CARRIER Air Conditioner/heat Pump(outside Unit) Manual L0604185
User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 20
Download | |
Open PDF In Browser | View PDF |
to the Expertg[ £n Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS INSTALLATION ....................... RECOMMENDATIONS INSTALLATION Check Equipment Step 2 - Install on Solid Pad ...................... 3 Step 3 - Clearance Requirements 3 Step 4 - Operating Ambient Step 5 - Elevate Step 6 - Install TXV Step 7 - Install Liquid Step 8 - Make Piping Step 9 - Make Electrical Unit instruction manual starting the MAJOR ........................ Unless otherwise instructions Information noted, information in these installation pertain to both 25HNA6 and 25HNA9 series units. that is unique to the 25HNA6 series will be identified as such; likewise information will also be identified. that is unique to the 25HNA9 series 3 - 4 4 Line Solenoid Connections Valve (LSV) CARE PURON ..... .............. Connections Crankcase Charge COMPONENTS CHECKS 3 ............ Heater 7 - 8 ............. 8 ...................... Selections 8 .................. 8 9 of ..................... 9 - 12 12 - 13 .......................... ........................ 14 14 - 17 ................................. AND MAINTENANCE REFRIGERANT 19 ...................... QUICK 5 5 - 7 .............................. TROUBLESHOOTING FINAL 3 .................. Step 14 - System Functions and Sequence Operation ................................. Step 15 - Check before ............... ...................... Accessories Step 13 - Start-Up NOTE: Read the entire installation. & Jobsite ............................ Step 12 - Make Airflow / 25HNA9 2 3 - 13 Step 1 - Step 11 - Install Fig. 1 - 25HNA6 ............. .............................. Step 10 - Compressor A05240 2 REFERENCE 19 GUIDE 19 SAFETY CONSIDERATIONS Improperinstallation,adjustment, alteration,service, maintenance, orusecancause explosion, fire.electrical shock, or otherconditions whichmaycause death, personal injury,or property damage. Consult aqualified installer, service agency, or yourdistributor or branch forinformation or assistance. The qualified installer oragency mustusefactory-authorized kitsor accessories when modifying thisproduct. Refer totheindividual instructions packaged withthekitsoraccessories when installing. Follow allsafety codes. Wear safety glasses, protective clothing, andworkgloves. Usequenching clothforbrazing operations. Havefire extinguisher available. Readtheseinstructions thoroughly andfollowallwarnings or cautions included in literature andattached totheunit.Consult localbuilding codes andNational Electrical Code (NEC) forspecial requirements. Recognize safety information. Thisisthesafety-alert symbol/_ When youseethissymbol ontheunitandin instructions or manuals, bealerttothepotential forpersonal injury.Understand these signalwords;DANGER. WARNING, andCAUTION. These wordsareused withthesafety-alert symbol. DANGER identifies themostserious hazards whichwillresultin severe personal injuryor death. WARNING signifies hazards which couldresultinpersonal injuryordeath. CAUTION is used to identify unsafe practices whichmayresultin minorpersonal injuryor product andproperty damage. NOTEis usedto highlight suggestions whichwillresult inenhanced installation, reliability, oroperation. ELECTRICAL SHOCK HAZARD Failure tofollowthiswarning couldresult in personal injuryordeath. Before installing, modifying, orservicing system, main electrical disconnect switch must beintheOFFposition. There maybemore than1disconnect switch. Lockout andtagswitch withasuitable warning label. UNITOPERATION ANDSAFETY HAZARD Failure tofollowthiswarning could result inpersonal injury orequipment damage. Puron _ refrigerant systems operate athigher pressures than standard R-22systems. DonotuseR-22service equipment orcomponents onPuron _refrigerant equipment. INSTALLATION RECOMMENDATIONS NOTE:Insome cases noise inthelivingarea hasbeen traced to gaspulsations fromimproper installation ofequipment. 1.Locate unitaway fromwindows, patios, decks, etc.where unitoperation sound maydisturb customer. 2.Ensurethatvaporandliquidtubediameters are appropriate forunitcapacity. 3.Runrefrigerant tubes asdirectly aspossible byavoiding unnecessary turns andbends. 4.Leave some slackbetween structure andunittoabsorb vibration. 5.Whenpassing refrigerant tubesthrough thewall,seal opening withRTVorotherpliable silicon-based caulk. (See Fig.2.) 6.Avoiddirect tubingcontact withwater pipes, ductwork, floorjoists, wallstuds, floors, andwalls. 7.Donotsuspend refrigerant tubingfromjoistsandstuds witha rigidwireor strap whichcomes indirect contact withtubing.(See Fig.2.) 8.Ensure thattubinginsulation ispliableandcompletely surrounds vapor tube. 9.When necessary, usehanger straps whichare1 in.wide andconform toshape oftubing insulation. (See Fig.2.) 10.Isolate hanger straps frominsulation by usingmetal sleeves benttoconforna toshape ofinsulation. When outdoor unitisconnected tofactory-approved indoor unit. outdoor unitcontains system refrigerant charge foroperation with ARIrated indoor unitwhen connected by15ft.offield-supplied or factory accessory tubing. Forproper unitoperation, check refrigerant charge usingcharging information located oncontrol boxcover and/or intheCheck Charge section ofthisinstruction. IMPORTANT: Maximum liquid-line sizeis3/8-in. ODforall residential applications including longlineapplications. IMPORTANT: Always installthefactory-supplied liquid-line filterdrier. Obtain replacement filterdriers fromyourdistributor orbranch. INSTALLATION NOTE: Avoid contact between tubing and structure INDOOR WALL LIQUID TUBE INSULATION THROUGH THE WALL HANGER STRAP_k _y,,,,_J (AROUND VAPOR X. k_ OIST INSULATION /_ VIEW _ TOP / UNIT BASE PAN DIMENSIONS h FROM VAPOR TUBE _ TIEDOWN KNOCKOUT LOCATIONS A B C m d t, 1"MIN. ------I I--,-- 36 1/2 x 40 11 5/8 6 13/16 28 3/4 29 1/2 X 33 10 1/16 5 5/8 23 3/4 LIQUID TUBE SUSPENSION A05242 Fig. A94026 Fig. 2 - Connecting Tube and obtain required R-22 retrofit. STEP unit 1 --Check Unpack Heat changes Using Puron(R) for specific Equipment and Job Refrigerant applications to and for Site STEP 3 --Clearance When installing, wiring, refrigerant carton taking care not to damage Equipment company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches STEP 2 --Install on a Solid, job specifications. Level Mounting Pad in./ft.) per Requirements allow sufficient space for airflow clearance. piping, and service. Allow 30-in. clearance to so water, snow. or ice from roof or eaves locate at least cannot fall on unit. On rooftop surface. applications, STEP 4 --Operating File claim with shipping _+2° (_+3/8 service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 skle of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. directly Remove Locations NOTE: Unit nmst be level to within compressor manufacturer specifications. Position Unit Move to final location. unit. Inspect Pumps Knockout Installation Specifications for this unit in residential new construction market require the outdoor unit, indoor unit, refrigerant tubing sets, metering device, and filter drier listed in presale literature. There can be no deviation. Consult the Service Manual - Air Conditioners 3 - Tiedown unit 6 in. above roof Ambient The minimum outdoor operating ambient in cooling mode is 55°F without low ambient cooling enabled and the maximum outdoor operating Infinity " 25HNA9), ambient in cooling mode is 125°F. communicating systems only (for both 25HNA6 low ambient cooling is available to 0°F. On and If conditions or local codes require the unit be attached to pad. tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. The maximum outdoor operating ambient in heating mode is 66°F on all models. Continuous operation in the heating mode is 3 to determine base pan size and knockout STEP 5 --Elevate For hurricane tie downs, Certification (Professional contact hole location. distributor Engineer), for details wind baffles. System Air Refrigerant units exposed Consult the Conditioners to winds above to building. 5 mph may require Service Manual - Residential Split and Heat Pumps Using Puron(R) for wind baffle construction. Unit if required. unit and minimize transmission of vibration local codes governing rooftop applications. Roof mounted to -30°F. and PE On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support Consult approved UNIT OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation. Do not allow water Elevate unit per local clearance above drainage of unit. and/or climate estimated ice to build up in base pan. and code requirements snowfall level and ensure to provide adequate 7. Connect equalizer on vapor 8. Attach UNITOPERATION HAZARD Failure tofollowthiscaution mayresult inequipment damage orimproper operation. Locate theunitin suchawaythatit is stable inall circumstances including adverse weather conditions. STEP6--InstallTXV NOTE:Applies tonon-TXV indoor unitsonly.If installing a ratedandapproved indoorcoilwithouta factoryinstalled Puron(_ TXV,remove andreplace thefixedorifice orR-22TXV expansion device withahardshutoff Puron TXV. Thethermostatic expansion valveis specifically designed to operate withPuron(a) refrigerant. DonotuseanR-22TXV.An existing R-22TXVmustbereplaced witha factory-approved TXVspecifically designed for Puronrefrigerant. Referto Product Data Digest fortheappropriate TXVkitnumber. using tube of TXV to 1/4-in. TXV bulb clamps 9. Proceed to horizontal provided. insulation tape. sensing bulb. _.10 equalizer fitting line adapter. See section Insulate Fig. with remainder bulb 4 for of suction line with field-supplied correct positioning of of unit installation. O'CLOCK SENSING 2 O'CLOCK] L_'SUCTION TUBE 8 O'CLOCK 4 O'CLOCK 7/8 IN. OD & SMALLER LARGER THAN 7/8 IN. OD A81032 Fig. UNITOPERATION HAZARD Failure tofollowthiscaution mayresult inequipment damage orimproper operation. Allindoor coilunitsmust beinstalled withahard shut offPuron® TXVmetering device. Replacing indoor The TXV coil as possible mounting the inlet should be mounted and in a vertical, tube upright vertically susceptible to malfunction down. A factory-approved down. as close to the position. Valve Avoid is more due to debris if inlet tube is facing filter drier must be installed in the 1. Pump system 2. Remove cabinet. Installing TXV in Place 1. Pump system down to 2 psig and recover refrigerant. 2. Remove hex nut from piston body. Use backup fan coils. 3. Remove and discard factory-installed piston. Be NOTE: hex nut. Finger If the piston not function tighten is not removed sure the body, TXV will properly. 4. Remove using a backup R-22 5. Using wire cutters, tube inside cabinet. 6. Remove damage bulb from vapor 7. Braze equalizer DAMAGE damage adapter to suction tube off flush closed. damage with vapor Use protective barrier as to drain pan. tubing. or valve, TXV support equalizer hole) to attach TXV to distributor. clamp (removed in item 3). See Fig. 4 for correct tube through in fitting panel inlet of TXV. marked excessive suction and "IN" heat which could damage positioning connection install in same supplied fitting to liquid of opening panel in line. Avoid valve. 13. Install vapor elbow with equalizer adapter to vapor line of line set and vapor connection to indoor coil. Adapter has swivel outlet. Use backup wrench to avoid damage to tubing or valve. Sweat inlet of TXV. marked "IN" to liquid line. Avoid excessive heat which could damage valve. with equalizer flare the equalizer tube of Puron TXV through opening in fitting panel prior to replacing to tubing a 1/4-in. elbow on 10. Attach TXV bulb to vapor tube inside cabinet, location as original was when removed, using 12. Sweat TXV with wet cloth or 5. Install TXV on indoor coil liquid line. Sweat adapter to inlet of indoor coil and attach to TXV wrench 8. Install TXV with 3/8-in. copper tubing through small hole in service panel. Use wrench and backup wrench, to avoid (large place. HAZARD Use a brazing shield and wrap use heat sink material. nut driver. tube inside cabinet. stub-tube to prevent a 5/16-in. front of to tubing. cut equalizer copper bulb clamps. sensing bulb. Failure to follow this caution may result in equipment damage or improper operation. 6. Install vapor TXV to prevent refrigerant. panel from using 11. Route EQUIPMENT and fitting clamp 9. Reinstall nut plus 1/2 turn. from panel on Teflon seal is in place. 4. Reinstall Coil 3. Remove TXV support Save the clamp. fitting panel around wrench Bulb down to 2 psig and recover IMPORTANT: Route suction line connection of Piston of Sensing Indoor coil access necessary liquid line. Position TXV on R-22 connections IMPORTANT: 4 - tube of line set and suction connection to indoor coil. Adapter has a 1/4-in. male connector for attaching equalizer tube. male connector for attaching equalizer tube. 14. Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor line adapter. Use backup wrench to prevent damage 15. Proceed to equalizer fitting. with remainder of unit installation. STEP 7 --In Solenoid For Long-Line Applications, Install Liquid-Line Valve (LSV) refrigerant piping arrangements with equivalent lengths greater than 80 ft. and/or when elevation difference between indoor and outdoor unit is greater than _+20 ft.. follow all requirements of the Long-Line Guideline--Air Conditioners and Heat Pumps Using Long-Line Guideline. UNIT Failure damage Puron® refrigerant. If required by install LSV kit, part no. KHALS0401LLS, toward included with accessory IMPORTANT: STEP outdoor unit. Follow the Installation to follow this caution or improper operation. Piping Instructions outdoor AND UNIT DAMAGE DAMAGE this warning could result in personal HAZARD Failure damage to follow this caution or improper operation. Observe the following: • Use a brazing HAZARD to follow this caution or improper operation. with wet cloth or use a heat sink 80 ft., substantial capacity and performance Following the recommendations in the may result sealed during in equipment Outdoor Unit Connected Outdoor unit Check Connections Information and Recommended is Specific Manual-Residential Split-System Pumps Using Puron® Refrigerant contains to Factolw-Approved correct system diameters. Indoor refrigerant Air will Unit: charge to 25HNA6 refrigerant Liquid charge and Vapor and 25HNA9 for maximum Tube efficiency. Diameters (In.) Models R&TED LIQUID VAPOR (up to 80 ft. T.E.L) UNIT SIZE Connection Diameter Notes: t. ,., 2. 3. for operation with factory approved ARI rated indoor unit with highest sales volume when connected by 15 ft. of field-supplied or factory-accessory tubing, and factory supplied filter drier. installation. Table 1--Refrigerant losses can Application reduce these losses. Refer to Table 1 for field tubing Refer to Table 2 for accessory requirements. Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing n in equipment Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements Guideline and Service Conditioners and Heat Failure damage result material. beyond occur. DAMAGE may shield. • Wrap service valves Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow-control devices, including solenoid valves. UNIT in equipnmnt Connections INJURY Failure to follow injury or death. result unit. UNIT PERSONAL HAZARD may kit. Flow arrow must point toward 8 --Make HAZARD If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. Do not bury lines longer than 36 in. specifically designed for Puron® refrigerant heat pumps. LSV should be installed within 2 ft. of outdoor unit with flow arrow pointing DAMAGE Tube Diameter Connection Diameter Tube Diameter 25HNA624 3/8 3/8 5/8 5/8 25HNA636 3/8 3/8 3/4 3/4 25HNA648 3/8 3/8 7/8 7/8 25HNA660 3/8 3/8 7/8 1 1/8 25HNA924 3/8 3/8 3/4 3/4 25HNA936 3/8 3/8 3/4 7/8 25HNA948 3/8 3/8 7/8 7/8 25HNA960 3/8 3/8 7/8 1 1/8 Tube diameters are for total equivalent lengths (TE.L.) up to 80 ft. Consult the Long Line Guideline refrigerant. Do not apply capillary tube or the fixed orifice indoor coils to these units. T.E.L. - Total Equivalent Length Air Conditioners and Heat Pumps using Puron@ REQUIRED Accessory Crankcase Table 2--Accessory Usage FOR LOW-AMBI- REQUIRED ENT APPLICATIONS (Below 55 °F) Standard Heater FOR LONG LINE REQUIRED APPLICATIONS* (Over 80 ft.) Standard FOR SEA COAST APPLICATIONS (Within 2 miles) Standard Standard with Infinity Control Evaporator Freeze Protection Winter (Low Ambient not allowed with noncommunicating thermostat) No No No No Standard on 25HNA6 models. Standard on 25HNA6 modets. Not required on 25HNA9 models Not required on 25HNA9 modets Standard on 25HNA6 modets. since compressor since compressor Standard with infinity Control (Low Ambient not allowed with non- Start Control communicating thermostat) Compressor Start Assist Capacitor and Relays n Low-Ambient Control always starts Not required on 25HNA9 models since compressor always starts unloaded, unloaded, Standard with Infinity Control (Low ambient not allowed with non-commu- No always starts unloaded. No nicating thermostat) Support Feet Liquid Line Solenoid Recommended Valve No No Ball Bearing Fan Motor Puron Balance Port Hard Shut-Off TXV Recommended Yes Standard No Standard Yes1- Standard Yes1- Yest For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (Total Equivalent Length), ers and Heat Pumps using Puron(_) refrigerant. tRequired on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils. refer to the Long Line Guideline Air Condition- $ Information is specific to 25HNA6 and 25HNA9 models. Install Liquid-Line Filter Drier Indoor Refrigerant Refer to Fig. 5 and install filter drier as follows: 1. Braze 5-in. Connect liquid tube to the indoor coil. 2. Wrap filter drier with damp cloth. 3. BrazefilterdriertoabaveS-in. point towards indoor coil. 4. Connect liquid tube.Flowarrowmust and braze liquid refrigerant tube to the filter drier. Tubing vapor connection tube valves (see Table 1). Install Adapter Outdoor to fitting on outdoor unit retainer 2. Check outdoor piston unit rating plate. holding outdoor size with matching 3. Locate plastic bag taped to unit containing Teflon_R3 washer open end of liquid service DAMAGE HAZARD Failure to follow this caution or improper operation. Installation of filter drier may result in equipment in liquid damage 5. Remove adapter to liquid service Sweat piston in liquid number listed on adapter tube. from bag and install on wdve. tube from bag and connect threaded nut valve. Tighten nut finger tight and then with wrench tighten an additional DO NOT OVERTIGHTEN! line is required. service Tube 1. Remove plastic service valve. 4. 4. Remove UNIT vapor 1/2 turn (15 ft-lb). Connections UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Service material valves must be wrapped such as a wet cloth. in a heat-sink Use refrigerant grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with A05227 Fig. 5 - Liquid Line Filter Drier a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints. Refrigerant Tubing and Indoor Coil I EVACUATE I m Evacuate [BREAK VACUUM WITH DRY NITROGEN UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Never use the system compressor as a vacuum [EVACUATE I pump. [BREAK VACUUM WITH DRY NITROGEN Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate outlined nitrogen. [EVACUATE] triple evacuation method may be used if the procedure below is followed. Always break a vacuum with dry CHECK Deep Vacuum The deep vacuum method requires a vacuum pump capable TIGHT, FOR (IF Method IT HOLDS DRY SYSTEM VACUUM) DEEP of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum I CHARGE SYSTEM I method Fig. Method is the most positive way of assuring a system A95425 is free of air and liquid water. (See Fig. 6) Final Tubing 5000 IMPORTANT: 4500 indoor 7 - Triple Check Check and outdoor close attention LEAKIN SYSTEM _3500 against to feeder tubes are secure g3000 to be certain factory unit has not shifted during tubes are not rubbing 4000 Evacuation tubing on shipment. both Ensure each other or any sheet metal. Pay tubes, making sure wire ties on feeder and tight. STEP 9 --Make Electrical Connections _2500 2000 VACUUM TIGH'T TOO WET 15001000 ELECTRICAL TIGHT DRY SYSTEM 500 Failure injury 1 2 3 4 MINUTES 5 6 SHOCK to follow HAZARD this warning could result in personal or death. Do not supply power box cover removed. to unit with compressor terminal A95424 Fig, 6 Triple Evacuation Deep Vacuum Graph Be sure field wiring and electrical codes, Method The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain Fig. 7 and proceed as follows: 1. Pump system to continue 2. Close down operating service valves any liquid water. Refer to for an additional and allow pump and shut off vacuum to system as indicated then be free of any contaminants in Fig. 7. System and water vapor. Operation and could not install unit permissible NOTE: unit. pump. of unit on improper affect unit reliability. in system line voltage constitutes See unit rating where voltage wire only between plate. may fluctuate above Do or limits. Use copper disconnect switch and and NOTE: 4. Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture. this procedure NOTE: below 15 minutes. 3. Connect a nitrogen cylinder and regulator open until system pressure is 2 psig. 5. Repeat on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device. abuse to 28 in. of mercury complies with local and national fire, safety, and voltage to system is within limits shown will NEC Install to handle sight from of NEC. Route branch unit and readily Ground circuit starting disconnect current. accessible and Power of adequate Locate size per disconnect within from unit, per Section 440-14 Wires Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box. STEP 10 --Compressor Furnish ELECTRICAL SHOCK HAZARD Failure to followthiswarning couldresultin personal injuryordeath. Theunitcabinet musthave anuninterrupted orunbroken ground tominimize personal injuryif anelectrical fault should occur. Theground mayconsist ofelectrical wireor metalconduit wheninstalled in accordance withexisting electrical codes. Connect Ground Connect and Power ground safety. Connect Wiles wire to ground power wiring to contactor in control as shown box for in Fig. 8. DISCONNECT PER N. E. C. AND/OR LOCAL CODES to crankcase starting unit. To furnish OFF and close electrical NOTE: On 25HNA6 minimum a minimum of 24 hr before starting of crankcase the compressor to without a heat prior to initial start-up chattering noise and possible damage to the compressor. STEP 11 --Install Refer to accessories Accessories the individual when installing. 12 --Make Only stats Using Airflow instructions Airflow Selection packaged Selections Non-Communicating The 58CVA/58MVB low-stage blower CONTACTOR heater models, of 12 hours Heater power to heater only, set thermostat disconnect to outdoor unit. may result in a compressor STEP connection power Crankcase for 25HNA6 (Non-Infinity) for 58CVA/58MVB variable operation with kits or Series Thermo- Furnaces speed furnaces to match the provide high-and capacities of the compressor at high and low stages. To select the recommended airflow and for adjustments to the manual switches labeled SWl-5. AC, and CF on the control board refer to the furnace FIELD POWER WIRING Installation. Start-UR and Operating Instructions. The 58CVA/58MVB utilizes a control center that allows the installing FIELD GROUND technician determines WIRING GROUND LUG A91056 Fig. 8 Connect Control Line Power to select the proper the airflow during high Airflow for high- and low-stage CFM per ton or 400 CFM per SWl-5. airflows. The HP switch stage compressor operation. can be calculated at either 350 ton, based on the positions of Connections Wiring Route low voltage control wires through and connect leads to control board. control wiring grommet When using communicating (Infinity) control, dipswitch adjustments are not necessary on furnaces. Airflows are determined by Infinity Control setup. Airflow Selection for FK4 or FV4 Fan Coils for 25HNA6 For 25HNA9 models, connect to Infinity connections ABCD only. Standard non-communicating thermostats are not allowed Series Only Thermostats unless it is an emergency that User Interface is not working properly and new User Interface is not available. For emergency use, connect to standard thermostat connections R, C, W. Y1. Y2, and O. The FV4 provides high- and low-stage blower operation to match the capacities of compressor at high- and low-stage. To select recommended airflow, refer to FV4 Installation NOTE: Instructions. allows the When unit is operating light will flash rapidly. Unit will operate For 25HNA6 models, connect standard thermostat connections General mode, STATUS in high stage ONLY. to ABCD for Infinity Control R. C, Wl, Y1. Y2. and O. or color-coded, All wiring must be NEC incoming power leads. furnace transformer, insulated Class fan (35°C 1 and must coil minimum) wire be separated from transformer, or accessory transformer for control power, 24v/40va minimum. The outdoor unit requires a minimum of 27va/24vac control power. Final Wiring IMPORTANT: to ensure Check Check factory terminations wiring are secured to ensure wires are not in contact and field wire connections properly. with tubing, Check wire routing sheet metal, etc. Non-Communicating adjustments to control CFM ADJUST setting. For other Digest. (Non-Infinity) The FV4 utilizes an Easy Select control board installing technician to select proper airflows. delay factory operation. Information Use No. 18 AWG for all installations. Use in enmrgency Using set board, select appropriate HP SIZE and This fan coil has an adjustable blower off at 90 combinations that For sec for of high- equipment and low-stage Consult Product blower Data STEP 13 --Start-Up STEP 14 --SYSTEM OPERATION The outdoor following UNIT OPERATION AND SAFETY Failure to follow this caution may result in minor injury, equipment damage or improper operation. Observe The personal unit in a vacuum • Do not disable low pressure • Dome temperatures system has or at negative special of the two-stage OF functions. control The functions: Operation model utilizes either a standard for first stage cooling, the outdoor stage compressor are energized. system with refrigerant. • Do not operate and Heating 25HNA6 AND SEQUENCE indoor thermostat or Infinity Communication User Interface. The 25HNA9 models utilize an Infinity communicating User Interface only. With a call the following: • Do not overcharge control is an overview Cooling HAZARD unit FUNCTIONS fan, reversing If low-stage valve, and low cannot satisfy cooling demand, high-stage cooling is energized by the second stage of indoor thermostat or User Interface. After second stage is pressure. switch satisfied, the unit returns to low-stage operation until first stage is satisfied or until second stage is required again. When both first stage and second stage cooling are satisfied, the compressor will may be hot. shut off. The reversing valve will remain energized until the control board power is removed or a call for heating in initiated. PERSONAL Failure INJURY to follow this caution Wear safety glasses, handling refrigerant. With a call for heating, the outdoor fan and compressor are energized. The compressor will operate in high or low stage operation, as needed to meet the heating demand. When the HAZARD may result in personal protective clothing, injury. and gloves heating demand is satisfied, the compressor and fan will shut off. The reversing valve is de-energized in the heating mode. when NOTE: When vapor two-stage (suction) single-stage NOTE: minute unit is operating pressure will system or high-stage Outdoor fan motor after compressor be than system a standard operation. will shuts at low-stage, higher continue off. to operate when outdoor for one ambient is within the greater than or equal to 100°F. ENVIRONMENTAL Failure to follow damage. this caution Federal require result in environmental Recover to propedv start during temperature. temperature up the system: seat (open) liquid front seated (closed) caps after system is to energize or User caps 1/12 system. Interface at desired Be sure set point is below indoor and is set low enough to energize ambient desired stage. control thermostat For (non-Infinity) equipped or User Interface to ON or AUTO 15 minutes. NOTE: Check mode, system 25HNA6 Series thermostat. with a 15-minute as desired. refrigerant only Carrier staging using Operate timer. This timer in low stage for 15 minutes, unless between and thermostat stage (after and fan control or User Interface to AUTO appropriate time delay(s). Check refrigerant charge. operates O is powered for a For Infinity Light on. and Status Control Function only, Green Lights communications (COMM) A green LED (COMM light) on the outdoor board (see Fig. 9) indicates successful communication with the other system products. The green LED will remain OFF until communications is established. Once a valid command is received, the green LED will turn ON continuously. If not communication is received within 2 minutes, the LED will be turned OFF until the next valid communication. Status Light mode and fault codes as specified in the troubleshooting See Table 5 for codes and definitions. prevents NOTE: colored Only STATUS light is used to display one code will are control board the Utility Interface there is at least a 5°F of 2 minutes adjust the set point at least 5°F below room 6. Set room thermostat unit be displayed (the most recent, the operation section. on the outdoor with the highest unit priority). at high stage until unit has been temperature a minimum demand, the next in high-stage. unit for thermostats difference low-stage upon An amber non-communicating electronic operating room or power-up, and fan charge. system high from operating to COOL two-stage force energized, Amber 5. Set room high- of 5 minutes Communication disconnects thermostat if unit has not operated a unit and with second stage of cooling, Y1, Y2, and O are on. For these systems, with first stage of heating Y1 is on and for second stage of heating, Y1 and Y2 are on. When the reversing valve is opened to refrigerant flow (back seated). Replace finger-tight and tighten with wrench an additional turn. 3. Close electrical models, or following On 25HNA6 models with non-communicating (non-Infinity) systems, with first stage of cooling, Y1 and O are powered on; system fully back 2. Unit is shipped with valve stem(s) and caps installed. Replace stem room thermostat that you do not vent 1. After system is evacuated, and vapor service valves. 4. Set On 25HNA6 12 hours, minimum regulations these steps past may refrigerant to the atmosphere. repair or final unit disposal. Follow NOTE: HAZARD or ON, Operate set point. To in low stage), ambient. to HEAT as desired. unit for or COOL Wait for 15 minutes. With Infinity Control The utility curtailment relay connections on the control should board be wired between R and Y2 for Infinity Communicating Systems only (see Fig. 9.) This input allows a power utility device to interrupt compressor operation during peak load periods. When the utility sends a signal to shut the system down, the User Interface will display, "Curtailment Active". One Minute When Stage Change compressor Time changes Delay on 25HNA6 stages from high high, there is a 1-minute time delay before The outdoor fan motor remains running. ('ompressor When Operation the compressor compressor on 25HNA6 Models operates high in stage When Time • compressor The lower refrigerant. compressor operates in low stage Five minute time delay to start cooling or heating operation when there is a call from the thermostat the and upper and both operation, include: or user interface. To bypass this feature, momentarily short and release Forced Defrost pins. refrigerant. the Delays The unit time delays restarts. operation, compressor motor rotates clockwise. Both the lower pistons are eccentric with the rotating crankshaft compress Models to low or low to • Five minute a brown-out compressor condition. • Two minute time delay to return to standby the re-cycle from last valid conmmnication motor reverses direction (rotates counterclockwise). piston becomes idle and the upper piston compresses The start and run windings ale reversed. • One minute cooling delay on return from time delay of outdoor mode when outdoor operation (with Infinity only). fan at termination ambient of is greater than or equal to 100°F. Crankcase Heater Operation • The crankcase of outside heater is energized air temperature during Fifteen unit off cycle regardless (OAT) on 25HNA6 models. • The crankcase heater is energized 25HNA9 models. Outdoor The Fan Motor outdoor unit during off cycle below energizes outdoor fan Twenty 65°F on any time compressor is operating, except for defrost. The ouMoor fan remains energized if a pressure switch or compressor overload Thirty second enabled. • On 25HNA6 between of defrost before is de-energized. delay at termination of defrost before fan is energized. • compressor models staging delay when quiet shift there is a 1 minute time delay from low to high and from high to low capacity. On 25HNA9 models there is no delay; the compressor will change from low to high and from should open. Outdoor fan motor will continue to operate for one minute after the compressor shuts off when the outdoor ambient is greater than or equal to 100°F. On 25HNA6 outdoor fan remains energized during the 1-minute staging time delay. delay at termination heat (Wl) second the outdoor Operation control second the auxiliary high to low capacity models, the compressor Compressor Operation on the fly to meet the demand. on 25HNA9 Models: When the compressor is operating in low stage, the modulating ring is de-activated, allowing two internal bypass ports to close off 33% of the scroll compression area, so the system operates part load capacity. The 24volt solenoid coil is de-energized at in low stage operation. When the compressor is operating in high stage, the modulating ring is activated, sealing the bypass ports, which allows the compressor to operate at full load capacity. The 24volt solenoid coil is energized in high stage operation. The contains a 230v to 24vac transformer to supply solenoid when it is energized. The compressor should not be included in the system power transformer sizing. 10 (furnace 25HNA9 unit power to the solenoid load or fan coil) control O I PWM2 .u'_O , fZII] 0 OO O rl rl 0 0 0 © sR[_ O oo [] [] 0 O0 MODEl. rlquid * SUPPLIED BY UTILITY B MODEL O EEIEEI Lille Solenoid PROVIDER A05247 Fig, GENERAL Control INFORMATION Low Ambient Controned low ambient This unit is capable when using Infinity temperature. This control 120 minutes, cooling: of low ambient cooling without a kit ONLY control. A low ambient kit is not required, up. Fan may not begin to cycle until about 40°F cycle based on coil and outdoor air temperature. low ambient models, • mode operates OAT. Interface AUTO defrost Fan will as follows: (the dip switches by dip switches • When • off to allow refrigerant defrost for first 3 minutes When The time 3-5 minutes, board the next defrost the next defrost time 5-7 minutes, the next defrost accumulates the next defrost compressor compressor running. If LPS closes within 10 minutes then cooling continues with the outdoor fan cycling per The defrost the coil temperature routine listed above for the remainder of the cooling cycle. If the LPS does not close within 10 If the coil temperature does not reach 32°F the interval timer will be reset and start over. then the normal LPS trip response and generate (shut time. As the defrost demand. If a defrost demand exists, a defrost cycle will be initiated at the end of the selected time interval. A defrost demand during exists when the coil temperature minutes during the interval. operation run accumulated run time approaches the selected defrost interval time, the control board monitors the coil temperature sensor for a low ambient start up. After 3 minutes, ifLPS trips, then outdoor fan motor is turned off for 10 minutes, with the minutes, on the last minutes. When defrost time >7 minutes, interval=30 minutes. control time based minutes. defrost interval=60 system to Fan is ON when outdoor coil temp > (outdoor air temperature + 25°F) or outdoor coil temp > 80°F or if interval When defrost time <3 minutes, interval= 120 minutes. minutes. (Fan is turned stabilize.) cooling on the are not used.) defrost adjusts the defrost time as follows: • • switch is ignored 30. 60, 90, On 25HNA9 , the defrost interval times: 30, 60, 90, and 120 minutes or AUTO are selected by the Infinity Control User Fan is OFF when outdoor coil temp is < (outdoor air temperature + 3 °F) or outdoor fan has been ON for 30 Low pressure times: settings. outdoor fan has been OFF for 30 minutes. (Fan is turned on to allow refrigerant system to stabilize.) • interval these are selected interval=90 • defrost unit control board or by the Infinity Control User Interface. The Infinity Control selection overrides the control board dip switch provides an automatic evaporator coil freeze protection algorithm that eliminates the the need for an evaporator freeze thermostat. Low ambient cooling must be enabled in the User Interface set cnntrolled offers 5 possible or AUTO. On 25HNA6 and the outdoor fan motor does not need to be replaced for Infinity controlled low ambient operation. The Infinity Control Infinity Board Defrost Cooling When this unit is operating below 55°F outdoor provisions must be made for low ambient operation. Infinity 9 - 2-Stage 65°F down • LPS trip error) will occur. cycle is terminated or 10 minutes Upon 11 32°F when the coil temperature for 4 reaches has passed. initial power within up the first defrost defaulted to 30 minutes. selected times. • is at or below Defrost is only allowed ambient temperature. Remaining the interval, interval intervals to occur below 50°F is are at outdoor Defrost Hold STEP On 25HNA6 models, in a non-comnaunicating system, thermostat becomes satisfied (Y1 or Y1 and Y2) defrost cycle is terminated, the control will "Hold" mode and finish On 25HNA6 all 25HNA9 the defrost the User Interface down the system. 2-pin header control board and 25HNA9 with communicating (Infinity) defrost is initiated with the User Interface. On all models, during • a Forced If coil temperature and outdoor air temperature defrost sequence • If coil temperature or outdoor of 32°K a full do not an abbreviated 30 second Accesso D, Control: solenoid solenoid Liquid When Models See with Infinity Communicating Infinity control, the liquid line solenoid refrigerant with Accessory Thermostat: and C terminal Only Procedure requires Liquid Solenoid The liquid connections. charging by the subcooling operate unit a minimum method. of 10 minutes high stage before checking charge. On 25HNA6 models, charging in low stage compressor damage chattering and possible in may cause to the Using liquid service gage to service valve pressure by attaching an port. subcooling high stage temperature is higher than indicated or reclaim refrigerant if temperature is lower. Allow a tolerance of _+3°F. output that is energized whenever the compressor is energized. It closes, in the compressor off mode. to prevent refrigerant migration into the unit through the liquid line. Non-Communicating connect to the Y1 plate, 6. To obtain required subcooling temperature at a specific liquid line pressure, add refrigerant if liquid line output is provided at the Y1 connection. Connect the as shown in the wiring label diagram. This is a 24vac On 25HNA6 rating pressure. Accessory Solenoid using the unit operation. In heat pump long-line applications, a liquid line solenoid is required to control refrigerant migration in the heating mode. The solenoid should be installed near the outdoor unit with the arrow of flow control. details. are not favorable. 5. Refer to Table 3. Find the point where required subcooling temperature intersects measured liquid service valve mode. facing the outdoor unit. This is the direction application manual for long-line application with 4. Refer to unit rating plate for required temperature. Subcooling amount is for sequence of operation will occur. Reversing valve and compressor will turn off for 30 seconds, then Line Solenoid conditions in accordance 3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil. turn back on to complete defrost. At the end of the defrost cycle. the reversing valve de-energizes, compressor will turn off for another 30 seconds, and the fan will turn off for 40 seconds, Liquid charging in in unit plate. accurate selecting the 3rd position of the 3-position dip switch. For 25HNA6 and 25HNA9 models with communicating (Infinity) systems, it must be enabled at the User Interface. When activated, in the heating unit the charging chart on the outdoor 2. Measure cycle and restarting of the heating cycle. On 25HNA6 models with non-communicating system, this feature must be enabled by starting on compressor. Shift before shown line above or below 15 ft.. fall within the ranges given on Cooling Quiet Shift is a field selectable defrost mode which may eliminate occasional noise that could be heard at the start of the defrost the following will energize be weighed 1. On all unites, air temperature are To calculate additional charge required for a 25-ft. line set: 25 ft. - 15 ft. = 10 ft. X 0.6 oz./ft. = 6 oz. of additional charge. will occur. meet the above requirements, defrost will occur. Quiet is below 50°K method _+0.6 oz./ft, of 3/8-in. liquid respectively. Favorable conditions This system temperature charging EXAMPLE: Defrost: is at defrost and If subcooling charge must (see Fig 9) on the On 25HNA6 control, forced charge NOTE: will complete with non-communicating (non-Infinity) can be initiated by manually shorting the labeled FORCED DEFROST for 5 seconds then releasing. Charge information plate. Charge Puron refrigerant units with cylinder inverted position and a commercial-type metering device manifold hose. Charge refrigerant into suction line. Defrost On 25HNA6 models control, forced defrost n Factory cycle on the next call for heat. because shutting 15 --Check Unit Charge before the in defrost models, with communicating Infinity Control and models, defrost hold is not needed in a communicating system the defrost cycle before Forced if the a solenoid is The liquid closes, in the compressor off mode. to prevent migration into the unit through the liquid line. 12 Heating Check Chart To check system Procedure operation is necessary during cycle, refer to the Heat charge must be weighed in accordance with label on outdoor relationship exists unit. This chart between system _+0.6 oz./ft, of liquid during Pump Charging Instructions indicates whether a correct NOTE: heating In heating mode, pressures are stable. If in doubt, correct refrigerant check refrigerant remove charge charge 3/8-in. line above heating unit or rating below season, plate, 15 ft., EXAMPLE: To calculate additional charge required for a 25-ft. line set: 25 ft. - 15 ft. = 10 ft. X 0.6 oz./ft. = 6 oz. of additional charge. charge. NOTE: charging respectively. operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. Do not use chart to adjust refrigerant When only when and weigh in charge. Table 3--Required LiQUiD PRESSURE AT SERVICE VALVE (PSIG) LiquidlLine REQUIRED Temperature SUBCOOLING (°F) TEMPERATURE (°F) 8 10 12 14 16 18 189 58 56 54 52 50 48 195 60 58 56 54 52 50 202 62 60 58 56 54 52 208 64 62 60 58 56 54 215 66 64 62 60 58 56 222 68 66 64 62 60 58 229 70 68 66 64 62 60 236 72 70 68 66 64 62 243 74 72 70 68 66 64 251 76 74 72 70 68 66 259 78 76 74 72 70 68 266 80 78 76 74 72 70 274 82 80 78 76 74 72 283 84 82 80 78 76 74 291 86 84 82 80 78 76 299 88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96 94 92 90 88 86 345 98 96 94 92 90 88 354 100 98 96 94 92 90 364 102 100 98 96 94 92 374 104 102 100 98 96 94 384 106 104 102 100 98 96 395 108 106 104 102 100 98 406 110 108 106 104 102 100 416 112 110 108 106 104 102 427 114 112 110 108 106 104 439 116 114 112 110 108 106 450 118 116 114 112 110 108 462 120 118 116 114 112 110 474 122 120 118 116 114 112 486 124 122 120 118 116 114 499 126 124 122 120 118 116 511 128 126 124 122 120 118 13 n MAJOR 2-Stage Control Systems Board The HP control n TROUBLESHOOTING COMPONENTS board controls • High • Outdoor • Reversing • Defrost • Low ambient • Crankcase • Compressor • Pressure • Time Delays • On 25HNA6 the following and low stage compressor functions: contactor If communication operation valve operation The control heater operation external Pressure protection The switch monitoring models, board outdoor only) On 25HNA6 models with communicating system 25HNA9 models, use the ABCD Infinity Connections. contains Compressor Relief motor Refer windings to Table is protected by an internal pressure discharge gas into the compressor The compressor is also protected to motor windings. Compressor Control and and fan operating the appropriate a 15 minute all call for cooling 7. In correct the for 15 minutes delay, if there is a call for cooling reset, the or appropriate or heating. event high-pressure of a high-pressure lockout, check 8. In the event of a low-pressure lockout, check the refrigerant relief (IPR) shell when (cooling) heating. by an internal overload Control the the appropriate be replaced. board and outdoor cycles, the switch trip refrigerant unit or charge, coil (in cooling) in heating. for switch trip or low-pressure charge and indoor airflow fan operation and outdoor coil in Fault If the outdoor Contactors control contactor fault code (see Table 5) 6. If LPS or HPS trips 3 consecutive operation is locked out for 4 hours. pressure exceeds psi on 25HNA9 The contactor(s) have a 24volt coil. The electronic controls the operation of the appropriate contactor. or low 5. If LPS or HPS has not closed after a 15 minute delay, the outdoor fan is turned off. If the open switch closes anytime after the 15 minute delay, then resume operation with a that provide 4 for If a low-pressure of a high compressor outdoor fan operation, and outdoor airflow restrictions, or indoor airflow differential between suction and discharge 500-550 psi on 25HNA6 models and 550-625 models. attached high- heating and LPS or HPS is compressor contactor is energized. Compressor operation. with the appropriate 2. Keep the outdoor connections located at the bottom of the control board (see Fig. 9.) On a non-communicating system, output W1 is connected at the bottom of the control board for auxiliary heat. 2-pole (3500 RPM) winding resistance. plug to operate. not operate and the shown in Table 5. Protection 1. De-energize 4. After The compressor which relieves must have a valid model unit is equipped On 25HNA6 models with non-communicating (non-Infinity) System, the two-stage control receives 24vac low-voltage control system inputs through the R, C, Y1, Y2 and O Internal control is lost with the User switches. If the control senses the opening pressure switch, it will respond as follows: high and low stage start relay and (Bristol Switch 3. Display The two stage compressor the Infinity valid model plug is not detected, it will control will flash the appropriate fault code, cooling Field Connections Two Stage with Model Plug operation operation Failure Interface, the control will flash the appropriate fault code. (See Table 5.) Check the wiring to the UI and the indoor and outdoor units. fan motor operation capacitor Communication Brown-Out unit control board has failed, the control fault code (see Table 5). The control will flash board should Protection If the line voltage is less than 187v for at least 4 seconds, the appropriate compressor contactor and fan relay are de-energized. Compressor and fan operation are not allowed until voltage is a minimum of 190v. The control will flash the appropriate fault code (see Table 5). 230V Line (Power Disconnect) Detection If there is no 230v at the compressor contactor(s) when the indoor unit is powered and cooling or heating demand exists, the appropriate fault code is displayed. Verify the disconnect and 230v wiring is connected to the unit. Compressor Voltage The board control is dosed Sensing input terminals labeled VS. VR and L2 on 25HNA6 models and VS and L2 on 25HNA9 models (see Fig. 9) are used to detect compressor voltage status, and alert the user of potential problems. The control continuously monitors the high voltage on the run capacitor of the compressor motor. Voltage should be present any time the compressor contactor and voltage should not be present when the de-energized. 14 is energized. contactor is Contactor Shorted Detection If there is compressor voltage sensed when there is no demand Troubleshooting 25HNA6 low & hiuh staues for Check 25HNA6 liquid pressure when switching from low to high capacity. Compressor current should increase 100-250% when switching from low to high stage. Compressor Thermal Cutout Troubleshooting inputs will indicate the thermal protector is closed. If the phase difference is 5 degrees or less for 10 seconds, the internal protector is open. The control de-energizes the appropriate cooling or heating, the appropriate 15 minutes. minute interval If the thermal check), protector closes, the unit will resume 25HNA9 at the units for proper Check the suction pressures at the pressure should be reduced by 3-10% service switching between service valves. when switching Suction from low NOTE: compressor high The liquid pressures stage operation, are very so liquid similar pressure between should troubleshooting. Compressor from low (at the next 15 current to high energized operation. should stage. increase 20-45% The compressor in high stage, should measure when switching solenoid when 24vac. If the thermal cutout trips for three consecutive cycles, then unit operation is locked out for 4 hours and the appropriate fault code is displayed. Thermistors Thermistors are electronic 25HNA9 are used to sense outdoor air (OAT) and coil temperature Refer to Fig. 12 for resistance values versus temperature. If the control senses Thermal the temperature Cutout the compressor voltage then absent for 10 consecutive seconds demand exists, the thermal protector after start-up, and is If the outdoor while cooling or heating is open. The control the has every 15 minutes. the next 15 minute If the thermal operation is locked is displayed. Low- or High Compressor interval cutout check), out for 4 hours Contactor consecutive (25HNA9 cycles, and the appropriate Open (25HNA6 voltage protector the unit will resume trips for three Contractor If the compressor If the thermal models) closes. - Compressor outdoor fail. the control air thermistor insure 11. thermistors are mounted will in the final and coil thermistor locations. properly Check to per Fig. 10 and Fig. The control temperature continuously monitors and compares the outdoor air sensor and outdoor coil temperature sensor to ensure (at operation. proper operating then unit • fault code Comparison conditions. In cooling The comparison if the outdoor air sensor is: indicates >- 10_'F warmer than the coil sensor (or) the outdoor air sensor indicates >- 20°F cooler than the coil sensor, the sensors are out of range. In heating the compressor if the outdoor air sensor indicates -> 35 °F warmer than the coil sensor (or) the outdoor air sensor indicates >- 10°F cooler than the coil sensor, the sensors are out of range. If the sensors are out of range, the control appropriate fault code as shown in Table 5. on The thermistor cooling Failed fault code. comparison or defrost Thermistor Factory outdoor In high stage, if the specified start voltage at VS terminal is not achieved, the start relay is de-energized after 1 second and the control will flash the appropriate fault code. If the specified start voltage is not achieved stage starts, low stage operation is locked (OCT). Sensor In low stage, if the specified start voltage at VR terminal is not achieved, the start relay is de-energized after 1 second and the control will flash the appropriate The mounted / No 230V at Start Detection should As Thermistors Thermistor should be starting, the appropriate contactor may be stuck open or there is a wiring error. The control will flash the appropriate fault code. Check the contactor and control box wiring. 25HNA6 Models Only Bristol Models Only sense temperature. decreases. fault code. (See Table 5.) be factory • when which the resistance should models) is not sensed devices air or coil thermistor IMPORTANT: not re-set, the outdoor fan is turned off. If the call for cooling or heating continues, the control will energize the compressor contactor increases, flash the appropriate de-energizes the compressor contactor for 15 minutes, but continues to operate the outdoor fan. The control Status LED will flash the appropriate code shown in table 5. After 15 minutes, with a call for low or high stage cooling or heating, compressor contactor is energized. If the thermal protector low and not be used for Temperature Compressor valves. to high capacity. contactor is energized. If the thermal protector has not re-set, the outdoor fan is turned off. If the call for cooling or heating continues, the control will energize the compressor contactor every pressures low & hiuh staues compressor contactor for 15 minutes, but continues to operate the outdoor fan. The control Status LED will flash the appropriate code shown in table 5. After 15 minutes, with a call for low or stage and liquid Suction pressure should be reduced by 5-10% when switching from low to high capacity. There should be a 10-20% increase in The control senses the compressor voltage at VR and VS. When starting or running, a phase difference of the voltages on the high suction between compressor operation, the contactor may be stuck closed or there may be a wiring error. The control will flash the appropriate fault code. Models_ the units for pl_oper switching is not performed will during flash the low ambient operation. Default Operation defaults have been provided in the event air thermistor and/or coil thermistor. of failure of If the OAT sensor should fail, low ambient cooling will not be allowed and the one-minute outdoor fan off delay will not occur. Defrost will be initiated based on coil temperature and time. for 3 consecutive low out for 30 minutes. If If the OCT sensor should fail, low ambient cooling will not be allowed. Defrost will occur at each time interval during heating the specified start voltage is not achieved for 3 consecutive high stage starts, high stage operation is locked out for 30 minutes. The control will flash the appropriate fault code. operation, but will terminate after 5 minutes. If there is a thermistor out of range error, defrost will occur at each time interval during heating operation, but will terminate after 5 minutes. Count the number of short and long flashes to determine the appropriate flash code. Table 5 gives possible causes and actions related to each error. 15 OAT Thermistor must be locked in place with spherical nib end facing towards the front of the control box OCT Thermistor must be secured tight on stub tube \ n Fig, 10 - Outdoor Air Thermistor Fig. (OAT) Attachment THERMISTOR 90 11 - Outdoor Coil Thermistor (OCT) Attachment CURVE , 20 40 60 80 TEMPERATURE 100 120 (DEG. F) A91431 Fig. 12 - Resistance Values Versus Temperature Table 4--Two-Stage Compressor Resistances (Winding Resistance at 70°F_+20 °) Winding Status 25HNA6024 25HNA6036 25HNA6048 25HNA6060 Start (S-C) 2.74 1.98 1.55 0.74 Run (R-C) 0.80 0.75 0.48 0.36 Winding 25HNA9024 25HNAg036 25HNA9048 25HNAg060 Start (S-C) 1.40 1.29 1.52 0.60 Run (R-C) 1.32 0.89 0.64 0.49 (:odes Table 5 shows the status codes flashed by the amber flashed by the amber status light on the control board. The codes are flashed by a series of short status and long flashes light. Most of the status system light. problems can be diagnosed The short flashes indicate by reading the first digit the status code as in the status code. followed by long flashes indicating the second digit of the error code. The short flash is 0.25 seconds ON and the long flash is 1.0 second ON. Time between flashes is 0.25 seconds. Time between short flash and first long flash is 1.0 second. Time between code repeating is 2.5 seconds with LED OFF. EXAMPLE: 3 short flashes followed by 2 long flashes indicates a 32 code. Table 5 shows 16 this to be low pressure switch open. Table 5--TROUBLESHOOTING OPERATION Standby tion no call for unit opera- Emergency Mode - Modet 25HNA9 only Low Stage Cool/Heat Operation High Stage Coot/Heat Operation AMBER LED FLASH CODE FAULT None On solid, no flash Standard Thermostat Control (25HNA9only) Rapid, continuous flashing POSSIBLE CAUSE AND ACTION Normal operation Unit being controlled by standard thermostat inputs instead of tnfinity Control. Only high stage operation is available. This operatimg mode should be used in emergency situations only. None 1, pause Normal operation None 2, pause Normal operation System Communications Failure 16 Communication with user interface lost. Check wiring to UI, indoor and outdoor units Invalid Model Plug 25 Control does not detect a modeI ptug or detects an invalid model plug. Unit wili not operate without correct model plug. High Pressure Switch Open 31 High-pressure switch trip. Check refrigerant charge, outdoor fan operation and coils for airflow restrictions. Low Pressure Switch Open 32 Control Fault 45 Low pressure switch trip. Check refrigerant charge and indoor air flow Outdoor unit control board has failed. Control board needs to be Brown Out (230 v) 46 No 230v at Unit 47 Outdoor Air replaced. Line voltage < 187v for at least 4 seconds. Compressor and fan operation not allowed until voItage>190v. Verify line voltage. There is no 230v at the contactor when indoor unit is powered and cooling/heating demand exists. Verify the disconnect is closed and 230v wiring is connected to the unit. Temp Sensor Fault 53 Outdoor air sensor not reading or out of range. Ohm out sensor and check wiring. Outdoor Coil Sensor Fault 55 Coii sensor not reading or out of range. Ohm out sensor and check wiring. Thermistors of range 56 Improper relationship between colt sensor and outdoor air sensor. Ohm out sensors and check wiring. No voltage phase difference is detected (on 25HNA6 models) or Low Stage Thermal Cutout 71 compressor voltage sensed, then disappears (on 25HNA9 models) while cooling or heating demand exists. Possible causes are internal compressor overload trip or start relay not releasing (if installed). No voltage phase difference is detected (on 25HNA6 models) or High Stage Thermal Cutout 72 compressor voltage sensed, then disappears (on 25HNA9 models) while cooling or heating demand exists. Possible causes are internal compressor overload trip or start relay not releasing (if installed). Contactor Shorted 73 No 230V at Compressor (25HNA9 Only) 74 Low Stage Did Not Start (25HNA6 Only) 75 out Compressor voltage sensed when no demand for compressor operation exists. Contactor may be stuck closed or there is a wiring error. Compressor voltage not sensed when compressor should be starting. Contactor may be stuck open or there is a wiring error. Specified start voltage at VR terminal was not achieved in low stage. Start relay was de-energized Low Stage Did Not Start 3 times (25HNA6OnIy) 76 High Stage Did Not Start (25HNA6 Only) 77 after 1 second. For 3 consecutive low stage starts, the specified start voltage at VR terminal was not achieved & start relay was de-energized. Low stage locked out for 30 minutes. Specified start voltage at VS terminal was not achieved in high stage. Start relay was de-energized after 1 second. High Stage Did Not Start 3 times (25HNA6 Only) 78 For 3 consecutive high stage starts, the specified start voltage at VS terminal was not achieved & start relay was de-energized. High stage locked out for 30 minutes. Low Stage Thermal Lockout 81 Thermal cutout occurs in three consecutive low/high stage cycles. Low stage locked out for 4 hours or untiI 24v power recycled. High Stage Thermal Lockout 82 Thermal cutout occurs in three consecutive high/low stage cycles. High stage locked out for 4 hours or until 24v power recycled. Low Pressure Lockout 83 Low pressure switch trip has occurred during 3 consecutive cycles. Unit operation locked out for 4 hours or until 24v power recycled. High Pressure Lockout Low Contactor Open (25HNA6 Only) High Contactor Open (25HNA6 Only) 84 High pressure switch trip has occurred during 3 consecutive cycles. Unit operation locked out for 4 hours or until 24v power recycled. Compressor voltage not sensed when compressor should be starting. Low stage contactor may be stuck open or there is a wiring error. Compressor voltage not sensed when compressor should be starting. High stage contactor may be stuck open or there is a wiring error. 85 87 17 INDOOR CONTROL FAN COIL 2-SPEED HEAT PUMP HybridHeat THERMOSTAT RVS COOLING HEAT/COOL STAGE HEAT STAGE I-q-Q RVS COOLING .... -4_}-.5.--_MO_ ----1 D_'JUMPERFOR 3 HEAT/COOL STAGE 24 VAC .... .... 1 ' 2 FAN E]_ HOT D --HEAT HEAT/COOL STAGE 1 (COMPRESSOR I O} _REMOVE n 24VAC COMM HUMIDIFY [ RVS HEATING 24 VAC J] FOR - HOT - 24 VAC COMM (24 MAC) N/A ] RVS SENSING - - 4 II [_ UOM 1- HUM I- - - I [_ r_ _ OUTDOOR I-r_. _ _ OUTDOOR SENSOR ]_ GON"EOT'O" LF_ SENSOR ___OUTDOOR___ SENSOR - FF@_q I __&_IHUM'D'F'ER I___J r_, ', I- I_LI- _ _ _ 4_R_l- I_ _ _ DEHUMIDIFY MODES .... E_ _uI i FAN __ .... - - i t]-L4_] HEAT/COOL STAGE 2 (COMPRESSOR HI} I_ _[_] E_ - w? RNACE/3 HEAT (F STAGE L-.E}. DEHUMIDIFY J r_ i STAGING TWO-STAGE HEATRUMP TWO-STAGE FURNACE _ J OONNEOTIONL_Lt_J" A02005 Fig, 13 - Infinity Wiring Heat Pump (applies with 2-Stage Puron A06157 refrigerant Fi 9, 14 (non-communicating) to 25HNA6 Models User Furnace - HybridHeat and Two-Stage TM Thermostat Heat Pump with Two-Stage (non-communicating) Only) Interface Fan Coil Communicating AC//HP ::D i Fig 9 - FE4A Fan Coil Wiring with 2-Speed AC/HP A03076 Fig, 15 - Infinity Furnace el" Fan (:oil Wiring with Communicating 18 Two-Stage AC / HP FINALCHECKS IMPORTANT: Before leaving job,besure todothefollowing: 1.Ensure thatallwiringis routed awayfromtubingand sheetmetaledgesto prevent rub-through or wire pinching. 2.Ensure thatallwiringandtubingissecure inunitbefore adding panels andcovers. Securely fasten allpanels and covers. 3.Tighten service valvestem caps to1/12-turn pastfinger tight. 4.LeaveUsersManualwith owner.Explainsystem operation andperiodic maintenance requirements outlined inmanual. 5.FilloutDealer Installation Checklist andplace in customer file. CARE ANDMAINTENANCE Forcontinuing highperformance andto minimize possible equipment failure, periodic maintenance mustbeperformed on thisequipment. Frequency ofmaintenance mayvarydepending upongeographic areas, suchascoastal applications. SeeOwner's Manual for information. PURON® (R-410A) REFRIGERANT QUICK • Puron refrigerant components • Puron refrigerant • Recovery • Puron operates cylinder service pressure should pumps pressure be designed • Do not use liquid-line • If indoor • When to certain unit is equipped all warnings, hose retard. with POE oils. from oil. pressures less than 600 psig. than 72 hours. oil to atmosphere. plastics and roofing materials. with wet cloth when brazing. filter drier is required with an R-22 on every unit. while for service, TXV or piston metering it is under recover device, it must be changed evacuate then break vacuum into the atmosphere. tube coils. cautions, to a hard shutoff Puron TXV. a vacuum. refrigerant, prior to recharging. refrigerant • Do not use capillary • Observe valves to atmosphere to 500 microns • Do not vent Puron device in the manifold TXV. system must be opened Evacuate type metering filter drier in liquid line. liquid-line • Never open system is only compatible moisture • Wrap all filter driers and service approved or DOT BW400. Use a commercial rating. rapidly. Do not expose • POE oils may cause damage • Do NOT use an R-22 and replacement operating line filter driers in line longer • Do not install a suction-line • A factory with liquid refrigerant. filter driers with rated working suction • POE oils absorb moisture equipment to detect HFC refrigerant. as with other HFCs. will not remove • Do not leave Puron Be sure that servicing be 700 psig high side and 180 psig low side with 550 psig low-side should refrigerant, • Vacuum than R-22. rating must be 400 psig, DOT 4BA400 be charged • Use hoses with 700 psig service • Puron pressures refrigerant into suction line with compressor sets should • Leak detectors higher with Puron GUIDE are rose colored. systems when charging percent to operate cylinders refrigerant • Manifold at 50-70 are designed REFERENCE and bold text. • All indoor coils must be installed with a hard shutoff Puron TXV metering 19 device. with dry nitrogen and replace filter driers. Copyright Mannfae_urer 2006 6;a11_er rese_'es Colp • the tlght 7310 W Mo1_is to change, at St • any Indianapolis, time. speeifieations IN 46231 and P1_i_ted designs without notice and in USA wit hou_ Catalo_ obligations. 2O No: 25HNA-2SI Replaces:25HNA ISI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 20 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 14:09:56 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools