Carrier 30Hxa Users Manual
30HXA to the manual b5774157-dab6-46fc-8da5-93f4efbe291b
2015-01-24
: Carrier Carrier-30Hxa-Users-Manual-311103 carrier-30hxa-users-manual-311103 carrier pdf
Open the PDF directly: View PDF .
Page Count: 28
Download | |
Open PDF In Browser | View PDF |
30HXA,HXC076-186 Water-Cooled and Condenserless Chillers 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-27 Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . 1 Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . 1 Step 3 — Piping Connections . . . . . . . . . . . . . . . . . 9 • COOLER FLUID, VENT, AND DRAIN • BRINE UNITS • PREPARATION FOR YEAR-ROUND OPERATION • 30HXA REFRIGERANT PIPING • 30HXC CONDENSER CONNECTIONS • INSTALL PRESSURE RELIEF REFRIGERANT VENT PIPING Step 4 — Make Electrical Connections . . . . . . . 14 • FIELD POWER CONNECTIONS • FIELD CONTROL POWER CONNECTIONS Step 5 — Install Accessories . . . . . . . . . . . . . . . . 26 • ELECTRICAL • 30HXA LOW-AMBIENT OPERATION • MINIMUM LOAD ACCESSORY • MISCELLANEOUS ACCESSORIES Step 6 — Leak Test Unit . . . . . . . . . . . . . . . . . . . . . 26 • 30HXC UNITS • 30HXA UNITS Step 7 — Refrigerant Charge . . . . . . . . . . . . . . . . 26 • 30HXC UNITS • 30HXA UNITS SAFETY CONSIDERATIONS Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components, and equipment location. Only trained, qualified installers and service mechanics should install, start up, and service this equipment. When working on the equipment, observe precautions in the literature, and on tags, stickers, and labels attached to the equipment. • Follow all safety codes. • Wear safety glasses and work gloves. • Use care in handling, rigging, and setting bulky equipment. INTRODUCTION These instructions cover installation of 30HX liquid chillers with electronic controls and units with factory-installed options (FIOPSs). IMPORTANT: This equipment generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with these instructions, this equipment may cause radio interference. The equipment has been tested and found to comply with the limits of a Class A computing device as defined by the FCC (Federal Communications Commission, U.S.A.) Regulations, Subpart J of Part 15, which are designed to provide reasonable protection against such interference when operated in a commercial environment. INSTALLATION Step 1 — Inspect Shipment — Inspect unit for damage upon arrival. If damage is found, file a claim with the shipping company right away. Do not store units in an area exposed to weather because of sensitive control mechanisms and electronic devices. Locate unit indoors. When considering unit location, consult National Electrical Code (NEC, U.S.A.) and local code requirements. Allow sufficient space for wiring, piping, and service. Install unit in an area which will not be exposed to subfreezing weather. See Fig. 1-4 for clearance details. Allow the following clearances for service access: Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm) Rear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm) Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ft (610 mm) Ends . . . . . . . . . . . . . . . tube removal at one (either) end; 3 ft (914 mm) at opposite end. Be sure surface beneath the unit is level and is capable of supporting the operating weight of the unit. See Fig. 5 and Tables 1A and 1B for unit operating weights. If necessary, add supporting structure (steel beams or reinforced concrete slabs) to floor to transfer weight to nearest beams. Step 2 — Rig and Place Unit Rig unit from the top heat exchanger only. Rigging from the bottom heat exchanger will cause the unit to be lifted unsafely. Personal injury or damage to the unit may occur. Do not remove unit from skid until unit is in its final location. Rig from the rigging holes provided in the top heat exchanger. See Fig. 1-5 for rigging and center of gravity information. Lower the unit carefully onto the floor or roller. Push or pull only on the skid, not the unit. If the unit is moved on rollers, use a minimum of 3 evenly-spaced rollers. Copy continued on page 9. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 PC 903 Catalog No. 563-052 Printed in U.S.A. Form 30HX-1SI Pg 1 5-96 Replaces: New Tab 5c LEGEND K.O. — Knockout THK — Thick TYP — Typical NOTES: 1. Denotes center of gravity. 2. Dimensions are in inches. Dimensions ( ) are in millimeters. 3. Recommended service clearance around unit (front, back, and one side) is 369 (914). DIMENSIONS — in. (mm) UNIT 30HXC 076 086 096 106 116 126 136 146 A B C D E F G H J K L M N P 102.12 (2594) 102.12 (2594) 102.12 (2594) 102.12 (2594) 132.56 (3367) 132.56 (3367) 132.56 (3367) 132.56 (3367) 45.87 (1165) 45.87 (1165) 37.63 (956) 37.63 (956) 72.12 (1832) 72.12 (1832) 72.12 (1832) 72.12 (1832) 45.87 (1165) 45.87 (1165) 54.12 (1375) 54.12 (1375) 50.63 (1286) 50.63 (1286) 50.63 (1286) 50.63 (1286) 9.87 (251) 9.87 (251) 9.87 (251) 10.47 (266) 9.87 (251) 9.87 (251) 9.87 (251) 9.87 (251) 9.36 (236) 9.36 (236) 9.36 (236) 10.28 (261) 9.36 (236) 9.36 (236) 9.36 (236) 9.36 (236) 43.50 (1105) 43.50 (1105) 43.50 (1105) 45.50 (1156) 43.50 (1105) 43.50 (1105) 43.50 (1105) 43.50 (1105) 15.60 (396) 15.60 (396) 15.60 (396) 15.60 (396) 31.11 (790) 31.11 (790) 31.11 (790) 31.11 (790) 85.15 (2163) 85.15 (2163) 85.15 (2163) 85.15 (2163) 100.66 (2557) 100.66 (2557) 100.66 (2557) 100.66 (2557) 4.00 (102) 4.00 (102) 4.00 (102) 5.00 (127) 4.00 (102) 4.00 (102) 4.00 (102) 4.00 (102) 95.00 (2413) 95.00 (2413) 95.00 (2413) 95.00 (2413) 126.00 (3200) 126.00 (3200) 126.00 (3200) 126.00 (3200) 65.22 (1657) 65.22 (1657) 65.22 (1657) 67.22 (1707) 65.22 (1657) 65.22 (1657) 65.22 (1657) 65.22 (1657) 1.90 (48) 1.90 (48) 1.90 (48) 1.90 (48) 1.70 (43) 1.70 (43) 1.70 (43) 1.70 (43) 47.00 (1194) 47.00 (1194) 47.00 (1194) 47.00 (1194) 62.20 (1580) 62.20 (1580) 62.20 (1580) 62.20 (1580) 30.80 (782) 30.80 (782) 30.80 (782) 30.80 (782) 29.40 (747) 29.40 (747) 29.40 (747) 29.40 (747) Fig. 1 — Base Unit Dimensions, 30HXC076-146 Units 2 DIMENSIONS — in. (mm) NOTES: UNIT 30HXC A B C D E 161 72.12 (1832) 61.37 (1559) 61.37 (1559) 50.63 (1286) 61.37 (1559) 61.37 (1559) 2.00 (51) 2.00 (51) 2.00 (51) 63.50 (1588) 63.50 (1588) 63.50 (1588) 31.00 (787) 31.00 (787) 31.00 (787) 171 186 1. Denotes center of gravity. 2. Dimensions are in inches. Dimensions ( ) are in millimeters. 3. Recommended service clearance around unit (front, back, and one side) is 369 (914). LEGEND K.O. — Knockout THK — Thick TYP — Typical Fig. 2 — Base Unit Dimensions, 30HXC161-186 Units 3 LEGEND K.O. — Knockout SAE — Society of Automotive Engineers, U.S.A. THK — Thick TYP — Typical NOTES: 1. Denotes center of gravity. 2. Dimensions are in inches. Dimensions ( ) are in millimeters. 3. Recommended service clearance around unit (front, back, and one side) is 369 (914). DIMENSIONS — in. (mm) UNIT 30HXA 076 086 096 106 116 126 136 146 A B C D E F G H J K L M 102.12 (2594) 102.12 (2594) 102.12 (2594) 102.12 (2594) 132.56 (3367) 132.56 (3367) 132.56 (3367) 132.56 (3367) 45.87 (1165) 45.87 (1165) 37.63 (956) 37.63 (956) 72.12 (1832) 72.12 (1832) 72.12 (1832) 72.12 (1832) 45.87 (1165) 45.87 (1165) 54.12 (1375) 54.12 (1375) 50.63 (1286) 50.63 (1286) 50.63 (1286) 50.63 (1286) 27.81 (706) 27.81 (706) 27.81 (706) 28.41 (721) 27.81 (706) 27.81 (706) 27.81 (706) 27.81 (706) 9.36 (236) 9.36 (236) 9.36 (236) 10.28 (261) 9.36 (236) 9.36 (236) 9.36 (236) 9.36 (236) 43.50 (1105) 43.50 (1105) 43.50 (1105) 45.50 (1156) 43.50 (1105) 43.50 (1105) 43.50 (1105) 43.50 (1105) 15.60 (396) 15.60 (396) 15.60 (396) 15.60 (396) 31.11 (790) 31.11 (790) 31.11 (790) 31.11 (790) 85.15 (2163) 85.15 (2163) 85.15 (2163) 85.15 (2163) 100.66 (2557) 100.66 (2557) 100.66 (2557) 100.66 (2557) 4.00 (102) 4.00 (102) 4.00 (102) 5.00 (127) 4.00 (102) 4.00 (102) 4.00 (102) 4.00 (102) 95.00 (2413) 95.00 (2413) 95.00 (2413) 95.00 (2413) 126.00 (3200) 126.00 (3200) 126.00 (3200) 126.00 (3200) 65.22 (1657) 65.22 (1657) 65.22 (1657) 67.22 (1707) 65.22 (1657) 65.22 (1657) 65.22 (1657) 65.22 (1657) 13.93 (354) 13.93 (354) 22.15 (563) 22.15 (563) 40.16 (1020) 40.16 (1020) 40.16 (1020) 40.16 (1020) N P 59.48 5.72 (1511) (145 ) 59.48 5.72 (1511) (145) 42.77 5.72 (1086) (145) 42.77 5.87 (1086) (149) 64.23 5.72 (1631) (145) 64.23 5.72 (1631) (145) 64.23 5.72 (1631) (145) 64.23 5.72 (1631) (145) Fig. 3 — Base Unit Dimensions, 30HXA076-146 Units 4 R S T U V 45.81 (1164) 45.81 (1164) 54.06 (1373) 54.06 (1373) 72.06 (1830) 72.06 (1830) 72.06 (1830) 72.06 (1830) 46.25 (1175) 46.25 (1175) 38.00 (965) 38.00 (965) 51.01 (1296) 51.01 (1296) 51.01 (1296) 51.01 (1296) 2.40 (61) 2.40 (61) 2.40 (61) 2.40 (61) 2.30 (58) 2.30 (58) 2.30 (58) 2.30 (58) 46.40 (1179) 46.40 (1179) 46.40 (1179) 46.40 (1179) 61.00 (1549) 61.00 (1549) 61.00 (1549) 61.00 (1549) 35.00 (889) 35.00 (889) 35.00 (889) 35.00 (889) 34.30 (871) 34.30 (871) 34.30 (871) 34.30 (871) LEGEND K.O. — Knockout SAE — Society of Automotive Engineers, U.S.A. THK — Thick TYP — Typical NOTES: 1. Denotes center of gravity. 2. Dimensions are in inches. Dimensions ( ) are in millimeters. 3. Recommended service clearance around unit (front, back, and one side) is 369 (914). DIMENSIONS — in. (mm) UNIT 30HXA A B C D E F G H J 161 72.12 (1832) 61.37 (1559) 61.37 (1559) 50.63 (1386) 61.37 (1559) 61.37 (1559) 48.56 (1233) 43.25 (1099) 43.25 (1099) 46.62 (1184) 46.62 (1184) 46.62 (1184) 72.06 (1830) 61.31 (1572) 61.31 (1572) 51.00 (1295) 61.75 (1568) 61.75 (1568) 2.70 (69) 2.70 (69) 2.70 (69) 62.50 (1588) 62.50 (1588) 62.50 (1588) 35.20 (894) 35.20 (894) 35.20 (894) 171 186 Fig. 4 — Base Unit Dimensions, 30HXA161-186 Units 5 WEIGHT DISTRIBUTION AT EACH MOUNTING PLATE, 30HXC UNITS — Lb (Kg) UNIT 30HXC 076 086 096 106 116 126 136 146 161 171 186 1 738 (335) 738 (335) 686 (311) 730 (331) 728 (330) 738 (335) 758 (344) 763 (346) 817 (371) 936 (425) 962 (436) MOUNTING 2 3 943 595 (428) (270) 947 597 (430) (271) 968 693 (439) (314) 1028 744 (466) (337) 1114 777 (505) (352) 1127 780 (511) (354) 1176 811 (533) (368) 1182 815 (536) (370) 1272 908 (577) (412) 1318 840 (598) (381) 1361 860 (617) (390) PLATE NO. 4 5 1110 1418 (503) (643) 1112 1427 (504) (647) 1027 1447 (466) (656) 1073 1510 (487) (685) 1053 1615 (478) (733) 1061 1628 (481) (738) 1083 1689 (491) (766) 1085 1697 (492) (770) 1219 1890 (553) (857) 1379 1946 (626) (883) 1410 1996 (640) (905) WEIGHT DISTRIBUTION AT EACH MOUNTING PLATE, 30HXA UNITS — Lb (Kg) UNIT 30HXA 6 896 (406) 902 (409) 1034 (469) 1092 (495) 1127 (511) 1131 (513) 1171 (531) 1172 (532) 1346 (610) 1241 (563) 1265 (574) 076 086 096 106 116 126 136 146 161 171 186 1 555 (252) 555 (252) 509 (231) 555 (252) 530 (240) 540 (245) 548 (249) 551 (250) 560 (254) 627 (284) 648 (294) NOTE: See Fig. 1-4 for center of gravity details. Fig. 5 — Rigging Information 6 MOUNTING 2 3 793 418 (360) (190) 798 418 (362) (190) 808 493 (367) (224) 869 541 (394) (245) 895 540 (406) (245) 905 541 (410) (245) 926 555 (420) (252) 930 555 (422) (252) 965 598 (438) (271) 968 534 (439) (242) 1004 552 (455) (250) PLATE NO. 4 5 926 1326 (420) (601) 928 1340 (421) (608) 848 1350 (385) (612) 896 1410 (406) (640) 855 1456 (388) (660) 864 1468 (392) (666) 8743 1498 (396) (679) 883 1506 (400) (683) 954 1650 (433) (748) 1072 1658 (486) (752) 1110 1703 (504) (772) 6 699 (317) 705 (320) 827 (375) 880 (399) 887 (402) 887 (402) 908 (412) 908 (412) 1025 (465) 918 (416) 939 (426) Table 1A — Physical Data, English UNIT SIZE UNIT WEIGHT (lb) Fluid Cooled (HXC) Condenserless (HXA) COMPRESSORS Quantity Nominal Capacity per Compressor (tons) Economizer No. Capacity Steps Standard Optional (maximum) Minimum Step Capacity (%) Standard Optional REFRIGERANT TYPE Charge* (lb) Circuit A/Circuit B COOLER TYPE Part No. 10HX400− Net Fluid Volume (gal) Maximum Refrigerant Pressure (psig) Maximum Fluid-Side Pressure (psig) Fluid Connections (in.) Inlet and Outlet Drain (NPT) 30HXA OIL SEPARATOR Part No. 09RX400− Maximum Refrigerant Pressure (psig) Refrigerant Connections (in.) Discharge Liquid CONDENSER (HXC) Part No. 09RX400− Net Fluid Volume (gal) Maximum Refrigerant Pressure (psig) Maximum Water-Side Pressure (psig) Water Connections (in.) Inlet and Outlet Drain (NPT) 076 086 096 106 5700 4717 5723 4744 5855 4835 6177 5151 116 126 136 146 161 171 186 6415 6465 6688 6718 5162 5205 5308 5333 Semi-Hermetic, Twin Screw 2 2 2 2 7452 5752 7660 5777 7854 5946 2 2 2 2 2 2 2 39/39 No 46/39 No 56/39 No 66/39 No 66/46 No 66/56 No 80/56 No 80/66 No 80/56 Yes 66/80 Yes 80/80 Yes 6 8 6 8 6 8 6 8 6 8 6 8 6 8 6 8 6 8 6 8 6 8 20 10 20 10 20 10 20 10 20 10 20 20 10 10 R-134a 20 10 20 10 20 10 20 10 55/55 66/55 79/55 95/55 95/66 114/95 130/90 109/130 130/130 012 28.5 013 33.4 95/79 114/79 001 17.0 001 17.0 002 19.0 Shell and Tube with Enhanced Copper Tubes 010 007 007 006 006 104 22.6 21.4 21.4 24.0 24.0 28.5 220 220 220 220 220 300 300 300 300 300 12 4 ⁄ 12 4 ⁄ 12 4 ⁄ 12 007 320 007 320 008 320 008 320 21⁄8 11⁄8 2 1 ⁄8 1 1 ⁄8 21⁄8 11⁄8 001 16.8 220 001 16.8 220 002 18.3 220 2 1 ⁄8 21⁄8 1 1 ⁄8 11⁄8 Shell and Tube 002 003 18.3 23.9 220 220 300 300 300 300 5 ⁄ 12 5 ⁄ 12 5 ⁄ 12 12 5 ⁄ 5 ⁄ 220 220 220 220 220 300 300 300 300 12 4 ⁄ 12 5 ⁄ 12 5 ⁄ 12 009 320 009 320 010 320 010 320 2 1 ⁄8 21⁄8 21⁄8 21⁄8 1 1 ⁄8 11⁄8 11⁄8 13⁄8 with Enhanced Copper Tubes 003 004 004 005 23.9 27.5 27.5 30.6 220 220 220 220 21⁄8 13⁄8 21⁄8 13⁄8 006 37.6 220 006 37.6 220 300 300 Steel Weld Couplings 4 4 4 1⁄2 1⁄2 1 ⁄2 009 320 009 320 300 009 320 300 300 Steel Weld Couplings 5 5 5 1⁄2 1⁄2 1 ⁄2 *Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only. 7 220 5 ⁄ 300 300 300 300 5 ⁄ 12 5 ⁄ 12 5 ⁄ 12 12 5 ⁄ Table 1B — Physical Data, SI UNIT SIZE UNIT WEIGHT (Kg) Fluid Cooled (HXC) Condenserless (HXA) COMPRESSORS Quantity Nominal Capacity per Compressor (kW) Economizer No. Capacity Steps Standard Optional (maximum) Minimum Step Capacity (%) Standard Optional REFRIGERANT TYPE Charge* (Kg) Circuit A/Circuit B COOLER TYPE Part No. 10HX400− Net Fluid Volume (L) Maximum Refrigerant Pressure (kPa) Maximum Fluid-Side Pressure (kPa) Fluid Connections (in.) Inlet and Outlet Drain (NPT) 30HXA OIL SEPARATOR Part No. 09RX400− Maximum Refrigerant Pressure (kPa) Refrigerant Connections (in.) Discharge Liquid CONDENSER (HXC) Part No. 09RX400− Net Fluid Volume (L) Maximum Refrigerant Pressure (kPa) Maximum Water-Side Pressure (kPa) Water Connections (in.) Inlet and Outlet Drain (NPT) 076 086 096 106 2586 2140 2596 2152 2656 2193 2802 2336 2 2 2 2 116 126 136 2910 2933 3034 2341 2361 2408 Semi-Hermetic, Twin Screw 2 2 2 146 161 171 186 3047 2419 3380 2609 3476 2620 3563 2697 2 2 2 2 137/137 162/137 197/137 232/137 232/137 232/197 281/197 281/232 281/197 232/281 281/281 No No No No No No No No Yes Yes Yes 6 8 6 8 6 8 6 8 6 8 6 8 6 8 6 8 6 8 6 8 6 8 20 10 20 10 20 10 20 10 20 10 20 10 R-134a 20 10 20 10 20 10 20 10 20 10 24.9/ 24.9 29.9/ 24.9 35.8/ 24.9 001 64.3 1517 001 64.3 1517 2068 12 4 ⁄ 43.1/ 43.1/ 51.7/ 29.9 35.8 35.8 Tube with Enhanced Copper 007 007 006 81.0 81.0 90.8 1517 1517 1517 51.7/ 43.1 Tubes 006 90.8 1517 59.0/ 40.8 49.4/ 59.0 59.0/ 59.0 002 71.9 1517 43.1/ 24.9 Shell and 010 85.5 1517 104 107.9 1517 012 107.9 1517 013 126.4 1517 2068 2068 2068 2068 2068 2068 2068 12 4 ⁄ 12 4 ⁄ 12 2068 2068 2068 Steel Weld Couplings 4 4 4 1⁄2 1⁄2 1⁄2 12 4 ⁄ 12 5 ⁄ 12 5 ⁄ 12 007 2205 007 2205 008 2205 008 2205 009 2205 009 2205 009 2205 010 2205 010 2205 21⁄8 11⁄8 2 1 ⁄8 1 1 ⁄8 21⁄8 11⁄8 2 1 ⁄8 1 3 ⁄8 002 69.3 1517 2 1 ⁄8 1 1 ⁄8 Tubes 004 104.1 1517 21⁄8 13⁄8 001 63.6 1517 2 1 ⁄8 21⁄8 21⁄8 1 1 ⁄8 11⁄8 11⁄8 Tube with Enhanced Copper 003 003 004 90.5 90.5 104.1 1517 1517 1517 2 1 ⁄8 1 3 ⁄8 001 63.6 1517 21⁄8 11⁄8 Shell and 002 69.3 1517 105 115.8 1517 006 142.3 1517 006 142.3 1517 2068 2068 2068 2068 2068 2068 2068 2068 5 ⁄ 12 5 ⁄ 12 5 ⁄ 12 2068 2068 2068 Steel Weld Couplings 5 5 5 1⁄2 1⁄2 1⁄2 5 ⁄ 12 5 ⁄ 12 5 ⁄ 12 12 5 ⁄ 5 ⁄ 009 2205 *Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only. 8 009 2205 12 5 ⁄ 5 ⁄ IMPORTANT: Some of the unit skids are larger than standard door openings. Be sure that the path to the unit’s final destination is wide enough to accommodate unit shipping skid. Remove the skid if necessary. If skid is removed and rollers are used, attach rollers to unit tube sheets while moving unit. Tighten all cooler head bolts to 250 ft-lb (339 N-m) before filling system with water (or brine). 6. Install field-supplied differential flow switches in the cooler piping for protection against loss of flow. The differential flow switches must be installed on top of the pipe in a horizontal run and should be at least 5 pipe diameters from any bend. Install the low-pressure differential flow switch into the outlet line piping, and install the high-pressure differential flow switch into the inlet line piping as shown in Fig. 8. 7. Provide openings in fluid piping for pressure gages and thermometers (if used). These openings should be 5 to 10 pipe diameters from the unit water nozzles. For thorough mixing and temperature stabilization, wells in the leaving fluid pipe should extend at least 2 in. (50 mm) into the pipe. Areas where unit mounting points will be located must be level to within 1⁄16 in. per ft (1 mm per m) along the long axis of the unit. Once unit is in place and level, bolt unit to the floor. Use isolation pads under the unit to aid in vibration isolation as required. Step 3 — Piping Connections — See Fig. 6 and 7 for typical piping applications. COOLER FLUID, VENT, AND DRAIN — The inlet (return) fluid connection is always the lower of the 2 cooler connections. See Fig. 6 for locations. A screen strainer with a minimum of 20 mesh should be installed ahead of the cooler inlet to prevent debris from damaging internal tubes of the cooler. Outlet (supply) fluid connection is the upper connection of the 2 cooler connections. The cooler has weld flanges to connect the field-supplied piping. Plan the piping arrangement in accordance with good piping practices and so that the piping does not cross in front of the cooler head. Use flexible connections on cooler piping to reduce vibration transmission. Offset the piping to permit removal of the cooler head for maintenance. Install pipe hangers where needed. Make sure no weight or stress is placed on the water nozzle. To install cooler piping: 1. Remove bolts on weld flanges, and remove flanges from cooler fluid heads. Accessory Victaulic-type connections are available. Follow the connection directions provided with the accessory. Although cooler has an air vent, it is recommended that a field-supplied air vent be installed in the system to facilitate servicing. Field-supplied shut-off and balancing valves should also be installed to facilitate servicing and flow balancing. Locate valves in return and supply fluid lines as close to the chiller as possible. Locate air vent at highest point of the cooler fluid system. See Fig. 6. Provide drain connections at all low points to permit complete drainage of the system. BRINE UNITS — Special factory modifications to the units are required to allow them to operate at fluid temperatures less than 34 F (1.1 C). Be sure that the fluid has sufficient inhibited ethylene glycol or other suitable corrosionresistant antifreeze solution to prevent cooler freeze up. Remove the weld flanges before welding piping to the flanges. Refer to Fig. 1-4 for weld flange locations. Failure to remove the flanges may damage the sensors and insulation. PREPARATION FOR YEAR-ROUND OPERATION — In areas where the piping or unit is exposed to 32 F (0 °C) or lower ambient temperatures, freeze-up protection is recommended using inhibited ethylene glycol or other suitable corrosion-resistant antifreeze solution and electric heater tapes. Heater tapes should have a rating for area ambient temperatures and be covered with a suitable thickness of closed-cell insulation. Route power for the heater tapes from a separatelyfused disconnect. Mount the disconnect within sight from the unit per local or NEC codes. Identify disconnect as heater tape power source with warning that power must not be turned off except when servicing unit. Fill the fluid loop with water (or brine) and a corrosionresistant inhibitor suitable for the water of the area. Consult the local water authority for characteristics of area water and a recommended inhibitor for the cooler fluid loop. It is recommended that once the cooler water lines have been installed and leak checked that the cooler heads be insulated with a suitable thickness of closed-cell insulation. This will minimize the amount of condensation that will form on the cooler heads. 2. To keep debris from entering the heat exchanger during shipping and storage, the gaskets between the weld flanges and the fluid heads do not have holes cut into them. The gaskets have perforations where the holes are to be cut. Carefully cut a hole along the designated perforations. IMPORTANT: Be sure to remove flanges and cut holes in the gaskets between the flanges and the fluid heads as indicated. 3. Apply a thin coat of oil to both sides of each gasket to help ensure a good seal, and reattach each gasket to each fluid head. 4. Weld the field-supplied piping to the weld flanges. 5. Bolt the weld flanges back onto their respective fluid heads. IMPORTANT: When bolting the weld flanges to the fluid heads, be sure to locate the flange such that the hole in each flange lines up completely with the hole in each fluid head. If installed incorrectly, part of the hole in the fluid head will be blocked off. This will result in impaired fluid flow in high pressure drop applications. IMPORTANT: Before starting the unit, be sure all of the air has been purged from the system. A drain connection is located at the bottom of the cooler head. See Fig. 3 and 4 for connection location. Install shutoff valves to the drain line before filling the system with fluid. 9 10 Field Wiring Field Piping Fig. 6 — Typical Cooler (30HXA, HXC) and Condenser (30HXC Only) Piping and Wiring NOTES: 1. Wiring and piping shown are for general point-of-connection only and are not intended to show details for specific installation. Certified field wiring and dimensional diagrams are available upon request. The 30HXA and HXC units should be installed using certified drawings. 2. All wiring must comply with applicable codes. 3. Refer to Carrier System Design Manual for details regarding piping techniques. 4. Piping, wiring, switches, valves, vent, gages, strainers, drain, and vibration isolation are all field supplied. LEGEND NOTES: 1. Piping shown is for general point-of-connection only and is not intended to show details for a specific installation. Certified field wiring and dimensional drawings are available upon request. The 30HXA units should be installed using certified drawings. 2. Refer to Carrier System Design Manual for details regarding piping techniques. 3. Piping and pressure relief devices are field supplied. 4. Vent pipes properly per local codes. TO REMOTE CONDENSER(S) TO REMOTE CONDENSER(S) TO REMOTE CONDENSER(S) COOLER* TO REMOTE CONDENSER(S) EXV EXV PRESSURE RELIEF OIL SEPARATOR LIQUID LINE DISCHARGE LINE ANGLE VALVE LIQUID LINE LEGEND EXV — Electronic Expansion Valve *See Fig. 6 for typical cooler piping. Fig. 7 — Typical 30HXA Refrigerant Piping to Remote Condenser 30HXA REFRIGERANT PIPING (See Fig. 7) — Take care when running the refrigerant piping from the 30HXA unit to the remote condenser(s) to avoid excessive pressure drops. The pressure drop using R-134a refrigerant is different than when using R-22 refrigerant. See Tables 2 and 3 for an example for a 2 F (1.1 C) pressure drop in saturated temperature in the discharge (hot gas) line and liquid line, respectively. Refer to Fig. 9 and 10 for line sizing information for the discharge and liquid lines for 30HXA (R-134a) units. Table 2 — Discharge Line 2 F (1.1 C) Drop in Saturated Temperature Example SATURATED DISCHARGE TEMP F C 126 52.2 124 51.1 D PRESSURE PRESSURE R-134a Psig 187.5 182.0 5.5 kPa 1293 1255 38 R-22 Psig 281.6 274.3 7.3 kPa 1942 1891 51 LEGEND COM — Common N.O. — Normally Open Fig. 8 — Differential Flow Switch 11 NOTES: 1. Values are for a 2° F pressure drop at 125 F (51.7 C) saturated discharge temperature, 120 F (48.9 C) saturated condensing temperature, and 105 F (40.6 C) liquid refrigerant temperature. 2. Size each circuit separately. Fig. 9 — R-134a Liquid Line Sizing, 30HXA Units Table 3 — Liquid Line 2 F (1.1 C) Drop in Saturated Temperature Example SATURATED LIQUID TEMP F C 100 37.7 98 36.7 D PRESSURE IMPORTANT: There is a Schrader-type fitting in each of the two 1⁄4-in. fittings. These Schrader-type fittings MUST BE REMOVED before running the line. PRESSURE R-134a Psig 124.3 120.1 4.2 kPa 857 828 29 R-22 Psig 195.9 190.2 5.7 The 30HXA units are shipped from the factory with a holding charge of R-134a. Before opening the refrigerant system, relieve system pressure and recover system refrigerant through the charging valve on the cooler. kPa 1351 1311 40 30HXC CONDENSER CONNECTIONS — The inlet fluid connection is always the lower of the 2 condenser connections. It is recommended that a screen strainer with a minimum of 20 mesh be installed ahead of the condenser inlet to prevent debris from damaging the internal condenser tubes. The outlet water connection is the upper connection of the 2 connections. The condenser has weld couplings to connect field-supplied piping. Plan the piping arrangement in accordance with good piping practices and so that the piping does not cross in front of the condenser head. Use flexible connections on the condenser piping to reduce vibration transmission. Offset the piping to permit condenser head removal for maintenance purposes. Install pipe hangers where needed. Make sure no weight or stress is placed on the water nozzle. Discharge lines should be looped above the compressors to avoid having charge flowing back to the oil separator and compressor during unit shutdown. Wrap back-pressure valve when brazing discharge line to avoid damaging the valve. It is recommended that field-supplied pressure relief valves be installed in each discharge line. Most local codes require that the relief valves be vented directly to the outdoors. The vent must not be smaller than the relief valve outlet, and the pressure setting should be 320 psig (2205 kPa). Run a field-supplied 1⁄4-in. (6.4 mm) copper line between the back-pressure valve on the oil separator (bottom pressure vessel) to the fitting on the refrigerant line entering the economizer port of the compressor to measure oil pressure differential. See Fig. 11. The back-pressure valve and the fitting on the refrigerant line have a 1⁄4-in. flare fitting for making this connection. The flare nut is field supplied. 12 NOTES: 1. Values are for a 2° F pressure drop at 125 F (51.7 C) saturated discharge temperature, 120 F (48.9 C) saturated condensing temperature, and 105 F (40.6 C) liquid refrigerant temperature. 2. Size each circuit separately. Fig. 10 — R-134a Discharge Line Sizing, 30HXA Units Fig. 11 — Field-Supplied 1⁄4-in. Copper Tube, 30HXA Units 13 INSTALL PRESSURE RELIEF REFRIGERANT VENT PIPING — To facilitate refrigerant vent piping, units have flares for all of the relief fittings. The low side relief valves on all units are provided with a 3/4 in. NPT flare connections, and are located on the cooler shell. There are 2 relief valves for the cooler; one on each circuit. The 30HXA high side relief valve is provided with a 5/8 in. SAE (Society of Automotive Engineers, U.S.A.) flare connection. The 30HXC high side relief valves are provided with a 3/4 in. NPT flare connection, and are located on the condenser shell. There are 2 relief valves for the separator (30HXA) and 2 for the condenser (30HXC); one for each circuit. Most local codes require that these devices be piped to the outside. If vent piping is required by local codes, these connections have been provided to aid in the connection of vent piping in accordance with ASHRAE 15 (American Society of Heating, Refrigeration, and Air Conditioning Engineers), Safety Code for Mechanical Refrigeration. If vent piping is required, do not restrict the vent flow in any way. NOTE: When accessory suction service valve kit is installed, there are 2 additional high-side pressure relief valves. Pipe these valves per local codes. These are located on the discharge line between the muffler and the discharge shutoff valve. To install condenser piping: 1. Remove bolts on weld flanges, and remove flanges from condenser water heads. Remove the weld flanges before welding piping to the flanges. Refer to Fig. 1 and 2 for weld flange locations. Failure to remove the flanges may damage the sensors and insulation. 2. To keep debris from entering the heat exchanger during shipping and storage, the gaskets between the weld flanges and the water heads do not have holes cut into them. The gaskets have perforations where the holes are to be cut. Carefully cut a hole along the designated perforations. IMPORTANT: Be sure to remove flanges and cut holes in the gaskets between the flanges and the water heads as indicated. 3. Apply a thin coat of oil to both sides of each gasket to help ensure a good seal, and reattach each gasket to each water head. 4. Weld the field-supplied piping to the weld flanges. 5. Bolt the weld flanges back onto their respective water heads. Step 4 — Make Electrical Connections — The electrical characteristics of the available power supply must agree with the unit nameplate rating. Supply voltage must be within the limits shown. IMPORTANT: When bolting the weld flanges to the water heads, be sure to locate the flange such that the hole in each flange lines up completely with the hole in each water head. If installed incorrectly, part of the hole in the water head will be blocked off. This will result in impaired water flow in high pressure drop applications. FIELD POWER CONNECTIONS (See Fig. 12) — All power wiring must comply with applicable local and national codes. Install field-supplied, branch circuit fused disconnect(s) of a type that can be locked off or open. Disconnect(s) must be located within sight and readily accessible from the unit in compliance with NEC Article 440-14. See Tables 4A and 4B for unit electrical data. See Tables 5A and 5B for compressor electrical data. Provide openings in water piping for pressure gages and thermometers (if used). These openings should be 5 to 10 pipe diameters from the unit water nozzles. For thorough mixing and temperature stabilization, wells in the leaving water pipe should extend at least 2 in. (50 mm) into the pipe. Accessory Victaulic-type connections and condenserwater thermistors are available. Follow the connection directions as provided with the accessory. If accessory differential pressure switch, water flow switch, or condenser water thermistor is to be installed, install the proper fittings into the condenser water lines before water is connected. Although condenser has an air vent, it is recommended that a field-supplied air vent be installed in the system to facilitate servicing. Field-supplied shut-off and balancing valves should also be installed to facilitate servicing and flow balancing. Locate valves in inlet and outlet lines as close to the chiller as possible. Locate air vents at the highest point of the system loop. See Fig. 6. Provide drain connections at all low points in the loop to permit complete system drainage. For installations where entering condensing water temperature could be below 70 F (21 C), a field-supplied leaving water temperature regulating valve is required. Operation below 70 F (21.1 C) without this valve may cause the unit to shut down on low oil pressure alarms. IMPORTANT: the 30HX units have a factory-installed option available for a non-fused disconnect for unit power supply. If the unit is equipped with this option, all field power wiring should be made to the non-fused disconnect since no terminal blocks are supplied. All units have a single location for power entry to simplify the field power wiring. Maximum wire size that the unit terminal block or non-fused disconnect will accept is 500 kcmil. All 380/415-3-50, 460-3-60, and 575-3-60 units require a single field-supplied power supply. All 230-3-50 and 208/230-3-60 units require 2 separate field-supplied power supplies. All 380-3-60 units (except the 30HXC/A186 units) require a single field-supplied power supply. The 30HXC/A186 units require 2 field-supplied power supplies. The 30HXA136-186 and 30HXC171,186, 346-3-50 units require 2 field-supplied power supplies. All other 346-3-50 units require a single field-supplied source. FIELD CONTROL POWER CONNECTIONS (See Fig. 13) — Units with a power supply of 208/230-, 460-, and 575-3-60 require 115-1-60 control circuit power. Units with a 380-3-60 power supply require 230-1-60 control circuit power. All other units 230-1-50 control circuit power. Field control power connections are made at terminals 1 and 2 of TB4. NOTE: This valve should be a temperature-controlled valve (DO NOT USE a pressure-controlled valve) which controls to 80 F (26.7 C) leaving water temperature. Be sure to add a bleed line between the entering and leaving water lines. Copy continued on page 26. 14 Table 4A — Unit Electrical Data, 30HXC Units* UNIT 30HXC 076 086 096 106 116 126 136 146 VOLTAGE Supplied Nameplate (3 Ph) Min Max 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 POWER CIRCUIT MCA MOCP Recommended Fuse Size 123/123 100 80 121 115/115 138 126 148/123 111 89 135 140/115 154 140 181/122 126 101 153 169/115 173 158 219/123 143 115 174 202/115 195 178 219/148 153 122 185 202/140 208 190 219/181 165 131 199 202/169 224 204 263/181 184 147 222 245/169 252 230 263/219 198 158 240 245/202 270 246 200/200 150 110 175 200/200 175 175 250/200 150 125 200 250/200 225 200 300/200 175 150 225 300/200 250 225 350/200 200 175 250 350/200 300 250 350/250 225 175 250 350/250 300 250 350/300 225 175 250 350/300 300 300 450/300 250 200 300 400/300 350 300 450/350 250 225 350 400/350 400 350 175/150 125 100 150 150/150 175 150 200/150 125 100 175 75/150 175 175 225/150 150 125 175 225/150 200 200 300/150 175 150 200 250/150 225 225 300/200 175 150 225 250/175 250 225 300/225 200 150 225 250/225 250 250 350/225 225 175 300 300/225 300 300 350/300 225 200 300 300/250 350 300 See legend and notes on page 16. 15 CONTROL CIRCUIT Voltage (Single Ph) 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 Min Max 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 MCA ICF MOCP 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 WD XL 307 148 118 169 266 118 165 307 148 118 169 305 208 190 354 172 137 195 347 237 216 405 197 158 223 397 271 247 426 207 166 234 417 284 259 452 219 175 248 440 300 273 512 249 199 282 496 338 308 542 262 210 299 523 355 324 † 374 299 419 † † 400 † 374 299 419 † † 479 † 449 359 502 † † 562 † 529 423 590 † † 661 † 539 431 601 † † 673 † 551 440 615 † † 687 † 646 536 720 † † 797 † 659 547 737 † † 813 Table 4A — Unit Electrical Data, 30HXC Units* (cont) UNIT 30HXC 161 171 186 VOLTAGE Supplied Nameplate (3 Ph) Min Max 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 POWER CIRCUIT CONTROL CIRCUIT MCA MOCP Recommended Fuse Size 285/197 200 160 242 266/182 273 249 238/285 215 172 260 219/266 145/176 267 285/285 232 185 156/156 266/266 176/176 289 500/350 300 225 350 450/300 400 350 400/500 300 250 350 350/450 250/300 350 500/500 300 250 250/250 450/450 300/300 400 350/250 250 200 300 350/225 350 300 300/400 250 200 300 300/350 175/225 300 400/400 300 225 200/200 350/350 225/225 350 LEGEND — Maximum Instantaneous Current Flow during start-up (the point in the starting sequence where the sum of the LRA for the start-up compressor, plus the total RLA for all running compressors, plus the total FLA for all running fan motors is at a maximum) MCA — Minimum Circuit Ampacity (for wire sizing) MOCP — Maximum Overcurrent Protection RLA — Rated Load Amps WD — Wye-Delta Start XL — Across-the-Line Start *Refer to Carrier’s electronic catalog for the most current electrical data. †Wye-Delta Start is standard. Not available in across-the-line start. **The 30HX186 units have 2 terminal blocks/non-fused disconnects and 6 parallel conductors/non-fused disconnects. ††The 30HXC171 and 186 units have 2 terminal blocks/non-fused disconnects and 6 parallel conductors/non-fused disconnects. NOTES: 1. Main power must be supplied from a field-supplied fused electrical service with a (factory- or field-installed) disconnect located in sight from the unit. 2. Control circuit power must be supplied from a separate source through a field-supplied disconnect. The control circuit accessory transformer may be applied to power from the main unit power supply. 3. Maximum incoming wire size for each terminal block is 500 kcmil. 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%. 5. Units with one MCA value have one main terminal block. Units with 2 MCA values require multiple conductors. 6. Use copper conductors only. Voltage (Single Ph) 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 Min Max 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 MCA ICF MOCP 15 15 15 15 15 15 WD XL 591 287 230 325 578 394 358 624 302 242 343 607 413 376 661 319 255 364 645 438 399 † 756 605 843 † † 944 † 771 617 861 † † 962 † 788 630 882 † † 985 7. The MOCP is calculated as follows: MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one size down from the result. The RLAs are listed on the unit nameplate. The recommended fuse size in amps (RFA) is calculated as follows: RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size up from the result. The RLAs are listed on the unit nameplate. 8. Units have the following power wiring terminal blocks and parallel conductors: ICF VOLTAGE 208/230 460 575 380** 230 346†† 380/415 16 TERMINAL BLOCKS OR NON-FUSED DISCONNECTS 2 1 1 1 2 1 1 PARALLEL CONDUCTORS OR NON-FUSED DISCONNECTS 6 3 3 3 6 3 3 Table 4B — Unit Electrical Data, 30HXA Units* UNIT 30HXA 076 086 096 106 116 126 136 146 VOLTAGE Supplied Nameplate (3 Ph) Min Max 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 POWER CIRCUIT MCA MOCP Recommended Fuse Size 180/180 146 117 177 169/169 201 183 215/180 162 130 196 205/169 225 206 262/180 183 147 222 248/169 254 231 319/180 209 167 253 300/169 289 263 319/215 222 177 269 300/205 308 281 319/262 239 191 289 300/248 331 302 389/262 271 216 328 369/248 245/164 343 389/319 291 233 353 369/300 245/199 369 300/300 200 150 250 300/300 250 250 350/300 225 175 250 350/300 300 300 450/300 250 200 300 400/300 350 350 500/300 300 250 350 500/300 400 400 500/350 300 250 400 500/350 450 400 500/450 350 250 400 500/400 400 400 700/450 400 300 450 600/400 400/250 500 700/500 400 300 500 600/500 400/350 500 225/225 175 150 200 225/225 225 225 300/225 200 150 225 250/225 300 250 350/225 225 175 300 300/225 300 300 400/225 250 200 300 400/225 350 300 400/300 300 200 350 400/250 350 350 400/350 300 225 350 400/300 400 350 500/350 350 250 400 450/300 300/200 400 500/400 350 300 400 450/400 300/250 450 See legend and notes on page 18. 17 CONTROL CIRCUIT Voltage (Single Ph) 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 Min Max 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 MCA ICF MOCP 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 WD XL 451 218 175 248 440 299 273 511 248 199 282 496 337 308 577 281 225 318 567 386 352 662 324 259 365 620 423 385 690 337 269 380 649 443 402 728 354 283 401 683 465 423 791 386 309 436 817 557 507 837 406 325 461 859 585 532 † 550 440 615 † † 687 † 645 536 720 † † 797 † 750 600 836 † † 938 † 885 708 985 † † 1042 † 898 718 1000 † † 1059 † 915 732 1021 † † 1080 † 1015 812 1132 † † 1346 † 1035 828 1157 † † 1371 Table 4B — Unit Electrical Data, 30HXA Units* (cont) UNIT 30HXA 161 171 186 VOLTAGE Supplied Nameplate (3 Ph) Min Max 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 187 414 518 342 207 325 342 187 414 518 342 207 325 342 187 414 518 342 207 325 342 253 506 633 418 253 380 440 253 506 633 418 253 380 440 253 506 633 418 253 380 440 POWER CIRCUIT CONTROL CIRCUIT MCA MOCP Recommended Fuse Size 437/295 304 243 368 415/275 276/183 385 359/437 327 261 396 334/415 222/276 413 437/437 355 284 239/239 415/415 276/276 453 700/500 450 350 500 700/450 450/300 500 600/700 450 350 500 600/700 350/450 600 700/700 500 400 400/400 700/700 450/450 600 600/400 350 300 450 500/350 350/225 450 450/600 400 300 450 450/500 300/350 500 600/600 400 350 300/300 500/500 350/350 600 LEGEND — Maximum Instantaneous Current Flow during start-up (the point in the starting sequence where the sum of the LRA for the start-up compressor, plus the total RLA for all running compressors, plus the total FLA for all running fan motors is at a maximum) MCA — Minimum Circuit Ampacity (for wire sizing) MOCP — Maximum Overcurrent Protection RLA — Rated Load Amps WD — Wye-Delta Start XL — Across-the-Line Start *Refer to Carrier’s electronic catalog for the most current electrical data. †Wye-Delta Start is standard. Not available in across-the-line start. **The 30HX186 units have 2 terminal blocks/non-fused disconnects and 6 parallel conductors/non-fused disconnects. ††The 30HXA136-186 units have 2 terminal blocks/non-fused disconnects and 6 parallel conductors/non-fused disconnects. NOTES: 1. Main power must be supplied from a field-supplied fused electrical service with a (factory- or field-installed) disconnect located in sight from the unit. 2. Control circuit power must be supplied from a separate source through a field-supplied disconnect. The control circuit accessory transformer may be applied to power from the main unit power supply. 3. Maximum incoming wire size for each terminal block is 500 kcmil. 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%. 5. Units with one MCA value have one main terminal block. Units with 2 MCA values require multiple conductors. 6. Use copper conductors only. Voltage (Single Ph) 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 115-60 115-60 115-60 230-60 230-50 230-50 230-50 Min Max 104 104 104 207 198 198 198 104 104 104 207 198 198 198 104 104 104 207 198 198 198 127 127 127 254 254 254 254 127 127 127 254 254 254 254 127 127 127 254 254 254 254 MCA ICF MOCP 15 15 15 15 15 15 WD XL 979 478 382 539 858 535 533 1030 501 401 567 905 616 562 1093 529 539 601 970 660 601 † 1282 1025 1428 † † 1398 † 1305 1044 1456 † † 1427 † 1333 1066 1490 † † 1466 7. The MOCP is calculated as follows: MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one size down from the result. The RLAs are listed on the unit nameplate. The recommended fuse size in amps (RFA) is calculated as follows: RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size up from the result. The RLAs are listed on the unit nameplate. 8. Units have the following power wiring terminal blocks and parallel conductors: ICF VOLTAGE 208/230 460 575 380** 230 346†† 380/415 18 TERMINAL BLOCKS OR NON-FUSED DISCONNECTS 2 1 1 1 2 1 1 PARALLEL CONDUCTORS OR NON-FUSED DISCONNECTS 6 3 3 3 6 3 3 Table 5A — Compressor Electrical Data, 30HXC Units UNIT SIZE 30HXC 076 076-WD 086 086-WD 096 096-WD 106 106-WD 116 116-WD NAMEPLATE V-Hz (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 COMPRESSOR NUMBERS A1 RLA * 44.3 35.4 53.7 * * 55.8 98.1 44.3 35.4 53.7 92.1 61.1 55.8 * 53.6 42.8 64.9 * * 67.7 118.6 53.6 42.8 64.9 111.8 74.2 67.7 * 65.5 52.3 79.2 * * 81.7 144.9 65.5 52.3 79.2 134.9 89.5 81.7 * 79.2 63.3 95.9 * * 97.8 175.4 79.2 63.3 95.9 161.7 107.3 97.8 * 79.2 63.3 95.9 * * 87.8 175.4 79.2 63.3 95.5 161.7 107.3 97.8 B1 LRA * 330 264 365 * * 344 209 104 83 115 174 120 109 * 330 264 365 * * 423 209 104 83 115 213 147 134 * 405 324 448 * * 506 256 128 102 141 255 176 160 * 485 388 536 * * 605 307 153 123 169 305 210 191 * 485 388 536 * * 605 307 153 123 169 305 210 191 LEGEND LRA — Locked Rotor Amps RLA — Rated Load Amps WD — Wye-Delta Start *Units are shipped with wye-delta start as standard. Across-the-line start is not available. 19 RLA * 44.3 35.4 53.7 * * 55.8 98.1 44.3 35.4 53.7 92.1 61.1 55.8 * 44.3 35.4 53.7 * * 55.8 98.1 44.3 35.4 53.7 92.1 61.1 55.8 * 44.3 35.4 53.7 * * 55.8 98.1 44.3 35.4 53.7 92.1 61.1 55.8 * 44.3 35.4 53.7 * * 55.8 98.1 44.3 35.4 53.7 92.1 61.1 55.8 * 53.6 42.8 64.9 * * 67.7 118.6 53.6 42.8 64.9 111.8 74.2 67.7 LRA * 330 264 365 * * 344 209 104 83 115 174 120 109 * 330 264 365 * * 344 209 104 83 115 174 120 109 * 330 264 365 * * 344 209 104 83 115 174 120 109 * 330 264 365 * * 344 209 104 83 115 174 120 109 * 330 264 365 * * 423 209 104 83 115 213 147 134 Table 5A — Compressor Electrical Data, 30HXC Units (cont) UNIT SIZE 30HXC 126 126-WD 136 136-WD 146 146-WD 161 161-WD 171 171-WD NAMEPLATE V-Hz (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 COMPRESSOR NUMBERS A1 RLA * 79.2 63.3 95.9 * * 97.8 175.4 79.2 63.3 95.9 161.7 107.3 97.8 * 94.9 75.8 114.9 * * 118.8 210.0 94.6 75.8 114.9 196.3 130.3 118.8 * 94.9 75.8 114.9 * * 118.8 210.0 94.9 75.8 114.9 196.3 130.3 118.8 * 103.1 82.4 124.8 * * 128.6 228.8 103.1 82.4 124.8 212.5 141.0 128.6 * 86.1 68.8 104.2 * * 105.8 190.6 86.1 68.8 104.2 174.8 116.0 105.8 B1 LRA * 485 388 536 * * 605 307 153 123 169 305 210 191 * 580 484 641 * * 715 367 183 147 203 361 248 226 * 580 484 641 * * 715 367 183 147 203 361 248 226 * 685 548 757 * * 856 433 216 173 239 432 297 270 * 580 484 641 * * 715 367 183 147 203 361 248 233 LEGEND LRA — Locked Rotor Amps RLA — Rated Load Amps WD — Wye-Delta Start *Units are shipped with wye-delta start as standard. Across-the-line start is not available. 20 RLA * 65.5 52.3 79.2 * * 81.7 144.9 65.5 52.3 79.2 134.9 89.5 81.7 * 65.5 52.3 79.2 * * 81.7 144.9 65.5 52.3 79.2 134.9 89.5 81.7 * 79.2 63.3 95.9 * * 97.8 175.4 79.2 63.3 95.9 161.7 107.3 97.8 * 71.2 56.9 86.2 * * 88.2 157.6 71.2 56.9 86.2 145.7 96.7 88.2 * 103.1 82.4 124.8 * * 128.6 228.8 103.1 82.4 124.8 212.5 141.0 128.6 LRA * 405 324 448 * * 506 256 128 102 141 255 176 160 * 405 324 448 * * 506 256 128 102 141 255 176 160 * 485 388 536 * * 605 307 153 123 169 305 210 191 * 525 420 580 * * 600 350 175 140 193 348 232 200 * 685 548 757 * * 856 433 216 173 239 432 297 270 Table 5A — Compressor Electrical Data, 30HXC Units (cont) UNIT SIZE 30HXC 186 186-WD NAMEPLATE V-Hz (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 COMPRESSOR NUMBERS A1 RLA * 103.1 82.4 124.8 * * 128.6 228.8 103.1 82.4 124.8 212.5 141.0 128.6 B1 LRA * 685 548 757 * * 856 433 216 173 239 432 297 270 LEGEND LRA — Locked Rotor Amps RLA — Rated Load Amps WD — Wye-Delta Start *Units are shipped with wye-delta start as standard. Across-the-line start is not available. 21 RLA * 103.1 82.4 124.8 * * 128.6 228.8 103.1 82.4 124.8 212.5 141.0 128.6 LRA * 685 548 757 * * 856 433 216 173 239 432 297 270 Table 5B — Compressor Electrical Data, 30HXA Units UNIT SIZE 30HXA 076 076-WD 086 086-WD 096 096-WD 106 106-WD 116 116-WD NAMEPLATE V-Hz (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 COMPRESSOR NUMBERS A1 RLA * 64.9 51.9 78.7 * * 81.5 143.8 64.9 51.9 78.7 134.8 89.4 81.5 * 77.6 62.1 94.0 * * 99.2 171.9 77.6 62.1 94.0 163.9 108.8 99.2 * 94.8 75.7 114.7 * * 119.9 209.8 94.8 75.5 114.7 198.2 131.4 119.9 * 115.4 92.2 139.7 * * 145.4 255.5 115.4 92.2 139.7 240.2 159.4 145.4 * 115.4 92.2 139.7 * * 145.4 255.5 115.4 92.2 139.7 240.2 159.4 145.4 B1 LRA * 485 388 536 * * 605 307 153 123 169 305 210 191 * 580 484 641 * * 715 367 183 147 203 361 248 226 * 685 548 757 * * 856 433 216 173 239 432 297 270 * 820 656 906 * * 960 518 259 207 286 485 334 303 * 820 656 906 * * 960 578 259 207 286 485 334 303 LEGEND LRA — Locked Rotor Amps RLA — Rated Load Amps WD — Wye-Delta Start *Units are shipped with wye-delta start as standard. Across-the-line start is not available. 22 RLA * 64.9 51.9 78.7 * * 81.5 143.8 64.9 51.9 78.7 134.8 89.4 81.5 * 64.9 51.9 78.7 * * 81.5 143.8 64.9 51.9 78.7 134.8 89.4 81.5 * 64.9 51.9 78.7 * * 81.5 143.8 64.9 51.9 78.7 134.8 89.4 81.5 * 64.9 51.9 78.7 * * 81.5 143.8 64.9 51.9 78.7 134.8 89.4 81.5 * 77.6 62.1 94.0 * * 99.2 171.9 77.6 62.1 94.0 163.9 108.8 99.2 LRA * 485 388 536 * * 605 307 153 123 169 305 210 191 * 485 388 536 * * 605 307 153 123 169 305 210 191 * 485 388 536 * * 685 307 153 123 169 305 210 191 * 485 388 536 * * 605 307 153 123 169 305 210 191 * 580 484 641 * * 715 367 183 147 203 361 248 226 Table 5B — Compressor Electrical Data, 30HXA Units (cont) UNIT SIZE 30HXA 126 126-WD 136 136-WD 146 146-WD 161 161-WD 171 171-WD NAMEPLATE V-Hz (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 COMPRESSOR NUMBERS A1 RLA * 115.4 92.2 139.7 * * 145.4 255.5 115.4 92.2 139.7 240.2 159.4 145.4 * 140.7 112.4 170.2 * * 178.8 311.4 140.7 112.4 170.2 295.3 195.9 178.8 * 140.7 112.4 170.2 * * 178.8 311.4 140.7 112.4 170.2 295.3 195.9 178.8 * 157.9 126.2 191.2 * * 201.2 349.6 157.9 126.2 191.2 332.3 220.5 201.2 * 129.6 103.6 156.9 * * 161.7 286.9 129.6 103.6 156.9 267.2 177.3 161.7 B1 LRA * 820 656 906 * * 960 518 259 207 286 485 334 303 * 920 736 1017 * * 1226 581 291 233 321 619 426 387 * 920 736 1017 * * 1226 581 291 233 321 619 426 387 * 1175 940 1299 * * 1265 743 371 297 410 638 439 400 * 920 736 1017 * * 1226 581 291 233 321 619 426 387 LEGEND LRA — Locked Rotor Amps RLA — Rated Load Amps WD — Wye-Delta Start *Units are shipped with wye-delta start as standard. Across-the-line start is not available. 23 RLA * 94.8 75.7 114.7 * * 119.9 209.8 94.8 75.7 114.7 198.2 131.4 119.9 * 94.8 75.7 114.7 * * 119.9 209.8 94.8 75.7 114.7 198.2 131.4 119.9 * 115.4 92.2 139.7 * * 145.4 255.5 115.4 92.2 139.7 240.2 159.4 145.4 * 106.6 85.1 129.0 * * 133.4 235.9 106.6 85.1 129.0 220.3 146.2 133.4 * 157.9 126.2 191.2 * * 201.2 349.6 157.9 126.2 191.2 332.3 220.5 201.2 LRA * 685 548 757 * * 856 447 216 173 239 432 297 270 * 685 548 757 * * 856 433 216 173 239 432 297 276 * 820 656 906 * * 960 518 259 207 286 485 334 303 * 790 630 870 * * 1045 527 263 211 290 607 402 348 * 1175 940 1299 * * 1265 743 371 297 410 638 439 400 Table 5B — Compressor Electrical Data, 30HXA Units (cont) UNIT SIZE 30HXA 186 186-WD NAMEPLATE V-Hz (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 COMPRESSOR NUMBERS A1 RLA * 157.9 126.2 191.2 * * 201.2 349.6 157.9 126.2 191.2 332.3 220.5 201.2 B1 LRA * 1175 940 1299 * * 1265 743 371 297 410 638 439 400 RLA * 157.9 126.2 191.2 * * 201.2 349.6 157.9 126.2 191.2 332.3 220.5 201.2 LRA * 1175 940 1299 * * 1265 743 371 297 410 638 439 400 LEGEND LRA — Locked Rotor Amps RLA — Rated Load Amps WD — Wye-Delta Start *Units are shipped with wye-delta start as standard. Across-the-line start is not available. EQUIP NEC TB Y-Delta XL — — — — — LEGEND Equipment National Electrical Code (U.S.A.) Terminal Block Wye-Delta Start Across-the-Line Start Field Power Wiring Field Control Wiring Factory-Installed Wiring NOTES: 1. Factory wiring is in accordance with NEC. Field modifications or additions must be in compliance with all applicable codes. 2. Wiring for main field supply must be rated 75° C minimum. Use copper for all units. Maximum incoming wire size for each terminal block is 500 kcmil. Fig. 12 — Field Power Wiring 24 ALM CCN COMM CWFS CWP CWPI EQUIP GND, GRD NEC TB — — — — — — — — — — LEGEND Alarm Carrier Comfort Network Communications Chilled Water (Fluid) Flow Switch Chilled Water (Fluid) Pump Chilled Water (Fluid) Pump Interlock Equipment Ground National Electrical Code (U.S.A.) Terminal Block Field Power Wiring Field Control Wiring Factory-Installed Wiring NOTES: 1. Factory wiring is in accordance with NEC. Field modifications or additions must be in compliance with all applicable codes. 2. Wiring for main field supply must be rated 75° C minimum. Use copper for all units. Maximum incoming wire size for each terminal block is 500 kcmil. 3. Power for control circuit should be supplied from a separate source through a field-supplied, fused disconnect with 15 amp maximum protection for all control circuits. Connect control circuit power to terminals 1 and 2 of TB4. Connect neutral side of supply to terminal 2 of TB4. Control circuit conductors for all units must be copper only. 4. Terminals 13 and 14 of TB2 are for field external connection for remote on-off. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load. Remove jumper between 13 and 14 of TB2 if remote on-off is installed. 5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water pump interlock (CWPI) functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load. 6. Terminals 4 and 5 of TB2 are for control of chilled water pump starter. The maximum load allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush. 7. Terminals 2 and 3 of TB2 are for alarm. The maximum load allowed for the alarm is 125 va sealed, 1250 va inrush. Fig. 13 — Field Control Wiring 25 30HXA LOW-AMBIENT OPERATION — If outdoor ambient operating temperatures below 60 F (15 C) are expected, refer to separate installation instructions for lowambient operation using accessory Motormastert III control. Terminals TB2-11 and TB2-12 are provided for field installation of a chilled water (fluid) pump interlock (CWPI) and a chilled water (fluid) flow switch (CWFS). These devices are to be installed in series. Contacts must be rated for day circuit applications capable of handling a 24-vac to 50 mA load. Accessory remote on-off switch can be wired into TB2-13 and TB2-14. To use this feature, remove the factory-installed jumper and install the device in series. See Fig. 13 for remote on-off, CWPI, and CWFS wiring. Contacts must be rated for dry load application capable of handling a 24-vac to 50 mA load. MINIMUM LOAD ACCESSORY — If minimum load accessory is required, use the appropriate package. Refer to unit Price Pages or contact your local Carrier representative for more details. For installation details, refer to separate installation instructions supplied with the accessory package. MISCELLANEOUS ACCESSORIES — For applications requiring special accessories, the following packages are available: control power transformer, minimum load control, sound reduction enclosure, external vibration isolation, expanded display, Victaulic-type connections, temperature reset sensor, and chilled fluid flow switch. Refer to individual accessory installation instructions for installation details. Do not use interlocks or other safety device contacts connected between TB2 terminals 13 and 14 as remote on-off. Connection of safeties or other interlocks between these 2 terminals will result in an electrical bypass if the REMOTE-OFF-LOCAL switch is in the LOCAL position. If remote on-off unit control is required, a field-supplied relay must be installed in the unit control box and wired as shown in Fig. 13. Failure to wire the remote on-off as recommended will result in tube freeze damage. Step 6 — Leak Test Unit 30HXC UNIT — These units are shipped from the factory with a full charge of R-134a (See Tables 1A and 1B). Perform a leak test to ensure that leaks have not developed during unit shipment. Dehydration of the system is not required unless the entire refrigerant charge has been lost. There are a number of Swage-Lok fittings used on the refrigerant piping. If a leak is detected at any of these fittings, tighten outside nut 1⁄8 turn. Terminals 2 and 3 of TB2 have been provided for a field-supplied remote alarm (ALM). If an audible alarm is installed, an alarm shutoff is also recommended. Contacts are rated for 125 va at either 115 or 230 v control power. See Fig. 13. Terminals 4 and 5 of TB2 have been provided for a field-supplied chilled water (fluid) pump relay (CWP). A field-supplied power supply of appropriate voltage must be provided. Contacts are rated for 125 va at either 115 or 230 v control power. See Fig. 13. Terminals 1 and 6 of TB2 have been provided for a field-supplied control relay for the remote condenser (30HXA) or a condenser pump relay (30HXC). A field-supplied power supply of appropriate voltage must be provided. DO NOT OVERTIGHTEN THESE FITTINGS. Overtightening will result in the tube being crushed and will cause a refrigerant system leak. 30HXA UNITS — These units are shipped with a holding charge of R-134a. Leak test and dehydrate the complete system (including both field and factory installed piping). Step 7 — Refrigerant Charge Step 5 — Install Accessories IMPORTANT: These units are designed for use with R-134a only. DO NOT USE ANY OTHER refrigerant in these units without first consulting your Carrier representative. ELECTRICAL — Several optional control accessories are available to provide the following features: • control transformer • cooler pump/flow switch interlock • cooler pump control • expanded display panel • remote alarm • remote on-off • pulldown control • occupancy scheduling • demand limit control • temperature reset (from occupied space or outdoor-air temperature) • dual set point control • condenser water sensors • level II communications (CCN [Carrier Comfort Network]) The liquid charging method is recommended for complete charging or when additional charge is required. When charging, circulate water through the condenser and cooler at all times to prevent freezing. Freezing damage is considered abuse and may void the Carrier warranty. DO NOT OVERCHARGE system. Overcharging results in higher discharge pressure with higher cooling fluid consumption, possible compressor damage, and higher power consumption. Refer to Start-Up and Operation literature and separate accessory installation instructions for additional information. 26 30HXC UNITS — The 30HXC units are shipped from the factory with a full charge of R-134a. Unit should not need to be charged at installation unless a leak was detected in Step 6 — Leak Test Unit section on page 26. If dehydration and recharging is necessary, use industry standard practices or refer to Carrier Standard Services Techniques Manual as required. NOTE: On the units equipped with economizers (30HXA161-186), the EXV is located inside the economizer so the temperature must be measured entering the economizer (tube entering bottom of economizer). 3. Check for a clear sight glass. If the unit is not fully loaded, the sight glass might be flashing. This is normal for a partially-loaded unit. 30HXA UNITS — The 30HXA units are shipped with a holding charge of R-134a. The complete charge for the 30HXA, the remote condenser(s), and interconnecting piping must be field supplied. Table 6 — 30HXA System Charge for Start-Up UNIT 30HXA To charge the 30HXA systems: 1. Add liquid charge into the cooler using the 1⁄4-in. Schradertype fitting located on the tube going into the bottom of the cooler. This fitting is located between the electronic expansion valve (EXV) (076-146 units) or the economizer (161-186 units) and the cooler. Add approximately 2 lb/nominal ton (0.9 kg/nominal kW). This amount of charge should be sufficient to allow the unit to start. The approximate system charges are shown in Table 6. 2. Raise the compressor discharge to approximately 125 F (51.7 C) saturated discharge temperature (185 psig [1276 kPa]) by throttling the condenser air (or water) intake. Add charge until there is approximately 18 to 20 F (10.0 to 11.1 C) of system subcooling (saturated discharge temperature − actual temperature entering the EXV). 076 086 096 106 116 126 136 146 161 171 186 27 CIRCUIT A CHARGE Lb Kg 75 34.0 94 42.6 114 51.7 134 60.8 137 62.1 137 62.1 147 66.7 161 73.0 190 86.2 154 69.9 186 84.4 CIRCUIT B CHARGE Lb Kg 75 34.0 80 36.3 80 36.3 80 36.3 95 43.1 116 52.6 125 56.7 132 59.9 132 59.9 186 84.4 186 84.4 PACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions. For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included. Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 PC 903 Catalog No. 563-052 Printed in U.S.A. Form 30HX-1SI Pg 28 5-96 Replaces: New Tab 5c
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes XMP Toolkit : 3.1-701 Create Date : 1996:08:06 09:26:04Z Modify Date : 2005:11:11 17:33:08-05:00 Metadata Date : 2005:11:11 17:33:08-05:00 Producer : Acrobat Distiller 2.0 for Windows Keywords : Format : application/pdf Title : Description : Creator : Carrier Corporation Subject : Document ID : uuid:a65f5b54-80a3-47d0-b997-02c312e5f4d8 Instance ID : uuid:cd9d7631-9877-404f-a318-d6db6b159395 Page Count : 28 Author : Carrier CorporationEXIF Metadata provided by EXIF.tools