CARRIER Air Conditioner/heat Pump(outside Unit) Manual L0604185
User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF
.
Page Count: 20
| Download | |
| Open PDF In Browser | View PDF |
to the Expertg[
£n
Installation
Instructions
TABLE
OF CONTENTS
PAGE
SAFETY
CONSIDERATIONS
INSTALLATION
.......................
RECOMMENDATIONS
INSTALLATION
Check
Equipment
Step 2 -
Install on Solid Pad ......................
3
Step 3 -
Clearance
Requirements
3
Step 4 -
Operating
Ambient
Step 5 -
Elevate
Step 6 -
Install TXV
Step 7 -
Install Liquid
Step 8 -
Make Piping
Step 9 -
Make Electrical
Unit
instruction
manual
starting
the
MAJOR
........................
Unless
otherwise
instructions
Information
noted,
information
in
these
installation
pertain to both 25HNA6
and 25HNA9 series units.
that is unique to the 25HNA6 series will be identified
as such; likewise information
will also be identified.
that is unique to the 25HNA9
series
3 - 4
4
Line Solenoid
Connections
Valve (LSV)
CARE
PURON
.....
..............
Connections
Crankcase
Charge
COMPONENTS
CHECKS
3
............
Heater
7 - 8
.............
8
......................
Selections
8
..................
8
9
of
.....................
9 - 12
12 - 13
..........................
........................
14
14 - 17
.................................
AND MAINTENANCE
REFRIGERANT
19
......................
QUICK
5
5 - 7
..............................
TROUBLESHOOTING
FINAL
3
..................
Step 14 - System Functions and Sequence
Operation
.................................
Step 15 - Check
before
...............
......................
Accessories
Step 13 - Start-Up
NOTE:
Read the entire
installation.
& Jobsite
............................
Step 12 - Make Airflow
/ 25HNA9
2
3 - 13
Step 1 -
Step 11 - Install
Fig. 1 - 25HNA6
.............
..............................
Step 10 - Compressor
A05240
2
REFERENCE
19
GUIDE
19
SAFETY
CONSIDERATIONS
Improperinstallation,adjustment,
alteration,service,
maintenance,
orusecancause
explosion,
fire.electrical
shock,
or
otherconditions
whichmaycause
death,
personal
injury,or
property
damage.
Consult
aqualified
installer,
service
agency,
or
yourdistributor
or branch
forinformation
or assistance.
The
qualified
installer
oragency
mustusefactory-authorized
kitsor
accessories
when
modifying
thisproduct.
Refer
totheindividual
instructions
packaged
withthekitsoraccessories
when
installing.
Follow
allsafety
codes.
Wear
safety
glasses,
protective
clothing,
andworkgloves.
Usequenching
clothforbrazing
operations.
Havefire extinguisher
available.
Readtheseinstructions
thoroughly
andfollowallwarnings
or cautions
included
in
literature
andattached
totheunit.Consult
localbuilding
codes
andNational
Electrical
Code
(NEC)
forspecial
requirements.
Recognize
safety
information.
Thisisthesafety-alert
symbol/_
When
youseethissymbol
ontheunitandin instructions
or
manuals,
bealerttothepotential
forpersonal
injury.Understand
these
signalwords;DANGER.
WARNING,
andCAUTION.
These
wordsareused
withthesafety-alert
symbol.
DANGER
identifies
themostserious
hazards
whichwillresultin severe
personal
injuryor death.
WARNING
signifies
hazards
which
couldresultinpersonal
injuryordeath.
CAUTION
is used
to
identify
unsafe
practices
whichmayresultin minorpersonal
injuryor product
andproperty
damage.
NOTEis usedto
highlight
suggestions
whichwillresult
inenhanced
installation,
reliability,
oroperation.
ELECTRICAL
SHOCK
HAZARD
Failure
tofollowthiswarning
couldresult
in personal
injuryordeath.
Before
installing,
modifying,
orservicing
system,
main
electrical
disconnect
switch
must
beintheOFFposition.
There
maybemore
than1disconnect
switch.
Lockout
andtagswitch
withasuitable
warning
label.
UNITOPERATION
ANDSAFETY
HAZARD
Failure
tofollowthiswarning
could
result
inpersonal
injury
orequipment
damage.
Puron
_ refrigerant
systems
operate
athigher
pressures
than
standard
R-22systems.
DonotuseR-22service
equipment
orcomponents
onPuron
_refrigerant
equipment.
INSTALLATION
RECOMMENDATIONS
NOTE:Insome
cases
noise
inthelivingarea
hasbeen
traced
to
gaspulsations
fromimproper
installation
ofequipment.
1.Locate
unitaway
fromwindows,
patios,
decks,
etc.where
unitoperation
sound
maydisturb
customer.
2.Ensurethatvaporandliquidtubediameters
are
appropriate
forunitcapacity.
3.Runrefrigerant
tubes
asdirectly
aspossible
byavoiding
unnecessary
turns
andbends.
4.Leave
some
slackbetween
structure
andunittoabsorb
vibration.
5.Whenpassing
refrigerant
tubesthrough
thewall,seal
opening
withRTVorotherpliable
silicon-based
caulk.
(See
Fig.2.)
6.Avoiddirect
tubingcontact
withwater
pipes,
ductwork,
floorjoists,
wallstuds,
floors,
andwalls.
7.Donotsuspend
refrigerant
tubingfromjoistsandstuds
witha rigidwireor strap
whichcomes
indirect
contact
withtubing.(See
Fig.2.)
8.Ensure
thattubinginsulation
ispliableandcompletely
surrounds
vapor
tube.
9.When
necessary,
usehanger
straps
whichare1 in.wide
andconform
toshape
oftubing
insulation.
(See
Fig.2.)
10.Isolate
hanger
straps
frominsulation
by usingmetal
sleeves
benttoconforna
toshape
ofinsulation.
When
outdoor
unitisconnected
tofactory-approved
indoor
unit.
outdoor
unitcontains
system
refrigerant
charge
foroperation
with
ARIrated
indoor
unitwhen
connected
by15ft.offield-supplied
or factory
accessory
tubing.
Forproper
unitoperation,
check
refrigerant
charge
usingcharging
information
located
oncontrol
boxcover
and/or
intheCheck
Charge
section
ofthisinstruction.
IMPORTANT:
Maximum
liquid-line
sizeis3/8-in.
ODforall
residential
applications
including
longlineapplications.
IMPORTANT:
Always
installthefactory-supplied
liquid-line
filterdrier.
Obtain
replacement
filterdriers
fromyourdistributor
orbranch.
INSTALLATION
NOTE: Avoid contact between tubing and structure
INDOOR WALL LIQUID TUBE
INSULATION
THROUGH THE WALL
HANGER STRAP_k
_y,,,,_J
(AROUND VAPOR
X. k_
OIST
INSULATION
/_
VIEW
_
TOP
/
UNIT BASE PAN
DIMENSIONS
h
FROM
VAPOR TUBE
_
TIEDOWN
KNOCKOUT
LOCATIONS
A
B
C
m
d
t,
1"MIN. ------I
I--,--
36
1/2 x 40
11 5/8
6 13/16
28 3/4
29
1/2 X 33
10 1/16
5 5/8
23 3/4
LIQUID TUBE
SUSPENSION
A05242
Fig.
A94026
Fig. 2 -
Connecting
Tube
and
obtain required
R-22 retrofit.
STEP
unit
1 --Check
Unpack
Heat
changes
Using
Puron(R)
for specific
Equipment
and Job
Refrigerant
applications
to
and for
Site
STEP 3 --Clearance
When installing,
wiring, refrigerant
carton
taking
care not to damage
Equipment
company
prior to installation
if shipment
is damaged or incomplete.
Locate unit rating plate on unit corner
panel. It contains
information
needed to properly
install unit.
Check
rating plate to be sure unit matches
STEP
2 --Install
on a Solid,
job specifications.
Level Mounting
Pad
in./ft.)
per
Requirements
allow sufficient
space for airflow clearance.
piping, and service. Allow 30-in. clearance to
so water,
snow.
or ice from
roof
or eaves
locate
at least
cannot
fall
on unit.
On rooftop
surface.
applications,
STEP 4 --Operating
File claim with shipping
_+2° (_+3/8
service end of unit and 48 in. above unit. For proper airflow, a
6-in. clearance on 1 skle of unit and 12 in. on all remaining sides
must be maintained.
Maintain a distance of 24 in. between units.
directly
Remove
Locations
NOTE:
Unit nmst be level to within
compressor
manufacturer
specifications.
Position
Unit
Move to final location.
unit.
Inspect
Pumps
Knockout
Installation
Specifications
for this unit in residential new construction
market
require the outdoor
unit, indoor unit, refrigerant
tubing sets,
metering device, and filter drier listed in presale literature. There
can be no deviation.
Consult
the Service
Manual
- Air
Conditioners
3 - Tiedown
unit
6 in. above
roof
Ambient
The minimum
outdoor
operating
ambient in cooling
mode is
55°F without low ambient cooling
enabled and the maximum
outdoor
operating
Infinity "
25HNA9),
ambient
in cooling
mode
is 125°F.
communicating
systems only (for both 25HNA6
low ambient cooling is available to 0°F.
On
and
If conditions
or local codes require the unit be attached to pad. tie
down bolts should be used and fastened
through
knockouts
provided in unit base pan. Refer to unit mounting
pattern in Fig.
The maximum
outdoor operating
ambient in heating mode is
66°F on all models.
Continuous
operation in the heating mode is
3 to determine
base pan size and knockout
STEP 5 --Elevate
For hurricane
tie downs,
Certification
(Professional
contact
hole location.
distributor
Engineer),
for details
wind baffles.
System
Air
Refrigerant
units
exposed
Consult the
Conditioners
to winds
above
to building.
5 mph may require
Service Manual
- Residential
Split
and Heat Pumps
Using
Puron(R)
for wind baffle construction.
Unit
if required.
unit and minimize transmission
of vibration
local codes governing
rooftop applications.
Roof mounted
to -30°F.
and PE
On rooftop applications,
mount on level platform or frame. Place
unit above a load-bearing
wall and isolate unit and tubing set
from structure.
Arrange
supporting
members
to adequately
support
Consult
approved
UNIT
OPERATION
HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not allow water
Elevate
unit
per local
clearance
above
drainage of unit.
and/or
climate
estimated
ice to build up in base pan.
and code requirements
snowfall
level
and ensure
to provide
adequate
7. Connect
equalizer
on vapor
8. Attach
UNITOPERATION
HAZARD
Failure
tofollowthiscaution
mayresult
inequipment
damage
orimproper
operation.
Locate
theunitin suchawaythatit is stable
inall
circumstances
including
adverse
weather
conditions.
STEP6--InstallTXV
NOTE:Applies
tonon-TXV
indoor
unitsonly.If installing
a
ratedandapproved
indoorcoilwithouta factoryinstalled
Puron(_
TXV,remove
andreplace
thefixedorifice
orR-22TXV
expansion
device
withahardshutoff
Puron
TXV.
Thethermostatic
expansion
valveis specifically
designed
to
operate
withPuron(a)
refrigerant.
DonotuseanR-22TXV.An
existing
R-22TXVmustbereplaced
witha factory-approved
TXVspecifically
designed
for Puronrefrigerant.
Referto
Product
Data
Digest
fortheappropriate
TXVkitnumber.
using
tube of TXV to 1/4-in.
TXV
bulb
clamps
9. Proceed
to horizontal
provided.
insulation
tape.
sensing bulb.
_.10
equalizer
fitting
line adapter.
See
section
Insulate
Fig.
with remainder
bulb
4 for
of suction
line
with field-supplied
correct
positioning
of
of unit installation.
O'CLOCK
SENSING
2 O'CLOCK]
L_'SUCTION
TUBE
8 O'CLOCK
4 O'CLOCK
7/8 IN. OD & SMALLER
LARGER
THAN 7/8 IN. OD
A81032
Fig.
UNITOPERATION
HAZARD
Failure
tofollowthiscaution
mayresult
inequipment
damage
orimproper
operation.
Allindoor
coilunitsmust
beinstalled
withahard
shut
offPuron®
TXVmetering
device.
Replacing
indoor
The
TXV
coil as possible
mounting
the
inlet
should
be mounted
and in a vertical,
tube
upright
vertically
susceptible
to malfunction
down. A factory-approved
down.
as close to the
position.
Valve
Avoid
is
more
due to debris if inlet tube is facing
filter drier must be installed in the
1. Pump system
2. Remove
cabinet.
Installing
TXV in Place
1. Pump
system down
to 2 psig and recover
refrigerant.
2. Remove hex nut from piston body. Use backup
fan coils.
3. Remove
and
discard
factory-installed
piston.
Be
NOTE:
hex nut. Finger
If the piston
not function
tighten
is not removed
sure
the body,
TXV
will
properly.
4. Remove
using
a backup
R-22
5. Using wire cutters,
tube inside cabinet.
6. Remove
damage
bulb from vapor
7. Braze equalizer
DAMAGE
damage
adapter
to suction
tube off flush
closed.
damage
with vapor
Use protective
barrier
as
to drain pan.
tubing.
or valve,
TXV support
equalizer
hole)
to attach TXV to distributor.
clamp (removed
in item 3).
See Fig. 4 for correct
tube through
in fitting
panel
inlet of TXV. marked
excessive
suction
and
"IN"
heat which could damage
positioning
connection
install
in same
supplied
fitting
to liquid
of
opening
panel
in
line. Avoid
valve.
13. Install vapor elbow with equalizer adapter to vapor line of
line set and vapor connection
to indoor coil. Adapter has
swivel
outlet.
Use backup wrench to avoid damage to tubing or valve.
Sweat inlet of TXV. marked "IN" to liquid line. Avoid
excessive heat which could damage valve.
with equalizer
flare
the equalizer tube of Puron TXV through
opening in fitting panel prior to replacing
to tubing
a 1/4-in.
elbow
on
10. Attach TXV bulb to vapor tube inside cabinet,
location as original was when removed,
using
12. Sweat
TXV with wet cloth or
5. Install TXV on indoor
coil liquid line. Sweat
adapter to inlet of indoor coil and attach to TXV
wrench
8. Install TXV with 3/8-in. copper tubing through small hole
in service panel. Use wrench and backup wrench, to avoid
(large
place.
HAZARD
Use a brazing shield and wrap
use heat sink material.
nut driver.
tube inside cabinet.
stub-tube
to prevent
a 5/16-in.
front of
to tubing.
cut equalizer
copper bulb clamps.
sensing bulb.
Failure to follow this caution may result in equipment
damage or improper operation.
6. Install vapor
TXV
to prevent
refrigerant.
panel from
using
11. Route
EQUIPMENT
and fitting
clamp
9. Reinstall
nut plus 1/2 turn.
from
panel
on
Teflon seal is in place.
4. Reinstall
Coil
3. Remove TXV support
Save the clamp.
fitting panel around
wrench
Bulb
down to 2 psig and recover
IMPORTANT:
Route
suction line connection
of Piston
of Sensing
Indoor
coil access
necessary
liquid line.
Position
TXV on R-22
connections
IMPORTANT:
4 -
tube
of line set and suction connection
to indoor coil. Adapter
has a 1/4-in. male connector for attaching equalizer tube.
male connector
for attaching
equalizer
tube.
14. Connect equalizer tube of TXV to 1/4-in. equalizer fitting
on vapor line adapter.
Use backup
wrench to prevent
damage
15. Proceed
to equalizer
fitting.
with remainder
of unit installation.
STEP
7 --In
Solenoid
For
Long-Line
Applications,
Install Liquid-Line
Valve (LSV)
refrigerant
piping
arrangements
with
equivalent
lengths
greater than 80 ft. and/or when elevation
difference
between
indoor
and outdoor
unit is greater
than _+20 ft.. follow all
requirements
of the Long-Line
Guideline--Air
Conditioners
and
Heat Pumps
Using
Long-Line
Guideline.
UNIT
Failure
damage
Puron®
refrigerant.
If required
by
install LSV kit, part no. KHALS0401LLS,
toward
included
with accessory
IMPORTANT:
STEP
outdoor
unit. Follow
the Installation
to follow this caution
or improper operation.
Piping
Instructions
outdoor
AND UNIT
DAMAGE
DAMAGE
this warning
could
result in personal
HAZARD
Failure
damage
to follow this caution
or improper operation.
Observe
the following:
• Use a brazing
HAZARD
to follow
this caution
or improper operation.
with wet cloth or use a heat sink
80 ft., substantial
capacity and performance
Following
the recommendations
in the
may
result
sealed during
in equipment
Outdoor
Unit Connected
Outdoor
unit
Check
Connections
Information
and Recommended
is Specific
Manual-Residential
Split-System
Pumps Using Puron®
Refrigerant
contains
to Factolw-Approved
correct
system
diameters.
Indoor
refrigerant
Air
will
Unit:
charge
to 25HNA6
refrigerant
Liquid
charge
and Vapor
and 25HNA9
for maximum
Tube
efficiency.
Diameters
(In.)
Models
R&TED
LIQUID
VAPOR
(up to 80 ft. T.E.L)
UNIT SIZE
Connection
Diameter
Notes:
t.
,.,
2.
3.
for
operation
with factory approved
ARI rated indoor unit with
highest sales volume
when connected by 15 ft. of field-supplied
or factory-accessory
tubing, and factory supplied
filter drier.
installation.
Table 1--Refrigerant
losses can
Application
reduce these losses. Refer to Table 1 for field tubing
Refer to Table 2 for accessory requirements.
Do not leave system open to atmosphere
any longer than
minimum
required for installation.
POE oil in compressor
is
extremely
susceptible
to moisture
absorption.
Always keep
ends of tubing
n
in equipment
Outdoor
units may be connected
to indoor
section
using
accessory
tubing
package
or field-supplied
refrigerant
grade
tubing of correct size and condition.
For tubing requirements
Guideline
and Service
Conditioners
and Heat
Failure
damage
result
material.
beyond
occur.
DAMAGE
may
shield.
• Wrap service valves
Relieve
pressure
and recover all refrigerant
before
system repair or final unit disposal. Use all service
ports and open all flow-control
devices,
including
solenoid valves.
UNIT
in equipnmnt
Connections
INJURY
Failure to follow
injury or death.
result
unit.
UNIT
PERSONAL
HAZARD
may
kit.
Flow arrow must point toward
8 --Make
HAZARD
If ANY refrigerant tubing is buried, provide a 6 in. vertical
rise at service valve. Refrigerant tubing lengths up to 36 in.
may be buried without further special consideration.
Do
not bury lines longer than 36 in.
specifically
designed
for Puron®
refrigerant
heat pumps. LSV
should be installed within 2 ft. of outdoor unit with flow arrow
pointing
DAMAGE
Tube
Diameter
Connection
Diameter
Tube
Diameter
25HNA624
3/8
3/8
5/8
5/8
25HNA636
3/8
3/8
3/4
3/4
25HNA648
3/8
3/8
7/8
7/8
25HNA660
3/8
3/8
7/8
1 1/8
25HNA924
3/8
3/8
3/4
3/4
25HNA936
3/8
3/8
3/4
7/8
25HNA948
3/8
3/8
7/8
7/8
25HNA960
3/8
3/8
7/8
1 1/8
Tube diameters are for total equivalent lengths (TE.L.) up to 80 ft. Consult the Long Line Guideline
refrigerant.
Do not apply capillary tube or the fixed orifice indoor coils to these units.
T.E.L. - Total Equivalent Length
Air Conditioners
and Heat Pumps using Puron@
REQUIRED
Accessory
Crankcase
Table 2--Accessory
Usage
FOR LOW-AMBI-
REQUIRED
ENT APPLICATIONS
(Below 55 °F)
Standard
Heater
FOR LONG LINE
REQUIRED
APPLICATIONS*
(Over 80 ft.)
Standard
FOR SEA
COAST APPLICATIONS
(Within 2 miles)
Standard
Standard with Infinity Control
Evaporator
Freeze Protection
Winter
(Low Ambient not allowed with noncommunicating thermostat)
No
No
No
No
Standard on 25HNA6 models.
Standard on 25HNA6 modets.
Not required on 25HNA9 models
Not required on 25HNA9 modets
Standard on 25HNA6
modets.
since compressor
since compressor
Standard with infinity Control
(Low Ambient not allowed with non-
Start Control
communicating thermostat)
Compressor
Start Assist Capacitor
and Relays
n
Low-Ambient
Control
always starts
Not required on 25HNA9
models since compressor
always starts
unloaded,
unloaded,
Standard with Infinity Control (Low
ambient not allowed with non-commu-
No
always starts unloaded.
No
nicating thermostat)
Support
Feet
Liquid Line Solenoid
Recommended
Valve
No
No
Ball Bearing Fan Motor
Puron Balance Port Hard Shut-Off
TXV
Recommended
Yes
Standard
No
Standard
Yes1-
Standard
Yes1-
Yest
For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (Total Equivalent Length),
ers and Heat Pumps using Puron(_) refrigerant.
tRequired on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.
refer to the Long Line Guideline
Air Condition-
$ Information is specific to 25HNA6 and 25HNA9 models.
Install Liquid-Line
Filter
Drier Indoor
Refrigerant
Refer to Fig. 5 and install filter drier as follows:
1. Braze 5-in.
Connect
liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. BrazefilterdriertoabaveS-in.
point towards indoor coil.
4. Connect
liquid tube.Flowarrowmust
and braze liquid refrigerant
tube to the filter drier.
Tubing
vapor
connection
tube
valves
(see Table 1).
Install
Adapter
Outdoor
to fitting
on
outdoor
unit
retainer
2. Check outdoor piston
unit rating plate.
holding
outdoor
size with matching
3. Locate plastic bag taped to unit containing
Teflon_R3
washer
open end of liquid service
DAMAGE
HAZARD
Failure to follow this caution
or improper operation.
Installation
of filter
drier
may result in equipment
in liquid
damage
5. Remove adapter
to liquid service
Sweat
piston
in liquid
number
listed on
adapter
tube.
from bag and install
on
wdve.
tube from bag and connect threaded nut
valve. Tighten nut finger tight and then
with wrench tighten an additional
DO NOT OVERTIGHTEN!
line is required.
service
Tube
1. Remove plastic
service valve.
4. 4. Remove
UNIT
vapor
1/2 turn (15 ft-lb).
Connections
UNIT
DAMAGE
HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Service
material
valves
must be wrapped
such as a wet cloth.
in
a heat-sink
Use refrigerant
grade tubing. Service valves are closed from
factory and ready for brazing. After wrapping
service valve with
A05227
Fig. 5 - Liquid
Line
Filter
Drier
a wet cloth, braze sweat connections
using industry
accepted
methods
and
materials.
Consult
local
code
requirements.
Refrigerant tubing and indoor coil are now ready for leak testing.
This check should
include
all field and factory joints.
Refrigerant
Tubing
and Indoor
Coil
I EVACUATE
I
m
Evacuate
[BREAK VACUUM WITH DRY NITROGEN
UNIT
DAMAGE
HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system
compressor
as a vacuum
[EVACUATE I
pump.
[BREAK VACUUM WITH DRY NITROGEN
Refrigerant
tubes and indoor coil should be evacuated
using the
recommended
deep vacuum
method
of 500
microns.
The
alternate
outlined
nitrogen.
[EVACUATE]
triple evacuation
method may be used if the procedure
below is followed. Always
break a vacuum with dry
CHECK
Deep Vacuum
The deep vacuum
method
requires
a vacuum
pump
capable
TIGHT,
FOR
(IF
Method
IT HOLDS
DRY
SYSTEM
VACUUM)
DEEP
of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately
measuring
this vacuum
depth. The deep vacuum
I CHARGE SYSTEM
I
method
Fig.
Method
is the most positive
way of assuring
a system
A95425
is free of air
and liquid water. (See Fig. 6)
Final
Tubing
5000
IMPORTANT:
4500
indoor
7 - Triple
Check
Check
and outdoor
close attention
LEAKIN
SYSTEM
_3500
against
to feeder
tubes are secure
g3000
to be certain
factory
unit has not shifted during
tubes are not rubbing
4000
Evacuation
tubing
on
shipment.
both
Ensure
each other or any sheet metal. Pay
tubes,
making
sure wire ties on feeder
and tight.
STEP 9 --Make
Electrical
Connections
_2500
2000
VACUUM TIGH'T
TOO WET
15001000
ELECTRICAL
TIGHT
DRY SYSTEM
500
Failure
injury
1
2
3
4
MINUTES
5
6
SHOCK
to follow
HAZARD
this warning
could
result
in personal
or death.
Do not supply power
box cover removed.
to unit with
compressor
terminal
A95424
Fig, 6 Triple
Evacuation
Deep Vacuum
Graph
Be sure field wiring
and electrical codes,
Method
The triple evacuation
method should only be used when vacuum
pump is only capable of pumping
down to 28 in. of mercury
vacuum and system does not contain
Fig. 7 and proceed as follows:
1. Pump
system
to continue
2. Close
down
operating
service
valves
any liquid
water. Refer
to
for an additional
and allow pump
and shut off vacuum
to system
as indicated
then be free of any contaminants
in Fig. 7. System
and water vapor.
Operation
and could
not install unit
permissible
NOTE:
unit.
pump.
of unit on improper
affect
unit reliability.
in system
line voltage
constitutes
See unit rating
where
voltage
wire only
between
plate.
may fluctuate
above
Do
or
limits.
Use copper
disconnect
switch
and
and
NOTE:
4. Close service valve and allow system to stand for 1 hr.
During this time, dry nitrogen
will be able to diffuse
throughout
the system absorbing moisture.
this procedure
NOTE:
below
15 minutes.
3. Connect a nitrogen cylinder and regulator
open until system pressure is 2 psig.
5. Repeat
on unit rating plate. Contact local power company for correction
of improper
voltage.
See unit rating plate for recommended
circuit protection device.
abuse
to 28 in. of mercury
complies with local and national fire, safety,
and voltage to system is within limits shown
will
NEC
Install
to handle
sight from
of NEC.
Route
branch
unit
and readily
Ground
circuit
starting
disconnect
current.
accessible
and Power
of adequate
Locate
size per
disconnect
within
from unit, per Section
440-14
Wires
Remove access panel to gain access to unit wiring. Extend wires
from disconnect
through power wiring hole provided
and into
unit control box.
STEP
10 --Compressor
Furnish
ELECTRICAL
SHOCK
HAZARD
Failure
to followthiswarning
couldresultin personal
injuryordeath.
Theunitcabinet
musthave
anuninterrupted
orunbroken
ground
tominimize
personal
injuryif anelectrical
fault
should
occur.
Theground
mayconsist
ofelectrical
wireor
metalconduit
wheninstalled
in accordance
withexisting
electrical
codes.
Connect
Ground
Connect
and Power
ground
safety. Connect
Wiles
wire to ground
power wiring
to contactor
in control
as shown
box for
in Fig. 8.
DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES
to crankcase
starting unit. To furnish
OFF and close electrical
NOTE:
On 25HNA6
minimum
a minimum
of 24 hr before
starting
of crankcase
the compressor
to
without
a
heat prior to initial start-up
chattering
noise
and possible
damage
to the compressor.
STEP
11 --Install
Refer to
accessories
Accessories
the individual
when installing.
12 --Make
Only
stats
Using
Airflow
instructions
Airflow
Selection
packaged
Selections
Non-Communicating
The 58CVA/58MVB
low-stage
blower
CONTACTOR
heater
models,
of 12 hours
Heater
power to heater only, set thermostat
disconnect to outdoor unit.
may result in a compressor
STEP
connection
power
Crankcase
for 25HNA6
(Non-Infinity)
for 58CVA/58MVB
variable
operation
with
kits
or
Series
Thermo-
Furnaces
speed furnaces
to match
the
provide high-and
capacities
of the
compressor
at high and low stages. To select the recommended
airflow
and for adjustments
to the manual
switches
labeled
SWl-5.
AC, and CF on the control board refer to the furnace
FIELD POWER
WIRING
Installation.
Start-UR
and
Operating
Instructions.
The
58CVA/58MVB
utilizes a control center that allows the installing
FIELD GROUND
technician
determines
WIRING
GROUND
LUG
A91056
Fig. 8 Connect
Control
Line Power
to select
the proper
the airflow during high
Airflow for high- and low-stage
CFM per ton or 400 CFM per
SWl-5.
airflows.
The HP switch
stage compressor
operation.
can be calculated at either 350
ton, based on the positions
of
Connections
Wiring
Route low voltage control wires through
and connect leads to control board.
control
wiring
grommet
When
using
communicating
(Infinity)
control,
dipswitch
adjustments
are not necessary
on furnaces.
Airflows
are
determined
by Infinity Control setup.
Airflow
Selection
for FK4
or FV4 Fan Coils
for 25HNA6
For 25HNA9
models,
connect to Infinity connections
ABCD
only. Standard non-communicating
thermostats
are not allowed
Series Only
Thermostats
unless it is an emergency
that User Interface is not working
properly and new User Interface is not available.
For emergency
use, connect to standard thermostat connections
R, C, W. Y1. Y2,
and O.
The FV4 provides
high- and low-stage
blower operation
to
match the capacities
of compressor
at high- and low-stage.
To
select
recommended
airflow,
refer
to
FV4
Installation
NOTE:
Instructions.
allows the
When
unit is operating
light will flash rapidly.
Unit will operate
For 25HNA6 models, connect
standard thermostat connections
General
mode,
STATUS
in high stage ONLY.
to ABCD for Infinity Control
R. C, Wl, Y1. Y2. and O.
or
color-coded,
All wiring must be NEC
incoming power leads.
furnace
transformer,
insulated
Class
fan
(35°C
1 and must
coil
minimum)
wire
be separated
from
transformer,
or
accessory
transformer
for control power, 24v/40va minimum.
The outdoor
unit requires a minimum of 27va/24vac
control power.
Final
Wiring
IMPORTANT:
to ensure
Check
Check factory
terminations
wiring
are secured
to ensure wires are not in contact
and field wire connections
properly.
with tubing,
Check
wire routing
sheet metal, etc.
Non-Communicating
adjustments
to control
CFM ADJUST setting.
For
other
Digest.
(Non-Infinity)
The FV4 utilizes an Easy Select control board
installing
technician
to select proper airflows.
delay factory
operation.
Information
Use No. 18 AWG
for all installations.
Use
in enmrgency
Using
set
board, select appropriate
HP SIZE and
This fan coil has an adjustable blower off
at 90
combinations
that
For
sec for
of
high-
equipment
and
low-stage
Consult
Product
blower
Data
STEP 13 --Start-Up
STEP 14 --SYSTEM
OPERATION
The
outdoor
following
UNIT
OPERATION
AND SAFETY
Failure to follow this caution may result in minor
injury, equipment damage or improper operation.
Observe
The
personal
unit in a vacuum
• Do not disable
low pressure
• Dome temperatures
system
has
or at negative
special
of the two-stage
OF
functions.
control
The
functions:
Operation
model
utilizes
either
a standard
for first stage cooling, the outdoor
stage compressor
are energized.
system with refrigerant.
• Do not operate
and Heating
25HNA6
AND SEQUENCE
indoor
thermostat
or Infinity Communication
User Interface. The 25HNA9 models
utilize an Infinity communicating
User Interface only. With a call
the following:
• Do not overcharge
control
is an overview
Cooling
HAZARD
unit
FUNCTIONS
fan, reversing
If low-stage
valve, and low
cannot
satisfy
cooling demand, high-stage
cooling is energized by the second
stage of indoor thermostat or User Interface. After second stage is
pressure.
switch
satisfied, the unit returns to low-stage
operation until first stage is
satisfied or until second stage is required again. When both first
stage and second stage cooling are satisfied, the compressor
will
may be hot.
shut off. The reversing
valve will remain energized
until the
control board power is removed or a call for heating in initiated.
PERSONAL
Failure
INJURY
to follow
this caution
Wear safety glasses,
handling refrigerant.
With a call for heating,
the outdoor
fan and compressor
are
energized.
The compressor
will operate in high or low stage
operation,
as needed to meet the heating demand.
When the
HAZARD
may result in personal
protective
clothing,
injury.
and gloves
heating demand is satisfied, the compressor
and fan will shut off.
The reversing valve is de-energized
in the heating mode.
when
NOTE:
When
vapor
two-stage
(suction)
single-stage
NOTE:
minute
unit is operating
pressure
will
system
or high-stage
Outdoor
fan motor
after
compressor
be
than
system
a
standard
operation.
will
shuts
at low-stage,
higher
continue
off.
to operate
when
outdoor
for one
ambient
is
within
the
greater than or equal to 100°F.
ENVIRONMENTAL
Failure to follow
damage.
this caution
Federal
require
result
in environmental
Recover
to propedv
start
during
temperature.
temperature
up the system:
seat
(open)
liquid
front seated (closed)
caps after system is
to energize
or
User
caps
1/12
system.
Interface
at
desired
Be sure set point is below indoor
and is set low enough to energize
ambient
desired
stage.
control
thermostat
For
(non-Infinity)
equipped
or User Interface
to ON or AUTO
15 minutes.
NOTE:
Check
mode,
system
25HNA6
Series
thermostat.
with a 15-minute
as desired.
refrigerant
only
Carrier
staging
using
Operate
timer. This timer
in low stage for 15 minutes,
unless
between
and thermostat
stage (after
and fan
control
or User Interface
to AUTO
appropriate
time delay(s).
Check refrigerant charge.
operates
O is powered
for
a
For Infinity
Light
on.
and Status
Control
Function
only,
Green
Lights
communications
(COMM)
A green LED (COMM
light) on the outdoor board (see Fig. 9)
indicates
successful
communication
with
the other
system
products. The green LED will remain OFF until communications
is established.
Once a valid command is received, the green LED
will turn ON continuously.
If not communication
is received
within 2 minutes, the LED will be turned OFF until the next valid
communication.
Status
Light
mode and fault codes as specified in the troubleshooting
See Table 5 for codes and definitions.
prevents
NOTE:
colored
Only
STATUS
light is used to display
one code will
are
control
board
the
Utility
Interface
there is at least a 5°F
of 2 minutes
adjust the set point at least 5°F below room
6. Set room thermostat
unit
be displayed
(the most recent,
the operation
section.
on the outdoor
with the highest
unit
priority).
at high stage until unit has been
temperature
a minimum
demand,
the next
in high-stage.
unit for
thermostats
difference
low-stage
upon
An amber
non-communicating
electronic
operating
room
or
power-up,
and fan
charge.
system
high
from operating
to COOL
two-stage
force
energized,
Amber
5. Set room
high-
of 5 minutes
Communication
disconnects
thermostat
if unit has not operated
a unit
and with second stage of cooling, Y1, Y2, and O are on. For
these systems, with first stage of heating Y1 is on and for second
stage of heating, Y1 and Y2 are on. When the reversing valve is
opened to refrigerant
flow (back seated). Replace
finger-tight
and tighten with wrench an additional
turn.
3. Close electrical
models,
or following
On 25HNA6
models
with non-communicating
(non-Infinity)
systems, with first stage of cooling, Y1 and O are powered on;
system
fully back
2. Unit is shipped with valve stem(s)
and caps installed.
Replace
stem
room
thermostat
that you do not vent
1. After system is evacuated,
and vapor service valves.
4. Set
On 25HNA6
12 hours,
minimum
regulations
these steps
past
may
refrigerant to the atmosphere.
repair or final unit disposal.
Follow
NOTE:
HAZARD
or ON,
Operate
set point. To
in low stage),
ambient.
to HEAT
as desired.
unit
for
or COOL
Wait for
15 minutes.
With Infinity
Control
The utility curtailment
relay
connections
on the control
should
board
be wired between R and Y2
for Infinity Communicating
Systems
only (see Fig. 9.) This input allows a power utility
device
to interrupt
compressor
operation
during
peak load
periods. When the utility sends a signal to shut the system down,
the User Interface
will display,
"Curtailment
Active".
One Minute
When
Stage Change
compressor
Time
changes
Delay on 25HNA6
stages
from
high
high, there is a 1-minute
time delay before
The outdoor fan motor remains running.
('ompressor
When
Operation
the
compressor
compressor
on 25HNA6
Models
operates
high
in
stage
When
Time
•
compressor
The lower
refrigerant.
compressor
operates
in
low
stage
Five minute time delay to start cooling or heating
operation when there is a call from the thermostat
the
and upper
and both
operation,
include:
or
user interface. To bypass this feature, momentarily
short and release Forced Defrost pins.
refrigerant.
the
Delays
The unit time delays
restarts.
operation,
compressor
motor rotates clockwise.
Both the lower
pistons
are eccentric
with the rotating
crankshaft
compress
Models
to low or low to
•
Five minute
a brown-out
compressor
condition.
•
Two minute
time delay to return to standby
the
re-cycle
from last valid conmmnication
motor reverses direction (rotates counterclockwise).
piston becomes idle and the upper piston compresses
The start and run windings
ale reversed.
•
One minute
cooling
delay on return from
time delay of outdoor
mode when outdoor
operation
(with Infinity only).
fan at termination
ambient
of
is greater than or
equal to 100°F.
Crankcase
Heater
Operation
•
The crankcase
of outside
heater is energized
air temperature
during
Fifteen
unit off cycle regardless
(OAT) on 25HNA6
models.
•
The crankcase heater is energized
25HNA9 models.
Outdoor
The
Fan Motor
outdoor
unit
during off cycle below
energizes
outdoor
fan
Twenty
65°F on
any
time
compressor
is operating,
except for defrost. The ouMoor fan
remains energized
if a pressure
switch or compressor
overload
Thirty second
enabled.
•
On 25HNA6
between
of defrost before
is de-energized.
delay at termination
of defrost before
fan is energized.
•
compressor
models
staging
delay when quiet shift
there is a 1 minute
time delay
from low to high and from high to low
capacity.
On 25HNA9 models there is no delay; the
compressor
will change from low to high and from
should open. Outdoor fan motor will continue to operate for one
minute after the compressor
shuts off when the outdoor ambient
is greater than or equal to 100°F.
On 25HNA6
outdoor fan remains energized
during the 1-minute
staging time delay.
delay at termination
heat (Wl)
second
the outdoor
Operation
control
second
the auxiliary
high to low capacity
models, the
compressor
Compressor
Operation
on the fly to meet the demand.
on 25HNA9
Models:
When the compressor is operating
in low stage, the modulating
ring is de-activated,
allowing two internal bypass ports to close
off 33% of the scroll compression
area, so the system operates
part load capacity.
The 24volt solenoid coil is de-energized
at
in
low stage operation.
When
the compressor
is operating
in high stage, the modulating
ring is activated,
sealing the bypass ports, which allows the
compressor
to operate at full load capacity.
The 24volt solenoid
coil is energized
in high stage operation.
The
contains
a 230v to 24vac transformer
to supply
solenoid when it is energized.
The
compressor
should not be included in the system
power transformer sizing.
10
(furnace
25HNA9
unit
power to the
solenoid load
or fan coil) control
O
I PWM2
.u'_O
, fZII] 0
OO
O
rl
rl
0
0 0
©
sR[_ O
oo
[] []
0
O0
MODEl.
rlquid
* SUPPLIED
BY UTILITY
B
MODEL
O
EEIEEI
Lille
Solenoid
PROVIDER
A05247
Fig,
GENERAL
Control
INFORMATION
Low Ambient
Controned
low ambient
This unit is capable
when using Infinity
temperature.
This control
120 minutes,
cooling:
of low ambient cooling without a kit ONLY
control. A low ambient kit is not required,
up. Fan may not begin to cycle until about 40°F
cycle based on coil and outdoor air temperature.
low ambient
models,
•
mode operates
OAT.
Interface
AUTO
defrost
Fan will
as follows:
(the dip switches
by dip switches
•
When
•
off to allow refrigerant
defrost
for first 3 minutes
When
The
time 3-5 minutes,
board
the next defrost
the next defrost
time 5-7 minutes,
the next defrost
accumulates
the next defrost
compressor
compressor
running.
If LPS closes within 10 minutes
then cooling continues with the outdoor fan cycling per
The defrost
the coil temperature routine listed above for the remainder
of the cooling cycle. If the LPS does not close within 10
If the coil temperature
does not reach 32°F
the interval timer will be reset and start over.
then the normal
LPS trip response
and generate
(shut
time.
As
the
defrost demand. If a defrost demand exists, a defrost cycle will be
initiated at the end of the selected time interval. A defrost demand
during
exists when the coil temperature
minutes during the interval.
operation
run
accumulated
run time approaches
the selected defrost interval
time, the control board monitors the coil temperature
sensor for a
low ambient start up. After 3 minutes, ifLPS trips, then
outdoor fan motor is turned off for 10 minutes, with the
minutes,
on the last
minutes.
When defrost time >7 minutes,
interval=30
minutes.
control
time based
minutes.
defrost
interval=60
system to
Fan is ON when outdoor
coil temp > (outdoor
air
temperature
+ 25°F) or outdoor coil temp > 80°F or if
interval
When defrost time <3 minutes,
interval= 120 minutes.
minutes. (Fan is turned
stabilize.)
cooling
on the
are not used.)
defrost adjusts the defrost
time as follows:
•
•
switch is ignored
30. 60, 90,
On 25HNA9
, the defrost interval times: 30, 60, 90, and 120 minutes
or AUTO
are selected by the Infinity
Control
User
Fan is OFF when outdoor coil temp is < (outdoor air
temperature
+ 3 °F) or outdoor fan has been ON for 30
Low pressure
times:
settings.
outdoor fan has been OFF for 30 minutes. (Fan is turned
on to allow refrigerant system to stabilize.)
•
interval
these are selected
interval=90
•
defrost
unit control board or by the Infinity Control User Interface.
The
Infinity Control selection overrides the control board dip switch
provides an automatic evaporator coil freeze protection algorithm
that eliminates the the need for an evaporator
freeze thermostat.
Low ambient cooling must be enabled in the User Interface set
cnntrolled
offers 5 possible
or AUTO.
On 25HNA6
and the outdoor
fan motor does not need to be replaced
for
Infinity controlled
low ambient operation.
The Infinity Control
Infinity
Board
Defrost
Cooling
When this unit is operating
below 55°F outdoor
provisions must be made for low ambient operation.
Infinity
9 - 2-Stage
65°F
down
•
LPS trip error) will occur.
cycle is terminated
or 10 minutes
Upon
11
32°F
when the coil temperature
for 4
reaches
has passed.
initial power
within
up the first defrost
defaulted to 30 minutes.
selected times.
•
is at or below
Defrost
is only allowed
ambient
temperature.
Remaining
the interval,
interval
intervals
to occur below 50°F
is
are at
outdoor
Defrost
Hold
STEP
On 25HNA6
models,
in a non-comnaunicating
system,
thermostat
becomes
satisfied
(Y1 or Y1 and Y2)
defrost cycle is terminated,
the control will "Hold"
mode and finish
On 25HNA6
all 25HNA9
the defrost
the User Interface
down the system.
2-pin header
control board
and 25HNA9
with communicating
(Infinity)
defrost is initiated with the User Interface.
On all models,
during
•
a Forced
If coil temperature
and outdoor
air temperature
defrost sequence
•
If coil temperature
or outdoor
of 32°K
a full
do not
an abbreviated
30 second
Accesso D,
Control:
solenoid
solenoid
Liquid
When
Models
See
with
Infinity
Communicating
Infinity
control,
the liquid
line
solenoid
refrigerant
with Accessory
Thermostat:
and C terminal
Only Procedure
requires
Liquid
Solenoid
The liquid
connections.
charging by the subcooling
operate
unit
a minimum
method.
of 10 minutes
high stage before checking charge.
On 25HNA6
models, charging in low
stage
compressor
damage
chattering
and
possible
in
may cause
to
the
Using
liquid
service
gage to service
valve
pressure
by
attaching
an
port.
subcooling
high
stage
temperature
is higher than indicated or reclaim refrigerant
if temperature
is lower. Allow a tolerance of _+3°F.
output that is energized whenever
the compressor
is energized. It
closes,
in the compressor
off mode.
to prevent
refrigerant
migration into the unit through the liquid line.
Non-Communicating
connect
to the Y1
plate,
6. To obtain required
subcooling
temperature
at a specific
liquid
line pressure,
add refrigerant
if liquid
line
output is provided
at the Y1 connection.
Connect the
as shown in the wiring label diagram. This is a 24vac
On 25HNA6
rating
pressure.
Accessory
Solenoid
using the
unit
operation.
In heat pump long-line
applications,
a liquid line solenoid is
required to control refrigerant migration in the heating mode. The
solenoid should be installed near the outdoor unit with the arrow
of flow control.
details.
are not favorable.
5. Refer to Table 3. Find the point where required subcooling
temperature
intersects
measured
liquid
service
valve
mode.
facing the outdoor unit. This is the direction
application manual for long-line
application
with
4. Refer
to unit
rating
plate for required
temperature.
Subcooling
amount
is for
sequence of operation will occur. Reversing valve
and compressor
will turn off for 30 seconds, then
Line Solenoid
conditions
in accordance
3. Measure liquid line temperature
by attaching an accurate
thermistor
type or electronic
thermometer
to liquid line
near outdoor coil.
turn back on to complete defrost. At the end of the defrost cycle.
the reversing
valve de-energizes,
compressor
will turn off for
another 30 seconds, and the fan will turn off for 40 seconds,
Liquid
charging
in
in
unit plate.
accurate
selecting
the 3rd position
of the 3-position
dip switch.
For
25HNA6
and 25HNA9
models with communicating
(Infinity)
systems, it must be enabled at the User Interface. When activated,
in the heating
unit
the charging chart on the outdoor
2. Measure
cycle and restarting
of the heating cycle.
On 25HNA6 models
with non-communicating
system, this feature must be enabled by
starting
on
compressor.
Shift
before
shown
line above or below
15 ft..
fall within the ranges given on
Cooling
Quiet Shift is a field selectable defrost mode which may eliminate
occasional
noise that could be heard at the start of the defrost
the following
will energize
be weighed
1. On all unites,
air temperature
are
To calculate additional charge required for a 25-ft. line set:
25 ft. - 15 ft. = 10 ft. X 0.6 oz./ft. = 6 oz. of additional charge.
will occur.
meet the above requirements,
defrost will occur.
Quiet
is below 50°K
method
_+0.6 oz./ft, of 3/8-in.
liquid
respectively. Favorable conditions
This system
temperature
charging
EXAMPLE:
Defrost:
is at defrost
and
If subcooling
charge must
(see Fig 9) on the
On 25HNA6
control, forced
charge
NOTE:
will complete
with non-communicating
(non-Infinity)
can be initiated by manually shorting the
labeled FORCED
DEFROST
for 5 seconds then releasing.
Charge
information plate. Charge Puron refrigerant units with cylinder
inverted position
and a commercial-type
metering
device
manifold hose. Charge refrigerant into suction line.
Defrost
On 25HNA6
models
control, forced defrost
n
Factory
cycle on the next call for heat.
because
shutting
15 --Check
Unit Charge
before the
in defrost
models, with communicating
Infinity Control and
models,
defrost
hold
is not needed
in a
communicating
system
the defrost cycle before
Forced
if the
a
solenoid
is
The liquid
closes,
in the compressor
off mode.
to prevent
migration into the unit through the liquid line.
12
Heating
Check
Chart
To check system
Procedure
operation
is necessary
during
cycle,
refer to the Heat
charge
must
be weighed
in accordance
with
label on outdoor
relationship
exists
unit. This chart
between
system
_+0.6
oz./ft,
of
liquid
during
Pump Charging
Instructions
indicates whether a correct
NOTE:
heating
In heating
mode,
pressures
are stable.
If in doubt,
correct refrigerant
check
refrigerant
remove
charge
charge
3/8-in.
line
above
heating
unit
or
rating
below
season,
plate,
15
ft.,
EXAMPLE:
To calculate additional charge required for a 25-ft. line set:
25 ft. - 15 ft. = 10 ft. X 0.6 oz./ft. = 6 oz. of additional charge.
charge.
NOTE:
charging
respectively.
operating
pressure
and air temperature
entering
indoor
and
outdoor units. If pressure and temperature do not match on chart,
system refrigerant charge may not be correct. Do not use chart to
adjust refrigerant
When
only when
and weigh
in
charge.
Table 3--Required
LiQUiD PRESSURE
AT SERVICE VALVE
(PSIG)
LiquidlLine
REQUIRED
Temperature
SUBCOOLING
(°F)
TEMPERATURE
(°F)
8
10
12
14
16
18
189
58
56
54
52
50
48
195
60
58
56
54
52
50
202
62
60
58
56
54
52
208
64
62
60
58
56
54
215
66
64
62
60
58
56
222
68
66
64
62
60
58
229
70
68
66
64
62
60
236
72
70
68
66
64
62
243
74
72
70
68
66
64
251
76
74
72
70
68
66
259
78
76
74
72
70
68
266
80
78
76
74
72
70
274
82
80
78
76
74
72
283
84
82
80
78
76
74
291
86
84
82
80
78
76
299
88
86
84
82
80
78
308
90
88
86
84
82
80
317
92
90
88
86
84
82
326
94
92
90
88
86
84
335
96
94
92
90
88
86
345
98
96
94
92
90
88
354
100
98
96
94
92
90
364
102
100
98
96
94
92
374
104
102
100
98
96
94
384
106
104
102
100
98
96
395
108
106
104
102
100
98
406
110
108
106
104
102
100
416
112
110
108
106
104
102
427
114
112
110
108
106
104
439
116
114
112
110
108
106
450
118
116
114
112
110
108
462
120
118
116
114
112
110
474
122
120
118
116
114
112
486
124
122
120
118
116
114
499
126
124
122
120
118
116
511
128
126
124
122
120
118
13
n
MAJOR
2-Stage
Control
Systems
Board
The HP control
n
TROUBLESHOOTING
COMPONENTS
board controls
•
High
•
Outdoor
•
Reversing
•
Defrost
•
Low ambient
•
Crankcase
•
Compressor
•
Pressure
•
Time Delays
•
On 25HNA6
the following
and low stage compressor
functions:
contactor
If communication
operation
valve operation
The control
heater operation
external
Pressure
protection
The
switch monitoring
models,
board
outdoor
only)
On 25HNA6
models
with
communicating
system
25HNA9 models, use the ABCD Infinity Connections.
contains
Compressor
Relief
motor
Refer
windings
to Table
is protected by an internal pressure
discharge
gas into the compressor
The compressor
is also protected
to motor windings.
Compressor
Control
and
and
fan operating
the appropriate
a 15 minute
all
call for cooling
7. In
correct
the
for 15 minutes
delay,
if there
is a call for cooling
reset,
the
or
appropriate
or heating.
event
high-pressure
of
a
high-pressure
lockout,
check
8. In the event of a low-pressure
lockout, check the refrigerant
relief (IPR)
shell when
(cooling)
heating.
by an internal overload
Control
the
the appropriate
be replaced.
board
and outdoor
cycles,
the
switch
trip
refrigerant
unit
or
charge,
coil (in cooling)
in heating.
for
switch trip or low-pressure
charge and indoor airflow
fan operation
and outdoor
coil in
Fault
If the outdoor
Contactors
control
contactor
fault code (see Table 5)
6. If LPS or HPS trips 3 consecutive
operation is locked out for 4 hours.
pressure
exceeds
psi on 25HNA9
The contactor(s)
have a 24volt coil. The electronic
controls the operation of the appropriate
contactor.
or low
5. If LPS or HPS has not closed after a 15 minute delay, the
outdoor fan is turned off. If the open switch closes anytime
after the 15 minute delay, then resume operation
with a
that provide
4 for
If a
low-pressure
of a high
compressor
outdoor fan operation,
and outdoor
airflow restrictions, or indoor airflow
differential
between
suction
and discharge
500-550
psi on 25HNA6 models and 550-625
models.
attached
high-
heating
and LPS or HPS
is
compressor
contactor is energized.
Compressor
operation.
with
the appropriate
2. Keep the outdoor
connections
located at the bottom of the control board (see Fig.
9.) On a non-communicating
system, output W1 is connected
at
the bottom of the control board for auxiliary heat.
2-pole
(3500 RPM)
winding resistance.
plug to operate.
not operate and the
shown in Table 5.
Protection
1. De-energize
4. After
The compressor
which relieves
must have a valid model
unit is equipped
On 25HNA6
models
with non-communicating
(non-Infinity)
System,
the two-stage
control
receives
24vac
low-voltage
control
system
inputs
through
the R, C, Y1, Y2 and O
Internal
control is lost with the User
switches.
If the control senses the opening
pressure switch, it will respond as follows:
high and low stage start relay and
(Bristol
Switch
3. Display
The two stage compressor
the Infinity
valid model plug is not detected,
it will
control will flash the appropriate
fault code,
cooling
Field Connections
Two Stage
with
Model Plug
operation
operation
Failure
Interface, the control will flash the appropriate fault code. (See
Table 5.) Check the wiring to the UI and the indoor and outdoor
units.
fan motor operation
capacitor
Communication
Brown-Out
unit control
board
has failed,
the control
fault code (see Table 5). The control
will flash
board
should
Protection
If the line voltage is less than 187v for at least 4 seconds, the
appropriate
compressor
contactor and fan relay are de-energized.
Compressor
and fan operation
are not allowed until voltage is a
minimum
of 190v. The control will flash the appropriate
fault
code (see Table 5).
230V Line
(Power
Disconnect)
Detection
If there is no 230v at the compressor
contactor(s)
when the indoor
unit is powered
and cooling
or heating
demand
exists, the
appropriate fault code is displayed. Verify the disconnect
and 230v wiring is connected
to the unit.
Compressor
Voltage
The
board
control
is dosed
Sensing
input
terminals
labeled
VS. VR
and L2 on
25HNA6 models and VS and L2 on 25HNA9 models (see Fig. 9)
are used to detect compressor
voltage status, and alert the user of
potential problems.
The control continuously
monitors the high
voltage on the run capacitor of the compressor
motor. Voltage
should be present any time the compressor
contactor
and voltage
should
not be present
when
the
de-energized.
14
is energized.
contactor
is
Contactor
Shorted
Detection
If there is compressor
voltage
sensed when there is no demand
Troubleshooting
25HNA6
low & hiuh staues
for
Check
25HNA6
liquid pressure when switching
from low to high capacity.
Compressor
current should increase 100-250%
when switching
from low to high stage.
Compressor
Thermal
Cutout
Troubleshooting
inputs will indicate the thermal protector is closed.
If the phase
difference
is 5 degrees
or less for 10 seconds,
the internal
protector
is open.
The control
de-energizes
the appropriate
cooling
or
heating,
the
appropriate
15 minutes.
minute
interval
If the thermal
check),
protector
closes,
the unit will resume
25HNA9
at the
units for proper
Check the suction pressures
at the
pressure should be reduced by 3-10%
service
switching
between
service valves.
when switching
Suction
from low
NOTE:
compressor
high
The liquid
pressures
stage operation,
are very
so liquid
similar
pressure
between
should
troubleshooting.
Compressor
from low
(at the next 15
current
to high
energized
operation.
should
stage.
increase
20-45%
The compressor
in high stage, should
measure
when switching
solenoid
when
24vac.
If the thermal cutout trips for three consecutive
cycles, then unit
operation is locked out for 4 hours and the appropriate fault code
is displayed.
Thermistors
Thermistors
are electronic
25HNA9
are used to sense outdoor air (OAT) and coil temperature
Refer to Fig. 12 for resistance values versus temperature.
If the control senses
Thermal
the temperature
Cutout
the compressor
voltage
then absent for 10 consecutive
seconds
demand
exists, the thermal protector
after start-up,
and is
If the outdoor
while cooling or heating
is open.
The control
the
has
every
15 minutes.
the next 15 minute
If the thermal
operation is locked
is displayed.
Low- or High
Compressor
interval
cutout
check),
out for 4 hours
Contactor
consecutive
(25HNA9
cycles,
and the appropriate
Open (25HNA6
voltage
protector
the unit will resume
trips for three
Contractor
If the compressor
If the thermal
models)
closes.
- Compressor
outdoor
fail. the control
air thermistor
insure
11.
thermistors
are mounted
will
in the
final
and coil thermistor
locations.
properly
Check
to
per Fig. 10 and Fig.
The control
temperature
continuously
monitors and compares the outdoor air
sensor and outdoor coil temperature
sensor to ensure
(at
operation.
proper operating
then unit
•
fault code
Comparison
conditions.
In cooling
The comparison
if the outdoor
air sensor
is:
indicates
>- 10_'F
warmer than the coil sensor (or) the outdoor air sensor
indicates >- 20°F cooler than the coil sensor, the sensors
are out of range.
In heating
the compressor
if the outdoor
air sensor
indicates
-> 35 °F
warmer than the coil sensor (or) the outdoor air sensor
indicates >- 10°F cooler than the coil sensor, the sensors
are out of range.
If the sensors
are out of range,
the control
appropriate fault code as shown in Table 5.
on
The thermistor
cooling
Failed
fault code.
comparison
or defrost
Thermistor
Factory
outdoor
In high stage, if the specified start voltage at VS terminal is not
achieved, the start relay is de-energized
after 1 second and the
control will flash the appropriate fault code.
If the specified start voltage is not achieved
stage starts, low stage operation
is locked
(OCT).
Sensor
In low stage, if the specified start voltage at VR terminal is not
achieved, the start relay is de-energized
after 1 second and the
control will flash the appropriate
The
mounted
/ No 230V at
Start Detection
should
As
Thermistors
Thermistor
should be starting, the appropriate
contactor may be stuck open or
there is a wiring error. The control will flash the appropriate
fault
code. Check the contactor and control box wiring.
25HNA6 Models Only
Bristol Models Only
sense temperature.
decreases.
fault code. (See Table 5.)
be factory
•
when
which
the resistance
should
models)
is not sensed
devices
air or coil thermistor
IMPORTANT:
not re-set, the outdoor fan is turned off. If the call for cooling or
heating
continues,
the control
will energize
the compressor
contactor
increases,
flash the appropriate
de-energizes
the compressor
contactor
for 15 minutes,
but
continues to operate the outdoor fan. The control Status LED
will flash the appropriate
code shown in table 5.
After 15
minutes, with a call for low or high stage cooling or heating,
compressor
contactor
is energized.
If the thermal protector
low and
not be used for
Temperature
Compressor
valves.
to high capacity.
contactor is energized.
If the thermal protector has not re-set, the
outdoor fan is turned off.
If the call for cooling
or heating
continues,
the control will energize the compressor
contactor
every
pressures
low & hiuh staues
compressor
contactor for 15 minutes, but continues to operate the
outdoor fan. The control Status LED will flash the appropriate
code shown in table 5. After 15 minutes, with a call for low or
stage
and liquid
Suction pressure should be reduced by 5-10% when switching
from low to high capacity. There should be a 10-20% increase in
The control senses the compressor voltage at VR and VS. When
starting or running,
a phase difference
of the voltages
on the
high
suction
between
compressor
operation, the contactor may be stuck closed or there
may be a wiring error. The control will flash the appropriate
fault
code.
Models_
the
units for pl_oper switching
is not performed
will
during
flash
the
low ambient
operation.
Default
Operation
defaults have been provided in the event
air thermistor and/or coil thermistor.
of failure
of
If the OAT sensor should fail, low ambient cooling will not be
allowed and the one-minute
outdoor fan off delay will not occur.
Defrost will be initiated based on coil temperature
and time.
for 3 consecutive
low
out for 30 minutes. If
If the OCT sensor should fail, low ambient cooling will not be
allowed.
Defrost will occur at each time interval during heating
the specified start voltage is not achieved for 3 consecutive
high
stage starts, high stage operation
is locked out for 30 minutes.
The control will flash the appropriate
fault code.
operation,
but will terminate
after 5 minutes.
If there is a thermistor
out of range error, defrost will occur at
each time interval during heating operation,
but will terminate
after 5 minutes.
Count the number
of short and long flashes to determine
the
appropriate
flash code. Table 5 gives possible causes and actions
related to each error.
15
OAT Thermistor must be locked in
place with spherical nib end facing towards the front of the control box
OCT Thermistor
must be secured
tight on stub tube
\
n
Fig,
10
- Outdoor
Air Thermistor
Fig.
(OAT) Attachment
THERMISTOR
90
11
- Outdoor
Coil Thermistor
(OCT)
Attachment
CURVE
,
20
40
60
80
TEMPERATURE
100
120
(DEG. F)
A91431
Fig.
12 -
Resistance
Values Versus
Temperature
Table 4--Two-Stage
Compressor Resistances
(Winding Resistance at 70°F_+20 °)
Winding
Status
25HNA6024
25HNA6036
25HNA6048
25HNA6060
Start (S-C)
2.74
1.98
1.55
0.74
Run (R-C)
0.80
0.75
0.48
0.36
Winding
25HNA9024
25HNAg036
25HNA9048
25HNAg060
Start (S-C)
1.40
1.29
1.52
0.60
Run (R-C)
1.32
0.89
0.64
0.49
(:odes
Table 5 shows the status codes flashed by the amber
flashed by the amber status light on the control board.
The codes
are flashed
by a series of short
status
and long flashes
light.
Most
of the status
system
light.
problems
can be diagnosed
The short flashes
indicate
by reading
the first digit
the status
code as
in the status
code.
followed by long flashes indicating the second digit of the error code. The short flash is 0.25 seconds ON and the long flash is 1.0 second
ON. Time between flashes is 0.25 seconds.
Time between short flash and first long flash is 1.0 second. Time between code repeating is 2.5
seconds with LED OFF.
EXAMPLE:
3 short flashes followed
by 2 long flashes indicates
a 32 code.
Table 5 shows
16
this to be low pressure
switch open.
Table 5--TROUBLESHOOTING
OPERATION
Standby
tion
no call for unit opera-
Emergency
Mode
-
Modet 25HNA9
only
Low Stage Cool/Heat Operation
High Stage Coot/Heat Operation
AMBER
LED
FLASH
CODE
FAULT
None
On solid,
no flash
Standard Thermostat Control
(25HNA9only)
Rapid, continuous flashing
POSSIBLE CAUSE AND ACTION
Normal operation
Unit being controlled by standard thermostat inputs instead of tnfinity Control. Only high stage operation is available. This operatimg mode should be
used in emergency situations only.
None
1, pause
Normal operation
None
2, pause
Normal operation
System Communications Failure
16
Communication with user interface lost. Check wiring to UI, indoor
and outdoor units
Invalid Model
Plug
25
Control does not detect a modeI ptug or detects an invalid model
plug. Unit wili not operate without correct model plug.
High Pressure
Switch Open
31
High-pressure
switch trip. Check refrigerant charge, outdoor fan
operation and coils for airflow restrictions.
Low Pressure
Switch Open
32
Control Fault
45
Low pressure switch trip. Check refrigerant charge and indoor air
flow
Outdoor unit control board has failed. Control board needs to be
Brown Out (230
v)
46
No 230v at Unit
47
Outdoor Air
replaced.
Line voltage < 187v for at least 4 seconds. Compressor and fan
operation not allowed until voItage>190v.
Verify line voltage.
There is no 230v at the contactor when indoor unit is powered and
cooling/heating demand exists. Verify the disconnect is closed and
230v wiring is connected to the unit.
Temp Sensor
Fault
53
Outdoor air sensor not reading or out of range. Ohm out sensor
and check wiring.
Outdoor Coil
Sensor Fault
55
Coii sensor not reading or out of range. Ohm out sensor and check
wiring.
Thermistors
of range
56
Improper relationship between colt sensor and outdoor air sensor.
Ohm out sensors and check wiring.
No voltage phase difference is detected (on 25HNA6 models) or
Low Stage Thermal Cutout
71
compressor voltage sensed, then disappears (on 25HNA9 models)
while cooling or heating demand exists. Possible causes are internal compressor overload trip or start relay not releasing (if installed).
No voltage phase difference is detected (on 25HNA6 models) or
High Stage Thermal Cutout
72
compressor voltage sensed, then disappears (on 25HNA9 models)
while cooling or heating demand exists. Possible causes are internal compressor overload trip or start relay not releasing (if installed).
Contactor
Shorted
73
No 230V at
Compressor
(25HNA9 Only)
74
Low Stage Did
Not Start
(25HNA6 Only)
75
out
Compressor voltage sensed when no demand for compressor operation exists. Contactor may be stuck closed or there is a wiring
error.
Compressor voltage not sensed when compressor should be starting. Contactor may be stuck open or there is a wiring error.
Specified start voltage at VR terminal was not achieved in low stage.
Start relay was de-energized
Low Stage Did
Not Start 3 times
(25HNA6OnIy)
76
High Stage Did
Not Start
(25HNA6 Only)
77
after 1 second.
For 3 consecutive low stage starts, the specified start voltage at VR
terminal was not achieved & start relay was de-energized.
Low
stage locked out for 30 minutes.
Specified start voltage at VS terminal was not achieved in high
stage. Start relay was de-energized
after 1 second.
High Stage Did
Not Start 3 times
(25HNA6 Only)
78
For 3 consecutive high stage starts, the specified start voltage at VS
terminal was not achieved & start relay was de-energized.
High
stage locked out for 30 minutes.
Low Stage Thermal Lockout
81
Thermal cutout occurs in three consecutive low/high stage cycles.
Low stage locked out for 4 hours or untiI 24v power recycled.
High Stage Thermal Lockout
82
Thermal cutout occurs in three consecutive high/low stage cycles.
High stage locked out for 4 hours or until 24v power recycled.
Low Pressure
Lockout
83
Low pressure switch trip has occurred during 3 consecutive cycles.
Unit operation locked out for 4 hours or until 24v power recycled.
High Pressure
Lockout
Low Contactor
Open
(25HNA6 Only)
High Contactor
Open
(25HNA6 Only)
84
High pressure switch trip has occurred during 3 consecutive cycles.
Unit operation locked out for 4 hours or until 24v power recycled.
Compressor voltage not sensed when compressor should be starting. Low stage contactor may be stuck open or there is a wiring
error.
Compressor voltage not sensed when compressor should be starting. High stage contactor may be stuck open or there is a wiring
error.
85
87
17
INDOOR
CONTROL
FAN COIL
2-SPEED
HEAT PUMP
HybridHeat
THERMOSTAT
RVS
COOLING
HEAT/COOL
STAGE
HEAT
STAGE
I-q-Q
RVS COOLING
.... -4_}-.5.--_MO_
----1 D_'JUMPERFOR
3
HEAT/COOL
STAGE
24 VAC
....
....
1
'
2
FAN
E]_
HOT
D
--HEAT
HEAT/COOL
STAGE 1
(COMPRESSOR I O}
_REMOVE
n
24VAC
COMM
HUMIDIFY
[
RVS
HEATING
24 VAC
J] FOR
-
HOT
-
24 VAC COMM
(24 MAC)
N/A
]
RVS SENSING
-
-
4
II
[_
UOM
1-
HUM
I-
-
-
I
[_
r_
_
OUTDOOR
I-r_.
_
_
OUTDOOR
SENSOR
]_
GON"EOT'O"
LF_
SENSOR
___OUTDOOR___
SENSOR
-
FF@_q I
__&_IHUM'D'F'ER
I___J
r_,
',
I-
I_LI-
_ _ _ 4_R_l- I_ _ _
DEHUMIDIFY
MODES
....
E_
_uI
i
FAN
__
....
- -
i
t]-L4_]
HEAT/COOL
STAGE 2
(COMPRESSOR HI}
I_ _[_]
E_
-
w?
RNACE/3
HEAT (F STAGE
L-.E}.
DEHUMIDIFY
J
r_
i
STAGING
TWO-STAGE
HEATRUMP
TWO-STAGE
FURNACE
_
J
OONNEOTIONL_Lt_J"
A02005
Fig, 13
- Infinity
Wiring
Heat Pump
(applies
with 2-Stage
Puron
A06157
refrigerant
Fi 9, 14
(non-communicating)
to 25HNA6
Models
User
Furnace
- HybridHeat
and Two-Stage
TM
Thermostat
Heat Pump
with Two-Stage
(non-communicating)
Only)
Interface
Fan
Coil
Communicating
AC//HP
::D
i
Fig
9 - FE4A
Fan
Coil Wiring
with
2-Speed
AC/HP
A03076
Fig,
15 - Infinity
Furnace
el" Fan
(:oil Wiring
with Communicating
18
Two-Stage
AC / HP
FINALCHECKS
IMPORTANT:
Before
leaving
job,besure
todothefollowing:
1.Ensure
thatallwiringis routed
awayfromtubingand
sheetmetaledgesto prevent
rub-through
or wire
pinching.
2.Ensure
thatallwiringandtubingissecure
inunitbefore
adding
panels
andcovers.
Securely
fasten
allpanels
and
covers.
3.Tighten
service
valvestem
caps
to1/12-turn
pastfinger
tight.
4.LeaveUsersManualwith owner.Explainsystem
operation
andperiodic
maintenance
requirements
outlined
inmanual.
5.FilloutDealer
Installation
Checklist
andplace
in
customer
file.
CARE
ANDMAINTENANCE
Forcontinuing
highperformance
andto minimize
possible
equipment
failure,
periodic
maintenance
mustbeperformed
on
thisequipment.
Frequency
ofmaintenance
mayvarydepending
upongeographic
areas,
suchascoastal
applications.
SeeOwner's
Manual
for
information.
PURON®
(R-410A)
REFRIGERANT
QUICK
• Puron
refrigerant
components
• Puron
refrigerant
• Recovery
• Puron
operates
cylinder
service
pressure
should
pumps
pressure
be designed
• Do not use liquid-line
• If indoor
• When
to certain
unit is equipped
all warnings,
hose
retard.
with POE oils.
from oil.
pressures
less than 600 psig.
than 72 hours.
oil to atmosphere.
plastics and roofing
materials.
with wet cloth when brazing.
filter drier is required
with an R-22
on every unit.
while
for service,
TXV or piston metering
it is under
recover
device,
it must be changed
evacuate
then break vacuum
into the atmosphere.
tube coils.
cautions,
to a hard shutoff
Puron TXV.
a vacuum.
refrigerant,
prior to recharging.
refrigerant
• Do not use capillary
• Observe
valves
to atmosphere
to 500 microns
• Do not vent Puron
device in the manifold
TXV.
system must be opened
Evacuate
type metering
filter drier in liquid line.
liquid-line
• Never open system
is only compatible
moisture
• Wrap all filter driers and service
approved
or DOT BW400.
Use a commercial
rating.
rapidly. Do not expose
• POE oils may cause damage
• Do NOT use an R-22
and replacement
operating
line filter driers in line longer
• Do not install a suction-line
• A factory
with liquid refrigerant.
filter driers with rated working
suction
• POE oils absorb moisture
equipment
to detect HFC refrigerant.
as with other HFCs.
will not remove
• Do not leave Puron
Be sure that servicing
be 700 psig high side and 180 psig low side with 550 psig low-side
should
refrigerant,
• Vacuum
than R-22.
rating must be 400 psig, DOT 4BA400
be charged
• Use hoses with 700 psig service
• Puron
pressures
refrigerant
into suction line with compressor
sets should
• Leak detectors
higher
with Puron
GUIDE
are rose colored.
systems
when charging
percent
to operate
cylinders
refrigerant
• Manifold
at 50-70
are designed
REFERENCE
and bold text.
• All indoor coils must be installed with a hard shutoff
Puron TXV metering
19
device.
with dry nitrogen
and replace filter driers.
Copyright
Mannfae_urer
2006
6;a11_er
rese_'es
Colp
•
the
tlght
7310
W
Mo1_is
to change,
at
St •
any
Indianapolis,
time.
speeifieations
IN
46231
and
P1_i_ted
designs
without
notice
and
in USA
wit hou_
Catalo_
obligations.
2O
No: 25HNA-2SI
Replaces:25HNA
ISI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 20 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 14:09:56 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools