Camden CX 12 Switching Network Installation Instructions A128 Manual NF Rev1
User Manual: Camden CX-12 Switching Network Installation Instructions Instructions
Open the PDF directly: View PDF .
Page Count: 10
Download | |
Open PDF In Browser | View PDF |
CX-12 Switching Network & Bi-Directional Door Sequencer Installation Instructions Section 1__________________ General Description For latching (ratchet or alternate action) functions, we recommend our Model CX-1000/78 multi-purpose timer, or Model SA-1 Switching Network. The CX-12 is the latest generation multi-purpose timer. It is designed to be versatile yet user friendly with easy to understand terminology and adjustments. (It supersedes Model CX-11 Ultra) IMPORTANT: Do not apply power to the unit until you have read the instructions fully and made the required adjustments. Used as a make/break relay (or Switching Network) it eliminates the binding of locked automatic doors, by delaying the door operator until the strike or electromagnet (de) activates first. Section 2__________________ Installation A new feature of this model is the ability to select one of 4 Modes of operation – momentary; maintained with Relay 1 held; maintained with Relay 2 held; and bi-directional door sequencing (SEE DIAGRAM 04). In the Momentary position, even a stuck switch input will allow the door to time out and close, thereby providing security to occupants. The CX-12 will however, still operate normally if one of the other inputs is activated. Essentially, it ignores the faulty activation source, as all inputs are isolated. The inputs to the CX-12 may be either dry or wet (powered), meaning that 3-terminal radio receivers may be connected directly to the CX-12 without fear of malfunction. SEE DIAGRAM 01. Mounting The LED’s are visible through the wrap-around sleeve, which also has cutouts for adjusting the potentiometers, and setting the dip-switch. Once the unit has been adjusted, it may be tucked up into the operator header or affixed using the supplied Velcro. Wiring Wiring of this unit is dependent on the mode desired, however the following commonalities apply. Note: Do not wire Safety devices to the CX-12. If installed, wire your safety device directly to the operator control box as per usual. Additionally, we provide a direct connection from an apartment interphone panel. Only Relay #1 (strike) will operate when a voltage is applied to this input. A vestibule courtesy switch will be energized for the time set by Pot. 1. SEE DIAGRAM 03 a or b. CAUTION: Do not apply power to the unit until all secondary wiring is complete, and dip-switches have been set. Select Relay 1 Maintained for an Access Control application. When a maintained signal is applied to WET 1 input, the lock will remain energized, while the DRY 2 input allows a wall switch to open the door. An input on DRY 1 will always unlock and open the door. Both relay outputs are Form C and are rated at 3 amps maximum. Use relay # 1 for the strike or electromagnet. Generally the N.O. & COM. terminals (#3 & 4) are used for a strike, and COM & N.C. (#4 & 5) are used with an electromagnet. SEE DIAGRAM 02b. Select Relay 2 Maintained if you are connecting the CX-12 to a fire alarm panel, or to a presence sensor. In this mode the lock will fire momentarily but the operator relay will be held in as long as the input is maintained. SEE DIAGRAM 02a. The door operator will be wired to relay #2 N.O. & COM terminals (#6 & 7). In a door sequencing application, door 1 is relay #1, and door 2 is relay #2. The unit will operate on 12 or 24 volts, AC or DC. Connect to Terminals 1 & 2, which are non-polarity sensitive. Page 1 of 10 CX-12 Switching Network & Bi-Directional Door Sequencer Installation Instructions An interior switch may be connected to DRY 1 (Terminals 11 & 12). This input will always unlock and open the door when activated. (Regardless of the status of input connected to WET 1). APPLICATIONS & SET-UP INSTRUCTIONS: STANDARD TIMER MODE Off / On Set dipswitches as shown > Refer also to Diagram 01. 1 2 If the interior switch is Wet (powered) connect to WET 2 (Terminals 13 & 14). EXTENDED TRIGGER MODE – RELAY 2 Connect a dry contact such as a wall switch to DRY1 (Terminals 11 & 12). A Wet (powered) output connects to WET 2 (Terminals 13 & 14). Off / On Set dipswitches as shown > 1 2 Upon a switch activation the strike relay will fire for the time set by potentiometer 1 (DOR RL1). After a delay, adjustable by potentiometer 2 (DOO RL2), the operator relay will fire. The hold time for relay #2 is set with potentiometer 2 (DOR RL2). Refer to Diagram 02a. Most modern door operators have built-in time delays, and if so, it is usually desirable to use them to add sufficient hold-open time. In this case adjust the CX-12 to send just a momentary pulse (1 or 2 seconds only). Connect the Wet (powered) output of the Fire panel to WET 2 (Terminals 13 & 14) Observe the door and adjust timers until desired operation is observed. Suitable for connection to a Fire Alarm Panel, this mode will fire the electric lock momentarily, then hold in the operator relay until the input is released. A device with a dry output such as a Presence sensor will connect to DRY 1 (Terminals 13 & 14). Bi-Directional Sequencing MODE Off / On The above dipswitch setting is also used for applications such as apartment entries with an interphone panel. Refer to Diagrams 03a & 03b. Set dipswitches as shown > In each case the interphone input (WET 1) will activate the strike relay only. If a courtesy switch is located in the vestibule, it is connected to DRY 2 (Terminals 15 & 16). This input is only active when the strike relay is energized. Turn on power and activate the Interior input (switch). Observe LED1, which should light immediately. The length of hold time is determined by adjusting the pot marked DOR/RL1, clockwise for more time, counter clockwise for less time. Another application using this mode is door sequencing in one direction only. Connect Door 1 operator to relay 1, and door 2 operator to relay 2. The delay between the two doors is adjusted via the DOO RL2 potentiometer. For bi-directional sequencing refer to specific set-up instructions below. The delay between the two doors is adjusted via the DOO RL2 potentiometer. EXTENDED TRIGGER MODE – RELAY 1 Off / On Set dipswitches as shown > Refer also to Diagram 02b. 1 2 Typically the access panel (or time clock) will be wet (powered) therefore connect to WET 1 (Terminals 9 &10). The exterior activating switch is wired to DRY 2 (Terminals 15 & 16). This input signals the door operator (Relay 2), and is only active when the strike relay is energized. Refer to Diagram 04. 1 2 After the above-mentioned delay, LED2 should light. The length of hold time is adjusted by the pot marked DOR/RL2. The ideal time delay between the two doors is best set by actual walk-testing. It should be set so that a person can walk in either direction without having to pause before the second door activates. Test in both directions. If an emergency (or anti-entrapment) switch is desired in the vestibule, then wire that switch directly to one of the operator inputs. Usually the exterior door is used in this case. Once the desired operation is achieved, proceed to Section 4, for System Inspection Instructions. Page 2 of 10 5502 Timberlea Blvd., Mississauga, ON Canada L4W 2T7 www.camdencontrols.com Toll Free: 1.877.226.3369 File: CX-12_NF_Rev1.doc Revised: 13 January 2010 Part No.: 40-82B103 CX-12 Switching Network & Bi-Directional Door Sequencer Installation Instructions Section 4 _________________ System Inspection Instructions Section 5_________________ Technical Data After the Installation and operational check of the system: Model CX-12 Size 3 ¼” x 2 ¼” x ¾” Mounting Velcro or double-sided tape Enclosure Protective paper sleeve. Operating voltage 12 / 24 Volts, AC / DC Current Draw 18 mA standby, 40 mA max. Response time 0.3 seconds Inputs 2 x “dry” contacts, 2 x “wet” contacts: (3-30 V AC/DC, Optically isolated, non-polarity sensitive). Relay Output 2 x Form C (SPDT) Relay contact rating 3 amps @ 20 VDC Time Delays DOR #1 1 to 30 seconds DOO # 2 1 to 30 seconds DOR #2 1 to 30 seconds Electrical Life 100,000 operations @ rated capacity 500,000 operations @ ½ rated capacity 1. Place warning label on the door (as per ANSI A156.10 or A156.19 guidelines). This will advise the person entering the swing side zone that the door will move. 2. Instruct the owner on door system operation and how to test it. This should be checked on a daily basis. 3. Instruct the owner on what to do if the door or any of its components become damaged. 4. Strongly recommend to the owner that the complete entry be inspected twice a year as part of the service agreement. Section 6_________________ Warranty Camden Door Controls guarantees the CX-12 to be free from manufacturing defects for 3 years from date of sale. If during the first 3 years the CX-12 fails to perform correctly, it may be returned to our factory where it will be repaired or replaced (at our discretion) without charge. Except as stated herein, Camden extends no warranties expressed or implied regarding function, performance or service. Questions? Call us toll-free at 1-877-226-3369 Page 3 of 10 5502 Timberlea Blvd., Mississauga, ON Canada L4W 2T7 www.camdencontrols.com Toll Free: 1.877.226.3369 File: CX-12_NF_Rev1.doc Revised: 13 January 2010 Part No.: 40-82B103 Off / On Radio Receiver 3 - Term. 1 RL1 RL2 LED LED DOR RL1 DOO RL2 DOR RL2 2 3 4 5 6 7 8 24V 1 2 Com Radio CX-12 Wet Input ie- Radio Receiver 9 10 11 12 13 14 15 16 12 / 24 V AC/DC Power Dry Input ie- Push Switch Door Operator Electric Strike MOV Camden Manufacturing Wire MOV (supplied) directly to strike or magnet SCALE: NONE Power for Strike DRAWN BY: DGW DATE: 11/16/09 5502 Timberlea Blvd. Mississauga, Ontario L4W 2T7 REVISED: CX-12 Application Diagram (typical Momentary Operation) DRAWING No: DRG-CX-12-01 FILENAME: CX_12 Diagram 1.vsd Off / On Fire Alarm Panel Shown with maintained & powered signal (Wet) 1 RL1 RL2 LED LED DOR RL1 DOO RL2 DOR RL2 2 FIRE CX-12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 12 - 24 V AC/DC Power Presence Sensor (Dry contact output) Door Operator Electric Strike (If Mag lock used, wire to Terminals 4 & 5) MOV Camden Manufacturing Wire MOV (supplied) directly to strike or magnet SCALE: NONE Power for Strike DRAWN BY: DGW DATE: 11/16/09 5502 Timberlea Blvd. Mississauga, Ontario L4W 2T7 REVISED: CX-12 Application Diagram (with Maintained Operator output) DRAWING No: DRG-CX12-02a FILENAME: CX_12 Diagram 2a.vsd Off / On 1 RL1 RL2 LED LED DOR RL1 DOO RL2 DOR RL2 2 Exterior Switch (in circuit only while Lock Relay is active) CX-12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Interior Switch (Always unlocks and opens door. 12 - 24 V AC/DC Power CAccess Control or Time Clock Sends a powered & maintained signal to keep door unlocked for desired time. Door Operator Electric Strike (If Mag lock used, wire to Terminals 4 & 5) MOV Camden Manufacturing Wire MOV (supplied) directly to strike or magnet SCALE: NONE Power for Strike DRAWN BY: DGW DATE: 11/16/09 5502 Timberlea Blvd. Mississauga, Ontario L4W 2T7 REVISED: CX-12 Application Diagram (with Maintained Lock Output) DRAWING No: DRG-CX12-02b FILENAME: CX_12 Diagram 2b.vsd Optional Vestibule mounted Convenience Switch (Only active when Lock relay energized) Switch opens door Off / On 1 RL1 RL2 LED LED DOR RL1 DOO RL2 DOR RL2 2 CX-12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Interior Switch Unlocks and opens door 12 - 24 V AC/DC Power Apartment Interphone Panel (powered signal) Unlocks door only Door Operator Electric Strike MOV Camden Manufacturing Wire MOV (supplied) directly to strike or magnet SCALE: NONE Power for Strike DRAWN BY: DGW DATE: 11/16/09 5502 Timberlea Blvd. Mississauga, Ontario L4W 2T7 REVISED: CX-12 Application Diagram for Apartment (typical) DRAWING No: DRG-CX12-03a FILENAME: CX_12 Diagram 3a.vsd NOTE: Use this diagram in case the Interphone outputs a dry contact instead of a powered signal. Optional Vestibule mounted Convenience Switch (Only active when Lock relay energized) Switch opens door Off / On 1 RL1 RL2 LED LED DOR RL1 DOO RL2 DOR RL2 2 CX-12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Interior Switch Unlocks and opens door 12 - 24 V AC/DC Power Apartment Interphone Panel (DRY contact) Unlocks door only Door Operator Electric Strike Vestibule Keyswitch (Optional) MOV Camden Manufacturing Wire MOV (supplied) directly to strike or magnet SCALE: NONE Power for Strike DRAWN BY: DGW DATE: 11/16/09 5502 Timberlea Blvd. Mississauga, Ontario L4W 2T7 REVISED: CX-12 Application Diagram for Apt. (with Vestibule Keyswitch) DRAWING No: DRG-CX12-03b FILENAME: CX_12 Diagram 3b.vsd Door #2 Push Switch Off / On 1 RL1 RL2 LED LED DOR RL1 DOO RL2 DOR RL2 2 CX-12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Wet output ie - RF receiver (optional) 12 - 24 V AC/DC Power Door #1 Operator Wet output ie - RF receiver (optional) Door #2 Operator Door #1 Push Switch Camden Door Controls SCALE: NONE DRAWN BY: DGW DATE: 11/16/09 5502 Timberlea Blvd Mississauga, Ontario L4W 2T7 REVISED: CX-12 Application Diagram (Bi-Directional Sequencer operation) DRAWING No: DRG-CX-12-04 FILENAME: CX_12 Diagram 4.vsd
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Author : Jack Lewis Create Date : 2010:01:14 18:53:18-05:00 Modify Date : 2010:01:18 09:52:25-05:00 Tagged PDF : No XMP Toolkit : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00 Metadata Date : 2010:01:18 09:52:25-05:00 Creator Tool : Adobe Acrobat 8.1 Combine Files Format : application/pdf Creator : Jack Lewis Document ID : uuid:40c212de-f1b4-407f-a3d4-ffe021147216 Instance ID : uuid:65de2a7e-fc15-4ee7-bec2-0e0aa6cd2c78 Producer : Adobe Acrobat 8.1 Page Count : 10EXIF Metadata provided by EXIF.tools