Carrier 48GS018040300 User Manual CENTRAL PACKAGE Manuals And Guides L0410010
CARRIER Package Units(both units combined) Manual L0410010 CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
User Manual: Carrier 48GS018040300 48GS018040300 CARRIER CENTRAL PACKAGE - Manuals and Guides View the owners manual for your CARRIER CENTRAL PACKAGE #48GS018040300. Home:Heating & Cooling Parts:Carrier Parts:Carrier CENTRAL PACKAGE Manual
Open the PDF directly: View PDF .
Page Count: 36
HFATUNG & COOLING
48GS, 48GX
Single Packaged Gas Heating/
Electric Cooling Units
%isdt_ v_v_carrier.corn
Installation, Start-Up, and Operating
48GS Sizes 018-060, 48GX Sizes 024-060
NOTE: Read the entire instruction manual before starting the
installation
TABLE OF CONTENTS
SAFETY C ONSIDERATI(INS 1
INTRODE CTION 2
RECEIVING AND INSTALLATION .......................................... 2
CHECK EQUIPMENT ............................................................. 2
IDENTIFY EJNIT ................................................................ 2
INSPECT SHIPMENT ........................................................ 2
INSTALLATION ................................................................ 2
PROVIDE UNIT SUPPORT. ................................................... 2
ROOF (LRB ....................................................................... 2
SLAB MOUNT ................................................................... 2
GROL_D MOL_T ............................................................ 5
FIELD FABRICATE DUCTW()RK ........................................ 5
PROVIDE CLEARAN( ES ...................................................... 6
RIG AND PLA(E ENIT ......................................................... 7
CONNECT CONDENSATE DRAIN ...................................... 7
INSTALL FLUE HOOD .......................................................... 8
INSTALL GAS PIPING ........................................................... 8
INSTALL DUCT ( ONNE( TIONS ...................................... 10
(ONFIGURING UNITS FOR DO\}_TLOW (VERTI-
CAL) DISCHARGE .......................................................... 10
INSTALL ELECTRICAL ( ONNE(TIONS ......................... 12
HIGH-V()LTAGE CONNECTIONS ................................ 12
SPECIAL PROCEDURES FOR 208°V OPERATION ._ 13
CONTROL VOLTAGE CONNECTIONS ....................... 13
HEAT ANTICIPATOR SETTING ................................... 13
TRAN SFORMER PR()TECTION .................................... 13
PRE-START-E P .......................................................................... 15
START-UP ................................................................................... 15
(HECK FOR REFRIGERANT LEAKS ............................... 15
START°UP HEATING AND MAKE ADJUSTMENTS ...... 16
CHE(K HEATING CONTROL ....................................... 16
CHECK GAS INPUT ........................................................ !6
ADJUST GAS INPET ...................................................... 16
CHECK BURNER FLAME .............................................. 20
AIRFLOW AND TEMPERATURE RISE ....................... 20
HEATING SEQUEN(E OF OPERATION ..................... 20
LIMIT SWITCHES ........................................................... 20
AE XILIARY LIMIT SWITCH (ROLLOE T) .................. 21
START°E P COOLING AND MAKE ADJUSTMENTS ...... 21
CHECKING COOLING CONTROL OPERATION ....... 2!
< HE(KING AND ADJUSTING REFRIGERANT
CHARGE ........................................................................... 21
INDOOR AIRFLOW AND AIRFLOW ADJUST-
MENTS .............................................................................. 22
COOLING SEQE ENCE OF OPERATION ..................... 22
MAINTENANCE ......................................................................... 22
AIR FILTER ...................................................................... 25
EVAPORATOR BLOWER AND MOT()R ..................... 25
FLEE GAS PASSAGEWAYS ......................................... 27
COMBUSTION-AIR BLOWER ....................................... 27
LIMIT SWIT(H ................................................................ 28
BURNER IGNITION ........................................................ 28
MAIN BE RNERS ............................................................. 28
CONDENSER COIL, EVAPORATOR (OIL, AND
CONDENSATE DRAIN PAN .......................................... 29
CONDENSER FAN .......................................................... 29
ELECTRICAL CONTROLS AND WIRING .................. 30
REFRIGERANT CIRCUIT ............................................... 30
GAS INPUT ...................................................................... 30
EVAPORATOR AIRFLOW ............................................. 30
METERING DEVICE A(UTROL DEVICE ............. 30
LIQUID LINE STRAINER .............................................. 30
TROE BLESHOOTING ............................................................... 30
START-UP CHEf KLIST ............................................................ 30
NOTE TO INSTALLER Before the installatiom READ THESE
INSTRU(TIONS CAREFELLY AND (OMPLETELY. Also,
make sure the User's Manual and Replacement Guide are left with
the unit after installation. The furnace is NOT to be used for
temporary heating of buildings or structures under construction.
A99338
Fig. 1--Unit 48GS and 48GX
(Low NO× Model Available)
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and ebctrical components Only
trained and qualified personnel should install, repair, or service
air-conditioning equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring oNigations.
PC 101 Catalog No 534-80128 Printed in U.S.A Form 48GS.GX-6SI Pg 1 11-02 Replaces: 48GS.GX-5SI
Untrained personnel can perfbrm basic maintenance functions of
cleaning coils and filters. All other operations should be perfbrmed
by tlained service personnel When working on air-conditioning
equipmenL observe precautions in the literature, tags, and labels
attached to the unit, and other safety precautions that may apply.
Follow all safe V codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available ibr all brazing operations.
Improper installation, adjustment, aheration, service, mainte-
nancQ or use can cause carbon monoxide poisoning, fire, or
an explosion which can result in personal injury or unit
damage. Consuh a qualified installer, service agency, or gas
supplier for information or assistance. The qualified installer
or agency must use only factory-authorized kits or accessories
when modifying this product
Beibre peribrming service or maintenance operations on mail
mrn off gas supply to unit. Then mrn off unit main power
switch and install lockout tag. Elecn'ical shock or explosion
could cause serious inju_ or death.
Recognize safety infbrmation This is the safety-alert symbolz_
When you see this symbol in instructions or manuals, be alert to
the potential _br personal injory.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safcV-alert symboh
DANGER identifies the most serious hazards which will result in
serious injury or death. WARNING signifies a hazard which could
result in serious inju V or death. CAUTION is used to identii_,
unsafe practices which would result in minor personal injury or
product and property damage. NOTE is used to highlight sugges-
tions which will result in enhanced installation, reliability, or
operation.
These instructions cover minimuna requirements and confbrm to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen-
tial construction practices. We require these instructions as a
minimum ibr a saf_ installation.
INTRODUCTION
The 48GS and 48GX units (See Fig. 1) are fu!ly self_containe&
combination Category- I gas heating/electric cooling units designed
ibr outdoor installation (See Fig. 2and 3 for unit dimensions). All
unit sizes have return and discharge openings ibr both horizontal
and downflow configurations, and are ii_ctory shipped with all
downflow duct openings covered. Units may be installed either on
a rooftop, a cement slab, or directly on the ground if local codes
permit (See Fig. 4 for roof curb dimensions).
Models with an N in the fifth position of the model nmnber are
dedicated Low NOxunits designed fbr California installations.
These models meet the California maximum oxides of nitrogen
(NOx) emissions requirements of 40 nanograms joule or less as
shipped from the factory and must be installed in California Air
Quality Management Districts where a Low NO× rule exists.
RECEBVING AND INSTALLATION
Step 1--CHECK EQUIPMENT
IDENTIFY UNIT
The unit model number and serial nunfber are stamped on unit
identification plate. Check this information against shipping papers
and job data. Verit}' unit voltage and amperage requirements listed
on unit rating plate agree with power supply provided to unit
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet.
If unit appears to be damaged or is torn loose t'rom its anchorage,
have it examined by transportation inspectors before removal
Forward claim papers directly to transportation company Manu-
facturer is not responsible for any damage incurred in transit
Check all items against shipping list Immediately notify the
nearest distributor if any item is missing.
To prevent loss or damage, leave all parts in original packages
until installation.
INSTALLATION
1. Remove unit from shipping carton Leave top shipping skid on
the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a
spreader bar of sufficient length to protect unit t_-om damage.
2. Position the tiffing bracket assembly around the base of the
unit. Be sure the strap does not twist
3. Place each of the 4 metal lifting brackets into the rigging holds
in the composite pan.
4. Thread liking bracket strapping around bottom perimeter of
unit as follows:
a Open lever of tension buckle (ratchet type)
b. Feed strapping throngh tension buckle as shown in Fig 7A.
c Pull strapping through tension buckle unit taut.
d. Snap lever down to lock strap in tension buckle To release
strapping, squeeze safkty latch, Ilk lever, and pull webbing
outward
5. Tighten the tension buckle until it is taut Lifting brackets
must be secure in the rigging holds
6. Attach field=supplied clevis or hook of sufficient strength to
hole in the liking bracket (See Fig. 7B).
7. Attach the 2safkty straps directly to the clevis or hook at the
4 rigging brackets. DO NOT attach the safkty straps to the
lifting brackets (See Fig. 7B).
8. Position liking point directly over the unit's center of gravity.
9. Lift unit. When unit is directly over the roof curb, remove the
2safety straps. Lower the equipment onto the roof curb.
Step 2--PROVIDE UNiT SUPPORT
ROOF CLRB
Install accessory roof curb in accordance with instructions shipped
with curb (See Fig. 4 for roof curb dimensions). Install insulation,
cant strips, roofing, and flashing Ductwork must be attached to
curb
IMPORTANT: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing can also result in air leaks
and poor unit perfbrmance.
Cm:b should be level to within 1/4 in. This is necessa_' for unit
drain to Nnction properly. Refkr to accessory roof curb installation
instructions for additional information as required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of
4 in. thick with 2in. above grade. The slab should be flush on the
compressor end of the unit (to allow condensate &ain installation)
and should extend 2in. on the three remaining sides of the unit
(See Fig. 6). Do not secure the unit to the slab e:vcept when
required by local codes.
(t CD,[ [_H [ GJ I _1,
ZS4 "" 5q } _ 5 :
[_9 K,] [ [2, _o] _ [o oo] i
i
86 I _ _ j
, : _C,_494_ 0_i t:¸
OPU 6
t '
i N
249 ;
i,, s1 550 5 ?49 6
IN _;i }9 8_]
REAR ViEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATL INCHES [mm]
TOP OF UNIT ................................................................................... 14.00 [355 6]
DUCT SIDE OF UNIT ......................................................................... 200 [508]
SIDE OPPOSITE DUCTS ................................................................ 14.00 [355 8]
BOTTOM OF UNIT ............................................................................. 050 [127]
ELECTRIC HEAT PANEL ................................................................. 3600 [914 4]
NEC. REQUIRED CLEARANCES,
INCHES [mm]
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 [1086 8]
UNIT AND UNGROUNDED SURFACES. POWER ENTRY SIDE 3800 [914 0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES POWER ENTRY SIDE ......................... 4200 [1066 8]
LEGEND
CO Center of OravRy
COND Condensor
EVAP Evap@ator
NEC National E[ectnca[Code
REQ'D Reqused
NOTE:Dimensionsare in in [mm]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING INCHES [mm]
EVAR COIL ACCESS SIDE ............................................................ 36.00 [914 0]
POWER ENTRY SIDE .................................................................... 3600 [914 0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ....................................................................................... 48.00 [1219 2]
SIDE OPPOSITE DUCTS .............................................................. 36.00 [914 0]
DUCT PANEL ................................................................................. 1200 [304 8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 1200 [304 8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE
UNIT
48GS018040
48GS024040/080
48GS030040/080
48GS038060/090
48GS042060/090
48GX624040/060
48GX036040/060
48GX036066/090
ELECTRICAL CHARACTERISTICS
208/230-1-60
208/230-1-60
208/230-1-60, 208/230-3-60
208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60
208/230-1-60, 208/230-3-60
208/230-1-60, 208/230-3-60,460-3-60
UNIT WEIGHT
Ib Tkg
249.0 113.2
280.0 127.3
280.0 127.3
320.0 145.1
355.0 161.4
290.0 131.5
313.0 142.0
321.0 145.6
UNIT HEIGHT IN. ([VIM)
,,A,_
35.02 (889.5)
35.02 (889.5)
35.02 (889.5)
37.02 (940.3)
35.02 (889.5)
37.02 (940.3)
39.02 (991.1)
35.02 (889.5)
X
20.0 (508.0)
22.5 (571.5)
21.5 (546.1)
22.5 (571.5)
21.5 (546.1)
22.0 (558.8)
22.0 (558.8)
22.0 (558.8)
Fig. 2--48GS018-042 and 48GX024-036 Unit Dimensions
CENTER OF GRAVITY
IN.(MM)
Y
140 (3556)
130 (3302)
1375 (349.3)
140 (355.6)
135 (342.9)
145 (3683)
153 (3874)
153 (387.4)
COOO55
Z
15.0(3810)
15.0(3810)
150 (3810)
130 (3302)
130 (3302)
16.0 (4064)
176 (4470)
165 (4191)
[33£1
70 4
[2 77] i
402 o
[15 83]
[1177
{a 631
i
88 3
[3 46] [13831 [13 62] [13831
REAR VIEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATE
INCHES [mini
TOP OF UNIT ................................................................................... 14,00 [355 6]
DUCT SIDE OF UNIT ......................................................................... 2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................ 14,00 [355 6]
BOTTOM OF UNIT ............................................................................. 0.50 [12.7]
FLUE PANEL .................................................................................... 36,00 [914 4]
NEC. REQUIRED CLEARANCES,
INCHES [mm]
BETWEEN UNITS, POWER ENTRY SIDE .................................... 4200 [1066.6]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE 3600 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 4200 [1066 8]
[16 O!]
i E_AP COIL
k_- 10906
[42 943
L._ It231
[44 22]
LEFT SIDEVIEW
UNiT
48G8048090/115/130
48GS0600901115/130
48GX042060/090
48GX048090/115/190
48GX060090f115/130
3558
{1411] _3427 _ 3558
[!3 49] [14 Oi]
SUPPLY
4066
[1601]
TOP VIEW
C01L
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
INCHES [mm]
EVAR COIL ACCESS SIDE ............................................................ 3600 [914 0]
POWER ENTRY SIDE .................................................................... 3600 [914 0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ....................................................................................... 4800 [1219.2]
SIDE OPPOSITE DUCTS .............................................................. 3600 [914 0]
DUCT PANEL ................................................................................. 1200 [304 8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 1200 [304 8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
LEGEND
CG - Center of Gravity
COND - Condensor
EVAP- Evaporator
NEC - National Electrical Code
REQ'D - Required
1939 _'< _ !15 4 NOTE:Dimensionsare in in, [ram]
47 OO] [4 54]
....... ,,OO/ i? L[4iR) " i...........
"....................... 12 i [O 881 OlA I@lE ' ..............
CONTROLEN/RY
[.8 1 VIiA_
i \ o
[ 68] MPRESSOR,BLOtlER 6AS S{CTION FLUE FLOOD fY _4] 7[O 50] N P T
329 O & Et CTR CAt £;¢[SS PANEl 528 GAS ENTRY 5 O
FRONTVIEW RIGHTSIDEVIEW 000056
ELECTRICAL CHARACTERISTICS
208-230/1/60, 208/230-3-60, 460-%60
208/230-1-60, 208/230-%60, 460-3%0
208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-%60, 460-3-60
208/230-1-60, 208/230-%60, 460-3-60
UNIT WEIGNT
Ib kg
415 1886
450 2045
382 1733
421 1910
468 2123
UNIT HEIGHT IN. (MM)
"A"
38.98 (990.2)
38.98 (990.2)
38.98 (990.2)
38.98 (990.2)
42.98 (1091.1)
X
22 (5585)
22 (5585)
23.0 (584.2)
21.5 (546.1)
23.5 (596.9)
Fig. 3--48G8048-060 and 48GX042-060 Unit Dimensions
CENTER OF GRAVITY
IN.(MM}
Y Z
16 (406.4) 17 (432 0)
16 (406.4) 17 (4320)
163 (412.8) 166 (4216)
166 (422.1) 180 (4572)
163 (412.8) 176 (4470)
RoofCurb for Small Cabinet
Note A: When uNt mounting screw is used,
retah3er bracket must also be used.
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
-->
R/A
\\
-'-_- Gasket around_
duct
S/A
/\
\
Long
SL pport
Suppolt
insulated
deck pan Gasket around
outer edge \ \,
iBXC}
C00076
UNiT S_ZE
48GS018o042 48GX024-036
48GS048o060 48GX042-060
NOTES:
1. Roof curb must be set up for unit beh_ginstalled
ODS CATALOG NUMBER
CPRFCURB006A00
CPRFCURB007A00
CPRFCURB008A00
CPRFCURB009A00
A
IN. {NM)
8 (203)
14 (356)
8 (203)
14 (356)
B
IN.(MM)
11(279)
11(279)
16 3/16 (411)
16 3/16 (411)
C
RN.(MM)
161/2 (419)
161/2 (419)
17 3/8 (441)
17 3/8 (441)
D
IN. (t_M)
2G3/4 (730)
28-3/4 (730)
40-1/4 (1022)
40-1/4 (1022)
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed
6. Attach ductwork to curb (flanges of duct rest on curb)
7. InsuIated panels: 1-in. thick fiberglass 1 Ib density.
8. Dimensions are in inches
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well This bracket must also be used when required by code for hurricane or
seismic conditions. This bracket is available through Micrometl.
Fig. 4--Roof Curb Dimensions
GROL ND MOL_T
The unit may be installed either on a slab or placed directly on the
ground if local codes permit. Place the unit on level ground
prepared with gravel _br condensate discharge.
Step 3--FIELD FABRICATI= DUCTWORK
Secure all ducts to roof curb and building strecture on vertical
discharge uriits Do t_nt connect duct_oHc to z_nit. For horizontal
applications, unit is provided with flanges on d_e horizontal
openings Installation of flexible duct connector is recommended
to prevent tlansmission of vibration and/or noise to stl_acture. All
ductwork should be secured to the flanges. Insulate and weather°
proof all external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
Y
4 x 3
C00070
48GS
CORNER # 018 024 030 036 042 048 060 024
1 47.3 53.2 53.2 59.7 675 789 85.5 55.1
2 44.8 50.4 50.4 56.5 639 747 81.0 52.2
3 77.2 86.8 86.8 97.3 1101 128.7 1395 89.9
4 79.7 89.6 89.6 106.5 1136 132.8 1440 92.8
TOTAL WEIGHT 249 280 280 320 355 415 450 290
48G×
030 036 042 048 060
595 61.0 72.6 800 88.9
563 57.8 68.8 758 84.2
970 99.5 1184 130.5 145.1
1002 102.7 1222 134.7 149.8
313 321 382 421 468
Fig. 8--48GS and 48GX Unit Corner We{ghts
2 F_
(50.8mn
EVAR COND.
COIL COIL
Fig. 6--Slab Mounting Details
C99014
HANDHOLD
/
J
Fig. 7A--Threading BoR for RiggBng
C99067
If a plemma return is used o,1 a vertical unit, the return should be
ducted through the roof'deck to comply with applicable i_re codex
A n_inimum clearance is not required around ductwork_ Cabinet
return=air static shall not exceed -25 in. wg.
PLAOE
BASEPAN SLOT (BELOW RIGGtNG HOLDS}
BEFORE RIGGING
SRZE
0t8
024
030
036
042
048
050
024
030
036
042
048
050
DIJCTS
SEAL STRIP MI _ST BE _N
PLACE BEFORE PLACING
_JN_T ON RO©F CURB
C99015
MAX,MUM WE,GNT [ A [ B
tb kg in. mm in. mm
271
302
302
342
377
437
472
312
335
343
404
443
490
UNIT 48G8
123.2 20.0 508.0 14.0 355.6
137.3 22.5 571.5 13.0 330.2
137.8 21.5 546.1 13.75 349.3
155.1 22.5 571.5 14.0 355.6
171.4 21.5 546.1 13.5 342.9
198.6 22.0 558.5 17.0 432.0
214.5 22.0 558.5 17.0 432.0
UNIT 48GX
142 22.0 558.5 14.50 368.3
152 22.0 558.5 15.30 388.6
156 22.0 558.5 15.30 388.6
183 23.0 584.2 16.3 414.0
201 21.5 546.1 16.3 414.0
222 23.5 596.9 16.3 414.3
Fig. 7B--Suggested Rigging
Step 4--PROVIDE CLEARANCES
The required minimum operating and service clearances are shm_n
in Fig 2 and 3 Adequate combustion, ventilation and condmlser
air must be provided in accordance with section 53, Air fbr
Table 1--Physical Data--UnR 48GS
UNIT SBZE 48GS
NOMINAL CAPACBTY (ton)
OPERATING WEIGHT (_b.)
COMPRESSORS
Quantity
REFRmGERANT (R-22)
Quantity (_b.)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER CORL
Rows...Finslin.
Face Area (sq ft)
CONDENSER FAN
NominN Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COBL
Rows...Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nomina_ Airflow (Cfm)
Size ({n.)
Notor BP (Rpm}
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drilt Size)
Propane Gas
RETURN-ABR FILTERS (in.)?
Throwaway
* Based on altitude of 0 to 2000 ft
018040 024040
1½ 2
249 280
024060
2
280
030040
2½
280
038080
3
320
042060
3½
355
042090
3½
355
.034 I .034 .034 .032 .034 .034
1 17 [ 1._17 1_17 1._17 1_.17 1._17
6 I n 9.1 9.1 10.9 9.1 9.1
2400
22
1/8 (825)
2000 1
1/8 (825) 1
030080 036060
2½ 3
280 320
Reciprocating
1
AcutroF M Device
.034 .032
1...17 1...17
9.1 10.9
2400 3000
22 22
1/8 (825) ¼ (1100)
2...15 3...15
3.1 3.1
1000 1200
10 x 10 11 x 10
lg (1075) 1/2 (I075)
2...38 2...38
2...46 2...46
20 X 20 20 X 24
3000
22
¼ (1100)
2400
22
1/8 (825)
3000
22
¼ (1100)
.O34
u
1...17
9.1
u
2400
22
1/8 (825)
u
2...15
3.1
u
8OO
10 x 10
1/4 (1075)
u
3000
22
¼(1100)
2...15 I 2...I5 2...15 3...15 4...15 4...15
" _ ' 3.1 3.1 3.1 3.1 3.1.J _ ,
600 I 800 1000 1200 1400 1400
10x10 I 10x10 10x10 11x10 11x10 11x10
1/4 (87511 1/4 (I075) 1/4 (1075) 1/2 (1075) 3/4 (1075) 3/4 (1075)
2...45 I 2...45 2...38 2...45 3...38 2...38 3...38
2...50 I 2...50 2...46 2...50 3...46 2...46 3...46
u
20x20 I 20x20 20X20 20x20 20X24 20x24 20x24
? Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
fi/minute for throwaway type or 450 if/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg
(ombustion and Ventilation, of the National Fuel Gas <ode ANSI
(American National Standards Institute) Z2231 or applicable
provisions of local building code In Canada, _bllow sections 7.2,
7.3, or 7.4 or CaniCGA. (Canadian Gas Association) B149
Installation Codes or applicable provisions of local building code.
Do not restrict condenser airflow. An air restriction at either
the outdoor-air inlet or the £m discharge can be detrimental to
compressor tiff.
The condenser £m pulls air through the condenser coil and
discharges it through the top cover Be sure that the fan discharge
does not recirculate to the condenser coil Do not locate the unit in
either a comer or under an overhead obstruction. The minin-mm
clearance under a pmlial overhang (such as a nomml house
overhang) is 48-im above the unit top. The nmximnm horizontal
extension of a partial overhang must not exceed 48-in_
Do not place the unit where water, ice, or snow flora an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting, tile, or other combustible materials. The unit nmy be
installed on wood flooring or on (;lass A, B, or ( roof covering
materials.
Step 5--RIG AND PLACE UNW
When installing the unit on a rooftop, be sure the roof will
support the additional _eight
Use spreader bars or crate top when rigging the uniL The units
must be rigged for lifting (See Fig 6). Refer to Table 1 and 2for
operating weight. L'xe e:v::'eme ca_ltio_v to prea,e_vt damage whe_
mu_ ing the _mit. Unit m_¢stremain in an upH@tpo,sition dHring a//
riggi<g a_d mo_,i_tg operaff(ms.The unit must be level within 14"
for proper condensate drainage; therefore, the ground°level pad or
accessory roof curb must be level before setting the unit in place.
When a field°fi_bricated support is used, be sure that the support is
level and properly supports the unit. Lifting point should be
directly over the center of gravity for the unit.
Step g--CONNECT CONDENSATE DRAIN
NOTE: When installing condensate &ain connection be sure to
comply with local codes and restrictions.
Models 48GS and 48GX dispose of condensate water through a
3/4 in. NPT fitting which exits through the compressor access
panel (See Fig. 2 and 3 for location).
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground-
level installations. Install a field°supplied condensate trap at end of
condensate connection to ensure proper drainage Make sure that
the outlet of the trap is at least 1 in. lower than the drain pan
condensate connection to prevent the pan fl'om overflowing (See
Fig 8) Prime the trap with water When using a gravel apron,
make sure it slopes away fl'om the unit
If the installation requires draining the condensate water away
from the unit, install a 2=ira trap at the condensate connection to
ensure proper &ainage (See Fig. 8). Make sure that the outlet of
the trap is at least 1 in. lower than the drainpan condensate
connection. This prevents the pan tiom overflowing.
Prime the trap with water. Connect a &ain tube using a mininmna
of 3/4-in. PVC or 3/4-in. copper pipe (all field=supplied) at the
outlet end of the 2=ira trap. Do not undersize the robe. Pitch the
Table 1--Physical Data--Unit 48GS (Continued)
UNiT SIZE 48GS
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSORS
Quantity
REFRIGERANT {R=22)
Quantity (lb.)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/im
Face Area {sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows...Finsiim
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Bp (Rpm)
FURNACE SECTION*
Burner Orifice No. {Qty...DrSI Size)
Natural Gas
Burner Orifice No. {Qty...DrSI Size)
Propane Gas
RETURN-AIR FILTERS {in.)?
Throwaway
* Based on altitude of 0 to 2000 ft
048090 048115 060 t 18 060130
4 4 5 5
415 415 450 450
Scroll Reciprocating
1 1
6.0 6.0 8.0 8.0
.032 .032 .030 .030
1._17 1._17 2._17 2._17
12.3 12.3 12.3 12.3
3600 3600 3600 3600
22 22 22 22
'/_ (1100) 1/_(1100) '/_ (1100) '/_ (1100)
3...15 3...15 4._15 4...15
4.7 4.7 4.7 4.7
1600 1600 2000 2000
11X10 11X 10 11X10 11X10
3/4 (1075) 3/4 (1075) 1.0 (1075) 1.0 (1075)
3._38 3...33 3_.33 3_.31
3...46 3...42 3...42 3...41
24 X 30 24 X 30 24 X 30 24 X 30
048130 0$0090
4 5
415 450
6.0 8.0
Acutrol Device
.032 .030
1...17 2...17
12.3 12.3
3600 3600
22 22
1/_(1100) '/_ (1100)
3...15 4._15
4.7 4.7
1600 2000
11 X 10 11 X 10
3/4 (1075) 1.0 (I075)
3...31 3...38
3...41 3...46
24 X 30 24 X 30
1 Reqaired filter sizes shown are based on the larger of the AR[ (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
ft/minate for throwaway type or 450 if/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in wg
drain robe downward at a slope of at least 1-in. %r every 10 ft of
horizontal run, Be sure to check the drain robe for leaks,
1" min.
TRAP
OUTLET
2" rain.
Fig. 8--Condensate Trap
C00009
Step 7--INSTALL FLUE HOOD
The flue hood assembly is shipped screwed to the coil panel in the
indoor blower compartment Remove the service access panel to
locate the assembly (See Fig. 3i).
NOTE: Dedicated low NO x models MUST be installed in Call=
fomia Air Quality Management Districts where a Low NO× rote
exists,
These models meet the California maximmn oxides of nitrogen
(NOx) emissions requirements of 40 nanogramsdoule or less as
shipped from the fhctory,
NOTE: Low NO x requirements apply only to natural gas instal-
lations,
1
The venting system is designed to ensure proper venting. The
flue hood assembly must be installed as indicated in this
section of the unit installation insm/ctions,
Install the flue hood as fbllows:
1, This installation must confot_n with local building codes and
with the National Fuel Gas (?ode (NFGC), ANSI Z223 1 (in
( anada., CANiCGA B 149,1, and B 149 2) or NFPA (National
Fire Protection Association) latest revision Refer to Provin=
cial and local plumbing or wastewater codes and other
applicable local codes,
2, Remove flue hood from shipping location (inside the blower
compartment) Place vent cap assembly over flue panel, Orient
screw holes in vent cap with holes in the flue panel
3, Secure flue hood to flue panel by inserting a single screw on
the right side and the tet_ side of the hood.
Step 8--INSTALL GAS PIPING
)"he gas supply pipe enters the unit through the access hole
provided, The gas connection to the unit is made to the 1/2=in, FPT
gas inlet on the manual shutoff or gas valve.
Install a gas supply line that runs to the heating section. Refer to
Table 3 and the NFGC for gas pipe sizing. Do _ot zlse cast-iros_
pipe. It is recommended that a black iron pipe is used. Check the
local utility for recommendations concerning existing lines. Size
gas supply piping for 0,5 in, wg maximum pressure drop, _\2_*er
_¢se pipe smaHe/' than the ].lL_:in+ FflY gax m/et up tile zmit ,?aX
ICt]1'C.
For natural gas applications, the gas pressure at unit gas connection
must not be less than 4.0 in. wg or greater than 13 in. wg while the
TaNe 2--Physicam Data--Unit 48GX
UNiT BBZE 48GX 024040 024000 030040 030000 030060 036090 042060 042090
NOMINAL CAPACITY (ton) 2 2 2"½ 2_½ 3 3 3½ 3½
OPERATING WEIGHT (lb.) 290 290 313 313 321 321 382 382
COMPRESSORS Scroll
Quantity 1
REFRmGERANT (R-22) 3.7 3.7 4.4 4.4 5.2 5.2 6.4 6.4
Quantity (_b.)
RBFRBGERANT METERBNG DEVICE .034 .034 .030 .030 .032 .032 .034 .034
Orifice ID (in.}
CONDENSER COBL 1._17 1._17 1_.17 1...17 2...I7 2...17 2...17 2._17
Rows...Fins/in. 10.8 10.8 12.7 12.7 9.1 9.1 12.3 12.3
Face Area (sq ft}
CONDENSER FAN 2350 2350 2350 2350 2350 2350 3300 3300
Nominal Cfm 22 22 22 22 22 22 22 22
Diameter (in.)
Motor Bp (Rpm) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825)
EVAPORATOR COIL 3...15 3_.15 3._15 3._15 3._15 3...15 3_.15 3_.15
Rows...Fins/in. 3.1 3.1 3.1 3.1 3.7 3.7 4.7 4.7
Face Area (sq ft}
EVAPORATOR BLOWER 800 800 1000 1000 1200 1200 1400 1400
Nominal Airflow (Cfm) 10X10 10X10 10X10 10X10 11X10 11X10 11X10 11X10
Size (in.)
Motor Hp {Rpm) 1/4 (1075) 1/4 (1075) 1/4 (1075) 1/4 (1075) 1/2 (1075) 1/2 (1075) 3/4 (1075) 3/4 (1075)
FURNACE SECTION*
Burner Orifice No. (Qty...DriH Size) 2...44 2_.38 2_.44 2...38 2...38 3...38 2...38 3_.38
NaturN Gas 2...50 2...46 2...50 2...46 2...46 3...46 2...46 3...46
Burner Orifice No. (Qty...DriH Size)
Propane Gas
R_:TURN-ABR FBLTERS (Jn.)t 20 X 20 20 X 20 20 X 20 20 X 20 20 X 24 20 X 24 24 X 30 24 X 30
Throwaway
* Based on altitude of Oto 2000 ft
? Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
if/minute for high-capacity type Air filter pressure drop for non-standard fitters must not exceed 008 in wg.
unit is operating. For propane applications, the gas pressure must
not be less than 7.0 in wg oi" greater than 13 in wg at the unit
connection
An 1/8-in. NPT plugged tapping, accessible fbr test gage conneco
tiom must be installed immediately upstream of the gas supply
connection to the gas valve.
When installing the gas supply line, obsel_'e local codes pertaining
to gas pipe installations. Ref)r to the NFGC ANSI Z223J-1988
NFPA latest edition (in Canada, (ANiCGA B 14% 1, (2)-M86). In
the absence of local building codes, adhere to the fbltowing
pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. in
ever?" 15 ft to prevent traps. Grade all horizontal runs
downward to risers. Use risers to connect to heating section
and to meter.
2. Protect all segments of piping system against physical and
thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a mininmm of one hanger eve N- 6ft. For
pipe sizes larger d_an 1/2 in., fbltow recommendations of
national codes.
3. Apply joint compound (pipe dope) sparingly and only to male
threads of joint when making pipe connections. Use only pipe
dope that is resistant to action of liquefied petroleum gases as
specified by local and/or national codes. :\;ever zz.se 7;e_7ot_
tope.
4. Install sediment trap in riser leading to heating section (See
Fig. 9). This &ip leg Nnctions as a trap fbr dirt and
condensate.
5. Install an accessible, external, manual main shutoff valve in
gas supply pipe within 6 ff of heating section.
6. Install groundojoint union close to heating section between
unit manual shutoff and external manual main shut-off valve.
? Pressure-test all gas piping in accordance witla local and
national plumbing and gas codes before connecting piping to
unit,
NOTI::: Pressure test the gas supply system qfter the gas supply
piping is connected to the gas valve. The supply piping must be
disconnected f?om the gas valve during the testing of the piping
systems when test pressure is in excess of 0.5 psig. Pressure test
the gas supply piping system at pressures equal to or less than 0.5
psig. The unit heating section must be isolated fi'om the gas piping
system by closing the external main manual shutoff valve and
slightly opening the ground-joint union.
Unstable operation may occur when the gas valve and
manifbld assembly are forced out of position while connect-
ing improperlyorouted rigid gas piping to the gas valve. Use
a baclcup wrench when making connection to avoid stlain on,
or distortion of, the gas contIol piping.
If a flexible conductor is required or allowed by the authority
having jurisdictiom black iron pipe shall be installed at the
gas valve and shall extend a nlinirnurn of 2in. outside the unit
casing.
Table 2--Physical Data--Unit 48GX (Continued)
UNiT BBZE 48G× 048090 048115 048130 0g0090 060115 060130
NOMINAL CAPACBTY (ton) 4 4 4 5 5 5
OPERATING WEIGHT (_b.) 421 421 421 468 468 468
COMPRESSORS Scrolt
Quantity 1
REFRmGERANT {R=22}
REFRIGERANT METERING OEVICE Acutrol Device
Orifice ID (in.) .034 .034 .034 .032 .032 .032
CONDENSER CORL 2...17 2._17 2._17 2...17 2_.17 2._17
Rows...Finstin. 12.3 12.3 12.3 16.4 16.4 16.4
Face Area {sq ft}
CONDENSER FAN 3300 3300 3300 3300 3300 3300
Nominal Cfm 22 22 22 22 22 22
Diameter (in.)
Motor Hp (Rpm) _A(1100) _¼(1100) _¼(1100) _A(1100) _A (1100) _A(1100)
EVAPORATOR COIL 4...15 4...15 4...15 4...15 4...15 4...15
Rows...Finslin. 4.7 4.7 4.7 4.7 4.7 4.7
Face Area {sq ft}
EVAPORATOR BLOWER 1600 1600 1600 1750 1750 1750
Nomina_ Airflow (Cfm} 11 X 10 11 X 10 11 X 10 11 X 10 11 X 10 11 X 10
Size ({n.} 3/4 (1075) 3/4 (1075) 3/4 (1075) 1.0 (I075) 1.0 (1075) 1.0 (1075)
Motor Bp (Rpm)
FURNACE SECTION*
Burner Orifice No. (Qty...DriH Size) 3._38 3...33 3...31 3...38 3_.33 3_.31
Natural Gas 3...46 3...42 3...41 3...46 3...42 3...41
Burner Orifice No. (Qty...Drill Size)
Propane Gas
RETURN-AIR FILTERS (in.)'( 24 X 30 24 X 30 24 X 30 24 X 30 24 X 30 24 X 30
Throwaway
Based on altitude of 0 to 2000 ft
1 Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velodty of 300
ft/minute for high-capacity type Air filter pressure drop for non-standard filters must not exceed 008 in. wg.
Table 3--Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE,
SIZE
(IN.}
V2
%
1
11/4
iNTERNAL LENGTH OF PIPE, FT¢
DIAMETER
(BN.} 10 20 30 40 50 60 70 80 90 100 125 150 175 200
.622 175 120 97 82 73 66 61 57 53 50 44 40 -- --
.624 360 250 200 170 151 138 125 118 110 103 93 84 77 72
1.049 660 465 375 320 285 260 240 220 205 195 175 160 145 135
1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280
1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430
Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 05-in wg (based on a 0.60 specific gravity gas). Refer to Tabte C-4, National
Fire Protection Association NFPA 54.
1 This length includes an ordinary number of fittings
l
Never use a match or other open flame when checking %r gas
leaks. Never purge gas line into combustion charuber. Failure
to follow this warning could result in an explosion causing
serious injury or death.
8. Check %r gas leaks at the field-installed and factow-installed
gas lines after all piping connections have been completed
Use soap-and-water solution (or method specified by local
codes and/or regulations)
Step g--INSTALL DUCT CONNECTmONS
The unit has duct flanges on the supply- and return-air openings on
the side and bottom o_["the unit, For downshot applications, the
ductwork connects to the roof cm'b (See Fig 2 and 3 for
connections sizes and locations)
10
CONFIGURING UNITS FOR DOV_q',rFLOW (VERTI(AL) DIS-
( HARGE
Be%re per%rming service or maintenance operations on the
system, mrn off main power to unit. Electrical shock could
cause serious injury or death.
1. Open all electrical disconnects be%re starting any service
work_
2. Remove return duct cover located on duct panel by breaking
connecting tabs with screw&iver and a hammer (See Fig. 10A
& 10B).
3. To remove supply duct cover, break flout and right side
connecting tabs with a screwdriver and a hammer. Push touver
down to break rear and left side tabs (See Fig. 10A & 10B)
OUT
I
3"MIN
__!_1
IN
--:u
TEE
_.._ NIPPLE
CAP
Fig. 9--Sediment Trap
C99020
o
o
/
/
SUPPLY RETURN
DUCT DUCT
OPENING OPENING C99011
Fig. 10A SupNy and Return Duct Opening
4. If unit duct_xork is to be attached to x ertical opening flanges
on the unit composite base (jackstand applications only), do so
at this time,
Collect ALL screws that v, ere removed. Do not lea_e screws
on rooftop as pem_anent damage to the roof may occur
5. It is recommended that the unit base insulation around the
perimeter of the vertical return°air opening be secured to the
unit base with aluminum tape. Applicable local codes may
require aluminum tape to prevent exposed fiberglass
6. Cover both horizontal duct openings with the duct covers fl'om
the accessory duct cover kit. Ensure opening is air- and
watertight.
7. After completing unit conversion, perform all safety checks
and power up unit.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA fbr installation of
nonresidence-type air conditioning and ventilating systems, NFPA
90A or residence-type, NFPA 90B; and/or local codes and
ordinances.
11
DUCT COVERS REMOVED
C99012
Fig. lOB--Vertical Duct Cover Removed
Adhere to the following criteria when selecting, sizing_ and
installing the duct system:
1Lnits are shipped for horizontal duct installation (by removing
&ct covers)
2 Select and size ductwork, supply-air registers, and return-air
grilles according to American Society of Heating, Refiigera-
tion and Air (onditioning Engineers (ASHRAE) recommen=
dations
3Lse flexible transition between rigid dnctwork and unit to
prevent transmission of" vibration. The transition may be
screwed or bolted to duct ['langes. Lse suitable gaskets to
ensure weathertight and airtight seal.
4 All units must have field-supplied filters or accessory filter
rack installed in the return-air side of the unit. Recommended
sizes fbr filters are shown in Tables 1 and 2.
5. Size all dnctwork for naaximnm required airflow (either
heating or cooling) for unit being installed. Avoid abrupt duct
size increases or decreases or perfimnance may be affected.
6. Adequately insulate and weatherproof all ductwork located
outdoors. Insulate ducts passing through unconditioned space,
and use vapor barrier in accordance with latest issue of Sheet
Metal and Air Conditioning Contractors National Association
(SMA(NA) and Air Conditioning Contractors of America
(AC(A) mininmm installation standards for heating and air
conditioning systems. Secure all dtlcts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings in
building structure in accordance with local codes and good
building practices.
UNIT
SBZE
48GS
018
824
O3O
836
042
048
OGO
V-PH-HZ
208/230-1-60
208/230-1-60
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
VOLTAGE
RANGE
Table 4--Electrical Data--Unit 48GS
COMPRESSOR OUTDOOR FAN INDOOR FAN
MOTOR MOTOR
FLA
1.8
2.0
2.0
2.0
3.6
3.6
1.9
3.8
3.8
2.0
3.8
3.8
2.0
6.2
6.2
3.2
Max RLA
253 9.0
253 12.8
253 14.4
253 12.6
253 13.0
253 9.0
506 4.5
253 18.6
253 10.7
506 5.3
253 25.3
253 13.5
506 6.7
253 28.9
253 18.6
506 8.5
Min
187
187
187
187
187
187
414
187
187
414
197
187
414
187
187
414
LRA
45.0
61.0
73.0
68.0
81.0
78.0
40.0
105.0
85.0
42.0
131.0
108.0
47.5
147.0
125.0
66.5
FLA
0.8
0.8
0.8
0.8
1.6
1.6
0.9
1.6
1.6
0.9
1.6
1.6
0.9
1.6
1.6
0.9
POWER SUPPLY
Max Fuse or
MCA Ckt Bkr
13.9 20
18.8 30
20.8 30
13.2 20
24.0 35
16.5 25
8.4 15
27.5 45
18.8 25
9.5 15
37.0 60
22.3 35
11.3 15
43.9 60
31.1 45
14.7 20
Step 10--INSTALL ELECTRICAL CONNECTIONS
The unit cabinet must have an unimetTupted, unbroken
electrical ground to minimize the possibility of serious injury
if an electrical fimlt should occur. This ground may consist of
an electrical wire connected to the unit ground lug in the
control compartment, or conduit approved for electrical
ground when installed in accordance with NEC (National
Electlical Code) ANSIiNFPA (latest edition) and local elec-
trical codes. In Canada, fi_llow Canadian Electrical Code
CSA (Canadian Standards Association) (22.1 and local
electrical codes. Failure to adhere to this warning could result
in serious injm?- or death.
Failure to %tlow these precautions could result in damage to
the unit being installed:
1 Make all electrical connections in accordance with NEC
ANSINFPA (latest edition) and local electrical codes
governing such wiring In Canada, all electrical connec-
tions must be in accordance with CSA standard C22.1
Canadian Electrical (?ode Part 1 and applicable local
codes RefBr to unit wiring diagram.
2 Use only copper conductor fbr connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE
3 Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate
4 Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc. On
3-phase units, ensure phases are balanced within 2percenL
Consult local power company fbr correction of improper
voltage an&or phase imbalance
HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field-
supplied, waterproof, disconnect switch mounted at, or within
sight fi'om, the unit Refer to the unit rating plate fbr maximum
Nseicircuit breaker size and minimum circuit amps (ampacity) for
wire sizing (See Tables 4 and 5 for electrical data).
12
The field-supplied disconnect switch box may be mounted on the
unit over the high-voltage inlet hole when the standard power and
tow-voltage entIy points are used (See Fig. 2and 3 fbr acceptable
location).
See unit wiring label and Fig. 11 fbr refhrence when making high
voltage connections. Proceed as follows to complete the high-
voltage connections to the unit.
HIGH VOLTAGE /
POWER LEADS .<_o_
(SEE UNITWIRING_
LABEL) _:_
CONTROLBOX
LOW-VOLTAGE _
POWER LEADS_
(SEE UNIT
WIRING LABEL)
mm
GND
'O"
O
O
SPLICE BOX
_ POWER
4Z::S JsuPPLY
FIELD-SUPPLED
FUSED DISCONNECT
VV_TLV_)_ @
YELLYL_ Q)
REDIRZ_> @
BRN!_ O" C)
THERMOSTAT
(TYPICAL)
C99018
Fig. 11--High= and Control=Voltage Connections
Single phase units:
1. Run the high-voltage (LI_ L2) and ground leads into the
control box.
2. Connect ground lead to chassis ground connection.
3. Connect L! to pressure tug connection 11 of the compressor
contactor,
4. Connect L2 to pressure tug connection 23 of the compressor
contactor.
Three-phase units:
1. Run the high-voltage (L!, L2, L3) and ground leads into the
control box.
LEGEND
FLA -- Full Load Amps
LRA -- Locked Rotor Amps
MCA -- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection
RLA -- Rated Load Amps
CKT BKR -- Circuit Breaker
NOTES:
1. tn compliance with NEC (National Electrical Code) requirements
for muttimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. Canadian units may be
fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply 'Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of 'voltage imbalance.
% Voltage imbalance
= 100 x max voltage deviation from average voltage
average voltage
EXAMPLE: Suppty voltage is 460-3-60.
A B C AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
3
_ 1371
3
= 457
Determine maximum deviation from average 'voltage.
(AB) 457 452=5v
(BC) 464 457=7v
(AC) 457 455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x --
457
: 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: tf the supply 'voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
c99024
Table4_Legend
2. Connect ground lead to chassis ground connection
3. Locate the black and yellow wires connected to the lines side
of the contactor
4. Connect field L1 to black wire on connection 11 of the
compressor contactor
5. (onnect field wire L2 to yellow wire on connection 13 of the
compressor contactor
6. (onnect field wire L3 to Blue wire flora compressor
SPE(IAL PRO(EDURES FOR 208-V OPERATION
N
iii_ iiiiiiiiiii_,
Be_bre making any wiring changes, make sure the gas supply
is switched off first. Thet_ switch off the power st_pply to the
unit and install tockot_t tag. Electrical shock can cause serious
injury or death.
CONTROL VOLTAGE CONNE( TIONS
Do not use any type of power-stealing thermostat Unit control
problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated
(35 C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft flora the unit (as measured along fl_e control
voltage wires), use no. 16 AWG color-coded, insulated (35 C
minimmn) wires.
Standard ( onnection
Remove knockout hole located in the flue panel adjacent to the
control access panel (See Fig. 2and 3). Remove the rubber
grommet fi'om the installer's packet (included with unit) and install
grommet in the knockout opening. Provide a drip loop before
running wire through panel.
Rtm the low-voltage leads fiom the thermostat, through the inlet
hole, and into unit tow-voltage splice box.
Locate five 18-gage wires leaving control box. These low-voltage
connection leads can be identified by the colors red, green, yellow,
brown, and white (See Fig. 1 i). Ensure the leads are long enough
to be routed into the low-voltage splice box (located below right
side of control box). Route leads through hole in bottom of control
box and make tow-voltage connections (See Fig 11) Secure all
cut wires, so that _hey do not interI:_re with operation of unit.
HEAT ANTICIPATOR SETTING
The room thermostat heat anticipator must be properly adjusted to
ensure proper heating performance. Set the heat anticipator, using
an ammeter between the W and R terminals to determine the exact
required setting.
NOT_:: For thermostat selection purposes, use 0.18 amp for fl-le
approximate required setting. Failure to make a proper heat
anticipator adjustment will result in improper operation, discom-
fort to the occupants of the conditioned space, and inefficient
energy utilization; however, the required setting may be changed
slightly to provide a greater degree of comfort for a particular
installation.
TRANSFORMER PROTE( TION
The tra_,_former is of fl_e energy-limiting type. It is set to
withstand a 30-sec. overload or shorted secondary condition.
13
UNIT
SBZE
48GX
O24
030
036
O42
O48
OGO
V-PN-NZ
208/230-1-80
208/230-1-60
208/230-3-80
208/230-1-60
208/230-3-80
460-3-60
208/230-1-80
208/230-3-80
460-3-80
208/230-1-60
208/230-3-80
480-3-60
208/230-1-80
208/230-3-60
460-3-80
VOLTAGE
RANGE
Tab{e 5--Electrical Data--Unit 48GX
COMPRESSOR OUTDOOR FAN INDOOR FAN
MOTOR MOTOR
FLA
2.0
2.1
2.1
3.6
3.6
1.9
4.1
4.1
2.0
4.1
4.1
1.9
6.2
6.2
3.2
Max RLA
253 10.9
253 13.5
253 9.0
253 16.7
253 11.2
506 5.4
253 17.9
253 12.4
506 6.I
253 23.4
253 13.0
506 6.4
253 28.8
253 17.3
506 9.0
Min
187
187
187
187
187
414
187
187
414
187
187
414
187
187
414
LRA
54.0
73.0
63.0
97.0
75.0
37.5
104.0
88.0
44.0
126.0
93.0
46.5
169.0
123.0
62.0
FLA
0.9
0.8
0.8
0.8
0.8
0.9
1.6
1.8
0.9
1.5
1.5
0.9
1.6
1.8
0.9
POWER SUPPLY
Max Fuse or
MCA Ckt Bkr
16.5 25
19.8 30
14.2 20
25.3 40
18.4 25
9.6 15
28.1 45
21.2 30
10.5 15
34.9 45
21.9 30
10.8 15
43.8 60
29.4 45
15.4 20
LEGEND Q
FLA -- Full Load Amps
LRA -- Locked RotorAmps C US
MCA -- Minimum CircuitAmps
MOCP -- Maximum Overcurrent Protection
RLA -- Rated Load Amps
CKT BKR -- Circuit Breaker
NOTES:
1. tn compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. Canadian units may be
fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. tf other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase int_balance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
= 100 x max voltage deviation fr
average voltage
EXAMPLE: Supply 'voltage is 460-3-60.
A B C AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
3
1371
3
= 457
Determine maximum deviation from average 'voltage.
(AB) 457 452=5v
(BC) 464 457=7v
(AC) 457 455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage imbalance = 100 x --
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
1
IMPORTANT: tf the suppty voltage phase imbalance is_
more than 2%, contact your local electric utility company I
immediately.
Tab{e 5--Legend
14
PREoSTARToUP
Failure to obselwe the %llowing warnings could result in
serious injury:
I Follow recognized safhty practices and wear protective
goggles when checking or se_'icing reffigeiant system
2 Do not operate compressor or provide any electric power to
onit unless compressor tem_inal cover is in place and
secured.
3. Do not remove compressor terminal cover until all electli=
cal sources are disconnected.
4. Relieve and recover all refrigerant fi'om system before
touching or disturbing anything inside terminal box if
ret'rigerant leak is suspected around compressor terminals.
5. Never attempt to repair soldered connection while refrig=
erant system is under pressure.
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure. To remove a
component, wear protective goggles and proceed as fbl=
lows:
a. Shut off gas supply and then electrical power to unit.
b. Relieve and recover all refrigerant fi'om system using
both high= and low=pressure ports.
c. Cut component connecting tubing with robing cutter and
remove component fi'om unit.
d. Carefully unsweat remaining tubing stubs when neces=
sary. Oil can ignite when exposed to torch flame.
Proceed as %llows to inspect and prepare the unit %r initial
startup:
1. Remove access panel
2. Read and follow instluctions on all WARNING, (AUTION,
and IN'FORMATION labels attached to, or shipped with, unit
3. Make the following inspections:
a Inspect for shipping and handling damages such as broken
lines, loose parts, disconnected wires, etc.
b. Inspect fbr oil at all refrigerant robing connections and on
unit base Detecting oil generally indicates a refrigerant
leak.
c Leak test all refrigerant robing connections using electronic
leak detector, halide torch, or liquid=soap solution If a
refrigerant leak is detected, see the Checkii_r Rc/i'ige_'c,t_t
Leal_s section.
d. Inspect all field= and fhctoo'=wiring connections. Be sure
that connections are completed and tight.
e. Ensure wires do not contact refrigerant robing or sharp
sheet metal edges.
f\ Inspect coil fins. If damaged during shipping and handling,
carefully straighten fins with a fin comb.
4. Veri/) the fbllowing conditions:
Do not purge gas supply into the con£bustion chamber Do not
use a match or other open flame to check for gas leaks
Failure to follow this warning could result in an explosion
causing serious injury or death.
a. Make sure gas line is fi'ee of air. Be%re lighting the unit %r
the first time, perfbrm the fbllowing with the gas valve in
the "OFF" position:
If the gas supply pipe was not purged before connecting
the unit, it will be full of air. It is recommended that the
15
ground joint union be loosened, and the supply line be
allowed to purge until the odor of gas is detected. Never
purge gas lines into a combustion chamber Immediately
upon detection of gas odor, retighten the union Allow 5
minutes to elapse_ then light unit.
b. Make sure that condenser-fan blade is correctly positioned
in fbn orifice. Leading edge of condenser=tim blade should
be 1/2 in. maximum from fan orifice venmri.
c. Ensure fan hub is 1/8 in. maximum fi'om motor housing
(See Fig. 12).
MOTOR _. .... , FAN GRILLE
1/8"MAX BETWEEN _J "'-
MOTORAND FAN HUB MOTOR SHAFT C99009
Fig. 12--Fan Blade Clearance
d. Make sure that air filter(s) is in place.
e. Make sure that condensate drain trap is filled with water to
ensure proper drainage.
£ Make sure that all tools and miscellaneous loose parts have
been removed.
MANIFOLD PIPE PLUG
C99019
Fig. 13--Burner Assembly
STAR%UP
Step I--CHECK FOR REFRIGERANT LEAKS
Proceed as follows to locate and repair a refrigerant leak and to
charge the unit:
1. Locate leak and make sure that refi'igerant system pressure has
been relieved and reclaimed Ii'om both high= and low-pressure
porls.
2. Repair leak fbllowing Refiigerant Service procedures.
NOTE[: Install a filter drier whenever the system has been opened
for repair.
3 Add a small charge of R-22 refi'igerant vapor to system and
leak-test unit.
BURNER FLAME
_Z NIFOLD
C99021
Fig. 14--Monoport Burner
4. Recover refi'igerant from ret'rigerant system and evacuate to
500 microns if additional leaks are not found
5. (barge unit with R-22 ret'rigerant, using a volumetric°
charging cylinder or accurate scale R@_' to _lnit _'atmg plate
fin" _'eq_li_'ed cha_'.ge_ Be sure to add extra ref?igerant to
compensate for internal volume of filter &ier.
Step 2--START-UP HEATING AND MAKE ADJUST-
MENTS
section bel\_re starting the unit
Do not jumper any safety devices when operating the unit
Make sure that burner orifices are properly aligned. Unstable
operation may occur when the burner orifices in the manifold are
misaligned
Follow the lighting instructions on the heating section operation
label (located inside the burner or blower access door) to start the
heating section.
NOTE: Make sure that gas supply has been purged, and that all
gas piping has been checked fbr leaks.
(HECK HEATING CONTROL
Start and check the unit fbr proper heating control operation as
fbllows (see fl/rnace lighting instructions located inside burner or
blower access panel):
1. Place room thermostat SYSTEM switch in the HEAT position
and d'*e fan switch is placed in AUTO position.
2. Set the heating temperature control of the thermostat above
ro on'l temperature
3. The induced-&aft motor will start.
4. After a call for heating, the main burner should light within 5
sec. If the burners do not tighk there is a 22-sec. delay bel\_re
another 5-sec. try. If the burners still do not light, this
sequence is repeated. If fl_e burners do not light within 15
minutes from the initial call for heat, there is a lockout. To
reset the control, break the 24-v power to W.
5. The evaporator fan will mrn on 45 sec. after fl_e flame has
been established. The evaporator fan will mm off45 sec. after
the thermostat has been satisfied.
(HECK GAS INPUT
Check gas input and manifbld pressure aker unit start=up (See
Table 6). If adjustment is required proceed as fbllows:
16
* The rated gas inputs shown in Table 6 are %r altitudes fiom sea
1eve1 to 2000 ft above sea tevel. These inputs are based on
natural gas with a heating value of 1050 Bmift 3 at 0.65 specific
gravity, or propane gas with a heating value of 2500 Bmifl 3 at
15 specific gravity.
* For elevations above 2000 if, reduce input 4 percent fbr each
1000 ft above sea level.
* When the gas supply being used has a different heating value or
specific gravity, refer to national and local codes, or contact
your distributor to determine the required orifice size.
These units are designed to consume the rated gas inputs
using fl-_e fixed orifices at specified manifold pressures as
shown in Table 6 DO NOT REDRILL THE ORIFICES
UNDER ANY CIRCUMSTAN(ES.
ADJUST GAS INPUT
The gas input to the unit is detem_ined by measuring the gas flow
at fl_e meter or by measuring the manifbld pressure Measuring the
gas flow at the meter is recommended for natural gas units. The
manifold pressure must he measured to determine the input of
propane gas units
Measure Gas Flow (Natural Gas Units)
Minor adjusm_ent to the gas flow can be made by changing the
mani_bld pressure. The manifold pressure must be maintained
between 3.4 and 3.6 in. wg.
If target adjustments are required,
change main burner orifices following
the recommendations of national
and local codes
NOTI=: All other appliances that use the same meter must be
turned off when gas flow is measured at the meter
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold (See Fig. 13) and connect
manometer. Turn on gas supply to unit.
3. Record number of seconds for gas meter test dial to make one
revolution
4. Divide number of seconds in Step 3 into 3600 (number of
seconds in one hour).
5. Muhiply result of Step 4 by the numbe* ofcu fl shown _br one
revolution of test dial to obtain cuff of gas flow pc* hour
6. Muhiply result of Step 5 by Bm heating value of gas to obtain
total measured input in Btuh. Compare this value with heating
input shown in Table 6 (Consult the local gas supplie* if the
heating value of gas is not known)
EXAMPLE: Assume d'mt the size of test dial is 1 cuft, one
revolution takes 32 sec, and the heating value of the gas is 1050
Btuift 3. Proceed as follows:
1. 32 sec. to complete one revolution.
2. 3600+32 112.5
3. 1125 x 1 1125 t't-_of gas flowihr
4. 1125 x 1050 118,125 Btuh input
If the desired gas input is i 15,000 Bmh, only a minor change in the
manifold pressure is required
Observe manifold pressure and proceed as follows to adjust gas
input:
1. Remove cover screw over regulator adjustment screw on gas
valve.
FIELD
SUPPLY
EQUIP GND
POWER
SCHEMATIC
208/230-1-60
COOLING FAN LOGIC
+3
G G
ENERGfZED DEENERGIZED
HEATINGFANLOGIC
ENERGIZED DE ENERGIZED
_OFF
HEAT
_HEAT
OAUTO
ON
FIELD-THERMOSTAT
i I
I
I I
I I r
I [i I.
W43 BLK
CAP 2
COMMON-- i i
¢/15YEL PRIMARY
TRAN1
SECONDARY
24V
W13 BLK
24V SPLICE BOX
W19 WHT
_W20GRN
Z_ w21 RED
CR
BR
W39 RED J2
IGC
o .........
QT
OFM
MG\/
FLAF_ESEN
YEL_ I
0 O BRN_
--W41 GRN-YEL
W32 BAN
W48 BAN
COMP
GROUNDED
TRU STANDOFF
IFM
IDM
W46 BAN
GRN-YEL_
W30BRN
UNIT COMPONENT ARRANGEMENT
OUTDOOR FAN []
SECTIDN
COblPRESSOR INDOOR FAN F_
SECTION SECTION
CAP2
COfIP
c s
R _ ...............
LARGE CHASSIS LOC
EQUIP
_lcAP; ji_,
o"
GASSECTION
m
DISCONNECT
PERNEC
LEGEND
AHA - Adjustable Heat NEC -NationN Electrical
Anticipator Code
BR - Blower Relay OFM - Outdoor-Fan Motor
C - Contactor QT -Quadruple TerminN
CAP - Capacitor RS -RoJiout Switch
CQMP - Compressor Motor SEN - Sensor
CR - Combustion Relay SW - Switch
CS - Centrifugal Switch TRAN - Transformer
EQUIP- Equipment
FS -Flame Sensor _ Field Splice
FU - Fuse
GND - Ground _ Terminal (Marked)
GV - Gas VaNe
GVR - GasVNve Relay _ Terminal(Unmarked)
HS - Hat] Effect Sensor
HV - High Voltage _ Splice
TRAN - Transformer
I - Ignitor _ Splice (Marked)
IDM - Induced-Draft Motor -- Factory Wiring
IFC - Indoor-Fan Contactor -- -- -Field Control Wiring
IFM - Indoor-Fan Motor
IGC - Integrated Gas Unit _ _ =Field Power Wiring
Controller .... Accessory or
L1 - Line Optional Wiring
LS - Limit Switch To indicate Common
LS1 - Limit Switch Potential Only, Not
MGV - Main GasVa]ve to Represent Wiring
NOTES:
1 If any of the original wires rum shed are replaced, they must be
replaced with type 90 degree C wire or its equivalent¸
2 See pdce pages for thermostat and subbases
3 Use 75 degree C copper conductors for field installation
4 For high speed IFM, disconnect RED wire from IGC terminal BM
and connect BLK wire from IFM For medium speed, disconnect
RED wire from IGC terminal BM and connect BLU wire from IFM
C00057
Fig. 15--208/230-1-60 Wiring Diagram, Units 48GS and 48GX
2. ]-urn regulator adjustment screw clockwise to increase gas decrease input Manifold pIessure must be between 3.4 and
input_ or turn regulator adjustment screw counterclockwise to 3,6 in, wg. Unsa/_ operation of the unit may result if maul/bid
17
COOL NG FAN LOGIC:
0 T T_30
G G
ENERGIZED DE ENERGIZED
HEATING FAN LOGIC
0 45 T T30
WBR WBR
ENERGIZED DE ENERGIZED
RC
TRANI
O__ W13 BLK-
COMMON------
RH
J l_l
--o OAUTO
ON
FIELD-THERMOSTAT
__ __ z_
W59YEL
-- W64 YEL--
W15YEL
SECONDARY
24V
OR
W56 BLU
F
o
g
IFM
IDM
I
I 24V SPLICE BOX
W19WHT
W20 GRN
W21 RED
UNIT COMPONENT ARRANGEMENT
OUTDOORFAN F_
SECTION
EQUIP
GND
EED' o SSO E
_ _ ,_
_cAP3 j! -
COMP
CS
GASSECTION
DISCONNECT
PERNED
BR
--W39 RED J2 1 _
IGC --L
@
F/_:> --I
__./<32:} SAF
@ -- __
@ -- __
, i
Y ' Q_'_* /o
_2J qF]
2
GROUNDED
TRUSTANDOFF
FLAMESEN
-W4I GRN-YEL
-- W32 BRN
W46 BRN
W46BRN--
W30 BRN
LEGEND
AHA - Adjustable Heat NEC -National Electrical
Anticipator Code
BR - Blower Relay OFM - Outdoor-Fan Motor
C - Contactor QT - QuadrupleTerminal
CAP - Capacitor RS - Rollout Switch
COMP - Compressor Motor SEN - Sensor
CR - Combustion Relay SW - Switch
CS - Centrifugal Switch TRAN - Transformer
EQUIP- Equipment
FS - Flame Sensor _ Field Splice
FU - Fuse
GND - Ground O Terminal (Marked)
GV - Gas Valve
GVR - GasValve Relay O Terminal (Unmarked)
HS - Hall Effect Sensor
HV - High Voltage _ Splice
TRAN - Transformer
I - ignitor <[_)@ Splice (Marked)
IDM - Induced-Draft Motor -- FactoryWiring
IFC - Indoor-Fan Contactor -- -- - Field Control Wiring
IFM - Indoor-Fan Motor
iGC - integrated Gas Unit -- -- - Field Power Wiring
Controller .... Accessory or
L1 - Line Optional Wiring
LS - Limit Switch To indicate Common
LS1 - Limit Switch Potential Only, Not
MGV - Main Gas Valve toRepresentWiring
NOTES:
1Fany of the odgina] wires furnished are replaced, they must be
replaced with type 90 degree C wire or its equivalent.
2 See price pages for thermostat and subbases
3. Use 75 degree C copper conductors for field installation
4 For high speed IFM, disconnect RED wire from IGC terminal BM
and connect BLK wire from IFM For medium speed, disconnect
RED wire from IGC terminal BM and connect BLU wire from IFM
Fig. 16--2081230-3-60 Wiring Diagram, Units 48GS and 48GX
18
C00058
OFM
COMP
COOLING FAN LOGIC
0 T T+30
G G
ENERGIZED DE ENERGIZED
HEATING FAN LOGC
0 45 T T÷30
W BR W BR
ENERGLZED DE ENER®JZED
RC
(7
° AUTO
ON
FIELD-THERMOSTAT
COMMON------
TRAN1
-W13 BLK
1 24V SPLICE BOX
i --
I I ---WSWNT
-W20 GRN
i i r
..... W21 RED
--I I
I
_q i
i
i
i
i __
UNIT COMPONENT ARRANGEMENT
OUTDOOR FAN []
SECTION
COMPRESSOR INDOORFAN F_
SECTON SECTION L2_
COMP
CS
R
EQUIP
FROMCONPl_Ap31 11(
OLo
GASSECTION
DISCONNECT
PEREC
IFM
IDM
4_SECONDARY]
24V
OR
BR
W39 RED
IGC
; F -_,j
r
!-]
J_
5 AMF
_z- -- 't0
BLU_--1
to MGV
,R
-IF] --W35 GRA
, W34 BRN
FLAMESEN
--O O--- BRN--_
-W41 GRN-YEL
-- W32 BRN
_W46 BRN
W46BRN--
GROUNDED
TRUSTANDOFF
W30BRN-
LEGEND
AHA - Adjustable Heat NBC - National Electrical
Anticipator Code
BR - Blower Relay OFM - OutdooFFan Motor
C - Contactor QT - Quadruple Terminal
CAP - Capacitor RS - Rollout Switch
COMP- Compressor Motor SEN - Sensor
CR - Combustion Relay SW - Switch
CS - Centrifugal Switch TRAN - Transformer
EQUIP- Equipment
FS - Flame Sensor FieldSplice
FU - Fuse
GND - Ground (_D Terminal (Marked)
GV - Gas \/alve
GVR - GasValve Relay O Terminal (Unmarked)
HS - Hall Effect Sensor
HV - High Voltage _ Splice
TRAN - Transformer
I - Ignitor _ Splice (Marked)
IDM - Induced-Draft Motor -- FactoryWiring
IFC - Indoor-Fan Contactor -- -- - FieldControl Wiring
IFM - Indoor-Fan Motor
IGC - Integrated Gas Unit _ _ - Field Power Wiring
Controller .... Accessory or
LI - Line Optional Wiring
LS - Limit Switch _ To Indicate Common
LS1 - Limit Switch Potential Only, Not
MGV - Main GasValve to Represent Wiring
NOTES:
1If any of the original wires furnished are replaced, they must be
replaced with type 90 degree C wire or its equivalent
2 See price pages for thermostat and subbases
3 Use 75 degree C copper conductors fo_ field installation
4 For high speed IFM, disconnect RED wire from IGC terminal BM
and connect BLK wire from IFM. For medium speed, disconnect
RED wire from IGC terminal BM and connect BLU wire from IFM
Fig. 17480-3-60 Wiring Diagram, Units 48GS and 48GX
19
C00059
Table 6--Heating inputs
HEATING
iNPUT
(BTUH)*
NUMBER
OF
ORIFICES
40,000 2
G0,000 2
90,000 3
115,000 3
130,000 3
Min
4.0
4.0
4.0
4.0
4.0
GAS SUPPLY PRESSURE
(IN, WG}
Natural Propanet
Min
4.0
4.0
4.0
4.0
4.0
Max
13.0
13.0
13.0
13.0
13.0
Natural
3.5
3.5
3.5
3.5
3.5
Max
13.0
13.0
13.0
13.0
13.0
MANIFOLD
PRESSURE
(IN, WG)
Propane¢
3.5
3.5
3.4
3.7
3.5
When a unit is converted to propane, different size orifices must be used. See separate, naturaMo-propane conversion kit instructions
1 Based on altitudes from sea level to 2000 fL above sea level. For altitudes above 2000 fL, reduce input rating 4 percent for each additional 1000 fl above sea level
In Canada, from 2000 ft above sea level to 4500 ft above sea level, derate the unit 10 percent
pressure is outside this range. Personal injury or unit damage
may result
Unsafe operation of the unit may result if mani%ld pressure
is outside this range Serious injury ,death or unit damage
may result
3. Replace cover screw cap on gas valve
4. Turn offgas supply to mail Remove manometer fi'om pressure
tap and replace pipe plug on gas valve. Turn on gas to unit and
check _br leaks.
Measure Manifbld Pressure (Propane Units)
The main burner orifices on a propane gas unit are sized for the
unit rated input when the manifold pressure reading matches the
level specified in Table 6.
Proceed as follows to adjust gas input on a propane gas unit:
1. Turn off gas to unit.
2. Remove pipe plug on manifold and connect manometer (See
Fig. 13).
3. Turn on gas to unit.
4. Remove cover screw over regulator adjustment screw on gas
valve.
5. Adjust regulator adjustment screw to the correct manifold
pressure, as specified in Table 6. Turn adjusting screw
clockwise to increase mani_bld pressure, or turn adjusting
screw counterclockwise to decrease mani_bld pressure.
6. Replace cover screw.
7. Turn off gas to unit. Remove manometer from pressure tap.
Replace pipe plug on gas valvQ then turn on gas to unit. (hock
£_r leaks.
CHECK B[ RNER FLAME
With burner access panel removed, observe the unit heating
operation. Watch the burner flames to see if they are light blue and
soft in appearance, and that the flames are approximately d-_esame
fbr each burner Propane will have blue flame with yellow tips
(See Fig. 14). Refer to the Ji_d_te_a_ce section for information on
burner removal.
AIRFLOW AND TEMPERATL RE RISE
The heating section for each size unit is designed and approved for
heating operation within the temperature=rise range stamped on the
unit rating plate
Table 7 shows the approved temperature rise range _br each
heating input, and the air delivery cfirt at rations temperature rises
The heating operation airflow must produce a temperature rise that
_511s within the approved range.
Refkr to/nduo*' Ai_3flon at_d Ai(f!on, Ac!j_zstme_v_:_ section to adjust
heating airflow when required.
HEATING SEQUENCE OF OPERATION
(See Fig. 15-17 and unit wiring label)
On a call fPr beating, terminal "W" of the thermostat is energized,
starting the indtlced=draft motor. When ff*e hall=effect sensor on
the induced=draft motor senses that it has reached d-_e required
speed, the burner sequence begins. This function is perfbm_ed by
the integrated gas control (IGC). The evaporator=fan motor is
energized 45 sec after flame is established. When the thermostat
is satisfied and "W" is deenergized, the burners stop firing and the
evaporator-tim motor shuts off after a 45=sec. time-off delay.
An LED (light=emitting diode) indicator is provided on the control
board to monitor operation. The control board is located by
removing the burner access panel. During normal operation, the
LED is continuously on (See Table 8 for error codes).
Table 8--LED Indications
ERROR CODE
Norma_ Operation
Hardware Failure
Fan OntOff Belay Modified
Limit Switch Fault
Flame Sense FauR
Four Consecutive Limit Switch Faults
Ignition Lockout Fault
induced-Draft Motor Fault
RoHout Switch FauR
Internal Control Fault
Temporary lock-out (1 hr)
NOTES:
1. There is a 3-sec pause between error code displays.
LED INDICATION
On
Off
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
2. If more than one error code exists, all applicable error codes will be
displayed in numerical sequence
3. This chart is on the wiring diagram located inside the burner access panel
2O
LIMIT SWITCHES
Normally closed limit switch (LS) completes the control circuit
through the thermostat R circuiL Should the leaving=air tempera°
rare rise above the maximum allowable temperature, the limit
switch opens and the R control circuit "breaks." Any interruption
in the R control circuit instantly closes the gas valve and stops gas
flow to the burners and pilot. The blower motor continues to 1tin
until LS resets.
When the air temperature at the limit switch drops to the
tow-temperature setting of the limit switch, the switch closes and
completes the R control circuit. The electric=spark ignition system
cycles and the unit returns to normal heating operation.
Table 7--Air Delivery {Cfm) at indicated Temperature Rise and Rated Heating input
HEATING
INPUT
(BTUH) 20 25 30
40,000 1500 1200 1000
60,000 2250 1800 1500
90,000 -- -- 2250
115,000 -- -- --
130,000 -- -- --
35
857
1286
1929
2464
2786
TEMPERATURE R_SB °F
40 45 50
750 667 600
1125 1000 900
1688 1500 1350
2156 1917 1725
2438 2167 1950
55
545
818
1227
1568
1773
6O
5OO
75O
1125
1438
1625
65
692
1038
1327
1500
NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.
7O
964
1232
AL XILIARY LIMIT SWITCH (ROLLOL T)
The function of the switch is to close the main gas valve in d-ie
event of flame rollout The switch is located above the main
burners. When the temperature at the auxilia_" switch reaches the
maximum allowable temperature, the R contlol circuit tlips,
closing the gas valve and stopping gas flow to the burners. The
indoor (evaporator) fin motor (IFM) and induced draft motor
continue to run until switch is reset. The IGC LED will display
FAULT (ODE 7.
Step a--START-UP COOUNG AND MAKE ADJUST-
MENTS
Complete the required procedures given in the Pro-Start-Up
section before starting the unit
Do not jumper any safety devices when operating the unit.
Do riot operate the compressor when the outdoor temperature
is below 40cT (unless accessory tow=ambient kit is installed).
Do riot rapid-cycle the compressor. Allow 5 minutes between
"on" cycles to prevent compressor damage.
(HE(KING (OOLING (ONTROL OPERATION
Start and check the unit for proper cooling controi operation as
follows:
1. Place room thermostat SYSTEM switch in OFF position
Observe that blower motor starts when FAN switch is placed
in ON position and shuts down when FAN switch is placed in
AUTO. position
2. Place SYSTEM switch in (COL position and FAN switch in
AUTO. position. Set cooling control below room temperature
Observe that compressor, condenser fm_, and evaporator
blower motors start. Observe that cooling cycle shuts down
when control setting is satisfied. The evaporator fhn will
continue to rnn for 30 sec.
3. When using an auto=changeover room thermostat, place both
SYSTEM and FAN switches in AUTO. positions. Observe
that unit operates in Heating mode when temperature control
is set to "call for heating" (above room temperature) arid
operates in (ooling mode when temperature control is set to
"call fbr cooling" (below room temperature)
IMPORTANT: Three-phase, scroll compressor units
(48GS048 arid 48GX030-060) are direction-oriented.
These units must be checked to ensure proper compressor
3-phase power lead orientation If not corrected within 5
minutes, the internal protector shuts off the compressor.
The 3-phase power leads to dte unit must be reversed to
cot_'ect rotation. When taming backwards, scroll compres-
sors emit elevated noise levels, and the difference between
compressor suction and discharge pressures may be &a-
matically lower than normal.
CHE(KING AND ADJUSTING REFRIGERANT (HARGE
The refrigerant system is fidly charged with R-22 refi'igerant,
tested, and fitctow-sealed,
NOTE: A({iustment of d'le ref?ige*ant charge is not required
unless the unit is suspected of not having the proper R-22 charge.
A superheat charging chart is attached to the outside of the service
access panel. The chart includes the required suction line tempera-
rare at given suction line pressures and outdoor ambient tempera-
tures
An accurate superheat, thermocouple- or d-iermistor-type ther-
mometer, a sling psychrometer, and a gauge manifold are required
when using the superheat charging method for evaluating the unit
charge. Do nut u,se7nerc_z_?' or .small diaT-O_e t,s_ermomete_'s
/_ecaz_se they are l_ot adeqzeate jot thi.s 07)e o/" mea.s_zrement.
N
When evaluating d_e refi'igerant charge, an indicated adjust°
ment to d_e specified factory charge must always be ve_-
minimal. If a substantial adjustment is indicated, an abnot_nai
condition exists somewhere in the cooling system, such as
insufi[icient airflow across either coil or both coils.
Proceed as follows:
1, Remove caps fiom tow- and high-pressure smwice fittings,
2 [sing hoses with valve core depressors, attach tow- and
high-pressure gauge hoses to low- and high-pressure service
fittings, respectively,
3 Start unit in Cooling mode and let unit run until system
pressures stabilize,
4 Measm'e and record the following:
a Outdoor ambient-air temperature (C>Fdb),
b Evaporator inlet-air tempe*ante (°F wb),
c Suction-tube temperature (°F) at tow-side service fitting
d Suction (low-side) pressure (psig),
5 Lsing "Cooling Charging Charts," compare outdoor-air ten>
perature (°F db) with the suction line pressure (psig) to
determine desired system operating suction line temperature
(See Fig, 18 30),
2i
6. (ompare actual suction=robe temperature with desired
suction-robe temperature [sing a tolerance of" + 3°F, add
refiigerant if"actual temperature is more than 3C>Fhighe* than
proper suction=tube temperature, or remove rel'rigerant if
actual ternperatme is more than 3C>Flower than required
suction-tube temperature
NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to the Cheek_br R@'igeras_t Leaks section
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
For cooling operation, the recommended airflow is 350 to 450
cIi*n fPr each 12,000 Btuh of rated cooling capacity. For
heating operation, the airflo_ must produce a temperature rise
that falls within the range stamped on the unit rating plate
Table 7 shows the temperature rise at various airflow rates Tables
11 and 13 show both heating and cooling airflows at various
external static pressures. Refer to these tables to determine the
airflow for the system being installed (See Tables 14 and 15 for
wet coil pressure &up).
NOTE: Be sure that all supply- and return-air grilles are open,
fi'ee fi'om obstrnctions, and adjusted properly
1
Be%re changing blower speed, shut off gas supply. Lhen
disconnect electrical power to the unit and install lockout tag.
Electrical shock or explosion can cause serious injury or
death.
Airflow can be changed by changing the lead connections of the
blower motor.
Unit 48GS two- or three=speed motors (except size 030) are
iactory wired ibr tow speed operation. Unit 48GS030 is factoQ'
wired for medium speed
All 4gGX units are factory wired fbr tow speed and may need to
be wired for medium or high speed in the field.
For 208/230V
For color coding on the 208/230V motor leads, see Table 9.
Table 9=Color Coding for 2081230=V Motor Leads
3=SPEED 2-SPEED
Naek = high speed black = high speed
blue = medium speed
red = low speed red = low speed
To change the speed of the blower motor (BM), remove the ihn
motor speed leg lead fi'om the blower relay (BR). This wire is
attached to terminal BM of the integrated gas control (IG() board
_br single- and 3=phase traits. To change the speed, remove and
replace with lead for desired blower motor speed. Inszdate the
removed lead lo avoid contact u,ith cha,ssi,spartx.
For 460=V GE Motors
For color coding on the 460=v GE motor teads, see Table 10.
To change the speed of the blower motor (BM), remove fan motor
speed lead from t!_e blower relay (BR) and replace with the lead
_br the desired blower motor speed. The motor speed lead is
attached to terminal BM of the integrated gas control (IGC) board
For low and mediunl speeds, black must be connected to the
jmalper wire i.s_d.te removed lead e_d to redid cu_tact nith
eha,s,sispart:,'. To select high speed on 460-v GE motors, separate
TaNe 10-Color Coding for 460-V GE Motor Leads
3-SPEED 2=SPEED
black = high speed black = high speed
violet = jumper blue = jumper
orange = medium speed
red = low speed red = tow speed
the black (female quick connect QC fi'om the jumper lead
(male quick connect QC) and connect the black lead to the BR
Ii_,s_date the imnl_er to redid eonlaet _itll a'/_3c,Sla,s,sispargx.
COOLING SEQUENCE OF OPERATION
With the room them?ostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO. position, the cooling sequence
of operation is as follows:
1. When the room temperature rises to a point that is slightly
above the cooling control setting of t!-_e them?ostat, the
thermostat completes the circuit between _hermostat terminal
R to terminals Y and G. These completed circuits through the
thermostat:
2. The normally open contacts of energized contactor (() close
and complete the circuit through compressor motor (COMP)
to condenser (outdoor) t5n motor (OFM). Both motors start
instantly.
3. The set of normally open contacts of energized relay BM close
and complete the circuit through evaporator blower (indoor)
_hn motor (IFM),
NOTE: (:)nee the compressor has started and then stopped, it
should not be started again until 5 minutes have elapsed. The
cooling cycle remains 'on" until the room temperature drops to a
point that is slightly below the cooling control setting of the room
thermostat At tl-_is point, the thermostat "breaks" tl-_e circuit
between thermostat tem_inal R to terminals Y and G. These open
circuits deenergize contactor coil (. The condenser and compres-
sor motors stop. After a 30=sec. delay, the blower motor stops. The
unit is in a "standby" condition, waiting for the next "call _br
cooling" fiom the room thermostat.
MAINTENANCE
To ensure continuing high per_brmance and to minimize the
possibility of premature equipment failure, periodic maintenance
must be per_brmed on this equipment This combination
heating/cooling unit should be inspected at least once each year by
a qualified stun'ice person. To troubleshoot cooling or heating of
units, refer to Tables 16 18.
NOTE: Consult your local dealer about the availability of a
l'naintenance contract
The ability to properly per%m_ maintenance on this equip=
ment requires certain expertise, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User's Manual. FAILURE
TO HEED THIS WARNING (OULD RESULT IN SERI=
OUS INJURY AND POSSIBLE DAMAGE TO THIS
EQUIPMENT.
22
Table 11--Dry Col! Air Delivery* - Horizontal Downflow Discharge -
Unit 48GS018°060 (Deduct 10 percent for 208 Volts)
230 AND 460 VOLT
Motor External Static Pressure (in. wg)
Unit Speed 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 227 212 196 177 165 153 .....
Low Cfm 1082 1016 929 796 668 428 .....
Watts ...........
0t8 Med Cfm ...........
Watts 287 275 266 253 242 234 226 ....
High Cfm 1270 1179 1054 932 780 633 372 ....
Watts 280 275 270 267 264 262 260 ....
Low Cfm 950 880 825 750 670 580 400 ....
Watts 380 375 365 360 355 350 344 335 312 -- --
024 Med Cfm 1220 1150 1090 1025 970 860 760 620 450 -- --
Watts 485 475 470 460 455 445 437 430 415 385 --
High Cfm 1475 1440 1350 1275 1200 1125 1025 925 750 400 --
Watts 280 275 270 267 264 262 260 ....
Low Cfm 950 880 825 750 670 580 400 ....
Watts 380 375 365 360 355 350 344 335 312 -- --
030 Med Cfm 1220 1150 1090 1025 970 860 760 620 450 -- --
Watts 485 475 470 460 455 445 437 430 415 385 --
High Cfm 1475 1440 1350 1275 1200 1125 1025 925 750 400 --
Watts 576 566 556 538 512 497 481 466 450 435 --
Low Cfm 1430 1403 1365 1263 1157 1068 973 900 827 704 --
Watts 680 671 660 624 604 620 602 558 534 512 496
036 Med Cfm 1720 1630 1538 1439 1346 1267 1167 1126 1018 858 781
Watts 810 800 790 782 766 742 723 709 688 661 627
High Cfm 1800 1745 1660 1600 1547 1465 1360 1270 1163 967 876
Watts -- 675 660 650 640 630 620 610 595 580 --
Low Cfm -- 1454 1387 1326 1275 1204 1142 1081 995 918 --
Watts -- 886 855 825 795 778 765 750 735 718 700
042 Med Cfm -- 1515 1458 1406 1350 1285 1224 1163 1091 1013 932
Watts -- -- -- 1000 950 925 910 890 875 855 833
High Cfm -- -- -- 1551 1488 1424 1360 1296 1233 1148 1071
Watts -- 727 712 700 688 666 644 622 595 569 --
Low Cfm -- 1678 1639 1600 1561 1500 1440 1379 1289 1198 --
Watts -- 853 836 821 807 782 756 730 699 667 640
048 Med Cfm -- 1914 1870 1825 1780 1711 1642 1573 1470 1367 1270
Watts -- 979 959 943 927 897 868 838 802 766 730
High Cfm -- 2150 2100 2050 2000 1922 1845 1767 1600 1535 1419
Watts 1033 949 864 836 822 808 772 737 705 674 642
Low Cfm 2105 2057 2009 1943 1909 1876 1823 1770 1698 1627 1531
Watts 1084 1054 1024 994 971 955 928 897 867 835 803
0$0 Med Cfm 2318 2248 2179 2110 2058 2000 1932 1885 1829 1740 1638
Watts -- -- 1184 1152 1120 1102 1084 1056 1029 997 965
High Cfm -- -- 2349 2278 2207 2124 2041 2000 1960 1853 1745
* Air delivery values are without air filter and are for dry coil (See Table 14-48GS Wet Coil Pressure Drop).
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting
UNiT SI£E
018,024, 030
036
042, 048, 060
Table 12--Filter Pressure Drop (in. wg)
CFM
FILTER $1Z _= 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15
20X24X1 0.09 0.10 0.11 0.13 0.14 0.15 0.16
24X30X 1 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
23
Table13--Dn]Coil Air Delivery* -Horizontam and Downflow Discharge-
Unit 48GX024=000 (Deduct 10 percent for 208 Volts)
Unit
O24
030
036
O42
O48
050
230 AND 450 VOLT
Motor External Static Pressure (in. wg)
Speed 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 281 282 281 278 276 ......
Low Cfm 899 828 757 691 619 ......
Watts -- -- -- 375 370 363 357 352 -- -- --
Med Cfm -- -- -- 969 897 824 744 649 -- -- --
Watts ..... 468 457 444 431 423 --
High Cfm ..... 994 913 826 730 620 --
Watts 246 244 243 241 .......
Low Cfm 982 860 808 736 .......
Watts 343 339 336 332 328 322 317 ....
Med Cfm 1233 1170 1109 1038 953 855 754 ....
Watts .... 441 432 421 410 400 -- --
High Cfm .... 1202 1111 1021 929 826 -- --
Watts -- 470 458 445 430 415 399 384 -- -- --
Low Cfm -- 1463 1406 1344 1273 1188 1091 983 -- -- --
Watts -- -- 514 501 487 47I 455 438 422 -- --
Med Cfm -- -- 1497 1428 1348 1255 1152 1042 929 -- --
Watts -- -- -- 646 636 626 614 602 589 -- --
High Cfm -- -- -- 1491 1412 1325 1228 1120 1003 -- --
Watts 643 625 614 605 593 574 549 518 485 454 --
Low Cfm 1626 1614 1579 1532 1478 1421 1361 1295 1218 1120 --
Watts .... 726 695 661 625 591 561 540
Med Cfm .... 1731 1672 1610 1541 1456 1345 1193
Watts ....... 790 766 742 713
High Cfm ....... 1699 1602 1494 1367
Watts 614 588 577 572 566 556 539 517 491 -- --
Low Cfm 1591 1549 1518 1490 1460 1421 1372 1312 1242 -- --
Watts 778 756 738 719 699 676 650 623 596 572 555
Med Cfm 1854 1837 1804 1759 1705 1643 1577 1508 1440 1375 1315
Watts .... 896 862 829 800 775 752 728
High Cfm .... 1956 1879 1797 1709 1615 1514 1406
Watts 834 813 782 746 712 680 652 626 -- -- --
Low Cfm 2016 1955 1898 1840 1781 1717 1646 1566 -- -- --
Watts 941 889 851 822 797 772 745 714 679 639 --
Med Cfm 2379 2233 2124 2038 1964 1892 1814 1727 1626 1511 --
Watts -- -- 960 949 920 883 845 812 783 753 --
High Cfm -- -- 2497 2224 2075 1986 1915 1831 1721 1588 --
* Air delivery values are without air filter and are for dry coil (See Table 15-48GX Wet Coil Pressure Drop table)
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure availabb for ducth_g
Failure to %ltow these warnings could result in serious injury:
1 First, mrn offgas supply to the uniL Yhe_ turn offelectlical
power to the unit and install lockout tag befbre perfbrming
any maintenance or service on the unit_
2. Use extreme caution when removing panels and parts. As
with any mechanical equipment, personal injury can result
fi'om sharp edges_ etc.
3. Never place anything combustible either on, or in contact
with, the unit.
4. Should overheating occur or the gas supply fhil to shut of 7,
turn off external main manual gas valve to the unit. The_
shut off electrical supply and install lockout tag.
Errors made when reconnecting wires may cause improper
and dangerous operation. Label all wires prior to disconnec=
tion when servicing.
The n_ininmm maintenance requirements fbr this equipment are as
follows:
1, Inspect air filter(s) each month (lean or replace when
necessaw Certain geographical locations may require more
fi'equent inspections,
2, Inspect indoor coil, outdoor coil, drain pan, and condensate
&ain each cooling season for cleanliness, (lean at least once
per heating cooling season or more often if'needed
3, Inspect blower motor and wheel fbr cleanliness at the begin=
ning of"each heating and cooling season Clean when neces=
saW Fo* fit:st heating and cooling season, inspect blower
wheel bi-monthly to determine proper cleaning frequency
24
30 40 50 60 70 80 90
SUCTION L]NE TEMPERATURE ("F)
I I I I I I I
4 10 IB 21 27 32
SUCT]ON LINE TEMPERATURE (_C)
Fig. 18--Cooling Charging Chart, 48GS018 U_ °46
30 40 50 50 70
SUCTION L]NE TEMPERATURE (_F)
I I I I I
4 10 18 21
SUCTION LINE TEMPERATURE (_C)
_ OUTDOOR TEMP
_ _F _ C
/15 46
-K_los <
_ ss ss
,_ 85 29
75 24
55 13
80 90
I I
27 32
Chart, 48GS024 U_ °42
30 40 SO 80 70 80 90
SUCTION LINE TEMPERATURE (_F)
I I I I I I I
4 10 16 21 27 32
SUCTION LINE TEMPERATURE ("C) C00043
Fig. 20--Cooling Charg{ng Chart, 48G8030 Units
4. Check electlical connections fbr tighmess and controls tbr
proper operation each heating and cooling season, Service
when necessa_-
5. Ensure wires are not contacting refrigerant robes or sharp
sheet metal edges.
6. Check and inspect heating section before each heating season.
Clean and adjust when necessary.
7. Check flue hood and remove any obstructions, if necessary.
30 40 50 SO 70 80 90
SUCTION LINE TEMPERATURE {'F)
I I I I I I I
4 10 1B 21 27 32
SUCTION LINE TEMPERATURE (_C)
Fig. 21--Cooling Charging Chart, 48GS036 U[_i_S044
AIR FILTER
Never operate the unit without a suitable air tilter in the
return-air duct system. Always replace the filter with the same
dimensional size and type as originally installed (See Tables
1 and 2 %r recommended filter sizes).
Inspect air filter(s) at least once each month and replace
(throwaway=type) or clean (cleanable=type) at least twice during
each heating and cooling season or whenever the filter(s) becomes
clogged with dust and/or lint.
EVAPORATOR BLOWER AND MOTOR
NOT_:: Ail motors are permanently lubricated. Do not attempt to
lubricate these motors.
25
30 40 50 60 70
SUCTION LINE TEMPERATURE (_F)
I I I I I
-1 4 10 16 21
SUCTION LINE TEMPERATURE (:C)
Fig 23--CooHn_
}L TDOOR TEMP
F C
115 46
105 41
95 35
85 29
75 24
65 18
55 13
45 7
80 90
I I
27 32
C00047
48G8048 UnRs
SUCTION LINE TEMPERATURE IF
-1 4 10 16 21 27 32
SUCTION LINE TEMPERATURE (:C) C00048
Fig. 24--Cooling Charging Chart, 48GS060 Units
For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease flora the blower wheel and
motor annually.
Befbre cleaning the blower motor and wheel, disconnect gas
supply. Then turn off and tag electrical power to the unit
Failure to adhere to this warning could cause serious injm T or
death.
(leaning the Blower Motor and Wheel
1, Remove and disassemble blower asserubly as %llows:
a, Remove unit access panel
b, Disconnect motor lead flora blower relay (BM) Discon=
nect yellow toad ['rom terminal L2 of the contactor
26
SUCTION LINE TEMPERATURE
Fig. 25--Cooling Charging Chart, 48GX024 UQ_0;049
c. On a/l units, remove blower assembly flora unit. Remove
screws securing blower to blower partition and slide
assembly out. Be care£hl not to tear insulation in blower
compartmenL
d. Ensure proper reassen£bly by marking blower wheel and
motor in relation _o blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft.
Remove screws that secure motor mount brackets m
housing, and slide motor and motor mount out of housing.
2. Remove and clean blower wheel as %llows:
a. Ensure proper reassembly by marking wheel orientation.
b. Lif_ wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights (clips)
on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel
(030) 60HZ CHARGING CHART
SUCTION LINE TEMPERATURE
26--Coolin{ 48GX0a0
(036) 60HZ CHARGING CHART
SUCTION UNE TEMPERATURE IF
-1 4 10 16 21 27 32
SUCTION LINE TEMPERATURE (C)
Fig. 27--Coolinc 48GX036 U_9c_°51
SUCTION LINE TEMPERATURE
-1 4 10 16 21 27 32
SUCTION LINE TEMPERATURE (:C) C00052
Fig. 28--Cooling ChargBng Chart, 48GX042 Units
and housing with vacuum cleaner, using soft brllsh attach°
ment. Remove grease and oil with mild solvent
d, Reassemble wheel into housing.
eReassemble motor into housing Be sure setscrews are
tightened on motor shak flats and not on round part of
shaft.
£ Reinstall unit access panel.
3. Restore electrical power to uniL Start unit and check for
proper blower rotation and motor speeds during heating and
cooling cycles.
FLI_E GAS PASSAGEWAYS
To inspect the flue collector box and upper areas of the heat
exchanger:
1. Remove the combustion blower wheel and motor assembly
according to directions in the d'oml_.stiut_-.ti_' Blo_ e_' section
27
SUCTION LINE TEMPERATURE
-1 4 10 16 21 27 32
SUCTION LINE TEMPERATURE (C)
Fig. 29--Cooling Charging Chart, 48GX048 U_i_ °53
2. Remove the 3 screws holding the blower housing to the flue
collector box cover (See Fig. 31 34).
3 Remove the 12 screws holding the flue collector box cover
(See Fig 33 34) to the heat exchanger assembly. Inspect the
heat exchangers.
4. (lean all surfitces, as required, using a wire brush.
COMBUSTION=AIR BLOWER
Clean periodically to assu*e proper airflow and heating efficiency.
Inspect blower wheel eve*y fall and periodically during the heating
season. For the first heating season, inspect blower wheel bi-
monthly to determine proper cleaning frequency
To inspect blower wheel, remove drak hood assembly Shine a
flashlight into opening to inspect wheel If cleaning is required,
remove motor and wheel as _bllows:
1 Remove unit access panel (See Fig. 32).
TaNe 14_48GS Wet Coit Pressure Drop
UNIT SiZE
48GS
018
024
030
036
042
048
060
AIRFLOW
(CFM)
500
600
7OO
7OO
800
900
900
1000
1100
1100
1200
1300
1300
1400
1500
1500
1600
1700
1900
2000
2100
PRESSURE DROP
(iN. WG)
0.049
0.070
0.095
0.077
0.100
0.127
0.065
0.080
0.097
0.084
0.100
0.177
0.103
0.120
0.138
0.088
0.100
0.113
0.108
0.120
0.132
Table 16--48GX Wet Coil Pressure Drop
UNIT SIZE
48GX
024
030
oa6
042
048
060
AIRFLOW
(CFM)
7OO
800
900
900
1000
1100
1100
1200
1300
1300
1400
1500
1500
1600
1700
1900
2000
2100
PRESSURE DROP
(IN. WG)
0.0535
0.067
0.123
0.0687
0.083
0.150
0.084
0.100
0.177
0.099
0.177
0.204
0.199
0.137
0.156
0.108
0.120
0.132
2, Remove the 7 screws that attach induced-drafl motor monnt-
ing plate to blower housing (See Fig 33)
3. Slide the motor and blower wheel assembly out of the blower
housing (See Fig. 33). Clean the blower wheel. If additional
cleaning is required, continue with Steps 4 and 5.
4. To remove blower, remove 2 setscrews
5. To remove motor and cooling fan assembly, remove 4 screws
that hold blower housing to mounting plate
6. To reinstall, reverse the procedure outlined above.
(060) 60HZ CHARGING CHART
SUCTION LINE TEMPERATURE (C C00054
Fig. 30--Cooling Charging Chart, 48GX060 Units
INDUCED DRAFT MOTOR MOUNT
CO
//
/
VENT HOOD
iN SHIPPING
LOCATION
A /
FLUE
t
ROLLOUT
SWITCH
COLLECTOR BLO'WER BURNER MOUNTING
BOX HOUSING RACK SCREW C99022
Fig. 31--Blower Housing and Flue Collector Box
BL RNER IGNITION
Unit is equipped with a direct spark ignition 100 percent tockont
system. Ignition modtlle is located in the control box. Module
contains a self'diagnostic LED. During servicing, refer to label
diagram for LED interpretation.
If lockout occurs, unit may be reset by either momentarily
interrupting power supply to unit or by turning selector switch to
OFF position at the thermostat
MAIN BURNERS
At the beginning of each heating season, inspect for deterioration
or blockage due to corrosion or other causes Obsma'e the main
burner flames and adjust, if necessary.
LIMIT SWITCH
Remove unit access panel Limit switch is located on the blower
partition
28
FRONT
ACCESS PANEL
Fig. 32--UNt Access Panel
C99091
HOUSING
2 SETSCREWS
(HIDDEN)
C99085
Fig. 33--Remova! of Motor and Blower Wheel
When servicing gas train, do not hit or plug orifice spuds.
Removal of Gas Train
To remove the gas train for servicing:
l. Shut of'["main gas valve.
2. Shut off power to unit and install lockout tag
3. Remove unit access panel (See Fig. 32)
4. Disconnect gas piping at unit gas valve
5. Remove wires connected to gas valve Mark each wire
6. Remove ignitor and sensor wires at the ignitor module.
7. Remove the mounting screw that attaches the burner rack to
the unit base (See Fig. 31)
8. Slide the burner rack out of the unit (See Fig 31 and 34)
29
C99086
Fig. 34--Burner Rack Removed
9 To reinstall, reverse the procedure outlined above
CONDENSER COIL, EVAPORATOR (OIL, AND
CONDENSATE DRAIN PAN
Inspect the condenser coil, evaporator coil, and condensate drain
pan at least once each year or more often if"necessa W
The coils are easily cleaned when du; therefbre, inspect and clean
the coils either befbre or after each cooling season. Remove all
obstructions, including weeds and shn/bs, that interfc, e with the
airflow through the condenser coil.
Straighten bent fins with a fin comb If coated with dirt or tint,
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be carefhl not to bend the fins If coated wit}*oil or
grease, clean the coils with a mild detergent-and=water solution.
Rinse coils with clear water, using a garden hose. Be careflfl not to
splash water on motors, insulation, wiring, or ai* filter(s) For best
resuhs, spray condenser coil fins f?om inside to outside the unit.
On units with an outer and inner condenser coil, be sure to clean
between the coils Be sure to f'lush all dirt and debris from the unit
base
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain par* and condensate drain by removing all
foreign matter from d*e pan Flush the pan and drain robe with
clear water Do not splash water on the insulation, motor, wiring,
or air fiher(s)_ If the drain tube is restricted, clear it with a
"plumbers snake" or similar probe device. Ensure that the auxiliary
drain port above the &ain robe is also clear
CONDENSER FAN"
Keep the condenser fan free from all obstructions to ensure
proper cooling operation Never place articles on top of the
unit, Damage to unit may result,
1. Remove 6 screws holding condenser grille and motor to top
cover,
2. Tuna motor/grille assembly upside down or* top cover to
expose the fan blade,
3.Inspectthefanblades%r cracks or bends
4. If fire needs to be removed, loosen the setscrew and slide the
fun off the motor shaft.
5. When replacing tim blade, position blade so the hub is 1/8 in.
away fi'om the motor end 11/8 in. of motor shaft will be
visible. See Fig. 12).
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
7. Replace grille.
ELECTRICAL (ONTROLS AND WIRING
Inspect and check the electrical controls and wiring annually. Be
sz_re to 1urn rfl tke gas .s_lp?/y, and then tke eleetr/ea/ pot_ er ;o the
_znif.
Remove access panel to locate all the electrical controls and
wiring. (heck al! electrical connections for tightness. Tighten all
screw connections. If any smoky or burned connections are
noticed, disassemble the connection, clean all the parts, restfip the
wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace the
access panel. Start the unit, and observe at least one complete
heating cycle arid one complete cooling cycle to ensure proper
operation. If discrepancies are observed in either or both operating
cycles, or if a suspected malfimction has occmTed, check each
electrical component with the proper electrical instrumentation.
Refer to the unit wiring label when making these checkouts.
NOTE: Refkr to the heating and/or cooling sequence of operation
in this publication as an aid in determining proper control
operation
REFRIGERANT CIRCUIT
Annually inspect all refi'igerant robing connections and the unit
base tbr oil accumulations. Detecting oil generally indicates a
refrigerant leak.
System urider pressure Relieve pressure arid recover al!
refrigerant before system repair or final unit disposal to avoid
serious injury or death. Use all service ports and open nil
flow=control devices, including solenoid vah'es.
If oil is detected or if low cooling perfbrmance is suspected,
leak-test all refi'igerant robing using an electronic leak=detector,
halide torch., or liquid-soap solmion If a refi'igerant leak is
detected, refer to the ('l_ecl;/br R@'igerat_f LeaI;s section.
If no refrigerant leaks are fbund and tow cooling performance is
suspected, refer to the ('becking and.4d]z_sfhg R@'/gerant (']ia_'ge
section.
GAS INPUT
The gas input does not require checking unless improper heating
performance is suspected. Ifa problem exists, refer to the Start-5})
section
EVAPORATOR AIRFLOW
The heating and/or cooling airflow does not require checking
unless improper perfbrmance is suspected. Ira pro/_/em exists, /:,e
.s_lre llIat all s_lp/)- a_'ld retail'n-airgrilles are olden and fi'eefi'om
ob.strz¢ctio_.s, and tkat tlie air filter is clean. When necessary, refer
to the Indoor .4i(flo_v at_d A i_;f](n_ A@¢stmet_s section to check the
system airflow.
METERING DEVKE A(UTROL DEVI(E
This metering device is a fixed orifice and is located in the header
to the evaporator coil
LIQUID LINE STRAINER
The liquid line strainer (to protect metering device) is made of wire
mesh and located in the liquid line on the inlet side of the metering
device.
TROUBLESNOOTNG
Use the Zl'o_lblc'skoofin_ Ch_ides (See Tables 1(_18) if problems
occur with these urks.
START-UP ¢HECKUST
Use the ,;;tar/{,_ (']_ee]dist to ensure proper start-up procedures are
followed.
3O
SYMPTOM
Compressor and condenser fan
will not start=
Compressor will not
start but condenser
fan runs.
Table 16--Troubleshooting Guide--Cooling
CAUSE
Power Failure
Fuse blown or circuit breaker tripped
Defective thermostat, contactor, transformer, or control relay
Insufficient line voltage
Incorrect or faulty wiring
Thermostat setting too high
Faulty wiring or loose connections in compressor circuit
Compressor motor burned out, seized, or internal
overload open
Defective run/start capadtor, overload, start relay
One leg of 3-phase power dead
Three-phase scroll compressor
(48GS048 and 48GX030=060 only}
makes excessive noise, and there may Scroll compressor is rotating in the wrong direction
be a low pressure differential.
Compressor cycles (other than
normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure,
Head pressure tOO lOW,
Excessive suction pressure,
Suction pressure too low=
Refrigerant overcharge or undercharge
Defective compressor
Insufficient line voltage
Blocked condenser
Defective run/start capacitor, ovedoad or start relay
Defective thermostat
Faulty condenser-fan motor or capacitor
Restriction in refrigerant system
Dirty air filter
Unit undersized for load
Thermostat set too low
Low reMgerant charge
Leaking valves in compressor
Air in system
Condenser soil dirty or restricted
Dirty air filter
Dirty condenser coil
Refrigerant overcharged
Air in system
Condenser air restricted or air short-cycling
Low refrigerant charge
Compressor valves leaking
Restriction in Hquid tube
High heat load
Compressor valves leaking
RsMgerant overcharged
Dirty air filter
Low refrigerant charge
Metering device or low side restricted
Insufficient evaporator airflow
Temperature too low in conditioned area
Outdoor ambient below 40°F
Field-installed filter-drier restricted
REMEDY
Call power company
Replace fuse or reset circuit breaker
Replace component
Determine cause and correct
Check wiring diagram and rewire correctly
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Determine cause
Replace compressor.
Determine cause and replace.
Replace fuse or reset circuit breaker
Determine cause.
Correct the direction of rotation by reversing the
3-phase power leads to the unit Shut down unit
to allow pressures to equalize.
Recover refrigerant, evacuate system, and recharge to
capacities shown on nameplate
Replace and determine cause
Determine cause and correct
Determine cause and correct
Determine cause and replace.
Replace thermostat.
Replace.
Locate restriction and remove
Replace filter.
Decrease load or increase unit size
Reset thermostat
Locate leak, repair, and recharge
Replace compressor.
Recover refrigerant, evacuate system, and recharge
Clean coil or remove restriction.
Replace filter.
Clean coil.
Recover excess refrigerant
Recover refrigerant, evacuate system, and recharge
Determine cause and correct
Check for leaks, repair, and recharge.
Replace compressor.
Remove restriction.
Check for source and eliminate.
Replace compressor.
Recover excess refrigerant
Replace Filter.
Check for leaks, repair, and recharge.
Remove source of restriction.
increase air quantity Check filter -- replace if necessary
Reset thermostat
install low-ambient kit.
Replace.
31
Table 17--Troubleshooting Guide-Heating
SYMPTOM CAUSE REMEDY
Water in gas line Drain. Install drip leg.
No power to furnace Check power supply fuses, wiring, or circuit breaker
Check transformer.
No 24-v power supply to contro{ circuit NOTE: Some transformers have internal overcurrent
protection that requires a cool-down period to reset.
Miswired or loose connections Check all wiring and wirenut connections
Burned-out heat anticipator in Replace thermostat.
Burners will not ignite, thermostat
Broken thermostat wire Run continuity check Replace wire if necessary
Check flame ignition and sense electrode positioning
Misaligned spark electrodes Adjust as necessary.
1Check gas line for air Purge as necessary
NOTE: After purging gas line of air, wait at least 5 minutes for any
No gas at main burners gas to dissipate before attempting to light unit
2 Check gas valve.
Dirty air filter Clean or replace filter as necessary.
Check gas pressure at manifold match with that on
Gas input to furnace too low unit nameplate
Unit undersized for application Replace with proper unit or add additional unit.
inadequate heating. Restricted airflow Clean or replace filter Remove any restriction.
Use faster speed tap if available, or install alternate
Blower speed too low motor.
Check rotation of blower, thermostat heat anticipator settings,
Limit switch cycles main burners temperature rise of unit Adjust as necessary.
1Tighten all screws around burner compartment
Incomplete combustion results in: 2 Cracked heat exchanger Replace.
Poor flame characteristics. Aldehyde odors, carbon monoxide, sooting 3 Unit overtired. Reduce input (change orifices or
flame, floating flame adjust gas line or manifold pressure).
4 Check burner alignment
32
Table18--TroubleshootingGuide-LEDErrorCodes
SYMPTOM CAUSE REMEDY
Check 5-amp fuse on IGC*, power to unit, 24-v circuit breaker, and
Hardware failure, transformer Units without a 24-v circuit breaker have an internal
Less of power to control module (IGC)*. overload in the 24-v transformer. If the overload trips, allow 10 rain-
(LED OFF) utes
for automatic reset.
High limit switch opens during heat
Fan ON/OFF delay modified exchanger warm-up period before fan-on Ensure unit is fired on rate: ensure temperature rise is correct.
delay expires. Ensure units external static pressure is within application guidelines
(LED/FLASH) Limit switch opens within three minutes
after blower-off delay timing in Heating mode.
Limit switch faults. Check the operation of the indoor (evaporator) fan motor. Ensure
(LED 2 flashes) High temperature limit switch is open. that the supply-air temperature rise is in accordance with the range
on the unit nameplate.
Flame sense fault. The IGC _ sensed flame that should not be
(LED 3 flashes) present. Reset unit. If problem persists, replace control board.
4 consecutive limit switch faults. Check operation of indoor (evaporator) fan motor and that supply-air
(LED 4 flashes) Inadequate airflow to unit temperature rise agrees with range on unit nameplate information
Ignition lockout. Unit unsuccessfully attempted ignition for Check ignitor and flame sensor electrode spacing, gaps, etc Ensure
(LED 5 flashes) 15 minutes, that flame sense and ignition wires are properly terminated. Verify
that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the speed
Indueed_draft motor fault. IGC does not sense that induced-draft sensor plug/IGC Terminal J2 connection Proper connection:
PIN 1-- White
(LED 6 flashes) motor is operating* PIN 2 -- Red
PIN 3 -- Black
Rollout switch will automatical{y reset, but IGC* will continue to Iock-
Rollout switch fault, out unit Check gas valve operation. Ensure that induced-draft
(LED 7 flashes} Rollout switch has opened. blower wheel is properly secured to motor shaft. Reset unit at unit
disconnect
Rollout control fault. Microprocessor has sensed an error in the If error code is not cleared by resetting unit power, replace the IGC*.
(LED 8 flashes) software or hardware
Reset 24-v. to control board or turn thermostat off,
Temporary software lock out. Electrical interference then on again Fault will automatically
(LED g flashes) impeding ]GC software reset itself in one (1) hour
* WARNING/_ X : If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board. The
IGC is sensibve to static electricity and may be damaged if the necessary precautions are not taken
IMPORTANT: Refer to Table 17--Troubleshooting Guide--Heating for additional troubleshooting analysis.
LEGEND
IGC -- Integrated Gas Unit Controller
LED -- Light-Emitting Diode
33
START-UPCHECKLIST
(RemoveandStoreinJob File)
LPRELIMINARY INFORMATION
MODEL NO: .............................................................................................................................................................
SERIAL NO: ..............................................................................................................................................................
DATE: ........................................................................................................................................................................
TECHNICIAN: ...........................................................................................................................................................
JOB LOCATION: ...........................................................................................................................................................
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK GAS PIPING FOR LEAKS
CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PEACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEEL PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS
IIL START-UP
ELE( TRI(AL
SUPPLY VOLTAGE LI-L2
COMPRESSOR AMPS L1
COMPRESSOR AMPS L1
]NDOOR (EVAPORATOR) FAN AMPS
L2-L3 L3-LI
L2 L3
L2 L3
TEMPERATURES
OUTDOOR (CONDENSER) AIR TEMPERATURE: DB
RETURN=AIR TEMPERATURE: DB WB
COOLING SUPPLY AIR: DB WB
GAS HEAT SUPPLY AIR:
PRESSURES
GAS INLET PRESSURE IN. WG
GAS MANIFOLD PRESSURE IN. WG
REFRIGERANT SUCTION PSIG
REFRIGERANT DISCHARGE PSIG
SUCTION LINE TEMP*
DISCHARGE LINE TEMPt
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR (48GS048 and 48GX030-060) IS ROTATING IN CORRECT
DIRECTION.
* Measured at s_mtion inlet to compressor
+ Measured at Iicp_id line leaving condenser
34
35
FormNo.48GS,GX-6SI Replaces:48GS,GX-5SIPage36 11/02 Copyright2002CarrierCorp. CatalogNo.534-80128