Carrier 58MTB060F10112 User Manual FURNACE Manuals And Guides L0902504
CARRIER Furnace/Heater, Gas Manual L0902504 CARRIER Furnace/Heater, Gas Owner's Manual, CARRIER Furnace/Heater, Gas installation guides
User Manual: Carrier 58MTB060F10112 58MTB060F10112 CARRIER FURNACE - Manuals and Guides View the owners manual for your CARRIER FURNACE #58MTB060F10112. Home:Heating & Cooling Parts:Carrier Parts:Carrier FURNACE Manual
Open the PDF directly: View PDF .
Page Count: 62
Download | ![]() |
Open PDF In Browser | View PDF |
® to the Expertg[ Installation, Start-up, and Operating Instructions Sizes 060-120, Series 110 Visit www.Carrier.com NOTE: Read the installation. the entire instruction manual Please retain these instructions after installation for future before starting with the furnace reference. ISO 9001:2000 NOTE: This furnace can be installed as a (2-pipe) direct vent or (1-pipe) non-direct vent condensing gas furnace. Special Venting Requirements Consignes for Installations in Canada Installation in Canada must conform to the requirements of CSA B149 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC $636. The special vent fittings and accessory concentric vent termination kits and accessory external drain trap have been certified to ULC $636 for use with those IPEX PVC vent components which have certified to this standard. In Canada, the primer and cement been must be of the same manufacturer as the vent system - IPEX System 636, PVC/CPVC Primer, Purple Violet for Flue Gas Venting and IPEX System 636(1) , PVC Cement for Flue Gas Venting, rated sp_ciales pour l'installation Uinstallation faite au Canada code CSA B149. Ce syst_me tuyaux, raccords, ciments tuyauterie de ventillation de ventillation au Canada doit se conformer aux exigences de ventillation doit se composer du de et appr_ts conformes au ULC $636. La des gaz, ses accessoires, le terminal concentrique mural ainsi que l'ensemble du drain de condensat ext_rieur ont _t_ certifies ULCS 636 pour l'application des composantes IPEX PVC qui sont certifi_es fi ce standard. Au Canada l'appr_t que le syst_me PVC/CPVC. et le ciment doivent _tre du m_me manufacturier de ventillation - IPEX Syst_me 636, Appr_t Mauve Violette pour conduit en _vacuation des gaz TM Class IIA, 65 deg C. must be used with this venting not mix primers and cements from one manufacturer system - do with a vent system from a different manufacturer. Follow the manufacturer's instructions in the use of primer and cement and never use primer or cement beyond its expiration The safe operation, as defined date. by ULC $636, of the vent system is based on following these installation instructions, the vent system manufacturer's installation instructions, and proper use of primer and cement. All fire stop and roof flashing used with this system must be UL listed material. Acceptability under Canadian standard CSA B149 is dependent upon full compliance with all installation instructions. Under this standard, it is recommended that the vent system be checked once a year by qualified service personnel. The TM, et le ciment d'un autre having jurisdiction (gas inspection authority, building department, fire department, etc) should be before installation to determine the need to obtain a permit. (1) System 636 is a trademark of IPEX Inc. d'un manufacturier avec le syst_me manufacturier. Bien suivre les manufacturier lors pas utiliser ceux-ci de ventillation indications du de l'utilisation de l'appr_t et du ciment si la date d'expiration est atteinte. Uop_ration s_curitaire, tel que d_finit par ULC $636, de ventilation est bass sur les instructions d'installation ainsi que l'usage appropri_ de l'appr_t et ciment. et ne du syst_me suivantes, Tout arr_t feu et solin de toit utilis_s avec ce syst_me doivent _tre des mat_riaux list,s UL. Uacceptation du standard Canadien CSA B419 est directement reli_ fi l'installation conforme aux instructions cihaut mentionn_es. Le standard Canadien recommande 1' inspection authority municipal consulted et IPEX Syst_me 636(1) ciment pour PVC pour conduit en _vacuation des gaz, _valu_ CLASSE IIA, 65 deg. C. doit _tre utilis_ avec ce syst_eme d'_vacuation - ne pas m_langer l'appr_t Les par un personel autorit_es qualifi_ ayant juridiction en bfitiments, d@artement consult_es avant l'installation requis. et ce, une fois par annie. (inspecteurs de gas, inspecteurs des incendies, etc) devraient _tre afin de d_terminer si un permis est Required Notice for Massachusetts Installations IMPORTANT The Commonwealth of Massachusetts 5.08: Modifications to NFPA-54, 2) Revise 10.8.3 by adding requires Chapter the following additional a. For all side wall horizontally in whole compliance with regulation 248 CMR as follows: 10 requirements: vented or in part for residential gas fueled purposes, equipment including those installed in every owned or operated dwelling, building or structure by the Commonwealth used and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. installing installed vented detector with an In addition, the plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner the installation of hard wired carbon monoxide detectors to secure the services of qualified licensed professionals for a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, shall have a period of thirty (30) days to comply with the above requirements; provided, however, (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed. 2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 3. SIGNAGE. A metal or plastic identification minimum height of eight (8) feet above grade fueled VENT accordance The state or local gas inspector of the side wall horizontally unless, upon inspection, the inspector observes carbon with 5. EXEMPTIONS: the provisions of 248 CMR The following equipment 5.08(2)(a)1 is exempt (1.) The equipment listed in Chapter 10 entitled NFPA 54 as adopted by the Board; and MANUFACTURER in accordance with the through REQUIREMENTS inch in size, "(}AS 4. from 248 CMR 5.08(2)(a)1 "Equipment - GAS (1/2) vented gas fueled equipment shall not approve monoxide detectors and signage installed in Not Required through 4: To Be Vented" in the most current (2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room the dwelling, building or structure used in whole or in part for residential purposes. c. the owner said thirty plate shall be permanently mounted to the exterior of the building at a directly in line with the exhaust vent terminal for the horizontally vented gas heating appliance or equipment. The sign shall read, in print size no less than one-half DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS". 4. INSPECTION. the installation that during EQUIPMENT VENTING SYSTEM or structure edition separate PROVIDED. of from When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 1. Detailed instructions 2. A complete for the installation parts list for the venting d. MANUFACTURER the manufacturer parts for venting satisfied parts venting design or venting - (}AS venting of instructions shall be Product installation all system" regarding or the venting system components; and system. EQUIPMENT VENTING SYSTEM NOT PROVIDED. When installation these requirements, and Gas Fitters, shall Approved be included by the Board, with the appliance and the instructions or equipment for that system installation shall include a instructions. instructions for equipment, all venting instructions, all parts shall remain with the appliance or equipment For questions design of a Product Approved side wall horizontally vented gas fueled equipment does not provide the the flue gases, but identifies "special venting systems", the following requirements shall be systems" list and detailed e. A copy system REQUIREMENTS system by the manufacturer: 1. The referenced "special instructions; and 2. The "special of the venting please contact 239 Causeway all Product Approved lists for venting at the completion the Commonwealth Street, Boston, side of Massachusetts MA wall instructions, and/or of the installation. 02114. Board 617-727-9952. horizontally all venting vented gas design instructions of State Examiners fueled of Plumbers TABLE SAFETY OF CONTENTS CONSIDERATIONS CODES Sequence .......................... AND STANDARDS 3 ........................... 5 Safety ............................................ General Installation .................................. Combustion and Ventilation Duct Systems Acoustical 5 5 Air ........................ and Fibrous Duct ................ Gas Piping and Gas Pipe Pressure Testing Electrical Connections ............................... Venting ........................................... ELECTROSTATIC INTRODUCTION DISCHARGE (ESD) .................................... APPLICATIONS General PRECAUTIONS ... ..................................... ........................................... Upflow Applications ................................. Downflow Applications Horizontal Left (Supply-Air Horizontal LOCATION General ............................. Discharge) Right (Supply-Air Discharge) ........................................ ...... Applications ..... .......................................... Furnace Location and Application ..................... AIR FOR COMBUSTION AND VENTILATION Leveling Installation in Upflow 53 7 7 Heat Pump Mode Component Self-Test 8 Operate Furnace 8 8 8 Adjust 8 Set Thermostat 12 ....... ............................. Treatment ..................... 21 23 ........................... ............................ Prime .................................... 29 29 Purge Gas Lines 30 45 45 ..................................... Drain Protection ...................... ................................... Off Delay (Heat Mode) Heat Anticipator 59 ................ 60 ..................... 60 Check Safety Controls .............................. Checklist ......................................... 60 61 AIRFLOW O q ozo RIGHTAIRF!O w AIRFLOW © AIRFLOW A93041 Fig. 1 - Multipoise Orientations SAFETY CONSIDERATIONS 30 ................. ........................................ Trap With Water 54 27 Air and Vent Pipe Systems Drain .................................. Condensate 54 54 ................................ 23 24 ..................................... ..................................... START-UR ADJUSTMENTS, AND General .......................................... 53 Rise .............................. 21 21 of Existing Furnaces from Vent Systems .............................. Application Condensation 53 ................................. .................................. 21 26 27 General .......................... .............................. 13 16 Gas Piping ........................................ Electrical Connections .............................. Combustion Condensate Blower Mode ................................. Set Gas Input Rate Set Temperature 25 26 Removal Common Furnace Restart 8 Filter Arrangement ................................. Bottom Closure Panel ............................... 115-v Wiring 48 21 ................. 24-v Wiring Accessories ...................... 21 Installation in Horizontal Applications Air Ducts ......................................... Air Connections Air Connections Mode) 17 18 ........................... Applications General Requirements Ductwork Acoustical Heating 48 Thermostat 17 17 .......... and Downflow Supply Return ......... .................................... Legs (If Desired) (Non-Adaptive With Two-Stage 16 Furnace Location Relative to Cooling Equipment Hazardous Locations ............................... INSTALLATION Heating Blower 10 Applications Two-Stage Continuous 7 ................ 47 Thermostat 49 49 7 Glass .............................. Heating With Single-Stage Mode) ................................. Cooling Mode ................................... Thermidistat Mode ............................... 7 ...................................... Lining of Operation Two-Stage (Adaptive SAFETY CHECK .................... ..... FIRE, EXPLOSION, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING HAZARD AND 45 46 Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage. 46 46 Improper installation, maintenance, or use 47 47 adjustment, could cause alteration, carbon service, monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factory-authorized and listed kits or accessories when modifying this product. This furnace is CSA (formerly for natural and propane gases installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. This furnace is factory-shipped for use with natural gas. A CSA listed gas conversion kit is required to FURNACE RELIABILITY HAZARD Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure. Application of this furnace attention given air temperature should be indoors convert hnproper installation, adjustment, alteration, maintenance, or use can cause explosion, fire, electrical other conditions which may cause death, personal This furnace or any other rate, service, shock, or injury, or qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Wear safety glasses, protective clothing, a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local Code (NEC) NFPA of the National and the National Fuel Gas Electrical 70. refer to the current of Canada Installation CAN/CSA-B149.1 and .2 Natural Gas and Propane Codes, and Canadian Electrical Code CSA C22.1 Recognize safety This is the safety-alert When you see this symbol on manuals, be alert to the potential Understand CAUTION. DANGER severe which of the National Standards symbol/_. the unit and in instructions for personal injury. or the signal words DANGER, WARNING, and These words are used with the safety-alert symbol. identifies the most serious hazards which will result in personal injury or death. WARNING signifies hazards could result in personal injury or death. CAUTION is used to personal identify unsafe practices which may result in minor injury or product and property damage. NOTE is used to highlight suggestions which installation, reliability, or operation. will result in built on site or a manufactured This furnace enhanced this caution may result in environmental pollution. Remove and recycle refrigerant, control all components boards, thermostat. db. Failure Return-air to follow of heat exchangers, or materials etc.) before (i.e., oil, unit final disposal. may result in personal 58MTB, 2-Stage, 4-way with the applications. (See Fig. 4.) drain and pressure Minor modifications 1. See details Multipoise, Category IV, condensing furnace is available ranging in high-stage gas input rates of 60,000 injury. RIGHT, direction) in Applications Always provide adequate combustion and ventilation air specified in section Combustion Air and Vent Pipe Systems these instructions to furnace. Combustion products must be discharged outdoors. Connect as of this furnace to an approved vent system only, as specified in the Combustion Air and Vent Piping sections of these instructions. Never test for gas leaks with an open flame. available soap solution made leaks to check all connections, section of these instructions. Always install furnace specifically as specified to operate within Use a commercially for the detection of in the GAS PIPING the furnace's intended a duct system which has an external static the allowable range, as specified in the SET RISE section of these instructions and furnace plate. furnace, the return the furnace casing the furnace. furnace supply ducts carry the space containing air the air shall also be handled by duct(s) sealed to and terminating outside the space containing may be used installation containing condition Gas-Fired, in model to 120,000 tubes are Install this furnace only in a location and position as specified in LOCATION and INSTALLATION sections of these instructions. for construction and operation is permanently complies installed the furnace. This prevents as created by the circulating flame rollout structure. model must not exceed 80°F (27°C) air limits may affect reliability and controls. in Fig. down to setback garage section must be of these heat provided that the with: with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces. The minimum operation a night in DOWNFLOW, HORIZONTAL LEFT (supply-air discharge as shown • The furnace this caution tile, For at final site. return-air A gas-fired furnace for installation in a residential installed as specified in the Hazardous Locations instructions. HAZARD to follow motors required when used or HORIZONTAL furnace Failure completed continuous temperature these return This furnace is shipped connected for UPFLOW The CUT for When a furnace is installed so that circulated by the furnace to areas outside HAZARD to follow building is designed temperature of 60°F (16°C) db or intermittent 55°F (13°C)db such as when used with rating Failure gas. to combustibles. manufacturer's coil assembly or when the manufacturer's coil box is used. The design of the 58MTB furnace is not CSA certified for installation in mobile homes, recreational vehicles, or outdoors. This furnace is suitable for installation in a structure rise range with pressure within TEMPERATURE ENVIRONMENTAL clearances SHALL NOT be installed directly on carpeting, combustible material other than wood flooring. applications section. In Canada, information. editions for use with propane downflow installations, a factory accessory floor base must be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on the property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The building codes, the current editions Code (NFGC) NFPA 54/ANSI Z223.1 furnace See Fig. 3 for required with special to vent sizing and material, gas input rise, unit leveling, and unit sizing. Follow all safety codes. and work gloves. Have AGA and CGA) design-certified (see furnace rating plate) and for sizes Btuh. and/or drawing a negative pressure air blower, causing combustion products a into the • The furnace is controlled by a thermostat. It may not be "hot wired" to provide heat continuously to the structure without thermostatic control. • Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components. • The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions. Step • The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value. • The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed. This furnace is shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment. Installer Packet includes: Installation, Startup, and Operating Instructions Service and Maintenance Instructions User's Information Manual Warranty Certificate Quantity 1 Collector Box or condensate trap extension tube 1 Inducer housing drain tube 1 1/2-in CPVC street elbow 2 Drain tube coupling 1 Drain tube coupling grommet 1 Condensate 3 trap hole filler plug Vent and combustion-air Combustion-air intake hole filler plug intake pipe perforated disk assembly 2 1 Gas line grommet 1 Vent pipe grommet 1 Combustion-air 1 pipe grommet Power entry hole filler plug Vent Pipe Extension *ONLY supplied 2 1" with some furnaces. The furnace shall be installed so that the electrical components are protected from water. For accessory installation detail, refer to the accessory installation instruction. NOTE: AND STANDARDS 1 - Safety • US: National Fuel (;as Code (NFGC) NFPA 54-2006/ANSI Z223.1-2006 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B • CANADA: National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC) CSA B149.1-05 • The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy. Loose Parts Bag includes: Pressure tube extension CODES Follow all national and local codes and standards in addition to these instructions. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction. In the United States and Canada, follow all codes and standards for the following: Remove all shipping materials before operating furnace. Step 2 - General Installation • US: NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001 • A manufactured (Mobile) home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when this standard is not applicable, the Standard for Manufitctured Home Installation (Manufactured Home Sites, Communities, and Set-Upsg, ANSI/NCS A225.1, and/or CAN/CSA-Z240, MH Series Mobile Homes • CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada. C O_ d_c_ c°*G_ _on "t::{ = 0Z o ,o E = = _ g_. "o_ 09 LO "_C'-- OLQ o c_d.-oS X_ CO _ 'i O.-C; "-_ _o_oo._ o _ x cO d 000 ='_ _ _0 -o_.o _EW:g °_o° 09(.0 E _ 0 _oe_< o _ _ 0 -- _ O '-u 0 _ _-0 _CO _$OLO O_ o O_ c '_ 0 05 O'TO _._ o o zn .,E o0o _ _E_Oo__OoO'- %- o:_O0 > m..m_"_-_z- o z: _ _ oli_ cO :_ O, 5 #.#.#mm# _ o_ 090_-- "'T _ '_ O,1 _O' 0 co Er) ,_'_'_om _LLLL E _LLo0 _0oooo_. _ _ C _o O_ 000000 o _- _O00_C_ 1_ _-_000000 '_ o'_u-www_ o _ o _olooooo --__0:0 .,: aJ 000_ I11 k- o Z A05053 Fig. 2 - Dimensional Drawing - In. (mm) NSTALLATION e • • • e e ® e • • This forced air fumace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size furnaces are only approved for altitudes 0 - 7,000 fL (0- Z135m). An accessory kit, supplied by the manufacturer, shah be used to convert to propane gas use or may be required for some natural gas applications. This famace is for indoor installation in a building constructed on site. This furnace may be installed in a manufactured (mobile) home when stated on rating plate and using factory authorized kit.. This furnace may be instated on combustible floodng in alsove or closet at Minimum Inches Clearance To Combustible Construction as described below. This _mace requires a special venting system. Refer to the installation instructions for parts list and method of installation. In the US this furnace is for use with schedule=40 PVC, PVC-DWV, CPVC, or AB,S-DWV pipe, and must not be vented in common with other gas-fired appliances. In Canada, refer to installation instructions for vent materiaN. Construction through which vent/air intake pipes may be installed is maximum 24 inches (610 ram), minimum 3/4 inches (19 mm) thickness (including roofing materials). Cette foumaise _ air puls6 est 6quip6e pour utilisation avec gaz naturem et altitudes comprises entre 0 - 3,050m (0 - 10,000 pi),except6 queles foumaises de 140 taifle sont pour altitudes comprises entre 0 - 2,135m (0 - 7,000pi). Utiiiser une trousse de conversion, foumie par le fabdcent, pour passer au gaz propane ou pour certaines installations au gaz natureL Cette foumaise _ air pulse est pour installation a Fintedeur dans un b_timent construit sur place. Cette foumaise a air puNe peut 6tre install6e dans une maison prCfabdqu6e (maison mobile) si prescrit par la plaque signal6tique et si'l on utilise une trousse specifi6e par le fabricent. C.ette foumaise pout 6tre install6e sur un piancher combustible dans un enfoncement ou un pmacerd en observant les D6gagernent Minimum En Pouces Avec EI6ments De Construction Combustibles. Cette foumaise n6cessite un syst_me d'6vacuation sp6cial. La m6thode d'instaliation et la liste des pi_ces n6cessaires figurent dana les instructions d'installation. Aux Etats-Unis, cette foumaise dolt s'utiliser avec la tuyautede des nomenclatures 40 PVC, PVC-DWV, CPVC, ou ,ABS-DWV et elle ne peut pas _tre ventii6e conjointment avec d'autres appareils & gaz. Au Canada, referer aux instructions d'installation pour lax matedaux a ventiler. Epaisseur de la construction au travers de laquene il est possible de faire passer les tuyaux d'aeration (admission/evacuation): 24 po (610 mm) maximum, 3/4 pc (19mm) minimum (y compds la toiture). For up&3w and downflow applications, furnace must be installed level, or pitched within 1/2" (12.7ram) of level. For a horizontal appllaatiorl, the furnace must be pitched mirlimum 1/4" (6.35mm) to maximum of 1/2" (12.7mm) forward proper drainage. See Installation Manual for IMPORTANT unit support details on horizontal applications. LEVEL 0" ( 0 ) TO for _,. MIN 114" (6.35mm) TO 1/2" (12.7mm) MAX t ¢_L-_-_ Pour des applications de flux ascendant et descendant, la foumaise doit ¢¢e install6e de niveau ou indin6e _ pas plus de 1/2" (12.7mm) du niveau. Pour une applicetion hodzontale, la foumaise dolt &,Ire inclin6e enli'e minimum T UPFLOW 1/4" (6.35mm) et maximum 1/2" (12.7ram) du niveau pour le drainage appropn6. En cas d'installation en position hodzootale, consulter les renseignements mMPORTANTS sur le support dans le manuel d'instaHation. DOWN OR 1/2" (12.7mm)MAX ............ ! F_0RONT_) FLOW HORIZONTAL MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION This furnace is approved for UPFLOW, DOWNFLOW and HORIZONTAL installations. ALL POSiTiONS: Minimum front clearance t 1 140 size furnaces DOWNFLOW POSITIONS: t for service require I inch back For installation on combustible NAHA01101SB, CoilAssembly, or WENC or WTNC. HORIZONTAL 24 inches (610mm). clearance 11oors only when Part No. CAR, to combustible Cette foumaise est approuv_e pour I'installation HORIZONTALE et la circulation d'air VERS LE HAUT et VERS LE BAS. materials. instated on special base No. KGASB0201ALL or CAP, CNPV, CNRV or Coil Casing, Part No. KCAKC, Clearance furnace is permissible jacket, Les _hes and building § Clearance shown O 120 and 140 size only between joists, lines formed studs, require of top and two sides of or framing. is for air inlet and air curet furnaces by intersections de degagement ne change pas avec I'orientation de la gen_rateur d'air chaud. furnace orientation, POSITIONSi Line contact arrows do not change with ends. 1 inch bottom clearance to combustible materials. DEGAGEMENT MNfl_UM EN POUCESAVEC I_LleMENTSDE CONSTRUCTION COMBUSTIBLES POUR TOUS LES POSITIONS: 1- t D@jagement avant minimum de 24 po (610mm ) pour l'entretien. Pour les foumaises de 140 taifle, 1 pc (25mm) d6gagement des mat6riaux requis au-arriere. POUR LA POSITION COURANT 1 Le contact deuxottes batiment. DESCENDANT: n ° KCAKC ou WENC ou ou WTNC. n'est permis qOentre les lignes form6es par les intersec_ons de la chemise de la foumaise, et des solives, des montants du dessus et des ou de la charpente du Vent clearance to combustibles 0". La distance indiqu_e conceme I'extr_mit6 du tuyau d'ardv_e d'air et I'extr_mit_ du tuyau de sortie d'aic Pour les foumaises de 120 et 140 taifie, 1 pc (25mm) d6gagement des materiaux combustibles est requis • US: Section Combustion • CANADA: and Ventilation 9.3 of the NFPA 54/ANSI Air Step 6 - Gas Piping Z223.1-2006, Air for and Ventilation and Air Supply Venting (ACCA) Manual Contractors Association Refrigeration, 2001 Fundamentals HVAC Systems Contractors Association and Equipment Step 5 - Acoustical • US and CANADA: (SMACNA), or Ainerican and Air Conditioning Handbook Chapters Engineers Chapter 34 or 2000 codes. of SMACNA, must be installed flexible not exceed Parts 4, 5, and 6, A, B, E, connectors Glass Duct NFPA 90B as 181 for (?lass I Rigid Air Ducts by a licensed plumber are used, the maximum or gas fitter. length shall 36 in. (914 mm) • When lever type gas shutoffs are used they shall not exceed 36 in. 014 mm). • The use of copper 9 and 16. Lining and Fibrous current edition tested by UL Standard Testing chapters 5, 6, 7, and 8 and CAN/CSA-B149.1-05 • This product • When D, Sheet Metal and Air Conditioning National plumbing • CANADA: and Gas Pipe Pressure Z223.1-2006; In the state of Massachusetts: Air Conditioning of Heating, (ASHRAE) 0 (pc) D_Jagement d'_vent aveccombustibles. G, and H. for Appliances Step 4 - Duct Systems • US and CANADA: • US: NFPA 54/ANSI national Part 8 of the CAN/CSA-B149.1-05, Systems Clearancein inches D6gagement(pc). au-dessous. Step 3 - Combustion Society est Pour Ilnstaflation sur le plancher cembustible seulement quand on utilise la base sp_ciale, piece n° KGASB0201ALL ou NAHA01101SB, I'ensemble serpentin, pi_:e n ° CAR, CAP, CNPV, CNRV, le carter de serpentin, piece POUR LA POSmON HORIZONTALE: § combustibles tubing for gas piping is not approved by the state of Massachusetts. Step 7 - Electrical • US: National • CANADA: Electrical Canadian Connections (?ode (NEC) Electrical ANSI/NFPA (?ode CSA (722.1 70-2008 INTRODUCTION Step 8 - Venting • US: NFPA 54/ANSI Z223.1-2006 Chapters 12 and 13. • CANADA: CAN/CSA-B149.1-05 Part 8 and Appendix C MAX 80°F (27 ° C) The model 58MTB 4-way multipoise, Gas-Fired, Category IV, condensing furnace is available in model sizes ranging from input capacity of 60,000 to 120,000 Btuh as a direct vent (2-pipe) application as well as a non-direct vent (1-pipe) application. APPLICATIONS MINOR PROPERTY DAMAGE FRONT Failure to follow this caution may result in minor property damage. MIN 60°F (16o C) Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling. Step 1 - General Fig. 4 - Return-Air Temperature A05004 ELECTROSTATIC PRECAUTIONS DISCHARGE (ESD) PROCEDURE Some assembly and modifications are required for furnaces installed in any of the 4 applications shown in Fig. 1. All drain and pressure tubes are connected as shown in Fig. 6. See appropriate application instructions for these procedures. Step 2 - Upflow Applications In an upflow application, the blower is located below the burner section, and conditioned air is discharged upwards. CONDENSATE TRAP LOCATION (FACTORY-SHIPPED UNIT Failure DAMAGE to follow HAZARD this caution may result in damage to unit components. Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential. 1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY'S ELECTROSTATIC CHARGE TO GROUND. 2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in hand during grounding will be discharged. 3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body (moving or shuffling feet, touching ungrounded objects, etc.). 4. If you touch ungrounded objects, firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires. 5. Use this procedure for installed and uninstalled (ungrounded) furnaces. 6. Before removing a new control from its container, discharge your body's electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers before touching ungrounded objects. 7. An ESD service kit (available from commercial may also be used to prevent ESD damage. sources) ORIENTATION) The condensate trap is factory installed in the blower shelf and factory connected for UPFLOW applications. A factory-supplied tube is used to extend the condensate trap drain connection to the desired furnace side for field drain attachment. See Condensate Trap Tubing (Factory-Shipped Orientation) section for drain tube extension details. (See Fig. 5.) CONDENSATE TRAP TUBING (FACTORY-SHIPPED ORIENTATION) NOTE: See Fig.6 or tube routing label on main furnace door to confirm location of these tubes. 1. Collector Box Drain, Inducer Housing Drain, Relief Port, and Pressure Switch Tubes These tubes should be factory attached to condensate trap and pressure switch ready for use in upflow applications. These robes can be identified by their connection location and also by a color label on each tube. These tubes are identified as follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green label), and pressure switch tube (pink label). 2. Condensate Trap Drain Tube The condensate trap drain connection must be extended for field attachment by doing the following: f. Determine location of field drain connection. (See Fig. 2 or 6) NOTE: If internal filter or side Filter/Media Cabinet is used, drain tube should be located to opposite side of casing from return duct attachment to assist in filter removal. g. Remove and discard casing drain hole plug button from desired side. h. Install drain tube coupling grommet (factory-supplied in loose parts bag) in selected casing hole. i. Slide drain tube coupling (factory-supplied in loose parts bag) through grommet ensuring long end of coupling faces blower. BLOWER SRELF ACE ,--"CONDENSATE ,---CONDENSATE \ / TRAP /TRAP(INSIDE) "k \ / RNACE DOOR -- FURNACE -7 / FURNACE SIDE S,Dy 4 102 146mm T 26 FIELD ALTERNATE DRAIN TUBE LOCATION CONDENSATETRAP-DRAINTUBE LOCATION 261/4 667 mm 3/4 19mm 38 mm SIDE VIEW END VIEW FRONT VIEW FRONT VIEW HORIZONTAL APPLICATIONS DOWNFLOW AND ALTERNATE EXTERNAL UPFLOW APPLICATIONS UPFLOW APPLICATIONS 667mm 146mm FIELD DRAIN CONN 1 /2 CONN DRAIN /4 _4 SLOT oO SO2fW -7 / 1/40D COLLECTOR BOX TO TRAP RELIEF PORT / 11/2 3Smm 1/2OD INDUCER HOUSING DRAIN CONNECTION 5/80D COLLECTOR BOX DRAIN CONNECTION __!/4 71/8 181 45 mm SCREW HOLE FOR UPFLOW OR DOWNFLOW APPLICATIONS (OPTIONAL) GUIDES 1/2-1N. PVC OR CPVC (WHEN USED) FRONT VIEW SIDE VIEW A93026 Fig. 5 - Condensate j. Cement 2 factory-supplied 1/2-in. (13 mm) street CPVC elbows to the rigid drain tube connection on the condensate trap. (See Fig. 6.) These elbows must be cemented together and cemented to condensate trap drain connection. NOTE: Failure and prevent to use CPVC elbows may allow drain to kink draining. k. Connect supplied larger diameter drain tube and clamp (factory in loose parts bag) to condensate trap and clamp securely. 1. Route tube to coupling In. Attach tube to coupling CONDENSATE UPFLOW NOTE: and cut to appropriate location Casing hole filler when condensate products being equipment room. 4. Install trap If the alternate left-hand is the left-hand side of casing Tubing (Alternate Upflow Orientation) attachment. To relocate condensate trap location side is used, port tubes must be See Condensate Trap section for tubing to the left hand side, the following: 1. Remove 3 tubes connected 2. Remove trap from inward and rotating 3. Install casing blower trap. hole parts bag) into blower filler shelf to condensate shelf cap (factory-supplied hole where this warning could HAZARD result in personal injury cap must be installed in blower shelf hole trap is relocated to prevent combustion drawn in from appliances in the condensate trap 5. Fill unused condensate caps (factory-supplied CONDENSATE UPFLOW NOTE: confirm into left-hand side casing tabs in loose trap was removed. NOTE: between trap casing holes with plastic in loose parts bag). TRAP TUBING See Fig.7 or tube routing location of these tubes. filler (ALTERNATE label on main furnace door to Box Drain Tube Connect collector condensate trap. pushing hole by hole and ORIENTATION) 1. Collector trap. by gently POISONING inserting tube connection stubs through casing rotating until tabs snap into locking position. (See Fig. 2 and 7.) the factory-connected drain and relief disconnected and modified for attachment. perform Failure to follow or death. (ALTERNATE for the condensate MONOXIDE length. and clamp securely. LOCATION CARBON ORIENTATION) An alternate of casing. TRAP Trap On 17-1/2 corrugated box drain tube (blue label) to in. (445 mm) wide furnaces ONLY, cut tube sections to prevent kinks from occurring. PLUG PLUG © CAP CAP COLLECTOR COLLECTOR BOX DRAIN TUBE (BLUE &WHITE STRIPED) DRAIN TUBE (BLUE &WHITE STRIPED) COLLECTOR TUBE (PINK) COLLECTOR BOX TUBE (PINK) N COLLECTOR BOX -TUBE (GREEN) COLLECTOR BOX TUBE (GREEN) COLLECTOR INDUCER (MOLDED) DRAIN TUBE (BEHIND COLLECTOR BOX DRAIN TUBE) BOX -- DRAIN TUBE (BLUE) O O COLLECTOR DRAIN TUBE (BLUE) CONDENSATETRAP .,.-,.*,,,.b__ INDUCER J HOUSING DRAIN TUBE (VIOLET) FACTORY-SUPPLIED DRAIN TUBE COUPLING (LEFT DRAIN OPTION) A01031 Fig. 7 - Alternate FIELD-INSTALLED FACTORY-SUPPLIED DRAIN TUBE PRESSURE FIE LD-INSTALLED FACTORY-SUPPLIED %-IN. (13 mm) CPVC STREET ELBOWS (2) FOR LEFT DRAIN OPTION FIELD- IN STALLED FACTORY-SUPPLIED DRAIN TUBE COUPLING (RIGHT DRAIN OPTION) 6 - Factory-Shipped (Shown with Blower Upflow Tube Access Panel Housing Drain Removed) Tube a. Remove and discard LOWER (molded) inducer housing drain tube which was previously connected condensate trap. b. Use inducer housing drain extension tube (violet condensate to d. Clamp 3. Relief tube to prevent length, cut, and connect any condensate label Upper Inducer tube. relief port tube (green condensate b. Extend tube (factory-supplied c. Determine CONDENSATE to trap. this tube (if required) diameter label) appropriate TRAP length, FIELD by splicing in loose parts bag). tube. to Condensate Housing Drain Connection Refer to Condensate Drain recommendations and procedures. DRAIN ATTACHMENT Refer Step 3 - Downflow Drain section for is a NOTE: See Fig.6 or 7 or tube routing label on main furnace door to check for proper connections. CONDENSATE TRAP FREEZE PROTECTION to small cut, and connect CONNECTIONS Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped. leakage. Port Tube a. Connect DRAIN factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged. NOTE: See Fig.6 or 7 or tube routing label on main furnace door to check for proper connections. trap. appropriate (UNUSED) Upper Collector Box Drain Connection Attached to the UPPER collector box drain connection and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the c. Determine TUBING NOTE: See Fig.6 or 7 or tube routing label on main furnace door to check for proper connections. UPPER COLLECTOR BOX AND INDUCER Configuration HOUSING 2. Inducer SWITCH and Trap Location The LOWER collector box pressure tube (pink label) is factory connected to the High Pressure Switch and should not require any modification. A01030 Fig. Upflow Configuration recommendations Protection section for Applications In a downflow furnace application, the blower is located above the burner section, and conditioned air is discharged downwards. CONDENSATE TRAP LOCATION and procedures. The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2, 8, or 9. 10 CC DRAIN TUBE (BLUE) COLLECTOR TUBE (GREEN) O COLLECTOR EXTENSION TUBE BOX DRAIN TUBE (BLUE) O BOX COLLECTOR TUBE (PINK) TUBE (PINK) )R BOX TUBE (GREEN) )R BOX EXTENSION TUBE DRAIN TUBE (BLUE & WHITE STRIPED) BOX DRAIN TUBE (BLUE & WHITE STRIPED) COLLECTOR BOX_ EXTENSION TUBE )R BOX EXTENSION TUBE INDUCER HOUSING DRAIN TUBE (VIOLET) TRAP © © TRAP )R BOX EXTENSION DRAINTUBE INDUCER HOUSING DRAIN TUBE (VIOLET) 'DRAIN TUBE 8 COUPLING "_ A01023 Fig. 8 - Downflow (Left-Hand To relocate location, condensate perform 1. Remove Trap trap A01024 Configuration Fig. 9 - Downflow Installation) from the (Right-Hand blower shelf 3 tubes connected casing to condensate blower trap. shelf trap. by gently hole filler cap from casing pushing tabs casing hole filler cap into blower Trap Configuration Installation) (3.) Condensate Trap Located on Left Side of Casing hole. a. Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut. (See Fig. 2, 8, or 9.) 4. Install Tube b. Install removed clamp and plug into UPPER collector box drain tube (blue label) which was connected to condensate trap. c. Connect LOWER collector box drain connection to condensate trap. to desired the following: 2. Remove trap from inward and rotating 3. Remove Tube shelf hole where trap was removed. b. Clamp tube to prevent any condensate leakage. (4.) Condensate Trap Located on Right Side of Casing CARBON MONOXIDE POISONING could a. Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue and white striped label) which was previously plugged. b. Connect larger diameter drain tube (factory-supplied in loose parts bag) to drain tube coupling, extending collector box drain tube for connection to condensate trap. c. Route extended collector box drain tube directly from collector box drain to condensate trap as shown in Fig. 9. HAZARD Failure to follow or death. this warning result in personal injury Casing hole filler when condensate products being equipment room. cap must be installed in blower shelf hole trap is relocated to prevent combustion drawn in from appliances in the 5. Install condensate trap into desired casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position. CONDENSATE TRAP TUBING d. Determine appropriate length and cut. e. Connect to condensate trap. f. Clamp tube to prevent any condensate leakage. NOTE: See Fig. 8 or 9 or robe routing label on main fi_rnace door to check for proper connections. Relocate robes as described below. 2. Inducer Housing Drain Tube a. Remove factory-installed cap and clamp from LOWER inducer housing drain connection. 1. Collector Box Drain Tube b. Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to condensate trap. a. Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label). c. Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed. 11 d. Use inducer housing drain tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap. Step 4 - Horizontal Applications CONDENSATE (1.) Condensate Trap Located on Left Side of Casing a. Determine appropriate length and cut. The c. Clamp tube to prevent any condensate leakage. (2.) Condensate Trap Located on Right Side of Casing 4. Install Drain NOTE: check section by POISONING this warning to desired trap. gently pushing tabs could HAZARD result in personal trap into left-hand condensate TRAP trap casing in loose side casing holes hole by hole and with plastic filler parts bag). TUBING See Fig. 10 or tube routing for proper injury cap must be installed in blower shelf hole trap is relocated to prevent combustion drawn in from appliances in the condensate label on main furnace door to connections. 1. Collector Box Drain a. Install Tube drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap. b. Connect large diameter drain tube and clamp (factory-supplied in loose parts bag) to drain tube coupling, extending collector box drain tube. c. Route extended tube (blue label) and cut to appropriate length. d. Clamp 2. Inducer tube to prevent Housing a. Remove Drain and discard b. Use inducer housing and factory-supplied for LOWER inducer condensate trap. and procedures. c. Determine d. Clamp any condensate LOWER 12 appropriate trap leakage. (molded) inducer was previously connected to drain extension tube (violet label in loose parts bag) to connect housing tube to prevent to condensate Tube housing drain tube which condensate trap. PROTECTION Protection MONOXIDE CONDENSATE tube to relief port connection. Condensate shelf to condensate shelf application trap. caps (factory-supplied 4. Extend collector box pressure tube (pink label) which was previously connected to High Pressure Switch by splicing to remaining small diameter tube (factory-supplied in loose parts bag). 5. Route this extended robe (pink label) to condensate trap relief port connection. 6. Determine appropriate length, cut, and connect tube. to the factory-installed selected the blower blower and rotating 5. Fill unused 3. Connect collector box pressure tube (green label) to High Pressure Switch connection labeled COLLECTOR BOX. recommendations from in inserting tube connection stubs through casing rotating until tabs snap into locking position. 1. Disconnect collector box pressure tube (pink label) attached to High Pressure Switch. 2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube (factory-supplied in loose parts bag). Refer trap Casing hole filler when condensate products being equipment room. TUBING FREEZE 3 tubes connected Failure to follow or death. recommendations NOTE: See Fig. 8 or 9 or robe routing label on main furnace door to check for proper connections. TRAP 1. Remove 2. Remove CARBON One collector box pressure tube (pink label) is factory connected to the High Pressure Switch for use when furnace is installed in upflow applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the High Pressure Switch in DOWNFLOW or HORIZONTAL RIGHT applications CONDENSATE from 3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed. d. Clamp tube to prevent any condensate leakage. 3. Relief Port Tube Refer to Pressure Switch Tubing section for connection procedure. CONDENSATE TRAP FIELD DRAIN ATTACHMENT 7. Clamp must be removed shelf location and relocated as shown in Fig. 2 or 10. inward c. Connect tube to condensate trap. for trap LOCATION To relocate condensate trap from location, perform the following: a. Route inducer housing drain tube (violet label) directly from inducer housing to condensate trap as shown in Fig. 9. b. Determine appropriate length and cut. section TRAP condensate blower location b. Connect tube to condensate trap. Drain Discharge) In a horizontal left furnace application, the blower is located to the right of the burner section, and conditioned air is discharged to the left. e. Connect inducer housing drain connection to condensate trap. Refer to Condensate and procedures. PRESSURE SWITCH Left (Supply-Air drain length, connection to the cut, and connect any condensate leakage. tube. PLUG -- AUXILIARY "J" BOX COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) _t I CAP _ O O CONDENSATE TRAP COLLECTC BOX EXTENSION DRAIN TUBE COLLECTOR BOX UCER HOUSING DRAIN TUBE (VIOLET) \ \\ \_'\ COLLECTOR BOX DRAIN TUBE (BLUE) EXTE.S,O. O E DRAINTUBE COUPLING _ %. COLLECTOR BOX TUBE (PINK) RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR 040,060, AND 080 HEATING INPUT FURNACES A01029 Fig. 10 - Horizontal Left Tube 3. Relief Port Tube 4. Determine appropriate length, cut, and reconnect tube to High Pressure Switch connection labeled COLLECTOR BOX. a. Extend collector box tube (green label) which was previously connected to the condensate trap by splicing to small diameter tube (factory-supplied in loose parts bag). b. Route extended collector box pressure tube to relief port connection on the condensate trap. c. Determine appropriate length, cut, and connect tube. CONDENSATE for recommendations TRAP FREEZE PROTECTION Refer to Condensate Drain Protection recommendations and procedures. CONSTRUCT A WORKING PLATFORM section for Construct working platform where all required furnace clearances are met. (See Fig. 3 and 11 or 12.) d. Clamp tube to prevent any condensate leakage. CONDENSATE TRAP FIELD DRAIN ATTACHMENTS Refer to Condensate Drain section procedures. PRESSURE SWITCH TUBING Configuration and UNIT MAY NOT OPERATE Failure to follow unit operation. The LOWER collector box pressure tube (pink label) is factory connected to the High Pressure Switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended, rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications for 060 and 080 heating input furnaces. NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections. Modify tube as described below: this caution may result in intermittent The condensate trap MUST be installed below furnace. See Fig. 5 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain. NOTE: Combustion-air and vent pipes are restricted minimum length of 5 ft. (2 M)(See Table 13.) to a NOTE: A 12-in. (305 mm) minimum offset pipe section is recommended with short (5 to 8 ft or 2 to 3 M)) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 11, 12 or 43.) 1. Disconnect collector box pressure tube (pink label) attached to High Pressure Switch. 2. Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in item 1. 3. Route extended tube: Step 5 - Horizontal Applications Right (Supply-Air Discharge) In a horizontal right furnace application, the blower is located to the left of the burner section, and conditioned air is discharged to the right. a. Behind inducer housing. b. Between blower shelf and inducer housing. 13 COMBUSTION INTAKE A 12-1N. (305 mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT / 1.5 TO 2.4 M) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE. 30" (762 mm)MIN (146 mm) MAN1 SHUTOFF GAS VALVE ACCESS OPENING FOR TRAP DRAIN SEDIMENT TRAP CONDENSATE TRAP NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS. A93031 Fig. 11 - Attic MINOR Location this caution may result in minor Local codes may require a drain pan under condensate trap when a condensing furnace application or over a finished ceiling. The to opposite Connection Platform PROPERTY DAMAGE Failure to follow damage. NOTE: and Working auxiliary junction box (J-Box) MUST CONDENSATE TRAP Vent CARBON MONOXIDE property blower location trap must shelf location and relocated as shown in Fig. 2 or 13. To relocate condensate trap from location, perform the following: 1. Remove 2. Remove inward 3 tubes trap connected from and rotating blower the in the factory-installed selected blower to condensate shelf HAZARD result in personal injury cap must be installed in blower shelf hole trap is relocated to prevent combustion drawn in from appliances in the until CONDENSATE NOTE: to desired check for proper a. Remove tabs in loose TRAP b. Install 3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed. holes with plastic filler parts bag). TUBING label on main furnace door to connections. Box Drain Tube: factory-installed box drain tube (blue trap. position. trap casing See Fig. 13 or tube routing 1. Collector trap. pushing tabs snap into locking condensate caps (factory-supplied application shelf by gently could 4. Install condensate trap into right-hand side casing hole by inserting tube connection stubs through casing hole and rotating from POISONING be relocated 13.) See Electrical LOCATION be removed Applications this warning Casing hole filler when condensate products being equipment room. 5. Fill unused The condensate (2-Pipe) Failure to follow or death. entire furnace and is used in an attic side of furnace casing. (See Fig. section for J-Box relocation. for Direct removed clamp plug from LOWER and white striped and plug into UPPER box drain tube (blue label) which connected to condensate trap. collector label). collector was previously c. Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut. d. Clamp 14 tube to prevent any condensate leakage. A 3-1N.(76mm) MINIMUM CLEARANCE TO COMBUSTION-AIR INTAKE IS REQUIRED. COMBUSTION INTAKE A 12-IN. (305mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT / 1.5 TO 2.4M) VENT TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE. 30-1N.(762mm) WORKAREA MIN IN. (146mm) MAN[ SHUTOFF GAS VALVE ACCESS OPENING FOR TRAP DRAIN SEDIMENT TRAP CONDENSATE TRAP NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS. A96184 Fig. 12 - Attic Location and Working 2. Inducer Housing a. Remove Drain Tube: factory-installed inducer housing Platform for Non-Direct Vent (1-pipe) Applications NOTE: check cap and clamp from LOWER Relocate drain connection. b. Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to condensate trap. condensate f. Clamp 3. Connect Pressure 4. Use length, cut, and connect tube to 3. Relief Port Tube: Refer to Pressure any condensate Tubing section leakage. Refer to 6. Clamp TRAP Condensate FIELD Drain DRAIN section ATTACHMENT for CONDENSATE recommendations Refer and procedures. PRESSURE to recommendations SWITCH TUBING CONSTRUCT One collector box pressure tube (pink label) is factory connected to the High Pressure Switch for use when furnace is installed in UPFLOW applications. used for the condensate splicing to small in loose parts bag). smaller diameter (pink label) This tube MUST be disconnected and trap relief port tube. The other collector applications. 15 diameter trap relief TRAP Condensate to High BOX. in box pressure tube connected to High tube (pink label) to port connection. appropriate tube to relief tube tube (factory-supplied length, cut, and connect tube. port connection. FREEZE Drain PROTECTION Protection section for and procedures. A WORKING PLATFORM Construct working platform where all required are met. (See Fig. 3 and 11 or 12.) box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the High Pressure Switch in DOWNFLOW or HORIZONTAL RIGHT remaining 5. Determine for connection procedure. CONDENSATE tube collector box pressure tube (green label) Switch connection labeled COLLECTOR condensate Switch below. loose parts bag) to extend collector (pink label) which was previously Pressure Switch. Route this extended trap. tube to prevent as described connection by (factory-supplied trap. appropriate door to 2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port d. Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate tubes label on main furnace connections. 1. Disconnect collector box pressure attached to High Pressure Switch. c. Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed. e. Determine See Fig. 12 or tube routing for proper furnace clearances COLLECTOR BOX DRAIN TUBE (BLUE) COLLECTOR BOX TU BE (GREEN) BOX EXTENSION TUBE PLUG COLLECTOR BOXTUBE (PINK) "J" BOX RELOCATED HERE TRAP COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) INDUCER HOUSING DRAINTUBE(VIOLET) COLLECTOR BOX EXTENSION TUBE A01028 Fig. 13 - Horizontal Right Tube Configuration shown on the furnace NOTE: Failure to follow unit operation. this furnace caution may result in intermittent mm) Combustion-air are restricted NOTE: pipe (when to a minimum A 12-in. (305 length mm) applicable) minimum offset pipe furnace, furnace wood flooring • be located directly so combustion-air where meet specifications • be attached Refer to the center are protected electric of the distribution air must The ducts also be terminate power system secondary lengths . plate. exchangers. by ducts the space condition air the sealed to containing will not occur result in fire, property L_ as possible. for servicing FRONT as close Refer to Air I_"MAX (6to13mm) UPFLOW OR DOWNFLOW with ample space (6 to ensure supply ducts carry the space containing handled outside F and be located Ducts section. • be provided heat 1/4-in. and gas supplies rating system pitch forward other than 13. on the furnace so that Do not install furnace on its back. (See Fig. 15.) Safety control operation will be adversely affected. Never connect return-air ducts to back of furnace. from water. material and vent pipe maximum to an air distribution return casing. CONSIDERATIONS). to Table available from Failure to follow this warning could damage, personal injury, or death. on any combustible (refer to SAFETY are not exceeded. • be located components applications (13 mm) maximum drainage furnace (13 mm) for proper FIRE, INJURY OR DEATH HAZARD must so the electrical install 1/2-in. is Step 1 - General • not be installed horizontal label. This from LOCATION • be installed within the furnace to ensure a negative pressure within equipment room or space. the vent pipe. (See Fig. 11, 12 or 43.) This furnace For to 1/2-in. condensate applications forward When a furnace is installed so that circulated by the furnace to areas outside 13.) section recommended with short (5 to 8 ft or 2 to 3 M) vent systems. recommendation is to reduce excessive condensate droplets exiting operation. to combustibles (See Fig. 14.) and vent pipe(s) of 5 ft. (2 M). (See Table or pitched minimum proper The condensate trap MUST be installed below furnace. See Fig. 5 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain. NOTE: For upflow/downflow it is level UNIT MAY NOT OPERATE clearance HORIZONTAL and cleaning. A02146 Always comply with minimum fire protection clearances Fig. 14 - Proper Condensate 16 Drainage UNIT DAMAGE This gas fllmace HAZARD may be used for construction heat provided that: -The furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/ or drawing combustion products into the structure. BACK -The furnace is controlled by a thermostat. It may not be "hot wired" to provide heat continuously to the structure without thermostatic control. -Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components. A93043 Fig. 15 - Prohibit Step 3 - Hazardous -The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation -The air temperature furnace rating plate, nameplate value. per our installation Improper location or explosion. rise is within the rated rise range on the and the firing rate has been set to the -The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed. NSCNGPIC. - After construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions. Step 4 DIRECT Furnace provisions DAMAGE Failure to follow unit damage. protection could result in fire (See Fig. 17.) Furnace Location and Application VENT (2-PIPE) APPLICATION may be located for dilution in a confined or ventilation space without special air. HAZARD this caution may result in minor property If this furnace is installed in an unconditioned space the ambient temperatures may be 32°F (0°C)or lower, protection measures must be taken. (See Fig. 16.) Step 2 - Furnace Equipment INJURY OR DEATH HAZARD or inadequate When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 in. (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with current edition of the NFGC or -The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy. UNIT on Back Locations FIRE, EXPLOSION, instructions. Installation Location Relative or where freeze to Cooling 32 ° F/0 ° C MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED The cooling coil must be installed parallel with or on downstream side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with a means to prevent operation of either unit unless the damper is in full-heat or full-cool position. /\ / A07911 Fig. 16 - Freeze 17 Protection If air is exposed to the following substances, used for combustion air, and outdoor air for combustion: • Permanent wave • Chlorinated • Chlorine swimming chemicals salts or chemicals type refrigerants • Cleaning solvents • Printing • Cements NON-DIRECT UNIT VENT DAMAGE not install atmosphere. requirements Refer section this furnace in Make sure are met. to the AIR FOR all may a result corrosive combustion COMBUSTION in or AND COMBUSTION circulating CARBON air for adequate combustion, AND and dilution air must be provided in accordance with: • U.S. Installations: Section 9.5 of the NFPA 54/ANSI Z223.1-2006, applicable Air for Combustion provisions • Canadian of the local building Installations: Venting Systems authorities having and Ventilation and codes. for Appliances burner and all jurisdiction. • Spaces POISONING this warning could having CORROSION Failure to follow component life. this warning Outdoor HAZARD could result cleaning products. in reduced solvents, The following types of furnace installations OUTDOOR AIR for combustion due to chemical • Commercial • Buildings furnace • Laundry • Hobby • Chemical salts, 2. air storage draft HAZARD result in personal injury AIR, STANDARD METHOD. or Air Method Fig. 18 illustrates OPENINGS, one how to provide TWO OUTDOOR inlet and one outlet combustion and air openings to the outdoors. a. One opening MUST commence within 12 in.(305 of the ceiling and the second opening MUST commence within 12 in. (305 mm) of the floor. may require exposures: b. Size openings and ducts per Fig. 18 and Table mm) 1. c. TWO HORIZONTAL DUCTS require 1 square inch of free area per 2,000 Btt h (1,100 mm 2 /kW) of combined input for all gas appliances in the space per Fig. 18 and Table 1. pools rooms or craft rooms, Combustion ventilation buildings with indoor from Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements could corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, fresheners, and other household and at least 50 cubic feet per 1,000 Btuh may use the INDOOR COMBUSTION KNOWN AIR INFILTRATION FURNACE area The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space. • Spaces having less than 50 cubic feet per 1,000 Btuh require the OUTDOOR COMBUSTION AIR METHOD. Part 8 of the CAN/CSA-B149.1-05, and Air Supply the for fuel negative must be duct to The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount of make-up air is available. VENTILATION ventilation, from MONOXIDE Failure to follow or death. VENTILATION Provisions dryers intermittent contaminated and for clothes materials All fuel-burning equipment must be supplied with air combustion. Sufficient air must be provided to avoid pressure in the equipment room or space. A positive seal made between the furnace cabinet and the return-air APPLICATION for details. AIR FOR acid washing prevent pulling air safeguard opening. caution etc. acid fabric softeners • Masonry HAZARD Failure to follow unit operation. Do (1-PIPE) varnishes, and glues • Antistatic A93044 (such as perchloroethylene) inks, paint removers, • Hydrochloric in a Garage pool chemicals tetrachloride • Halogen Fig. 17 - Installation and cleaners based • Carbon 18-1N. (457.2 mm) MINIMUM TOBURNERS solutions waxes • Water softening • De-icing it should not be may be required and areas 18 Table 1- FURNACE INPUT (BTUH) Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS (1 SQ. INJ2,000 BTUH) (1,100SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/K3/V) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW) Free Area of Round Duct Free Area of Opening Round Duct Free Area of Opening Round Duct Opening and Duct Dia. and Duct Dia. and Duct Dia. Sq. In. (mm) In. (mm) Sq. In (mm) In. (mm) Sq. In (mm) In. (mm) 44,000 22 (14194) 6 (152) 14.7 (9494) 5 (127) 11 (7097) 4 (102) 66,000 33 (21290) 7 (178) 22 (14193) 6 (152) 16.5 (10645) 5 (127) 88,000 110,000 44 (28387) 55 (35484) 8 (203) 9 (229) 29.3 (18903) 36.7 (23677) 7 (178) 7 (178) 22 (14193) 27.5 (17741) 6 (152) 6 (152) 132,000 66 (42581) 10 (254) 44 (28387) 8 (203) 33 (21290) 7 (198) 154,000 77 (49677) 10 (254) 51.3 (33096) 9 (229) 38.5 (24838) 8 (203) EXAMPLE: Determining FURNACE Free Area WATER HEATER TOTAL INPUT 110,000 + 30,000 = (140,000 divided by 4,000) = 66,000 + 40,000 = (106,000 divided by 3,000) = 88,000 + 30,000 = (118,000 divided by 2,000) = Table 2 - Minimum Space Volumes for 100% Combustion, ! 40 ! 35.3 Sq. In. for a Single Duct or Opening 59.0 Sq. In. for each of two Horizontal Ventilation OTHER THAN FAN-ASSISTED TOTAL (1,000'S BTUH GAS INPUT RATE) 30 35.0 Sq. In. for each two Vertical Ducts or Openings and Dilution Air from Ducts Outdoors FAN-ASSISTED TOTAL (1,000'S BTUH GAS INPUT RATE) 50 44 ACH ! 66 ! 88 Space Volume Ft3 (M 3) ! 110 ! 132 ! 154 0.60 1,050 (29.7) 1,400 (39.6) 1,750 (49.5) 1,100 (31.1) 1,650 (46.7) 2,200 (62.2) 2,750 (77.8) 3,300 (93.4) 3,850 (109.0) 0.50 1,260 (35.6) 1,680 (47.5) 2,100 (59.4) 1,320 (37.3) 1,980 (56.0) 2,640 (74.7) 3,300 (93.4) 3,960 (112.1) 4,620 (130.8) 0.40 1,575 (44.5) 2,100 (59.4) 2,625 (74.3) 1,650 (46.7) 2,475 (70.0) 3,300 (93.4) 4,125 (116.8) 4,950 (140.1) 5,775 (163.5) 0.30 2,100 (59.4) 2,800 (79.2) 3,500 (99.1) 2,200 (62.2) 3,300 (93.4) 4,400 (124.5) 5,500 (155.7) 6,600 (186.8) 7,700 (218.0) 0.20 3,150 (89.1) 4,200 (118.9) 5,250 (148.6) 3,300 (93.4) 4,950 (140.1) 6,600 (186.8) 8,250 (233.6) 9,900 (280.3) 11,550 (327.0) O.10 6,300 (178.3) 8,400 (237.8) 10,500 (297.3) 6,600 (186.8) 9,900 (280.3) 13,200 (373.7) 16,500 (467.2) 19,800 (560.6) 23,100 (654.1) 0.00 NP NP NP NP NP NP NP NP NP Indoor d. TWO OPENINGS OR VERTICAL DUCTS require 1 square inch of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Fig. 18 and Table 1. 3. ONE OUTDOOR OPENING requires: The Standard 1 and 13. 2. The POISONING Failure to supply outdoor air via grilles death and/or personal injury. Rate Methods and rate is not known 1. Less than 0.40 ACH 2. Equal to or greater Infiltration minimum to be less than 0.40 per hour (ACH). The Known Air Infiltration Rate infiltration rate is known to be: through a vertical or horizontal duct to or spaces (crawl or attic) that freely with the outdoors. MONOXIDE in the space air infiltration air changes back and 6 in. (152 mm) from the front. The opening shall directly communicate with the outdoors or shall CARBON & AGA Method: installed in the space. The opening shall commence within 12 in. (305 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and communicate the outdoors communicate NFPA 1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas appliances b. Not less than the sum of the areas of all vent connectors Air© and Known-Air-Infiltration Indoor combustion air is permitted for combustion, ventilation, and dilution, if the Standard or Known-Air-Infiltration Rate Method is used. a. 1 square inch of free area per 3,000 Btuh (734 mm2/kW) for combined input of all gas appliances in the space per Table Combustion Standard Method shall be used, if the and than 0.10 ACH rates greater than 0.60 ACH shall not be used. The required volume of the space varies with the number of ACH and shall be determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum HAZARD required or ducts could result in Table volume for the space. 2 - Minimum Space Volumes were the following equations from the National Z223.1-2006/NFPA 54-2006,9.3.2.2: Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual. 19 determined Fuel by using Gas Code ANSI CIRCULATING DUCTS I I AIR I I I I I II _: 12" MAX (305mm) ------1 SQ IN, PER 1000 BTUH* IN DOOR INTERIOR HEATED SPACE O_ OR WALL O UNCONFINED O SPACE 6" MIN (152mm) z (FRONT)0 1 SQ IN, <_ <_ -- PER 1000 BTUH* IN DOOR OR WALL © i i CIRCULATING OUTDOORS L 12" MAX (305rnm) AIR DUCTS BTUH* _' Minimum opening size is 100 sq in. (64516 mm 2) with minimum *Mininmm dimensions of 3 in. (76 mm). Use any of the following combinations of openings: A&BC&DD&EF&G dimensions of 3 in. (76 mm) t Minimum of 3 in. (76 mm) when type-B1 vent is used. A03174 Fig. 18 - Air for Combustion, Ventilation, Outdoors 1. For other than hood-equipped Volume fan-assisted water Dilution A03175 for Fig. 19 - Air for Combustion, appliances, such c. Combining Other ACH _000 appliances Btu/hr d such and Dilution from space on different floor levels. The volumes of spaces on different floor levels shall be considered as communicating spaces if connected by 3 !other Ventilation, Indoors as a draft heater: _ 21ft 3 _ 2. For fan-assisted and one or more permanent openings in doors or floors having free area of at least 2 in.2/1,000 Btuh A04002 (4,400 mm2/kW) gas appliances. as this furnace: of total input rating of all 2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are Volume Fan ACH 00(J Btu/hr adequate permanent ventilation openings directly outdoors having free area of at least 1-in.2/4,000 Btuh total input rating for all gas appliances in the space. A04003 If: Io_her=combined input of all ether appliances in Btu/hr If_,,= combined ACH input of all fan-assisted = air changes per hour (ACH The following requirements the Known Air Infiltration 1. Adjoining a. There than fan-assisted rooms appliances shall not exceed apply to the Standard Rate Method. can be considered are no closable doors 3. In spaces infiltration and to Unusually Construction if: rooms. a. Walls (2,000 mm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 in. 2 (0.06 m2). One opening shall commence within 12 in. commence minimum and the second opening shall ventilation and construction and ceilings exposed vapor and dilution of flue (See Fig. 19.) NOTE: effect 2O to the outdoors barrier. windows Openings as have a are c. Other joints openings are caulked or sealed. These include around window and door frames, between sole In determining assumed louvers defined and openable of the louvers, the free is b. Doors plates and floors, between wall panels, at penetrations and gas lines, etc. within 12 in. (305 mm) of the floor. The dimension of air openings shall be at least 3 in. (76 mm). tight with: continuous, sealed gasketed or sealed b. Combining spaces on same floor level. Each opening shall have free area of at least 1 in.2/1,000 Btuh (305 mm) of the ceiling permanent Method, air for gases. However, in buildings with unusually tight construction, additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section. 0.60.) part of a space between combustion, in Btu/hr Method that use the Indoor Combustion Air should be adequate to provide to of that wood louvers and screens or grille design must the blocking be considered. is unknown, have a 20 percent have a 60 percent and wall-ceiling joints, between for plumbing, electrical the free area of an opening, grilles, area of a louver or grilles are weatherstripped If it may be free area, and metal free area. Screens, when used, mustnotbesmaller than1/4-in.(6 mm)mesh. Louvers and grilles must beconstructed sotheycannot beclosed. When combustion airductsareused, theymustbeofthesame cross sectional area asthefreearea oftheopenings towhichthey connect. Theminimum dimension ofducts must notbelessthan 3in.(76mm). Combination ofIndoor andOutdoor Air 1.Indooropeningsshall complywith the Indoor Combustion Air Method below and, 2.Outdooropenings shallbe locatedas required in theOutdoorCombustion Air Methodmentioned previously and, 3.Outdoor openings shallbesized asfollows: a.Calculate theRatio ofallIndoor Space volume divided byrequired volume forIndoorCombustion Air Method below. b.Outdoor opening sizereduction Factor is 1minus the Ratioina.above. c.Minimum sizeofOutdoor openings shallbethesize required inOutdoor Combustion Air Method above multiplied byreduction Factorinb.above. The minimum dimension ofairopenings shallbenotless than3in.(76mm). INSTALLATION Step 1 - Leveling When furnace in upflow The maximum length position with side inlet(s), of bolt should 2. For each hole, in bottom install nut in hole. (Install 3. Install another flat washer closure not exceed 1-1/2 in panel nut on other side closure Closure must Panel of furnace Step 2 - Installation Applications in Upflow For downflow use on combustible manufacturer) not required Assembly is used. be used section. applications, flooring when when 1. Determine bolt base. this furnace being special and base installed dimensions are they furnace interfere To remove is approved for (available UNIT from with duct flange and until forth it NOT OPERATE in intermittent unit in Fig. 24. in Horizontal or installed from each Applications in either horizontal left the furnace can either on suitable blocks or pad. corner by hanger bolts and are provided from Table Coil for hole locations. (See in Table 3 in Table NOT OPERATE in intermittent unit The entire length of furnace MUST be supported when furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf area. 3. specified MAY Failure to follow this caution may result operation or performance satisfaction. base is Part No. KCAKC specified is used, install perforated, mating perforated, duct pliers, MAY Legs Step 4 - Air Ducts 3 GENERAL REQUIREMENTS Box Part No. KCAKC subbase. A89014 Fig. 20 - Leveling shown in Fig. 25. Dimples Fig. 2.) 4. If downflow subbase (KGASB) is used, install as shown in Fig. 22. If Coil Assembly Part No. CD5 or CK5 or Coil when 1 angle iron supports. (See Fig. 25.) Cut hanger bolts (4 each 3/8-in. (10 mm) all-thread rod) to desired length. Use 1 X 3/8-in. flat washers, 3/8-in. lock washers, and 3/8-in. nuts on hanger rods as legs on manufacturer's or Coil Box 3. Construct plenum and Fig. 21. Remove 1 3/4" (44mm) be hung from floor joist Furnace can be suspended and tighten is used. Special per dimensions NOTE: (44mm) These furnaces can be installed horizontally or right discharge position. In a crawlspace, (Install leveling this furnace 2. Construct hole in floor and Fig. 21. to 5/16" and Downflow is installed application height, when Part No. KGASB0201ALL Part No. CD5 or CK5, (8mrn) Step 3 - Installation as if desired.) NOTE: Bottom used. See Bottom (44ram) shown if desired.) 4. Adjust outside nut to provide desired inside Nut to secure arrangement. NOTE: may be used nut on bolt and then install flat washer 1 3/4" Do not bend duct flanges inward as shown in Fig. 21. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210 ° as 1. Position furnace on its back. Locate and drill a 5/16-in. (8 mm) diameter hole in each bottom corner of furnace. (See Fig. 20.) Holes guide locations. ) Failure to follow this caution may result operation or performance satisfaction. leveling legs may be desired. (See Fig. 20.) Install field-supplied, corrosion-resistant 5/16-in. (8 mm) machine bolts and nuts. NOTE: 1 3/4' (44ram) UNIT Legs (If Desired) is used (8mm) as shown supply-air flanges supply-air on off. Be in Fig. 23. duct careful use wide to bend flange of sharp should be designed and sized according to standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air flanges or downflow duct flanges, tool, or hand seamers breaks coil The duct system accepted national Conditioning Engineers (ASHRAE), Design Guidelines reference tables back edges. distributor. The duct required system design (See Fig. 24.) 21 or consult available The Air Systems from your local system should be sized to handle CFM at the design static pressure. the FURNACE (OR OTHER MANUFACTURER'S COILCASING WHEN USED) COMBUSTIBLE FLOORING SUBBASE SHEET METAL ...._ PLENUM FLOOR OPENING A07585 A96283 Fig. 21 - Floor and Plenum Opening Dimensions Fig. 22 - Furnace, Plenum, and Subbase on a Combustible Floor Installed FU RNACE APPROVED COIL ASSEMBLY OR COIL BOX COMBUSTIBLE FLOORING I --\ SHEET METAL PLENUM FLOOR OPENING A08556 Fig. 23 - Furnace, Plenum, and Coil Assembly or Coil Box Installed 22 on a Combustible Floor Table FURNACE CASING WIDTH 3 - Opening Dimensions - In. (mm) PLENUM OPENING APPLICATION A B C D 16 (406) 24-1/8 (613) 16-5/8 (422) 24-3/4 (629) 15-7/8 (403) 19 (483) 16-1/2 (419) 19-5/8 (498) Downflow Applications on Combustible Flooring Using KGASB Subbase Furnace with or without CAP, CAR, CNPV, CNRV Coil Assembly or KCAKC Coil Box 15-1/8 (384) 19 (483) 16-3/4 20-3/8 (425) (518) Downflow Applications on Combustible Flooring NOT Using KGASB Subbase Furnace with CAP, CAR, CNPV, CNRV Coil Assembly or KCAKC Coil Box 15-1/2 (394) 19 (483) 16-1/2 20 (419) (508) 19-1/2 (495) 24-1/8 (613) 20-1/8 (511 ) 24-3/4 (629) 19-3/8 (492) 19 (483) 20 (508) 19-5/8 (498) Downflow Applications on Combustible Flooring Using KGASB Subbase Furnace with or without CAP, CAR, CNPV, CNRV Coil Assembly or KCAKC Coil Box 18-5/8 (473) 19 (483) 20-1/4 20-3/8 (514) (518) Downflow Applications on Combustible Flooring NOT Using KGASB Subbase Furnace with CAP, CAR, CNPV, CNRV Coil Assembly or KCAKC Coil Box 19 19 20 20 (483) (483) (508) (508) 23 (584) 24-1/8 (613) 23-5/8 (600) 24-3/4 (629) 22-7/8 (581) 19 (483) 23-1/2 (597) 19-5/8 (498) Downflow Applications on Combustible Flooring Using KGASB Subbase Furnace with or without CAP, CAR, CNPV, CNRV Coil Assembly or KCAKC Coil Box 22-1/8 (562) 19 (483) 23-3/4 20-3/8 (603) (518) Downflow Applications on Combustible Flooring NOT Using KGASB Subbase Furnace with CAP, CAR, CNPV, CNRV Coil Assembly or KCAKC Coil Box 22-1/2 (572) 19 (483) 23-1/2 20 (597) (508) Upflow Applications Downflow Applications 17-1/2 (445) on Non-Combustible Flooring Upflow Applications Downflow Applications 21 (533) on Non-Combustible Flooring Upflow Applications Downflow Applications 24-1/2 (622) FLOOR OPENING on Non-Combustible Flooring Flexible connections furnace DISCHARGE FLANGE DUCT should to prevent be transmission used between of vibration. ductwork Ductwork through unconditioned space should be insulated to system performance. When air conditioning is used, barrier is recommended. NO and passing enhance a vapor Maintain a 1-in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. (915 mm) horizontally from the furnace. See NFPA 90B or local code for further For YES I--] I I requirements. a furnace be provided be accessible such a size that openings sampling 210 DEG. MIN not shall shall using the prevent Metal the heat light air with a cooling exchanger assistance stream. coil, the outlet duct access panel. This opening is installed and shall be of can be viewed or a probe The cover for possible can be inserted for attachment shall leaks. DUCTWORK YES equipped with a removable when the furnace ACOUSTICAL duct systems TREATMENT that do not have a 90 degree elbow and 10 ft (3 M) of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the A93029 latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply Fig. 24 - Duct Flanges with NFPA air ducts. When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return the furnace casing the furnace. Secure ductwork Seal supply-and approved air must also be handled and terminating outside with proper return-duct SUPPLY by a duct(s) sealed to the space containing fasteners for type of ductwork connections to furnace with Upflow 90B as tested AIR by UL Standard 181 for Class 1 Rigid CONNECTIONS Furnaces Connect supply-air duct to 3/4-in. flange on furnace supply-air outlet. The supply-air duct attachment must ONLY be connected used. code to furnace casing tape or duct sealer. 23 supply-/outlet-air (when used). duct flanges or air conditioning DO NOT cut main furnace casing coil to attach supplysideair duct,humidifier, or otheraccessories. All accessories MUSTbeconnected external tofurnace maincasing. Downflow Furnaces covering an opening air plenum on ducts Connect supply-air duct to supply-air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning installed on non-combustible coil casing (when used), when material. When installed on combustible duct attachment material, supply-air must ONLY be connected to an accessory subbase or factory approved conditioning coil casing. DO NOT cut main furnace casing air to FIRE Connect in the furnace fan compartment in the closed position. or in a return HAZARD Failure to follow injury, or death. Never attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing. Supply air opening duct flanges must be modified per Fig. 24. Horizontal communicating with another fuel-burning appliance not of the direct-vent type, shall be operable only when any door or panel connect this warning return-air could ducts Return-air duct connections upflow applications only. to the on result in fire, personal back furnace of the furnace. side(s) permitted to bottom, sides in Furnaces supply-air duct to supply air opening on furnace. The Upflow supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external RETURN AIR to furnace main The casing. portion The furnace and its return air system shall be designed and installed so that negative pressure created by the air circulating air supply or act air, and that the air circulating in an enclosure of of return-air Downflow fan cannot affect another appliance's combustion to mix products of combustion with circulating the furnace, if installed The COMBUSTION-AIR (NON-DIRECT duct must be connected (left or right), or a combination of bottom and side(s) of main furnace casing. Bypass humidifier may be attached into unused side return air portion of the furnace casing. DO NOT connect any CONNECTIONS fan Furnaces return-air duct to back of furnace and Horizontal return-air duct casing. Furnaces must be connected to return-air opening provided. DO NOT portion of return-air cut into casing sides or back to attach any duct. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace. INTAKE VENT COMBUSTION-AIRPIPE DIRECT VENT/2-PIPE ?ATION) ;) _COMBUSTION-AIR INTAKE IS REQUIRED"_ !1 (NON-DIRECTVENT/1-PIPE APPLICATION,) 3/8-1N. (10 mm) ROD ANGLE IRON OR EQ 5 3/4" (146 ram) ALTERNATE SUPPORT LOCATION 4qN. (102 mm) MIN 3-IN. (203 mm) MAX (A) (A) ROD LOCATION USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS) (a) & WASHER (4) REQD PER ROD NOTES: (A) PREFERRED ROD LOCATION 13/16-1N. (21 mm) MAX ALTERNATESUPPORT LOCATIONFROMBACK 1. A 1-in. (25.4 mm) clearance minimum between top of furnace and combustible material. (B) ALTERNATE ROD LOCATION 2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage. 3. For non-direct vent/I-pipe application, bottom side combustion-air entry cannot be used when furnace is installed with hangers as shown. A05054 Fig. 25 - Crawlspace Horizontal Application and for Non-Direct for Direct Vent/l-Pipe 24 Vent/2-Pipe Installation Installation Step 5 - Filter Arrangement FIRE, CARBON MONOXIDE POISONING HAZARD AND Failure to follow injury or death. could result a filter or Never operate door removed. The air filter this warning unit without arrangement will orientation, and filter type. external Filter/Media cabinet vary 21-IN. (533mm) WIDE CASINGS ONLY: SUPPORT RODS (3) EXTEND 1/4" (6mm)ON EACH SiDE OF FILTER AND REST ON CASING FLANGE 171/2-1N.(444mm) WIDE CASINGS ONLY: INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER. in fire, with personal filter access due to application, furnace The filter may be installed (if provided) or the furnace in an blower \ compartment. If a factory-supplied instructions for its external Filter/Media application, assembly, cabinet is provided, and installation are packaged with the cabinet. The Filter/Media cabinet can be used with a factory-specified washable filter or a factory-specified high-efficiency If installing disposable the filter filter in (see cabinet the furnace instructions). blower compartment, determine location for filter and relocate filter retaining wire if necessary. See Table 4 to determine correct filter size for desired filter location. Table 4 indicates filter size and location for this furnace. return-air See Fig. openings. 2 for location and size of bottom and side FILTER Table 4 - Filter Information AiR FILTER LOCATED Furnace Casing Width In. (mm) 17-1/2 (445) 21 (533) 24-1/2 (622) IN BLOWER COMPARTMENT Filter Size Side Return*t (1) 16X 25 X3/4 (406 X 635 X 19) (1) 16X25X3/4 (406 X 635 In. (ram) Bottom Return* (1) 16X 25 X3/4 (406 X 635 (1 or2) 16X25 X 3/4 (406 X 635 X 19) (508 X 635 (1) 24X Washable X 19) 25 X3/4 (609 X 635 Washable X 19) (1) 20 X 25 X 3/4 X 19) Filter Type Framed SUPPORT Washable FILTER RETAINER X 19) A08605 * Alternate sizes can be ordered from your distributor or dealer. 1- Upflow only. Alternate sizes and additional filters may be ordered from your dealer. Fig. 27 - Bottom Filter Arrangement FILTER FILTER RETAINER ! I | | | I BOTTOM CLOSURE PANEL PANEL A08587 Fig. 26 - Filter Installed for Side Inlet A93047 Fig. 28 - Removing 25 Bottom Closure Panel Risers must be used to connect to furnace all gas piping with appropriate straps, CUT minimum of 1 hanger every 6 ft. (2 M). Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas. HAZARD Failure personal to follow injury. this caution may result in minor Use care when cutting support rods in filters to protect flying pieces and sharp rod ends. Wear safety glasses, and appropriate protective clothing. against gloves, FIRE OR EXPLOSION Failure to follow injury or death. -Connect damaging UNIT MAY NOT OPERATE Failure to follow this caution may result operation or performance satisfaction. in intermittent Side UPFLOW Bottom return-air openings configurations. return-air Install opening can filter(s) and discard Step 6 - Bottom -Use proper manifold. used in in Fig. 26. widths. Install closure panel when furnace is shipped with bottom closure 1. Tilt or raise filler panel. 2. Rotate filter be in place perform installed filler panel downward closure 2 screws holding front to release holding tabs. panel. front filler panel INTERNAL SUPPLY MANUAL _/ SHUTOFF VALVE 10 (3.0) 20 (6.0) 30 (9.1 / 40 (12.1) 50 (15.21 (158) 175 120 97 82 73 0.824 (20.9) 360 250 200 170 151 (26.6) 680 465 375 320 285 (31.8) 1.380 (35.0) 1400 950 770 660 580 1-1/2 1.610 2100 1460 1180 990 IN. (MM) 3/4 (19.0) wrench to avoid be facing forward or tilted of pipe to avoid stress on gas control a minimum of 2 in. (51 mm) outside " II _ _ SEDIMENT ''1 [ TRAP UNION ..-a 0.622 1/2 (12.7) a backup (REQUIRED)/ f LENGTH OF PIPE - FT (M) DIA. IN. (MM) length GAS _ and screws. Table 5 - Maximum Capacity of Pipe* NOMINAL IRON PIPE SIZE personal Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so straight-through section of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 29.) the following: and remove MUST in fire, in when (See Fig. 28.) bottom 4. Reinstall panel MUST using result -Protect gas valve from water and debris. Gas valve inlet and/or inlet piping must remain capped until gas supply line is permanently installed to protect the valve from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gas valve. bottom closure panel panel, furnace front 3. Remove bottom switch gas valve and extend furnace casing. Panel This shutoff could -If a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at furnace all 4 orientations. furnace bottom Closure bottom return-air opening. side return air is used. To remove with this warning -Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. in Fig. 27. NOTE: Remove inlet is used. This be as shown may be used Filter may need to be cut to fit some as shown ONLY HAZARD gas pipe to furnace gas controls. -Gas valve upward. unit For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of I side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM. NOTE: and to meter. Support hangers, etc. Use a 1.049 1 (25.4) 1-1/4 (38.1) * Cubic (40.9) ft of gas per hr for gas pressures a pressure drop Table 9.2 NFGC. of O.5-in wc (based of 0.5 on a 0.60 psig (14-in. specific 900 wc) gravity or tess and gas). Ref: A93324 Step 7 - Gas Piping Fig. 29 - Typical Gas Pipe Arrangement Gas piping must be installed in accordance with national local codes. Refer to current edition of NFGC in United and the If local codes States. Canadian NSCNGPIC installations must and all authorities be made having in accordance allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector has previously served another gas appliance. with An accessible jurisdiction. manual shutoff valve MUST be installed which external to furnace casing and within 6 ft (2 M)of furnace. A 1/8-in. NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve. Gas supply line should be a separate line running directly from meter to furnace, if possible. Refer to Table 5 for recommended gas pipe sizing. 26 Table 6- Electrical OPERATING VOLTAGE RANGE VOLTSHERTZPHASE Data MIN WIRE SIZE MAX WIRE LENGTH FT (M):I: MAX FUSE OR CKT BKR AMPS** Max* Min* MAX UNIT AMPS 060-12/036060 115-60-1 127 104 8.4 11.3 14 33(10.0) 15 080-12/036080 115-60-1 127 104 8.1 10.8 14 34(10.3) 15 080-16/048080 115-60-1 15.3 12 37(11.2) 115-60-1 115-60-1 104 104 11.6 100-16/048100 100-20/060100 127 127 104 15.4 17.5 12 12 37(11.2) 33(10.0) 2O 2O 127 11.6 13.3 120-20/060120 115-60-1 127 104 12.9 16.8 12 34(10.3) UNIT SIZE UNIT AMPACITYI 2O 2O Permissible limits of voltage range at which unit will operate satisfactorily. Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' etc.) full load amps. :l: Length shown is measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay type is recommended. Piping should be pressure tested in accordance with edition of the NFGC, local and national plumbing before the furnace has been connected. In Canada, Step 8 - Electrical the current and gas codes refer to current (EAC, humidifier, Connections See Fig. 31, 32, and 50-57 for field wiring diagram typical field 115-v and 24-v wiring. Check all factory electrical connections for tightness. edition of NSCNGPIC. If the pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from the furnace and showing and field capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on furnace gas valve and accessible manual shutoff valve before test. After all connections leakage. have been made, purge lines and check ELECTRICAL for FIRE OR EXPLOSION HAZARD could result Field-supplied wiring 63°F (3. 5o C) rise. UNIT Gas line grommet (factory-supplied loose parts used when installing gas piping. Gas line entry bag) should be hole filler plug should (See Fig. 30.) NOTE: gas line entry hole. The gas valve inlet pressure use as test gauge connection exceed 0.5 psig (14-in. pressure shall maximum tap connection providing is suitable test pressure wc) stated Furnace gas NOT on gas valve. (See l15-V supply be within the maximum minimum inlet supply pressures marked on the rating the furnace burners ON at HI-HEAT and OFF. COMBUSTION-AIR and HOLE FILLER PLUG A05057 Pipe control with the limitations of this must caution may be grounded result in for proper intermittent operation or WIRING The furnace local codes; ENTRY HOLE FILLER IN FACTORY-SUPPLIED Gas injury OPERATE with electrical connections, make certain that and phase correspond to that specified on the equipment. Refer to electrical specifications. A05057 Fig. 30 - Typical in personal furnace rating plate. Also, check to be sure that service provided by power supply is sufficient to handle load imposed by this PIPE GROMMET 2_6}'4-- GAS L,NE ENTRY PIPE GROMMETS AND PLUGS ARE INCLUDED LOOSE PARTS BAG NOT Before proceeding voltage, frequency, plate with UNUSED 1÷3/4 -IN. (44 mm) DIAMETER GAS HOLE NOTE: result control will lock out. Control is grounded through green/yellow wire routed to gas valve C-terminal and burner box screw. to DOES MAY shall conform Failure to follow unit operation. Fig. 58.) The could in serious Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion could result causing property damage, personal injury or loss of life. in unused this warning Blower access door switch opens 115-v power to furnace control. No component operation can occur. Do not bypass or close switch with panel removed. Failure to follow this warning exactly injury, death, or property damage. be installed SHOCK HAZARD Failure to follow or death. Arrangement 27 rating plate or Table 6 for equipment must be electrically grounded in accordance with or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 and/or the Canadian Electric Code, CSA C22.1, Part I, if an external electrical source is utilized. .... .... -- FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING 115-V FUSED DISCONNECT SWITCH (WHEN REQUIRED) 1. Connect Y-terminal as shown for proper operation. 2. Some thermostats require a "C" terminal connection as shown. 3. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire. A99071 Fig. 31 - Typical Heating and Cooling Application Wiring Diagram 1-Stage .... .... -- Thermostat and Condensing Unit FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING 2-STAGE THERMOSTAT TERMINALS [ THREE-WIRE__ HEATINGONLY BLK.__BLK 115-V FUSED DISCONNECT SWITCH (WHEN REQUIRED) I I I Ii II I T ', ', ', I I I I I I I I I I I I I I I "_,,__ -"h_]]_ I @ it; [ _1 I I I .... p---l----+----[----4-- l l l .... [ I ....... II [--"OJ FIELD-SUPPLIED FUSED DISCONNECT 208/230- OR 460-V PHASE Hm JUNCTION -] BOX CONTROL BOX Li--_ OY2 (_ I [ j (_ 24-V TERMINAL BLOCK FURNACE -._E_®_ _ b / T__:I::I [ ----GND/ - - 1 208/230-V /SINGLE PHASE 2-SPEED CONDENSING UNIT NOTES: 1. Connect Y4ermina[ as shown for proper operation. 2. Some thermostats require a "C" terminal connection as shown. 3. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire. A99072 Fig. 32 - Typical Heating and Cooling Application Wiring 28 Diagram 2-Stage Thermostat and Condensing Unit INSTALLED LOCATION ELECTRIC DISCONNECT SWITCH POWER ENTRY HOLE FILLER PLUG (FACTORYSUPPLIED LOOSE PARTS BAG) @ UNUSED 7/SqN. DIAMETER ENTRY (22 I POWER HOLES A93033 Fig. 33 - Disconnect Switch A05113 and Furnace Fig. 34 - Factory within sight from and readily NOTE: Proper maintained for l15-v status polarity indicator and wiring. light accessible proper If polarity will flash must is incorrect, rapidly and be control LED furnace will NOT operate. FIRE HAZARD Failure to follow this warning could operation or performance satisfaction. result Do not connect disconnect furnace. aluminum Use only copper ELECTRICAL wire between in intermittent switch 1. Electronic Air (.'leaner (EAC) Two male quick-connect terminals marked EAC-1 and EAC-2 are provided for EAC connection. (See Fig. 37.) These terminals are energized with 115-v (1.0-amp maximum) during blower motor operation. and wire. (See Fig. 33.) 2. Humidifier (HUM) Connect an accessory 24 VAC, 0.5 amp maximum humidifier (if used) to the 1/4-in. male quick-connect HUM terminal and COM-24V screw terminal on the control board thermostat strip. The HUM terminal is energized when gas valve is energized. (See Fig. 36 or 37.) NOTE: A field-supplied, 115-v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation. SHOCK AND FIRE HAZARD Failure to follow fire, or death. this warning could result in electrical The furnace casing MUST have an uninterrupted ground according to NEC ANSI/NFPA 70-2008 Electrical Code CSA C22.1 or local codes shock, or unbroken and Canadian to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. UNIT Factory Install Installed J-Box electrical entry parts bag) in unused J-Box 2. Rotate hole filler power plugs (factory-supplied 2 screws entry holes. (See Fig. 34.) holding 180 ° and auxiliary attach J-box. (See Fig. 35.) box to left side, loose 35.) electrical parts ELECTRICAL Bag) entry hole in unused SHOCK AND filler plugs power using FIRE Failure to follow this warning could operation or performance satisfaction. (factory-supplied entry holes. Fig. HAZARD result in intermittent If manual disconnect switch is to be mounted select a location where a drill or fastener will electrical (See NOT connect this furnace caution control may HUM result terminal in unit to HUM (humidifier) terminal on Thermidistaff M, Zone Controller or similar device. See Thermidistat'M, Zone Controller, thermostat, or controller manufacturer's instructions for proper connection. holes provided. 3. Install HAZARD Failure to follow component damage. in loose DO J-box DAMAGE Location Relocation 1. Remove Location Make field 24-v connections at 24-v terminal block on furnace. (See Fig. 37.) Connect terminal Y/Y2 as shown in Fig. 31 and 32 for proper cooling operation. Use only AWG No. 18, color-coded, copper thermostat wire for lengths up to 100 ft. (30 M). For wire lengths over 100 ft. (30 M), use AWG No. 16 wire. The 24-v circuit contains an automotive-type, 3-amp fuse located on furnace control. (See Fig. 37.) Any direct shorts of 24-v wiring during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse of identical size/type. The control will flash code 24 when fuse needs replacement. ACCESSORIES to furnace. grounding J-Box 24-V WIRING Use a separate, fused branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 6 for wire size and fuse specifications. A disconnecting means must be located Installed unit on furnace, not contact or gas components. 29 ALTERNATE -FIELD LOCATION S iNSTALLED LOCATION ACTORY POWER ENTRY HOLE iiiiii:0 _,,_1 ,..-----.- FILLER PLUG (FACTORYSUPPLIED LOOSE PARTS BAG) J POWER ENTRY HOLE ______n-u.. .... FILLER PLUG (FACTORY ....... SUPPLIED LOOSE PARTS BAG) •_. UNUSED 7/8-1N. (22 ram) DIAMETER POWER ENTRY HOLES / UNUSED 7/8-1N. (22 mm) DIAMETER POWER ENTRY HOLES A05058 Fig. 35 - Relocating Step 9 - Removal of Existing Common Vent Systems Furnaces from When an existing Category I furnace is removed original venting system may no longer be sized or replaced, the to properly vent the remaining attached appliances. An Category I venting system could cause improperly sized the formation of condensate in the furnace and vent, leakage combustion products, spillage of combustion living space, etc. of condensate and products into the Step 10 - Combustion GENERAL Vent system may need to be resized. when resizing vent or connector must be using appropriate systems sized to table Multistory and common DIRECT VENT/2-PIPE venting vent (1-pipe) or vent approach kit MUST NON-DIRECT in 4. Close SYSTEM be used in a direct range hoods at maximum (in loose pipe elbow. vent (2-pipe) system. bag) MUST be used in Natural and vent pipe, fittings, primers, and to and bathroom exhausts, so they are operating speed. Do not operate a summer exhaust fan. being at 8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.12006/NFPA 54-2006 and/or CSA B149.1-05, MATERIALS Combustion-air not connected fans, such as 7. Test for spillage from draft hood equipped appliances the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. SYSTEM parts dampers. 6. Follow the lighting instructions. Place the appliance inspected into operation. Adjust the thermostat so appliance is operating continuously. In a non-direct vent (1-pipe) system, all air for combustion is taken from the area adjacent to furnace, and all flue products are discharged to outdoor atmosphere. A factory-supplied perforated disk assembly combustion-air fireplace 5. Turn on clothes dryers and any appliance the venting system. Turn on any exhaust are prohibited. VENT/I-PIPE system. 3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. In a direct-vent (2-pipe) system, all air for combustion is taken directly from outdoor atmosphere, and all flue products are discharged to outdoor atmosphere. A factory accessory vent termination in venting Natural Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition. in the procedures openings 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1-2006/NFPA 54-2006 or the CSA B149.1-05, system shall be installed in accordance with the direct vent (2-pipe) procedures in the following Combustion Air and Vent Pipe Systems section. For non-direct vent (1-pipe) to the non-direct HAZARD The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: For any found POISONING Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. can be vented as either a direct vent (all sizes) or as vent (except for 140 size) application. A direct vent applications, refer the same section. MONOXIDE 1. Seal any unused minimum size as determined NFGC or NSCNGPIC. The 58MTB a non-direct CARBON Air and Vent Pipe Systems or vent connectors other appliances connectors, system J-Box Gas and Propane Installation Code. 9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust solvents must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards. See Table 7 for approved materials for use in the U.S.A. fans, fireplace dampers and any other gas-fired appliance to their previous conditions of use. 3O burning PRINTED CIRCIUT BOARD z 0_+o,I1"' °+"-_d¢ tu 8z E i_ £ E _o_ _ _ o _ _ _ _o _ _ _ < _'=' -ol _ / ACRDJ O,S B, AIR CONDITIONING TEST!TWIN ,/ -- -- TRANSFORMER PLI- sEo, %02"I 11 DIAGNOSTIC LIGHT FUSE _ LED3-AMP OPERATION&_p,_= 115-VAC (L2) NEUTRAL _ CO N N ECTtO N S _ I _= LOW VOLTAGE MAIN HARNESS CONNECTOR _ ,g__ _;_:, 24-VAC CONNECT,ONS _ PL3 o BHi/LOR BLWR HEAT -i _J[_Z[] LO HEAT- _' - = SPA _ spRE-1SPARE-2 EAC-1 S E LECTIO N :TgR_/I_I_ALS _ BLOWER SPEEDIPX y \ COOL, EAC-1 _I_;_V_L_A_O(IN) SPARE-2 / L_Eo N PG:_T, oTi R_O:N_D_U:_T_O E (115-VAC A02017 Fig. 37 - Control Center 4. Permanently attach elbow/perforated straight portion of pipe using RTV shown UNIT CORROSION HAZARD Assembly Excessive exposure to contaminated combustion in safety and performance related problems. Combustion air because inside which include These elements must not be taken from System air may result air is frequently contaminated by halogens, fluorides, chlorides, bromides, and iodides. are found in aerosols, detergents, bleaches, NOTE: within cleaning solvents, salts, air fresheners, adhesives, paint, and other household products. Locate combustion-air inlet as far as possible from swimming pool and swimming pool pump house. All pipe combustion-air inlet may be necessary Assembly System joints pipe must to inlet to remove of Combustion have cemented housing attachment connection, of since Table 13, Do not count furnace MAY Failure to combustion, it pipe for servicing. Air Pipe (Non-Direct Vent-2-Pipe determine the smallest elbows (All elbows or pipe sections shown combustion diameter air and use it for in terminations or in Fig. 44 and Fig. 45 are not to be counted). UNIT NOTE: Air Pipe (Direct ONLY) diameter permitted. Pick the larger both combustion and vent pipe. structure to as in Fig. 39. of Combustion 1. Using inside disk assembly or by cementing NOT OPERATE follow this caution may flame disturbance, or flame result in incomplete sense lockout. When installing combustion air and vent system of short pipe length, the smallest allowable pipe diameter must be used. Vent/I-Pipe ONLY) 1. Permanently install perforated disk assembly NOTE: furnace (factory-supplied in loose parts bag) in combustion-air elbow using RTV or by cementing, as shown in Fig. 39. For 120,000 Btuh size units only: separate the 2 halves of perforated disk half. disk assembly and 2. Determine the length of straight inlet pipe from Fig. 39. use only portion 3. Cut field-supplied 2-in. (51 mm) length as determined per Fig. 39. the casing shouldered PVC pipe per Table (factory-supplied where combustion set is required, to 33 be used within outside furnace per Fig. 41. 2. If required of combustion-air diameter A 2-in. (51 mm) diameter pipe must casing. Make all pipe diameter transitions 13, insert perforated disk assembly in loose parts bag) in intake housing air pipe will be connected. If half disk install only shouldered disk half. / i! / ! .......... \ \ A .... ..... "\ ...... ............ C _ to a _y t_m_lnal _tn F Cl_r_e _ra_"_e _ _s_ of 2 feet(61cm) f_om _e _oa_ o_tstd_ ¢o_er Clearar_e to _ J 25-24_2 ctosed _ow a horl_ m_ter ot _ _I \ \ ............ ..... ..... ¢Om_o_ se_¢_ _ulator to nor_-m_a_ air |r_tet to _ _U_ _s_b_ assembly ve_ _et a_r sut_;:)ty Inlet to bt_idi_ _r rneter, rteg_l_ asserrd_ 3 f_st (9_ _m) or ap_$e_;_ 12 inches and < (30 cm) 100,000 appliances for applieances Btuh(3OkW), > 100,000 > 10,000 36 inches Btuh(3 (91cm) kW) for 50,000 BtL_h(i _, i 2 in_es (_)lot app_ Btuh(3OkW) A08600 Table 8 - Direct Vent Termination 34 Clearance H 25-24-65-2 [_ VENTTERMINAL Item Clearance A Clearance above anticipated B snow Clearance C Clearance D Vertical grade, or door to a permanently clearance that deck, to an unventilated E Clearance to an outside G Clearance to an inside H Clearance to each may closed balcony, or 6 inches soffit located above of 2"(61cm) U.S. Installation 12 inches (30 cm) 4 feet(l.2 m) below (2) (15 cm) for appliances _< 10,000 Btuh (3 kW) 12 inches ( 30 cm) for appliances > 10,000 Btuh (3 kW0) and -< 100,000 Btuh (30 kW), 36 inches (91 cm) for appliances > 100,000 Btuh (39 kW) above 3 feet (91 cm) within 3 feet (91 cm) or to the side of the opening, t foot (30 cm the opening. corner corner side of the centerline extended regulator regulator above assembly K Clearance to a mechanical L Clearance under vent outlet M Clearance to each below terminal air supply a veranda, porch, of the furnace appliance's direct or extended t 2 inches(3O above to a dryer or water 15 feet (4.5 m) above the meter/regulator 4 feet(1.2 m) below above opening. intake 3 feet (91 cm) above cm) or to the side of opening: if within 1 foot (30 cm) 10 feet (3 m horizontally) + or heater or exhaust. Clearance to the vent terminal of a dryer vent, water heater vent, or other appliances direct vent intake or exhaust. O Clearance p Clearance above driveway located vent _iithin assembly 6 feet (1.83 m) or balcony N a plumbing the meter/regulator 6 inches (15 cm) for appliances -< 10,000 Btuh (3 kW) 12 inches ( 30 cm) for appliances > 10,000 Btuh (3 kWO) and < 100,900 Btuh (30 kW) 36 inches (91 cm) for appliances > t00,000 Btuh (30 kW) inlet vent m) above 3 feet (91 cm) deck, side of the centerline 15 feet(4.5 assembly Clearance to non-mechanical air supply inlet to building the combustion air inlet to any other appliance (1.) (1) # the J from Installation IS NOT PERMITED the from Clearance or other (30cm) TERMINAL soffit or gas service to service be opened I vent, 12 inches WHERE window distance Clearance vent AREA INLET Canadian porch, to a ventilated E meter AIR SUPPLY level to a window electrical _ Descriptions veranda, terminal within a horizontal centerline of the terminal stack paved sidewalk or paved on public property 7 feet (2.13m)** 7 feet (2.13m) InaccordaecewiththecurrentCSABt49.1,NaturalGasandPropanelnstallationCode (2.) InaccordancewiththecurrentANSIZ223.1/NFPA54, # 18" + Permitted ** \\ (46 cm) above only if veranda, porch, For clearances not specified Manufacturer's installation A vent NationalFuelGasCode roof surface shall not terminate deck, in ANSI or balcony is fully open Z223.1/NFPA 54 or CSA on a minimum B149.1, of two sides clearances shall beneath the floor. be in accordance with local installation codes and the requirements of the gas supplier and the instructions. above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. Notes: 1. 2. The vent for this appliance b. Nears__it_ents_rcraw_spacevents_r_therareaswherec_ndensate_rvap_rc_u_dcreateanusiance_rhazard_rpr_pertydamage;_r c. Wh_rec_ndensatevap_rc_u_dcausedamage_rc_u_dbedetrime_ta_t_t_e_p_rati_n_fregu_at_rs_r__iefva_ves__r_therequipme_t_ locating Recirculation 3 Avoid venting walkways; not terminate Over When public shall a. or vent terminations, can cause under consideration poor combustion, a deck or large must be given inlet condensate overhang. Recirculation to prevailing problems, could and occur winds, location, accelerated and cause and other c onditions corrosion performance of the heat or system which may cause recirculation of the combustiob products of adjacent vents. exchangers. problems. A08601 Table 9 - Other than Direct Vent Termination 35 Clearance Table 10 - Maximum Allowable Winter UNIT SIZE WINTER DESIGN TEMPERATURE 060 °F (°C) Exposed Design Vent Pipe Length Temperature With and Without Insulation in Ambient* MAX PIPE DIAMETER IN. (mm) WITHOUT INSULATION FT (i) WITH 3/8-1N. (10 mm) OR THICKER INSULATION FT (a)l 20 (-7) 2 (51) 44 (13) 70 (21) 0 (-18) 2 (51) 21 (6) 70 (21) 2 (51) 20 (6) 57 (17) 20 (-7) 2 (51) 55 (17) 55 (17) 0 (-18) 2 (51) 30 (9) 55 (17) 2 (51) 16 (5) 55 (17) 20 (-7) 2.5 (64) 58 (18) 70 (21) 0 (-18) 2.5 (64) 29 (9) 70 (21) 2.5 (64) 14 (4) 67 (20) 20 (-7) 2.5 (64) 40 (12) 40 (12) 0 (-18) 2.5 (64) 38 (12) 40 (12) 2.5 (64) 21 (6) 40 (12) -20 -20 (-29) (-29) 080 -20 -20 (-29) (-29) 100 3 (76) 0 (-18) 3 (76) 30 (9) 70 (21) 3 (76) 12 (4) 70 (21) 20 (-7) 3 (76) 70 (21) 70 (21) 0 (-18) 3 (76) 38 (12) 70 (21) 3 (76) 19 (6) 70 (21) 20 (-7) 4 (102) 65 (20) 70 (21) 0 (-18) 4 (102) 26 (8) 70 (21) 4 (102) 5 (2) 65 (20) -20 120 -20 -20 (-29) (-29) (-29) * Pipe length (ft) specified for maximum pipe lengths located in unconditioned length as specified in Table 11. 1- Insulation thickness based on R value of 3.5 per in. Attachment of Combustion 63 (19) 20 (-7) 70 (21) spaces= Pipes located in unconditioned Air Pipe space cannot exceed total allowable pipe field-supplied 3/8-in. tube. This tube should be routed to open condensate drain for furnace and A/C (if used), and should be trapped, as shown in Fig. 42. 1. Determine location of combustion air intake pipe connection to combustion air intake housing as shown in Fig. 38 for application. NOTE: (Direct Vent/2-Pipe System ONLY). Moisture in combustion air intake may be a result of improper termination. Ensure combustion air pipe termination is similar to those as shown in Fig. 44 so that it will not be susceptible to area where light snow or other sources of moisture could be pulled in. VENT PIPE 2. Reposition combustion air intake housing plug fitting in appropriate unused intake housing connection. 3. Install combustion-air pipe grommet (factory-supplied in loose parts bag) into selected furnace casing combustion-air pipe hole. (See Fig. 40.) 4. Insert assembled combustion air inlet pipe into intake housing as shown in Fig. 38. General Furnace vent connection must be attached as shown in Fig. 38. 5. Drill a I/S-in. (3 mm) hole in 2-in. (51 mm), combustion air pipe using the hole in intake housing as a guide. 6. Install a field-supplied No. 6 or No. 8 sheet metal screw into combustion air pipe. CARBON MONOXIDE DAMAGE HAZARD 7. Install casing hole filler cap (factory-supplied in loose parts bag) in unused combustion air pipe casing hole. POISONING AND PROPERTY Failure to follow this warning could result in property damage, personal injury, or death. NOTE: Do not attach combustion air intake pipe permanently to combustion air intake housing since it may be necessary to remove pipe for service of burner box components or flame sensor. Vent pipes must be airtight. NOTE: A 2-in. (51 mm) diameter Attachment of Combustion Air Intake Housing Plug Fitting furnace The combustion-air intake plug fitting must be installed in unused combustion air intake housing. This fitting must be attached by using RTV sealant, or by drilling a 1/8-in. (3 mm) hole in fitting, using hole in intake housing as a guide. Install a field-supplied No. 6 or No. 8 sheet metal screw. casing NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur. excessive Fig. 43.) A plugged drain connection has been provided on this fitting for use when moisture is found in combustion air intake pipe and combustion box. If use of this drain connection is desired, drill out fitting's tap plug with 3/16-in. drill and connect a Attachment casing. Make pipe must be used all pipe diameter transitions within outside the furnace per Fig. 41. The minimum vent pipe length for these furnaces is 5 ft. (2 M). Short pipe lengths (5-8 ft or 2-3 M) may discharge condensate droplets. These condensate (305 mm) minimum offset condensate droplets may be undesirable. pipe section is recommended droplets from exiting vent pipe outlet. (See of Vent Pipe 1. Determine vent pipe diameter using Table 13. 36 A 12-in. to reduce and maximum pipe lengths Table 11 SETUP SWITCH NOTE: NO. SWITCH NAME Furnace NORMAL Setup Switch Description POSITION DESCRIPTION OF USE When off, allows 2-stage operation with a single-stage thermostat. Turn on when using 2-stage thermostat to allow Low Heat operation when R to W/W1 closes and High Heat operation when R to W/W1 and W2 close. SW-1 Adaptive Heat Mode OFF Blower OFF delay ON or OFF Control blower OFF delay time. Used in conjunction See Table 9B. with SW-3. SW-2 Blower OFF delay ON or OFF Control blower OFF delay time. Used in conjunction See Table 9B. with SW-2. SW-3 Select 1 vent pipe connection and 1 combustion-air pipe connection. AIR COMBUSTION-AIR _ COMBUSTION-AIR _t[-F!'EL' NOTE: Select 1 vent pipe connection and 1 combustion-air pipe connection. ' ---F,ELD-SUPPL, ED PVC 90 ° ELBOWJ ,z" __ 4__ W TO 2-IN. (51 mm) DIA. PVC PiPE _ _ VENT f COMBUSTIONAIR _7 AiR FLOW A COMBUSTIONAIR _LCOMBUSTION-AIR UPFLOW DISC DOWNFLOW (FACTORY-SUPPLIED LOOSE PARTS BAG) COMBUSTIONAIR COMBUSTIONAIR VENT IN A96211 Length VENT of Straight Combustion-Air Pipe Portion Inlet Pipe Assembly of - In. (mm) CASING WIDTH 17-1/2 A (445) 21 (533) 24-1/2 (622) HORIZONTAL-LEFT DISCHARGE HORIZONTAL-RIGHT NOTE: DISCHARGE (Direct same diameter in section For Non-Direct Vent (1-Pipe) system, orient elbow so that its opening faces down. system NOTE: For Non-Direct Vent (1 -Pipe) system, orient elbow so that its opening faces sideways. within 1 An external trap kit (see furnace product data sheet) must be used. tt Bottom combustion-air not allowed for non-direct 38 -+1/2 (287 -+13) Inlet Pipe Assembly - Combustion-Air Table 12 - Blower and Vent Pipe Vent/2-pipe "Assembly of Combustion Do not count furnace elbows (all elbows housing location as shown pipe system has the air pipe mentioned Air Pipe (Direct or pipe sections shown Vent/2-Pipe in terminations or in Fig. 44 and Fig. 45 are not be of vent pipe connection Units 4. Reposition elastomeric (rubber) and clamp to appropriate Tighten to inducer in Fig. 38 for application. 3. Install vent pipe grommet (factory-supplied bag) into selected furnace casing vent Fig. 44.) Connections connection. DESIRED HEATING MODE BLOWER-OFF DELAY (SEC) vent as combustion ONLY)." 2. Determine Off Delay Setup Switch (SW) 2-Stage with PSC Blower Motors ONLY) and same length to counted). vent A05092 Fig. 10-1/2 12 -+1/2 (318 -+13) Fig. 39 - Combustion-Air ** -+1/2 (216 -+13) tt t * 8-1/2 inducer unused in loose pipe hole. housing inducer parts (See outlet cap housing clamp. SETUP SWITCH 90 SW-2 OFF SW-3 OFF 120 OFF ON UNIT 150 ON OFF 180 ON ON Failure to follow this caution may result in unit component damage. DAMAGE HAZARD Inducer housing outlet cap must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage. 37 Table 13 - Maximum ALTITUDE FT (i) UNIT MAX INPUT RATE (BTUH) 60,000 80,000 DIRECT VENT (2-PIPE) ONLY TERMINATI PIPE DIA ON TYPE IN. (MM)* 2 Pipe or 2-in. (51 ram) Concentric 2 (51) 1 - 1/2 (38) 1 - 1/2 (38) 2 (51) (64) 2-1/2 (64) 3 (76) 2-1/2 60,000 80,000 2001 to 3000 100,000 (610 to 914) 120,000 60,000 80,000 3001 to 4000 (914 to 1219) 100,000 120,000 2 Pipe or 3-in. (76 ram) Concentric 2 Pipe or 2-in. (51 ram) Concentric 2 Pipe or 2-in. (51 ram) Concentric 2 Pipe or 3-in. (76 ram) Concentric 2 Pipe or 3-in. (76 ram) Concentric 2 Pipe or 2-in. (51 ram) Concentric 2 Pipe or 2-in. (51 ram) Concentric 2 Pipe or 3-in. (76 mm) Concentric 2 Pipe or 3-in. (76 mm) Concentric 4t no disk See notes at end (64) one disk 2 (51) 2-1/2 (64) 2 (51) 2-1/2 (64) 3 (76) 2-1/2 (64) NA 3 (76)t 3 (76)t no disk 3 (76)t 1 - 1/2 (38) 1 - 1/2 (38) 2 (51) 2 (51) 2 (51) 2 (51) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 3 (76) 3 (76) 3 (76) NA NA NUMBER OF 90 ° ELBOWS DIA 2 (51) 2 (51) 2 Pipe or 3-in. (76 ram) Concentric PIPE IN. (MM)* 1 - 1/2 (38) 2 Pipe or 2-in. (51 ram) Concentric - Ft. (M) (1 -PIPE) ONLY 1 - 1/2 (38) 2-1/2 120,000 Pipe Length NON-DIRE CT VENT 0 to 2000 (0 to 610) 100,000 Allowable 3 (76)t 3 (76)t no disk NA 4t no disk 4t no disk 1 - 1/2 (38) 1 - 1/2 (38) 2 (51) 2 (51) 2 (51) 2 (51) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 3 (76) 3 (76) 3 (76)t no disk NA NA 3 (76)t 4t no disk 4t no disk of table 38 1 2 3 4 5 6 2O (6.1) 70 (21.3) 10 (3.0) 55 (16.7) 70 (21.3) 15 (4.6) 70 (21.3) 10 (3.0) 70 (21.3) 5 (1.5) 70 (21.3) NA NA 70 (21.3) 70 (21.3) NA NA NA NA NA 50 (15.2) 70 (21.3) 35 (10.6) 70 (21.3) 30 (9.1) 70 (21.3) 30 (9.1) 70 (21.3) 20 (6.1) 70 (21.3) 5 (1.5) 40 (12.1) 70 (21.3) NA NA NA NA NA 30 (9.1) 20 (6.1) 20 (6.1) 10 (3.0) NA 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 10 (3.0) NA NA NA NA NA 45 40 35 30 25 20 (13.7) (12.1) (10.6) (9.1) (7.6) (6.1) 70 70 70 70 70 70 (21.3) (21.3) (21.3) (21.3) (21.3) (21.3) 17 (5.1) 12 (3.6) 7 (2.1) NA NA NA 70 67 66 61 61 61 (21.3) (20.4) (20.1) (18.5) (18.5) (18.5) 49 44 30 25 25 15 (14.9) (13.4) (9.1) (7.6) (7.6) (4.6) 70 70 70 70 70 70 (21.3) (21.3) (21.3) (21.3) (21.3) (21.3) 35 26 16 16 6 (10.6) (7.9) (4.8) (4.8) (1.8) 70 70 70 70 66 61 (21.3) (21.3) (21.3) (21.3) (20.1) (18.5) 14 (4.2) 9 (2.7) NA NA NA NA 63 62 62 61 61 61 (19.2) (18.8) (18.8) (18.5) (18.5) (18.5) NA 70 70 63 56 50 43 (21.3) (21.3) (19.2) (17.) (15.2) (13.1) 70 70 70 70 70 70 (21.3) (21.3) (21.3) (21.3) (21.3) (21.3) NA 16 11 (4.8) (3.3) (18.8) 6 NA NA 68 63 62 57 57 56 (20.7) (19.2) (18.8) (17.3) (17.3) (17.0) 46 41 28 23 22 13 (14.0) (12.4) (8.5) (7.0) (6.7) (3.9) 70 70 70 70 70 70 (21.3) (21.3) (21.3) (21.3) (21.3) (21.3) 33 24 15 14 5 (10.0) (7.3) (4.6) (4.2) (1.5) 70 70 70 66 61 56 (21.3) (21.3) (21.3) (20.1) (18.5) (17.0) NA 65 58 51 44 38 31 (19.8) (17.6) (15.5) (13.4) (11.5) (9.4) 59 59 58 57 57 56 (17.9) (17.6) (17.6) (17.3) (17.3) (17.0) 70 70 70 70 70 70 (21.3) (21.3) (21.3) (21.3) (21.3) (21.3) Table 13--Maximum ALTITUDE FT (a) UNIT MAX INPUT RATE (BTUH) 60,000 80,000 4001 to 5000 (1219 to 1524)* 100,000 120,000 80,000 80,000 5001 to 6000 (1524 to 1829)* 100,000 120,000 60,000 80,000 6001 to 7000 (1829 to 2134)* 100,000 DIRECT VENT TERMINATION TYPE 2 Pipe or 2-in. (51 mm) Concentric 2 Pipe or 2-in. (51 mm) Concentric 2 Pipe or 3-in. (76 mm) Concentric 2 Pipe or 3-in. (76 mm) Concentric 2 Pipe or 2-in. (51 mm) Concentric 2 Pipe or 2-in. (51 mm) Concentric 2 Pipe or 3-in. (76 mm) Concentric 2 Pipe or 3-in.. (76 mm) Concentric 2 Pipe or 2-in. (51 mm) Concentric 2 Pipe or 2-in. (51 mm) Concentric 2 Pipe or 3-in. (76 mm) Concentric Allowable Pipe Length - Ft. (M) (Continued) (2-PIPE) ONLY PIPE DIA NON-DIRE CT VENT PIPE (IN.)* 1-1/2 1-1/2 2 (51) 2 (51) 2 (51) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 3 (76) 3 (76) 3 (76)1- no disk NA NA 3 (76)1- 41-no disk 41- no disk (38) 1-1/2 120,000 (38) 2 (51) 2 (51) 2 (51) 2 (51) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 3 (76) 3 (76) 3 (76)1- no disk NA NA 3 (76)1- 41-no disk 41- no disk 1-1/2 1-1/2 (38) (38) 2 (51) 2 (51) 2 (51) 2 (51) 2-1/2 (64) 2-1/2 (64) 2-1/2 2-1/2 3 (76) (64) (64) 3 (76) NA 3 (76)1- no disk 2 Pipe or 3-in. (76 mm) Concentric (38) 2 (51) 1-1/2 NA 3 (76)1- 41-no disk 41- no disk See Notes at the end of table 39 OF 90 ° ELBOWS DIA (IN.)* (38) NUMBER (1 -PIPE) ONLY 1 2 3 4 5 6 15 (4.6) 64 (19.5) 44 (13.4) 70 (21.3) 31 (9.4) 10 (3.0) 59 (17.9) 39 (11.8) 7O (21.3) 22 (6.7) 5 (1.5) 58 (17.6) 26 (7.9) 70 (21.3) 13 (3.9) NA NA NA 53 (18.1) 21 (6.4) 70 (21.3) 12 (3.6) 52 (15.8) 20 (6.0) 70 (21.3) 52 (15.8) 11 (3.3) 70 (21.3) NA NA 70 (21.3) 53 (18.1) 56 (17.0) 7O (21.3) 14 (4.2) 6O (18.2) 41 (12.4) 70 (21.3) 46 (14.0) 55 (16.7) 70 (21.3) 9 (2.7) 55 (16.7) 36 (10.9) 67 (20.4) 40 (12.1 ) 54 (16.4) 70 (21.3) 62 (18.8) 33 (10.0) 53 (16.1) 70 (21.3) 57 (17.3) 26 (7.9) 52 (15.8) 70 (21.3) 52 (15.8) 20 (6.0) 52 (15.8) 70 (21.3) NA NA NA NA 54 (16.4) 23 (7.0) 49 (14.9) 18 (5.9) 48 (14.6) 17 (5.1) 47 (14.3) 8 (2.4) 7O (21.3) 29 7O (21.3) 21 (6.4) 67 (20.4) 35 (10.6) 52 (15.8) 7O (21.3) 8 (2.4) 52 (15.8) 33 70 (21.3) 12 (3.6) 70 (21.3) 11 (3.3) 70 (21.3) 70 (21.3) NA NA 62 (18.8) 29 (8.8) 50 (15.2) 70 (21.3) 57 (17.3) 22 (6.7) 49 (14.9) 70 (21.3) 52 (15.8) 15 (4.6) 48 (14.6) 70 (21.3) 47 (14.3) 9 (2.7) 47 (14.3) 70 (21.3) NA NA NA NA 50 (15.2) 21 (6.4) 68 (20.7) 45 (13.7) 16 (4.8) 67 (20.4) 44 (13.4) 15 (4.6) 66 (20.1) 43 (13.1) 6 (1.8) 64 (19.5) 10 (3.0) 9 (2.7) NA NA 58 (17.6) 18 (5.4) 53 (16.1) 11 (3.3) 48 (14.6) 43 (13.1) NA NA 47 (14.3) 70 (21.3) 45 (13.7) 70 (21.3) 44 (13.4) 67 (20.4) 43 (13.1) 62 (18.8) (8.8) 70 (21.3) 42 (12.8) 53 (18.1) 7O (21.3) 13 (3.9) 57 (17.3) 38 (11.5) 7O (21.3) 27 (8.2) 68 (20.7) 31 (9.4) 49 (14.9) 7O (21.3) (1o.o) 7o (21.3) 19 (5.7) 63 (19.2) 24 (7.3) 48 (14.6) 70 (21.3) Table ALTITUDE FT (i) UNIT SIZE (BTUR) 60,000 80,000 7001 to 8000 (2134 to 2438), 100,000 13--Maximum Allowable 60,000 80,000 8001 to 9000 (2438 to 2743)* 100,000 PIPE DIA (IN.)* PIPE DIA (IN.)* 1 2 3 4 5 6 2 Pipe or 2-in. (51 mm) Concentric 1 - 1/2 (38) 1 - 1/2 (38) 12 (3.6) 7 (2.1) NA NA NA NA 2 (51) 2 (51) 2 (51) 2 (51) 48 (14.6) 31 (9.4) 46 (14.0) 19 (5.7) 41 (12.4) 14 (4.2) 40 (12.1) 12 (3.6) 38 (11.5) 2 Pipe or 2-in. (51 mm) Concentric 53 (16.1) 36 (10.9) 66 (20.1) 25 (7.6) 65 (19.8) 17 (5.1) 63 (19.2) 8 (2.4) 62 (18.8) 7 (2.1) 60 (18.2) 59 (17.9) NA NA 63 (19.2) 20 (6.0) 58 (17.6) 13 (3.9) 53 (16.1) 7 (2.1) 48 (14.6) 43 (13.1) 38 (11.5) NA NA NA 46 (14.0) 44 (13.4) 43 (13.1) 41 (12.4) 40 (12.1) 38 (11.5) 61 (18.5) 11 (3.3) 56 (17.0) 6 (1.8) 51 (15.5) 46 (14.0) 41 (12.4) 36 (10.9) NA NA NA NA 49 (14.9) 33 (10.0) 44 (13.4) 28 (8.5) 42 (12.8) 17 (5.1) 37 (11.2) 12 (3.6) 35 (10.6) 10 (3.0) 34 (10.3) 62 (18.8) 23 (7.0) 60 (18.2) 15 (4.6) 58 (17.6) 7 (2.1) 56 (17.0) 5 (1.5) 55 (16.7) 53 (16.1) NA NA 59 (17.9) 10 (3.0) 54 (16.4) 49 (14.9) 44 (13.4) 39 (11.8) 34 (10.3) NA NA NA NA NA 41 (12.4) 30 (9.1) 39 (11.8) 25 (7.6) 37 (11.2) 20 (6.1) 35 (10.6) 15 (4.6) 34 (10.3) 10 (3.0) 2 Pipe or 3-in. (76 mm) Concentric 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 3 (76) 2 Pipe or 3-in. (76 mm) Concentric no disk NA 3 (76)t 4t no disk 4t no disk 2 Pipe or 2-in. (51 mm) Concentric 1 - 1/2 (38) 1 - 1/2 (38) 2 (51) 2 (51) 2 Pipe or 2-in. (51 mm) Concentric 2 (51) 2 (51) 2 Pipe or 3-in. (76 mm) Concentric 120,000 60,000 2 Pipe or 2-in. (51 mm) Concentric 80,000 2 Pipe or 2-in. (51 ram) Concentric 120,000 3 (76) NA 2 Pipe or 3-in. (76 mm) Concentric 100,000 NUMBER OF 90 ° ELBOWS TERMINATIO N TYPE 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 3 (76) 3 (76)f 9001 to 10,000 (2743 to 3048)* - Ft. (M) (Continued) NON-DIRE CT VENT (1 -PIPE) ONLY DIRECT VENT (2-PIPE) ONLY 3 (76)f 120,000 Pipe Length 2 Pipe or 3-in. (76 mm) Concentric 2 Pipe or 3-in. (76 mm) Concentric 3 (76) no disk NA NA NA NA 3 (76)t 4t no disk 4t no disk 43 (13.1) 35 (10.6) 2 (51) 2 (51) 45 (13.7) 40 (12.1) 38 (11.5) 33 (10.0) 31 (9.4) 29 (8.8) 2 (51) 2 (51) 30 (g. 1) 25 (7.6) 14 (4.2) 9 (2.7) 7 (2.1) NA 57 (17.3) 21 (6.4) 55 (16.7) 13 (3.9) 53 (16.1) 5 (1.5) 51 (15.5) 49 (14.9) 47 (14.3) NA NA NA 54 (16.4) 39 (11.8) 10 (3.0) 49 (14.9) 37 (11.2) 5 (1.5) 44 (13.4) 35 (10.6) 39 (11.8) 33 (10.0) 34 (10.3) 31 (9.4) 29 (8.8) 29 (8.8) NA NA NA NA 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 2-1/2 (64) 3 (76) 3 (76) NA 3 (76)t 4t no disk 4t no disk *Disk usage - Unless otherwise specified, use perforated disk assembly (factory-supplied in loose parts bag). If one disk is stated, separate 2 halves of perforated disk assembly and use shouldered disk half. When using shouldered disk half, install screen side toward inlet box. tWide radius elbow. SVent sizing for Canadian installations over 4500 ft (1370 M) above sea level are subject to acceptance by the local authorities having jurisdiction. NA-Not Allowed; pressure switch will not make. NOTES: 1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur. 2. Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes. 3. Assume two 45 ° elbows equal one 90 ° elbow. Wide radius elbows are desirable 4. Elbows and pipe sections within the furnace casing and at the vent termination 5. The minimum pipe length is 5 ft (2 M) for all applications. 6. Use 3-in. (76 mm) diameter vent termination kit for installations and may be required in some cases. should not be included requiring 4-in. (102 mm) diameter pipe. 40 in vent length or elbow count. 5. Be certain connection that mating surfaces of inducer elastomeric (rubber) coupling, and mm) diameter vent elastomeric (rubber) pipe are clean vent coupling housing 2-in. (51 4. Chamfer outside edge primer and cement. and dry. Assemble the (with 2 loose clamps) 5. Clean and dry all surfaces 6. Check onto inducer housing connection. Insert the 2-in. (51 mm) diameter vent pipe through the elastomeric (rubber) coupling and fully into inducer housing connection until it touches a stop inside the inducer housing outlet. the screws on both clamps to 15-in-lb. of torque, inducer housing. Tighten the clamp screws Starting at furnace, (6 mm) per linear slope vent pipe a minimum ft with no sags between distribution of to be joined. dry fit of pipe and mark insertion end of pipe depth on pipe. to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat. of torque. NOTE: for better 7. After pipes have been cut and preassembled, apply generous layer of cement primer to pipe fitting socket and Tighten pipe to to 15 in.-lb, of pipe 8. While cement is still wet, twist pipe into socket with turn. Be sure pipe is fully inserted into fitting socket. of 1/4-in. hangers. 9. Wipe excess cement will 1/4 cement from joint. A continuous bead of be visible around perimeter of a properly made joint. UNIT DAMAGE HAZARD 10. Handle Failure to follow this caution may result in unit component damage. supportive combustion Inducer housing outlet cap must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage. 6. Install casing hole filler parts bag) in unused Attachment Furnaces with 100,000 (factory-supplied vent pipe casing of Vent Extension PVC vent extension cap Btuh hole. input are supplied (51 mm) diameter with by 12-in. on ALL upflow NOTE: and downflow See label on vent extension This pipe may be shortened extension Guidelines until the cement venting sets. system support. and vent portions a 14. Use (305 of the venting the accumulation appropriate methods system is is used to seal combustion air pipe (if applicable) through roof or sidewall. COMBUSTION-AIR openings and vent 1. Attach all permanently combustion in sections 2. Working that before PIPE GROMMET installation. to connect UNUSED 1-3/4 -IN. (44 mm) DIAMETER GAS HOLE vent Air Pipe and Vent illi0 _-- GAS L,NE ENTRY pipes be cementing cut, prepared, inside FILLER PLUG and any joint. Air Pipe" furnace to outside, and outside of pipe. and "Vent Pipe." cut pipe to required NOTE: length(s). 3. Deburr pass air pipe and vent pipe per instructions "Combustion from where pipe vent pipe. for Combustion recommended or shall be installed HOLE pre-assembled be Support piping a of condensate. Pipe It shall applications. pipe for proper if an elbow tube to field-installed Installation of to prevent sagging air piping (if applicable) so as to prevent mm) long). This pipe has a built-in channel to assist vent condensate disposal. When this vent extension pipe is supplied, it MUST be used to connect the field vent pipe to furnace inducer housing carefully 12. Slope combustion air piping (if applicable) and vent piping downward towards furnace a minimum of 1/4 in. (6 mm) per linear ft with no sags between hangers. in loose 13. Horizontal and larger portions minimum of every 5 ft (2 M) (3 ft or .9 M for SDR-21 -26 PVC) using perforated metal hanging strap. Pipe pipe (2-in. pipe joints 11. Horizontal PIPE GROMMETS AND ENTRY HOLE FILLER PLUGS ARE INCLUDED IN FACTORY-SUPPLIED LOOSE PARTS BAG A05057 A05057 Fig. 40 - Typical 41 Gas Pipe Arrangement EXAMPLE: ( An 080-12 size furnace located in Indianapolis, elevation 650 fl (198 M) above sea level, could be installed as either a direct vent/2-pipe system that requires 3 elbows and 32 fl (10 M) of vent pipe, along with 5 elbows and 34 fl (10 M) of combustion-air pipe OR a non-direct vent/I-pipe system that requires 3 elbows and 32 fl (10 M) vent pipe. FURNACE For a direct vent/2-pipe system, Table 13 indicates this application would allow a 2-in. (51 mm) diameter vent pipe, but require a 2-1/2 in. (64 mm) diameter combustion air pipe. According to Table 13, 2-in. (51 mm) diameter pipe is good for 35 fi (11 M) with 3 elbows, but only 30 ft (9 M) with 5 elbows. Therefore, 2-1/2 in. (64 mm) diameter pipe must be used for both vent and combustion-air pipes since larger required diameter must always be used for both pipes. NOT IN HORIZONTAL SECTION TRANSITION iN VERTICAL SECTION A93034 For a non-direct vent/I-pipe system, Table 13 indicates that this application would allow a 2-in. (51 mm) diameter vent pipe. If same installations were in Albuquerque, elevation 5250 ft (1600 M) above sea level: Fig. 41 - Combustion-Air and Vent Pipe Diameter Transition Location and Elbow Configuration COMBUSTION AIR TAKE HOUSING 3/8 ID TUBE -- 7 --_ D I1, For a direct vent/2-pipe system, Table 13 indicates that 2-1/2 in. (64 mm) diameter vent pipe and combustion-air pipe are required. BURNER BOX -- j_.-_ ['1, COMBUSTION-AIR I _PIPE (DIRECT VENT/2 PIPE) b_€ For a non-direct vent/I-pipe system, Table 13 indicates that 2-1/2-in. (64 mm) diameter vent pipe is required. \ If same applications are to be installed (1524 to 1829 M)elevation: COMBUSTION-AIR PIPE (NON-DIRECT VENT/I-PIPE) For a direct vent/2-pipe system, 2-in. (51 mm) pipe is only good for 23 ft (7 M) (with 3 elbows) and 17 fl (5 M)(with 5 elbows). Therefore, 2-1/2 in. (64 mm) diameter combustion air and vent pipe must be used. TRAPJt TO OPEN DRAIN -- For a non-direct vent/I-pipe system, a 2-in. (51 mm) diameter pipe is only good for 23 fl (7 M) with 3 elbows. A 2-1/2-in. (64 mm) diameter vent pipe must be used. A05093 Fig. 42 - Air Intake at 5001 to 6000 fi Housing Plug Fitting Drain 42 --12MN 1 -,_l--_ 12" MI N ------B_ I (305mm) VENT PIPE 0 HORIZONTAL L U -- TO ROOF HORIZONTAL F VENT COMBUSTION-AIR PIPE PIPE VENT VERTICAL TO ROOF PIPE TO SIDEWALL COMBUSTION-AIR COMBUSTION-AIR _ VERTICAL PIPE TO SIDEWALL NOTE: A 12-in. (304.8mm) minimum offset pipe section is recommended with short (5 to 8 ft / 1.5 to 2.5M) vent systems. This recommendation is to reduce excessive condensate droplets. A96230 Fig. 43 - Short VENT Vent (5 to 8 ft (1.5 to 2.4 M)) System TERMINATION building airborne flue gases, 4. Termination or termination kit should be positioned it will not be damaged by or subjected to foreign such as stones, balls, etc. where objects General Combustion-air (direct must terminate outside For vent termination Vent/2-Pipe system vent/2-pipe system only) and vent pipe structure, either through sidewall or roof. clearance, refer to Table 8 for Direct and Table 9 for Non-direct 5. Termination Vent/I-Pipe system. For exterior piping arrangements, refer Fig. 44 for Direct Vent/2-Pipe system and Fig. 45 Non-Direct/I-Pipe system. vent vapors to for Extended termination require sealing with a corrosive resistance combustion products or shielding material due of building to corrosive ambient When Vent/2-Pipe of vent system. determining the following 1. Comply or Table System Only)" appropriate for termination, all clearance or termination vent vapors will not conditioning equipment. 3. Termination it will not by insulating stated consider in Table 8 damage be positioned plants/shrubs where or pipe as indicated in Table air pipe 10. diameter (direct design temperature required (used in load for your for exposed pipe temperature insulation thickness length(s). NOTE: kit should where Pipes combustion winter 3. Determine requirements Sidewall calculations), find appropriate application and furnace model. 9 per application. 2. Termination Exposed 2. Using guidelines: with be positioned vent/2-pipe system only) and vent pipe diameter, as stated above, using total pipe length and number of elbows. in this instruction. location kit should are not objectionable. 1. Determine NOTE: (Direct Vent/2-Pipe system ONLY). A factory accessory termination kit MUST be used. See section "Vent Termination Kit (Direct or termination of Sidewall combustion air pipe termination (direct vent/2-pipe system only) and vent pipe termination may be extended beyond area shown in Fig. 44 or in Fig. 45 per application in outside Roof termination is preferred since it is less susceptible to damage or contamination, and it has less visible vent vapors. Sidewall surfaces corners, nor by recirculation leaves, or light snow. located air Pipe pipe length as specified Vent Termination or termination kit should be positioned so that be affected by wind eddy, such as inside NOTE: Always latest version. 43 length in unconditioned (ft) specified spaces in Table Kit (Direct for maximum cannot exceed pipe total lengths allowable 13. Vent/2-Pipe refer to the instructions System Only) in termination kit for the Table 14 DIRECT VENT (2-PIPE) TERMINATION Vent Termination KIT Kit for Direct TERMINATION Vent/2-Pipe DIAM, OF COMBUSTION AIR AND VENT PIPES - IN (mm) SYSTEM 2-in. (51 mm) Concentric Vent Kit Single Penetration of Wall or Roof 3-in. (76 ram)Concentric Vent Kit Single Penetration of Wall or Roof 2-in. (51 ram)Termination Bracket Kit 2-Pipe Termination System 3-in. (76 ram) Termination Bracket Kit 2-Pipe Termination System Rool _ rmlnatlon System 1, 1 - 1/2, 2, or 2-1/2 2-1/2, 1, 1-1/2 2-1/2, (25, 38, 51,64 mm) 3 or 4 (64, 76, 102 mm) or 2 (25, 38, 51 mm) 3 or 4 (64, 76, 102 mm) (Preferred) At Feast 36 in (914mm) Con c_mtric V#nt and Combustion Roo f f_r ruination (preferred) Air .................. Vertical separation between combustion air and vent Maintain 12 in (3O5mm) min clearance above highest anticipatod snow level maximum of 24 i{I above roof "-,. Maintain 12 in (3O5mm)min clearance above ......... _ _go_ % vaen ................ i ............. A05090 Fig. 44 - Combustion Air and Vent Pipe Termination Roof Termination for Direct Vent (2-pipe) System (Preferred) .... I--.. Maintain 12 in 3O5mm " """ above highest anticipated snow [evel maximum of 24 _n (610ram) abov_ roof _. Abandoned masonry used as raceway (per code) "\\ overhang or roof whichever w_th Sha[ght Maintain 12 in _s greater P_pe (preferred) 3O5mm m[n[mu m c earance above highest anticipated s_qow level or grade "_Mchever _s greater Side wall termination w_th 2 elbows (preferred) \\\\\\\\\ A05091 Fig. 45 - Vent Pipe Termination for Non-Direct 44 Vent (1-pipe) System (Direct Vent/2-Pipe System ONLY) - When 2 or more 58MTB furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 44, but next vent termination must be at least 36 in. (914 mm) away from first 2 terminations. It is important that vent terminations be made as shown in Fig. 44 to avoid recirculation of flue gases. Combustion air and vent pipes MUST terminate outside structure. A factory accessory termination kit must be installed as shown in Table 14. termination NOTE: There are four options of vent/combustion kits available as shown in Table 14. Combustion air pipe must have the same air diameter as vent pipe. Concentric Vent/Combustion Vent/2-Pipe System Air Termination Determine an appropriate location for termination guidelines provided in section "Vent Termination: this instruction. 1. Cut one 4-in. (102 mm) diameter 3. Slide NOTE: inside assemble components assembled through kit Do not allow terminations with rain shield 4. Disassemble loose same procedures 5. Check required Termination guidelines provided this instruction. pipe dimensions Kit (Direct in section 1. Cut 2 holes, 1 for each size being used. through roof and cement pipe, System Termination: of appropriate 2. Loosely install elbow in bracket and place combustion-air pipe. Roof terminations - Loosely install pipe properly cut vent pipe. Coupling must bracket will mount as shown in Fig. 44. using making Only) kit using the General" in size for pipe assembly on coupling on be positioned so a U-fitting. Multi-venting When required The furnace, A/C, and humidifier drains may be combined and drained together. The A/C drain must have an external, field-supplied trap prior to the furnace drain connection. All drain connections (furnace, A/C, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible to prevent siphoning of the equipment's drain. in Fig. 44. dimensions as shown using See Fig. 46 for example of possible field drain attachment using 1/2-in. (13 mm) CPVC or PVC tee for vent and A/C or humidifier drain connection. in Fig. 44. and Vent Terminations 2 or more 58MTB Furnaces each furnace must be individually or breach vent 58MTB furnaces. are vented vented. intermittent Furnace condensate is mildly acidic, typically in the pH range of 3.2 to 4.5. Due to corrosive nature of this condensate, a condensate pH neutralizing filter may be desired. Check with local authorities to determine if a pH neutralizer is required. APPLICATION A 180 ° U-fitting 3. Disassemble loose pipe fittings. Clean and cement same procedures as used for system piping. 4. Check in When a condensate pump is required, select a pump which is approved for condensing furnace applications. To avoid condensate spillage, select a pump with an overflow switch. Sidewall terminations - Install bracket as shown in Fig. 44. For applications using vent pipe option indicated by dashed lines in Fig. 44, rotate vent elbow 90 ° from shown result The field drain connection (condensate trap or drain tube coupling) is sized for 1/2-in. (13 mm) CPVC, 1/2-in. (13 mm) PVC, or 5/8-in. (16 mm) ID tube connection. Drain pipe and fittings must conform to ANSI standards and ASTM D1785, D2466 or D2846. CPVC or PVC cement must conform to ASTM D2564 or F493. Primer must conform to ASTM F656. In Canada, use CSA or ULC listed schedule 40 CPVC or PVC drain pipe, fittings, and cement. For applications using combustion-air pipe option, indicated by dashed lines in Fig. 44, install 90 ° street elbow into 90 ° elbow, may be used. may An external trap is not required when connecting the field drain to this condensate trap. in Fig. 44. for termination "Vent caution Condensate trap is shipped installed in the blower shelf and factory connected for UPFLOW applications. Condensate trap must be RELOCATED for use in DOWNFLOW and HORIZONTAL applications. to piping. Vent/2-Pipe location this Condensate trap MUST be used for all applications. Clean as shown OPERATE GENERAL hole. in Fig. 44. fittings. NOT Unit must not be installed, operated, and then turned off and left in an unoccupied structure during cold weather when temperature drops to 32°F (0°C) and below unless drain trap and drain line have adequate freeze protection. See Service and Maintenance Instructions for winterizing procedure. air in kit. Locate assembly through positioned no more than 1-in. (25 as used for system an appropriate position Drain to accumulate it through - Locate assembly as shown in Fig. 44. MAY Failure to follow unit operation. REMOVED or other materials from wall as shown Determine vent/combustion using instructions rainshield when installing Roof terminations appropriate height Two-Pipe (51 mm) hole for 3-in. (76 mm) with insulation of pipe assembly mm) concentric together UNIT hole. Sidewall sidewall 11 - Condensate kit using the General" in hole for 2-in. kit, or one 5-in. (127 mm) diameter kit. 2. Loosely termination Step Kit (Direct Only) near each NEVER common other, Outdoor draining of the furnace is permissible if allowed by local codes. Caution should be taken when freezing. Ambient may freeze drain pipe and prohibit draining. vent 45 __/ \__ CONDENSATE PIPE FOR A/C OR HUMIDIFIER OPEN STAND/ DRAIN WIRE (3 WRAPS TIE HEAT MINIMUM) A94054 Fig. 46 - Example of Field Drain Attachment A93036 Fig. 47 - Condensate Trap Heat Tape Step 1 - General PERSONAL INJURY The furnace must have a 115-v power and grounded. HAZARD Caution should be taken to prevent draining conditions may cause personal injuries. Excessive conditions condensate draining may which could result in damage where slippery cause saturated to plants. soil NOTE: Proper maintained for 115-v wiring. indicator light will flash rapidly Thermostat line may If freeze required 2-stage cooling, protection is required, use condensate freeze protection accessory or equivalent 3 to 6 watt per ft at 120-v and 40°F (4°C) self-regulating, shielded, and waterproof heat tape. See Installation Instructions supplied manufacturer's recommendations. with 1. Fold heat tape in half and wrap 2. Locate heat tape between accessory on itself or heat made tape 3 times. sides of condensate trap positioned in notches heat tape in place. Wire of condensate sides. trap back. ties can be (See approximately 5. When using manufacturer's drain pipe 1 wrap with remaining heat tape, per ft. field-supplied instructions heat tape, follow heat tape for all other installation guidelines. START-UP ADJUSTMENT SAFETY CHECK FURNACE MAY NOT wire for gas connections heating must control be status will not operate. 0.5 psig (14-in. at R and W/W1 operation. connected W2 must wc), are the minimum be connected for heating thermostats. COM, Y/Y2, and G are required for heat pumps, and some clock thermostats. These must be at the 24-v terminal block on the control. This furnace can be installed a 2-stage heating thermostat. with either For single-stage connect and Table field grounding is incorrect, and the furnace thermostats, low- and high-gas heat for optimum (SW-1) must be in the factory-shipped Fig. 47.) 4. Wrap proper properly (See Fig. 37.) a single-stage thermostat heating or W to W/W1 at furnace control terminal block. (See Fig. 31 and 50H.) For single-stage thermostats, the control will determine, based on length of previous heating on and off cycles, when to operate in (See Fig. 47.) 3. Use wire ties to secure and If polarity Natural gas service pressure must not exceed and be no less than 0.16 psig (4.5-in. wc). CONDENSATE DRAIN PROTECTION Freezing condensate left in condensate trap and drain cause cracks, and possible water damage may occur. polarity supply AND OPERATE Failure to follow this caution may result in furnace operation stopping and water pipes freezing during cold weather. Furnace control must be grounded for proper operation, or control will lockout. Control is grounded through green/yellow wire connected to gas valve C-terminal and burner box screw. 46 11 and 12 for setup switch comfort. Setup switch-1 OFF position. See Fig. 36 information. FIRE HAZARD Failure to follow this caution may result operation or performance satisfaction. in intermittent unit This furnace is equipped with a manual reset limit switch in the burner box area. The switch will open and shut off power to the gas valve if a flame rollout or overheating condition occurs in the burner enclosure area. DO NOT bypass the switch. Correct inadequate combustion-air supply, component failure, or restricted flue gas passageway before resetting the switch. Step 2 - Prime Condensate \ UNIT MAY NOT Trap With Water OPERATE Failure to follow this caution may result operation or performance satisfaction. Housing Drain Tube unit Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap. A99118 Fig. 48 - Inducer in intermittent Cap If a 2-stage heating thermostat is to be used, move SW-1 to ON position at end of furnace installation. This overrides built-in 1. Remove upper Fig. 48.) inducer housing drain connection cap. (See control process for selecting high and low fire and allows the 2-stage thermostat to select gas heating modes. The W2 from thermostat must be connected to W2 on control terminal block. 2. Connect field-supplied 1/2-in. (13 mm) ID tube to upper inducer housing drain connection. (See Fig. 32 and 50-57.) 3. Insert field-supplied 4. Pour 1 quart Before operating furnace, check each flame rollout manual reset switch for continuity. If necessary, press and release button reset switch. The blower compartment door must be in place complete the l15-v circuit to to through inducer flow into open to the furnace. funnel of water into housing, into tube. funnel/tube. overfill field drain. Water should run condensate trap, and (See Fig. 49.) 5. Remove funnel and tube from inducer drain connection cap and clamp. Step 3 - Purge housing and replace Gas Lines After all connections check for leaks. have been FIRE AND EXPLOSION made, purge the gas lines and HAZARD Failure to follow this warning personal injury, or death. could result in a fire, explosion, never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in "Gas Piping" and "Start-up Adjustment, and Safety Check" sections of these instructions. Step 4 - Sequence Using schematic operation through very carefully. NOTE: A99119 Fig. 49 - Filling Condensate Trap or W/W1 selected blower thermostat flash interruption occurs and W2), the control off delay is still calling code 12 during continuous furnace diagram in Fig. 36, follow the sequence of the different modes. Read and follow diagram If power (W/W1 of Operation period power for gas heating. this period, as long as no faults will respond after during after which are detected. to the thermostat "call for will run the blower heat" for the is restored, The amber if the LED will the LED will be ON After this period, the normally. The blower door must be installed for power to be conducted through blower door interlock switch ILK to furnace control 47 CPU,transformer BLWM, TRAN, hot surface TWO-STAGE inducer igniter HEATING THERMOSTAT WITH (ADAPTIVE (See Fig. 31 for thermostat NOTE: low-heat-only mode OFF, in response This furnace can operate blower motor control three GV. SINGLE-STAGE SEC1 SW-1, when ON, selects or either adaptive the furnace or SEC2 to the furnace heating high speed with a single-stage until flame 5. Blower-On thermostat because furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low-gas- Delay motor BLWM opened. heat or high-gas-heat operation. This selection is based upon the stored history of the length of previous gas heating on/off periods of the single-stage thermostat. is no longer - If burner is energized Low-heat - The blower HEAT speed. proved. flame motor BLWM low-gas heat on time (from 0 to 16 minutes) before switching to high-heat. is energized and remains energized motor BLWM is energized. If power happens, 6. Switching is interrupted, the stored history is erased. When this the control CPU will initially select low-heat for up to control furnace 16 minutes and then switch to high-heat, as long as the thermostat continues to "call for heat." Subsequent selection is based on stored history of thermostat cycle times. When wall thermostat The furnace control "calls for heat", performs R-W/W1 a self check, circuit verifies and high-heat pressure switch contacts LPS and HPS and starts inducer motor IDM in high speed. 1. Inducer Prepurge Period selects low-heat operation up to speed, the furnace period. furnace - If the furnace control CPU the inducer motor IDM comes the low-heat pressure control CPU begins After the low-heat control CPU will period, and high-speed. continue are open, motor IDM low-heat operate pressure switch at low-heat gas pressure switch after ignition. closes for of warm-up seconds begins. flame period is sensed begins. 4. Flame-Proving flame-proving IDM switches and the furnace the 2-second flame CPU begins the blower-ON switch When pressure gas valve solenoid BLWM will switch the furnace control - The control CPU - When the thermostat de-energizing is satisfied, the gas the valve energized for a 15-second post-purge motor BLWM and air cleaner terminal remain energized for 90, 120, 150, on selection at blower-OFF control CPU is factory-set or 180 seconds delay switches). for a 120-second delay. HEATING WITH TWO-STAGE (NON-ADAPTIVE for thermostat the low-heat In this mode, the low-heat only operation R-to-W1 circuits period. EAC-1 circuit. always HEATING connections). only switch mode Closing causes of the low-heat-only MODE) in response the high-heat must be ON to to closing thermostat operation, the R-to-W1 regardless of switch. for heat", closing the R to W1 circuit the R to W1 and-W2 circuits for high-heat. The furnace control performs a self-check, verifies the low-heat and high-heat pressure switch contacts LPS and HPS are open, and starts the inducer motor IDM in high-speed. The start-up and shutdown functions and delays described in except for item 1 above apply to 2-stage heating mode as well, switching from low-to high-heat and vice versa. proving 1. Switching From Low- To High-Heat - If the thermostat R to W1 circuit is closed and the R to W2 circuit closes, the furnace control CPU will switch the inducer motor - When burner flame is proved at the sensor electrode FSE, the inducer motor to low-speed unless running at high-speed, control high-heat is opened, The wall thermostat "calls for low-heat or closing warm-up closes, a 2-second flame period will remain energized until the or until - If the furnace to high-heat. NOTE: and-W2 The gas valve GV permits gas flow to the burners it is ignited by the Hot Surface Igniter HSI. Five after the GVR The HIS igniter the To Low-Heat (See Fig. 32 and 50-56 thermostat period is completed the main gas valve relay contacts GVR close to energize the gas valve GV, the gas valve opens. where delay THERMOSTAT 2 minutes the igniter High- circuit blower-OFF the setting - When available low-heat TWO-STAGE the the - At end of the inducer prepurge period, Igniter HSI is energized for a 17-sec Sequence is from From (depending The furnace period. 3. Trial-For-Ignition as the blower The high-heat pressure to close the NC contact. CPU switches will closes, the furnace will rate until the high-heat a maximum To High-Heat and the high-heat The blower motor five seconds after will remain The blower select 2. IgniterWarm-Up the Hot Surface igniter LPS flow at LO GV-M, stopping gas flow to the burners, and de-energizing the humidifier terminal HUM. The inducer motor IDM the high-heat pressure switch HPS closes, and the high-heat gas valve solenoid GV-HI is energized. The furnace control CPU begins a 15-second prepurge period pressure switch LPS closes. If switch HPS fails to close and pressure R to W high-heat pressure switch relay HPSR is de-energized to close the NC contact. When sufficient pressure is available low-heat pressure Low- as long switch HPS closes, GV-HI is energized. to HI HEAT speed 8. Blower-Off at If the furnace control CPU selects high-heat operation, the inducer motor IDM remains running at high-speed, and the after the high-heat is energized is will not switch from high-heat to low-heat while the thermostat R-to-W circuit is closed when a single-stage thermostat is used. switch LPS closes, and a 15-second prepurge the inducer From 7. Switching pressure switch re-closes the begin a 15-second prepurge to run GV-M CPU switches from low-heat to high-heat, the control CPU will switch the inducer motor IDM sufficient closes. the blower BLWM is energized at HI HEAT speed. the electronic air cleaner terminal EAC-1 speed from low to high. relay HPSR is de-energized the low-heat is proven 66 sec after gas valve Hi-heat - The Simultaneously, is permitted CPU (not at W/Wl, when flame should not be CPU will lock out of the inducer motor IDM on The furnace will start up in either low-or high-gas heat. If the furnace starts up in low-gas heat, the control CPU determines the which sequence for up to before going to control G, R, etc.). If flame is proved present, the furnace control Gas-Heating mode and operate to a call for heat. (See Fig. 37.) as a 2-stage CPU will repeat the ignition more Trials-For-Ignition Ignition-Lockout. Lockout will be reset automatically after three hours, by momentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power at MODE) switch, operation IDM, connections.) Low-heat-only mode when motor HSI, and gas valve IDM speed from low to high. The switch relay HPSR is de-energized delay contact. period and continues to hold the gas valve GV-M open. If the burner flame is not proved within two seconds, the control CPU will close the gas valve GV-M, and the 48 When sufficient pressure pressure switch HPS closes, solenoid GV-HI is energized. high-heat to close is available the high-heat and the high-heat The blower pressure the NC motor gas valve BLWM willswitch toHIHEAT speed fiveseconds aftertheRto W2circuit closes. 2.Switching From High-To Low-Heat - If the thermostat R G-and-Yl-and-Y/Y2 motor to W2 circuit opens, and the R to Wl circuit remains closed, the furnace control CPU will switch the inducer motor IDM speed from high to low. The high-heat pressure switch relay HPSR is energized to open the NC contact and de-energize the high-heat gas valve COOLING 1. Single-Speed solenoid terminal seconds. opens. EAC-1 control The outdoor motor BLWM additional will continue to 5 seconds. 2. Two-Speed Cooling (Adaptive cooling This furnace includes for thermostat can operate single-stage The the cool- Thermostat thermostat because which operation. This selection the length thermostat. of previous the furnace adaptive selects cooling sequence low-cooling is based cooling control CPU history the EAC-1 Jumper high-cooling upon the stored to enable relay disable seconds. of the adaptive cooling mode ACRDJ is satisfied, unit staging. must in response (See Fig. 37.) switch the outdoor either low-or the furnace control CPU high-cooling. control CPU to unit can start up the cooling If starting determines on-time (from 0 to 20 minutes) switching to high-cooling. to If the power is interrupted, unit in is permitted before The the stored history is erased will YI is satisfied, the R-to-G-and-Yl circuits are opened. The blower BLWM and electronic remain energized for an to DHUM to reduce the for Thermidistat cooling operation with a Thermidistat. and described motor BLWM (same speed is based speed, on stored and the R to G-and-Yl starts the furnace blower motor (same speed as LO HEAT). BLWM at low-cool R-to additional 90 seconds. cooling off-delay to 5 the DHUM is removed should DHUM. input is from the the DHUM input logic is ON when no dehumidify by the furnace control on circuits speed If the furnace control CPU switches from low-cooling to high-cooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the R to Yl-and-Y2 circuits switch the outdoor unit to high-cooling speed, and the R to 49 above the R to G-and-Yl a demand The wall thermostat "calls for cooling", closing the R to G-and-Y circuits. The R to YI circuit starts the outdoor unit on low-cooling or outdoor unit stops, air cleaner terminal connections.) The exceptions ACR to energize the Y/Y2 terminal and switch the outdoor unit to high-cooling, as long as the thermostat continues to call for cooling. Subsequent selection history of the thermostat cycle times. with MODE a. When control CPU will select and then energize the start the (See Fig. 37.) low-cooling for up to air conditioning relay the furnace 20 minutes for the DHUM input, the furnace control operates in Thermidistat mode. If the DHUM input is low or OFF for more than 48 hours, the furnace control reverts back to non-Thermidistat mode. up in low-cooling, the low-cooling which circuits The dehumidification output, DHUM on the Thermidistat be connected to the furnace control thermostat terminal high-cooling. The furnace for low- circuits The R to YI circuit starts the outdoor unit on speed, and the R to G-and-Yl circuit starts the DHUM input terminal. In other words, reversed. The DHUM input is turned demand exists. Once 24 vac is detected and circuits the R to G-and-Yl-and-Y2 energize terminal to Thermostat the R to G-and-Yl When there is a dehumidify demand, activated, which means 24 vac signal Y/Y2 R (See Fig. 37.) a call for cooling. (See Fig. 32.) When in place the furnace control CPU can turn on the air conditioning relay ACR to the the The outdoor unit stops, and and electronic air cleaner and Two-Stage closes THERMIDISTAT of the single-stage jumper Cooling thermostat (See Fig. 50-53 The air conditioning thermostat to 5 seconds. or closes G-and-Yl-and-Y2 and the furnace a of controlled or period with as on at The electronic air cleaner terminal EAC-1 is energized 115 vac whenever the blower motor BLWM is operating. When unit the high-cooling speed, and the R to G-and-Y/Y2 furnace blower motor BLWM on COOL speed. connections.) a two-speed a programmed operation, be connected on COOL speed for an Single-Stage back furnace blower motor BLWM on low-cool speed (same speed as LO-HEAT). R-to-Yl-and-Y2 circuits start the outdoor unit on blower (See Fig. 37.) and speed comes EAC-1 will remain energized for an additional 90 Jumper YI to DHUM to reduce the cooling high-cooling. low-cooling Mode) (See Fig. 31 and 50-57 NOTE: operating 90 sec. Jumper Y/Y2 to DHUM to reduce ing off-delay When of the outdoor is ener- unit will stop, and furnace (same the the air cleaner terminal EAC-1 is energized whenever the blower motor BLWM is The thermostat gized with 115-v when blower motor BLWM is operating. When the thermostat is satisfied, the R-to-G-and-Y circuits are opened. blower (See Fig. 32 and Fig. 50-56 for thermostat connections) NOTE: The ACRDJ must be disconnected to allow thermostat Cooling terminal speed unit compressor G-and-Y circuit are opened. the furnace blower BLWM 3. Two-Speed air cleaner at low-cool the outdoor operating. for cooling". The electronic to run until The electronic with 115 vac (See Fig. 31 or 32 and 50, 52, or 54 for thermostat connections.) The thermostat closes R-to-G-and-Y circuits. The Rto-Y circuit starts the outdoor unit, and R-to-G-and-Y/Y2 circuits start the furnace blower motor BLWM on COOL speed. furnace continues LO-HEAT) high speed. off-delay "calls the BLWM MODE The thermostat switch speed. When transitioning from low-cooling to high-cooling unit compressor will shutdown for 1 minute while long as the low-heat pressure switch LPS remains closed. The blower motor BLWM will switch to LO HEAT speed after the R to W2 circuit circuits to COOL NOTE: outdoor GV-HI. When the inducer motor IDM reduces pressure sufficiently, the high-heat pressure switch HPS will open. The gas valve solenoid GV-M will remain energized as five seconds BLWM circuit for dehumidification, will continue as LO HEAT). also applies to operation are listed below: is closed the furnace running and there is blower at low-cool speed THERMIDISTAT THERMIDISTAT HEAT STAGE TWO-STAGE FURNACE 2 I_- NOTE 11 _1_ RVS HEAT STAGE 1 I_-_ COOL STAGE 1 __ FAN _l F_ 24 VAC HOT __ DEHUMIDIFY I_0__ SINGLE-SPEED HEAT PUMP 1 F_q -l_q ___ -l_-- ........ -l_q -l_q -p_ N/A I_ TWO-STAGE FURNACE SINGLE-SPEED AIR CONDITIONER COOLING_ NOTE 11 HEATSTAGE3_ (FURNACEHI) HEAT STAGE 2 [_ (FURNACE LO) HEAT/COOL STAGE 1 (COMPRESSOR) C_ FAN 1_ 24 VAC HOT 1_ DEHUMIDIFY [_ 24 VAC COMM __ 24 VAC COMM [_ 1 HUM ........ I I_ HUM HUMIDIFY [_0__ _ ........ z_ HUMIDIFIER(24 VAC) I_L---i HUMIDIFY '_ { HUMIDIFIER (24 VAC) ] _ i N/A I_ N/A [_ Os%_OO __-l_q - ........ _ OUTDOORsENSOR _{ i i CONNECT,ON Ll_q- OUTDOOR SENSOR _, CONNECT,ON [_ See notes 2, 5, 7, 10, and 11 See notes 1, 2, 4, 6, 7, 9, 10, 11, and 15 A00275 A00277 Fig. 50 - Two-Stage Furnace with Single-Speed Air Conditioner THERMIDISTAT NOTE HEAT STAGE COOL STAGE 1 _. HEAT 1 IW_-. STAGE Heat Pump TWO-STAGE TWO-SPEED FURNACE AIR CONDITIONER -I_ I_F. TWO-STAGE FURNACE TWO-SPEED HEAT PUMP --- HEAT STAGE 3 _. (FURNACE) _ NOTE 12 HEAT/COOL STAGE 2 _. (COMPRESSOR HI) 24 VAC HOT I_F. 24 VAC COMM Fuel) RVS COOLING FAN I_F. I_0_. (Dual THERMIDISTAT -F_q with Single-Speed 12 2 I_. DEHUMIDIFY Furnace HEAT/COOL STAGE 1 _. (COMPRESSOR LO) NOTE COOL STAGE 11 2 I_-. Fig. 52 - Two-Stage -I_F -24 VAC FAN [_. HOT [_. DEHUMIDIFY 24 VAC [_ COMM I_ FI HUM [_ HUM ........ HUMIDIFY I_MI HUMIDIFIER (24 VAC) _. ____ HUMIDIFY[_ ............... _!_ HUMIDIFIER(24 VAC) k _q! --_i N/A I_ N/A [_ OUTDOOR SENSOR Os_T_OO __-r_h • CONNECT,ON Ll_h i CON.EOT,ON L_ See notes 2, 5, 8, 10, 11, and 12 See notes1, 2, 3, 4, 6, & 9,10,12,13, A00276 Fig. 51 - Two-Stage Furnace Air Conditioner and15 A00278 with Two-Speed Fig. 53 - Two-Stage Furnace Heat Pump 50 (Dual with Two-Speed Fuel) DUAL FUEL THERMOSTAT RVS TWO-STAGE FURNACE TWO-STAGE THERMOSTAT SINGLE-SPEED HEAT PUMP NOTE 11 COOLING NOTE [_- 11 HEAT STAGE 3 (FURNACE HI) I qI qI qI qI q- HEAT STAGE 2 (FURNACE LO) HEAT/COOL STAGE 1 (COMPRESSOR) C_ E2_ FAN 24 VAC 24 VAC HOT TWO-STAGE FURNACE [_ TWO-SPEED AIR CONDITIONER -F q -i q NOTE 12 -F_ --- -I q COMM N/A RVS SENSING I HUM [_ I °s_T#°° __E?!_ OUTDOOR SENSOR CONNECT,ON LE2_ See notes HUM _ See notes 2, 11, and 12 1, 2, 4, 1 t, 14, 15, and t 6 A00279 Fig. 54 - Dual Fuel Thermostat with Two-Stage Single-Speed Heat DUAL FUEL THERMOSTAT RVS Furnace A00281 and Fig. 56 - Two-Stage Pump Thermostat and Two-Speed TWO-STAGE FURNACE TWO-SPEED HEAT PUMP SINGLE-STAGE THERMOSTAT with Two-Stage Furnace Air Conditioner TWO-STAGE FURNACE TWO-SPEED AIR CONDITIONER COOLING E2_ HEAT/COOL STAGE 1 (COMPRESSOR LO) HEAT STAGE 3 (FURNACE) NOTE 12 HEAT/COOL STAGE 2 (COMPRESSOR HI) [_ C_ E2_ [_ I FAN 24 VAC 24 MAC HOT -I q IW31 COMM N/A RVS SENSING HUM [_ I OUTDOOR SENSOR HUM _jZ_, See note 2 CONNECT'ON i_ See notes I, 2, 3, 4, I2, 13, 14, 15, and I7 A00280 Fig. 55 - Dual Fuel Thermostat Two-Speed with Two-Stage Furnace A00262 and Fig. 57 - Single-Stage Heat Pump Thermostat and Two-Speed 51 with Two-Stage Air Conditioner Furnace NOTES 1. Heat pump MUST 2. Refer to outdoor 3. Select the "ZONE" 4. Outdoor have a high pressure equipment Installation position Air Temperature switch Sensor for dual fuel applications. Instructions on the two-speed FOR FIG. 50-57: for additional heat pump must be attached should be set in OFF 6. Dip switch No. 1 on Thermidistat should be set in ON position 7. Dip switch No. 2 on Thermidistat This is factory default. should be set in OFF 8. Dip switch should be set in ON position Option 10. NO connection No. 10 "Dual should Fuel Selection" be made to the furnace HUM dip switch 12. Optional connection. If wire is connected, to control outdoor unit staging. ACRDJ must control 14. The RVS Sensing its own high-stage terminal "L" should heating 17. Dip switch D on Dual Fuel Thermostat D on Dual Fuel Thermostat terminal not be connected. should for two-speed installations. compressor compressor operation. operation. using a Thermidistat. control should be set in ON position on furnace control should via furnace control algorithm. This is internally or "BALANCE Fuel Thermostat. be removed option for two-speed compressor Thermidistat/ default. operation. on the two-speed for single-speed to allow to allow Thermidistat/Thermostat This is factory used to sense defrost POINT" position be set in ON position 52 default. ON in all dual fuel applications. when be set in OFF This is factory installations. for single-speed No. 1 on furnace operation should for air conditioner for heat pump position jumper 15. DO NOT SELECT the "FURNACE INTERFACE" This is controlled internally by the Thermidistat/Dual 16. Dip switch default. position must be turned 11. Optional connection. If wire is connected, Thermostat to control furnace staging. 13. Furnace procedure. in all dual fuel applications. No. 1 on Thermidistat 9. Configuration and setup control. 5. Dip switch No. 2 on Thermidistat information compressor operation. heat pump operation. control This board. is factory b.When theRtoG-and Y/Y2circuitisclosed andthere isademand fordehumidification, thefurnace blower motor BLWM willdroptheblower speed fromCOOL toHIHEAT foramaximum of10minutes before reverting backtoCOOL speed. If there isstilla demand fordehumidification after20minutes, the furnace control CPUwilldroptheblower speed back toHIHEAT speed. Thisalternating 10-minute cycle willcontinue aslongasthere isacallforcooling. c.When the:'callforcooling" issatisfied andthere isa demand fordehumidification, thecooling blower-off delay isdecreased from90seconds to5seconds. CONTINUOUS When motor BLOWER on for the selected blower-OFF delay period. If the R-to W/Wl-and-Y1 signals disappear, leaving the G signal, the blower motor BLWM will remain on for the selected blower-OFF delay at COOL speed. motor delay period before When reverting the thermostat BLWM will switch to continuous-blower :'calls for low-cooling", to operate at low-cool (same speed :'calls for high-cooling", at COOL speed. When the R to G circuit continue function is opened, Continuous Blower Speed Selection NOTE: motor from is operating. The furnace if no as CPU will helps failure. The energized, blower the furnace motor BLWM control shift 1. Remove the at low cool quick- longer disappear motor connect for safety reasons. is energized. This in case of a component will not operate if any and not until all time delays If TEST/TWIN door switch. on control and motor rapidly for 2-stage previous starts LED furnace 53 off. is as follows: on high-speed is energized component code 4 times. and continues to test sequence. for 15 sec, then off. d. Blower motor operates on LO-HEAT speed for 10 sec. e. Blower motor operates on HI-HEAT speed for 10 sec. f. Blower motor operates on COOL g. Inducer motor goes to low-speed speed for 10 sec. for 10 sec, then stops. 5. Reconnect R lead to furnace control, remove blower door switch, and re-install blower door. will remain turns are jumpered and ignore status Step g of component igniter until COM-24V (5 mm) (See Fig. 37.) COM-24V terminals will flash test sequence control. 2 sec, short (jumper) the to the TEST/TWIN 3/16-in. from terminals. than 2 sec, LED c. Hot surface as LO door. R lead from furnace terminal jumper run until to or turn on the BLWM access thermostat b. Inducer input signal disappears, the furnace control begins a inducer post-purge period and the blower remains running HEAT speed. If the R-to-W/Wl-and-Yl-and-G signals at the same time, the blower all and Self-Test: a. LED will display HEAT), and begin a low-heat cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 seconds then come back on at LO HEAT speed. When the W/W1 normal at LO allows the gas valve blower feature at control close blower Remove the R to circuits are speed when problem test 4. For approximately terminal on control the furnace control to avoid long blower (same a system blower 3. Manually Component speed test except SHOCK HAZARD 2. Disconnect connections) CPU will switch component time; Blower access panel door switch opens 115-v power to control board. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. - To test request. When or G the Failure to follow this warning could result in electrical shock, personal injury, or death. will PUMP defrost cycles. W/Wl-and-Yl-and-G W/WI-and-Y/Y2 disappear, leaving are not energized is present ELECTRICAL HEAT off times during demand W/Wl-and-Y1 or R to the furnace will remain on for the selected then switch to continuous- control component Component NOTE: pump, sequence R-to signals is energized diagnose signal selection can be changed as many times as desired and is stored in the memory to be automatically used following a power interruption. When installed with a heat automatically changes the timing disappears, 90 to at the thermostat will shift the continuous-blower speed from HI HEAT to COOL. Repeating the procedure will shift the continuous-blower speed from COOL to LO HEAT speed. The for thermostat signal the HUM terminal feature To Begin continuousblower speed from the factory setting of LO HEAT to HI HEAT speed. Momentarily turning off the FAN switch again (See Fig. 50 C-F motor disappear at the same time, the blower remain on for the selected blower-OFF furnace terminal thermostat other Thermostat control input to run for a short The EAC-1 select different continuous-blower speeds from the room thermostat, momentarily turn off the FAN switch or push-button on the room thermostat for 1 - 3 seconds after the blower motor BLWM The blower the end of the prepurge period, then come back on at HI HEAT are completed. BLWM 5 seconds, operation. cycle. furnace BLWM SELF-TEST The components the blower motor the thermostat is the blower operating for an additional requires blower motor BLWM the W/W1 COMPONENT motor speed satisfied, the blower motor BLWM will operate an additional seconds on COOL speed before reverting back continuous-blower speed. When a high-heat signal, the blower motor BLWM blowerOFF delay period blower speed. motor LO HEAT). When the thermostat is satisfied, the blower BLWM will operate an additional 90 seconds on low-cool before reverting back to continuous-blower speed. When the thermostat BLWM will operate When humidifier the blower and begin delay period. If R-to-W/Wl-and-Yl-and-Y/Y2 speed. speed speed, Y/Y2-and-G signals motor BLWM will BLWM will stop during igniter (7 seconds), and blower-ON In high-heat, the furnace control CPU will hold the blower BLWM at HI HEAT speed during the selected blower-OFF speed. R-to-W/Wl-andor R-to-W/W1- control begins a normal inducer post-purge period and the blower switches to COOL speed after a 3 second delay. If the R-to-W/Wl-and-Y/Y2-and-G or R-to W/Wl-and-Yl-and- set to LO HEAT, HI HEAT, or COOL speed). Factory default is LO HEAT speed. Terminal EAC-1 is energized as long as the blower motor BLWM is energized. to heat delay to continuous-blower R-to W/WI-and-Y/Y2, R-to W/Wl-and-Yl-and-Y/Y2, BLWM will remain on until then shut off for 24 seconds the R to G circuit is closed by the thermostat, the blower BLWM will operate on continuous-blower speed (can be delay (66 seconds), allowing the furnace heat exchangers up more quickly, then restarts at the end of the blower-ON period at LO HEAT or HI HEAT speed respectively. then switch and-Yl-andY/Y2-and-G circuits are energized the control CPU will switch to or turn on the blower motor MODE During a call for heat, the blower warm-up (17 seconds), ignition period When the Y/Y2-and-G, tape from 6.Operate furnace perinstruction onouter door. 7.Verifyfurnace shutdownbylowering thermostat setting below roomtemperature. 8.Verifythatfurnace restarts by raising thermostat setting above roomtemperature. OPERATE operating instructions label attached d. Jumper control temperature above room altitudes input rate up to 2000 In the U.S.A., 1.3-in. rating plate is for installations pressure at obtain ft. (610 M). the input M) must be reduced sea level. ratings for altitudes by 2 percent for each above 2000 manifold Furnace input pressure to obtain rate must be within Pressure For Correct average UNIT Failure furnace Orifice of input Size And Manifold gas specific (at installed gravity from local gas altitudes altitudes (in) to increase NOT set wc or more than is outside pressure low-heat connections on input rate. manifold 1.7-in. pressure wc for natural this range, change main less than gas. If manifold burner orifices to to life. HAZARD follow this size. aligned orifice of 2001 of 2001 to 4500 to 3000 ft. (610 ft (610 Never caution redrill may e. Find closest natural on Table 15. gas heat value f. Move setup completing g. Jumper result in reduced switch to 1372 A burr-free for proper flame gravity NOTE: 3.2-in. pressure obtain operation. DO NOT is outside connections furnace high-heat manifold pressure wc for natural this range, change in this range. i. When correct input on in rate rate. than 3.8-in. pressure locked screw (3/32 hex Allen (out) to decrease input (in) to increase set after adjustment. R and W1 and W2 thermostat wc or more and squarely characteristics. SW-1 to OFF position low-heat h. Turn high-heat adjusting wrench) counterclockwise f. Follow heat value and specific gravity lines to point of intersection to find orifice size and manifold pressure for proper or it is suspected to have a numbered drill bit of control. (See Fig. 37.) This keeps high-heat operation. to 914 M) in and specific an orifice. hole is essential or clockwise settings to ON in this range. DAMAGE correct 20,000/13,000 (High/Low) Btuh per burner. d. Find installation altitude in Table 15. For Canada DO NOTE: If orifice hole appears damaged been redrilled, check orifice hole with altitude) supplier. M), use U.S.A. Table 15. center in low-heat DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures. on furnace c. Verify furnace model and size. Table 15 can only be used for model 58MTB furnaces with heating inputs of NOTE: locked Input. a. Obtain average gas heat value from local gas supplier. b. Obtain furnace fl (610 input rate. - 2 percent rating plate adjusted for altitude. 1. Determine Natural Gas SW-1 on control 1000 ft. (305 M) above In Canada, the input ratings must be derated by 5 percent for altitudes of 2001 fi to 4500 fl (610 to 1372 M)above sea level. Adjust switch R and W/WI thermostat to start furnace. clock-wise NOTE: on with e. Turn low-heat adjusting screw (3/32 hex Allen wrench) counterclockwise (out) to decrease input rate or Step 5 - Adjustments SET GAS INPUT RATE gas be measured (See Fig. 58.) setup position. This keeps operation. RESTART With furnace operating, set thermostat below room and observe that furnace goes off. Set thermostat temperature and observe that furnace restarts. Furnace regulators. c. Move on always b. Remove regulator seal caps that conceal adjustment screws for low-and high-heat gas valve pressure FURNACE Follow procedures to furnace. FURNACE NOTE: Manifold pressure MUST burner enclosure front REMOVED. is obtained, main less than gas. If manifold burner replace orifices caps that conceal gas valve regulator adjustment screws. Main burner flame should be clear blue, almost transparent. EXAMPLE: (0 - 2000 ft (0-610 M) altitude using Table 15) (See Fig. 59.) Heating value = 1050 Btu/cu fi j. Remove jumper R-to-W1 and W2. Specific gravity = 0.62 Therefore: Orifice No. 45 Manifold pressure 3.6-in. wc for high heat 1.5-in. wc for low heat UNIT DO NOT out-of-round misdirection g. Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE; ALWAYS CHECK AND VERIFY. Manifold a. Remove burner Pressure To Obtain enclosure HAZARD Failure to follow this caution may result in component damage due to flame impingement of burners and heat exchangers. * Furnace is shipped with No. 45 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain the proper input rate. 2. Adjust DAMAGE Input Rate. front. 54 redrill orifices. Improper holes, etc.) can cause excessive of burner flames. (See Fig. 60.) drilling (burrs, burner noise and to Table 15 - Model 58MTB Orifice Size and High/Low-Heat for Use with 060 Through (Tabulated Derated Data Based 2 Percent on 20,000/13,000 for Each 1000 t_ "o t_ o t_ 0 to 2000 (0 to 61O) 0% derate AVG GAS HEAT VALUE (BTU/CU FT) 0.58 U,S, t_ o "o <. Altitudes 2001 to 3000 (610 to 914) or Canada Altitudes 2001 to 4500 (610 to 1371) 5% derate _>, • ,_. ::5 3001 to 4000 (914 to 1219) 7% derate Inputs Sea Level)* GRAVITY OF NATURAL GAS 0.62 0.64 Orifice no. Manifold Pressure Orifice no. Manifold Pressure Orifice no. Manifold Pressure Orifice no. 850 43 3.7/1.5 43 3.8/1.6 42 3.2/1.4 875 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6 900 44 3.7/1.6 43 3.4/1.4 43 925 44 3.5/1.5 44 3.7/1.6 950 44 3.4/1.4 44 975 44 3.2/1.3 1000 45 1025 0.66 Manifold Pressure Orifice no. Manifold Pressure 42 3.3/1.4 42 3.4/1.4 43 3.8/12.6 42 3.2/1.4 3.5/1.5 43 3.6/1.5 43 3.7/1.6 44 3.8/1.6 43 3.4/1.4 43 3.5/1.5 3.5/1.5 44 3.6/1.5 44 3.7/1.6 44 3.8/1.6 44 3.3/1.4 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5 3.7/1.6 45 3.8/1.6 44 3.2/1.4 44 3.4/1.4 44 3.5/1.5 45 3.5/1.5 45 3.6/1.5 45 3.7/1.6 44 3.2/1.3 44 3.3/1.4 1050 45 3.3/1.4 45 3.4/1.5 45 3.6/1.5 45 3.7/1.6 45 3.8/1.6 1075 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5 1100 47 3.6/1.5 47 3.7/1.6 45 3.2/1.4 45 3.4/1.4 45 3.5/1.5 AVG GAS HEAT VALUE (BTU/CU FT) 0.58 GRAVITY OF NATURAL GAS 0.60 0.62 0.64 0.66 Orifice no. Manifold Pressure Orifice no. Manifold Pressure Orifice no. Manifold Pressure Orifice no. Manifold Pressure Orifice no. Manifold Pressure 775 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4 42 3.4/1.4 42 3.5/1.5 800 43 3.5/1.5 43 3.7/1.5 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4 825 44 3.8/1.6 43 3.4/1.5 43 3.6/1.5 43 3.7/1.5 43 3.8/1.6 850 44 3.6/1.5 44 3.7/1.6 44 3.8/1.6 43 3.5/1.5 43 3.6/1.5 875 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5 44 3.7/1.6 43 3.4/1.4 900 44 3.2/1.4 44 3.3/1.4 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5 925 45 3.7/1.5 45 3.8/1.6 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 950 45 3.5/1.5 45 3.6/1.5 45 3.7/1.6 45 3.8/1.6 44 3.3/1.4 975 45 3.3/1.4 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5 45 3.8/1.6 1000 47 3.7/1.6 45 3.2/1.4 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5 1025 47 3.6/1.5 47 3.7/1.6 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4 SPECIFIC ALTITUDE RANGE FT (a) for Correct Btuh per Burner, 0.60 SPECIFIC ALTITUDE RANGE FT (a) Pressures Only ft (305 M)Above SPECIFIC ALTITUDE RANGE FT (a) Manifold 120 Size Furnaces AVG GAS HEAT VALUE (BTU/CU FT) 0.58 Orifice no. Manifold Pressure GRAVITY OF NATURAL GAS 0.60 0.62 0.64 0.66 Orifice no. Manifold Pressure Orifice no. Manifold Pressure Orifice no. Manifold Pressure Orifice no. Manifold Pressure 750 43 3.7/1.6 43 3.8/1.6 42 3.3/1.4 42 3.4/1.4 42 3.5/1.5 775 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6 43 3.8/1.6 42 3.2/1.4 800 44 3.7/1.6 43 3.4/1.4 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6 825 44 3.5/1.5 44 3.6/1.5 44 3.8/1.6 43 3.4/1.4 43 3.5/1.5 850 44 3.3/1.4 44 3.4/1.4 44 3.5/1.5 44 3.7/1.5 44 3.8/1.6 875 45 3.8/1.6 44 3.2/1.4 44 3.3/1.4 44 3.5/1.5 44 3.6/1.5 900 45 3.6/1.5 45 3.7/1.6 45 3.8/1.6 44 3.3/1.4 44 3.4/1.4 925 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5 45 3.7/1.6 44 3.2/1.3 950 45 3.2/1.4 45 3.3/1.4 45 3.4/1.5 45 3.5/1.5 45 3.7/1.5 975 47 3.6/1.5 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4 45 3.5/1.5 1000 47 3.5/1.5 47 3.6/1.5 45 3.7/1.6 45 3.2/1.4 45 3.3/1.4 Orifice numbers shown in shading are factory installed. NOTE: Percents of derate are based on midpoints of U=S=altitude ranges. 55 Table 15 - Model 58MTB Orifice Size and High/Low-Heat for Use With 060 Through (Tabulated Derated ALTITUDE RANGE FT (a) AVG GAS HEAT VALUE (BTU/CU FT) 725 >, 4 _,, "_ 4001 to 5000 (1219 75O 775 8OO to 825 85O 1524) 9% derate 875 9OO 925 95O ALTITUDE RANGE FT (a) AVG GAS HEAT VALUE (BTU/CU FT) >, "_ 0 _J :5 • _. _. 6001 to 7000 (1829 Manifold Pressure Orifice no. Manifold Pressure 43 44 3.7/1.5 3.4/1.4 43 43 3.8/1.6 3.5/1.5 42 43 3.2/1.4 3.7/1.5 42 43 3.3/1.4 3.8/1.6 42 42 3.4/1.4 3.2/1.4 44 44 3.7/1.6 3.51.5 44 44 3.8/1.6 3.6/1.5 43 44 3.4/1.4 3.7/1.6 43 44 3.5/1.5 3.8/1.6 43 43 3.7/1.5 3.4/1.4 44 3.2/1.4 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5 44 3.7/1.6 45 45 3.5/1.5 3.3/1.4 45 45 3.8/1.6 3.6/1.5 44 45 3.3/1.4 3.7/1.6 44 44 3.4/1.4 3.2/1.3 44 44 3.5/1.5 3.3/1.4 45 47 3.3/1.4 3.7/1.6 45 45 3.4/1.4 3.2/1.4 45 45 3.5/1.5 3.3/1.4 45 45 3.6/1.5 3.4/1.5 45 45 3.8/1.6 3.6/1.5 47 3.5/1.5 47 3.6/1.5 45 3.2/1.3 45 SPECIFIC GRAVITY OF NATURAL GAS 3.3/1.4 45 3.4/1.4 0.58 0.60 45 45 3.4/1.4 3.2/1.4 47 3.6/1.5 47 48 3.4/1.4 3.7/1.6 1000 48 48 3.5/1.5 3.3/1.4 AVG GAS HEAT VALUE (BTU/CU FT) Orifice no. Manifold Pressure Orifice 65O 42 3.2/1.3 675 43 44 3.6/1.5 3.8/1.6 44 44 3.6/1.5 3.3/1.4 45 45 3.8/1.6 3.5/1.5 85O 45 47 3.3/1.4 3.7/1.6 875 47 3.5/1.5 2134) 13% derate 8OO 825 0.66 Orifice no. 3.2/1.3 3.6/1.5 to 0.64 Manifold Pressure 44 45 75O 775 0.62 Orifice no. 3.6/1.5 3.4/1.4 7OO 725 Sea Level)* Manifold Pressure 44 44 9OO 925 Btuh per Burner; Orifice no. 43 875 (Continued) Manifold Pressure 3.6/1.5 3.4/1.4 825 85O Inputs Orifice no. 43 43 95O 975 ALTITUDE RANGE FT (a) 0.60 Orifice 775 8OO on 20,000/13,000 for Correct Only SPECIFIC GRAVITY OF NATURAL GAS 0.58 Manifold Pressure 725 75O Pressures for Each 1000 ft (305 M) Above Orifice no. 7OO 5001 to 6000 (1524 to 1829) 11% derate Data Based 2 Percent Manifold 120 Size Furnaces no. 43 44 44 44 45 45 45 47 47 48 48 0.64 0.66 Manifold Pressure Orifice no. Manifold Pressure Orifice no. Manifold Pressure Or_ce no. Manifold Pressure 3.7/1.6 3.5/1.5 42 43 3.2/1.3 3.6/1.5 42 43 3.3/1.4 42 3.4/1.4 3.7/1.6 3.8/1.6 3.7/1.6 3.5/1.5 43 44 3.4/1.4 3.6/1.5 43 44 3.5/1.5 43 43 3.4/1.4 3.3/1.5 3.7/1.6 44 44 3.4/1.4 3.2/1.4 44 44 3.5/1.5 43 44 3.4/1.4 3.5/1.5 3.3/1.4 45 45 3.6/1.5 3.4/1.5 45 45 3.8/1.6 44 44 3.6/1.5 45 3.7/1.5 3.7/1.6 45 3.3/1.4 45 3.4/1.4 3.5/1.5 3.5/1.5 3.8/1.6 47 47 3.7/1.5 3.5/1.5 45 47 3.2/1.3 45 45 3.7/1.6 3.4/1.4 47 47 3.7/1.6 48 3.8/1.6 Manifold Pressure 3.7/1.6 3.3/1.4 3.6/1.5 3.6/1.5 48 3.8/1.6 47 3.5/1.5 48 3.6/1.5 48 SPECIFIC GRAVITY OF NATURAL GAS 48 0.58 0.62 0.60 0.62 0.64 3.6/1.5 3.6/1.5 3.2/1.4 3.3/1.4 3.5/1.5 0.66 no. Manifold Pressure Orifice no. Manifold Pressure Orifice no. Manifold Pressure 42 3.3/1.4 42 3.4/1.4 42 3.5/1.5 Or_ce no. 42 43 3.7/1.6 3.4/1.5 43 43 3.8/1.6 3.6/1.5 42 43 3.2/1.4 42 3.3/1.4 3.7/1.6 3.8/1.6 3.7/1.6 3.4/1.5 44 44 3.8/1.6 3.6/1.5 43 44 3.4/1.4 43 43 3.8/1.6 3.2/1.4 3.7/1.5 44 45 3.3/1.4 3.8/1.6 44 44 3.4/1.5 44 44 3.3/1.4 45 45 3.6/1.5 3.4/1.4 45 45 3.7/1.6 45 3.4/1.5 3.2/1.4 44 45 3.5/1.5 45 3.6/1.5 47 3.6/1.5 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4 43 44 44 44 45 45 Orifice numbers shown in shading are factory installed. NOTE: Percents of derate are based on midpoints of U.S. altitude ranges. 56 3.7/1.6 3.2/1.4 3.6/1.6 3.5/1.5 3.5/1.5 3.8/1.6 Table 15 - Model 58MTB Orifice Size and High/Low-Heat for Use With 060 Through (Tabulated Derated ALTITUDE RANGE FT (a) 7001 to 8000 (2134 2438)to 15% derate :5 ALTITUDE RANGE FT (a) AVG GAS HEAT VALUE (BTU/CUFT) ALTITUDE RANGE FT (a) _>, • <. cn :5 9001 to 10000 (2743 to 3048) 19% derate on 20,000/13,000 for Correct Inputs (Continued) Only Btuh per Burner; for Each 1000 ft (305 M) Above Sea Level)* SPECIFIC GRAVITY OF NATURAL GAS 0.58 Orifice Manifold no. Pressure 0.60 Orifice Manifold no. Pressure Orifice no. 0.62 Manifold Pressure Orifice no. 0.64 Manifold Pressure Orifice no. 0.66 Manifold Pressure 43 3.8/1.6 42 3.3/1.4 42 3.4/1.4 42 3.5/1.5 42 3.6/1.5 65O 43 44 3.5/1.5 3.8/1.6 43 43 3.7/1.6 3.4/1.4 43 43 3.8/1.6 3.5/1.5 42 43 3.2/1.4 3.6/1.5 42 43 3.3/1.4 3.7/1.6 44 44 3.5/1.5 3.3/1.4 44 44 3.6/1.5 3.4/1.4 44 44 3.8/1.6 3.5/1.5 43 44 3.4/1.4 3.6/1.5 43 44 3.5/1.5 3.7/1.6 45 45 3.7/1.6 3.5/1.5 45 45 3.8/1.6 3.6/1.5 44 45 3.3/1.4 3.7/1.6 44 45 3.4/1.4 3.8/1.6 44 44 3.5/1.5 3.3/1.4 825 45 47 3.3/1.4 3.6/1.5 45 45 3.4/1.4 3.2/1.3 45 45 3.5/1.5 3.3/1.4 45 45 3.6/1.5 3.4/1.4 45 45 3.7/1.6 3.5/1.5 85O 47 3.4/1.4 47 3.5/1.5 47 3.7/1.5 45 SPECIFIC GRAVITYOF NATURALGAS 3.2/1.3 45 3.3/1.4 AVG GAS HEAT VALUE (BTU/CUFT) Orifice no. 675 7OO 725 75O 775 8OO 0.58 Manifold Pressure Orifice no. 0.60 Manifold Pressure Orifice no. 0.62 Manifold Pressure Orifice no. 0.64 Manifold Pressure Orifice no. 0.66 Manifold Pressure 43 43 3.8/1.6 3.5/1.5 42 43 3.3/1.4 3.6/1.5 42 43 3.4/1.4 3.8/1.6 42 42 3.5/1.5 3.2/1.4 42 42 3.6/1.5 3.3/1.4 44 3.7/1.6 43 3.4/1.4 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6 44 44 3.5/1.5 3.2/1.4 44 44 3.6/1.5 3.3/1.4 44 44 3.7/1.6 3.4/1.5 44 44 3.8/1.6 3.6/1.5 43 44 3.4/1.5 3.7/1.6 45 45 3.6/1.5 3.4/1.4 45 45 3.8/1.6 3.5/1.5 44 45 3.2/1.4 3.6/1.5 44 45 3.3/1.4 3.8/1.6 44 44 3.4/1.4 3.2/1.4 8OO 45 47 3.2/1.3 3.6/1.5 45 47 45 45 3.6/1.5 3.4/1.4 AVG GAS HEAT VALUE (BTU/CUFT) Orifice no. 625 :5 Pressures 625 6OO Altitudes 8001 to 9000 (2438 to 2743) 17% derate Data Based 2 Percent Manifold 120 Size Furnaces 65O 675 7OO 725 75O 775 575 6OO 0.58 Manifold Pressure 3.3/1.4 45 3.4/1.4 45 3.5/1.5 3.7/1.6 45 3.2/1.3 45 3.3/1.4 SPECIFIC GRAVITYOF NATURALGAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold no. Pressure no. Pressure no. Pressure Orifice no. 0.66 Manifold Pressure 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4 42 3.3/1.5 42 3.6/1.5 43 44 3.5/1.5 3.7/1.6 43 44 3.6/1.5 3.8/1.6 43 43 3.7/1.6 3.5/1.5 42 43 3.2/1.3 3.6/1.5 42 43 3.3/1.4 3.7/1.6 44 3.4/1.4 44 3.5/1.5 44 3.7/1.5 44 3.8/1.6 43 3.4/1.4 44 45 3.8/1.6 3.6/1.5 44 45 3.3/1.4 3.7/1.6 44 45 3.4/1.4 3.8/1.6 44 44 3.5/1.5 3.3/1.4 44 44 3.6/1.5 3.4/1.4 75O 45 47 3.3/1.4 3.7/1.6 45 45 3.4/1.5 3.2/1.4 45 45 3.6/1.5 3.3/1.4 45 45 3.7/1.6 3.4/1.5 45 45 3.8/1.6 3.5/1.5 775 47 3.5/1.5 47 3.6/1.5 47 3.7/1.6 45 3.2/1.4 45 3.3/1.4 625 65O 675 7OO 725 *Orifice numbers shown in shading are factory installed. NOTE: Percents of derate are based on midpoints of U.S. altitude ranges. 57 )FF SWITCH LOW-FIRE ADJUSTMENT ALLEN SCREW (UNDER CAP) NOTE: Be sure pipes, and burner input by clocking At and vent checking gas meter. a. Calculate UNITED HIGH-FIRE ADJUSTMENT ALLEN SCREW (UNDER CAP) " INLET PRESSURE all pressure tubing, combustion-air enclosure front are in place when high-altitude STATES altitudes approved above adjustment 2000 for 2 percent sea level. See multiplier factor. ft, this derate Example (if required). furnace for each and has 1000 Table 16 been ft above for derate EXAMPLE: 100,000 Btuh input furnace Furnace Input Rate at Sea Level X installed Derate Multiplier at 4300 ft. = Furnace Input Rate at Installation Factor 100,000 X Altitude 0.91 = 91,000 CANADA At installation altitudes from 2001 to 4500 ft, this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer. To determine correct input MANIFOLD PRESSURE TAP A97358 Fig. 58 - Redundant BURNER Automatic rate for altitude, see example above and use 0.95 as derate multiplier factor. b. Reinstall burner box cover. Gas Control NOTE: Clocking gas input rate MUST with the burner box cover INSTALLED. Valve FLAME "-_ f_," V BURNER correct be performed c. Check proper that gas valve adjustment input to be clocked. caps are in place d. Obtain yearly for local gas supply. NOTE: :;i:"7 always Be sure for your adjustment heat value average heating value altitude. of gas used Consult of gas heating local for for calculations gas utility for is altitude value. e. Check and verify orifice size in furnace. NEVER ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY. f. Turn off all other gas appliances J h. Jumper run for 3 minutes in low-heat j. Measure time (in sec) for gas meter revolution. Note reading. A89020 k. Refer Flame to Table 1. Multiply In. Move This keeps R-to-W/W1. i. Let furnace MAN IFOLD J Fig. 59 - Burner and pilots. g. Move setup switch SW-1 to ON position. furnace locked in low-heat operation. 1 17 for cubic ft of gas per hr. gas rate cu ft/hr by heating setup operation. to complete switch value (Btu/cu SW-1 to OFF position ft). and jumper R and W1 and W2 thermostat connections. This keeps furnace locked in high-heat operation. Repeat items 'i' through '1' for high-heat operation. Example: (0 - 2000 ft altitude) Furnace input from rating plate is 100,000 Btu heating input = Btu/cu ft X cu ft/hr Btuh. Heating value of gas = 975 Btu/cu ft Time for 1 revolution of 2-cu ft dial -- 70 sec _I _ Gas rate = 103 cu ft/hr (from Table 17) Btu heating input = 103 X 975 = 100,425 Btuh. In this example, the orifice size and manifold pressure adjustment ORIFICE BURNER is within NOTE: within A93059 Fig. 60 - Burner Orifice ---2percent Measured ---2 percent installed at sea installed at higher of the furnace input rate. gas inputs (high-heat and low-heat) must be of that stated on furnace rating plate when level or derated per that stated above when altitudes. n. Remove jumper across R, W/W1, and W2 thermostat connections to terminate call for heat. 3. Verify Natural Gas Input Rate By Clocking Gas Meter. 58 SET TEMPERATURE Table 16- Altitude Derate Multiplier for USA. ALTITUDE FT (i) 0-2000 (0-610) 2001-3000 (610-914) 3001-4000 (914-1219) 4001-5000 (1219-1524) 5001-6000 1524-1829) 6001-7000 (1829-2134) 7001-8000 (2134-2438) 8001-9000 (2438-2743) PERCENT OF DERATE 9001-10,000 (2743-3048) DERATE MULTIPLIER FACTOR* 0 1.00 4-8 0.95 8-8 0.93 8-10 0.91 Temperature rating plate. 10-12 0.89 range or slightly 12-14 0.87 14-16 0.85 16-18 0.83 temperature temperature 18-20 0.81 low gas heat. UNIT factors are based on midpoint Table SECONDS FOR 1 REVOLUTION 17 - Gas Rate SIZE OF TEST DIAL 1 Cu Ft 2 Cu Ft 5 Cu Ft 10 360 720 1800 11 327 555 1536 12 300 600 13 277 14 15 rise must be within limits specified on furnace Recommended operation is at midpoint of rise above. 2 Cu Ft 5 Cu Ft 50 72 144 360 51 71 141 355 1500 52 69 138 346 555 1385 53 68 136 340 257 514 1286 54 67 133 333 240 480 1200 55 65 131 327 16 225 450 1125 56 64 129 321 17 212 424 1059 57 63 126 316 operate within on the furnace as follows: must rating 200 400 1000 58 62 124 310 19 189 379 947 59 61 122 305 20 180 360 900 60 60 120 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 286 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 100 200 500 92 39 78 196 37 97 195 486 94 38 76 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 88 172 429 104 35 69 173 43 84 167 419 106 34 68 170 44 82 164 409 108 33 67 167 45 80 160 400 110 33 65 164 46 78 157 391 112 32 64 161 47 76 153 383 116 31 62 155 48 75 150 375 120 30 80 150 49 73 147 367 124 29 58 145 temperature plate. rise ranges Determine the air not "see" heat exchangers so that radiant heat does not affect thermometer readings. This is particularly important b. When with straight thermometer return-air determine If the temperature run ducts. readings temperature temperature rise is outside a. Gas input for low-and b. Derate 18 the a. Place duct thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do SIZE OF TEST DIAL 1 Cu Ft Jumper R to W/W1 and W2 to check rise. To check low-gas-heat jumper to W2. Determine air rise for both high and low gas heat. Do not exceed rise ranges specified on unit rating plate for high and furnace specified temperature (CU FT/HR) REVOLUTION HAZARD Place SW-1 in ON position. high-gas-heat temperature temperature rise, remove altitude for altitude range. SECONDS FOR 1 DAMAGE Failure to follow this caution may result in overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate. This * Derate multiplier RISE for altitude stabilize, subtract from supply-air rise. this range, temperature check to the following: high gas heat operation. if applicable. c. Return and supply ducts for excessive restrictions causing static pressures greater than 0.50-in. wc. d. Adjust temperature rise by adjusting blower Increase blower speed to reduce temperature Decrease ELECTRICAL blower speed to increase speed. rise. temperature rise. SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect 115-v electrical power before changing speed tap. For high-heat, the HEAT on control: a. Med-high following connections can be at HI (Yellow) b. Med (Orange) - Available only on 5-speed Factory setting for these motors. c. Med-Low(Blue) - Do NOT on 80K & 120K Btuh for 4-speed motors. 59 made input motors. use for HI GAS-HEAT models. Factory setting Step 6 - Check UNITDAMAGE This section covers before the installation HAZARD connect 2. Do NOT Low connect "HI-HEAT" model sizes. on Speed (Red) Medium 80,000 Btuh 1. Check wire to "HI HEAT". Low Speed and (Blue) 120,000 wire Btuh Primary Limit input SPEED White Common High Cool Med - High SPARE Orangef Med High-Gas Blue Med- Low Spare/High-Gas Red Low* Low-Gas of checking to permit to check this limit control is to Heat THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED Heat Heat HOOK-AROUND VO LT/AM M ETER speed For low-heat, the following HEAT on control: a. Med (Orange) b. Med-Low normal air circulation. By limit control, it can be established that limit is functioning properly and operates if there is a restricted return-air supply or motor failure. If limit control does not function during this test, cause must be determined and corrected. 1-Available on 5-speed blowers only connections - Available can be made only on 5-speed at LO- motors (Blue) c. Low (RED) blower blower procedure Control method should be unblocked using this method COM Black remove in the Start-up shuts off gas control system and energizes blower motor if furnace overheats. Recommended AS SHIPPED Yellow To change must be checked sensor, gas valve, gradually block off return air after furnace has been operating for a period of at least 5 minutes. As soon as limit control has shut off burners, return-air opening LEAD COLOR blower the safety controls that is complete. The flame This control air-circulating to Table 18 - Speed Selection * Continuous Controls and pressure switch were all checked section as part of normal operation. Failure to follow this caution may result in damage to the heat exchangers due to over temperature or condensate corrosion. 1. NEVER Safety - Factory motor motor setting. speed selections lead from control for heating HI-HEAT mode, terminal. (See Fig. 37.) Select desired blower motor speed lead from one of the other motor leads and relocate it to HI-HEAT terminal. See Table 18 for lead color identification. SPARE terminal. Follow of LO-HEAT and COOL Set Blower Reconnect this same procedure speed selection. original for proper lead on 10TURNS selection FROM UNIT 24-VOLT TERMINAL BLOCK Off Delay a. Remove Blower Access Door if installed. b. Turn Dip switch 2 and 3 ON or OFF for desired blower off delay. See Table 11 and 12 or Fig. 36 and 37. ADJUST BLOWER OFF DELAY (HEAT EXAMPLE: SET THERMOSTAT of switches HEAT on control draw readings R and W. can be obtained 2. at thermostat center. Check Check Pressure operation the thermostat amp draw of Accurate amp subbase Fig. 61 - Amp This control ANTICIPATOR When using a nonelectronic thermostat, heat-anticipator must be set to match the the electrical components in R-W/W1 circuit. - 0.5 AMPS FOR THERMOSTAT an easy method should be taken of obtaining after blower measuring must be See thermostat manufacturer's instructions for anticipator and for varying heating cycle length. adjusting When using per hour. an electronic thermostat, set cycle of draft inducer. Check switch to furnace. door outer furnace lead wires pressure and disconnect inducer from wire harness. to furnace. to "call for heat" switch is functioning and wait 1 minute. properly, hot surface igniter should not glow, and status code LED flashes a Status Code 32. If hot surface ignitor glows when inducer motor is disconnected, shut furnace down immediately. Determine reason pressure switch did not function properly and correct condition. current. If thermostat has disconnected from R and SW-1 operation as follows: d. Set thermostat actual amp draw. motor has started W/W1 wires during current measurement Return desired location after completing the reading. Switch proves c. Turn on 115-v power terminals with Ammeter a. Turn off 115-v power motor and furnace is operating in low heat. To operate furnace in low-heat, first move SW-1 to ON position, then connect ammeter wires as shown in Fig. 61. The thermostat anticipator should NOT be in the circuit while no subbase, the thermostat Draw b. Remove When Fig. 61 illustrates The amp reading SETTING A80201 MODE) If desired, the main blower off time delay period may be lengthened or shortened when operating in the heating mode to provide greater comfort. See Table 11 for position of switches and Fig. 36 or 37 for location 5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS e. Turn off 115-v power f. Reconnect to final door, heat rate for 3 cycles 6O inducer to furnace. motor leads, and turn on 115-v power reinstall supply. main furnace CHECKLIST 1. Put away tools 2. Check and instruments. SW-1 through Clean up debris. SW-3 after completing ensure desired settings for thermostat blower-OFF delay (SW-2 and SW-3). 3. Verify flame rollout 4. Verify that blower manual type (SW-1) are properly and 8. Leave User's of Guide with literature thermostat. accessories packet per manufacturer's owner. near furnace. installed. VENT CALCULATION (2-PIPE) Condensate INSTALLATION Drain Unit Level or Pitched Forward Heating Load (Btuh) Cooling with room 6. Check operation instructions. has continuity. CHECKLISTmDIRECT LOAD to 7. Review reset switch and outer doors 5. Cycle test furnace installation Load (Btuh) Internal Tubing Connections Kinks and Traps Free of Furnace Model Selection External Drain Connection COMBUSTION AIR AND VENT Leak Tight and Sloped PIPING Condensate Termination Location Heat Tape Installed if Required Roof or Sidewall Termination Trap Primed before Start-Up CHECKLIST - START-UP Kit - 2 Pipe or Concentric Combustion-Air Combustion-Air Pipe Length Gas Input Rate (Set Within 2 percent of Rating Plate) Pipe Elbow Quantity Temperature Vent Pipe Length Thermostat Rise Adjusted Anticipator Vent Pipe Elbow Quantity Anticipator Setting Adjusted or Pipe Diameter Determined from Sizing Table Cycle Rate (3 Cycles per Hr) Selected Pipe Sloped To Furnace Safety Pipe Insulation Controls Check Operation Primary Limit Over Ceilings ...... Pressure Switch Low-Ambient Exposed Pipes 61 CHECKLIST LOAD - NON DIRECT VENT CALCULATION (1-PIPE) Condensate INSTALLATION Drain Heating Load (Btuh) Unit Level or Pitched Forward Cooling Internal Tubing Connections Free of Kinks and Traps Load (Btuh) Furnace Model Selection VENT External Sloped PIPING Drain Condensate Termination Location Connection Leak Tight and Trap Primed before Start-Up Heat Tape Installed if Required Roof or Sidewall CHECKLIST--START-UP Vent Pipe Length Vent Pipe Elbow Quantity Gas Input Rate (Set Within 2 percent of Rating Plate) Pipe Diameter Determined from Sizing Table Temperature Pipe Sloped To Furnace Thermostat Anticipator Pipe Insulation Anticipator Over Ceilings Low-Ambient Rise Adjusted Setting Adjusted or Cycle Rate (3 Cycles per Hr) Selected Exposed Pipes Safety Controls Check Operation Primary Limit Pressure Switch Copyright 2008 Carrier Corp. ° 7310 W. Morris St. • Indianapolis, Manufacturer reserves the right to change, IN 46231 at any time, specifications and designs Printed in U.S.A. without Edition Date: notice and without 62 12/08 obligations, Catalog No: 58MTB-2SI Replaces: 58MTB- 1St
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 62 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun Mar 08 04:20:53 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools