CARRIER Package Units(both Units Combined) Manual L0502457
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 56
Download | |
Open PDF In Browser | View PDF |
50HJ020-028 Single Package Rooftop Units Electric Cooling with Electric Heat Option Installation Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS ...................... 1 INSTALLATION ................................ 2-25 Step 1 -- Provide Unit Support ................... 2 • ROOF CURB • ALTERNATE UNIT SUPPORT • SLAB MOUNT Step 2 -- Remove Shipping Rails ................ 2 Step 3 -- Rig and Place Unit ..................... 2 • POSITIONING • ROOF MOUNT • INSTALLATION ONTO CURB Step 4 -- Field Fabricate Ductwork ............... 9 Step 5 -- Make Unit Duct Connections ........... 9 • VERTICAL CONFIGURATION • HORIZONTAL APPLICATIONS Step 6 --Trap Condensate Drain ................ 10 Step 7- Make Electrical Connections .......... 10 • FIELD POWER SUPPLY • FIELD CONTROL WIRING Step 8 -- Install Outdoor-Air Hood .............. 23 • MANUAL DAMPER ASSEMBLY Step 9 -- Position Optional Power Exhaust or Barometric Relief Damper Hood ............ 25 Step 10- Non-Fused Disconnect ............... 25 Step 11 -- Install All Accessories ............... 25 PRE-START-UP .................................. 26 START-UP .................................... 26-43 Unit Preparation ................................. 26 Compressor Mounting .......................... 26 Refrigerant Service Ports ....................... 26 Crankcase Heaters .............................. 26 Compressor Phasing ............................ 26 Internal Wiring .................................. 26 Evaporator Fan .................................. 26 Condenser Fans and Motors .................... 26 Return-Air Filters ................................ 26 Outdoor-Air Inlet Screens ....................... 26 Optional EconoMiSer IV ......................... 37 Operating Sequence ............................ 42 SERVICE ..................................... 43-49 Cleaning ........................................ 43 Lubrication ...................................... 43 Evaporator Fan Service and Replacement ....... 43 Manufacturer Page Evaporator Fan Performance Adjustment ....... 44 Belt Tension Adjustment ........................ 44 Condenser Fan Adjustment ..................... 45 Power Failure ................................... 45 Refrigerant Charge .............................. 45 Filter Drier ...................................... 45 Protective Devices .............................. 45 Relief Devices ................................... 46 Control Circuit, 24-v ............................. 46 Replacement Parts .............................. 46 TROUBLESHOOTING ........................ 50-53 Unit Troubleshooting ............................ 50 EconoMiSer IV Troubleshooting ................. 51 START-UP CHECKLIST ........................ CL-I SAFETY Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions of replacing filtel:s. All other operations should be perforated by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations. Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. I operating limits. If limits are exceeded, the units will automatically lock the complessor out of operation. IMPORTANT: have high mnbient temperature Manu;d reset willUnits be required to restart the compressor reserves the right to discontinue, or change at any time, specifications Catalog No. 04-53500013-01 Printed in U.S,A, CONSIDERATIONS or designs without notice and without incurring obligations. Form 50HJ-30SI Pg 1 10-05 Replaces: 50HJ-26SI I I INSTALLATION Step 1 -- Provide Step 3 -- Rig and Place Unit -- Inspect unit for transpollation &image. See Tables 1-3 for physical claim with transportation agency. Unit Support ROOF CURB -- Assemble or install accessory roof curb in accor&mce with instructions shipped with this accessory. See Fig. 1. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Ductwork must be attached to curb and not to unit. Curb must be level. This is necessary to permit unit diain to function properly. Unit leveling tolerance is _+J/m(_in. per linear fl in any direction. Refer to Accessory Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering matetial. Carrier roof curb accessoties are for flat roofs or slab mounting. IMPORTANT: The gasketing of the unit to the roof curb is ctitic_d for a watertight seal. Install gasket with the roof curb as shown in Fig. 1. Improperly applied gasket can _dso result in air leaks and poor unit performance. Do not slide unit to position on roof curb. ALTERNATE UNIT SUPPORTWhen a curb cannot be used, install unit on a noncombustible surface. Support unit with sleepel_, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equ_dly spaced 4-in. x 4-in. pads on each side. SLAB MOUNT (Horizontal Units Only) -- Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to plevent gross and foliage from obstructing airflow. NOTE: Horizontal required. units may be installed on a roof curb if Step 2 -- Remove Shipping Rails -- Remove shipping rails ptior to loweting unit onto roof curb. See Fig. 2. The rails are attached to the unit at both the return end and condenser end. Remove the screws from both ends of each rail. Be cmeful not to drop the rails onto any surface that could be &imaged. Discard the mils. It is important to replace the screws into the unit to avoid any tfir or water leakage. Do not allow the shipping rail to drop on the roof surface. Dmnage to the roof surface may result. data. File any All panels must be in place when rigging. Unit is not designed for handling by fork truck. Damage to unit can result. Do not &op unit; keep uptight. Use spreader bm_ over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frmne as a leference; leveling tolerance is _+1/1(_in. per linetu ft in any direction. See Fig. 3 for additional information. Unit rigging weight is shown in Fig. 3. Four lifting holes me provided in the unit base mils as shown in Fig. 3. Refer to rigging instructions on unit. POSITIONING -- Maintain clearance, per Fig. 4, around and above unit to provide minimum distance from combustible matetials, proper airflow, and service access. Do not install unit in an indoor location. Do not locate air inlets nero exhaust vents or other sources of contaminated all: Although unit is weatherproof, higher level runoff and overhangs. guard against water from ROOF MOUNT -- Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1. INSTALLATION ONTO CURB -- The 50HJ units are designed to fit on the accessory full perimeter curb. Correct placement of the unit onto the curb is ctitical to operating performance. To aid in correct positioning, 3/_-in. diameter locating holes have been added to the unit base rails. When placing the unit, these holes should line up with the roof curb edge as shown in Fig. 5 and 6, to assure proper duct opening alignment. For placement on the curb, use the alignment holes located approximately 2-in. from the end of the base rail on the return end of the unit. See labels on the side of the unit for more details. Do not slide unit to position it when it is sitting on the curb. Curb gasketing matetial may be &imaged and leaks may result. _z c_ _J ._ oo r_ o I \ I I o_ _ SHIPPING RAIL_ Fig. 2 -- Shipping Rail Removal CAUTIONNOTICETO AM. PAriS MUSTBE IN PLACE_ RIGGERS: RIGGING. NOTICETO RIGGB_S: Rig by bserti_ hooks 120 inches (3048 protect con of 50HJ UNIT SIZE 020 MAX WEIGHT (Ib) 3358 024 028 _ urit from top from of unit to ilto unit base eyehoolL Leave rails as shown. Ma_ltain a distance of con cover attached to ur(t _ dgg_g damage. CENTER OF GRAVITY (in.) X 63.9 Y 34.0 Z 30.5 3380 63.9 34.5 30.5 3769 67.8 35.0 35.0 NOTES: 1. Add 150 Ib (68 kg) for domestic crating. 2. See label for unit location on roof curb. Fig. 3 -- Rigging Details 10'-0 o (3048 MM) to r _i 8 i i i i J _ _1 o @ @ / m ii €,,, ,£ €,,, E ........... L............................................................ _ .................... J €,,, II1 I Table 1 -- Physical Data UNIT 50HJ NOMINAL CAPACITY (tons) OPERATING WEIGHT (Ib) AI/AI* COMPRESSOR Quantity Number of Refrigerant Circuits Oil (ounces) Ckt A...Ckt B...Ckt C REFRIGERANT TYPE Expansion Device Operating Charge (Ib) Circuit A Circuit B Circuit C CONDENSER FAN Nominal Cfm (Total, Quantity...Diameter Motor Hp...Rpm Watts Input (Total) CONDENSER COIL Rows... Fins/in. Total Face Area (sq EVAPORATOR FAN Quantity...Size Type Drive Nominal Cfm Motor Bearing Type Maximum Allowable EVAPORATOR COIL Rows... Fins/in. Total Face Area (sq all fans) (in.) ft) Fan Rpm ft) HIGH-PRESSURE SWITCH (psig) Cutout Reset (Auto) OUTDOOR-AIR INLET SCREENS Quantity...Size (in.) RETURN-AIR FILTERS Quantity...Size (in.) LEGEND N/A TXV --- Not Applicable Thermostatic Expansion Valve *Aluminum evaporator coil and aluminum condenser coil. 020 18 024 20 028 25 2139 2187 2446 3 3 68._68._90 3 3 90...90...90 2 2 110...110...N/A TXV TXV TXV 13.1 12.7 15.2 13.8 13.9 15.5 21.8 20.3 N/A 14,000 4...22 1/4_.1100 1400 14,000 4...22 1/4...1100 1400 21,000 6...22 1/4_.1100 2100 2...17 57.78 2...17 57.78 2...17 66.67 2._15xl 1 Belt 7000 Ball 1400 2_.15xl 1 Belt 8000 Ball 1400 2...15xl 1 Belt 10,000 Ball 1400 3...15 23.33 4...15 23.33 4...15 27.22 426 320 426 320 426 320 3._20x25 3...20x25 3._20x25 9... 16x25 9... 16x25 9... 18x24 Table 2 -- Fan Motor and Drive Data -- Vertical Supply/Return O2O 50HJ LOW RANGE Motor Hp Drive Motor Nominal Rpm Drive Maximum Continuous Bhp Drive Maximum Continuous Watts Motor Frame Size Motor Shaft Diameter (in.) Fan Rpm Range Motor Pulley Min. Pitch Diameter (in.) Motor Pulley Max. Pitch Diameter (in.) Blower Pulley Pitch Diameter (in.) Blower Pulley Shaft Diameter (in.) Blower Pulley Type Pulley Center Line Distance (in.) Belt, Quantity...Type...Length (in.) Speed Change per Turn - Moveable Pulley Moveable Pulley Maximum Full Turns Factory Speed Setting (rpm) MID-LOW RANGE Motor Hp Motor Nominal Rpm Maximum Continuous Bhp Maximum Continuous Watts Motor Frame Size Motor Shaft Diameter (in.) Fan Rpm Range Motor Pulley Min. Pitch Diameter (in.) Motor Pulley Max. Pitch Diameter (in.) Blower Pulley Pitch Diameter (in.) Blower Pulley Shaft Diameter (in.) Blower Pulley Type Pulley Center Line Distance (in.) Belt, Quantity...Type...Length (in.) Speed Change per Turn - Moveable Pulley Moveable Pulley Maximum Full Turns Factory Speed Setting (rpm) MID-HIGH RANGE Motor Hp Motor Nominal Rpm Maximum Continuous Bhp Maximum Continuous Watts Motor Frame Size Motor Shaft Diameter (in.) Fan Rpm Range Motor Pulley Min. Pitch Diameter (in.) Motor Pulley Max. Pitch Diameter (in.) Blower Pulley Pitch Diameter (in.) Blower Pulley Shaft Diameter (in.) Blower Pulley Type Pulley Center Line Distance (in.) Belt, Quantity...Type...Length (in.) Speed Change per Turn - Moveable Pulley Moveable Pulley Maximum Full Turns Factory Speed Setting (rpm) HIGH RANGE Motor Hp Motor Nominal Rpm Maximum Continuous Bhp Maximum Continuous Watts Motor Frame Size Motor Shaft Diameter (in.) Fan Rpm Range Motor Pulley Min. Pitch Diameter (in.) Motor Pulley Max. Pitch Diameter (in.) Blower Pulley Pitch Diameter (in.) Blower Pulley Shaft Diameter (in.) Blower Pulley Type Pulley Center Line Distance (in.) Belt, Quantity...Type...Length (in.) Speed Change per Turn - Moveable Pulley Moveable Pulley Maximum Full Turns Factory Speed Setting (rpm) LEGEND Bhp N/A --- Brake Horsepower Not Applicable (rpm) (rpm) (rpm) (rpm) O24 208/230 and 460 v 575 v N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 208/230 and 460 v 3.7 1725 4.25 3698 56HZ 7/8 685-939 2.7 3.7 6.8 1.1875 Fixed 5 1745 5.75 4900 184T 11/8 949-1206 3.7 4.7 6.8 1.1875 Fixed 5 1745 5.75 4900 S 184T 11/8 949-1206 3.7 4.7 6.8 1.1875 Fixed 9,81-13.055 1...BX...38 43 6 1078 5 1745 5.75 4900 S184T 11& 897-1139 3.7 4.7 7.2 1.1875 Fixed 9,81-13.055 1...BX...38 40 6 1018 5 1745 5.75 4900 184T 11/8 873-1108 3.7 4.7 7.4 1.1875 Fixed 9.81-13.055 1...BX...36 39 6 991 7.5 1745 8.63 7267 $213T 941-1176 4.8 6.0 8.9 1.1875 Fixed 9.025-12.179 1...BX...42 39 6 1059 7.5 1745 8.63 7267 $213T 10 1745 11.5 9582 $215T 13/8 5 1745 5.75 4900 184T 11/8 751-954 3.7 4.7 8.6 1.1875 Fixed 9.81-13.055 1 ...BX...40 34 6 853 3 1725 3.45 3149 56HZ 7/8 810-1072 3.1 4.1 6.6 1.1875 Fixed 11,286-14,475 1...BX...38 44 6 941 1078-1274 5.5 6.5 8.9 1.1875 Fixed 9.025-12.179 1...BX...42 33 6 1176 575 v 11.293-13.544 1...BX...38 42 6 812 3.7 1725 4.25 3698 56HZ 7/8 647-886 2.7 3.7 7.2 1.1875 Fixed 11.293-13.544 1 ...BX...38 40 6 767 7.5 1745 8.63 7267 $213T 13/8 1078-1274 5.5 6.5 8.9 1.1875 Fixed 9.025-12.179 1...BX...42 33 6 1176 O28 13/8 13/8 1014-1297 4.3 5.5 7.4 1.1875 Fixed 9.025-12.179 2...BX...38 47 6 1156 208/230 and 460 v 5 1745 5.75 4900 S 184T 1% 687-873 3.7 4.7 9.4 1.1875 Fixed 9.81-13.055 1...BX...41 31 6 780 5 1745 5.75 4900 S184T 11_ 805-1007 4.8 6.0 10.4 1.1875 Fixed 575 v 5 1745 5.75 4900 184T 11/8 687-873 3.7 4.7 9.4 1.1875 Fixed 9,81-13,055 1...BX...41 31 6 780 5 1745 5.75 4900 184T 11/8 805-1007 4.8 6.0 10.4 1.1875 Fixed 9,81-13,055 1...BX...45 34 6 906 9.81-13.055 1...BX...38 43 6 1078 9.81-13.055 1...BX...45 34 6 906 7.5 1745 8.63 7267 S213T 13/8 941-1176 4.8 6.0 8.9 1.1875 Fixed 9.025-12.179 1...BX...42 39 6 1059 7.5 1745 8.63 7267 S213T 13/8 941-1176 4.8 6.0 8.9 1.1875 Fixed 9.025-12.179 1...BX...42 39 6 1059 7.5 1745 8.63 7267 S213T 1_8 941-1176 4.8 6.0 8.9 1.1875 Fixed 9.025-12,179 1...BX...42 39 6 1059 10 1745 11.5 9582 S215T 13/8 1014-1297 4.3 5.5 7.4 1.1875 Fixed 9.025-12.179 2...BX...38 47 6 1156 10 1745 11.5 9582 $215T 13/8 1014-1297 4.3 5.5 7.4 1.1875 Fixed 9.025-12,179 2...BX...38 47 6 1156 lO 1745 11.5 9582 $215T 13/8 1014-1297 4.3 5.5 7.4 1.1875 Fixed 9.025-12,179 2...BX...38 47 6 1156 Table 3 -- Fan Motor and Drive Data -- Horizontal Supply/Return 020 50HJ 208/230 and 460 v LOW RANGE N/A Motor Hp N/A Motor Nominal Rpm N/A Maximum Continuous Bhp Maximum Continuous Watts N/A Motor Frame Size N/A N/A Motor Shaft Diameter (in.) N/A Fan Rpm Range N/A Motor Pulley Min. Pitch Diameter (in.) N/A Motor Pulley Max. Pitch Diameter (in.) N/A Blower Pulley Pitch Diameter (in.) N/A Blower Pulley Shaft Diameter (in.) N/A Blower Pulley Type N/A Drive Pulley Center Line Distance (in.) N/A Drive Belt, Quantity...Type...Length (in.) N/A Drive Speed Change per Turn - Moveable Pulley (rpm) N/A Drive Moveable Pulley Maximum Full Turns N/A Drive Factory Speed Setting (rpm) MID-LOW RANGE 3.7 Motor Hp 1725 Motor Nominal Rpm 4.25 Maximum Continuous Bhp Maximum Continuous Watts 3698 Motor Frame Size 56HZ 7/8 Motor Shaft Diameter (in.) 647-886 Fan Rpm Range 2.7 Motor Pulley Min. Pitch Diameter (in.) 3.7 Motor Pulley Max. Pitch Diameter (in.) 7.2 Blower Pulley Pitch Diameter (in.) 1,1875 Blower Pulley Shaft Diameter (in.) Fixed Blower Pulley Type 11.293-13.544 Pulley Center Line Distance (in.) 1...BX,,.38 Belt, Quantity...Type...Length (in.) 40 Speed Change per Turn - Moveable Pulley (rpm) 6 Moveable Pulley Maximum Full Turns 767 Factory Speed setting (rpm) MID-HIGH RANGE 5 Motor Hp 1745 Motor Nominal Rpm 5.75 Maximum Continuous Bhp Maximum Continuous Watts 4900 Motor Frame Size $184T 1% Motor Shaft Diameter (in.) Fan Rpm Range 897-1 139 3.7 Motor Pulley Min. Pitch Diameter (in.) 4.7 Motor Pulley Max. Pitch Diameter (in.) 7.2 Blower Pulley Pitch Diameter (in.) 1.1875 Blower Pulley Shaft Diameter (in.) Fixed Blower Pulley Type 9.81-13.055 Drive Pulley Center Line Distance (in.) 1 ...BX...38 Belt, Quantity...Type...Length (in.) 4O Speed Change per Turn - Moveable Pulley (rpm) 6 Moveable Pulley Maximum Full Turns 1018 Factory Speed Setting (rpm) HIGH RANGE 7.5 Motor Hp 1745 Motor Nominal Rpm 8.63 Maximum Continuous Bhp Maximum Continuous Watts 7267 Motor Frame Size S213T 13/8 Motor Shaft Diameter (in.) 1078-1274 Fan Rpm Range 5.5 Motor Pulley Min. Pitch Diameter (in.) 6.5 Motor Pulley Max. Pitch Diameter (in.) 8.9 Blower Pulley Pitch Diameter (in.) 1.1875 Blower Pulley Shaft Diameter (in.) Fixed Blower Pulley Type 9.025-12,179 Pulley Center Line Distance (in.) 1...BX...42 Belt, Quantity...Type...Length (in.) 33 Speed Change per Turn - Moveable Pulley (rpm) 6 Moveable Pulley Maximum Full Turns 1176 Factory Speed Setting (rpm) LEGEND Bhp N/A --- Brake Horsepower Not Applicable 024 028 575 v 208/230 and 460 v 575 v N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 3.7 1725 4.25 3698 56HZ 7/8 685-939 2.7 3.7 6.8 1.1875 Fixed 1.293-13.544 1...BX...38 42 6 812 5 1745 5.75 4900 184T 11/8 751-954 3.7 4.7 8.6 1.1875 Fixed 9,81-13,055 1...BX...4O 34 6 853 5 1745 5.75 4900 S 184T 11/8 687-873 3.7 4.7 9.4 1.1875 Fixed 9,81-13,055 1...BX...41 31 6 780 5 1745 5.75 4900 184T 11/8 687-873 3.7 4.7 9.4 1.1875 Fixed 9.81-13,055 1 ...BX,..41 31 6 780 5 1745 5.75 4900 S184T 11/8 949-1206 3.7 4.7 6.8 1.1875 Fixed 9.81-13.055 1 ...BX,,.38 43 6 1078 5 1745 5.75 4900 184T 11/8 949-1206 3.7 4.7 6.8 1.1875 Fixed 9,81-13,055 1 ._BX_.38 43 6 1078 5 1745 5.75 4900 S 184T 11/8 805-1007 4.8 6.0 10.4 1.1875 Fixed 9,81-13,055 1...BX...45 34 6 906 5 1745 5.75 4900 184T 11/8 805-1007 4.8 6.0 10.4 1.1875 Fixed 9.81-13,055 1...BX...45 34 6 906 3 1725 3.45 3149 56HZ 7/8 810-1072 3.1 4.1 6,6 1.1875 Fixed 11,286-14.475 1...BX...38 44 6 941 5 1745 5.75 4900 184T 11/8 873-1108 3.7 4.7 7.4 1.1875 Fixed 9.81-13.055 1...BX...38 39 6 991 7.5 1745 8.63 7267 S213T 13/8 1078-1274 5.5 6.5 8.9 1.1875 Fixed 9.025-12.179 1 ...BX...42 33 6 1176 7.5 1745 8.63 7267 $213T 13/8 941 - 1176 4.8 6.0 8.9 1.1875 Fixed 9.025-12.179 1...BX...42 39 6 1059 lO 1745 11.5 9582 $215T 13/8 1014-1297 4.3 5.5 7.4 1.1875 Fixed 9.025-12,179 2...BX...38 47 6 1156 7.5 1745 8.63 7267 S213T 13/8 941-1176 4.8 6.0 8.9 1.1875 Fixed 9.025-12,179 1 ...BX...42 39 6 1059 10 1745 11.5 9582 $215T 1_8 1014-1297 4.3 5.5 7.4 1.1875 Fixed 9.025-12.179 2...BX...38 47 6 1156 208/230 and 460 v 575 v 7.5 1745 8.63 7267 $213T 7.5 1745 8.63 7267 S213T 1_8 941-1176 4.8 6.0 8.9 1.1875 Fixed 9.025-12.17£ 1...BX...42 39 6 1059 941-1176 4.8 6.0 8.9 1.1875 Fixed 9.025-12,179 1...BX...42 39 6 1059 lO 1745 11.5 9582 S215T 13/8 1014-1297 4.3 5.5 7.4 1.1875 Fixed 9.025-12.17£ 2...BX...38 47 6 1158 10 1745 11.5 9582 S215T 13/8 1014-1297 4.3 5.5 7.4 1.1875 Fixed 9.025-12,179 2...BX...38 47 6 1156 13/8 ALIGNMENT HOLE (IN BASE RAIL)\ HOLE SHOULD LINE UP WITH ROOF CURB EDGE FLANGE ALIGNMENT q EDGE FLANGE For vertical supply and return units, tools or pmls could diop into ductwork and cause an injury. Install a 90-degree turn in the return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from ftdling into the conditioned space. f Units with electric heat require a 1-in. clearance for the first 24 in. of ductwork. Outlet grilles must not lie directly below unit discharge. Fig. 5 -- Alignment Hole Details NOTE: A 90-deglee elbow must be provided ductwork to comply with UL (Underwriters' codes for use with electric heat. RETURN OPENING ALIGNMENT SIDES CURB SUPPL OPENING HOLES FOR CURB-BOTH _"--...._ HORIZONTAL APPLICATIONS -- Horizontal units are shipped with outer panels that tdlow for side by side horizontal duct connections. If specified during ordering, the unit will be shipped with the vertical duct openings blocked off from the factoq, ready for side supply installation. If the horizontal option was not specified fit time of ordering the unit, a fieldinstalled accessory kit is required to convert the vertical unit into a horizontal supply configuration. SUPPLY OPENING CURB RETURN OPENINg.- Installation of the duct block-off covers should be completed prior to placing the unit unless sufficient side clem'ance is available. A minimum of 66 in. is required between the unit and any obstruction to install the duct block-off covers. _ ROOF CURB Fig. 6 -- Alignment Hole in the supply Laboratories) Location ECONOMIZER Step 4 -- Field Fabricate Ductwork -- On vertical units, secure all ducts to roof curb and building structure. Do not connect ducm'ork to unit. For horizontal applications, fieldsupplied flanges should be attached to horizontal dischalge openings and all ductwork secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned insulated and covered with a vapor baniel: space must SEE NOTE be If a plenum return is used on a vertictd unit, the return should be ducted through the roof deck to comply with applicable fire codes. A minimum clearance is not required around ductwork. Cabinet leturn-air static plessure (a negative condition) shall not exceed 0.35 in. wg with economizer or 0.45 in. wg without economizer ,N....... @ OUT A,R AIR NOTE: Do not drill in this area; damage to basepan may result in water leak. Fig. 7 -- Air Distribution -Vertical Supply and Return These units are designed for a minimum continuous returnair temperature in heating of 50 F (dry bulb), or an intermittent operation down to 45 F (di'y bulb), such as when used with a night set-back thermostat. ECONOMIZER To operate fit lower return-air temperatures, a field-supplied outdoor-air temperature control must be used to initiate both stages of heat when the temperature is below 45 K Indoor comfort may be compromised when these lower air temperatures are used with insufficient heating temperature rise. Step 5 -- Make Unit Duct Connections VERTICAL CONFIGURATION -- Unit is shipped for thruthe-bottom duct connections. DuctwoN openings are shown in Fig. 1 and 4. Duct connections for vertical supply and return configuration are shown in Fig. 7. Field-fabricated concentric ductwork may be connected as shown in Fig. 8 and 9. The unit is designed to attach the ductwork to the roof curb. Do not attach duct directly to the unit. ;EE NOTE SEE AIR OUT AIR IN AIR OUT NOTE: Do not drill in this area; damage to basepan may result in water leak. Fig. 8 -- Air Distribution -- Concentric Duct Field wiring must conform to temperature type "T" wire. All field wiring must comply local requirements. limitations for with NEC and Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%. Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. FIELD CONTROL WIRING -- Unit c_m be controlled with a C_uTier-approved accessory thermostat. Install therlnostat according to the installation instructions included with accessory. Locate thennostat assembly on a solid interior w_dl in the conditioned space to sense average temperature. Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit into unit to lowvoltage connections as shown on unit label wiring diagraln and in Fig. 13. BAFFLE NOTE: Dimensions diffuser. A, A', B, and B' are obtained from field-supplied ceiling Shaded areas indicate block-off pans. Fig. 9 -- Concentric Duct Details NOTE: For wire runs up to 50 fl, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 fl, use no. 14 AWG insulated wire (35 C Minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat. Side supply duct dimensions and locations are shown on Fig. 4. Connect ductwork to horizontal duct flange connections on side of unit. Step 6 -- Trap Condensate Drain -- See Fig. 10 for drain location. One 3/4-in. half coupling is provided outside unit evaporator section for condensate diain connection. A trap at least 4-in. deep must be used. See Fig. 11. Text continued All units must have an external trap for condensate diainage. Install a trap at least 4 in. deep and protect against freezeup. If drain line is installed downstrealn from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection. Step 7 -- Make Electrical on puge 23. -DAMPER ACCESS i 1 MOTOR COVER m_--.-- Connections F[ELD POWER SUPPLY -- Unit is factory wired for voltage shown on unit nalneplate. Be sure to check for correct voltage. CONDENSATE ACCESS When inst_flling units, provide disconnect per NEC (National Electrical Code) of adequate size (MOCP [Maximum Overcurrent protectionl of unit is on the informative plate). See Tables 4A and 4B. All field wiring must comply with NEC and local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 12 for power wiring connections to the unit power termimd block and equipment grounds. J DRAIN (P .... DI CONNECTION [1208] / 5-1/4 [132 I SUPPLY AIR Fig. 10- Route power and ground lines through control box end panel or unit basepan (see Fig. 4) to connections as shown on unit wiring diagram and Fig. 12. The correct power phasing is critical to the operation of the scroll compressors. An incorrect phasing will result in compressor shutdown on thermal overload and possible dmnage to compressor. Should this occur, power phase correction must be made to the incoming powec ONE_N. PER 1OFT Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occuc This ground may consist of electrical wire connected to unit ground lug in control comp_utment, or conduit approved for electrical ground when inst_dled in accordance with NEC, ANSI/NFPA (National File Protection Association), latest edition, and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others. OFUNE RETURN AIR Condensate Drain Details BASE \ \ RAIL I --I I I INq" _-[__J/t z' MiNI [ Z/I SEE NOTE T OOi _ROOF I CURB NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended, Fig. 11 -- Condensate 10 Drain Piping Details Table 4A -- Electrical Data -- Units Without Convenience Outlet UNIT SIZE 50HJ NOMINAL VOLTAGE (3 Ph, 80 Hz) VOLTAGE RANGE MIn Max COMPRESSOR No. 2 No. 1 RLA LRA RLA LRA OFM ELECTRIC HEAT No. 3 RLA LRA Gty Hp FLA kW -- 208/230 187 253 16.7 130 16.7 130 22.4 184 4 0.25 FLA Hp -- 19/25 52/ POWER EXHAUST IFM 60 FLA 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 1.5 38/50 56/75t 104/120 156/180 020 -- -- 25 460 414 506 9 70 9 70 10.7 90 4 0.25 30 3.7 4.8 5 7.6 7.5 11 3.7 4.8 5 7.6 7.5 11 3.7 4.8 5 7.6 7.5 11 0.7 50 60 Gty 2 75 LEGEND FLA NACR --- IFM LRA --- Full Load Amps Heating, AirConditioningand Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps MCA MOCP NEC OFM RLA ------ Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps 90 11 deviation is 7 v. 5.9 MCA MOCP* 78/ 77 100/ 90/ 89 100/100 84/ 83 100/100 90/ 89 104/102 90 FLA 83/ 82 97/ 96 1 5.9 96/ 94 100/100 92/ 89 100/100 99/ 96 2 1 5.9 104/101 125/110 112/110 78/ 87 100/ 2 1 5.9 93/102 100/110 97/ 96 100/100 110/110 90/ 89 104/102 90 83/ 82 2 1 5.9 86/ 94 101/109 95/103 100/110 99/ 96 2 1 5.9 110/117 125/125 112/110 143/132 150/150 132/149 2 1 5.9 158/147 175/150 145/163 151/139 175/150 139/155 166/154 175/175 152/169 160/148 175/150 147/163 2 1 5.9 2 1 5.9 175/162 78/ 77 200/175 100/ 90 161/177 83/ 82 2 1 5.9 90/ 89 100/100 97/ 96 84/ 83 100/100 90/ 89 104/102 2 1 5.9 96/ 94 100/100 92/ 89 100/100 99/ 96 2 1 5.9 104/101 125/110 112/110 39 45 42 2 1 3.1 45 50 49 42 48 50 50 45 52 45 50 49 51 60 56 44 45 42 51 60 49 47 50 45 55 60 52 51 60 49 2 1 3.1 2 1 3.1 2 2 1 1 3.1 3.1 2 1 3.1 59 66 60 80 56 75 2 1 3.1 74 80 82 70 80 78 77 80 85 74 80 82 82 90 89 96 100 109 3.1 104 110 116 100 107 110 125 112 119 104 125 116 112 125 123 2 2 1 1 1 3.1 3.1 2 1 3.1 2 1 3.1 from average w>ltage. percent o1 voltage imbalance. 7 100x Imbalance= = 1.53% of phase imbalance is satisfactory IMPORTANT: local electric utility If thecompany supply voltage immediately, phase as it is below the maximum imbalance allowable is more than 2%, contact your 3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field. 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively. 5. The FLA load amps provided in the table for electric heaters are based on 208/240,480 and 600 v. 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). max voltage deviatk)n from average voltage average voltage AC = 455 v Average Voltage BC = 464 v 7.5 Maximum This amount 2%. Example: Supply voltage is 460-3-60. A B C AB = 452 v (_ 7.6 maximum deviation - 452 = 5 v - 457 = 7 v - 455 = 2 v % Voltage NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x 5 Determine (AB) 457 (BC) 464 (AC) 457 Determine *Fuse or HACR circuit breaker. 1-208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. 4.8 1 _La_ DISCONNECT SIZE 2 2 3.7 Hp POWER SUPPLY = 452 + 464 + 455 3 1371 =---;= 457 11 Table 4A -- Electrical Data -- Units Without Convenience UNIT SIZE 5OHJ VOLTAGE RANGE NOMINAL VOLTAGE (3Ph, 80Hz) Mln COMPRESSOR NO. 2 NO. 1 Max RLA LRA RLA OFM ELECTRIC HEAT NO. 3 LRA RLA LRA Qty Hp FLA _,'ea' kW Outlet (cont) IFM FLA POWER EXHAUST Hp FLA 3 3.9 5 6.1 7.5 9 24.8 020 575 518 633 7 55 7 55 9.3 73 4 0.25 3.9 5 6.1 7.5 9 3 3.9 5 6.1 7.5 9 3 3.9 5 6.1 7.5 9 24 Hp _L,I MCA 32 MOCP* 40 FLA 35 2 1 2.4 37 45 40 35 40 37 39 45 43 37 45 40 42 50 46 35 40 35 2.4 41 45 40 38 44 40 45 37 43 41 45 40 47 50 46 62 70 57 68 70 63 65 70 60 71 80 65 69 70 63 2 1 48.3 46 75 2 1 2.4 2 1 2.4 2 1 2 UNIT SIZE 50HJ NOMINAL VOLTAGE 020 208/240 VOLTAGE RANGE MIn COMPRESSOR NO. 2 NO. 1 Max LRA OFM ELECTRIC HEAT NO. 3 LRA LRA Qty (ea) ........ UNIT SIZE NOMINAL VOLTAGE 50HJ (3 Ph, 80 HZ) MIn COMPRESSOR NO. 2 NO. 1 Max RLA LRA RLA LRA NO. 3 2 1 2.4 75 80 80 90 69 91 2 1 2.4 86 90 96 83 90 93 89 190 99 86 100 97 92 190 102 1 RLA LRA Gty Hp FLA (ea) 208/230 187 253 16.7 130 16.7 130 22.4 184 4 0.25 1.5 LEGEND FLA HACR --- IFM LRA --- Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Arnps MCA MOCP NEC OFM RLA ------ Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps *Fuse or HACR circuit breaker. 1-208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. POWER EXHAUST A Supply voltage a C Hp FLA (ea) MCA MOCP* FLA -- -- -- 156/180 175/200 179/207 kW = POWER EXHAUST IFM FLA Hp 156/180 Qty FLA 10.6/ 9.6 5 16.7/15.2 7.5 24.2_2.0 2 2 2 Hp 1 1 1 POWER SUPPLY FLA 5.9 5.9 5.9 DISCONNECT SIZE MCA MOCP* FLA 169/192 200/225 192/218 184/207 209/225 205/232 177/199 209/225 199/224 192/214 209/225 212/238 186/208 200/225 207/232 201/222 225/225 221/246 Determine (AB) 457 (BC) 464 (AC) 457 maximum deviation from average voltage. - 452 = 5 v - 457 = 7 v - 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 Imbalance = 100 x of phase imbalance is satisfactory as it is below the maximum allowable is more than 2%, contact 452 + 464 + 455 3 1371 3 = 457 12 ] your ] 3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field. 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 469, 575-v units, respectively. 5. The FLA load amps provided in the table for electric heaters are based on 208/240, 480 and 600 v. 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). v Average BC = 464 Voltage v 56/75 HEATt local electric utility immediately. IMPORTANT: If thecompany supply voltage phase imbalance AC = 455 v (_ DISCONNECT SIZE = 1.53% is 460-3=60. AB =452 POWER SUPPLY FLA This amount 2%. max voltage deviation from average voltage average voltage Example: 2.4 156/180 % Voltage NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 449), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imhalar_ce in supply voltage is greater than 2%. Use the folk)wing formula to determine the percent o1 voltage imbalance. % Voltage Imbalance = 100 x 1 kW 3.7 020 2.4 56/75 ELECTRIC HEAT OFM 2.4 HEAT't IFM FEEDER CIRCUIT FOR 208/230 UNIT WITH 75-kW ELECTRIC VOLTAGE RANGE 2.4 1 2 HEAT BRANCH CIRCUIT 208/240 75-kW ELECTRIC 2.4 1 2 ELECTRIC 2.4 1 2 0.7 DISCONNECT SIZE Qty 2 3 POWER SUPPLY Table 4A -- Electrical Data -- Units Without Convenience Outlet (cont) UNIT SIZE 50HJ NOMINAL VOLTAGE (3Ph, 6OHz) VOLTAGE RANGE Mln Max No. 1 RLA LRA COMPRESSOR No. 2 RLA LRA OFM ELECTRIC HEAT No. 3 RLA LRA Gty Hp _!!FLA kW FLA POWER EXHAUST IFM Hp FLA Qty Hp POWER SUPPLY FLA (ea) ] 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 19/25 208/230 187 253 22.4 184 22.4 184 22.4 184 4 0.25 30.8/28 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 10 30.8/28 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 10 30.8/28 52/60 1.5 88/50 104/120 56/75t 10.6/9.6 5 16.7/15.2 7.5 24.2/22 10 30.8/28 5.9 101/100 2 1 5.9 107/106 2 3.7 4.8 5 7.6 7.5 11 10 14 3.7 4.8 46O 414 506 10.7 90 10.7 90 10.7 90 4 0.25 5 7.6 7.5 11 10 14 3.7 4.8 5 7.6 7.5 11 10 14 3.7 4.8 5 7.6 30 0.7 50 75 100/100 103/102 125/125 117/115 103/101 125/110 112/109 115/113 125/125 126/123 112/108 125/125 120/116 5.9 124/120 150/125 133/130 100/100 110/110 96/ 95 110/109 5.9 60 2 1 5.9 100/100 103/102 2 1 5.9 107/109 125/125 117/115 103/103 125/110 112/109 115/117 125/125 126/123 112/110 125/125 120/116 124/125 150/125 133/130 143/132 150/150 132/149 96/ 2 2 1 1 5.9 5.9 7.5 11 94 2 1 5.9 158/147 151/139 175/150 175/150 145/163 139/155 2 1 5.9 166/154 175/175 152/169 160/148 175/150 147/163 175/162 200/175 161/177 169/155 175/175 155/170 183/170 200/175 169/184 2 1 1 5.9 5.9 89/ 88 100/100 96/ 95 2 1 5.9 101/100 110/110 110/109 2 1 5.9 96/ 94 107/106 100/100 125/125 103/102 117/115 103/101 125/110 112/109 2 1 5.9 115/113 125/125 126/123 112/108 125/125 120/116 124/120 150/125 133/130 2 2 1 1 5.9 3.1 42 50 46 49 50 53 45 50 49 2 1 3.1 51 49 60 50 56 53 2 1 3.1 55 60 60 52 60 56 59 60 63 44 50 46 51 60 53 47 50 49 3.1 55 60 56 51 59 60 60 53 60 55 60 56 63 70 63 66 80 75 74 80 82 70 80 78 77 80 85 74 80 82 90 90 89 85 2 2 1 1 1 3.1 3.1 2 1 3.1 2 1 3.1 2 2 1 1 3.1 3.1 2 1 3.1 82 78 2 1 3.1 85 90 92 96 1O0 109 104 110 116 100 110 112 107 125 119 104 125 116 112 125 123 2 2 90 94 89/ 88 101/102 2 25 1 95 110/109 96/ 1 FLA 96/ 110/110 156/180 024 MOCP* 100/100 88 1 2 3.7 MCA 89/ 2 2 10 [ DISCONNECT SIZE 2 1 1 1 3.1 3.1 3.1 12O 127 See legend and notes on next page. ]3 Table 4A -- Electrical Data -- Units Without Convenience UNIT SIZE 5OHJ NOMINAL VO LTAG E (3 Ph, 80 HZ) VOLTAGE RANGE MIn COMPRESSOR NO. 2 NO. 1 Max RLA LRA RLA OFM ELECTRIC HEAT NO. 3 LRA RLA LRA Qty Hp FLA iea} kW Outlet (cont) IFM FLA POWER EXHAUST Hp FLA 5 6.1 7.5 9 10 11 5 6.1 024 575 518 633 9.3 73 9.3 73 9.3 73 4 0.25 24 7.5 9 10 11 5 6.1 7.5 9 10 11 5 6.1 7.5 9 10 11 Hp _L4 MCA 39 2 1 2.4 44 50 48 42 50 46 47 50 51 44 50 48 49 60 53 39 45 42 2.4 44 50 48 42 47 50 50 46 51 44 50 48 50 60 53 65 70 60 71 80 65 69 70 63 75 80 69 71 80 66 2 1 48.3 46 78 ELECTRIC UNIT SIZE 50HJ NOMINAL VOLTAGE 024 208/240 VOLTAGE RANGE MIn Max LRA OFM ELECTRIC HEAT NO. 3 LRA LRA Qty (ea) ........ UNIT SIZE NOMINAL VOLTAGE 50HJ (3 Ph, 80 HZ) 024 208/230 MIn 187 Max 253 COMPRESSOR NO. 2 NO. 1 RLA LRA 22.4 RLA 184 22.4 LRA 184 NO. 3 RLA 22.4 LRA 184 Qty 4 Hp 0.25 FLA (ea) 1.5 LEGEND FLA HACR --- IFM LRA --- Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps MCA MOCP NEC OFM RLA Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps 2.4 1 2.4 1 2.4 2 1 2.4 77 83 80 90 71 93 2 1 2.4 89 100 99 86 100 97 92 100 102 89 100 99 95 100 104 2 1 2.4 2 1 2.4 HEATt POWER EXHAUST POWER SUPPLY DISCONNECT SIZE FLA Hp FLA (ea) MDA MOCP* FLA -- -- -- 156/180 175/200 179/207 kW 56/75 HEATt POWER EXHAUST IFM FLA Hp FLA 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 10 30.8/28 156/180 Maximum % Voltage maximum Qty 2 2 Hp 1 1 POWER SUPPLY FLA 5.9 5.9 DISCONNECT SIZE MCA MOCP* FLA 169/192 200/225 192/218 184/207 200/225 205/232 177/199 200/225 199/224 192/214 200/225 212/238 186/208 200/225 207/232 2 1 5.9 201/222 195/215 225/225 225/225 221/246 215/239 2 1 5.9 209/230 225/250 228/253 deviation from average voltage. deviation is 7 v. percent of voltage imbalance. 7 = 100 x Imbalance = 1.53% This amount 2%. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent o1 voltage imbalance. of phase imbalance is satisfactory as it is below the maximum local electric utility immediately. IMPORTANT: If thecompany supply voltage phase imbalance 3. The 75-kW 208/240-v rately in the field. Imbalance electric heat can be factory 5. The FLA load amps provided in the table for electric and 600 v. Example: Supply voltage is 460-3-60. A 8 c AB=452v alk)wable is more than 2%, contact installed but it must be wired 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, units, respectively. max voltage deviation from average voltage average voltage 460, heaters are based on 208/240, 1 your ] sepa575-v 480 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). AC = 455 v 452 + 464 + 455 Average BC = 464 Voltage v 1 (AB) 457 - 452 = 5 v (BC) 464 - 457 = 7 v (AC) 457 - 455 = 2 v *Fuse or HACR circuit breaker. 1-208/230 v 75=kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. = 100 x 2 156/180 Determine % Voltage 2.4 FLA 42 kW Determine ------ 1 MODP* 45 56/75 ELECTRIC HEAT OFM 2 2 IFM FEEDER CIRCUIT FOR 208/230 UNIT WITH 75-kW ELECTRIC VOLTAGE RANGE 2.4 1 2 HEAT BRANCH CIRCUIT 208/240 75-kW ELECTRIC COMPRESSOR NO. 2 NO. 1 75 2.4 1 2 0.7 DISCONNECT SIZE Qty 2 24.8 POWER SUPPLY = 3 1371 3 = 457 ]4 Table 4A -- Electrical Data -- Units Without Convenience Outlet (cont) UNIT SIZE 50HJ NOMINAL VOLTAGE (3Ph, 6OHz) VOLTAGE RANGE Mln Max COMPRESSOR No. 2 No. 1 RLA LRA RLA LRA RLA LRA ELECTRIC HEAT OFM No. 3 Gty Hp _!!FLA kW POWER EXHAUST IFM FLA Hp FLA 5 16.7/15.2 7.5 24.2/22 10 30.8/28 Oty Hp POWER SUPPLY FLA (ea) MCA MOCP* FLA 132/180 175/175 138/138 143/142 175/175 151/150 139/137 175/175 147/144 151/149 175/175 160/158 146/143 175/175 154/151 158/155 200/200 168/164 132/130 175/175 138/136 5.9 143/142 175/175 151/150 139/137 151/149 175/175 175/175 147/144 160/158 146/143 175/175 154/151 158/155 200/200 168/164 151/139 175/175 139/155 166/154 175/175 152/169 160/148 175/175 147/163 175/162 200/175 161/177 169/155 175/175 155/170 ] -- -- 2 2 2 19/25 208/230 187 253 47.1 245 47.1 245 6 0.25 52/60 5 16.7/15.2 7.5 24.2/22 10 30.8/28 5 16.7/15.2 7.5 24.2/22 10 30.8/28 5 16.7/15.2 7.5 24.2/22 10 30.8/28 1.5 38/50 56/75t 104/120 156/180 2 -- -- 25 460 414 506 19.6 125 19.6 125 6 0.25 30 5 7.6 7.5 11 10 14 5 7.6 7.5 11 10 14 5 7.6 7.5 11 10 14 0.7 50 60 75 LEGEND FLA RACR --- IFM LRA --- Full Load Amps Heating, AirCondgioningand Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps MCA MOCP NEC OFM RLA ------ Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps 90 14 Maximum deviation is 7 v. 5.9 5.9 2 1 5.9 2 2 1 1 5.9 5.9 2 1 5.9 183/170 132/130 200/200 175/175 169/184 138/136 2 1 5.9 143/142 175/175 151/150 139/137 175/175 147/144 151/149 175/175 160/158 146/143 175/175 154/151 158/155 200/200 168/164 2 2 1 1 1 5.9 5.9 56 60 59 3.1 62 80 66 59 66 60 80 63 70 62 80 66 69 80 73 56 60 59 62 80 66 59 60 63 66 80 70 62 80 66 2 1 3.1 2 1 3.1 2 2 1 1 3.1 3.1 2 1 3.1 69 70 80 80 73 78 2 1 3.1 77 80 85 74 80 82 82 90 89 78 90 85 85 90 92 100 110 112 3.1 107 125 119 104 112 125 125 116 123 108 125 120 115 125 127 2 2 1 1 1 3.1 3.1 2 1 3.1 2 1 3.1 from average w>ltage. percent of voltage imbalance. 7 100x = 1.53% of phase imbalance is satisfactory IMPORTANT: local electric utility If thecompany supply voltage immediately, phase as it is below the maximum imbalance allowable is more than 2%, contact your 3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field. 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively. 5. The FLA load amps provided in the table for electric heaters are based on 208/240,480 and 600 v. 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). max voltage deviatk)n from average voltage average vogage AC = 455 v Average Voltage BC = 464 v 10 maximum deviation - 452 = 5 v - 457 = 7 v - 455 = 2 v This amount 2%. Example: Supply voltage is 460-3-60. A B C AB = 452 v (_ 11 1 5.9 % Vogage Imbalance= NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x 7.5 Determine (AB) 457 (BC) 464 (AC) 457 Determine *Fuse or HACR circuit breaker. 1-208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. 7.6 1 5.9 1 2 5 1 [ 2 2 028 1 DISCONNECT SIZE = 452 + 464 + 455 3 1371 =---;= 457 15 Table 4A -- Electrical Data -- Units Without Convenience UNIT SIZE 5OHJ VOLTAGE RANGE NOMINAL VO LTAG E (3 Ph, 80 HZ) MIn COMPRESSOR NO. 2 NO. 1 Max RLA LRA RLA OFM ELECTRIC HEAT NO. 3 LRA RLA LRA Qty Hp FLA iea} kW Outlet (cont) IFM FLA POWER EXHAUST Hp FLA 5 6.1 7.5 9 10 11 Qty Hp _L4 2 1 2.4 2 1 2 24.8 028 575 518 633 15.8 100 15.8 100 6 0.25 24 46 78 UNIT SIZE 50HJ NOMINAL VOLTAGE 028 208/240 VOLTAGE RANGE MIn Max LRA 7.5 9 10 11 5 6.1 7.5 9 10 11 5 6.1 75 7.5 9 10 11 OFM ELECTRIC HEAT NO. 3 LRA LRA Qty (ea) ........ UNIT SIZE NOMINAL VOLTAGE 50HJ (3 Ph, 80 HZ) 028 208/230 MIn 187 COMPRESSOR NO. 2 NO. 1 Max RLA 253 47.1 LRA RLA 245 47.1 LRA 245 NO. 3 RLA LRA Qty 6 Hp 0.25 FLA (ea) 1.5 LEGEND FLA HACR --- IFM LRA --- Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Arnps MCA MOCP NEC OFM RLA ------ Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps *Fuse or HACR circuit breaker. 1-208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. A Supply voltage a C = 60 59 46 60 48 2.4 51 60 54 49 54 60 60 52 57 51 60 54 56 60 59 65 70 60 71 80 65 69 70 63 75 80 69 71 80 66 2.4 2 1 2.4 2.4 1 2.4 2 1 2.4 77 83 80 90 71 93 2 1 2.4 89 100 99 86 100 97 92 100 102 89 100 99 95 100 104 2 1 2.4 2 1 2.4 POWER EXHAUST POWER SUPPLY DISCONNECT SIZE FLA Hp FLA (ea) MDA MOCP* FLA -- -- -- 156/180 175/200 179/207 kW 56/75 HEATt POWER EXHAUST IFM FLA Hp 156/180 FLA 5 16.7/15.2 7.5 24.2/22 10 30.8/28 Qty 2 2 2 Hp 1 1 1 POWER SUPPLY FLA 5.9 5.9 5.9 DISCONNECT SIZE MCA MOCP* FLA 177/199 200/225 199/224 192/214 200/225 212/238 186/208 200/225 207/232 201/222 225/225 221/246 195/215 225/225 215/239 209/230 225/250 228/253 Determine (AB) 457 (BC) 464 (AC) 457 maximum deviation from average voltage. - 452 = 5 v - 457 = 7 v - 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 Imbalance = 100 x of phase imbalance is satisfactory as it is below the maximum allowable is more than 2%, contact 452 + 464 + 455 3 1371 3 = 457 16 ] your ] 3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field. 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively. 5. The FLA load amps provided in the table for electric heaters are based on 208/240, 480 and 600 v. 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). v Average BC = 464 Voltage v 54 56 local electric utility immediately. IMPORTANT: If thecompany supply voltage phase imbalance AC = 455 v (_ 60 = 1.53% is 460-3=60. AB =452 57 51 156/180 This amount 2%. max voltage deviation from average voltage average voltage Example: 60 kW % Voltage NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imhalar_ce in supply voltage is greater than 2%. Use the folk)wing formula to determine the percent o1 voltage imbalance. % Voltage Imbalance = 100 x 52 54 56/75 ELECTRIC HEAT OFM 54 60 HEAT't IFM FEEDER CIRCUIT FOR 208/230 UNIT WITH 75-kW ELECTRIC VOLTAGE RANGE 60 1 2 FLA 48 51 2 1 MODP* 60 DISCONNECT SIZE 49 2.4 1 2 MCA 46 2.4 1 2 HEAT BRANCH CIRCUIT 208/240 75-kW ELECTRIC COMPRESSOR NO. 2 NO. 1 6.1 0.7 48.3 ELECTRIC 5 POWER SUPPLY Table 4B -- Electrical Data -- Units With Optional Convenience Outlet UNIT SIZE 50HJ NOMINAL VOLTAGE (3Ph, SOHz) VOLTAGE RANGE MIn Max COMPRESSOR No. 2 No. 1 RLA LRA RLA LRA OFM ELECTRIC HEAT No. 3 RLA LRA Oty Hp _"t!FLA kW -- 187 253 16.7 130 16.7 130 22.4 184 4 0.25 FLA -- 19/25 208/230 IFM 52/60 POWER EXHAUST Hp FLA 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 1.5 38/50 56/75t 104/120 156/180 020 -- -- 25 46O 414 506 9 70 9 70 10.7 90 4 0.25 30 3.7 4.8 5 7.6 7.5 11 3.7 4.8 5 7.6 7.5 11 3.7 4.8 5 7.6 7.5 11 0.7 50 60 Oty Hp 2 1 75 LEGEND FLA RACR --- IFM LRA --- Full Load Amps Heating, AirConditioningand Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps MCA MOCP NEC OFM RLA ------ Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps 90 11 deviation is 7 v. _"t!FLA MCA 83/ 82 MOCP* 100/100 5.9 95/ 94 100/100 89/ 88 100/100 FLA 89/ 88 103/101 96/ 94 1 5.9 101/ 99 110/100 110/108 97/ 94 100/100 105/102 2 1 5.9 109/106 125/125 118/116 85/ 93 100/100 89/ 88 2 1 5.9 99/108 100/110 103/101 2 1 5.9 92/100 107/115 100/110 110/125 96/ 94 110/108 102/109 110/110 105/102 2 1 5.9 116/124 125/125 118/116 150/138 150/150 138/155 164/153 175/175 151/168 157/145 175/150 145/161 172/160 175/175 158/175 167/154 175/175 153/169 181/169 83/ 82 200/175 100/100 167/183 89/ 88 103/101 2 2 1 1 5.9 5.9 2 1 5.9 2 1 5.9 95/ 94 100/100 89/ 88 100/100 96/ 94 2 1 5.9 101/ 99 110/100 110/108 97/ 94 100/100 105/102 2 1 5.9 109/106 125/125 118/116 2 1 42 50 45 3.1 48 50 52 45 51 50 60 48 56 48 50 52 54 60 59 47 50 45 55 60 52 51 60 48 59 60 56 55 60 52 2 1 3.1 2 1 3.1 2 2 1 1 3.1 3.1 2 1 3.1 63 70 70 80 59 78 2 1 3.1 78 80 85 73 80 81 81 90 88 78 80 85 85 90 92 100 110 112 3.1 108 125 120 103 111 125 125 116 123 108 125 120 115 125 127 2 2 1 1 1 3.1 3.1 2 1 3.1 2 1 3.1 from average w>ltage. percent of voltage imbalance. 7 100x Imbalance= = 1.53% of phase imbalance is satisfactory electric utility immediately. I local IMPORTANT: If thecompany supply voltage phase as it is below the maximum imbalance is more than allowable 2%, contact your 3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field. 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively. 5. The FLA load amps provided in the table for electric heaters are based on 208/240,480 and 600 v. 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x {IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). max voltage deviatk)n from average voltage average voltage AC = 455 v Average Voltage BC = 464 v 7.5 Maximum This amount 2%. Example: Supply voltage is 460-3-60. A B C AB = 452 v (_ 7.6 maximum deviation - 452 = 5 v - 457 = 7 v - 455 = 2 v % Voltage NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x 5 Determine (AB) 457 (BC) 464 (AC) 457 Determine *Fuse or HACR circuit breaker. 1-208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. 4.8 DISCONNECT SIZE 2 2 3.7 POWER SUPPLY = 452 + 464 + 455 3 1371 =.--_= 457 17 Table 4B -- Electrical Data -- Units With Optional Convenience Outlet (cont) UNIT SIZE 5OHJ VOLTAGE RANGE NOMINAL VO LTAG E (3 Ph, 80 HZ) MIn COMPRESSOR NO. 2 NO. 1 Max RLA LRA RLA OFM ELECTRIC HEAT NO. 3 LRA RLA LRA Qty Hp FLA iea} kW IFM FLA POWER EXHAUST Hp FLA 3 3.9 5 6.1 7.5 9 24.8 020 575 518 633 7 55 7 55 9.3 73 4 0.25 NOMINAL VOLTAGE 020 208/240 VOLTAGE RANGE MIn Max LRA 7.5 9 3 3.9 _L4 MCA 35 2 1 2.4 40 45 43 38 45 4O 2 1 2.4 42 50 46 40 45 44 45 50 49 39 40 38 5 6.1 7.5 9 3 3.9 5 6.1 7.5 9 46 75 OFM NO. 3 LRA LRA ELECTRIC HEAT IH -- Qty (ea) ........ kW FLA Hp 156/180 -- UNIT SIZE NOMINAL VOLTAGE 50HJ (3 Ph, 80 HZ) 020 208/230 MIn 187 COMPRESSOR NO. 2 NO. 1 Max RLA 253 LRA 16.7 RLA 130 16.7 LRA 130 NO. 3 RLA 22.4 LRA 184 ELECTRIC HEAT OFM Qty 4 Hp 0.25 FLA (ea) 1.5 LEGEND FLA HACR --- IFM LRA --- Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps MCA MOCP NEC OFM RLA ------ Minimum Circuit Arnps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps *Fuse or HACR circuit breaker. 1-208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. A Supply voltage B C = 1 2.4 41 47 45 50 4O 46 45 50 44 2 1 2.4 51 60 49 66 70 61 72 80 66 69 70 63 75 80 69 73 80 67 156/180 1 2.4 1 2.4 2 1 2.4 79 84 80 90 72 94 2 1 2.4 90 100 100 86 100 97 92 100 102 90 100 100 96 100 106 2 1 2.4 2 1 2.4 POWER SUPPLY FLA (ea) MDA -- -- 156/180 FLA 10.6/9.6 5 16.7/15.2 7.5 24.2/22 MOCP* FLA 175/200 179/207 HEATt POWER EXHAUST 3.7 I DISCONNECT SIZE Qty 2 2 2 Hp 1 1 1 POWER SUPPLY FLA 5.9 5.9 5.9 DISCONNECT SIZE MCA MOCP* FLA 176/198 200/225 197/224 190/213 200/225 211/237 183/205 200/225 204/230 198/220 200/225 218/244 193/214 200/225 213/238 207/229 225/250 227/252 Determine (AB) 457 (BC) 464 (AC) 457 maximum deviation from average voltage. - 452 = 5 v - 457 = 7 v - 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 Imbalance = 100 x of phase imbalance is satisfactory as it is below the maximum allowable is more than 2%, contact 452 + 464 + 455 3 1371 3 = 457 18 1 your ] 3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field. 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively. 5. The FLA load amps provided in the table for electric heaters are based on 208/240, 480 and 600 v. 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). v Average BC = 464 Voltage v 2 local electric utility immediately. IMPORTANT: If thecompany supply voltage phase imbalance AC = 455 v (_ 43 = 1.53% is 460-3=60. AB =452 45 HEATt I Hp This amount 2%. max voltage deviation from average voltage average voltage Example: 56/75 45 IFM FLA % Voltage NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the folk)wing formula to determine the percent o1 voltage imbalance. % Voltage Imbalance = 100 x kW 2.4 POWER EXHAUST FEEDER CIRCUIT FOR 208/230 UNIT WITH 75-kW ELECTRIC VOLTAGE RANGE 1 2 IFM 56/75 2.4 38 2 2 HEAT BRANCH CIRCUIT 208/240 75-kW ELECTRIC COMPRESSOR NO. 2 NO. 1 6.1 0.7 78 UNIT SIZE 50HJ 5 24 48.3 ELECTRIC 3.9 FLA Hp 1 MODP* 4O DISCONNECT SIZE Qty 2 3 POWER SUPPLY Table 4B -- Electrical Data -- Units With Optional Convenience UNIT SIZE 50HJ NOMINAL VOLTAGE (3Ph, 6OHz) VOLTAGE RANGE Mln Max No. 1 RLA LRA COMPRESSOR No. 2 RLA LRA OFM ELECTRIC HEAT No. 3 RLA LRA Oty Hp _a!!FLA kW F LA IFM POWER EXHAUST Hp F LA 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 Qty Hp 2 1 2 2 19/25 208/230 187 253 22.4 184 22.4 184 22.4 184 4 0.25 10 30.8/28 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 10 30.8/28 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 10 30.8/28 52/60 1.5 38/50 104/120 2 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 10 30.8/28 3.7 4.8 5 7.6 7.5 11 10 14 3.7 4.8 414 506 10.7 90 10.7 90 10.7 90 4 0.25 5 7.6 7.5 11 10 14 3.7 4.8 5 7.6 7.5 11 10 14 3.7 4.8 5 7.6 30 0.7 50 75 1 F LA 102/101 106/105 125/125 116/115 101/ 110/100 109/107 112/111 125/125 123/121 108/106 125/125 118/115 120/118 125/125 131/129 117/113 125/125 125/122 5.9 129/125 150/150 139/136 94/ 93 106/108 100/100 125/125 102/101 116/115 101/100 110/110 109/107 112/115 125/125 123/121 108/109 125/125 118/115 120/124 125/125 131/129 117/116 125/125 125/122 129/131 150/150 139/136 150/138 150/150 138/155 5.9 5.9 5.9 5.9 2 1 5.9 2 2 1 1 5.9 5.9 60 7.5 11 99 2 1 5.9 164/153 157/145 175/175 175/150 151/168 145/161 2 1 5.9 172/160 175/175 158/175 167/154 175/175 153/169 181/169 200/175 167/183 175/161 175/175 161/176 190/176 200/200 174/190 100/100 102/101 2 1 1 5.9 5.9 94/ 2 1 106/105 125/125 116/115 101/ 99 112/111 110/100 125/125 109/107 123/121 108/106 125/125 118/115 120/118 125/125 131/129 117/113 125/125 125/122 129/125 150/150 139/136 1 5.9 2 1 5.9 2 2 1 1 93 5.9 2 5.9 3.1 45 50 49 52 60 56 48 50 52 2 1 3.1 54 52 60 60 59 56 2 1 3.1 58 60 63 55 60 60 62 70 67 47 50 49 55 60 56 51 60 52 3.1 59 60 59 55 63 60 70 56 63 59 60 60 67 70 67 70 80 78 78 80 85 73 80 81 81 90 88 78 80 85 85 81 90 90 92 89 2 2 1 1 1 3.1 3.1 2 1 3.1 2 1 3.1 2 2 1 1 3.1 3.1 2 1 3.1 2 1 3.1 2 2 90 MCA 94 /93 DISCONNECT SIZE MOCP* 100/100 1 2 460 1 _a!FLA 156/180 024 25 1 POWER SUPPLY 2 2 56/75t Outlet (cont) 2 1 1 1 3.1 3.1 3.1 89 100 96 100 110 112 108 125 120 103 125 116 111 125 123 108 125 120 115 125 127 123 13O See legend and notes on next page. 19 Table 4B -- Electrical Data -- Units With Optional Convenience Outlet (cont) UNIT SIZE 5OHJ NOMINAL VO LTAG E (3 Ph, 80 HZ) VOLTAGE RANGE MIn COMPRESSOR NO. 2 NO. 1 Max RLA LRA RLA OFM ELECTRIC HEAT NO. 3 LRA RLA LRA Qty Hp FLA iea} kW IFM FLA POWER EXHAUST Hp FLA 5 6.1 7.5 9 10 11 24.8 024 575 518 633 9.3 73 9.3 73 9.3 73 4 0.25 24 6.1 7.5 9 10 11 Hp _L4 MCA 42 2 1 2.4 47 50 51 45 50 49 2 1 5 6.1 48.3 46 7.5 9 10 11 5 6.1 78 75 7.5 9 10 11 UNIT SIZE 50HJ NOMINAL VOLTAGE 024 208/240 VOLTAGE RANGE MIn COMPRESSOR NO. 2 NO. 1 Max LRA OFM ELECTRIC HEAT NO. 3 LRA LRA Qty (ea) ........ UNIT SIZE NOMINAL VOLTAGE 50HJ (3 Ph, 80 HZ) 024 208/230 MIn 187 Max 253 COMPRESSOR NO. 2 NO. 1 RLA LRA 22.4 RLA 184 22.4 LRA 184 NO. 3 RLA 22.4 LRA 184 Qty 4 Hp 0.25 FLA (ea) 1.5 LEGEND FLA HACR --- IFM LRA --- Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps MCA MOCP NEC OFM RLA Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps 2.4 47 50 51 45 51 50 60 49 55 48 50 51 54 60 57 69 70 63 75 80 69 73 80 67 79 80 72 75 80 69 1 2.4 2.4 1 2.4 2 1 2.4 81 86 90 100 75 97 2 1 2.4 92 100 102 90 100 100 96 100 106 93 100 102 99 100 108 1 2.4 1 2.4 HEATt POWER EXHAUST POWER SUPPLY DISCONNECT SIZE FLA Hp FLA (ea) MDA MOCP* FLA -- -- -- 156/180 175/200 179/207 kW 56/75 HEATt POWER EXHAUST IFM FLA Hp FLA 3.7 10.6/9.6 5 16.7/15.2 7.5 24.2/22 10 30.8/28 156/180 Maximum % Voltage maximum Qty 2 2 Hp 1 1 POWER SUPPLY FLA 5.9 5.9 DISCONNECT SIZE MCA MOCP* FLA 176/198 200/225 197/224 190/213 200/225 211/237 183/205 200/225 204/230 198/220 200/225 218/244 193/214 200/225 213/238 2 1 5.9 207/229 201/221 225/250 225/225 227/252 221/245 2 1 5.9 216/236 225/250 234/259 deviation from average voltage. deviation is 7 v. percent of voltage imbalance. 7 = 100 x Imbalance = 1.53% This amount 2%. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent o1 voltage imbalance. of phase imbalance is satisfactory as it is below the maximum local electric utility immediately. IMPORTANT: If thecompany supply vol '_ge phase imbalance 3. The 75-kW 208/240-v rately in the field. Imbalance electric heat can be factory 5. The FLA load amps provided in the table for electric and 600 v. Example: Supply voltage is 460-3-60. A 8 c AB=452v alk)wable is more than 2%, contact your installed but it must be wired 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, units, respectively. max voltage deviation from average voltage average voltage 460, heaters are based on 208/240, sepa575-v 480 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). AC = 455 v 452 + 464 + 455 Average BC = 464 Voltage v 46 (AB) 457 - 452 = 5 v (BC) 464 - 457 = 7 v (AC) 457 - 455 = 2 v *Fuse or HACR circuit breaker. 1-208/230 v 75=kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. = 100 x 50 156/180 Determine % Voltage 57 42 kW Determine ------ 60 56/75 ELECTRIC HEAT OFM 51 52 2 2 IFM FEEDER CIRCUIT FOR 208/230 UNIT WITH 75-kW ELECTRIC VOLTAGE RANGE 55 50 2.4 2 HEAT BRANCH CIRCUIT 208/240 75-kW ELECTRIC 50 1 1 FLA 46 50 2 2 MODP* 50 47 2.4 1 2 ELECTRIC 2.4 1 2 0.7 DISCONNECT SIZE Qty 2 5 POWER SUPPLY = 3 1371 3 = 457 20 I I Table 4B -- Electrical Data -- Units With Optional Convenience UNIT SIZE 50HJ NOMINAL VOLTAGE (3Ph, 6OHz) VOLTAGE RANGE Mln Max COMPRESSOR No. 2 No. 1 RLA LRA RLA LRA OFM No. 3 RLA LRA ELECTRIC HEAT Gty Hp _!!FLA kW POWER EXHAUST IFM FLA Outlet (cont) Hp FLA 5 16.7/15.2 7.5 24.2/22 10 30.8/28 Oty Hp POWER SUPPLY FLA (ea) MCA MOCP* FLA 137/135 175/175 144/142 148/147 175/175 157/155 144/142 175/175 152/150 156/154 200/200 166/163 151/148 175/175 160/157 163/160 200/200 173/170 137/135 175/175 144/142 5.9 148/147 175/175 157/155 144/142 156/154 175/175 200/200 152/150 166/163 151/148 175/175 160/157 163/160 200/200 173/170 157/145 175/175 145/161 172/160 175/175 158/175 167/154 175/175 153/169 181/169 200/200 167/183 175/161 175/175 161/176 ] -- -- 2 2 2 19/25 208/230 187 253 47.1 245 47.1 245 6 0.25 52/60 5 16.7/15.2 7.5 24.2/22 10 30.8/28 5 16.7/15.2 7.5 24.2/22 10 30.8/28 5 16.7/15.2 7.5 24.2/22 10 30.8/28 1.5 38/50 56/75t 104/120 156/180 2 -- -- 25 460 414 506 19.6 125 19.6 125 6 0.25 30 5 7.6 7.5 11 10 14 5 7.6 7.5 11 10 14 5 7.6 7.5 11 10 14 0.7 50 60 75 LEGEND FLA RACR --- IFM LRA --- Full Load Amps Heating, AirCondgioningand Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps MCA MOCP NEC OFM RLA ------ Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps 90 14 Maximum deviation is 7 v. 5.9 5.9 2 1 5.9 2 2 1 1 5.9 5.9 2 1 5.9 190/176 137/135 200/200 175/175 174/190 144/142 2 1 5.9 148/147 175/175 157/155 144/142 175/175 152/150 156/154 200/200 166/163 151/148 175/175 160/157 163/160 200/200 173/170 2 2 1 1 1 5.9 5.9 59 60 62 3.1 65 80 69 62 69 80 80 66 73 65 80 69 72 90 77 59 60 62 65 80 69 62 80 66 69 80 73 65 80 69 2 1 3.1 2 1 3.1 2 2 1 1 3.1 3.1 2 1 3.1 72 73 90 80 77 81 2 1 3.1 81 90 88 78 80 85 85 90 92 81 90 89 89 100 96 103 125 116 3.1 111 125 123 108 115 125 125 120 127 111 125 123 119 125 130 2 2 1 1 1 3.1 3.1 2 1 3.1 2 1 3.1 from average w>ltage. percent of voltage imbalance. 7 100x = 1.53% of phase imbalance is satisfactory IMPORTANT: local electric utility If thecompany supply voltage immediately, phase as it is below the maximum imbalance allowable is more than 2%, contact your 3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field. 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively. 5. The FLA load amps provided in the table for electric heaters are based on 208/240,480 and 600 v. 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). max voltage deviatk)n from average voltage average vogage AC = 455 v Average Voltage BC = 464 v 10 maximum deviation - 452 = 5 v - 457 = 7 v - 455 = 2 v This amount 2%. Example: Supply voltage is 460-3-60. A B C AB = 452 v (_ 11 1 5.9 % Vogage Imbalance= NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x 7.5 Determine (AB) 457 (BC) 464 (AC) 457 Determine *Fuse or HACR circuit breaker. 1-208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. 7.6 1 5.9 1 2 5 1 [ 2 2 028 1 DISCONNECT SIZE = 452 + 464 + 455 3 1371 =---;= 457 21 Table 4B -- Electrical Data -- Units With Optional Convenience Outlet (cont) UNIT SIZE 5OHJ VOLTAGE RANGE NOMINAL VO LTAG E (3 Ph, 80 HZ) MIn COMPRESSOR NO. 2 NO. 1 Max RLA LRA RLA OFM ELECTRIC HEAT NO. 3 LRA RLA LRA Qty Hp FLA iea} kW IFM FLA POWER EXHAUST Hp FLA 5 6.1 7.5 9 10 11 24.8 028 575 518 633 15.8 100 15.8 100 6 0.25 24 6.1 7.5 9 _L4 MCA 49 2 1 2.4 54 60 57 52 60 55 57 60 6O 54 60 57 59 60 63 49 60 52 2.4 54 60 57 52 57 60 60 55 6O 54 60 57 59 60 63 69 70 63 75 80 69 73 80 67 79 80 72 75 80 69 1 10 11 5 6.1 48.3 46 7.5 9 10 11 5 6.1 78 75 7.5 9 10 11 2 1 2.4 2 1 2.4 2 1 2 UNIT SIZE 50HJ NOMINAL VOLTAGE 028 208/240 VOLTAGE RANGE MIn COMPRESSOR NO. 2 NO. 1 Max LRA OFM ELECTRIC HEAT NO. 3 LRA LRA Qty (ea) ........ UNIT SIZE NOMINAL VOLTAGE 50HJ (3 Ph, 80 HZ) 028 208/230 MIn 187 COMPRESSOR NO. 2 NO. 1 Max RLA 253 47.1 LRA RLA 245 47.1 LRA 245 NO. 3 2 1 2.4 81 86 90 100 75 97 2 1 2.4 92 100 102 90 100 100 96 100 106 93 100 102 99 100 108 1 RLA LRA Qty 6 Hp 0.25 FLA (ea) 1.5 LEGEND FLA HACR --- IFM LRA --- Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Arnps MCA MOCP NEC OFM RLA ------ Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps *Fuse or HACR circuit breaker. 1-208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits. A Supply voltage a C POWER EXHAUST Hp FLA (ea) MDA MOCP* FLA -- -- -- 156/180 175/200 179/207 = kW 56/75 HEATt POWER EXHAUST IFM FLA Hp 156/180 FLA 5 16.7/15.2 7.5 24.2/22 10 30.8/28 Qty 2 2 2 Hp 1 1 1 POWER SUPPLY FLA 5.9 5.9 5.9 DISCONNECT SIZE MCA MOCP* FLA 183/205 200/225 204/230 198/220 200/225 218/244 193/214 200/225 213/238 207/229 225/250 227/252 201/221 225/225 221/245 216/236 225/250 234/259 Determine (AB) 457 (BC) 464 (AC) 457 maximum deviation from average voltage. - 452 = 5 v - 457 = 7 v - 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 Imbalance = 100 x of phase imbalance is satisfactory as it is below the maximum allowable is more than 2%, contact 452 + 464 + 455 3 1371 3 = 457 22 ] your ] 3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired separately in the field. 4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively. 5. The FLA load amps provided in the table for electric heaters are based on 208/240, 480 and 600 v. 6. MCA calculation for 50HJ units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA). v Average BC = 464 Voltage v DISCONNECT SIZE FLA local electric utility immediately. IMPORTANT: If thecompany supply voltage phase imbalance AC = 455 v (_ POWER SUPPLY = 1.53% is 460-3=60. AB =452 2.4 156/180 This amount 2%. max voltage deviation from average voltage average voltage Example: 1 kW % Voltage NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imhalar_ce in supply voltage is greater than 2%. Use the folk)wing formula to determine the percent o1 voltage imbalance. % Voltage Imbalance = 100 x 2.4 56/75 ELECTRIC HEAT OFM 2.4 52 HEAT't IFM FEEDER CIRCUIT FOR 208/230 UNIT WITH 75-kW ELECTRIC VOLTAGE RANGE 2.4 1 2 HEAT BRANCH CIRCUIT 208/240 75-kW ELECTRIC 2.4 1 2 ELECTRIC 2.4 1 2 0.7 FLA Hp 2 MODP* 60 DISCONNECT SIZE Qty 2 5 POWER SUPPLY nents, remove section. TBI I FIELD P I POWER the outdoor air intake 4. Remove inner tilter track from shipping position in outdoor section. Position inner filter track so the track is facing outward from the unit. Install the filter track with 4 screws provided. 5. Apply seal strip (provided) to back flange of both hood sides where hood side connects to the unit back panel. See Fig. 15. Apply seal strip (provided) to top flange of both hood sides where hood sides connect to the hood top panels. See Fig. 15. [nst;dl hood sides to the back panels using the screws from Step 2. The sloped flanges point outward. The diip edges of file side panels should face outwm'd as well. The filter guides should face inward to hold the tilters in place. See Fig. 15. SUPPLY z_ the panel below €.)W me_t .=. i I ! I I L ........... EQUIP 6. GND J LEGEND EQUIP GND NEC TB ---I 7. Equipment Ground National Electrical Code Terminal Board NOTE: The maximum Fig. 12- wire size for TB1 is 2/0. Field Power Wiring Connections 8. 9. THERMOSTAT ASSEMBLY 10. I E+ ER[ Jll 1 2 Fig. 13- NOTE: For units with manual &lmpers, replace the end tilters with the manual dalnpers. Install the filter in the center between the manual &lmpers. 3 4 5 6 7 8 11. Inst_fll the filter retainer Uack along the bottom edge of the outdoor air hood using 4 screws provided. See Fig. 15. 12. Inst_dl top section of the outdoor-tfir hood using 9 screws provided. See Fig. 15. See Fig. 16 for a picture of the assembled outdoor-air hood. Field Control Thermostat Wiring Set heat anticipator NOTE: For tilter removal, remove the four screws holding the tilter retainec The filters can then be removed, cleaned, or replaced, install file filters by reversing the procedure. settings as shown in Table 5. Table 5 -- Heat Anticipator Settings UNIT SIZE 50HJ ELECTRIC HEAT (kW) 25 020-028 5O 75 STAGE 1 (Wl) ON Voltage 208/240 480 0.2 0.2 0.4 0.4 0.2 0.2 600 0.2 0.2 0.2 MANUAL DAMPER ASSEMBLY-For units equipped with manual dampers, the assembly process is similar to the outdoor-air hood for units with economizers. There are two slide &tmpers shipped with the unit to allow for manual setting of the outside tfir volume. When assembling the hood, place one of the manual slide dampers in each of the end positions and the remaining filter in the center position. The manual &Lmpers can then be moved to the appropriate position and then locked into place using the screws mounted in the adjustment slots. See Fig. 17. STAGES 1 AND 2 (Wl and W2) ON Voltage 208/240 480 600 0.4 0.4 0.4 0.8 0.8 0.4 0.4 0.4 0.4 Settings may be changed slightly to provide a greater degree of comfort for a pallicular instalhnion. Step 8 -- Install Apply seal strip along the entire length of the bottom flange of the hood top. See Fig. 15. Inst;fll the bottom part of the hood top using 4 sclews provided. See Fig. 15. Remove the packaging from filtel.s (3) and install into the tilter tracks. Slide the filters to the sides then place the last tilter into the center of the filter track. Outdoor-Air Hood -- Perform the following procedure to inst_dl file outdoor-air equipped with an economize1: two-position outdoor-air dmnper: hood on units dalnper, oi" HOODTOP 1. Remove blank panel from return end of unit (hood section). Save the screws. See Fig. 14 for shipping location of components. 2. Hood sides are fastened to sides of outdoor air opening. Remove the hood sides and save the screws (3 each side). 3. Remove the bracket holding the bottom half of the hood in the shipping position. Remove the hood bottom half and filtels (or manual &tmpers on units so equipped) from outdoor section. HOOD SIDE HOOD TOP BOTTOM HALF) HOOD SIDE SECTION NOTE: On units without economizers, the components are attached to the unit basepan. To access the compo- Fig. 14 -- Outdoor-Air Hood Compartment Shipping Location 23 TOP HOOD SECTION SEAL STRIP HOOD SIDE ADD SEAL STRIP ADD STRIP INNER FILTER ADD SEAL STRIP HOOD SECTION ADD SEAL GUIDE FILTER FINER HOOD SIDE DAMPER (IF EQUIPPED) NOTE: Units with manual damper only UNIT BACK PANEL use one filter. Fig. 15 -- Outdoor-Air Hood Details MOVEABLE DAMPER AIR FILTER POSITION Fig. 16 -- Outdoor-Air Hood Assembled j MOVEABLE Fig. 17 -- Manual Damper Details 24 DAMPER Step 9 -- Position Optional Power Exhaust or Barometric Relief Damper Hood -- The optional power exhaust or barometric relief dampers are shipped assembled and tilted back into the unit for shipping. Brackets and extra screws are shipped in shrink wrap around the dampers. 1. Remove 9 screws holding each dmnper assembly in place. See Fig. 18. Each damper assembly is secured with 3 screws on each side and 3 screws along the bottom. Save screws. From the inside of the corner post, attach the handle mounting screws to file handle. Slide the shaft fully into file handle and tighten the set screws(s) on the disconnect to lock file shall. Tighten file screws that attach the handle to the corner post. 8. Rotate the handle back to the "OFF" position. 9. Replace _fll panels and doors. 10. Restore power to unit. Step 11 -- Install All Accessories --After all of the factory-installed options have been adjusted, install all field-inst_dled accessories. Refer to the accessory installation instructions included with each accessory. Consult the C_urier Price Pages for accessory package numbeLs for particular applications. Use cme when tilting blower assembly. Hoods and blowers me heavy and can cause injury if diopped. 2. 7. Pivot the damper assembly outwaM until top edge of damper assembly rests against inside wall of unit. 3. Secure each damper assembly to unit with 6 screws across top (3 screws provided) and bottom (3 screws from Step 1) of dampo: 4. With screws saved from Step 1, install brackets on each side of &tmper assembly. See Fig. 19. 5. Remove tape from damper blades. Step 10 -- Non-Fused Disconnect -- The handle for the factory-installed non-fused disconnect is shipped inside the unit to prevent the handle from &tmage during shipping. Follow these steps to complete inst_fllation of the handle. @ © Be sure power is shut off to file unit fiom tile building power supply. Electrical shock could cause personal injury. 1. Open the control box access dool: 2. Remove the small cover plate located on the unit corner post near the control section. 3. Remove the inner control box covel: The handle and shaft are located in a plastic bag at the bottom of the control box. 4. Insert the square shaft into the disconnect with the pins vertical. On the 100 amp disconnect the shaft is keyed into the disconnect and can only be installed one way with the pins vertical. 5. Insert the handle through the corner post and onto the shaft with the handle positioned so that "OFF' is on top. 6. Rotate the handle to the "ON" position to lock the pins into the handle. Fig. 19- Bracket and Hood Positioning __ REMOVE _ SCREWS REMOVE SCREWS\ REMOVE SCREWS Fig. 18 -- Power Exhaust or Barometric Relief Damper Mounting Details 25 PRE-START-UP Unit Preparation accordance ble codes. -- Check that unit has been installed in with these installation instructions and all applica- Compressor MountingFailure to observe the following warnings could result in serious personal injuu: 1. Follow recognized safety practices and wear protective goggles when checking or servicing refiigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured. spring mounted. down bolts. Crankcase heaters are energized as long as there is power to the unit and the compressor is not operating. I IMPORTANT: Unit power must be on for 24 hours prior to start-up. Otherwise, damage to compressor may result. Compressor I Phasing hnproper wiring will cause compressor stoppage and possible unit &image. Correct wiring by switching leads as indicated below. On 3-phase units, it is important to be certain the compressors are rotating in the proper direction. To determine whether or not compressors are rotating in the proper direction, use a phase-rotation meter on the unit input power to check for L I -L2-L3 or clockwise rotation. If the compressor is rotating in the wrong direction, the suction pressure will not diop and the discharge pressure will not rise. NOTE: Indoor or outdoor fan rotation direction may not indicate proper input power phase sequence, as some 3-phase units use single-phase fan motors. Check fan rotation where applicable. 1. Remove all access panels. 2. Read and follow instructions on all WARNING. CAUTION, and INFORMATION labels attached to or shipped with unit. 3. Make the following inspections: a. Inspect for shipping and handling &_mages such as broken lines, loose parts, or disconnected wires. b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. c. Inspect all field-wiring and factoq-wiring connections. Be sure that connections are completed and tight. d. Inspect coil fins. If damaged during shipping and handling, ctu'elhlly straighten fins with a fin comb. 4. Verify the following: a. Make sure that condenser-fan blades are correctly positioned in fan orifice. Refer to Condenser-Fan Adjustment section on page 45 for more details. b. Make sure that air filters are in place. c. Make sure that condensate drain trap is filled with water to ensure proper di'ainage. d. Make sure that all tools and miscellaneous loose parts have been removed. To correct the wrong compressor the following procedure: rotation direction, perform 1. Turn off power to the unit and lock out the power. 2. Switch any two of the incoming unit power leads. 3. Turn on power to the unit. 4. Verify corrected where applicable. compressor rotation Internal Wiring- Check all electric_d unit control boxes; tighten as required. and fan rotation connections in Evaporator FanFan belt and vmiable pulleys are factory-inst;dledi See Tables 6-12 for fan performance data. Be sure that fans rotate in the proper direction. See Table 13 for air quantity limits. See Table 14 for evaporator fan motor specifications. See Table 15 for fan rpm at v;uious motor pulley settings. See Table 16 for electric resistance heater &_ta. See Tables 17 and 18 for accessory/FIOP static pressure.To alter fan performance, see Evaporator Fan Performance Adjustment section on page 44. Condenser Fans and Motors -- Condenser fans and motors _u'e factory set. Refer to Condenser-Fan Adjustment section (page 45) as required. Return-Air FiltersCheck that correct filters are installed in filter tracks (see Table 1). Do not operate unit without return-air filters. has been pertubing. NOTE: For units with 4-in. filter option, units ;ue shipped with standard 2-in. filteLs. To install 4-in. filters, the filter spacers must be removed. START-UP Use the following inforlnation and St_ut-Up Checklist page CL-I to check out unit PRIOR to start-up. hold- Crankcase Heater(s)- Proceed as follows to inspect and prepare the unit for initkd st¢ut-up: NOTE: Ensure wiring does not contact any refiigemnt compressor Each independent refi'igerant system has a total of 3 Schmder-type service gage ports per circuit. One port is located on the suction line, one on the complessor disch;uge line, and one on the liquid line. Be sure that caps on the ports are tight. a. Shut off electrical power to unit and inst_dl lockout tag. b. Relieve all pressme from system using both high-and low-pressme ports. Use accepted methods to recover refrigerant. c. Cut component connection tubing with tubing cutter and lemove component from unit. d. Carefully unsweat remaining tubing stubs when necesstu'y. Oil can ignite when exposed to torch flmne. Make sure that the st_ut-up checklist formed and filled out. Compressors are internally or remove Refrigerant Service Ports-- 3. Do not remove compressor terminal cover until all electrical sources are disconnected and properly tagged. 4. Relieve all pressure fiom system before touching or disturbing anything inside terminal box if refrigerant leak is suspected _u_ound compressor terminals. Use accepted methods to recover refrigerant. 5. Never attempt to repair soldered connection while refrigerant system is under pressure. 6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wetu _ protective goggles and proceed as follows: e. Do not loosen on Outdoor-Air Inlet Screens --Outdoor-air must be in place before operating unit. 26 inlet screens Table 6 -- Fan Performance -- 50HJ020 Vertical AIRFLOW (Cfm) 35O0 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 EXTERNAL STATIC 0.6 PRESSURE (in. wg) 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 423 454 487 522 559 598 637 677 718 759 801 522 675 859 1077 1330 1621 1953 2327 2745 3209 3722 0.60 0.78 0.99 1.24 1.53 1.86 2.25 2.68 3.16 3.69 4.28 521 545 572 601 632 664 698 734 770 808 846 715 884 1082 1311 1573 1873 2212 2593 3018 3489 4007 0.82 1.02 1.24 1.51 1.81 2.15 2.54 2.98 3.47 4.01 4.61 605 625 648 673 700 729 759 791 824 858 893 906 1093 1307 1550 1826 2137 2486 2876 3309 3787 4311 1.04 1.26 1.50 1.78 2.10 2.46 2.86 3.31 3.81 4.36 4.96 679 697 717 739 763 789 817 846 876 907 940 1093 1299 1529 1789 2080 2405 2766 3167 3609 4095 4628 1.26 1.49 1.76 2.06 2.39 2.77 3.18 3.64 4.15 4.71 5.32 747 762 780 800 822 846 871 898 926 956 986 1278 1502 1750 2026 2332 2671 3046 3459 3913 4410 4952 1.47 1.73 2.01 2.33 2,68 3,07 3,50 3,98 4.50 5,07 5.69 Bhp 2.30 2.64 3.01 3.40 3.83 4.29 4.78 5.32 5.90 6.53 7.21 Rpm 1024 1034 1045 1058 1073 1090 1108 1128 1150 1173 1197 Watts 2176 2490 2826 3185 3570 3986 4434 4917 5436 5995 6596 AIRFLOW (Of m) 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 AVAILABLE 0.4 0.2 Discharge Units* AVAILABLE EXTERNAL 1.4 1.2 Rpm 810 823 839 857 877 899 923 948 975 1002 1031 Watts 1461 1703 1969 2261 2583 2937 3327 3753 4219 4727 5280 Bhp 1.68 1.96 2.26 2.60 2.97 3.38 3.83 4.32 4.85 5.44 6.07 Rpm 868 880 894 911 930 950 972 996 1021 1047 1075 Watts 1642 1902 2185 2494 2832 3202 3606 4045 4525 5045 5609 Bhp 1.89 2.19 2.51 2.87 3.26 3.68 4.15 4.65 5.20 5.80 6.45 Rpm 923 934 947 962 979 999 1020 1042 1066 1091 1117 LEGEND STATIC PRESSURE (in. wg) 1.6 1.8 Watts 1821 2100 2400 2726 3080 3465 3883 4337 4829 5362 5938 Bhp 2.09 2.42 2.76 3.14 3.54 3.98 4.47 4.99 5.55 6.17 6.83 Rpm 975 985 997 1011 1027 1045 1065 1086 1109 1133 1158 Watts 1999 2296 2613 2956 3326 3726 4159 4627 5134 5680 6268 2.0 Bhp 2.50 2.86 3.25 3.66 4.11 4.58 5.10 5.65 6.25 6.90 7.59 NOTES: 1. Maximum continuous bhp is: Low Range: Not Used Mid-Low Range: 4.25 (208/230 and 460-v), 3.45 (575-v) Mid-High Range: 5.75 High Range: 8.63 2. See below for general fan performance notes. Bhp -- Brake Horsepower Input to Fan Watts -- Input Watts to Motor *Motor drive ranges: Low Range: Not Used Mid-Low Range: 647-886 (208/230 and 460-v), 810-1072 (575-v) Mid-High Range: 897-1139 (208/230 and 460-v). 873-1108 (575-v) High Range: 1078-1274 All other rpms require field-supplied drive. GENERAL FAN PERFORMANCE NOTES: 1. Values include losses for filters, unit casing, and wet coils. See Tables 17 and 18 for accessory/factory-installed option static pressure information. 2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the wattage ratings shown will not NOTES result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Performance in Table 14 on page 33 for additional information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details. 4. Interpolation is permissible. Do not extrapolate. 27 Table 7 -- Fan Performance -- 50HJ024 Vertical Discharge Units* AIRFLOW (Cfm) 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 533 571 610 650 691 732 775 817 860 903 947 AIRFLOW (Cfm) 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 AVAILABLE EXTERNAL 0.4 0.2 Watts 1106 1366 1666 2007 2391 2820 3297 3823 4400 5031 5715 Bhp 1.27 1.57 1.92 2.31 2.75 3.24 3.79 4.40 5.06 5.79 6.57 Rpm 611 643 676 712 748 786 824 863 904 944 985 Watts 2294 2625 2990 3391 3830 4311 4835 5405 6022 6691 7412 Bhp 1.54 1.86 2.21 2.61 3.06 3.57 4.12 4.74 5.41 6.14 6.93 Rpm 682 711 740 772 805 839 874 911 948 986 1025 Bhp 2.64 3.02 3.44 3.90 4.40 4.96 5.56 6.22 6.93 7.70 8.52 Rpm 918 938 960 984 1008 1035 1062 1091 1121 1152 1184 Watts 2527 2875 3254 3670 4123 4617 5153 5735 6364 7042 7773 Bhp 2.91 3.31 3.74 4.22 4.74 5.31 5.93 6.60 7.32 8.10 8.94 Rpm 969 988 1008 1030 1054 1079 1105 1133 1161 1191 1222 LEGEND Bhp Watts Watts 1582 1867 2188 2548 2949 3395 3887 4428 5019 5663 6360 Bhp 1.82 2.15 2.52 2.93 3.39 3.91 4.47 5.09 5.77 6.51 7.32 Rpm 748 773 800 829 859 891 924 958 993 1028 1065 (in. wg) 0.8 Watts 1822 2121 2456 2829 3242 3698 4200 4749 5347 5998 6703 1.0 Bhp 2.10 2.44 2.82 3.25 3.73 4.25 4.83 5.46 6.15 6.90 7.71 Rpm 808 832 857 883 911 941 972 1003 1036 1070 1105 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 1.2 Rpm 865 886 910 935 961 989 1018 1048 1079 1112 1145 Watts 1342 1613 1922 2271 2663 3100 3585 4118 4702 5339 6030 STATIC PRESSURE 0.6 Watts 2760 3123 3518 3948 4415 4922 5472 6065 6706 7395 8135 Bhp 3.17 3.59 4.05 4.54 5.08 5.66 6.29 6.98 7.71 8.51 9.36 Rpm 1018 1035 1054 1075 1098 1122 1147 1173 1201 1229 1259 Watts 2990 3369 3779 4224 4706 5227 5790 6396 7048 7749 8500 Wa_s 2059 2374 2724 3110 3536 4004 4516 5075 5683 6343 7055 2.0 Bhp 3.44 3.87 4.35 4.86 5.41 6.01 6.66 7.36 8.11 8.91 9.78 Rpm 1065 1081 1099 1118 1140 1163 1187 1212 1239 1266 1295 Watts 3219 3614 4040 4499 4996 5530 6106 6725 7390 8102 8864 NOTES: 1. Maximum continuous bhp is: Low Range: 4.25 (208/230 and 460-v), 5.75 (575-v) Mid-Low Range: 5.75 Mid-High Range: 8.63 High Range: 11.50 2. See page 27 for general fan performance notes. --Brake Horsepower Input to Fan -- Input Watts to Motor *Motor drive ranges: Low Range: 685-939 (208/230 and 460-v), 751-954 (575-v) Mid-Low Range: 949-1206 Mid-High Range: 941-1176 High Range: 1014-1297 All other rpms require field-supplied drive. 28 Bhp 2.37 2.73 3.13 3.58 4.07 4.61 5.19 5.84 6.54 7.29 8.11 Bhp 3.70 4.16 4.65 5.18 5.75 6.36 7.02 7.73 8.50 9.32 10.20 Table 8 -- Fan Performance -- 50HJ028 Vertical Discharge Units* AIRFLOW (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 EXTERNAL STATIC 0.6 PRESSURE (in. wg) 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 734 728 746 786 827 870 913 957 1002 1047 1092 1137 1182 2384 2506 2738 3148 3611 4125 4691 5312 5988 6719 7507 8356 9264 2.74 2.88 3.15 3.62 4.15 4.74 5.40 6.11 6.89 7.73 8.63 9.61 10.65 752 792 831 869 905 940 975 1010 1047 1086 1126 1168 1210 2482 2911 3375 3868 4384 4921 5480 6073 6715 7416 8180 9009 9903 2.85 3.35 3.88 4.45 5.04 5.66 6.30 6.98 7.72 8.53 9.41 10.36 11.39 803 844 884 925 964 1003 1042 1079 1115 1150 1185 1220 1256 2,752 3,220 3,734 4,292 4,891 5,529 6,202 6,906 7,635 8,388 9,163 9,975 10,835 3.16 3.70 4.29 4.94 5.63 6.36 7.13 7.94 8.78 9.65 10.54 11.47 12.46 848 887 927 968 1008 1049 1089 1128 1167 1205 1242 1278 1314 2,998 3,484 4,023 4,612 5,251 5,939 6,674 7,453 8,275 9,133 10,025 10,945 11,891 3.45 4.01 4.63 5.30 6.04 6.83 7.68 8.57 9.52 10.50 11.53 12.59 13.68 891 928 966 1006 1046 1086 1127 1167 1207 1247 1286 1325 -- 3,250 3,742 4,293 4,901 5,564 6,281 7,053 7,876 8,751 9,674 10,642 11,654 -- 3.74 4.30 4.94 5.64 6.40 7.22 8.11 9.06 10.06 11.13 12.24 13.40 -- AIRFLOW (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 AVAILABLE 0.4 0.2 AVAILABLE 1.4 1.2 EXTERNAL STATIC 1.6 PRESSURE (in. wg) 1.8 2.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 934 967 1003 1041 1081 1121 1161 1202 1242 1282 1322 3,521 4,010 4,565 5,181 5,859 6,595 7,390 8,244 9,154 10,118 11,136 4.05 4.61 5.25 5.96 6.74 7.59 8.50 9.48 10.53 11.64 12.81 978 1007 1040 1076 1114 1153 1193 1233 1273 1314 1354 3,822 4,297 4,847 5,465 6,150 6,899 7,710 8,584 9,519 10,514 11,568 4.40 4.94 5.57 6.29 7.07 7.93 8.87 9.87 10.95 12.09 13.30 1023 1048 1078 1111 1147 1184 1223 1263 1303 1343 1384 4,160 4,612 5,148 5,762 6,448 7,202 8,025 8,913 9,866 10,884 11,964 4.78 5.30 5.92 6.63 7.42 8.28 9.23 10.25 11.35 12.52 13.76 1071 1090 1116 1146 1179 1215 1253 1291 1331 1371 ...... 4,540 4,960 5,474 6,076 6,756 7,512 8,340 9,237 10,203 11,237 5.22 5.70 6.30 6.99 7.77 8.64 9.59 10.62 11.73 12.92 1119 1134 1155 1181 1212 1246 1282 1319 1358 1397 4,961 5344 5,830 6,412 7,081 7,832 8,660 9,563 10,537 11,584 5.71 6.15 6.71 7.37 8.14 9.01 9.96 11.00 12.12 13.32 LEGEND NOTES: 1.Maximum continuous bhp is: Low Range: 5.75 Mid-Low Range: 5.75 Mid-High Range: 8.63 High Range: 11.50 2.See page 27 for general fan performance Bhp -- Brake Horsepower Input to Fan Watts -- Input Watts to Motor *Motor drive ranges: Low Range: 687-873 Mid-Low Range: 805-1007 Mid-High Range: 941-1176 High Range: 1014-1297 All other rpms require field-supplied drive. 29 notes. Table 9 -- Fan Performance -- 50HJ020 Horizontal Discharge Units* AIRFLOW (Of m) AVAILABLE 0.4 0.2 EXTERNAL STATIC 0.6 PRESSURE (in. wg) 0.8 1.0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 445 484 524 566 608 651 695 740 785 831 878 546 718 923 1166 1450 1777 2152 2576 3051 3581 4167 0.63 0.83 1.06 1.34 1.67 2.04 2.47 2.96 3.51 4.12 4.79 526 559 596 634 672 712 753 794 836 878 922 712 896 1116 1373 1667 2002 2381 2807 3282 3810 4394 0.82 1,03 1.28 1,58 1,92 2,30 2,74 3,23 3.77 4,38 5.05 603 627 658 692 729 766 805 844 885 925 966 892 1079 1308 1576 1884 2232 2623 3059 3544 4077 4664 1.03 1.24 1.50 1.81 2.17 2.57 3.02 3.52 4.08 4.69 5.36 681 694 717 747 780 815 852 890 929 969 1008 1102 1280 1508 1781 2099 2459 2863 3312 3807 4352 4948 1.27 1.47 1.73 2,05 2,41 2,83 3,29 3,81 4,38 5,01 5.69 761 763 777 800 829 862 897 933 971 1009 1048 1346 1505 1724 1996 2318 2686 3100 3561 4069 4625 5233 1.55 1.73 1.98 2.30 2.67 3.09 3.57 4.10 4.68 5.32 6.02 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 AIRFLOW (Of m) 35O0 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 AVAILABLE 1.4 1.2 Rpm Watts Bhp 833 838 854 878 907 939 974 1010 1047 1085 1759 1961 2226 2546 2918 3339 3809 4328 4896 5515 2.02 2,26 2.56 2.93 3.36 3.84 4.38 4.98 5.63 6.34 EXTERNAL STATIC 1.6 PRESSURE (in. wg) 1.8 2,0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp ............ 900 909 927 952 981 1013 1047 1083 1120 2223 2473 2787 3158 3583 4059 4587 5165 5795 2.56 2.84 3.21 3.63 4.12 4.67 5.28 5.94 6.66 962 964 976 996 1022 1052 1084 1118 1154 2507 2740 3042 3408 3834 4314 4848 5435 6074 2,88 3.15 3.50 3.92 4.41 4.96 5.58 6.25 6.99 ...... 1020 1026 1041 1063 1090 1120 1153 1187 3029 3315 3672 4094 4575 5112 5706 6353 3.48 3.81 4.22 4.71 5.26 5.88 6.56 7.31 -1077 1087 1105 1128 1156 1187 1220 -3606 3950 4364 4843 5382 5980 6634 -4.15 4.54 5.02 5.57 6.19 6.88 7.63 LEGEND NOTES: 1. Bhp --Brake Horsepower Input to Fan Watts -- Input Watts to Motor Maximum continuous bhp is: Low Range: Not Used Mid-Low Range: 4.25 (208/230 Mid-High Range: 5.75 High Range: 8.63 *Motor drive ranges: Low Range: Not Used Mid-Low Range: 647-886 (208/230 and 460-v), 810-1072 (575-v) Mid-High Range: 897-1139 (208/230 and 460-v), 873-1108 (575-v) High Range: 1078-1274 All other rpms require field-supplied drive. 2. 30 See page 27 for general and 460-v), fan performance 3.45 notes. (575-v) Table 10AIRFLOW (Cfm) 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 575 619 663 708 753 800 847 894 941 989 1037 Watts 1193 1483 1817 2198 2629 3112 3650 4244 4896 5610 6386 Bhp 1.37 1.71 2.09 2.53 3.02 3.58 4.20 4.88 5.63 6.45 7.34 Rpm 642 682 723 765 807 850 894 939 983 1029 1075 Watts 862 886 916 949 984 1021 1059 1099 1138 1179 1220 2260 2586 2965 3395 3875 4406 4988 6623 6312 7057 7860 Watts 1400 1702 2048 2435 2871 3357 3897 4491 5145 5858 6634 Bhp 1.61 1.96 2.35 2.80 3.30 3.86 4.48 5.17 5.92 6.74 7.63 AVAILABLE 1,4 1,2 Rpm 50HJ024 Horizontal Discharge Units* AVAILABLE EXTERNAL 0.4 0.2 AIRFLOW (Cfm) 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Fan Performance- Bhp 2.60 2.97 3.41 3.90 4.46 5.07 5.74 6.47 7.26 8.12 9.04 Rpm 700 737 776 816 857 898 940 982 1025 1069 1113 EXTERNAL STATIC PRESSURE 0,6 Watts 1603 1918 2276 2677 3125 3621 4169 4770 5428 6145 6923 STATIC 1,6 Bhp 1.84 2.21 2.62 3.08 3.59 4.16 4.80 5.49 6.24 7.07 7.96 Rpm 754 788 825 863 902 942 982 1024 1065 1108 1150 PRESSURE (in. wg) 0.8 Watts 1810 2134 2503 2916 3377 3885 4445 5056 5723 6447 7231 1.0 Bhp 2.08 2.45 2.88 3.35 3.88 4.47 5.11 5.82 6.58 7.41 8.32 Rpm 808 837 871 906 944 982 1022 1062 1103 1144 1186 (in. wg) 1.8 Wat_ 2028 2355 2731 3155 3626 4146 4717 5340 6018 6753 7546 Bhp 2.33 2.71 3.14 3.63 4.17 4.77 5.43 6.14 6.92 7.77 8.68 2,0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 917 935 960 990 1023 1059 1095 1133 1172 1212 1282 2510 2829 3207 3641 4127 4666 6258 6903 6603 7359 8174 2.89 3.25 3.69 4.19 4.75 5.37 6.05 6.79 7.59 8.46 9.40 972 985 1005 1032 1062 1095 1130 1167 1205 1244 1283 2781 3089 3461 3894 4383 4928 5528 6182 6893 7660 8485 3.20 3.55 3.98 4.48 5.04 5.67 6.36 7.11 7.93 8.81 9.76 1028 1035 1050 1073 1100 1131 1165 1200 1237 1276 1313 3073 3365 3728 4157 4647 5195 5800 6463 7182 7959 8794 3.53 3.87 4.29 4.78 5.34 5.98 6.67 7.43 8.26 9.15 10.11 1084 1086 1096 1114 1139 1167 1199 1232 1268 1305 1342 3384 3660 4009 4430 4918 5468 6077 6745 7472 8258 9103 3.89 4.21 4.61 5.10 5.66 6.29 6.99 7.76 8.59 9.60 10.47 LEGEND NOTES: 1. Maximum continuous bhp is: Low Range: 4.25 (208/230 and 460-v), 5.75 (575-v) Mid-Low Range: 5.75 Mid-High Range: 8.63 High Range: 11.50 2. See page 27 for general fan performance notes. Bhp -- Brake Horsepower Input to Fan Watts -- Input Watts to Motor *Motor drive ranges: Low Range: 685-939 (208/230 and 460-v), 751-954 (575-v) Mid-Low Range: 949-1206 Mid-High Range: 941-1176 High Range: 1014-1297 All other rpms require field-supplied drive. 3! Table 11 -- Fan Performance -- 50HJ028 Horizontal Discharge Units* AIRFLOW (Cfm) 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 Rpm Watts Bhp Rpm 759 810 862 913 965 1017 1069 1121 1173 1226 1278 1331 2,517 3,020 3,581 4,206 4,894 5,651 6,477 7,376 8,350 9,401 10,532 11,745 2.89 3.47 4.12 4.84 5.63 6.50 7.45 8.48 9.60 10.81 12.11 13.51 804 2,753 853 3,274 903 3,856 953 4,500 1003 5,209 1054 5,988 1105 6,834 1156 7,755 1207 8,751 1259 9,823 1310 10,975 ............ AIRFLOW (Cfm) Watts STATIC PRESSURE 0.6 Watts 3,710 4,245 4,854 5,535 6,289 7,115 8,016 8,993 10,048 11,183 Bhp 4.27 4.88 5.58 6.37 7.23 8.18 9.22 10.34 11.56 12.86 Rpm 1003 1037 1075 1116 1159 1204 1249 1296 1343 1390 Watts 4,005 4,527 5,129 5,808 6,563 7,394 8,301 9,286 10,351 11,496 Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 3.17 3.77 4.43 5.18 5.99 6.89 7.86 8.92 10.06 11.30 12.62 844 891 939 988 1037 1087 1137 1187 1238 1288 1339 2,975 3,509 4,105 4,765 5,491 6,285 7,150 8,089 9,103 10,194 11,366 3.42 4.04 4.72 5.48 6.32 7.23 8.22 9.30 10.47 11.72 13.07 883 928 974 1021 1069 1118 1167 1216 1266 1316 1366 3,202 3,743 4,348 5,019 5,758 6,567 7,446 8,400 9,430 10,538 11,726 3.68 4.30 5.00 5.77 6.62 7.55 8.56 9.66 10.85 12.12 13.49 922 964 1008 1053 1100 1147 1195 1243 1292 1342 -- 3,445 3,986 4,596 5,274 6,022 6,841 7,733 8,699 9,744 10,866 -- 3.96 4.58 5.29 6.07 6.93 7.87 8.89 10.01 11.21 12.50 -- Bhp 5.41 5.95 6.61 7.36 8.22 9.18 10.22 11.37 12.61 Rpm 1135 1155 1182 1214 1249 1288 1329 1371 -- Watts 5,103 5,547 6,091 6,733 7,467 8,289 9,198 10,193 -- Bhp 4.61 5.21 5.90 6.68 7.55 8.50 9.55 10.68 11.90 13.22 3250 3350 3450 3550 3650 3750 3850 3950 4050 4250 4450 4650 4850 5050 5250 5450 5650 5850 ESP 0.32 0.23 0.17 0.13 0.09 Bhp 1.41 1.44 1.46 1.47 1.49 2.0 Bhp 5.87 6.38 7.01 7.74 8.59 9.53 10.58 11.72 -- notes. Power Exhaust Fan Performance ESP 0.70 0.63 0.59 0.56 0.53 0.51 0.48 0.45 0.40 Bhp 1.49 1.52 1.55 1.56 1.58 1.60 1.62 1.64 1.67 V Watts 1670 1700 1730 1745 1765 1790 1810 1835 1865 208 V HIGH SPEED 230,460,575 V 208 V 230,460,575 V ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts 0.60 0.55 0.49 0.43 0.39 0.33 0.27 0.22 0.17 0.00 1.51 1.54 1.56 1.59 1.62 1.64 1.66 1.68 1.74 1.79 1690 1720 1750 1780 1815 1835 1860 1885 1945 2005 0.82 0.78 0.73 0.68 0.64 0.59 0.54 0.49 0.40 0.30 0.22 0.16 0.12 1.62 1.64 1.67 1.70 1.72 1.74 1.76 1.79 1.84 1.89 1.94 1.98 2.02 1810 1840 1870 1900 1930 1950 1975 2000 2060 2115 2170 2215 2260 0.60 0.56 0.51 0.41 0.31 0.20 0.11 0.04 1.85 1.87 1.89 1.92 1.97 2.04 2.09 2.13 2070 2095 2120 2145 2205 2280 2335 2385 ----- 0.73 0.69 0.65 0.56 0.47 0.37 0.30 0.23 0.17 0.12 0.07 0.04 1.99 2.01 2.04 2.06 2.12 2.19 2.24 2.28 2.33 2.38 2.40 2.42 2230 2255 2280 2310 2370 2450 2505 2555 2610 2665 2690 2710 LEGEND Bhp -ESP -- Watts 4,701 5,174 5,744 6,403 7,149 7,978 8,890 9,884 10,960 MEDIUM SPEED 230,460,575 Watts 1580 1610 1635 1645 1665 Rpm 1090 1115 1145 1180 1219 1260 1302 1346 1391 drive. LOW SPEED 208 V Bhp 4.98 5.56 6.24 7.01 7.88 8.83 9.88 11.02 12.25 (in. wg) 1.8 NOTES: 1. Maximum continuous bhp is: Low Range: 5.75 Mid-Low Range: 5.75 Mid-High Range: 8.63 High Range: 11.50 2. See page 27 for general fan performance Table 12AIRFLOW (Cfm) STATIC PRESSURE 1.6 Rpm Watts 1045 4,334 1075 4,836 1110 5,424 1148 6,096 1189 6,849 1232 7,681 1276 8,591 1321 9,582 1367 10,655 ......... --Brake Horsepower Input to Fan -- Input Watts to Motor *Motor drive ranges: Low Range: 687-873 Mid-Low Range: 805-1007 Mid-High Range: 941-1176 High Range: 1014-1297 All other rpms require field-supplied 1.0 Rpm LEGEND Bhp Watts (in. wg) 0.8 Bhp AVAILABLE EXTERNAL 1.4 1.2 Rpm 962 1000 1041 1085 1129 1175 1222 1270 1318 1366 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 12,500 AVAILABLE EXTERNAL 0.4 0.2 Brake Horsepower External Static Pressure (in. wg) 32 Table 13 -- Operation Air Quantity Limits 50HJ UNIT SIZE Minimum Cfm COOLING 020 5,400 Maximum Cfm ELECTRIC HEAT (Vertical) MINIMUM CFM ELECTRIC HEAT (Horizontal) MINIMUM CFM 4,500 5,400 3,750 4,800 Low Heat (25 kW) 3,750 3,750 High Heat (75 kW) 4,500 5,400 3,750 4,800 Low Heat (25 kW) 3,750 3,750 High Heat (75 kW) 4,500 5,400 3,750 4,800 3,750 3,750 ELECTRIC HEAT High Heat (75 kW) 024 9,000 5,500 028 Medium 10,000 Medium 11,500 6,000 Medium Heat (50 kW) Heat (50 kW) Heat (50 kW) Low Heat (25 kW) Table 14 -- Evaporator Fan Motor Specifications 5OHJ UNIT SIZE DRIVE Low Mid-Low Mid-High High ORIENTATION Vertical Vertical Vertical Vertical O2O Low Mid-Low Mid-High High Horizontal Horizontal Horizontal Horizontal MOTOR PIN NOMINAL HP VOLTAGE ---- EFFICIENCY % MAX BHP MAX BkW MAX AMPS N/A N/A 208 N/A N/A N/A N/A N/A N/A N/A 230 N/A N/A N/A N/A N/A N/A N/A 460 N/A N/A N/A N/A N/A N/A N/A 575 N/A N/A N/A N/A N/A HD60FK651 3.7 208 3698 85.8 4.25 3.17 10.6 HD60FK651 3.7 230 3698 85.8 4.25 3.17 9.6 HD60FK651 3.7 460 3698 85.8 4.25 3.17 4.8 HD58DL575 3 575 3149 81.7 3.45 2.57 3.9 HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9 N/A N/A 208 N/A N/A N/A N/A N/A N/A N/A 230 N/A N/A N/A N/A N/A N/A N/A 460 N/A N/A N/A N/A N/A N/A N/A 575 N/A N/A N/A N/A N/A HD60FK651 3.7 208 3698 85.8 4.25 3.17 10.6 HD60FK651 3.7 230 3698 85.8 4.25 3.17 9.6 HD60FK651 3.7 460 3698 85.8 4.25 3.17 4.8 HD58DL575 3 575 3149 81.7 3.45 2.57 3.9 HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9 LEGEND Bhp N/A P/N MAX WATTS Brake Horsepower Not Applicable Part Number 33 Table 14 -- Evaporator Fan Motor Specifications 50HJ UNIT SIZE DRIVE Low Mid-Low Mid-High High ORIENTATION Vertical Vertical Vertical Vertical O24 Low Mid-Low Mid-High High Low Mid-Low Mid-High High Horizontal Horizontal Horizontal Horizontal Vertical Vertical Vertical Vertical 028 Low Mid-Low Mid-High High Horizontal Horizontal Horizontal Horizontal MOTOR PIN NOMINAL HP VOLTAGE MAX WATTS (cont) EFFICIENCY % MAX BHP MAX BkW MAX AMPS HD60FK651 3.7 208 3698 85.8 4.25 3.17 10.6 HD60FK651 3.7 230 3698 85.8 4.25 3.17 9.6 HD60FK651 3.7 460 3698 85.8 4.25 3.17 4.8 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9 HD64FL650 10 208 9582 89.5 11.5 8.58 30.8 HD64FL650 10 230 9582 89.5 11.5 8.58 28 HD64FL650 10 460 9582 89.5 11.5 8.58 14 HD64FL575 10 575 9582 89.5 11.5 8.58 11 HD60FK651 3.7 208 3698 85.8 4.25 3.17 10.6 HD60FK651 3.7 230 3698 85.8 4.25 3.17 9.6 HD60FK651 3.7 460 3698 85.8 4.25 3.17 4.8 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9 HD64FL650 10 208 9582 89.5 11.5 8.58 30.8 HD64FL650 10 230 9582 89.5 11.5 8.58 28 HD64FL650 10 460 9582 89.5 11.5 8.58 14 HD64FL575 10 575 9582 89.5 11.5 8.58 11 HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9 HD64FL650 10 208 9582 89.5 11.5 8.58 30.8 HD64FL650 10 230 9582 89.5 11.5 8.58 28 HD64FL650 10 460 9582 89.5 11.5 8.58 14 HD64FL575 10 575 9582 89.5 11.5 8.58 11 HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD60FL650 5 208 4900 87.5 5.75 4.29 16.7 HD60FL650 5 230 4900 87.5 5.75 4.29 15.2 HD60FL650 5 460 4900 87.5 5.75 4.29 7.6 HD60FL575 5 575 4900 87.5 5.75 4.29 6.1 HD62FL650 7.5 208 7267 88.5 8.63 6.43 24.2 HD62FL650 7.5 230 7267 88.5 8.63 6.43 22 HD62FL650 7.5 460 7267 88.5 8.63 6.43 11 HD62FL575 7.5 575 7267 88.5 8.63 6.43 9 HD64FL650 10 208 9582 89.5 11.5 8.58 30.8 HD64FL650 10 230 9582 89.5 11.5 8.58 28 HD64FL650 10 460 9582 89.5 11.5 8.58 14 HD64FL575 10 575 9582 89.5 11.5 8.58 11 34 Table 15 -- Fan Rpm and Motor Pulley Settings* 50HJ UNIT SIZE MOTOR RANGE PULLEY 21/2 TURNS 3 OPEN 0 1/2 1 11/2 2 31/2 4 41/2 5 51/2 6 Mid-Low Range Vertical 647 667 687 707 727 747 767 786 806 826 846 866 886 Mid-High 897 917 937 958 978 998 1018 1038 1058 1079 1099 1119 1139 1078 1094 1111 1127 1143 1160 1176 1192 1209 1225 1241 1258 1274 647 667 687 707 727 747 767 786 806 826 846 866 886 897 917 937 958 978 998 1018 1038 1058 1079 1099 1119 1139 1078 1094 1111 1127 1143 1160 1176 1192 1209 1225 1241 1258 1274 Mid-Low Range Vertical 810 832 854 876 897 919 941 963 985 1007 1028 1050 1072 Mid-High 873 893 912 932 951 971 991 1010 1030 1049 1069 1088 1108 1078 1094 1111 1127 1143 1160 1176 1192 1209 1225 1241 1258 1274 810 832 854 876 897 919 941 963 985 1007 1028 1050 1072 873 893 912 932 951 971 991 1010 1030 1049 1069 1088 1108 High Range Horizontal 1078 1094 1111 1127 1143 1160 1176 1192 1209 1225 1241 1258 1274 Low Range Vertical 685 706 727 749 770 791 812 833 854 876 897 918 939 Mid-Low Range Vertical 949 970 992 1013 1035 1056 1078 1099 1120 1142 1163 1185 1206 Low Range Vertical 020 (230 and 460 volt) Range Vertical High Range Vertical Low Range Horizontal Mid-Low Range Horizontal Mid-High Range Horizontal High Range Horizontal Low Range Vertical 020 (575 volt) Range Vertical High Range Vertical Low Range Horizontal Mid-Low Range Horizontal Mid-High Range Horizontal 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176 High Range Vertical 1014 1038 1061 1085 1108 1132 1156 1179 1203 1226 1250 1273 1297 Low Range Horizontal 685 706 727 749 770 791 812 833 854 876 897 918 939 Mid-Low Range Horizontal 949 970 992 1013 1035 1056 1078 1099 1120 1142 1163 1185 1206 Mid-High 024 (230 and 460 volt) Range Vertical 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176 High Range Horizontal 1014 1038 1061 1085 1108 1132 1156 1179 1203 1226 1250 1273 1297 Low Range Vertical 751 768 785 802 819 836 853 869 886 903 920 937 954 Mid-Low Range Vertical 949 970 992 1013 1035 1056 1078 1099 1120 1142 1163 1185 1206 Mid-High Range Horizontal 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176 High Range Vertical 1014 1038 1061 1085 1108 1132 1156 1179 1203 1226 1250 1273 1297 Low Range Horizontal 751 768 785 802 819 836 853 869 886 903 920 937 954 Mid-Low Range Horizontal 949 970 992 1013 1035 1056 1078 1099 1120 1142 1163 1185 1206 Mid-High 024 (575 volt) Range Vertical 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176 High Range Horizontal 1014 1038 1061 1085 1108 1132 1156 1179 1203 1226 1250 1273 1297 Low Range Vertical 687 703 718 734 749 765 780 796 811 827 842 858 873 Mid-Low Range Vertical 805 822 839 856 872 889 906 923 940 957 973 990 1007 Mid-High Range Horizontal 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176 High Range Vertical 1014 1038 1061 1085 1108 1132 1156 1179 1203 1226 1250 1273 1297 Low Range Horizontal 687 703 718 734 749 765 780 796 811 827 842 858 873 Mid-Low Range Horizontal 805 822 839 856 872 889 906 923 940 957 973 990 1007 Mid-High O28 (all voltages) Mid-High Range Vertical *Approximate 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176 1014 1038 1061 1085 1108 1132 1156 1179 1203 1226 1250 1273 1297 Range Horizontal High Range Horizontal fan rpm shown. Table 1650HJ UNIT SIZE 020, 024,028 HEATER kW Unit Voltages 240 460 480 Electric Resistance Heater Data MINIMUM HEATER STAGES % HEAT PER STAGE MAXIMUM STAG ES* 208 230 575 600 19 23 25 23 25 23 25 2 50/50 2 38 46 50 46 50 44 48 2 50/50 2 56 69 75 69 75 72 78 2 50/50 2 *Maximum number of stages using accessory low-ambient temperature and low-ambient temperature kit. NOTE: Heaters are rated at 208,240, 480, and 600 v. Heating Cfm Cfm L/s 4800 2265 HEATER AMPS 208 230 240 460 480 575 600 52.0 58.0 60.0 29.0 30.0 23.0 24.0 104.0 115.0 120.0 58.0 60.0 44.0 48.0 156.0 173.0 180.0 86.0 90.0 72.0 75.0 kit or head _ressure control device 35 Table 17 -- Accessory/FlOP COMPONENT EconoMi$er IV COMPONENT EconoMi$er IV I 4,000 0.02 I 8,500 0.11 I I EconoMi$er IV Static Pressure (in. wg)* 4,500 5,000 5,500 0.03 0.04 0.05 9,000 9,500 0.12 0.13 I IoF°I 6,000 6,500 7,000 7,500 0.06 0.07 0.08 0.09 IcFMI 10,000 0.15 10,500 11,000 0.16 0.17 I 11,500 0.19 I I 8,000 0.10 12,000 0.20 LEGEND FlOP -- Factory-Installed Option *The static pressure must be added to external static pressure. The sum and the evaporator entering-air should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts. cfm Table 18 -- Accessory Electric Heat Static Pressure (in. wg) ELECTRIC UNIT 50HJ Unit Voltages 208/240-3-60 020, 024,028 480-3-60 575-3-60 Cfm Nominal Heater Size (kW) Pressure Drop (in. wg) --- Pressure Drop (in. wg) Nominal Heater Size (kW) Pressure Drop (in. wg) 4,800 0.01 0.02 0.03 5,000 0.01 0.02 0.04 6,000 7,000 0.02 0.04 0.06 0.03 0.06 0.08 8,000 9,000 0.04 0.08 0.12 0.05 0.10 0.15 10,000 0.06 0.13 0.20 11,500 4,800 0.09 0.18 0.27 0.01 0.02 0.03 5,000 0.01 0.02 0.04 6,000 0.02 0.04 0.06 7,000 0.03 0.06 25 50 0.08 0.04 0.05 0.10 0.15 10,000 0.06 0.13 0.20 11,500 0.09 0.18 0.27 4,800 0.01 0.02 0.03 5,000 6,000 0.01 0.02 0.04 0.02 0.04 0.06 7,000 8,000 0.03 0.06 0.08 0.04 0.08 0.12 9,000 0.05 0.10 0.15 10,000 0.06 0.13 0.20 11,500 0.09 0.18 0.27 2. Brake Horsepower Factory-Installed Option NOTES: 1. Heaters are rated at 240 v, 480 v, and 600 v. 36 0.08 75 8,000 9,000 LEGEND Bhp FlOP HEATERS Nominal Heater Size (kW) 0.12 The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance table to determine blower rpm, bhp, and watts. ECONOMISER IV CONTROLLER WIRING AND OPERATIONAL MODES -- Determine the EconoMiSer IV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 19. The EconoMiSer IV is supplied fiom the factory with a supply-air temperature sensor and an outdoor air temperature sensol: This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to _dlow for different types of changeover control and operation of the EconoMiSer IV and unit. Optional EconoMiSer IV -- See Fig. 20 for EconoMi$er IV component locations. The optional EconoMi$er IV comes fi_m the factory fi.dly wiled and assembled. No field wMng or assembly is required for standard outdoor &-y bulb changeover operation. Field wiring of accesso U sensors is required for diffelent operational modes. ECONOMI$ER IV STANDARD SENSORS Outdoor Air Temperature (OAT) Sensor -- The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMiSer IV in the outdoor airstream. See Fig. 21. The operating range of temperature measurement is 40 to 100 E Outdoor D U Bulb Changeover -- The standard controller is shipped from the factory configmed for outdoor dry bulb changeover control. The outdoor air and supply-air temperature sensors me included as stand_u'd. For this control mode, the outdoor temperature is compaled to an adjustable set point selected on the control. If the outdoor-air temperatme is above the set point, the EconoMi$er IV will adjust the outdoor-air dampers to minimum position. If the outdoor-air temperature is below the set point, the position of the outdoor-air dalnpel_ will be controlled to provide free cooling using outdoor ail: When in this mode, the LED next to the free cooling set point potenfiometer will be on. The changeover temperature set point is controlled by the free cooling set point potentiometer located on the control. The sc_de on the potentiometer is A, B, C, and D. See Fig. 22 for the corresponding temperature changeover values. Supply-Air Temperature (SAT) Sensor -The supply-air temperature sensor is a 3 K thermistor located at the outlet of the indoor fan. See Fig. 21. This sensor is factoly installed. The operating range of temperature measmement is 0 ° to 158 E The temperature sensor is a short probe with blue wires running to it. Outdoor Air Lockout Sensor -- The Economi$er IV is equipped with an ambient temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42 F ambient temperature. Table 19 -- EconoMi$er IV Sensor Usage APPLICATION ECONOMI$ER IV WITH OUTDOOR DRY BULB SENSOR Accessories Outdoor Differential Single Air Dry Bulb None. The outdoor Dry Bulb CO2 for DCV Control using a Wall-Mounted CO2 Sensor CO2 Sensor Required air dry bulb sensor CRTEMPSN002A00* Accessories is factory installed. (2) CRTEMPSN002A00* None. The single _) enthalpy sensor is factory installed. CRENTDIF004A00* 33ZCSENCO2 and 33ZCSENCO2133ZCASPCO2** Required CRTEMPSN002A00* HH57AC078 and CRENTDIF004A00* Differential Enthalpy Duct-Mounted ECONOMISER IV WITH SINGLE ENTHALPY SENSOR HH57AC078 Enthalpy CO2 for DCV Control using a AIR 33ZCSENC02 CRCBDiOX005A001-1- and 33ZCSENCO2133ZCASPCO2** *CRENTDiF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these needed for installation. 1-33ZCSENCO2 is an accessory CO2 sensor. **33ZCASPCO2 is an accessory aspirator box required for duct-mounted applications. 1-1-CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories. 37 CRCBDIOX005A001-1- kits may contain parts that will not be DAMPER ASSEMBLY WIRE HARNESS DAMPER ACTUATOR ECONOMIZER BLOCK OFF Fig. 20 i EconoMiSer IV Component Locations (Exploded View) 19 LED _ON 18 17 16- LED ON - LED OFF 15 < E14 LED O_ 13 12 LED ON- -- 11 10 9 4O 45 50 55 60 65 DEGREES Fig. 21 i Supply-Air Temperature Sensor Location Fig. 22 i 38 70 75 80 85 90 95 100 FAHRENHEIT Outdoor-Air Temperature Changeover Set Points Differential Dry Bulb Control -- For differentkd cfly bulb control the stan&u_d outdoor dry bulb sensor is used in conjunction with an additional accessory c_h_bulb sensor (part number CRTEMPSN002A00). Tile accessory sensor must be mounted in the return ail_tream. Wiring is provided in file EconoMi$er IV wiling h_u'ness. See Fig. 23. In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn file enth_flpy set point potentiometer fully clockwise to the D setting. Outdoor Enthalpy Changeover -- For enth_dpy control, accesso U enthalpy sensor (p_ut number HH57AC078) is required. Replace the standmd outdoor @ bulb temperature sensor with the accessory enthalpy sensor in file same mounting location. When file outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air &tmper moves to its minimum position. The outdoor enthalpy changeover set point is set with the outdoor enth_dpy set point potentiometer on the EconoMiSer IV controllel: The set points me A, B, C, and D. See Fig. 24. The factory-installed 620-ohm jumper must be in place across termin_ds SR and + on the EconoMiSer IV controllel: See Fig. 23. Differential Enthalpy Control -- For differentkd enthalpy control, the EconoMiSer IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMiSer [V controller compares file outdoor air enthalpy to the return air enthalpy to determine EconoMi$er [V use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when file outdoor air has a lower enthalpy than the return ail: the EconoMiSer IV opens to bring in outdoor air for free cooling. Replace file standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. Mount the return air enth_dpy sensor in the return air duct. Wiring is provided in the EconoMiSer IV wiring harness. See Fig. 23. The outdoor enth_dpy changeover set point is set with the outdoor enthalpy set point potentiometer on file EconoMi$er IV controllel: When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting. See Fig. 25. Indoor Air Quality (IAQ) Sensor Input -- The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct. Mount the optional IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQI terminals of the controllel: Adjust the DCV (demand controlled ventilation) potentiometels to correspond to the DCV voltage output of file indoor air quzdity sensor at the user-determined set point. See Fig. 26. If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be dmnaged. Exhaust Set Point Adjustment -- The exhaust set point will determine when the exhaust fan runs based on dmnper position (if accessory power exhaust is insLdled). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometel: See Fig. 25. The set point represents the damper position above which the exhaust fans will be turned on. When there is a c_dl for exhaust, the EconoMiSer IV controller provides a 45 _+15 second delay before exhaust fan activation to _dlow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessmy fan overload. LEGEND -4RA_>Pu-6 PU-B _I_BLU'] -_LU_> _i-S I PLH ECB I <_-- -- -RED-N I -- --RED ---_ -p_ _ PL1-9 [_> IA --Indoor Air IAQ -- Indoor Air Quality OA -- Outdoor Air OAS-- Outdoor-Air Temperature Sensor PL -- Plug RAS-- Return-Air Temperature Sensor SAT -- Supply-Air Temperature Sensor PLI-12 ORN _ Pu-l N MINIMUM BI • I GRA I ..I FPNK_ -- -BLU-_C)-- _ 1_-- BLK IED A_.I_BLK-O PLI-IO (_- 1 -- -GRA@ -REI: ,,i i Tf" I I;i +L L,_U--,&' 14 I SAT 1 '-"-' ........... L _ _I BR _ \\ Loo_c-Yl I;_-_ OR_ _ PL. "k RED \ _[_ _D41EN Fig. 23 -- EconoMi$er IV Wiring 39 _STALLINO IA ENTHALPY OR RETURN AIR SENSOR REMOVE 6L_O_'_ RESISTOR _ETWEEN SR+ & _ AN0 ":| (_--IS BISE_CEO WHEN DA ENII.IALPYIS INSTALLED _c_iz_ SVTTCH ENA_-E ACCY CDNNZCT BLU & ORN VIES CONTROL CONTROL 85 90 95 100 105 110 (29) (32) (35) (38) (41) (43) POINT CURVE APPROX. °F (°C) AT 50% RH A 73 (23) B 70/21 ) C D 67 (19) 63 (17) LIMIT CURVE 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 (2) (4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43) DRY BULB APPROXIMATE TEMPERATURE Fig. 24 -- Enthalpy i °F (°C) Changeover Set Points CO 2 SENSOR MAX RANGE SETTING EXHAUST FAN SETPOtNT 6000 LED LIGHTS WHEN EXHAUST CONTACT tS MADE MINIMUM POSITION 5000 DAMPER SETTING z 2 MAXIMUM DAMPER DEMAND CONTROL VENTILATION SET POINT +800 3000 LED LIGHTS WHEN_ DEMAND CONTROL VENTILATION INPUT IS ABOVE SET POINT _1000 z +1100 2000 _900 w z < DEMAND CONTROL VENTILATION SET POINT LED LIGHTS WHEN OUTDOOR AIR IS 2 ENTHALPY SET POINT Fig. 25 -- EconoMi$er IV Controller and LED Locations ppm ppm ppm ppm 1000 3 4 5 6 7 DAMPER VOLTAGE FOR MAX VENTILATION FREE COOLING SUITABLE FOR CHANGEOVER 4000 8 RATE Fig. 26 -- 002 Sensor Maximum Range Setting Potentiometer 40 Minimum Position Control -- There is a minimum damper position potentiometer on the EconoMiSer IV controllel: See Fig. 25. The minimum dmnper position maintains the minimum airflow into the building during the occupied period. When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compounds) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation. When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise. Adjust the minimum position potentiometer to fdlow the minimum amount of outdoor air. as required by local codes, to enter the building. Make minimum position adjustments with fit least 10° F temperature difference between the outdoor and return-air temperatures. To determine the minimum position setting, perfoml the following procedure: 1. Calculate the appropriate mixed air temperature following formula: OA RA (To x l-q--if(57 + (TR x l-q--if(57 = TM is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field-supplied timeclock lhnction in place of the jumper between TR and N. See Fig. 23. When the timeclock contacts are closed, the EconoMiSer IV control will be in occupied mode. When the timeclock contacts are open (removing the 24-v signal from terminal N), the EconoMiSer IV will be in unoccupied mode. Demand Control Ventilation -- When using the EconoMiSer IV for demand control ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evfduated for design conditions. The maximum damper position must be calculated to provide the desired fresh all: Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per pel.son, using normfd outside air design criteria. A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rote fit design conditions. Exceeding file required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportionalanticipatory strategy will cause file fresh air supplied to increase as the room CO2 level increases even though the CO2 set point has not been reached. By the time the CO2 level reaches the set point, the damper will be fit maximum ventilation and should maintain the set point. In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures. using the To = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Telnperature RA = Percent of Return Air TM = Mixed-Air Temperature As an exmnple, if local codes require 10% outdoor during occupied conditions, outdoor-air temperature 60 IF.and return-air temperature is 75 IF. air is (60 x. 10) + (75 x .90) = 73.5 F 2. Disconnect TI. the supply-air 3. Ensure that terminals P used, make Fig. 23 and turned lully Connect 24 the factory-installed jumper is in place across and PI. If remote damper positioning is being sure that the terminals are wired according to that the minimum position potentiometer is clockwise. vac across terminals TR and TRI. 4. 5. sensor from terminals T and OA 7 + (TR x l-q--if(5-7 RA (To x l-q--if(5= TM To = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature Cmefully adjust the minimum position potentiometer until file measured mixed-air temperature matches the caiculated vaiue. Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position. 6. Reconnect the supply-air sensor to terminals T and Tl. Remote control of the EconoMiSer IV dmnper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell pfut number $963B11287 is wired to the EconoMiSer IV controller, the minimum position of the damper can be controlled from a remote location. To control the minimum damper the factory-installed jumper on the EconoMiSer IV controllel: Wire the ter to the P and PI termimds on file See Fig. 23. The same equation can be used to determine the occupied or maximum ventilation rote to the building. For exmnple, tin output of 3.6 volts to the actuator provides a base ventilation rate of 5% and tm output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 26 to determine the maximum setting of the CO2 sensor. For example, a 1100 ppm set point relates to a 15 cfin per person design. Use the 1100 ppm curve on Fig. 26 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chmt to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMiSer IV controller will output the 6.7 volts fi_m the CO2 sensor to the actuator when the COo concentration in the space is fit 1100 ppm. The DCV set point may be left fit 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometel: position remotely, remove P and PI terminals on the field-supplied potentiomeEconoMiSer IV controllel: Damper Movement -- Damper movement from full open to full closed (or vice versa) takes up to 21/2 minutes. Thermostats -- The EconoMi$er IV control works with conventional thermostats that have a YI (cool stage 1), Y2 (cool stage 27, WI (heat stage 1), W2 (heat stage 27, and G (fan). The EconoMiSer IV control does not support space temperature sensors like the T55 or T56. Connections are made at the thermostat terminal connection board located in the main control box. Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high-humidity levels. Occupancy Control -- The factory default configuration for the EconoMiSer IV control is occupied mode. Occupied status 41 Operating Sensor Configuration -- Tile CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 20. CO.2 Use setting 1 or2 for Carrier equipment. See Table 20. 1. Press Clem" and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode. 2. Press Mode twice. The STDSET 3. Use the Up/Down Table 20. Menu will appeal: 4. Press Enter to lock in file selection. button to select the preset numbec See 5. Press Mode to exit and resume normal operation. The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings: 1. Press Cletu and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode. 2. Press Mode twice. The STDSET 3. Use the Up/Down and press Enter. 4. Use the Up/Down button to toggle through each of the nine vmiables, starting wifll Altitude, until file desired setting is reached. Press Mode to move through the vmiables. 5. 6. If more cooling is required, the thermostat will call for a second stage of cooling, energizing Y2. This will _dlow relay CRI to energize, which in turn energizes the compressor contactor (C.CI on three-compressor units or C.BI on two-compressor units). The second stage compressor (CI on three-compressor units or B I on two-compressor units is then started. Menu will appeal: button to toggle to the NONSTD menu HEATING. Press Enter to lock in the selection, continue to the next variable. 20 -- 002 Sensor OUTPUT VENTILATION RATE (ofm/Person) Proportional Any Proportional Any 3 Exponential Any 4 Proportional 15 Proportional 20 6 Exponential 15 7 Exponential 20 1 2 Interface w/Standard Building Control System 5 Economizer 8 9 Health & Safety Parking/Air Intakes/ Loading Docks ECONOMIZER units have 2 stages of electric heat. If additional heating is required, file thermostat will call for a second stage of heating, energizing W2. This will energize the second stage of electric heat. COOLING. UNITS WITH ECONOMISER IV -- When free cooling is not available, the compressol_ will be controlled by the zone themlostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50 to 55 F mixed-air temperature into the zone. As the mixed-air temperature fluctuates above 55 or below 50 K the dampel_ will be modulated (open or close) to bring the mixed-air temperatme back within control. If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery and/or a dehumidification option should be considered. EQUIPMENT WITHOUT When the thermostat calls for one stage of heating, Wl is energized. The themlostat must be configured such that the blower output (G) is energized when there is a WI call for heating. The indoor-fan contactor (IFC) and first stage electric heat contactor(s) me energized and the indoor-fan motol: and first stage electric heater me started. Dehumidification of Fresh Air with DCV Control -- Information from ASHRAE (American Society of Heating, Refi'igeration, and Air Conditioning Engineers) indicates that the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as a 62AQ energy recovery unit is added to reduce the moisture content of the fiesh air being brought into the building when the enthalpy is high. In most cases, the norm_d heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications. SETTING UNITS NOTE: The 50HJ020-028 then press Mode to Table Sequence COOLING. UNITS WITHOUT ECONOMIZER -- When the thermostat calls for one stage of cooling, YI and G are energizedi The indoor-fan conmctor (IFC) and complessor contactor(s) (C.AI and C.BI on three-compressor units or C.AI only on two-compressor units), and outdoor-fan contactors (OFCI and OFC2 when outdoor temperature is above FCS [fan control switch] setting) are energized and the indoor-fan motol: compressor(s) (A 1 and BI on three-compressor units or A 1 only on two-compressor units), and outdoor fans controlled by OFCI are sttutedi If the outdoor temperature is above the setting of the fan control switch, the outdoor fans controlled by OFC2 are _dso stm-ted. Standard ANALOG OUTPUT 0-10V 4-20 mA 2-10V 7-20 mA 0-10V 4-20 mA 0-10V 4-20 mA 0-10V 4-20 mA 0-10V 4-20 mA 0-10V 4-20 mA Settings CO2 CONTROLRANGE (ppm) OPTIONAL RELAY SETPOINT (ppm) RELAY HYSTERESIS (ppm) 0-2000 1000 50 0-2000 1000 50 0-2000 1100 50 0-1100 1100 50 0- 900 900 50 0-1100 1100 50 0- 900 900 50 Proportional 0-10V 4-20 mA 0-9999 5000 500 Proportional 0-10V 4-20 mA 0-2000 700 50 LEGEND ppm -- Parts Per Million 42 Above 50 F supply-air temperature, the dmnpers will modulate from 100% open to the minimum open position. From 50 F to 45 F supply-air temperature, the &Lmpers will maintain at the minimum open position. Below 45 F the dampers will be completely shut. As the supply-air temperature rises, the dampers will come back open to the minimum open position once the supply-air temperature nses to 48 E panel is removed, the insulation behind the access panel will need to be cut away. Carefully cut the insulation with a knife or blade on three sides so the insulation can be folded out of the way during cleaning. Be cmeful not to damage components behind the insulation while cutting. Once cleaning is completed, fold the insulation back into place and secure the access panel in the original position. If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. FILTERS -- Clean or replace at stm-tof each heating and cooling season, or more often if operating conditions require. Refer to Table 1 for type and size. OUTDOOR-AIR INLET SCREENS -- Clean screens with steam or hot water grada mild detergent. Do not use throwaway filters in place of screens. See Table 1 for quantity and size. If field-installed accessory CO2 sensors are connected to the EconoMiSer IV control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the &_mper will be increased proportionally. As the CO2 level decreases because of the increase in fresh aik the outdoo>air &tmper will be proportionally closed. For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position. Lubrication COMPRESSORS -- Each compressor is chmged with the corlect mnount of oil at the factory. Conventiomd white oil (Zerol 150T or Sontex SA32) is used. White oil is compatible with 3GS oil, and 3GS oil may be used if the addition ofoil is required. See compressor nmneplate for origimd oil chmge. Oil mchmge amount is shown in Table 1. When a compressor is exchanged in the field it is possible that a major portion of the oil from the mplaced compressor may still be in the system. While this will not affect the reliability of the replacement compmssol, the extra oil will add rotor drag and increase power usage. To remove this excess oil, an access v_dvemay be added to the lower portion of the suction line at the inlet of the compressol: The compressor should then be mn for 10 minutes, shut down and the access valve opened until no oil flows. This should be repeated twice to make sure the proper oil level has been achieved. FAN SHAFT BEARINGS -- Lubricate betuings at least eveU 6 months with suitable bearing grease. Typical lubricants me given below: When the EconoMi$er IV control is in the occupied mode and a call for cooling exists (YI on the thermostat), the control will first check for indoor fan operation. If the fan is not on, then cooling will not be activated. If the fan is on, then the control will open the EconoMi$er IV dmnper to the minimum position. Damper movement from full closed to full open (or vice veLsa) will take between 11/2and 21/2 minutes. If free cooling can be used as determined from the appropriate changeover command (switch, din bulb, enthalpy curve, differential dry bulb, or differential enthalpy), then the control will modulate the dampeLs open to maintain the mixed air temperature set point at 50 to 55 E If there is a further demand for cooling (cooling second stage -- Y2 is energized), then the control will bring on compressor stage 1 to maintain the mixed-air temperature set point. The EconoMiSer IV &unper will be open at maximum position. EconoMiSer IV operation is limited to a single compressoE HEATING, UNITS WITH ECONOMI$ER IV -- When the room temperature calls for heat, the heating controls am energized as described in the Heating, Units Without Economizer section. The IFM is energized and the EconoMiSer IV damper modulates to the minimum position. When the thermostat is satisfied, the damper modulates closed. Texaco Mobil MANUFACTURER Sunoco Texaco ] Regal AFB-2* Mobilplex EP No. 1 LUBRICANT Prestige 42 Multifak 2 *Preferred lubricant because it contains rust and oxidation inhibitors. CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGSThe condenser and evaporator-fan motors have permanently sealed bearings, so no field lubrication is necessary. Evaporator Fan Service and Replacement -- The 50HJ units feature a slide-out fan deck for easy servicing of the indoor-fan motor, pulleys, belt, and bearings. To service components in this section, perform the following procedure: SERVICE 1. Shut offunit Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. 2. 3. Open the fan section access panel. Remove three no. 10 screws at front of slide-out fan deck. Save screws. See Fig. 27. 4. Disconnect the electrical plugs slide-out fan deck (evaporator mistor, and fan status switch, &_maged if not disengaged. Fan deck can now be slid Cleaning -- Inspect unit interior at beginning of each heating and cooling season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interioc EVAPORATOR COIL -- Clean as required with commercial coil cleanel: power supply. 5. and wires connected to the fan plug, supply air therif installed). Wires may be out to access serviceable components. CONDENSER COIL--Clean condenser coil annually and as required by location and outdoo>air conditions. Inspect coil monthly; clean as required. CONDENSATE DRAIN -- Check and clean each year at the start of the cooling season. In winter, keep diains and traps diN. An access panel is located above the condensate connection to allow easy clean out of the condensate pan. The first time the DO NOT SLIDE FAN DECK OUT PAST THE STOP BRACKET. [f further access is required, the fan deck must be suppolled. Make sum plugs and wiring are not pinched between fan housing and unit center post. Damage to unit may result. 43 6. Toreplace fandecktooperating position, slidefandeck backintotheunit.Secure withthethreeno.10screws removed inStep3. 7. Re-attach electrical plugs andwires. 8. Close fansection access door. 9. Restore power to unit. Evaporator Fan Performance (Fig. 27 and 28) -- Fan motor for speed shown in Table 1. MOTOR - PULLEY (HIDDEN) FAN PULLEY" Adjustment pulleys are factoq set - MOTOR To change fan speeds: 1. Shut off unit power supply. 2. Ix)osen nuts on the 4 caniage bolts in file mounting base. Using adjusting bolts and plate, slide motor and remove belt. 3. 4. 5. 6. 7. MOUNTING -BASE SLIDE-OUT FAN DECK [ Ix_osen movable-pulley flange setsclew (see Fig. 28). Screw movable flange toward fixed flange to increase speed and away fiom fixed flange to decrease speed. Incleasing fan speed increases load on motol: Do not exceed maximum speed specified in Table 1. Fig. 27 -- Evaporator-Fan See Table 13 for air quantity limits. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See 321ble 1 for speed change for each full turn of pulley flange.) STRAIGHTEDGE PARALLEL WITH BELT Replace and tighten belts (see Belt Tension Adjustment section below). Restore power to unit. Motor Adjustment MUST PULLEY To align fan and motor pulleys: 1. Ix_osen fan pulley setscrews. 2. 3. Slide fan pulley along fan shaft. Make angular alignment by mounting plate. 4. Restore power to unit. Belt Tension 2. 3. 4. 5. 6. loosening motor fi_m PULLEY Adjustment 1. Shut offpowerto MOVABLE FLANGES MOTOR AND FAN SHAFTS MUST BE PARALLEL -- Toadjust belt tension: SETSCREWS_ unit. Slide out fan deck to service position as shown in Evaporator Fan Service and Replacement section above. Ix_osen fan motor bolts. FIXED FLANGES SINGLE-GROOVE Move motor mounting plate to adjust to proper belt tension. See Table 21. Motor adjuster bolts may be used to tighten belts. See Fig. 27. Check for proper belt alignment. Adjust if necessary. 7. Tighten motor mounting plate bolts to lock motor in pint,per position. Return fan deck back into operating position. 8. Restore power to unit. Table 50HJ 10 B,K 4.9 C,L 5.1 D,M 5.7 E,N NA F,P 4.9 G,Q 5.1 H,R 5.7 460 NA 4.9 5.1 5.7 NA 4.9 5.1 5.7 575 NA 3.9 5.2 5.7 NA 3.9 5.2 5.7 4.8 5.1 5.6 4.5 4.8 5.1 5.6 4.5 460 4.8 5.1 5.6 4.5 4.8 5.1 5.6 4.5 575 5.3 5.1 5.6 4.5 5.3 5.1 5.6 4.5 4.5 5.4 5.9 4.5 4.5 5.4 5.9 4.5 460 4.5 5.4 5.9 4.5 4.5 5.4 5.9 4.5 575 4.5 5.4 5.9 4.5 4.5 5.4 5.9 4.5 208/230 028 Adjustment A,J NA 208/230 024 Belt Tension BELT TENSION (Ib) Unit Model Number Position VOLTAGE 208/230 020 21 -- Fig. 28 -- Evaporator-Fan Alignment and Adjustment 44 Condenser-Fan Adjustment (Fig. 29) I. 2. Shut off unit power supply. Remove condenser-fan assembly (grille, motor, cover, and fan) and loosen fan hub setscrews. 3. 4. Adjust fan height as shown in Fig. 29. Tighten setscrews and replace condenser-fan CHARGING CHART fALLCIRCUITS) ALL OUTDOOR FANS MUST BE OPERATING motor assembly. / 3,4!. Fig. 29 -- Condenser-Fan Adjustment LIOUIO Power Failure -- Dampers have a spnng return. In event of power failure, &Empel.s will return to fully closed position until power is restored. Do not manually ol)e_z_te damper PRESSURE [NTERIN6 TXV. [psigl Fig. 30 -- Cooling Charging 50HJ020 Units Chart -- lifO[OF. Refrigerant Charge -- Amount of refrigerant charge is listed on unit nameplate and in Table 1. Refer to C;urier GFAC II; Module 5; Charging, Recovery, Recycling, and Reclmnation section for ch;uging methods and procedures. Unit panels must be in place when unit is operating during charging procedure. NOTE: Do not use recycled contaminants. refrigerant as it may CHARGING IIIIIllllllllllllllllllllllllllllllllllll IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIllllllllllllllllllllllllllllllllllll IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII contain @_AGD CHARGE IF ABOVE THECURVE IllllllllIIlllllll IIIIIIIIIIIIIIIIII llllllIIIlllllllII IllllllllIIlllllll IlllllIIIIIlllllII Illllllllllllllll_ IIIIIIIIIIIIIIIA_?I IIIIIIIIIIIIA_IIIII NO CHARGE -- Use standard evacuating techniques. After evacuating system, weigh in the specified mnount of refrigerant (refer to Table 1). LOW CHARGE COOLING -- Using cooling charging chart (see Fig. 30-32), add or remove refrigenmt until conditions of the chart are met. An accurate pressure gage and temperaturesensing device is required. Charging is accomplished by ensuring the proper amount of liquid subcooling. Measure liquid line pressure at the liquid line service valve using pressure gage. Connect temperature sensing device to the liquid line ne;u the liquid line service valve and insulate it so that outdoor ambient temperature does not affect reading. TO USE THE COOLING CHARGING CHART -- Use the above temperature and pressure readings, and find the intersection point on the cooling charging chart. If intersection point on ch_ul is above line, add refrigerant. If intersection point on chmt is below line, cmefully recover some of the charge. Recheck suction pressme as charge is adjusted. NOTE: Indoor-air cfm must be within normal operating of unit. All outdoor fans must be operating. CHART FALL CSRCUST$) ALL OUTDOORFANS MUST BE OPERATZNG I I I I I I I I I l--F'l IIIIIIIIII]_H-IIIII llllllLg_i_lllllllll lll]_rllllllllIIll ],H_]IIIIIIIIIIIIIII llllIIIIIlllllIIII llllllllllllllllII llllllIIIlllllllII llllIIllllllllIIll I I I I I I REMOVE CHARGE IF BELOW THE CURVE {III N_{{IIIII{{ ,,,,,, ,,,,,, II.M"IIIIIIIIIIIIII .i/[llllililllllllil IIIIIIIIIIIIIIIIII IIIIII IIIlil IIIIII IIIIll Illill IIIIll 444+FH_°E_°_GE_H IIIlll IIIIIIIIllllllllll leo IIIIII l_e LIOUID 2oo PRESSURE ENTERING TXV, IIIIll aee [psigl Fig. 31 -- Cooling Charging 50HJ024 Units CHARGING HJ024 zso Chart -- CHART FALL CIRCUITS) ALLOUTDOOR tANSMUSt OPrRATING range The TXV (thermostatic expansion valve) is set to maintain between 10 and 15 degrees of superheat at the compressors. The valves are factory set and should not requile re-adjustment. Filter Drier -- Replace posed to atmosphere. Protective COMPRESSOR whenever refrigerant system is ex- Devices PROTECTION Overcurrent -- Each compressor has internal line break motor protection. Overtemperature -- Each compressor has an internal protector to protect it against excessively high dischmge gas temperatures. 2_o LIOUID Compressor Lockout -- If any of the safeties (high-pressure, low-pressure, freeze protection thermostat, compressor internal thermostat) trip, or if there is loss of power to the compressors, the CLO (compressor lockout) will lock the compressors off. To reset, manually move the thermostat setting. PRESSURE ENTERING TXV, [psig] Fig. 32 -- Cooling Charging 50HJ028 Units 45 Chart -- EVAPORATOR FANMOTORPROTECTION -- A manual reset,calibrated trip, magnetic circuitbreakerprotects against overcurrent. Donotbypass connections orincrease the sizeoffilebreaker tocorrect trouble. Determine file cause and correct it before resetting the breaker. CONDENSER-FAN MOTOR PROTECTION condenser-fan motor is internally protected overtemperature. -- FREEZE PROTECTION THERMOSTAT (FPT) -- An FPT is located on the top and bottom of the evaporator coil. It detects frost build-up and turns off the compressor, allowing the coil to clear Once the frost has melted, file compressor can be reenergized. Each against Relief Devices -- All units have relief devices to protect against &image from excessive pressures (i.e., fire). These devices protect the high and low side. Fuses m'e also located in the control box and feed power to the condenser fan motors. Always replace blown fuses with the correct size fuse as indicated on file unit fuse label. Control Circuit, 24-V- HIGH-PRESSURE AND LOW-PRESSURE SWITCHES -If either switch trips, or if the complessor overtempemture switch activates, that refrigerant circuit will be automatically locked out by the CLO. To reset, manually move file thermostat setting. Replacement Each control circuit is protected against overcurrent by a 3.2 amp circuit breakel: Breaker can be reset. If it trips, determine cause of trouble before resetting. See Fig. 33-35 for unit wiring. parts may request. Parts be obtained -- A complete list of replacement from any Carrier distributor upon LEGEND Fig. 33 -Fig. 34 -.A AHA AUX -= = .B -- .C -- C CAP CB CCH CLO COMP CR ECB FCS FlOP FPT FU GND HACR HERM HPS IA IAQ IFC IFCB IFM = = ------------------ Low Voltage Power Schematic Control and Fig. 35 -- Circuit A Adjustable Heat Anticipator Auxiliary Contact Circuit B Circuit C Compressor, Contactor Capacitor Circuit Breaker Crankcase Heater Compressor Lockout Compressor Compressor Relay EconoMi$er Control Board Fan Cycling Switch Factory-Installed Option Freeze Protection Thermostat Fuse Ground Heating, Air Conditioning and Refrigeration Hermetic High-Pressure Switch Indoor Air Indoor Air Quality Indoor-Fan Contactor Indoor Fan Circuit Breaker Indoor-Fan Motor LPS OA OFC OFM PEC PEM QT RAS RAT SAT TB TRAN ----- Common Fan Thermostat Power 1st Stage of Heating Component m m m m m m m m m m m m © Arrangement Low-Pressure Switch Outdoor Air Outdoor-Fan Contactor Outdoor-Fan Motor Power Exhaust Contactor Power Exhaust Motor Quadruple Terminal Return-Air Sensor Return-Air Thermistor Supply-Air Temperature Terminal Block Transformer Terminal (Unmarked) Terminal Block Splice Factory Wiring Field Wiring .... To Indicate FlOP or Accessory To Indicate Common Potential Only, Not To Represent Wiring THERMOSTAT C G R Wl Schematic, MARKINGS W2 X Y1 Y2 ----- 2nd Stage of Heating Alarm Output 1st Stage of Cooling 2nd Stage of Cooling NOTES: 1. Factory wiring is in accordance with the National Electrical Codes. Any field modifications or additions must be in compliance with all applicable codes. 2. Use 75 ° C minimum wire for field power supply. Use copper wires for all units. 3. All circuit breakers "Must Trip Amps" are equal to or less than 156% RLA (rated load amps). 4. Compressor and fan motors are thermally protected. Three-phase motors protected against primary single phase conditions. 5. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check these devices. 46 ......... RED \ LS _ ,C AI _?_AN I c >C _1 >IFC >CLO _1 >CLO_I >¢R1 x CLO BI is _I$CO_NECI[D_[N ACC? OA [NI_ALPY IS I_STALL[D Fig. 33 -- Low Voltage 47 Control Schematic \ \ o, W I:::::_:::_:o:o:o:o:o:o:o:o:o:o:o_:o:,:,_::;::::::o:o>:o:o:o:o:o:o:o:o_:::::: t E _m o E o I €_ _ °° LJ 49 TROUBLESHOOTING Unit Troubleshooting troubleshooting -- Refer to Tables 22 and 23 for details. Table 22 -- Cooling PROBLEM Compressor Service Analysis CAUSE and REMEDY Power failure. Condenser Fan Will Not Start. Call power company. Fuse blown or circuit breaker tripped. Defective thermostat, relay. Insufficient Replace fuse or reset circuit breaker. contactor, transformer, or control line voltage. Determine cause and correct. Incorrect or faulty wiring. Compressor Thermostat setting too high. Faulty wiring or loose connections Will Not Start but Condenser Runs. Fan Compressor load open. Replace component. Check wiring diagram and rewire correctly. in compressor circuit. motor burned out, seized, or internal over- Lower thermostat setting below room temperature. Check wiring and repair or replace. Determine cause. Replace compressor. Defective overload. Determine cause and replace. Compressor Determine cause for safety trip and reset lockout. locked out One leg of 3-phase power dead. Replace fuse or reset circuit breaker. Determine cause. Compressor Cycles (other than normally Refrigerant Recover refrigerant, to nameplate. satisfying Defective compressor. Replace and determine cause. Insufficient line voltage. Blocked condenser. Determine cause and correct. Determine cause and correct. Defective overload. Determine cause and replace. thermostat). overcharge or undercharge. Defective thermostat. Faulty condenser-fan Compressor Operates Continuously. Replace thermostat. motor. Replace. Restriction in refrigerant system. Locate restriction and remove. Dirty air filter. Unit undersized for load. Replace filter. Decrease load or increase unit size. Thermostat Reset thermostat. set too low. Low refrigerant charge. Excessive Head Pressure. Locate leak, repair, and recharge. Air in system. Recover refrigerant, Condenser coil dirty or restricted. Dirty air filter. Clean coil or remove restriction. Replace filter. Dirty condenser Clean coil. Refrigerant coil. overcharged. Excessive Too Low. Suction Pressure. Air in system. 1. Check TXV bulb mounting and secure tightly to suction line. 2. Replace TXV if stuck open or closed. Recover refrigerant, evacuate system, and recharge. Condenser air restricted or air short-cycling. Determine cause and correct. Low refrigerant charge. Restriction in liquid tube. Check for leaks, repair, and recharge. Remove restriction. High heat load. Check for source and eliminate. Faulty TXM 1. Check TXV bulb mounting and secure tightly to suction line. 2. Replace TXV if stuck open or closed. Refrigerant Suction Pressure Too Low. overcharged. Recover excess refrigerant. Dirty air filter. Replace filter. Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted. Faulty TXM Remove source of restriction. 1. Check TXV bulb mounting and secure tightly to suction line. 2. Replace TXV if stuck open or closed. Insufficient Increase air quantity. Check filter and replace if necessary. evaporator airflow. Temperature too low in conditioned Field-installed area. Reset thermostat. filter drier restricted. Replace. LEGEND TXV -- Thermostatic evacuate system, and recharge. Recover excess refrigerant. Faulty TXV. Head Pressure evacuate system, and recharge Expansion Valve 5O Table 23 -- Heating Service Analysis PROBLEM CAUSE No Heat. REMEDY Power failure. Call power company. Fuse blown or circuit breaker tripped. CB1, CB2, CB3. Replace fuse or reset circuit breaker. Thermostat Check thermostat. not calling for heating. No 24 vac at primary contactor. Check transformer No power (high voltage) to L2 of primary contactor. Bad electrical elements. Check safety switches, one shot backup, and auto limit. EconoMiSer IV Troubleshooting for EconoMi$er IV logic. -- See Table 24 3. power at TR and TRI, All LEDs fan contacts should be open, 2, Disconnect device 3, Jumper 4, Disconnect wires across T and TI. 5. Jumper TR to 1. 6. Jumper TR to N. 7. If connected, remove Connect 1.2 kilo-ohm terminals So and +. 8. Put 620-ohm 9. Set minimum potentiometers should be 4. 5,6 kilo-ohm sensor fiom terminals So find +. 4074EJM checkout resistor across 6. across terminals SR and +. position, DCV set point, fully CCW (counterclockwise). 10. Set DCV (clockwise). maximum 11. Set enthalpy potentiometer 12. Apply (24 vac) to termimds power DIFFERENTIAL resistor 5. resistor position and exhaust lully Make sine EconoMiSer IV check prepfuation differential procedure Place 620-ohm resistor 3. Place 1.2 kilo-ohm resistor Cool LED should be lit. 4. Remove 620-ohm Cool LED should 5. Return EconoMi$er after completing across resistor turn off. IV So and +. across SR find +. The settings So and and wiring +. The to Turn the DCV Maximum point. The actuator should open. Turn the DCV Maximum CCW. The actuator should Free Position potentiometer to middrive to between 20 and 80% Position potentiometer drive fully closed. to fully 5. Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 find 80% open. 6. Turn the Minimum Position Potentiometer actuator should drive fully open. 7. Remove the jumper fiom TR and N. The actuator c_kivefully closed. normal 51 has 3. Free troubleshooting. procedure Connect a 9-v battery to AQ (positive node) and AQI (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open. 4. across IV preparation 2. has been perfomled. 2. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on. 1. Make sure EconoMiSer been performed. TR and TRI. enthalpy: 1. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9 v. The actuator should c_kivefully closed. Return EconoMiSer IV settings and wiring to normal after completing troubleshooting. DCV MINIMUM AND MAXIMUM POSITION -- To check the DCV minimum and maximum position: CW to D. To to D (fully CW). The Free 7. potentiometer ENTHALPY-- The 1. Make sure EconoMiSer IV preparation procedure has been performed. 2. Ensure terminals AQ and AQI are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed. 3. Connect a 9-v battery to AQ (positive node) and AQI (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 find 95% open. at P and Pl, Place Set the enthalpy potentiometer Cool LED should turn off. has Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. DCV (Demand Controlled Ventilation) AND POWER EXHAUST -- To check DCV and Power Exhaust: P to PI. at T and TI, -- To check single enthalpy: 4. of all poten- Disconnect off, Exhaust ENTHALPY 1. Make sure EconoMi$er IV preparation procedure been performed. 2. Set the enthfdpy potentiometer to A (fully CCW). Free Cool LED should be lit. NOTE: This procedure lequires a 9-v battery. 1.2 kilo-ohln resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMiSer IV. 1, With power off, remove high voltage wires and check resistance of heater. Replace if open. SINGLE ECONOMISER IV PREPARATION -- This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by pellorming the following procedure. A fiJnctional view of the EconoMi$er IV is shown in Fig. 36. Typicfd settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available fiom Canier to help with EconoMiSer IV training and troubleshooting. tiometers before Bestarting IMPORTANT: sure totroubleshooting, record the positions and circuit breaker. fully CW. The should 8. Return EconoMiSer IV settings andwiringto normal al_er completing troubleshooting. SUPPLY-AIR INPUT-- Tocheck supply-air input: 1. MakesureEconoMiSer IV preparation procedure has beenperformed. 2. SettheEnthalpy potentiometer toA.TheFreeCoolLED turnson.Theactuator should &iveto between 20and 80%open. 3. Remove the5.6kilo-ohm resistor andjumperT toTI. Theactuator should drivefullyopen. 4. Remove thejumper across T andTI.Theactuator should drivefullyclosed. 5. Return EconoMiSer IV settings andwiringto normal al_er completing troubleshooting. ECONOM[$ER IV TROUBLESHOOTING COMPLETION-- Thisprocedure isused toreturntheEconoMiSer IV tooperation. Notroubleshooting ortesting isdonebyperformingthefollowing procedure. 1. Disconnect power atTRandTRI. 2. Setenthalpy potentiometer toprevious setting. 3. SetDCVmaximum position potentiometer toprevious setting. 4. Setminimumposition,DCVsetpoint,andexhaust potentiometers toprevious settings. 5. Remove 620-ohm resistor fromterminals SRand+. 6. Remove 1.2kilo-ohm checkout resistor fromterminals Soand+.If used, reconnect sensor fromterminals Soand +. 7. Remove jumperfromTRtoN. 8. Remove jumperfromTRto1. 9. Remove 5.6kilo-ohm resistor fromTandTI.Reconnect wiresatTandTI. 10. Remove jumperfromPtoPI.Reconnect device atPand PI. 11.Applypower(24vac)totermimds TRandTRI. Table 24 -- EconoMi$er IV Input/Output Logic INPUTS Demand Control Ventilation (DCV) Below set (DCV LED Off) Above set (DCV LED On) OUTPUTS Enthalpy* Outdoor N Terminalt Compressor Return Y1 Y2 Stage 1 High (Free Cooling LED Off) Low On On On Off On On On Off Off Off Off Off Low (Free Cooling LED On) High On On On Off On Off Off Off High (Free Cooling LED Off) Low On On On Off Off Low (Free Cooling LED On) High On On Off *For single enthalpy control, the module compares enthalpy to the ABCD set point. 1-Power at N terminal determines Occupied/Unoccupied 24 vac (Occupied), no power (Unoccupied). **Modulation is based on the supply-air sensor signal. 1-1-Modulation is based on the DCV signal. Stage 2 Occupied Unoccupied Dam )er Minimum position Closed Off Off Modulating** (between min. position and full-open) Modulating** (between closed and full-open) Off Off Minimum position Closed On On On Off Modulating1-1- (between min. position and DCV maximum) Off Off Off Modulating1-1- (between closed and DCV maximum) On Off On Off Off Off Modulating*** Modulating1-1-1- Off Off Off outdoor ***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal). I-I-I-Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air signal). setting: 52 Fig. 36 -- EconoMiSer IV Functional View 53 SERVICE Packaged Service discussed A large Training in this manual, selection materials. Classroom are an excellent way to increase • Maintenance • Installation • Operating of product, Overview theory, video and/or Training and skills slides, which CALL ] Packaged includes FOR Service programs plus companion increased confidence that really pays dividends and schedules are in our catalog. [ your knowledge of the equipment including: • Unit Familiarization All include Service programs TRAINING "hands-on" are available, Training using popular video-based formats and book. experience in faster troubleshooting FREE Sequence CATALOG [ with the products and fewer in our labs can mean callbacks. Course descriptions 1-800-644-5544 ] Classroom Service Training Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications Catalog No. 04-53500013-01 Printed in U.S.A. or designs without notice and without incurring obligations. Form 50HJ-30SI Pg 54 10-05 Replaces: 50HJ-26SI START-UP MODEL CHECKLIST NO.: SERIAL DATE: NO.: TECHNICIAN: PRE-START-UP: [] VERIFY THAT ALL PACKING [] VERIFY INSTALLATION MATERIALS [] VERIFY THAT CONDENSATE [] VERIFY THAT ALL ELECTRICAL [] CHECK THAT RETURN-AIR [] CHECK THAT OUTDOOR [] VERIFY THAT UNIT IS LEVEL [] CHECK FAN WHEEL IS TIGHT [] VERIFY THAT FAN SHEAVES [] VERIFY THAT SCROLL [] VERIFY INSTALLATION [] VERIFY THAT CRANKCASE OF OUTDOOR HAVE BEEN REMOVED CONNECTION IS INSTALLED CONNECTIONS FILTERS FROM UNIT AIR HOOD ARE CLEAN AIR INLET SCREENS AND PROPELLER PER INSTRUCTIONS AND TERMINALS ARE TIGHT AND IN PLACE ARE IN PLACE FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW LU ARE ALIGNED COMPRESSORS AND BELTS ARE PROPERLY ARE ROTATING TENSIONED IN THE CORRECT 2: C_ DIRECTION LU I-- OF THERMOSTAT/SPACE SENSOR rm HEATERS HAVE BEEN ENERGIZED FOR AT LEAST 24 HOURS Z o, II. START-UP < D o ELECTRICAL SUPPLY VOLTAGE COMPRESSOR L 1-L2 AMPS L2-L3 L3-L 1 COMPRESSOR AI LI L2 L3 COMPRESSOR B1 LI L2 L3 CI (020, 024 ONLY) LI L2 L3 LI L2 L3 -- COMPRESSOR SUPPLY FAN AMPS ELECTRIC HEAT AMPS (IF EQUIPPED) TEMPERATURES OUTDOOR-AIR RETURN-AIR TEMPERATURE F DB (Dry Bulb) FDB TEMPERATURE COOLING SUPPLY AIR ELECTRIC HEAT SUPPLY AIR (IF EQUIPPED) U3 F WB (Wet Bulb) F F rm U3 PRESSURES REFRIGERANT SUCTION z Z o CIRCUIT A CIRCUIT B PSIG PSIG CIRCUIT C CIRCUIT A CIRCUIT B PSIG (020, 024 ONLY) PSIG PSIG CIRCUIT C PSIG (020, 024 ONLY) < o REFRIGERANT DISCHARGE [] VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGE 45. GENERAL [] [] ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS VERIFY INSTALLATION OF ALL OH'IONS AND ACCESSORIES Copyright 2005 Carrier Corporation Manufacturerreserves the rightto discontinue,or changeat any time, specificationsor designswithout noticeand without incurringobligations. Book 111 Catalog No. 04-53500013-01 Printed in U,S.A. Form 50HJ-30SI Pg CL-1 10-05 Replaces: 50HJ-26SI Tab F
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 56 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 16:14:58 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools