CARRIER Controls And HVAC Accessories Manual L0210356

User Manual: CARRIER CARRIER Controls and HVAC Accessories Manual CARRIER Controls and HVAC Accessories Owner's Manual, CARRIER Controls and HVAC Accessories installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

H_/7#JG &Og*DLMG
Visit www.camer.com
Thermidistaff M Control
Installation, Start-Up, and Operating Instructions
NOTE: Read the entire instruction manual before starting the
installation.
This symbol --> indicates a change since the last issue.
INDEX
Page
SAFETY CONSIDERATIONS ..................................................... 1
INTRODUCTION .......................................................................... 1
INSTALLATION CONSIDERATIONS ....................................... 1
INSTALLATION ........................................................................ 2-8
Thermidistat Cuntro! Location ................................................. 2
Set DIP Switches ...................................................................... 2
Install Tl_rta_distat Contro! .................................................. 2-3
Set Thermidistat Control Configuration ............................... 3-7
System Start-Up and Checkout ............................................. 7-8
Final Settings ............................................................................ 8
HUMIDITY CONTROL FEATURES ..................................... 8-11
Humidification .......................................................................... 8
Dehumidification ................................................................. 9- I0
Vacation ............................................................................. 10-1 I
OPERATIONAL INFORMATION ............................................. 11
THERMIDISTA T CONTROL TROUBLESHOOTING ............ l 1
THERMIDISTAT CONTROL CONFIGURATION RECORD. 12
WIRING DIAGRAM .............. See Thermidistat Wiring Diagrams
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or installa-
tion may damage Thermidistat Control.
Recognize safety information. This is the safety-alert symbol Z_.
When you see this symbol on the equipment and in the instruction
manual, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING. and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in person_ injury or de,._b. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
INTRODUCTION
Carrier's 7-day programmable/non-programmable Thermidistat
Control is a wall-mounted, low-voltage control which combines
temperature and humidity control in a single attractive unit. An
extension of Carrier's proven line of thermostats, it provides
separate set points for heating and cooling, and now adds humidi-
fiealioD 9DO de_u!q_idJEwalion, l_fferem he,_jng and cooling set
points and times are programmable for 4 periods per day and 7
days per week. The Thermidistat Control can also be field-
configured as a non-programmable thermostat. When operating in
the non-programmable configuration it will still have both tem-
perature and humidity control. Humidify and dehumidify outputs
provide direct control of humidity. Batteries are not used. During
power loss an internal memory stores programs and settings for
unlimited time, and the clock continues to ran for at least 8 hr.
A98426
,E,Q,r(I,.) IWIOT,(I..) I OEPTH(,..)
4-3/8 [ 7-3/8 [ 1-3/8
Fig. l_Thermidistat Control
INSTALLATION CONSIDERATIONS
POWER
Note that this control does not require batteries and is not "power
stealing." It does require 24vac (R and C terminals) of the
low-voltage transformer to be connected to it for proper operation.
It will not operate without these 2 connections.
MODELS
There is a single programmable/non-programmable model for all
applications. It can be configured for AC or HP, 1- or 2-speed
compressor, and for dual fuel installations, allowing it to be used
in place of all Cartier thermostats.
HUMIDIFY EQUIPMENT AND CONNECTIONS
The humidify output connects directly to 24vac operated humidi-
tiers. No other connection or interlock is required. Any of several
installer-selectable operating modes are available.
-->
DEHUMIDIFY EQUIPMENT AND CONNECTIONS
The dehumidify output connects to the dehumidify input on
variable-speed furnaces and fan coils. Additional dehumidification
is done by controlling the compressor. A variety of operating
modes are available.
OUTDOOR TEMPERATURE SENSOR
Optimum performance is obtained when an outdoor temperature
sensor is used with the Thermidistat Control. Plan installation so
that 2 wires can be ran from Thermidistat Control to an outdoor
location, preferably on the north side of the house or refer to
Installation Instructions included with the outdoor temperature
sensor for simplified connection. Sensor can be mounted to
outdoor unit and existing control wires may be used for its
connection. Details are provided in sensor instructions.
Manufacturer reserves the dght to discontinue, or change at any Ume, specifications or designs without notice and without Incurring obligations.
TabB°°k[1 [4::misc. misc. PC t0t Catalog NO. 03TS-TAt 7 Printed In U.S.A, Form TSTAT-23SI Pgl 8-99 Replaces: TSTAT-1 tiSI
INSTALLATION
Step 1--Thermidistat Control Location
Thermidistat Control should be mounted:
Approximately 5 ft (1.Sm) from floor.
Close to or in a frequently used room. preferably on an inside
partitioning wall.
On a section of wall without pipes or duct work.
Tbermidistat Control should NOT be mounted:
Close to a window, on an outside wall, or next to a door leading
to the outside.
Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperatare-radiating objects which could cause a false
reading.
Close to or in direct airflow from supply registers and return-air
registers.
In areas with poor air circulation, such as behind a door or in
an alcove.
Step 2---Set DIP Switches
There is a 4 section DIP switch within the Thermidistat Control
which must be properly set by the installer. It is easiest to set these
4switches before the Tbermidistat Control is mounted to the wall,
so STOP and complete the following steps:
1. Open hinged Thermidistat Control cover.
2. Remove cover completely by snapping it apart at hinge.
3. Open Thermidistat Control by pressing back half of the fight
end of plastic case inward while, at the same time. pulling
front and back halves apart at the right end. The 2 halves will
swing apart.
4. Snap hinge apart to completely separate the 2 halves.
5. Switches are located in upper right corner of circuit board. To
change switch position, use corner of a small screwdriver to
slide switch to opposite position.
6. After switches have been set, do not reassemble the 2 halves.
The rear plastic will first be mounted to the wall.
SWITCH I--AC!HP SELECT
Use this switch to select between air conditioner and heat pump
systems.
TO SET:
OFF--for air conditioner installations. This is factory default.
ON--for heat pump installations, using either a fan coil or furnace
(dual fuel).
SWITCH 2--1 SPEED/2 SPEED
This switch tells the system whether the compressor is 1 or 2
speed.
TO SET:
OFF--for single-speed compressor. This is factory default.
ON--for 2-speed compressors, whether AC or HP.
SWITCH 3--SMART/CONVENTIONAL RECOVERY
Selects between conventional and smart recovery from setback.
Conventional recovery changes to new set point at programmed
time. Smart recovery, which is active in both heating and cooling.
starts 90 minutes earlier and smoothly adjusts set point so room
will arrive at programmed temperature at programmed time.
TO SET:
OFF--for smart recovery. This is factory default.
ON_oc conventional recovery.
SWITCH 4--INSTALLER TEST OFF/ON
Selects a special installer test mode which assists with system
startup and checkout. See Step 5, System Startup and Cbeck-out.
TO SET:
OFF--for normal operation. This is factory default.
ON--for installer test mode.
Step 3--Install Thermidistat Control
1. Turn off all power to equipment.
2. If an existing thermostat is being replaced:
a. Remove existing thermostat from wall.
b. Disconnect wires from existing thermostat. 1at a time.
c. As each wire is disconnected, record wire color and
terminal marking.
d. New or additional wire may be needed to accommodate
added humidity outputs.
e. Discard or recycle old thermostat,
NOTE: Mercury is a hazardous waste and MUST be disposed of
properly.
3. Select Thermidistat Control rear plastic. (If it is not separated
from the remainder of the Thermidistat Control. refer to Step
2 above.)
4. Route wires through large hole in rear plastic. Level rear
plastic against wall (for aesthetic value only--Thermidistat
Control need not be leveled for proper operation) and mark
wall through 2 mounting holes.
5. Drill two 3/16-in. mounting holes in wall where madced.
6. Secure rear plastic to wall with 2 screws and anchors
provided. Additional mounting holes are available for more
secure mounting if needed. Make sure all wires extend
through hole in mounting base.
7. Adjust length and rooting of each wire to reach proper
connector block and terminal on rear plastic with l/4-in, extra
length. Strip only 1/4 in. of insulation from each wire to
prevent adjacent wires from shorting together when con-
nected.
8. Match and connect equipment wires to proper terminals of
each connector block. (See Low Voltage Wiring Diagram
Reference Chart and Figs. 1 through 28 in separate Wiring
Diagram literature). Remember R and C must be connected
for proper operation.
2
9. Push any excess wire into wall and against rear plastic. Seal
hole in wall to prevent air leaks. Leaks can affect operation.
!0. Reattach Thermidistat Control body to rear plastic by first
reattaching hinge.
l 1. Close Thermidistat Control assembly, making sure pins on
back of circuit board align with sockets in connector.
12. Turn on power to equipment.
On power up, all display segments will light for 5 sec. For the next
5 sec, a 2-digit code appears on large display which identifies
Thermidistat Control configuration:
1. AC--for l-speed air conditioner
2. HP--for l-speed heat pump
3.A2--for 2-speed air conditioner
4. H2--for 2-speed heat pump
5. dF--for l-speed dual fuel
6. d2--for 2-speed dual fuel
7. HS--for I-speed heat pump with Intelligent Heat Staging
(3-stage auxiliary heat with 40FK, FK4C, or FV4A Series fan
coils.)
When _his identifier disappears, normal operation begins. The
MODE control should be set to OFF and FAN control to AUTO,
so equipment does not start until further confguration and check-
out is completed.
Step 4---Set Thermidistat Control Configuration
Configuration options, like DIP switch settings, are intended to be
selected at installation and normally are not modified by the
homeowner. These options are not discussed in the homeowner's
manual and therefore must be made as part of the installation. A
special procedure allows entry into the configuration mode. While
in configuration mode, up to 17 selections can be made. A
description of each selection and how to use the configuration
mode follows.
CONFIGURATION OPTIONS -- SUMMARY:
Option 1--Anticipator adjustment
Option 2--Clean filter timer adjustment
Option 3--English/Metric selection
Option 4---Fan (G) ON with W selection
Option 5_Variable-speed blower present selection
Option 6---Cooling lockout below 55" selection
Option 7--Variable-speed super dehumidification selection (only
available when variable-speed blower is used)
Option 8--Auxiliary heat lockout temperature setting (only avail-
able when heat pump is used)
Option 9--Intelligent Heat Staging selection (only available when
single-speed heat pump is used)
Option 10_Dual Fuel selection (only available when heat pump is
used)
Option 11--Balance point setting (only available when Dual Fuel
is selected)
Option 12_Defrost heat selection (only available when heat pump
is used)
Option 13_Room temperature offset adjustment
Option 14---Heat/eonl dead band adjustment
Option 15--Enable Auto mode
Option 16---Enables Super Comfort Heat Mode
Option 17_Non-Programmable selection
TO ENTER CONFIGURATION MODE:
Press and hold FAN button for approximately 10 sec until COOL
set point display indicates aflashing 1. The Thermidistat Control
is now in configuration mode. It will automatically exit this mode
if no button is pressed for 3 minutes. Pressing END button will exit
configuratioh mode immediately.
WHILE IN CONFIGURATION MODE:
The upper small (COOL set point) display indicates selected
option number and large display indicates selection made within
that option. One of these will be flashing. The up and down buttons
are used beth to move between available options and to make
selection for each option. When option number (small display) is
flashing, up and down buttons adjust it, moving between available
option numbers, After desired option number has been selected,
press SET TIME/TEMP button once. The large display will now
flash, indicating that up and down buttons now control available
choices within that option. Each press of TIME/TEMP button
switches between available option (small display) and available
selections within each option (large display).
CONFIGURATION OPTIONS -- SELECTION:
Option l--Anticlpator Adjustment
This adjustment controls sensitivity and cycle rate of Tbermidistat
Control. Higher numbers decrease sensitivity and slow cycle rate.
Lower numbers increase sensitivity and cycle rate. However, a
limiting feature will not allow more than 4 cycles per hr, regardless
of setting. Anticipator values can range from i to 9. Factory
default is 3. This default selection provides optimum performance
in nearly all installations. Try it first. Do not change setting unless
there is evidence of need to do so.
Unlike conventional anticipators, this setting is not determined by
current draw. There is no need to measure, know, or compensate
for current draw. There is also no droop with this Thermidislat
Control. Regardless of setting and number of stages, both heating
and cooling will control to their respective set points.
TO ADJUST:
1. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." The upper small (COOL set
point) display will be flashing 1. If not, use up and down
buttons to move it to i.
2. Press SET TIME/TEMP button once to flash current selection
of 1, 2, 3, 4, 5, 6, 7, 8, or 9 on large display. Factory default
is 3.
3. Use up and down buttons to move between available choices.
4. Press SET TIME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 2---Clean Filter Timer
Select hours of blower operation (heating, cooling, or fan) before
CLEAN FILTER icon is displayed. With OFF selected, icon will
never come on. disabling this feature. Time selection can range
from 400 to 3600 hr by selecting numbers 1 through 9. (Time is
400 X number selected.) Factory default is 2 (800 hr). Recom-
mended selections are: disposable filter_00 to 800 hr, media
filter--1200 to 1600 hr, or electronic air cleaner--1600 to 2400 hr
of blower operation.
TO SELECT OR ADJUST:
I. Enter configuration mode if not already there. See Step 4"To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 2.
2. Press SET TIME/TEMP button once to flash current selection
of OF, 1, 2, 3, 4, 5, 6, 7, 8, or 9 on large display. Factory
default is 2.
3. Use up and down buttons to move between available choices.
4. Press SET T1ME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 3----English/Metric
Select between Fahrenheit and Celsius operation. Factory default
is Fahrenheit.
TO SELECT OR ADJUST:
1. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 3.
2. Press SET TIME/TEMP button once to flash current selection
of F or C. Factory default is F.
3. UseupanddownbuttonstomovebetweenFandConlarge
display.
4. PressSETTIME/TEMPbuttonagainto flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 4---Fan (G) On With W
This selection deternaines whether fan (G) output is to be ON or
OFF when any W (furnace or strip heat) output is ON. Most
furnaces and fan coils manage their own blowers and do not
require separate G signal. For these applications, ,select OFF. Some
auxiliary heaters require separate G signal to turn on blower. In
this ease, select ON. Factory default is OF (off).
TO SELECT:
1. Enter configuration mode if not already there, See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 4.
2. Press SET TIME/q_MP button once to flash large display.
3. Use up or down buttons to alternate between OF and ON on
large display. Factory default is OF.
4. Press SET TIME.rI'EMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 5----Varlable-Speed (ICM) Blower
[f furnace or fan coil contains a variable-speed (ICM) blower, set
this option to ON. For normal (PSC) blowers, set to OF. This
selection enables system to use special features available only in
units with an ICM blower. Factory default is OF (off).
TO SELECT:
I. Enter configuration mode if not already there, See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 5.
2. Press SET T1ME/TEMP button once to flash large display.
3. Use up or down buttons to alternate between OF and ON on
large display. Factory default is OF.
4. Press SET TIME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 6---Cooling Lockout Below 55°F
This optioo disables cooling when outdoor temperature is below
55°F. It requires an outdoor temperature sensor. Set to OF to allow
cooling below 55°F. Set to ON to prevent cooling below 55°F.
Factory default is OF (off).
TO SELECT:
I. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 6.
2. Press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to alternate between OF and ON on
large display. Factory default is OF.
4. Press SET TIME/"I_MP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 7--Variable-Speed Superdehumidify
This option requires prior selection of varlable-speed (ICM)
blower (Option 5). When selected, this option operates blower at
further reduced airflow from that of normal dehumidification when
there is a dehumidification demand without a cooling demand,
achieving maximum humidity removal with minimum cooling. It
is done by supplying blower with a Y signal and no G signal on a
call for cooling. Not all products with ICM blowers have this
feature. Check Installation Instructions for ICM air handier used.
Select OF for normal operation (Y and G supplied on a cooling
call). Select ON for super dehumidification (Y with no G on a
dehumidify only call). Factory default is OF (off).
TO SELECT:
1. Enter configuration mode if not already there. See Step 4"To
Enter Configuration Mode," Use up and down buttons to make
small (now flashing) display indicate 7.
2.
3.
4.
Press SET TIMEtTEMP button once to flash large display.
Use up or down buttons to alternate between OF and ON on
large display. Factory default is OF.
Press SET TIME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 8--Auxiliary Heat Lockout Setting
This option requires prior selection of heat pump (DIP switch 1--
ON). It allows selection of an outdoor temperature of 5°through
55°F. (or equivalent values in C), or OF (off). Auxiliary heat
(furnace in Dual Fuel applications) is prevented from operating for
outdoor temperatures above selected temperature. If OF (off) is
selected, auxiliary heat (furnace if Dual Fuel) operation is allowed
at all outdoor temperatures. If selected, emergency heat (EHEAT)
overrides this feature. Factory default is OF (off). This setting can
only be equal to or above the setting choice made for Option 11.
Moving this setting lower may 'push' Option 1l setting down-
ward.
TO SELECT:
1. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 8.
2. press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to move between OF, 5, 10, 15, 20.
25, 30, 35.40, 45.50, or 55 on large display. Factory default
is OF.
4. Press SET TIMEdlEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 9---Intelligent Heat Staging
This option requires prior selection of single-speed heat pump
(DIP switch l---ON, DIP switch 2--OF). It provides 3 stages of
electric heat from W1 and W2 by sequencing Wl only, then W2
only, then both WI and W2. See FK or FV Series Fan Coil
Installation Instructions for further information. For 3-stage heat,
select ON. For normal I- or 2-stage heat, select OF. Factory
default is OF (off).
TO SELECT:
1. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 9.
2. Press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to alternate between OF and ON on
large display. Factory default is OF.
4. Press SET TIME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
4
Option 10.--Dual Fuel Equipment
The high pressure switch protects compressor and indoor coil from
overpressare which would occur if a failure or wiring error
resulted in the heat pump and furnace operating at the same time.
High Pressure Switch Kit includes required switch and instructions
for proper operation. For all dual fuel installations, outdoor
temperature sensor must be attached. If not, E3 error message will
appear. See "Error Codes."
This option requires prior selection of heat pump (DIP switch
1--<)N), and must be selected in dual fuel installations. It prevents
simultaneous operation of both furnace and heat pump, and
prevents direct transition from heat pump to furnace operation.
When system is dual fuel (heat pump and furnace), set to ON.
When system contains fan coil, set to OF. Factory default is OF
(off).
TO SELECT:
1. Enter configuration mode if not already there. See Step 4 'To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 10.
2. Press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to alternate between OF and ON on
large display. Factory default is OF.
4. Press SET TIMEFI'EMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option ll--Balanee Point Setting
This option is for dual fuel installations only. It requires prior
selection of heat pump (DIP switch 1 -- ON) and dual fuel
equipment (Option 10 -- ON). It allows selection of an outdoor
temperature of 5°F. through 55°F. (or equivalent values in C.), or
OF (off). Heat pump is prevented from operating for outdoor
temperatures below selected temperature. If OF (off) is selected,
beat pump operation is allowed at all outdoor temperatures.
Factory default is OF (off). This setting can only be equal to or
below the setting choice made for Option 8. Moving the setting
higher may "push' Option 8setting upward.
If the outdoor temperature is above the "balance point setting", the
heat pump will energize first to try to satisfy the indoor tempera-
ture demand. If the heat pump does not make a sufficient
improvement within a reasonable time period (i.e. 15 minutes),
then the gas furnace will come on to satisfy the indoor temperature
demand. If the outdoor temperature is below the "balance point
setting" the heat pump will not be allowed to operate (i.e. locked
out), and the gas furnace will be used to satisfy the indoor
temperature.
There are three separate concepts which are related to selecting the
final "balance point setting". Read each of the following carefully
to determine the best "balance point setting" in a dual fuel
installatiom
CAPACITY BALANCE TEMPERATURE:
This is the point where the beat pomp cannot provide sufficient
capacity to keep up with the indoor temperature demand because
of declining outdoor temperature. At or below this point, the
furnaceis needed to maintain proper indoor temperature.
ECONOMIC BALANCE TEMPERATURE:
Above this point, the heat pump is the most cost efficient to
operate, and below this poinL the furnace is the most cost efficient
to operate. This can be somewhat complicated to determine and it
involves knowing the cost of gas and electricity, as well as the
efficiency of the furnace and heat pump. For the most economical
operation, the heat pump should operate above this temperature
(assuming it has sufficient capacity), and the furnace should
operate below this temperature.
COMFORT BALANCE TEMPERATURE:
When the heat pump is operating below this point, the indoor
supply air feels uncomfortable (i.e. too cool). This is purely
subjective and will depend on the homeowner's idea of comforl.
Below this temperature, the gas furnace should operate in order to
satisfy the desire of indoor comtort.
TO SELECT:
I. Enter configuration mode if not already there. See Step 4"To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 1l.
2. Press SET TIMFJTEMP button once to flash large display.
3. Use up or down buttons to move between OF, 5, i0, 15.20,
25, 30, 35, 40, 45.50. or 55 on large display. Factory default
is OF.
4. Press SET TIME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 12---Defrost Heat Select
This option allows installer to select the amount of heat provided
by Thermidistat Control during a heat pump defrost cycle. This can
be very helpful in maintaining a comfortable leaving air tempera-
ture during defrost. The Thermidistat Control senses when defrost
is in progress by monitoring voltage placed on the O line by the
heat pump while defrosting. It responds by turning on selected
combination of WI and W2 during defrost. Note that this is very
different from the operation of an ordinary thermostat, which
cannot sense defrost in progress and only turns on its W outputs in
response to a temperature demand. Combinations of WI and W2
are selected via the following:
Table 1--Wl IW2 Outputs
SELECTION DEFINITION
Neither W1 or W2 is turned on.
0 This is factory default,
1 Only W1 is turned on.
2 Both W1 and W2 turned on.
Only W2 turned on (available
3 only if 3-stage heat is selected).
The selection procedure is given below. If 0 is selected, operation
is like that of an ordinary thermostat, and a wire is required
between W2 of outdoor unit and a selected W on indoor unit.
When selection l, 2, or 3 is made, no wire should be connected
from outdoor W2 because this connection may override selection
made. Obviously the heater must be in 2sections, and fan coil
jumper must be removed between WI and W2 for there to be a
difference between selections l, 2, and 3. For most heaters, Wl is
lower wattage heater, .and W2 is higher, although some have equal
elements for WI and W2. Consult fan coil/heater combination for
the actual wattage connected to each of Wl and W2.
In dual fuel applications, above selection choices apply and can be
used to select low or high heat if furnace is 2 stage. WI will
produce low heat. WI and W2 together produce high heat. This
option provides no value with single-stage furnaces because only
1 value of heat is available.
The selection choices guarantee selected outputs will be on during
defrost. If room temperature demand requires additional heat, it
wiltbesupplied,resulting in additional outputs being turned on, If
room overheats, specified outputs will not turn off, guaranteeing a
sufficiently warm leaving air temperature during defrost. Tempera-
ture overshoot during defrost can occur, but is almost never
noticeable because of the short duration of the defrost cycle (4
minutes typical, 10 minutes maximum).
An additional feature of Thermidistat Control defrost is that it
always allows defrost cycle to run to completion. The Thermidistat
Control leaves the Y output on as long as outdoor unit holds
voltage on the O line. even if it is satisfied. This prevents
premature termination of defrost cycles, which occur with normal
thermostats.
TO SELECT:
1. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." Use up and clown buttons to make
small (now flashing)display indicate 12.
2. Press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to move between 0, 1, 2, or 3 (if
available) on large display. See Table 1 for effect of these
choices. Factory default is 0.
4. Press SET TIME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 13---Room Temperature Offset Adjust
This option allows calibration (or deliberate miscalibration) of
room temperature sensor. There are various reasons why home-
owners may want to have displayed temperature adjusted to a
higher or lower value. The selected number is number of degrees
farhenbeit, plus or minus, which will be added to actual tempera-
ture. The numbers can range between -5 and +5. Factory default is
0. This adjusted value will be used as actual temperature for both
display and control action. For example, if 2 is selected, 72°F
actual will read 74°F. If set point is 72°F, the room will control to
an actual temperature of 70°F which will be displayed and acted
upon as if it were 72°F. The effect is that a positive number
selection will make the room temperature lower and vice versa.
The Thermidistat Control is calibrated within an accuracy of plus
or minus I°F when shipped from the factory, so this adjustment
will provide the best accuracy when set to 0.
TO SELECT:
1. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 13.
2. Press SET TIMFJI'EMP button once to flash large display.
3. Use up or down buttons to move between -5, -4, -3, -2, -1, O,
1, 2, 3, 4, or 5on large display. Factory default is O.
4. Press SET TIMFdTEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 14---HeaffCool Dead Band Adjustment
This option selects the minimum difference between heat and cool
set points. A larger difference saves energy and a smaller differ-
ence decreases temperature difference between heating and cool-
ing. Factory default is 2, which means cooling set point must be a
minimum of 2" above heating set point. An attempt to move them
closer will result in one "pushing" the other to maintain the
required difference.
Depending on set points, moving dead band closer than 2°may
resuR in regular cycling between heat and cool when AUTO mode
is selected, However, this cycling cannot occur more often than 1
transition every 20 minutes. The system has a built-in requirement
that it cannot switch between heat and cool without a 20 minute
"off" time between the 2 operations. Specifically, to switch from 1
mode to the other, there must be no demand for the old mode and
a demand for the new mode. and this must exist continually for 20
minutes before transition to the new mode will occur.
TO SELECT:
I. Enter configuration mode if not already there. See Step 4"To
enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 14.
2. Press SET T1ME/TEMP button once to flash large display.
3. Use up or down buttons to move between 0, 1.2.3, 4, 5, or 6
on large display. Factory default is 2.
4. Press SET TIMFJTEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 15---Enable Auto Mode
This option allows the installer to enable or disable AUTO mode
(automatic changeover between heat and cool). When disabled,
AUTO icon does not appear when successive presses of MODE
button are used to move between OFF. HEAT, COOL, and
EHEAT (in heat pump systems). Factory default is ON (AUTO
enabled).
TO SELECT:
1. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small Inow flashing) display indicate 15.
2. Press SET TIME/TEMP button once to flash large display.
3. Use up and down buttons to move between OF and ON on
large display. Factory default is ON (AUTO enabled).
4. Press SET TIMEFI'EMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 16--Enable Super Comfort Heat Mode
--->This option requires prior ON selection of heat pump (DIP switch
No. 1) and Configuration Option No. 5 (Select Variable-Speed
Blower). Super Comfort Heat mode is part of the Comfort Heat
Pump system, which comprises a selected combination of Ther-
midistat Control, variable speed Fan Coil, and 3-stage electric
heater to provide superior heat pump leaving air temperatures
under all conditions. This option selection modifies heat pump
blower and auxiliary heat operation to contribute to comfortable
leaving air temperature. Specifically, this selection provides:
Reduced heat pump airflow for outdoor temperatures between
12° and 40°F.
At least 1 stage of electdc heat ON for all heating below 12°F.
-'-)'While outdoor air temperature is between 12°F and 40°F, the
Therraidistat Control removes the G signal during heat pump
heating. The 40FK, FK4C, or FV4A Variable-Speed Fan Coils
respond by reducing their airflow in the absence of the G signal,
raising leaving air temperature. For any heating demand below
12°F, G and W/WI are turned ON. assuring at least 1 stage of
electric heat is on, and also increasing leaving air temperature.
As part of the Comfort Heat pump system. Configuration Option
No. 9 (Intelligent Heat Staging) should also be set to ON if the heat
pump is single stage and a 3-stage heater is present.
TO SELECT:
I. Enter configuration mode if not already there. See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 16.
2, Press SET TIMFdTEMP but_n once to flash largo display.
6
PROGRAMMABLECONFIGURATION
(OPTION 17 OFF) NON-PROGRAMMABLE CONFIGURATION
{OPTION 17 ONI
Fig. 2--Programmable/Non-Programmable Keypad Labels
Agg059
3. Use up and down buttons to move between OF and ON on
large display. Factory default is OF.
4. Press SET TIME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
Option 17--Enable Non-Programmable Operation
This option converts the programmable Thermidistat Control to a
non-programmable control for those users who do not want
programmability. The clock is retained, but the days of the week
and the daily schedules have been eliminated, making it operate as
if HOLD were permanently ON. Some of the buttons (used in
programming only and now not needed) are redefined to simplify
the non-programmable operation. To match these redefined but-
tons, a new keypad label, included with the Thermidistat, must be
placed over the original keypad label. Fig. 2 shows both the
original keypad label and the non-programmable keypad label.
When this option is selected, the new keypad label must be applied
over (or in place of) the original. Because these adhesive-backed
keypad labels are not designed to be removed, this conversion
should be considered permanent. Once the change to non-
programmable operation is done, a procedure is not provided to
easily change it back. Should this change be needed, it is best to
trade the Tharmidistat for one which has not been converted.
Both programmable and non-programmable versions of the Ho-
meowner's Manual are available. Be sure to leave only the correct
version of the Homeowner's Manual with the homeowner.
Once it has been determined that a particular installation is to be
made non-programmable, the only changes required are:
Attach non-programmable keypad label over original program-
mable one.
Attach non-programmable start-up sticker instructions to back
of door.
Set Configuration Option No. 17 to ON.
Leave non-programmable homeowner's manual with home-
owner.
To attach the provided non-programmable keypad label, caretillly
peel off its backing and apply it over the original keypad label.
PLEASE HEED: Once the new keypad label makes contact, it will
stick fitrrdy in place and adjustments cannot be made. CARE-
FULLY locate an edge of the keypad label, making sure its
position and orientation are correct. Then, from the attached edge.
smooth the restof the keypad label over the original. Make sure the
new keypad label does not interfere with the motion of the buttons
which it surrounds.
TO SELECT:
I. Enter configuration mode if not already them. See Step 4 "To
Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 17.
2. Press SET TIME/TEMP button once to flash large display.
3. Use up and down buttons to move between ON and OF on
large display. Factory default is OF.
4. Press SET TIME/TEMP button again to flash upper small
display for selection of another option, or press END to exit
configuration mode.
REDEFINITION OF BUTFONS
Fig. 2 shows the original (programmable) button labels on the left
and the redefined (non-programmable) buttons on the right. In the
figure, the buttons are numbered for easy reference. They are not
numbered on the actual product. Six of the buttons (numbers 1
through 5 and 9) have been redefined.
Button 3 originally altematod between time, cool set point, and
heat set point with each press. Now, button 1 selects the cool set
point, button 2 selects the heat set point, and button 3 selects time.
now used only to set the clock. Note that the days of the week ate
gone.
Button 5 used to alternate between humidify and dehumidify. Now
button 4 selects dehumidify and button 5 selects humidify.
Button 9 now loses the HOLD label, making it END only. This
button is only used to END the humidity screen and the configu-
ration mode.
These changes both simplify operation for the homeowner and find
use for the buttons which are no longer needed when programma-
bility is removed.
Step 5--System Start-Up and Checkout
The Thermidistat Control is designed with a built-in installer test
capability. It allows easy operation of equipment without delays or
set point adjustments to force heating or cooling.
To enable installer test mode, move DIP switch No. 4to ON
position. To access this switch, open case as described in Step 2.
Use the corner of a small screwdriver to slide switch No. 4 to ON
position.
While in installer setup mode, clock will display "lnSt," FAN
button will control fan, and MODE button will control heating and
cooling.
TO TEST FAN:
Fan button switches FAN icon between AUTO and ON. While ON
is displayed, G output will be on, turning fan on. Allow up to 10
see after button is pressed for fan to turn on and off. On some fan
coils, fan continues to operate for 90 sec after G signal is removed.
Cool--O to 2 minutes
Coo1_2 to 4 minutes
Heat--O to 2 minutes
Heat--2 to 4 minutes
Eheat---0 to 2 minutes
Eheat--2 to 4 minutes
Two-stage heatnotava_able
Table 2---Equipment Outputs
1-SPEED AC 2-SPEED AC 1-SPEED HP 2-SPEED HP
Y,G Y1,G Y,G,O Y1, G, O
Y,G Y1, Y2, G Y,G,O Y1, Y2, G, O
W1 Wl Y, G Y1, G
Wl, W2 Wl, W2 Y, GY1, Y2, G
...... Wl Wl
...... Wl, W2T Wl*
NOTE: For Y_Jse terminal Y/Y2, for Y1---use temlinal Y1/W2, for W2---use terminal O/W2,
for O--use terminal O/W2, for Wf--use terminal W/Wt, for W2t use terminal ¥ t/W2
TO TEST COOLING AND DEHUMIDIFICATION:
Press MODE button until COOL icon turns on. Cooling begins
within 10 sec and remains on for 4 minutes. If system is 2-speed,
low speed comes on for first 2 minutes, followed by high speed for
second 2 minutes. At the end of 4-minute run, cooling stops, and
MODE reverts back to OFF. At any time during 4-minute run time,
cooling may be turned off by pressing MODE button until OFF
appears. While cooling is on, successive presses of HUMIDITY
button turn dehumidify output on and off. While this output is
active, "dh" appears in cool set point display. Equipment outputs
for different equipment types are listed in Table 2.
TO TEST PRIMARY HEATING AND HUMIDIFICATION:
Press MODE button until HEAT icon turns on. Primary heating
begins within 10 sec and remains on for 4 minutes. This will be
furnace or electric beat in AC system and heat pump heating in
heat pump system. If system has 2 stages of primary heat. first
stage will be on for 2 minutes followed by second stage for 2
minutes. At the end of 4-minute run, heating stops, and MODE
reverts back to OFF. At any time during 4-minute run time, heating
may be turned off by pressing MODE button until OFF appears.
While heating is on, successive presses of HUMIDITY button turn
humidify output on and off. While this output is active, "ha"
appears in heat set point display. Equipment outputs for different
equipment types are listed in Table 2.
TO TEST AUXILIARY HEATING:
Auxiliary heating only exists in heat pump systems. To test, press
MODE button until EHEAT icon rams on. This will be nlectdc
heat in standard heat pump systems and furnace in dual fuel
systems. Auxiliary heating begins within 10 sec and remains on for
4 minutes. If there are 2 stages of auxiliary heat, first stage comes
on for 2 minutes followed by second stage for 2 minutes. At the
end of 4-minute run, heating stops and MODE reverts back to
OFF. At any time during 4-minute mn time, heating may be turned
off by pressing MODE button until OFF appears. Actual outputs
for different equipment types are listed in Table 2.
Step 6--Final Settings
Be sure to return DIP switch No. 4back to OFF position to exit
installer setup mode. Assuming system is to be left in operation
after installation is complete, use MODE button to select between
HEAT, COOL, or AUTO to provide desired operation of heating,
cooling, or both.
The default set points and programmed schedule conform to the
Energy Star_ requirements of the U.S. Department of Energy for
beth heating and cooling. These provide energy saving tempera-
ture settings. Refer to Table 3.
If programmed schedule is to be used,make sure HOLD icon is
off. This feature is turned on and off by HOLD button.
If fixed temperatures are desired, use HOLD button to turn on
HOLD icon. This will maintain set points, not allowing them to
change with programmed schedule.
Table 3--Energy Star Default Schedule
SCHEDULE IHEAT COOL
Wake 6:00 AM I68_F 78°F
Day 8:00 AM 60°F 85°F
Evening 5:00 PM 68°F 78°F
Sleep 10:00 PM 60°F 82°F
The FAN button may be used to select between AUTO (fan on
only with equipment) and FAN (fan on continuously) fan modes.
For further information on temperature selection and program-
ming, refer to Homeowner's Guide.
HUMIDITY CONTROL FEATURES
The various humidity control features of the Thermidistat Control
are explained below. They are grouped into 2 sections: humidifi-
cation and dehumidification. At the end of each sectina, instruc-
tions on how to select each feature are given.
HUMIDIFICATION
The Thermidistat Control directly connects to a standard 24-vac
humidifier to control humidification in the home. A humidify set
point between 10 and 45 percent relative humidity is selected by
the homeowner, or all humidification can be tamed off. When
humidity in home drops below set point, humidifier will be turned
on to raise humidity level. Humidification can only occur in
heating mode (HEAT or AUTO/HEAT). Five different humidifi-
cation selections are available and are described below.
l. Normal Humidify
2.
In normal humidify, humidifier will be on if there is a
humidity demand and any heating equipment is oil This will
include furnace, heat pump. or auxiliary heat. In heat pump
applications, this is an improvement over using an external
humidistat, which only supplies humidity when auxiliary heat
is on,
Fan Humidify
3.
This configuration allows a humidify demand m turn on fan
and humidifier together, even if there is no heat demand. It is
particularly useful when the furnace is oversized, resulting in
short heating cycles. It allows the humidifier to run longer,
supplying more humidity to the home. Note that fan hours will
increase, using more electricity. Also, the humidifier delivers
less moisture to cooler air than it does to heated air.
Auto Humidify
This feature is designed to eliminate the problem of sweating
windows in very cold weather. When selected, the set point is
automatically reduced by 1 percent for every drop of 2°F in
outdoor temperature between 50°F and 0°F. The set point may
be changed at any time, and it will continue to track outdoor
temperature from the new set point and current outdoor
temperature. The adjusted set point range is still limited to
between 10 and 45 percent relative humidity. To use this
feature, an outdoor temperature sensor MUST be attached. If
not, E3 error message will be displayed.
Table 4--Humidification Selections
HUMIDIFY SET POINT
SELECTION MODE DISPLAY FAN DISPLAY DISPLAY
Normal Humidify Blank Blank Humidify Set Point Value
Fan Humidify Blank FAN Humidify Set Point Value
Auto Humidify AUTO Blank Humidify Set Point Value
Auto and Fan AUTO FAN Humidify Set Point Value
Humidify Off Blank Blank OF
4. Auto and Fan Humidify
The 2 choices of AUTO and FAN can be selected together.
This provides both functions simultaneously.
5. Humidify Off
The humidify function can be turned offcompletely. This does
not require changing existing set points.
To Select Humidification (Between NORMAL, FAN, AUTO,
FAN and AUTO, or OFF) (See Table 4.)
Press HUMIDITY button to bring up humidity select screen. It is
indicated by "hu" or "dhu" in clock display. Successive presses
will change between "hu" and "dhu" in clock display. Select "hu"
for humidity functions. The large display shows actual humidity
level. The smaller display (in heat set point location) shows
humidity set point (Humidify Set Point) or OF (off). When
Humidity Set Point value is displayed, its value can be changed
with up and down buttons. Successive presses of MODE button
will move between 5 choices described above and each will be
indicated as shown in Table 4.
To exit humidity select screen, press END button.
Additional Humidify Comments
The humidifier is actually turned on when humidity is 2 percent
below set point and turned off when it reaches 2 percent above set
point. This built-in hysteresis prevents humidify output from
toggling on and off when humidity level is near set point.
The vacation mode provides some additional humidification func-
tions. These are specially designed to provide protection for an
unoccupied home while simultaneously minimizing energy use.
Refer to "Vacation" section for additional information.
DEHUMIDIFICATION
Dehumidification is done only during cooling. Depending on type
of equipment used, compressor speed, blower speed, set point
adjustment, and equipment cycling are modified to provide added
dehumidification. Adehumidification set point (separate from
humidification set point) is available to the homeowner. It can
range from 50 to 90 percent relative humidity. When actual
humidity is higher than set point, a dehumidification demand
exists. The TbermidistaI Control responds by activating its dehu-
midify output. It may also control the compressor and blower,
depending on equipment type and dehumidify selection choice.
The 3 available selections are described below.
The amount of extra dehumidification available is very dependent
on the type of equipment in the home. Without a variable-speed
blower, the system's ability to adjust dehumidification is very
limited.
I. Normal Dehumidify Operation
When normal dehumidify is selected, the compressor will not
turn on without a cooling demand. If dehumidify demand
exists while cooling, dehumidify output will also be active
(24vat removed). This output commands variable-speed
blowers to reduce Iheir airflow, which improves water re-
moval from the cooled air.
2. Cool to Dehumidify
3.
The cool to dehumidify selection tells the system to operate
the compressor, within limits, when there is a dehumidify
demand even if there is no cooling demand. The limits are that
the system may overcool up to 3°, but no more. while
attempting to satisfy a dehumidify demand. Within this 3°
range, there is an additional balance between overcooling and
humidity satisfaction. When overcooling must occur, the
dehumidify set point is adjusted upward by 2 percent per
degree of overcooling. For example, a cooling set point of
76°F and a dehumidify set point of 60 percent is equivalent to
a cooling set point of 75°F and a dehumidify set point of 62
percent. This dehumidify set point change is internal to the
Thermidistat Control and is not shown on the display.
During cool-to-dehumidify demand, the compressor runs a
maximum of 10 minutes on, followed by 10 minutes off.
When the compressor turns off, the fan (G output) is also
turned off immediately. The immediate fan shutoff prevents
re-evapormion of water on the coil, improving dehumidifica-
tion. If fan is set to continuous, the G (fan on) signal is
removed for 5 minutes starting when compressor turns off.
In most furnaces and fan coils, the blower operates for 90 sec
after beth Y and G disappear. This 90-see delay should be
removed, if possible, for maximum dehumidification perfor-
mance. Consult furnace or fan coil Installation Instructions to
see if delay can be disabled.
Dehumidify Off
Dehumidification can be turned off completely. This can be
done without changing existing set points.
To Select Dehumidification (Between NORMAL, COOL TO,
and OFF)
Press HUMIDITY button to bring up humidity selections. Succes-
sive presses will show "hu" or "dhu" in clock display. Select "dhu"
for dehumidify selections. The large display shows actual humidity
level. The smaller display (in cool set point location) shows
dehumidify set point (DSP) or OF (off). When DSP value is
displayed, its value can be changed with up and down buttons.
Successive presses of MODE button moves between 3 choices
above and each will be indicated as in Table 5.
Superdehumidify (With Cool to Dehumidify)
This selection only affects cool-to-dehumidify operation. It is part
of the installer setup (see Configuration Option No. 7) and must be
made by installer. The Homeowner's Guide does not cover this
selection. A requirement is the use of a variable-speed indoor unit
with supordehumidify capability. During cool-to-dehumidify call,
it provides maximum dehumidification by reducing airflow to a
minimum. The actual superdehumidify command from Thermidis-
tat Control to the indoor unit is a Y signal without a G signal in
addition to dehumidify signal. The indoor unit responds to this
combination by reducing the airflow to a minimum. All other
characteristics of cool to dehumidify are the same.
Additional Dehumidify Comments
Dehumidification can be enhanced (with some €fficiency loss) by
turning blower off immediately at the end of each cooling cycle
(eliminating normal 90 sec blower off delay). Where maximum
9
Table 5---Dehumidification Selections
SELECTION MODF DISPLAY FAN DISPLAY
Normal Dehumidify
Cool to Dehumidify
Oehumidify OFF
Blank
COOL
Blank
DEHUMIDIFY SET POINT
DISPLAY
Blank Dehumidif,/Set Point Value
Blank Dehumidify Set Point Va)ua
Blank OF
humidity removal is desired, this should be done, if possible. Fan
coils have the capability of removing this off delay, furnaces do
not. On FK or FV Fan Coils, set delay tap to 0/0. On standard fan
coils, a jumper can be cut to disable off delay. Refer to fan coil
Installation Instructions for details. If FAN is set for continuous
operation (fan ON icon displayed), G output is tamed off for 5
minutes at the end of each cooling cycle as long as dehumidify
demand exists.
Like humidify, dehumidify actions are initiated when humidity is
2 percent above set point and are terminated when humidity drops
to 2 percent below set point. This prevents unnecessary toggling of
dehumidify actions when humidity is near set point.
The vacation mode contains additional dehumidify features de-
signed to protect an unoccupied home. Refer to the "Vacation"
section for additional information.
With any dehumidify selection, if the system has a 2-speed
compressor (DIP switch No. 2 is ON) and does NOT have a
variable-speed blower (Configuration Option No. 5 set to OFF), all
cooling will be done at high speed while dehumidify demand
exists. This is because the combination of 2-speed compressor
without variable-speed blower generally has poor water removal
on low speed.
Dehumidify Output and Equipment Connections
When there is a dehumidify demand, dehumidify output is
activated, which means that a24-vac signal is removed from the
DHUM output terminal. In other words, dehumidify output logic is
reversed -- output is turned ON when no dehumidify demand
exists and is tamed OFF when demand exists. This logic reversal
has come about from historical use of a standard humidistat to do
dehumidification. The humidistat contacts open on high humidity,
thus removing a 24-vac signal to initiate dehumidification. Equip-
ment has been designed to operate in this manner, so the
Thermidistat Control must now accommodate the existing equip-
ment.
Carrier FK and FV Series Variable-Speed Fan Coils, all 58UHV
and 58UXV 80% Variable-Speed Furnaces, and 58MVP 90%
Variable-Speed Furnaces with the DE connection have dehumidify
inputs which connect directly to Thermidistat Control DHUM
output. They are compatible with the reverse logic output and will
reduce their cooling CFM by approximately 20 percent when a
dehumidify demand is present.
The FK and FV Series Fan Coils have a terminal marked DH
which should be connected to the Thermidistat Control DHUM
output. Jumper J1 on fan coil MUST be removed. It is located
behind the DH terminal. Additionally blower delay tap on fan coil
should be set to (3/0 (no ON delay and no OFF delay) when using
cool to dehumidify. With this selection, the blower stops when G
signal is removed, preventing re-evaporation of water from the coil
which would occur during the normal 90 sec blower off delay. (See
Wiring Diagram Reference Chart and Fig. 5 through 8 in Wiring
Diagram/iterature).
On 58UHV and 58UXV Furnaces, a green wire marked DHUM is
connected to a spade lug which is connected to the G input
terminal. Unplug spade lug, cut off spade receptacle from wire
end, and splice awire between green DEHUM wire and Thermi-
distat Control DHUM terminal. (See Wiring Diagram Reference
Chart and Fig. 17 through 20 in Wiring Diagram literature).
Carrier 58MVP Furnaces also have a DEHUM input. The DE-
HUM input acts differently depending on which style of variable-
speed fumace control you have. The older style variable-speed
furnace comml DOES NOT have a DE connection while the newer
style variable-speed furnace control has a DE connection. Both of
these variable-speed furnace controls function the same except the
DEHUM logic is reversed.
On the older style variable-speed furnace controls, a field-
supplied relay is required between the Thermidistat Control
and furnace. The relay coil is connected between DHUM output
on the Thermidistat Control and COM terminal on the furnace
control. Its normally closed contact is connected between R and
DEHUM terminals on the furnace control, where the DEHUM
terminal is a spade lug located next to the transformer secondary
connections. (See Wiring Diagram Reference Chart and Fig. 21
through 24 in Wiring Diagram literature). When a dehumidify
demand exists, relay is de-energized, and normally closed contacts
supply 24vat to the furnace DEHUM terminal. As a result the
furnace control reduces the blower airflow by 15 percent.
On newer style variable-speed furnace controls, afield-
supplied relay IS NOT required. The DHUM output on the
Thermidistat Control is instead connected directly to the DEHUM
terminal on the furnace control, where the DEHUM terminal is a
spade lug located next to the transformer secondary connections.
In addition the DE jumper located next to the DEHUM terminal
must be removed to enable the DEHUM input. (See Wiring
Diagram Reference Chart and Fig. 25 through 28 in Wiring
Diagram literature). When a dehumidify demand exists the furnace
control reduces the blower airflow by 21 percent.
VACATION
A vacation selection is available specifically for times where the
home will not be occupied for an extended period. For conve-
nience. 1button selects vacation mode which is indicated by OUT
icon on display. Vacation mode also has an automatic hold,
meaning that set points are not affected by the programmed
schedule. While in vacation mode, the system provides tempera-
ture and humidity protection for the home in all seasons, but not
comfort.
Vacation Set Points
A special set of temperature and humidity set points exists which
are active in vacation mode. They are adjustable by the home-
owner, are exclusively for vacation mode, and are remembered
from 1 vacation selection to the next. These set points will be
higher for cool and dehumidify and lower for heat and humidify
than those of occupied mode.
Vacation Humidification
Normal humidify is available, using vacation set points. Humidi-
fication by fan only is not available as vacation selection. Auto
humidification is available, adjusting its set point with outdoor
temperature the same as when occupied. The maximum humidity
set point can be adjusted separately from the occupied value, but
it must always be less than occupied value. This allows humidi-
fication to track outdoor temperature identically, whether occupied
or vacation, but allows maximum humidification to be less when
unoccupied. Vacation humidification can be turned off indepen-
dently of occupied humidification.
10
SYMPTOM
NO display
"-" ia p_ace of room _mpe_
"E3" ar "-" in place of outdoor temperature
"E4" or "E5"
"E6"
"Clean Filter" icon displayed
Cooling or heating will not come on
Humidify or dehumidify will not come on
Thermidistat Control Troubleshooting
WHAT TO CHECK
Open Thermidistat Control. Check for 24vac between R and Cat screw terminals on mounting base. Reassemble. making
sure pins on board engage sockets in mounting base. If display does not appear, replace Thermidistat Control.
Thecmi_st_t Cot_ttel c_r_ot _rG_yd£ re._d re_'# tert_ec_tuce. Re#ta_e _at Control.
_ermidistat Control cannot propedy read outdoor temperature. Check outdoor sensor and its wiring.
Internal failure. Replace Thermidistat Control.
System is Stuck in defrost. Check wiring and heat pump defrost control board.
Filter timer has expired. Clean or replace filter and then press VACATION and HOLD/END buttons together to reset•
See Installer Setup to force heating or cooling. Check for 24vac at equipment terminals. It not present, check wiring.
See installer Setup to force HUM or DEHUM. Check for 24vac at equipment terminals. If not present, check wiring•
Vacation Dehumidification
Normal Dehumidify, Cool to Dehumidify, and Dehumidify OFF,
are all available in vacation mode, and selection of I of these can
be different from that of occupied. Vacation dehumidification
selection and set points are remembered the next time vacation is
used.
Cool to dehumidify operates slightly differently, allowing the
home to be cooled to as low as 70°F when trying to achieve
dehumidify set point. The balance between dehumidify and
temperature set point adjustments is 1 percent set point increase
per degree of overcooling for temperatures below 76°F. For
example, at 74°F dehumidify set point is raised 2 percent, and at
72°F dehumidify set point is raised 4 percent. At temperatures
above 76°F, dehumidify set point is not changed.
OPERATIONAL INFORMATION
FIVE-MINUTE COMPRESSOR TIMEGUARD
This timer prevents compressor from starting unless it has been off
for at least 5 minutes. It can be defeated for 1 cycle by
simultaneously pressing FAN button and INCREASE TEMPERA-
TURE button.
FIFIEEN-MINUTE CYCLE TIMER
This timer prevents the start of a heating or cooling cycle until at
least 15 minutes after the last start of the same cycle. Its function
is to assure that equipment is not cycled more than 4 times per hr.
This timer is defeated for 1 cycle when desired temperature is
manually changed. It can also be defeated for 1 cycle by
simultaneously pressing FAN button and INCREASE TEMPERA-
TURE button.
FIFI'EEN-MINUTE STAGING TIMER
In multistage heating or cooling, this timer prevents any higher
stage from turning on until preceding stage has been on for 15
minutes. This timer is defeated if temperature error is greater than
5°F (usu,:dly due to alarge chaztge in desired temperature).
THREE-MINUTE MINIMUM ON TIME
In normal operation, when a stage turns on, it will not turn off for
a minimum of 3 minutes. If the set point is changed, this timer is
automatically canceled, allowing the equipment to turn off inune-
diately when the demand is removed.
HEAT/COOL SET POINTS (DESIRED "I_MPERATURE)
A minimum difference of 2°is enforced between heating and
cooling desired temperatures. This is done by allowing Isetting to
"push" the other, to maintain this difference. This difference is
adjustable via Configuration Option 14.
EQUIPMENT ON INDICATORS
When cooling equipment is on, a COOL icon preceded by a small
triangle is displayed below cool set point. While cooling equip-
ment tam on is delayed by a staging or cycle timer, triangle will
flash. The same is true for HEAT icon and its preceding triangle
located under heat set point. These 2 arrows are also used to
hncticate state of humidiD' and dehumidify ¢ntq_u_s. See next
section.
HUMIDIFY AND DEHUMIDIFY INDICATORS
The humidity screen (selected by pressing the HUMIDITY button)
uses the same triangles referenced in the above paragraph to
indicate the state of the HUM and DHUM outputs. When
humidification or dehumidification is active, the triangle under its
set point is turned on.
AUTO CHANGEOVER
When auto changeover mode is selected, a change from heat to
cool (or vice versa) will not occur until an opposite mode demand
has existed for 20 minutes. If set point is changed. 20-minute
requirement is deleted.
EMERGENCY HEAT MODE
When Thermidistat Control is configured as aheat pump and
emergency heat is selected, all Y signals are locked out, and W
becomes energized aport acall for heat.
POWER ON CHECK
When AC power is first applied, all segments of display are turned
on for a few seconds. Following this, temperature display indicates
model/configuration via following 2-digit code:
AC--l-speed air conditioner, HP--l-speed heat pump, A2--2-
speed air conditioner. H2_2-speed heat pump. HS--l-speed heat
pump with 3-stage auxiliary heat, dF_ual fuel, d2--<lual fuel
with 2-speed.
ERROR CODES
.... If Thermidistat Control cannot properly read room tem-
perature, display will indicate -- and all outputs (except
fan if on) will turn off.
El, E2 -- There is no El or E2 error message.
E3 -- If Thera_ddistat Control canrtot properly' read outdoor
temperature, and it is needed for proper operation, display
will indicate E3.
E4 -- If Thermidistat Control's internal memory fails, F_Awill be
displayed. Replace Thermidistat Control.
E5 -- If Thermidistat Control cannot properly read humidity. E5
wilI be displayed. Replace Thermidistat Control.
E6 -- If defrost cycle continues for longer than 15 minutes. E6
will be displayed. Check heat pump wiring or for failed
heat pump defrost control.
SMART RECOVERY
With Smart Recovery selected, transition out of setback begins a
fixed time period before selected recovery time and gradually
adjusts room temperature an desired temperature will be achieved
at selected recovery time. The fixed time period is 1.5 hr. It
operates in beth heating and cooling. This only applies ta
programmable operation.
11
I
I
THERMIDISTAT CONTROL CONFIGURATION RECORD
Date
Owner/Operator Thermidistat Model No.
A) Hardware Configuration
Switch A __-- AC/HP Select. (OFF =AC)
Switch S ---- 1 o_ 2-Speed Compressor. (OFF = 1-Speed)
Switch C __ Smart Recovery, (OFF =Enable)
Switch D _-- Installer Test. (OFF = Disable)
S) Mode Settings
--__ Hold (On or Off)
__ Mode (Off, Heat, Cool, Auto, Eheat)
__ Heating Set Point Value
--__ Cooling Set Point Value
-- Fan (Auto or On)
C) Configuration Options
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
__ Anticipator (1-9: lactory default = 3)
--- Clean Filter Timer (Off or 1-9: lactory default = 2)
-- Fahrenheit or Celsius (F or C: factory default = F)
-- Fan On with W (Off or On: factory default = Oft)
____ Variable Speed ICM Motor (Off or On: factory default = Off)
___ Cooling Lockout Below 55°F (Off or On: factory default = Off)
---- Variable Speed Superdehumiddy (Off or On: factory default = Off, or Not Available)
___ Auxiliary Heat Lockout Setting (Olf or 5-55°F: factory default =Off, or Not Available)
-- Integigent Heat Staging Selection (Off or On: factory default =Off, or Not Available)
-- Dual Fuel Equipment Selection (Off or On: factory default = Off, or Not Available)
-- Balance Point Setting (Off or 5-55°F: tactory default =Off, or Not Available)
_-- Defrost Heat Select (0, 1, 2. 3: factory default =0, or Not Available)
--__ Room Temperature Olfset (-5 to +5: factory default = 0)
-- Heat/Cool Dead Band (0 to 6: factory default = 2)
__ Enable Auto Mode (On or Off: factory default = On)
-- Enable Super Comfort Heat Mode (Off or On: factory default is Off, or not Available)
___ Enable Non-Programmable Operation (nP or P: factory defaug is Pfor programmable)
D) Schedule
WAKE
TIME HEAT COOL
Mon
Tue ....
Wed
Thu
Pri
Sat
Sun
DAY EVE SLEEP
TI HTOL TIME HEAT COOL TIME HEAT COOL
E) Humidity Settings
Heat Mode Coot Mode
Selectioq Set Point% Disolay Selection Set Point% Diso]ay
Normal Humidify (hu) Normal Dehumidify (d hu)
Fan Humidify (hu, Fan) Cool to Dehumidify {d hu, COOL)
Auto Humidify (hu, AUTO) Dehumidify Off no set point (d hu, OF)
Auto and Fan Humidify (hu. AUTO, Fan)
Hum[dif_ Off no set point (hu, OF)
E) Vacation Humidity Settings
Heat Mode Cool Mode
Selection Set Point% Oisolav Selection Set Point% Oisolav
Normal Humidify ¿hu, OUT) Normal Dehumidify (d hu, OUT)
Auto Humidify (hu, OUT, AUTO) Cool to Dehumidify (d hu,OUT, COOL)
Auto and Fan Humidily (hu, OUT, AUTO, Fan) Dehumidify Off no set point (d hu, OUT,OF)
Humidify Off no set point (hu, OUT, OF)
A99015
Copyright 1999 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 tstt?_L_
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without thcurdng obligations.
Book I 4PC 101 Catalog No, 03TS-TA17 Pdnted in U.S.A. Form TSTAT-23SI Pg 12 g-99 Replaces: TSTAT-19SI
Page 1 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 2 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 3 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 4 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 5 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 6 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 7 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 8 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 9 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 10 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 11 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356
Page 12 of 12 - CARRIER  Controls And HVAC Accessories Manual L0210356

Navigation menu