11.20 34,400 3.46 21,000 2.44 7.9 315(A,J)AV048090
CNPV*3617A** 33,200 TDR&TXV 13.50 11.20 34,400 3.44 21,000 2.42 7.9 355AAV042060
CNPV*3617A** 33,400 TXV 13.00 10.50 35,600 3.44 22,000 2.38 7.9
CNPV*3621A** 33,600 TDR&TXV 13.50 11.20 34,400 3.48 21,000 2.44 8.0 315(A,J)AV060110
CNPV*3621A** 33,200 TDR&TXV 13.50 11.00 34,400 3.40 21,000 2.40 7.8 355AAV042080
CNPV*3621A** 33,200 TDR&TXV 13.50 11.20 34,400 3.44 21,000 2.42 7.9 355AAV060080
CNPV*3621A** 33,400 TDR&TXV 13.50 11.20 34,400 3.46 21,000 2.42 7.9 355AAV060100
CNPV*3621A** 33,400 TXV 13.00 10.50 35,600 3.44 22,000 2.38 7.9
CNPV*4221A** 33,800 TDR&TXV 14.00 11.70 34,400 3.60 20,800 2.52 8.2 315(A,J)AV060110
CNPV*4221A** 33,400 TDR&TXV 14.00 11.50 34,400 3.54 21,000 2.48 8.1 355AAV042080
CNPV*4221A** 33,600 TDR&TXV 14.00 11.50 34,600 3.56 21,000 2.48 8.1 355AAV060080
CNPV*4221A** 33,600 TDR&TXV 14.00 11.50 34,400 3.58 21,000 2.50 8.2 355AAV060100
CNPV*4221A** 33,800 TXV 13.00 10.60 35,800 3.54 22,000 2.42 8.1
CSPH*3612A** 33,400 TDR&TXV 14.00 11.50 34,600 3.58 21,200 2.48 8.2 315(A,J)AV036070
CSPH*3612A** 33,400 TDR&TXV 14.00 11.50 34,600 3.62 21,000 2.50 8.2 315(A,J)AV048090
CSPH*3612A** 33,400 TDR&TXV 14.00 11.50 34,600 3.64 21,200 2.52 8.3 315(A,J)AV060110
CSPH*3612A** 33,400 TDR&TXV 14.00 11.50 34,600 3.64 21,000 2.52 8.3 315(A,J)AV066135
CSPH*3612A** 33,400 TDR&TXV 14.00 11.70 34,600 3.66 21,000 2.54 8.3 315(A,J)AV066155
CSPH*3612A** 33,400 TDR&TXV 13.50 11.20 34,600 3.56 21,200 2.48 8.1 355AAV042040
CSPH*3612A** 33,400 TDR&TXV 14.00 11.50 34,600 3.60 21,200 2.50 8.2 355AAV042060
CSPH*3612A** 33,400 TDR&TXV 13.50 11.20 34,600 3.54 21,200 2.46 8.1 355AAV042080
CSPH*3612A** 33,400 TDR&TXV 14.00 11.50 34,600 3.60 21,200 2.48 8.2 355AAV060080
CSPH*3612A** 33,400 TDR&TXV 14.00 11.50 34,600 3.60 21,200 2.50 8.2 355AAV060100
CSPH*3612A** 33,400 TDR&TXV 14.00 11.50 34,600 3.60 21,000 2.50 8.2 355AAV060120
CSPH*3612A** 33,400 TXV 13.00 10.70 35,600 3.62 22,200 2.44 8.2
CSPH*4212A** 33,800 TDR&TXV 14.00 11.50 34,600 3.64 21,200 2.50 8.3 315(A,J)AV036070
CSPH*4212A** 33,800 TDR&TXV 14.00 11.50 34,600 3.68 21,000 2.52 8.4 315(A,J)AV048090
CSPH*4212A** 33,800 TDR&TXV 14.00 11.50 34,600 3.70 21,200 2.54 8.4 315(A,J)AV060110
CSPH*4212A** 33,800 TDR&TXV 14.00 11.70 34,600 3.70 21,000 2.54 8.4 315(A,J)AV066135
CSPH*4212A** 33,800 TDR&TXV 14.00 11.70 34,600 3.74 21,000 2.56 8.4 315(A,J)AV066155
CSPH*4212A** 33,600 TDR&TXV 14.00 11.50 34,600 3.64 21,200 2.48 8.3 355AAV042040
CSPH*4212A** 33,600 TDR&TXV 14.00 11.50 34,600 3.66 21,200 2.52 8.3 355AAV042060
CSPH*4212A** 33,600 TDR&TXV 14.00 11.50 34,600 3.62 21,200 2.48 8.2 355AAV042080
CSPH*4212A** 33,600 TDR&TXV 14.00 11.50 34,600 3.66 21,200 2.50 8.3 355AAV060080
CSPH*4212A** 33,800 TDR&TXV 14.00 11.50 34,600 3.68 21,200 2.52 8.3 355AAV060100
CSPH*4212A** 33,800 TDR&TXV 14.00 11.50 34,600 3.66 21,200 2.52 8.3 355AAV060120
CSPH*4212A** 33,800 TXV 13.20 10.80 35,800 3.66 22,200 2.46 8.3
042---A
*FY4ANF042 40,500 TDR&TXV 13.00 10.40 42,000 3.54 26,400 2.46 8.1
FV4BNB006 42,500 TDR&TXV 14.00 12.40 39,500 3.68 25,800 2.56 8.4
FV4BNF003 40,000 TDR&TXV 14.00 11.50 41,000 3.42 25,600 2.40 7.9
FV4BNF005 42,000 TDR&TXV 14.00 12.10 40,500 3.64 25,800 2.50 8.3
FX4BNF042 40,500 TDR&TXV 13.00 10.40 42,500 3.54 26,400 2.46 8.1
FX4BNF048 41,500 TDR&TXV 13.20 10.60 41,000 3.56 26,600 2.50 8.2
FX4CN(B,F)042 41,500 TDR&TXV 14.00 11.20 42,000 3.70 25,800 2.56 8.4
FX4CN(B,F)048 42,500 TDR&TXV 14.00 11.70 40,000 3.76 25,800 2.66 8.7
FY4ANF048 41,500 TDR&TXV 13.20 10.60 41,000 3.56 26,600 2.50 8.2
Seenoteonpg.17
213A
15
COMBINATION RATINGS CONTINUED
Unit
S i z e ---
Series
Indoor Model Cooling
Capacity
ARI Standard Ratings
Cooling Heating
Furnace Model
Factory
Enhance
Standard
Rating
SEER
TDR EER
High Temp Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
042---A
CAP**4221A** 40,000 TDR&TXV 14.00 11.20 41,000 3.50 25,200 2.52 8.1 315(A,J)AV060110
CAP**4221A** 39,500 TDR&TXV 13.50 10.90 41,500 3.42 25,400 2.46 7.9 355AAV042080
CAP**4221A** 40,000 TDR&TXV 13.50 11.00 41,500 3.46 25,200 2.48 8.0 355AAV060080
CAP**4221A** 40,000 TDR&TXV 13.50 11.20 41,000 3.48 25,200 2.50 8.0 355AAV060100
CAP**4221A** 40,000 TXV 13.00 10.40 42,500 3.50 26,200 2.46 8.0
CAP**4224A** 40,000 TDR&TXV 14.00 11.40 41,000 3.54 25,000 2.54 8.2 315(A,J)AV066135
CAP**4224A** 40,000 TDR&TXV 14.00 11.50 41,000 3.52 25,000 2.54 8.2 315(A,J)AV066155
CAP**4224A** 39,500 TDR&TXV 13.50 11.00 41,000 3.44 25,200 2.48 8.0 355AAV042040
CAP**4224A** 40,000 TDR&TXV 14.00 11.20 41,000 3.48 25,200 2.50 8.0 355AAV060120
CAP**4224A** 40,000 TXV 13.00 10.40 42,500 3.50 26,200 2.46 8.0
CAP**4817A** 40,000 TDR&TXV 14.00 11.40 40,500 3.68 25,400 2.58 8.4 315(A,J)AV048090
CAP**4817A** 40,000 TDR&TXV 14.00 11.30 40,500 3.64 25,600 2.56 8.4 355AAV042060
CAP**4817A** 40,500 TXV 13.00 10.70 41,000 3.64 26,400 2.54 8.4
CAP**4821A** 41,000 TDR&TXV 14.00 11.40 41,000 3.68 25,400 2.58 8.4 315(A,J)AV060110
CAP**4821A** 40,500 TDR&TXV 13.50 11.40 41,500 3.58 25,600 2.52 8.2 355AAV042080
CAP**4821A** 40,500 TDR&TXV 13.50 11.20 41,000 3.62 25,400 2.54 8.3 355AAV060080
CAP**4821A** 40,500 TDR&TXV 14.00 11.30 41,000 3.64 25,400 2.56 8.4 355AAV060100
CAP**4821A** 41,000 TXV 13.00 10.60 42,000 3.62 26,400 2.52 8.3
CAP**4824A** 41,000 TDR&TXV 14.00 11.60 41,000 3.70 25,200 2.60 8.5 315(A,J)AV066135
CAP**4824A** 41,000 TDR&TXV 14.00 11.60 41,000 3.70 25,200 2.60 8.5 315(A,J)AV066155
CAP**4824A** 40,500 TDR&TXV 13.50 11.10 41,000 3.60 25,400 2.52 8.3 355AAV042040
CAP**4824A** 40,500 TDR&TXV 14.00 11.40 41,000 3.64 25,200 2.56 8.4 355AAV060120
CAP**4824A** 41,000 TXV 13.00 10.60 42,000 3.62 26,400 2.52 8.3
CNPF*4818A** 40,500 TXV 13.00 10.50 42,000 3.58 26,400 2.48 8.2
CNPH*4221A** 40,000 TDR&TXV 13.50 11.10 41,500 3.48 25,200 2.50 8.0 315(A,J)AV036070
CNPH*4221A** 40,000 TDR&TXV 14.00 11.40 41,000 3.52 25,000 2.54 8.2 315(A,J)AV048090
CNPH*4221A** 40,500 TDR&TXV 14.00 11.50 41,000 3.56 25,000 2.56 8.2 315(A,J)AV060110
CNPH*4221A** 40,500 TDR&TXV 14.00 11.60 41,000 3.58 25,000 2.56 8.2 315(A,J)AV066135
CNPH*4221A** 40,500 TDR&TXV 14.00 11.60 41,000 3.58 24,800 2.56 8.2 315(A,J)AV066155
CNPH*4221A** 40,000 TDR&TXV 13.50 11.20 41,000 3.48 25,200 2.50 8.0 355AAV042040
CNPH*4221A** 40,000 TDR&TXV 14.00 11.30 41,000 3.50 25,200 2.52 8.1 355AAV042060
CNPH*4221A** 40,000 TDR&TXV 13.50 11.10 41,000 3.48 25,200 2.50 8.0 355AAV042080
CNPH*4221A** 40,000 TDR&TXV 14.00 11.20 41,000 3.50 25,200 2.52 8.1 355AAV060080
CNPH*4221A** 40,000 TDR&TXV 14.00 11.40 41,000 3.54 25,000 2.54 8.2 355AAV060100
CNPH*4221A** 40,000 TDR&TXV 14.00 11.40 41,000 3.52 25,000 2.54 8.2 355AAV060120
CNPH*4221A** 40,500 TXV 13.00 10.40 42,500 3.50 26,200 2.46 8.0
CNPH*4821A** 40,500 TDR&TXV 13.50 11.10 41,000 3.60 25,600 2.52 8.3 315(A,J)AV036070
CNPH*4821A** 41,000 TDR&TXV 14.00 11.40 41,000 3.66 25,200 2.58 8.4 315(A,J)AV048090
CNPH*4821A** 41,000 TDR&TXV 14.00 11.50 41,000 3.68 25,400 2.58 8.4 315(A,J)AV060110
CNPH*4821A** 41,000 TDR&TXV 14.00 11.60 41,000 3.70 25,200 2.60 8.5 315(A,J)AV066135
CNPH*4821A** 41,000 TDR&TXV 14.00 11.70 41,000 3.70 25,200 2.60 8.5 315(A,J)AV066155
CNPH*4821A** 40,500 TDR&TXV 13.50 11.20 41,500 3.60 25,400 2.52 8.2 355AAV042040
CNPH*4821A** 40,500 TDR&TXV 14.00 11.30 41,500 3.62 25,400 2.56 8.3 355AAV042060
CNPH*4821A** 40,500 TDR&TXV 13.50 11.10 41,500 3.58 25,400 2.52 8.2 355AAV042080
CNPH*4821A** 40,500 TDR&TXV 14.00 11.20 41,000 3.62 25,400 2.54 8.3 355AAV060080
CNPH*4821A** 40,500 TDR&TXV 14.00 11.40 41,000 3.66 25,400 2.56 8.4 355AAV060100
CNPH*4821A** 40,500 TDR&TXV 14.00 11.40 41,000 3.64 25,200 2.56 8.3 355AAV060120
CNPH*4821A** 41,000 TXV 13.00 10.60 42,000 3.64 26,400 2.52 8.3
CNPV*4221A** 40,000 TDR&TXV 14.00 11.50 41,000 3.56 25,000 2.56 8.2 315(A,J)AV060110
CNPV*4221A** 40,000 TDR&TXV 13.50 11.10 41,000 3.48 25,200 2.50 8.0 355AAV042080
CNPV*4221A** 39,500 TDR&TXV 14.00 11.20 41,000 3.50 25,200 2.52 8.1 355AAV060080
CNPV*4221A** 40,000 TDR&TXV 14.00 11.40 41,000 3.54 25,000 2.54 8.1 355AAV060100
CNPV*4221A** 40,000 TXV 13.00 10.40 42,500 3.50 26,200 2.46 8.0
CNPV*4821A** 41,000 TDR&TXV 14.00 11.50 41,000 3.68 25,400 2.58 8.4 315(A,J)AV060110
CNPV*4821A** 40,500 TDR&TXV 13.50 11.10 41,500 3.58 25,400 2.52 8.2 355AAV042080
CNPV*4821A** 40,500 TDR&TXV 14.00 11.20 41,000 3.62 25,400 2.54 8.3 355AAV060080
CNPV*4821A** 40,500 TDR&TXV 14.00 11.40 41,000 3.66 25,400 2.56 8.4 355AAV060100
CNPV*4821A** 41,000 TXV 13.00 10.60 42,000 3.64 26,400 2.52 8.3
CNPV*4824A** 41,000 TDR&TXV 14.00 11.60 41,000 3.70 25,200 2.60 8.5 315(A,J)AV066135
CNPV*4824A** 41,000 TDR&TXV 14.00 11.60 41,000 3.70 25,200 2.60 8.5 315(A,J)AV066155
Seenoteonpg.17
213A
16
COMBINATION RATINGS CONTINUED
Unit
S i z e ---
Series
Indoor Model Cooling
Capacity
ARI Standard Ratings
Cooling Heating
Furnace Model
Factory
Enhance
Standard
Rating
SEER
TDR EER
High Temp Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
042---A
CNPV*4824A** 40,500 TDR&TXV 13.50 11.20 41,000 3.60 25,400 2.52 8.2 355AAV042040
CNPV*4824A** 40,500 TDR&TXV 14.00 11.40 41,000 3.64 25,200 2.56 8.3 355AAV060120
CNPV*4824A** 41,000 TXV 13.00 10.60 42,000 3.64 26,400 2.52 8.3
CSPH*4212A** 39,500 TDR&TXV 13.50 11.10 41,500 3.60 25,600 2.52 8.2 315(A,J)AV036070
CSPH*4212A** 40,000 TDR&TXV 14.00 11.40 41,000 3.66 25,400 2.56 8.4 315(A,J)AV048090
CSPH*4212A** 40,000 TDR&TXV 14.00 11.40 41,000 3.66 25,400 2.58 8.4 315(A,J)AV060110
CSPH*4212A** 40,000 TDR&TXV 14.00 11.50 41,000 3.70 25,200 2.60 8.4 315(A,J)AV066135
CSPH*4212A** 40,000 TDR&TXV 14.00 11.60 41,000 3.68 25,200 2.60 8.4 315(A,J)AV066155
CSPH*4212A** 39,500 TDR&TXV 13.50 11.10 41,500 3.58 25,600 2.52 8.2 355AAV042040
CSPH*4212A** 40,000 TDR&TXV 14.00 11.30 41,500 3.62 25,400 2.54 8.3 355AAV042060
CSPH*4212A** 39,500 TDR&TXV 13.50 11.10 41,500 3.58 25,600 2.52 8.2 355AAV042080
CSPH*4212A** 40,000 TDR&TXV 14.00 11.20 41,500 3.62 25,600 2.54 8.3 355AAV060080
CSPH*4212A** 40,000 TDR&TXV 14.00 11.30 41,500 3.64 25,400 2.56 8.3 355AAV060100
CSPH*4212A** 40,000 TDR&TXV 14.00 11.40 41,500 3.62 25,400 2.56 8.3 355AAV060120
CSPH*4212A** 40,000 TXV 13.00 10.70 42,500 3.66 26,400 2.52 8.3
CSPH*4812A** 41,000 TDR&TXV 13.50 11.10 41,500 3.64 25,600 2.54 8.3 315(A,J)AV036070
CSPH*4812A** 41,000 TDR&TXV 14.00 11.40 41,000 3.70 25,400 2.58 8.4 315(A,J)AV048090
CSPH*4812A** 41,000 TDR&TXV 14.00 11.40 41,000 3.70 25,400 2.58 8.5 315(A,J)AV060110
CSPH*4812A** 41,000 TDR&TXV 14.00 11.60 41,000 3.74 25,400 2.60 8.5 315(A,J)AV066135
CSPH*4812A** 41,000 TDR&TXV 14.00 11.60 41,000 3.72 25,200 2.60 8.5 315(A,J)AV066155
CSPH*4812A** 40,500 TDR&TXV 13.50 11.20 41,500 3.62 25,600 2.52 8.3 355AAV042040
CSPH*4812A** 40,500 TDR&TXV 14.00 11.30 41,000 3.66 25,400 2.56 8.4 355AAV042060
CSPH*4812A** 40,500 TDR&TXV 13.50 11.10 41,500 3.62 25,600 2.52 8.3 355AAV042080
CSPH*4812A** 40,500 TDR&TXV 14.00 11.30 41,000 3.66 25,600 2.56 8.4 355AAV060080
CSPH*4812A** 40,500 TDR&TXV 14.00 11.30 41,000 3.68 25,400 2.56 8.4 355AAV060100
CSPH*4812A** 40,500 TDR&TXV 14.00 11.40 41,000 3.68 25,400 2.56 8.4 355AAV060120
CSPH*4812A** 41,000 TXV 13.00 10.70 42,000 3.68 26,400 2.52 8.4
048---A
*FY4ANF048 46,500 TDR&TXV 13.00 10.8 48,500 3.60 30,800 2.58 8.3
FV4BNB006 48,000 TDR&TXV 14.00 12.50 46,000 3.86 29,400 2.78 8.8
FV4BNF005 47,000 TDR&TXV 14.00 12.20 47,500 3.78 29,400 2.72 8.6
FX4BNB060 47,500 TDR&TXV 13.00 11.20 45,000 3.52 30,800 2.62 8.4
FX4BNF048 46,500 TDR&TXV 13.00 11.10 48,500 3.60 30,800 2.58 8.3
FX4CN(B,F)048 47,500 TDR&TXV 14.00 11.70 47,500 3.78 30,000 2.70 8.6
FX4CN(B,F)060 48,000 TDR&TXV 14.00 12.00 44,000 3.74 30,000 2.76 8.7
FY4ANB060 47,500 TDR&TXV 13.50 11.00 45,000 3.52 30,800 2.62 8.4
CAP**4817A** 45,000 TDR&TXV 14.00 11.50 47,500 3.70 29,800 2.62 8.4 315(A,J)AV048090
CAP**4817A** 45,000 TXV 13.00 10.80 48,000 3.66 30,200 2.60 8.4
CAP**4821A** 45,500 TDR&TXV 14.00 11.50 48,000 3.68 29,600 2.62 8.4 315(A,J)AV060110
CAP**4821A** 45,500 TDR&TXV 14.00 11.50 48,500 3.62 29,800 2.58 8.3 355AAV060080
CAP**4821A** 45,500 TDR&TXV 14.00 11.50 48,000 3.64 29,600 2.60 8.3 355AAV060100
CAP**4821A** 46,000 TXV 13.00 10.80 49,000 3.68 30,400 2.60 8.4
CAP**4824A** 45,500 TDR&TXV 14.00 11.70 48,000 3.70 29,400 2.64 8.5 315(A,J)AV066135
CAP**4824A** 46,000 TDR&TXV 14.00 11.50 48,000 3.74 29,400 2.66 8.5 315(A,J)AV066155
CAP**4824A** 45,500 TDR&TXV 14.00 11.50 48,000 3.64 29,600 2.60 8.3 355AAV060120
CAP**4824A** 46,000 TXV 13.00 10.80 49,000 3.68 30,400 2.60 8.4
CAP**6021A** 45,500 TDR&TXV 14.00 11.70 46,000 3.68 29,600 2.66 8.5 315(A,J)AV060110
CAP**6021A** 45,500 TDR&TXV 14.00 11.70 46,000 3.64 29,800 2.62 8.4 355AAV060080
CAP**6021A** 45,500 TDR&TXV 14.00 11.70 46,000 3.66 29,600 2.64 8.4 355AAV060100
CAP**6021A** 46,000 TXV 13.00 10.80 45,000 3.50 30,600 2.62 8.3
CAP**6024A** 47,000 TDR&TXV 14.00 11.70 46,000 3.70 29,600 2.68 8.5 315(A,J)AV066135
CAP**6024A** 47,000 TDR&TXV 14.00 12.00 46,000 3.72 29,400 2.68 8.6 315(A,J)AV066155
CAP**6024A** 46,500 TDR&TXV 14.00 11.70 46,000 3.64 29,600 2.64 8.4 355AAV060120
CAP**6024A** 47,000 TXV 13.00 10.80 45,000 3.50 30,600 2.62 8.3
CNPF*4818A** 45,000 TXV 13.00 10.80 48,500 3.50 30,000 2.54 8.1
CNPH*4821A** 44,500 TDR&TXV 14.00 11.50 48,000 3.62 29,600 2.60 8.3 315(A,J)AV048090
CNPH*4821A** 44,500 TDR&TXV 14.00 11.50 48,000 3.64 29,600 2.62 8.4 315(A,J)AV060110
CNPH*4821A** 45,000 TDR&TXV 14.00 11.70 48,000 3.68 29,400 2.64 8.4 315(A,J)AV066135
CNPH*4821A** 45,000 TDR&TXV 14.00 11.70 48,000 3.70 29,400 2.66 8.5 315(A,J)AV066155
CNPH*4821A** 44,500 TDR&TXV 14.00 11.50 48,500 3.60 29,600 2.60 8.3 355AAV060080
CNPH*4821A** 44,500 TDR&TXV 14.00 11.50 48,000 3.62 29,600 2.60 8.3 355AAV060100
CNPH*4821A** 44,500 TDR&TXV 14.00 11.50 48,000 3.62 29,600 2.60 8.3 355AAV060120
Seenoteonpg.17
213A
17
COMBINATION RATINGS CONTINUED
Unit
S i z e ---
Series
Indoor Model Cooling
Capacity
ARI Standard Ratings
Cooling Heating
Furnace Model
Factory
Enhance
Standard
Rating
SEER
TDR EER
High Temp Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
048---A
CNPH*4821A** 45,000 TXV 13.00 10.80 49,000 3.68 30,400 2.60 8.4
CNPH*6024A** 46,500 TDR&TXV 14.00 11.70 46,000 3.68 29,600 2.64 8.4 315(A,J)AV048090
CNPH*6024A** 46,500 TDR&TXV 14.00 11.70 46,000 3.70 29,600 2.66 8.5 315(A,J)AV060110
CNPH*6024A** 46,500 TDR&TXV 14.00 12.00 46,000 3.74 29,400 2.68 8.5 315(A,J)AV066135
CNPH*6024A** 47,000 TDR&TXV 14.00 12.00 46,000 3.76 29,400 2.68 8.6 315(A,J)AV066155
CNPH*6024A** 46,500 TDR&TXV 14.00 11.50 46,000 3.66 29,800 2.62 8.4 355AAV060080
CNPH*6024A** 46,500 TDR&TXV 14.00 11.70 46,000 3.68 29,600 2.64 8.4 355AAV060100
CNPH*6024A** 46,500 TDR&TXV 14.00 11.70 46,000 3.68 29,600 2.64 8.4 355AAV060120
CNPH*6024A** 47,000 TXV 13.00 10.80 45,000 3.66 30,600 2.62 8.5
CNPV*4821A** 45,500 TDR&TXV 14.00 11.50 48,000 3.64 29,600 2.62 8.4 315(A,J)AV060110
CNPV*4821A** 45,500 TDR&TXV 14.00 11.50 48,500 3.60 29,600 2.60 8.3 355AAV060080
CNPV*4821A** 45,500 TDR&TXV 14.00 11.50 48,000 3.62 29,600 2.60 8.3 355AAV060100
CNPV*4821A** 46,000 TXV 13.00 10.80 49,000 3.68 30,400 2.60 8.4
CNPV*4824A** 45,500 TDR&TXV 14.00 11.70 48,000 3.68 29,400 2.64 8.4 315(A,J)AV066135
CNPV*4824A** 46,000 TDR&TXV 14.00 11.50 48,000 3.70 29,400 2.66 8.5 315(A,J)AV066155
CNPV*4824A** 45,500 TDR&TXV 14.00 11.50 48,000 3.62 29,600 2.60 8.3 355AAV060120
CNPV*4824A** 46,000 TXV 13.00 10.80 49,000 3.68 30,400 2.60 8.4
CNPV*6024A** 46,500 TDR&TXV 14.00 12.00 46,000 3.74 29,400 2.68 8.5 315(A,J)AV066135
CNPV*6024A** 47,000 TDR&TXV 14.00 12.00 46,000 3.76 29,400 2.68 8.6 315(A,J)AV066155
CNPV*6024A** 46,500 TDR&TXV 14.00 11.70 46,000 3.68 29,600 2.64 8.4 355AAV060120
CNPV*6024A** 47,000 TXV 13.00 10.80 45,000 3.66 30,600 2.62 8.5
CSPH*4812A** 45,500 TDR&TXV 14.00 11.50 48,000 3.68 29,800 2.62 8.4 315(A,J)AV048090
CSPH*4812A** 45,500 TDR&TXV 14.00 11.50 48,000 3.70 29,600 2.62 8.4 315(A,J)AV060110
CSPH*4812A** 45,500 TDR&TXV 14.00 11.70 48,000 3.72 29,600 2.64 8.5 315(A,J)AV066135
CSPH*4812A** 45,500 TDR&TXV 14.00 11.70 48,000 3.76 29,400 2.66 8.6 315(A,J)AV066155
CSPH*4812A** 45,500 TDR&TXV 14.00 11.50 48,500 3.66 29,800 2.60 8.4 355AAV060080
CSPH*4812A** 45,500 TDR&TXV 14.00 11.50 48,000 3.68 29,800 2.62 8.4 355AAV060100
CSPH*4812A** 45,500 TDR&TXV 14.00 11.50 48,000 3.66 29,600 2.62 8.4 355AAV060120
CSPH*4812A** 46,000 TXV 13.00 10.80 49,000 3.72 30,600 2.62 8.5
CSPH*6012A** 46,500 TDR&TXV 14.00 11.70 46,000 3.74 29,600 2.66 8.5 315(A,J)AV048090
CSPH*6012A** 47,000 TDR&TXV 14.00 11.70 46,000 3.76 29,600 2.68 8.6 315(A,J)AV060110
CSPH*6012A** 47,000 TDR&TXV 14.00 12.00 46,000 3.78 29,600 2.70 8.6 315(A,J)AV066135
CSPH*6012A** 47,000 TDR&TXV 14.00 12.00 46,000 3.80 29,400 2.70 8.7 315(A,J)AV066155
CSPH*6012A** 46,500 TDR&TXV 14.00 11.70 46,000 3.70 29,800 2.64 8.5 355AAV060080
CSPH*6012A** 46,500 TDR&TXV 14.00 11.70 46,000 3.72 29,800 2.66 8.5 355AAV060100
CSPH*6012A** 46,500 TDR&TXV 14.00 11.70 46,000 3.72 29,600 2.66 8.5 355AAV060120
CSPH*6012A** 47,000 TXV 13.00 10.80 45,000 3.68 30,600 2.64 8.5
060---A
*FY4ANB060 59,500 TDR&TXV 13.00 10.8 60,000 3.62 38,500 2.56 8.0
FV4BNB006 60,000 TDR&TXV 14.00 11.50 58,500 3.74 36,200 2.68 8.2
FX4CN(B,F)060 60,000 TDR&TXV 14.00 12.00 58,500 3.74 36,200 2.68 8.3
CAP**6021A** 58,000 TDR&TXV 13.50 11.20 56,500 3.48 36,000 2.52 7.8 315(A,J)AV060110
CAP**6021A** 59,000 TXV 13.00 10.80 58,000 3.48 36,400 2.52 7.8
CAP**6024A** 59,000 TDR&TXV 13.50 11.50 57,500 3.50 35,800 2.54 7.8 315(A,J)AV066135
CAP**6024A** 59,000 TDR&TXV 14.00 11.50 57,500 3.54 35,800 2.56 7.9 315(A,J)AV066155
CAP**6024A** 60,000 TXV 13.00 10.80 59,000 3.60 37,000 2.54 8.0
CNPH*6024A** 58,500 TDR&TXV 13.50 11.20 57,500 3.46 36,000 2.52 7.7 315(A,J)AV060110
CNPH*6024A** 58,500 TDR&TXV 13.50 11.20 57,000 3.48 35,800 2.54 7.8 315(A,J)AV066135
CNPH*6024A** 59,000 TDR&TXV 14.00 11.50 57,000 3.52 35,800 2.56 7.8 315(A,J)AV066155
CNPH*6024A** 59,500 TXV 13.00 10.80 58,500 3.54 37,600 2.60 8.0
CNPV*6024A** 58,500 TDR&TXV 13.50 11.20 57,000 3.48 35,800 2.54 7.8 315(A,J)AV066135
CNPV*6024A** 59,000 TDR&TXV 14.00 11.50 57,000 3.52 35,800 2.56 7.8 315(A,J)AV066155
CNPV*6024A** 59,500 TXV 13.00 10.80 58,500 3.54 36,800 2.54 7.9
CSPH*6012A** 59,000 TDR&TXV 13.50 11.20 57,500 3.52 36,000 2.54 7.8 315(A,J)AV060110
CSPH*6012A** 59,000 TDR&TXV 14.00 11.50 57,500 3.56 35,800 2.56 7.9 315(A,J)AV066135
CSPH*6012A** 59,000 TDR&TXV 14.00 11.50 57,500 3.58 35,800 2.58 7.9 315(A,J)AV066155
CSPH*6012A** 60,000 TXV 13.00 10.80 59,000 3.62 37,000 2.56 8.0
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80_F(27_C) db 67_F(19_C) wb indoor entering air temperature and 95_F(35_C) db air entering outdoor unit.
High---Temp Heating Standard: 70_F(21_C) db indoor entering air temperature and 47_F(8_C) db 43˚F(6_C) wb air entering outdoor unit.
Low---Temp Heating Standard: 70_F(21_C) db indoor entering air temperature and 17_F(±9_C) db 15˚F(±10_C) wb air entering outdoor unit.
SEER — Seasonal Energy Efficiency Ratio
COP — Coefficient of Performance
TDR — Time---Delay Relay
HSPF — Heating Seasonal Performance Factor
EER — Energy Efficiency Ratio
213A
18
DETAILED COOLING CAPACITIES
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
213ANA018---A Outdoor Section With FY4ANF018 Indoor Section
525
72 20.64 10.54 1.23 19.61 10.14 1.39 18.55 9.74 1.56 17.47 9.33 1.76 16.33 8.90 1.97 15.11 8.45 2.22
67 18.78 13.08 1.25 17.82 12.66 1.40 16.83 12.24 1.58 15.83 11.82 1.77 14.77 11.38 1.99 13.63 10.91 2.24
63 17.40 12.62 1.26 16.51 12.21 1.42 15.58 11.79 1.59 14.63 11.36 1.79 13.63 10.91 2.01 12.56 10.44 2.25
62 17.05 15.58 1.26 16.18 15.14 1.42 15.29 14.69 1.59 14.39 14.21 1.79 13.52 13.52 2.01 12.66 12.66 2.25
57 16.48 16.48 1.27 15.79 15.79 1.42 15.07 15.07 1.60 14.32 14.32 1.79 13.52 13.52 2.01 12.66 12.66 2.25
600
72 21.01 11.02 1.25 19.93 10.62 1.41 18.83 10.20 1.59 17.71 9.79 1.78 16.54 9.36 2.00 15.27 8.90 2.24
67 19.12 13.88 1.27 18.12 13.46 1.43 17.10 13.03 1.60 16.05 12.60 1.80 14.96 12.15 2.02 13.79 11.68 2.26
63 17.74 13.38 1.29 16.80 12.96 1.44 15.84 12.53 1.62 14.85 12.09 1.81 13.82 11.63 2.04 12.72 11.15 2.28
62 17.42 16.67 1.29 16.53 16.19 1.45 15.64 15.64 1.62 14.84 14.84 1.81 14.00 14.00 2.03 13.09 13.09 2.27
57 17.14 17.14 1.29 16.40 16.40 1.45 15.64 15.64 1.62 14.84 14.84 1.81 14.00 14.00 2.03 13.09 13.09 2.27
675
72 21.28 11.47 1.28 20.17 11.06 1.44 19.03 10.64 1.61 17.88 10.23 1.81 16.68 9.80 2.03 15.38 9.33 2.27
67 19.38 14.65 1.30 18.34 14.22 1.46 17.29 13.79 1.63 16.22 13.35 1.83 15.10 12.89 2.05 13.91 12.39 2.29
63 17.99 14.10 1.31 17.02 13.67 1.47 16.03 13.23 1.65 15.02 12.78 1.84 13.96 12.31 2.06 12.83 11.81 2.31
62 17.74 17.61 1.31 16.91 16.91 1.47 16.10 16.10 1.64 15.27 15.27 1.84 14.39 14.39 2.06 13.44 13.44 2.30
57 17.69 17.69 1.31 16.91 16.91 1.47 16.10 16.10 1.64 15.27 15.27 1.84 14.39 14.39 2.06 13.44 13.44 2.30
Cooling Indoor Model Capacity Power Furnace Model
*FY4ANF018 1.00 1.00
CAP**1814A** 0.99 0.99
CAP**2414A** 1.02 0.99
CAP**2417A** 1.02 0.99
CNPF*2418A** 1.02 0.99
CNPH*2417A** 1.02 0.99
CNPV*1814A** 0.99 0.97
CNPV*2414A** 1.02 0.99
CNPV*2417A** 1.02 0.99
CSPH*2412A** 1.02 0.99
FF1ENP018 1.00 1.00
FF1ENP024 1.02 1.00
FV4BNF002 1.04 0.91
FX4CNF018 1.02 0.92
FX4CNF024 1.04 0.91
FY4ANF024 1.01 1.01
Cooling Indoor Model Capacity Power Furnace Model
CAP**1814A** 0.99 0.89 315(A,J)AV036070
CAP**2414A** 1.01 0.91 315(A,J)AV036070
CNPH*2417A** 1.01 0.91 315(A,J)AV036070
CNPV*1814A** 0.99 0.89 315(A,J)AV036070
CNPV*2414A** 1.01 0.91 315(A,J)AV036070
CSPH*2412A** 1.01 0.91 315(A,J)AV036070
CAP**2417A** 1.02 0.89 315(A,J)AV048090
CNPH*2417A** 1.02 0.91 315(A,J)AV048090
CNPV*2417A** 1.02 0.91 315(A,J)AV048090
CSPH*2412A** 1.01 0.89 315(A,J)AV048090
CNPH*2417A** 1.01 0.91 355AAV042040
CSPH*2412A** 1.01 0.91 355AAV042040
CAP**2417A** 1.01 0.91 355AAV042060
CNPH*2417A** 1.01 0.91 355AAV042060
CNPV*2417A** 1.01 0.91 355AAV042060
CSPH*2412A** 1.01 0.89 355AAV042060
CNPH*2417A** 1.02 0.91 355AAV042080
CSPH*2412A** 1.01 0.91 355AAV042080
See notes on pg. 24
213A
19
DETAILED COOLING CAPACITIES CONTINUED
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
213ANA024---A Outdoor Section With FY4ANF024 Indoor Section
700
72 26.97 13.80 1.66 25.72 13.32 1.86 24.41 12.81 2.09 23.03 12.29 2.34 21.54 11.73 2.61 19.91 11.13 2.91
67 24.65 17.15 1.66 23.49 16.65 1.86 22.26 16.12 2.09 20.97 15.57 2.34 19.59 15.00 2.62 18.09 14.38 2.92
63 22.94 16.60 1.66 21.84 16.09 1.86 20.68 15.56 2.09 19.46 15.01 2.34 18.16 14.43 2.62 16.76 13.81 2.92
62 22.50 20.46 1.66 21.42 19.93 1.86 20.30 19.36 2.09 19.14 18.75 2.34 17.96 17.96 2.62 16.82 16.82 2.92
57 21.73 21.73 1.66 20.87 20.87 1.86 19.96 19.96 2.09 19.00 19.00 2.34 17.96 17.96 2.62 16.82 16.82 2.92
800
72 27.42 14.42 1.69 26.13 13.93 1.90 24.76 13.42 2.12 24.27 13.23 2.06 21.80 12.33 2.65 20.12 11.72 2.94
67 25.09 18.20 1.69 23.88 17.68 1.90 22.60 17.15 2.12 21.27 16.60 2.37 19.84 16.01 2.65 18.29 15.38 2.95
63 23.37 17.58 1.69 22.22 17.07 1.90 21.02 16.52 2.13 19.76 15.96 2.38 18.41 15.37 2.65 16.96 14.73 2.95
62 22.96 21.88 1.69 21.86 21.30 1.90 20.72 20.69 2.13 19.67 19.67 2.38 18.57 18.57 2.65 17.37 17.37 2.95
57 22.57 22.57 1.69 21.66 21.66 1.90 20.70 20.70 2.13 19.67 19.67 2.38 18.57 18.57 2.65 17.37 17.37 2.95
900
72 27.75 15.01 1.73 26.42 14.51 1.93 26.10 14.39 1.86 24.55 13.82 2.09 22.87 13.22 2.36 20.25 12.28 2.98
67 25.40 19.19 1.73 24.16 18.68 1.93 22.85 18.13 2.16 21.48 17.57 2.41 20.02 16.97 2.69 18.43 16.31 2.98
63 23.68 18.52 1.73 22.50 17.99 1.93 21.26 17.44 2.16 19.97 16.87 2.41 18.59 16.26 2.69 17.11 15.60 2.99
62 23.36 23.12 1.73 22.32 22.31 1.93 21.30 21.30 2.16 20.23 20.23 2.41 19.07 19.07 2.69 17.81 17.81 2.99
57 23.27 23.27 1.73 22.31 22.31 1.93 21.30 21.30 2.16 20.23 20.23 2.41 19.07 19.07 2.69 17.81 17.81 2.99
Cooling Indoor
Model
Capacity Power Furnace Model
*FY4ANF024 1.00 1.00
FF1ENP024 1.01 0.99
FF1ENP030 1.01 1.02
FV4BNF002 1.03 0.92
FV4BNF003 1.04 0.91
FX4CNF024 1.02 0.94
FX4CNF030 1.04 0.93
FY4ANF030 1.02 1.01
CAP**2414A** 1.01 1.01
CAP**2417A** 1.01 1.01
CAP**3014A** 1.02 1.01
CAP**3017A** 1.02 1.01
CNPF*2418A** 1.01 1.01
CNPH*2417A** 1.01 1.01
CNPH*3017A** 1.02 1.01
CNPV*2414A** 1.01 1.01
CNPV*2417A** 1.01 1.01
CNPV*3014A** 1.02 1.01
CNPV*3017A** 1.02 1.01
CSPH*2412A** 1.01 1.00
CSPH*3012A** 1.02 1.01
CAP**2414A** 1.00 0.91 315(A,J)AV036070
CAP**3014A** 1.02 0.91 315(A,J)AV036070
CNPH*2417A** 1.00 0.91 315(A,J)AV036070
CNPH*3017A** 1.02 0.91 315(A,J)AV036070
CNPV*2414A** 1.00 0.91 315(A,J)AV036070
CNPV*3014A** 1.02 0.91 315(A,J)AV036070
CSPH*2412A** 1.00 0.91 315(A,J)AV036070
CSPH*3012A** 1.02 0.91 315(A,J)AV036070
CAP**2417A** 1.01 0.91 315(A,J)AV048090
CAP**3017A** 1.02 0.91 315(A,J)AV048090
CNPH*2417A** 1.01 0.91 315(A,J)AV048090
CNPH*3017A** 1.02 0.91 315(A,J)AV048090
CNPV*2417A** 1.01 0.92 315(A,J)AV048090
CNPV*3017A** 1.02 0.91 315(A,J)AV048090
CSPH*2412A** 1.00 0.90 315(A,J)AV048090
CSPH*3012A** 1.02 0.91 315(A,J)AV048090
CNPH*2417A** 1.01 0.92 315(A,J)AV060110
CNPH*3017A** 1.02 0.91 315(A,J)AV060110
CSPH*2412A** 1.00 0.91 315(A,J)AV060110
CSPH*3012A** 1.02 0.91 315(A,J)AV060110
CNPH*2417A** 1.01 0.92 315(A,J)AV066135
CNPH*3017A** 0.10 0.09 315(A,J)AV066135
CSPH*2412A** 1.00 0.90 315(A,J)AV066135
CSPH*3012A** 1.02 0.91 315(A,J)AV066135
Cooling Indoor
Model
Capacity Power Furnace Model
CNPH*2417A** 1.01 0.92 315(A,J)AV066155
CNPH*3017A** 1.02 0.91 315(A,J)AV066155
CSPH*2412A** 1.00 0.90 315(A,J)AV066155
CSPH*3012A** 1.02 0.91 315(A,J)AV066155
CNPH*2417A** 1.01 0.92 355AAV042040
CNPH*3017A** 1.02 0.91 355AAV042040
CSPH*2412A** 1.00 0.91 355AAV042040
CSPH*3012A** 1.02 0.91 355AAV042040
CAP**2417A** 1.01 0.91 355AAV042060
CAP**3017A** 1.02 0.91 355AAV042060
CNPH*2417A** 1.01 0.92 355AAV042060
CNPH*3017A** 1.02 0.91 355AAV042060
CNPV*2417A** 1.01 0.92 355AAV042060
CNPV*3017A** 1.02 0.91 355AAV042060
CSPH*2412A** 1.00 0.90 355AAV042060
CSPH*3012A** 1.02 0.91 355AAV042060
CNPH*2417A** 1.01 0.92 355AAV042080
CNPH*3017A** 1.02 0.91 355AAV042080
CSPH*2412A** 1.00 0.91 355AAV042080
CSPH*3012A** 1.02 0.91 355AAV042080
CNPH*2417A** 1.01 0.92 355AAV060080
CNPH*3017A** 1.02 0.91 355AAV060080
CSPH*2412A** 1.00 0.91 355AAV060080
CSPH*3012A** 1.02 0.91 355AAV060080
CNPH*2417A** 1.01 0.92 355AAV060100
CNPH*3017A** 1.02 0.91 355AAV060100
CSPH*2412A** 1.00 0.90 355AAV060100
CSPH*3012A** 1.02 0.91 355AAV060100
CNPH*2417A** 1.00 0.91 355AAV060120
CNPH*3017A** 1.02 0.91 355AAV060120
CSPH*2412A** 1.00 0.91 355AAV060120
CSPH*3012A** 1.02 0.91 355AAV060120
See notes on pg. 24
213A
20
DETAILED COOLING CAPACITIES CONTINUED
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
213ANA030---A Outdoor Section With FY4ANF030 Indoor Section
875
72 34.73 17.57 2.23 33.11 16.93 2.50 31.41 16.27 2.79 29.62 15.58 3.11 27.66 14.83 3.45 25.48 14.02 3.83
67 31.78 21.67 2.22 30.31 21.02 2.49 28.75 20.35 2.78 27.09 19.64 3.10 25.29 18.88 3.45 23.31 18.06 3.82
63 29.62 21.02 2.22 28.24 20.36 2.49 26.78 19.68 2.78 25.22 18.97 3.10 23.55 18.21 3.44 21.70 17.39 3.82
62 29.07 25.74 2.22 27.72 25.06 2.48 26.29 24.35 2.77 24.80 23.58 3.09 23.20 22.72 3.44 21.54 21.54 3.82
57 27.79 27.79 2.22 26.72 26.72 2.48 25.58 25.58 2.77 24.36 24.36 3.09 23.03 23.03 3.44 21.54 21.54 3.82
1000
72 35.33 18.30 2.28 33.65 17.66 2.54 31.88 16.99 2.83 30.02 16.29 3.15 27.99 15.53 3.50 25.73 14.71 3.87
67 32.36 22.91 2.27 30.83 22.26 2.53 29.20 21.57 2.83 27.47 20.85 3.15 25.61 20.07 3.49 23.55 19.23 3.87
63 30.19 22.19 2.27 28.75 21.52 2.53 27.22 20.83 2.82 25.60 20.11 3.14 23.86 19.33 3.49 21.95 18.48 3.86
62 29.66 27.43 2.27 28.27 26.72 2.53 26.81 25.94 2.82 25.31 25.03 3.14 23.78 23.78 3.49 22.20 22.20 3.86
57 28.86 28.86 2.26 27.72 27.72 2.53 26.50 26.50 2.82 25.21 25.21 3.14 23.79 23.79 3.49 22.20 22.20 3.86
1125
72 35.80 19.01 2.32 34.05 18.36 2.59 32.23 17.68 2.88 30.31 16.97 3.20 28.22 16.21 3.54 25.90 15.37 3.92
67 32.81 24.12 2.32 31.22 23.45 2.58 29.53 22.75 2.87 27.75 22.01 3.19 25.84 21.22 3.54 23.73 20.35 3.91
63 30.63 23.32 2.31 29.13 22.65 2.58 27.56 21.94 2.87 25.89 21.20 3.19 24.10 20.40 3.53 22.14 19.52 3.91
62 30.16 28.99 2.31 28.75 28.19 2.57 27.28 27.28 2.87 25.89 25.89 3.19 24.40 24.40 3.53 22.73 22.73 3.91
57 29.74 29.74 2.31 28.54 28.54 2.57 27.26 27.26 2.87 25.89 25.89 3.19 24.40 24.40 3.54 22.73 22.73 3.91
Cooling Indoor Model Capacity Power Furnace Model
*FY4ANF030 1.00 1.00
FF1ENP030 0.99 1.00
FF1ENP036 1.01 1.00
FV4BNF002 1.01 0.93
FV4BNF003 1.02 0.92
FV4BNF005 1.05 0.91
FX4CN(B,F)036 1.03 0.95
FX4CNF030 1.01 0.95
FY4ANF036 1.01 1.02
CAP**3014A** 1.01 1.01
CAP**3017A** 1.01 1.01
CAP**3614A** 1.01 1.01
CAP**3617A** 1.01 1.01
CAP**3621A** 1.01 1.01
CNPF*3618A** 1.01 1.01
CNPH*3017A** 1.01 1.01
CNPH*3617A** 1.01 1.01
CNPV*3014A** 1.01 1.01
CNPV*3017A** 1.01 1.01
CNPV*3617A** 1.01 1.01
CNPV*3621A** 1.01 1.01
CSPH*3012A** 1.01 1.00
CSPH*3612A** 1.01 0.99
CAP**3014A** 1.00 0.94 315(A,J)AV036070
CAP**3614A** 1.01 0.93 315(A,J)AV036070
CNPH*3017A** 1.01 0.93 315(A,J)AV036070
CNPH*3617A** 1.01 0.93 315(A,J)AV036070
CNPV*3014A** 1.00 0.94 315(A,J)AV036070
CSPH*3012A** 1.00 0.93 315(A,J)AV036070
CSPH*3612A** 1.01 0.92 315(A,J)AV036070
CAP**3017A** 1.01 0.92 315(A,J)AV048090
CAP**3617A** 1.01 0.92 315(A,J)AV048090
CNPH*3017A** 1.01 0.92 315(A,J)AV048090
CNPH*3617A** 1.01 0.92 315(A,J)AV048090
CNPV*3017A** 1.01 0.92 315(A,J)AV048090
CNPV*3617A** 1.01 0.92 315(A,J)AV048090
CSPH*3012A** 1.00 0.92 315(A,J)AV048090
CSPH*3612A** 1.01 0.91 315(A,J)AV048090
CAP**3621A** 1.01 0.92 315(A,J)AV060110
CNPH*3017A** 1.01 0.92 315(A,J)AV060110
CNPH*3617A** 1.01 0.92 315(A,J)AV060110
CNPV*3621A** 1.01 0.92 315(A,J)AV060110
CSPH*3012A** 1.00 0.92 315(A,J)AV060110
CSPH*3612A** 1.01 0.91 315(A,J)AV060110
Cooling Indoor Model Capacity Power Furnace Model
CNPH*3017A** 1.01 0.92 315(A,J)AV066135
CNPH*3617A** 1.01 0.92 315(A,J)AV066135
CSPH*3012A** 1.00 0.92 315(A,J)AV066135
CSPH*3612A** 1.01 0.90 315(A,J)AV066135
CNPH*3017A** 1.01 0.92 315(A,J)AV066155
CNPH*3617A** 1.01 0.92 315(A,J)AV066155
CSPH*3012A** 1.00 0.92 315(A,J)AV066155
CSPH*3612A** 1.01 0.90 315(A,J)AV066155
CNPH*3017A** 1.01 0.94 355AAV042040
CNPH*3617A** 1.01 0.94 355AAV042040
CSPH*3012A** 1.00 0.94 355AAV042040
CSPH*3612A** 1.01 0.92 355AAV042040
CAP**3017A** 1.00 0.93 355AAV042060
CAP**3617A** 1.01 0.92 355AAV042060
CNPH*3017A** 1.00 0.94 355AAV042060
CNPH*3617A** 1.00 0.93 355AAV042060
CNPV*3017A** 1.00 0.93 355AAV042060
CNPV*3617A** 1.00 0.93 355AAV042060
CSPH*3012A** 1.00 0.93 355AAV042060
CSPH*3612A** 1.01 0.92 355AAV042060
CAP**3621A** 1.01 0.92 355AAV042080
CNPH*3017A** 1.01 0.93 355AAV042080
CNPH*3617A** 1.01 0.93 355AAV042080
CNPV*3621A** 1.01 0.93 355AAV042080
CSPH*3012A** 1.00 0.94 355AAV042080
CSPH*3612A** 1.01 0.92 355AAV042080
CAP**3621A** 1.01 0.92 355AAV060080
CNPH*3017A** 1.01 0.93 355AAV060080
CNPH*3617A** 1.01 0.93 355AAV060080
CNPV*3621A** 1.01 0.93 355AAV060080
CSPH*3012A** 1.00 0.93 355AAV060080
CSPH*3612A** 1.01 0.92 355AAV060080
CAP**3621A** 1.01 0.92 355AAV060100
CNPH*3017A** 1.01 0.93 355AAV060100
CNPH*3617A** 1.01 0.93 355AAV060100
CNPV*3621A** 1.01 0.92 355AAV060100
CSPH*3012A** 1.00 0.93 355AAV060100
CSPH*3612A** 1.01 0.91 355AAV060100
CNPH*3017A** 1.01 0.92 355AAV060120
CNPH*3617A** 1.01 0.92 355AAV060120
CSPH*3012A** 1.00 0.92 355AAV060120
CSPH*3612A** 1.01 0.91 355AAV060120
See notes on pg. 24
213A
21
DETAILED COOLING CAPACITIES CONTINUED
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
213ANA036---A Outdoor Section With FY4ANF042 Indoor Section
1050
72 40.73 21.10 2.51 38.83 20.37 2.78 36.79 19.60 3.08 34.66 18.81 3.42 32.34 17.95 3.78 31.18 17.52 3.75
67 37.22 26.47 2.51 35.44 25.71 2.78 33.56 24.91 3.08 31.57 24.08 3.42 29.44 23.20 3.78 27.10 22.25 4.17
63 34.65 25.59 2.51 32.97 24.83 2.78 31.20 24.02 3.08 29.33 23.18 3.41 27.32 22.30 3.78 25.14 21.34 4.17
62 34.00 31.76 2.51 32.37 30.94 2.78 30.68 30.05 3.08 28.95 28.95 3.41 27.33 27.33 3.78 26.26 26.26 3.72
57 33.18 33.18 2.51 31.86 31.86 2.78 30.45 30.45 3.08 28.95 28.95 3.41 27.33 27.33 3.77 26.26 26.26 3.72
1200
72 41.35 22.07 2.57 39.36 21.33 2.84 37.27 20.55 3.14 35.06 19.74 3.47 32.66 18.88 3.84 30.03 17.94 4.23
67 37.80 28.11 2.57 35.95 27.34 2.84 34.00 26.53 3.14 31.95 25.68 3.47 29.75 24.79 3.83 27.35 23.80 4.23
63 35.22 27.14 2.57 33.47 26.36 2.84 31.63 25.53 3.14 29.70 24.68 3.47 27.64 23.77 3.83 25.39 22.78 4.22
62 34.66 33.91 2.57 33.01 33.01 2.84 31.50 31.50 3.14 29.91 29.91 3.47 28.19 28.19 3.83 26.29 26.29 4.23
57 34.40 34.40 2.57 32.99 32.99 2.84 31.50 31.50 3.14 29.91 29.91 3.47 28.19 28.19 3.83 26.29 26.29 4.23
1350
72 41.78 22.99 2.62 39.74 22.24 2.90 37.58 21.45 3.20 35.32 20.64 3.53 32.87 19.76 3.89 30.17 18.81 4.28
67 38.22 29.69 2.62 36.32 28.90 2.90 34.31 28.07 3.20 32.21 27.20 3.53 29.96 26.28 3.89 27.51 25.25 4.28
63 35.62 28.60 2.62 33.83 27.80 2.90 31.94 26.97 3.20 29.96 26.09 3.53 27.86 25.15 3.89 25.57 24.11 4.28
62 35.39 35.39 2.62 33.91 33.91 2.90 32.35 32.35 3.20 30.68 30.68 3.53 28.88 28.88 3.89 26.88 26.88 4.28
57 35.39 35.39 2.62 33.92 33.92 2.90 32.35 32.35 3.20 30.69 30.69 3.53 28.88 28.88 3.89 26.88 26.88 4.28
Cooling Indoor Model Capacity Power Furnace Model
*FY4ANF042 1.00 1.00
FF1ENP036 0.99 0.98
FV4BNF002 0.98 0.93
FV4BNF003 0.99 0.92
FV4BNF005 1.03 0.91
FX4CN(B,F)036 1.00 0.95
FX4CN(B,F)042 1.02 0.94
FY4ANF036 0.97 0.98
CAP**3614A** 0.95 0.96
CAP**3617A** 0.98 0.99
CAP**3621A** 0.98 0.99
CAP**4221A** 0.99 0.99
CAP**4224A** 0.99 0.99
CNPF*3618A** 0.98 0.99
CNPH*3617A** 0.98 0.99
CNPH*4221A** 0.99 0.99
CNPV*3617A** 0.98 0.99
CNPV*3621A** 0.98 0.99
CNPV*4221A** 0.99 0.99
CSPH*3612A** 0.98 0.97
CSPH*4212A** 0.99 0.98
CAP**3614A** 0.95 0.92 315(A,J)AV036070
CNPH*3617A** 0.98 0.92 315(A,J)AV036070
CNPH*4221A** 0.99 0.91 315(A,J)AV036070
CSPH*3612A** 0.98 0.91 315(A,J)AV036070
CSPH*4212A** 0.99 0.92 315(A,J)AV036070
CAP**3617A** 0.98 0.91 315(A,J)AV048090
CNPH*3617A** 0.98 0.93 315(A,J)AV048090
CNPH*4221A** 0.99 0.90 315(A,J)AV048090
CNPV*3617A** 0.98 0.93 315(A,J)AV048090
CSPH*3612A** 0.98 0.91 315(A,J)AV048090
CSPH*4212A** 0.99 0.92 315(A,J)AV048090
CAP**3621A** 0.99 0.91 315(A,J)AV060110
CAP**4221A** 0.99 0.92 315(A,J)AV060110
CNPH*3617A** 0.98 0.93 315(A,J)AV060110
CNPH*4221A** 0.99 0.90 315(A,J)AV060110
CNPV*3621A** 0.99 0.94 315(A,J)AV060110
CNPV*4221A** 0.99 0.90 315(A,J)AV060110
CSPH*3612A** 0.98 0.91 315(A,J)AV060110
CSPH*4212A** 0.99 0.92 315(A,J)AV060110
CAP**4224A** 0.99 0.92 315(A,J)AV066135
CNPH*3617A** 0.98 0.93 315(A,J)AV066135
CNPH*4221A** 0.99 0.90 315(A,J)AV066135
CSPH*3612A** 0.98 0.91 315(A,J)AV066135
CSPH*4212A** 0.99 0.90 315(A,J)AV066135
Cooling Indoor Model Capacity Power Furnace Model
CAP**4224A** 0.99 0.90 315(A,J)AV066155
CNPH*3617A** 0.98 0.91 315(A,J)AV066155
CNPH*4221A** 0.99 0.90 315(A,J)AV066155
CSPH*3612A** 0.98 0.89 315(A,J)AV066155
CSPH*4212A** 0.99 0.90 315(A,J)AV066155
CAP**4224A** 0.99 0.94 355AAV042040
CNPH*3617A** 0.98 0.93 355AAV042040
CNPH*4221A** 0.98 0.91 355AAV042040
CSPH*3612A** 0.98 0.93 355AAV042040
CSPH*4212A** 0.99 0.91 355AAV042040
CAP**3617A** 0.98 0.93 355AAV042060
CNPH*3617A** 0.98 0.92 355AAV042060
CNPH*4221A** 0.99 0.90 355AAV042060
CNPV*3617A** 0.98 0.92 355AAV042060
CSPH*3612A** 0.98 0.91 355AAV042060
CSPH*4212A** 0.99 0.91 355AAV042060
CAP**3621A** 0.98 0.92 355AAV042080
CAP**4221A** 0.98 0.93 355AAV042080
CNPH*3617A** 0.97 0.94 355AAV042080
CNPH*4221A** 0.98 0.91 355AAV042080
CNPV*3621A** 0.98 0.94 355AAV042080
CNPV*4221A** 0.98 0.91 355AAV042080
CSPH*3612A** 0.98 0.93 355AAV042080
CSPH*4212A** 0.99 0.91 355AAV042080
CAP**3621A** 0.98 0.92 355AAV060080
CAP**4221A** 0.99 0.91 355AAV060080
CNPH*3617A** 0.98 0.92 355AAV060080
CNPH*4221A** 0.99 0.91 355AAV060080
CNPV*3621A** 0.98 0.92 355AAV060080
CNPV*4221A** 0.99 0.91 355AAV060080
CSPH*3612A** 0.98 0.91 355AAV060080
CSPH*4212A** 0.99 0.91 355AAV060080
CAP**3621A** 0.98 0.91 355AAV060100
CAP**4221A** 0.99 0.91 355AAV060100
CNPH*3617A** 0.98 0.92 355AAV060100
CNPH*4221A** 0.99 0.91 355AAV060100
CNPV*3621A** 0.98 0.93 355AAV060100
CNPV*4221A** 0.99 0.91 355AAV060100
CSPH*3612A** 0.98 0.91 355AAV060100
CSPH*4212A** 0.99 0.92 355AAV060100
CAP**4224A** 0.99 0.91 355AAV060120
CNPH*3617A** 0.98 0.92 355AAV060120
CNPH*4221A** 0.99 0.90 355AAV060120
CSPH*3612A** 0.98 0.91 355AAV060120
CSPH*4212A** 0.99 0.92 355AAV060120
See notes on pg. 24
213A
22
DETAILED COOLING CAPACITIES CONTINUED
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
213ANA042---A Outdoor Section With FY4ANF042 Indoor Section
1225
72 48.26 24.63 3.08 46.00 23.75 3.41 43.63 22.84 3.77 41.15 21.90 4.17 38.47 20.90 4.61 35.49 19.80 5.09
67 44.21 30.69 3.06 42.14 29.80 3.39 39.96 28.86 3.76 37.67 27.90 4.16 35.20 26.87 4.60 32.50 25.76 5.08
63 41.23 29.75 3.05 39.29 28.85 3.38 37.24 27.91 3.75 35.09 26.94 4.15 32.79 25.91 4.60 30.28 24.80 5.08
62 40.45 36.69 3.05 38.56 35.75 3.38 36.58 34.74 3.74 34.53 33.66 4.15 32.38 32.38 4.60 30.32 30.32 5.08
57 39.05 39.05 3.04 37.54 37.54 3.37 35.93 35.93 3.74 34.22 34.22 4.15 32.37 32.37 4.60 30.32 30.32 5.08
1400
72 48.98 25.68 3.16 46.64 24.79 3.48 44.18 23.87 3.84 41.64 22.93 4.25 38.84 21.90 4.68 35.77 20.79 5.16
67 44.93 32.50 3.14 42.77 31.59 3.47 40.50 30.64 3.83 38.12 29.66 4.23 35.57 28.61 4.68 32.78 27.46 5.16
63 41.93 31.44 3.13 39.91 30.53 3.45 37.78 29.58 3.82 35.55 28.58 4.23 33.17 27.53 4.67 30.58 26.38 5.16
62 41.22 39.13 3.12 39.28 38.11 3.45 37.28 36.95 3.82 35.34 35.34 4.22 33.37 33.37 4.67 31.19 31.19 5.16
57 40.48 40.48 3.12 38.87 38.87 3.45 37.16 37.16 3.82 35.34 35.34 4.22 33.38 33.38 4.67 31.19 31.19 5.16
1575
72 49.51 26.67 3.23 47.10 25.77 3.56 44.56 24.84 3.92 41.96 23.89 4.32 39.08 22.86 4.76 35.93 21.74 5.23
67 45.43 34.21 3.21 43.21 33.29 3.54 40.87 32.32 3.90 38.43 31.32 4.31 35.82 30.25 4.75 32.96 29.06 5.23
63 42.44 33.06 3.20 40.35 32.13 3.53 38.16 31.15 3.89 35.87 30.14 4.30 33.43 29.06 4.74 30.78 27.86 5.23
62 41.88 41.27 3.20 39.96 39.96 3.53 38.15 38.15 3.89 36.24 36.24 4.30 34.17 34.17 4.74 31.87 31.87 5.23
57 41.65 41.65 3.20 39.96 39.96 3.53 38.15 38.15 3.89 36.24 36.24 4.30 34.18 34.18 4.74 31.87 31.87 5.23
Cooling Indoor Model Capacity Power Furnace Model
*FY4ANF042 1.00 1.00
FV4BNB006 1.05 0.88
FV4BNF003 0.99 0.89
FV4BNF005 1.04 0.89
FX4CN(B,F)042 1.02 0.95
FX4CN(B,F)048 1.05 0.93
FY4ANF048 1.02 1.01
CAP**4221A** 0.99 0.99
CAP**4224A** 0.99 0.99
CAP**4817A** 1.00 0.97
CAP**4821A** 1.01 0.99
CAP**4824A** 1.01 0.99
CNPF*4818A** 1.00 0.99
CNPH*4221A** 1.00 1.00
CNPH*4821A** 1.01 0.99
CNPV*4221A** 0.99 0.99
CNPV*4821A** 1.01 0.99
CNPV*4824A** 1.01 0.99
CSPH*4212A** 0.99 0.96
CSPH*4812A** 1.01 0.98
CNPH*4221A** 0.99 0.93 315(A,J)AV036070
CNPH*4821A** 1.00 0.94 315(A,J)AV036070
CSPH*4212A** 0.98 0.91 315(A,J)AV036070
CSPH*4812A** 1.01 0.95 315(A,J)AV036070
CAP**4817A** 0.99 0.90 315(A,J)AV048090
CNPH*4221A** 0.99 0.90 315(A,J)AV048090
CNPH*4821A** 1.01 0.92 315(A,J)AV048090
CSPH*4212A** 0.99 0.90 315(A,J)AV048090
CSPH*4812A** 1.01 0.92 315(A,J)AV048090
CAP**4221A** 0.99 0.92 315(A,J)AV060110
CAP**4821A** 1.01 0.92 315(A,J)AV060110
CNPH*4221A** 1.00 0.90 315(A,J)AV060110
CNPH*4821A** 1.01 0.92 315(A,J)AV060110
CNPV*4221A** 0.99 0.89 315(A,J)AV060110
CNPV*4821A** 1.01 0.92 315(A,J)AV060110
CSPH*4212A** 0.99 0.90 315(A,J)AV060110
CSPH*4812A** 1.01 0.92 315(A,J)AV060110
CAP**4224A** 0.99 0.90 315(A,J)AV066135
CAP**4824A** 1.01 0.91 315(A,J)AV066135
CNPH*4221A** 1.00 0.90 315(A,J)AV066135
CNPH*4821A** 1.01 0.91 315(A,J)AV066135
CNPV*4824A** 1.01 0.91 315(A,J)AV066135
CSPH*4212A** 0.99 0.89 315(A,J)AV066135
CSPH*4812A** 1.01 0.91 315(A,J)AV066135
CAP**4224A** 0.99 0.89 315(A,J)AV066155
CAP**4824A** 1.01 0.91 315(A,J)AV066155
CNPH*4221A** 1.00 0.90 315(A,J)AV066155
CNPH*4821A** 1.01 0.90 315(A,J)AV066155
CNPV*4824A** 1.01 0.91 315(A,J)AV066155
CSPH*4212A** 0.99 0.89 315(A,J)AV066155
CSPH*4812A** 1.01 0.91 315(A,J)AV066155
Cooling Indoor Model Capacity Power Furnace Model
CAP**4224A** 0.98 0.92 355AAV042040
CAP**4824A** 1.00 0.94 355AAV042040
CNPH*4221A** 0.99 0.92 355AAV042040
CNPH*4821A** 1.00 0.93 355AAV042040
CNPV*4824A** 1.00 0.93 355AAV042040
CSPH*4212A** 0.98 0.91 355AAV042040
CSPH*4812A** 1.00 0.93 355AAV042040
CAP**4817A** 0.99 0.91 355AAV042060
CNPH*4221A** 0.99 0.91 355AAV042060
CNPH*4821A** 1.00 0.92 355AAV042060
CSPH*4212A** 0.99 0.91 355AAV042060
CSPH*4812A** 1.00 0.92 355AAV042060
CAP**4221A** 0.98 0.93 355AAV042080
CAP**4821A** 1.00 0.91 355AAV042080
CNPH*4221A** 0.99 0.93 355AAV042080
CNPH*4821A** 1.00 0.94 355AAV042080
CNPV*4221A** 0.99 0.93 355AAV042080
CNPV*4821A** 1.00 0.94 355AAV042080
CSPH*4212A** 0.98 0.91 355AAV042080
CSPH*4812A** 1.00 0.94 355AAV042080
CAP**4221A** 0.99 0.93 355AAV060080
CAP**4821A** 1.00 0.93 355AAV060080
CNPH*4221A** 0.99 0.92 355AAV060080
CNPH*4821A** 1.00 0.93 355AAV060080
CNPV*4221A** 0.98 0.91 355AAV060080
CNPV*4821A** 1.00 0.93 355AAV060080
CSPH*4212A** 0.99 0.92 355AAV060080
CSPH*4812A** 1.00 0.92 355AAV060080
CAP**4221A** 0.99 0.92 355AAV060100
CAP**4821A** 1.00 0.92 355AAV060100
CNPH*4221A** 0.99 0.90 355AAV060100
CNPH*4821A** 1.00 0.91 355AAV060100
CNPV*4221A** 0.99 0.90 355AAV060100
CNPV*4821A** 1.00 0.91 355AAV060100
CSPH*4212A** 0.99 0.91 355AAV060100
CSPH*4812A** 1.00 0.92 355AAV060100
CAP**4224A** 0.99 0.92 355AAV060120
CAP**4824A** 1.00 0.91 355AAV060120
CNPH*4221A** 0.99 0.90 355AAV060120
CNPH*4821A** 1.00 0.91 355AAV060120
CNPV*4824A** 1.00 0.91 355AAV060120
CSPH*4212A** 0.99 0.90 355AAV060120
CSPH*4812A** 1.00 0.91 355AAV060120
See notes on pg. 24
213A
23
DETAILED COOLING CAPACITIES CONTINUED
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
213ANA048---A Outdoor Section With FY4ANF048 Indoor Section
1400
72 55.40 28.31 3.28 52.85 27.32 3.64 50.16 26.29 4.04 47.32 25.21 4.48 44.24 24.07 4.96 40.83 22.81 5.48
67 50.66 35.30 3.27 48.32 34.30 3.63 45.85 33.24 4.03 43.23 32.13 4.47 40.39 30.96 4.95 37.28 29.68 5.48
63 47.16 34.17 3.27 44.97 33.16 3.63 42.65 32.10 4.03 40.18 30.98 4.47 37.54 29.81 4.95 34.64 28.52 5.47
62 46.25 42.22 3.27 44.12 41.16 3.63 41.87 40.03 4.03 39.52 38.79 4.47 37.13 37.13 4.95 34.77 34.77 5.47
57 44.75 44.75 3.27 43.04 43.04 3.63 41.21 41.21 4.03 39.26 39.26 4.47 37.13 37.13 4.95 34.77 34.77 5.47
1600
72 56.26 29.55 3.36 53.63 28.56 3.72 50.81 27.50 4.12 47.87 26.42 4.56 44.68 25.26 5.04 41.16 23.99 5.56
67 51.50 37.44 3.36 49.07 36.42 3.72 46.50 35.35 4.12 43.77 34.22 4.56 40.83 33.02 5.04 37.62 31.70 5.56
63 47.98 36.18 3.35 45.70 35.15 3.71 43.28 34.07 4.11 40.73 32.94 4.55 37.99 31.73 5.03 35.00 30.41 5.56
62 47.16 45.12 3.35 44.97 43.96 3.71 42.69 42.69 4.11 40.59 40.59 4.55 38.33 38.33 5.03 35.82 35.82 5.56
57 46.44 46.44 3.35 44.61 44.61 3.71 42.67 42.67 4.11 40.59 40.59 4.55 38.34 38.34 5.03 35.83 35.83 5.56
1800
72 56.87 30.73 3.45 54.16 29.72 3.81 51.25 28.65 4.20 48.26 27.57 4.64 44.97 26.39 5.12 41.36 25.11 5.64
67 52.10 39.48 3.44 49.59 38.45 3.80 46.94 37.35 4.20 44.13 36.19 4.64 41.13 34.96 5.12 37.84 33.60 5.64
63 48.58 38.09 3.44 46.22 37.05 3.80 43.74 35.94 4.20 41.11 34.78 4.64 38.30 33.54 5.12 35.25 32.17 5.64
62 47.96 47.60 3.44 45.90 45.90 3.80 43.85 43.85 4.20 41.66 41.66 4.64 39.30 39.30 5.12 36.65 36.65 5.64
57 47.82 47.82 3.44 45.90 45.90 3.80 43.86 43.86 4.20 41.67 41.67 4.64 39.30 39.30 5.12 36.65 36.65 5.64
Cooling Indoor Model Capacity Power Furnace Model
*FY4ANF048 1.00 1.00
FB4BNB070 1.02 0.99
FV4BNB006 1.03 0.89
FV4BNF005 1.01 0.89
FX4CN(B,F)048 1.02 0.94
FX4CN(B,F)060 1.03 0.93
FY4ANB060 1.02 1.00
CAP**4817A** 0.97 0.97
CAP**4821A** 0.99 0.99
CAP**4824A** 0.99 0.99
CAP**6021A** 0.99 0.99
CAP**6024A** 1.01 1.01
CNPF*4818A** 0.97 0.97
CNPH*4821A** 0.97 0.97
CNPH*6024A** 1.01 1.01
CNPV*4821A** 0.99 0.99
CNPV*4824A** 0.99 0.99
CNPV*6024A** 1.01 1.01
CSPH*4812A** 0.99 0.99
CSPH*6012A** 1.01 1.01
CAP**4817A** 0.97 0.91 315(A,J)AV048090
CNPH*4821A** 0.96 0.90 315(A,J)AV048090
CNPH*6024A** 1.00 0.92 315(A,J)AV048090
CSPH*4812A** 0.98 0.92 315(A,J)AV048090
CSPH*6012A** 1.00 0.92 315(A,J)AV048090
CAP**4821A** 0.98 0.92 315(A,J)AV060110
CAP**6021A** 0.98 0.90 315(A,J)AV060110
CNPH*4821A** 0.96 0.90 315(A,J)AV060110
CNPH*6024A** 1.00 0.92 315(A,J)AV060110
CNPV*4821A** 0.98 0.92 315(A,J)AV060110
CSPH*4812A** 0.98 0.92 315(A,J)AV060110
CSPH*6012A** 1.01 0.93 315(A,J)AV060110
CAP**4824A** 0.98 0.90 315(A,J)AV066135
CAP**6024A** 1.01 0.93 315(A,J)AV066135
CNPH*4821A** 0.97 0.89 315(A,J)AV066135
CNPH*6024A** 1.00 0.90 315(A,J)AV066135
CNPV*4824A** 0.98 0.90 315(A,J)AV066135
CNPV*6024A** 1.00 0.90 315(A,J)AV066135
CSPH*4812A** 0.98 0.90 315(A,J)AV066135
CSPH*6012A** 1.01 0.91 315(A,J)AV066135
CAP**4824A** 0.99 0.93 315(A,J)AV066155
CAP**6024A** 1.01 0.91 315(A,J)AV066155
CNPH*4821A** 0.97 0.89 315(A,J)AV066155
CNPH*6024A** 1.01 0.91 315(A,J)AV066155
CNPV*4824A** 0.99 0.93 315(A,J)AV066155
CNPV*6024A** 1.01 0.91 315(A,J)AV066155
CSPH*4812A** 0.98 0.90 315(A,J)AV066155
CSPH*6012A** 1.01 0.91 315(A,J)AV066155
Cooling Indoor Model Capacity Power Furnace Model
CAP**4821A** 0.98 0.92 355AAV060080
CAP**6021A** 0.98 0.90 355AAV060080
CNPH*4821A** 0.96 0.90 355AAV060080
CNPH*6024A** 1.00 0.94 355AAV060080
CNPV*4821A** 0.98 0.92 355AAV060080
CSPH*4812A** 0.98 0.92 355AAV060080
CSPH*6012A** 1.00 0.92 355AAV060080
CAP**4821A** 0.98 0.92 355AAV060100
CAP**6021A** 0.98 0.90 355AAV060100
CNPH*4821A** 0.96 0.90 355AAV060100
CNPH*6024A** 1.00 0.92 355AAV060100
CNPV*4821A** 0.98 0.92 355AAV060100
CSPH*4812A** 0.98 0.92 355AAV060100
CSPH*6012A** 1.00 0.92 355AAV060100
CAP**4824A** 0.98 0.92 355AAV060120
CAP**6024A** 1.00 0.92 355AAV060120
CNPH*4821A** 0.96 0.90 355AAV060120
CNPH*6024A** 1.00 0.92 355AAV060120
CNPV*4824A** 0.98 0.92 355AAV060120
CNPV*6024A** 1.00 0.92 355AAV060120
CSPH*4812A** 0.98 0.92 355AAV060120
CSPH*6012A** 1.00 0.92 355AAV060120
See notes on pg. 24
213A
24
DETAILED COOLING CAPACITIES CONTINUED
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
213ANA060---A Outdoor Section With FY4ANF060 Indoor Section
1750
72 71.08 36.09 4.41 67.69 34.77 4.86 64.09 33.39 5.36 60.33 31.96 5.90 56.30 30.45 6.50 51.84 28.81 7.14
67 65.19 45.05 4.36 62.05 43.69 4.81 58.73 42.27 5.30 55.30 40.82 5.85 51.61 39.29 6.44 47.57 37.62 7.09
63 60.79 43.67 4.31 57.85 42.31 4.76 54.78 40.90 5.26 51.57 39.45 5.81 48.15 37.91 6.40 44.41 36.26 7.05
62 59.61 53.90 4.30 56.75 52.49 4.75 53.77 51.00 5.25 50.69 49.41 5.80 47.50 47.50 6.40 45.90 45.90 6.36
57 57.48 57.48 4.28 55.20 55.20 4.74 52.79 52.79 5.24 50.24 50.24 5.79 47.49 47.49 6.40 44.42 44.42 7.06
2000
72 72.12 37.62 4.54 68.55 36.26 4.99 64.87 34.89 5.48 60.98 33.44 6.03 56.80 31.91 6.62 52.19 30.25 7.26
67 66.24 47.72 4.48 62.96 46.34 4.93 59.50 44.89 5.43 55.93 43.42 5.97 52.11 41.85 6.57 47.93 40.14 7.21
63 61.83 46.19 4.44 58.77 44.80 4.89 55.56 43.36 5.38 52.22 41.88 5.93 48.67 40.31 6.53 44.80 38.60 7.18
62 60.73 57.58 4.43 57.79 56.05 4.88 54.77 54.33 5.38 51.88 51.88 5.93 48.94 48.94 6.53 47.37 47.37 6.51
57 59.63 59.63 4.42 57.18 57.18 4.87 54.60 54.60 5.38 51.89 51.89 5.93 48.94 48.94 6.53 45.66 45.66 7.19
2250
72 72.83 39.05 4.66 69.16 37.69 5.11 65.40 36.31 5.61 61.39 34.85 6.15 57.10 33.30 6.74 52.35 31.61 7.37
67 66.96 50.26 4.61 63.58 48.86 5.06 60.01 47.39 5.55 56.35 45.89 6.09 52.43 44.28 6.69 48.14 42.52 7.33
63 62.58 48.57 4.56 59.40 47.16 5.01 56.09 45.69 5.51 52.66 44.18 6.05 49.01 42.56 6.65 45.05 40.80 7.30
62 61.68 60.83 4.56 58.79 58.79 5.01 56.05 56.05 5.51 53.19 53.19 6.06 50.08 50.08 6.66 46.62 46.62 7.31
57 61.37 61.37 4.55 58.79 58.79 5.01 56.06 56.06 5.51 53.19 53.19 6.06 50.08 50.08 6.66 46.62 46.62 7.31
Cooling Indoor Model Capacity Power Furnace Model
*FY4ANB060 1.00 1.00
FV4BNB006 1.01 0.95
FX4CN(B,F)060 1.01 0.91
CAP**6021A** 0.99 0.99
CAP**6024A** 1.01 1.01
CNPH*6024A** 1.00 1.00
CNPV*6024A** 1.00 1.00
CSPH*6012A** 1.01 1.01
CAP**6021A** 0.97 0.94 315(A,J)AV060110
CNPH*6024A** 0.98 0.95 315(A,J)AV060110
CSPH*6012A** 0.99 0.96 315(A,J)AV060110
CAP**6024A** 0.99 0.93 315(A,J)AV066135
CNPH*6024A** 0.98 0.95 315(A,J)AV066135
CNPV*6024A** 0.98 0.95 315(A,J)AV066135
CSPH*6012A** 0.99 0.93 315(A,J)AV066135
CAP**6024A** 0.99 0.93 315(A,J)AV066155
CNPH*6024A** 0.99 0.93 315(A,J)AV066155
CNPV*6024A** 0.99 0.93 315(A,J)AV066155
CSPH*6012A** 0.99 0.93 315(A,J)AV066155
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F(27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80_F(27_C).
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
EWB — Entering Wet Bulb
213A
25
HEAT PUMP HEATING PERFORMANCE
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES deg F
--- 3 717 27 37 47 57 67
EDB CFM
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg*
213ANA018--- A Outdoor Section With FY4ANF018 Indoor Section
65
525 6.43 5.92 1.23 8.38 7.70 1.28 10.46 9.53 1.33 12.69 11.27 1.38 15.19 13.83 1.44 17.98 17.98 1.52 20.66 20.66 1.59 23.20 23.20 1.67
600 6.59 6.06 1.25 8.56 7.87 1.29 10.68 9.74 1.33 12.92 11.48 1.37 15.51 14.11 1.43 18.25 18.25 1.49 20.72 20.72 1.55 23.20 23.20 1.61
675 6.74 6.20 1.27 8.72 8.01 1.31 10.85 9.89 1.34 13.13 11.66 1.38 15.74 14.33 1.43 18.51 18.51 1.48 20.74 20.74 1.53 23.06 23.06 1.58
70
525 6.09 5.60 1.27 8.12 7.46 1.33 10.19 9.29 1.39 12.41 11.02 1.44 14.88 13.54 1.51 17.65 17.65 1.60 20.42 20.42 1.67 22.95 22.95 1.75
600 6.25 5.75 1.29 8.28 7.61 1.35 10.39 9.47 1.39 12.63 11.22 1.44 15.15 13.79 1.50 18.00 18.00 1.57 20.51 20.51 1.63 23.03 23.03 1.70
675 6.40 5.89 1.31 8.44 7.75 1.36 10.56 9.63 1.40 12.83 11.39 1.44 15.39 14.01 1.50 18.16 18.16 1.55 20.56 20.56 1.60 22.95 22.95 1.66
75
525 5.73 5.27 1.32 7.79 7.16 1.39 9.90 9.03 1.45 12.14 10.78 1.51 14.56 13.25 1.58 17.32 17.32 1.67 20.17 20.17 1.76 22.69 22.69 1.84
600 5.89 5.42 1.34 7.97 7.32 1.40 10.10 9.21 1.46 12.36 10.97 1.51 14.84 13.50 1.57 17.64 17.64 1.65 20.35 20.35 1.71 22.82 22.82 1.79
675 6.04 5.56 1.36 8.13 7.47 1.42 10.28 9.37 1.47 12.55 11.15 1.51 15.07 13.71 1.57 17.88 17.88 1.63 20.38 20.38 1.68 22.80 22.80 1.75
Heating Indoor Model Capacity Power Furnace Model
*FY4ANF018 1.00 1.00
CAP**1814A** 1.00 1.01
CAP**2414A** 1.00 0.97
CAP**2417A** 1.00 0.97
CNPF*2418A** 1.00 0.95
CNPH*2417A** 1.00 0.95
CNPV*1814A** 1.00 0.97
CNPV*2414A** 1.00 0.95
CNPV*2417A** 1.00 0.95
CSPH*2412A** 0.99 0.95
FF1ENP018 1.00 1.00
FF1ENP024 0.99 0.97
FV4BNF002 0.96 0.88
FX4CNF018 0.98 0.92
FX4CNF024 0.97 0.89
FY4ANF024 0.99 0.99
CAP**1814A** 0.95 0.96 315(A,J)AV036070
CAP**2414A** 0.96 0.92 315(A,J)AV036070
CNPH*2417A** 0.96 0.91 315(A,J)AV036070
CNPV*1814A** 0.95 0.92 315(A,J)AV036070
CNPV*2414A** 0.96 0.91 315(A,J)AV036070
CSPH*2412A** 0.96 0.91 315(A,J)AV036070
CAP**2417A** 0.96 0.91 315(A,J)AV048090
CNPH*2417A** 0.96 0.91 315(A,J)AV048090
CNPV*2417A** 0.96 0.90 315(A,J)AV048090
CSPH*2412A** 0.96 0.90 315(A,J)AV048090
CNPH*2417A** 0.96 0.91 355AAV042040
CSPH*2412A** 0.96 0.91 355AAV042040
CAP**2417A** 0.96 0.92 355AAV042060
CNPH*2417A** 0.96 0.91 355AAV042060
CNPV*2417A** 0.96 0.91 355AAV042060
CSPH*2412A** 0.96 0.91 355AAV042060
CNPH*2417A** 0.96 0.90 355AAV042080
CSPH*2412A** 0.96 0.90 355AAV042080
Seenoteonpg.31
213A
26
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES deg F
--- 3 717 27 37 47 57 67
EDB CFM
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg*
213ANA024--- A Outdoor Section With FY4ANF024 Indoor Section
65
700 9.58 8.82 1.52 11.98 11.01 1.59 14.58 13.29 1.66 17.51 15.56 1.75 20.82 18.94 1.86 24.20 24.20 1.96 27.14 27.14 2.06 30.15 30.15 2.17
800 9.77 8.99 1.54 12.19 11.20 1.60 14.81 13.51 1.66 17.80 15.81 1.74 21.14 19.24 1.84 24.17 24.17 1.91 26.94 26.94 2.00 29.60 29.60 2.09
900 9.94 9.15 1.56 12.37 11.37 1.61 15.03 13.70 1.67 18.06 16.04 1.74 21.40 19.47 1.83 24.07 24.07 1.89 26.59 26.59 1.97 28.87 28.87 2.03
70
700 9.29 8.54 1.59 11.70 10.75 1.67 14.30 13.04 1.74 17.18 15.26 1.84 20.47 18.63 1.95 23.95 23.95 2.06 26.95 26.95 2.17 30.01 30.01 2.29
800 9.48 8.72 1.61 11.91 10.94 1.67 14.53 13.25 1.74 17.46 15.51 1.82 20.79 18.92 1.93 24.00 24.00 2.01 26.83 26.83 2.11 29.61 29.61 2.20
900 9.65 8.87 1.63 12.09 11.11 1.69 14.73 13.43 1.75 17.71 15.73 1.83 21.06 19.16 1.92 23.97 23.97 1.99 26.60 26.60 2.07 29.03 29.03 2.15
75
700 8.96 8.24 1.67 11.40 10.48 1.75 14.02 12.78 1.83 16.85 14.97 1.93 20.14 18.33 2.05 23.63 23.63 2.17 26.71 26.71 2.28 29.80 29.80 2.41
800 9.15 8.42 1.68 11.61 10.67 1.75 14.25 12.99 1.83 17.13 15.21 1.91 20.44 18.60 2.03 23.84 23.84 2.12 26.68 26.68 2.22 29.54 29.54 2.32
900 9.33 8.58 1.70 11.80 10.84 1.77 14.45 13.17 1.83 17.37 15.43 1.91 20.71 18.84 2.02 23.82 23.82 2.09 26.53 26.53 2.18 29.10 29.10 2.27
Heating Indoor
Model Capacity Power Furnace Model
*FY4ANF024 1.00 1.00
FF1ENP024 1.00 1.00
FF1ENP030 1.01 1.00
FV4BNF002 0.97 0.90
FV4BNF003 0.96 0.90
FX4CNF024 0.99 0.94
FX4CNF030 0.98 0.91
FY4ANF030 1.00 0.97
CAP**2414A** 1.02 1.00
CAP**2417A** 1.02 1.00
CAP**3014A** 0.98 0.97
CAP**3017A** 0.98 0.97
CNPF*2418A** 1.02 0.98
CNPH*2417A** 1.02 0.98
CNPH*3017A** 0.98 0.97
CNPV*2414A** 1.02 0.98
CNPV*2417A** 1.02 0.98
CNPV*3014A** 0.98 0.97
CNPV*3017A** 0.98 0.97
CSPH*2412A** 1.01 0.97
CSPH*3012A** 0.97 0.96
CAP**2414A** 0.98 0.96 315(A,J)AV036070
CAP**3014A** 0.96 0.93 315(A,J)AV036070
CNPH*2417A** 0.98 0.95 315(A,J)AV036070
CNPH*3017A** 0.96 0.93 315(A,J)AV036070
CNPV*2414A** 0.98 0.94 315(A,J)AV036070
CNPV*3014A** 0.96 0.93 315(A,J)AV036070
CSPH*2412A** 0.98 0.93 315(A,J)AV036070
CSPH*3012A** 0.95 0.92 315(A,J)AV036070
CAP**2417A** 0.98 0.94 315(A,J)AV048090
CAP**3017A** 0.96 0.92 315(A,J)AV048090
CNPH*2417A** 0.98 0.94 315(A,J)AV048090
CNPH*3017A** 0.96 0.92 315(A,J)AV048090
CNPV*2417A** 0.98 0.93 315(A,J)AV048090
CNPV*3017A** 0.96 0.92 315(A,J)AV048090
CSPH*2412A** 0.98 0.92 315(A,J)AV048090
CSPH*3012A** 0.95 0.91 315(A,J)AV048090
CNPH*2417A** 0.98 0.94 315(A,J)AV060110
CNPH*3017A** 0.96 0.92 315(A,J)AV060110
CSPH*2412A** 0.98 0.93 315(A,J)AV060110
CSPH*3012A** 0.95 0.92 315(A,J)AV060110
CNPH*2417A** 0.98 0.94 315(A,J)AV066135
CNPH*3017A** 0.96 0.92 315(A,J)AV066135
CSPH*2412A** 0.98 0.92 315(A,J)AV066135
CSPH*3012A** 0.95 0.91 315(A,J)AV066135
CNPH*2417A** 0.98 0.94 315(A,J)AV066155
CNPH*3017A** 0.96 0.92 315(A,J)AV066155
CSPH*2412A** 0.98 0.92 315(A,J)AV066155
CSPH*3012A** 0.95 0.91 315(A,J)AV066155
Heating Indoor
Model Capacity Power Furnace Model
CNPH*2417A** 0.98 0.94 355AAV042040
CNPH*3017A** 0.96 0.92 355AAV042040
CSPH*2412A** 0.98 0.93 355AAV042040
CSPH*3012A** 0.95 0.92 355AAV042040
CAP**2417A** 0.98 0.95 355AAV042060
CAP**3017A** 0.96 0.92 355AAV042060
CNPH*2417A** 0.98 0.94 355AAV042060
CNPH*3017A** 0.96 0.92 355AAV042060
CNPV*2417A** 0.98 0.94 355AAV042060
CNPV*3017A** 0.96 0.92 355AAV042060
CSPH*2412A** 0.98 0.93 355AAV042060
CSPH*3012A** 0.95 0.92 355AAV042060
CNPH*2417A** 0.98 0.94 355AAV042080
CNPH*3017A** 0.96 0.92 355AAV042080
CSPH*2412A** 0.98 0.93 355AAV042080
CSPH*3012A** 0.95 0.92 355AAV042080
CNPH*2417A** 0.98 0.94 355AAV060080
CNPH*3017A** 0.96 0.92 355AAV060080
CSPH*2412A** 0.98 0.93 355AAV060080
CSPH*3012A** 0.95 0.92 355AAV060080
CNPH*2417A** 0.98 0.94 355AAV060100
CNPH*3017A** 0.96 0.92 355AAV060100
CSPH*2412A** 0.98 0.92 355AAV060100
CSPH*3012A** 0.95 0.91 355AAV060100
CNPH*2417A** 0.98 0.95 355AAV060120
CNPH*3017A** 0.96 0.93 355AAV060120
CSPH*2412A** 0.98 0.93 355AAV060120
CSPH*3012A** 0.95 0.92 355AAV060120
Seenoteonpg.31
213A
27
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES deg F
--- 3 717 27 37 47 57 67
EDB CFM
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg*
213ANA030--- A Outdoor Section With FY4ANF030 Indoor Section
65
875 12.79 11.76 2.08 16.02 14.72 2.19 19.46 17.75 2.30 23.12 20.54 2.42 27.25 24.80 2.57 31.79 31.79 2.75 37.07 37.07 2.98 42.79 42.79 3.20
1000 13.05 12.01 2.10 16.31 14.98 2.20 19.78 18.03 2.30 23.49 20.86 2.40 27.71 25.21 2.54 32.34 32.34 2.70 37.78 37.78 2.90 43.34 43.34 3.08
1125 13.29 12.23 2.13 16.56 15.22 2.21 20.05 18.28 2.30 23.81 21.14 2.40 28.06 25.54 2.52 32.80 32.80 2.67 38.30 38.30 2.84 43.65 43.65 3.01
70
875 12.32 11.34 2.17 15.60 14.33 2.29 19.06 17.38 2.41 22.74 20.20 2.54 26.76 24.35 2.70 31.27 31.27 2.88 36.43 36.43 3.12 42.19 42.19 3.36
1000 12.59 11.58 2.19 15.89 14.60 2.30 19.38 17.67 2.41 23.09 20.51 2.52 27.20 24.75 2.66 31.80 31.80 2.83 37.12 37.12 3.04 42.77 42.77 3.23
1125 12.83 11.80 2.22 16.15 14.84 2.32 19.66 17.92 2.41 23.39 20.78 2.52 27.64 25.15 2.64 32.25 32.25 2.79 37.70 37.70 2.98 43.16 43.16 3.16
75
875 11.81 10.86 2.26 15.15 13.92 2.39 18.63 16.99 2.53 22.33 19.84 2.67 26.29 23.92 2.83 30.78 30.78 3.02 35.80 35.80 3.27 41.54 41.54 3.51
1000 12.08 11.11 2.28 15.43 14.18 2.40 18.96 17.29 2.52 22.69 20.15 2.65 26.72 24.32 2.79 31.28 31.28 2.96 36.49 36.49 3.19 42.21 42.21 3.39
1125 12.32 11.34 2.31 15.70 14.42 2.42 19.24 17.54 2.53 23.00 20.43 2.64 27.10 24.66 2.77 31.71 31.71 2.93 37.04 37.04 3.13 42.60 42.60 3.31
Heating Indoor Model Capacity Power Furnace Model
*FY4ANF030 1.00 1.00
FF1ENP030 1.00 1.01
FF1ENP036 1.01 1.00
FV4BNF002 0.97 0.95
FV4BNF003 0.97 0.94
FV4BNF005 0.97 0.88
FX4CN(B,F)036 0.99 0.95
FX4CNF030 0.99 0.95
FY4ANF036 1.01 1.01
CAP**3014A** 1.01 1.00
CAP**3017A** 1.01 1.00
CAP**3614A** 1.01 1.00
CAP**3617A** 1.01 1.00
CAP**3621A** 1.01 1.00
CNPF*3618A** 1.01 1.00
CNPH*3017A** 1.01 1.00
CNPH*3617A** 1.01 1.00
CNPV*3014A** 1.01 1.00
CNPV*3017A** 1.01 1.00
CNPV*3617A** 1.01 1.00
CNPV*3621A** 1.01 1.00
CSPH*3012A** 1.01 1.00
CSPH*3612A** 1.01 0.96
CAP**3014A** 0.97 0.98 315(A,J)AV036070
CAP**3614A** 0.97 0.97 315(A,J)AV036070
CNPH*3017A** 0.97 0.97 315(A,J)AV036070
CNPH*3617A** 0.97 0.97 315(A,J)AV036070
CNPV*3014A** 0.97 0.98 315(A,J)AV036070
CSPH*3012A** 0.97 0.97 315(A,J)AV036070
CSPH*3612A** 0.97 0.94 315(A,J)AV036070
CAP**3017A** 0.97 0.97 315(A,J)AV048090
CAP**3617A** 0.97 0.96 315(A,J)AV048090
CNPH*3017A** 0.97 0.97 315(A,J)AV048090
CNPH*3617A** 0.97 0.97 315(A,J)AV048090
CNPV*3017A** 0.97 0.97 315(A,J)AV048090
CNPV*3617A** 0.97 0.97 315(A,J)AV048090
CSPH*3012A** 0.97 0.96 315(A,J)AV048090
CSPH*3612A** 0.97 0.94 315(A,J)AV048090
CAP**3621A** 0.97 0.95 315(A,J)AV060110
CNPH*3017A** 0.97 0.96 315(A,J)AV060110
CNPH*3617A** 0.97 0.96 315(A,J)AV060110
CNPV*3621A** 0.97 0.96 315(A,J)AV060110
CSPH*3012A** 0.97 0.97 315(A,J)AV060110
CSPH*3612A** 0.97 0.93 315(A,J)AV060110
Heating Indoor Model Capacity Power Furnace Model
CNPH*3017A** 0.97 0.96 315(A,J)AV066135
CNPH*3617A** 0.97 0.96 315(A,J)AV066135
CSPH*3012A** 0.97 0.96 315(A,J)AV066135
CSPH*3612A** 0.97 0.93 315(A,J)AV066135
CNPH*3017A** 0.97 0.96 315(A,J)AV066155
CNPH*3617A** 0.97 0.96 315(A,J)AV066155
CSPH*3012A** 0.97 0.96 315(A,J)AV066155
CSPH*3612A** 0.97 0.93 315(A,J)AV066155
CNPH*3017A** 0.97 0.97 355AAV042040
CNPH*3617A** 0.97 0.97 355AAV042040
CSPH*3012A** 0.97 0.98 355AAV042040
CSPH*3612A** 0.97 0.94 355AAV042040
CAP**3017A** 0.97 0.98 355AAV042060
CAP**3617A** 0.97 0.97 355AAV042060
CNPH*3017A** 0.97 0.97 355AAV042060
CNPH*3617A** 0.97 0.97 355AAV042060
CNPV*3017A** 0.97 0.97 355AAV042060
CNPV*3617A** 0.97 0.97 355AAV042060
CSPH*3012A** 0.97 0.97 355AAV042060
CSPH*3612A** 0.97 0.94 355AAV042060
CAP**3621A** 0.97 0.96 355AAV042080
CNPH*3017A** 0.97 0.97 355AAV042080
CNPH*3617A** 0.97 0.97 355AAV042080
CNPV*3621A** 0.97 0.97 355AAV042080
CSPH*3012A** 0.97 0.97 355AAV042080
CSPH*3612A** 0.97 0.93 355AAV042080
CAP**3621A** 0.97 0.96 355AAV060080
CNPH*3017A** 0.97 0.97 355AAV060080
CNPH*3617A** 0.97 0.97 355AAV060080
CNPV*3621A** 0.97 0.97 355AAV060080
CSPH*3012A** 0.97 0.97 355AAV060080
CSPH*3612A** 0.97 0.93 355AAV060080
CAP**3621A** 0.97 0.96 355AAV060100
CNPH*3017A** 0.97 0.97 355AAV060100
CNPH*3617A** 0.97 0.97 355AAV060100
CNPV*3621A** 0.97 0.97 355AAV060100
CSPH*3012A** 0.97 0.97 355AAV060100
CSPH*3612A** 0.97 0.94 355AAV060100
CNPH*3017A** 0.97 0.97 355AAV060120
CNPH*3617A** 0.97 0.97 355AAV060120
CSPH*3012A** 0.97 0.97 355AAV060120
CSPH*3612A** 0.97 0.94 355AAV060120
Seenoteonpg.31
213A
28
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES deg F
--- 3 717 27 37 47 57 67
EDB CFM
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg*
213ANA036--- A Outdoor Section With FY4ANF042 Indoor Section
65
1050 14.42 13.27 2.31 18.07 16.60 2.40 21.93 19.99 2.50 26.06 23.15 2.60 30.80 28.03 2.74 35.94 35.94 2.86 40.65 40.65 2.99 45.56 45.56 3.15
1200 14.73 13.55 2.34 18.39 16.90 2.43 22.28 20.32 2.51 26.48 23.52 2.60 31.28 28.47 2.72 36.09 36.09 2.82 40.59 40.59 2.93 45.17 45.17 3.06
1350 15.01 13.81 2.38 18.68 17.17 2.46 22.60 20.61 2.53 26.84 23.84 2.62 31.71 28.85 2.73 36.12 36.12 2.80 40.35 40.35 2.90 44.12 44.12 3.00
70
1050 13.90 12.79 2.40 17.58 16.15 2.50 21.48 19.59 2.61 25.62 22.75 2.72 30.21 27.49 2.86 35.42 35.42 3.00 40.20 40.20 3.13 45.16 45.16 3.30
1200 14.21 13.08 2.43 17.92 16.47 2.53 21.84 19.91 2.62 26.00 23.10 2.72 30.77 28.00 2.85 35.80 35.80 2.95 40.30 40.30 3.07 45.00 45.00 3.21
1350 14.50 13.34 2.47 18.22 16.74 2.56 22.16 20.21 2.64 26.37 23.42 2.73 31.18 28.37 2.85 35.83 35.83 2.93 40.17 40.17 3.04 44.49 44.49 3.15
75
1050 13.33 12.27 2.49 17.07 15.69 2.61 21.00 19.15 2.72 25.17 22.35 2.84 29.67 27.00 2.98 34.85 34.85 3.14 39.73 39.73 3.28 44.72 44.72 3.45
1200 13.65 12.55 2.53 17.42 16.01 2.63 21.37 19.49 2.73 25.56 22.70 2.84 30.16 27.44 2.97 35.37 35.37 3.09 39.94 39.94 3.22 44.67 44.67 3.36
1350 13.93 12.82 2.57 17.72 16.28 2.66 21.71 19.79 2.75 25.92 23.02 2.85 30.58 27.82 2.97 35.60 35.60 3.07 39.93 39.93 3.18 44.35 44.35 3.31
Heating Indoor
Model Capacity Power Furnace Model
*FY4ANF042 1.00 1.00
FF1ENP036 0.99 1.02
FV4BNF002 0.97 0.98
FV4BNF003 0.96 0.96
FV4BNF005 0.94 0.90
FX4CN(B,F)036 0.98 0.97
FX4CN(B,F)042 0.98 0.93
FY4ANF036 0.98 1.04
CAP**3614A** 0.98 1.03
CAP**3617A** 0.99 1.02
CAP**3621A** 0.99 1.02
CAP**4221A** 1.00 1.01
CAP**4224A** 1.00 1.01
CNPF*3618A** 0.99 1.03
CNPH*3617A** 0.99 1.03
CNPH*4221A** 1.00 1.01
CNPV*3617A** 0.99 1.03
CNPV*3621A** 0.99 1.03
CNPV*4221A** 1.00 1.01
CSPH*3612A** 0.99 0.98
CSPH*4212A** 1.00 0.97
CAP**3614A** 0.97 1.00 315(A,J)AV036070
CNPH*3617A** 0.96 1.00 315(A,J)AV036070
CNPH*4221A** 0.97 0.97 315(A,J)AV036070
CSPH*3612A** 0.97 0.96 315(A,J)AV036070
CSPH*4212A** 0.97 0.95 315(A,J)AV036070
CAP**3617A** 0.96 0.98 315(A,J)AV048090
CNPH*3617A** 0.96 0.99 315(A,J)AV048090
CNPH*4221A** 0.96 0.96 315(A,J)AV048090
CNPV*3617A** 0.96 0.99 315(A,J)AV048090
CSPH*3612A** 0.97 0.95 315(A,J)AV048090
CSPH*4212A** 0.97 0.93 315(A,J)AV048090
CAP**3621A** 0.96 0.98 315(A,J)AV060110
CAP**4221A** 0.97 0.97 315(A,J)AV060110
CNPH*3617A** 0.96 0.99 315(A,J)AV060110
CNPH*4221A** 0.96 0.95 315(A,J)AV060110
CNPV*3621A** 0.96 0.99 315(A,J)AV060110
CNPV*4221A** 0.96 0.95 315(A,J)AV060110
CSPH*3612A** 0.97 0.95 315(A,J)AV060110
CSPH*4212A** 0.97 0.93 315(A,J)AV060110
CAP**4224A** 0.96 0.96 315(A,J)AV066135
CNPH*3617A** 0.96 0.99 315(A,J)AV066135
CNPH*4221A** 0.96 0.95 315(A,J)AV066135
CSPH*3612A** 0.97 0.95 315(A,J)AV066135
CSPH*4212A** 0.97 0.93 315(A,J)AV066135
CAP**4224A** 0.96 0.95 315(A,J)AV066155
CNPH*3617A** 0.96 0.98 315(A,J)AV066155
CNPH*4221A** 0.96 0.94 315(A,J)AV066155
CSPH*3612A** 0.97 0.94 315(A,J)AV066155
CSPH*4212A** 0.97 0.92 315(A,J)AV066155
Heating Indoor
Model Capacity Power Furnace Model
CAP**4224A** 0.97 0.98 355AAV042040
CNPH*3617A** 0.96 1.00 355AAV042040
CNPH*4221A** 0.97 0.97 355AAV042040
CSPH*3612A** 0.97 0.97 355AAV042040
CSPH*4212A** 0.97 0.95 355AAV042040
CAP**3617A** 0.96 0.99 355AAV042060
CNPH*3617A** 0.96 1.00 355AAV042060
CNPH*4221A** 0.96 0.96 355AAV042060
CNPV*3617A** 0.96 1.00 355AAV042060
CSPH*3612A** 0.97 0.96 355AAV042060
CSPH*4212A** 0.97 0.94 355AAV042060
CAP**3621A** 0.96 1.00 355AAV042080
CAP**4221A** 0.97 0.99 355AAV042080
CNPH*3617A** 0.96 1.01 355AAV042080
CNPH*4221A** 0.96 0.97 355AAV042080
CNPV*3621A** 0.96 1.01 355AAV042080
CNPV*4221A** 0.96 0.97 355AAV042080
CSPH*3612A** 0.97 0.97 355AAV042080
CSPH*4212A** 0.97 0.95 355AAV042080
CAP**3621A** 0.96 0.99 355AAV060080
CAP**4221A** 0.97 0.98 355AAV060080
CNPH*3617A** 0.96 1.00 355AAV060080
CNPH*4221A** 0.97 0.97 355AAV060080
CNPV*3621A** 0.96 1.00 355AAV060080
CNPV*4221A** 0.97 0.97 355AAV060080
CSPH*3612A** 0.97 0.96 355AAV060080
CSPH*4212A** 0.97 0.94 355AAV060080
CAP**3621A** 0.96 0.98 355AAV060100
CAP**4221A** 0.97 0.98 355AAV060100
CNPH*3617A** 0.96 0.99 355AAV060100
CNPH*4221A** 0.96 0.96 355AAV060100
CNPV*3621A** 0.96 0.99 355AAV060100
CNPV*4221A** 0.96 0.96 355AAV060100
CSPH*3612A** 0.97 0.96 355AAV060100
CSPH*4212A** 0.97 0.94 355AAV060100
CAP**4224A** 0.96 0.97 355AAV060120
CNPH*3617A** 0.96 1.00 355AAV060120
CNPH*4221A** 0.96 0.96 355AAV060120
CSPH*3612A** 0.97 0.96 355AAV060120
CSPH*4212A** 0.97 0.94 355AAV060120
Seenoteonpg.31
213A
29
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES deg F
--- 3 717 27 37 47 57 67
EDB CFM
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg*
213ANA042--- A Outdoor Section With FY4ANF042 Indoor Section
65
1225 17.53 16.13 2.72 21.61 19.86 2.83 26.00 23.71 2.95 30.74 27.30 3.08 36.21 32.95 3.26 42.09 42.09 3.43 47.60 47.60 3.60 53.07 53.07 3.79
1400 17.88 16.45 2.75 21.99 20.20 2.85 26.39 24.06 2.96 31.20 27.71 3.08 36.75 33.44 3.25 42.44 42.44 3.38 47.57 47.57 3.53 52.73 52.73 3.69
1575 18.21 16.75 2.80 22.32 20.51 2.89 26.75 24.39 2.99 31.61 28.08 3.10 37.22 33.87 3.25 42.50 42.50 3.36 47.37 47.37 3.49 52.15 52.15 3.63
70
1225 17.06 15.69 2.84 21.17 19.45 2.96 25.58 23.32 3.09 30.29 26.90 3.23 35.68 32.47 3.42 41.58 41.58 3.60 47.11 47.11 3.77 52.62 52.62 3.98
1400 17.40 16.01 2.88 21.52 19.78 2.99 25.97 23.68 3.10 30.69 27.26 3.23 36.21 32.96 3.40 42.00 42.00 3.55 47.24 47.24 3.70 52.50 52.50 3.87
1575 17.74 16.32 2.92 21.88 20.11 3.02 26.32 24.00 3.12 31.11 27.63 3.24 36.68 33.38 3.40 42.19 42.19 3.52 47.15 47.15 3.66 52.04 52.04 3.81
75
1225 16.54 15.21 2.96 20.69 19.02 3.09 25.13 22.91 3.23 29.85 26.51 3.39 35.03 31.88 3.57 41.04 41.04 3.78 46.60 46.60 3.95 52.13 52.13 4.17
1400 16.89 15.54 3.00 21.08 19.37 3.12 25.53 23.28 3.24 30.29 26.90 3.38 35.58 32.38 3.55 41.57 41.57 3.72 46.84 46.84 3.88 52.10 52.10 4.06
1575 17.21 15.83 3.05 21.41 19.67 3.16 25.90 23.62 3.27 30.67 27.24 3.40 36.15 32.90 3.56 41.81 41.81 3.69 46.84 46.84 3.84 51.83 51.83 3.99
Heating Indoor Model Capacity Power Furnace Model
*FY4ANF042 1.00 1.00
FV4BNB006 0.94 0.90
FV4BNF003 0.98 1.01
FV4BNF005 0.96 0.93
FX4CN(B,F)042 1.00 0.96
FX4CN(B,F)048 0.95 0.89
FY4ANF048 0.98 0.97
CAP**4221A** 1.01 1.02
CAP**4224A** 1.01 1.02
CAP**4817A** 0.98 0.95
CAP**4821A** 1.00 0.98
CAP**4824A** 1.00 0.98
CNPF*4818A** 1.00 0.99
CNPH*4221A** 1.01 1.02
CNPH*4821A** 1.00 0.97
CNPV*4221A** 1.01 1.02
CNPV*4821A** 1.00 0.97
CNPV*4824A** 1.00 0.97
CSPH*4212A** 1.01 0.98
CSPH*4812A** 1.00 0.96
CNPH*4221A** 0.99 1.01 315(A,J)AV036070
CNPH*4821A** 0.98 0.96 315(A,J)AV036070
CSPH*4212A** 0.99 0.97 315(A,J)AV036070
CSPH*4812A** 0.99 0.96 315(A,J)AV036070
CAP**4817A** 0.96 0.93 315(A,J)AV048090
CNPH*4221A** 0.98 0.98 315(A,J)AV048090
CNPH*4821A** 0.98 0.94 315(A,J)AV048090
CSPH*4212A** 0.98 0.95 315(A,J)AV048090
CSPH*4812A** 0.98 0.93 315(A,J)AV048090
CAP**4221A** 0.98 0.99 315(A,J)AV060110
CAP**4821A** 0.98 0.94 315(A,J)AV060110
CNPH*4221A** 0.98 0.97 315(A,J)AV060110
CNPH*4821A** 0.98 0.94 315(A,J)AV060110
CNPV*4221A** 0.98 0.97 315(A,J)AV060110
CNPV*4821A** 0.98 0.94 315(A,J)AV060110
CSPH*4212A** 0.98 0.94 315(A,J)AV060110
CSPH*4812A** 0.98 0.93 315(A,J)AV060110
CAP**4224A** 0.98 0.98 315(A,J)AV066135
CAP**4824A** 0.98 0.93 315(A,J)AV066135
CNPH*4221A** 0.98 0.97 315(A,J)AV066135
CNPH*4821A** 0.98 0.93 315(A,J)AV066135
CNPV*4824A** 0.98 0.93 315(A,J)AV066135
CSPH*4212A** 0.98 0.93 315(A,J)AV066135
CSPH*4812A** 0.98 0.92 315(A,J)AV066135
CAP**4224A** 0.98 0.98 315(A,J)AV066155
CAP**4824A** 0.98 0.93 315(A,J)AV066155
CNPH*4221A** 0.98 0.97 315(A,J)AV066155
CNPH*4821A** 0.98 0.93 315(A,J)AV066155
CNPV*4824A** 0.98 0.93 315(A,J)AV066155
CSPH*4212A** 0.98 0.94 315(A,J)AV066155
CSPH*4812A** 0.98 0.93 315(A,J)AV066155
Heating Indoor Model Capacity Power Furnace Model
CAP**4224A** 0.98 1.01 355AAV042040
CAP**4824A** 0.98 0.96 355AAV042040
CNPH*4221A** 0.98 0.99 355AAV042040
CNPH*4821A** 0.99 0.97 355AAV042040
CNPV*4824A** 0.98 0.96 355AAV042040
CSPH*4212A** 0.99 0.97 355AAV042040
CSPH*4812A** 0.99 0.96 355AAV042040
CAP**4817A** 0.96 0.94 355AAV042060
CNPH*4221A** 0.98 0.99 355AAV042060
CNPH*4821A** 0.99 0.96 355AAV042060
CSPH*4212A** 0.99 0.97 355AAV042060
CSPH*4812A** 0.98 0.94 355AAV042060
CAP**4221A** 0.99 1.02 355AAV042080
CAP**4821A** 0.99 0.97 355AAV042080
CNPH*4221A** 0.98 0.99 355AAV042080
CNPH*4821A** 0.99 0.97 355AAV042080
CNPV*4221A** 0.98 0.99 355AAV042080
CNPV*4821A** 0.99 0.97 355AAV042080
CSPH*4212A** 0.99 0.98 355AAV042080
CSPH*4812A** 0.99 0.97 355AAV042080
CAP**4221A** 0.99 1.01 355AAV060080
CAP**4821A** 0.98 0.95 355AAV060080
CNPH*4221A** 0.98 0.99 355AAV060080
CNPH*4821A** 0.98 0.95 355AAV060080
CNPV*4221A** 0.98 0.99 355AAV060080
CNPV*4821A** 0.98 0.95 355AAV060080
CSPH*4212A** 0.99 0.97 355AAV060080
CSPH*4812A** 0.98 0.94 355AAV060080
CAP**4221A** 0.98 0.99 355AAV060100
CAP**4821A** 0.98 0.95 355AAV060100
CNPH*4221A** 0.98 0.98 355AAV060100
CNPH*4821A** 0.98 0.95 355AAV060100
CNPV*4221A** 0.98 0.98 355AAV060100
CNPV*4821A** 0.98 0.95 355AAV060100
CSPH*4212A** 0.99 0.96 355AAV060100
CSPH*4812A** 0.98 0.94 355AAV060100
CAP**4224A** 0.98 0.99 355AAV060120
CAP**4824A** 0.98 0.95 355AAV060120
CNPH*4221A** 0.98 0.98 355AAV060120
CNPH*4821A** 0.98 0.95 355AAV060120
CNPV*4824A** 0.98 0.95 355AAV060120
CSPH*4212A** 0.99 0.96 355AAV060120
CSPH*4812A** 0.98 0.94 355AAV060120
Seenoteonpg.31
213A
30
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES deg F
--- 3 717 27 37 47 57 67
EDB CFM
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg*
213ANA048--- A Outdoor Section With FY4ANF048 Indoor Section
65
1400 21.02 19.34 3.15 25.66 23.58 3.27 30.63 27.92 3.39 36.31 32.25 3.55 42.60 38.76 3.70 48.84 48.84 3.87 54.32 54.32 4.05 56.50 56.50 4.10
1600 21.41 19.70 3.20 26.07 23.95 3.30 31.08 28.34 3.41 36.82 32.70 3.55 43.01 39.14 3.68 48.80 48.80 3.84 51.13 51.13 3.89 52.63 52.63 3.91
1800 21.77 20.03 3.25 26.44 24.30 3.35 31.50 28.72 3.45 37.27 33.10 3.58 43.11 39.23 3.69 47.24 47.24 3.79 48.26 48.26 3.80 49.37 49.37 3.81
70
1400 20.52 18.88 3.29 25.21 23.16 3.42 30.19 27.53 3.55 35.74 31.74 3.71 41.99 38.21 3.90 48.41 48.41 4.06 54.98 54.98 4.29 57.35 57.35 4.34
1600 20.92 19.24 3.33 25.62 23.55 3.45 30.62 27.92 3.57 36.31 32.25 3.72 42.58 38.75 3.85 48.50 48.50 4.02 52.26 52.26 4.12 53.93 53.93 4.15
1800 21.28 19.58 3.39 26.01 23.90 3.49 31.03 28.29 3.60 36.75 32.64 3.74 42.83 38.98 3.86 48.16 48.16 4.01 49.40 49.40 4.02 50.74 50.74 4.04
75
1400 19.98 18.39 3.42 24.76 22.75 3.57 29.75 27.12 3.72 35.19 31.25 3.88 41.42 37.69 4.08 48.00 48.00 4.26 54.51 54.51 4.49 58.18 58.18 4.60
1600 20.37 18.74 3.47 25.14 23.10 3.60 30.19 27.53 3.73 35.69 31.70 3.88 42.01 38.22 4.04 48.14 48.14 4.21 53.06 53.06 4.36 54.85 54.85 4.40
1800 20.76 19.10 3.53 25.53 23.46 3.64 30.60 27.90 3.77 36.15 32.11 3.90 42.46 38.64 4.04 48.15 48.15 4.20 50.73 50.73 4.26 52.17 52.17 4.28
Heating Indoor Model Capacity Power Furnace Model
*FY4ANF048 1.00 1.00
FV4BNB006 0.95 0.89
FV4BNF005 0.98 0.94
FX4CN(B,F)048 0.98 0.94
FX4CN(B,F)060 0.91 0.87
FY4ANB060 0.93 0.95
CAP**4817A** 0.99 0.97
CAP**4821A** 1.01 0.99
CAP**4824A** 1.01 0.99
CAP**6021A** 0.93 0.95
CAP**6024A** 0.93 0.95
CNPF*4818A** 1.00 1.03
CNPH*4821A** 1.01 0.99
CNPH*6024A** 0.93 0.91
CNPV*4821A** 1.01 0.99
CNPV*4824A** 1.01 0.99
CNPV*6024A** 0.93 0.91
CSPH*4812A** 1.01 0.98
CSPH*6012A** 0.93 0.91
CAP**4817A** 0.98 0.96 315(A,J)AV048090
CNPH*4821A** 0.99 0.98 315(A,J)AV048090
CNPH*6024A** 0.95 0.93 315(A,J)AV048090
CSPH*4812A** 0.99 0.97 315(A,J)AV048090
CSPH*6012A** 0.95 0.92 315(A,J)AV048090
CAP**4821A** 0.99 0.97 315(A,J)AV060110
CAP**6021A** 0.95 0.93 315(A,J)AV060110
CNPH*4821A** 0.99 0.98 315(A,J)AV060110
CNPH*6024A** 0.95 0.92 315(A,J)AV060110
CNPV*4821A** 0.99 0.98 315(A,J)AV060110
CSPH*4812A** 0.99 0.96 315(A,J)AV060110
CSPH*6012A** 0.95 0.91 315(A,J)AV060110
CAP**4824A** 0.99 0.96 315(A,J)AV066135
CAP**6024A** 0.95 0.92 315(A,J)AV066135
CNPH*4821A** 0.99 0.97 315(A,J)AV066135
CNPH*6024A** 0.95 0.92 315(A,J)AV066135
CNPV*4824A** 0.99 0.97 315(A,J)AV066135
CNPV*6024A** 0.95 0.92 315(A,J)AV066135
CSPH*4812A** 0.99 0.96 315(A,J)AV066135
CSPH*6012A** 0.95 0.90 315(A,J)AV066135
CAP**4824A** 0.99 0.96 315(A,J)AV066155
CAP**6024A** 0.95 0.92 315(A,J)AV066155
CNPH*4821A** 0.99 0.96 315(A,J)AV066155
CNPH*6024A** 0.95 0.91 315(A,J)AV066155
CNPV*4824A** 0.99 0.96 315(A,J)AV066155
CNPV*6024A** 0.95 0.91 315(A,J)AV066155
CSPH*4812A** 0.99 0.95 315(A,J)AV066155
CSPH*6012A** 0.95 0.90 315(A,J)AV066155
Heating Indoor Model Capacity Power Furnace Model
CAP**4821A** 1.00 0.99 355AAV060080
CAP**6021A** 0.95 0.94 355AAV060080
CNPH*4821A** 1.00 1.00 355AAV060080
CNPH*6024A** 0.95 0.93 355AAV060080
CNPV*4821A** 1.00 1.00 355AAV060080
CSPH*4812A** 1.00 0.99 355AAV060080
CSPH*6012A** 0.95 0.92 355AAV060080
CAP**4821A** 0.99 0.98 355AAV060100
CAP**6021A** 0.95 0.94 355AAV060100
CNPH*4821A** 0.99 0.98 355AAV060100
CNPH*6024A** 0.95 0.93 355AAV060100
CNPV*4821A** 0.99 0.98 355AAV060100
CSPH*4812A** 0.99 0.97 355AAV060100
CSPH*6012A** 0.95 0.92 355AAV060100
CAP**4824A** 0.99 0.98 355AAV060120
CAP**6024A** 0.95 0.94 355AAV060120
CNPH*4821A** 0.99 0.99 355AAV060120
CNPH*6024A** 0.95 0.93 355AAV060120
CNPV*4824A** 0.99 0.99 355AAV060120
CNPV*6024A** 0.95 0.93 355AAV060120
CSPH*4812A** 0.99 0.97 355AAV060120
CSPH*6012A** 0.95 0.92 355AAV060120
Seenoteonpg.31
213A
31
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES deg F
--- 3 717 27 37 47 57 67
EDB CFM
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Capacity
MBtuh
Total
Sys-
tem
KW†
Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg* Total In-
teg*
213ANA060--- A Outdoor Section With FY4ANF060 Indoor Section
65
1750 25.07 23.07 3.86 30.90 28.40 4.00 37.17 33.89 4.16 43.81 38.91 4.34 51.11 46.51 4.54 59.85 59.85 4.79 68.95 68.95 5.02 78.00 78.00 5.31
2000 25.62 23.57 3.93 31.49 28.94 4.06 37.79 34.45 4.20 44.47 39.50 4.36 51.96 47.28 4.54 60.88 60.88 4.74 69.47 69.47 4.95 78.33 78.33 5.20
2250 26.13 24.04 4.01 32.03 29.44 4.13 38.34 34.96 4.26 45.07 40.03 4.40 52.72 47.97 4.57 61.49 61.49 4.73 69.75 69.75 4.92 77.76 77.76 5.13
70
1750 24.34 22.40 4.03 30.22 27.77 4.19 36.54 33.32 4.36 43.21 38.37 4.55 50.41 45.87 4.76 58.98 58.98 5.03 68.13 68.13 5.26 77.06 77.06 5.56
2000 24.89 22.90 4.10 30.80 28.30 4.24 37.17 33.89 4.40 43.87 38.96 4.57 51.17 46.57 4.75 60.00 60.00 4.97 68.71 68.71 5.18 77.50 77.50 5.44
2250 25.40 23.37 4.18 31.34 28.80 4.31 37.72 34.39 4.45 44.46 39.49 4.60 51.85 47.19 4.77 60.72 60.72 4.95 69.06 69.06 5.15 77.77 77.77 5.39
75
1750 23.57 21.68 4.21 29.50 27.11 4.38 35.86 32.70 4.57 42.56 37.80 4.77 49.72 45.25 4.99 57.81 57.81 5.26 67.28 67.28 5.51 76.15 76.15 5.82
2000 24.12 22.19 4.29 30.09 27.65 4.44 36.50 33.28 4.60 43.24 38.40 4.78 50.48 45.93 4.98 58.94 58.94 5.21 67.93 67.93 5.43 76.69 76.69 5.70
2250 24.63 22.66 4.37 30.63 28.15 4.51 37.07 33.80 4.66 43.83 38.93 4.82 51.15 46.54 5.00 59.80 59.80 5.19 68.35 68.35 5.40 76.95 76.95 5.64
Heating Indoor
Model Capacity Power Furnace Model
*FY4ANB060 1.00 1.00
FV4BNB006 0.98 0.94
FX4CN(B,F)060 0.98 0.94
CAP**6021A** 0.97 1.00
CAP**6024A** 0.98 0.99
CNPH*6024A** 0.98 0.99
CNPV*6024A** 0.98 0.99
CSPH*6012A** 0.98 0.98
Heating Indoor
Model Capacity Power Furnace Model
CAP**6021A** 0.94 0.98 315(A,J)AV060110
CNPH*6024A** 0.96 1.00 315(A,J)AV060110
CSPH*6012A** 0.96 0.98 315(A,J)AV060110
CAP**6024A** 0.96 0.99 315(A,J)AV066135
CNPH*6024A** 0.95 0.99 315(A,J)AV066135
CNPV*6024A** 0.95 0.99 315(A,J)AV066135
CSPH*6012A** 0.96 0.98 315(A,J)AV066135
CAP**6024A** 0.96 0.98 315(A,J)AV066155
CNPH*6024A** 0.95 0.98 315(A,J)AV066155
CNPV*6024A** 0.95 0.98 315(A,J)AV066155
CSPH*6012A** 0.96 0.97 315(A,J)AV066155
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement
heaters should be added to those values to obtain total system capacity.
{The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to
obtain total system kilowatts.
EDB — Entering Dry Bulb
213A
32
GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor--mounted, air--cooled, split--system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller--type
condenser fan, and a control box. Unit will discharge supply
air upward as shown on contract drawings. Unit will be used in
a refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
Unit will be rated in accordance with the latest edition
of ARI Standard 240.
Unit will be certified for capacity and efficiency, and
listed in the latest ARI directory.
Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
Unit will be constructed in accordance with UL
standards and will carry the UL label of approval.
Unit will have C--UL approval.
Unit cabinet will be capable of withstanding Federal
Test Method Standard No. 141 (Method 6061) 500--hr
salt spray test.
Air--cooled condenser coils are pressure tested and the
outdoor unit is leak tested.
Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is
stored and handled per unit manufacturer’s
recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air--cooled heat
pump unit. Contained within the unit enclosure is all
factory wiring, piping, controls, compressor,
refrigerant charge Puronr(R--410A), and special
features required prior to field start--up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
Fans
Condenser fan will be direct--drive propeller type,
discharging air upward.
AIR--COOLED, SPLIT--SYSTEM HEAT PUMP
213A
1--1/2 TO 5 NOMINAL TONS
Condenser fan motors will be totally enclosed,
1--phase type with class B insulation and permanently
lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically
balanced.
Condenser fan openings will be equipped with steel
wire safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins
mechanically bonded to copper tubes which are then
cleaned, dehydrated, and sealed.
Refrigeration Components
Refrigeration circuit components will include
liquid--line shutoff valve with sweat connections,
vapor--line shutoff valve with sweat connections,
system charge of Puronr(R--410A) refrigerant, POE
compressor oil, accumulator, and reversing valve.
Operating Characteristics
The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F. The power
consumption at full load will not exceed _____ kW.
Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F wet bulb
and _____ _F dry bulb, and air entering the unit at
_____ _F.
The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
Nominal unit electrical characteristics will be _____ v,
three phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying
accessories and descriptions for specific features and
available enhancements.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
EBryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.
. Edition Date: 03
/
06
Replaces: NEW
Catalog No. PDS 213
A
.18.1
213A

Navigation menu