Carrier 38TKB018 SERIES330 User Manual CONDENSING UNIT Manuals And Guides L0211022
CARRIER Air conditioner/heat pump(outside unit) Manual L0211022 CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides
User Manual: Carrier 38TKB018 SERIES330 38TKB018 SERIES330 CARRIER CONDENSING UNIT - Manuals and Guides View the owners manual for your CARRIER CONDENSING UNIT #38TKB018SERIES330. Home:Heating & Cooling Parts:Carrier Parts:Carrier CONDENSING UNIT Manual
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
38TKB Air Conditioning Unit HEATING & COOLING Vish www c_rier corn Installation and Start-Up Instructions NOTE: Read the entire instruction manual before beginning the installation. This symbol -+ indicates a change since last issue. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, nr use can cause explosion, fire. electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for inlbrmation or assistance, The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear sal_ty glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize When safety you manuals, see information. This is the safety-alert this symbol on the unit be alert to the potential and for personal symbol A98519 ____) Fig. 1--Model ,_. in instructions or injury. 5. When passing opening Understand these signal words; DANGER. WARNING. and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE: In some cases, gas pulsations from noise improper I. Locate the unit away 2. Ensure that vapor the capacity 3. Run from turns as arc appropriate to by aw_iding and the unit to absorb reserves the dght that to discontinue, Catalog No. 563-754 tubing from joists comes in direct tubing or change at any time, specifications Printed in U.S.A. seal caulk. the (See insulation use hanger the hanger unit straps with the and completely sur- (See the insulation Fig. 3.) by using metal of the insulation. to factory-approved charge For proper install indoor unit. for operation with operation, located size is 3/8dn. a liquid-line part filter nmnher. on control O.D. tbr all drier. Reler Obtain to filter or branch. notice and without incurring Pg 1 by check long line. for appropriate local distributor unit information liquid-line including without are I in. wide and insulation. unit of the same size when connected tubing. Always or designs Form 38TKB-SSI floor and studs with a contact which refrigerant using charging Digesl your from system Maximum Data strops to the shape is connected indoor charge is pliable of the tubing bent to conform applications from dnctwork, line. unit contains Product which to the shape outdoor residential with water pipes, refrigerant the vapor factory-approved driers PC 101 wall. (See Fig. 3.) IMPORTANT: the structure the silicombased and walls. necessary, refrigerant box cover. contact or strap IMPORTANT: possible through floors, 15 fi of field-supplied vibration. Manufacturer wire tubing. outdoor and bends. 4. Leave some slack between rigid When 1.) as 7, Do not suspend sleeves has been traced to lineset wall studs, 10. Isolate of equipment. line diameters directly direct joists, conform windows. and liquid tubes area installation of the unit. (See Table refrigerant unnecessary in the living 6. Avoid 9. When RECOMMENDATIONS tubes or other pliable Fig. 3.) rounds Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death. refrigerant with RTV 8. Ensure 'i2LIitTIIX,-1 ' INSTALLATION 38TKB 11-98 obligations. Replaces: 38TKB-3SI Table 1--Refrigerant Connections and Recommended LIQUID UNIT SIZE Connection Diameter VAPOR Diameter Connection Tube Diameter Liquid and Vapor Tube Diameters (In.) 018, 024 3/8 3/8 5/8 5/8 030, 036 3/8 3/8 3/4 3/4 042, 048 060 3/8 3/8 3/8 3/8 7/8 7/8 Notes: 7/8 1-1/8 1 Tube diameters are for lengths up to 50 It For tube sets ever 50 ft. consu)t Residential 2 DO not apply capillary tube indoor coils to these units INSTALLATION Step 1--Check INSPECT EQUIPMENT--File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit service panel. (See Fig, 2.) It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications. on a Solid, Level Mounting should be used and fastened 1-1/8 Guideline. Roof mounted units exposed to winds above 5 mph may require wind baffles. Consuft Low-Ambient Guideline for wind baffle construction. Pad NOTI=: Unit must be level to within -+2_ per compressor manufacturer specifications. If conditions or local codes require the unit be attached to a pad, bolts 7/8 1-1/8 On rooftop applications, mount on level platfonn Dr frame. Place unit above a load-bearing wall and isolate unit and tubing set frDm structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications. UNPACK UNIT-- Move to final location. Remove carton taking care not to damage unit. tie down Long-Line Application 3/4 provided in unit base paR. Refer to unit mounting pattern shown in Fig. 2 te determine base pan size and knockout hole location. Equipment and Job Site Step 2--Install VAPOR (LONG LINE) Tube Diameter Connection Diameter 5/8 3/4 7/8 7/8 Tube Diameter through knockouts AIR tN AIR DISCHARGE I, 1, - i _ i ,o_ IL --', 3f8" (9 53) DIA TIEDOWN KNOCKOUTS IN SASEPAN ! "i (2) PLACES c AIR DISCHARGE _- UNIT MOUNTING PATTERN VIEW FROM TOP AIR IN "_ B 8 3G6" (207.9) • ,_1_ AIR DISCHARGE 1 9/1"_1_16".-_d_ o A 2 1/2" 1637) _-718" FIELD POWER SUPPLY CONN (2222) DIA HOLE WITH I l/B" (28 57) DIA KNOCKOUT (ALL SIZES) AND 1 3/B" (3492) DIA KNOCKOUT SIZES ONLY) (036 THRU 06C ACCESS FIELD CONTROL CONN IIII SUPPLY PANEL 7f8" (22 22) DIA HOLE " .I __ 10 V2" (2667) _-_j 4 3116" (106 3")_ LINE CONNECTION t 144-6) NOTES: 1 ALLOW 30" (762) CLEARANCE TO sEevIcE END OF 3 4 5 UNIT 48" (1219) ABOVE UNIT, 6" (152) ON ONE SIDE, 12" (306) ON REMAINING SIDE, AND 24" (610) BE nNEEN UNITS FOR PROPER AIRFLOW 2 MINIMUM 55F OUTDOOR OPERATING (12 8_C), (UNLESS AMBIENT LOW AMBIENT IN COOLING CONTROL MODE IS USED) MAX MAXIMUM OUTDOOR OPERATING AMBIENT IN HEATING MODE DIMENSIONS IN PARENTHESIS ARE IN MILLIMETERS SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT MODEL NUMBER IS 66 F {16.9o0) IS 125"F (51 7°C) A91055 MODEL 38TKB A B C D In In. In. In. 013, 024, 030, 036 22-1/2 27-1/2 2-13/16 6-15/16 042, 048, 060 30 34-15/16 4 9-3/4 Fig. 2--Unit Reference Drawing 2 NOTE: Avoid contact OUTDOOR between tubing and structure WALl: INDOOR WALL .___) CAULK_IQUID _L.__INSULATION TUBE _7'_y _'_ F,,_[,{_T_[,]: To prevent L.-- VAPOR TUBE h) urm or damage I service valves the observe 1hi)owing: THROUGH THE WALL • Use a brazing shield. • Wrap service ma_eriah Outdoor INSULATION package capacity TUBE_I i, VAPORTUBE moisture Allow space 30 in. clearance unit. For proper airflow, Refer to service INDOOR end of a 6 in. clearance UNIT ant on UNIT-- charge Outdoor for operation fall directly REFRIGERANT TUBING- door vapor and grade tubing. unit at feast The minimum outdoor and the maximum 125°F. Check on unit. 6 in. above roof refrigerant unit Ambients SWEAT operating tory and ready outdoor ambient operating in ¢ooling ambient mode is 55°F. in cooling mode Indoor Check indoor coil shown on unit rating piston with piston piston AccuRater_ Piston, to see if it matches plate. If it does not match, shipped unit is correct with this unit. The for any approved indoor replace -- for brazing. bearing now ready piston factory unit require- your local they and tubing valves. Service valves when tubing. set can be brazed to fittings (See to the service Refrigerant brazing tubing This check should 1.) Use from the service bearing on out- Table are closed wrapping or non-silver for leak testing. refriger- size efficiency. service After system of same or factory-accessory Connect liquid CONNECTION silver correct indoor for maximum sult local code requirements. if Required the required charge a wet cloth, the robing is either Step 5--Replace I for field tubing TO FACTORY-APPROVED by 15 fi of field-supplied refrigerant Step 4--Operating outdoor locate the recomApplication 2 for accessory unit contains with snow, appfications, Following Long-Line than 36 in.. consult CONNECTED connected On rooftop surface. size in the system, sides must be main_aineO. units. Position so water. cannot of correct 50 It. substantial Refer to Table to Table greater 1 side of anit and 12 in. on all remaining Maintain a distance of 24 m. between roof or eaves beyond Split System these losses. length. using accessory tubing losses can occur. applications OUTDOOR wiring, ret_ig- for airflow, section If refrigerant tubes or indoor coil are exposed to atmosphere, must be evacuated to 500 microns to eliminate contamination Installation Requirements allow sufficient line ---). For buried-line distributor. A94028 Fig. 3--Piping or ice from sink morns. LIQUID TUBE and service, will reduce equivalent SUSPENSION unit and 48 in. abouve or use a heat refrigerant requiremcnts in the Residential Guideline 1" MIN _ For tubing and performance mendations h erant piping, cloth to indoor or field-supplied and condition. installing, wet units may be connected tubing When with .,_r/'-JOIST HANGER STRAP (AROUNDVAPOR--_-- Step 3--Clearance valves fac- valve with valve using material. Con- and indoor coil are include all field and joints. indoor coil piston shipped g_] ['_-t iJ[']21 with coil cmnbination. To avoid valve damage while brazing, service valves must be wrapped in a heat-sinking material such as a wet cloth. Step Step 6--Make Tubing Connections Vt_lLrJ/'-._:UI17 [_] 7--Make pressure and recover all refrigerant before syslem wiring complies and electrical codes, and voltage including solenoid is within fire. safety. limits company improper rating lbr recommended voltage. See unit plate shown for correction of circuit device Operation of and could aft_ct install 3 to system local power abuse valves. with local and national on unit rating plate. Contact NOTE: repair or final unit disposal to avoid per_onal mjut 3' or dcznb. Use all ,service pots and open all flow-control devices. Connections Be sure field protection Relieve Electrical unit unil in system fluctuate above NOTE=: unit. Use where or below copper on bnproper unit reliability. wire voltage permissible only line voltage constitutes See unit rating plate. Do not or phase imbalance may limits, between disconnect switch and -..) Table 2--Accessory ACCESSORY Crankcase Heater Usage REQUIRED FOR LOW-AMBIENT APPLICATIONS (BELOW 55°F) Yes REQUIRED FOR LONG-LINE APPLICATIONS* (OVER 50 FT) Yes REQUIRED FOR SEA COAST APPLICATIONS (WITHIN 2 MILES) No Evaporator Freeze Thermostat Winter Start Control Yes No No Yes1" No No Accumulator NO No NO Compressor Start Assist Capacitor and Relay Yes Yes No Low-Ambient Controller, MotorMaster_ Control, or Low-Ambient Pressure Switch Yes No No Wind Baffle See Low-Ambient Coastal Filter Instructions No Recommended Support Feet Solenoid Valve or Hard Shutoff TXV No No Yes No Liquid-Line Recommended See Long-Line Application Guideline No Yes:[: Ball Bearing Fan Motor No NO No No • For tubing line sets between .50 and 175 ft, refer to Residential Split System Long-Line Application Guideline. t Only when low-pressure switch is used :_ Required for Low-Ambient Controller (full modulation feaature) and MotorMaster Control only CONNECT GROUND AND POWER WIRES -- Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 4. CONNECT NOTE: Install branch circuit of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit per Section 440-14 of NEC. r,.] w._,d The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when inslalJed in accordance with existing electrical codes. Failure to follow this warning can result in an electrical shock, fire, or death. ROUTE GROUND AND POWER WIRES--Remove access panel and control box cover to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box, DISCONNECT PER N. E. C. AND/OR LOCAL CODES CQNTACTOR I I I FIELDPQWER ] C>°C} WIRING ©oC> FIELD GROUND WIRING GROUND LUG A91056 Fig. 4--Line Power Connections WIRING--Route 24-v control wires and connect leads to control Use No, 18 AWG color-coded, insulated (35 ° C minimum) wire. If thermostat is located more than 100 ft from unit as measured along the control voltage wires, use No. 16 AWG color-coded wires to avoid excessive voltage drop. All wiring must be NEC Class I and must be separated from incoming power leads. Use furnace transformer, fan-coil transformer, or accessory Iransformer for control power. 24-v/40va minimum. NOTE: Use of available 24-v accessories may exceed the minimum 40-va power requirement. Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required. Step 8_Compressor Crankcase Heater When equipped with a crankcase heater, furnish power to heater a minimum of 24 hrs before starting unit. To furnish pewer to heater only, set dlcrmostat to OFF position and close eleclrical disconnect to outdoor unit. A crankcase heater is required if the refrigerant tubing is longer Ihan 50 ft Rel_r to Residential Split System Long-Line Application Guideline. Step 9--Install Electrical Accessories, Refer to the individual instructions accessory when insla]ling. Q j CONTROL through control wiring grommet wiring. (See Fig. 5.) If Any packaged with the kit or CARRIER NON-PROGRAMMABLE THERMOSTAT MODEL AC 24 VAC HOT _.-, 24 VAC COM _-" SINGLE-STAGE FURNACE CARRIER NON-PROGRAMMABLE THERMOSTAT MODEL AC AIR CONDITIONER 24 VAC HOT FA. FS, FC, FD, FF FAN COIL AIR CONDITIONER _-r_q HEAT STAGE 1 COOL STAGE 1 INDOOR ...... J _ SEE NOTE2 HEATSTAGE1 COOLSTAGE1 .... L_ I FAN CL_--- SEE NOTE2 .... _- 24 VAC COM INDOOR _ FAN _--° A9468 A97467 CARRIER PROGRAMMABLE THERMOSTAT MODELAC SINGLE-STAGE FURNACE CARRIER PROGRAMMABLE THERMOSTAT MODEL AC AIR CONDITIONER FA, FB, FC, FD, FF, FX FAN COIL AIR CONDITIONER I -24 VAC HOT INDOOR 24 VAC HOT [_ --[_ INDOOR [_ --[w] HEAT STAGE 1 [_ FAN HEAT STAGE 1 COOL STAGE 1 FAN COOL STAGE 1 NOT USED _'_ NOT USED SEE NOTE2 NOT USED SEE NOTE2 NOT USED -El- 24 VAC COM NOT USED [_]1 NOT USED r_J I 24 VAC COM E_ NOT USED {_11 NOT USED J'_'_J 1 A97469 OPTIONAL OUTDOOR -- SENSOR CONNECTION S'_7 OTHER NON-PROGRAMMABLE AC THERMOSTAT 24 VAC A97595 31 OUTDOOR SENSOR CONNECTIO OPT,ONAL _E_I I SINGLE-STAGE FURNACE COOL INDOOR I_-I OTHER NON-PROGRAMMABLE AC THERMOSTAT AIR CONDITIONER I FA, FB, FC, FO, FF, FX FAN COIL AIR CONDITIONER I HOT 24VACHOT HEAT ' STAGE STAGE PAN 1 Y_ _'_ n. SEE NOTE2 1 _- HEATSTAGE' D _- E}-. -_1 -J C / SEE NOTE2 OOOLSTAGE, [B--R ..... 'NDOORFAN D a--@ A97367 Fig. 5---24-v Control Circuit Connections A97593 CARRIER NON-PROGRAMMABLE THERMOSTAT MODEL AC FK4C. FV4A FAN COfL AIR CONDITIONER II¢/_J1JUMPER 24 MAC COM CARRIER PROGRAMMADLE THERMOSTAT MODEL AC _ __ HEAT STAGE 1 _ _]_ FAN AIR CONDITIONER SEE NOTE2 COOL STAGE 1 INDOOR FK4C, FV4A AN COIL L 24 VAC HOT [_ INDOOR [_ FAN -IN"J_.___,_UMP_ -IN HEAT STAGE 1 [] [] A97596 r-_ _'_JUMPER COOL STAGE 1 NOT USED OTHER NON-PROGRAMMABLE AC THERMOSTAT NOT USED FK4C, FV4A FAN COIL AIR CONDITIONER I SEE NOTE 2 4V OO 4g]- J1 JUMPER [] [] NOT USED NOT USED HEAT STAGE 1 2,VAC.OT COOL STAGE INDOOR 1 SEE NOTE2 i A97597 OUTDOOR SSNSOR OPTIONAL CONNECTIO FAN N_ I -_GI I _ I011 f IYll I A97592 NOTES: 1. CARRIER 2. WIRING 3. SOME CYCLE 4, THERMOSTAT MUST UNITS A LIQUID-LINE HOUR 6. TO CONFORM ARE LIMIT. STAGE ARE ELECTRIC DIAGRAMS NEC OR WITH CONNECT SOLENOID SEE TO EQUIPPED PROTECTION. 5. THERMOSTATS WIRING THERMOSTAT RESISTANCE LOCAL FIELD ACCURATE SWlTCH(ES), WIRING IS REQUIRED CONFIGURED ON WITH INSTALLATION HEAT. ONLY FOR MODEL NUMBERS BEGINNING WITH TSTAT CODES. PRESSURE 24-V VALVE FACTORY ARE TO TEMPERATURE SOME OR STRIPPED 5-M1NUTE COMPRESSOR LEADS, UNITS, 5-MINUTE INSTRUCTIONS CONSULT SWITCH, FACTORY-PROVIDED OUTDOOR COMPRESSOR FOR CYCLE PROTECTION AND 4 CYCLES PER DETAILS. THERMOSTAT INSTALLATION INSTRUCTIONS. LEGEND 24-V FACTORY WIRING 24-V FIELD WIRING © © FIELD SPLICE CONNECTION CONTACTOR A97368 Fig. 5---Typical 24-v Circuit Connections (Continued) Step 10--Start-Up and Check Charge NOTE: If superheat favorable, plate To prevent compressor damage or personal injury, + 0.6 system • Do not operate unit • Do not disable low-pressure In scroll compressor • Dome temperatures • In 3 phase observe with rcl?-igerant. in a vacumn ozJfl pressure. switch may he hot+ application, incorrect in elevated I. Operate phasing noise will cause levels, reverse equalized by reversing pres- unit 2. Measure power suction mistor valve. prevent personal injury and gloves wear safety when handling glasses, protective refiigemnt • Back sealing service valves are not equipped Fully back seat (counter gage clockwise) with Schrader valve stem before seating service or final these valves are equipped with Schrader to atmosphere. Recover during system seat (open) with installed. liquid and vapor valve Replace stem(s) tube service front seated stem caps after electrical is below disconnects thermostat indoor at desired ambient 5. Set room thermostat mode. as desired. refrigerant to energize R-Y energizes starting When circuit. the indoor Operate and blower unit CHARGE the thermostat at ON or AUTO Check motor relay on power makes contactor, starting suction pressure of I0 minutes before is checking suction by attaching an accurate gage In port. temperature type or electronic has a lower 10. If outdoor by attaching thermometer suction reclaim air charge Step 12--Final system IMPORTANT: an accurate ther- to suction line at service with thermometer. line refrigerant temperature until charted than charted temperature is temperature or to new suction pressure at suction line temperature valve indicated on Checks Before leaving job, be sure to do the following: 1. Securely fasten all panels and covers. circuits outdoor the indoor to indoor and R-Y and R-G. fan motor unit blower and 3. Leave User's Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual. 4. Fill out Dealer Installation file. its contacts Compressor with CARE AND MAINTENANCE open. and motors a time-delay relay de-energizing stop circuit, 90 sec_mds to increase the system For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment. Frequency Charge Factory Adjust charge by flfllowing located on unit. charge procedure is shown shown Checklist and place in customer relay. on high speed. will run an additional -- charge The fi)llowing procedure +_ 21% of its rated CFM. 2. Tighten service valve stem caps to 1/12-turn past finger tight. is equipped Step 11'--Check a minimum valve service temperature, reached. changes, chart. Be sure set point unit for 15 minutes. is satisfied, If indoor = 6 oz of additional to with system. and fan control R-G energizes contactor UNIT is opened and tighten temperature. at COOL blower the thermostat indoor blower efficiency and charge. On a call for cooling, compressor 15 ft temperature. SEQUENCE OF OPERATION -- Turn outdoor units. Transformer is energized. Circuit 9. If unit valves. (closed) system refrigerant flow. Replace caps finger-tight wrench an additional 1/12 turn. 4. Set room below 8. If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached. to start up the system: 2. Unit is shipped 3. Close or 7. Refer to Table 4. Find superheat temperature located in item 6 and suction pressure. At this intersection, note suction line temperature. unit disposal. steps I. Fully back caps above not rating 6. Refer to Table 3. Find outdoor temperature and evaporator entering air wet-bulb temperature. At this intersection, note superheat. port cap Do not vent refrigerant Fofiow line are with unit 5. Measure indoor air (entering indoor coil) wet-bulb temperalure with a sling psychrometer. ¥.'_[@211ii['/21 repair liquid 4. Measure outdoor air dry-bulb temperature and observe the following: • Front valves. conditions charge, 3. Measure removing 3/g-in. COOLING ONLY PROCEDURE-valid when indoor airflow is within applications: resulting valves. of 25 t_ - 15 ft = I0 fl X 0.6 o_ft or at negative sures and reduced current draw. Correct connection LI and L2 on contactor. clothing, charging in accordance EXAMPLE: • Do not overcharge To or subcooling must be weighed respectively. the following: rotation, charge on uniI raling plale. on charging tables of maintenance areas, such as coastal frequent mainlenance. may vary applications, depending which may on geographic require more Table 3--Superheat EVAPORATOR Charging OUTDOOR TEMP (OF) 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14 17 20 23 26 29 32 35 37 40 42 45 (°FWB) 7 10 12 15 18 21 24 27 30 33 35 38 40 43 65 -- 6 10 13 16 19 21 24 27 30 33 36 38 41 70 -- -- 7 10 13 16 19 21 24 27 30 33 36 39 75 -- -- -- 6 9 12 15 18 21 24 28 31 34 37 80 .... 5 8 12 15 18 21 25 28 31 35 65 ...... 8 11 15 19 22 26 30 33 90 ...... 5 9 13 16 20 24 27 31 95 ....... 6 10 14 18 22 25 29 100 ........ 8 12 15 20 23 27 105 ........ 5 9 13 17 22 26 110 .......... 6 11 15 20 25 115 .......... 8 14 18 23 60 --Where ENTERING AIR TEMPERATURE a dash appears, do not attempt to charge system under these conditions or refngerant slugging may occur Charge must be weighed in.NOTE: Superheat °F is at low-side service pod, Table 4---Required Suction-Line Temperature SUPERHEAT SUCTION PRESSURE AT SERVICE (°F) 61,5 64.2 67.1 70.0 73.0 0 35 37 39 41 2 37 39 41 43 4 39 41 43 6 41 43 8 43 10 PORT (PSIG) i E..ivl I- 76.0 79.2 82.4 85.7 43 45 47 49 51 45 47 49 51 53 45 47 49 61 53 55 45 47 49 51 53 55 57 45 47 49 51 53 55 57 59 45 47 49 51 53 55 57 59 61 12 47 49 51 53 85 57 59 61 63 14 49 51 55 57 59 61 63 65 16 51 53 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 2O 57 59 61 63 65 67 69 71 22 55 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 65 67 69 71 73 75 77 79 30 63 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 73 75 77 79 81 83 85 87 38 73 75 77 79 81 83 85 87 89 4O 75 77 79 81 83 85 87 89 91 Copyright 1999CARRIER Coq3.• 7310 W. Morris St. • Indianapolis, IN 46231 38tkb5si PC 101 Catalog No. 563-754 Printed in U.S.A. Form 38TKB-5SI Pg 8 11 m98 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces: 38TKB-3SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 8 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 12:51:05 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools