Form No. PDS 697C.18.3B
SPLIT-SYSTEM
HEAT PUMP UNITS
697C (60 HZ)
Sizes 018 thru 060
The
AeroQuiet System (AQS)
consists of 4 design features to
achieve ultra-low sound ratings.
Aerocoustic Design
featuring the Aeromax opening and wire
dome top results in quieter and more efficient operation.
Energy-Efficient Fan and Fan Motor
provide a slower fan oper-
ation, thus reducing noise and improving efficiency.
Sound Hood
muffles noise from operation.
Discharge Muffler
minimizes low frequency sound and pres-
sure pulsation generated by compressor discharge gas.
The 697C Outdoor Sections of Split-System Heat Pumps are
designed for quiet, reliable heating during the winter and
cooling during the summer. These heat pump systems pro-
vide economy of operation through energy conservation with
SEER up to 14.0 and HSPF up to 9.0. They recover heat for
indoor comfort from outdoor air during the heating season
and, by automatically reversing the refrigerant system, re-
move indoor heat and excess humidity during the cooling
season. All models are listed with UL, c-UL, ARI, and CEC.
FEATURES
ELECTRICAL RANGE
—All units are single phase 208/230v.
COMPRESSOR
—This unit features a scroll compressor,
which is significantly more efficient than conventional com-
pressors. Its simple design offers improved reliability. Each
compressor is mounted on rubber isolators for additional
sound reduction. The scroll compressor starts under most
system loads, thus eliminating the need for start assistance
components. For improved serviceability, the 018 through
042 models are equipped with a compressor terminal plug.
Continuous operation is approved down to –30
°
F (–34.4
°
C)
in the heating mode and down to 55
°
F (12.8
°
C) in the cooling
mode. (See heating and cooling performance tables.) The
scroll compressor is covered with a standard 10-year limited
warranty.
BUILT-IN-RELIABLE COMPONENTS
—All units include a suc-
tion tube accumulator that minimizes the amount of liquid re-
frigerant that reaches the compressor; a high-pressure
switch for high-pressure protection; and a low-pressure
switch for loss of charge protection.
DEFROST CONTROL BOARD
—Incorporates a built-in 5-
minute compressor time-delay relay, defrost relay, defrost
timer, and low-voltage terminal board. The defrost control is a
time/temperature initiation/termination control, which includes
3 field-selectable time periods of 30, 50, and 90 minutes.
THERMOSTATIC EXPANSION VALVE (TXV)
—This unit
must be installed with a TXV on the indoor coil. The FC4 and
FK4 indoor fan coils come factory equipped with a bi-flow
TXV. When installed in this application, no further change is
required. If any other indoor fan coil or furnace coil is used,
an accessory bi-flow TXV must be installed. See accessory
list in this publication for correct part no.
WEATHER-PROTECTIVE CABINET
—Steel is galvanized and
coated with a layer of zinc phosphate. A coat of modified
polyester powder coating is then applied and baked-on, pro-
viding each unit with a hard, smooth finish that will last for
many years.
All screws on cabinet exterior are coated for a long-lasting,
rust-resistant, quality appearance.
UNIT DESIGN
—All units are equipped with totally enclosed
fan motors for greater reliability under rain and snow condi-
tions. The large, wraparound coil uses copper tube and en-
hanced aluminum fin and is designed for optimum heat
transfer during heating and cooling. The vertical air discharge
carries the sound and air up and away from adjacent patio ar-
eas and foliage. Rows of composite coils can be cleaned with
a common garden hose.
EXTERNAL SERVICE VALVES
—Both service valves are
brass, back seating type with sweat connections. Each valve
has a service port for ease of checking operating refrigerant
pressures. The suction service port provides for ease of
checking operating pressure in the heating mode.
LIMITED WARRANTY
—Standard 1-year warranty on all
parts, with an additional 9-year warranty on compressor.
—2—
DIMENSIONS
A94148
ACCESS
PANEL
1 1/4
"
1. Allow 30 in.
clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side,
and 24 in. between units for proper airflow.
Minimum outdoor operating ambient in cooling mode is 55°F (unless low ambient control is used) max 125°F.2.
Maximum outdoor operating ambient in heating mode is 66°F.3.
Series designation is the 14th position of the unit model number.4.
Center of gravity .5.
NOTES:
AIR DISCHARGE
AIR DISCHARGE
AIR IN
AIR IN
AIR IN
2 1/2
"
AIR DISCHARGE
1 3/4
"
4
"
3/8 IN.
DIA LIQUID
LINE CONN
H
DIA SUCTION
LINE CONN
8 3/16
"
7/8 IN.
DIA HOLE
FIELD POWER SUPPLY CONN 7/8 IN.
DIA (22.22)
HOLE WITH 1 1/8 IN.
DIA (34.92) KNOCKOUT
AND 1 3/8 IN.
DIA KNOCKOUT
3/8 IN.
DIA (9.5) TIEDOWN KNOCKOUTS
(2) PLACES IN BASEPAN
10 1/2
"
FIELD CONTROL
SUPPLY CONN
1 9/16
"
LC
F
N
G
A
B
M
K
E
D
C
L
DIMENSIONS (IN.)
UNIT
SIZE SERIES
UNIT DIMENSIONS MINIMUM MOUNTING
PAD DIMENSIONS
ABCDEFGHKLMSupport Feet Snow Stand
018 B 33-13/16 30 33 5-1/16 9-11/16 21-15/16 28-3/8 5/8 16-13/16 20-1/2 14 26 x 32 31 x 35
024 B 33-13/16 30 33 5-1/16 9-11/16 21-15/16 28-3/8 3/4 16-13/16 20-1/2 14 26 x 32 31 x 35
030 B 33-13/16 30 33 5-1/16 9-11/16 21-15/16 28-3/8 3/4 16-1/2 20-3/8 15 26 x 32 31 x 35
036 B 39-13/16 30 33 5-1/16 9-11/16 27-15/16 34-3/8 7/8 16-1/2 20-3/8 16 26 x 32 31 x 35
042 B 33-13/16 30 33 5-1/16 9-11/16 21-15/16 28-3/8 7/8 16-1/2 20-3/8 15 26 x 32 31 x 35
048 A 39-13/16 30 33 5-1/16 9-11/16 27-15/16 34-3/8 7/8 15-13/16 19-7/8 16 26 x 32 31 x 35
060 A 39-13/16 38-5/8 42-1/16 7-1/8 12-1/8 27-15/16 34-3/8 7/8 19-7/8 26 17-1/2 32 x 42 36 x 46
—3—
RECOMMENDED TUBE DIAMETERS
* For tube set over 50 ft, consult Long-Line Application Guideline.
METERING DEVICE
* TXV must be installed when indoor coil is not equipped with a TXV. TXV listed is for any approved
coil combination. All TXVs are bi-flow, hard shutoff.
UNIT
SIZE TUBE LENGTH
(Ft)* LIQUID TUBE
DIAMETER (In.) VAPOR TUBE
DIAMETER (In.)
018
0 to 50 3/8
5/8
024, 030 3/4
036-048 7/8
060 1-1/8
UNIT
SIZE SERIES OUTDOOR
PISTON INDOOR
TXV*
018 B 42 KHATX0901HSO
024 B 49 KHATX1001HSO
030 B 52 KHATX1101HSO
036 B 59 KHATX1201HSO
042 B 63 KHATX1201HSO
048 A 70 KHATX1301HSO
060 A 73 KHATX1401HSO
M
A
N
U
F
A
C
T
U
R
E
R
C
E
R
T
I
F
I
E
D
T
O
A
R
I
A
S
C
O
M
P
L
Y
I
N
G
W
I
T
H
A
R
I
S
T
A
N
D
A
R
D
2
4
0
U
N
I
T
A
R
Y
H
E
A
T
P
U
M
P
E
Q
U
I
P
M
E
N
T
®
CERTIFICATION APPLIES ONLY WHEN THE
COMPLETE SYSTEM IS LISTED WITH ARI.
CERTIFICATION OF MANUFACTURING SITE.
As an ENERGY STAR
SM
Partner. Bryant has
determined that this
product meets the
ENERGY STAR guidelines
for energy efficiency.
—4—
SPECIFICATIONS
See notes on page 5.
UNIT SIZE-SERIES 018-B 024-B 030-B 036-B 042-B
Operating Weight (Lb) 198 198 221 211 231
ELECTRICAL
Unit Volts-Hertz-Phase 208/230-60-1
Operating Voltage Range 187—253
Unit Ampacity for Wire Sizing 16.1 17.5 18.7 21.0 32.0
Min Wire Size (60
°
C/75
°
C Copper) (AWG)* 14/14 14/14 14/14 12/12 8/10
Maximum Length (60
°
C/75
°
C) (Ft)** 46/44 44/42 41/39 60/57 97/59
Max. Branch Circuit Fuse Size (Amps)‡ 25 25 30 30 50
Compressor Rated Load Amps 12.5 13.6 14.2 16.0 24.9
Locked Rotor Amps 47.0 61.0 72.5 88.0 104.0
Fan Motor HP and RPM 1/15 and 820 1/15 and 820 1/8 and 820 1/8 and 820 1/8 and 820
Full Load Amps 1.0 1.0 1.0 1.0 1.0
COMPRESSOR AND REFRIGERANT
Compressor Type Scroll
Refrigerant—Type and Amount (Lb)† R-22 and 5.63 R-22 and 8.88 R-22 and 7.13 R-22 and 10.88
OUTDOOR COIL AND FAN
Coil Face Area (Sq Ft) 15.15
Rated Airflow (CFM) 2500 2400 2900
OPTIONAL EQUIPMENT
Support Feet Kit—4 In. (4) KSASF0101AAA
Snow Stand—18 In. KHASS0206MPK
Time-Delay Relay KAATD0101TDR
Interface Control‡‡‡ KHAIC0101AAA
Service Alarm KHASA0101AAA††
Outdoor Thermostat KHAOT0301FST
Secondary Outdoor Thermostat KHAOT0201SEC
Cycle Protector Standard
Crankcase Heater KAACH1201AAA
Start Assist—PTC KAACS0201PTC
Start Capacitor and Relay KSAHS1501AAA
Sound Hood Standard
TXV Kits (Hard Shutoff) KHATX0901HSO KHATX1001HSO KHATX1101HSO KHATX1201HSO
TXV Kits (RPB) N/A
Low-Pressure Switch Standard
High-Pressure Switch Standard
Evaporator Freeze Thermostat KAAFT0101AAA‡‡
Isolation Relay KHAIR0101AAA‡‡
Liquid Solenoid Valve KHALS0101LLS
Filter Drier—Bi-flow P504-8083S (RCD) P504-8163S (RCD)
Low-Ambient Controller P251-0083(RCD)
MotorMaster® Control 32LT660004***
Ball Bearing Fan Motor HC38GE230 (RCD)
Thermostat, Auto Changeover,
Non-Programmable,
°
F/
°
C,
2-Stage Heat, 1-Stage Cool TSTATBHNHP01-A
Thermostat, Auto Changeover,
7-Day Programmable,
°
F/
°
C,
2-Stage Heat, 1-Stage Cool TSTATBHPHP01-A
Thermostat, Manual Changeover,
Non-Programmable,
°
F,
2-Stage Heat, 1-Stage Cool HH07AT214
Thermostat, Auto Changeover,
Non-Programmable,
°
F/
°
C,
Dual Fuel Thermostat. Must be used with
Outdoor Sensor (TSTATBBSEN01) TSTATBHPDF01-A†††
Outdoor Sensor TSTATBBSEN01
—5—
SPECIFICATIONS Continued
* If wire is applied at ambient greater than 30
°
C (86
°
F), consult Table 310-16 of the NEC (ANSI/NFPA 70). If other than uncoated (non-plated), 60
°
or 75
°
C
(140
°
or 167
°
F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the
NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60
°
C (140
°
F) conductors, per the NEC
(ANSI/NFPA 70) Article 336-30.
† The factory refrigerant charge is for 15 ft of interconnecting tubing. For tubing lengths other than 15 ft, see Long-Line Application Guideline for additional
refrigerant requirements.
‡ Time-delay fuse or HACR breaker.
** Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
†† For indicator light function, thermostat specified must be used and wired according to efficiency service alarm Installation Instructions.
‡‡ Used with low-ambient controller.
*** Fan motor with ball bearings required.
††† High-pressure switch must be added if not supplied with the system.
‡‡‡ Outdoor thermostat required.
N/A—Not Applicable
UNIT SIZE-SERIES 048-A 060-A
Operating Weight (Lb) 265 327
ELECTRICAL
Unit Volts-Hertz-Phase 208/230-60-1
Operating Voltage Range 187—253
Unit Ampacity for Wire Sizing 34.0 45.0
Min Wire Size (60
°
C/75
°
C Copper) (AWG)* 8/10 6/8
Maximum Length (60
°
C/75
°
C) (Ft)** 91/56 116/66
Max. Branch Circuit Fuse Size (Amps)‡ 50 60
Compressor Rated Load Amps 26.5 34.9
Locked Rotor Amps 129.0 169.0
Fan Motor HP and RPM 1/8 and 820 1/5 and 820
Full Load Amps 1.0 1.4
COMPRESSOR AND REFRIGERANT
Compressor Scroll
Refrigerant—Type and Amount (Lb)† R-22 and 11.88 R-22 and 14.88
OUTDOOR COIL AND FAN
Coil Face Area (Sq Ft) 18.18 24.89
Rated Airflow (CFM) 2900 3600
OPTIONAL EQUIPMENT
Support Feet—4 In. (4) KSASF0101AAA
Snow Stand—18 In. KHASS0206MPK KHASS0306MPK
Time-Delay Relay KAATD0101TDR
Interface Control‡‡‡ KHAIC0101AAA
Service Alarm KHASA0101AAA††
Outdoor Thermostat KHAOT0301FST
Secondary Outdoor Thermostat KHAOT0201SEC
Cycle Protector Standard
Crankcase Heater Standard
Start Assist—PTC KAACS0201PTC
Start Capacitor and Relay KSAHS1601AAA
Sound Hood Standard
Bi-flow TXV Kits (Hard Shutoff) KHATX1301HSO KHATX1401HSO
Bi-flow TXV Kits (RPB) N/A
Low-Pressure Switch Standard
High-Pressure Switch Standard
Evaporator Freeze Thermostat KAAFT0101AAA‡‡
Isolation Relay KHAIR0101AAA‡‡
Liquid Solenoid Valve (LSV) KHALS0101LLS
Filter Drier—Bi-flow P504-8163S (RCD)
Low-Ambient Controller P251-0083 (RCD)
MotorMaster® Control 32LT660004***
Ball Bearing Fan Motor HC38GE230 (RCD)
Thermostat, Auto Changeover,
Non-Programmable,
°
F/
°
C,
2-Stage Heat, 1-Stage Cool TSTATBHNHP01-A
Thermostat, Auto Changeover,
7-Day Programmable,
°
F/
°
C,
2-Stage Heat, 1-Stage Cool TSTATBHPHP01-A
Thermostat, Manual Changeover,
Non-Programmable,
°
F,
2-Stage Heat, 1-Stage Cool HH07AT214
Thermostat, Auto Changeover,
Non-Programmable,
°
F/
°
C,
Dual Fuel Thermostat. Must be used with
Outdoor Sensor (TSTATBBSEN01) TSTATBHPDF01-A†††
Outdoor Sensor TSTATBBSEN01
—6—
ACCESSORY USAGE GUIDELINE
* For tubing line sets between 50 and 175 ft, refer to Residential’s Split System Long-Line Application Guidelines.
† For buried line applications, refer to Residential’s Split Systems Buried Line Application Guidelines.
‡ Only when low-pressure switch is used.
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1. Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where low-ambient controller (full modulation feature) or MotorMaster® Control has been added.
2. Compressor Start Assist-Capacitor/Relay Type
Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft. Installations where outdoor design temperature exceeds 105
°
F (40.6
°
C).
Replacement installations with hard shutoff expansion valve on indoor coil. Units installed with low-ambient controller. Units installed with liquid
solenoid valve.
3. Compressor Start Assist-PTC Type
Solid-state electrical device which gives a “soft” boost to the compressor at each start-up.
SUGGESTED USE: Installations with marginal power supply.
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on
restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
When unit will be operated below 55
°
F (12.8
°
C) outdoor air temperature. (Use with low-ambient controller.)
5. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: With low-ambient controller.
6. Filter Drier—Bi-flow
A device for removing contaminants from refrigerant circulating in a heat pump system; 2-direction flow for heat pumps.
SUGGESTED USE: Split-system heat pumps.
7. Interface Control
An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a predeter-
mined economic balance point temperature, then switches to allow furnace operation only below that temperature. Requires outdoor thermostat (Item 12) to
be adjusted for economic balance point temperature.
SUGGESTED USE: For heat pump and gas- or oil-fired furnace combination systems.
8. Isolation Relay
An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.
SUGGESTED USE: All heat pumps where low-ambient controller has been added.
9. Liquid Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor operation.
Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
SUGGESTED USE: In certain long-line applications. (Refer to Long-Line Application Guideline.)
10. Low-Ambient Controller
Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the
outdoor fan motors in order to maintain condensing temperature within normal operating limits (approximately 130 to 110
°
F high, 70 to 50
°
F low). The control
will maintain working head pressure at low-ambient temperatures down to 0
°
F when properly installed.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55
°
F (12.8
°
C).
11. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing tem-
perature during operation in cooling mode only. For outdoor temperatures down to –20
°
F, it maintains condensing temperature at 100
°
F
±
10
°
F.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55
°
F.
All commercial installations.
12. Outdoor Thermostat
An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.
SUGGESTED USE: Heat pump installations with multiple-stage supplemental heaters.
ACCESSORY
REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(Below 55
°
F)
REQUIRED FOR
LONG-LINE
APPLICATIONS*
(Over 50 Ft)
REQUIRED FOR
BURIED LINE
APPLICATIONS†
(Over 3 Ft)
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 Miles)
Crankcase Heater Yes Yes Yes No
Evaporator Freeze Thermostat Yes No No No
Winter Start Control Yes‡ No No No
Accumulator No No Yes No
Compressor Start Assist
Capacitor and Relay Yes Yes Yes No
Low Ambient Controller
or
MotorMaster® Control Yes No No No
Wind Baffle See Low-Ambient
Instructions No No No
Coastal Filter No No No Yes
Support Feet Recommended No No Recommended
Liquid-Line Solenoid Valve
or
Hard Shutoff TXV No
See
Long-Line
Application Guideline Yes No
Ball Bearing Fan Motor Yes No No No
—7—
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued
13. Secondary Outdoor Thermostat
An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second-
stage set point.
SUGGESTED USE: Heat pump installations where 3-stage operation of supplemental heaters is desired.
14. Service Alarm
A current-sensing lockout relay which provides immediate notification that compressor is not operating during a call for heating or cooling. Used with proper
room thermostat, the thermostat light is turned on signifying service is required. This can minimize electrical cost increase due to operation of supplemental
heaters only.
SUGGESTED USE: As a feature to notify owner immediately when the system is not operating most efficiently.
15. Snow Stand
Coated wire rack which supports unit 18 in. above mounting pad to allow for drainage from unit base.
SUGGESTED USE: Heat pump installations in heavy snowfall areas.
Heat pump installations in snowdrift locations.
Heat pump installations in areas of prolonged subfreezing temperatures.
All commercial installations.
16. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces unit sound level by about 2 dBA.
SUGGESTED USE: Unit installed closer than 15 ft to quiet areas—bedrooms, etc.
Unit installed between 2 houses less than 10 ft apart.
17. Support Feet
Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes
corrosion.
SUGGESTED USE: Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
18. Thermostatic Expansion Valve (TXV)—Bi-flow
A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evap-
orator. Kit includes valve, adapter tubes, and external equalizer tube.
SUGGESTED USE: Required for improved system performance. (Refer to ARI Unitary Directory.)
Required for use on all zoning systems.
19. Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.)
—8—
COMBINATION RATINGS*
See notes on page 15.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA) INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment Standard
Rating
Field-Supplied
Accessory‡
TXV
TXV&TDR**
TC COP TC COP
018-B
72
FC4BNF024† 18,000 TDR & TXV 12.20 — — 17,500 3.12 11,600 2.28 7.20/8.00
F(A,B)4AN(F,C)018 17,500 TDR — 11.70 — 17,000 2.84 11,400 2.16 6.80/7.20
F(A,B)4AN(F,C)024 18,000 TDR — 12.20 — 17,500 3.12 11,600 2.28 7.20/8.00
FD3ANA018 17,500 None — — 11.70 17,000 2.76 11,500 2.12 6.80/7.00
FD3ANA024 18,000 None — — 12.70 17,000 2.98 11,300 2.24 7.00/7.50
FF1BNA018 17,500 TDR — 12.50 — 17,000 2.92 11,200 2.22 7.00/7.50
FF1BNA024 18,500 TDR — 12.70 — 17,500 3.08 11,500 2.28 7.20/7.70
FG3AA024 18,000 None — — 12.20 17,000 2.92 11,400 2.20 7.00/7.50
FK4BNF001 19,000 TDR & TXV 14.00 — — 17,000 3.32 11,100 2.44 7.50/8.20
FK4BNF002 19,000 TDR & TXV 14.50 — — 17,000 3.52 11,100 2.54 8.00/8.50
FK4CNF001 19,000 TDR & TXV 14.50 — — 16,500 3.18 10,700 2.38 7.50/8.20
FK4CNF002 19,000 TDR & TXV 15.00 — — 16,600 3.30 10,700 2.42 7.80/8.50
CC5A/CD5A/CD5BA018 17,500 None — — 12.00 17,000 2.76 11,300 2.14 6.80/7.00
CC5A/CD5A/CD5BA024 18,000 None — — 12.50 17,500 2.94 11,400 2.22 7.00/7.50
CC5A/CD5A/CD5BW024 18,000 None — — 12.50 17,500 2.94 11,400 2.22 7.00/7.50
CD3(A,B)A018 17,500 None — — 12.00 17,000 2.76 11,300 2.14 6.80/7.00
CD3(A,B)A024 18,000 None — — 12.50 17,500 2.94 11,400 2.22 7.00/7.50
CE3AA024 18,000 None — — 12.50 17,500 2.98 11,500 2.24 7.00/7.50
CF5AA024 18,000 None — — 12.50 17,500 3.00 11,500 2.24 7.00/7.50
CJ5A/CK5A/CK5BA018 17,000 None — — 12.00 17,000 2.94 11,300 2.22 7.00
CJ5A/CK5A/CK5BA024 17,500 None — — 12.20 17,000 3.06 11,300 2.26 7.20
CJ5A/CK5A/CK5BW024 17,500 None — — 12.20 17,000 3.06 11,300 2.26 7.20
CK3BA024 17,500 None — — 12.20 17,000 3.06 11,300 2.26 7.20
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA024 18,000 TDR — 14.00 — 17,000 2.98 10,900 2.28 7.00/7.70
CC5A/CD5A/CD5BW024 18,000 TDR — 14.00 — 17,000 2.98 10,900 2.28 7.00/7.70
CD3(A,B)A024 18,000 TDR — 14.00 — 17,000 2.98 10,900 2.28 7.00/7.70
CE3AA024 18,000 TDR — 13.50 — 17,000 2.96 11,000 2.26 7.00/7.70
CJ5A/CK5A/CK5BA018 17,500 TDR — 13.50 — 17,000 3.12 10,900 2.34 7.20
CJ5A/CK5A/CK5BA024 17,500 TDR — 14.00 — 17,000 3.24 10,900 2.40 7.50
CK3BA024 17,500 TDR — 14.00 — 17,000 3.24 10,900 2.40 7.50
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA024 18,000 TDR — 14.00 — 17,000 2.98 10,800 2.28 7.00/7.70
CC5A/CD5A/CD5BW024 18,000 TDR — 14.00 — 17,000 2.98 10,800 2.28 7.00/7.70
CD3(A,B)A024 18,000 TDR — 14.00 — 17,000 2.98 10,800 2.28 7.00/7.70
CE3AA024 18,000 TDR — 13.50 — 17,000 2.98 11,000 2.26 7.00/7.70
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA024 18,500 TDR — 14.00 — 17,000 3.08 11,000 2.32 7.20/8.00
CC5A/CD5A/CD5BW024 18,500 TDR — 14.00 — 17,000 3.08 11,000 2.32 7.20/8.00
CD3(A,B)A024 18,500 TDR — 14.00 — 17,000 3.08 11,000 2.32 7.20/8.00
CJ5A/CK5A/CK5BW024 18,000 TDR — 13.80 — 17,000 3.32 11,100 2.42 7.50
CK3BA024 18,000 TDR — 13.80 — 17,000 3.32 11,100 2.42 7.50
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA024 18,500 TDR — 14.00 — 17,000 3.08 11,000 2.32 7.20/8.00
CC5A/CD5A/CD5BW024 18,500 TDR — 14.00 — 17,000 3.08 11,000 2.32 7.20/8.00
CD3(A,B)AS024 18,500 TDR — 14.00 — 17,000 3.08 11,000 2.32 7.20/8.00
CJ5A/CK5A/CK5BW024 18,000 TDR — 14.00 — 17,000 3.32 11,000 2.44 7.50
CK3BA024 18,000 TDR — 14.00 — 17,000 3.32 11,000 2.44 7.50
024-B
72
FC4BNF030† 24,000 TDR & TXV 12.00 — — 25,000 3.40 15,500 2.40 7.80/8.20
F(A,B)4AN(F,C)024 23,600 TDR — 11.70 — 25,000 3.34 15,600 2.36 7.70/8.00
F(A,B)4AN(F,C)030 24,000 TDR — 12.00 — 25,000 3.40 15,500 2.40 7.80/8.20
FC4BNF024 23,600 TDR & TXV 11.70 — — 25,000 3.34 15,600 2.36 7.70/8.00
FC4BNF033 24,600 TDR & TXV 12.00 — — 25,000 3.50 15,700 2.44 8.00/8.50
FD3ANA024 23,200 None — — 11.70 25,000 3.22 15,400 2.30 7.50/8.00
FD3ANA030 24,000 None — — 11.80 25,000 3.38 15,700 2.38 7.70/8.20
FF1(A,B)NA024 23,600 TDR — 11.70 — 25,000 3.36 15,600 2.36 7.70/8.20
FF1(A,B)NA030 24,000 TDR — 11.80 — 25,000 3.42 15,700 2.40 7.80/8.20
FG3AAA024 23,200 None — — 11.50 25,000 3.16 15,500 2.28 7.40/7.80
FK4BNF001 24,800 TDR & TXV 13.00 — — 25,000 3.62 15,200 2.54 8.20/8.50
FK4BNF002 25,000 TDR & TXV 13.20 — — 25,000 3.76 15,200 2.60 8.50/9.00
FK4BNF003 25,000 TDR & TXV 13.50 — — 24,400 3.68 15,000 2.58 8.50/9.00
FK4CNF001 24,400 TDR & TXV 13.00 — — 24,600 3.54 15,000 2.50 8.00/8.50
FK4CNF002 24,600 TDR & TXV 13.20 — — 24,800 3.68 15,100 2.56 8.20/8.80
FK4CNF003 24,800 TDR & TXV 13.50 — — 24,600 3.64 15,000 2.58 8.20/8.70
CC5A/CD5A/CD5BA024 23,400 None — — 11.50 25,000 3.20 15,500 2.28 7.50/8.00
CC5A/CD5A/CD5BA030 23,600 None — — 11.70 25,000 3.22 15,500 2.30 7.50/8.00
CC5A/CD5A/CD5BA036 24,400 None — — 12.00 25,000 3.46 15,600 2.42 8.00/8.20
CC5A/CD5A/CD5BW024 23,400 None — — 11.50 25,000 3.20 15,500 2.28 7.50/8.00
CC5A/CD5A/CD5BW030 23,600 None — — 11.70 25,000 3.22 15,500 2.30 7.50/8.00
CD5A/CD5BW036 24,400 None — — 12.00 25,000 3.46 15,600 2.42 8.00/8.20
CD3(A,B)A024 23,400 None — — 11.50 25,000 3.20 15,500 2.28 7.50/8.00
CD3(A,B)A030 23,600 None — — 11.70 25,000 3.22 15,500 2.30 7.50/8.00
CD3(A,B)A036 24,400 None — — 12.00 25,000 3.46 15,600 2.42 8.00/8.20
CE3AA024 23,400 None — — 11.50 25,000 3.18 15,500 2.30 7.50/8.00
CE3AA030 24,000 None — — 11.80 25,000 3.36 15,600 2.38 7.60/8.00
CF5AA024 23,600 None — — 11.70 25,000 3.26 15,600 2.32 7.50/8.00
—9—
COMBINATION RATINGS* Continued
See notes on page 15.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA) INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment Standard
Rating
Field-Supplied
Accessory‡
TXV
TXV&TDR**
TC COP TC COP
024-B
72
CJ5A/CK5A/CK5BA024 23,200 None — — 11.50 25,000 3.30 15,500 2.34 7.50
CJ5A/CK5A/CK5BA030 23,600 None — — 11.70 24,400 3.28 15,500 2.34 7.50
CJ5A/CK5A/CK5BW024 23,200 None — — 11.50 25,000 3.30 15,500 2.34 7.50
CJ5A/CK5A/CK5BW030 23,600 None — — 11.70 24,400 3.28 15,500 2.34 7.50
CK3BA024 23,200 None — — 11.50 25,000 3.30 15,500 2.34 7.50
CK3BA030 23,600 None — — 11.70 24,400 3.28 15,500 2.34 7.50
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA030 23,800 TDR — 13.00 — 24,000 3.26 14,900 2.38 7.70/8.20
CC5A/CD5A/CD5BW030 23,800 TDR — 13.00 — 24,000 3.26 14,900 2.38 7.70/8.20
CD3(A,B)A030 23,800 TDR — 13.00 — 24,000 3.26 14,900 2.38 7.70/8.20
CE3AA030 24,000 TDR — 13.00 — 24,000 3.42 15,000 2.44 8.00/8.50
CJ5A/CK5A/CK5BA024 23,600 TDR — 12.50 — 24,000 3.46 15,000 2.46 8.00
CJ5A/CK5A/CK5BA030 24,000 TDR — 13.00 — 24,000 3.46 15,000 2.48 8.00
CJ5A/CK5A/CK5BW030 24,000 TDR — 13.00 — 24,000 3.46 15,000 2.48 8.00
CK3BA024 23,600 TDR — 12.50 — 24,000 3.46 15,000 2.46 8.00
CK3BA030 24,000 TDR — 13.00 — 24,000 3.46 15,000 2.48 8.00
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA030 23,800 TDR — 13.00 — 24,000 3.28 14,900 2.38 7.70/8.20
CC5A/CD5A/CD5BW030 23,800 TDR — 13.00 — 24,000 3.28 14,900 2.38 7.70/8.20
CD3(A,B)A030 23,800 TDR — 13.00 — 24,000 3.28 14,900 2.38 7.70/8.20
CE3AA030 24,000 TDR — 13.00 — 24,000 3.42 15,000 2.44 8.00/8.50
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA030 23,800 TDR — 13.00 — 24,000 3.30 14,900 2.40 7.70/8.20
CC5A/CD5A/CD5BW030 23,800 TDR — 13.00 — 24,000 3.30 14,900 2.40 7.70/8.20
CD3(A,B)A030 23,800 TDR — 13.00 — 24,000 3.30 14,900 2.40 7.70/8.20
CE3AA030 24,000 TDR — 13.00 — 24,000 3.46 14,900 2.46 8.00/8.50
COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA030 23,800 TDR — 13.00 — 24,000 3.28 14,900 2.38 7.70/8.20
CC5A/CD5A/CD5BW030 23,800 TDR — 13.00 — 24,000 3.28 14,900 2.38 7.70/8.20
CD3(A,B)A030 23,800 TDR — 13.00 — 24,000 3.28 14,900 2.38 7.70/8.20
CE3AA030 24,000 TDR — 13.00 — 24,000 3.44 15,000 2.46 8.00/8.50
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA030 24,200 TDR — 13.00 — 24,000 3.38 15,100 2.42 7.80/8.40
CC5A/CD5A/CD5BW030 24,200 TDR — 13.00 — 24,000 3.38 15,100 2.42 7.80/8.40
CD3(A,B)A030 24,200 TDR — 13.00 — 24,000 3.38 15,100 2.42 7.80/8.40
CJ5A/CK5A/CK5BW030 24,400 TDR — 12.80 — 24,200 3.52 15,200 2.50 8.00
CK3BA024 23,800 TDR — 12.50 — 24,400 3.52 15,200 2.48 8.00
CK3BA030 24,400 TDR — 12.80 — 24,200 3.52 15,200 2.50 8.00
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA030 24,200 TDR — 12.80 — 24,000 3.38 15,100 2.42 7.80/8.40
CC5A/CD5A/CD5BW030 24,200 TDR — 12.80 — 24,000 3.38 15,100 2.42 7.80/8.40
CD3(A,B)A030 24,200 TDR — 12.80 — 24,000 3.38 15,100 2.42 7.80/8.40
CJ5A/CK5A/CK5BW024 23,800 TDR — 12.50 — 24,400 3.52 15,200 2.48 8.00
CJ5A/CK5A/CK5BW030 24,400 TDR — 12.80 — 24,400 3.52 15,200 2.50 8.00
CK3BA024 23,800 TDR — 12.50 — 24,400 3.52 15,200 2.48 8.00
CK3BA030 24,400 TDR — 12.80 — 24,400 3.52 15,200 2.50 8.00
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA030 24,200 TDR — 13.00 — 24,000 3.40 15,100 2.44 7.80/8.40
CC5A/CD5A/CD5BW030 24,200 TDR — 13.00 — 24,000 3.40 15,100 2.44 7.80/8.40
CD3(A,B)A030 24,200 TDR — 13.00 — 24,000 3.40 15,100 2.44 7.80/8.40
CJ5A/CK5A/CK5BW024 24,000 TDR — 12.80 — 24,200 3.56 15,100 2.52 8.00
CJ5A/CK5A/CK5BW030 24,400 TDR — 13.00 — 24,200 3.56 15,100 2.52 8.00
CK3BA024 24,000 TDR — 12.80 — 24,200 3.56 15,100 2.52 8.00
CK3BA030 24,400 TDR — 13.00 — 24,200 3.56 15,100 2.52 8.00
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA030 24,200 TDR — 13.00 — 24,000 3.40 15,100 2.44 7.80/8.40
CC5A/CD5A/CD5BW030 24,200 TDR — 13.00 — 24,000 3.40 15,100 2.44 7.80/8.40
CD3(A,B)A030 24,200 TDR — 13.00 — 24,000 3.40 15,100 2.44 7.80/8.40
030-B
72
FC4BNF036† 28,400 TDR & TXV 12.10 — — 30,000 3.14 18,500 2.28 7.70/8.00
F(A,B)4ANF030 28,000 TDR — 12.30 — 30,000 3.12 18,300 2.28 7.70/8.00
F(A,B)4ANF036 28,400 TDR — 12.10 — 30,000 3.14 18,500 2.28 7.70/8.00
FC4BNF030 28,000 TDR & TXV 12.30 — — 30,000 3.12 18,300 2.28 7.70/8.00
FC4BNF033 28,800 TDR & TXV 12.50 — — 30,000 3.22 18,400 2.32 8.00/8.20
FD3ANA030 28,000 None — — 12.10 30,000 3.12 18,400 2.26 7.70/8.00
FF1(A,B)NA030 28,200 TDR — 12.20 — 30,000 3.16 18,400 2.28 7.70/8.00
FG3AAA036 28,200 None — — 12.20 30,000 3.12 18,300 2.28 7.70/8.00
FK4BNF001 29,000 TDR & TXV 13.00 — — 30,000 3.28 18,000 2.38 8.00/8.50
FK4BNF002 29,200 TDR & TXV 13.50 — — 30,000 3.42 18,100 2.42 8.20/8.70
FK4BNF003 29,600 TDR & TXV 14.00 — — 29,800 3.42 17,800 2.46 8.20/8.70
FK4BNF004 29,800 TDR & TXV 13.50 — — 30,000 3.56 18,100 2.50 8.50/9.00
FK4CNF001 28,600 TDR & TXV 13.50 — — 29,600 3.28 17,900 2.40 8.00/8.30
FK4CNF002 28,800 TDR & TXV 13.50 — — 29,800 3.38 18,000 2.44 8.20/8.50
FK4CNF003 29,200 TDR & TXV 14.00 — — 29,600 3.38 17,800 2.46 8.20/8.50
—10—
COMBINATION RATINGS* Continued
See notes on page 15.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA) INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment Standard
Rating
Field-Supplied
Accessory‡
TXV TXV&TDR** TC COP TC COP
030-B
74
CC5A/CD5A/CD5BA030 27,800 None — — 12.00 30,000 3.00 18,300 2.22 7.50/7.70
CC5A/CD5A/CD5BW030 27,800 None — — 12.00 30,000 3.00 18,300 2.22 7.50/7.70
CC5A/CD5A/CD5BA036 28,600 None — — 12.50 30,000 3.18 18,400 2.30 7.70/8.00
CD5A/CD5BW036 28,600 None — — 12.50 30,000 3.18 18,400 2.30 7.70/8.00
CD3(A,B)A030 27,800 None — — 12.00 30,000 3.00 18,300 2.22 7.50/7.70
CD3(A,B)A036 28,600 None — — 12.50 30,000 3.18 18,400 2.30 7.70/8.00
CE3AA030 28,000 None — — 12.00 30,000 3.12 18,300 2.28 7.70/8.00
CE3AA036 28,400 None — — 12.50 30,000 3.12 18,300 2.28 7.70/8.00
CF5AA036 28,600 None — — 12.50 30,000 3.16 18,400 2.30 7.70/8.00
CJ5A/CK5A/CK5BA030 27,800 None — — 12.00 29,400 3.06 18,200 2.26 7.50
CJ5A/CK5A/CK5BA036 28,800 None — — 12.50 30,000 3.22 18,500 2.32 7.70
CJ5A/CK5A/CK5BW030 27,800 None — — 12.00 29,400 3.06 18,200 2.26 7.50
CJ5A/CK5A/CK5BW036 28,800 None — — 12.50 30,000 3.22 18,500 2.32 7.70
CK3BA030 27,800 None — — 12.00 29,400 3.06 18,200 2.26 7.50
CK3BA036 28,800 None — — 12.50 30,000 3.22 18,500 2.32 7.70
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA036 28,800 TDR — 13.50 — 29,000 3.28 18,000 2.40 8.00/8.50
CD5A/CD5BW036 28,800 TDR — 13.50 — 29,000 3.28 18,000 2.40 8.00/8.50
CD3(A,B)A036 28,800 TDR — 13.50 — 29,000 3.28 18,000 2.40 8.00/8.50
CE3AA036 28,400 TDR — 13.20 — 29,000 3.20 17,900 2.36 7.80/8.20
CJ5A/CK5A/CK5BA030 28,200 TDR — 13.00 — 29,000 3.18 17,800 2.34 7.70
CJ5A/CK5A/CK5BW030 28,200 TDR — 13.00 — 29,000 3.18 17,800 2.34 7.70
CK3BA030 28,200 TDR — 13.00 — 29,000 3.18 17,800 2.34 7.70
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA036 29,000 TDR — 13.70 — 29,000 3.30 17,800 2.42 8.00/8.50
CD5A/CD5BW036 29,000 TDR — 13.70 — 29,000 3.30 17,800 2.42 8.00/8.50
CD3(A,B)A036 29,000 TDR — 13.70 — 29,000 3.30 17,800 2.42 8.00/8.50
CE3AA036 28,600 TDR — 13.50 — 29,000 3.22 17,800 2.38 8.00/8.20
CJ5A/CK5A/CK5BW030 28,200 TDR — 13.20 — 29,000 3.20 17,700 2.36 7.70
CK3BA030 28,200 TDR — 13.20 — 29,000 3.20 17,700 2.36 7.70
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA036 29,000 TDR — 14.00 — 29,000 3.32 17,800 2.44 8.00/8.50
CD5A/CD5BW036 29,000 TDR — 14.00 — 29,000 3.32 17,800 2.44 8.00/8.50
CD3(A,B)A036 29,000 TDR — 14.00 — 29,000 3.32 17,800 2.44 8.00/8.50
CE3AA036 28,600 TDR — 13.70 — 29,000 3.26 17,800 2.40 8.00/8.50
COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA036 28,800 TDR — 13.50 — 29,000 3.28 18,000 2.40 8.00/8.50
CD5A/CD5BW036 28,800 TDR — 13.50 — 29,000 3.28 18,000 2.40 8.00/8.50
CD3(A,B)A036 28,800 TDR — 13.50 — 29,000 3.28 18,000 2.40 8.00/8.50
CE3AA036 28,400 TDR — 13.20 — 29,000 3.20 17,900 2.36 7.80/8.20
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA036 29,000 TDR — 13.30 — 30,000 3.30 18,200 2.40 8.00/—
CD5A/CD5BW036 29,000 TDR — 13.30 — 30,000 3.30 18,200 2.40 8.00/—
CD3(A,B)A036 29,000 TDR — 13.30 — 30,000 3.30 18,200 2.40 8.00/—
CJ5A/CK5A/CK5BW030 28,400 TDR — 12.70 — 29,400 3.18 18,100 2.34 7.70
CJ5A/CK5A/CK5BW036 29,000 TDR — 13.20 — 30,000 3.34 18,100 2.40 8.00
CK3BA030 28,400 TDR — 12.70 — 29,400 3.18 18,100 2.34 7.70
CK3BA036 29,000 TDR — 13.20 — 30,000 3.34 18,100 2.40 8.00
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA036 29,000 TDR — 13.30 — 30,000 3.30 18,200 2.40 8.00/—
CD5A/CD5BW036 29,000 TDR — 13.30 — 30,000 3.30 18,200 2.40 8.00/—
CD3(A,B)A036 29,000 TDR — 13.30 — 30,000 3.30 18,200 2.40 8.00/—
CJ5A/CK5A/CK5BA036 29,000 TDR — 13.20 — 30,000 3.34 18,100 2.40 8.00
CJ5A/CK5A/CK5BW030 28,400 TDR — 12.70 — 29,400 3.18 18,100 2.34 7.70
CK3BA030 28,400 TDR — 12.70 — 29,400 3.18 18,100 2.34 7.70
CK3BA036 29,000 TDR — 13.20 — 30,000 3.34 18,100 2.40 8.00
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA036 29,000 TDR — 13.50 — 30,000 3.34 18,100 2.42 8.00/—
CD5A/CD5BW036 29,000 TDR — 13.50 — 30,000 3.34 18,100 2.42 8.00/—
CD3(A,B)A036 29,000 TDR — 13.50 — 30,000 3.34 18,100 2.42 8.00/—
CJ5A/CK5A/CK5BW030 28,400 TDR — 13.00 — 29,000 3.20 18,100 2.34 7.70
CJ5A/CK5A/CK5BW036 29,000 TDR — 13.00 — 29,400 3.36 18,000 2.42 8.00
CK3BA030 28,400 TDR — 13.00 — 29,000 3.20 18,100 2.34 7.70
CK3BA036 29,000 TDR — 13.00 — 29,400 3.36 18,000 2.42 8.00
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA036 29,000 TDR — 13.50 — 30,000 3.34 18,100 2.42 8.00/—
CD5A/CD5BW036 29,000 TDR — 13.50 — 30,000 3.34 18,100 2.42 8.00/—
CD3(A,B)A036 29,000 TDR — 13.50 — 30,000 3.34 18,100 2.42 8.00/—
CJ5A/CK5A/CK5BA030 28,600 TDR — 13.20 — 29,000 3.24 17,900 2.38 8.00
CJ5A/CK5A/CK5BA036 29,000 TDR — 13.50 — 29,400 3.40 17,900 2.44 8.00
CJ5A/CK5A/CK5BW030 28,600 TDR — 13.20 — 29,000 3.24 17,900 2.38 8.00
CJ5A/CK5A/CK5BW036 29,000 TDR — 13.50 — 29,400 3.40 17,900 2.44 8.00
CK3BA030 28,600 TDR — 13.20 — 29,000 3.24 17,900 2.38 8.00
CK3BA036 29,000 TDR — 13.50 — 29,400 3.40 17,900 2.44 8.00
—11—
COMBINATION RATINGS* Continued
See notes on page 15.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA) INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment Standard
Rating
Field-Supplied
Accessory‡
TXV TXV&TDR** TC COP TC COP
030-B
74
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BA030 28,600 TDR — 13.00 — 29,000 3.22 18,000 2.36 8.00
CJ5A/CK5A/CK5BW030 28,600 TDR — 13.00 — 29,000 3.22 18,000 2.36 8.00
CJ5A/CK5A/CK5BW036 29,000 TDR — 13.50 — 29,400 3.38 18,000 2.44 8.00
CK3BA030 28,600 TDR — 13.00 — 29,000 3.22 18,000 2.36 8.00
CK3BA036 29,000 TDR — 13.50 — 29,400 3.38 18,000 2.44 8.00
036-B
74
FC4BN(F,B)042† 34,200 TDR & TXV 12.00 — — 36,000 3.34 22,800 2.42 7.80/8.20
F(A,B)4ANF036 33,600 TDR — 11.50 — 36,000 3.24 22,800 2.36 7.60/8.00
F(A,B)4AN(F,B)042 34,200 TDR — 12.00 — 36,000 3.34 22,800 2.42 7.80/8.20
FC4BNF036 33,600 TDR & TXV 11.50 — — 36,000 3.24 22,800 2.36 7.60/8.00
FC4BNF033 34,200 TDR & TXV 11.70 — — 36,000 3.34 22,800 2.42 7.80/8.20
FG3AAA036 33,400 None — — 11.50 36,000 3.24 22,600 2.38 7.60/8.00
FK4BNF001 33,800 TDR & TXV 12.00 — — 36,000 3.34 22,400 2.42 7.80/8.20
FK4BNF002 33,800 TDR & TXV 12.00 — — 36,000 3.44 22,600 2.46 7.80/8.50
FK4BNF003 34,800 TDR & TXV 13.00 — — 35,600 3.50 22,000 2.52 8.00/8.50
FK4BNF004 34,600 TDR & TXV 12.50 — — 36,000 3.64 22,400 2.58 8.20/9.00
FK4CNF001 33,600 TDR & TXV 12.50 — — 35,400 3.32 22,000 2.46 7.80/8.20
FK4CNF002 33,600 TDR & TXV 12.50 — — 35,800 3.44 22,200 2.50 8.00/8.50
FK4CNF003 34,400 TDR & TXV 13.00 — — 35,200 3.46 21,800 2.54 8.00/8.50
CC5A/CD5A/CD5BA036 34,000 None — — 12.00 36,000 3.32 22,600 2.42 7.70/8.20
CD5A/CD5BW036 34,000 None — — 12.00 36,000 3.32 22,600 2.42 7.70/8.20
CC5A/CD5A/CD5BA042 34,000 None — — 12.00 36,000 3.32 22,600 2.42 7.70/8.20
CC5A/CD5A/CD5BW042 33,800 None — — 12.00 36,000 3.28 22,600 2.40 7.70/8.20
CC5A/CD5A/CD5BA043 34,000 None — — 12.00 36,000 3.32 22,600 2.42 7.70/8.20
CC5A/CD5A/CD5BW043 34,000 None — — 12.00 36,000 3.32 22,600 2.40 7.70/8.20
CD3(A,B)A036 34,000 None — — 12.00 36,000 3.32 22,600 2.42 7.70/8.20
CD3(A,B)A042 34,000 None — — 12.00 36,000 3.32 22,600 2.42 7.70/8.20
CE3AA036 33,600 None — — 11.70 36,000 3.26 22,600 2.38 7.60/8.20
CE3AA042 34,400 None — — 12.00 36,000 3.36 22,600 2.44 7.70/8.20
CF5AA036 34,000 None — — 12.00 36,000 3.30 22,600 2.40 7.70/8.20
CJ5A/CK5A/CK5BA036 33,600 None — — 12.00 36,000 3.32 22,400 2.42 7.70
CJ5A/CK5A/CK5BA042 34,200 None — — 12.00 36,000 3.36 22,800 2.44 7.80
CJ5A/CK5A/CK5BN042 33,600 None — — 12.00 36,000 3.32 22,400 2.42 7.70
CJ5A/CK5A/CK5BW036 34,200 None — — 12.00 36,000 3.32 22,400 2.42 7.70
CK3BA036 33,600 None — — 12.00 36,000 3.36 22,800 2.44 7.80
CK3BA042 34,200 None — — 12.00 36,000 3.36 22,800 2.44 7.80
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA042 34,000 TDR — 12.70 — 35,400 3.36 22,000 2.46 7.80/8.20
CC5A/CD5A/CD5BW042 34,000 TDR — 12.70 — 35,400 3.36 22,000 2.46 7.80/8.20
CD3(A,B)A042 34,000 TDR — 12.70 — 35,400 3.36 22,000 2.46 7.80/8.20
CC5A/CD5A/CD5BC048 33,600 TDR — 12.70 — 35,200 3.26 22,000 2.44 7.70/8.00
CE3AA042 34,200 TDR — 12.70 — 35,600 3.40 22,200 2.48 7.80/8.50
CJ5A/CK5A/CK5BA036 34,000 TDR — 12.50 — 35,600 3.40 22,000 2.48 7.80
CK3BA036 34,000 TDR — 12.50 — 35,600 3.40 22,000 2.48 7.80
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA042 34,200 TDR — 13.00 — 35,200 3.40 21,800 2.50 7.80/8.50
CC5A/CD5A/CD5BW042 34,200 TDR — 13.00 — 35,200 3.40 21,800 2.50 7.80/8.50
CD3(A,B)A042 34,200 TDR — 13.00 — 35,200 3.40 21,800 2.50 7.80/8.50
CC5A/CD5A/CD5BC048 33,600 TDR — 13.00 — 35,000 3.30 21,800 2.46 7.80/8.20
CE3AA042 34,400 TDR — 13.00 — 35,400 3.44 22,000 2.52 8.00/8.50
CJ5A/CK5A/CK5BA042 34,600 TDR — 12.50 — 36,000 3.48 22,200 2.52 8.00
CJ5A/CK5A/CK5BW036 34,200 TDR — 12.80 — 35,400 3.44 22,000 2.50 8.00
CK3BA036 34,200 TDR — 12.80 — 35,400 3.44 22,000 2.50 8.00
CK3BA042 34,600 TDR — 12.50 — 36,000 3.48 22,200 2.52 8.00
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA042 34,200 TDR — 13.00 — 35,200 3.42 21,800 2.52 8.00/8.50
CC5A/CD5A/CD5BW042 34,200 TDR — 13.00 — 35,200 3.42 21,800 2.52 8.00/8.50
CD3(A,B)A042 34,200 TDR — 13.00 — 35,200 3.42 21,800 2.52 8.00/8.50
CC5A/CD5A/CD5BC048 33,800 TDR — 13.00 — 35,000 3.34 21,600 2.48 7.80/8.20
CE3AA042 34,400 TDR — 13.00 — 35,200 3.48 21,800 2.54 8.00/8.50
CJ5A/CK5A/CK5BA042 34,800 TDR — 13.00 — 35,800 3.54 22,000 2.56 8.00
CJ5A/CK5A/CK5BW036 34,400 TDR — 13.00 — 35,200 3.48 21,800 2.54 8.00
CK3BA036 34,400 TDR — 13.00 — 35,200 3.48 21,800 2.54 8.00
CK3BA042 34,800 TDR — 13.00 — 35,800 3.54 22,000 2.56 8.00
COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA042 34,200 TDR — 13.00 — 35,200 3.40 21,800 2.50 7.80/8.50
CC5A/CD5A/CD5BW042 34,200 TDR — 13.00 — 35,200 3.40 21,800 2.50 7.80/8.50
CD3(A,B)A042 34,200 TDR — 13.00 — 35,200 3.40 21,800 2.50 7.80/8.50
CC5A/CD5A/CD5BC048 33,600 TDR — 13.00 — 35,000 3.32 21,800 2.46 7.80/8.20
CE3AA042 34,400 TDR — 13.00 — 35,400 3.46 22,000 2.52 8.00/8.50
CJ5A/CK5A/CK5BA042 34,800 TDR — 13.00 — 35,800 3.54 22,000 2.56 8.00
CJ5A/CK5A/CK5BW036 34,400 TDR — 13.00 — 35,400 3.46 21,800 2.54 8.00
CK3BA036 34,400 TDR — 13.00 — 35,400 3.46 21,800 2.54 8.00
CK3BA042 34,800 TDR — 13.00 — 35,800 3.54 22,000 2.56 8.00
—12—
COMBINATION RATINGS* Continued
See notes on page 15.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA) INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment Standard
Rating
Field-Supplied
Accessory‡
TXV TXV&TDR** TC COP TC COP
036-B
74
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA042 34,400 TDR — 12.50 — 36,000 3.40 22,400 2.46 7.80/—
CD3(A,B)A042 34,400 TDR — 12.50 — 36,000 3.40 22,400 2.46 7.80/—
CJ5A/CK5A/CK5BA042 34,400 TDR — 12.50 — 36,000 3.44 22,400 2.48 8.00
CJ5A/CK5A/CK5BW036 34,400 TDR — 12.00 — 36,000 3.40 22,600 2.46 7.80
CK3BA036 34,400 TDR — 12.00 — 36,000 3.40 22,600 2.46 7.80
CK3BA042 34,400 TDR — 12.50 — 36,000 3.44 22,400 2.48 8.00
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA042 34,400 TDR — 12.50 — 36,000 3.40 22,400 2.46 7.80/—
CD3(A,B)A042 34,400 TDR — 12.50 — 36,000 3.40 22,400 2.46 7.80/—
CJ5A/CK5A/CK5BA036 34,400 TDR — 12.00 — 36,000 3.40 22,400 2.46 7.80
CJ5A/CK5A/CK5BN042 34,400 TDR — 12.50 — 36,000 3.44 22,400 2.48 8.00
CK3BA036 34,400 TDR — 12.00 — 36,000 3.40 22,400 2.46 7.80
CK3BA042 34,400 TDR — 12.50 — 36,000 3.44 22,400 2.48 8.00
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA042 34,600 TDR — 12.70 — 35,800 3.44 22,200 2.50 7.80/—
CD3(A,B)A042 34,600 TDR — 12.70 — 35,800 3.44 22,200 2.50 7.80/—
CJ5A/CK5A/CK5BA042 34,600 TDR — 12.50 — 36,000 3.46 22,200 2.50 8.00
CJ5A/CK5A/CK5BW036 34,400 TDR — 12.50 — 36,000 3.42 22,400 2.48 8.00
CK3BA036 34,400 TDR — 12.50 — 36,000 3.42 22,400 2.48 8.00
CK3BA042 34,600 TDR — 12.50 — 36,000 3.46 22,200 2.50 8.00
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA042 34,600 TDR — 12.70 — 35,800 3.44 22,200 2.50 7.80/—
CD3(A,B)A042 34,600 TDR — 12.70 — 35,800 3.44 22,200 2.50 7.80/—
CJ5A/CK5A/CK5BA042 34,600 TDR — 12.80 — 35,800 3.50 22,200 2.54 8.00
CJ5A/CK5A/CK5BW036 34,600 TDR — 12.50 — 36,000 3.48 22,200 2.50 8.00
CK3BA036 34,600 TDR — 12.50 — 36,000 3.48 22,200 2.50 8.00
CK3BA042 34,600 TDR — 12.80 — 35,800 3.50 22,200 2.54 8.00
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BA042 34,600 TDR — 12.80 — 35,800 3.50 22,200 2.54 8.00
CJ5A/CK5A/CK5BW036 34,600 TDR — 12.50 — 35,800 3.48 22,200 2.52 8.00
CK3BA036 34,600 TDR — 12.50 — 35,800 3.48 22,200 2.52 8.00
CK3BA042 34,600 TDR — 12.80 — 35,800 3.50 22,200 2.54 8.00
042-B
74
FK4CNF005† 41,000 TDR & TXV 14.00 — — 41,000 3.72 24,800 2.66 8.20/8.40
F(A,B)4AN(F,B)042 39,000 TDR — 12.00 — 41,000 3.32 25,600 2.40 7.50/7.70
F(A,B)4AN(F,B)048 39,500 TDR — 12.50 — 41,000 3.46 25,600 2.46 7.70/7.90
FC4BNF038 40,500 TDR & TXV 12.50 — — 41,000 3.56 25,800 2.50 7.80/8.00
FC4BN(F,B)042 39,000 TDR & TXV 12.00 — — 41,000 3.32 25,600 2.40 7.50/7.70
FC4BN(F,B)048 39,500 TDR & TXV 12.50 — — 41,000 3.46 25,600 2.46 7.70/7.90
FG3AAA048 39,000 None — — 12.00 41,000 3.38 25,400 2.44 7.50/7.70
FK4BNB005 41,500 TDR & TXV 13.50 — — 41,000 3.74 25,400 2.62 8.20/8.40
FK4BNF003 39,500 TDR & TXV 13.00 — — 41,000 3.44 250,00 2.50 7.80/8.00
FK4CNF003 39,500 TDR & TXV 13.50 — — 40,000 3.42 24,800 2.52 7.80/8.00
CC5A/CD5A/CD5BA042 39,000 None — — 12.00 41,000 3.32 25,400 2.40 7.50/7.70
CC5A/CD5A/CD5BW042 38,500 None — — 12.00 41,000 3.28 25,400 2.38 7.40/7.60
CC5A/CD5A/CD5BA043 39,000 None — — 12.00 41,000 3.32 25,400 2.40 7.50/7.70
CC5A/CD5A/CD5BW043 39,000 None — — 12.00 41,000 3.30 25,400 2.40 7.50/7.70
CD5A/CD5BA048 39,000 None — — 12.50 41,000 3.36 25,400 2.42 7.50/7.70
CC5A/CD5A/CD5BC048 38,500 None — — 12.50 41,000 3.22 25,400 2.38 7.30/7.50
CC5A/CD5A/CD5BW048 39,000 None — — 12.50 41,000 3.36 25,400 2.42 7.50/7.70
CD3(A,B)A042 39,000 None — — 12.00 41,000 3.32 25,400 2.40 7.40/7.60
CD3(A,B)A048 39,000 None — — 12.50 41,000 3.36 25,400 2.42 7.50/7.70
CE3AA042 39,500 None — — 12.00 41,000 3.36 25,400 2.42 7.50/7.70
CE3AA048 39,500 None — — 12.50 41,000 3.40 25,400 2.44 7.50/7.70
CF5AA048 39,500 None — — 12.50 41,000 3.34 25,400 2.42 7.50/7.50
CJ5A/CK5A/CK5BA042 40,000 None — — 12.00 41,000 3.34 25,600 2.42 7.50
CJ5A/CK5A/CK5BA048 40,000 None — — 12.00 41,000 3.40 25,600 2.44 7.50
CJ5A/CK5A/CK5BN042 40,000 None — — 12.00 41,000 3.34 25,600 2.42 7.50
CJ5A/CK5A/CK5BW048 40,000 None — — 12.00 41,000 3.40 25,600 2.44 7.50
CK3BA042 40,000 None — — 12.00 41,000 3.34 25,600 2.42 7.50
CK3BA048 40,000 None — — 12.00 41,000 3.40 25,600 2.44 7.50
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE
CD5A/CD5BA048 39,000 TDR — 13.00 — 40,000 3.28 24,600 2.44 7.50/7.70
CC5A/CD5A/CD5BW048 39,000 TDR — 13.00 — 40,000 3.28 24,600 2.44 7.50/7.70
CD3(A,B)A048 39,000 TDR — 13.00 — 40,000 3.28 24,600 2.44 7.50/7.70
CC5A/CD5A/CD5BC048 38,500 TDR — 13.00 — 40,000 3.24 24,800 2.42 7.30/7.50
CE3AA048 39,500 TDR — 13.00 — 41,000 3.44 25,000 2.50 7.50/7.70
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
CD5A/CD5BA048 39,000 TDR — 13.00 — 40,000 3.28 24,600 2.44 7.50/7.70
CC5A/CD5A/CD5BW048 39,000 TDR — 13.00 — 40,000 3.28 24,600 2.44 7.50/7.70
CD3(A,B)A048 39,000 TDR — 13.00 — 40,000 3.28 24,600 2.44 7.50/7.70
CC5A/CD5A/CD5BC048 38,500 TDR — 13.00 — 40,000 3.26 24,800 2.42 7.30/7.50
CE3AA048 39,500 TDR — 13.50 — 41,000 3.44 25,000 2.52 7.50/7.70
CJ5A/CK5A/CK5BA042 40,000 TDR — 13.00 — 41,000 3.44 25,200 2.48 7.50
CJ5A/CK5A/CK5BA048 40,000 TDR — 13.20 — 41,000 3.50 25,200 2.52 7.70
—13—
COMBINATION RATINGS* Continued
See notes on page 15.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA) INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment Standard
Rating
Field-Supplied
Accessory‡
TXV TXV&TDR** TC COP TC COP
042-B
74
CK3BA042 40,000 TDR — 13.00 — 41,000 3.44 25,200 2.48 7.50
CK3BA048 40,000 TDR — 13.20 — 41,000 3.50 25,200 2.52 7.70
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
CD5A/CD5BA048 39,000 TDR — 13.50 — 40,000 3.32 24,400 2.48 7.50/7.70
CC5A/CD5A/CD5BW048 39,000 TDR — 13.50 — 40,000 3.32 24,400 2.48 7.50/7.70
CD3(A,B)A048 39,000 TDR — 13.50 — 40,000 3.32 24,400 2.48 7.50/7.70
CC5A/CD5A/CD5BC048 39,000 TDR — 13.50 — 40,000 3.30 24,600 2.46 7.50/7.70
CE3AA048 39,500 TDR — 13.50 — 41,000 3.50 24,800 2.54 7.80/8.00
CJ5A/CK5A/CK5BA042 40,000 TDR — 13.50 — 40,000 3.50 25,000 2.52 7.70
CJ5A/CK5A/CK5BW048 40,500 TDR — 13.75 — 41,000 3.56 25,000 2.56 8.00
CK3BA042 40,000 TDR — 13.50 — 40,000 3.50 25,000 2.52 7.70
CK3BA048 41,000 TDR — 13.50 — 41,000 3.56 25,000 2.56 8.00
COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
CD5A/CD5BA048 39,000 TDR — 13.50 — 40,000 3.28 24,600 2.44 7.50/7.70
CC5A/CD5A/CD5BW048 39,000 TDR — 13.50 — 40,000 3.28 24,600 2.44 7.50/7.70
CD3(A,B)A048 39,000 TDR — 13.50 — 40,000 3.28 24,600 2.44 7.50/7.70
CC5A/CD5A/CD5BC048 39,000 TDR — 13.00 — 40,000 3.28 24,600 2.44 7.50/7.70
CE3AA048 39,500 TDR — 13.50 — 41,000 3.46 24,800 2.52 7.50/7.70
CJ5A/CK5A/CK5BA042 40,000 TDR — 13.50 — 41,000 3.48 25,000 2.52 7.70
CJ5A/CK5A/CK5BW048 40,500 TDR — 13.50 — 41,000 3.56 25,000 2.54 8.00
CK3BA042 40,000 TDR — 13.50 — 41,000 3.48 25,000 2.52 7.70
CK3BA048 40,500 TDR — 13.50 — 41,000 3.56 25,000 2.54 8.00
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CD5A/CD5BA048 39,000 TDR — 12.50 — 41,000 3.26 25,400 2.38 7.30/—
CD3(A,B)A048 39,000 TDR — 12.50 — 41,000 3.26 25,400 2.38 7.30/—
CJ5A/CK5A/CK5BW048 40,000 TDR — 12.50 — 42,000 3.44 26,000 2.44 7.50
CK3BA048 40,000 TDR — 12.50 — 42,000 3.44 26,000 2.44 7.50
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CD5A/CD5BA048 39,000 TDR — 12.50 — 41,000 3.26 25,400 2.40 7.30/—
CD3(A,B)A048 39,000 TDR — 12.50 — 41,000 3.26 25,400 2.40 7.30/—
CK3BA048 40,000 TDR — 12.50 — 42,000 3.46 25,800 2.46 7.50
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CD5A/CD5BA048 39,000 TDR — 13.00 — 41,000 3.32 25,200 2.42 7.50/—
CD3(A,B)A048 39,000 TDR — 13.00 — 41,000 3.32 25,200 2.42 7.50/—
CJ5A/CK5A/CK5BA042 40,000 TDR — 12.50 — 42,000 3.40 25,800 2.44 7.50
CJ5A/CK5A/CK5BA048 40,500 TDR — 12.50 — 42,000 3.50 25,800 2.48 7.50
CK3BA042 40,000 TDR — 12.50 — 42,000 3.40 25,800 2.44 7.50
CK3BA048 40,500 TDR — 12.50 — 42,000 3.50 25,800 2.48 7.50
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CD5A/CD5BA048 39,500 TDR — 13.00 — 41,000 3.34 25,000 2.44 7.50/—
CD3(A,B)A048 39,500 TDR — 13.00 — 41,000 3.34 25,000 2.44 7.50/—
CJ5A/CK5A/CK5BA042 40,000 TDR — 12.50 — 41,000 3.46 25,600 2.46 7.50
CJ5A/CK5A/CK5BA048 40,500 TDR — 13.00 — 41,000 3.54 25,600 2.52 7.70
CK3BA042 40,000 TDR — 12.50 — 41,000 3.46 25,600 2.46 7.50
CK3BA048 40,500 TDR — 13.00 — 41,000 3.54 25,600 2.52 7.70
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BA042 40,000 TDR — 13.00 — 41,000 3.46 25,600 2.48 7.50
CJ5A/CK5A/CK5BW048 40,500 TDR — 13.00 — 41,000 3.54 25,600 2.52 7.70
CK3BA042 40,000 TDR — 13.00 — 41,000 3.46 25,600 2.48 7.50
CK3BA048 40,500 TDR — 13.00 — 41,000 3.54 25,600 2.52 7.70
048-A
76
FK4CNF005† 47,500 TDR & TXV 12.50 — — 48,500 3.38 30,200 2.50 7.80/8.00
F(A,B)4AN(F,B)048 45,500 TDR — 11.40 — 49,500 3.16 30,800 2.34 7.40/7.60
F(A,B)4AN(F,B)060 47,000 TDR — 11.50 — 50,000 3.24 31,000 2.36 7.50/7.70
FB4ANB070 47,500 TDR — 12.00 — 50,000 3.40 30,800 2.58 8.00/8.20
FC4BN(F,B)048 45,500 TDR & TXV 11.40 — — 49,500 3.16 30,800 2.34 7.40/7.60
FC4BNB054 48,000 TDR & TXV 12.10 — — 50,000 3.46 30,600 2.52 8.00/8.20
FC4BN(F,B)060 47,000 TDR & TXV 11.50 — — 50,000 3.24 31,000 2.36 7.50/7.70
FC4BNB070 47,500 TDR & TXV 12.00 — — 50,000 3.40 30,800 2.58 8.00/8.20
FG3AAA048 45,000 None — — 11.40 49,000 3.08 30,400 2.32 7.20/7.40
FG3AAA060 46,000 None — — 11.70 49,000 3.12 30,400 2.34 7.30/7.50
FK4BNB006 48,000 TDR & TXV 13.00 — — 49,000 3.56 30,200 2.56 8.10/8.30
FK4CNB006 48,000 TDR & TXV 13.00 — — 49,000 3.54 30,000 2.58 8.10/8.30
CD5A/CD5BA048 45,000 None — — 11.40 48,500 3.04 30,400 2.30 7.20/7.40
CC5A/CD5A/CD5BC048 44,500 None — — 11.30 48,000 2.88 30,200 2.22 6.90/7.10
CC5A/CD5A/CD5BW048 45,000 None — — 11.40 48,500 3.04 30,400 2.30 7.20/7.40
CC5A/CD5A/CD5BA060 45,000 None — — 11.50 48,500 3.00 30,400 2.28 7.10/7.30
CC5A/CD5A/CD5BW060 46,500 None — — 11.80 49,000 3.18 30,600 2.36 7.50/7.70
CD3(A,B)A048 45,000 None — — 11.40 48,500 3.04 30,400 2.30 7.20/7.40
CD3(A,B)A060 45,000 None — — 11.50 48,500 3.00 30,400 2.28 7.10/7.30
CE3AA048 45,500 None — — 11.60 49,000 3.08 30,400 2.32 7.30/7.50
CE3AA060 46,500 None — — 12.00 49,000 3.18 30,600 2.36 7.50/7.70
CF5AA048 45,500 None — — 11.60 48,500 3.02 30,400 2.28 7.10/7.30
CJ5A/CK5A/CK5BA048 45,000 None — — 11.50 48,500 3.10 30,400 2.32 7.20
CJ5A/CK5A/CK5BA060 46,000 None — — 11.50 49,000 3.12 30,400 2.34 7.20
CJ5A/CK5A/CK5BN060 46,000 None — — 11.50 49,000 3.12 30,400 2.34 7.20
—14—
COMBINATION RATINGS* Continued
See notes on page 15.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA) INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment Standard
Rating
Field-Supplied
Accessory‡
TXV TXV&TDR** TC COP TC COP
048-A
76
CJ5A/CK5A/CK5BW048 45,000 None — — 11.50 48,500 3.10 30,400 2.32 7.20
CJ5A/CK5A/CK5BX060 47,000 None — — 12.00 49,000 3.24 30,400 2.40 7.50
CK3BA048 45,000 None — — 11.50 48,500 3.10 30,400 2.32 7.20
CK3BA060 46,000 None — — 11.50 49,000 3.12 30,400 2.34 7.20
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 45,000 TDR — 11.80 — 48,000 2.98 30,000 2.32 7.00/7.20
CD3(A,B)A060 45,000 TDR — 11.80 — 48,000 2.98 30,000 2.32 7.00/7.20
CC5A/CD5A/CD5BW060 46,500 TDR — 12.00 — 48,500 3.20 30,200 2.42 7.50/7.70
CE3AA060 46,500 TDR — 12.00 — 48,500 3.20 30,200 2.40 7.50/7.70
CJ5A/CK5A/CK5BA048 45,500 TDR — 11.80 — 48,500 3.12 30,200 2.36 7.20
CK3BA048 45,500 TDR — 11.80 — 48,500 3.12 30,200 2.36 7.20
CK3BA060 46,000 TDR — 12.00 — 48,500 3.16 30,000 2.38 7.20
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 45,500 TDR — 12.00 — 47,500 3.04 29,800 2.34 7.00/7.20
CD3(A,B)A060 45,500 TDR — 12.00 — 47,500 3.04 29,800 2.34 7.00/7.20
CC5A/CD5A/CD5BW060 46,500 TDR — 12.50 — 48,000 3.26 29,800 2.44 7.50/7.70
CE3AA060 47,000 TDR — 12.50 — 48,000 3.24 30,000 2.44 7.50/7.70
CJ5A/CK5A/CK5BA060 46,500 TDR — 12.50 — 48,000 3.24 29,600 2.44 7.50
CJ5A/CK5A/CK5BW048 46,000 TDR — 12.20 — 48,000 3.20 29,600 2.42 7.50
CJ5A/CK5A/CK5BX060 47,500 TDR — 12.80 — 48,500 3.38 29,800 2.50 7.50
CK3BA048 46,000 TDR — 12.20 — 48,000 3.20 29,600 2.42 7.50
CK3BA060 46,500 TDR — 12.50 — 48,000 3.24 29,600 2.44 7.50
COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 45,500 TDR — 12.00 — 47,500 3.02 29,800 2.34 7.00/7.20
CD3(A,B)A060 45,500 TDR — 12.00 — 47,500 3.02 29,800 2.34 7.00/7.20
CC5A/CD5A/CD5BW060 46,500 TDR — 12.50 — 48,500 3.22 30,000 2.44 7.50/7.70
CE3AA060 46,500 TDR — 12.50 — 48,500 3.22 30,000 2.42 7.50/7.70
CJ5A/CK5A/CK5BA060 46,500 TDR — 12.50 — 48,000 3.22 29,800 2.42 7.50
CJ5A/CK5A/CK5BW048 46,000 TDR — 12.20 — 48,000 3.18 29,800 2.40 7.20
CJ5A/CK5A/CK5BX060 47,500 TDR — 12.50 — 48,500 3.36 29,800 2.48 7.50
CK3BA048 46,000 TDR — 12.20 — 48,000 3.18 29,800 2.40 7.20
CK3BA060 46,500 TDR — 12.50 — 48,000 3.22 29,800 2.42 7.50
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 45,000 TDR — 11.50 — 48,500 2.94 30,400 2.26 7.00/7.20
CD3(A,B)A060 45,000 TDR — 11.50 — 48,500 2.94 30,400 2.26 7.00/7.20
CC5A/CD5A/CD5BW060 46,000 TDR — 11.80 — 49,000 3.16 30,400 2.36 7.30/7.50
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 45,000 TDR — 11.50 — 48,500 2.96 30,400 2.28 7.00/7.20
CD3(A,B)A060 45,000 TDR — 11.50 — 48,500 2.96 30,400 2.28 7.00/7.20
CC5A/CD5A/CD5BW060 46,000 TDR — 11.80 — 49,000 3.16 30,400 2.38 7.30/7.50
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 45,000 TDR — 11.80 — 48,500 2.98 30,200 2.30 7.00/7.20
CD3(A,B)A060 45,000 TDR — 11.80 — 48,500 2.98 30,200 2.30 7.00/7.20
CC5A/CD5A/CD5BW060 46,000 TDR — 12.00 — 49,000 3.18 30,200 2.40 7.50/7.70
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 45,000 TDR — 11.80 — 48,500 2.98 30,000 2.32 7.00/7.20
CD3(A,B)A060 45,000 TDR — 11.80 — 48,500 2.98 30,000 2.32 7.00/7.20
CC5A/CD5A/CD5BW060 46,500 TDR — 12.20 — 49,000 3.20 30,200 2.42 7.50/7.70
CJ5A/CK5A/CK5BA060 47,000 TDR — 11.50 — 49,000 3.20 30,600 2.38 7.50
CJ5A/CK5A/CK5BN060 47,000 TDR — 11.50 — 49,000 3.20 30,600 2.38 7.50
CJ5A/CK5A/CK5BX060 48,000 TDR — 13.00 — 49,000 3.48 30,000 2.56 8.00
CK3BA060 47,000 TDR — 11.50 — 49,000 3.20 30,600 2.38 7.50
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BA060 47,000 TDR — 11.80 — 49,000 3.22 30,600 2.40 7.50
CJ5A/CK5A/CK5BW048 46,000 TDR — 11.50 — 49,000 3.18 30,600 2.36 7.20
CJ5A/CK5A/CK5BX060 47,500 TDR — 12.00 — 49,000 3.34 30,600 2.46 7.50
CK3BA048 46,000 TDR — 11.50 — 49,000 3.18 30,600 2.36 7.20
CK3BA060 47,000 TDR — 11.80 — 49,000 3.22 30,600 2.40 7.50
060-A
76
FK4CNB006† 59,000 TDR & TXV 12.50 — — 61,000 3.32 39,000 2.58 8.30/8.50
F(A,B)4AN(F,B)060 57,500 TDR — 11.50 — 61,000 3.06 39,500 2.40 7.80/8.20
FB4ANB070 58,500 TDR — 12.00 — 61,000 3.22 39,500 2.48 8.00/8.20
FC4BN(F,B)060 57,500 TDR & TXV 11.50 — — 61,000 3.06 39,500 2.40 7.80/8.00
FC4BNB070 58,500 TDR & TXV 12.00 — — 61,000 3.22 39,500 2.48 8.00/8.20
FG3AAA060 56,500 None — — 11.50 61,000 2.94 39,000 2.36 7.50/7.70
FK4BNB006 59,000 TDR & TXV 12.50 — — 61,000 3.30 39,000 2.54 8.30/8.50
CC5A/CD5A/CD5BA060 55,500 None — — 11.50 61,000 2.82 38,500 2.30 7.30/7.50
CC5A/CD5A/CD5BW060 56,500 None — — 11.50 61,000 3.00 39,000 2.40 7.70/7.90
CD3(A,B)A060 55,500 None — — 11.50 61,000 2.82 38,500 2.30 7.30/7.50
CE3AA060 57,500 None — — 12.00 61,000 3.00 39,000 2.40 7.70/7.90
CJ5A/CK5A/CK5BA060 57,500 None — — 11.50 61,000 2.94 39,000 2.38 7.50
CJ5A/CK5A/CK5BX060 58,000 None — — 12.00 61,000 3.08 39,000 2.44 7.80
CK3BA060 57,500 None — — 11.50 61,000 2.94 39,000 2.38 7.50
—15—
COMBINATION RATINGS* Continued
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit.
High-Temp Heating Standard: 70°F (21°C) db indoor entering air temperature and 47°F (8°C) db 43°F (6°C) wb air entering outdoor unit.
Low-Temp Heating Standard: 70°F (21°C) db indoor entering air temperature and 17°F (–9°C) db 15°F (–10°C) wb air entering outdoor unit.
† Outdoor section/indoor section combination tested in accordance with DOE test procedures for heat pumps. Ratings for other combinations are determined
under DOE computer simulation procedures.
‡ Requires hard shutoff TXV; based on computer simulation.
** TDR is on all furnaces, except 394HAD.
UNIT SIZE-
SERIES
AND
SOUND
RATING
(dBA) INDOOR
UNIT
ARI STANDARD RATINGS*
Cooling Heating
TC
Seasonal Efficiency SEER
High-Temp Low-Temp Seasonal
Efficiency
HSPF/HSPF
with LSV
Factory-
Supplied
Enhance-
ment Standard
Rating
Field-Supplied
Accessory‡
TXV TXV&TDR** TC COP TC COP
060-A
76
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 55,500 TDR — 11.50 — 61,000 2.84 38,500 2.32 7.20/7.40
CD3(A,B)A060 55,500 TDR — 11.50 — 61,000 2.84 38,500 2.32 7.20/7.40
CC5A/CD5A/CD5BW060 57,000 TDR — 12.00 — 61,000 3.04 39,000 2.44 7.80/8.00
CE3AA060 57,500 TDR — 12.00 — 61,000 3.02 39,000 2.42 7.80/8.00
CJ5A/CK5A/CK5BA060 57,500 TDR — 12.00 — 61,000 2.94 38,500 2.40 7.50
CJ5A/CK5A/CK5BX060 58,500 TDR — 12.20 — 61,000 3.12 38,500 2.48 7.80
CK3BA060 57,500 TDR — 12.00 — 61,000 2.94 38,500 2.40 7.50
COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 55,000 TDR — 11.50 — 61,000 2.80 39,000 2.30 7.20/7.40
CD3(A,B)A060 55,000 TDR — 11.50 — 61,000 2.80 39,000 2.30 7.20/7.40
CC5A/CD5A/CD5BW060 56,500 TDR — 12.00 — 61,000 3.02 39,000 2.42 7.50/7.70
CE3AA060 57,500 TDR — 12.00 — 61,000 3.00 39,000 2.42 7.50/7.70
CJ5A/CK5A/CK5BA060 57,500 TDR — 11.80 — 61,000 2.96 38,500 2.38 7.50
CJ5A/CK5A/CK5BX060 58,000 TDR — 12.00 — 61,000 3.10 38,500 2.46 7.80
CK3BA060 57,500 TDR — 11.80 — 61,000 2.96 38,500 2.38 7.50
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA060 55,000 TDR — 11.20 — 61,000 2.80 39,500 2.30 7.20/7.40
CD3(A,B)A060 55,000 TDR — 11.20 — 61,000 2.80 39,500 2.30 7.20/7.40
CC5A/CD5A/CD5BW060 56,500 TDR — 11.50 — 61,000 3.00 39,500 2.40 7.50/7.70
SEER — Seasonal Energy Efficiency Ratio LSV — Liquid Solenoid Valve
COP — Coefficient of Performance TDR — Time-Delay Relay
HSPF — Heating Seasonal Performance Factor TXV — Thermostatic Expansion Valve
TC — Total Capacity (Btuh)
—16—
697C BALANCE POINT WORKSHEET
BUILDING HEAT LOSS, 1000 BTU/HR
UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR
Printed in U.S.A. 11-95 838-756
OUTDOOR TEMPERATURE, °F
-10 010 20 30 40 50 60 70 80
2.9
5.9
8.8
11.7
14.7
17.6
20.5
70
60
50
40
30
20
10
KW
BASED ON INDOOR ENT. AIR AT
70°F AND AT RATED CFM
23.4
80
697CN024-A/B
FC4BNF030
697CN030-A/B
FC4BNF036
697CN036-A/B
FC4BN(F,B)042
697CN042-A/B
FK4CNF005
697CN048-A
FK4CNF005
697CN060-A
FK4CNB006
697CN018-B
FC4BNF024
A95490
—17—
DETAILED COOLING CAPACITIES*
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C018-B Outdoor Section With FC4BNF024 Indoor Section
600
72 21.3 10.8 1.30 20.4 10.5 1.46 19.5 10.1 1.63 18.6 9.81 1.8 17.7 9.51 2.05 16.7 9.14 2.27
67 19.4 13.8 1.30 18.7 13.5 1.47 17.8 13.2 1.64 17.0 12.8 1.8 16.2 12.5 2.05 15.2 12.1 2.27
63†† 18.1 13.4 1.31 17.4 13.1 1.47 16.6 12.7 1.64 15.8 12.4 1.8 14.9 12.0 2.04 14.1 11.7 2.27
62 17.9 16.7 1.31 17.2 16.4 1.48 16.4 16.0 1.64 15.7 15.6 1.8 15.0 15.0 2.04 14.2 14.2 2.27
57 17.5 17.5 1.32 16.9 16.9 1.47 16.3 16.3 1.65 15.7 15.7 1.8 15.0 15.0 2.05 14.3 14.3 2.28
650
72 21.5 11.1 1.31 20.6 10.8 1.48 19.7 10.4 1.65 18.8 10.1 1.8 17.8 9.81 2.07 16.8 9.45 2.29
67 19.6 14.3 1.32 18.9 14.0 1.49 18.0 13.7 1.66 17.2 13.3 1.8 16.2 13.0 2.06 15.3 12.6 2.29
63†† 18.3 13.9 1.33 17.5 13.6 1.49 16.8 13.2 1.67 15.9 12.9 1.8 15.1 12.5 2.07 14.2 12.1 2.29
62 18.1 17.4 1.33 17.4 17.0 1.49 16.7 16.6 1.67 16.0 16.0 1.8 15.3 15.3 2.07 14.5 14.5 2.29
57 17.9 17.9 1.33 17.3 17.3 1.49 16.7 16.7 1.67 16.0 16.0 1.8 15.3 15.3 2.07 14.5 14.5 2.29
700
72 21.6 11.4 1.33 20.8 11.1 1.50 19.8 10.7 1.67 18.9 10.4 1.8 17.9 10.1 2.08 16.9 9.74 2.32
67 19.8 14.8 1.34 19.0 14.5 1.51 18.1 14.2 1.68 17.3 13.9 1.8 16.3 13.5 2.08 15.4 13.1 2.31
63†† 18.5 14.4 1.35 17.7 14.0 1.50 16.9 13.7 1.68 16.0 13.3 1.8 15.2 13.0 2.08 14.3 12.6 2.31
62 18.4 18.0 1.35 17.6 17.6 1.51 16.9 16.9 1.68 16.3 16.3 1.8 15.5 15.5 2.08 14.8 14.8 2.31
57 18.2 18.2 1.35 17.6 17.6 1.51 16.9 16.9 1.68 16.3 16.3 1.8 15.5 15.5 2.08 14.8 14.8 2.31
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
FC4BNF 024 1.00 1.00 CK3BA 024 0.97 0.89
F(A,B)4AN(F,C) 018 0.97 1.00 CC5A/CD5A/CD5BW 024 1.00 0.90
024 1.00 1.00 CD3(A,B)A 024 1.00 0.90
FD3ANA 018 0.97 1.02 CE3AA 024 1.00 0.92
024 1.00 0.98 CJ5A/CK5A/CK5BA 018 0.97 0.90
FF1BNA 018 0.97 0.96 024 0.97 0.89
024 1.03 0.99 COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
FG3AA 024 1.00 1.00 CC5A/CD5A/CD5BA 024 1.00 0.89
FK4BNF 001 1.06 0.90 CC5A/CD5A/CD5BW 024 1.00 0.89
002 1.06 0.89 CD3(A,B)A 024 1.00 0.89
FK4CNF 001 1.06 0.88 CE3AA 024 1.00 0.92
002 1.06 0.88 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA 018 0.97 1.00 CC5A/CD5A/CD5BA 024 1.03 0.91
024 1.00 0.99 CC5A/CD5A/CD5BW 024 1.03 0.91
CC5A/CD5A/CD5BW 024 1.00 0.99 CD3(A,B)A 024 1.03 0.91
CD3(A,B)A 018 0.97 1.00 CJ5A/CK5A/CK5BW 024 1.00 0.91
024 1.00 0.99 CK3BA 024 1.00 0.91
CE3AA 024 1.00 0.99 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CF5AA 024 1.00 0.99 CC5A/CD5A/CD5BA 024 1.03 0.91
CJ5A/CK5A/CK5BA 018 0.94 0.97 CC5A/CD5A/CD5BW 024 1.03 0.91
024 0.97 0.97 CD3(A,B)A 024 1.03 0.91
CJ5A/CK5A/CK5BW 024 0.97 0.97 CJ5A/CK5A/CK5BW 024 1.00 0.90
CK3BA 024 0.97 0.97 CK3BA 024 1.00 0.90
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE —— —
CC5A/CD5A/CD5BA 024 1.00 0.90
—18—
DETAILED COOLING CAPACITIES* Continued
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**
Capacity
MBtuh† Total
Sys.
Kw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C024-B Outdoor Section With FC4BNF030 Indoor Section
700
72 28.3 13.9 1.83 27.1 13.5 2.05 25.8 13.0 2.27 24.5 12.5 2.5 23.0 12.0 2.80 21.7 11.6 3.10
67 25.9 17.6 1.81 24.9 17.1 2.02 23.7 16.7 2.25 22.4 16.1 2.5 21.3 15.7 2.79 20.1 15.2 3.09
63†† 24.2 17.1 1.79 23.2 16.7 2.00 22.3 16.3 2.25 21.1 15.8 2.5 19.9 15.2 2.78 18.7 14.7 3.07
62 23.8 21.1 1.78 22.9 20.7 2.00 21.8 20.2 2.24 20.7 19.6 2.4 19.7 19.1 2.77 18.6 18.5 3.07
57 22.9 22.9 1.78 22.1 22.1 2.00 21.3 21.3 2.23 20.4 20.4 2.4 19.5 19.5 2.78 18.6 18.6 3.07
800
72 28.7 14.5 1.87 27.5 14.1 2.08 26.1 13.6 2.31 24.7 13.1 2.5 23.2 12.6 2.83 21.9 12.1 3.13
67 26.5 18.7 1.85 25.3 18.2 2.06 24.0 17.7 2.29 22.7 17.2 2.5 21.5 16.7 2.82 20.3 16.2 3.12
63†† 24.7 18.2 1.83 23.6 17.7 2.04 22.6 17.2 2.28 21.4 16.7 2.5 20.1 16.2 2.81 18.9 15.7 3.10
62 24.4 22.6 1.83 23.3 22.1 2.04 22.2 21.5 2.27 21.2 20.9 2.5 20.2 20.2 2.82 19.1 19.1 3.11
57 23.7 23.7 1.82 22.9 22.9 2.04 22.0 22.0 2.27 21.0 21.0 2.5 20.1 20.1 2.81 19.1 19.1 3.11
900
72 29.0 15.1 1.91 27.8 14.7 2.12 26.4 14.2 2.35 24.9 13.7 2.6 23.5 13.2 2.88 22.0 12.7 3.16
67 26.8 19.7 1.89 25.5 19.2 2.09 24.2 18.7 2.32 23.1 18.2 2.5 21.7 17.7 2.86 20.4 17.2 3.15
63†† 25.0 19.1 1.87 23.9 18.6 2.08 22.8 18.1 2.32 21.6 17.6 2.5 20.4 17.1 2.86 19.0 16.5 3.14
62 24.8 23.9 1.86 23.7 23.3 2.07 22.6 22.5 2.31 21.6 21.6 2.5 20.7 20.7 2.86 19.5 19.5 3.15
57 24.5 24.5 1.87 23.6 23.6 2.07 22.6 22.6 2.31 21.7 21.7 2.5 20.6 20.6 2.85 19.6 19.6 3.15
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
FC4BNF 024 0.98 1.01 COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
030 1.00 1.00 CC5A/CD5A/CD5BA 030 0.99 0.92
033 1.02 1.01 CC5A/CD5A/CD5BW 030 0.99 0.92
F(A,B)4AN(F,C) 024 0.98 1.01 CD3(A,B)A 030 0.99 0.92
030 1.00 1.00 CE3AA 030 1.00 0.93
FD3ANA 024 0.97 0.99 COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
030 1.00 1.02 CC5A/CD5A/CD5BA 030 0.99 0.91
FF1(A,B)NA 024 0.98 1.01 CC5A/CD5A/CD5BW 030 0.99 0.91
030 1.00 1.02 CD3(A,B)A 030 0.99 0.91
FG3AAA 024 0.97 1.01 CE3AA 030 1.00 0.92
FK4BNF 001 1.03 0.94 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
002 1.04 0.94 CC5A/CD5A/CD5BA 030 0.99 0.92
003 1.04 0.92 CC5A/CD5A/CD5BW 030 0.99 0.92
FK4CNF 001 1.02 0.93 CD3(A,B)A 030 0.99 0.92
002 1.02 0.93 CE3AA 030 1.00 0.92
003 1.03 0.91 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA 024 0.98 1.01 CC5A/CD5A/CD5BA 030 1.01 0.94
030 0.98 1.01 CC5A/CD5A/CD5BW 030 1.01 0.94
036 1.02 1.01 CD3(A,B)A 030 1.01 0.94
CC5A/CD5A/CD5BW 024 0.98 1.01 CJ5A/CK5A/CK5BA 024 0.99 0.95
030 0.98 1.01 030 1.02 0.95
CD5A/CD5BW 036 1.02 1.01 CJ5A/CK5A/CK5BW 024 0.99 0.95
CD3(A,B)A 024 0.98 1.01 030 1.02 0.95
030 0.98 1.01 CK3BA 024 0.99 0.95
036 1.02 1.01 030 1.02 0.95
CE3AA 024 0.98 1.01 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
030 1.00 1.01 CC5A/CD5A/CD5BA 030 1.01 0.94
CF5AA 024 0.98 1.01 CC5A/CD5A/CD5BW 030 1.01 0.94
CJ5A/CK5A/CK5BA 024 0.97 0.99 CD3(A,B)A 030 1.01 0.94
030 0.98 0.99 CJ5A/CK5A/CK5BW 024 0.99 0.95
CJ5A/CK5A/CK5BW 024 0.97 0.99 030 1.02 0.95
030 0.98 0.99 CK3BA 024 0.99 0.95
CK3BA 024 0.97 0.99 030 1.02 0.95
030 0.98 0.99 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE CC5A/CD5A/CD5BA 030 1.01 0.94
CC5A/CD5A/CD5BA 030 0.99 0.93 CC5A/CD5A/CD5BW 030 1.01 0.94
CC5A/CD5A/CD5BW 030 0.99 0.93 CD3(A,B)A 030 1.01 0.94
CD3(A,B)A 030 0.99 0.93 CJ5A/CK5A/CK5BW 024 1.00 0.94
CE3AA 030 1.00 0.93 030 1.02 0.94
CJ5A/CK5A/CK5BA 024 0.98 0.93 CK3BA 024 1.00 0.94
030 1.00 0.93 030 1.02 0.94
CJ5A/CK5A/CK5BW 030 1.00 0.93 COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CK3BA 024 0.98 0.93 CC5A/CD5A/CD5BA 030 1.01 0.94
030 1.00 0.93 CC5A/CD5A/CD5BW 030 1.01 0.94
— — — CD3(A,B)A 030 1.01 0.94
—19—
DETAILED COOLING CAPACITIES* Continued
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C030-B Outdoor Section With FC4BNF036 Indoor Section
850
72 32.1 16.0 2.43 30.7 15.5 2.65 29.3 14.9 2.89 27.8 14.4 3.16
67 29.3 20.3 2.41 28.0 19.8 2.62 26.8 19.3 2.86 25.5 18.8 3.13
63†† 27.3 19.7 2.39 26.1 19.2 2.60 24.8 18.7 2.84 23.4 18.1 3.10
62 26.8 24.5 2.38 25.8 24.0 2.60 24.5 23.4 2.84 23.2 22.7 3.10
57 26.0 26.0 2.38 25.1 25.1 2.59 24.2 24.2 2.83 23.1 23.1 3.10
950
72 32.4 16.5 2.47 31.0 16.0 2.69 29.6 15.5 2.94 28.0 15.0 3.20
67 29.8 21.4 2.45 28.4 20.8 2.67 27.1 20.3 2.91 25.6 19.7 3.17
63†† 27.7 20.7 2.43 26.4 20.2 2.65 25.2 19.7 2.89 23.8 19.1 3.15
62 27.3 25.9 2.43 26.2 25.3 2.64 25.1 24.7 2.89 23.8 23.8 3.15
57 26.8 26.8 2.43 25.9 25.9 2.64 24.9 24.9 2.89 23.8 23.8 3.15
1050
72 32.9 17.2 2.52 31.5 16.7 2.74 30.0 16.1 2.98 28.1 15.5 3.25
67 30.0 22.4 2.49 28.7 21.8 2.71 27.4 21.3 2.95 25.9 20.7 3.22
63†† 27.9 21.6 2.48 26.6 21.1 2.69 25.4 20.6 2.93 24.1 20.0 3.20
62 27.8 27.2 2.48 26.6 26.4 2.69 25.5 25.5 2.93 24.4 24.4 3.20
57 27.5 27.5 2.47 26.6 26.6 2.69 25.6 25.6 2.94 24.4 24.4 3.20
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
FC4BNF 030 0.99 0.98 CD5A/CD5BW 036 1.02 0.91
033 1.01 0.98 CD3(A,B)A 036 1.02 0.91
036 1.00 1.00 CE3AA 036 1.01 0.91
F(A,B)4ANF 030 0.99 0.98 CJ5A/CK5A/CK5BW 030 0.99 0.92
036 1.00 1.00 CK3BA 030 0.99 0.92
FD3ANA 030 0.99 0.99 COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
FF1(A,B)NA 030 0.99 0.99 CC5A/CD5A/CD5BA 036 1.02 0.90
FG3AAA 036 0.99 0.98 CD5A/CD5BW 036 1.02 0.90
FK4BNF 001 1.02 0.94 CD3(A,B)A 036 1.02 0.90
002 1.03 0.94 CE3AA 036 1.01 0.90
003 1.04 0.92 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
004 1.05 0.93 CC5A/CD5A/CD5BA 036 1.01 0.92
FK4CNF 001 1.01 0.92 CD5A/CD5BW 036 1.01 0.92
002 1.01 0.92 CD3(A,B)A 036 1.01 0.92
003 1.03 0.90 CE3AA 036 1.00 0.93
CC5A/CD5A/CD5BA 030 0.98 0.98 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
036 1.01 0.99 CC5A/CD5A/CD5BA 036 1.02 0.95
CC5A/CD5A/CD5BW 030 0.98 0.98 CD5A/CD5BW 036 1.02 0.95
CD5A/CD5BW 036 1.01 0.99 CD3(A,B)A 036 1.02 0.95
CD3(A,B)A 030 0.98 0.98 CJ5A/CK5A/CK5BW 030 1.00 0.96
036 1.01 0.99 036 1.02 0.95
CE3AA 030 0.99 0.98 CK3BA 030 1.00 0.96
036 1.00 0.98 036 1.02 0.95
CF5AA 036 1.01 0.99 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BA 030 0.98 0.97 CC5A/CD5A/CD5BA 036 1.02 0.95
036 1.01 0.99 CD5A/CD5BW 036 1.02 0.95
CJ5A/CK5A/CK5BW 030 0.98 0.97 CD3(A,B)A 036 1.02 0.95
036 1.01 0.99 CJ5A/CK5A/CK5BA 036 1.02 0.95
CK3BA 030 0.98 0.97 CJ5A/CK5A/CK5BW 030 1.00 0.96
036 1.01 0.99 CK3BA 030 1.00 0.96
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE 036 1.02 0.95
CC5A/CD5A/CD5BA 036 1.01 0.92 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CD5A/CD5BW 036 1.01 0.92 CC5A/CD5A/CD5BA 036 1.02 0.94
CD3(A,B)A 036 1.01 0.92 CD5A/CD5BW 036 1.02 0.94
CE3AA 036 1.00 0.93 CD3(A,B)A 036 1.02 0.94
CJ5A/CK5A/CK5BA 030 0.99 0.93 CJ5A/CK5A/CK5BW 030 1.00 0.95
CJ5A/CK5A/CK5BW 030 0.99 0.93 036 1.02 0.94
CK3BA 030 0.99 0.93 CK3BA 030 1.00 0.95
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE 036 1.02 0.94
CC5A/CD5A/CD5BA 036 1.02 0.91 — — —
—20—
DETAILED COOLING CAPACITIES* Continued
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C030-B Outdoor Section With FC4BNF036 Indoor Section Continued
850
72 32.1 16.0 2.43 30.7 15.5 2.65 29.3 14.9 2.89 27.8 14.4 3.16
67 29.3 20.3 2.41 28.0 19.8 2.62 26.8 19.3 2.86 25.5 18.8 3.13
63†† 27.3 19.7 2.39 26.1 19.2 2.60 24.8 18.7 2.84 23.4 18.1 3.10
62 26.8 24.5 2.38 25.8 24.0 2.60 24.5 23.4 2.84 23.2 22.7 3.10
57 26.0 26.0 2.38 25.1 25.1 2.59 24.2 24.2 2.83 23.1 23.1 3.10
950
72 32.4 16.5 2.47 31.0 16.0 2.69 29.6 15.5 2.94 28.0 15.0 3.20
67 29.8 21.4 2.45 28.4 20.8 2.67 27.1 20.3 2.91 25.6 19.7 3.17
63†† 27.7 20.7 2.43 26.4 20.2 2.65 25.2 19.7 2.89 23.8 19.1 3.15
62 27.3 25.9 2.43 26.2 25.3 2.64 25.1 24.7 2.89 23.8 23.8 3.15
57 26.8 26.8 2.43 25.9 25.9 2.64 24.9 24.9 2.89 23.8 23.8 3.15
1050
72 32.9 17.2 2.52 31.5 16.7 2.74 30.0 16.1 2.98 28.1 15.5 3.25
67 30.0 22.4 2.49 28.7 21.8 2.71 27.4 21.3 2.95 25.9 20.7 3.22
63†† 27.9 21.6 2.48 26.6 21.1 2.69 25.4 20.6 2.93 24.1 20.0 3.20
62 27.8 27.2 2.48 26.6 26.4 2.69 25.5 25.5 2.93 24.4 24.4 3.20
57 27.5 27.5 2.47 26.6 26.6 2.69 25.6 25.6 2.94 24.4 24.4 3.20
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
COILS + 355MAV060100 VARIABLE-SPEED FURNACE CK3BA 030 1.01 0.93
CC5A/CD5A/CD5BA 036 1.02 0.94 036 1.02 0.93
CD5A/CD5BW 036 1.02 0.94 COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CD3(A,B)A 036 1.02 0.94 CJ5A/CK5A/CK5BW 036 1.02 0.93
CJ5A/CK5A/CK5BW 030 1.01 0.93 CK3BA 030 1.01 0.94
036 1.02 0.93 036 1.02 0.93
—21—
DETAILED COOLING CAPACITIES* Continued
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh† Total
System
KW**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C036-B Outdoor Section With FC4BN(F,B)042 Indoor Section
1100
72 38.6 19.8 3.05 37.0 19.2 3.35 35.2 18.6 3.67 33.2 17.9 4.02
67 35.6 25.7 3.02 34.0 25.0 3.31 32.3 24.3 3.63 30.4 23.6 3.98
63†† 33.2 25.0 3.00 31.7 24.3 3.29 30.1 23.6 3.60 28.4 22.9 3.96
62 32.8 31.2 3.00 31.4 30.4 3.28 29.9 29.6 3.60 28.5 28.5 3.96
57 32.2 32.2 2.98 31.1 31.1 3.28 29.8 29.8 3.60 28.4 28.4 3.95
1200
72 38.9 20.4 3.09 37.3 19.8 3.39 35.4 19.2 3.71 33.3 18.5 4.06
67 35.9 26.7 3.07 34.2 26.1 3.35 32.4 25.4 3.67 30.8 24.7 4.03
63†† 33.5 25.9 3.04 31.9 25.2 3.33 30.4 24.6 3.66 28.7 23.8 4.00
62 33.2 32.5 3.04 31.8 31.6 3.33 30.4 30.4 3.64 29.0 29.0 4.00
57 32.9 32.9 3.03 31.8 31.8 3.33 30.4 30.4 3.64 28.9 28.9 3.99
1300
72 39.1 21.0 3.13 37.5 20.4 3.43 35.5 19.7 3.75 33.5 19.0 4.10
67 36.1 27.7 3.10 34.4 27.1 3.39 32.8 26.4 3.73 30.9 25.7 4.07
63†† 33.7 26.9 3.08 32.1 26.2 3.37 30.6 25.5 3.69 28.8 24.7 4.04
62 33.7 33.5 3.08 32.3 32.3 3.37 30.9 30.9 3.69 29.5 29.5 4.05
57 33.7 33.7 3.08 32.3 32.3 3.37 30.9 30.9 3.69 29.5 29.5 4.05
Multipliers for Determining the Performance With Other Indoor Section
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
FC4BN(F,B) 042 1.00 1.00 CD3(A,B)A 042 1.00 0.92
FC4BNF 033 1.00 1.00 CC5A/CD5A/CD5BC 048 0.98 0.91
036 0.98 1.01 CE3AA 042 1.01 0.92
F(A,B)4ANF 036 0.98 1.01 CJ5A/CK5A/CK5BA 042 1.01 0.96
F(A,B)4AN(F,B) 042 1.00 1.00 CJ5A/CK5A/CK5BW 036 1.00 0.93
FG3AAA 036 0.98 0.99 CK3BA 036 1.00 0.93
FK4BNF 001 0.99 0.97 042 1.01 0.96
002 0.99 0.98 COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
003 1.02 0.94 CC5A/CD5A/CD5BA 042 1.00 0.91
004 1.01 0.96 CC5A/CD5A/CD5BW 042 1.00 0.91
FK4CNF 001 0.98 0.94 CD3(A,B)A 042 1.00 0.91
002 0.98 0.94 CC5A/CD5A/CD5BC 048 0.99 0.90
003 1.01 0.91 CE3AA 042 1.01 0.91
CC5A/CD5A/CD5BA 036 0.99 0.99 CJ5A/CK5A/CK5BA 042 1.02 0.94
042 0.99 0.99 CJ5A/CK5A/CK5BW 036 1.01 0.91
043 0.99 0.99 CK3BA 036 1.01 0.91
CC5A/CD5A/CD5BW 042 0.99 0.99 042 1.02 0.94
043 0.99 0.99 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
CD5A/CD5BW 036 0.99 0.99 CC5A/CD5A/CD5BA 042 1.00 0.92
CD3(A,B)A 036 0.99 0.99 CC5A/CD5A/CD5BW 042 1.00 0.92
042 0.99 0.99 CD3(A,B)A 042 1.00 0.92
CE3AA 036 0.98 0.99 CC5A/CD5A/CD5BC 048 0.98 0.91
042 1.01 0.99 CE3AA 042 1.01 0.92
CF5AA 036 0.99 0.99 CJ5A/CK5A/CK5BA 042 1.02 0.94
CJ5A/CK5A/CK5BA 036 0.98 0.97 CJ5A/CK5A/CK5BW 036 1.01 0.92
042 1.00 1.00 CK3BA 036 1.01 0.92
CJ5A/CK5A/CK5BN 042 1.00 1.00 042 1.02 0.94
CJ5A/CK5A/CK5BW 036 0.98 0.97 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CK3BA 036 0.98 0.97 CC5A/CD5A/CD5BA 042 1.01 0.97
042 1.00 1.00 CD3(A,B)A 042 1.01 0.97
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE CJ5A/CK5A/CK5BA 042 1.01 0.97
CC5A/CD5A/CD5BA 042 0.99 0.93 CJ5A/CK5A/CK5BW 036 1.01 0.98
CC5A/CD5A/CD5BW 042 0.99 0.93 CK3BA 036 1.01 0.98
CD3(A,B)A 042 0.99 0.93 042 1.01 0.97
CC5A/CD5A/CD5BC 048 0.98 0.93 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CE3AA 042 1.00 0.94 CC5A/CD5A/CD5BA 042 1.01 0.97
CJ5A/CK5A/CK5BA 036 0.99 0.94 CD3(A,B)A 042 1.01 0.97
CK3BA 036 0.99 0.94 CJ5A/CK5A/CK5BA 036 1.01 0.97
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE CJ5A/CK5A/CK5BN 042 1.01 0.97
CC5A/CD5A/CD5BA 042 1.00 0.92 CK3BA 036 1.01 0.97
CC5A/CD5A/CD5BW 042 1.00 0.92 042 1.01 0.97
—22—
DETAILED COOLING CAPACITIES* Continued
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C036-B Outdoor Section With FC4BN(F,B)042 Indoor Section Continued
1100
72 38.6 19.8 3.05 37.0 19.2 3.35 35.2 18.6 3.67 33.2 17.9 4.02
67 35.6 25.7 3.02 34.0 25.0 3.31 32.3 24.3 3.63 30.4 23.6 3.98
63†† 33.2 25.0 3.00 31.7 24.3 3.29 30.1 23.6 3.60 28.4 22.9 3.96
62 32.8 31.2 3.00 31.4 30.4 3.28 29.9 29.6 3.60 28.5 28.5 3.96
57 32.2 32.2 2.98 31.1 31.1 3.28 29.8 29.8 3.60 28.4 28.4 3.95
1200
72 38.9 20.4 3.09 37.3 19.8 3.39 35.4 19.2 3.71 33.3 18.5 4.06
67 35.9 26.7 3.07 34.2 26.1 3.35 32.4 25.4 3.67 30.8 24.7 4.03
63†† 33.5 25.9 3.04 31.9 25.2 3.33 30.4 24.6 3.66 28.7 23.8 4.00
62 33.2 32.5 3.04 31.8 31.6 3.33 30.4 30.4 3.64 29.0 29.0 4.00
57 32.9 32.9 3.03 31.8 31.8 3.33 30.4 30.4 3.64 28.9 28.9 3.99
1300
72 39.1 21.0 3.13 37.5 20.4 3.43 35.5 19.7 3.75 33.5 19.0 4.10
67 36.1 27.7 3.10 34.4 27.1 3.39 32.8 26.4 3.73 30.9 25.7 4.07
63†† 33.7 26.9 3.08 32.1 26.2 3.37 30.6 25.5 3.69 28.8 24.7 4.04
62 33.7 33.5 3.08 32.3 32.3 3.37 30.9 30.9 3.69 29.5 29.5 4.05
57 33.7 33.7 3.08 32.3 32.3 3.37 30.9 30.9 3.69 29.5 29.5 4.05
Multipliers for Determining the Performance With Other Indoor Section
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
COILS + 355MAV042080 VARIABLE-SPEED FURNACE CJ5A/CK5A/CK5BA 042 1.01 0.94
CC5A/CD5A/CD5BA 042 1.01 0.95 CJ5A/CK5A/CK5BW 036 1.01 0.95
CD3(A,B)A 042 1.01 0.95 CK3BA 036 1.01 0.95
CJ5A/CK5A/CK5BA 042 1.01 0.96 042 1.01 0.94
CJ5AS/CK5A/CK5BW 036 1.01 0.97 COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CK3BA 036 1.01 0.97 CJ5A/CK5A/CK5BA 042 1.01 0.94
042 1.01 0.96 CJ5A/CK5A/CK5BW 036 1.01 0.95
COILS + 355MAV060100 VARIABLE-SPEED FURNACE CK3BA 036 1.01 0.95
CC5A/CD5A/CD5BA 042 1.01 0.95 042 1.01 0.94
CD3(A,B)A 042 1.01 0.95 — — —
—23—
DETAILED COOLING CAPACITIES* Continued
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C042-B Outdoor Section With FK4CNF005 Indoor Section
1103
72 46.2 23.3 3.06 44.1 22.5 3.40 42.1 21.8 3.7 40.2 21.1 4.19
67 42.5 29.4 3.03 40.5 28.6 3.36 38.7 27.9 3.7 37.0 27.2 4.14
63†† 39.7 28.7 3.00 38.1 28.0 3.34 36.5 27.3 3.7 34.4 26.4 4.10
62 39.3 35.5 3.00 37.5 34.7 3.33 35.7 33.8 3.6 33.9 32.9 4.09
57 37.8 37.8 2.99 36.6 36.6 3.32 35.3 35.3 3.6 33.7 33.7 4.09
1225
72 46.7 24.1 3.09 44.5 23.4 3.43 42.6 22.7 3.8 40.6 22.0 4.22
67 43.0 30.9 3.06 41.0 30.1 3.39 39.2 29.4 3.7 37.5 28.7 4.17
63†† 40.3 30.1 3.03 38.6 29.4 3.37 37.0 28.7 3.7 34.8 27.7 4.13
62 40.0 37.6 3.03 38.2 36.7 3.36 36.4 35.7 3.7 34.6 34.6 4.13
57 39.0 39.0 3.02 37.7 37.7 3.36 36.4 36.4 3.7 34.6 34.6 4.13
1409
72 47.4 25.4 3.13 45.1 24.7 3.47 43.1 24.0 3.8 41.1 23.3 4.26
67 43.7 33.1 3.10 41.9 32.4 3.44 39.8 31.6 3.8 37.9 30.8 4.21
63†† 40.9 32.2 3.07 39.3 31.4 3.41 37.5 30.7 3.7 35.3 29.7 4.17
62 40.9 40.3 3.08 39.1 39.1 3.41 37.5 37.5 3.7 35.8 35.8 4.18
57 40.6 40.6 3.07 39.2 39.2 3.41 37.7 37.7 3.7 35.8 35.8 4.18
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
F(A,B)4AN(F,B,C) 042 0.95 1.07 CJ5A/CK5A/CK5BA 042 0.96 1.00
048 0.96 1.08 048 0.96 1.00
FC4BN(F,B) 042 0.95 1.07 CK3BA 042 0.96 1.00
048 0.96 1.08 048 0.96 1.00
FC4BNF 038 0.99 1.09 COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
FG3AAA 048 0.95 1.06 CC5A/CD5A/CD5BC 048 0.95 1.00
FK4BNB 003 0.96 1.03 CC5A/CD5A/CD5BW 048 0.95 0.99
FK4BNF 005 1.01 1.05 CD3(A,B)A 048 0.95 0.99
FK4CNF 003 0.96 1.00 CD5A/CD5BA 048 0.95 0.99
005 1.00 1.00 CE3AA 048 0.96 1.00
CC5A/CD5A/CD5BA 042 0.95 1.06 CJ5A/CK5A/CK5BA 042 0.96 0.98
043 0.95 1.06 CJ5A/CK5A/CK5BW 048 0.98 0.98
CC5A/CD5A/CD5BC 048 0.94 1.06 CK3BA 042 0.96 0.98
CC5A/CD5A/CD5BW 042 0.94 1.06 048 0.99 0.98
043 0.95 1.06 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
048 0.95 1.06 CC5A/CD5A/CD5BC 048 0.95 1.01
CD3(A,B)A 042 0.95 1.06 CC5A/CD5A/CD5BW 048 0.95 1.00
048 0.95 1.06 CD3(A,B)A 048 0.95 1.00
CD5A/CD5BA 048 0.95 1.06 CD5A/CD5BA 048 0.95 1.00
CE3AA 042 0.96 1.07 CE3AA 048 0.96 1.01
048 0.96 1.07 CJ5A/CK5A/CK5BA 042 0.96 0.98
CF5AA 048 0.96 1.07 CJ5A/CK5A/CK5BW 048 0.98 0.98
CJ5A/CK5A/CK5BA 042 0.96 1.04 CK3BA 042 0.96 0.98
048 0.96 1.04 048 0.98 0.98
CJ5A/CK5A/CK5BN 042 0.96 1.04 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BW 048 0.96 1.04 CD3(A,B)A 048 0.95 1.06
CK3BA 042 0.96 1.04 CD5A/CD5BA 048 0.95 1.06
048 0.96 1.04 CJ5A/CK5A/CK5BW 048 0.96 1.06
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE CK3BA 048 0.96 1.06
CC5A/CD5A/CD5BC 048 0.94 1.02 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BW 048 0.95 1.01 CD3(A,B)A 048 0.95 1.06
CD3(A,B)A 048 0.95 1.01 CD5A/CD5BA 048 0.95 1.06
CD5A/CD5BA 048 0.95 1.01 CK3BA 048 0.96 1.05
CE3AA 048 0.96 1.02 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE CD3(A,B)A 048 0.95 1.04
CC5A/CD5A/CD5BC 048 0.94 1.01 CD5A/CD5BA 048 0.95 1.04
CC5A/CD5A/CD5BW 048 0.95 1.00 CJ5A/CK5A/CK5BA 042 0.96 1.05
CD3(A,B)A 048 0.95 1.00 048 0.98 1.04
CD5A/CD5BA 048 0.95 1.00 CK3BA 042 0.96 1.05
CE3AA 048 0.96 1.02 048 0.98 1.04
—24—
DETAILED COOLING CAPACITIES* Continued
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C042-B Outdoor Section With FK4CNF005 Indoor Section Continued
1103
72 46.2 23.3 3.06 44.1 22.5 3.40 42.1 21.8 3.7 40.2 21.1 4.19
67 42.5 29.4 3.03 40.5 28.6 3.36 38.7 27.9 3.7 37.0 27.2 4.14
63†† 39.7 28.7 3.00 38.1 28.0 3.34 36.5 27.3 3.7 34.4 26.4 4.10
62 39.3 35.5 3.00 37.5 34.7 3.33 35.7 33.8 3.6 33.9 32.9 4.09
57 37.8 37.8 2.99 36.6 36.6 3.32 35.3 35.3 3.6 33.7 33.7 4.09
1225
72 46.7 24.1 3.09 44.5 23.4 3.43 42.6 22.7 3.8 40.6 22.0 4.22
67 43.0 30.9 3.06 41.0 30.1 3.39 39.2 29.4 3.7 37.5 28.7 4.17
63†† 40.3 30.1 3.03 38.6 29.4 3.37 37.0 28.7 3.7 34.8 27.7 4.13
62 40.0 37.6 3.03 38.2 36.7 3.36 36.4 35.7 3.7 34.6 34.6 4.13
57 39.0 39.0 3.02 37.7 37.7 3.36 36.4 36.4 3.7 34.6 34.6 4.13
1409
72 47.4 25.4 3.13 45.1 24.7 3.47 43.1 24.0 3.8 41.1 23.3 4.26
67 43.7 33.1 3.10 41.9 32.4 3.44 39.8 31.6 3.8 37.9 30.8 4.21
63†† 40.9 32.2 3.07 39.3 31.4 3.41 37.5 30.7 3.7 35.3 29.7 4.17
62 40.9 40.3 3.08 39.1 39.1 3.41 37.5 37.5 3.7 35.8 35.8 4.18
57 40.6 40.6 3.07 39.2 39.2 3.41 37.7 37.7 3.7 35.8 35.8 4.18
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
COILS + 355MAV060100 VARIABLE-SPEED FURNACE COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CD3(A,B)A 048 0.96 1.03 CJ5A/CK5A/CK5BA 042 0.96 1.03
CD5A/CD5BA 048 0.96 1.03 CJ5A/CK5A/CK5BW 048 0.98 1.02
CJ5A/CK5A/CK5BA 042 0.96 1.03 CK3BA 042 0.96 1.03
048 0.98 1.02 048 0.98 1.02
CK3BA 042 0.96 1.03 — — —
048 0.98 1.02
—25—
DETAILED COOLING CAPACITIES* Continued
See notes on page 26.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C048-A Outdoor Section With FK4CNF005 Indoor Section
1260
72 53.2 26.3 4.00 51.1 25.5 4.51 48.6 24.6 5.0 46.0 23.6 5.65
67 48.9 32.9 3.96 46.7 32.0 4.45 44.4 31.1 4.9 42.0 30.1 5.56
63†† 45.8 32.2 3.93 43.7 31.3 4.42 41.5 30.3 4.9 39.5 29.4 5.53
62 45.0 39.5 3.93 43.0 38.5 4.41 40.9 37.5 4.9 38.7 36.5 5.50
57 42.9 42.9 3.90 41.5 41.5 4.40 39.8 39.8 4.9 38.0 38.0 5.49
1400
72 54.1 27.3 4.05 51.7 26.4 4.55 49.0 25.4 5.0 46.3 24.5 5.68
67 49.8 34.6 4.01 47.5 33.7 4.50 45.1 32.7 5.0 42.6 31.7 5.62
63†† 46.4 33.7 3.97 44.4 32.8 4.47 42.2 31.8 5.0 40.1 30.9 5.58
62 45.8 41.7 3.97 43.7 40.7 4.45 41.5 39.6 4.9 39.6 38.6 5.57
57 44.5 44.5 3.96 42.8 42.8 4.44 41.0 41.0 4.9 39.1 39.1 5.55
1610
72 54.8 28.6 4.11 52.4 27.7 4.61 49.7 26.8 5.1 46.6 25.7 5.73
67 50.6 36.9 4.06 48.4 36.0 4.57 45.9 35.1 5.1 43.4 34.1 5.69
63†† 47.2 35.8 4.03 45.3 35.0 4.54 43.0 34.0 5.0 40.6 33.0 5.64
62 46.8 44.8 4.03 44.9 43.8 4.53 42.7 42.5 5.0 40.7 40.7 5.65
57 46.3 46.3 4.03 44.4 44.4 4.52 42.7 42.7 5.0 40.7 40.7 5.64
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
F(A,B)4AN(F,B,C) 048 0.96 1.05 CJ5A/CK5A/CK5BA 060 0.97 0.99
060 0.99 1.07 CJ5A/CK5A/CK5BW 048 0.96 0.99
FB4ANB 070 1.00 1.06 CJ5A/CK5A/CK5BX 060 0.99 0.99
FC4BN(F,B) 048 0.96 1.05 CK3BA 048 0.96 0.99
060 0.99 1.07 060 0.97 0.99
FC4BNB 054 1.01 1.04 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
070 1.00 1.06 CC5A/CD5A/CD5BA 060 0.96 0.99
FG3AAA 048 0.95 1.04 CC5A/CD5A/CD5BW 060 0.98 0.99
060 0.97 1.04 CD3(A,B)A 060 0.96 0.99
FK4BNB 006 1.01 1.00 CE3AA 060 0.98 1.00
FK4CNB 006 1.01 0.98 CJ5A/CK5A/CK5BA 060 0.97 1.00
FK4CNF 005 1.00 1.00 CJ5A/CK5A/CK5BW 048 0.96 1.00
CC5A/CD5A/CD5BA 060 0.95 1.04 CJ5A/CK5A/CK5BX 060 0.99 0.99
CC5A/CD5A/CD5BC 048 0.94 1.04 CK3BA 048 0.96 1.00
CC5A/CD5A/CD5BW 048 0.95 1.04 060 0.97 1.00
060 0.98 1.04 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CD3(A,B)A 048 0.95 1.04 CC5A/CD5A/CD5BA 060 0.95 1.03
060 0.95 1.04 CC5A/CD5A/CD5BW 060 0.97 1.03
CD5A/CD5BA 048 0.95 1.04 CD3(A,B)A 060 0.95 1.03
CE3AA 048 0.96 1.04 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
060 0.98 1.04 CC5A/CD5A/CD5BA 060 0.95 1.02
CF5AA 048 0.96 1.04 CC5A/CD5A/CD5BW 060 0.97 1.02
CJ5A/CK5A/CK5BA 048 0.94 1.04 CD3(A,B)A 060 0.95 1.02
060 0.96 1.04 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BN 060 0.96 1.04 CC5A/CD5A/CD5BA 060 0.95 1.01
CJ5A/CK5A/CK5BW 048 0.94 1.04 CC5A/CD5A/CD5BW 060 0.97 1.01
CJ5A/CK5A/CK5BX 060 0.98 1.04 CD3(A,B)A 060 0.95 1.01
CK3BA 048 0.94 1.04 COILS + 355MAV060100 VARIABLE-SPEED FURNACE
060 0.96 1.04 CC5A/CD5A/CD5BA 060 0.95 1.00
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE CC5A/CD5A/CD5BW 060 0.98 1.00
CC5A/CD5A/CD5BA 060 0.95 1.00 CD3(A,B)A 060 0.95 1.00
CC5A/CD5A/CD5BW 060 0.98 1.00 CJ5A/CK5A/CK5BA 060 0.98 1.06
CD3(A,B)A 060 0.95 1.00 CJ5A/CK5A/CK5BN 060 0.98 1.06
CE3AA 060 0.98 1.01 CJ5A/CK5A/CK5BX 060 1.00 1.00
CJ5A/CK5A/CK5BA 048 0.95 1.02 CK3BA 060 0.98 1.06
CK3BA 048 0.95 1.02 COILS + 355MAV060120 VARIABLE-SPEED FURNACE
060 0.96 1.02 CJ5A/CK5A/CK5BA 060 0.98 1.05
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE CJ5A/CK5A/CK5BW 048 0.96 1.05
CC5A/CD5A/CD5BA 060 0.96 0.98 CJ5A/CK5A/CK5BX 060 0.99 1.04
CC5A/CD5A/CD5BW 060 0.98 0.98 CK3BA 048 0.96 1.05
CD3(A,B)A 060 0.96 0.98 060 0.98 1.05
CE3AA 060 0.99 0.99 — — —
—26—
DETAILED COOLING CAPACITIES* Continued
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-89. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C).
** System kw is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
EWB—Entering Wet Bulb
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115
CFM EWB
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Capacity
MBtuh† Total
System
Kw**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
697C060-A Outdoor Section With FK4CNB006 Indoor Section
1575
72 66.2 32.7 4.89 63.3 31.7 5.42 60.2 30.5 6.0 57.0 29.4 6.63
67 61.0 41.4 4.82 58.4 40.3 5.35 55.5 39.2 5.9 52.5 38.0 6.54
63†† 57.2 40.5 4.77 54.6 39.4 5.29 52.0 38.2 5.8 49.2 37.0 6.47
62 56.2 49.9 4.76 53.7 48.7 5.28 51.1 47.5 5.8 48.4 46.2 6.46
57 54.0 54.0 4.73 52.1 52.1 5.26 50.1 50.1 5.8 47.8 47.8 6.45
1750
72 67.0 33.9 4.95 64.1 32.9 5.49 60.8 31.7 6.0 57.5 30.5 6.69
67 61.8 43.4 4.89 59.0 42.3 5.41 56.1 41.2 5.9 53.0 39.9 6.61
63†† 57.9 42.4 4.84 55.3 41.2 5.36 52.6 40.0 5.9 49.7 38.8 6.54
62 57.1 52.7 4.83 54.5 51.5 5.35 51.9 50.1 5.9 49.2 48.7 6.53
57 55.7 55.7 4.81 53.6 53.6 5.34 51.4 51.4 5.9 49.0 49.0 6.53
2012
72 67.8 35.6 5.05 64.7 34.5 5.58 61.5 33.3 6.1 58.0 32.2 6.79
67 63.1 46.5 4.99 60.2 45.4 5.52 56.8 44.0 6.0 53.6 42.8 6.70
63†† 58.8 45.1 4.93 56.1 43.9 5.45 53.3 42.7 6.0 50.2 41.5 6.64
62 58.5 56.7 4.93 55.6 55.1 5.45 53.1 53.1 6.0 50.6 50.6 6.65
57 57.7 57.7 4.92 55.5 55.5 5.45 53.2 53.2 6.0 50.7 50.7 6.65
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling Indoor
Section Size
Cooling
Capacity Power Capacity Power
F(A,B)4AN(F,B,C) 060 0.97 1.06 CD3(A,B)A 060 0.94 1.01
FB4ANB 070 0.99 1.04 CE3AA 060 0.97 1.01
FC4BN(F,B) 060 0.97 1.06 CJ5A/CK5A/CK5BA 060 0.97 1.00
FC4BNB 070 0.99 1.04 CJ5A/CK5A/CK5BX 060 0.99 0.99
FG3AAA 060 0.96 1.02 CK3BA 060 0.97 1.00
FK4BNB 006 1.00 1.01 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
FK4CNB 006 1.00 1.00 CC5A/CD5A/CD5BA 060 0.93 1.02
CC5A/CD5A/CD5BA 060 0.94 1.02 CC5A/CD5A/CD5BW 060 0.96 1.01
CC5A/CD5A/CD5BW 060 0.96 1.02 CD3(A,B)A 060 0.93 1.02
CD3(A,B)A 060 0.94 1.02 CE3AA 060 0.97 1.02
CE3AA 060 0.97 1.03 CJ5A/CK5A/CK5BA 060 0.97 1.01
CJ5A/CK5A/CK5BA 060 0.97 1.02 CJ5A/CK5A/CK5BX 060 0.98 1.00
CJ5A/CK5A/CK5BN 060 0.97 1.02 CK3BA 060 0.97 1.01
CJ5A/CK5A/CK5BX 060 0.98 1.02 COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CK3BA 060 0.97 1.02 CC5A/CD5A/CD5BA 060 0.93 1.04
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE CC5A/CD5A/CD5BW 060 0.96 1.04
CC5A/CD5A/CD5BA 060 0.94 1.01 CD3(A,B)A 060 0.93 1.04
CC5A/CD5A/CD5BW 060 0.97 1.00 — — —
—27—
HEAT PUMP HEATING PERFORMANCE
See notes on page 34.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 172737475767
EDB CFM
Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
697C018-B Outdoor Section With FC4BNF024 Indoor Section
65 600 7.79 7.17 1.29 9.35 8.59 1.33 11.1 10.1 1.37 13.0 11.5 1.4 15.2 13.8 1.48 17.6 17.6 1.57 20.3 20.3 1.69 23.3 23.3 1.8
650 7.87 7.24 1.30 9.43 8.66 1.33 11.2 10.2 1.37 13.1 11.6 1.4 15.3 13.9 1.48 17.7 17.7 1.57 20.4 20.4 1.68 23.5 23.5 1.8
700 7.93 7.30 1.31 9.50 8.73 1.34 11.3 10.3 1.38 13.1 11.7 1.4 15.4 14.0 1.48 17.8 17.8 1.57 20.5 20.5 1.69 23.6 23.6 1.8
70 600 7.67 7.06 1.34 9.23 8.49 1.39 10.9 9.98 1.44 12.8 11.4 1.4 15.0 13.6 1.56 17.4 17.4 1.65 20.0 20.0 1.77 23.0 23.0 1.9
650 7.74 7.12 1.35 9.31 8.56 1.40 11.0 10.1 1.44 12.9 11.5 1.4 15.1 13.7 1.55 17.5 17.5 1.64 20.2 20.2 1.76 23.2 23.2 1.9
700 7.81 7.19 1.36 9.38 8.62 1.40 11.1 10.1 1.45 13.0 11.5 1.4 15.2 13.8 1.56 17.6 17.6 1.64 20.3 20.3 1.76 23.3 23.3 1.9
75 600 7.53 6.92 1.40 9.11 8.38 1.45 10.8 9.86 1.51 12.7 11.2 1.5 14.8 13.5 1.64 17.2 17.2 1.73 19.8 19.8 1.85 22.7 22.7 2.0
650 7.61 7.00 1.41 9.19 8.45 1.46 10.9 9.93 1.51 12.8 11.3 1.5 14.9 13.6 1.63 17.3 17.3 1.72 19.9 19.9 1.84 22.9 22.9 2.0
700 7.68 7.07 1.42 9.26 8.51 1.47 11.0 10.0 1.51 12.8 11.4 1.5 15.0 13.6 1.63 17.4 17.4 1.72 20.0 20.0 1.84 23.0 23.0 2.0
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating Indoor
Section Size
Heating
Capacity Power Capacity Power
FC4BNF 024 1.00 1.00 COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE
F(A,B)4AN(F,C) 018 0.97 1.07 CC5A/CD5A/CD5BA 024 0.97 1.02
024 1.00 1.00 CC5A/CD5A/CD5BW 024 0.97 1.02
FD3ANA 018 0.97 1.10 CD3(A,B)A 024 0.97 1.02
024 0.97 1.02 CE3AA 024 0.97 1.02
FF1BNA 018 0.97 1.04 CJ5A/CK5A/CK5BA 018 0.97 0.97
024 1.00 1.01 024 0.97 0.94
FG3AA 024 0.97 1.04 CK3BA 024 0.97 0.94
FK4BNF 001 0.97 0.91 COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
002 0.97 0.86 CC5A/CD5A/CD5BA 024 0.97 1.02
FK4CNF 001 0.94 0.93 CC5A/CD5A/CD5BW 024 0.97 1.02
002 0.95 0.90 CD3(A,B)A 024 0.97 1.02
CC5A/CD5A/CD5BA 018 0.97 1.10 CE3AA 024 0.97 1.02
024 1.00 1.06 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BW 024 1.00 1.06 CC5A/CD5A/CD5BA 024 0.97 0.98
CD3(A,B)A 018 0.97 1.10 CC5A/CD5A/CD5BW 024 0.97 0.98
024 1.00 1.06 CD3(A,B)A 024 0.97 0.98
CE3AA 024 1.00 1.05 CJ5A/CK5A/CK5BW 024 0.97 0.91
CF5AA 024 1.00 1.04 CK3BA 024 0.97 0.91
CJ5A/CK5A/CK5BA 018 0.97 1.03 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
024 0.97 0.99 CC5A/CD5A/CD5BA 024 0.97 0.98
CJ5A/CK5A/CK5BW 024 0.97 0.99 CC5A/CD5A/CD5BW 024 0.97 0.98
CK3BA 024 0.97 0.99 CD3(A,B)A 024 0.97 0.98
— — — CJ5A/CK5A/CK5BW 024 0.97 0.91
CK3BA 024 0.97 0.91
—28—
HEAT PUMP HEATING PERFORMANCE Continued
See notes on page 34.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 172737475767
EDB CFM
Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
697C024-B Outdoor Section With FC4BNF030 Indoor Section
65 700 10.7 9.88 1.67 13.0 11.9 1.74 15.5 14.1 1.80 18.1 16.1 1.8 21.3 19.4 1.96 25.0 25.0 2.08 29.3 29.3 2.24 34.3 34.3 2.4
800 10.9 10.0 1.68 13.1 12.1 1.74 15.6 14.2 1.79 18.3 16.2 1.8 21.5 19.6 1.93 25.2 25.2 2.04 29.6 29.6 2.21 34.7 34.7 2.4
900 11.0 10.1 1.70 13.3 12.2 1.74 15.7 14.3 1.78 18.4 16.4 1.8 21.7 19.7 1.92 25.4 25.4 2.03 29.9 29.9 2.19 34.9 34.9 2.3
70 700 10.5 9.67 1.74 12.9 11.8 1.83 15.4 14.0 1.90 18.0 16.0 1.9 21.1 19.2 2.07 24.7 24.7 2.19 29.0 29.0 2.36 33.8 33.8 2.5
800 10.7 9.83 1.75 13.0 12.0 1.83 15.5 14.1 1.89 18.2 16.1 1.9 21.3 19.4 2.04 25.0 25.0 2.15 29.3 29.3 2.31 34.3 34.3 2.5
900 10.8 9.96 1.77 13.1 12.1 1.84 15.6 14.3 1.89 18.3 16.3 1.9 21.5 19.6 2.02 25.2 25.2 2.14 29.6 29.6 2.29 34.6 34.6 2.5
75 700 10.2 9.37 1.78 12.7 11.6 1.91 15.2 13.9 2.00 17.9 15.9 2.0 21.0 19.1 2.18 24.5 24.5 2.31 28.6 28.6 2.48 33.4 33.4 2.7
800 10.4 9.56 1.80 12.8 11.8 1.92 15.4 14.0 1.99 18.0 16.0 2.0 21.2 19.3 2.15 24.8 24.8 2.27 29.0 29.0 2.43 33.8 33.8 2.6
900 10.6 9.71 1.82 13.0 11.9 1.92 15.5 14.1 1.99 18.2 16.2 2.0 21.3 19.4 2.14 25.0 25.0 2.25 29.2 29.2 2.40 34.2 34.2 2.6
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating Indoor
Section Size
Heating
Capacity Power Capacity Power
FC4BNF 024 1.00 1.02 COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE
030 1.00 1.00 CC5A/CD5A/CD5BA 030 0.96 1.00
033 1.00 0.97 CC5A/CD5A/CD5BW 030 0.96 1.00
F(A,B)4AN(F,C) 024 1.00 1.02 CD3(A,B)A 030 0.96 1.00
030 1.00 1.00 CE3AA 030 0.96 0.95
FD3ANA 024 1.00 1.06 COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
030 1.00 1.01 CC5A/CD5A/CD5BA 030 0.96 0.99
FF1(A,B)NA 024 1.00 1.01 CC5A/CD5A/CD5BW 030 0.96 0.99
030 1.00 0.99 CD3(A,B)A 030 0.96 0.99
FG3AAA 024 1.00 1.08 CE3AA 030 0.96 0.94
FK4BNF 001 1.00 0.94 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
002 1.00 0.90 CC5A/CD5A/CD5BA 030 0.96 1.00
003 0.98 0.90 CC5A/CD5A/CD5BW 030 0.96 1.00
FK4CNF 001 0.98 0.95 CD3(A,B)A 030 0.96 1.00
002 0.99 0.92 CE3AA 030 0.96 0.95
003 0.98 0.92 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA 024 1.00 1.06 CC5A/CD5A/CD5BA 030 0.96 0.97
030 1.00 1.06 CC5A/CD5A/CD5BW 030 0.96 0.97
036 1.00 0.98 CD3(A,B)A 030 0.96 0.97
CC5A/CD5A/CD5BW 024 1.00 1.06 CJ5A/CK5A/CK5BW 030 0.97 0.94
030 1.00 1.06 CK3BA 024 0.98 0.94
CD5A/CD5BW 036 1.00 0.98 030 0.97 0.94
CD3(A,B)A 024 1.00 1.06 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
030 1.00 1.06 CC5A/CD5A/CD5BA 030 0.96 0.97
036 1.00 0.98 CC5A/CD5A/CD5BW 030 0.96 0.97
CE3AA 024 1.00 1.07 CD3(A,B)A 030 0.96 0.97
030 1.00 1.01 CJ5A/CK5A/CK5BW 024 0.98 0.94
CF5AA 024 1.00 1.04 030 0.98 0.94
CJ5A/CK5A/CK5BA 024 1.00 1.03 CK3BA 024 0.98 0.94
030 0.98 1.01 030 0.98 0.94
CJ5A/CK5A/CK5BW 024 1.00 1.03 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
030 0.98 1.01 CC5A/CD5A/CD5BA 030 0.96 0.96
CK3BA 024 1.00 1.03 CC5A/CD5A/CD5BW 030 0.96 0.96
030 0.98 1.01 CD3(A,B)A 030 0.96 0.96
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE CJ5A/CK5A/CK5BW 024 0.97 0.92
CC5A/CD5A/CD5BA 030 0.96 1.00 030 0.97 0.92
CC5A/CD5A/CD5BW 030 0.96 1.00 CK3BA 024 0.97 0.92
CD3(A,B)A 030 0.96 1.00 030 0.97 0.92
CE3AA 030 0.96 0.95 COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BA 024 0.96 0.94 CC5A/CD5A/CD5BA 030 0.96 0.96
030 0.96 0.94 CC5A/CD5A/CD5BW 030 0.96 0.96
CJ5A/CK5A/CK5BW 030 0.96 0.94 CD3(A,B)A 030 0.96 0.96
CK3BA 024 0.96 0.94 — — —
030 0.96 0.94
—29—
HEAT PUMP HEATING PERFORMANCE Continued
See notes on page 34.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 1727374757
EDB CFM
Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
697C030-B Outdoor Section With FC4BNF036 Indoor Section
65 850 12.9 11.9 2.08 15.5 14.2 2.17 18.5 16.8 2.27 21.9 19.4 2.38 25.7 23.4 2.52 30.0 30.0 2.69 34.9 34.9 2.91
950 13.1 12.0 2.11 15.7 14.4 2.19 18.7 17.0 2.29 22.1 19.6 2.39 26.0 23.7 2.53 30.4 30.4 2.69 35.2 35.2 2.91
1050 13.2 12.2 2.14 15.9 14.6 2.22 18.9 17.2 2.31 22.3 19.8 2.41 26.2 23.9 2.54 30.6 30.6 2.71 35.5 35.5 2.91
70 850 12.7 11.7 2.16 15.4 14.1 2.26 18.3 16.7 2.36 21.6 19.2 2.48 25.4 23.1 2.62 29.7 29.7 2.80 34.5 34.5 3.03
950 12.9 11.9 2.19 15.5 14.3 2.28 18.5 16.9 2.38 21.9 19.4 2.49 25.7 23.4 2.63 30.0 30.0 2.80 34.8 34.8 3.02
1050 13.1 12.0 2.22 15.7 14.4 2.31 18.7 17.0 2.40 22.1 19.6 2.51 25.9 23.6 2.64 30.3 30.3 2.81 35.1 35.1 3.02
75 850 12.5 11.5 2.24 15.3 14.0 2.35 18.1 16.5 2.46 21.4 19.0 2.58 25.1 22.9 2.74 29.4 29.4 2.92 34.1 34.1 3.15
950 12.7 11.7 2.27 15.4 14.2 2.37 18.3 16.7 2.47 21.6 19.2 2.59 25.4 23.1 2.73 29.7 29.7 2.91 34.4 34.4 3.14
1050 12.9 11.9 2.30 15.6 14.3 2.40 18.5 16.9 2.50 21.8 19.4 2.61 25.6 23.3 2.74 29.9 29.9 2.92 34.7 34.7 3.14
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating Indoor
Section Size
Heating
Capacity Power Capacity Power
FC4BNF 030 1.00 1.01 CD5A/CD5BW 036 0.97 0.91
033 1.00 0.98 CD3(A,B)A 036 0.97 0.91
036 1.00 1.00 CE3AA 036 0.97 0.93
F(A,B)4ANF 030 1.00 1.01 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
036 1.00 1.00 CC5A/CD5A/CD5BA 036 0.97 0.93
FD3ANA 030 1.00 1.01 CD5A/CD5BW 036 0.97 0.93
FF1(A,B)NA 030 1.00 0.99 CD3(A,B)A 036 0.97 0.93
FG3AAA 036 1.00 1.01 CE3AA 036 0.97 0.95
FK4BNF 001 1.00 0.96 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
002 1.00 0.92 CC5A/CD5A/CD5BA 036 1.00 0.95
003 0.99 0.91 CD5A/CD5BW 036 1.00 0.95
004 1.00 0.88 CD3(A,B)A 036 1.00 0.95
FK4CNF 001 0.99 0.94 CJ5A/CK5A/CK5BW 030 0.98 0.97
002 0.99 0.92 036 1.00 0.94
003 0.99 0.92 CK3BA 030 0.98 0.97
CC5A/CD5A/CD5BA 030 1.00 1.05 036 1.00 0.94
036 1.00 0.99 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BW 030 1.00 1.05 CC5A/CD5A/CD5BA 036 1.00 0.95
CD5A/CD5BW 036 1.00 0.99 CD5A/CD5BW 036 1.00 0.95
CD3(A,B)A 030 1.00 1.05 CD3(A,B)A 036 1.00 0.95
036 1.00 0.99 CJ5A/CK5A/CK5BA 036 1.00 0.94
CE3AA 030 1.00 1.01 CJ5A/CK5A/CK5BW 030 0.98 0.97
036 1.00 1.01 CK3BA 030 0.98 0.97
CF5AA 036 1.00 0.99 036 1.00 0.94
CJ5A/CK5A/CK5BA 030 0.98 1.01 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
036 1.00 0.98 CC5A/CD5A/CD5BA 036 1.00 0.94
CJ5A/CK5A/CK5BW 030 0.98 1.01 CD5A/CD5BW 036 1.00 0.94
036 1.00 0.98 CD3(A,B)A 036 1.00 0.94
CK3BA 030 0.98 1.01 CJ5A/CK5A/CK5BW 030 0.97 0.95
036 1.00 0.98 036 0.98 0.92
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE CK3BA 030 0.97 0.95
CC5A/CD5A/CD5BA 036 0.97 0.93 036 0.98 0.92
CD5A/CD5BW 036 0.97 0.93 COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CD3(A,B)A 036 0.97 0.93 CC5A/CD5A/CD5BA 036 1.00 0.94
CE3AA 036 0.97 0.95 CD5A/CD5BW 036 1.00 0.94
CJ5A/CK5A/CK5BA 030 0.97 0.95 CD3(A,B)A 036 1.00 0.94
CJ5A/CK5A/CK5BW 030 0.97 0.95 CJ5A/CK5A/CK5BW 030 0.97 0.94
CK3BA 030 0.97 0.95 036 0.98 0.91
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE CK3BA 030 0.97 0.94
CC5A/CD5A/CD5BA 036 0.97 0.92 036 0.98 0.91
CD5A/CD5BW 036 0.97 0.92 COILS + 355MAV0601020 VARIABLE-SPEED FURNACE
CD3(A,B)A 036 0.97 0.92 CJ5A/CK5A/CK5BW 030 0.97 0.94
CE3AA 036 0.97 0.94 036 0.98 0.91
CJ5A/CK5A/CK5BW 030 0.97 0.95 CK3BA 030 0.97 0.94
CK3BA 030 0.97 0.95 036 0.98 0.91
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE —— —
CC5A/CD5A/CD5BA 036 0.97 0.91
—30—
HEAT PUMP HEATING PERFORMANCE Continued
See notes on page 34.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 1727374757
EDB CFM
Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
697C036-B Outdoor Section With FC4BN(F,B)042 Indoor Section
65 1100 16.0 14.7 2.43 19.3 17.7 2.53 22.8 20.8 2.64 26.7 23.7 2.74 31.2 28.4 2.87 36.1 36.1 3.03 41.8 41.8 3.23
1200 16.2 14.9 2.46 19.4 17.9 2.55 23.0 21.0 2.65 26.9 23.9 2.75 31.4 28.6 2.87 36.4 36.4 3.03 42.1 42.1 3.22
1300 16.4 15.1 2.48 19.7 18.1 2.58 23.2 21.1 2.66 27.1 24.1 2.76 31.6 28.7 2.88 36.6 36.6 3.03 42.4 42.4 3.22
70 1100 15.7 14.5 2.52 19.1 17.5 2.64 22.6 20.6 2.75 26.5 23.5 2.87 30.9 28.1 3.00 35.7 35.7 3.17 41.3 41.3 3.37
1200 15.9 14.6 2.55 19.2 17.7 2.66 22.8 20.8 2.76 26.7 23.7 2.87 31.1 28.3 3.00 36.0 36.0 3.16 41.6 41.6 3.36
1300 16.1 14.8 2.57 19.4 17.8 2.68 23.0 20.9 2.78 26.9 23.9 2.88 31.3 28.5 3.01 36.2 36.2 3.16 41.9 41.9 3.35
75 1100 15.4 14.1 2.62 18.9 17.3 2.74 22.4 20.4 2.87 26.2 23.3 2.99 30.6 27.8 3.14 35.4 35.4 3.31 40.9 40.9 3.52
1200 15.6 14.3 2.64 19.0 17.5 2.76 22.6 20.6 2.88 26.4 23.5 3.00 30.8 28.0 3.14 35.6 35.6 3.30 41.2 41.2 3.50
1300 15.7 14.5 2.67 19.2 17.6 2.78 22.7 20.7 2.89 26.6 23.6 3.01 31.0 28.2 3.14 35.9 35.9 3.30 41.5 41.5 3.50
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating Indoor
Section Size
Heating
Capacity Power Capacity Power
FC4BN(F,B) 042 1.00 1.00 CJ5A/CK5A/CK5BW 036 0.98 0.95
FC4BNF 033 1.00 1.00 CK3BA 036 0.98 0.95
036 1.00 1.03 042 1.00 0.96
F(A,B)4ANF 036 1.00 1.03 COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
F(A,B)4AN(F,B) 042 1.00 1.00 CC5A/CD5A/CD5BA 042 0.98 0.95
FG3AAA 036 1.00 1.03 CC5A/CD5A/CD5BW 042 0.98 0.95
FK4BNF 001 1.00 1.00 CD3(A,B)A 042 0.98 0.95
002 1.00 0.97 CC5A/CD5A/CD5BC 048 0.97 0.97
003 0.99 0.94 CE3AA 042 0.98 0.94
004 1.00 0.92 CJ5A/CK5A/CK5BA 042 0.99 0.94
FK4CNF 001 0.98 0.99 CJ5A/CK5A/CK5BW 036 0.98 0.94
002 0.99 0.97 CK3BA 036 0.98 0.94
003 0.98 0.94 042 0.99 0.94
CD5A/CD5BW 036 1.00 1.01 COILS ± 333(B,J)AV060120 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA 036 1.00 1.01 CC5A/CD5A/CD5BA 042 0.98 0.96
042 1.00 1.01 CC5A/CD5A/CD5BW 042 0.98 0.96
043 1.00 1.01 CD3(A,B)A 042 0.98 0.96
CC5A/CD5A/CD5BW 042 1.00 1.02 CC5A/CD5A/CD5BC 048 0.97 0.98
043 1.00 1.01 CE3AA 042 0.987 0.95
CD3(A,B)A 036 1.00 1.01 CJ5A/CK5A/CK5BA 042 0.99 0.94
042 1.00 1.01 CJ5A/CK5A/CK5BW 036 0.98 0.95
CE3AA 036 1.00 1.02 CK3BA 036 0.98 0.95
042 1.00 0.99 042 0.99 0.94
CF5AA 036 1.00 1.01 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BA 036 1.00 1.01 CC5A/CD5A/CD5BA 042 1.00 0.98
042 1.00 0.99 CD3(A,B)A 042 1.00 0.98
CJ5A/CK5A/CK5BN 042 1.00 0.99 CJ5A/CK5A/CK5BA 042 1.00 0.97
CJ5A/CK5A/CK5BW 036 1.00 1.01 CJ5A/CK5A/CK5BW 036 1.00 0.98
CK3BA 036 1.00 1.01 CK3BA 036 1.00 0.98
042 1.00 0.99 042 1.00 0.97
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA 042 0.98 0.98 CC5A/CD5A/CD5BA 042 1.00 0.98
CC5A/CD5A/CD5BW 042 0.98 0.98 CD3(A,B)A 042 1.00 0.98
CD3(A,B)A 042 0.98 0.98 CJ5A/CK5A/CK5BA 036 1.00 0.98
CC5A/CD5A/CD5BC 048 0.98 1.00 CJ5A/CK5A/CK5BN 042 1.00 0.97
CE3AA 042 0.99 0.97 CK3BA 036 1.00 0.98
CJ5A/CK5A/CK5BA 036 0.99 0.97 042 1.00 0.97
CK3BA 036 0.99 0.97 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE CC5A/CD5A/CD5BA 042 0.99 0.97
CC5A/CD5A/CD5BA 042 0.98 0.96 CD3(A,B)A 042 0.99 0.97
CC5A/CD5A/CD5BW 042 0.98 0.96 CJ5A/CK5A/CK5BA 042 1.00 0.97
CD3(A,B)A 042 0.98 0.96 CJ5A/CK5A/CK5BW 036 1.00 0.98
CC5A/CD5A/CD5BC 048 0.97 0.98 CK3BA 036 1.00 0.98
CE3AA 042 0.98 0.95 042 1.00 0.97
CJ5A/CK5A/CK5BA 042 1.00 0.96 — — —
—31—
HEAT PUMP HEATING PERFORMANCE Continued
See notes on page 34.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 1727374757
EDB CFM
Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
697C036-B Outdoor Section With FC4BN(F,B)042 Indoor Section Continued
65 1100 16.0 14.7 2.43 19.3 17.7 2.53 22.8 20.8 2.64 26.7 23.7 2.74 31.2 28.4 2.87 36.1 36.1 3.03 41.8 41.8 3.23
1200 16.2 14.9 2.46 19.4 17.9 2.55 23.0 21.0 2.65 26.9 23.9 2.75 31.4 28.6 2.87 36.4 36.4 3.03 42.1 42.1 3.22
1300 16.4 15.1 2.48 19.7 18.1 2.58 23.2 21.1 2.66 27.1 24.1 2.76 31.6 28.7 2.88 36.6 36.6 3.03 42.4 42.4 3.22
70 1100 15.7 14.5 2.52 19.1 17.5 2.64 22.6 20.6 2.75 26.5 23.5 2.87 30.9 28.1 3.00 35.7 35.7 3.17 41.3 41.3 3.37
1200 15.9 14.6 2.55 19.2 17.7 2.66 22.8 20.8 2.76 26.7 23.7 2.87 31.1 28.3 3.00 36.0 36.0 3.16 41.6 41.6 3.36
1300 16.1 14.8 2.57 19.4 17.8 2.68 23.0 20.9 2.78 26.9 23.9 2.88 31.3 28.5 3.01 36.2 36.2 3.16 41.9 41.9 3.35
75 1100 15.4 14.1 2.62 18.9 17.3 2.74 22.4 20.4 2.87 26.2 23.3 2.99 30.6 27.8 3.14 35.4 35.4 3.31 40.9 40.9 3.52
1200 15.6 14.3 2.64 19.0 17.5 2.76 22.6 20.6 2.88 26.4 23.5 3.00 30.8 28.0 3.14 35.6 35.6 3.30 41.2 41.2 3.50
1300 15.7 14.5 2.67 19.2 17.6 2.78 22.7 20.7 2.89 26.6 23.6 3.01 31.0 28.2 3.14 35.9 35.9 3.30 41.5 41.5 3.50
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating Indoor
Section Size
Heating
Capacity Power Capacity Power
COILS + 355MAV060100 VARIABLE-SPEED FURNACE COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BA 042 0.99 0.97 CJ5A/CK5A/CK5BA 042 0.99 0.95
CD3(A,B)A 042 0.99 0.97 CJ5A/CK5A/CK5BW 036 0.99 0.95
CJ5A/CK5A/CK5BA 042 0.99 0.95 CK3BA 036 0.99 0.95
CJ5A/CK5A/CK5BW 036 1.00 0.96 042 0.99 0.95
CK3BA 036 1.00 0.96 — — —
042 0.99 0.95
—32—
HEAT PUMP HEATING PERFORMANCE Continued
See notes on page 34.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 1727374757
EDB CFM
Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
697C042-B Outdoor Section With FK4CNF005 Indoor Section
65 1103 17.2 15.8 2.38 20.8 19.2 2.50 24.9 22.7 2.62 29.3 26.0 2.7 34.5 31.4 2.92 40.5 40.5 3.12 47.4 47.4 3.36
1225 17.3 16.0 2.38 21.0 19.3 2.49 25.0 22.8 2.60 29.5 26.2 2.7 34.8 31.6 2.88 40.8 40.8 3.07 47.5 47.5 3.27
1409 17.5 16.1 2.39 21.1 19.4 2.48 25.2 23.0 2.59 29.7 26.4 2.7 35.1 31.9 2.85 41.1 41.1 3.03 47.2 47.2 3.18
70 1103 16.9 15.6 2.49 20.7 19.0 2.62 24.7 22.5 2.75 29.0 25.8 2.9 34.1 31.1 3.07 40.0 40.0 3.28 46.8 46.8 3.54
1225 17.1 15.7 2.49 20.8 19.1 2.61 24.8 22.6 2.73 29.2 25.9 2.8 34.4 31.3 3.03 41.0 41.0 3.23 47.2 47.2 3.45
1409 17.3 15.9 2.49 21.0 19.3 2.61 25.0 22.8 2.72 29.4 26.1 2.8 34.7 31.6 2.99 40.7 40.7 3.17 47.4 47.4 3.37
75 1103 16.6 15.3 2.60 20.5 18.8 2.75 24.5 22.3 2.89 28.8 25.5 3.0 33.8 30.8 3.22 39.5 39.5 3.44 46.3 46.3 3.72
1225 16.8 15.4 2.59 20.6 18.9 2.74 24.6 22.4 2.87 28.9 25.7 3.0 34.0 31.0 3.18 40.8 40.8 3.39 46.6 46.6 3.64
1409 17.0 15.6 2.60 20.8 19.1 2.73 24.8 22.6 2.85 29.2 25.9 2.9 34.3 31.2 3.14 40.8 40.8 3.33 47.1 47.1 3.55
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating Indoor
Section Size
Heating
Capacity Power Capacity Power
F(A,B)4AN(F,B,C) 042 1.00 1.12 CC5A/CD5A/CD5BW 048 0.98 1.09
048 1.00 1.07 CD3(A,B)A 048 0.98 1.09
FC4BN(F,B) 042 1.00 1.12 CD5A/CD5BA 048 0.98 1.09
048 1.00 1.07 CE3AA 048 1.00 1.06
FC4BNF 038 1.00 1.04 CJ5A/CK5A/CK5BA 042 0.98 1.04
FG3AAA 048 1.00 1.10 CJ5A/CK5A/CK5BW 048 1.00 1.05
FK4BNB 003 1.00 1.08 CK3BA 042 0.98 1.04
FK4BNF 005 1.00 0.99 048 1.00 1.05
FK4CNF 003 0.98 1.06 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
005 1.00 1.00 CC5A/CD5A/CD5BC 048 0.98 1.10
CC5A/CD5A/CD5BA 042 1.00 1.12 CC5A/CD5A/CD5BW 048 0.98 1.10
043 1.00 1.12 CD3(A,B)A 048 0.98 1.10
CC5A/CD5A/CD5BC 048 1.00 1.15 CD5A/CD5BA 048 0.98 1.10
CC5A/CD5A/CD5BW 042 1.00 1.13 CE3AA 048 1.00 1.07
043 1.00 1.12 CJ5A/CK5A/CK5BA 042 1.00 1.07
048 1.00 1.10 CJ5A/CK5A/CK5BW 048 1.00 1.05
CD3(A,B)A 042 1.00 1.12 CK3BA 042 1.00 1.07
048 1.00 1.10 048 1.00 1.05
CD5A/CD5BA 048 1.00 1.10 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CE3AA 042 1.00 1.10 CD3(A,B)A 048 1.00 1.14
048 1.00 1.09 CD5A/CD5BA 048 1.00 1.14
CF5AA 048 1.00 1.11 CJ5A/CK5A/CK5BW 048 1.02 1.11
CJ5A/CK5A/CK5BA 042 1.00 1.12 CK3BA 048 1.02 1.11
048 1.00 1.10 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BN 042 1.00 1.12 CD3(A,B)A 048 1.00 1.14
CJ5A/CK5A/CK5BW 048 1.00 1.10 CD5A/CD5BA 048 1.00 1.14
CK3BA 042 1.00 1.12 CK3BA 048 1.02 1.11
048 1.00 1.10 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE CD3(A,B)A 048 1.00 1.12
CC5A/CD5A/CD5BC 048 0.98 1.12 CD5A/CD5BA 048 1.00 1.12
CC5A/CD5A/CD5BW 048 0.98 1.10 CJ5A/CK5A/CK5BA 042 1.02 1.13
CD3(A,B)A 048 0.98 1.10 048 1.02 1.09
CD5A/CD5BA 048 0.98 1.10 CK3BA 042 1.02 1.13
CE3AA 048 1.00 1.08 048 1.02 1.09
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5A/CD5BC 048 0.98 1.11 CD3(A,B)A 048 1.00 1.11
CC5A/CD5A/CD5BW 048 0.98 1.10 CD5A/CD5BA 048 1.00 1.11
CD3(A,B)A 048 0.98 1.10 CJ5A/CK5A/CK5BA 042 1.00 1.08
CD5A/CD5BA 048 0.98 1.10 048 1.00 1.06
CE3AA 048 1.00 1.08 CK3BA 042 1.00 1.08
CJ5A/CK5A/CK5BA 042 1.00 1.09 048 1.00 1.06
048 1.00 1.07 COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CK3BA 042 1.00 1.09 CJ5A/CK5A/CK5BA 042 1.00 1.08
048 1.00 1.07 CJ5A/CK5A/CK5BW 048 1.00 1.06
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE CK3BA 042 1.00 1.08
CC5A/CD5A/CD5BC 048 0.98 1.10 048 1.00 1.06
—33—
HEAT PUMP HEATING PERFORMANCE Continued
See notes on page 34.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 1727374757
EDB CFM
Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
697C048-A Outdoor Section With FK4CNF005 Indoor Section
65 1260 21.2 19.5 3.06 25.5 23.4 3.22 30.3 27.6 3.38 35.9 32.7 3.5 41.6 37.9 3.79 48.6 48.6 4.07 56.9 56.9 4.43
1400 21.4 19.7 3.06 25.7 23.6 3.20 30.5 27.8 3.35 36.2 33.0 3.5 42.0 38.2 3.73 49.1 49.1 3.99 57.4 57.4 4.33
1610 21.6 19.9 3.07 25.9 23.8 3.19 30.8 28.0 3.33 36.6 33.3 3.5 42.4 38.6 3.67 49.6 49.6 3.91 58.1 58.1 4.23
70 1260 20.8 19.1 3.21 25.3 23.2 3.39 30.0 27.4 3.57 35.6 32.4 3.7 41.2 37.5 4.00 48.1 48.1 4.29 56.1 56.1 4.66
1400 21.0 19.3 3.20 25.4 23.4 3.37 30.2 27.5 3.54 35.9 32.7 3.7 41.5 37.8 3.94 48.5 48.5 4.20 56.7 56.7 4.56
1610 21.3 19.6 3.21 25.7 23.6 3.37 30.5 27.8 3.51 36.2 33.0 3.6 41.9 38.2 3.87 49.0 49.0 4.12 57.4 57.4 4.45
75 1260 20.4 18.8 3.36 25.0 23.0 3.57 29.7 27.1 3.76 35.2 32.1 3.9 40.7 37.1 4.22 47.5 47.5 4.53 55.5 55.5 4.91
1400 20.6 19.0 3.36 25.2 23.2 3.55 29.9 27.3 3.73 35.5 32.3 3.9 41.1 37.4 4.15 47.9 47.9 4.44 56.0 56.0 4.80
1610 20.9 19.2 3.36 25.4 23.4 3.54 30.2 27.5 3.70 35.8 32.6 3.9 41.5 37.7 4.09 48.4 48.4 4.35 56.6 56.6 4.69
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating Indoor
Section Size
Heating
Capacity Power Capacity Power
F(A,B)4AN(F,B,C) 048 1.02 1.10 CJ5A/CK5A/CK5BA 060 0.98 1.08
060 1.03 1.08 CJ5A/CK5A/CK5BW 048 0.98 1.09
FB4ANB 070 1.03 1.03 CJ5A/CK5A/CK5BX 060 1.00 1.02
FC4BN(F,B) 048 1.02 1.10 CK3BA 048 0.98 1.09
060 1.03 1.08 060 0.98 1.08
FC4BNB 054 1.03 1.01 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
070 1.03 1.03 CC5A/CD5A/CD5BA 060 0.98 1.10
FG3AAA 048 1.01 1.12 CC5A/CD5A/CD5BW 060 1.00 1.05
060 1.01 1.10 CD3(A,B)A 060 0.98 1.10
FK4BNB 006 1.01 0.96 CE3AA 060 1.00 1.05
FK4CNB 006 1.01 0.97 CJ5A/CK5A/CK5BA 060 0.98 1.08
FK4CNF 005 1.00 1.00 CJ5A/CK5A/CK5BW 048 0.98 1.10
CC5A/CD5A/CD5BA 060 1.00 1.13 CJ5A/CK5A/CK5BX 060 0.99 1.05
CC5A/CD5A/CD5BC 048 0.99 1.16 CK3BA 048 0.98 1.10
CC5A/CD5A/CD5BW 048 1.00 1.12 060 0.98 1.08
060 1.01 1.08 COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CD3(A,B)A 048 1.00 1.12 CC5A/CD5A/CD5BA 060 1.00 1.15
060 1.00 1.13 CC5A/CD5A/CD5BW 060 1.01 1.09
CD5A/CD5BA 048 1.00 1.12 CD3(A,B)A 060 1.00 1.15
CE3AA 048 1.01 1.12 COILS + 355MAV042060 VARIABLE-SPEED FURNACE
060 1.01 1.08 CC5A/CD5A/CD5BA 060 1.00 1.14
CF5AA 048 1.00 1.13 CC5A/CD5A/CD5BW 060 1.01 1.09
CJ5A/CK5A/CK5BA 048 0.99 1.14 CD3(A,B)A 060 1.00 1.14
060 1.00 1.14 COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BN 060 1.00 1.14 CC5A/CD5A/CD5BA 060 1.00 1.13
CJ5A/CK5A/CK5BW 048 0.99 1.14 CC5A/CD5A/CD5BW 060 1.01 1.08
CJ5A/CK5A/CK5BX 060 1.00 1.10 CD3(A,B)A 060 1.00 1.13
CK3BA 048 0.99 1.14 COILS + 355MAV060100 VARIABLE-SPEED FURNACE
060 1.00 1.14 CC5A/CD5A/CD5BA 060 1.00 1.13
COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE CC5A/CD5A/CD5BW 060 1.01 1.07
CC5A/CD5A/CD5BA 060 0.99 1.13 CD3(A,B)A 060 1.00 1.13
CC5A/CD5A/CD5BW 060 1.00 1.06 CJ5A/CK5A/CK5BA 060 1.00 1.11
CD3(A,B)A 060 0.99 1.13 CJ5A/CK5A/CK5BN 060 1.00 1.11
CE3AA 060 1.00 1.06 CJ5A/CK5A/CK5BX 060 1.00 1.02
CJ5A/CK5A/CK5BA 048 0.99 1.13 CK3BA 060 1.00 1.11
CK3BA 048 0.99 1.13 COILS + 355MAV060120 VARIABLE-SPEED FURNACE
060 0.99 1.12 CJ5A/CK5A/CK5BA 060 1.00 1.11
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE CJ5A/CK5A/CK5BW 048 1.00 1.12
CC5A/CD5A/CD5BA 060 0.98 1.10 CJ5A/CK5A/CK5BX 060 1.00 1.07
CC5A/CD5A/CD5BW 060 0.99 1.03 CK3BA 048 1.00 1.12
CD3(A,B)A 060 0.98 1.10 060 1.00 1.11
CE3AA 060 0.99 1.04 — — —
—34—
HEAT PUMP HEATING PERFORMANCE Continued
* The Btuh heating capacity values shown are net “integrated’’ values from which the defrost effect has been subtracted. The Btuh heating from supplement
heaters should be added to those values to obtain total system capacity.
† The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to
obtain total system kilowatts.
EDB—Entering Dry Bulb
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 1727374757
EDB CFM
Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr Capacity
(MBtuh) Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
697C060-A Outdoor Section With FK4CNB006 Indoor Section
65 1575 28.0 25.8 3.81 33.2 30.6 4.02 39.1 35.6 4.24 45.3 40.3 4.4 52.8 48.0 4.81 61.2 61.2 5.20 71.0 71.0 5.73
1750 28.3 26.0 3.82 33.5 30.8 4.01 39.4 35.9 4.22 45.7 40.5 4.4 53.2 48.4 4.76 61.7 61.7 5.14 71.7 71.7 5.65
2012 28.6 26.3 3.84 33.9 31.1 4.02 39.7 36.2 4.21 46.1 40.9 4.4 53.7 48.9 4.72 62.3 62.3 5.09 72.0 72.0 5.52
70 1575 27.7 25.5 3.98 32.9 30.3 4.21 38.7 35.3 4.45 44.9 39.8 4.7 52.1 47.5 5.05 60.5 60.5 5.45 70.2 70.2 5.99
1750 28.0 25.7 3.99 33.2 30.5 4.20 39.0 35.6 4.43 45.2 40.1 4.6 52.6 47.8 4.99 61.0 61.0 5.38 71.6 71.6 5.91
2012 28.3 26.0 4.02 33.5 30.8 4.21 39.4 35.9 4.42 45.6 40.5 4.6 53.1 48.3 4.95 61.6 61.6 5.32 71.5 71.5 5.84
75 1575 27.4 25.2 4.16 32.6 30.0 4.41 38.3 35.0 4.67 44.4 39.4 4.9 51.6 47.0 5.29 59.8 59.8 5.72 69.3 69.3 6.27
1750 27.6 25.4 4.16 32.9 30.2 4.40 38.6 35.2 4.64 44.7 39.7 4.9 52.0 47.3 5.23 60.3 60.3 5.64 70.0 70.0 6.17
2012 28.0 25.7 4.19 33.2 30.5 4.41 39.0 35.6 4.63 45.2 40.1 4.8 52.5 47.8 5.18 60.9 60.9 5.57 70.7 70.7 6.10
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating Indoor
Section Size
Heating
Capacity Power Capacity Power
F(A,B)4AN(F,B,C) 060 1.00 1.09 CD3(A,B)A 060 1.00 1.17
FB4ANB 070 1.00 1.03 CE3AA 060 1.00 1.10
FC4BN(F,B) 060 1.00 1.09 CJ5A/CK5A/CK5BA 060 1.00 1.12
FC4BNB 070 1.00 1.03 CK5A/CK5A/CK5BX 060 1.00 1.06
FG3AAA 060 1.00 1.13 CK3BA 060 1.00 1.12
FK4BNB 006 1.00 1.01 COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
FK4CNB 006 1.00 1.00 CC5A/CD5A/CD5BA 060 1.00 1.19
CC5A/CD5A/CD5BA 060 1.00 1.18 CC5A/CD5A/CD5BW 060 1.00 1.10
CC5A/CD5A/CD5BW 060 1.00 1.11 CD3(A,B)A 060 1.00 1.19
CD3(A,B)A 060 1.00 1.18 CE3AA 060 1.00 1.11
CE3AA 060 1.00 1.11 CJ5A/CK5A/CK5BA 060 1.00 1.11
CJ5A/CK5A/CK5BA 060 1.00 1.12 CK5A/CK5A/CK5BX 060 1.00 1.06
CJ5A/CK5A/CK5BN 060 1.00 1.12 CK3BA 060 1.00 1.11
CJ5A/CK5A/CK5BX 060 1.00 1.07 COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CK3BA 060 1.00 1.12 CC5A/CD5A/CD5BA 060 1.00 1.19
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE CC5A/CD5A/CD5BW 060 1.00 1.11
CC5A/CD5A/CD5BA 060 1.00 1.17 CD3(A,B)A 060 1.00 1.19
CC5A/CD5A/CD5BW 060 1.00 1.10 — — —
—35—
System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C).
4. Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C).
5. Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C).
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below =150 ft. (See items 8 and 9
following).
8. For interconnecting refrigerant tube lengths greater than 50 ft, consult Long-Line Application Guideline available from equipment distributor.
9. Not more than 36 in. of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in.
vertical rise to the valve connections at the unit.
10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
—36—
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Cancels: PDS 697C.18.2B
©1997 Bryant Heating & Cooling Systems, 7310 W. Morris Street, Indianapolis, IN 46231 PRINTED IN U.S.A. Catalog No. BY-3269-711 3-97
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your
knowledge of the equipment discussed in this manual, including:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular
video-based formats and materials. All include video and/or slides, plus companion
book.
Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.