30GXN,R080-528
30HX076-271
Minimum Load Control Accessory
50/60 Hz

Installation Instructions
Part No. 30GX-900---048,
(60 Hz — 115-v Control)
Part No. 30GX-900---049
(50 or 60 Hz — 230-v Control)
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Step 1 — Examine Package Contents . . . . . . . . . . . . 1
Step 2 — Install Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• REMOVE MINIMUM LOAD PORT PLUGS
AND INSTALL FITTINGS
• INSTALL PIPING
• INSTALL BALL AND SOLENOID VALVES
• CONNECT PIPING
• 30GXN,R UNITS ONLY
Step 3 — Dehydrate and Recharge Circuit. . . . . . . . 3
Step 4 — Install Control Wiring. . . . . . . . . . . . . . . . . . . 3
• 30HX UNITS
• 30GXN,R UNITS
• ALL UNITS
Step 5 — Configure Unit for Minimum
Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 —Test Minimum Load Relay
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 7 — Adjust Setting of Minimum
Load Ball Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location.
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When working on air-conditioning equipment, observe precautions in the literature and on tags, stickers, and labels
attached to the equipment.
Follow all safety codes. Wear safety glasses and work
gloves. Use care in handling equipment.

IMPORTANT: When removing refrigerant, use an
approved refrigerant recovery device. Do not vent refrigerant into the atmosphere.

INTRODUCTION
The minimum load control accessory allows 30HX and
30GXN,R chillers to have their capacities decreased below the
standard fully unloaded condition. The accessory provides
more precise control of leaving fluid temperature during light
load conditions.
The 30GXN,R and 30HX chillers have a dual-circuit
design. Each minimum load control accessory package contains the items required for both circuits. Because of an automatic lead/lag feature on the chillers, the accessory should be
installed on both circuits.

INSTALLATION
Step 1 — Examine Package Contents — Package includes solenoid valves, ball valves, O-ring seal fittings,
and instructions. Examine each item. If any part is damaged or
missing, file a claim immediately with the shipper and notify
your Carrier representative. See Table 1 for accessory package
contents and field-supplied material.
Table 1 — Accessory Package Contents
and Field-Supplied Material
ACCESSORY PACKAGE
COMPONENTS
Solenoid Valve
Ball Valve
O-Ring Seal Fitting
Tube Assembly
Tube Assembly (Condenser
Oil Separator)

ACCESSORY PART NUMBER
30GX-900---048
30GX-900---049
(2) EF23JX212
(2) EF23JX231
(2) EP71BA201
(2) EP71BA201
(4) 30GX503492
(4) 30GX503492
(2) 30GX503487
(2) 30GX503457
(2) 30HX402343

(2) 30HX402343

FIELD SUPPLIED MATERIAL — REQUIRED PARTS
(Ordered Separately)
5/ -in. OD Copper Tubing, Wiring, Conduit,
8
Field Supplied
Thread Sealant, Electrical Supplies

Be sure power to equipment is shut off before performing
maintenance or service.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903
Catalog No. 533-00009
Printed in U.S.A.
Form 30GX,HX-14SI
Pg 1
102
7-00
Replaces: 30GX,HX-7SI
Book 2
Tab 5c

Step 2 — Install Piping

INSTALL PIPING — On 30GXN,R units, carefully thread the
cooler tube assemblies (P/N 30GX503487) on the O-ring seal
fittings installed in the cooler port. Do not tighten. Install fieldsupplied 5/8-in. OD copper tubing between the tube assembly
and the brazed nipple on the discharge line.
On 30HX units, carefully thread the cooler tube assemblies
(P/N 30GX503487) and the condenser oil separator tube assembly (P/N 30HX402343) on the O-ring seal fittings installed
in the cooler and condenser/oil separator ports. Do not tighten.
Install field-supplied 5/8-in. OD copper tubing between the
tube assemblies on the cooler shell and condenser (30HXC) or
oil separator (30HXA).
INSTALL BALL AND SOLENOID VALVES — Using good
piping practice, braze ball valve and solenoid valve into 5/8-in.
minimum load piping. Fig. 2 shows a typical 30HX installation
and Fig. 3A and 3B show a typical 30GXN,R installation, including valve locations and orientation. Ensure that ball valve
is fully open, and that both the ball and solenoid valve are protected from excess heat during brazing process. Wrap wet
cloths around valve bodies and tube assembly locking nuts
during brazing to prevent damage to the valves and O-rings
from heat.
CONNECT PIPING — Lubricate O-rings with a light coating
of polyalphaolefin lubricant suitable for R-134a systems.
Thread tube assembly nuts onto the O-ring seal fittings until
they are finger-tight. Lightly snug the nut with a wrench;
DO NOT OVER TIGHTEN. You should be able to feel the Oring compress on the last 1/4-turn.

Shut off all power to the unit, then lock out and safety-tag
all disconnects before proceeding with installation.

Remove refrigerant charge from circuits using an approved refrigerant recovery device before proceeding with
installation.
NOTE: The units have 2 circuits. Perform all of the following
piping installation procedures on both A and B circuits.
REMOVE MINIMUM LOAD PORT PLUGS AND INSTALL FITTINGS — Plugs must be removed from these
ports and replaced with O-ring seal fittings. Note that plugs
were factory-installed with Loctitet 554 or equivalent
refrigerant-compatible sealant. Fittings should be installed with
similar sealant on threads.
30GXN,R — Cut plug end off of minimum load port braze
nipple on discharge line, located between oil separator and condenser. Remove plug from minimum load port on cooler shell.
See Fig. 1. Using thread sealant, install O-ring seal fitting in
minimum load port on cooler. Port on nipple in discharge line
is reserved for a brazed connection.
30HX — Remove plugs from minimum load ports on the cooler shell and the condenser shell (30HXC) or oil separator
(30HXA). See Fig. 2. Using thread sealant, install O-ring seal
fittings in minimum load ports.

→

IMPORTANT: DO NOT over tighten the O-ring seal
nut. Damage will occur to the seal, resulting in leaks.

Fig. 1 — Installing Fittings, 30GXN,R (Typical Size 080-150, 160 Shown)
102

2

Fig. 2 — Installing Fittings and Valves, 30HX (Typical)

codes and NEC (National Electrical Code, U.S.A.). Wire size
must be no. 16 AWG (American Wire Gage) (1.5 mm2) minimum. See Fig. 4 and 5 for field wiring.
30HX UNITS — Remove the screws holding the right-side
access panel to the unit control box. Open the right-side access
panel.
Route wires through field-supplied conduit and attach the
conduit to the unit control box, using a suitable conduit fitting
and one of the available 7/8-in. knockout openings. Attach the
other end of the conduit to the solenoid valve, using a suitable
fitting. Repeat for the other circuit. See Fig. 4.
30GXN,R UNITS —Route the field-supplied water proof conduit from the solenoid valves to the control box at the end of
the unit. See Fig. 4 and 5.
ALL UNITS — Using good wiring practice, connect a white
wire from the solenoid valve on circuit A to a white wire from
the solenoid valve on circuit B. Connect both wires to TB2-9
(30HX) or TB4-2 (30GX).
Connect a pink wire to the solenoid valve on circuit A.
Connect a gray wire to the solenoid valve on circuit B. Connect both the pink and gray wires to TB5-9 for all units.
Figure 4 shows the correct location of the wiring connection
points on the chiller.

30GXN,R UNITS ONLY — Using good brazing practice,
braze the 5/8-in. minimum load tubing to the copper nipple on
the discharge line (minimum load port) between the condenser
coil and oil separator. See Fig. 1, 3A and 3B.

Step 3 — Dehydrate and Recharge Circuit —
When piping has been completed, leak test the assembly. If
one of the O-ring seal fittings leaks, slowly tighten the O-ring
nut until the leak stops. If this does not fix the leak, the connection must be reinstalled using a new O-ring in the fitting. Contact your Carrier representative for assistance in locating these
parts.
After leak testing, evacuate, dehydrate, and recharge the circuit using an approved refrigerant recovery device. Correct
type and amount of refrigerant are listed on unit nameplate and
in base unit documentation.

Step 4 — Install Control Wiring

Be sure all power to the unit is off before proceeding. Lock
out and safety-tag all disconnects.
Wires between field-installed components and unit control
box must be enclosed in field-supplied conduit. Follow all local

3

MINIMUM LOAD
CONTROL PORTS

SOLENOID VALVE (TYP)

BALL VALVE (TYP)
CIRCUIT A (080-138)
CIRCUIT B (150, 160)

O-RING SEAL FITTING
AND ADAPTER (TYP)

CIRCUIT B (080-138)
CIRCUIT A (150, 160)

→

Fig. 3A — Typical Piping and Valve Installation 30GXN,R080-178
and Associated Modular Sizes (080-150, 160 Shown)

SEE DETAIL C

O-RING SEAL
FITTING

DETAIL C

SOLENOID
VALVE

FIELD INSTALLED
PIPING TO
CIRCUIT B DISCHARGE
LINE

BALL
VALVE

MINIMUM LOAD PORT
CIRCUIT B

MINIMUM LOAD PORT
CIRCUIT A

FIELD INSTALLED PIPING
TO CIRCUIT A DISCHARGE LINE

→

Fig. 3B — Typical Piping and Valve Installation 30GXN,R204-350
and Associated Modular Sizes (204-268 Shown)

102

4

30GXN,R080-178*
MLC-B
CONDUIT

MLC-A
CONDUIT

30HX076-186
LEGEND
C
CB
CCP
CLHR
EMM
EQUIP
EXV
FB
FR
GFI-CO

— Contactor Compressor
— Circuit Breaker
— ComfortLink™ Compressor
Protection
— Cooler Heater Relay
— Energy Management Module
— Equipment
— Electronic Expansion Valve
— Fuse Block
— Fan Relay
— Ground Fault Interrupter Convenience Outlet

GND
LR
MLC
OPC
PL
PRI
SCB
SN

—
—
—
—
—
—
—

Ground
Loader Relay
Minimum Load Control
Oil Pump Contactor
Plug Assembly
Primary
Screw Compressor
Board
— Sensor (Toroid)

SPT
TB
TRAN

— Suction Pressure
Transducer
— Terminal Block
— Transformer
Terminal Block Connection
Unmarked Splice
Factory Wiring

*And associated modular sizes.

→

Fig. 4 — Typical Minimum Load Control Wiring

5

102

MLC-B
CONDUIT

MLC-A
CONDUIT

30HX206-271

30GXN,R204-350*
*And associated modular sizes.

→

Fig. 4 — Typical Minimum Load Control Wiring (cont)

102

6

Fig. 4 — Typical Minimum Load Control Wiring (cont)

ROUTE CONDUITS THROUGH TRAY
AND ATTACH TO BOTTOM OF SHELF
ON TB-4 SIDE OF CONTROL BOX

Fig. 5 — Routing Field-Supplied Wiring and Conduit (30GXN,R Shown)

7

Step 5 — Configure Unit for Minimum Load
Control — Once the piping installation and wiring installation are complete, the chiller must be configured for minimum
load control operation. This may be done using the Navigator.
Set the Enable/Off/Remote/Contact switch in the OFF position.
1. Press

key until display reads ‘SELECT A MENU

ESCAPE

ITEM.’ Press
Press
Press

. Press

ENTER

ENTER

key to light up Configuration mode.
key to select sub-mode ‘OPT1’.

.

2. Press the down arrow

key to select MLVS NO.

3. To enable the minimum load valve feature, press the
ENTER key.
4. The display may read as follows. (If not, skip to Step 7.)
ENTER PASSWORD
5. Press 1 1 1 1 then

ENTER

key.

6. The Navigator again displays the following:
MLVS NO
7. Press

ENTER The Navigator displays:
key and key.

MLVS YES
The chiller is now configured for minimum load valve
control.

Step 6 — Test Minimum Load Relay Outputs — After the accessory components are installed and the
unit is recharged and reconfigured, test the operation of the relay and solenoid valve using the Service Test software function. Test both circuits as follows:
1. Press the

ESCAPE

key until the Navigator displays ‘SE-

LECT A MENU ITEM.’ Press the

key and light up

the Service Test mode. Press the ENTER key. Press the ENTER
key and ‘TEST OFF’ will be displayed with ‘OFF’ flashing. Press the
key then ENTER key and the Navigator
displays ‘TEST ON.’ Switch the Enable/Off/Remote
contact switch to the Enable position.
2. The display may read as follows. (If not, skip to Step 4.)
ENTER PASSWORD
3. Press 1 1 1 1 then

ENTER

4. Press the down arrow
mode. Press the
OFF.
5. Press the

ENTER

ENTER

key.
key to select the ‘COMP’ sub-

key and

key to display MLV

6. Press the
and ENTER key to energize the relays. The
display reads:
MLV ON
An audible click will be heard. Verify that the solenoid
valves for both circuits are energized.
7. Press the ENTER ,
and ENTER keys to turn the solenoids
off. When finished, exit the Service Test mode (change
‘TEST ON’ to ‘TEST OFF’). Put the Enable/Off/Remote
Contact switch in the desired position.
After testing is complete, recheck all electrical connections
for proper location and tightness. Replace and secure the access
panels for the unit control box.

Step 7 — Adjust Setting of Minimum Load Ball
Valve — Before the installation is complete, the minimum
load ball valve must be adjusted to suit the application. Calibrate one circuit at a time as follows:
1. Adjust the ball valve so that it is approximately half open.
2. Operate the chiller in Service Test mode, with one circuit
operating, and all compressor loaders deenergized.
NOTE: Operation of the chiller in Manual Control mode is
described in the Controls, Start-Up, Operation, and Troubleshooting Guide that is included with the 30GXN,GXR,HX
ComfortLink™ chillers.
3. Record the cooler ∆T (the difference between cooler entering fluid temperature and cooler leaving fluid temperature) at this fully unloaded condition.
4. Use the Service Test feature to enable the minimum load
valve output.
5. Observe and record the cooler ∆T with the minimum load
valve energized.
6. Adjust the minimum load ball valve until the cooler temperature difference reading from Step 5 is equal to half of
the temperature difference reading from Step 3.
7. Open the ball valve to decrease the temperature difference or close the ball valve to increase the temperature
difference (∆T). When the valve is adjusted correctly, the
difference between cooler entering and leaving fluid temperatures when the minimum load control is energized
must be at least half of the temperature difference when
the minimum load control is deenergized. For example, if
the difference between the cooler entering and leaving
water temperature is 3° F with the valve deenergized,
then the difference between cooler entering and leaving
water temperature must be at least 1.5° F with the valve
energized.
Once the outputs have been tested and the ball valve adjusted, the installation is complete.

key.

Copyright 2000 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903
Catalog No. 533-00009
Printed in U.S.A.
Form 30GX,HX-14SI
Pg 8
102
7-00
Replaces: 30GX,HX-7SI
Book 2
Tab 5c



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
XMP Toolkit                     : 3.1-701
Create Date                     : 2002:02:06 14:47:29Z
Creator Tool                    : ADOBEPS4.DRV Version 4.20
Modify Date                     : 2005:11:11 17:27:35-05:00
Metadata Date                   : 2005:11:11 17:27:35-05:00
Format                          : application/pdf
Creator                         : Carrier Corporation
Title                           : 
Description                     : 
Subject                         : 
Producer                        : Acrobat Distiller 4.0 for Windows
Keywords                        : 
Document ID                     : uuid:70fadb89-7f9b-4e73-b23e-9a66059d26d9
Instance ID                     : uuid:5b014728-2043-4a70-9f34-564a74b052ed
Page Count                      : 8
Author                          : Carrier Corporation
EXIF Metadata provided by EXIF.tools

Navigation menu