CARRIER Air Conditioner/heat Pump(outside Unit) Manual L0211024

User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 8

HEATING & COOLING
Visit www.calrier.com
38EZA, 38ETA, 38ESA
12, 13, 14 SEER Split-System
Air Conditioner with Puron®
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the
instanmion.
This symbol _ indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire. electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factoty-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol ,_.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
Before installing, modifying, or servicing system, main elec-
trical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label. Electrical shock can
cause personal injury or death.
IRSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installatinn of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit
operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate for
unit capacity.
A99327
Fig. 1--Models 38EZA, 38ETA, 38ESA
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends+
4. Leave some slack between structure and unit to absorb
vibration.
5. When passing refrigerant tubesthrough the wall, seal opening
with RTV or other pliable silicon-based caulk. (See Fig. 2.)
6. Avoid direct tubing contact with water pipes, duct work. floor
joists, wall studs, floors, and walls.
7.
8.
9.
10.
Do not suspend refrigerant tubing from joists and studs with a
rigid wire or strap which comes in direct contact with tubing.
(See Fig. 2.)
Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube,
When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 2.)
Isolate hanger sWaps from insulation by using metal sleeves
bent to conform to shape of insulation.
When outdoor unit is connected to factory-approved indoor uniL
outdoor unit contains system refrigerant charge for operation with
indoor unit of the same size when connected by 15 fl of
field-supplied or factory accessory tubing. For proper unit opera-
tion, check refrigerant charge using charging information located
on control box cover and/or in the Check Charge section of thLs
instruction.
IMPORTANT: Maximum liqnid-line size is 3/8-in. O.D. for all
residential applications including long line.
IMPORTANT: Always install the factory-supplied liquid-line ill-
ter drier. If replacing the f'dter drier, refer to Product Data Digest
for appropriate part number. Obtain replacement falter driers from
your distributor or branch.
Manufacturer _the right to diseontintm, or change at any time, specifications or designs without notice and without incurring obligations,
PC 101 Catalog No. 533-80056 Printed in U.S.A. Form 38ESA-3SI Pg 19-O2 Replaces: 38ESA-2SI
O'CLOCK SWEAT CONNECTION
2
SENSING
SUCTION TU_
8 O'CLOCK 4 O'CLOCK
7/8 IN. OD & SMALLER LARGER THAN 7/s IN. OD
A81032
Fig. 5--Position of Sensing Bulb
11'.,_["T_T_T_,_j
If ANY refrigerant tubing is buried, provide a 6 in. vertical
rise at service valve, Refrigerant tubing lengths up to 36 in.
may be buried without further special consideration. Do not
bury lines for lengths over 36 in.
To prevent damage to unit or service valves observe the
following:
Use a brazing shield
Wrap service valves with wet cloth or use a heat sink
material.
Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, substan-
tial capacity and performance losses can occur. Following the
recommendations in the Application Guideline and Service
Manual -- Residential Split-System Air Conditioners and Heat
Pumps Using Puron® Refrigerant will reduce these losses. Refer
to Table 1 for field tubing diameters. Refer to Table 2 for
accessory requirements.
No buried-line applications greater than 36 in.
If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.
OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT
Outdoor unit contains correct system refrigerant charge for opera-
tion with ARI rated indoor unit with highest sales volume when
connected by 15 ft of field-supplied or factory-accessory tubing.
Check refrigerant charge for maximum efficiency.
INSTALL LIQUID-LINE FILTER DRIER
Service valves are closed from factory and ready for brazing. After
wrapping service valve and filter drier with a wet cloth, braze
sweat connections using industry accepted methods and materials.
Consult local code requh-ements. Refrigerant tubing and indoor
coil are now ready for leak testing. This check should include all
field and factory joints.
EVACUATE REFRIGERANT TUBING AND INDOOR COIL
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used if the procedure outlined
below is followed. Always break a vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum
method is the most positive way of assuring a system is free of air
and liquid water. (See Fig. 7.)
Triple Evacuation Method
The triple evacuation method should only be used when vacuum
pump is only capable of pumping down to 28 in. of mercury
vacuum and system does not contain any liquid water. Refer to
Fig. 8 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to
continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open
until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1hr. During
this time, dry nitrogen will be able to diffuse throughout the
system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 8. System will then
be free of any contaminants and water vapor.
FINAL TUBING CHECK
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes axe
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.
Step 8_Make Electrical Connections
Refer to Fig. 6 and install filter drier as follows:
1, Braze 5-in. connector tube to liquid service valve. Wrap filter
drier with damp cloth.
2, Braze filter drier between connector tube and liquid tube to
indoor coil, Flow arrow must point towards indoor coil.
REFRIGERANT TUBING
Connect vapor tube to fitting on outdoor unit vapor service valves.
Connect liquid tube to filter drier. (See Fig. 6 and Table 1.) Use
refrigerant grade tubing.
Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unitrating plate. Do not
CONNECTOR
TUBE
Fig. 6--Liquid-Line Filter Drier
A99331
Tabl, 1--Refrigerant Connections and Recommended Liquid Line and Vapor Tube Diameters (In.)
UNIT
SIZE
018, 024
030, 036
042, 048
060
NOTES:
LIQUID
Connection Diameter
3/8
3/8
3/8
3/8
Tube Diameter
3/8
3/8
3/8
3/8
VAPOR
Connection Diameter Tube Diameter
5/8 5/8
3/4 3/4
7/8 7/8
7/8 1-1/8
VAPOR (LONG LINE)
Connection Diameter Tube Diameter
5/8 3/4
3/4 7/8
7/8 1-1/8
7/8 1-1/8
f, Tube diamefers are for lengths up to 50 tt. For tubing lengths greater than 50 ft horizontal, or greater than 20 fl vertical differential, consult the Application Guideline
and Service Manual -- Air Conditioners and Heat Pumps Using Puron_ Refrigerant.
2, DO not apply capillaw tube indoor coils to these units.
ACCESSORY
Crankcase Heater
Evaporator Freeze Thermostat
Winter Start Control
Accumulator
Compressor Start Assist
Capacitor and Relay
MotorMastarO Control,
or
Low-Ambient Pressure Switch
Wind Baffle
Coastal Filter
Liquid-Line Solenoid Valve
or
Hard Shutoff TXV
Ball Bearing Fan Motor
Table 2--Accessory Usage
REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(BELOW 55°F)
Yes
Yes
Yeet
No
Yes
Yes
See low-ambientinstructions
No
No
Yee$
REQUIRED FOR
LONG-MNE
APPLICATIONS*
(OVER 5OFT)
Yes
No
No
No
Yes
No
No
No
See Long-Line
Application
Guideline
No
REQUIRED FOR
SEA COAST
APPLICATIONS
(WITHIN 2 MILES)
No
No
No
No
No
No
No
Yes
No
No
• For tubing line sets between 50 and 175 ft, refer to Application Guideline and Service Manual -- Air COnditioners and Heat Pump= Using Puron_ Reffigerant.
_-Only when low-pressure switch is used.
:_ Required for low-ambient controller (full modulation feature) and MotorMaste_ Control only.
install unit in system where voltage may fluctuate above or below
permissible limits.
NOTE: UsE copper wire only between disconnect switch and
unit.
NOTE: Install branch circuit disconnect of adequate size per
NEC to handle unit starting current. Locate disconnect within sight
from and readily accessible from unit, per Section 440-14 of NEC.
ROUTE GROUND AND POWER WIRES
Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit
cont,'o[ box.
5
The unit cabinet must have an uninterrupted or unbroken
ground to minimize personal injury if an electrical fault
should occur. The ground may consist of electrical wire or
metal conduit when installed in accordance with existing
electrical codes. Failure to follow this warning can result in an
electric shock, fire, or death.
CONNECT GROUND AND POWER WIRES
Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 9.
5000
4500
4000
3500
aooo
_ 2500
i2ooo
1500
1000
50O
f SYSTEM
l r_:_ ................... _VAC;U UM TIGHT
I,_ TOO WET
FTIGHT
DRY SYSTEM
DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES
CONTACTOR
I
FIELD POWER /W,R,NG '1 OC>
P.ASEONLY S
FIELD GROUND
WIRING @
II[
1 ; ; ; 7 __ J GROUNO
LUG
MINUTES A94025
A95424
Fig. 7--Deep Vacuum Graph
A9_25
EVACUATE]
IBREAK VACUUM WITH DRY NITROGEN]
[EVACUATE]
IBREAK VACUUM WITH DRY NITROGEN I
[EVACUATE]
CHECK FOR TIGHT, DRY SYSTEM I
( F IT HOLDS DEEP VACUUM) I
} CHARGE SYSTEM I
6
Fig. 8---Triple Evacuation Method
CONNECT CONTROL WIRING
Route 24v control wires through control wiring grommet and
connect leads to control wiring. (See Fig. lI.)
Use No. |8 AWG color-coded, insulated (35°C minimum) wire. If
thermostat is located more than I00 ft from uint, as measured
along the control voltage wires, use No. 16 AWG color-coded wire
to avoid excessive voltage drop.
All wiring must be NEC Class l and must be separated from
incoming power leads.
Use furnace U'ansformer, fan coil transformer, or accessory tram-
former for control power, 24v/40va minimum.
NOTE: Use of available 24v accessories may exceed the mini-
mum 40va power requirement. Determine total transformer load-
ing and increase the transformer capacity or split the load with an
accessory transformer as required.
FINAL WIRING CHECK
IMPORTANT: Check factory wiring and field wire connections
to ensure terminations are secm'ed properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.
Step 9---Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close elecuical disconnect to
outdoor unit.
Fig. 9_Line Power Connections
A crankcase heater is required if refrigerant tubing is longer than
50 ft. Refer to Application Guideline and Service Manual --
Residential Split-System Air Conditioners and Heat Pumps using
Puron@ Refrigerant.
Step 10---Install Electrical Accessories
Refer to the individual instructions packaged with kits or acces-
sories when installing.
Step 11--Start-Up
To prevent compressor damage or personal injury, observe
the following:
Do not overcharge system with refrigerant.
Do not operate unit in a vacuum or at negative pressure.
Do not vent refrigerant to atmosphere. Recover during
system repair or final unit disposal.
Do not disable low-pressure switch.
In scroll-compressor applications:
Dome temperatures may be hot.
To prevent personal injury wear safety glasses, protective
clothing, and gloves when handling refrigerant and observe
the following:
Back-seaimg service valves are not equipped with Schrader
valves. Fully back seat (counterclockwise) valve stem before
removing gage-port cap.
Front-seating service valves are equipped with Schrader
valves.
• 3-phase scroll compressors are rotation sensitive.
A flashing LED on phas,e monitor indicates reverse rotation.
(See Fig. 10 and Table 3.)
This will not allow contactur to be energized.
Disconnect power to unit and interchange 2 field wiring
leads on unit contactor.
Follow these steps to properly start up the system.
I. After system is evacuated, fully back seat (open) liquid and
vapor service valves.
2. Unit is shipped with valve stem(s) front seated (closed) and
caps installed, replace stem caps after system is opened to
refrigerant flow. Replace caps finger-tight and tighten with
wrench an additional 1/12 turn.
3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set point
is below indoor ambient temperature.
5. Set room thermostat to COOL and fan control to ON or AUTO
mode, as desired. Operate unit for 15 minutes Check system
refrigerant charge.
SEQUENCE OF OPERATION
Turn on power to indoor and outdoor units. Transformer is
energized.
On a call for cooling, thermostat makes circuits R-Y and R-G. On
three phase models witb scroll compressors, the units are equipped
with a phase monitor to detect in the incoming power is correctly
phased for compressor operation. If the phasing is correct, circuit
R-Y energizes contactor, starting outdoor fan motor and compres-
sor circuit. R-G energizes indoor unit blower relay, starting indoor
blower motor on high speed.
NOTE: If the phasing is incorrect, the contactor will not be
energized. To correct the pha,(mg, interchange any two of the three
power connections on the field side.
When thermostat is satisfied, its contacts open, de-energizing
contactor and blower relay. Compressor and motors stop.
If indoor unit is equipped with a time-delay relay circuit, the
indoor blower runs an additional 90 sec to increase system
efficiency.
CONTACTOR 24VAC COn
0
(
OFF;NO 24VAC
ON:OK
FLASH:PHASE PROBLEM L2
0
Fig. lO--Phase Monitor Control
A00010
Table 3--Phase Monitor Led Indicators
LED STATUS
OFF No call for compressor operation
FLASHING Reversed phase
ON Normal
Step 12_heck Charge
UNIT CHARGE
Factory charge and charging method are shown on unit informa-
tion plate. Charge Puron® units using a commercial-type metering
device in manifold hose. Charge refrigerant into suction line.
NOTE: If superheat or subcooling charging conditions are not
favorable, charge must be weighed in accordance with unit rating
plate -+ 0.6 oTJft of 3/8-in. liquid line above or below 15 ft
respectively.
Table 4---Required Liquid-Line Temperature (°F)
REQUIRED SUBCOQLING
LIQUID TEMPERATURE
PRESSURE AT (QF)
SERVICE VALVE 810 12 14 16 18
189 58 56 54 52 50 48
195 60 58 56 54 52 50
202 62 60 58 56 54 52
208 64 62 60 58 56 54
215 66 64 62 60 58 56
222 68 66 64 62 60 58
229 70 68 66 64 62 60
236 72 70 68 66 64 62
243 74 72 70 68 66 64
251 76 74 72 70 68 66
259 78 76 74 72 70 68
266 80 78 76 74 72 70
274 82 80 78 76 74 72
283 84 82 80 78 76 74
291 86 84 82 80 78 76
299 88 86 84 82 80 78
308 90 88 86 84 82 80
317 92 90 88 86 84 82
326 94 92 90 88 86 84
335 96 g4 92 90 88 86
345 98 96 94 92 90 88
354 100 98 96 g4 92 90
364 102 100 98 96 94 92
374 104 102 100 98 96 94
384 106 104 102 100 98 96
395 108 106 104 102 100 98
406 110 108 106 104 102 100
416 112 110 108 106 104 102
427 114 112 110 108 106 104
439 116 114 112 110 108 106
450 118 116 114 112 110 108
462 120 118 116 114 112 110
474 122 120 118 116 114 112
486 124 122 120 118 116 114
499 126 124 122 120 118 116
511 128 126 124 122 120 118
OUTDOOR
TE:MP
(°F) 0 52 54
55 9 12 14
60 710 12
65 -- 6 10
70 -- -- 7
75 -- -- --
80 -- -- --
85 -- -- --
90 -- __ --
95 -- -- --
100 -- -- --
105 -- -- --
110 -- -- --
115 -- -- --
Table 5_Superheat Charging
EVAPORATOR ENTERING AIR TEMPERATURE (_FWB)
56 58 60 62 64 66
17 20 23 26 29 32
15 18 21 24 27 30
13 16 19 21 24 27
10 13 16 19 21 24
6 9 12 15- 18 21
-- 58 12 15 18
-- -- -- 811 15
-- -- -- 59 13
.... 6 10
68 70 72 74 76
35 37 40 42 45
33 35 38 40 43
30 33 36 38 41
27 30 33 36 39
24 28 31 34 37
21 25 28 31 35
19 22 26 30 33
16 20 24 27 31
14 18 22 25 29
12 15 20 23 27
9 13 17 22 26
6 11 15 20 25
-- 814 18 23
EXAMPLE:
To calculate additional charge required for a 25-ft line set:
25 ft - 15 ft = 10 ft X 0.6 ovJft = 6 oz of additional charge
COOLING ONLY PROCEDURE
Units with Cooling Mode Puron® TXV
Units installed with cooling mode TXV require charging by the
subcooling method.
I. Operate unit a nfinimum of 10 minutes before checking
charge.
2. Measure liquid service valve pressure by attaching an accurate
gage to service port.
3. Measure liquid line temperature by attaching an accurate
thermistor type or electronic thermometer to liquid near
outdoor coil.
4. Refer to unit rating plate for required subcooling temperature.
5. Refer to Table 4. Find the point where required subcooling
temperature intersects measured liquid service valve pressure.
6. To obtain required subeooling temperature at a specific liquid
line pressure, add refrigerant if liquid line temperature is
higher than indicated or reclaim refrigerant if temperature is
lower. Allow a tolerance of +_3°F.
Units with Indoor Pistons
Units installed with indoor pistons require charging by the super-
heat method.
The following procedure is valid when indoor airflow is within _
21 percent of its rated CFM.
1. Operate unit a minimum of 10 minutes before checking
charge.
2. Measure suction pressure by attaching an accurate gage to
suction valve service port.
3. Measure suction temperature by attaching an accurate ther-
mistor type or electronic thermometer to suction line at service
valve.
4. Measure outdoor air dry-bulb temperature with thermometer.
5. Measure indoor air (entering indoor coil) wet-bulb tempera-
ture with a sling psychrometer.
6,
7.
8.
9.
10.
II.
Refer to Table 5. Find outdoor temperature and evaporator
entering air wet-bulb temperature. At this intersection, note
superheat.
Refer to Table 6. Find superheat temperature located in item 6
and suction pressure. At this intersection, note suction line
temperature.
If a unit has a higher suction line temperature than charted
temperature, add refrigerant until charted temperature is
reached.
[f unit has a lower suction line temperature than charted
temperature, reclaim refrigerant until charted temperature is
reached.
When adding refrigerant, charge in liquid form into suction
service port using a flow-restricting device.
If outdoor air temperature or pressure at suction valve
changes, charge to new suction line temperature indicated on
chart.
Step 13_Final Cheeks
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring and tubing is secure in unit before
adding panels and covers. Securely fasten all panels and
covers.
2. Tighten service valve stem caps to 1/12-turn past t'tnger tight.
3. Leave User's Manual with owner. Explain system operation
and periofftc maintenance requirements outlined in manual+
4. Fill out Dealer Installation Checklist and place in customer
file.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip-
ment failure, periodic maintenance must be performed on this
equipment.
Frequency of maintenance may vary depending upon geographic
areas, such as coastal applications. See User's Manual for infor-
mation.
SUPERHEAT
TEMP
(°F)
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
4O
Table 6--Required Suction-Line Temperature (°F WB)
107.8
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
112.2
37
39
41
43
48
4"7
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
SUCTION PRESSURE AT SERVICE PORT (PSIG)
116.8
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
78
121.2
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
126.0
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
130.8
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
138.8
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
140.8
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
145,8
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
91
9
LEGEND
24-v FACTORY WIRING
-- 24-V FIELD WIRING
FIELD SPLICE CONNECTION
CONTACTOR
A97368
PURON® (R-410A) QUICK REFERENCE GUIDE
• Puron® refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and
replacement compenents are designed to operate with Puron_.
• Puren_ refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.
Puron_ systems should be charged with liquid refrigerant. Use acommercial type metedng device in the
manifold hose when charging into suction line with compressor operating.
• Manifold sets shoutd be at least 700 psig high side and 180 psig low side with 550 psig low-side retard.
Use hoses with 700 psig service pressure rating.
• Leak detectors shouk:l be designed to detect HFC refdgerent.
• Puroo_, as with other HFCs, is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
Do not leave Puror_ suction line filter doers in line longer than 72 hrs.
Do not use liquid-line filter dders with rated working pressures less than 60(3 psig.
• Do not install a suction-lLnefilter drier in liquid line.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere,
• Poe oils may cause damage to certain plastics and roofing materials.
Wrap all filter dders and service valves with wet cloth when brazing.
• A tactory-appreved liquid-line filter drier is required on every unit.
Do not use an R-22 TXV.
If indoor unit is equipped with an R-22 TXV, it must be changed to a Puron_ TXV.
• Never open system to atmosphere while if is under a vacuum.
When system must be opened for service, recover refrigerant, break vacuum with dry nitrogen prior to
opening to atmosphere. Evacuate to 500 microns pdor to recharging.
• Always replace filter drier after opening system for service.
Do not vent Purer_ into the atmosphere.
• Do not use cepUlary tube coils.
• Observe all warnings, cautions, and bold text.
Copyright 200"2 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 38esa3si
I
Manufacturer reserves the right to discontinue, or change at any time, spe_irmations or designs without notice and without incurring obligations,
._ PC 101 Catalog No. 533-80066 printed in U.S,A, Form 381=SA*3SI 12 9_2 38ESA-2SI
Pg Replaces:

Navigation menu