CARRIER Air Conditioner/heat Pump(outside Unit) Manual L0801361
User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
rn to the Expertg_ Installation Instructions NOTE: Read installation. the entire instruction manual SAFETY CONSIDERATIONS before starting the 5, (See Fig. 1.) 6, Improper installation, adjustment, alteration, When passing refrigerant tubes through the wall. seal opening with RTV or other pliable silicon-based caulk. service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual packaged with the kits or accessories when installing. Avoid direct tubing contact with water floor joists, wall studs, floors, and walls. tubing.(See g, Ensure conform 10. Isolate Electrical Recognize Code (NEC) safety information. 7 is the safety-alert these signal words: DANGER, insulation (See Fig. 1.) by using metal sleeves of insulation. tubing and structure INDOOR WAL_7 LIQUID TUBE or b........ J and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies which could result in personal injury or death. CAUTION to shape WALL'-_ symbol/_. WARNING, insulation. straps from OUTDOOR and completely use hanger straps which are 1 in. wide and to shape of tubing hanger is pliable CAULK When you see this symbol on the unit and in instructions manuals, be alert to the potential for personal injury. Understand insulation tube. NOTE: Avoid contact between for special requirements. This tubing vapor bent to conform thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Fig. 1.) that 9. When necessary, Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions duct work. 7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with surrounds instructions pipes, ............. r'q THROUGH THE WALL hazards is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions operation. which will result in enhanced ELECTRICAL SHOCK Failure to follow or death. this warning installation, reliability, or HAZARD could result in personal Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. INSTALLATION NOTE: In some gas pulsations RECOMMENDATIONS cases noise from improper in the living installation area has been traced to of equipment. 1. Locate unit away from windows, patios, decks, unit operation sound may disturb customer. 2. Ensure that vapor and liquid tube diameters etc. where are appropriate for unit capacity. 3. Run refrigerant unnecessary 4. Leave some vibration. tubes turns slack as directly as possible by avoiding and bends. between structure and unit SUSPENSION injury to absorb A94028 Fig. 1 - Connecting Tubing Installation When outdoor unit is connected to factory-approved indoor outdoor unit contains system refrigerant charge for operation unit. with ARI rated indoor unit when connected by 15 ft. (4.57 m) of field-supplied or factory accessory tubing. For proper unit operation, check refrigerant charge using charging information located on control this instruction. IMPORTANT: residential box cover and/or Maximum applications IMPORTANT: filter drier. Obtain branch. Always liquid-line including install replacement in the Check Charge size is 3/8-in. section of OD for all line line. the factory-supplied liquid-line filter driers from your distributor or INSTALLATION Check Operating and Job Site Remove without accessory operating ambient maximum outdoor Equipment Unpack Unit Move unit. to final location. carton taking care not to damage minimum outdoor operating ambient in cooling mode is 55°F (12.78°C), and the maximum outdoor in cooling mode is 125°F (51.67°(?). The operating ambient in heating mode is 66 °F (18.89°C). Inspect Check Equipment File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. Check It contains information needed to properly install rating plate to be sure unit matches job specifications. Install on a Solid, Level Mounting If conditions or local codes require unit. Pad the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location. For Ambient The hurricane Certification tie downs, (Professional On rooftop applications, unit above a load-bearing contact distributor Engineer), mounted baffes. NOTE: Conditioners must and be level manufacturer Clearance When it is properly and in. long. (See Fig. 3.) The defrost thermostat should be located on stub tube. Note that there is only one stub tube used with liquid header, and on most units it is the bottom circuit. to adequately support unit to building. Consult local Heat DEFROSTD THERMOSTAT 5 mph may require - Residential Split Pumps for wind baffle A97517 to within _+2° (_+3/8 in./ft) Location per specifications. Make Piping Connections Requirements installing, allow sufficient unit. For proper airflow, a 6-in. unit and 12-in. (304.8 mm) space for airflow clearance, (152.4 mm) clearance on 1 side of on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units. Position so water, snow, or ice from roof or eaves cannot fall on unit. On rooftop surface. located and PE wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above directly to ensure Fig. 3 - Defrost Thermostat Unit compressor thermostat mount on level platform or frame. Place wall and isolate unit and tubing set from units exposed to winds above Consult the Service Manual System Air construction. defrost securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of the one of the feeder tubes, there is a 3/8 in. O.D. stub tube approximately 2 if required. structure. Arrange supporting members and minimize transmission of vibration codes governing rooftop applications. Roof wind for details Check Defrost Thermostat applications, locate unit at least 6 in. above roof PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow or death. this warning Relieve pressure and recover repair or final unit disposal. Use all service ports and including solenoid valves. could result in personal all refrigerant open before all flow-control injury system devices, 3/8-in. (9.53 mm) Dia. Tiedown Knockouts in Basepan(2) Places UNIT DAMAGE HAZARD Failure to follow this caution or improper operation. may result in equipment damage If ANY refrigerant tubing is buried, provide a 6-in (152.4 mm). vertical rise at service valve. Refrigerant tubing lengths up to 36-in (914.4 mm). may be buried without further special consideration. Do not bury lines longer than 36 in (914.4 mm). 1 B l View From Top Outdoor UNIT BASE PAN Dimension 26X26 31 1/2X31 35 X 35 1/2 TIEDOWN KNOCKOUT LOCATIONS in. (ram) A B C 9 1/3(231.3) 4 9 1/8(231,8) 6 9/16(166,7) 24 9 1/8 6 28 (231,8) 7/16(112,7) 9/16 21 (166,7) 1/4(539.8) 11/16(627,1) 7/16 (722,3) A05177 Fig. 2 - Tiedown Knockout Locations units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 80 ft. substantial capacity the recommendations and performance losses can occur. Following in the Application Guideline and Service Manual-Residential Split-System Air Conditioners and Heat Pumps will reduce these losses. Refer to Table 1 for accessory requirements. Refer to Table 2 for field tubing diameters. There are no buried-line applications greater than 36 in. (914.4 mm) If refrigerant tubes or indoor coil are exposed to atmosphere, must be evacuated to 500 microns to eliminate contamination moisture in the system. they and Table REQUIRED Accessory Ball Bearing Fan Motor Start Assist Capacitor Relay Crankcase and Heater Evaporator Freeze Thermostat Hard Shutoff TXV Isolation Liquid Relay Line Solenoid REQUIRED FOR LONG LINE APPLICATIONS* Valve Yest No No Yes Yes No Yes Yes No Yes Yes No Yes No Yes No No See No or Long- Line Application Guideline Yes Feet Recommended Unit Connected To Factory Approved Table unit contains with approved correct system refrigerant ARI rated indoor unit when 15 ft (4.57 m) of field-supplied or factory-accessory factory supplied filter drier. Check refrigerant charge charge connected Refrigerant Tubing Connect tube to fitting on outdoor vapor and Sweat Connections unit vapor UNIT 018, 024 030, 036 042, 048 060 DAMAGE tube valves on liquid HAZARD to follow this caution or improper operation. Service valves must be wrapped such as a wet cloth while brazing. result in equipment Tube Diameter Connection Diameter 3_ 3_ 5/8 5/8 38 38 3/4 3/4 38 38 7/8 38 38 7/8 7/8 1 Tube diameters 2 Do not apply capillary are for tota_ equivalent * For Tubing Set _engths between 80 and 200 ft. (24.38 and 6098 m) horizontal or 20 ft. (6.10 m) vertical differential (250 ft/762 re)Total Equivalent Length), refer to the Longline GuidelineAir Conditioners and Heat Pumps using Puron ® Refrigerant Liquid lengths up to 80 ft (2438 tube or fixed orifice indoor I/8 Line Filter Drier m) coils to these units Indoor Refer to Fig. 5 and install filter drier as fnllows: 1. Braze 5 in. (127 mm) liquid tube to the indoor in a heat-sinking m)* Tube Diameter 1 material coil. 2. Wrap filter drier with damp cloth. 3. Braze filter drier to 5 in. (127 arm) long liquid tube from step 1. Remove plastic retainer holding outdoor piston in liquid service valve, leaving the piston and piston retainer inside the valve. sweat/flare refrigerant VAPOR up to 80 ft, (24.38 Notes: Install may Liquid (In.) SIZE Connection Diameter tubing, and for maximum service Long[ine and Recommended Diameters LIQUID Connections (see Table 2). Connect liquid tubing to adapter service valve. Use refrigerant grade tubing. Connect Connect 2 - Refrigerant Split-System RATED for by efficiency. Failure damage Recommended refer to Residential and Vapor Tube Outdoor operation UNIT No No Indoor FOR No No For tubing line sets between 80 and 200 ft. (24.38 and 80.98 m) and/or 20 ft. (8.09 m) vertical differential, Applicat@n Guideline. t Additional requirement for Low-Ambient Controller (full modu[at@n feature) MotorMaster '_ Control. Outdoor Unit REQUIRED SEA COAST APPLICATIONS (Within 2 miles / 3.22 kin) Standard (Over 80 ft. / 24,38 m) Standard Yes Motor Master@ Control Low Ambient Switch Support Usage COOLING APPLICATIONS (Below 88°F / 12.8°C) Standard Accumulator Compressor 1 - Accessory FOR LOW-AMBIENT 4. Connect and braze liquid refrigerant tube to the filter drier. adapter provided, to valve. (See Fig. 4.) tubing to fittings on outdoor unit vapor and liquid service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth. tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Do not use soft solder (materials which melt below 800°F/427°C). Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints. TEFLON ® SEAL A05227 Fig. 5 - Liquid Line Filter Drier Evacuate UNIT Failure damage Refrigerant DAMAGE Tubing to follow this caution or improper operation. Refrigerant A05226 Fig. 4 - Liquid Service Valve recommended tubes Coil HAZARD Never use the system compressor LIQUID SERVICE VALVE and Indoor and indoor deep vacuum may as a vacuum coil should method result in equipment pump. be evacuated of 500 microns. using the The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen. 3 Deep Vacuum Connect Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method Ground and Power Wires Connect ground wire to ground connection in control box safety. Connect power wiring to contactor as shown in Fig. 7. for is the most positive way of assuring a system is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 6. 5000 4500 SHOCK Failure death. this warning to follow HAZARD could result in personal injury or The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. 4000 LEAKIN 3500 ELECTRICAL SYSTEM 3000 2500 o 2000 Connect ground wire to ground connection in control box safety. Connect power wiring to contactor as shown in Fig. 7. DISCONNECT[_ PER N.EC AND/OR_ LOCAL CODES 1000 TIGHT DRY SYSTEM 500 0 1 2 3 4 5 1500 Tubing Check IMPORTANT: Check and outdoor not rubbing attention secure CONTACTOR 7 FIELD POWER WIRING _uO WET Fig. 6 - Deep Vacuum Final 6 MINUTES A95424 3 PHASE Graph FIELD ONLY factory tubing _ GROUNDG LUG on both indoor A94025 unit has not shifted during shipment. Ensure tubes are against each other or any sheet metal. Pay close to feeder tubes, makings BLUE ( GROUND WIRING to be certain for Fig. 7 - Line Connections CDNTAU,OR 24VAt CBM sure wire ties on feeder tubes are and tight. Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper protection voltage. device. See unit NOTE: Operation of unit rating plate for recommended on improper abuse and could affect unit reliability. install unit in system permissible limits. where voltage line voltage circuit constitutes See unit rating plate. Do may fluctuate above not OFF:NO 24VAE ON:OK or below FLASH:PHASE PROBLEM o o L3 LI A00010 Fig. 8 - 3-Phase (Applies to 3-Phase Table 3 - 3-Phase Installation Make of filter Electrical drier in uid line is aired. Connections Failure death. SHOCK Do not supply cover removed. power with compressor NOTE: Use copper wire only between NOTE: Install branch circuit unit starting current. to handle and readily Route Remove accessible Ground and access panel from disconnect control box. Route could result in personal to unit disconnect Locate from unit, per Section Power power box size per NEC within 440-14 sight from wiring to unit wiring. hole provided LED Indicators STATUS Extend Control 24v connect Instructions No call for cornpressor operation Reversed phase Normal Wiring control leads Only) to wires through control for wiring wiring. specific Use No. 18 AWG color-coded, control wiring See Thermostat unit combinations. insulated grommet wires and into unit and Installation (See Fig. 9.) (35°C minimum) wire. If thermostat is located more than 100 ft (30.5 m) from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop. All wiring must be NEC incoming power leads. Class 1 and must be separated Use furnace transformer, fan coil transformer, transformer for control power, 24v/40va minimum. of NEC. Wires to gain access through or switch and unit. of adequate disconnect injury terminal disconnect Units Monitor OFF FLASHING ON HAZARD to follow this warning Control LED Connect ELECTRICAL Monitor NOTE: Use of minimum 40va power available or from accessory 24v accessories may exceed requirement. Determine total transformer the loading andincrease thetransformer capacity orsplittheloadwith anaccessory transfornmr asrequired. Final Wiring Cheek IMPORTANT: to ensure Check terminations 24 VAC HOT factory wiring are secured and field properly. ensure wires are not in contact with tubing, Compressor Heater Crankcase When equipped with a crankcase minimum of 24 hr before starting only, set thermostat outdoor unit. to OFF wire routing to HEAT STAGE electrical disconnect j--. _¢LE] sheet metal, etc. close ____ 24 VAC COM _Jbmt_l-w_ 2 F_ COOL/HEAT STAGE 1 heater, furnish power to heater a unit. Tn furnish power to heater and = wire connections Check HEAT PUMP TYPICAL FAN COIL HP THERMOSTAT -4-Tc_, ivv,Jl INDOOR FAN to RVS COOLING A crankcase heater is required if refrigerant tubing 80 ft. Refer to the Long Line Guideline-Residential Air Conditioners and Heat Pumps. Install Electrical is longer than Split-System EMERGENCY HEAT IFAVAILABLE Accessories LEGEND Refer to the accessories individual instructions packaged with kits or when installing. Start-Up 24v FACTORY 24V FIELD WIRIN G WIRING FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLE ME NTAL HEAT R ELAY PERSONAL Failure injury. INJURY to follow HAZARD this caution may result in personal A02325 / Ag741S Wear safety glasses, protective clothing, and handling refrigerant and observe the following: Front seating service valves are equipped gloves Fig. 9 - Generic when (See Thermostat with Schrader Sequence NOTE: Failure HAZARD to follow Turn this caution may result in environmental control on power Cooling On a call for cooling, AND SAFETY board upon is equipped with 5 minute any interruption to indoor Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal. OPERATION Instructions combinations) and lockout of power. outdoor units. Transformer is energized. damage. UNIT unit of Operation Defrost timer that is initiated ENVIRONMENTAL Diagrams Installation for specific valves. Wiring thermostat makes circuits R-O, R-Y, and R-G. Circuit R-O energizes reversing valve, switching it to cooling position. Circuit R-Y sends low voltage through the safeties and energizes the T1 terminal on the circuit board. If the compressor has been off for 5 minutes, or power has not been cycled for 5 minutes, the OF2 relay and T2 terminal will energize. This will close the contactor, and start the outdoor fan motor and HAZARD compressor. Failure to follow this caution equipment damage or improper Do not overcharge may result operation. in personal injury, When the cycle is complete. R-Y is turned compressor and outdoor fan. The 5 minute system with refrigerant. Do not operate unit in a vacuum Do not disable low pressure or at negative counting. Compressor will not expires. In the event of a power pressure. not allow switch in scroll compressor applications. Compressor Follow dome temperatures these steps start up 1. After system is evacuated, service valves. fully open liquid and vapor refrigerant flow (back seated). Replace caps finger-tight tighten with wrench an additional 1/12 turn. room disconnects thermostat point is below indoor 5. Set room ON or minutes. thermostat to energize at desired come on again until this delay interruption, the time guard will cycle for 5 minutes. Heating system: 2. Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to 4. Set stopping the guard begins NOTE: If the indoor blower off delay is enabled, it will run up to an additional 90 seconds to increase system efficiency. may be hot. to properly 3. Close electrical another off, time and system. ambient temperature. or COOL circuit. If the compressor has been off for 5 minutes, or power has not been cycled for 5 minutes, the OF2 relay and T2 terminal will energize. This will motor and compressor. close the contactor, start the outdoor set When the cycle is complete. R-Y is turned compressor and outdoor fan. The 5 minute and fan control to counting. Compressor will not come on again until this time delay expires. In the event of a power interruption, the time guard will 15 not allow AUTO mode, as desired. Operate Check system refrigerant charge. Be unit for another cycle for 5 minutes. off, time fan sure temperature. to HEAT On a call for heating, thermostat makes circuits R-Y and R-G. Circuit R-Y sends low voltage through the safeties and energizes the T1 terminal on the circuit board. T1 energizes the defrost logic stopping the guard begins Quiet Shift Check Quiet shift is a field which will eliminate selectable defrost mode (factory set to OFF), occasional noise that could be heard at the start of defrost and restarting by placing position. When cycle DIP switch of heating 3 on defrost Quiet Shift switch board is placed initiated, the following sequence valve will energize, compressor cycle. It is selected (see Fig. 10) in the ON in ON position, and a defrost is of operation will occur. Reversing will turn off for 30 seconds, and then turn back on to complete defrost. At the start of heating after conclusion of defrost, reversing valve will de-energize, compressor will turn off for another 30 seconds, and the fan will turn off for 40 seconds, before starting in the heating mode. Defrost The defrost control is a time/temperature control selectable settings of 30, 60, 90, or 120 minutes, minutes. These settings represent after closure begins. of the defrost The thermostat defrost the amount thermostat senses has field set to 90 of time that nmst pass before coil which factory the defrost temperature sequence throughout heating cycle. When the coil temperature reaches the defrost thermostat setting of approximately 32 °F, it will close, which energizes the DFT terminal and begins the defrost timing sequence. charge amount and desired subcooling are shown on unit rating plate. Charging method is shown on infnrmation plate inside unit. To properly check or adjust charge, conditions must be favorable for subcooling charging. when the outdoor temperature is (21.11°C and 37.78°C), 70°F and 80°F below: Favorable conditions exist between 70°F and 100°F and the indoor (21.11°C temperature and 26.67°C). Follow is between the procedure Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15ft (4.57 m) respectively. For standard refrigerant line lengths (80 ft/24.38 m or less), allow system to operate in cooling mode at least 15 minutes. If conditions are favorable, check system charge by subcooling method. If any adjustment is necessary, operate for 15 minutes charged the Charge Factory adjust charge slowly and allow system to to stabilize before declaring a properly system. If the indoor temperature is above 80°F (26.67"C), and the outdoor temperature is in the favorable range, adjust system charge by weight based on line length and allow the indoor temperature to drop to 80W by subcooling (26.67°C) before attempting method as described above. to check system charge When the DFT has been energized for the selected time, the defrost cycle begins. Defrost cycle is terminated when defrost thermostat If the indoor temperature is below temperature is not in the favorable opens, or automatically length above or below 15ft (4.57 m) only. Charge level should then be appropriate for the system to achieve rated capacity. The charge level could then be checked at another time when the both indoor Defrost after 10 minutes. Speedup To initiate a forced defrost, speedup pins (J1) must be shorted with a fiat head screwdriver for 5 seconds and RELEASED. If the defrost thermostat is open, a short defrost cycle will be observed and outdoor NOTE: temperatures If line length are in a more favorable is beyond (actual length depends on Quiet Shift switch position). When Quiet Shift is off, only a short 30 second defrost cycle is observed. With Quiet Shift ON. the speedup sequence is one minute; 30 second compressor off period followed by 30 seconds of defrost with ft (6.10 m) vertical separation, special charging requirements. compressor operation. When returning compressor will turn off for an additional for 40 seconds. To If the defrost thermostat is closed, to heating 30 seconds a complete mode, the and the fan defrost cycle is initiated. If the Quiet Shift switch is turned on, the compressor will be turned off for two 30 second intervals as explained previously. Heating Check check Chart system 70°F (21.11°C), or the outdoor range, adjust charge for line set 80 ft (24.38 range. m) or greater See Long Line than 20 Guideline for Procedure operation during heating cycle, refer to the Heating Check Chart on outdoor unit. This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, not be correct. Do not use chart system refrigerant to adjust refrigerant charge may charge. Final Checks IMPORTANT: Before leaving job. be sure to do the following: 1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub-through or wire pinching. 2. Ensure adding covers. 3. Tighten tight. that all wiring panels service and tubing and covers. valve is secure Securely stem caps fasten in unit before all panels to 1/12-turn past 4. Leave Owner's Manual with owner. Explain operation and periodic maintenance requirements in manual. Speedup pil_s Shift DIP 5. Fill out Dealer file. switches A05378 Fig. 10 - Defrost Table 4 - Defrost PARAMETER Control Control Speedup-Timing Sequence MINIMUM MAXIMUM SPEEDUP (MINUTES) (MINUTES) (NOMINAL) 30 - minute cycle 27 33 7 sec 50 - minute cycle 45 55 12 sec 90-minute cycle 81 99 21 sec lO-minute cycle 9 11 2 sec 4.5 5.5 1 sec 5 minutes Installation CARE Checklist and place and finger system outlined in customer AND MAINTENANCE For continuing high performance and to minimize possible equipment failure, periodic maintenance must be perfnrmed on this equipment. Frequency of maintenance areas, such as coastal information. may vary depending upon geographic applications. See Users Manual for PURON® • Puron (R-410A) refrigerant components • Puron operates are designed refrigerant • Recovery • Puron QUICK charging • Manifold at 50- 70 percent service pressure • Puron, pumps • Do not use liquid-line moisture moisture driers. Evacuate • Observe • All indoor valves pressures less than 600 psig. than 72 hours. materials. with wet cloth when brazing. on every unit. TXV or piston metering device, it must be changed refrigerant, evacuate then break vacuum prior to recharging. into the atmosphere. tube coils. cautions, coils must be installed to a hard shutoff Puron TXV. while it is under a vacuum. for service, recover to 500 microns all warnings, retard. oil to atmosphere. filter drier is required to atmosphere • Do not use capillary hose when with POE oils. Do not expose with an R-22 must be opened • Do not vent Puron device in the manifnld TXV. • If indoor unit is equipped • When system type metering from oil. to certain plastics and roofing liquid-line • Do NOT use an R-22 • Never open system or DOT BW400. filter drier in liquid line. rapidly. • Wrap all filter driers and service approved Use a commercial rating. line filter driers in line longer • POE oils may cause damage • A factory and replacement to detect HFC refrigerant. filter driers with rated working suction • Do not install a suction-line • POE oils absorb equipment operating is only compatible will not remove • Do not leave Puron Be sure that servicing rating must be 400 psig, DOT 4BA400 pressure should be designed as with other HFCs, • Vacuum than R-22. be 700 psig high side and 180 psig low side with 550 psig low-side • Use hoses with 700 psig service • Leak detectors pressures with liquid refrigerant. line with compressor sets should higher are rose colored. should be charged into suction GUIDE to operate with Puron cylinders cylinder systems REFERENCE and bold text. with a hard shutoff Puron TXV metering device. with dry nitrogen and replace filter Copyright 2007 Carrier Corp. * 7310 W Morris Manufacturer reserves the right to change, St • Indianapolis, IN 46231 at any time, specifications and designs Printed without in US.A. Edition Date: notice and without 8 12/07 obligations. Catalog No: 25HCA-4SI Reptaces: 25HCA-3SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 8 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Mar 31 04:19:53 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools