Burnham Series 4S Power Flame Data Sheet 7 8 13

2015-06-08

: Burnham Burnham-Series-4S-Power-Flame-Data-Sheet-738068 burnham-series-4s-power-flame-data-sheet-738068 burnham pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadBurnham Burnham-Series-4S-Power-Flame-Data-Sheet- 4S Series 7-8-13  Burnham-series-4s-power-flame-data-sheet
Open PDF In BrowserView PDF
SERIES 4S
`

Power Flame Burner Information
Burner Model

Motor
Standard UL Flame Safeguard

Gas and
Boiler Size Gas/#2 Oil
#2 Oil
4S-100
C3-25B
C3-OB
4S-125
C4-30
C4-OA
4S-150
C4-30
C4-OB
4S-175
C5-30
C5-O
4S-200
C6-30
C6-O
4S-250
C6-30
C6-O
4S-300
C7-30
C7-O
4S-350
C8-30
C8-O*
4S-400
CM9B-30 CM9B-O
4S-500
CM10-30
CM10-O
4S-600
CM10B-30 CM10B-O
4S-700
CM10C-30 CM10C-O
4S-800
CM11-30 CM11C-O
[1] Explanation of Firing Sequences:

HP
3
5
5
71/2
10
10
15
15
71/2
10
15
20
25

Voltage
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3
208-460/60/3

Firing Sequence [1]
L-H-O
L-H-O
L-H-O
Full Mod
Full Mod
Full Mod
Full Mod
Full Mod
Full Mod
Full Mod
Full Mod
Full Mod
Full Mod

Gas
RM7897C/UV
RM7897C/UV
RM7897C/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV

#2 Oil
RM7897C/UV
RM7897C/UV
RM7897C/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV
RM7840L/UV

[2]
Gas/#2 Oil Size
RM7897C/UV
2
RM7897C/UV 21/2
RM7897C/UV 21/2
RM7840L/UV
3
RM7840L/UV
3
RM7840L/UV
3
RM7840L/UV
3
RM7840L/UV
3
RM7840L/UV
3
RM7840L/UV
3
RM7840L/UV
3
RM7840L/UV 3 / 4
RM7840L/UV 3HF

Gas Train
Min. Pres.
7.3" w.c.
9.9" w.c.
13.2" w.c.
11.6" w.c.
12.8" w.c.
17.0" w.c.
26.8" w.c.
32.4" w.c.
40.9" w.c.
63.0" w.c.
91.0" w.c.
90.0" w.c.
94.0" w.c.

Max. Pres.
14.0" w.c.
14.0" w.c.
14.0" w.c.
28.0" w.c.
28.0" w.c.
28.0" w.c.
10 psig
10 psig
10 psig
10 psig
10 psig
10 psig
10 psig

*order burner with 6" insertion depth.

Gas and Gas Sequence on Combination Gas/Oil Boilers
L-H-O

Low fire start (not proven), high fire run, air control by linkage to motorized gas valve.

Full Mod

Full modulation with proven low fire start, synchronized fuel/air control with modulating motor.

Oil and Oil Sequence on Combination Gas/Oil Boilers
L-H-O

Low fire start (not proven), high fire run, oil cylinder air control (reduced input start) with by-passing type nozzle, oil valve and oil pressure
regulating valve.

Full Mod

Full modulation with proven low fire start, synchronized fuel/air control with modulating motor, oil by-passing type nozzle, oil metering valve,
oil pressure regulating valve.

[2] Models 4S-700 - Dual size gas trains: Leak test cock, main gas valve and auxiliary gas valve are indicated by the first number; gas regulator and main
shutoff cock are indicated by the second number.
11/3/06

SERIES 4S
Power Flame Burner Equipment
Equipment
Control Cabinet

Fuel
Gas, #2 Oil, Gas/#2 Oil NEMA 1A with hinged door.

Control Voltage Transformer

Gas, #2 Oil, Gas/#2 Oil Included

Motor Starter

Gas, #2 Oil, Gas/#2 Oil Magnetic starter with overload protection with.

Fusing

Gas, #2 Oil, Gas/#2 Oil Control circuit only.

Ignition

Gas and Gas/#2 Oil
#2 Oil

Signal Lights
Air Flow Safety Switch

Gas/Electric pilot.
Direct spark 100 through 150.
Gas/Electric pilot 200 and larger.

Gas, #2 Oil, Gas/#2 Oil LHO, Two [power on and fuel on]. Full Modulation, Four [power on, fuel valve open, call
for heat, flame failure.]
Gas
#2 Oil
Gas/#2 Oil

Gas Train

Gas and Gas/#2 Oil

All models.
On models 175 and larger.
All models, functions with both fuels.
UL gas train for minimum inlet pressure indicated on Burner Information table.
Assembled, wired and mounted on unit consisting of the following:
z
z
z
z
z
z

Oil Pump

Pilot Gas Controls
Fuel Changeover

Description

#2 Oil and Gas/#2 Oil

Manual shut-off valve.
Gas pressure regulator.
Manual leak test valve.
Automatic gas valve: Motorized. Proof of closure on model 125 and larger.
Safety gas valve: Solenoid type. Motorized on model 200 and larger.
High and Low gas pressure switches

Two stage, integral with burner on model 100.
Separate oil pump set with motor and accessories mounted on boiler skid model 125
and larger.

Gas, #2 Oil, Gas/#2 Oil All models with gas/electric pilot have manual pilot shut-off valve, gas pressure regulator
and solenoid gas valve.
Gas/#2 Oil

Manual switch.
6/23/2005



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Author                          : CNosal
Create Date                     : 2013:07:09 13:40:57-04:00
Modify Date                     : 2013:07:09 13:41:19-04:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Format                          : application/pdf
Title                           : 4S Series 7-8-13.xls
Creator                         : CNosal
Creator Tool                    : PScript5.dll Version 5.2.2
Metadata Date                   : 2013:07:09 13:41:19-04:00
Producer                        : Acrobat Distiller 9.5.5 (Windows)
Document ID                     : uuid:82d2f47e-a38f-4eab-bdd8-a8f0fa703c9f
Instance ID                     : uuid:ca4b569e-a04f-4ab5-9ae8-6dc071d13713
Page Count                      : 2
EXIF Metadata provided by EXIF.tools

Navigation menu