Burnham Series V11 Brochure

2015-06-08

: Burnham Burnham-Series-V11-Brochure-738054 burnham-series-v11-brochure-738054 burnham pdf

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadBurnham Burnham-Series-V11-Brochure-  Burnham-series-v11-brochure
Open PDF In BrowserView PDF
V11 Series
Cast Iron Commercial Water or Steam Boiler

837 to 5733 MBH Input
Oil, Gas, or Oil/Gas Combination
30, 50, or 80 PSI
Cast Iron Sectional Design
Water or Steam
Top or Rear Venting
Exclusive Optional SBC Boiler Controlª
Ð M aximizes System Efficiency
1

V11 Series

Cast Iron Commercial Water or Steam Boiler

Your Commercial Heating Solution!
Available in twenty sizes with gross output ratings from
667	to	4551	MBH,	the	V11	Series	is	commonly	used	in	
schools, hospitals, and other large commercial applications
where comfort and reliability are critical. The product meets
the	energy	efficiency	requirements	of	ASHRAE	90.1	with	
combustion efficiencies up to 85%.

Installation & Service Flexibility

Cast iron construction, ease of assembly, two venting options,
and	stringent	testing	methods	make	the	V11	Series	boiler	by	
Burnham Commercial your commercial heating solution.

• Hassle-free Section Assembly

The	cast	iron	sectional	design	of	the	V11	boiler	makes	it	easy	to	
maneuver through doorways and into the boiler room. In addition to being shipped as loose sections, the boiler is available
with factory-assembled sections or as a completely packaged
and fire-tested unit.
V11	boiler	sections	have	reinforced	lugs	that	are	used		
to assemble the sections with individual draw rods
resulting in fast, strain-free assembly.

American-Made Cast Iron ConstructionÐ
BC25-HSi

Burnham CommercialÕ s unique
BC25-HSi	cast	iron	formula	has	
an extremely high silicon content,
making it stronger and more
flexible than the iron used in
competitor's boiler sections. It offers
better thermal shock resistance and
greater heat transfer capabilities
than other cast iron products.
BC25-HSi's	properties	allow	Burnham	Commercial	to	
maintain the highest level of quality from start to finish, and
provide a product that is optimized
for hydronic heating applications.

The sections can be assembled using two common
toolsÑ a 3/4" drive ratchet with a 1-1/16" deep socket
and wrench. The sections are surface ground to ensure
smooth surface mating. An elastic sealant and fiberglass
rope are used on all section joints for a completely sealed
and pressure-tight assembly.

• extensive Testing Methods

Each boiler section is hydrostatically tested at 2-1/2 times
	 the	rated	working	pressure	at	the	foundry.	Factory-		
	
assembled sections are tested a second time at 1.5 times the
rated working pressure.

• Manufactured with Quality
Cast iron sections are produced at
	 Burnham	Foundry	LLC	in	Ohio,		 	
ensuring quality and availability of
boiler sections.

• Rear or Top Venting

As	a	forced	draft	boiler,	the	V11
provides optimum draft for controlled
efficiency, eliminating the need for
high chimneys or induced draft fans.
	 A	unique	feature	of	the	V11	boiler
is that it can be vented from the
rear or the top. This enables easy
chimney or sidewall venting for
maximum installation flexibility.
Top outlet venting saves floor space
and reduces installation time and
materials. A plugged tapping is
provided to take flue outlet pressure
readings.

• Cast Iron nipple Difference
V11	sections	are	held	together
using cast iron nipples, which
are well known as being of the
highest standard for boiler
construction. Unlike gaskets used
by many other boiler
manufacturers, cast iron nipples are impervious to flue
gases, oils, petroleum-based chemicals and other
contaminants, which means fewer costly repairs and a
longer lasting boiler.

2

Commitment to Quality

Burnham Commercial, "America's Boiler Company," has earned
a reputation for quality and dependability. Built for a variety of
applications,	the	V11	Series	is	right	for	your	next	job.	

Top or Rear Outlet
with adjustable lock-type damper (not
shown); includes plugged tapping for outlet
pressure readings

Front Mounted Controls
for easy adjustment
and maintenance

Aluminized
Steel Canopy

Burner Mounting plate
with flame observation port

Cast Iron nipples
ensure the integrity of the
section assembly and resist
petroleum based chemicals
and flue gases

Removable Side Jacket panels
Easy access to all cleanouts
and flue surfaces

Cast Iron Sections
Vertical	flue	design	with	
pinned heating surface for
maximum heat extraction

4 Burner
Manufacturers

Rear Observation port

Options	to	best	
fit your needs

Includes plugged tapping
for over-fire draft readings

Individual Draw Rods

Wet Base

with reinforced lugs for
strain free assembly

Side wall insulation
creates improved
thermal circulation

Optional
Tankless Heater
Provides	domestic	hot	water

Also AvailableÉ

SBC

TM

Integrated Boiler Control System

Burnham CommercialÕ s SBC is a complete boiler
monitoring and automation system. Available as an option, this exclusive feature
was	designed	and	developed	by	Burnham	Commercial’s	engineers	and	is	available	ONLY	
on Burnham Commercial products.

SBC Exclusives
	 Designed	to	maximize	system	efficiency	
and minimize energy usage
Easily connected to building management
systems
	 Proven	control	platform,	used	successfully	
for years at other Burnham companies
	 Fail-safe	design	insures	boiler	operation

•	 Advanced	Adaptability
•	 Peer-To-Peer	Network
	•	Fail-Safe System Operations
•	 Boiler	Monitoring	&	Diagnostic	Displays
•	 Modulation	Rate	and	On/Off	Modes
•	 Outdoor Air Temperature Reset
•	 Warm Weather Shutdown (WWSD)
•	 Domestic Hot Water Priority (DHWP)
•	 System Control Outputs

3

The SBC Boiler
Control SystemÉ
Only available
from Burnham
Commercial!

V11 Series Dimensions
BURneR DIMenSIOn - 'M' *
BOILeR
MODeL
V1104
V1105
V1106
V1107
V1108
V1109
V1110
V1111
V1112
V1113
V1114
V1115
V1116
V1117
V1118
V1119
V1120
V1121
V1122
V1123

nUMBeR
OF
SeCTIOnS
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23

BeCKeTT
'A'
26-5/8
32-3/4
38-7/8
45
51-1/8
57-1/4
63-3/8
69-1/2
75-5/8
81-3/4
87-7/8
94
100-1/8
106-1/4
112-3/8
118-1/2
124-5/8
130-3/4
136-7/8
143

'B'
18-7/8
25
31-1/8
37-1/4
43-3/8
49-1/2
55-5/8
61-3/4
67-7/8
74
80-1/8
86-1/4
92-3/8
98-1/2
104-5/8
110-3/4
116-7/8
123
129-1/8
135-1/4

'C'
Ñ
Ñ
31-1/8
37-1/4
43-3/8
49-1/2
24-3/4
37
37
37
24-3/4
24-3/4
30-7/8
30-7/8
30-7/8
30-7/8
30-7/8
30-7/8
30-7/8
30-7/8

'D'
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
30-7/8
24-3/4
30-7/8
37
24-1/2
24-1/2
36-3/4
36-3/4
24-1/2
24-1/2
24-1/2
24-1/2
24-1/2
24-1/2

'e'
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
30-7/8
37
24-3/4
30-7/8
24-1/2
24-1/2
36-3/4
36-3/4
24-1/2
24-1/2

'F'
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ

Ñ
24-3/4
30-7/8
24-3/4
30-7/8
24-1/2
24-1/2

'G'
'H'
Ñ
13-13/16
Ñ
19-15/16
Ñ
26-1/16
Ñ
32-3/16
Ñ
38-5/16
Ñ
44-7/16
Ñ
50-9/16
Ñ
56-11/16
Ñ
56-5/8
Ñ
53-5/16
Ñ
53-5/16
Ñ
53-5/16
Ñ
53-5/16
Ñ
53-5/16
Ñ
53-5/16
Ñ
53-5/16
Ñ
53-5/16
Ñ
53-5/16
24-3/4 53-5/16
30-7/8 53-5/16

'J'
55
55
55
54
54
54
53
53
53
53
52
52
52
52
51
51
51
51
50
50

all dimensions in inches
*	 Burner	control	panel	configuration	may	change	this	dimension	

FRONT
OBSERVATION
PORT

4

'K'
8
8
8
10
10
10
12
12
12
12
14
14
14
14
16
16
16
16
18
18

'L'
1
2
2
3
3
4
4
4
5
5
5
6
6
6
7
7
8
8
9
9

CF
24-3/4
24-3/4
24-3/4
24-1/4
24-1/4
24-1/4
24-1/4
24-1/4
25-3/4
25-3/4
27
27
26
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ

CG
21-3/4
21-3/4
28-3/4
29-1/4
29-1/4
29-1/4
29-1/4
29-5/8
29-5/8
29-5/8
29-5/8
29-5/8
29-5/8
29-5/8
29-5/8
29-5/8
Ñ
Ñ
Ñ
Ñ

pOWeRFLAMe WeBSTeR
CARLIn
Ñ
19-3/4
19-3/4
20-1/2
20-1/2
20-1/2
25-5/8
25-5/8
25-5/8
26-1/8
26-1/8
26-1/8
26-1/8
26-1/8
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ

CR
30
30
35
35
35
35
35
40
40
40
40
40
40
40
40
40
40
40
46
46

JR**
20-1/4
20-1/4
23-3/4
23-3/4
23-3/4
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ

JB
25
25
25
25
25
25
25
29
29
29
29
29
29
29
29
29
29
29
29
29

AppROX.
WeIGHT OF
SeCTIOn
(Assembly Only)
1833
2226
2618
3010
3403
3795
4188
4580
4972
5365
5757
6150
6542
6934
7327
7719
8112
8504
8896
9289

V11 Series Piping Recommendations
Water Boiler

pipe Sizing and notes
nOTeS:
1.		 All	piping	is	schedule	40.
2.		 Pipe	size	listed	are	based	on	a	20°	F	or	40°	F	
differential (temperature drop). Select one to match application.
3.		 When	specified	return	piping	size	is	less	than	3",	
install 3" x 12" nipple and appropriate size bell reducer
directly into boiler return tapping as shown.
4.		 Drain	valve	-	ball	valve	preferable,	gate	valve	acceptable		
	
alternative (supplied by others).
	 	 Minimum	valve	size	per	ASME	code	is	3/4"	NPT.
5. Swing joints on two riser systems may be piped over the
top of the boiler if space is limited.
6. Boilers require protection from flue gas condensation and thermal
	 	 shock	when	operating	below	135°F	return	water	temperatures

BOILeR
MODeL
V1104
V1105
V1106
V1107
V1108
V1109
V1110
V1111
V1112
V1113
V1114
V1115
V1116
V1117
V1118
V1119
V1120
V1121
V1122
V1123

SUppLy pIpInG SIZe In InCHeS
(1B)
(1A)
SUppLy RISeR
SUppLy
(1)
(QTy.) SIZe
HeADeR
SUppLy
20¡ F 40¡ F 20¡ F 40¡ F 20¡ F 40¡ F
DROp DROp DROp DROp DROp DROp
Ñ
Ñ
Ñ
Ñ
2
2-1/2
Ñ
Ñ
Ñ
Ñ
2
2-1/2
Ñ
Ñ
Ñ
Ñ
2
2-1/2
Ñ
Ñ
Ñ
Ñ
2
3
Ñ
Ñ
Ñ
Ñ
2
3
Ñ
Ñ
Ñ
Ñ
2-1/2
4
Ñ
Ñ
Ñ
Ñ
2-1/2
4
Ñ
Ñ
Ñ
Ñ
2-1/2
4
Ñ
Ñ
Ñ
Ñ
3
4
Ñ
Ñ
Ñ
Ñ
3
4
Ñ
Ñ
Ñ
Ñ
3
4
Ñ
Ñ
Ñ
Ñ
3
4
Ñ
(2) 3
Ñ
3
3
5
Ñ
(2) 3
Ñ
3
3
5
Ñ
(2) 4
Ñ
4
4
5
Ñ
(2) 4
Ñ
4
4
5
Ñ
(2) 4
Ñ
4
4
5
Ñ
(2) 4
Ñ
4
4
5
Ñ
(2) 4
Ñ
4
4
5
Ñ
(2) 4
Ñ
4
4
5

5

ReTURn pIpInG SIZe In InCHeS
(2B)
(2A)
ReTURn BRAnCH
ReTURn
(2)
(QTy.) SIZe
HeADeR
ReTURn
20¡ F 40¡ F 20¡ F 40¡ F
20¡ F
40¡ F
DROp DROp DROp DROp DROp
DROp
Ñ
Ñ
Ñ
Ñ
2
2-1/2
Ñ
Ñ
Ñ
Ñ
2
2-1/2
Ñ
Ñ
Ñ
Ñ
2
2-1/2
Ñ
Ñ
Ñ
Ñ
2
3
Ñ
Ñ
Ñ
Ñ
2
3
Ñ
(2) 3
Ñ
3
2-1/2
4
Ñ
(2) 3
Ñ
3
2-1/2
4
Ñ
(2) 3
Ñ
3
2-1/2
4
Ñ
(2) 3
Ñ
3
3
4
Ñ
(2) 3
Ñ
3
3
4
Ñ
(2) 3
Ñ
3
3
4
Ñ
(2)
3
Ñ
3
3
4
Ñ
(2) 3
Ñ
3
3
5
Ñ
(2) 3
Ñ
3
3
5
(2) 3
(3) 3
3
4
4
5
(2) 3
(3) 3
3
4
4
5
(2) 3
(3) 3
3
4
4
5
(2) 3
(3) 3
3
5
4
5
(2) 3
(3) 3
3
5
4
5
(2) 3
(3) 3
3
5
4
5

V11 Series Piping Recommendations
Steam Boiler

pIpInG SIZe In InCHeS
(1)
RISeR
(2)
(3)
(4)
BOILeR
MODeL (QTy.) SIZe ReTURn HeADeR eQUALIZeR
2-1/2
4
2
(1) 4
V1104
2-1/2
4
2
(1) 4
V1105
2-1/2
6
2-1/2
(2) 4
V1106
2-1/2
6
2-1/2
(2) 4
V1107
2-1/2
6
2-1/2
(2) 4
V1108
2-1/2
6
2-1/2
(2) 4
V1109
2-1/2
6
2-1/2
(3) 4
V1110
4
8
3
(3) 4
V1111
4
8
3
(3) 4
V1112
4
8
3
(3) 4
V1113
4
8
3
(4) 4
V1114
4
8
3
(4) 4
V1115
4
8
3
(4) 4
V1116
4
8
3
(4) 4
V1117
4
8
3
(5) 4
V1118
4
10
3
(5) 4
V1119
4
10
3
(5) 4
V1120
4
10
3
(5) 4
V1121
4
10
3
(6) 4
V1122
4
10
3
(6) 4
V1123

RISeR SpACInG In InCHeS
ÔAÕ
Ñ
Ñ
31-1/8
37-1/4
43-3/8
49-1/2
24-3/4
37
37
37
24-3/4
24-3/4
30-7/8
30-7/8
30-7/8
30-7/8
30-7/8
30-7/8
30-7/8
30-7/8

ÔBÕ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
30-7/8
24-3/4
30-7/8
37
24-1/2
24-1/2
36-3/4
36-3/4
24-1/2
24-1/2
24-1/2
24-1/2
24-1/2
24-1/2

ÔCÕ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
30-7/8
37
24-3/4
30-7/8
24-1/2
24-1/2
36-3/4
36-3/4
24-1/2
24-1/2

ÔD Õ
Ô eÕ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
Ñ
24-3/4
Ñ
30-7/8
Ñ
24-3/4
Ñ
30-7/8
24-1/2 24-3/4
24-1/2 30-7/8

nOTeS:
1.	 All	piping	is	schedule	40.
2. To prevent condensate from being trapped in header, do not reduce
equalizer elbow at header connection.
3.	 Drain/blowoff	valve	—	ball	valve	preferable,	gate	valve	acceptable		
alternative (supplied by others).
	 -	Minimum	valve	size	per	ASME	code	is	1"	NPT	(V1104-1106),	1-1/4"		
	 	 NPT	(V1107-1112),	1-1/2"	NPT	(V1113-1123).
- Increasing the valve size will improve the blowdown operation
- In all cases, piping connecting blowoff valve to boiler shall be full
size to the point of discharge.
4.	 Header	piping	may	be	run	over	the	top	of	boiler	if	space	does	not	
allow for piping arrangement shown.
	 However,	increased	service	requirements	will	result.
5. Supply from boiler header must be connected between the first boiler
	 riser	and	the	header	drip	(or	hartford	loop).	Do	not	connect	supply		
between risers or opposite end of boiler header.
6.	 For	pumped	return	systems,	see	V11	installation	manual.

'A'
'B'

'A'

V1106 THRU V1109

V1104 AND V1105

V1 110 THRU V1113

'A'
18"
MIN.

'A'
'A'

'B'

'B'

'C'
'C'

'B'
'C'

'D'

'D'

24"
MIN.

'E'

1
RISER

3
HEADER
4
EQUALIZER
CLOSE NIPPLE

V1114 THRU V1117

V1118 THRU V1121

6

WATER LINE
2" TO 4"
REAR OF BOILER

HARTFORD LOOP
(REQ'D ON GRAVITY
RETURN SYSTEM)

SUPPLY

(SEE NOTE 5)

2
RETURN

V1122 AND V1123

5
BLOWOFF/DRAIN VALVE
(SEE NOTE 3)

V11 Series Burner Schedule
OIL BURneRS
BeCKeTT
CARLIn
pOWeR FLAMe
WeBSTeR
BOILeR
nUMBeR
BURneR MODeL
H.p.
BURneR MODeL
H.p.
BURneR MODeL
H.p.
BURneR MODeL
H.p.
V1104
CF1400
1/2
Ñ
Ñ
CR1-OS
1/2
JB1O-03
1/3
V1105
CF1400
1/2
702CRD
1/2
CR1-OS
1/2
JB1O-03
1/3
V1106
CF1400
1/2
702CRD
1/2
CR2-OAS
3/4
JB1O-03
1/3
V1107
CF2300
3/4
801CRD
3/4
CR2-OAS
3/4
JB1O-05
1/2
V1108
CF2300
3/4
801CRD
3/4
CR2-OAS
3/4
JB1O-05
1/2
V1109
CF2300
3/4
801CRD
3/4
CR2-OAS
3/4
JB1O-07
3/4
V1110
CF2300
3/4
1050FFD
1
CR2-OAS
1-1/2
JB1O-07
3/4
V1111
CF2300
3/4
1050FFD
1
CR3-O
2
JB2O-10
1
V1112
CF2500
2
1050FFD
1-1/2
CR3-O
2
JB2O-10
1
V1113
CF2500
2
1050FFD
1-1/2
CR3-O
2
JB2O-10
1
V1114
CF3500
2
1150FFD
1-1/2
CR3-O
2
JB2O-10
1
V1115
CF3500
2
1150FFD
1-1/2
CR3-O
2
JB2O-10
1
V1116
CF3500
2
1150FFD
1-1/2
CR3-O
3
JB2O-15
1-1/2
V1117
Ñ
Ñ
1150FFD
1-1/2
CR3-O
3
JB2O-30
3
V1118
Ñ
Ñ
Ñ
Ñ
CR3-OB
3
JB2O-30
3
V1119
Ñ
Ñ
Ñ
Ñ
CR3-OB
3
JB2O-30
3
V1120
Ñ
Ñ
Ñ
Ñ
CR3-OB
3
JB2O-30
3
V1121
Ñ
Ñ
Ñ
Ñ
CR3-OB
3
JB2O-50
5
V1122
Ñ
Ñ
Ñ
Ñ
CR4-OA
5
JB2O-50
5
V1123
Ñ
Ñ
Ñ
Ñ
CR4-OA
5
JB2O-50
5
STANDARD BURNER MOTOR VOLTAGE: Beckett	–	CF1400,	and	CF2300	are	120/60/1.	CF2500	and	CF3500	are	240/60/3.	Carlin	–	All	sizes	240/60/1.	power Flame	–	CR1-OS	is	
120/60/1.	CR2-OAS	is	240/60/1.	All	others	are	240/60/3.	Webster	–	JB10-03,	JB10-05	and	JB10-07	are	120/60/1.	JB20-10	is	240/60/1.	All	others	are	240/60/3.

GAS BURneRS*
BeCKeTT
pOWeR FLAMe - 'CR'= pOWeR FLAMe - 'JR'=
WeBSTeR
BOILeR
BURneR
MIn. GAS
BURneR
BURneR
BURneR
MIn. GAS
nUMBeR
MODeL
H.p.
pReSS. (In.)
MODeL
H.p.
MODeL
H.p.
MODeL
H.p. pReSS. (In.)
V1104
CG10.6S
1/3
4.6
CR1-G-12
1/3
JR30A-10
1/3
JB1G-03
1/3
6
V1105
CG10.6S
1/3
6.6
CR1-G-12
1/2
JR30A-12
1/3
JB1G-03
1/3
4
V1106
CG15.4S
1/2
6.2
CR2-G-15
1/2
JR50A-15
1/3
JB1G-03
1/3
6
V1107
CG25.2S
3/4
5.2
CR2-G-15
1/2
JR50A-15
1/2
JB1G-05
1/2
5
V1108
CG25.3S
3/4
5.0
CR2-G-15
1/2
JR50A-15
1/2
JB1G-05
1/2
5
V1109
CG25.4S
3/4
5.2
CR2-G-15
1/2
Ñ
Ñ
JB1G-07
3/4
8
V1110
CG25.5S
3/4
5.2
CR2-G-20A
1
Ñ
Ñ
JB1G-07
3/4
8
V1111
CG50.2S
2
5.7
CR3-G-20
1-1/2
Ñ
Ñ
JB2G-10
1
8
V1112
CG50.3S
2
4.3
CR3-G-20
1-1/2
Ñ
Ñ
JB2G-10
1
6
V1113
CG50.3S
2
5.7
CR3-G-20
1-1/2
Ñ
Ñ
JB2G-10
1
7
V1114
CG50.4S
2
5.7
CR3-G-20
1-1/2
Ñ
Ñ
JB2G-15
1-1/2
8
V1115
CG50.5S
2
5.0
CR3-G-20
1-1/2
Ñ
Ñ
JB2G-30
3
8
V1116
CG50.5S
2
5.3
CR3-G-25
3
Ñ
Ñ
JB2G-30
3
8
V1117
CG50.5S
2
6.1
CR3-G-25
3
Ñ
Ñ
JB2G-30
3
9
V1118
CG50.5S
2
6.9
CR3-G-25B
3
Ñ
Ñ
JB2G-30
3
10
V1119
CG50.5S
2
7.3
CR3-G-25B
3
Ñ
Ñ
JB2G-30
3
11
V1120
Ñ
Ñ
Ñ
CR3-G-25B
3
Ñ
Ñ
JB2G-30
3
12
V1121
Ñ
Ñ
Ñ
CR3-G-25B
3
Ñ
Ñ
JB2G-50
5
14
V1122
Ñ
Ñ
Ñ
CR4-G-25
3
Ñ
Ñ
JB2G-50
5
15
V1123
Ñ
Ñ
Ñ
CR4-G-25
3
Ñ
Ñ
JB2G-50
5
16
STANDARD BURNER MOTOR VOLTAGE: power Flame C Series–CR1-G-12	and	CR2-G-15	are	120/60/1.	CR2-G-20A	is	240/60/1.	All	others	are	240/60/3.	power Flame JR Series
–	All	burners	are	120/60/1.	Webster–JB1G-03,	JB1G-05	and	JB1G-07	are	120/60/1.	JB2G-10	is	240/60/1.	All	others	are	240/60/3.		
*	For	inlet	gas	connection	size,	see	Gas/Oil	Burner	Chart					=	For	minimum	gas	pressure	requirements,	see	Gas/Oil	Burner	Chart.

GAS/OIL BURneRS
pOWeR FLAMe - 'CR' SeRIeS
WeBSTeR
BOILeR
BURneR
InLeT GAS
MIn. GAS
BURneR
InLeT GAS
MIn. GAS
nUMBeR
MODeL
H.p. COnneCTIOn (In.) pReSS. (In.)
MODeL
H.p. COnneCTIOn (In.) pReSS. (In.)
V1104
CR1-GO-12
1/2
1
4.7
JB1C-03
1/3
1
7.0
V1105
CR1-GO-12
1/2
1
4.8
JB1C-03
1/3
1-1/4
4.9
V1106
CR2-GO-15
3/4
1
5.4
JB1C-03
1/3
1-1/4
7.0
V1107
CR2-GO-15
3/4
1
6.4
JB1C-05
1/2
1-1/4
6.2
V1108
CR2-GO-15
3/4
1
7.5
JB1C-05
1/2
1-1/2
6.9
V1109
CR2-GO-15
3/4
1-1/4
6.4
JB1C-07
3/4
1-1/2
7.0
V1110
CR2-GO-20A 1-1/2
1-1/4
5.8
JB1C-07
3/4
1-1/2
7.0
V1111
CR3-GO-20
2
2
5.8
JB2C-10
1
2
6.3
V1112
CR3-GO-20
2
1-1/2
6.0
JB2C-10
1
2
5.6
V1113
CR3-GO-20
2
1-1/2
6.8
JB2C-10
1
2
6.3
V1114
CR3-GO-20
2
1-1/2
7.4
JB2C-10
1
2
7.0
V1115
CR3-GO-20
2
1-1/2
7.3
JB2C-10
1
2
6.8
V1116
CR3-GO-25
3
2
6.6
JB2C-15 1-1/2
2
7.0
V1117
CR3-GO-25
3
2
7.1
JB2C-30
3
2
7.3
V1118
CR3-GO-25B
3
2
7.7
JB2C-30
3
2-1/2
8.1
V1119
CR3-GO-25B
3
2-1/2
6.5
JB2C-30
3
2-1/2
9.2
V1120
CR3-GO-25B
3
2-1/2
7.0
JB2C-30
3
2-1/2
10.0
V1121
CR3-GO-25B
3
2-1/2
7.0
JB2C-50
5
2-1/2
11.0
V1122
CR4-GO-25
5
2-1/2
6.3
JB2C-50
5
2-1/2
12.4
V1123
CR4-GO-25
5
2-1/2
6.9
JB2C-50
5
2-1/2
13.1
STANDARD BURNER MOTOR VOLTAGE: power Flame	-	CR1-GO-12	is	120/60/1.	CR-2-GO-15	and	CR2-GO-20A	are	240/60/1.	All	others	are	240/60/3.		Webster–JB1C-03,	JB1C05,	JB1C-07	are	120/60/1.	JB2C-10	is	240/60/1.		All	others	are	240/60/3.
**For	minimum	gas	pressure	requirements,	see	Gas	Burner	Chart.		NOTES:			1.	The	minimum	gas	pressures	shown	are	for	standard	UL	burners	with	the	standard	firing	sequence.	IRI,	FM	
and	CSD-1	requirements	may	result	in	different	pressures	and	prices.

7

Specifications
V11 RATInGS
BOILeR
MODeL
(1)
V1104
V1105
V1106
V1107
V1108
V1109
V1110
V1111
V1112
V1113
V1114
V1115
V1116
V1117
V1118
V1119
V1120
V1121
V1122
V1123

GROSS
OUTpUT
MBH
BOILeR
(2)
H.p.
667
19.9
857
25.6
1069
31.9
1281
38.3
1517
45.3
1729
51.7
1941
58.0
2154
64.3
2334
69.7
2503
74.8
2730
81.6
2957
88.3
3129
93.4
3353
100.2
3580
106.9
3739
111.7
3957
118.2
4174
124.7
4334
129.5
4551
136.0

I=B=R neT RATInG (3)
STeAM
MBH
500
643
802
963
1159
1335
1507
1672
1812
1943
2120
2296
2427
2603
2780
2903
3072
3241
3365
3533

SQ. FT.
2083
2679
3342
4013
4829
5563
6279
6967
7550
8096
8833
9567
10113
10846
11583
12096
12800
13504
14021
14721

WATeR
MBH
580
745
930
1114
1319
1503
1688
1873
2030
2177
2374
2571
2718
2916
3113
3251
3441
3630
3769
3957

BURneR InpUT
OIL
GpH
(4)
5.8
7.4
9.2
11.0
13.0
14.8
16.6
18.4
20.0
21.5
23.5
25.5
27.0
29.0
31.0
32.5
34.5
36.5
38.0
40.0

GAS
MBH
837
1068
1328
1588
1876
2136
2396
2656
2887
3103
3392
3680
3897
4186
4474
4691
4979
5268
5485
5733

neT
FIReBOX
VOLUMe
(In. WTR.
COLUMn)
7.9
10.6
13.2
15.9
18.5
21.1
23.8
26.5
29.1
31.8
34.4
37.1
39.7
42.4
45.0
47.7
50.3
53.0
55.6
58.3

pReSSURe
In
FIReBOX
(In. WTR.
COLUMn)
.35
.36
.37
.42
.42
.39
.42
.40
.42
.40
.38
.36
.38
.41
.39
.38
.38
.40
.41
.43

I=B=R
VenT DIA.
(In.)
8
8
8
10
10
10
12
12
12
12
14
14
14
14
16
16
16
16
18
18

AppROX.
SHIppInG
AnD LIFTInG
WeIGHT
(LBS.)
2105
2510
2920
3325
3733
4147
4557
4964
5374
5771
6184
6601
7008
7417
7823
8231
8638
9053
9456
9865

1.	 Suffix	“S”	indicates	steam	boiler,	“W”	indicates	water	boiler.	Suffix	“G”	indicates	gas-fired,	“O”	indicates	oil	fired	and	“GO”	indicates	combination		
gas/oil fired.
2.	 Boiler	ratings	are	based	on	13%	CO2	on	oil;	10.0%	CO2	on	gas,	and	+	.10	in.	water	column	pressure	at	boiler	flue	outlet.
3.	 I=B=R	net	ratings	shown	are	based	on	piping	and	pick	up	allowances	which	vary	from	1.333	to	1.288	for	steam	and	1.15	for	water.	Consult	
manufacturer for installations having unusual piping and pick up requirements, such as intermittent system operation, extensive piping systems, etc.
4.	 The	I=B=R	burner	capacity	in	GPH	is	based	on	oil	having	a	heat	value	of	140,000	BTU	per	gallon.
Ratings	shown	above	apply	to	altitudes	up	to	1000	feet	for	oil	and	2000	feet	for	gas.	For	altitudes	above	those	indicated,	the	ratings	should	be	reduced	
at	the	rate	of	4%	for	each	1000	feet	above	sea	level.
nOTe: 	 Maximum	allowable	working	pressure	(MAWP):	
	
Steam:	 	
15	PSI
	
Water	–	USA:	
80	PSI	(Standard	relief	valve	provided	is	50	PSI)	(80	PSI/30	PSI	Optional)
	
Water	–	Canada:	 50	PSI	(Standard	relief	valve	provided	is	50	PSI)	(30	PSI	Optional)

STAnDARD eQUIpMenT
ALL BOILeRS:	Sections	unassembled,	flush	insulated	jacket,	burner	mounting	plate,	rear	observation	port	cover,	fire	wall	plates,	target	wall	(V1104-1106	
only), rear flue outlet damper (top outlet optional), flue canopy, trim, and miscellaneous plugs, bushing and fittings
STeAM TRIM:	15	PSI	safety	valve,	L404F	pressuretrol,	gauge	glass	assembly,	steam	gauge
WATeR TRIM:	50	PSI	safety	relief	valve,	L4006A	high	limit,	pressure	temperature	gauge
OIL BOILeRS:	Flange	mounted	flame	retention	oil	burner	furnished	with	2	stage	fuel	unit,	primary	control	and	dual	oil	valves
GAS BOILeRS:	Flange	mounted	gas	burner	with	standard	controls	meeting	the	latest	UL	requirements,	dual	gas	valves,	gas-electric	ignition	with	proven	
gas	pilot,	flame	rod	on	JR	burner,	ultra	violet	flame	detector	on	others,	electronic	programming	controls	and	components	are	factory	wired	in	a	burner	
mounted	control	panel	(except	JR	-	panel	available	as	an	option)
GAS/OIL BURneRS:	Flange	mounted	combination	gas/oil	burner	with	standard	controls	meeting	latest	UL	requirements,	manually	operated	fuel	transfer	
switch for dual fuel changeover, dual gas valves and oil valves, electric ignition with proven gas pilot on both fuels (direct spark ignition of oil is optional), ultra-violet flame detector, electronic programming controls and components are factory wired in a burner mounted control panel

OpTIOnAL eQUIpMenT
Assembled sections; completely packaged (includes manual reset high limit and manual reset low water cutoff); packaged and fire-tested; top outlet flue
damper;	tankless	heaters;	side	inspection	tappings	with	brass	plugs;	pressure	relief	door;	30	PSI	and	80	PSI	safety	relief	valves;	combustion	and	hydronic	
controls	to	meet	special	applications	including	F.M.,	I.R.I.,	and	ASME	CSD-1.

Burnham	Commercial	-	Lancaster,	PA
Phone:	-888-791-3790
www.burnhamcommercial.com

8



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Modify Date                     : 2011:07:08 11:55:45-04:00
Create Date                     : 2011:06:29 16:50:36-04:00
Metadata Date                   : 2011:07:08 11:55:45-04:00
Creator Tool                    : Adobe InDesign CS4 (6.0)
Format                          : application/pdf
Document ID                     : uuid:0e70e3e0-4158-419b-b25c-b415e632f2fd
Instance ID                     : uuid:18f2c5da-1ec1-4155-bd04-8f545221032b
Producer                        : Adobe PDF Library 9.0
Page Count                      : 8
Creator                         : Adobe InDesign CS4 (6.0)
EXIF Metadata provided by EXIF.tools

Navigation menu