CARRIER Air Conditioner/heat Pump(outside Unit) Manual L0611351

User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 21

Coolinq Model Heat Pump
BNC009 BNQ009
BNC012 BNQ012
BNC018 BNQ018
51302618912-C 0706
BNC/BNQ 009,012,018
Duct Free Systems
Only trained, qualified installers and service mechanics should
install, start-up, and selwice this equipment.
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be per-
formed by trained selwice personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the equip-
ment.
Follow all safety codes. Wear safety glasses and work gloves.
Keep quenching cloth and fire extinmJisher nearby when brazing.
Use care in handling, rigging, and setting bulky equipment.
Before installing or servicing system, always turn offmain power
to system and install lockout tag on disconnect. There may be
more than one disconnect switch. Electrical shock can cause
personal injury.
GENERAL
These instructions cover the installation, start-up and servic-
ing of 38BNC/BNQ outdoor and 40BNC/BNQ indoor units cool-
ing only and heat pump duct free systems. See Table 1 for parts
included. See Tables 2 and 3 t\_rPhysical Data.
System Requirements
IMPORTANT: The Indoor unit & the inter units cable
voltage is 30 VDC.
IMPORTANT: Each refrigerant line must be insulated
Separately. See line sizing requirements in tabel 2.
Manufacturer reserves the right to discontinne, or change at an} time, specifications or designs without notice and without inc.
Pg 1
Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.
Max. cable length. Total voltage drop should not exceed IV.
Therefore max. length:
For #18 AWG 24.3 Feet (7.4 m)
For #16 AWG 37.7 Feet (11.5 m)
For #14 AWG 50.0 Feet (18 m)
Use only type "G" or "C" fuses. Use single length power
cable without extension. Allow sufficient space t\_r airflow
clearance on condens-ing units for wiring, refiigerant piping,
and servicing unit. See Fig. 1 and 2 for minimum required
distances between unit and walls or ceilings.
Indoor and outdoor units should be installed at a
Minimum length of 10 ft. apart.
Maximum line length of 50 ft. and
vertical separation of 30 ft.
Do not install indoor units near a direct source of heat such as
direct sunlight, steam or flame.
Do not bury more than 36 in. of refrigerant pipe in the _ound. If
any section of pipe is buried, there must be a 6 in. vertical rise to
the valve connections on the outdoor units. If more than the rec-
omlnended length is buried, refrigerant may mLm'ateto the cooler
buried section during extended periods of systeln shutdown. This
causes refiiger-ant slugging and could possibly damage the com-
pressor at start-up.
FRONT (min.)
2" (0.6m)
Fig. 1A -- 38BNC/BNQ 009 Outdoor
FRONT (rnin.)
2" (0.6m)
Fig. 1B --38BNC/BNQ 012, 018 Outdoor Unit Clearances
Printed in Israel
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical compo-
nents, and equipment location (root;, elevated structures, etc.).
CONTENTS Page
SAFETY CONSIDERATIONS ................................ 1
GENERAL ........................................................... 1-5
INSTALLATION ................................................ 6-17
Indoor Unit Installation ........................................ 6
Outdoor Unit Installation ..................................... 8
Power Supply ....................................................... 9
Leak Test ............................................................... 9
Wiring Diagrams ............................................ 11-16
START-U P ........................................................... 17
System Checks ................................................... 17
CARE AND MAINTENANCE ............................... 17
Outdoor Units ..................................................... 17
Indoor Units ........................................................ 17
To Clean the Indoor Unit Front Panel ............... 17
To Clean Indoor Coil .......................................... 17
Air Filters for Indoor Units ................................ 17
SERVICE ............................................................. 17
TROUBLESHOOTING .................................... 18-21
Installation, Start-Up and Service Instructions
Table 1 mParts List mHigh Wall Units
ITEM QTY DIAGRAM
4
Mounting Bracket
Long Screws
Outdoor Sensor
Connecting Cable
Absorption Cushions
Electric Terminals
Remote Controller
Mounting Bracket
Remote Controller
and Batteries
Insulation for indoor Fittings
Owner's Manual
Wall mounted Receiver RTX
1 Mounting Bracket
with 2 screws
(OPTIONAL)
(Not included)
40BNC/BNQ 009,012 or 40BNC/BNQ 018
_'_:_-(Av_a_ailable for HEAT PUMP ONLY)
--....j
2
Table 2 - Physical Data - Cooling Only
Indoor Unit
Cooling Capacity
Efficiency Cooling SEER
System Chargh
MOISTURE REMOVAL
Air Flow (Turbo/High/Low)
Dimensions (LxHxD)
REFRIGERANT TYPE
Net Weight
40BNC009
Btu/h 9,000
SEER 13
Lb. 27
pt/hr 26
cfm 350/280/220
in 32.08 x 1023 x 7.28
TYPE
Lb. 19
40BNC0!2
11,600
13
3.1
4.5
370 /280 /220
3208 x 10.23 x 728
R-22
19
40BNC0!8
19,000
13
4.1
5.3
670 /570 /480
42.12 x 11.41 x 7.48
27.5
Outdoor Unit
TUBE CONNECTIONS
Vertical lift/Vertical Drop/Max. Length
NOMINAL LINE SIZING
Mixed Phase....Suction
COMPRESSOR TYPE
Dimensions (LxHxD)
Net Weight
METERING TYPE
Feet
38BNC009 38BNC0!2
30/30/50
38BNC018
1/4"- 1/2"
Panasonic-2R 13S 126A6F
in 2874 x 2125 x 1043
Lb. 73
1/4"-1/2"
Panasonic-2P17SR128B1A
35.43 x 25.20 x 12.60
114
Piston (Accurator)
Accurator is non-serviceable
3/8" -5/8"
Panasonic-2K25S236AHA
43.30 x 25.20 x 12.60
136
LEGEND
SEER -- Seasonal Energy Efficiency Ratio
*Units are shipped with a factory charge based on 25 ft of refrigerant lines.
Table 3 -Physical Data -Heat Pump
Indoor Unit
Cooling Capacity Btu/h
Efficiency Cooling SEER SEER
Heating Capacity Btu/h
HSPF HSPF
Heating Seasonal Performance Factor
System Chargh
MOISTURE REMOVAL
Air Flow (Turbo/High/Low)
Dimensions (LxHxD)
REFRIGERANT TYPE
Net Weight
40BNQ009 40BNQ012
9,000
13
8,600
7.7
Lb. 2.7
pt/hr 2.6
cfm 350 / 280 /220
m/h 594 /475 /373
in 32.08 x 10.23 x 7.28
mm 815 x 260 x 185
Lb. 19
11,600
13
tl,800
7.7
3.1
4.5
370 /280 /228
628 /475 /373
32.08 x 10.23 x 7.28
815 x 260 x 185
R-22
19
40BNQ018
19,000
13
18,300
7.7
4.1
5.3
670 /570 /460
1138/968/781
42.12 x 11.41 x 7.48
1,070 x 290 x 190
27.5
Outdoor Unit
TUBE CONNECTIONS
Vertical lift/Vertical Drop/Max. Length
NOMINAL LINE SIZING
Mixed Phase....Suction
COMPRESSOR TYPE
Dimensions (LxHxD)
Net Weight
METERING TYPE
Feet
38BNQ009 38BNQ012
30/30/50
38BNQ018
in 1/4"-1/2"
Panasonic-2R 13S 126A6F
in 28.74 x 21.25 x 10.43
Lb. 73
1/4"-1/2"
Panasonic-2P 17SR126B 1A
35.43 x 25.20 x 12.60
114
Piston (Accurator)
Accurator is non-serviceable
3/8" - 5/8"
Panasonic-2K25S236AHA
43.30 x 25.20 x 12.60
136
LEGEND
HSPF- Heating Seasonal Performance Factor
SEER- Seasonal Energy Efficiency Ratio
*Units are shipped with a factory charge based on 25 ft of refrigerant lines.
NOTE: Standard Ambient Operating Limitations - 55 °F to 125 °F (12.7 °C to 51.6 °C).
4_
UNIT
40BNC009
40BNQ009
40BNC012
40BNQ012
40BNC018
40BNQ018
A B C D E F G H L K Weight
linch] 32.08 10.23 7.28 25 9.06 1.57 1/2 1/4 1.06 1.96 18.7 Ib
[mm] (815) (260) (185) (635) (230) (40) (12.7) (6.35) (27) (50) (8.5) Kg
linch] 32.08 10.23 7.28 25 9.06 1.57 1/2 1/4 1.06 1.96 18+7 Ib
[mm] (815) (260) (185) (635) (230) (40) (12.7) (6.35) (27) (50) (8.5) Kg
linch] 42.12 11.41 7A8 35.23 10.82 2.56 5/8 3/8 1,96 1,96 27.5 Ib
[mm] (1070) (290) (190) (895) (275) (65) (15.87) (9.5) (50) (50) (12,5) Kg
NOTES:
1. DiMENSiONS IN iNCHES, [ ] ARE FN MILLIMETERS-DO NOT
SCALE
2. _ DIRECTfON OFAIR FLOW
3. REFRIGERANT, DRAINAND POWER CONNECTFONS MAY JP
BE MADE REAR (LEFT TO RIGHT), LEFT SIDE. RIGHT S_DE.
OR BOTTOM LEFT
ENLETA_R
!
I TOP VIEW I
MiN,
x
0+50
[lO]
3 0 DiA [76]
FOR REFRIGERANT. DRAIN,
POWER AND SIGNAL LINES
/
[100 ] MIN+ 11+81 [300] MIN+
MINIMUM CLEARANCE FOR SERVICE AND AIR FLOW
VIEW i AiRFiL_ERS
I LEFT SIDE _(OPEN COVERFORACCESS)
/EVAPORATOR COfL
INLETAIR
DRAIN TRAY
COOLING
%
HEATING if'@
LKNOCKOUT FOR LEFT SiDE
REFRIGERANT, DRA_N. POWER AND
SIGNAL LINES
I RIGHT SIDE VIEW I
[FRONT VIEW] S_GNALLINES
_A _ • _NFRARED REMOTE
OVERRIDE SW_TCH
/
/
IBOTTOM VIEW I KNOCKOUTFORBOTTOM
REFRIGERANT, DRAIN, POWER AND
SIGNAL LINES
KNOCKOUT FOR RIGHT SiDE
REFRIGERANT, DRAIN, POWER AND
E
..... _----_----:---+--';L---
n ,1_ ° u:lI._dl:+ +0::q:'2t +V+_I ,
I,f
z
p,
Z (09,t2)=/64 mm Z (t8)=/76 mm
(2.5) (3)
(K
+J
/
m m
-t
m
m
> m
<
UNIT SIZE
38BNC009
38BNQ009
38BNC012 25,20 640 35,43 900 12,60 320 14,17 360 0 0 14,96 380 5,31 135
38BNQ012
38BNC018 25,20 640 43.30 1100 12,60 320 14.17 360 0 0 14.96 380 5,31 135
38BNQ018
IlFIl MOUTING
SLOT
]
O
A B C D E F G H S J K L M N P (8UCTIONFLARE) R (UQUIDFLARE) DPEP'ATIN6WGf" _O
iNCHES [mini iNCHES [mini INCHES [mini iNCHES [nlm] INCHES [mini iNCHES [mini iNCHES [mini INCHES [mini INCHES [mini iNCHES [mini iNCHES [mini iNCHES [mini NCHES [mini iNCHES [mini iNCHES [mm] iNCHES [mm] LBS [kg] O m
21.25 540 28,74 730 10.43 265 11.22 285 0 0 11.61 295 5,31 135 0 0 18,50 470 4,33 110 8,07 205 2,28 58 5.51 140 17.91 455 1/4 6.35 1/2 12.7 73 33.1
Ob
<1
I
i=
"E" "H" "G"
B I I.
IAIR IN ,,[O,15M]I
It I ikk /_\_// /"
, , ,-,' _----I_-¢_ /
AIR DISCHARGE 2'
[O,6M]
TOP VIEW
" t
ii
ii
ii
%J
I
I
FRONT VIEW
\_,_L"
2' [0.6M]
t
MINIMUM CLEARANCES]
SEE NOTE t
0,8
[20MM] --
0 0 24,72 628 5,12 130 8,66 220 2,28 58 16.73 425 15,23 387 1/4 6.35 1/2 12,7 114 51.7 m
_m
0 0 32,60 828 5.12 130 8.66 220 2,87 73 16,73 425 15,23 387 5/8 15,9 3/8 9.5 136 61.7 z ,_
NOTES:
1. REQUIRED CLEARANCES, WITH COIL FACING WALL - ALLOW 6 MINIMUM
1.1 WITH COIL FACING WALL ALLOW6 MINIMUM CLEARANCE ON COIL SIDE & END. m u
AND 2 FEET MINIMUM CLEARANCE ON COMPRESSOR END FAN SIDE __
1.2 WITH FAN FACING WALL ALLOW 2 MINIMUM CLEARANCE ON FAN SIDE AND 6 ON COIL END. _4
AND 2 FEET MINIMUM CLEARANCE ON COMPRESSOR END COIL SIDE Z_
1.3 ALLOW 2 FEET MINIMUM CLEARANCE OVER THE TOP OF UNIT C)
1.4 WITH MULTI UNIT APPLICATION, ARRANGE UNITS S0 DISCHARGE OF ONE DOES NOT ENTER INLET OF OTHER
2 DIMENSIONS IN PARENTHESIS ARE tN METRIC
3 BRACKET WITH 1.125 DIA HOLE FOR FIELD POWER SUPPLY
[0dSM]
/ 1 6,,[0,15M] //
N_ z°
2' [0 6M l _
W_'_ -_I"1 ._ F,ELDPOWERCONNECTION_. _
".,I I_"'--...._ & CONTROL CONNECT ON /\
__ _ ----_ _'_ UNDER THIS COVER /" .i i Z_
B__ _ ! i\ i q_
I _ \k " " DIA VAPOR LINE "M"
, [ ] FLARE CONNECTION --'_
SERVICE PORT \ I_ /_ 30, TYP--I
'I 25 FLARE CONNECT'ON_ /_lb_ "_/ _' '
_ SERVICE PORT I I,K.
_"N" (FROM LIQUID LINE) _
::_ 25 FLARE CONNECTION/
j,_, ,oI -- "R" DIA LIQUID UNE _-- , _,
k
-- _?_ -i FLARE CONNECTION ¢ _ I o
:
RIGHT SIDE VIEW ] "I _ '
VIEW "A"
6" (0.15m)_min.
Fig. 2mIndoor Unit Clearances
INSTALLATION
Plan the installation carefully to avoid component failures
and make installation easier.
Indoor Unit Installation
REFRIGERANT LINE ROUTING The refrigerant lines may
be routed in any of the t\_ur directions shown in Fig. 3.
INSTALL THE MOUNTING BRACKET
1. Carefully remove the mounting bracket, which is
connected to the back of the indoor unit's base with screws.
2.
3.
4.
5.
Position the mounting bracket on the walt and level it
using a spirit level (see Fig. 2 for minimum required
clearance distances).
Mark the four drilling holes on the wall, as they appear in
Fig. 4.
Drill the holes, insert the wall plugs and use four long
screws to attach the mounting bracket to the wall.
Check that the bracket is leveled and securely fastened to
the wall.
DRILLA HOLE IN THE WALL FOR DRAINAGE
AND INTER-UNIT CONNECTIONS-
To make the connections between the indoor and outdoor units,
drill a (09, 12) 2.5-in, (18) 3-in. hole through the wall for the
refiigerant lines, drainage hose and control cable passage as
shown in Fig. 5.
1. Mark the center of the hole to be drilled according to the
refrigerant line routing used and dimensions shown in Fig.
4.
2.
3.
Make sure to drill ou_vards and downwards, so that the
opening in the outside wall is at least 1/2-in. lower than the
opening on the inside.
Make sure the drainage hose is at the bottom side of the
hole.
4. If refrigerant line route no. 1,2 or 4 are used, use a small
saw blade to carefully remove the corresponding plastic
covering on the side panel.
5.
6.
Run the outdoor sensor cable, electrical cable, refrigerant
lines, and drainage tube through the hole.
Fill the remaining wall hole gap with an appropriate
sealant material.
Fig. 3 mRefrigerant Lines
09, 12 25
3
2
G-2 ALL DIMENSIONS ARE IN inches
09, 12 635
G-2 ALL DIMENSIONS ARE IN mm
Fig. 4 mMounting Bracket 38BNC/BNQ 009, 012
18
G-3 ALL DIMENSIONS ARE IN inches
18 899
G-3 ALL DIMENSIONS ARE IN mm
Fig. 4 _Mounting Bracket 38BNC/BNQ 018
(Optional for HEAT PUMP SYSTEMS}
REFRIGERANT
LINES
DRAINAGE
CABLE TUBE
Fig. 5- Drill Holes
WIRE THE INDOOR UNIT
1. Strip the cables back 1/4 inch.
2. Remove the unit's fiont panel by lifting the lower part and
pulling it gently outward and upward. See Fig. 6.
3. Remove the two screws t?romthe control box cover and take
off the cover. See Fig. 7. Save the screws to reassemble.
NOTE: In general wiring the indoor unit does not require the
removal of the grille fiame but in case of need do as t\_llow:
4. Remove the two screws from the air discharge opening.
Save the screws to reassemble. See Fig. 7A.
Pull downwards and outwardston the bottom of the _itle
and gently raise the frame of the top of the unit.
Once all covers are off; mount the unit onto the wall
mounting bracket. See Fig. 8.
NOTE: Leave covers off until after the Making Drainage Con-
nections section.
Route the interconnecting unit's electric cable and the
outdoor sensor cable towards the lower right hand corner of
the indoor unit.
Make sure that the wires are connected in accordance with
the wiring diagram on the inside of the unit front cover or
within this instruction manual.
Secure the control cables to the strain relief.
For heat pump systems only, connect the outdoor sensor
TH3 to its mating black terminal. See Fig. 9.
Make sure that all wires and screws are firmly thstened. Loose
wires or connections can cause damage and present a tire
hazard.
MAKE DRAINAGE CONNECTIONS
1. Connect the unattached end of the drainage tube to the
drainage hose outlet.
2. Seal the drainage connection to prevent leakage.
3. Make sure there are no kinks, "U" bends or flattened sections
in the tube.
4. Check that the drainage functions properly. Fill the pan below
the unit's coil with water and obsel-ve that it fieely drains out.
5. Make sure the drainage hose is at the bottom side of the walt
through-hole (see Fig. 5).
REASSEMBLE
1. Connect the display connector to the display panel printed
circuit board.
2. Put the control box cover and _ille fiame back on using the
appropriate screws (Steps 3 and 4 of Wire the Indoor Unit
section). Put the grille insert back on.
Fig. 6 mRemove Grille Insert
Fig. 7 mRemove Control Cover
Fig. 7A - Remove the screws from the air
discharge opening.
Mount the indoor unit on the mounting bracket
©
Gently push with the arrow direction
Fig. 8 _ Indoor Unit Mounting
Standard Dip Switches
status from the factory
HEAT PUMP
Model-0t2 DIP Switches location
(on the (ontrol Box side)
HEAT PUMP
Models-009,018 DIP Switches location
(on the Control Box side)
COOLING ONLY
Model-0t2 DIP Switches location
(on the ( ontrol Box side)
COOLING ONLY"
Models-009,018 DIP Switches location
(on the ( ontrol Box side)
Inter unit
terminal block
30VDC
Display
Connection
TH1
123456 TH3
(Heat Pump Only)
\Inter unit cable clamp
Fig. 9 -- Outdoor Sensor Connection
ATTACH THE REMOTE CONTROLLER
MOUNTING BRACKET
1. Use the two screws supplied with the controller to attach the
Mounting Bracket to the wall in the location selected by the
customer (see Fig. 10 ).
2. Install batteries in the remote control.
3. Place remote control into remote control Mounting Bracket.
4. For remote control operation, refer to the unit O,a_er's
Manual.
.... REMOTE CONTROL /
I [ REMOTE CONTROL
MOUNTING BRACKET
Fig. 10 mAttach Mounting Bracket to the Wall
(OPTIONAL)
Fig. 11 mWall Mounted Unit - RTX
Outdoor Unit Installation
NOTE: The outdoor unit must be installed on a solid surface
0nounting base).
1. Place the rubber absorption cushions (supplied with the
outdoor unit) under the unit's feets to prevent vibrations.
2. Fasten the outdoor unit legs to the mounting base, as shown
in Fig. 12. The cushion goes between the legs and the
mounting base.
3. Be sure that the unit is leveled.
MAKE REFRIGERANT PIPING CONNECTIONS (OUTDOOR
UNIT) To connect the refrigerant lines:
Use only "L" type sealed, dehydrated copper reliigerant tub-
ing. No other type of tubing may be used. Use of other types of
tubing will void the lnanufacturer's warranty.
Do not open service valves or remove protective caps from
tubing ends until all the connections are made.
Bend robing with special bending tools to avoid the forlna-
tion of sharp bends. Take care to avoid kinks or flattening of the
tubing.
Keep the tubing tree of dirt, sand, moisture, and other con-
taminants to avoid damaging the refrigerant system.
Avoid sags in the suction line to prevent the formation ofoil
traps.
Insulate each tube with 3/8-in. walled thermal pipe insu-
lation. Inserting the tubing into the insulation before making
the connections will save time and improve installation The suc-
tion and mixed-phase lines should never come in direct contact.
INTER UNIT
TERMINAL BLOCK
POWER SUPPLY
TERMINAL BLOCK
HIGH/LOW
VOLTAGE METAL
BARRIER
TH3 SENSOR
(HEAT PUMP ONLY)
METAL
CONDUIT
CONNECTION
PLATE
POWER SUPPLY CABLE
INTER UNIT CABLE
4 ABSORPTION CUSHION TO
BE PUT UNDER EACH FEET
Fig. 12 -- Legs Mounting Base and Wiring
Outdoor Units Models: 38BNC/BNQ 012, 018
Fig. 12A mLegs Mounting Base and Wiring
Outdoor Units
Model 38BNC/BNQ009
INDOOR UNIT 009,012,018
Operation push button for
automatic operation (23°C/73°F),
turning the a/c OFF, canceling
the malfunction indication,
and resetting the filter LED.
PLASTIC CONTROL .....
COVER <_
FLARING AND CONNECTING REFRIGERANT LINES
1. Remove the protective cap from the flare fitting.
2. Remove the protective cap from the robing and cut to the
required length. Be sure that the cut is perpendicular and
clean, without burrs.
3. Slip the flare nut on the tubing and flare the tube end using
standard flaring tools.
4. Tighten the nut until resistance is met. Mark the nut and the
fitting. Using a suitable wrench tighten an additional 1/4
turn. Use the tbtlowing specified torque, according to
connection size:
Mixed-Phase line:
1/4 in.-(12.3 ft-lb.)
3/8 in.-(29 ft-lb.)
Suction line:
1/2 in.-(36 ft-lb.)
5/8 in.-(47 ft-lb.)
Both refrigerant lines
need to be insulated separatly
NOTE: The service valves on the outdoor unit must remain closed
until all 4 connections have been made.
EVACUATE TUBINGAND CHARGE THE SYSTEM When
all the fittings are connected, air must be expelled, then refriger-
ant charge must be checked and adjusted. Follow the steps below.
1. Open the service port cap on the suction line valve (laNe
valve).
SERVICE LED
3.
4.
5.
6.
7.
IR RECEIVER FILTER
Fig. 12B m Indoor unit LED's and Wiring
Connect the vacuum pump to the service port via the pressure
gage and evacuate to 500 microns to eliminate contamination
and moisture.
Disconnect the vacuum pump. Unit should maintain 500
microns for 5 minutes.
Remove the service port caps from the mixed-phase valve
and suction line valve
Open the mixed-phase valve (small valve) with an Allen
wrench.
Open the suction line valve (large valve) with an Allen
wrench.
The outdoor unit is supplied with sufficient R-22 refriger-
ant for up to 25 ft. lineset length. Add 0.9 oz. of refriger-
ant for each additional 3 ft. of tubing length.
Make sure that the valves are properly opened. Be careful not
to open them more than required as this may damage the
thread.
Replace the service port cap. Using refrigerant oil, lubricate
the cap beam and hand tighten until resistance is met. Use a
suitable wrench to tighten the cap by an additional 1/2 turn.
Power Supply See Tables 4 and 5 tbr electrical data and Fig.
13-18 for system wiring dia_ams.
Leak Test Leak test all fittings with appropriate test equip-
ment.
Table 4 mElectrical Data, Indoor Units m30VDC
UNIT VOLTAGE MCA* MOCP* FULLLOAD FANMOTOR COMPRESSOR COMPRESSORLOCKED
AMPS AMPS AMPS ROTORAMPS
009 30VDC N/A N/A 1.8 1.1 N/A N/A
40BNC
012 30VDC N/A N/A 1.8 1.5 N/A N/A
40BNQ
018 30VDC N/A N/A 2.4 0.84 N/A N/A
LEGEND
MCA --Minimum CircuitAmps
MOCP -- Maximum Overcurrent Protection
*If indoor unit is powered from outdoor terminal block, the MOCP for
the outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change without notice. 3095897
Table 5 -- Electrical Data, Outdoor Units -- 115, 208/230-1-60
UNIT VOLTAGE MCA* MOCP* FULLLOAD FANMOTOR COMPRESSOR COMPRESSORLOCKED
AMPS AMPS AMPS ROTORAMPS
009 115VAC 9.0 15 9.7 0.90 6.1 42
38BNC
012 115VAC 11.6 20 13.7 1.00 7.6 58
38BNQ
018 208-230VAC 10.7 20 10.0 0.88 6.5 42
LEGEND
MCA --Minimum CircuitAmps
MOCP -- Maximum Overcurrent Protection
*If indoor unit is powered from outdoor terminal block, the MOCP
for the outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change without notice. 3095897
10
TH1
J12
STEPPER
MOTOR
NDOOR UNIT
TH2
] 3 cz]
J7 J_l
---I K
.I
J14
J1
_ K
8
_--i K9
,J
_/--_ K
,I 7
TAC 671 MaLn Board
FAN
H.L.T.V
RVS
COMP.
+12V RED
-12V BLK
+30V WH
FAN 1 BLUE
FAN 2 RED
FAN 3 BLK
TAC 670 control
I
TAC 672 A
Motor Control
Model 09 Wiring Diagram Cooling Only
TB
BLK I_- .....
YEL _-
RED I_-
GR_-N]_
GR/YEL _ GND
CC -Compressor CapacLtor
COMP*Compressor
FC -Fan Capacitor
GND -Ground
TB -TermLnal Block
TH -Thermistor
7153A
RED + 30 VDC
BLKDC RTN
YEL V_
WHT+
BLDC
MOTOR
*** -16 AWG iLEGEND
** -14 AWG
-12 AWG
ALL OTHER WIRES 18 AWG
o -Spfice
-Terminal (Unmarked)
Factory WLring
FLeId Control WLring
FLetd Power WLring
......... Accessory or Optional Wiring
TB
**BLK 21
**WH 3
4
**RED 5
**GREEN 6
IGND
L1 N / GRO
115 MAC
Mains AC Supply
J1
***RED
FAN
H.L.T.V
RVS
COMP 1
DC RTN
TAC 673
Relay Board
TB
GREEN
GREEN
*BR
* BLUE
GR/YEL
*** GR/YEL
DC AC
Out IN
DC Out (+)
w.
UC RTN (-)
30VDC
Power Supply
OUTDOOR UNIT
BLK L
rY
N L DC
BLK -o 0 BLK
BLK TB
*BLUE
BLK
0
*OR
FC_ WHT[
! v
n,"
Z
N BLUE
L1 BR
COMP.
***GREEN
24791
32 W
FAN
MOTOR
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with Type 90° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and
local codes.
3. Thermistor wiring cable 32 ft long provided with indoor unit.
4. Compressor and fan motors are protected by internal thermal
overloads.
Fig. 13--System Wiring Schematic 40BNC009 Fan Coil with 38BN0009 Condensing Unit
THI!
L2L
6 J7 J_18
F--E K
_'FE6
F--_K5
I_ E
_J12 J14
STEPPER [_]
MOTOR J 1
F--i K
+_/,r 8
I I
,i K9
K
7
TAC 671 Main Board
TAC 670 control
CC -Compressor Capacitor
COMP-Compressor
FC -Fan Ca pacLtor
GND -Ground
RVS -ReversLng Valve SotenoLd
HLTV -Heating Low Temp. Valve
TB -Terminal Block
TH -ThermLstor
7130F
INDOOR UNIT
TH2 TH3
FANI
H,L.T.V I
RVS
COMP.
+12V RED
-12V BLK
+30V WH !
FAN 1 BLUE
!L__
FAN 2 RED |
L_
FAN 3 BLK
Model 09 Wiring Diagram Heat pump
RED + 30 VDC
BLK DC RTN
YEL VSP
WHT_
BLDC
MOTOR
TB
BLK _ _ _
G_
_GND
J5
21
31
41
N
TAC 672 A
Motor Control
*** -16 AWG [LEGEND
** -14 AWG
-12 AWG
ALL OTHER WIRES 18 AWG
o -Splice
-Terminal (Unmarked)
Factory Wiring
Field Control Wiring
Field Power WirLng
......... Accessory or Optional WLring
TB
**BLK 1
I GND
,-p
IR
m
L] N ___GRO
1 15 VAC
Mains AC Supply
***RED
J1
FAN
_ H.L.T.V
RVS
COMP1
DC RTN
TAC 673
Relay Board
TB
OUTDOOR UNIT
TH3
0 GR/YEL
BLK _
B_LK RVS
BLK
*BLUE
BLK
GREEN
GREEN
*BR
* BLUE
GR/YEL
*** GR/YEL
N BLUE
L1 BR
DC AC
Out IN
DC Out (+)
BC RTN (-)
30VDC
Power Supply
GF_D
N L1 DC
RTN
*OR
COMP.
***GREEN
FAN
MOTOR
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with Type 90 ° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and
local codes.
3. Thermistor wiring cable 32 ft long provided with indoor unit.
4. Compressor and fan motors are protected by internal thermal
overloads.
,,-I,
B
Fig. 14 --System Wiring Schematic 40BNQ009 Fan Coil with 38BNQ009 Condensing Unit
INDOOR UNIT
TH1! ! TH2
E]
- - - FAN
H.L.T.V [
RVS
COM P:_ _
J12 +12V RED J5
Model 12 Wiring Diagram Cooling Only
STEPPER [_
MOTOR J 1
---_ K
_/',_ 8
_j--I K9
,JI
__--I K
,I 7
TAC 671 Main Board
-12V BLK
+30V WH 1
FAN 1 BLUE
/ L
FAN 2 RED /
L
FAN 3 BLK
TAC 670 control
21
31
41
51
TO t
BLK .... __*BLK
WH **WH 3_
N
J1
RED + 30 VDC
_BLK DC RTN
YEL VBP
BLDC
MOTOR
CC -Compressor CapacRor
COMP-Compressor
FC -Fan Capacitor
GND -Ground
TB -Terminal Block
TH -Thermmtor
7154A
TAC 672 B
Motor Control
IGND
-J
uJ
IRI
m
P[!
LINJ_
115 VAC
*** -16 AWG iLEGEND** -14 AWG
-12 AWG
ALL OTHER WIRES 18 AWG
o-Splice
-Terminal (Unmarked)
Factory Wiring
Field Control Wiring
-_ Field Power Wiring
J1
FAN
HLTV
RVS
COMP1
DC RTN
TAC 673
Relay Board
TB
GREEN
GREEN
*BR
* BLUE
GR/YEL
*** GR/YEL
DC Out (+)
***RED DC RTN (-)
Accessory or OptionaI Wiring Mains AC Supply
DC AC
Out IN
30VDC
Power Supply
BLK
BLK
-\
_#
N BLUE
L1 BR
OUTDOOR UNIT
COMP.
F(
0
BLK
*BLUE
BLK
*OR
_ LLI
C_D
NL _
BLK _ l
FB
WHT I
FAN
MOTOR
***GREEN
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with Type 90 ° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and
local codes.
3. Thermistor wiring cable 32 ft long provided with indoor unit.
4. Compressor and fan motors are protected by internal thermal
overloads.
Fig. 15 --System Wiring Schematic 40BNC012 Fan Coil with 38BNC012 Condensing Unit
THt T
J7 J8
6 Jl_
---I K
_---_ K5
i__J
I F
_K _-
I J12 J14
STEPPER _]
MOTOR J 1
_-m K
,I 8
I I 9
E I
F--_ K
_/" __ 7
TAC 671 MaLn Board
TAC 670 control
INDOOR UNIT
TH3
FAN
H,L.T.V
RVS
COMP.
+12V RED
-12V BLK ]
+30V WH 1
FAN 1 BLUE |
L_
/
FAN 2 RED L
FAN 3 BLK
TAC 672 B
Motor Controt
Model
TB
BLK
YEL
WH
OR
RED
GREEN
RED + 30 VDC
BLK DC RTN
YEL VSP
WHT+ 12VDC
12
CC -Compressor Capacitor
COMP-Compressor
FC -Fan Capacitor
GND -Ground
RVS -Reversing VaNe Setenoid
HLTV -Heating Low Temp. Valve
TB -Terminal Biock
TH -Thermistor
7152A
BLDC
MOTOR
*** -16 AWG JLEGEN D** -14 AWG
-12 AWG
ALL OTHER WIRES 18 AWG
o-Spfice
-Terminal (Unmarked)
Factory WLring
FLetd Control WLring
FLetd Power WLring
......... Accessory or Optional Wiring
Wiring Diagram Heat pump OUTDOOR UNIT
TH3
0GR/YEL
TB
**BLK 1
**YEL 2
**WH 3
**OR 4
**RED 5
**GREEN 6
r-U
I GND
P[!
L1N__
11 5 VAC
Mains AC Supply
DC Out (+)
***RED BC RTN(-)
J1 TB 1
RAN j_
COM P
TAC673
Relay Board
BLK
BLK HL'FV
GREEN
GREEN
*BR
* BLUE
GR/YEL
*** GR/YEL
DC AC
Oat IN
O q_-
t-
30VDC
Power Supply
N BLUE
L1 BR
rn
-x
COMP.
FAN
MOTOR
***GREEN
BLK
RVS
BLK
*BLUE
BLK
*OR
WHT
I-'z >- "*" I
T _ _j
rY
>-
d
DC PK
©
TB
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with Type 90° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and
local codes.
3. Thermistor wiring cable 32 ft long provided with indoor unit.
4. Compressor and fan motors are protected by internal thermal
overloads.
Fig. 16 -- System Wiring Schematic 40BNQ012 Fan Coil with 38BNQ012 Condensing Unit
INDOOR UNIT
TH,: TH2
3
J7 J8
6 J18
F--_ K
_'FE6
I__J
_J12 J14
STEPPER [_
MOTOR J1
F--_ K
_,r 8
i__J
_.,,--i K9
,I
I I K
7
I
TAC 671 Main Board
TAC 670 control
FANI
H,L.T.V
RVS
COMP.
J5
+12v RED
-12V BLK [_]
+30V WH /
FAN 1 BLUE
!L__
FAN 2 RED |
L_
FAN 3 BLK E
21
31
41
TAC 672 A
Motor Control
Model 18 Wiring Diagram Cooling Only
TB
BLK _ _ _
WH
RED
G_ ---
J GND
CC -Compressor Capacffor
COMP-Compressor
FC -Fan Capacffor
GND -Ground
TB -Terminal Block
TH -ThermLstor
RED + 30 VDC
BLK DC RTN
YEL VSP
WHT_
BLDC
MOTOR
TB
I I GND
iJ
w
12i
m
LIL2 J_
208\230 VAC
*** -16 AWG [LEGEND** -14 AWG
-12 AWG
ALL OTHER WIRES 18 AWG
o-Splice
-Terminal (Unmarked)
Factory WLring
Field Control Wiring
Field Power Wiring
J1 TB 1
FAN
RVS
COMP 1
DC RTN
TAC 673
Relay Board
BLK
o
DC Out (+:
***RED DC RTN (-:
GREEN
GREEN
*BR
* BLUE
GR/YEL
*** GR/YEL
DC AC
Out IN0--
II
30VDC
Power Supply
L2 BLUE
L1 BR
COMP.
***GREEN
7155A ......... Accessory or Optional Wirin( Mains AC Supply
OUTDOOR UNIT
BLK
*BLUE
BLK
*OR
)
FCl
J W
FAN
OTOR
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with Type 90 ° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and
local codes.
3. Thermistor wiring cable 32 ft long provided with indoor unit.
4. Compressor and fan motors are protected by internal thermal
overloads.
GND
DC
L2 L1 RTN
,-I,
'B
Fig. 17 --System Wiring Schematic 40BNC018 Fan Coil with 38BNC018 Condensing Unit
©J12
STEPPEF
MOTOR
TH'tL
J7 J8
6 J1
_K
-b_.| 6
_C(',K5
I__J
J14
--j K
J_J 8
I I
,i K9 __
I I K
_F 7
E
TAC 671 Main Board
INDOOR UNIT
TH3
FAN
H,L.T.V
RVS
COMP.
+12V RED
-12V BLK
+30V WH
FAN 1 BLUE
FAN 2 RED
FAN 3 BLK
L
L
Model 18 Wiring Diagram Heat Pump OUTDOORUNIT
TB
BLK _ _ _
YEL _ _ _
WH
RED - --
GREEN - - -
ND
J5
21
31
41
TAC 670 control
RED + 30 VDC
BLK DC RTN
YEL VSP
WHT+ 12VDC
CC -Compressor Capacitor
COMP*Compressor
FC -Fan Capacitor
GND -Ground
RVS -Reversing Valve Solenoid
HLTV -Heating Low Temp. Valve
TB -Terminal Block
TH -Thermistor
7137F
BLDC
MOTOR
TAC 672 A
Motor Control
*** -16 AWG [LEGEND** -14 AWG
-12 AWG
ALL OTHER WIRES 18 AWG
o-Splice
-Terminal (Unmarked)
Factory Wiring
Field Control Wiring
Field Power Wiring
......... Accessory or Optional Wirinc
TB
**BLK 1
**YEL 2
**WH 3 ....
**RED
**GREEN
I
I I I GND
IIli
Iwlp
II_al
H!
L1L2/
208\230 VAC
Mains AC Supply
J1
***RED
FAN
HLTV
RVS
COMP 1
DC RTN
TAC 673
Relay Board
DC Out (+)
DC RTN (-)
TB
F--
HLTV
RVS
GREEN
GREEN
*BR
* BLUE
GR/YEL
*** GR/YEL
DC AC
Out IN -__
41 0-- L2 BLUE
0-
= L1 BR
e-
30VDC
Power Supply
TH3 [_ _J
GR/YEL I G_D I_
BL__ BL_
RVS [ ]KIKIKITB
BLK BLK I/1_,_,_1
J-- BLUE |L_U__uJ
HLTV I | /]\ /
BLK | Ill
Ill
*OR II1,, i
WHT I
FC _._
_ _':i_I
CC. ___
_ L1 2 34 5 6_
j|pK iz_rZ
'rn m rcLu _ _
OtOR
***GREEN
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with Type 90 ° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and
local codes.
3. Thermistor wiring cable 32 ft long provided with indoor unit.
4. Compressor and fan motors are protected by internal thermal
overloads.
Fig. 18 --System Wiring Schematic 40BNQ018 Fan Coil with 38BNQ018 Condensing Unit
System Checks
1.
2.
START-UP
Conceal the tubing where possible.
Make sure that the drainage tube slopes downward along its
entire length.
3. Ensure all tubing and connections are properly insulated.
4. Fasten robes to the outside wall.
5. Seal the hole through which the cables and tubing pass.
6. Connect the air conditioner to the power source and turn it
on.
7. Check all air conditioner operating modes. Refer to Owner's
Manual for operating details.
INDOOR UNIT
1. Do all the remote controller buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drainage work?
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
2. Is noise, drain water or airflow from the unit likely to disturb
the neighbors?
3. Are there aW gas leaks?
EXPLAIN THE FOLLOWING ITEMS TO THE CUSTOMER,
WITH THE AID OF THE OWNER'S MANUAL:
1. How to turn the air conditioner on and off; selecting cooling,
heating and other operating modes; setting a desired tempera-
ture; setting the timer to automatically start and stop air
conditioner operation; and the other features of the remote
controller and display panel.
2. How to remove and clean the air filter.
3. How to set the air deflection louver.
4. Explain care and maintenance.
5. Present the Owner's Manual and installation instructions to
the customer.
CARE AND MAINTENANCE
The t\_ltowing may be pert\_rmed by the equipment owner.
Outdoor Units
Before per forming recolrnnended maintenance, be sure unit main
power switch is tamed off Failure to do so may result in electric
shock or injury from rotating tan blade.
CLEANING COILS Coil should be washed out with wa-
ter or blown out with compressed air. Clean coil annually or as
required by location and outdoor air conditions. Inspect coil monthly
and clean as required. Fins are not continuous through coil sec-
tions. Dirt and debris may pass through first section, become trapped
between the row of fins and restrict outdoor unit airflow. Use a
flashlight to determine if dirt or debris has collected between coil
sections. Clean coil as follows:
1.
2.
Turn offunit power and install lockout tag.
Using a garden hose or other suitable equipment, flush coil
from the outside to remove dirt. Be sure to flush all dirt and
debris fiom drain holes in base of unit. Fan motors are
waterproof.
Indoor Units
To avoid the possibility of electric shock, bet\_re performing any
cleaning and maintenance operations, always turn offpower to
the system by pressing the ON/OFF button on the remote con-
trol and turn off the separate disconnect switch located near the
unit.
If the indoor unit is on a separate switch, be sure to turn this
disconnect off as well.
Do not wash filter in water over 120°F (to avoid shrinkage). Do
not expose filter to fire (to avoid fire damage). Do not expose
tilter to direct sunlight. Clean tilter more frequently when air is
extremely dirty.
Do not attempt to clean or seraqce components in controlbox.
To (.'lean the Indoor Unit Front Panel if the front panel of the
unit becomes dirty or smudged, wipe the out-side of the panel with
a soft dry cloth. Use a mild liquid deter-gent and wipe offcarefulty
with a dry cloth.
To (.'lean Indoor (,'oil To clean the coil, remove indoor unit
front panel and vacumn the coil tins, using care not to bend or dam-
age tins.
LUBRICATION The indoor-l_an, automatic air sweep, and the
outdoor-fan motors are factory lubricated and require no oiling.
Air Filters for Indoor Units
Operating your system with dirty air filters may damage the in-
door unit and, in addition, can cause reduced perfor-mance, in-
termittent system operation, frost build up on the indoor coil,
and blown fuses. Inspect and clean or replace the air filters
monthly.
TO REMOVE AIR FILTERS Open the unit's front panel by
lifting the lower part and pulling it gently outward and upward.
Pull out the filters.
TO CLEAN OR REPLACE FILTERS Filters can be vac-uumed
or washed in warm water. Shake tilter to remove any excess water,
and replace it back. If the filter has begun to break do,am or is tom,
replace it. Replacement tilters are available through a local dealer.
SERVICE
The following should be performed by a qualified service techni-
cian.
(,'lean Condensate Drains Clean all drains and drain pans at
the start of each cooling season. Check the flow by pouring water
into the drain.
(.'lean or Replace Drain Pan The drain pan should only be
cleaned or replaced by a qualified selaqce technician.
1. Place a plastic sheet on the floor to catch any water that may
spill from the drain pan.
2.
3.
Remove the intake _itte and distribution assembly.
Remove the condensate water in the drain pan by letting
water drain into a 3-gallon bucket.
17
TROUBLESHOOTING (Tables 6-8, and Fig. 19)
Be sure to check for broken wires or loose cable lugs
before troubleshooting system.
Table 6 m Service Indicators
LAMP STATUS INDICATION CORRECTION ACTION
Check the TH1 thermistor for correct resistance.
1 Flash Faulty TH1 Sensor Check for proper connection.
Replace thermistor if necessary.
Check the TH2 thermistor for correct resistance.
2 Flashes Faulty TH2 Sensor Check for proper connection.
Replace thermistor if necessary.
Check system pressures.
3 Flashes Low Pressure Check refrigerant charge.
Check thermistors (TH1 and TH2) for correct resistance.
Check system pressures.
4 Flashes High Pressure Check refrigerant charge.
Check thermistors (TH1 and TH2) for correct resistance.
Check operating voltage.
5 Flashes Low Voltage Check electrical connections.
Check operating voltage.
6 Flashes High Voltage Check electrical connections.
LED.
INDICATES ERROR
POWER LED.
OFF WHEN SYSTEM IS
OPERATING AND FLASHES
WHEN SYSTEM IS IN ERROR.
(DOES NOT INDICATE ERROR CODE)
CLEAN FILTER INDICATOR
FLASHED AFTER 250 HOURS
OF OPERATION
Fig. 19m Indicator Lights
18
Table 7 -BNC/BNQ Thermistor TH-1, TH-2, and TH-3 Temperature to Resistance Conversion
TEMPEATURE
(OF)
-4.0
-2.2
-0.4
1.4
3.2
5.0
6.8
8.6
10.4
12.2
14.0
15.8
17.6
19.4
21.2
23.0
24.8
26.6
28.4
30.2
32.0
33.8
35.6
37.4
39.2
41.0
42.8
44.6
46.4
48.2
50.0
51.8
53.6
55.4
57.2
59.0
60.8
62.6
64.4
66.2
68.0
69.8
71.6
73.4
75.2
77.0
78.8
80.6
82.4
84.2
86.0
87.8
89.6
91.4
93.2
95.0
96.8
98.6
NOTE:
TEMPERATURE
(°C)
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
2O
21
22
23
24
25
26
27
28
29
3O
31
32
33
34
35
36
37
Resistance tolerance _+3%.
TEMPERATURE TEMPERATURE MINIMUM MEAN MAXIMUM
TOLERANCE TOLERANCE RESISTANCE RESISTANCE RESISTANCE
(OF) (°C) (K_Q) (K_Q) (K_Q)
_+2.0 _+1,1 30.89 32.44 34.05
•+2.0 _+1,1 29.46 30.93 32,45
•+2.0 _+1,1 28.12 29.51 30,94
•+2.0 _+1.1 26.84 28.16 29.51
•+2.0 _+1.1 25.64 26.88 28.15
•+2.0 _+1.1 24.49 25.66 26.87
•+2.0 _+1.1 23.40 24.52 25.66
•+2.0 _+1.1 22.38 23.43 24.50
•+2.0 _+1.1 21.40 22.39 23.41
_+2.0 _+1.1 20,47 21.41 22.38
_+1.8 _+1.0 19,59 20.48 21.40
_+1.8 _+1.0 18,74 19.59 20.45
_+1.8 _+1.0 17,94 18.74 19.56
_+1.8 _+1.0 17,17 17.93 18.71
_+1.8 _+1.0 16,44 17.16 17.90
_+1.8 _+1.0 15,75 16.43 17.13
_+1.8 _+1.0 15,10 15.74 16.40
_+1.8 _+1.0 14,47 15.08 15.71
•+1.8 _+1.0 13.87 14.46 15.05
•+1.8 _+1.0 13.31 13.86 14.42
•+1.8 _+1.0 12.77 13.29 13.83
•+1.8 _+1.0 12.25 12.74 13.25
•+1.8 _+1.0 11.75 12.22 12.70
•+1.8 _+1.0 11.28 11.73 12.18
•+1.8 _+1,0 10.83 11.25 11,68
•+1.8 _+1,0 10.40 10.80 11.21
•+1.8 _+1,0 9.986 10.370 10.76
•+1.8 _+1,0 9.595 9.960 10.33
_+1.8 _+1.0 9,222 9.569 9.921
_+1.8 _+1.0 8,866 9.196 9.530
_+1.8 _+1.0 8,526 8.840 9.157
_+1.8 _+1.0 8,197 8.496 8.797
_+1.8 _+1.0 7,883 8.167 8.453
•+1.6 _+0.9 7.583 7.853 8.125
_+1.6 _+0.9 7,296 7.553 7.812
_+1.6 _+0.9 7,022 7.267 7.513
•+1.6 -+0.9 6.761 6.993 7.227
•+1.6 -+0.9 6.510 6.731 6.954
•+1.6 _+0.9 6.271 6.481 6.693
•+1.6 _+0.9 6.042 6.242 6.444
•+1.6 _+0.9 5.822 6.013 6.205
•+1.6 _+0.9 5.611 5.793 5.975
•+1.6 _+0,9 5.408 5.581 5,755
•+1.6 _+0,9 5.214 5.379 5,544
•+1.6 _+0,9 5.028 5.185 5,343
•+1.6 _+0,9 4.850 5.000 5,150
•+1.6 _+0,9 4.675 4.821 4,968
•+1.6 _+0,9 4.508 4.650 4,793
•+1.6 _+0,9 4.347 4.486 4,626
•+1.8 _+1,0 4.193 4.329 4,466
•+1.8 _+1,0 4.046 4.179 4,312
•+1.8 _+1.0 3.904 4.033 4.163
•+1.8 _+1.0 3.767 3.894 4.020
•+1.8 _+1.0 3.637 3.760 3.884
•+1.8 _+1.0 3.511 3.631 3.752
•+1.8 _+1.0 3.391 3.508 3.626
•+2.0 _+1.1 3.275 3.390 3.505
_+2.0 _+1.1 3,164 3.276 3.389
19
Table 7 -BNC/BNQ Thermistor TH-1, TH-2, and TH-3 Temperature to Resistance Conversion (Cont.)
TEMPEATURE TEMPERATURE TEMPERATURE TEMPERATURE MINIMUM MEAN MAXIMUM
TOLERANCE TOLERANCE RESISTANCE RESISTANCE RESISTANCE
(OF) (°C) (OF) (0C) ( K=o_)(KO_) (K=o_)
100.4 38 _+2.0 _+1.1 3,058 3,167 3.277
102.2 39 _+2.0 _+1.1 2,956 3,062 3.169
104.0 40 _+2.0 _+1.1 2.857 2.961 3.066
105.8 41 _+2.0 _+1.1 2,762 2,864 2.966
107.6 42 _+2.0 _+1.1 2.671 2.770 2.870
109.4 43 _+2.2 _+1.2 2.583 2.679 2.777
111.2 44 _+2.2 _+1.2 2.498 2.593 2.688
113.0 45 _+2.2 _+1.2 2.417 2.509 2.602
114.8 46 _+2.2 _+1.2 2.339 2.429 2.520
116.6 47 _+2.2 _+1.2 2.264 2.352 2.441
118.4 48 _+2.3 _+1.3 2.192 2.227 2.364
120.2 49 _+2.3 _+1.3 2.122 2.206 2.291
122.0 50 _+2.3 _+1.3 2.055 2.137 2.220
123.8 51 _+2.3 _+1.3 1.990 2.070 2.151
125.6 52 _+2.3 _+1.3 1.928 2.006 2.085
127.4 53 _+2.3 _+1.3 1.867 1.943 2.021
129.2 54 _+2.3 _+1.3 1.809 1.883 1.959
131.0 55 _+2.5 _+1.4 1.753 1.826 1.900
132.8 56 _+2.5 _+1.4 1.699 1.770 1.842
134.6 57 _+2.5 _+1.4 1.647 1.717 1.787
136.4 58 _+2.5 _+1.4 1.597 1.665 1.734
138.2 59 _+2.5 _+1.4 1.549 1.615 1.683
140.0 60 _+2.5 _+1.4 1.503 1.567 1.633
141.8 61 _+2.7 _+1.5 1.458 1.521 1.585
143.6 62 _+2.7 _+1.5 1.414 1.476 1.539
145.4 63 _+2.7 _+1.5 1.372 1.432 1.494
147.2 64 _+2.7 _+1.5 1.332 1.391 1.451
149.0 65 _+2.7 _+1.5 1,293 1,350 1.409
150.8 66 _+2.9 _+1.6 1.255 1.311 1.369
152.6 67 _+2.9 _+1.6 1.219 1.274 1.330
154.4 68 _+2.9 _+1.6 1.184 1.237 1.292
156.2 69 _+2.9 _+1.6 1.150 1.202 1.256
158.0 70 _+2.9 _+1.6 1.117 1.168 1.221
NOTE: Resistance tolerance _+3%.
20
Table 8 -- General System Troubleshooting Guide
SYMPTOM CORRECTIVE ACTION
Checkfor proper connectionof power at disconnect
Unit Falls to Start.
Only Indoor Fan
Works when Cooling
or Heating is Desired.
NOTE: Indoor fan runs
continuously in
cooling mode.
PROBABLE CAUSE
Powersupply fromoutdoor unit to indoor
unitis not connected.
Power supplyto unit not connected
(POWER LEDOff).
Fuse blown/POWER LED Off).
ON/SEND button has not been pressed.
Indoor unitdoes net receive transmitted commands
The selectedmode is Fan Only,or Coolwhen
heatingis desired.
Temperature isset to a value which is
too high(in Cool mode).
Resetcircuit breakeror replace line fuse.
Press ON/SENDbutton on remote control.
Make sure that nothingis blocking the remote controltransmissionto the unit.
Check if the remote control is in the desired mode. If not, selectthe
correct mode (refer to User manual). Also note that every 15 minutes
(maximum) the compressorwill be switched minimallyon for 3 minutes.
Only Indoor Fan Motor Overload safety deviceon compressoris cut out
and Outdoor Fan Motor due to high temperature
areWorking. No Cooling Compressorrun capacitor isburnt. Replacecompressor runcapacitor
and/or Heating Takes Compressor winding shorted. Replacecompressor
Place.
No Air Supply at Indoorfan motor is blocked or turns slowly.
Indoor Unit
(Compressor Operates). Indoorfan motor capacitor is burnt
Indoorfan motor winding is burnt
In Heat mode: Delayed start for indoorfan motor.
Clogged air filters
Lackof refrigerant. Ice formation on the evaporatorcoil.
gas leak.
Clogged air filters
A!C operatingin defrost cycle.
Observe the temperature settingon the remote control Also notethat
each 15 minutes(maximum), the compressorwill be switched on
minimallyfor 3 minutes
Switch oft powerand try againafter one hour.
1. Check voltage. Repairwiring if necessary.
2. Check indoor fan wheel if tight on motor shaft. Tightenif necessary
Replaceindoor fan motor capacitor.
Replaceindoor fan motor.
Normalsoftware delay (maximumof 20 sec).
Clean filters.
Unitmust be charged (accordingto the nameplate) after localizingthe
Low Capacity.
Clean filters.
In Heat Mode, Only Wait 10 minutes (maximum) until the unit resumes normaloperation.
Compressor Runs.
Outdoor and Indoor
Fan Motors are Stopped.
Water Accumulates and Drainpan pipeor hose is cloggedor the spoutof drain Disassembleplastic drain pipe fromspout of evaporator drain pan.
Overflows from pan isclogged. Flushwith cleanwater
Evaporator Drain Pan.
The unit is in the Auto, (emergency)mode.
Faultyremote control settings
Unit Does Not Operate in
Desired Mode,
The Unit Receives
Interference from
Other Remote Control
or the Remote Control
Interferes with Other
Instruments.
Remotecontrol Iow battery.
Common InfraredCode
Pushbuttononce to cancelAuto, (emergency)mode.
1. If remote control symbols respond to the commands correctly,check
the unit ID Code (Standardor Alternative).Refer to "Changing Unit
ID Code"in the Owner's Manual.
2. If Cool commands are OK, but Heat symbol is skipped on LCD, refer
to setting the remoteto coolingor heat pumpon the Owner's Manual.
3. Replace remote control.
Replaceremote controlbatteries.
Modify the RemoteControl IR transmissioncode.
Referto "Changing Unit IDCode" in the Owner's Manual.
IMPORTANT:
The units are designed to work in heat mode only down to -10°C (14°F) outdoor
ambient temperature.
If at starting time outdoor temperature is equal or lower than -10°C (14°F) the unit
will not start and the filter led will flash five (5) times to indicate that low temperature
protection is activated.
Copyright 2006 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at anytime, specifications or designs without notice and without incurring obligations.
Printed in Israel
21

Navigation menu